0173.03.48 F Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop type 0 Triplex-K-1 Single anti-flood protection type 1 Triplex-K-2 Double anti-flood protection type 2 DIN EN 13564 ACO Haustechnik Installation information
Transcript
Page 1: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

0 1 7 3 . 0 3 . 4 8 F

Triplex-K Cleaning pipeTriplex-K-0 Single backflow stop type 0 Triplex-K-1 Single anti-flood protection type 1Triplex-K-2 Double anti-flood protection type 2

DIN EN 13564

ACO HaustechnikI n s t a l l a t i o n i n f o r m a t i o n

Page 2: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

ContentsChapter Page(s)

1 Product Identification

1.1 Addresses 3

1.2 EC Conformity declaration 4

1.3 Plant description / Type / Scope of supply 5

2 Function/Fields of Application

Triplex-K Cleaning pipe 6

Triplex-K-0 Single backflow stop type 0 6

Triplex-K-1 Single anti-flood protection system type 1 6

Triplex-K-2 Double anti-flood protection system type 2 6

3 Installation

Installation principles (gradient, installation site) 7

Installation in the above ground pipes (without shaft system) 8

Installation in the base plate (with shaft system) 9/10

4 Inspection and Servicing

Triplex-K-0 Single backflow stop type 0 11

Triplex-K-1 Single anti-flood protection system type 1 11

Triplex-K-2 Double anti-flood protection system type 2 12

5 Retrofitting Possibilities 13

6 Spare Parts and Accessories 14

7 Technical Data

Product dimensions 15

Suggested installations 16

8 Inspection Log Book and Hand-over Record 17

9 Maintenance Contract 18

10 Warranty 19

11 After-sales Partners 19

Caution!This operating manual has to be handed out to the user and to be kept in a safe place.Maintenance works have to be recorded in the relevant inspection pages.

2Subject to technical alterations

Page 3: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

3Subject to technical alterations

ACO Haustechnik0 1 7 3 . 0 3 . 4 8 F

Name and address of the manufacturer

ACO Passavant GmbHPostfach 11 6236267 PhilippsthalUlsterstraße 336269 Philippsthal After-sales service divisionTel. 0 66 20/77- 0 Service Tel. ++49 (0) 3 69 65 - 819 - 444Fax 0 66 20/77- 52 Service Fax. ++49 (0) 3 69 65 - 819 - 367

Name and address of the supplier

_________________________ ___________________________________________________________________________

After-sales service divisionTel. _____________________ __________________________Fax ____________________ __________________________

Name and address of the electrician

_________________________ ___________________________________________________________________________

After-sales service divisionTel. _____________________ __________________________Fax ____________________ __________________________

Name and address of the plumber

_________________________ ___________________________________________________________________________

After-sales service divisionTel. _____________________ __________________________Fax ____________________ __________________________

1 Product identification

1.1 Addresses

Page 4: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

4Subject to technical alterations

1.2 EC Conformity declaration

EC Conformity declaration within the meaning of the EC Machinery Directive

We, ACO Passavant GmbH, Ulsterstrasse 3, 36269 Philippsthal

hereby state under our sole responsibility that the designs of the following anti-flood protection systems, put in circulation by us, correspond to DIN EN 13564-1:2002 Standard, Anti-flood Protection Systems for Buildings; as well as to the following EC Directives and DIN Standards:

Product designation: Anti-flood Protection System Triplex-K Use: Anti-flood protection of buildings; for rainwater utilization plants

Type 0: Nominal width: Art. no.:DN 100 620356, 620358DN 125 620480, 620481DN 150 620357, 620359

Type 1: DN 100 620360, 620362DN 125 620482, 620483DN 150 620361, 620363

Product designation: Anti-flood Protection System Triplex-K Use: Anti-flood protection of buildings; for rainwater utilization plants and wastewater free of faeces

Type 2: DN 100 620364, 620366DN 125 620484, 620485DN 150 620365, 620367

The housing is made of PP material, the cover is made of PA material.

The requirements for gas proofness, watertightness, efficiency, temperature stability, mechanic rigidity and durability are met.

