TSi Power Corporation ~ Product Specifications and White Papers Book
Product Specificationsand White Papers
TSi Power CorporationTSi Power Corporation Power with a Precision Attitude™
2 TSi Power CorporationPower with a Precision Attitude
TSi-Power-Book-Cover-2006-10-16.pdf
Copyright © 2006 TSi Power Corporation. All rights reserved.
Please e-mail any problems with PDF loading or any errors to [email protected] Thank you.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
3
TSi Power Corporation
Product Specificationsand White Papers
TSi Power Corporation ~ Product Specifications and White Papers BookTSi Power Corporation ~ OverviewARm Series ~ Automatic Redundancy Module/UPS Bypass
ARm-1000 ~ 15A, 1750VA, 120vac .................................................................................. 11ARm-1000E ~ 10A, 2300VA, 230vac ................................................................................. 13
ATs Series ~ Automatic Transfer Switches for Redundant PowerATs-1000 ~ 30/40A, 3.6 /4.8kVA, 120vac ......................................................................... 17ATs-1000E ~ 30/40A, 7.2/9.6kVA, 230vac ........................................................................ 19
EXt Series ~ Battery Extension UnitsEXt-8000 ~ 120vac input, 24vdc output ............................................................................. 23
FLc Series ~ Ferroresonant Isolation Transformer Line ConditionersFLc-750/1000/1500 ~ 6.3/8.3/12A, 750VA/1/1.5kVA, 120vac........................................ 27
ILc Series ~ Low-Impedance Isolation Transformer Line ConditionersILc-600B/1000B ~ 5/ 8.3A, 600/1kVA, 120vac.................................................................. 31ILc-1800 / 2000 ~ 15/16A, 1.8/2kVA, 120vac.................................................................... 33ILc-2400/3600 ~ 20/30A, 2.4 /3.6kVA, 120vac................................................................. 35ILc-2400/3600-230V ~ 10/15A, 2.4/ 3.6kVA, 208/220/230 or 240vac............................. 37ILc-4400/5500-230V ~ 19/24A, 4.4/5.5kVA, 208/220/230 or 240vac ............................. 39ILc-9000/16500-0338 ~ 9/16.6kVA, 9/16.6kW, 400V delta in, 230/400V wye out.......... 41ILc-15000-0232 ~ 15kVA, 80A, 208vac, single phase......................................................... 43
ILc-Med Series ~ Medical Isolation TransformersILc-1000/1400Med4 ~ 8.3/ 11.7A, 1/ 1.4kVA, 120vac...................................................... 47
Table of Contents
4
Outdoor Series ~ UPS, Precision AVR and Line ConditionersOutdoorXUPs-600-6339 ~ 600VA, 480W, 120vac, UPS+AVR, Pole-mountable................ 51OutdoorXUPs-600A/B ~ 600VA, 420W, 120vac, UPS+AVR ............................................. 55OutdoorXUPs-600AHV/BHV ~ 600VA, 420W, 230vac, UPS+AVR ................................... 59OutdoorXUPs-600C ~ 600VA, 420W, 120vac, 11hrs@400W, UPS+AVR ........................ 63OutdoorXUPs-600CHV-OEM ~ 600VA, 420W, 230vac, 11hrs@400W, UPS+AVR .......... 67OD-XUPs-400C/600C ~ 400/600VA, 250/ 420W, 120vac, UPS+AVR ............................. 71OutdoorXUPs-1000A/B ~ 1000VA, 700W, 120vac, UPS+AVR ......................................... 75OutdoorXUPs-1000AHV/BHV ~ 1000VA, 700W, 230vac, UPS+AVR ............................... 79OutdoorUPs-400Conf1-2 ~ 400VA, 250W, 120vac ........................................................... 83Outdoor-UPs-10000-16000-21000 ~ 1 -1.6-2.1kVA, 750W-1.2kW-1.5kW, 120V .......... 85OutdoorXUPs-1000-8024~230vac in, 400W@230vac+200W@48vdc out, UPS+AVR. 89Outdoor-UPs-8009/8010 ~ 60 watts, 115 or 230 vac input, 12 vdc output UPS ................. 93Outdoor-UPs-8015/8016 ~ 96 watts, 115 or 230 vac input, 12 vdc output UPS ................. 97Outdoor-UPs-8011/8012 ~ 96 watts, 115 or 230 vac input, 24 vdc output UPS ............... 101Outdoor-UPs-8013/8014 ~ 96 watts, 115 or 230 vac input, 48 vdc output UPS ............... 105Outdoor-VRx-4400-0455/0460 ~ 4.4kVA, 230vac, PWM AVR+line conditioner ............. 109Outdoor-VRp-ILc-15000/30000-5339 ~ 15/30kVA, 400 vac delta,230/400 vac wye....... 113
RMk Series ~ Rack-mounting Kits for TSi Rack-mountable ProductsRMk Series ~ Rack-mounting kits for 19”, 23”, 24” racks, and wall-mounting.................... 119
SLc Series ~ Automatic Voltage Stabilizing Line ConditionersSLc-600/1200/1800 ~ 5/10/15A, 600VA/1.2 /1.8kVA, 120vac ...................................... 123SLc-600E/1200E /1800E ~ 2.6/5/ 7.8A, 600VA/ 1.2/1.8kVA, 230vac.............................. 125SLc-1100B/2000B ~ 9/16A, 1.1kVA/2 kVA, 120vac........................................................ 127SLc-1100BE/2000BE ~ 5.5 /10A, 1100/2000 VA, 230vac................................................. 129
XUPs and UPs Series ~ Uninterruptible Power SystemsXUPs-600/1000 ~ 600VA /1000VA, 420W/700W,120vac, UPS+AVR ........................... 133XUPs-600HV/1000HV ~ 600VA /1000VA, 420W/700W, 230vac, UPS+AVR................ 137UPs-400Wtb ~ 400VA, 250W, 120vac, with wide temperature battery ............................ 141XUPs-600/1000-8022 ~ 600VA /1000VA, 420W/700W, 115vac, OEM UPS+AVR....... 143XUPs-600/1000-8023 ~ 600VA /1000VA, 420W/700W, 230vac, OEM UPS+AVR....... 147UPs-600 ~ 600VA, 400W, 120vac ................................................................................... 151UPs-10000/16000/21000 ~ 1 /1.6/2.1kVA, 750/1000/1500W, 120vac......................... 153XUPs and UPs Automatic Shutdown Instructions for Windows XP Professional ................... 157
VRp Series ~ Precision PWM Automatic Voltage RegulatorsILc-2000-VRp-Dual-Range ~ 2kVA, 1.8kW, 120+240vac................................................ 161VRp-3000/5000-120V ~ 3/5kVA, 3/5kW, 40/70A, 120vac............................................. 165VRp-3000/5500-0230 ~ 3/5.5kVA, 3/5.5kW, 208/220/230/240vac .............................. 167VRp-3500-0233 ~ 3.5kVA, 3.5kW, 208/220/230/240vac ............................................... 169VRp-4000-0235 ~ 4kVA, 4 kW, 208/220/230 or 240vac, single phase ............................ 171VRp-7500/10000 ~ 7.5/10kVA, 7.5/10kW, 208/220/230 or 240vac, single phase......... 173VRp-9000/16500 ~ 9/16.5kVA, 9/16.5kW, 220/380V or 230/400vac wye, grey............ 175VRp-9000/16500-0338 ~ 9/16.5kVA, 9/16.5kW, 220/380vac or 230/400vac wye ........ 177VRp-15000/20000-0230 ~ 15/20kVA, 15/20kW, 208/220/230 or 240vac, single phase 179VRp-22500/30000-0338 ~ 22.5/ 30kVA, 22.5/30kW, 220/380V or 230/400vac wye .... 181VRp-ILc-16500-0338 ~ 16.5kVA, 16.5kW, 400vac delta to 230/400vac wye ................... 183
5
XINv Series ~ Dc to Ac Inverters with Transformer IsolationXINv-600/900-24V ~ 600/900VA, 600/900W, 24vdc to 115vac ................................... 189XINv-600E/900E-24V ~ 600/900 VA, 600/900 W, 24vdc to 230vac ............................... 193XINv-400/700/1400-48V ~ 400/700/1400VA, 400/700/1400W, 48vdc to 115vac ...... 197XINv-400E/700E/1400E-48V ~ 400/700/1400VA, 400/700/1400W, 48vdc to 230vac . 201
White Paper Series ~ TSi Power White Papers on Power ProtectionCoordination of Telecommunications SPDs in Countries with Unstable Power ................... 207TSi Power Case Studies ~ Mission-critical Solutions........................................................... 217Choosing UPS Protection for Underdeveloped Countries ................................................... 221Designing for Surge Immunity in International Markets....................................................... 225IEC 1312 Surge Protective Device Coordination................................................................. 231Benefits Provided by UPS and Line Conditioners with an Isolation Transformer.................. 235The Merits of a Standby UPS with a Modified Sine Wave Output....................................... 237Power Primer ~ A Guide to UPS and Power Terms ........................................................... 239Why Power Supplies and Semiconductors Fail ................................................................... 243Protection of Telecom Sites in Countries with Unstable Ac Mains....................................... 245
6
This page intentionally left blank.
TSi Power CorporationPower with a Precision Attitude
7
TSi Power Corporation
TSi Power Corporation ~ Overview
Power with a Precision Attitude™
Since 1987, TSi’s mission has been helping you solve your power protection problems, to help you satisfy your special equipment input power requirements, and to make it possible for you to relax easier, knowing your systems are protected to the best level possible.
What we manufacture and can customize for youTSi Power makes ac line conditioners, isolation transformers, precision ac automatic voltage regulators, automatic transfer switches (ATS), indoor and outdoor uninterruptible power supplies, dc to ac inverters, and overvoltage protection devices.TSi offers a range of unique line conditioners (including a medical grade series), isolation transformers, precision and extended range automatic voltage regulators and overvoltage protection products while offering competitive automatic transfer switches (ATS), UPS and dc to ac inverters. We specialize in custom products for relatively small volumes. Customization can mean offering special wiring terminals on a standard voltage regulator product or mean the development of a hospital grade power conditioner to a unique requirement. We create our power protection products from a library of standard board designs and an extensive library of CAD designs. This combination allows us to respond quickly and economically to many varying requirements.
Examples of TSi power quality products developed include, but are not limited to:• Custom precision voltage regulators with automatic bypass and built-in isolation
transformers.• Custom OEM uninterruptible power supplies with special wiring harnesses.
Ideal for use in control cabinets or for integration in OEM produced product.• Custom UPS meeting the requirements of medical OEM’s.• Custom ac power distribution units (PDU) for protection, distribution
and control of ac power for medical imaging systems.• Custom outdoor rated hardwired UPS (or AVR or line conditioners) with wide
temperature batteries, built-in auto bypass, and a wide input voltage range.• Custom line conditioners for universal input power supplies.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
8 TSi Power CorporationPower with a Precision Attitude
TSi-Power-Overview-2006-10-16.pdf
How we do itTSi strives to offer the very best value to our customers at every stage of the process. We do this by operating with a very low overhead through the utilization of appropriate technology and a cost-effective location in North-central Wisconsin. As such, we do not suffer from the productivity losses caused by big-city commuting and the high cost of living, which inevitably reduces the pool of qualified employees. Additionally, we have decided to eliminate most traditional layers of manufacturers' representatives and distributors, as they typically increase cost while in many cases not adding any significant value. We do however have a network of truly qualified and specialized distributors, representatives, retailers and OEMs that we work closely with to give you fast track service even when you are dealing with us indirectly. When you contact TSi Power we will do our best to provide technically competent and personalized service. Each customer is served by a sales engineer who understands ourproducts down to the board level and who has at least 10 years direct experience in powerprotection systems. At the bottom line, Peter Nystrom, President of TSi Power, has extensive worldwide experience in developing power protection products and solutions. His background includes founding Powervar; once serving as the three phase manager for Oneac; and his working for Ericsson developing solutions to their worldwide telecommunications power quality requirements. The TSi Power sales engineer will help each customer with the best possible solution to a particular requirement.
Our commitment to youOur commitment to customers is simple: we will serve you directly, or indirectly on a fast track, through our network of qualified and specialized distributors, representatives and OEMs.
What does this mean?• Faster communication, as information does not have to travel
back and forth through many layers of people• Reduced time to market and lower cost• Customers can be assured that the TSi sales engineer puts
them before commissions
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ARm SeriesAutomatic Redundancy Module / UPS Bypass
9
ARmARm
ARm Series ~ Automatic Redun-dancy Module/UPS Bypass
ARm SeriesAutomatic redundancy module
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
10 Page For NotesARm Series
ARm-Series-2006-10-16.pdf
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ARm SeriesAutomatic Redundancy Module/UPS Bypass
11
TSi Power’s ARm-1000 redundancy module automatic bypass system is recommended when no downtime from power outage is tolerated. Internet service providers, critical servers and telecom equipment, and export markets with bad power would find this technology valuable.
Typical ARm applications Designed for situations where reliability and predictability matter to the enterprise. Examples: telecommunications equipment, export markets, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment. Note: Both power sources Must be In Phase. If cannot be guaranteed, see the ATs-1000.
Key ARm benefitsThe ARm unit will provide uninterrupted ac to your load even in the event of UPS failure. ARms your critical equipment against extended power outages and catastrophic system shutdowns caused by accidental circuit breaker trips, UPS overload conditions, weak or old UPS batteries, routine and preventive maintenance of UPS, accidental UPS shut-down, loose power cords, or UPS failure.The ARM Series permits daisy chaining with any sine wave in-phase UPS, providing unlimited redundancy using any combination of independant (separate) ac circuits, UPS systems, generator-backed ac circuits, etc.
How the ARm worksThe ARm is fed by two ac power sources. When the primary power source detector circuit senses a loss of power on that circuit, a relay immediately switches the load over to the backup power source feed in less than 10 ms. This is fast enough to be invisible to computer switch-mode power supplies.
Two ac inputs ~ one ac output UPS bypass switch Compact
Key ARm Series features• Enables redundant UPS,
backup generators or otherac power sources to be used for a single load.
• Less than 10ms transfer time from source A to source B.
• Low cost• LED status indicators• DB9 communications interface• Audible alarms with
enable/disable switch
UPS #1 orother power source
automaticredundancy
module
primary feed
backup feed
UPS #2 orother power Source
system
telecom
mission
critical
serveror
ARmARmARm model 1000
15 amps1750 VA1750 watts120 volts
ARm-1000 ~ 15A, 1750VA, 120vac
Automatic Redundancy Module
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
12 SpecificationsARm-1000
Specifications ARm-1000Electrical
Capacity in VA (watts) 1750VA (1750W)Switching technology Fast operating/releasing relays
Inputs Nominal voltage 120 volts ac, single phase
Primary ac voltage 100 to 135 volts acBackup ac voltage 100 to 135 volts acFrequency range 60 Hz +/-5%Over-current protection Both primary and backup ac are protected by fusesFuse ratings 15 ampsTypical transfer time Less than 10ms, primary to back-up and back-up to primary
Input/output wire size 2.5mm2 (14 AWG) recommendedAc inputs (two) 1.8m(6 ft.) cords and 5-15P plugs
OutputNominal voltage 120 volts ac, single phaseLoad regulation Better than 2% from no load to full loadPower efficiency 98% or higherAc receptacles Four NEMA 5-15R output receptaclesIndicators Green LED for primary ac presence, yellow LED for backup ac
presence, flashing red LED for loss of primary or backup ac.Audible alarms Buzzer beeps when loss of primary or backup ac occurs.Audible alarm switch Audible alarm (buzzer) and alarm enable/disable switchAlarm contacts interface A rear-mounted DB-9 connector sends loss of primary ac
and loss of backup ac. (Pins 1 and 5 are used).Physical
Dimensions 254mmW x 203mmD x 76 mmH(10”wide x 8” deep x 3.2” high)
Weight 2.7 kg (6 lbs)Rack mount option Front mount kit for a 19” rack: # MK-5019A
EnvironmentalAmbient temperature 0o to +40oC(32o to +104oF). 10 to 90% relative humidity(non-condensing)
WarrantyWarranty Two year limited warranty, parts and labor.
Automatic redundancymodule
ARm system architecture
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
ARm-1000-120V-2006-10-16.pdf
Rear viewARm-1000
mechanical relay #1
ac output
backup * ac input
relay # 2
ground
120 V
power supply
alarmlogic
DB9 alarm signals
primary * ac input
120V
primary ac detection
120V
hot
neutral
neutral
hot
neutral
hot
* Note: Primary and back-up ac must be in phase. Otherwise, relay contacts may be damaged.
backup ac detection
15Afuses
10ms transfer time
ground
ground15A
fuses
Specifications
ARmARm
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ARm SeriesAutomatic Redundancy Module / UPS Bypass
13
ARm-1000E ~ 10A, 2300VA, 230vac
ARm model1000E
10 amps2300 VA2300 watts230 volts
Automatic Redundancy Module~230V
Two ac inputs ~ one ac output Automatic redundancy Compact
TSi Power’s ARm-1000 redundancy module automatic bypass system is recommended when no downtime from power outages is tolerated. Internet service providers, critical servers and telecom equipment, and export markets with bad power would find this technology valuable. The ARm Series permits daisy chaining with any UPS, providing unlimited redundancy using any combination of independant (separate) ac cir-cuits, UPS systems, generator-backed ac circuits, and so on. Note: Both power sources must be in phase. If cannot be guaranteed, see the ATs-1000E.
Typical applications Designed for situations where reliability and predictability matter to the enterprise. Examples: telecommunications equipment, export markets, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.
Key benefitsARm will provide uninterrupted ac to your load even in the event of UPS failure. ARms your critical equipment against extended power outages and catastrophic system shutdowns caused by accidental circuit breaker trips, UPS overload conditions, weak or old UPS batteries, routine & preventive maintenance of UPS, accidental UPS shut down, loose power cords, or UPS failure.ARm-1000 permits unlimited redundancy using any combination of independent (separate) ac cir-cuits, UPS systems, generator-backed ac circuits, etc.
How the ARm worksThe ARm is fed by two ac power sources. When the primary power source detector circuit senses a loss of power on that circuit, a relay immediately switches the load over to the backup power source feed in less than 10 ms. This is fast enough to be invisible to computer switch-mode power supplies.
Key features of the TSi Powerautomatic redundancy module
• Enables redundant UPS, backup generators or other ac power sources to be used for a single load.
• Less than a 10ms transfer time from source A to source B.
• Low cost• LED status indicators• DB9 communications interface• Audible alarms with
enable/disable switch
UPS #1 orother power source
automaticredundancy
module
primary feed
backup feed
UPS #2 orother power source
system
telecom
mission
critical
serveror
ARmARm
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
14 SpecificationsARm-1000E
ARm-1000E-230V-2006-10-16.pdf
Specification ARm-1000EElectrical
Capacity in VA (Watts) 2300VA (2300W)Switching technology Fast operating/releasing relays
Input Nominal voltage 230 volts ac single phase
Primary ac voltage 190 to 260 volts acBackup ac voltage 190 to 260 volts acFrequency range 50 Hz +/-5%Overcurrent protection FusesFuse ratings 10 ampsTypical transfer time Less than 10ms, primary to back-up and back-up to primary.
Ac input 1.8m (6 ft.) 3-conductor 2.5mm2 (14 AWG) SJT cord & IEC 320 plugs. Output
Nominal voltage 230 volts ac, single phase Load regulation Better than 2% from no load to full load Power efficiency 98% or higher Ac receptacles Four IEC 320 output receptacles Indicators Green LED for primary ac presence, yellow LED for backup ac
presence, flashing red LED for loss of primary or backup ac.Audible alarms Buzzer beeps when loss of primary or backup ac occurs.Audible alarm switch Audible alarm (buzzer) and alarm enable/disable switch. Alarm contacts interface
A rear-mounted DB-9 connector sends loss of primary ac and loss of backup ac signal for external power monitoring. Pins 4 and 5 are used.
PhysicalDimensions 254mm(10”) wide x 203.2mm(8”)deep x 76 mm(3.2” )high Weight 2.7kg (6 lbs)Rack mount option Front mount kit: For a 19” rack: use # MK-1019A
Special NoteIn Phase Requirement Primary and back-up ac must be sinusoidal and always be in phase.
EnvironmentalAmbient Temperature 0o to 40oC(32o to 104oF). 10 to 90% Relative humidity(non-condensing).
WarrantyWarranty Two year limited warranty, parts and labor.
Automatic redundancymodule
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
* Note: Primary and back-up ac must be in phase. Otherwise, relay contacts may be damaged.
Rear view(ARm-1000 120V shown)
ARmARm
mechanical relay #1
ac output
backup * ac input
relay # 2
ground
230 V
power supply
alarmlogic
DB9 alarm signals
primary * ac input
230V
primary ac detection
230V
hot
neutral
neutral
hot
neutral
hotbackup ac detection
10Afuses
10ms transfer time
ground
ground10A
fuses
ARm system architecture
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ATs SeriesAutomatic Transfer Switch
15
ATs SeriesAutomatic transfer switches
ATs Series ~ Automatic Transfer Switches for Redundant Power
ATs ATs
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
16 ATs SeriesAutomatic Transfer Switch
ATs-Series-2006-10-16.pdf
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ATs SeriesAutomatic Transfer Switch
17
ATs-1000 ~ 30/40A, 3.6 /4.8kVA, 120vac
backup feed
TSi Power’s ATs Series user customizable automatic transfer switches (ATS) are for enabling the use of redundant power sources, such as small uninterruptible power systems feeding industrial controls, PLC cabinets, internet servers, telecom systems, etc.
Typical ATs applications Designed for situations where reliability and predictability matter to the enterprise. Examples: telecommunications equipment, rectifiers, cell sites, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.
Key ATs benefitsIf the ATs DIP Switch is set to “Fast transfer” (20ms typical transfer time) mode, then when redundant power sources are present, it can replace an expensive UPS system and battery banks for most computers, telecommunication, and industrial equipment (since switchmode power supplies used in most new electronics equipment provide a minimum of 20ms in capacitor hold-up time under full load conditions). If a ‘positive power break’ is needed during the transfer, then the ATs may be set to “Slow transfer” (1 second) mode to ensure a full 1 second ac power outage during transfer.Also, the two ac sources do not have to be synchronized since the ATs is designed to switch between two asynchronous ac sources without damage to itself or to equipment powered by switchmode power supplies.
How the ATs worksThe ATs is fed by two independent ac power sources. When the primary power source detector circuit senses a loss of power on the primary circuit, it immediately switches the load over to the backup power source feed in less than 20 ms. Upon restoration of primary power, the ATs will switch back in less than 20ms. This is fast enough to be invisible to computer switch-mode power supplies.
ModelATs-1000
30 amps3600 VA3600 watts120 volts
ATs-1000-40A40 amps4800 VA4800 watts120 volts
Two ac inputs ~ one ac output Automatic transfer switch Compact
Key ATs features• Enables redundant UPS, backup
generators or other ac powersources to be used for a single load.
• Less than a 20ms transfer time from source A to source B.
• User selectable transfer times of 20ms, 40ms or 1 second.
• Built-in circuit breakers• Designed to handle out-of-phase
and/or asynchronous ac sources• Rack-mountable• LED status indicators• DB9 communications interface• Audible alarms with
enable/disable switch
AutomaticTransfer Switch
UPS #1 orother power source
automatic transferswitch
primary feed
UPS #2 orother power source
system
telecom
mission
critical
serveror
ATs ATs
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
18 ATs SeriesATs-1000-30A/40A
hardwire120vac+/-20%
Specification ATs-1000 (30A) ATs-1000-40AElectrical
Capacity in VA (Watts) 3600VA (3600W) maximum 4800VA (4800W) maximumSwitching technology Solid-state relays (SSR’s)
Input Nominal voltage 120 volts ac single phase
Primary ac voltage 95 to 135 volts ac Backup ac voltage 95 to 135 volts ac Frequency range 47 to 63 HzOver-current protection User resettable circuit breaker Circuit breaker ratings 30 amps 40 ampsTypical transfer time 20ms, 40ms or 1000ms (user selectable) Transfer time selection Via an internal four position DIP switch (factory set at 20ms)
Input /output wire size 10mm2 (AWG8) minimum Ac input Hardwire terminals (Optional ~ plugs and receptacles)
OutputNominal voltage 120 volts ac, single phase Load regulation Better than 2% from no load to full loadPower efficiency 98% or higher Ac distribution Hardwire terminals (plugs and receptacles optional).
