Copyright © SEL 2009Copyright © SEL 2009
Trends in Station Bus and Process Bus
Communications Via the Several
IEC 61850 Protocols
Schweitzer Engineering Laboratories, Inc.
Reduce Cost / Complexity of Field Wiring
1. Traditional Topology
Physical
Equipment
Terminal
BlockRelay
Marshalling
Cabinet
Terminal
Block /
Test Plug
44 Wires 44 Wires 44 Wires 44 Wires
Yard House
2. Relays in Yard
Physical
Equipment
Terminal
Block /
Test Plug
Relay44 Wires 44 Wires
Yard
3. I/O
Modules in
Yard
Physical
Equipment
Terminal
BlockRelay
Terminal
Block /
Test Plug
Marshalling
Cabinet
I/O
Transceiver
44 Wires 24 Wires
20 Wires
24 Wires24 Wires
1 Cable
YardHouse
4. Merging Unit Topology
Physical
Equipment
Terminal
Block /
Test Plug
RelayMerging
Unit
Switch or
Processor
44 Wires 44 Wires 1 Cable 1 Cable
Yard House
Va, b, c,
neutral, busbar
la, b, c, neutral
(prot)
la, b, c
(meas)
Merging
Unit
Digital
Communication
Po
we
r S
up
ply
Clo
ck In
pu
tD
iscre
te S
tatu
s
an
d A
larm
Merging Unit Concept Aggregates Data
Onto Digital Link
Discrete I/O, Programmable
Automation Controllers, and RTDs
Multiple Merging Unit Payloads
• Discrete only: DMU
• Measured analog plus discrete: MMU
• Temperatures: TMU
• Synchrophasors: PMU
• Smart breaker: BMU
• Sampled (raw) analog plus discrete: MU
• SMART Protocol™ – metering, targets,
equipment data, temperatures, and
synchrophasors
• IEC 61850 GOOSE, Sampled Values (SV)
• IEEE C37.118 synchrophasors
• IEEE 1588–2008: precision time
synchronization (in progress via PSRC)
Process Bus Protocols Move Analog
Values, Discrete Status, and Alarms
SEL Devices Publish and Subscribe
MIRRORED
BITS® DMU
Fast Message
MMU
Fast Message
PMU
IEC 61850
GSE DMU
IEC 61850
GSE MMU
IEC 62271
BMU
IEEE C37.118
PMU
MIRRORED
BITS DMU
Fast Message
PMU
IEC 61850
GSE DMU
IEC 61850
GSE MMU
IEC 62271
BMU
IEC 61850-9-2
MU
IEC 61850-9-2
MU
Publications
Fast Message
TMU
IEEE C37.118
PMU
Subscriptions
SEL Provides Integration Choices
Nonrouted Architecture Routed Architecture
Focus on IEC 61850 Protocols
• Reporting, polling, and control via
client server (MMS)
• Control and unsolicited updates via peer to
peer (GOOSE or SV)
• Primary equipment data acquisition peer to
peer (GOOSE or SV)
Ethernet
Ethernet
Switched Ethernet Station and
Process Bus From Beginning
Process Bus Shares Data Among IEDs
and Smart Sensors
Bay
Controller
Relay
A
Relay
B
Modern
Switchgear
Modern
CT / VTs
Process Bus
SEL ApproachUse Global, Standardized Methods
• Offer choice of installation method / location
• Provide highest protection reliability
• Continue lowest system / installation cost
• Use existing protection
• Design for interoperability
• Provide system-wide protection and
synchrophasors
Relay-Based Process Bus System
Process
Level
Bay
Level
Instrument Transfer
Merging Unit
50, 51, 21
Breaker Controller
Breaker
Station
Level
Time Source
Ethernet Switch
Station
Controller
HMI
Ethernet Switch
87BFR
Advantages of SEL Approach
• Primary protection continues if
communications fail
• Minimum number of devices
• Relay receives and transmits IEC 61850-9-2
• Fixed-rate sampling
• Absolute time reference per IEEE 1588
• Share analog data among devices
Flex Connect Choose From Several Standard Connections
• Reduce wiring
• Reuse data
• Recycle information
Choose Any Installation Method:
Interoperable – Multivendor
Relays in
control building
Relays in field
termination kiosks
Flex Connect: Flexible Data
Acquisition and Control – Multivendor
• SELECT Direct: standard, hard-wired copper
conductors
• SELECT Fiber: digital communications over
standard, fiber-optic cable