Machinery Directive 89/392/ EEC in the version of 98/68/EECBuilding Products Directive 89/106/EEC in the version of 93/68/EEC

CE Identification Directive System 4; see Directive 89/106/EEC (BPR), Attachment III.2(ii), 3rd option

Harmonised standards applied:DIN EN 12056-1:2001-01DIN EN 12056-2:2001-01DIN EN 13564-2:2002DIN EN 13564-3:2004DIN 1986-100:2008-05DIN EN 1451-1:1999

D - 36269 Philippsthal, September 2008

ACO Passavant GmbH

R. SandGeneral Manager

Page 5: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

Triplex-K Triplex-K-0 (Typ 0) Triplex-K-1 (Typ 1) Triplex-K-2 (Typ 2)Reinigungsrohr Einfachrückstau Einfachrückstauverschluss Doppelrückstauverschluss

Art. no. 620352 (DN 100) Art. no. 620356 (DN 100) Art. no. 620360 (DN 100) Art. no. 620364 (DN 100)Art. no. 620478 (DN 125) Art. no. 620480 (DN 125) Art. no. 620482 (DN 125) Art. no. 620484 (DN 125)Art. no. 620353 (DN 150) Art. no. 620357 (DN 150) Art. no. 620361 (DN 150) Art. no. 620365 (DN 150)

consisting of:Body Body Body Body

+ cover with sealing + cover with sealing + cover with sealing + cover with sealingand emergency seal and emergency seal

+ six nuts + six nuts + six nuts + six nuts with flat washers with flat washers with flat washers with flat washers

+ backflow flap + backflow flap + two backflow flaps+ test pipe

Retrofitting possibility toTriplex-K-0, Triplex-K-1, Triplex-K-1, Triplex-K-2, Triplex-K-2,Quatrix-K Quatrix-KTriplex-K-2, Quatrix-K Quatrix-K

Triplex-K for above ground pipes

Triplex-K Cleaning pipe

Triplex-K-0 (type 0) Single backflow stop

Triplex-K-1 (type 1) Single anti-flood

protection system

Triplex-K-2 (type 2) Double anti-flood protection system

Triplex-K Triplex-K-0 (Typ 0) Triplex-K-1 (Typ 1) Triplex-K-2 (Typ 2)Reinigungsrohr Einfachrückstau Einfachrückstauverschluss Doppelrückstauverschluss

Art. no. 620354 (DN 100) Art. no. 620358 (DN 100) Art. no. 620362 (DN 100) Art. no. 620366 (DN 100)Art.-Nr. 620479 (DN 125) Art.-Nr. 620481 (DN 125) Art.-Nr. 620483 (DN 125) Art.-Nr. 620485 (DN 125)Art. no. 620355 (DN 150) Art. no. 620359 (DN 150) Art. no. 620363 (DN 150) Art. no. 620367 (DN 150)

consisting of:

Body Body Body Body+ top section with sealing + top section with sealing + top section with sealing + top section with sealing

and cover and cover and cover and cover+ cover with sealing + cover with sealing + cover with sealing + cover with sealing

and emergency seal and emergency seal+ six nuts + six nuts + six nuts + six nuts

with flat washers with flat washers with flat washers with flat washers+ backflow flap + backflow flap + two backflow flaps

+ test pipe

Retrofitting possibility to

Triplex-K-0, Triplex-K-1, Triplex-K-1, Triplex-K-2, Triplex-K-2,Quatrix-K Quatrix-KTriplex-K-2, Quatrix-K Quatrix-K

Triplex-K with shaft system for installation in the base plate

Triplex-K Cleaning pipe

Triplex-K-0 (type 0) Single backflow stop

Triplex-K-1 (type 1) Single anti-flood

protection system

Triplex-K-2 (type 2) Double anti-flood protection system

1.3 Plant description / Type / Scope of supply

5Subject to technical alterations

ACO Haustechnik0 1 7 3 . 0 3 . 4 8 F

Page 6: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

6Subject to technical alterations

2 Function/Fields of application

Triplex-K Cleaning pipe(Art. no.: 620352, 620478, 620353, 620354,

620479, 620355)

The Triplex-K cleaning pipe is used as a revision opening. It can be fittedin pipes with wastewater free of faeces or containing faeces. The clea-ning pipe can be converted into an anti-flood protection system at anytime. In accordance with DIN EN 13564-1, following conversions arepossible:

Anti-flood protection system type 0 (for rainwater utilization plants)Anti-flood protection system type 1 (for rainwater utilization plants)Anti-flood protection system type 2 (for rainwater utilization plants orwaste-water free of faeces) Anti-flood protection system type 3 F (for wastewater free of faeces orcontaining faeces)

If the cleaning pipe is fitted in wastewater containing faeces, it maylater only be converted into an automatic anti-flood protection system(type 3 F).