Hardwired units must be installed by a qualified electrician.Indicators Green LED for primary ac presence, yellow LED for backup ac
presence, flashing red LED for loss of primary or backup ac. Audible alarms Buzzer beeps when loss of primary or backup ac occurs. Audible alarm switch Audible alarm (buzzer) and enable/disable switch. Alarm contacts A rear-mounted DB-9 connector sends loss of primary ac and
loss of backup ac signal for external power status monitoring. Physical
Dimensions 406mm (16”) wide x 83mm (3.25”)high x 305mm(12”)deep Weight 7kg (15 lbs) Rack mount options Front mount kits: For a 19” Rack: use # MK-5019A
For a 23” Rack: use # MK-5023A For a 24” Rack: use # MK-5024ACenter mount kits: For a 19” Rack: use # MK-5019F For a 23” Rack: use # MK-5023F For a 24” Rack: use # MK-5024F
Wall or Floor mount kits: use # MK-5000CEnvironmental
Ambient temperature 0o to 40oC (32° to 104°F). 10 to 90% relative humidity (non-condensing).
WarrantyWarranty Two year limited warranty, parts and labor.
Automatic transferswitch
ATs system architecture
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trade-marks of their respective companies.
ac output
120vac
hardwire120vac+/-20%
solid-staterelay #1
L2
L1backup ac input
ground
solid-staterelay # 2
ground
circuit breaker30 or 40A
power supply
alarm
logic ‘xx’msdelay
DB9 alarm signalsground
L
L
L2
L1primary ac input
primary ac detection
backup ac detection
circuit breaker
30 or 40A
Knockout covers and cable glands for line cords shown
ATs rear view withknockout covers off ready to hardwire
ATs ATs
ATs-1000-120V-2006-10-16.pdf
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ATs SeriesAutomatic Transfer Switch
19
ATs-1000E ~ 30/40A, 7.2/9.6kVA, 230vac
Key ATs features • Enables redundant UPS, backup
generators or other ac powersources to be used for a single load.
• Less than a 20ms transfer time from source A to source B.
• User selectable transfer times of 20ms, 40ms or 1 second.
• Built-in circuit breakers• Designed to handle out-of-phase
and/or asynchronous ac sources• Rack-mountable• LED status indicators• DB9 communications interface• Audible alarms with
enable/disable switch
TSi Power’s ATs Series user customizable automatic transfer switches (ATS) are for enabling the use of redundant power sources, such as small uninterruptible power systems feeding industrial controls, PLC cabinets, internet servers, telecom systems, etc.
Typical ATs applications Designed for situations where reliability and predictability matter to the enterprise. Examples: telecommunications equipment, rectifiers, cell sites, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.
Key ATs benefitsIf the ATs DIP Switch is set to “Fast transfer” (20ms typical transfer time) mode, then when redundant power sources are present, it can replace an expensive UPS system and battery banks for most computers, telecommunication, and industrial equipment (since switchmode power supplies used in most new electronics equipment provide a minimum of 20ms in capacitor hold-up time under full load conditions). If a ‘positive power break’ is needed during the transfer, then the ATs may be set to “Slow transfer” (1 second) mode to ensure a full 1 second ac power outage during transfer.Also, the two ac sources do not have to be synchronized since the ATs is designed to switch between two asynchronous ac sources without damage to itself or to equipment powered by switchmode power supplies.
How the ATs worksThe ATs is fed by two ac power sources. When the primary power source detector circuit senses a loss of power on that circuit, it immediately switches the load over to the backup power source feed in less than 20ms. Upon restoration of primary power, the ATs will switch back in less than 20ms. This is fast enough to be invisible to computer switch-mode power supplies.
ModelATs-1000E
30 amps7200 VA7200 watts230 volts
ATs-1000E-40A40 amps7200 VA7200 watts230 volts
Two ac inputs ~ one ac output Automatic transfer switch Compact
Automatic Transfer Switch
ATs ATs
backup feed
UPS #1 orother power source
automatic transferswitch
primary feed
UPS #2 orother power source
system
telecom
mission
critical
serveror
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
20 ATs SeriesATs-1000E-30A/40A
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
solid-staterelay #1
hardwire L2
L1
ac output
backup ac input
Ground
solid-staterelay # 2
ground
Hardwire230vacpower supply
alarm
logic ‘xx’msDelay
DB9 alarm signalsground
L2
L1
L2
L1primary ac input
230vac primary ac Detection
backup ac Detection
230vaccircuit breaker
30 or 40A
circuit breaker30 or 40A
ATs-1000E-230V-2006-10-16.pdf
Specification ATs-1000E (30A) ATs-1000E-40A Electrical
Capacity in VA (watts) 7200VA (7200W) maximum 9600VA (9600W) maximum Switching technology Solid-state relays (SSR’s)
Input Nominal voltage 230 volts ac single phase
Primary ac voltage 200 to 270 volts acBackup ac voltage 190 to 270 volts acFrequency range 47 to 63 HzOver-current protection User resettable circuit breakerCircuit breaker ratings 30 amps 40 ampsTypical transfer time 20ms, 40ms or 1000ms (user selectable)Transfer time selection Via a four position DIP switch ~ factory set at 20ms
Input /output wire size 10mm2 (AWG8) Ac input Hardwire terminals (plugs and receptacles optional - please call)
OutputNominal voltage 230 volts ac, single phase Load regulation Better than 2% from no load to full loadPower efficiency 98% or higher Ac distribution Hardwire terminals (plugs and receptacles optional).
Hardwired units must be installed by a qualified electrician.Indicators Green LED for primary ac presence, yellow LED for backup ac
presence, flashing red LED for loss of primary or backup ac. Audible alarms Buzzer beeps when loss of primary or backup ac occurs. Audible alarm switch Audible alarm (buzzer) and enable/disable switch. Alarm contacts A rear-mounted DB-9 connector sends loss of primary ac and
loss of backup ac signal for external power status monitoring. Physical
Dimensions 406mm (16”) wide x 83mm (3.25”)high x 305mm(12”)deep Weight 7kg (15 lbs) Rack mount options Front mount kits: For a 19” Rack: use # MK-5019A
For a 23” Rack: use # MK-5023A For a 24” Rack: use # MK-5024ACenter mount kits: For a 19” Rack: use # MK-5019F For a 23” Rack: use # MK-5023F For a 24” Rack: use # MK-5024F
Wall or Floor mount kits: use # MK-5000CEnvironmental
Ambient temperature 0o to 40oC (32° to 104°F). 10 to 90% Relative Humidity(non-condensing).
Warranty Warranty Two year limited warranty, parts and labor.
ATs system architecture
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trade-marks of their respective companies.
Specifications
ATs ATs
Automatic transferswitch
Knockout covers and cable glands for line cords shown
ATs rear view withknockout covers off ready to hardwire
EXt SeriesBattery Extension Cabinets
21
EXt SeriesBattery extension cabinets
EXt Series ~ Battery Extension Units
EXtEXt
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
22 EXt SeriesBattery Extension Cabinets
EXt-Series-2006-10-16.pdf
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
EXt SeriesBattery Extension Cabinet
23
EXt-8000 ~ 120vac input, 24vdc output
EXt model8000
120vac input24vdc ouput
Built-in battery chargers Battery extension cabinets for TSi UPs
Key features of the EXt-8000• 120 vac input• Two or more units can be
daisy-chained for back-up of 8 hours or more
• Rack-mountable profile• Rack-mounting kits• Internal battery charger provides
recharge in less than 6 hours• 48 vdc bus voltage• Low cost• Two year limited warranty
EXtEXt
The modular TSI Power Battery Extension Unit is designed to provide extended back-up for use with TSI's UPs-10000, 16000 and 21000 systems.
Typical applications Sometimes power goes out for hours and a standard five or ten minute reserve just won't do. Longer hold-up times may be needed for users that upload/download large files on the Internet, or the following applications: extensive account-ing or engineering programs, point-of-salesystems, control systems, portable medical systems, inventory control systems, as well as telecom systems that need to be up all the time.
Key benefitsEXt-8000 units can be daisy-chained to provide hold-up times of eight hours or more depending on the number of EXt-8000 units and the load it powers. EXt-8000 can be rack-mounted and several different mounting kits are available. EXt-8000 can also be mounted on a movable cart together with a TSi UPS to provide long-term back-up while moving equipment from location to location.
How the EXt-8000 worksEach EXt-8000 contains its own battery charger, which keeps typical recharge time to 6 hours or less. This feature is extremely important as extension modules containing only batteries have to be recharged from the UPS's internal charger – recharge can take several days for large batteries, which may result in back-up not being available when needed the most.
Battery Extension Cabinet forUPs-10000/16000/21000
A TSi UPs-16000 and EXt-8000 Battery extension unit shown mounted inside a 19” wide cabinet using MK-8019A and
MK-8019B Front and Rear rack-mount kits
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
24 SpecificationsEXt-8000
EXt-8000-120V-2006-10-16.pdf
Batteryextensioncabinet
EXtEXt Specification EXt-8000 (for 120vac UPs-10000/16000/21000)AC Input
Input 100 to 133VRMS ac, 60Hz Input cord and plug 6 feet (1.8 m) three-conductor 14 AWG SJT cord with NEMA 5-15P plug
Battery charger/output Back-up time Supplies an additional 35 to 45 minutes backup time, depending on load.
Battery charger 54vdc, 3ABattery recharge time 4 to 6 hours typical recharge time( 48vdc, 14 Ah )
Battery bus voltage 48vdcBattery connectors Anderson PP 50 male/female low-voltage connectors Power consumption 150 watts during charging
PhysicalSize 432mm(17")wide x 533mm(21")deep x 127 mm(5”)highWeight 32 kg (70 lbs)
EnvironmentAmbient temperature 0° to 40oC(32° to 104°F). 10 to 90% Relative humidity(non-condensing).
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
Rack-mount optionsRack mount kits Please call factory for assistance on rack-mount options.
UPS compatibilityDesigned for use with: 120vac UPs-10000, UPs-16000 and UPs-21000
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
UPs-10000 with four EXt-8000
Rear view ofEXt-8000 end unit
Rear view of UPs-10000
Front view of EXt-8000
Rear view of EXt-8000 middle unit
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
FLc SeriesFerroresonant Transformer Line Conditioner
25
FLc SeriesFerroresonant transformer line conditioners
FLc Series ~ Ferroresonant Isolation Transformer Line Conditioners
FLcFLc
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
26 FLc SeriesFerroresonant Line Conditioner
FLc-Series-2006-10-16.pdf
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
FLc SeriesFerroresonant Isolation Transformer Line Conditioner
27
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
FLc-750/1000/1500 ~ 6.3/8.3/12A, 750VA/1/1.5kVA, 120vac
To provide isolated constant output voltage and stable power, even when the incoming ac mains or generator set voltage is extremely low or high.
Typical applications FLc Series line conditioners are suitable where you want the ultimate in industrial-strength ac line protection for computers, point-of-sale terminals, copiers, data acquisition and control systems, as well as other data processing equipment.The FLc Series is recommended for use with a stable load and input frequency, and where audible noise and heat are of less concern.
Key benefits The FLc Series constant voltage regulated output protects switch-mode power supplies from failure caused by unstable ac mains. FLc provides a combination of isolation and constant output voltage transformer technology, which makes it an ideal device to replace a dedicated circuit when cost of installing same is prohibitive. Highest grade ac power can be obtained even when the mains contain high noise and/or harmonics. FLc provides three stage surge protection and significant reduction of surge voltage dV/dt rise times. The FLc internal transformer draws only sinewave current, which helps to reduce harmonics in supplied loads. The FLc line conditioner can be used between a UPS and the ac mains to provide greater protection for the connected equipment, while saving the UPS's internal batteries for true black-outs.
How the FLc Series worksFLc incorporates a constant voltage output ferroresonant isolation transformer, which provides 100% isolation from the input ac line. The secondary neutral is bonded to ground thus eliminating all surge voltages between neutral and ground. Surge protection is further enhanced due to the built-in low-pass filter, which reduces fast-rise transients from 6kV/µs to less than 10V/µs.
FLc model750
6.3 amps750 VA750 watts120 volts
1000 8.3 amps1000 VA1000 watts120 volts
1500 12.5 amps1500 VA1500 watts120 volts
Key features of the TSi Powerferroresonant line conditioner
• Constant output voltage guaranteed• Ferroresonant isolation transformer
with neutral-to-ground bond.• Coordinated surge protection
per IEC61312.3• Advanced noise and interference
filter reduces dV/dt from 6kV/µS to less than 10V/µS
• Front panel power switch• Replaces dedicated ac circuit• Reduces harmonics from
non-linear loads• The best surge protection available• Five year warranty
Ferroresonant Constant Voltage Output Isolation Transformer Line Conditioner
Ferroresonant transformer Voltage regulation UL/cUL listedFLcFLc
Power with a Precision Attitude™
28 SpecificationsFLc-750/1000/1500
FLc-750-1000-1500-2006-10-16.pdf
Ferroresonant line conditioner
Specification FLc-750 FLc-1000 FLc-1500Electrical
Capacity in VA (watts) 750VA (750W) 1000VA (1000W) 1500VA (1500W)Transformer Type Constant voltage output ferroresonant isolation transformer.
Input Nominal voltage 120 volts ac
Operating voltage 80 to 145 volts ac Nominal frequency 60Hz
Ac 6 ft. input cord with NEMA 5-15R plug NEMA 5-15R plug NEMA 5-20R plug Output
Ac output voltage 120 volts ac +/-3%Waveform Output wave form: sine wave, regardless of input for 60Hz +/-3% Noise filtering Low-pass filter reduces noise over a wide frequency range.
The measured rate of voltage rise/fall (dV/dt of the remnant waveform is less than 200V/µS with input test waveform dV/dt of 6kV/µS.
Surge protection Three-way surge protection system. Surge test conditions Per ANSI/IEEE C62.41-1991 test pulse,
Category B3, Combination Wave, 6000V, 3000A.Test pulse injection: Line-neutral, line-ground, and neutral-ground.
Surge let-through voltages
Remnant voltage: L-N: 5V, L-G: 5V, N-G: 0.5V.
Power efficiency 90% or higher for full load conditions.80% typical for half load conditions.
Power on/off switch Master on/off rocker power switch control. Ac output receptacles Six (NEMA 5-15R). Optional terminal blocks for OEMs.
PhysicalDimensions 235mm(9.25”)wide x 165mm(6.5”)high x 330mm(13.0”)deepWeight 25 kg(55 lbs) 27.2 kg(60 lbs) 27.2 kg(60 lbs)
SafetyAgency approvals UL and cUL 1950 Listed
EnvironmentalAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Five year limited warranty, parts and labor.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may betrademarks of their respective companies.
FLc Series system architecture
Rear viewFLc-1500
FLcFLc
groundsurge
protectionand
80-145Vac
input hotfuse
neutral
hot
ground
EMI / RFInoise filter
neutral
constant voltage output ferroresonant isolation transformer
120V+/-3%ac output
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ILc SeriesIsolation Line Conditioner
29
ILc SeriesIsolation transformer line conditioners
ILc Series ~ Low-Impedance Isolation Transformer Line Conditioners
ILcILc
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
30 ILc SeriesIsolation Line Conditioner
ILc-Series-2006-10-16.pdf
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ILc SeriesIsolation Transformer Line Conditioner
31
Key features of the TSi Powerisolation line conditioner
• Coordinated surge protectionper IEC 61312.3
• Low-impedance isolation transformer
• True isolation• Common-mode noise elimination• Advanced noise and interference
filter reduces dV/dt from 6kV/µS to less than 10V/µS
• High efficiency• Four ac outlets• Low weight• Quiet operation• Five year warranty
TSi Power’s ILc Series line conditioners provide the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line, the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection and filtering devices.
Typical applications Designed for situations where reliability and predictability matter to the enterprise. Examples include: point-of-sale terminals, tele-communications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.
Key benefitsILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.
How ILc conditioners workThe integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC 61312.3
ILc-600B/1000B ~ 5/ 8.3A, 600/1kVA, 120vac
Low-impedance Isolation transformer UL/cUL listed ILcILcILc model600B
5 amps600 VA600 watts120 volts
1000B8.3 amps1000 VA1000 watts120 volts
Isolation Transformer Line Conditioner
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
32 SpecificationsILc-600B/1000B
ILc-600B-1000B-2006-10-16.pdf
Isolation line conditioner
groundsurge
protectionand
acinput hot
circuitbreaker
neutral
hot
ground
ILcoutput
EMI / RFI noise filter
neutral
isolationtransformer
ILcILc
ILc system architecture
Specification ILc-600B ILc-1000BElectrical
Capacity in VA (Watts) 600VA (600W) 1000VA (1000W)Transformer type Low-impedance E-I core isolation transformer
Input Nominal voltage 120 volts ac single phase
Operating voltage 100 to 130 volts ac Nominal frequency 60 Hz +/-3 Over-current protection User resettable circuit breaker Circuit breaker rating 5 amps 10 amps
Ac input cord 6 foot long ac power cord with NEMA 5-15P plugOutput
Nominal voltage 120 volts ac single phase Power efficiency 94% (typical) Total harmonic distortion < 1%Surge protection A three-stage surge protection system consisting of
isolation transformer, capacitor and M.O.V. is included. Surge test conditions Per ANSI/IEEE C62.41-1991 test waveforms Surge let-throughvoltages
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V
Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt) of the remnant waveform
is less than 10V/µS with input test waveform dV/dt of 6kV/µS. Ac output receptacles Four (NEMA 5-15R.)
PhysicalDimensions 152mm (6”) wide x 127mm (5”)high x 229mm(9”)deepWeight 11.3kg (25 lbs) 15kg (33 lbs)
SafetyAgency approvals UL and cUL listed
EnvironmentalAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Five year limited warranty, parts and labor.
Rear view ILc-1000Bshown without
6’ line cord/plug
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may betrademarks of their respective companies.
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ILc SeriesIsolation Transformer Line Conditioner
33
ILc-1800 / 2000 ~ 15/16A, 1.8/2kVA, 120vac
Low-impedance Isolation transformer UL/cUL listed ILcILcILc model1800
15 amps1800 VA1800 watts120 volts
200016 amps2000 VA2000 watts120 volts
Key features of the TSi Powerisolation line conditioner
• Coordinated surge protection per IEC61312.3
• Low-impedance isolation transformer
• True isolation• Common-mode noise elimination• Advanced noise and interference
filter reduces dV/dt from 6kV/µS to less than 10V/µS
• High efficiency• Six ac outlets• On/off rocker switch• Low weight• Quiet operation• Five year warranty
TSi Power’s ILc Series line conditioner provides the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line, the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection and filtering devices.
Typical applications Designed for situations where reliability and predictability matter to the enterprise. Examples include: point-of-sale terminals, tele-communications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.
Key benefitsILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.
How ILc conditioners workThe integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.3.
Isolation Transformer Line Conditioner
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
34 ILc SeriesILc-1800/2000
Specification ILc-1800 ILc-2000Electrical
Capacity in VA (watts) 1800VA (1800W) 2000VA (2000W)Transformer type Low-impedance E-I core isolation transformer
Input Nominal voltage 120 volts ac, single phase
Operating voltage 100 to 130 volts acNominal frequency 60Hz +/-3Over-current protection User resettable circuit breaker built-inCircuit breaker rating 15 amps 20 amps
Ac input cord 6 foot cord with 5-15P plug 6 foot cord with 5-20P plugOutput
Nominal voltage 120 volts ac, single phase Power efficiency 95 to 97% (typical)Total harmonic distortion < 1%Surge protection A three-stage surge protection system consisting of
isolation transformer, capacitor and MOV is included. Surge test conditions Per ANSI/IEEE C62.41-1991 test waveforms Surge let-throughvoltages
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5 V Ring wave: L-N: 20 V, L-G: 20 V, N-G: 0.5V
Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5VThe measured rate of voltage rise/fall (dV/dt) of the remnant waveform
is less than 10V/µS with input test waveform dV/dt of 6kV/µS.Indicators Green LED indicates ac power is present On/off switch On/off rocker style switchAc Receptacles Six NEMA 5-15R Six NEMA 5-20R
Physical Dimensions 216mm(8.5”)wide x 165mm(6.5”)high x 279mm(11.0”)deep
Weight 22.7 kg(50 lbs) 22.7 kg(50 lbs)Safety
Agency approvals UL and cUL listed. Environmental
Ambient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing). Warranty
Warranty Five year limited warranty, parts and labor.
ILc-1800-2000-2006-10-16.pdf
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may betrademarks of their respective companies.
Isolation line conditioner
groundsurge
protectionand
acinput hot
circuitbreaker
neutral
hot
ground
ILcoutput
EMI / RFI noise filter
neutral
isolationtransformer
ILcILc
ILc system architecture
Rear viewILc-1800
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ILc SeriesIsolation Transformer Line Conditioner
35
Low-impedance Isolation transformer 3 stage protection
ILc-2400/3600 ~ 20/30A, 2.4 /3.6kVA, 120vac
ILcILc
TSi Power’s ILc Series line conditioners provide the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line ~ the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection/filtering devices.
Typical applications Designed for situations where reliability and predictability matter to the enterprise. Examples include: point-of-sale terminals, tele-communications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.
Key ILc benefitsILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.
How ILc conditioners workThe integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.3.
ILc model2400
20 amps2400 VA2400 watts120 volts
3600 30 amps3600 VA3600 watts120 volts
Key features of the TSi Powerisolation line conditioner
• Coordinated multi-stage surge suppression
• Low-impedance isolation transformer
• True isolation• Common-mode noise elimination• Advanced noise and interference
filter reduces dV/dt from 6kV/µS to less than 10V/µS
• High efficiency• On/off rocker style power switch• Low weight• Quiet operation• Five year warranty
Isolation Transformer Line Conditioner
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
36 SpecificationsILc-2400-3600
ILc-2400-3600-120V-2006-10-16.pdf
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may betrademarks of their respective companies.
groundsurge
protectionand
acinput hot
circuitbreaker
neutral
hot
ground
ILcoutput
EMI / RFI noise filter
neutral
isolationTransformer
ILcILc
ILc system architecture
Specification ILc-2400 ILc-3600Electrical
Capacity in VA (watts) 2400VA (2400W) 3600VA (3600W)Transformer type Low-impedance E-I core isolation transformer
Input Nominal voltage 120 volts ac single phase
Operating voltage 100 to 130 volts ac Nominal frequency 60 Hz +/-3Circuit breaker rating 20 amps 30 amps
6 foot ac input cord with NEMA 5-30 plug ( Specify )Output
Nominal voltage 120 volts ac, single phase Power efficiency 97% (typical) Total harmonic distortion <1%Surge protection A three-stage surge protection system consisting of
isolation transformer, capacitor and M.O.V. is included.Surge test conditions Per ANSI/IEEE C62.41-1991 test waveformsSurge let-throughvoltages
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V
Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5VThe measured rate of voltage rise/fall (dV/dt) of the remnant waveform
is less than 10V/µS with input test waveform dV/dt of 6kV/µS.Power on/off On/off rocker style power switch/circuit breakerIndicators Green LED indicates ac power is presentAc output receptacles(Other options available)
Four NEMA 5-20R and four NEMA 5-15R _
Four NEMA 5-20R andfour NEMA 5-15R
PhysicalDimensions 254mm(10”)wide x 190mm(7.5”)high x 368mm(14.5”)deepWeight 27.3 kg(60 lbs) 36.3 kg(80 lbs)
SafetyAgency approvals Designed to meet UL, cUL and IEC standards. Over-current protection User resettable circuit breaker.
EnvironmentalAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Five year limited warranty, parts and labor.
Rear view
Isolation line conditioner
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ILc SeriesIsolation Transformer Line Conditioner
37
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ILc-2400/3600-230V ~ 10/15A, 2.4/ 3.6kVA, 208/220/230 or 240vac
ILcILc
TSi Power’s ILc Series line conditioners provide the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line ~ the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection/filtering devices.
Typical applications Designed for situations where reliability and predictability matter to the enterprise. Examples include: point-of-sale terminals, tele-communications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.
Key benefitsILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.
How ILc conditioners workThe integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.3.
ILc model2400-230V
10 amps2400 VA2400 watts208/220,230/240 volts
3600-230V 15 amps3600 VA3600 watts208/220,230/240 volts
Key features of the ILc seriesisolation line conditioner
• Coordinated multi-stage surge suppression
• Low-impedance isolation transformer
• True isolation• Common-mode noise elimination• Advanced noise and interference
filter reduces dV/dt from 6kV/µS to less than 10V/µS
• High efficiency• On/off rocker style power switch• Low weight• Quiet operation• Five year warranty
Low-impedance Isolation transformer 3 stage protection
Isolation Transformer Line Conditioner
38 SpecificationsILc-2400/3600-230V
ILc-2400-3600-230V-2006-10-16.pdf
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may betrademarks of their respective companies.