• Hybrid
♦ Analog via SELECT Direct
♦ Discrete via SELECT Fiber
SELECT Direct Connectorized® or Conventional Copper
Conductor Terminations
Choose from copper off the spool or
premade harnesses
SELECT Fiber Digital Communication Over Standard
Fiber-Optic Cable
Choose fiber off the spool or premade cables
SEL Confidential
HybridDigital Communication Via Standard Fiber
Plus Conventional Copper Conductors
• Copper off the spool
• Premade harnesses
• Fiber off the spool
• Premade cables
Choose from:
Compare Four-Feeder Substation SAS
Communications and
control building (CCB)
Communications and
control kiosk (CCK)
Field termination cabinet
(FTC) and kiosk (FTK)
Copper
conductors
(CCs)
Fiber
connectors
(F)
Process Bus
SELECT Direct
Hard-Wire
• 72 CC analog
• 60 CC discrete
Station Bus
SELECT Fiber
Fiber Process Bus FTK
• SEL MU
• Publish / subscribe
SV and GOOSE
Hybrid Process Bus FTK
• SEL DMU
• Publish / subscribe
GOOSE
• Analogs via CCs
Process BusHybrid
• SELECT Fiber
Star, 6 F digital
• SELECT Direct,
72 CC analog
Station Bus SELECT Fiber
Active Redundant Network: Dual Ethernet
“Failover” – IED Controls Data Flow
Survive loss of any
switch, cable, relayNetwork
Process BusHybrid
• SELECT Fiber Dual
Star, 12 F digital
• SELECT Direct,
72 CC analog
Station Bus SELECT Fiber
Passive Redundant Network: Internal Ethernet
Switches – Switch Controls Data Flow
Survive loss of any
switch, cable, relayNetwork
Managed
Ether
Switch
Managed
Ether
Switch
Process BusHybrid
• SELECT Fiber
Ring, 7 F digital
• SELECT Direct,
72 CC analog
Station Bus SELECT Fiber
Merging Units Support SV and GOOSE
But Disable Local Protection
Process Bus
SELECT Fiber
Star, 6 F
Station Bus
SELECT Fiber
Process Bus
SELECT Fiber
Dual Star, 12 F
Station Bus
SELECT Fiber
Fiber Optics Replace Copper
Process Bus
• SELECT Fiber
Star, 7 F
• Unused
Station Bus
SELECT Fiber
Process Bus
SELECT Fiber
Star, 7 F
Station Bus
SELECT Fiber
Station
Controller
Rev.
Meter
Ethernet
Switch
Ethernet
Switch
Time
Source
Instrument
Transfer
Merging Unit, Disable Local Protection,
But Maintain Breaker Control
Merging
Unit
Breaker
Controller
Process
Level
Bay/Unit
Level
Station
Level
Breaker
Merging
Unit
Breaker
Controller
Instrument
Transfer
Breaker
87
50, 51,
21
50, 51,
21
50, 51,
21
50, 51,
21
Station
Controller
Revenue
Meter
Ethernet
Switch
Ethernet
Switch
Time
Source
Instrument
Transfer
Merging Unit Plus Local Protection
Supporting System Protection Over LAN
Merging
Unit
87
Breaker
Controller
Process
Level
Bay/Unit
Level
Station
Level
Breaker
50, 51, 21
Merging
Unit
Breaker
Controller
50, 51, 21
Instrument
Transfer
Breaker
Merging Unit With I/O
Time
Source
Merging
Unit
Instrument
Transf.Ethernet
Switch
Relay Ethernet
Switch
Breaker
Controller
Switched System MTBF = 300 / 4 = 75 Years
Process Level Bay/Unit Level Station Level
Station
Controller
Breaker
Merging Unit With Intelligence
Performing Local Protection
Time
Source
Merging
Unit
Instrument
Transf.
Relay
Ethernet
Switch
Breaker
Controller
System MTBF = 300 Years
Process Level Bay/Unit Level Station Level
Station
Controller
BreakerRevenue
Meter
Merging Unit Plus Local Protection
Supporting System Protection Over LAN
Time
Source
Merging
Unit
Instrument
Transf.
Ethernet
Switch
87
Ethernet
Switch
Breaker
Controller
Localized Protection MTBF = 300 Years
Merging Unit Prot. MTBF = 300/4 = 75 Years
Process Level Bay/Unit Level Station Level
Station
Controller
Breaker
50, 51, 21
Revenue
Meter
2nd Merging
Unit for 50,
51, 21, 87
Replace Copper
With Fiber,
Monitor Health of
Signal, Reduce
Footprint / Cost