Triplex-K-0 Single backflow stop(Art. no.: 620356, 620480, 620357, 620358,

620481, 620359)

The Triplex-K-0 single backflow stop has an integrated backflow flap.Normally, this flap fits flush against a fitted seal. In the event of a back-flow, the water from the sewers flows against the backflow flap. Theflap is pressed against the flap sealing ring to seal off the anti-flood pro-tection system. In this condition, drainage via the anti-flood protectionsystem is not possible.

As per DIN EN 13564, the Triplex-K-0 may only be used for safeguar-ding rainwater utilization plants. The backflow unit can be converted toanti-flood protection systems type 1, 2 or 3F (for description, see aboveunder Triplex-K cleaning pipe).

Triplex-K-1 Single anti-flood protection system(Art. no.: 620360, 620482, 620361, 620362,

620483, 620363)

The Triplex-K-1 single anti-flood protection system has an integrated bak-kflow flap and an emergency seal. In the event of a backflow, the waterfrom the sewers flows against the backflow flap. The flap is pressedagainst the flap sealing ring to seal off the anti-flood protection system.In this condition, drainage via the anti-flood protection system is not pos-sible. With the help of the emergency seal, the flap can in addition belocked manually.

As per DIN EN 13564, the Triplex-K-1 may only be used for safeguar-ding rainwater utilization plants. The anti-flood protection system can beconverted to anti-flood protection systems type 2 or 3F (for description,see above under Triplex-K cleaning pipe).

Triplex-K-2 Double anti-flood protection system(Art. no.: 620364, 620484, 620365, 620366,

620485, 620367)

The Triplex-K-2 double anti-flood protection system has two backflowflaps of which one is equipped with an emergency seal. In the event of abackflow, the water from the sewers flows against the last backflowflap, viewed in flow direction. The flap is pressed against the flap sealingring to seal off the anti-flood protection system. In this condition, draina-ge via the anti-flood protection system is not possible.

If this backflow flap is leaking, the second flap takes over the protectivefunction and seals off the anti-flood protection system. The second flapviewed in flow direction can be locked manually by means of the emer-gency seal. During long periods away from home (e. g. holidays) it isrecommended engaging this emergency seal. But remember to releaseit again when returning home. As per DIN EN 13564, the Triplex-K-2may only be used for safeguarding rainwater utilization plants or waste-water free of faeces in private households. The following criteria have tobe met:

The wastewater must be capable of draining away along a naturalslope.There must only be a small number of users.Installation must be located in a room with inferior utilisation.The drainage point(s) cannot be used during a backflow situation.

The anti-flood protection system can be converted into an automaticanti-flood protection system type 3F (for description, see above underTriplex-K cleaning pipe).

Page 7: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

7Subject to technical alterations

ACO Haustechnik0 1 7 3 . 0 3 . 4 8 F

3 Installation - Installation principles

Drainage objects lying above the backflow level (left figure) must notdrain via an anti-flood protection system. In this case, wastewater accu-mulating above the backflow level could not be drained anymore in caseof back-flow. Because of the principle of communicating pipes, thewastewater would escape from the lowest drain points below thebackflow level and flood the cellar.

CORRECTINCORRECT

For this reason, all drainage objects fitted above the backflow level haveto be connected behind an anti-flood protection system (right figure). Inthe case of backflow, the downpipe fills up to road level at the most, theanti-flood protection system prevents the wastewater from drawback inlower drainage objects and it thus escapes via the manhole covers.

Installation site

Gradient

The ACO Triplex cleaning pipes/anti-flood protection systems are excel-lently suited for refurbishment as they only have a minimum proper gra-dient of 12 mm. The anti-flood protection systems must be fitted in thepipe gradient, the proper gradient is a result of the product construc-

tion. If the pipe gradient is not sufficient, the anti-flood protectionsystem must not be fitted with an inclination (counter gradient), asfaults may occur.

Horizontal installation Installation with counter gradient

CORRECT INCORRECT

Page 8: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

8Subject to technical alterations

3 Installation in above ground pipe (without shaft system)

1. Fix body in local shaft or freely accessible e. g. at wall. Caution!Do not cast body into concrete.

3. Connect pipes to anti-flood protection system as per relevant instal-lation instructions (plastic, steel, cast iron or stoneware).