ILcILc
ILc system architecture
Rear viewwith optionalreceptacles
groundsurge
protectionand
acinput hot
circuitbreaker
neutral
hot
ground
ILcoutput
EMI / RFInoise filter
neutral
isolationtransformer
208, 220,230, or240V
208, 220,230, 240V
Specification ILc-2400-230V ILc-3600-230VElectrical
Capacity in VA (watts) 2400VA (2400W) 3600VA (3600W)Transformer type Low-impedance E-I core isolation transformer
Input Nominal voltage 208/220/230 or 240 volts ac, single phase
Operating voltage 190 to 250 volts acNominal frequency 60Hz +/-3Circuit breaker rating 15 amps 20 amps
6 foot ac input cord with Hardwire (terminal block connector)Output
Nominal voltage 208/220/230 or 240 volts ac, single phasePower efficiency 97% (typical)Total harmonic distortion <1%Surge protection A three-stage surge protection system consisting of
isolation transformer, capacitor and M.O.V. is included.Surge test conditions Per ANSI/IEEE C62.41-1991 test waveformsSurge let-throughvoltages
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V
Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5VThe measured rate of voltage rise/fall (dV/dt) of the remnant waveform
is less than 10V/µS with input test waveform dV/dt of 6kV/µS.Power on/off On/off rocker style power switch/circuit breakerIndicators Green LED indicates ac power is presentAc output receptacles(Other options available)
Hardwired output terminals (L1, Neutral, and Ground) are standard. Optional ac receptacles are available.
PhysicalDimensions 254mm(10”)wide x 190mm(7.5”)high x 368mm(14.5”)deepWeight 27.3 kg(60 lbs) 36.3 kg(80 lbs)
SafetyAgency approvals Designed to meet UL, cUL standards Over-current protection User resettable circuit breaker
EnvironmentalAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Five year limited warranty, parts and labor.
Isolationtransformer line conditioner
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ILc SeriesIsolation Transformer Line Conditioner
39
ILc-4400/5500-230V ~ 19/24A, 4.4/5.5kVA, 208/220/230 or 240vac
ILcILcILc model4400-230V
19 amps4400 VA4400 watts208/220,230/240 volts
5500-230V24 amps5500 VA5500 watts208/220,230/240 Volts
TSi Power’s ILc Series line conditioners provide the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line. The secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection/filtering devices.
Typical applications Designed for situations where reliability and predictability matter to the enterprise. Examples include: point-of-sale terminals, tele-communications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.
Key benefitsILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.
How ILc conditioners workThe integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.3.
Key features of the TSi Powerisolation line conditioner
• Coordinated multi-stage surge suppression
• Low-impedance isolation transformer
• True isolation• Common-mode noise elimination• Advanced noise and interference
filter reduces dV/dt from 6kV/µS to less than 10V/µS
• High efficiency• On/off rocker style power switch• Low weight• Quiet operation• Five year warranty
Isolation Transformer Line Conditioner
Low-impedance Isolation transformer 3 stage protection
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
40 SpecificationsILc-4400/5500-230V
ILc-4400-5500-230V-2006-10-16.pdf
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may betrademarks of their respective companies.
Isolation transformerline conditioner
ILcILc Specification ILc-4400 ILc-5500Electrical
Capacity in VA (watts) 4400VA (2400W) 5500VA (5500W)Transformer type Low-impedance E-I core isolation transformer
Input Nominal voltage 208/220/230 or 240 volts ac, single phase
Operating voltage 190 to 250 volts acNominal frequency 60 Hz +/-3Circuit breaker rating 25 amps 30 amps
Ac input Hardwire (terminal block connector) Output
Nominal voltage 208/220/230 or 240 volts ac, single phase Power efficiency 97% (typical)Total harmonic distortion <1%Surge protection A three-stage surge protection system consisting of
isolation transformer, capacitor and MOV is included. Surge test conditions Per ANSI/IEEE C62.41-1991 test waveforms. Surge let-throughvoltages
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V
Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5VThe measured rate of voltage rise/fall (dV/dt) of the remnant waveform
is less than 10V/µS with input test waveform dV/dt of 6kV/µS.Power on/off On/off rocker style power switch/circuit breaker. Indicators Green LED indicates ac power is present. Ac output Hardwired output terminals (L1, neutral, and ground) are standard.
Optional ac receptacles are available. Physical
Dimensions 254mm(10”)wide x 190mm(7.5”)high x 368mm(14.5”)deepWeight 43.56 kg(100 lbs) 54.6 kg(120 lbs)
SafetyAgency approvals Designed to meet UL, cUL standards. Over-current protection User resettable circuit breaker.
EnvironmentalAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Five year limited warranty, parts and labor.
ILc system architecture
groundsurge
protectionand
acinput hot
circuitbreaker
neutral
hot
ground
ILcoutput
EMI / RFInoise filter
neutral
isolationtransformer
208, 220,230, or240V
208, 220,230, 240V
Specifications
Rear viewwith optionalreceptacles
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ILc SeriesIsolation Transformer Line Conditioner
41
ILc-9000/16500-0338 ~ 9/16.6kVA, 9/16.6kW, 400V delta in, 230/400V wye out
ILcILcILc model9000-0338
9 kVA9 kW400V delta3 phase input230/400V wye3 phase output
16500-033816.5 kVA16.5 kW400V delta3 phase input230/400V wye3 phase output
International Isolation transformer 3 stage protection
Key features of the TSi isolation line conditioner
• Coordinated surge protection per IEC61312
• Three separate low-impedance isolation transformers (1 per phase) are used for maximum reliability
• Common-mode noise elimination• Advanced noise and interference
filter reduces dV/dt from 6kV/µS to less than 10V/µS
• Wall-fixing kit included• High efficiency• Quiet operation• Five year warranty
TSi Power’s ILc Series line conditioners provide the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line, the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection and filtering devices.
Typical applications Designed for situations where reliability and predictability matter to the enterprise. Examples include: sensitive telecommunications industrial and medical equipment, and other sensitive, specialized microprocessor-based equipment.
Key benefitsILc Series conditioners provide maximum equipment protection against surges, spikes and transients, for higher equipment reliability and maximum equipment operating life. In addition, improved repeatability, fewer reboots or system lock-ups. In addition, a reduction in equipment down time and service costs can be expected.TSi’s use of three separate transformers, one per phase, minimizes single phasing or lost phase problems associated with a common core three phase transformer.
How ILc conditioners workThe integral isolation transformers provide complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground. The leakage inductance of the isolation transformer in combination with capacitive elements and MOVs, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.
Three Phase Low-Impedance Isolation Transformer Line Conditioner
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
42 SpecificationsILc-9000-16500-0338
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Specification ILc-9000-0338 ILc-16500-0338Electrical
Capacity in VA (watts) 9 kVA (9,000W) 16.5 kVA (16,500W)Transformer type Three separate isolation transformers are used (1 per phase)
Input Nominal voltage 400 volts ac three phase delta
Operating range 400V(L-L), +30%,-20% Nominal frequency 50 Hz +/-3Input circuit breakers 3 x 30 amps (ganged) 3 x 40 amps (ganged)
Ac connections Terminal block (L1, L2, L3 and ground wires) provided. Output
Nominal voltage 230/400 volts ac three phase wye Power efficiency 96% at 400V(L-L), (typical) Operating range 230/400 volts +30%,-20% Matching AVR VRp-9000-0338 VRp-16500-0338 Surge protection A three-stage surge protection system consisting of
isolation transformer, capacitor and MOV is included. Surge test conditions* Class 2 and Class 3 simulated lightning surge (Combination wave)
Per ANSI/IEEE C62.41-1991, Cat.C test waveform: 6kV, 3kA, 8x20µS. *Note: ILc is not a Primary (Class 1) surge arrestor - customer must provide a separate primary surge arrestor at service entry point.
Surge let-throughvoltages
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5VRing wave: L-N: 20V, L-G: 20V, N-G: 0.5VCombination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt) of the remnant waveform is less than 10V/µS with input test waveform dV/dt of 6kV/µS.
Common mode filtering Neutral-ground bond eliminates all noise or voltage on neutral (< 0.5V) Normal mode filtering A built-in inductor-capacitor filter attenuates EMI/RFI noise from output. Ac connections Terminal block (L1, L2, L3, neutral and ground wires) provided.
PhysicalDimensions 610mm(24”)W x 965mm(38”)H x 305mm(12”)D. Rubber mounting feet. Weight 140kg(309 lbs) 170kg (375 lbs)
SafetyStandards Designed to meet IEC 60950. Enclosure protection class: IP20.
EnvironmentalAmbient temperature -5° to +35°C (23° to 95°F). 10 to 90% relative humidity(non-condensing).
Cooling method Fan cooled.Warranty
Warranty Five year limited warranty, parts and labor.
ILc-9000-16500-0338-3Ph-2006-10-16.pdf
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
ILcILc
groundsurge
protectionand
acinput hot
circuitbreaker
neutral
hot
ground
ILcoutput
(per phase)
EMI / RFInoise filter
neutral
isolationtransformer
Isolation line conditioner
ILc system architecture (per phase)
Left-side front view
Specifications
ILc SeriesIsolation Transformer Line Conditioner
43
ILc-15000-0232 ~ 15kVA, 80A, 208vac, single phase
Low-impedance Isolation transformer Line conditionerILcILcModelILc-15000-0232
80 amps15 kW15 kVA208 voltsSingle phase
Key features• Coordinated surge protection
per IEC 61312• Low-impedance
isolation transformer• True isolation• Common-mode noise elimination• Advanced noise and interference
filter reduces dV/dt from 6kV/µS to less than 10V/µS
• High efficiency• Input circuit breaker• Low weight• Quiet operation• Five year warranty
TSi Power’s ILc Series line conditioner provides the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line, the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection & filtering devices.
Typical applications Designed for situations where reliability and predictability matter to the enterprise. Examples include: telecommunications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.
Key benefitsILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.
How the ILc-15000 worksThis ILc line conditioner utilizes a low-impedance transformer, capacitors and ultra-fast Metal Oxide Varistors (MOVs) in an optimized 3-way noise filtering and IEC 61312 compliant surge protection design to provide maximum protection of sensitive industrial and telecommunications equipment against harmful surges, spikes and noise produced by lightning strikes, utility grid switching and heavy machinery turn on and off cycles. The neutral-ground bond at the output winding of the transformer also provides maximum protection against the harmful effects of stray voltage and/or noise on the neutral conductor.
Low-Impedance Isolation Transformer Line Conditioner
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
44 SpecificationsILc-15000-0232
Specification ILc-15000-0232Electrical
Capacity in VA (watts) 15kVA (15kW)Transformer technology Low-impedance isolation transformer
Input Rating Nominal voltage 208 volts ac, single phase
Operating input voltage 190 to 240 volts acNominal frequency 47 to 63HzMaximum input current 80AInput circuit breaker Two pole, 90A circuit breaker is included. Operating displacement power factor
0.3 leading to 0.3 lagging
Output RatingNominal output voltage 208 volts ac, single phaseLoad regulation Better than +/-2% Power efficiency 95% (typical) Load power factor Tightly coupled isolation transformer winding provides compatibility
with switchmode power supplies and SCR controlled devices.Ac output quality Qualifies as a separately derived ac power source per NEC 250-5D.Surge protection A three-stage surge protection system forms a hybrid filter recom-
mended by IEC 61312 (coordination of surge protective devices). Filter consists of an isolation transformer, capacitors and MOVs.
Surge test conditions Per ANSI/IEEE C62.41-1991 single pulse, ring and combination wave.(Category C test waveforms: 6000V, 3000A, 8x20µS).
Surge test results(remnant voltages)
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5VRing wave: L-N: 20V, L-G: 20V, N-G: 0.5VCombination wave: L-N: 250V, L-G: 250V, N-G: 0.5V
Reduction in rate of voltage rise/fall (dv/dt)
The measured rate of voltage rise/fall (dV/dt) of the remnant waveform is <10V/µS w/input test waveform dV/dt of 6kV/µS. (600:1 reduction ratio).
Common mode noise filtering
Neutral-to-ground bond eliminates all noise or voltage on output neutral.
Normal mode noise filtering
A built-in inductor-capacitor filter attenuates EMI/RFI noise from the output.
MechanicalInput/output connection Hard-wired (terminal blocks). Dimensions 610mm(24”) wide x 710mm(28”)high x 560mm(22”)deep. Finish and weight Powder-painted. Weight is approx. 181kg (400 lbs).
Environmental and WarrantyAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing). Heat loss and cooling At 80% load, heat loss is approx. 850 BTU/hr. Convection cooled.Warranty (expected life) Five year limited warranty, parts and labor. (twenty years).
ILc-15000-0232-2006-10-16.pdf
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies. These units are for indoor use only.
groundsurge
protectionand
acinput L1
circuitbreaker
L2
hot
ground
ILcoutput
EMI / RFInoise filter
neutral
isolationtransformer
ILcILc
ILc system architecture
Note: Unit ships on a wooden pallet for ease of shipping and handling.
208vac
ground
208vac
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ILc-Med SeriesMedical Isolation Transformer
45
ILc-Med SeriesMedical isolation transformers
ILc-Med Series ~ Medical Isolation Transformers
ILc-MedILc-Med
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
46 ILc-Med SeriesMedical Isolation Transformer
ILc-Med-Series-2006-10-16.pdf
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ILc-Med SeriesMedical Isolation Transformer
47
ILc-1000/1400Med4 ~ 8.3/ 11.7A, 1/ 1.4kVA, 120vac
TSi Power’s ILc-Med line conditioners provide the best all-round hospital-grade 'low-leakage current' line conditioning and surge protection for sensitive medical equipment. The integral isolation transformer provides 100% isolation from the input ac line, the secondary neutral-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection and filtering devices.
Key ILc-Med benefitsTSi Power’s hospital- grade line conditioner reduces the need for a high quality “isolated and dedicated” line, while eliminating interference from adjacent sources of disturbances. ILc-Med contributes to enhanced systems operation, greater reliability, improved repeatability, fewer reboots and system lock-ups and extended operating life. Reductions in hospital equipment down time and service costs can be expected.
How ILc-Med conditioners workThe integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.3.In addition, ILc-Med has an extremely low input ac leakage current (typical 50µA) rating which exceeds both domestic US (UL 60601-1), and international (IEC 601) medical standards for a leakage current limit of 300µA maximum for non-patient connected medical equipment and instruments.
Typical ILc-Med applications These are designed for medical systems requiring line conditioners having UL 60601-1 (formerly UL 2601 and UL 544) agency approval. Examples include: imaging systems, analyzers, patient care/ monitoring equipment, audio systems and other patient-critical applications.
ILc-Med model1000Med4
8.3 amps1000 VA1000 watts120 volts
1400Med4 11.7 amps1400 VA1400 watts120 volts
Hospital-grade Isolation transformer UL/cUL 60601-1
Hospital Grade UL/cUL 60601-1 Medical Isolation Transformer
Key features of the TSi Powermedical isolation transformer
• Typical leakage current <50µA• UL/cUL 60601-1 listed • Low-impedance
isolation transformer• Coordinated surge protection
per IEC61312.3• Filtering and MOVs• Resettable circuit breaker• Eight “green dot” medical grade
outlets/receptacles• High efficiency• 100% common mode
noise elimination• True isolation• Quiet operation• Five year warranty
ILc-MedILc-Med
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
48 SpecificationsILc-1000Med4/1400Med4
ILc-1000-1400Med4-120V-2006-10-16.pdf
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may betrademarks of their respective companies.
Rear viewILc-1000Med4
Rear viewILc-1400Med4
Specification ILc-1000Med4 ILc-1400Med4Electrical
Capacity in VA (watts) 1000VA (1000W) 1400VA (1400W)Transformer type Hospital-grade low-leakage E-I core isolation transformer
Input Nominal voltage 120 volts ac, single phase
Operating voltage 100 to 130 volts ac Nominal frequency 60Hz +/-5%Leakage current 50µA typical (300µA maximum)Over-current protection User resettable circuit breakerCircuit breaker rating 10 amperes 15 amperes
Ac input cord 15 foot long hospital-grade ac power cord with NEMA 5-15P plugOutput
Nominal voltage 120 volts ac, single phase Power efficiency 94 to 96%Total harmonic distortion < 1%Surge protection A three-stage surge protection system consisting of isolation
transformer, capacitor and MOV is included.Surge test conditions Per ANSI/IEEE C62.41-1991 test waveformsSurge let-throughvoltages
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5 VRing wave: L-N: 20 V, L-G: 20 V, N-G: 0.5VCombination wave: L-N: 250V, L-G: 250V, N-G: 0.5VThe measured rate of voltage rise/fall (dV/dt) of the remnant waveform is less than 10V/µS with input test waveform dV/dt of 6kV/µS.
Ac output receptacles Eight hospital-grade “green dot” NEMA 5-15R receptacles. Physical
Dimensions 190mmW x 133mmH x 229mmD(7.5” W x 5.25”H x 9.0”D)
216W x 165H x 229mmD(8.5” W x 6.5”H x 9.0”D)
Weight 29 lbs (13.2kg) 49 lbs (22.3kg)Safety
Agency approvals UL/cUL 60601-1 listed (formerly UL 2601). UL control number 85EF.
EnvironmentalAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Five year limited warranty, parts and labor.
ILc-Med system architecture
groundsurge
protectionand
acinput hot
circuitbreaker
neutral
hot
ground
ILc-Medoutput
EMI / RFInoise filter
neutral
isolationtransformer
ILc-MedILc-Med
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor UPs SeriesOutdoor Uninterruptible Power Systems
49
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor Series ~ UPS, Precision AVR and Line Conditioners
Outdoor SeriesUPS, AVR and line conditioners
Outdoor Outdoor
*Please note that the UPs-400Wtb, though it haswide temperature batteries and is often used in OEM
outdoor enclosures, does not have it’s own outdoorenclosure, so is found in the UPS section. And, the
OEM XUPS units, designed for wide temperatureenvironments, are also suitable for use inside outdoor
enclosures, and are found in the UPS section.
50 Outdoor UPs SeriesOutdoor Uninterruptible Power Systems
This page intentionally left blank.
Outdoor-Series-2006-10-16.pdf
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
51
OutdoorXUPs-600-6339 ~ 600VA, 480W, 120vac, UPS+AVR, Pole-mountable
Outdoor XUPsand EXt modelXUPs-600-6339
600 VA480 watts120/240V input120V output40 min @480W-20° to +60°C;-40° to +60°Cwith optionalbattery heater
EXt-6369For 600 VA,or 480 wattsload, adds 80 min @480W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
Pure sine wave Wide temperature batteries Voltage regulation
The XUPs-600-6339 outdoor UPS is constructed with extreme wide temperature batteries, and is housed in a weather protected IP44(NEMA-3R) enclosure designed to be mounted on a power pole and blend in with the environment. This unit offers line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with noise filtering, communications capability, maintenance bypass switch and options of automatic bypass switch, extended battery backup, and ‘hotel’ capability for OEMs.
Key Outdoor XUPs benefitsThis rugged UPS design, with microprocessor-controlled 15kHz sine wave inverter, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. Battery run-times for the outdoor XUPs-600-6339 are approximately 40 minutes at 480 watts load; the optional EXt-6369 provides an additional 80 minutes.
How the Outdoor XUPs worksThe Outdoor XUPs Series UPS provides auto-matic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 140vac, and undervoltage protection with a threshold of 95vac per leg. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems. Optional automatic bypass switches to bypass in case of UPS failure, and may be used to enable some maintenance without loss of power to the load.By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators, a convenience outlet, maintenance bypass switch, circuit breakers, and a power on/off switch.
Typical applicationsThis heavy duty outdoor UPS is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial RTUs.
Key Outdoor XUPs features• Cabinet and color are designed
for pole mounting and blending in with the environment
• Full weather outdoor protectionIP44(NEMA-3R) metal cabinet
• Pure sine wave output• Over/under-voltage protection• Built-in maintenance bypass.
Automatic static bypass (optional) • Wide temperature batteries• Surge protection and noise filtering• Automatic voltage regulation• Comprehensive array of
status bargraphs for voltage,load and battery levels
• Two year warranty on electronicsManufacturer’s battery warranty
XUPsOutdoor XUPsOutdoor
Outdoor UPS with Voltage Regulation
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
52 SpecificationsXUPs-600-6339
Specifications XUPs-600-6339Electrical
Capacity in VA (watts) 600VA (480W maximum output)UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter.
InputNominal voltage 120/240vac, split phase, L1, L2, N & Ground with 2 pole circuit breaker Input current maximum UPS: 5A @ 120vac. Convenience outlet: 15A @ 120vac.UPS operating voltage 95 to 140vac (within which UPS will not have to use batteries).Frequency 47 to 63Hz.Main electric service connect capability
Unit can be combined with utility type meter can if required, and internal provision for NG bond is available when used for main service.
Hardwire connection Four (4) position terminal blocks provided for four (4) x 1.5mm2 (16AWG) connections via 25mm(1”) liquid-tight cable glands.
OutputNominal voltage 120 volts ac Voltage regulation 115 vac +/- 8% upon changes in line or load Crest ratio 3:1Output waveform Pure sine wave, less than 3% THD with linear load Power efficiency 97%, under full load conditions Power on/off switch On/off rocker style power switch Transfer time <4 millisecondsBatteries Two 32 amp hours, 12 vdc wide temperature sealed gel-cells
rated for -20° to +60°C (-4° to+140°F); -40° to +60°C (-40° to+140°F) with optional battery heater.
Battery backup time and recharge time
40 minutes @ 480 watts load. 2 hours @ 240 watts load.8 hours to 90% capacity after full discharge.
Optional extra battery pack(s) for longer backup time(heater optional)
Optional matching size EXt-6369 extra battery cabinet available with SB50 connector. Provides extra four 12vdc, 32Ah wide temperature batteries for an extra 80 minutes of run-time @ 480W load. 24 hours to 90% capacity after full discharge. Weight: 55kg(120 lbs).
SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (for TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Surge let-throughvoltages
Test pulse injection: Line-Neutral: Line-Ground: and Neutral-Ground. Combination Wave: L-N: 450V, L-G: 300 V, N-G: 300V
Status indicators 5 LEDs for load level: 0 to 100% of rated load. 5 LEDs for battery charge level: from 0 to 100% of rated charge. 3 LEDs for: in boost, buck or normal mode. 3 LEDs for: inverter on/off, battery fault and overload.
Output connections Two (2) switched UPS output circuits for a combined maximum 4A, and one (1) switched 15A convenience outlet.
Maintenance bypass and optional ARm unit
Includes built-in maintenance bypass switch. Optional static bypass switch (automatic redundancy module) available in case of UPS failure.
PhysicalDimensions 508mm(20”)high x 406mm(16”)wide x 203mm(8”)deepWeight 45kg(100 lbs) Steel cabinet Full weather IP44(NEMA-3R) outdoor design in gray color. Mounting options Pole mountable (steel bands optional for steel monopole mounting),
pedestal (ground) or wall mountable. “H” style bracket included. Environmental
Operating temperature,battery heater option
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater.
XUPsOutdoor XUPsOutdoor
Outdoor line-interactive UPSwith automaticvoltage regulation,maintenancebypass and wide temperature batteries
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
53
XUPs-600-6339 at a glanceHeavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• 40 minutes @ 480 watts load• 120 minutes @ 480 watts load
with the addition of an EXt-6369
• 115vac +/-8% output from 95 to 140vac input without going to batteries
• Microprocessor-controlled 15kHz PWM sine wave inverter
• Built-in bypass switch for UPS maintenance.
• Optional automatic bypass in case of UPS failure
XUPsOutdoor XUPsOutdoor
one size of OEM “hotel” area
internal status LED panel
input breaker, 2 switched UPS output circuits; and one 15A convenience outlet
input terminal blocks
bottominside view
top insideview
120/240V split phase input
ac surgeprotection, noise filter
andovervoltage,undervoltage disconnect
circuits
L1
battery and
charger
relay 2
115vac +/-8%regulated output
neutral
EXt-6369extra battery
cabinet(optional)
logic
-10%
+10%0%
2-polecircuit breaker
chassis
relay 1
inverterac
dcgroundearth
XUPs-600-6339 system architecture
L2
neutral DB9 comm portterminal blockoptional heater
connect
optionalheater15A
convenienceoutlet
ARmauto
bypassunit
(optional)
switch A
switch B
switch C
maintenance bypass switch
neutral
neutral
L1
L1
L1
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
54 Outdoor XUPs SeriesXUPs-600-6339
Mounting on a pole with steel bands or boltsFollowing are two pictures showing the ‘H’ style mounting bracket on the rear of the Outdoor XUPs Series unit. This bracket facilitates mounting to a standard pole via the two bolt holes in the center U channel, or to a steel monopole with optional steel bands through the two sets of steel band slots in the sides of the U channel. The Outdoor XUPs cabinet (or OutdoorEXt cabinet) is mounted to the ‘H’ style bracket with four (4) mounting feet at the four (4) corners.For detailed information on the optional steel bands, please call.