4. If the pipe is laid along a wall, two pipe mountings have to be fittedaround the pipe shortly before and shortly behind the anti-flood pro-tection system and to be fixed to the wall. For proper operation, theemergency seal (Triplex-K-1 or Triplex-K-2 only) must be open (leverposition “1”)!

Drop in height 12 mm.

Caution!

2. Fit body in flow direction and align horizontally. Body may not beinstalled tilted - neither to the side nor to the front or to the back.The individual parts (flap, cover etc.) may not be soiled by buildingmaterials and thus affected in their functioning.

Page 9: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

9Subject to technical alterations

ACO Haustechnik0 1 7 3 . 0 3 . 4 8 F

3 Installation in the base plate (with shaft system)

1. Apply granular sub-grade course to ground.

2. Fit body in flow direction and align horizontally. Body may not beinstalled tilted - neither to the side nor to the front or to the back.

3. The individual parts (flap, cover etc.) may not be soiled by buildingmaterials and thus affected in their functioning.

4. Connect pipes to anti-flood protection system as per relevant instal-lation instructions (plastic, steel, cast iron or stoneware).

5. Continue granular sub-grade course (e. g. sand) above pipe upperedge.

6. In case of need: Fit sealing flange (art. no. 620382) againstpressurised water to intermediate section. In order to keep excessor shortage at a minimum, the sealing flange can be fitted stepwiseto the various grooves (for height-adjustability of flange, refer topage 13).

Drop in height 12 mm.

Caution!

Page 10: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

=<

10Subject to technical alterations

9. In case of need: If the cleaning pipe / the anti-flood protectionsystem is to be converted at a later date to an automatic anti-floodprotection system Quatrix-K, a cable duct DN 40 has to be fitted totop section during construction phase already (use core bit 50 mm).

H1min changes to 460 mm.The blank cable duct has to be laid with a gradient to the anti-floodprotection system. Possible angles have to be carried out withelbows (elbows 45°) .

8. Fit top section to body and align to final height of finished floor levelas well as to tile pattern. Continue setting up the floor structure.

10. Cover can now be fitted to top section.

Cover upper side: plastic coverCover underside: suitable for tile layer (see para 11)

Insert reversing plate before tile layer is laid. Grease O-ring before inserting the reversing plate.Fill joint of top section and floor covering with permanentlyelastic mass.

The emergency seal (Triplex-K-1 or Triplex-K-2 only) must be open tooperate properly (lever position “1”)!

11. In case of need: Cover (ABS) must be free of grease and verydry. Apply tile adhesive to cover underside and fit floor tiles intocover. Tiles with a thickness up to 10 mm can be used. The max.possible filling height (tile adhesive suitable for plastic + tiles) is15 mm.

7. In case of need: Fit extension piece (art. no. 620381) to body. Lipseal of body must seat properly. In order to achieve a minimumcoverage of the WU concrete (impervious to water), the sealingflange (art. no. 620382) can be fitted stepwise to the variousgrooves.

Caution!

Page 11: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

11Subject to technical alterations

ACO Haustechnik0 1 7 3 . 0 3 . 4 8 F

4 Inspection and servicing

Servicing of the Triplex-K-0 single backflow stop type 0

Anti-flood protection systems for continuous horizontal pipes must bevisually checked once a month by the operator and the emergency seal,if any, must be operated to check that it is functioning properly. In addi-tion, the anti-flood protection system should be serviced by properlyqualified personnel twice a year. The following works have to be carriedout:

Emergency seal must be open (position „1“).Undo cover screws. Remove cover. Take outbackflow flap.

Undo cover screws. Remove cover. Take outbackflow flap.

Re-insert flap in body, observe seal seating.Seal has to be greased before. Screw coveragain onto body.

Check and clean cover seal and backflowflap seal and exchange, if required. Rinsebody.

Re-insert flap in body, observe seal seating.Seal and seating have to be greased before.Screw cover again onto body.

Servicing of the Triplex-K-1 single anti-flood protection system type 1

Check and clean cover seal and backflowflap seal and exchange, if required. Rinsebody.

Tightening torque

Tightening torque: 5 - 8 Nm.The screws of the flaps should be tightened as shown besides.

Page 12: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

12Subject to technical alterations

Servicing of the Triplex-K-2 double anti-flood protection system type 2

Emergency seal must be open (position „1“).Undo cover screws. Remove cover. Take outbackflow flaps.