Outdoor-XUPs-600-6339-2006-10-16.pdf
XUPsOutdoor XUPsOutdoor
center alignedbolt holes for standard polemounting
minimum height609mm (24”)above groundrecommended
steel mountingband slots
508mm (20”)
Mounting feetclose-up drawing
IP44(NEMA-3R)metal cabinet
holes for 25mm (1”)liquid-tightcable glands
19mm(.75”)
19mm(.75”)
19mm(.75”)
19mm(.75”)
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
55
OutdoorXUPs-600A/B ~ 600VA, 420W, 120vac, UPS+AVR
Outdoor XUPsmodel600A
600 VA420 watts120 vac1 hour @420W2.2 hrs @210W 8 hours@50W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
600B 600 VA420 watts120 vac2.2 hrs @420W 4.6 hrs @210W 16 hrs @ 50W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
Pure sine wave Wide temperature batteries Voltage regulation
The TSi Power Outdoor XUPs-600A/B units are constructed with extreme wide temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.
Key Outdoor XUPs benefitsThis rugged UPS design, with microprocessor-controlled 15kHz sine wave inverter and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-times for the OutdoorXUPs-600A are approximately 1 hour at 420 watts load, 2.2 hours at 210 watts load, and 8 hours at 50W; for the OutdoorXUPs-600B, approximately 2.2 hours at 420 watts, 4.6 hours at 210 watts, and 16 hours with a 50 watts load.
How the Outdoor XUPs worksThe Outdoor XUPs Series UPS provides auto-matic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 140vac, and undervoltage protection with a threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems.LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.
Typical applicationsThis heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key Outdoor XUPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44(NEMA-3R) metal cabinet• Pure sine wave output• Over/under-voltage protection• Remote power on/off (optional) • Wide temperature batteries• Heavy-duty surge protection
and noise filtering• Automatic voltage regulation• Comprehensive array of
status bargraphs for voltage,load and battery levels
• Two year warranty on electronicsOne year warranty on batteries
XUPsOutdoor XUPsOutdoor
Outdoor UPS with Voltage Regulation
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
56 SpecificationsOutdoorXUPs-600A/B
Specification OutdoorXUPs-600A OutdoorXUPs-600BElectrical
Capacity in VA (watts) 600VA (420W) UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter
Input Nominal voltage 120 volts ac
Input current 5A maximum @ 120 vac Operating voltage 95 to 140 vac without using batteriesOperating frequency 47 to 63Hz
OutputNominal voltage 120 volts ac Voltage regulation 115vac +/- 8% upon changes in line or load Crest ratio 3:1Output waveform Pure sine wave, less than 3% THD with linear load Power efficiency 97%, under full load conditions Power on/off switch On/off rocker style power switch Transfer time <4 millisecondsBatteries 32 amp hours, 24 vdc 64 amp hours, 24 vdc
Wide temperature sealed gel-cells -20° to +60°C (-4° to+140°F); -40° to +60°C (-40° to+140°F) with optional battery heater.
Battery backup time 1 hour @ 420 watts load.2.2 hours @ 210 watts load.8 hours @ 50 watts load.
2.2 hours @ 420 watts load.4.6 hours @ 210 watts load.16 hours @ 50 watts load.
Recharge time 8 hours to 90% capacity after full discharge.
16 hours to 90% capacity after full discharge.
SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (for TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Surge let-throughvoltages
Test pulse injection: Line-Neutral: Line-Ground: and Neutral-Ground. Combination Wave: L-N: 450V, L-G: 300 V, N-G: 300V
Status indicators 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload.
Input/output connections
3 position terminal blocks provided for 3 x 1.5mm2 (16AWG)connections via 25mm(1”) liquid-tight cable glands.
PhysicalDimensions 406mm(16”)wide x 305mm(12”)deep x 711mm(28”)highWeights 45kg(100 lbs) 68kg(150 lbs)
Steel cabinet Full weather IP44(NEMA-3R) outdoor design. Mounting options Bolting or banding mountable to monopole via optional ‘H’ style
bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting ‘feet’ are included.
EnvironmentalOperating temperature,battery heater option and cooling method
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater. Thermostat controlled exhaust fan.
Moisture protection(optional)
Optional conformal coating of electronic boards is available formoisture resistance to protect against high humidity environments.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
XUPsOutdoor XUPsOutdoor
Outdoor line-interactive UPSwith automaticvoltage regulationand extreme/wide temperature batteries
Specifications
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Ac input and UPS output cable entry via two 25mm (1”) liquid-tight cable glands
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
57
OutdoorXUPs-600A/B at a glanceHeavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• 24vdc battery bus• 1 hour @ 420 watts load, or
2.2 hours @ 210 watts load with the OutdoorXUPs-600A
• 2.2 hours @ 420 watts load, or4.6 hours @ 210 watts load withthe OutdoorXUPs-600B
• 115vac +/-8% output from 95 to 140vac inputwithout going to batteries
• Weather protected IP44/NEMA-3Rpainted metal cabinet
• SNMP compatible (optional)• Less than 4ms transfer time • Microprocessor-controlled
15kHz PWM sine wave inverter• Thermostat controlled
fan is included
utilityac
input heavy-dutyac surge
protection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
battery and
charger
hot
relay 2
regulated XUPs output 115vac +/-8%
neutral
external battery(optional)
logic
-10%
+10%0%
95 to 140vac
chassis
relay 1
Inverterac
dc
groundchassis
groundearth
OutdoorXUPs-600A/B system architecture
XUPsOutdoor XUPsOutdoor
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
optional bandable or boltable monopole mounting brackets
accircuit
breaker
58 Outdoor XUPs SeriesOutdoorXUPs-600A/B
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Mounting on a concrete pad with Unistrut® (or similar)Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad.The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners.For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
OutdoorXUPs-600-2006-10-16.pdf
XUPsOutdoor XUPsOutdoor
406mm (16”)
thermostatcontrolledhot air vent forexhaust fan
concrete pad609mm (24”)above groundrecommended
XUPsoutput
hole to hole368mm(14.5”)
305mm(12”)
711mm (28”)
acinput
doorhinges
intakeair ventunderneath
Outdoor XUPspad mounted 711mm
(28”)Mounting feetclose-up drawing
IP44(NEMA-3R)metal cabinet
holes for 25mm (1”)liquid-tightcable glands
door latch
19mm(.75”)
19mm(.75”)
19mm(.75”)
19mm(.75”)
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
59
OutdoorXUPs-600AHV/BHV ~ 600VA, 420W, 230vac, UPS+AVR
Outdoor XUPsmodel600AHV
600 VA 420 watts230 vac1 hour @420W 2.2 hrs @ 210W 8 hours @ 50W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
600BHV 600 VA 420 watts230 vac2.2 hrs @420W 4.6 hrs @210W 16 hrs @ 50W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
The TSi Outdoor XUPs-600AHV/BHV units are constructed with extreme/wide temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. This series offers line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.
Key Outdoor XUPs benefitsThis rugged UPS design, with microprocessor-controlled 15kHz sine wave inverter and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-times for the OutdoorXUPs-600AHV are approximately 1 hour at 420 watts load, 2.2 hours at 210 watts load, and 8 hours at 50W; for the OutdoorXUPs-600BHV, approximately 2.2 hours at 420 watts load, 4.6 hours at 210 watts and 16 hours with a 50 watts load.
How the Outdoor XUPs worksThe Outdoor XUPs Series UPS provides auto-matic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 280vac, and undervoltage protection with a threshold of 190vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems.LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.
XUPsOutdoor XUPsOutdoor
Outdoor UPS with Voltage Regulation
Pure sine wave Wide temperature batteries Voltage regulation
Typical applicationsThis heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key Outdoor XUPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44(NEMA-3R) metal cabinet• Pure sine wave output• Over/under-voltage protection• Remote power on/off (optional) • Wide temperature batteries• Heavy-duty surge protection
and noise filtering• Automatic voltage regulation• Comprehensive array of
status bargraphs for voltage,load and battery levels
• Two year warranty on electronicsOne year warranty on batteries
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
60 SpecificationsOutdoorXUPs-600AHV/BHV
Specification OutdoorXUPs-600AHV OutdoorXUPs-600BHVElectrical
Capacity in VA (watts) 600VA (420W) UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter.
Input Nominal voltage 230 volts ac
Input current 2.5A maximum @ 230vacOperating voltage. Freq. 190 to 280vac without using batteries. Frequency: 47 to 63Hz.
OutputNominal voltage 230 volts acVoltage regulation 230 vac +/-8% upon changes in line or load.Crest ratio 3:1Output waveform Pure sine wave, less than 3% THD with linear load. Power efficiency 97%, under full load conditions. Power on/off switch On/off rocker style power switch.Transfer time <4 millisecondsBatteries 32 amp hours, 24vdc 64 amp hours, 24vdc
Wide temperature sealed gel-cells -20° to +60°C (-4° to+140°F); -40° to +60°C (-40° to+140°F) with optional battery heater.
Battery backup time 1 hour @ 420 watts load.2.2 hours @ 210 watts load.8 hours @ 50 watts load.
2.2 hours @ 420 watts load.4.6 hours @ 210 watts load.16 hours @ 50 watts load.
Recharge time 8 hours to 90% capacity after full discharge.
16 hours to 90% capacity after full discharge.
SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (for TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Surge let-throughvoltages
Test pulse injection: Line-Neutral: Line-Ground: and Neutral-Ground. Combination Wave: L-N: 450V, L-G: 300 V, N-G: 300V
Status indicators 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload.
Input/output connections
3 position terminal blocks provided for 3 x 1.5mm2 (16AWG) connections via liquid-tight cable glands.
PhysicalDimensions 406mm(16”)wide x 305mm(12”)deep x 711mm(28”)high Weights 45kg (100 lbs) 68kg (150 lbs)
Steel cabinet Full weather IP44(NEMA-3R) outdoor design Mounting options Bolting or banding mountable to monopole via optional ‘H’ style
bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting ‘feet’ are included.
SafetyAgency approvals Designed to meet UL, cUL and IEC safety standards
EnvironmentalOperating temperature,battery heater option and cooling method
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater. Thermostat controlled exhaust fan.
Moisture protection(optional)
Optional conformal coating of electronic boards is available for moisture resistance to protect against high humidity environments.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
XUPsOutdoor XUPsOutdoor
Outdoor line-interactive UPSwith automaticvoltage regulationand extreme/wide temperature batteries
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Ac input and UPS output cable entry via two 25mm (1”) liquid-tight cable glands
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
61
utilityac
input heavy-dutyac surge
protection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
battery and
charger
hot
relay 2
regulated XUPs output 230vac +/-8%
neutral
external battery(optional)
logic
-10%
+10%0%
190 to 280vac
chassis
relay 1
inverterac
dc
groundchassis
groundearth
OutdoorXUPs-600AHV/BHV system architecture
OutdoorXUPs-600AHV/BHV at a glanceHeavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• 24vdc battery bus• 1 hour @ 420watts load, or
2.2 hours @ 210watts load with the OutdoorXUPs-600AHV
• 2.2 hours @ 420watts load, or4.6 hours @ 210watts load withthe OutdoorXUPs-600BHV
• 230vac +/-8% output from 190 to 280vac inputwithout going to batteries
• Weather protected IP44 (NEMA-3R) painted metal cabinet
• SNMP compatible (optional)• Less than 4ms transfer time • Microprocessor-controlled
15kHz PWM sine wave inverter• Thermostat controlled
fan is included
XUPsOutdoor XUPsOutdoor
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
optional bandable or boltable monopole mounting brackets
accircuit
breaker
62 Outdoor XUPs SeriesOutdoorXUPs-600AHV/BHV
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi OutdoorXUPs-600HV-2006-10-16.pdf
Mounting on a concrete pad with Unistrut® (or similar)Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad.The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners.For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
XUPsOutdoor XUPsOutdoor
406mm (16”)
thermostatcontrolledhot air vent forexhaust fan
concrete pad609mm (24”)above groundrecommended
UPSoutput
hole to hole368mm(14.5”)
305mm(12”)
711mm (28”)
acinput
doorhinges
intakeair ventunderneath
Outdoor XUPspad mounted
711mm (28”)
Mounting feetclose-up drawing
IP44 (NEMA-3R )metal cabinet
holes for 25mm (1”)liquid-tightcable glands
door latch
19mm(.75”)
19mm(.75”)
19mm(.75”)
19mm(.75”)
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
63
OutdoorXUPs-600C ~ 600VA, 420W, 120vac, 11hrs@400W, UPS+AVR
Outdoor XUPsmodel600C
600 VA 420 watts120vac 50/60Hz-20° to +60°C;-40° to +60°Cwith optional battery heater11 hrs @ 400W
Pure sine wave Wide temperature -40° to +60°C UPS Voltage regulation
Extreme Wide Temperature Outdoor UPS with Voltage Regulation and 11 Hours Backup Time
XUPsOutdoor XUPsOutdoor
Typical applications This heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key Outdoor XUPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44(NEMA-3R) metal cabinet• Pure sine wave output• Automatic voltage regulation with
over/under voltage protection• Remote power on/off (optional) • Wide temperature batteries• Heavy-duty surge protection
and noise filtering• Comprehensive array of
status bargraphs for voltage,load and battery levels
• Two year warranty on electronicsOne year warranty on batteries
The TSi Power Outdoor XUPs-600C is constructed with wide temperature batteries and housed in a weather protected IP44 (NEMA-3R) enclosure. It offers line-interactive automatic voltage regulation, over/under-voltage and surge protection with heavy duty noise filtering, communications capability and extended battery backup.
Key Outdoor XUPs-600C benefitsThis rugged UPS design with optional conformal coated boards and microprocessor-controlled 15kHz sinewave inverter reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs-600C extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-time for the OutdoorXUPs-600C is 11 hours with a 400 watts load.
How the Outdoor XUPs worksThe Outdoor XUPs-600C provides constant voltage regulation, surge protection, including an overvoltage threshold protection of 140vac, and an undervoltage threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the Outdoor XUPs-600C will transfer to battery in less than 4 milliseconds, enabling uninterrupted operation of your telecom, surveillance systems, signaling or other outdoor systems.LEDs provide visual assessment of UPS status. By unlatching the two latches, the front door swings open; inside the cabinet, an array of LED status indicators and power on/off control switch are provided.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
64 SpecificationOutdoorXUPs-600C
Specification OutdoorXUPs-600C Electrical
Capacity in VA (watts) 600VA (420 watts) UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter.
Input Nominal voltage 120 vac
Input current 5 A maximum @ 115vac Operating voltage 95 to 140vac, without using batteries. Operating frequency 47 to 63Hz
OutputNominal voltage 115 vac Voltage regulation 115 vac +/-8% for mains ac & battery modes, all operating conditions. Crest ratio 3:1Output waveform Pure sine wave, less than 3% THD with linear load.Power efficiency 97%, under full load conditions. Power on/off switch On/off rocker style power switch.Transfer time <4 milliseconds Batteries Six wide temperature sealed gel-cells -20° to +60°C (-4° to+140°F);
-40° to +60°C (-40° to+140°F) with optional battery heater. Battery backup time Eleven (11) hours @ 400 watts load.Recharge time Recharge time: 48 hours to 90% capacity after full discharge. SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Surge let-throughvoltages
Test pulse injection: Line-neutral: Line-ground: and Neutral-ground.Combination wave: L-N: 450V, L-G: 300 V, N-G: 300V
Status indicators 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload.
Input/output connections
Three position terminal blocks provided for 3 x 1.5mm2(16 AWG)via 25mm(1”) liquid-tight cable glands.
PhysicalDimensions 609mm(24”)wide x 305mm(12”)deep x 914mm(36”)highWeights 200kg(440 lbs)Steel cabinet Full weather IP44(NEMA-3R) outdoor design. Mounting options Bolting or banding mountable to monopole via optional ‘H’ style
bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting ‘feet’ are included.
EnvironmentalOperating temperature -20° to +60°C (-4° to+140°F); -40° to +60°C(- 40° to +140°F) with
optional battery heater. Includes thermostat controlled exhaust fan. Moisture protectionoption
Optional conformal coating of electronic boards is available formoisture resistance to protect against high humidity environments.
WarrantyWarranty Two year limited warranty, parts and labor (depot).
One year manufacturer’s warranty on batteries. TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
XUPsOutdoor XUPsOutdoor
Wide temperature outdoor line-interactive UPSwith automaticvoltage regulation
Ac input and UPS output cable entry (two liquid-tight cable glands)
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
65
XUPsOutdoor XUPsOutdoor
OutdoorXUPs-600C at a glance:Heavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme wide-temperature batteries
• 11 hours @ 400 watts withthe OutdoorXUPs-600C
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• Microprocessor-controlled 15kHz PWM sine wave inverter
• 115vac +/-8% output from 95 to 140vac inputwithout going to batteries
• Weather protected IP44 (NEMA-3R) metal cabinet
• SNMP compatible (optional)• Less than 4ms transfer time • 24vdc battery bus• Thermostat controlled fan
utilityac
input heavy-dutyac surge
protection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
battery and
charger
hot
relay 2
regulated XUPs output 115vac +/-8%
neutral
external battery(optional)
logic
-10%
+10%0%
95 to 140vac
chassis
relay 1
inverterac
dc
groundchassis
groundearth
OutdoorXUPs-600A/B system architecture
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
optional bandable or boltable monopole mounting brackets
accircuit
breaker
66 Outdoor XUPs SeriesOutdoorXUPs-600C
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPs
OutdoorXUPs-600C-2006-10-16.pdf
Outdoor XUPsOutdoor
Mounting on a concrete pad with Unistrut® (or similar)Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad.The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners.For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
610mm (24”)
thermostatcontrolledhot air vent forexhaust fan
concrete pad610mm (24”)above groundrecommended
XUPsoutput
hole to hole572mm(22.5”)
305mm(12”)
914mm (36”)
acinput
doorhinges
intakeair ventunderneath
Outdoor XUPspad mounted 914mm
(36”)Mounting feetclose-up drawing
IP44(NEMA-3R)metal cabinet
holes for 25mm (1”)liquid-tightcable glands
door latch
19mm(.75”)
19mm(.75”)
19mm(.75”)
19mm(.75”)
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
67
OutdoorXUPs-600CHV-OEM ~ 600VA, 420W, 230vac, 11hrs@400W, UPS+AVR
Outdoor XUPsmodel600CHV-OEM *without batteries
600 VA 420 watts230 vac 50/60Hz
*OEM versiondesigned foruse with sixOEM suppliedextreme/wide temperaturebatteries for11 hrs @ 400W
Pure sine wave Wide temperature UPS (OEM version) Voltage regulation
The TSi Power Outdoor XUPs-600CHV-OEM is constructed for use with wide temperature batteries, and is housed in a weather protected IP44(NEMA-3R) enclosure. This unit offers line-interactive automatic voltage regulation, over/under-voltage and surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.
Key Outdoor XUPs benefitsThis rugged UPS design with conformal coated boards and microprocessor-controlled 15kHz sinewave inverter reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs batteries are recommended to be special wide temperature batteries which allow operation of the UPS system over an ambient temperature range of -40° to +55°C. A thermostat controlled fan exhausts hot air, if temperature exceeds a preset limit, to protect batteries and electronics. Expected battery run-time for the TSi PowerOutdoorXUPs-600CHV-OEM (with six user supplied wide temperature batteries) would be approximately: 11 hours at 400 Watts load.
How The Outdoor XUPs WorksThe Outdoor XUPs-600CHV provides constant voltage regulation, surge protection, including an overvoltage threshold protection of 280vac, and an undervoltage threshold of 180vac. Upon a brownout, overvoltage, or loss of power, the Outdoor XUPs-600CHV will transfer to battery in less than 4 milliseconds, enabling uninterrupted operation of your telecom, surveillance systems, signaling or other outdoor systems.LEDs provide visual assessment of UPS status. By unlatching the two latches, the front door swings open. Inside the cabinet, an array of LED status indicators and power on/off control switch are provided.
XUPsOutdoor XUPsOutdoor
Typical applications This heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTU’s).
Key Outdoor XUPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44(NEMA-3R) metal cabinet• Pure sine wave output• Automatic voltage regulation with
over/under voltage protection• Remote power on/off (optional) • Designed for use with user/OEM
supplied wide temperature batteries• Heavy-duty surge protection
and noise filtering• Comprehensive array of
status bargraphs for voltage,load and battery levels
• Two year warranty on electronics
Extreme Wide Temperature Outdoor UPS with Voltage Regulation, and without Batteries(OEM supplied)
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
68 SpecificationsOutdoorXUPs-600CHV-OEM
Specification OutdoorXUPs-600CHV-OEM (without batteries)Electrical
Capacity in VA (watts) 600VA (420 watts) UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter.
Input Nominal voltage 230 volts ac
Input current 2.5A maximum @ 230vac Operating voltage 180 to 280vac without using batteries Operating frequency 47 to 63Hz
OutputNominal voltage 230 volts acVoltage regulation 230vac +/-8% for mains ac and battery modes, all operating conditions. Crest ratio 3 : 1Output waveform Pure sine wave, less than 3% THD with linear load.Power efficiency 97%, under full load conditions. Power on/off switch On/off rocker style power switch.Transfer time <4 millisecondsBattery recommended(User/OEM supplied)Engineering will recom-mend based on excel-lent track record and high reliability.
Recommended battery manufacturer/battery: Please call. (6) wide temperature batteries (-40o to +55oC ), 12vdc, 70AH. Each battery weighs 25kg, so six batteries will add 150kg, for a total system weight of about 200kg. Approximately 70% of the unit’s internal space is left open for your battery placement. Batter-ies should be connected to provide 24vdc. 210AH battery bank.
Battery back-up time This UPS is designed to accommodate 11 hours @ 400 watts load. Recharge time Recharge time: 48 hours to 90% capacity after full discharge. SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP and SMTP protocols).
Surge let-throughvoltages
Test pulse injection: Line-neutral: Line-ground: and Neutral-ground.Combination wave: L-N: 450V, L-G: 300 V, N-G: 300V
Status indicators 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload.
Input/output connect. Terminal blocks provided for 3 x 1.5mm2(16AWG) via cable glands.Physical
Dimensions 610mm(24”)wide x 305mm(12”)deep x 914mm(36”)highWeights 46kg (100 lbs)Steel cabinet Full weather IP44(NEMA-3R) outdoor design. Mounting options Bolting or banding mountable to monopole via optional ‘H’ style
bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting ‘feet’ are included.
EnvironmentalOperating temperature -20° to +55°C (-4° to +131°F) ambient air temperature.
Thermostat controlled exhaust fan. (Battery heater optional). Moisture protection Electronic boards are conformal coated for moisture
resistance to protect against high humidity environments.Warranty
Warranty Two year limited warranty, parts and labor (depot). (Does not include user supplied batteries).
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
XUPsOutdoor XUPsOutdoor
Outdoor line-interactive UPS(without batteries)with automaticvoltage regulationand designed for wide temperatures
Ac input and UPS output cable entry (two liquid-tight cable glands)
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
69
utilityac
input heavy-dutyac surge
protection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
battery and
charger
hot
relay 2
regulated XUPs output 230 vac +/-8%
neutral
external battery(optional)
logic
-10%
+10%0%
180 to 280vac
chassis
relay 1
inverterac
dc
groundchassis
groundearth
OutdoorXUPs-600CHV-OEM(without batteries) system architecture
OutdoorXUPs-600CHV-OEM at a glance:Heavy-duty outdoor UPS with line-interactive automatic voltage regulation and designed for use with extreme wide-temperature batteries
• Designed for a configuration of 11 hours @ 400 watts withuser supplied batteries
• We recommend the use of wide ambient temperature range sealed gel-cell batteries:-40° to +60°C (-40° to +140°F)
• Thermostat controlled fan• Microprocessor-controlled
15kHz PWM sine wave inverter
• 230vac +/-8% output from 180 to 280vac inputwithout going to battery
• Weather protected IP44 (NEMA-3R) metal cabinet
• SNMP compatible (optional)• Less than 4ms transfer time • 24vdc battery bus• Comes without batteries
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPsOutdoor XUPsOutdoor
optional bandable or boltable monopole mounting brackets
accircuit
breaker
70 Outdoor XUPs SeriesOutdoorXUPs-600CHV-OEM
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPs
OutdoorXUPs-600CHV-OEM-2006-10-16.pdf
Outdoor XUPsOutdoor
Mounting on a concrete pad with Unistrut® (or similar)Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad.The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners.For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
610mm (24”)
thermostatcontrolledhot air vent forexhaust fan
concrete pad610mm (24”)above groundrecommended
XUPsoutput
hole to hole572mm(22.5”)
305mm(12”)
914mm (36”)
acinput
doorhinges
intakeair ventunderneath
Outdoor XUPspad mounted 914mm
(36”)Mounting feetclose-up drawing
IP44(NEMA-3R)metal cabinet
holes for 25mm (1”)liquid-tightcable glands
door latch
19mm(.75”)
19mm(.75”)
19mm(.75”)
19mm(.75”)
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
71
ModelsOD-XUPs-400C
400VA, 250W120vac15 Min @250W30 Min @125W-20° to +60°C;-40° to +60°C w/ Optional Battery Heater
OD-XUPs-600C
Pure sine wave Wide temperature batteries Voltage regulation
The TSi Power Outdoor Od-XUPs-400C/600C UPS are constructed with extreme wide/low temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. This unit offers line-interactive automatic voltage regulation, over/under-voltage and surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.
Key benefitsThis rugged UPS design, with microprocessor-controlled 15kHz sine wave inverter and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-time’s for the Od-UPs-400C are approximately 15 minutes at 250 watts load, and 30 minutes with a 125 watts load; and for the Od-XUPs-600C, approximately 1.2 hours at 420 watts load, and 3 hours at 210 watts load.
How the Outdoor XUPs worksThe Outdoor XUPs Series UPS provides auto-matic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 140vac, and undervoltage protection with a threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems.LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.
Typical applications This heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance & security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTU’s).
Key Outdoor XUPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44(NEMA-3R) metal cabinet• Pure sine wave output• Over/under-voltage protection• Remote power on/off (optional) • Wide temperature batteries• Heavy-duty ac surge protection
and ac noise filtering• Automatic voltage regulation• Comprehensive array of
status bargraphs for voltage,load and battery levels
• Two year warranty on electronicsOne year warranty on batteries
XUPsOutdoor XUPsOutdoor
OD-XUPs-400C/600C ~ 400/600VA, 250/ 420W, 120vac, UPS+AVR
Od-XUPsmodel400C
400 VA 250 watts120vac15 min @250W30 min @125W-20° to +60°C;-40° to +60°Cwith optional battery heater
600C 600 VA420 watts120 vac1.2 hrs @ 420W 3 hrs @ 210W-20° to +60°C;-40° to +60°C with optional battery heater
Outdoor UPS with Voltage Regulation
Sample photo only, enclosure size may vary per custom application
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
72 SpecificationsOd-XUPs-400C/600C
Specification Od-XUPs-400C Od-XUPs-600CElectrical
Capacity in VA (watts) 600VA (420 watts) UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter.
Input Nominal voltage 120 volts ac
Input current 5A maximum @ 120 vac Operating voltage 95 to 140 vac without using batteries Operating frequency 47 to 63Hz
OutputNominal voltage 120 volts acVoltage regulation 115 vac +/-8% upon changes in line or load. Crest ratio 3 : 1Output waveform Pure sine wave, less than 3% THD with linear load. Power efficiency 97%, under full load conditions. Power on/off switch On/off rocker style power switch.Transfer time <4 millisecondsBatteries 5 amp hours, 24 vdc 32 amp hours, 24 vdc
Wide temperature sealed gel-cells -20° to +60°C (-4° to+140°F); -40° to +60°C (-40° to+140°F) with optional battery heater.
Battery backup time 15 minutes @ 250 watts load.30 minutes @ 125 watts load.
1.2 hours @ 420 watts load.3 hours @ 210 watts load.
Recharge time Recharge time: 4 to 6 hours to 95% capacity after full discharge. SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Surge let-throughvoltages
Test pulse injection: Line-neutral: Line-ground: and Neutral-ground. Combination wave: L-N: 450V, L-G: 300 V, N-G: 300V
Status indicators 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 4 status LED’s: Inverter on indicator, ac present indicator, battery fault indicator, and overload indicator.
Input/output connections
Three position terminal blocks provided for 3 x 1.5mm2 (16AWG) via 25mm(1”) liquid-tight cable glands.
PhysicalDimensions 507mm(20”)wide x 305mm(12”)deep x 609mm(24”)highWeights 22.7 kg(50 lbs) 36.3 kg(80 lbs)
Steel cabinet Full weather IP44(NEMA-3R) outdoor design. Mounting options Bolting or banding mountable to monopole via optional ‘H’ style
bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting ‘feet’ are included.
EnvironmentalOperating temperature,battery heater option, and cooling method
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater. Thermostat controlled exhaust fan.
Moisture protectionoption
Optional conformal coating of electronic boards is available formoisture resistance to protect against high humidity environments.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
XUPsOutdoor XUPsOutdoor
Outdoor UPS with automatic voltageregulation and wide temperature batteries
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Ac input and UPS output cable entry via two 25mm (1”) liquid-tight cable glands
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
73
Od-XUPs-400C/600C at a glanceHeavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme wide-temperature batteries
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• 24vdc battery bus• 15 minutes @ 250 watts load
30 minutes @ 125 watts with the Od-XUPs-400C
• 1.2 hours @ 420 watts load3 hours @ 210 watts withthe Od-XUPs-600C
• 115vac +/-8% output from 95 to140vac inputwithout going to batteries
• Weather protected IP44 (NEMA-3R) metal cabinet
• SNMP compatible (optional)• Less than 4ms transfer time • 15kHz microprocessor-controlled
PWM sinewave inverter• Thermostat controlled
fan is included
utilityac
input heavy-dutyac surge
protection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
battery and
charger
hot
relay 2
regulated XUPs output 115vac +/-8%
neutral
external battery(optional)
logic
-10%
+10%0%
95 to 140vac
chassis
relay 1
Inverterac
dc
groundchassis
groundearth
Od-XUPs-400C/600C system architecture
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPsOutdoor XUPsOutdoor
optional bandable or boltable monopole mounting brackets
accircuit
breaker
74 Outdoor XUPs SeriesOd-XUPs-400C/600C
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPsMounting on a concrete pad with Unistrut® (or similar)Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad.The Outdoor XUPs cabinet (or Outdoor EXt cabinet) is provided with four (4) mounting feet at the four (4) corners.For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
Od-XUPs-400C-600C-2006-10-16.pdf
Outdoor XUPspad mounted
Outdoor XUPsOutdoor
Mounting feetclose-up drawing
19mm(.75”)
19mm(.75”)
19mm(.75”)
19mm(.75”)
508mm (20”)
thermostatcontrolledhot air vent forexhaust fan
concrete pad609mm (24”)above groundrecommended
XUPsoutput
hole to hole470mm(18.5”)
305mm(12”)
610mm (24”)
acinput
doorhinges
intakeair ventunderneath
IP44(NEMA-3R)metal cabinet
holes for 25mm (1”)liquid-tightcable glands
door latch
610mm (24”)
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
75
Pure sine wave Wide temperature batteries Voltage regulation
OutdoorXUPs-1000A/B ~ 1000VA, 700W, 120vac, UPS+AVR
Outdoor XUPsmodel1000A
1000 VA700 watts120 vac30 min @700W1.1 hrs @350W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
1000B 1000 VA700 watts120 vac1.1 hrs @700W2.3 hrs @350W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
The TSi Outdoor XUPs-1000A/B units are constructed with extreme/wide temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.
Key Outdoor XUPs benefitsThis rugged UPS design, with microprocessor-controlled 15kHz sine wave inverter and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-time’s for the OutdoorXUPs-1000A are approximately 30 minutes at 700 watts load, and 1.1 hours with a 350 watts load; for the OutdoorXUPs-1000B, approximately 1.1 hours at 700 watts load, and 2.3 hours at 350 watts.
How the Outdoor XUPs worksThe Outdoor XUPs Series UPS provides auto-matic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 140vac, and undervoltage protection with a threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems.LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.
XUPsOutdoor XUPsOutdoor
Outdoor UPS with Voltage Regulation
Typical applicationsThis heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key Outdoor XUPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44(NEMA-3R) metal cabinet• Pure sine wave output• Over/under-voltage protection• Remote power on/off (optional) • Wide temperature batteries• Heavy-duty surge protection
and noise filtering• Automatic voltage regulation• Comprehensive array of
status bargraphs for voltage,load and battery levels
• Two year warranty on electronicsOne year warranty on batteries
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
76 SpecificationsOutdoorXUPs-1000A/B
Specifications OutdoorXUPs-1000A OutdoorXUPs-1000BElectrical
Capacity in VA (watts) 1000VA (700W) UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter
Input Nominal voltage 120 volts ac
Input current 8.3A maximum @ 120vac Operating voltage 95 to 140vac without using batteries Operating frequency 47 to 63Hz
OutputNominal voltage 120 volts acVoltage regulation 115 vac +/-8% upon changes in line or load Crest ratio 3:1Output waveform Pure sinewave, less than 3%THD with linear load Power efficiency 97%, under full load conditions Power on/off switch On/off rocker style power switchTransfer time <4 millisecondsBatteries 32 amp hours, 24vdc 64 amp hours, 24vdc
Wide temperature sealed gel-cells -20° to +60°C (-4° to+140°F); -40° to +60°C (-40° to+140°F) with optional battery heater.
Battery backup time 30 minutes @ 700 watts load.1.1 hours @ 350 watts load.
1.1 hours @ 700 watts load.2.3 hours @ 350 watts load.
Recharge time 8 hours to 90% capacity after full discharge.
16 hours to 90% capacity after full discharge.
SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Surge let-throughvoltages
Test pulse injection: Line-neutral: Line-ground: and Neutral-ground. Combination Wave: L-N: 450V, L-G: 300 V, N-G: 300V
Status indicators 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload.
Input/output connections
3 position terminal blocks provided for 3 x 1.5mm2 (16AWG)connections via 25mm(1”) liquid-tight cable glands.
PhysicalDimensions 406mm(16”)wide x 305mm(12”)deep x 711mm(28”)highWeights 50kg(110 lbs) 73kg(160 lbs)
Steel cabinet Full weather IP44(NEMA-3R) outdoor design. Mounting options Bolting or banding mountable to monopole via optional ‘H’ style
bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting ‘feet’ are included.
EnvironmentalOperating temperature,battery heater option and cooling method
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater. Thermostat controlled exhaust fan.
Moisture protection(optional)
Optional conformal coating of electronic boards is available formoisture resistance to protect against high humidity environments.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
XUPsOutdoor XUPsOutdoor
Outdoor line-interactive UPSwith automaticvoltage regulationand extreme/wide temperature batteries
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Ac input and UPS output cable entry via two 25mm (1”) liquid-tight cable glands
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
77
OutdoorXUPs-1000A/B at a glanceHeavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• 24vdc battery bus• 30 minutes @ 700 watts, or
1.1 hours @ 350watts with the OutdoorXUPs-1000A
• 1.1 hours @ 700 watts, or2.3 hours @ 350 watts withthe OutdoorXUPs-1000B
• 115vac +/-8% output from 95 to 140vac inputwithout going to batteries
• Weather protected IP44 (NEMA-3R) metal cabinet
• SNMP compatible (optional)• Less than 4ms transfer time • Microprocessor-controlled
15kHz PWM sine wave inverter• Thermostat controlled
fan is included
utilityac
input heavy-dutyac surge
protection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
battery and
charger
hot
relay 2
regulated XUPs output 115vac +/-8%
neutral
external battery(optional)
logic
-10%
+10%0%
95–140vac
chassis
relay 1
inverterac
dc
groundchassis
groundearth
OutdoorXUPs-1000A/B system architecture
XUPsOutdoor XUPsOutdoor
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
optional bandable or boltable monopole mounting brackets
accircuit
breaker
78 Outdoor XUPs SeriesOutdoorXUPs-1000A/B
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPs
OutdoorXUPs-1000-2006-10-16.pdf
Outdoor XUPsOutdoor
Mounting on a concrete pad with Unistrut® (or similar)Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad.The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners.For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
406mm (16”)
thermostatcontrolledhot air vent forexhaust fan
concrete pad609mm (24”)above groundrecommended
UPSoutput
hole to hole368mm(14.5”)
305mm(12”)
711mm (28”)
acinput
doorhinges
intakeair ventunderneath
Outdoor XUPspad mounted
711mm (28”)
Mounting feetclose-up drawing
IP44 /NEMA-3Rmetal cabinet
holes for 25mm (1”)liquid-tightcable glands
door latch
19mm(.75”)
19mm(.75”)
19mm(.75”)
19mm(.75”)
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
79
OutdoorXUPs-1000AHV/BHV ~ 1000VA, 700W, 230vac, UPS+AVR
OutdoorXUPsmodel1000AHV
1000 VA700 watts230vac30 min @700W1.1 hrs @350W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
1000BHV1000 VA700 watts230vac1.1 hrs @700W 2.3 hrs @350W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
The TSi Outdoor XUPs-1000AHV/BHV are constructed with extreme/wide temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. These units offer line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy-duty noise filtering, communications capability and optional extended battery backup.
Key Outdoor XUPs benefitsThis rugged UPS design, with microprocessor-controlled 15kHz sine wave inverter and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-times for: OutdoorXUPs-1000AHV are 30 minutes at 700 watts load, and 1.1 hours with a 350 watts load; battery run-times for the OutdoorXUPs-1000BHV are 1.1 hrs at 700 watts load, and 2.3 hours with a 350 watts load.
How the Outdoor XUPs worksThe Outdoor XUPs Series UPS provides auto-matic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 280vac, and undervoltage protection with a threshold of 190vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems.LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.
XUPsOutdoor XUPsOutdoor
Outdoor UPS with Voltage Regulation
Pure sine wave Wide temperature batteries Voltage regulation
Typical applicationsThis heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key Outdoor XUPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44 (NEMA-3R) metal cabinet• Pure sine wave output• Over/under-voltage protection• Remote power on/off (optional) • Wide temperature batteries• Heavy-duty surge protection
and noise filtering• Automatic voltage regulation• Comprehensive array of
status bargraphs for voltage,load and battery levels
• Two year warranty on electronicsOne year warranty on batteries
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
80 SpecificationsOutdoorXUPs-1000AHV/BHV
Specification OutdoorXUPs-1000AHV OutdoorXUPs-1000BHVElectrical
Capacity in VA (watts) 1000VA (700W) UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter.
Input Nominal voltage 230 volts ac
Input current 4.2A maximum @ 230vac Operating voltage 190 to 280 vac without using batteries Operating frequency 47 to 63Hz
OutputNominal voltage 230 volts ac Voltage regulation 230vac +/-8% upon changes in line or load. Crest ratio 3:1Output waveform Pure sine wave, less than 3% THD with linear load. Power efficiency 97%, under full load conditions. Power on/off switch On/off rocker style power switch. Transfer time <4 millisecondsBatteries 32 amp hours, 24 vdc 64 amp hours, 24 vdc
Wide temperature sealed gel-cells -20° to +60°C (-4° to+140°F); -40° to +60°C (-40° to+140°F) with optional battery heater.
Battery backup time 30 minutes @ 700 watts load. 1.1 hours @ 350 watts load.
1.1 hours @ 700 watts load. 2.3 hours @ 350 watts load.
Recharge time 8 hours to 90% capacity after full discharge.
16 hours to 90% capacity after full discharge.
SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Surge let-throughvoltages
Test pulse injection: Line-neutral: Line-ground: and Neutral-ground. Combination wave: L-N: 450V, L-G: 300 V, N-G: 300V
Status indicators 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload.
Input/output connections
3 position terminal blocks provided for 3 x 1.5mm2 (16AWG) connections via 25 mm (1”) liquid-tight cable glands.
PhysicalDimensions 406mm(16”)wide x 305mm(12”)deep x 711mm(28”)highWeights 50kg(110 lbs.) 73kg(160 lbs.)
Steel cabinet Full weather IP44(NEMA-3R) outdoor design. Mounting options Bolting or banding mountable to monopole via optional ‘H’ style
bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting ‘feet’ are included.
EnvironmentalOperating temperature,battery heater option and cooling method
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater. Thermostat controlled exhaust fan.
Moisture protection(optional)
Optional conformal coating of electronic boards is available formoisture resistance to protect against high humidity environments.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
XUPsOutdoor XUPsOutdoor
Outdoor line-interactive UPSwith automaticvoltage regulationand extreme/wide temperature batteries
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Ac input and UPS output cable entry via two 25mm (1”) liquid-tight cable glands
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
81
OutdoorXUPs-1000AHV/BHV at a glanceHeavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• 24vdc battery bus• 30 minutes @ 700watts, or
1.1 hours @ 350 watts with The OutdoorXUPs-1000AHV
• 1.1 hours @ 700 watts, or2.3 hours @ 350 watts withthe OutdoorXUPs-1000BHV
• 230vac +/-8% output from 190 to 280vac inputwithout going to batteries
• Weather protected IP44 (NEMA-3R) painted metal cabinet
• SNMP compatible (optional)• Less Than 4ms transfer time • Microprocessor-controlled
15kHz PWM sine wave inverter• Thermostat controlled
fan is included
utilityac
input heavy-dutyac surge
protection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
battery and
charger
hot
relay 2
regulated XUPs output 230vac +/-8%
neutral
external battery(optional)
logic
-10%
+10%0%
190 to 280vac
chassis
relay 1
inverterac
dc
groundchassis
groundearth
OutdoorXUPs-1000AHV/BHV system architecture
XUPsOutdoor XUPsOutdoor
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
optional bandable or boltable monopole mounting brackets
accircuit
breaker
82 Outdoor XUPs SeriesOutdoorXUPs-1000AHV/BHV
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPsOutdoor XUPsOutdoor
OutdoorXUPs-1000HV-2006-10-16.pdf
Mounting on a concrete pad with Unistrut® (or similar)Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad.The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners.For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
406mm (16”)
thermostatcontrolledhot air vent forexhaust fan
concrete pad609mm (24”)above groundrecommended
UPSoutput
hole to hole368mm(14.5”)
305mm(12”)
711mm (28”)
acinput
doorhinges
intakeair ventunderneath
Outdoor XUPspad mounted
711mm (28”)
Mounting feetclose-up drawing
IP44 (NEMA-3R )metal cabinet
holes for 25mm (1”)liquid-tightcable glands
door latch
19mm(.75”)
19mm(.75”)
19mm(.75”)
19mm(.75”)
Outdoor UPs SeriesOutdoor Uninterruptible Power System
83
OutdoorUPs-400Conf1-2 ~ 400VA, 250W, 120vac
These TSi Power Outdoor Series UPS are constructed with extreme wide/low temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. This series offers exterior battery backup with good surge protection and communications capability.
Key benefitsThis rugged outdoor UPS design, is the ideal UPS for exterior computer or telecommunications equipment in extreme wide temperature -20o to +60oC(-4o to +140 oF) environments where ac power delivery is unreliable and long battery backup times may be necessary. It is suitable where power outages are a regular occurrence, or in areas where utilities need to conduct rolling blackouts.Outdoor UPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. Battery run-time’s for the OutdoorUPs-400Conf1 are approximately 1 hour at 250 watts load, and 2 hours at a 125 watts load; the OutdoorConf2, 2 hours at 250 watts, and 4 hours at 125 watts.
How the OutdoorUPs-400 worksUpon brownout, or loss of power, the OutdoorUPs-400Conf unit will transfer to battery in <8ms, enabling uninterrupted operation of your telecom, surveillance systems, signaling or other outdoor systems.One LED provides visual assessment of UPS status. Front panel rocker switches control UPS functions. Audible alarms activate upon power outage and low-battery conditions.
Typical applications These outdoor extreme wide temperature rated UPS are ideal for surveillance cameras, cellular repeater sites, mission-critical 911 and telecommunications equipment, and other areas where reliability and/or extended battery backup time is required, or ac power is unpredictable.
Outdoor UPs model400Conf1
400 VA250 watts120 vac 1 hour@250W2 hrs @ 125W4 hours @ 50W -20° to +60°C;-40° to +60°C with optional battery heater
400Conf2400 VA250 watts120 vac 2 hrs @ 250W4 hrs @ 125W8 hours @ 50W -20° to +60°C;-40° to +60°C with optional battery heater
Outdoor UPS Wide temperature batteries IP44/NEMA-3R enclosure
Key features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather protection
IP44(NEMA 3R) metal cabinet• Wide temperature batteries• Conformal coated boards for
moisture ingress protection• Undervoltage protection• Enhanced surge protection• Two year warranty on electronics
One year warranty on batteries • Status and alarm signals available
through DB9 connector
Outdoor Uninterruptible Power System
Outdoor
UPs UPsOutdoor
Sample photo only, enclosure size may vary per custom application
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Ac input and UPS output cable entry via two 25mm (1”) liquid-tight cable glands
84 SpecificationsOutdoorUPs-400Conf1/2
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Specification OutdoorUPs-400Conf1 OutdoorUPs-400Conf2Electrical
Capacity in VA (watts) 400VA (250W) UPS type Single conversion UPS with less than 8 ms transfer time.
InputNominal voltage 120 volts ac single phase Operating voltage 100 to130 volts ac Ac input (hardwire) Terminal block via through-wall watertight fittingsOperating frequency 57 to 63Hz
OutputNominal voltage 120 volts ac, single phase, sine wave during normal operation.Nominal frequency 57 to 63HzPower efficiency >98% for normal operation, 80% or higher during battery inverter operation. Transfer time Less than 8ms typical between ac and inverter,
phase-locked to the ac mains voltage.UPS inverter output 105 to 130VRMS, 60Hz +/-1%,
pulse-width-modulated, modified square wave.Transfer: ac to inverter Brown-out threshold: 97+/-2VRMSTransfer: inverter to ac The line voltage has to stabilize to between 100 and 130VRMS
for at least 2 seconds in order to transfer back to ac mains.Batteries Wide temperature sealed gel-cells -20° to +60°C (-4° to+140°F);
-40° to +60°C (-40° to+140°F) with optional battery heater.Battery backup time 30Ah, 12 volts
1 hour @ 250 watts load. 2 hours @ 125 watts load. 4 hours @ 50 watts load.
60Ah, 12 volts 2 hours @ 250 watts load. 4 hours @ 125 watts load. 8 hours @ 50 watts load.
Indicators and alarm LED indicator and audible signals for ac, inverter, and battery status. Communications DB-9 connector provides RS-232 compatible alarm signals. Ac output (hardwire) Terminal block via through-wall 25mm(1”) cable glands (water-tight fittings).
PhysicalDimensions 406mm(16”)high x 305mm(12”)wide x 203mm(8”)deepWeight 27 kg(60 lbs) 39 kg(85 lbs)Cabinet IP44 (NEMA-3R) fully weather protected metal cabinet.Mounting options Bolting or banding mountable to monopole via optional ‘H’ style
bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting ‘feet’ are included.
SafetyOverload protection Internal fuses protect all ac and dc circuits.
EnvironmentalOperating temperature,battery heater option
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater.
Moisture protection Conformal coating of electronic boards for moisture resistance to protect against high humidity environments.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
Outdoor UPS
groundsurge
protectionand
noisefilter
acinput
hotfuse
neutral
dc to acinverter
battery and
charger
hot
ground
relay
UPSoutput
neutral
external batteryconnector
Outdoor-UPs-400Conf1/2 system architecture
Outdoor-UPs-400Conf1-2-2006-10-16.pdf
Outdoor
UPs UPsOutdoor
Specifications
optional bandable or boltable monopole mounting brackets
TSi’s ongoing product improvement process makes specifications subject to change without notice. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Outdoor UPs SeriesOutdoor Uninterruptible Power System
85
Outdoor
Outdoor-UPs-10000-16000-21000 ~ 1 -1.6-2.1kVA, 750W-1.2kW-1.5kW, 120V
UPs UPs
TSi Power’s Outdoor Series UPS are constructed with a rugged, ferroresonant no-break design and a fully isolated sine wave output with neutral-to-ground bond. They are housed in a weather protected (NEMA 3R rated design) enclosure. This series offers the best surge protection available, with excellent noise filtering, long battery back-up time built-in automatic bypass.
Key -4871 benefitsThis rugged industrial-strength ferroresonant design reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor UPS batteries are special wide temperature batteries which allow operation of the UPS system over an ambient temperature range of -40° to +55° C. Built-in battery run-time is approximately 90 minutes under a typical 600 watts load.