Re-insert flap in body, observe seal seating.Seal and seating have to be greased before.Screw cover again onto body.

Check and clean cover seal and backflow flapseal and exchange, if required. Rinse body.

Tightness test of the Triplex-K-2 double anti-flood protection system type 2

Lock emergency seal. When pulling the emer-gency seal lever, a “click” must be clearly audible.

Fill in clear water up to upper edge of test pipe(100 mm).

Remove test screw and screw in test pipe.

Monitor water level for 10 minutes. If fillinglevel sinks, replenish with clear water untilwater column of 100 mm is again reached.Note down water quantity which needed to bereplenished.

If during a period of 10 minutes less than500 cm3 water have to be replenished, thetightness test was passed.Remove test funnel, re-insert test screws, openemergency seal.

If during a period of 10 minutes more than500 cm3 water have to be replenished, the flapseals and the flaps have to be checked againand be exchanged, if required. Then, tightnesstest has to be repeated.

Page 13: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

13Subject to technical alterations

ACO Haustechnik0 1 7 3 . 0 3 . 4 8 F

Backflow flapwith insertion element X X X

art. no. 620378

Backflow flapwith insertion element

art. no. 620378 Locking cover X Xwith emergency seal

Locking cover incl. rubber sealingwith emergency seal art. no. 620379incl. rubber sealing

art. no. 620379

Backflow flap with insertion element

Umrüstsatz art. no. 620378 Backflow flapArt.-Nr. 620373 with insertion element X

Locking cover art. no. 620378with emergency sealincl. rubber sealing

art. no. 620379

Conversion kit Conversion kit Conversion kit Conversion kitart. no. 620372 art. no. 620372 art. no. 620372 art. no. 620372

Triplex-K Cleaning pipe

Triplex-K-0 (type 0) Single backflow stop

Triplex-K-1 (type 1) Single anti-flood

protection system

Triplex-K-2 (type 2) Double anti-floodprotection system

Quatrix-K Automaticanti-floodprotection

system

TRIPLEX-K-0

(type 0) Single

backflowstop

TRIPLEX-K-1

(type 1) Single

anti-floodprotection

systen

TRIPLEX-K-2

(type 2) Double

anti-floodprotection

system

Horizontal : original productVertical: retrofitting possibilities

Example: If the Triplex-K-0 is to be retrofitted to a Triplex-K-1, the lok-king cover with emergency seal incl. rubber sealing art. no.620379 is required.

5 Retrofitting possibility

Page 14: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

14Subject to technical alterations

Product Illustration Art. no.

6 Spare parts / Accessories

ACO conversion kit to automatic anti-flood pro-tection system Quatrix-K. For conversion ofcleaning pipes or anti-flood protection systemsfor wastewater free of faeces.

Extension set 10 m;for Quatrix-K automatic anti-flood protectionsystem.

ACO conversion kit to double anti-flood protec-tion system Triplex-K-2. For conversion of clea-ning pipes and anti-flood protection systemstype 0 or 1.

ACO backflow flap with insertion element, sui-table for Triplex-K-2, Triplex-K-1,Triplex-K-0 andTriplex cleaning pipe.

ACO locking cover incl. rubber seal and emer-gency seal, suitable for Triplex-K-2, Triplex-K-1,Triplex-K-0 and Triplex-K cleaning pipe.

ACO locking cover incl. rubber seal, suitablefor Triplex-K-0 and Triplex-K cleaning pipe.

ACO extennsion element with lip seal, suitablefor Triplex-K anti-flood protection systems andcleaning pipes with shaft system. Height: 100mm

ACO sealing flange, suitable for Triplex-K anti-flood protection systems and cleaning pipeswith shaft system.

ACO top section for Triplex-K anti-flood protec-tion systems and cleaning pipes with shaftsystem.

ACO cover and reversing plate, surface-water-tight, suitable for Triplex-K anti-flood protectionsystems and cleaning pipes with shaft system.

ACO test pipe, suitable for all double anti-floodprotection system Triplex-K-2 and automaticanti-flood protection system Quatrix-K.