How the -4871worksThe constant output isolation transformer provides 100% isolation from the input ac line. The regulated output protects switchmode power supplies from failure caused by unstable ac mains. The secondary neutral is bonded to ground, thus eliminating all surge voltages between neutral and ground. This type of surge protection is superior to all other technologies and is further enhanced with a built-in low-pass filter, which takes the edge off fast transients.UPS status is monitored by LED indicators, LED bargraph displays and audible signals for ac status, inverter status, output voltage, load, and battery status. Alarm interface: Upon loss of power, the audible alarm will beep. Because the Outdoor Series is a continuous sinewave ‘no-break’ UPS system, power to equipment loads will be completely unaffected. As the battery level drops until only a few minutes of holdup time remains, the audible alarm will change, warning of impending shutdown.
Outdoor UPsmodels10000-4871
750 watts120vac
16000-4871 1200 watts120vac
21000-4871 1500 watts120vac
Pure sinewave Ferroresonant voltage regulation Transformer isolated
Typical outdoor applications These heavy-duty outdoor rated UPS are ideal for cell sites, critical 911 and telecom equipment, LED traffic signal systems, and other areas where reliability is a must, extended back-up might be necessary, or the power source is unpredictable.
Key -4871 features• Cabinet can be pedestal (ground),
pole, or wall mounted• Full weather protection
(NEMA 3R rated design)• No-break, pure sine wave output• Wide temperature batteries• Best surge protection available• Constant voltage regulation and
ferroresonant isolation transformer• Reduces harmonics
from non-linear loads • Built-in failsafe automatic bypass • Comprehensive array of
status bargraphs for voltage,load and battery levels
• 2 yr. warranty on electronic parts,mfgr’s warranty on batteries
Outdoor UPS with Ferroresonant Constant Voltage Transformer, Extreme Wide Temperature Batteries and Failsafe Automatic Bypass
Outdoor
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
86 UPs Outdoor SeriesOutdoor-UPs-10000-16000-21000-4871
Specification UPs-10000-4871 UPs-16000-4871 UPs-21000-4871Electrical
Capacity in VA (watts) 1000VA (750watts) 1600VA (1200watts) 2100VA (1500 watts)Transformer type Ferroresonant constant voltage output isolation transformer. Isolation 100% input/output isolation & output neutral-ground bonding qualifies the
UPS output as a “separately derived ac power source” via NEC 250-5D. Input
Nominal voltage 120 volts acOperating voltage 90 to 140 volts ac without using batteriesNominal frequency 60Hz sinusoidal +/- 5%Ac input Hardwire (14AWG) terminal block
OutputNominal voltage 120 volts acVoltage regulation +/-3% upon changes in line or loadCrest ratio 3 : 1Output wave form Pure sine wave, less than 3% THD with linear loadPower efficiency 90%, under full load conditionsPower on/off switch On/Off rocker style power switchTransfer time Zero (continuous no-break)Batteries Wide temperature -40° to +55° C, maintenance-free sealed gel-cells.Back-up time @ 50% load 2 hours 1.5 hours 1 hourRecharge time Recharge time: 48 hours to return to 90% capacity after full discharge.Automatic bypass Built-in for continued operation even if UPS failure occurs.Noise filtering Low-pass filter reduces noise over a wide frequency range.Surge protection Built-in multi-stage, coordinated surge protection system. Surge test conditions ANSI/IEEE C62.41-1991 test pulse. Category B3,
Combination Wave, 6000 volts, 3000 amps.Surge let-throughvoltages
Test pulse injection: Line-neutral, Line-ground and Neutral-ground. Combination Wave: L-N: 35V, L-G: 35V, N-G: 0.5V
Indicators ‘10 LED’ bar-graph indicators: output voltage, battery voltage, and show the output load from 0 to 100% of rated power.
4 status LED’s indicating - ac power present; inverter status; output mode; ac load, and battery status.
Ac output 3 separately fused (15A fuses) terminal blocks.Physical
Dimensions 24” wide x 12” deep x 36” high (609mmW x 304mmD x 914mmH) Weight 73kgs(160 lbs) 77kgs(170 lbs) 82kgs(180 lbs)Mounting options Bolting or banding mountable to monopole via optional ‘H’ style
bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting ‘feet’ are included.
Enclosure Durable, all-steel NEMA 3R enclosure withstands transport in hostile environments and operation in severe outdoor applications.
SafetyAgency approvals Designed to meet UL, cUL and IEC safety standards. FET inverter circuit FET inverter circuit ensures efficiency and reliability.
EnvironmentalOperating temperature -40° to +55°C. (-40° to +131°F )Moisture protection Conformal coated boards are moisture resistant.
WarrantyWarranty 2 Year limited warranty, parts & labor. Manufacturer’s battery warranty.
Outdoor NEMA 3Rheavy-duty UPSwith ferroresonantvoltage regulatingisolation transformer
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Outdoor
UPs UPsOutdoor
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor UPs SeriesOutdoor Uninterruptible Power System
87
acinput
3- way MOVsurge
protectionhot
ground
neutral
EMI / RFInoise filter
solid-staterelay
inverter
batterycharger
ferroresonanttransformer
resonantcapacitor
neutral
hot
ground
fuse
+48vdc
batte
ry
UPSoutput
Outdoor-UPs-10000/16000/21000-4871 system architecture
Heavy-duty outdoor NEMA 3R rated UPS with ferroresonant constant voltage regulating isolation transformer
• ‘No-break’ zero transfer time
• Ferroresonant constantvoltage-regulating isolation transformer
• Weather protected NEMA 3R rated cabinet
• 48vdc battery bus• Failsafe automatic bypass
• Wide temperature batteries -40° to +55° C ambient temperature range
• 1000VA / 750 watts rating1600VA / 1200 watts rating2100VA / 1500 watts rating
• Thermostat controlled battery heater is included
• Thermostat controlled fan is included
Outdoor
UPs UPsOutdoor
* automatic bypass not shown
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
88 UPs Outdoor SeriesOutdoor-UPs-10000-16000-21000-4871
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Mounting on a concrete pad with Unistrut (or similar)Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-UPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad.The Outdoor-UPs cabinet is provided with four (4) mounting feet at the four (4) corners.For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
Outdoor-UPs-10000-16000-21000-4871-2006-10-16.pdf
Outdoor
UPs UPsOutdoor
24”
thermostaticallycontrolledhot air vent forexhaust fan
concretepad
doorlatches
outputs1,2 & 3
hole to hole
22.5”
12”
36”
input
doorhinges
intakeair ventunderneath
Outdoor-UPspad mounted
0.75”
0.75”
0.75”
0.75”
36”mounting feetclose-up drawing
NEMA 3REnclosure
Input Hole For A1” Liquid-TightConnector
output holes for1” liquid-tightconnectors
Optional bandable or boltable monopole mounting brackets
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
89
OutdoorXUPs-1000-8024~230vac in, 400W@230vac+200W@48vdc out, UPS+AVR
OutdoorXUPsmodel1000-8024
230vac output 400 watts 1.74 amps48vdc output 200 watts 4.2 amps2 hours @ 600W 20° to +60°C;-40° to +60°C with optional battery heater
The TSi Power Outdoor XUPs-1000-8024 is constructed with extreme/wide temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. These units offer both ac and dc outputs, line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy-duty noise filtering, communications capability and optional extended battery backup.
Key Outdoor XUPs benefitsThis rugged UPS design, with microprocessor-controlled 15kHz sine wave inverter, and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-time for OutdoorXUPs-1000-8024 is 2 hours at 600 watts load (based on a total output of 400 watts of ac and 200 watts of dc).
How the Outdoor XUPs worksThe Outdoor XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 280vac, and under-voltage protection with a threshold of 190vac. Upon a brownout, over-voltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems. +/-48vdc output is also provided.LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.
XUPsOutdoor XUPsOutdoor
Outdoor UPS with Voltage Regulation
Ac + dc output Wide temperature batteries Voltage regulation
Typical applicationsThis heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key Outdoor XUPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44 (NEMA-3R) metal cabinet• Provides both ac and dc output• Pure ac sine wave• Over/under-voltage protection• Remote power on/off (optional) • Wide temperature batteries• Heavy-duty surge protection
and noise filtering• Automatic voltage regulation• Comprehensive array of
status bargraphs for voltage,load and battery levels
• Two year warranty on electronicsOne year warranty on batteries
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
90 SpecificationsOutdoorXUPs-1000-8024
Specification Outdoor XUPs-1000-8024Electrical
Capacity in VA (watts) 1000VA (600W) UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter.
Input Nominal voltage 230 volts ac
Input current 6A maximum @ 230vac. Operating voltage 190 to 280 vac without using batteries. Operating frequency 47 to 63Hz
OutputNominal voltage,amps and watts
Ac: 230 volts, 1.74 amps, 400 watts.Dc: +/-48 volts, 4.2 amps, 200 watts.
Ac voltage regulation 230vac +/-8% upon changes in line or load. Crest ratio 3:1Ac output wave form Pure sine wave, less than 3% THD with linear load. Power efficiency 97%, under full load conditions. Power on/off switch On/off rocker style power switch. Transfer time <4 millisecondsBatteries 74 amp hours, 24vdc
Wide temperature sealed gel-cells -20° to +60°C (-4° to+140°F); -40° to +60°C (-40° to+140°F) with optional battery heater.
Backup time 2 hours @ 600 watts load. (with total output of 400 watts at 230 vac, and 200 watts at 48 dc).
Recharge time 16 hours to 90% capacity after full discharge. SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Surge let-throughvoltages
Test pulse injection: Line-neutral: Line-ground: and Neutral-ground. Combination wave: L-N: 450V, L-G: 300 V, N-G: 300V
Status indicators 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload.
Input/output connections
3 position terminal blocks provided for 3 x 1.5mm2 (16AWG) ac connections via 25 mm (1”) liquid-tight cable glands. 2 position terminal blocks provided for 48vdc output connections.
PhysicalDimensions 610mm(24”)wide x 203mm(8”)deep x 762mm(30”)highWeight 100kg(220 lbs)Steel cabinet Full weather IP44(NEMA-3R) outdoor design. Mounting options Bolting or banding mountable to monopole via optional ‘H’ style
bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting ‘feet’ are included.
EnvironmentalOperating temperature,battery heater option and cooling method
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater. Thermostat controlled exhaust fan.
Moisture protection(optional)
Conformal coating of electronic boards is available for moisture resistance to protect against high humidity environments.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
XUPsOutdoor XUPsOutdoor
Outdoor line-interactive UPSwith automaticvoltage regulation,wide temperature batteries, and bothac and dc output
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Ac input and UPS output cable entry via two 25mm (1”) liquid-tight cable glands
Outdoor XUPs SeriesOutdoor Uninterruptible Power System
91
OutdoorXUPs-1000-8024 at a glanceHeavy-duty outdoor ac and dc output UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries
• 400 watts, 230vac +/-8% output from 190 to 280vac inputwithout going to batteries
• 200 watts, +/-48vdc output• 2 hours @ 600watts, at a
total of 400 watts at 230vac and 200 watts at 48vdc
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• Less than 4ms transfer time• Weather protected
IP44 (NEMA-3R) painted metal cabinet
• SNMP compatible (optional) • 24vdc battery bus• Microprocessor-controlled
15kHz PWM sine wave inverter• Thermostat controlled
fan is included• Optional conformal coated
boards for moisture protection
utilityac
input heavy-dutyac surge
protection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
battery and
charger
hot
relay 2
regulated XUPs output 230vac +/-8%
neutral
external battery(optional)
logic
-10%
+10%0%
190 to 280vac
chassis
relay 1
inverterac
dc
groundchassis
groundearth
OutdoorXUPs-1000-8024 system architecture
XUPsOutdoor XUPsOutdoor
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
optional bandable or boltable monopole mounting brackets
48 vdc outputterminal block
dc circuitbreaker
ac circuitbreaker
92 Outdoor XUPs SeriesOutdoorXUPs-1000-8024
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPsOutdoor XUPsOutdoor
OutdoorXUPs-1000-8024-2006-10-16.pdf
Mounting on a concrete pad with Unistrut® (or similar)Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad.The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners.For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
610mm (24”)
thermostatcontrolledhot air vent forexhaust fan
concrete pad610mm (24”)above groundrecommended
UPSoutput
hole to hole572mm(22.5”)
203mm(8”)
762mm (30”)
acinput
doorhinges
intakeair ventunderneath
Outdoor XUPspad mounted
762mm (30”)
Mounting feetclose-up drawing
IP44 (NEMA-3R )metal cabinet
holes for 25mm (1”)liquid-tightcable glands
door latch
19mm(.75”)
19mm(.75”)
19mm(.75”)
19mm(.75”)
Outdoor UPs SeriesOutdoor Uninterruptible Power System
93
Outdoor-UPs-8009/8010 ~ 60 watts, 115 or 230 vac input, 12 vdc output UPS
Outdoor UPsmodel8009
60 wattsinput can be 115 or 230 vacoutput is 12 vdc1.3 hrs @60W2.5 hrs @36W-20° to +60°C;-40° to +60°Cwith optionalbattery heater
8010 60 wattsinput can be 115 or 230 vacoutput is 12 vdc5 hours @60W8 hours @36W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
Dc output Wide temperature batteries Wide ac input voltage window
The TSi Power Outdoor-UPs-8009/8010 with dc output are for dc powered applications needing backup power in extreme weather conditions. They are constructed with wide temperature batteries and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer a wide input voltage window (88 to 264 vac) and low ripple 12 vdc output, with heavy duty surge protection and noise filtering.
Key Outdoor UPs benefitsThis rugged outdoor dc output UPS design is suitable for use in severe outdoor environments. Outdoor UPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. The wide input voltage window enables dc output without having to drain or exercise the batteries, thereby ensuring long battery life.Battery run-times for the Outdoor-UPs-8009 are approximately 1.3 hours at 60 watts load, and 2.5 hours at a 36 watts load. For the Outdoor-UPs-8010, approximately 5 hours at 60 watts load, and 8 hours with a 36 watts load.
How the Outdoor UPs worksThe outdoor UPs with dc output provides extended battery backup through a system which takes nominal 115 or 230 vac input (from 88 to 264 vac), converts it to dc, charges the batteries, and delivers a nominal 12 vdc (10 to 14 vdc) with a less than 200 millivolts peak to peak ripple. The heavy duty surge protection and noise filtering on the ac input helps protect the unit and load from transient surges on the line. Because the unit is already delivering dc power, upon a deep brownout or loss of power, the Outdoor UPs with dc output has a zero transfer time to the reserve power in the batteries. For OEMs, a small ‘hotel’ space is provided inside the unit for your equipment to reside.
Typical applicationsThese heavy duty outdoor UPS systems are designed to power wireless communications, perimeter surveillance cameras (CCTV), security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key Outdoor UPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44(NEMA-3R) metal cabinet• Dc output with low ripple • Wide temperature batteries• Heavy-duty surge protection
and noise filtering• Wide ac input voltage window
lengthens battery life• Two year warranty on electronics
One year warranty on batteries
Outdoor On-line UPS with Dc Output
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor
UPs UPsOutdoor
94 SpecificationsOutdoor-UPs-8009/8010
Specification Outdoor-UPs-8009 Outdoor-UPs-8010 Electrical
Capacity in watts 60 watts UPS topology Ac to dc rectifier, battery charger and sealed gel-cell batteries
Input Nominal voltage 115 or 230 volts ac
Operating voltage 88 to 264 vac without using batteries Input current 1A maximum @ 115 vac, or 0.5A maximum @ 230 vacOperating frequency 50 or 60Hz (47 to 63Hz)
OutputNominal voltage 12 volts dc Operating voltage 10 to 14 volts dc (depending on battery charge status) Output current 5A maximum @ 12vdcDc ripple voltage Less than 200 millivolts peak to peak Power efficiency 84% (typical) Power on/off switch On/off rocker style power switch Transfer time to backup Zero transfer timeBattery backup time 1.3 hours @ 60 watts(5A) load,
2.5 hours @ 36 watts(2.5A) load.5 hours @ 60 watts(5A) load,8 hours @ 36 watts(2.5A) load.
Recharge time 4 hours to 90% capacity after full discharge.
16 hours to 90% capacity after full discharge.
Batteries 10 amp hours, 12vdc 30 amp hours, 12vdcWide temperature sealed gel-cells -20° to +60°C (-4° to+140°F); -40° to +60°C (-40° to+140°F) with optional battery heater.
Ac connections 3 position terminal block provided for 3 x 1mm2 (18AWG), L1, L2 and Ground connections via 12mm(1/2”) diameter liquid-tight cable glands.
Dc connections 2 position terminal block provided for dc output wires connection via 19mm(3/4”) diameter liquid-tight cable glands.
PhysicalDimensions 254mm(10”)wide x 305mm(12”)high x 152mm(6”)deepWeights 14kg(30 lbs) 21kg(45 lbs)
Steel cabinet Full weather IP44(NEMA 3R) UL50 outdoor padlockable enclosure. Mounting options Pole mountable to monopole via optional ‘H’ style bracket (mounting
bands not included). Wall mountable via enclosure’s top+bottom brackets. Also, optional pedestal (ground) brackets are available.
‘Hotel’ space for OEM option
Approximately 254mm(10”)wide x 76mm(3”)high x 152mm(6”)deep, (if more space is needed, unit can be built with a larger enclosure).
EnvironmentalOperating temperature,battery heater option
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
Outdoor dc output UPS with a wide ac input voltage window and extreme/wide temperature batteries
Specifications
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.TSi Power Corporation
Represented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor
UPs UPsOutdoor
Outdoor UPs SeriesOutdoor Uninterruptible Power System
95
Outdoor-UPs-8009/8010 at a glanceHeavy-duty outdoor on-line UPS with dc output, wide ac input voltage window, and wide temperature batteries
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• Low dc output ripple• 12vdc battery bus• 1.3 hours @ 60 watts load, or
2.5 hours @ 36 watts load with the Outdoor-UPs-8009
• 5 hours @ 60 watts load, or8 hours @ 36 watts load withthe Outdoor-UPs-8010
• Nominal 12 volts dc(10 to 14vdc) output from 88 to 264vac inputwithout going to batteries
• Weather protected IP44/NEMA-3R, UL50painted metal cabinet
• Optional pole, wall or floor mounting brackets available. Must be specified/ordered at time of purchase order.
• Larger OEM ‘hotel’ space is available, please call if more space is necessary.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
optional bandable or boltable monopole mounting brackets
Outdoor
UPs UPsOutdoor
ac input is via a12mm (1/2”) diameter liquid-tight cable gland,and dc output is via a19mm (3/4”) diameterliquid-tight cable gland
Outdoor-UPs-8009-8010-115or230vac-12vdc-60W-2006-10-16.pdf
96 Outdoor UPs SeriesOutdoor Uninterruptible Power System
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
This page intentionally left blank.
Outdoor UPs SeriesOutdoor Uninterruptible Power System
97
Outdoor-UPs-8015/8016 ~ 96 watts, 115 or 230 vac input, 12 vdc output UPS
Outdoor UPsmodel8015
96 wattsinput can be 115 or 230 vac output is 12 vdc0.4 hour @ 96W 1 hour @ 48W-20° to +60°C;-40° to +60°Cwith optionalbattery heater
8016 96 wattsinput can be 115 or 230 vac output is 12 vdc 1 hour @ 96W2 hours @ 48W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
Dc output Wide temperature batteries Wide ac input voltage window
The TSi Power Outdoor-UPs-8015/8016 with dc output are for dc powered applications needing backup power in extreme weather conditions. They are constructed with wide temperature batteries and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer a wide input voltage window (88 to 264 vac) and low ripple 12 vdc output, with heavy duty surge protection and noise filtering.
Key Outdoor UPs benefitsThis rugged outdoor dc output UPS design is suitable for use in severe outdoor environments. Outdoor UPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. The wide input voltage window enables dc output without having to drain or exercise the batteries, thereby ensuring long battery life.Battery run-times for the Outdoor-UPs-8015 are approximately 0.4 hour at 96 watts load, and 1 hour at a 48 watts load. For the Outdoor-UPs-8016, approximately 1 hour at 96 watts load, and 2 hours with a 48 watts load.
How the Outdoor UPs worksThe outdoor UPs with dc output provides extended battery backup through a system which takes nominal 115 or 230 vac input (from 88 to 264 vac), converts it to dc, charges the batteries, and delivers a nominal 12 vdc (10 to 14 vdc) with a less than 200 millivolts peak to peak ripple. The heavy duty surge protection and noise filtering on the ac input helps protect the unit and load from transient surges on the line. Because the unit is already delivering dc power, upon a deep brownout or loss of power, the Outdoor UPs with dc output has a zero transfer time to the reserve power in the batteries. For OEMs, a small ‘hotel’ space is provided inside the unit for your equipment to reside.
Typical applicationsThese heavy duty outdoor UPS systems are designed to power wireless communications, perimeter surveillance cameras (CCTV), security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key Outdoor UPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44(NEMA-3R) metal cabinet• Dc output with low ripple • Wide temperature batteries• Heavy-duty surge protection
and noise filtering• Wide ac input voltage window
lengthens battery life• Two year warranty on electronics
One year warranty on batteries
Outdoor On-line UPS with Dc Output
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor
UPs UPsOutdoor
98 SpecificationsOutdoor-UPs-8015/8016
Specification Outdoor-UPs-8015 Outdoor-UPs-8016 Electrical
Capacity in watts 96 watts UPS topology Ac to dc rectifier, battery charger and sealed gel-cell batteries
Input Nominal voltage 115 or 230 volts ac
Operating voltage 88 to 264 vac without using batteries Input current 2A maximum @ 115vac, or 1A maximum @ 230 vacOperating frequency 50 or 60Hz (47 to 63Hz)
OutputNominal voltage 12 volts dc Operating voltage 10 to 14 volts dc (depending on battery charge status) Output current 8A maximum @ 12vdcDc ripple voltage Less than 200 millivolts peak to peak Power efficiency 84% (typical) Power on/off switch On/off rocker style power switch Transfer time to backup Zero transfer timeBattery backup time 0.4 hour @ 96 watts(8A) load,
1 hour @ 48 watts(4A) load.1 hour @ 96 watts(8A) load,2 hours @ 48 watts(4A) load.
Recharge time 4 hours to 90% capacity after full discharge.
8 hours to 90% capacity after full discharge.
Batteries 5 amp hours, 12vdc 10 amp hours, 12vdcWide temperature sealed gel-cells -20° to +60°C (-4° to+140°F); -40° to +60°C (-40° to+140°F) with optional battery heater.
Ac connections 3 position terminal block provided for 3 x 1mm2 (18AWG), L1, L2 and Ground connections via 12mm(1/2”) diameter liquid-tight cable glands.
Dc connections 2 position terminal block provided for dc output wires connection via 19mm(3/4”) diameter liquid-tight cable glands.
PhysicalDimensions 254mm(10”)wide x 305mm(12”)high x 152mm(6”)deepWeights 14kg(30 lbs) 21kg(45 lbs)
Steel cabinet Full weather IP44(NEMA 3R) UL50 outdoor padlockable enclosure. Mounting options Pole mountable to monopole via optional ‘H’ style bracket (mounting
bands not included). Wall mountable via enclosure’s top+bottom brackets. Also, optional pedestal (ground) brackets are available.
‘Hotel’ space for OEM option
Approximately 254mm(10”)wide x 76mm(3”)high x 152mm(6”)deep, (if more space is needed, unit can be built with a larger enclosure).
EnvironmentalOperating temperature,battery heater option
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
Outdoor dc output UPS with a wide ac input voltage window and extreme/wide temperature batteries
Specifications
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.TSi Power Corporation
Represented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor
UPs UPsOutdoor
Outdoor UPs SeriesOutdoor Uninterruptible Power System
99
Outdoor-UPs-8015/8016 at a glanceHeavy-duty outdoor on-line UPS with dc output, wide ac input voltage window, and wide temperature batteries
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• Low dc output ripple• 12vdc battery bus• 0.4 hour @ 96 watts load, or
1 hour @ 48 watts load with the Outdoor-UPs-8015
• 1 hour @ 96 watts load, or2 hours @ 48 watts load withthe Outdoor-UPs-8016
• Nominal 12 volts dc(10 to 14vdc) output from 88 to 264vac inputwithout going to batteries
• Weather protected IP44/NEMA-3R, UL50painted metal cabinet
• Optional pole, wall or floor mounting brackets available. Must be specified/ordered at time of purchase order.
• Larger OEM ‘hotel’ space is available, please call if more space is necessary.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
optional bandable or boltable monopole mounting brackets
Outdoor
UPs UPsOutdoor
ac input is via a12mm (1/2”) diameter liquid-tight cable gland,and dc output is via a19mm (3/4”) diameterliquid-tight cable gland
Outdoor-UPs-8015-8016-115or230vac-12vdc-96W-2006-10-16.pdf
100 Outdoor UPs SeriesOutdoor Uninterruptible Power System
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
This page intentionally left blank.