620372

620438

620373

620378

620379

620380

620381

620382

620383

620384

6010.00.15

Page 15: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

15Subject to technical alterations

ACO Haustechnik0 1 7 3 . 0 3 . 4 8 F

6 Technical data - Dimensional drawings

Triplex-K Cleaning pipe and Triplex-K-O single backflow stop without shaft system

Triplex-K-1 Single anti-flood protection and Triplex-K-2 double anti-flood protection without shaft system

Triplex-K Cleaning pipe, Triplex-K-0, Triplex-K-1, Triplex-K-2 with shaft system (optionally with flange)

*If a later conversion is intended, measurement Hmin 460 mm has to be

considered.

Measurement 405 is achieved by cutting (XX) the top section to length.

H1

400

DN

12

DN205 27

0

L

250

H1

400

DN 12

DN205

338

L

250

Art. no. DN DN/OD L (mm) H1 (mm)

620360 100 110 460 79620482 125 125 469 86620361 150 160 500 104620364 100 110 460 79620484 125 125 469 86620365 150 160 500 104

Sealingflange (optional)

360 x 300

H1

DN

12

DN

H2 H m

ax. 5

12

H m

in. 4

05*(

XX)

20

20

L

30

ø 67

6

ø 46

0

Art. no. DN DN/OD L (mm) H1 (mm)

620352 100 110 460 79620478 125 125 469 86620353 150 160 500 104620356 100 110 460 79620480 125 125 469 86620357 150 160 500 104

Art. no. DN DN/OD L (mm) H1 (mm) H2 (mm)

620354 100 110 460 79 217620479 125 125 469 86 205620355 150 160 500 104 192620358 100 110 460 79 217620481 125 125 469 86 205620359 150 160 500 104 192620362 100 110 460 79 217620483 125 125 469 86 205620363 150 160 500 104 192620366 100 110 460 79 217620485 125 125 469 86 205620367 150 160 500 104 192

Page 16: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

16Subject to technical alterations

7 Technical data - Suggested installations

Triplex-K-1 Single anti-flood protection and Triplex-K-2 double anti-flood protection without shaft system

Triplex-K Cleaning pipe, Triplex-K-0, Triplex-K-1, Triplex-K-2 with shaft system

Tiles + tile adhesive

Screed

Thermal insulationGround ceiling

(concrete impermeable to water = WU, thickness as per specif.)

Excess and shortage of flange min. 40 mm

Granular sub-gradecourse (e. g. sand)

Ground

Tiles + tile adhesive

Ground

Base plate

Insulation

Screed

ACO Sealing flange

ACO Double anti-flood protec-tion system TRIPLEX--K-2, DN 100 for above ground pipes

ACO Double anti-flood protec-tion system TRIPLEX--K-2, DN 150 with telescopicallyadjustable top section andcover plate K3

Page 17: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

17Subject to technical alterations

ACO Haustechnik0 1 7 3 . 0 3 . 4 8 F

8 Hand-over record

Inspection log book

Commissioning and functional check of plant was carriedout in accordance with the installation and operatingmanual:

Briefing of operator was carried out:

(Stamp / Date / Signature)

Plumber Operator

(Stamp / Date / Signature) (Date / Signature)

Date Works carried out Carried out by:

Page 18: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

18Subject to technical alterations

9 Maintenance contract

A maintenance contract covering regular maintenance is closed between the following undersigned parties.

Ordering party: Consignee:

Product description:

Scope of supply:

Dates:

Contract duration:

According to DIN EN 13564, anti-flood protection systems should be serviced twice a year. During such servi-cing, all fittings have to be cleaned, moveability of backflow insert has to be checked and defective parts, ifany, must be exchanged (at extra charge and working time). In the case of type 2 anti-flood protectionsystems, a functional test as per DIN 13564-2 has to be carried out additionally.

Appointment is suggested by consignee. If in a special case, the consignee cannot keep this maintenancedate agreed upon, this does not result in any right to claim by the ordering party. However, the ordering partymust be informed about this deadline shift by the consignee.

This maintenance contract is closed for an indefinite time. It is prolonged by each one year if it not terminatedin writing three months prior to year’s end.

Ordering party: Consignee:

(Date / Stamp / Signature / Town) (Date / Signature / Town)

Costs: For each half-yearly maintenance, the consignee charges an amount of ______ Euro (plus VAT).Invoice is issued after maintenance works were carried out. Spare parts possibly required are charged extra.

Beginning of contract:

Duties of the ordering party: For proper maintenance, the ordering party ensures accessibility of product and will not accept any delay incarrying out the works.

For further notes on maintenance contracts, please refer to www.aco-haustechnik.de.

Page 19: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

19Subject to technical alterations

ACO Haustechnik0 1 7 3 . 0 3 . 4 8 F

10 Excerpt from the Sales Terms and Delivery Conditions ACO Passavant GmbH

1 In order to guarantee proper operation of the anti-flood protection system, allanti-flood protection systems should be serviced every 6 months. If no servicingis carried out as per DIN EN 13564-1 regulations, the warranty claim expires.For detailed information on DIN EN 13564-1 regulations, please refer to the

chapter „Inspection and Maintenance“. As maintenance works have to be carriedout by properly qualified staff twice a year, the closing of a maintenance contractcovering the complete drainage plant is strongly recommended.

11 Service partners

For more details on our service partners, please refer to:

www.aco-haustechnik.de/servicepartner

Supplier shall be liable for property damage and deficiency in title withany further claims excluded, with the reservation of paragraph 7 andirrespective of sections 478, 479 German Civil Code as specifiedhereinafter:

1. Any and all of those parts included in the delivery, that after deliveryturn out to be unusable or not irrelevantly impaired in their serviceability,the cause of which lies prior to passage of risk, shall be repaired orsupplied again at no cost for Purchaser. Supplier may choose betweenrepair and substitute delivery. Purchaser shall be entitled to reduction ofthe purchase price or withdrawal from contract after the second unsuc-cessful attempt of repair or replacement or should repair or replace-ment be unacceptable. For the rest, Supplier shall be liable for damagesonly in the scope of the following section 7. Supplier shall be informedimmediately of detected defects. Irrespective of the statutory mer-chants' requirement of examination and requirement to give notice ofdefects, written notice of evident defects shall be given to Supplier notlater than 14 days upon delivery, otherwise the warranty shall cease.Replaced parts shall become Supplier's property.

2. Upon consultation with Supplier, Purchaser shall grant Supplier suffi-cient time and opportunity for performing repairs and replacements con-sidered necessary by Supplier, otherwise Supplier shall be releasedfrom liability for consequential damages. Purchaser shall be entitled torepair the defect himself or to having the defect repaired by any thirdparty and to demand reimbursement of incurred costs from Supplieronly in urgent cases of risk of improper operational safety and/or forpreventing unreasonably large damage or should Supplier be in defaultwith the elimination of defect. In such cases, Supplier shall be informedimmediately.

3. Repair and/or replacement costs to be borne by Supplier – as far asthe objection is justified – shall include costs for the replaced part inclu-ding inland shipping costs as well as reasonable costs for removal andinstallation, and furthermore, if reasonably demandable in the individualcase, costs for possible provision of its fitters and assistants.

4. In particular, no warranty shall be granted in the following cases:Unsuitable or improper use, faulty assembly and/or putting into opera-tion by Purchaser or any third party, natural wear and tear, faulty ornegligent usage, improper maintenance1, unsuitable operating means,defective construction works, unsuitable construction ground, chemical,electrochemical or electrical impacts – as far as such impacts are notdue to Supplier's intention or negligence.

5. Supplier shall not be responsible for consequences resulting fromPurchaser's or any third Party's improper repairs. This provision shallapply also to alterations made to the object of delivery without Supp-lier's prior consent.

6. The claims as fixed under section 6 – except of those resulting fromsection 478, 479, 438 subsection 1 no. 2, 634a subsection 1 no. 2German Civil Code – shall expire by limitation one year after delivery.

1. General2. Price and payment3. Time of delivery, delivery delays4. Dispatch, transfer of risk, acceptance5. Retention of title6. Warranty

7. Liability of supplier for compensation8. Excluding a redemption9. Use of software10. Applicable law, jurisdiction

For complete Sales Terms and Delivery Conditions of ACO PassavantGmbH, please refer to:

www.aco-haustechnik.de/unternehmen

Page 20: Triplex-K Cleaning pipe Triplex-K-0 Single backflow stop ...

HT 5

12I/

10/2

009 �

LTC

- Su

bjec

t no

. 01

73.0

3.48

FSu

bjec

t to

tech

nica

l alte

ratio

ns

The ACO Group. A strong family you can build on.

ACO Passavant GmbH

Im Gewerbepark 11c36457 StadtlengsfeldTel. ++49 (0) 36965 819–0Fax ++49 (0) 36965 819–361

www.aco-haustechnik.de