Outdoor UPs SeriesOutdoor Uninterruptible Power System
101
Outdoor-UPs-8011/8012 ~ 96 watts, 115 or 230 vac input, 24 vdc output UPS
Outdoor UPsmodel8011
96 wattsinput can be 115 or 230 vacoutput is 24 vdc1 hour @ 96W2 hours @ 48W-20° to +60°C;-40° to +60°Cwith optionalbattery heater
8012 96 wattsinput can be 115 or 230 vacoutput is 24 vdc2 hours @ 96W4 hours @ 48W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
Dc output Wide temperature batteries Wide ac input voltage window
The TSi Power Outdoor-UPs-8011/8012 with dc output are for dc powered applications needing backup power in extreme weather conditions. They are constructed with wide temperature batteries and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer a wide input voltage window (88 to 264 vac) and low ripple 24 vdc output, with heavy duty surge protection and noise filtering.
Key Outdoor UPs benefitsThis rugged outdoor dc output UPS design is suitable for use in severe outdoor environments. Outdoor UPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. The wide input voltage window enables dc output without having to drain or exercise the batteries, thereby ensuring long battery life.Battery run-times for the Outdoor-UPs-8011 are approximately 1 hour at 96 watts load, and 2 hours at a 48 watts load. For the Outdoor-UPs-8012, approximately 2 hours at 96 watts load, and 4 hours with a 48 watts load.
How the Outdoor UPs worksThe outdoor UPs with dc output provides extended battery backup through a system which takes nominal 115 or 230 vac input (from 88 to 264 vac), converts it to dc, charges the batteries, and delivers a nominal 24 vdc (20 to 28 vdc) with a less than 200 millivolts peak to peak ripple. The heavy duty surge protection and noise filtering on the ac input helps protect the unit and load from transient surges on the line. Because the unit is already delivering dc power, upon a deep brownout or loss of power, the Outdoor UPs with dc output has a zero transfer time to the reserve power in the batteries. For OEMs, a small ‘hotel’ space is provided inside the unit for your equipment to reside.
Typical applicationsThese heavy duty outdoor UPS systems are designed to power wireless communications, perimeter surveillance cameras (CCTV), security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key Outdoor UPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44(NEMA-3R) metal cabinet• Dc output with low ripple • Wide temperature batteries• Heavy-duty surge protection
and noise filtering• Wide ac input voltage window
lengthens battery life• Two year warranty on electronics
One year warranty on batteries
Outdoor On-line UPS with Dc Output
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor
UPs UPsOutdoor
102 SpecificationsOutdoor-UPs-8011/8012
Specification Outdoor-UPs-8011 Outdoor-UPs-8012 Electrical
Capacity in watts 96 watts UPS topology Ac to dc rectifier, battery charger and sealed gel-cell batteries
Input Nominal voltage 115 or 230 volts ac
Operating voltage 88 to 264 vac without using batteries Input current 2A maximum @ 115vac, or 1A maximum @ 230 vacOperating frequency 50 or 60Hz (47 to 63Hz)
OutputNominal voltage 24 volts dc Operating voltage 20 to 28 volts dc (depending on battery charge status) Output current 4A maximum @ 24vdcDc ripple voltage Less than 200 millivolts peak to peak Power efficiency 84% (typical) Power on/off switch On/off rocker style power switch Transfer time to backup Zero transfer timeBattery backup time 1 hour @ 96 watts (4A) load,
2 hours @ 48 watts(2A) load.2 hours @ 96 watts(4A) load,4 hours @ 48 watts(2A) load.
Recharge time 4 hours to 90% capacity after full discharge.
16 hours to 90% capacity after full discharge.
Batteries 5 amp hours, 24vdc 10 amp hours, 24vdcWide temperature sealed gel-cells -20° to +60°C (-4° to+140°F); -40° to +60°C (-40° to+140°F) with optional battery heater.
Ac connections 3 position terminal block provided for 3 x 1mm2 (18AWG), L1, L2 and Ground connections via 12mm(1/2”) diameter liquid-tight cable glands.
Dc connections 2 position terminal block provided for dc output wires connection via 19mm(3/4”) diameter liquid-tight cable glands.
PhysicalDimensions 254mm(10”)wide x 305mm(12”)high x 152mm(6”)deepWeights 14kg(30 lbs) 21kg(45 lbs)
Steel cabinet Full weather IP44(NEMA 3R) UL50 outdoor padlockable enclosure. Mounting options Pole mountable to monopole via optional ‘H’ style bracket (mounting
bands not included). Wall mountable via enclosure’s top+bottom brackets. Also, optional pedestal (ground) brackets are available.
‘Hotel’ space for OEM option
Approximately 254mm(10”)wide x 76mm(3”)high x 152mm(6”)deep, (if more space is needed, unit can be built with a larger enclosure).
EnvironmentalOperating temperature,battery heater option
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
Outdoor dc output UPS with a wide ac input voltage window and extreme/wide temperature batteries
Specifications
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.TSi Power Corporation
Represented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor
UPs UPsOutdoor
Outdoor UPs SeriesOutdoor Uninterruptible Power System
103
Outdoor-UPs-8011/8012 at a glanceHeavy-duty outdoor on-line UPS with dc output, wide ac input voltage window, and wide temperature batteries
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• Low dc output ripple• 24vdc battery bus• 1 hour @ 96 watts load, or
2 hours @ 48 watts load with the Outdoor-UPs-8011
• 2 hours @ 96 watts load, or4 hours @ 48 watts load withthe Outdoor-UPs-8012
• Nominal 24 volts dc(20 to 28vdc) output from 88 to 264vac inputwithout going to batteries
• Weather protected IP44/NEMA-3R, UL50painted metal cabinet
• Optional pole, wall or floor mounting brackets available. Must be specified/ordered at time of purchase order.
• Larger OEM ‘hotel’ space is available, please call if more space is necessary.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
optional bandable or boltable monopole mounting brackets
Outdoor
UPs UPsOutdoor
ac input is via a12mm (1/2”) diameter liquid-tight cable gland,and dc output is via a19mm (3/4”) diameterliquid-tight cable gland
Outdoor-UPs-8011-8012-115or230vac-24vdc-96W-2006-10-16.pdf
104 Outdoor UPs SeriesOutdoor Uninterruptible Power System
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
This page intentionally left blank.
Outdoor UPs SeriesOutdoor Uninterruptible Power System
105
Outdoor-UPs-8013/8014 ~ 96 watts, 115 or 230 vac input, 48 vdc output UPS
Outdoor UPsmodel8013
96 wattsinput can be 115 or 230 vacoutput is 48 vdc2 hour @ 96W4 hours @ 48W-20° to +60°C;-40° to +60°Cwith optionalbattery heater
8014 96 wattsinput can be 115 or 230 vacoutput is 48 vdc4 hours @ 96W8 hours @ 48W -20° to +60°C;-40° to +60°Cwith optionalbattery heater
Dc output Wide temperature batteries Wide ac input voltage window
The TSi Power Outdoor-UPs-8013/8014 with dc output are for dc powered applications needing backup power in extreme weather conditions. They are constructed with wide temperature batteries and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer a wide input voltage window (88 to 264 vac) and low ripple 48 vdc output, with heavy duty surge protection and noise filtering.
Key Outdoor UPs benefitsThis rugged outdoor dc output UPS design is suitable for use in severe outdoor environments. Outdoor UPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20°to +60°C (- 4° to +140°F); - 40° to +60°C (-40° to +140°F) with optional battery heater. The wide input voltage window enables dc output without having to drain or exercise the batteries, thereby ensuring long battery life.Battery run-times for the Outdoor-UPs-8013 are approximately 2 hours at 96 watts load, and 4 hours at a 48 watts load. For the Outdoor-UPs-8014, approximately 4 hours at 96 watts load, and 8 hours with a 48 watts load.
How the Outdoor UPs worksThe outdoor UPs with dc output provides extended battery backup through a system which takes nominal 115 or 230 vac input (from 88 to 264 vac), converts it to dc, charges the batteries, and delivers a nominal 48 vdc (40 to 56 vdc) with a less than 200 millivolts peak to peak ripple. The heavy duty surge protection and noise filtering on the ac input helps protect the unit and load from transient surges on the line. Because the unit is already delivering dc power, upon a deep brownout or loss of power, the Outdoor UPs with dc output has a zero transfer time to the reserve power in the batteries. For OEMs, a small ‘hotel’ space is provided inside the unit for your equipment to reside.
Typical applicationsThese heavy duty outdoor UPS systems are designed to power wireless communications, perimeter surveillance cameras (CCTV), security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key Outdoor UPs features• Cabinet can be pedestal(ground),
pole, or wall mounted• Full weather outdoor protection
IP44(NEMA-3R) metal cabinet• Dc output with low ripple • Wide temperature batteries• Heavy-duty surge protection
and noise filtering• Wide ac input voltage window
lengthens battery life• Two year warranty on electronics
One year warranty on batteries
Outdoor On-line UPS with Dc Output
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor
UPs UPsOutdoor
106 SpecificationsOutdoor-UPs-8013/8014
Specification Outdoor-UPs-8013 Outdoor-UPs-8014 Electrical
Capacity in watts 96 watts UPS topology Ac to dc rectifier, battery charger and sealed gel-cell batteries
Input Nominal voltage 115 or 230 volts ac
Operating voltage 88 to 264 vac without using batteries Input current 2A maximum @ 115vac, or 1A maximum @ 230 vacOperating frequency 50 or 60Hz (47 to 63Hz)
OutputNominal voltage 48 volts dc Operating voltage 40 to 56 volts dc (depending on battery charge status) Output current 2A maximum @ 48vdcDc ripple voltage Less than 200 millivolts peak to peak Power efficiency 84% (typical) Power on/off switch On/off rocker style power switch Transfer time to backup Zero transfer timeBattery backup time 2 hour @ 96 watts (2A) load,
4 hours @ 48 watts (1A) load.4 hours @ 96 watts (2A) load,8 hours @ 48 watts (1A) load.
Recharge time 8 hours to 90% capacity after full discharge.
16 hours to 90% capacity after full discharge.
Batteries 5 amp hours, 48vdc 10 amp hours, 48vdcWide temperature sealed gel-cells -20° to +60°C (-4° to+140°F); -40° to +60°C (-40° to+140°F) with optional battery heater.
Ac connections 3 position terminal block provided for 3 x 1mm2 (18AWG), L1, L2 and Ground connections via 12mm(1/2”) diameter liquid-tight cable glands.
Dc connections 2 position terminal block provided for dc output wires connection via 19mm(3/4”) diameter liquid-tight cable glands.
PhysicalDimensions 254mmWx305mmHx152mmD
(10”wide x 12”high x 6”deep)406mmWx406mmHx152mmD (16”wide x 16”high x 6”deep)
Weights 14kg(30 lbs) 23kg(50 lbs)
Steel cabinet Full weather IP44(NEMA 3R) UL50 outdoor padlockable enclosure. Mounting options Pole mountable to monopole via optional ‘H’ style bracket (mounting
bands not included). Wall mountable via enclosure’s top+bottom brackets. Also, optional pedestal (ground) brackets are available.
‘Hotel’ space for OEM option
Approximately 254mm(10”)wide x 76mm(3”)high x 152mm(6”)deep, (if more space is needed, unit can be built with a larger enclosure).
EnvironmentalOperating temperature,battery heater option
-20° to +60°C (-4° to+140°F) ambient air temperature. -40° to +60°C (-40° to+140°F) with optional battery heater.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
Outdoor dc output UPS with a wide ac input voltage window and extreme/wide temperature batteries
Specifications
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Outdoor
UPs UPsOutdoor
Outdoor UPs SeriesOutdoor Uninterruptible Power System
107
Outdoor-UPs-8013/8014 at a glanceHeavy-duty outdoor on-line UPS with dc output, wide ac input voltage window, and wide temperature batteries
• Wide ambient temperature range sealed gel-cell batteries:-20° to +60°C (-4° to +140°F); or-40° to +60°C (-40° to +140°F) with optional thermostat controlled battery heater
• Low dc output ripple• 48vdc battery bus• 2 hours @ 96 watts load, or
4 hours @ 48 watts load with the Outdoor-UPs-8013
• 4 hours @ 96 watts load, or8 hours @ 48 watts load withthe Outdoor-UPs-8014
• Nominal 48 volts dc(40 to 56 vdc) output from 88 to 264 vac inputwithout going to batteries
• Weather protected IP44/NEMA-3R, UL50painted metal cabinet
• Optional pole, wall or floor mounting brackets available. Must be specified/ordered at time of purchase order.
• Larger OEM ‘hotel’ space is available, please call if more space is necessary.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
optional bandable or boltable monopole mounting brackets
Outdoor
UPs UPsOutdoor
ac input is via a12mm (1/2”) diameter liquid-tight cable gland,and dc output is via a19mm (3/4”) diameterliquid-tight cable gland
Outdoor-UPs-8013-8014-115or230vac-48vdc-96W-2006-10-16.pdf
108 Outdoor UPs SeriesOutdoor Uninterruptible Power System
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
This page intentionally left blank.
Outdoor VRx SeriesOutdoor PWM Automatic Voltage Regulator Line Conditioner
109
Outdoor-VRx-4400-0455/0460 ~ 4.4kVA, 230vac, PWM AVR+line conditioner
TSi Power’s Outdoor VRx precision PWM automatic voltage regulator with optional built-in low-impedance isolation transformer allows trouble-free operation of electronic equipment over a wide mains ac voltage range of 172 to 276V found in many developing countries. There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer primary winding. VRx is also designed with a fail-safe automatic bypass which enables the VRx to provide power to the load even in the event of internal failure that may otherwise result in a disruption of power to the load. VRx with optional isolation transformer provides complete isolation from the ac line, with a neutral-to-ground bond to eliminate all surge voltages between neutral and ground.
Typical applicationsDesigned for critical outdoor systems where reliability and predictability matter, such as remote transceiver base stations, fixed wireless applications, as well as for other outdoor equipment requiring additional protection. They are also for mission-critical applications such as telecom applications in remote environments where consistent voltage levels cannot be trusted, and where service calls are expensive.VRx provides highly available regulated power and protection from mains voltages outside of the design limits for RBS power plants, typically 172 to 276vac. A low input voltage can result in inadequately charged batteries as the ac to dc power system is unable to draw the power required. An input voltage in excess of 276V, even for a short time, can cause the destruction of ac to dc power systems. In summary, VRx is designed to protect equipment even in the most challenging worldwide electrical, mechanical and environmental conditions.
Outdoor Precision PWM Automatic Voltage Regulator with optional Low-impedanceIsolation Transformer
VRx VRx
Key features of the VRx-4400• Accepts continuous 172 to 276vac
at 50/60Hz input• PWM automatic voltage regulation• Built-in over-voltage (OVP) and
under-voltage (UVP) protection• Automatic fail-safe bypass• Fail-safe design ensures
OVP functions even if voltage regulation circuits fail and unit transfers to bypass
• Coordinated surge protection in accordance with IEC 61312
• EFT and noise protection withlow dv/dt• True isolation and neutral-ground bond
with optional isolation transformer• Low weight and high efficiency• Quiet operation• 2 year warranty
International Precision voltage regulator Isolation transformer
Od-VRx model4400-0455
19 amps4.4kVA4.4 kW230vac-20° to +52°C
4400-0460 19 amps4.4kVA4.4 kW230vacwith isolation transformer-20° to +52°C
OutdoorOutdoor
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
110 Outdoor VRx SeriesOd-VRx-4400-0455-0460
How the VRx Series worksThe high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve precisely regulated 230 +/-3% vac output. The automatic bypass will be activated when there is a fault condition. Two green LED’s indicate Normal (regulating protected mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition.The over-voltage and under-voltage cutoff is activated whenever the ac mains voltage becomes dangerously high or low (outside 172 to 276 vac). It automatically restarts whenever ac mains voltage is restored within 172 to 276 vac.An optional low-impedance isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground. The leakage inductance of the isolation transformer, in combination with capacitive elements and MOVs, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.
Key VRx Series benefitsThe lightweight, high efficiency Outdoor VRx is easy to install in severe weather exposed environments. The unit comes in a specially designed IP44 (NEMA-3R) outdoor rated enclosure and has removable lifting eyes to enable use of lifting equipment.The automatic bypass assures that connected equipment will not shut down, even if VRx fails. VRx is compatible with all loads as it does not switch any components in the power path. VRx’s ultra-low impedance assures stability even with the most demanding loads.The automatic over-voltage / under-voltage cutoff with automatic restart ensures that operation is off-line during serious over-voltage or under-voltage situations that could damage the system and/or load, and then restarts without intervention when the ac mains voltage becomes within the operating range. The optional isolation line conditioner provides maximum equipment protection against surges, spikes and transients, for higher equipment reliability and maximum equipment operating life. In addition, improved repeatability, fewer reboots or system lock-ups, a reduction in equipment down time and service costs can be expected.
ground
circuit breaker
L2 G
L1
buck-boosttransformer
L
N
microprocessorcontrol
230vac+/-3%
VRxoutputautomatic bypass
over/undervoltage cutoff
surge prot.and
noisefilter
input172 to276vac
isolation transformer(optional)
noisefilter
dcac
ground
Outdoor VRx system architecture
VRx VRxOutdoorOutdoor
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
SpecificationsOD-VRx-4400/0455-0460
111
Outdoor rated wide voltage range precision automaticvoltage regulator
Specification Od-VRx-4400-0455 Od-VRx-4400-0460Electrical
Capacity in VA (watts) 4400VA (4400W)Regulator engine High frequency 20kHz IGBT driven voltage regulation converter Transformer type PWM buck-boost transformer PWM buck-boost transformer
plus isolation transformer Input
Operating voltage 172 to 276 vacNominal frequency 47 to 63HzCircuit breaker rating Upstream two-pole, 50A is recommended (to be supplied by customer). VRx circuit breaker rating Internal two-pole, 32A. Input wire size (two wires plus ground)
10mm2 (AWG 8) for both power and earth conductors. Stranded copper wire with min. 105oC insulation system recommended.
OutputNominal voltage 230 vac, single phase. Voltage regulation Combined 3% maximum under 0 to 100% load and input of 172~276V. Over-voltage protection OVP removes power to protected load if output voltage exceeds 264V.
Automatic reset returns power when voltage levels are back in tolerance. Power efficiency 96% (typical) 90% (typical) Automatic bypass Automatic bypass will be activated when there is a fault condition. System status indicators
System status LED’s provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (non-regulated output); Red LED indicates Overload (system may shut down).
Surge protection A coordinated surge protection system consisting of buck-boost transformer, filter and MOV. (Plus isolation transformer on -0460).
Surge test conditions Class 2 and Class 3 simulated lightning surge (Combination wave) Per ANSI/IEEE C62.41-1991, Cat. C test waveform: 6kV, 3kA, 8x20µS
Surge let-throughVoltage
L-N L-G Single pulse: 50 V 50 V Ring wave: 20 V 20 V Comb. wave: 250 V 250 V
L-N L-G N-G Singlepulse: 50V 50V 0.5V Ring wave: 20V 20V 0.5V Comb. wave: 250V 250V 0.5V
Ac connection Terminal block connectors via 19mm(3/4”) liquid-tight cable glands. Physical
Dimensions 406mm(16”)wide x 711mm(28”)high x 305mm(12”)deep Weight 36.3kg(80 lbs) 72.6kg(160 lbs)Mounting options Pole mountable with optional pole mounting kit, pedestal(ground), or
wall-mountable, four wall-mounting ‘feet’ included. Enclosure System is built in a weather tight IP44 (NEMA 3R) metal enclosure.
SafetyAgency approvals Designed to meet UL, cUL and IEC standards.
EnvironmentalAmbient temperature - 20o to +52oC. (- 40o to +52oC with optional built-in heater),
- 4o to +125oF. (- 40o to +125oF with optional built-in heater).Altitude From sea level to 10,000 feet (3000m) above sea level.
WarrantyWarranty Two year limited warranty, parts and labor.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
VRx VRx
VRx-4400liquid-tight cable glands
VRx-4400 with isolation
transformer option
OutdoorOutdoor
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
112 Outdoor VRx SeriesOd-VRx-4400-0455-0460
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Mounting on a concrete pad with Unistrut (or similar)Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor VRx Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad.The Outdoor VRx cabinet is provided with four (4) mounting feet at the four (4) corners.For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
Outdoor VRxpad mounted
Od-VRx-4400-0455-0460-2006-10-16.pdf
VRx VRxOutdoorOutdoor
406mm (16”)
thermostatcontrolledhot air vent forexhaust fan
concrete pad609mm (24”)above groundrecommended
VRxoutput
hole to hole368mm(14.5”)
305mm(12”)
711mm (28”)
acinput
doorhinges
intakeair ventunderneath
711mm (28”)
Mounting feetclose-up drawing
IP44(NEMA-3R)metal cabinet
holes for 19mm (3/4”)liquid-tightcable glands
door latch
19mm(.75”)
19mm(.75”)
19mm(.75”)
19mm(.75”)
Outdoor VRp-ILc SeriesPrecision Voltage Regulator + Isolation Transformer
113
Outdoor VRp-ILc models 15000-5339
15 kVA15 kWinput 400Vdeltaoutput 230/400V wyethree phase
30000-533930 kVA30 kWinput 400Vdeltaoutput 230/400V wyethree phase
TSi Power’s Outdoor VRp-ILc automatic precision voltage regulator with built-in low-impedance isolation transformer allows trouble-free operation of electronic equipment over a very wide mains ac voltage range of 400V+/-20% found in many developing countries. There is no switching of taps nor any break in the power path thanks to continuous pulse width modulation (PWM) switching of a buck-boost transformer primary winding.
Typical applications Designed for applications where absolutely safe and precisely regulated ac power is required, such as radio base stations (RBS), telecommunication transmission sites for backhaul (including microwave links), TV/radio broadcasting, industrial equipment and end-of-line utility equipment.
International Precision voltage regulator Isolation transformer
Precision PWM Automatic Voltage Regulator with Isolation Transformer,Automatic Bypass and Automatic Cutoff
Key Outdoor VRp-ILc features • Outstanding voltage regulation
performance: output is within 230/400vac+/-3% under a normal input range of 400vac +/-20%
• No switching of power path and unit always starts up on sine wave zero crossing
• Over-voltage cutoff, with automatic restart when ac mains voltage returns to normal (safe) condition
• Failsafe: automatic bypass (even during bypass, the over-voltage protection is active)
• Lightweight design
• A three phase low-impedance isolation transformer is used for maximum reliability
• Coordinated surge protection per IEC61312
• Advanced noise and interference filter reduces dV/dt from 6kV/µs to less than 10V/µs
• Pedestal-mountable cabinet• Common-mode noise elimination• IP23 outer enclosure with sensitive
components housed in an IP55 inner case (overall equivalent to IP44/NEMA-3R)
• Two year warranty
VRp-ILcVRp-ILcOutdoorOutdoor
Power with a Precision Attitude™
Outdoor-VRp-ILc-15000/30000-5339 ~ 15/30kVA, 400 vac delta,230/400 vac wye
VRp-ILcprovides
continuous,fast, no-break
voltage regulation
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
114 Outdoor VRp-ILc SeriesOutdoor-VRp-ILc-15000/30000-5339
Key Outdoor VRp-ILc benefitsThe lightweight, high efficiency Outdoor VRp-ILc is easy to install in outdoor environments. The unit comes in a specially designed outdoor rated enclosure with multiple air exhaust fans. To maximize cooling, the isolation transformer is housed in an IP23 outer enclosure. Sensitive components are housed in an IP55 inner case. Overall equivalent is to an IP44(NEMA-3R) enclosure. The automatic bypass assures that connected equipment will not shut down, even if VRp-ILc fails. VRp-ILc is compatible with all loads as it does not switch any components in the power path. VRp-ILc’s ultra-low impedance assures stability even with the most demanding loads.The automatic over-voltage cutoff with automatic restart ensures that operation is off-line during serious over-voltage situations that could damage the system and/or load, and then restarts without intervention when the ac mains voltage returns to the normal operating range. The ILc isolation line conditioner components provide maximum equipment protection against surges, spikes and transients, for higher equipment reliability and maximum equipment operating life. In addition, the VRp-ILc offers improved repeatability, fewer reboots or system lock-ups. A reduction in equipment down time and service costs can also be expected.
How the Outdoor VRp-ILc worksThe high frequency insulated gate bi-polar transistor (IGBT) driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve precisely regulated 230/400 vac three phase output. The Automatic Bypass will be activated when there is a fault condition. A green LED indicates normal regulated protected mode operation.The over-voltage cutoff is activated whenever the ac mains voltage becomes dangerously high (over 475vac). It automatically restarts whenever ac mains voltage is restored to a safe level.At extremely low ac input conditions it can be operated at limited duty cycle.A low-impedance isolation transformer provides complete isolation between the primary and secondary, and permits bonding between output neutral to ground, which completely eliminates all disturbances between neutral and ground. The leakage inductance of the isolation transformer, in combination with capacitive elements and metal oxide varistors (MOVs), provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312. Multiple cooling fans control the unit’s internal temperature, with intakes at the bottom of the unit and exhaust through the top rear of the unit, protected with a rain guard/sunshield.
Outdoor ratedprecision PWM voltage regulator with isolationtransformer
VRp-ILcVRp-ILcOutdoorOutdoor
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
SpecificationsPrecision Voltage Regulator + Isolation Transformer
115
Specification 15000-5339 30000-5339Electrical
Capacity in VA (watts) 15kVA (15kW) 30kVA (30kW)Regulator technology High frequency IGBT driven voltage regulation converter Transformer type Three phase isolation transformer used
Input Nominal voltage Three phase delta: 400 volts ac
Normal operating range 400 volts ac +/-25% at limited duty cycle Nominal frequency 47 to 63 Hz Input circuit breaker Input circuit breaker with limited inrush current capability. Over-voltage cutoff with auto-restart
Over-voltage cutoff activated when >475vac with automatic restart when voltage returns to normal.
Circuit breaker rating 40A 60AInput wire size 10mm2(AWG 8) 15mm2 (AWG 6)Ac connection Terminal block (L1, L2, L3 and ground wires) provided.
OutputNominal voltage Three phase wye: 230/400 volts acPower efficiency 95% maximumVoltage regulation Better than +/-3% Automatic bypass Automatic bypass will be activated when there is a fault condition. Overload protection Output circuit breaker provides protection against overload conditions. Surge protection A three-stage surge protection system consisting of isolation
transformer, capacitor and MOV is included. System status indicator Green LED indicates Normal (regulating) mode operation.Surge test conditions Class 2 and Class 3 Simulated lightning surge (Combination wave)
Per ANSI/IEEE C62.41-1991, Cat. C test waveform: 6kV,3kA,8x20µs.Optional Class 1 surge arrester available for primary protection.
Surge let-throughvoltages
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5VMeasured rate of voltage rise/fall (dV/dt) of the remnant waveformis less than 10V/µs with input test waveform dV/dt of 6kV/µs.
Common mode filtering Neutral-ground bond eliminates all noise or voltage on neutral (< 0.5V) Normal mode filtering A built-in inductor-capacitor filter attenuates EMI/RFI noise from output. Circuit breaker rating 30A 50A Output wire size 6mm2 (AWG 10) 15mm2 (AWG 6)Ac connection Terminal block (L1, L2, L3, neutral and ground wires) provided.
PhysicalDimensions 1040mm(40.9”)wide
450mm(17.7”)deep 1170mm(46.1”)high
1150mm(45.3”)wide 600mm(23.6”)deep 1300mm(51.2”) high
Weight 250kg (550 lbs) 450kg(990 lbs)Safety
Standards Designed to meet IEC 60950 standards.Environmental
Ambient temperature -20o to +40oC(-4o to +104oF). Cooling method Multiple air exhaust fans are used. Weather protection IP23 outer enclosure with sensitive components housed in
an IP55 inner case (overall equivalent to IP44/NEMA-3R).Warranty
Warranty Two year limited warranty, parts and labor.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Outdoor precisionPWM voltage regulator withisolation transformer
VRp-ILcVRp-ILcOutdoorOutdoor
Power with a Precision Attitude™
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
116 Outdoor VRp-ILc SeriesOutdoor-VRp-ILc-15000/30000-5339
the Outdoor VRp-ILc providesexcellent protection, superior
thermal management andease of installation
Front right side view
Outdoor VRp-ILc system architecture (per phase)
ground
3 phasecircuit breaker
L2 G
L1
buck-boosttransformer
L
N
microprocessorcontrol
230vac+/-3%
VRp-ILcoutputautomatic bypass
over-voltagecutoff
surge prot.and
noisefilter
input400vac+/-20%
isolation transformer
noisefilter
dcac
ground
1300
mm
Outdoor-VRp-ILc-15000-30000-5339-2006-10-16.pdf
VRp-ILcVRp-ILcOutdoorOutdoor
ventilatedbase
600mm
Right side rear view
input/outputcable glands openings
hot airexhaust
front panelis a hingeddoor with locks
(23.6”)
(51.
2”)
1150mm(45.3”)
model-30000
450mm(17.7”)
model-15000
1040mm
(40.9”)
1170
mm
(46.
1”)
Inside view
ac surge protection and filter module
three separatebuck-boosttransformers
hot air exhaust via multiple fans (not shown)
VRp electronic module with fans
ac input/outputvia cable glands
delta to wyetransformer
ac input/outputconnectionterminals
cold air entrythrough mesh
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
RMk SeriesRack-Mounting Kits
117
RMk SeriesRack-mounting kits
RMk Series ~ Rack-mounting Kits for TSi Rack-mountable Products
RMkRMk
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
118 RMk SeriesRack-Mounting Kits
RMk-Series-2006-10-16.pdf
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
RMk ~ Rack-Mounting Kits 119
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ModelsMK-5019AMK-8019A
19” Front
MK-5023A MK-8023A
23” Front
MK-5024A 24” Front
MK-8024A &MK-8024B
24” Front and Rear
MK-5019F MK-8019F
19” Center
MK-5023F MK-8023F
23” Center
MK-5024F MK-8024F
24” Center
MK-8019B 19” Rear
MK-8023B 23” Rear
MK-5000C MK-5019C
Wall/floor
A TSi UPs-7200 & EXt-5000 battery extension unit shown mounted inside a 19” wide cabinet using an MK-5019A (Front rack-mount kit).
TSi offers a range of different brackets allowing you to mount our products on the rack of your choice. We can help you to choose the most suitable set for your specific product and rack size. Also, please see the back of this page for a table of standard kits.
A TSi UPs-16000 and EXt-8000 Battery Extension Unit shown mounted inside a 19” wide cabinet using an MK-8019A & MK-8019B (Front and Rear rack-mount kits).
All of TSi's products can be placed virtually any-where that fits your space considerations. This includes desktop and floor mount options. If a rackmount configuration is what you require, TSi's XINv, INv, ATs, XUPs and most UPs systems are designed to accommodate most standard component rack/cabinet enclosures.
Key benefitsWith one of these simple rack mount kit options, you can place your rack-mountable UPs (uninter-ruptible power system), XINv/INv (inverter) ARm (automatic redundancy module), or ATs (auto-matic transfer switch) in either a 19". 23", or 24" rack and facilitate the space requirements of your systems, not the UPS or transfer switch.
Shown mounted inside a standard telco-style 19” wide, 40” tall rack, are:
• An ARm-1000FAA automatic redundancymodule (automatic transfer switch), usingan MK-5019F Center-mounting kit.
• A TSi Power UPs-10000, and two EXt-8000 battery extension units, using MK-8019F Center-mounting kits.
RMk Series ~ Rack-mounting kits for 19”, 23”, 24” racks, and wall-mounting
For 19”, 23” or 24” racks Rackmount kits for XUPs/UPs, XINv and ATs
Rack/ floor/wall Mounting Kits forXUPs/UPs, XINv, and ATs Series
RMkRMk
120 SpecificationsRack-mounting Kits
by Kit part numbers Rackmount kit description For 19” racks Mk-5019A 19” Front mounting kit MK-5019F 19” Center mounting kit Mk-8019A 19” Front mounting kit Mk-8019B 19” Rear mounting kit MK-8019F 19” Center mounting kit For 23” racks MK-5023A 23” Front mounting kit MK-5023F 23” Center mounting kit MK-8023A 23” Front mounting kit MK-8023B 23” Rear mounting kit MK-8023F 23” Center mounting kit For 24” racks MK-5024A 24” Front mounting kit MK-5024F 24” Center mounting kit MK-8024A And MK-8024B
24” Front And Rear mounting kit
MK-8024F 24” Center mounting kit Wall / floor mount MK-5000C Wall / floor mounting kit MK-5019C Wall / floor mounting kit By Specific Product rack-mount Kit Choices by Specific product Rackmount kit choices For XUPs-600/1000/600E/1000E, XINv-400/700/1400/400E/700E/1400E Rackmount options Front-mount kits: For a 19” rack: use # MK-5019A
For a 23” rack: use # MK-5023A For a 24” rack: use # MK-5024ACenter-mount kits: For a 19” rack: use # MK-5019F For a 23” rack: use # MK-5023F For a 24” rack: use # MK-5024FWall/floor-mount kits: use # MK-5000C
For VRp-3000/5000/5500 Wall/floor-mount Wall/floor-mount kits: Use # MK-5019C For ARm-1000 Rackmount option Front-mount kit: For a 19” rack: use # MK-1019A For ARm-1000FAA, Rackmount options
Front-mount kits: For a 19” rack: use # MK-5019A For a 23” rack: use # MK-5023A For a 24” rack: use # MK-5024A Center-mount kits: For a 19” rack: use # MK-5019F For a 23” rack: use # MK-5023F For a 24” rack: use # MK-5024F Wall/floor-mount kits: Use # MK-5000C
For ATs-1000/1000E Rackmount options Front-mount kits: For a 19” rack: use # MK-5019A
For a 23” rack: use # MK-5023A For a 24” rack: use # MK-5024ACenter-mount kits: For a 19” rack: use # MK-5019F For a 23” rack: use # MK-5023F For a 24” rack: use # MK-5024FWall /floor-mount kits: use # MK-5000C
For INv-750/1000/1500, UPs-10000/16000/21000, and EXt-8000 Rackmount options (Heavy units should have both front & rear)
For 19” cabinet: use Front Pair # MK-8019A and Rear Pair # MK-8019B
For telecom center-mount rack: use Center pair # MK-8019F
Rackmount kits
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
RMkRMk
RMk-2006-10-16.pdf
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
SLc SeriesStabilizing Line Conditioners
121
SLc SeriesVoltage stabilizing line conditioners
SLc Series ~ Automatic Voltage Stabilizing Line Conditioners
SLcSLc
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
122 SLc SeriesStabilizing Line Conditioners
SLc-Series-2006-10-16.pdf
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
SLc SeriesStabilizing Line Conditioner
123
Auto-transformer Automatic voltage regulator UL/cUL listed
SLc-600/1200/1800 ~ 5/10/15A, 600VA/1.2 /1.8kVA, 120vac
This automatic voltage regulator provides stable power even when the ac mains or back-up generator voltage is extremely low or high.
Typical applications SLc Series conditioners provide low-cost ac line protection for computers, point-of-sale terminals, copiers, data acquisition and control systems, as well as other data processing equipment. SLc’s can also be used to protect low-cost stand-by UPS to prevent discharge of UPSbatteries due to low- or high-voltage transfer to inverter.
Key benefitsTSi Power’s SLc Series regulated output protects switch-mode power supplies from failure caused by unstable ac mains. SLc provides three-way surge protection and reduction of surge voltage. The SLc line conditioner can be used between a UPS and the ac mains to provide even greater protection for the connected equipment, while saving the UPS's internal batteries for true black-outs.
How the SLc Series worksThe SLc Series incorporates a four-winding auto-transformer, which provides four levels of line regulation: two boost-stage and one buck-stage. Even when the input voltage varies between 75 to 150V, the output is regulated to within 105 and 130V, well within the range of most equipment. SLc operation is monitored by four status LED’s, indicating normal, boost 1, boost 2 and buck stages of voltage regulation. The front panel power switch turns the SLc unit on and supplies power to the equipment.
SLc model600
5 amps600 VA600 watts120 volts
1200 10 amps1200 VA1200 watts120 volts
1800 15 amps1800 VA1800 watts120 volts
Four-stage Auto-transformer Voltage Regulator Line Conditioner
SLcSLc
Key features of the SLc Seriesstabilizing line conditioner
• Four stages of regulated output voltages
• Wide input range• Multi-mode surge protection• Quiet operation• Four ac outlets• Front panel power switch• Four status LED display indicators• High efficiency• Low cost• Two year warranty
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
124 SpecificationsSLc-600-1200-1800
SLc-600-1200-1800-120V-2006-10-16.pdf
Specification SLc-600 SLc-1200 SLc-1800 Electrical
Capacity in VA (watts) 600VA (600W) 1200VA (1200W) 1800VA (1800W)Transformer type Four winding auto-transformer.
Input Nominal voltage 120 volts ac
Operating voltage 75 to 150 volts acNominal frequency 60 Hz
Ac input cord 6 foot long ac power cord with NEMA 5-15P plug. Output
Ac output voltage 105 to 130 volts acSurge protection Three-way surge protection system. Surge test conditions Per ANSI/IEEE C62.41-1991 test pulse,
Category A3, Ring wave, 6000V, 200A. Test pulse injection: Line-neutral, Line-ground, and Neutral-ground.
Surge let-through voltages
Remnant voltage: L-N: 15V, L-G: 15V, N-G: 400V.
Power efficiency > 97% at full load.Power on/off switch On/off rocker power switch.Response time Transfers to new stage within 20 cycles of new ac input voltage.Transfer time Less than 4ms between stages.Hysteresis 6V minimum. Prevents unnecessary switch-overs
due to momentary ac sags and brownouts. Indicators Four status LED’s indicating normal, boost 1,
boost 2, and buck stages of voltage regulation. Ac output receptacles Four (NEMA 5-15R)
PhysicalDimensions 152mm(6”)wide x 102mm(4.0”)high x 203mm(8.0”)deep Weight 3.6 kg(8 lbs) 5.0 kg(11 lbs) 6.8 kg(15 lbs)
SafetyAgency approvals UL and cUL listed
EnvironmentalAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Two year limited warranty, parts and labor.
Four stage auto-transformer voltage regulator
Rear view
SLcSLc
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
groundsurge
protection and
noisefilter
acinput
hot
fuse
neutral
hot
ground
SLcoutput
neutral
four tap voltage regulator
powersupply
logic
-15%
+40%+20%
0%
ac output105 to 130 vac
75 to 150 vac
SLc Series system architecture
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
SLc SeriesStabilizing Line Conditioner
125
SLc-600E/1200E /1800E ~ 2.6/5/ 7.8A, 600VA/ 1.2/1.8kVA, 230vac
SLc model600E
2.6 amps600 VA600 watts230 volts
1200E 5 amps1200 VA1200 watts230 volts
SLcSLc
Key features of the SLc Seriesstabilizing line conditioner
• Four stages of regulated output voltages
• Wide input range• Multi-mode surge protection• Quiet operation• Four ac outlets• Front panel power switch• Four status LED display indicators• High efficiency• Low cost• Two year warranty
This automatic voltage regulator provides stable power even when the ac mains or back-up generator voltage is extremely low or high.
Typical applications SLc Series conditioners provide low-cost ac line protection for computers, point-of-sale terminals, copiers, data acquisition and control systems, as well as other data processing equipment. SLc’s can also be used to protect low-cost stand-by UPS to prevent discharge of UPSbatteries due to low- or high-voltage transfer to inverter.
Key benefitsTSi Power’s SLc Series regulated output protects switch-mode power supplies from failure caused by unstable ac mains. SLc provides three-way surge protection and reduction of surge voltage. The SLc line conditioner can be used between a UPS and the ac mains to provide even greater protection for the connected equipment, while saving the UPS's internal batteries for true black-outs.
How the SLc Series worksThe SLc Series incorporates a four-winding auto-transformer, which provides four levels of line regulation: two boost-stage and one buck-stage. Even when the input voltage varies between 75 to 150V, the output is regulated to within 105 and 130V, well within the range of most equipment. SLc operation is monitored by four status LED’s, indicating normal, boost 1, boost 2 and buck stages of voltage regulation. The front panel power switch turns the SLc unit on and supplies power to the equipment.
Four stage Auto-transformer Voltage Regulator Line Conditioner
Auto-transformer Automatic voltage regulator UL/cUL listed
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
126 SpecificationsSLc-600E-1200E-1800E
SLc-600E-1200E-1800E-230V-2006-10-16.pdf
Four stage 230Vauto-transformervoltage regulator
SLcSLc
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Specification SLc-600E SLc-1200E SLc-1800EElectrical
Capacity in VA (watts) 600VA (600W) 1200VA (1200W) 1800VA (1800W)Transformer type Four winding auto-transformer.
Input Nominal voltage 230 volts ac
Operating voltage 150 to 280 Volts acNominal frequency 50/60 Hz
Ac input cord 6 foot long ac power cord with IEC-320 plug.Output
Ac output voltage 200 to 250 volts acSurge protection Three-way surge protection system. Surge test conditions Per ANSI/IEEE C62.41-1991 test pulse,
Category A3, Ring wave, 6000V, 200A.Test pulse injection: Line-neutral, Line-ground, and Neutral-ground.
Surge let-through voltages
Remnant Voltage: L-N: 15V, L-G: 15V, N-G: 400V.
Power efficiency > 97% at full load. Power on/off switch On/off rocker power switch. Response time Transfers to new stage within 20 cycles of new ac input voltage.Transfer time Less than 4 mS between stages. Hysteresis 6V minimum. Prevents unnecessary switch-overs
due to momentary ac sags and brownouts.Indicators Four status LEDs indicating normal, boost 1,
boost 2, and buck stages of voltage regulation. Ac output receptacles Four IEC-320, (E Option) or two Schuko (EC Option)
PhysicalDimensions 152mm(6”)wide x 102mm(4.0”)high x 203mm(8.0”)deep Weight 3.6 kg(8 lbs) 5.0 kg(11 lbs) 6.8 kg(15 lbs)
SafetySafety Standards Designed to meet UL, cUL and IEC standards.
EnvironmentalAmbient Temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Two year limited warranty, parts and labor.
SLc system architecture
groundsurge
protection and
noisefilter
acinput
hot
fuse
neutral
hot
ground
SLcoutput
neutral
four tap voltage regulator
powersupply
logic
-15%
+40%+20%
0%
SLc output200 to 250 vac
150 to 280vac
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
SLc-B SeriesWide Voltage Input ~ Stabilizing Line Conditioner
127
SLc-1100B/2000B ~ 9/16A, 1.1kVA/2 kVA, 120vac
This automatic voltage regulator provides stable power even when the ac mains or back-up generator voltage is extremely low or high.
Typical applications SLc-B Series conditioners provide low-cost ac line protection for copiers, digital printers, fax, data acquisition and control systems, as well as other data processing equipment. SLc-B’s can also be used to protect low-cost stand-by UPS to prevent discharge of UPSbatteries due to low- or high-voltage transfer to inverter.
Key SLc-B benefitsTSi Power’s SLc-B Series regulated output protects switch-mode power supplies from failure caused by unstable ac mains. SLc-B provides three-way surge protection and reduction of surge voltage. The SLc-B line conditioner can be used between a UPS and the ac mains to provide even greater protection for the connected equipment, while saving the UPS's internal batteries for true black-outs.
How The SLc-B Series worksThe SLc-B Series incorporates a four-winding auto-transformer, which provides four levels of line regulation: two boost-stage and one buck-stage. Even when the input voltage varies between 80 to 150V, the output is regulated to within 104 and 126V, well within the range of most equipment. A rocker style power switch/circuit breaker turns the unit on and supplies power to the equipment.
SLc model1100B
9 amps1100VA1100 watts120 volts
2000B 16 amps2000VA2000 watts120 volts
Auto-transformer Automatic voltage regulator Wide input rangeSLc-BSLc-B
Four stage Auto-transformer Voltage Regulator Line Conditioner
Key SLc-B Series features• Four stages of regulated
output voltages• Wide input voltage range• Three-stage surge protection• Quiet operation• Four NEMA 5-15R outlet receptacles• Front panel power switch• High efficiency• Low cost• Five year warranty
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
128 SpecificationsSLc-1100B/2000B
SLc-BSLc-B
SLc-1100B-2000B-2006-10-16.pdf
Four stage 120Vauto-transformer voltage regulator
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Specification SLc-1100B SLc-2000BElectrical
Capacity in VA (Watts) 1100VA (1100W) 2000VA (2000W)Transformer type Four winding auto-transformer.
Input Nominal voltage 120 volts ac+/-33%
Operating voltage 80 to 150 volts acNominal frequency 50/60 Hz (47 to 63Hz)Ac input 6 foot cord with NEMA 5-15P plug 6 foot cord with NEMA 5-20P plugMaximum input current 9 amps @ 120vac 16 amps @ 120vac
OutputAc output voltage 115 volts+/-10% ac (104 to 126 vac)Maximum output 9 amps 16 ampsSurge protection Three-stage surge protection system.Power efficiency 97% or higher under all conditions.Power on/off switch On/off rocker power switch.Response time Transfers to new stage within 20 cycles of new ac input voltage.Transfer time Less than 4 mS between stages.Hysteresis 6V minimum. Prevents unnecessary switch-overs
due to momentary ac sags and brownouts.Ac output receptacles Four standard NEMA 5-15RAudible noise Less than 45 dBA (at 1 meter)
PhysicalDimensions 152mm(6”) wide x 127mm(5.0”)high x 229mm(9”)deepWeight 8.2kgs(18 lbs) 9kgs(20 lbs)
SafetySafety standards Designed to meet UL, cUL and IEC standards.
EnvironmentalAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Five year limited warranty.
(Replacement boards will be provided free of charge upon failure ~ board is the only part that can fail and can be easily replaced by the user).
groundsurge
protection and
noisefilter
acinput
hotfuse
neutral
hot
ground
neutral
four tap voltage regulator
powersupply
logic
-15%
+40%+20%
0%
80 to150vac
SLc-B output115vac+/-10%
SLc-B system architecture
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
SLc-Be SeriesWide Voltage Input ~ Stabilizing Line Conditioner
129
SLc-1100BE/2000BE ~ 5.5 /10A, 1100/2000 VA, 230vac
This automatic voltage regulator provides stable power even when the ac mains or back-up generator voltage is extremely low or high.
Typical applications SLc-Be Series conditioners provide low-cost ac line protection for copiers, digital printers, fax, data acquisition and control systems, as well as other data processing equipment. SLc-Be’s can also be used to protect low-cost stand-by UPS to prevent discharge of UPSbatteries due to low- or high-voltage transfer to inverter.
Key SLc-Be benefitsTSi Power’s SLc-Be Series regulated output protects switch-mode power supplies from failure caused by unstable ac mains. SLc-Be provides three-way surge protection and reduction of surge voltage. The SLc-Be line conditioner can be used between a UPS and the ac mains to provide even greater protection for the connected equipment, while saving the UPS's internal batteries for true black-outs.
How the SLc-Be Series worksThe SLc-Be Series incorporates a four-winding auto-transformer, which provides four levels of line regulation: two boost-stage and one buck-stage. Even when the input voltage varies between 154 to 306V, the output is regulated to within 207 and 253V, well within the range of most equipment. A rocker style power switch/circuit breaker turns the unit on and supplies power to the equipment.
SLc model1100BE
5.5 amps1100VA1100 watts230 volts
2000BE 10 amps2000VA2000 watts230 volts
Key SLc-Be Series features• Four stages of regulated
output voltages• Wide input voltage range• Three-stage surge protection• Quiet operation• Four IEC320 ac outlet receptacles• Front panel power switch• High efficiency• Low cost• Five year warranty
SLc-BeSLc-Be
Four stage Auto-transformer Voltage Regulator Line Conditioner
Auto-transformer Automatic voltage regulator Wide input range
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
130 SpecificationsSLc-1100BE/2000BE
SLc-1100BE-2000BE-2006-10-16.pdf
Four stage 230Vauto-transformer voltage regulator
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Specification SLc-1100BE SLc-2000BEElectrical
Capacity in VA (watts) 1100VA (1100W) 2000VA (2000W)Transformer type Four winding auto-transformer.
Input Nominal voltage 230 volts ac+/-33%
Operating voltage 154 to 306 volts acNominal frequency 50/60 Hz (47 to 63Hz)Ac input IEC320 inlet (ac input cord plug provided by customer per country spec) Maximum input current 6 amps @ 200vac 11 amps @ 200vac
OutputAc output voltage 230 volts+/-10% ac(207 to 253 vac)Maximum output 5.5 amps 10 ampsSurge protection Three-stage surge protection system.Power efficiency 97% or higher under all conditions.Power on/off switch On/off rocker power switch.Response time Transfers to new stage within 20 cycles of new ac input voltage.Transfer time Less than 4 mS between stages.Hysteresis 6V minimum. Prevents unnecessary switch-overs
due to momentary ac sags and brownouts.Ac output receptacles Four IEC-320Audible noise Less than 45 dBA (at 1 meter)
PhysicalDimensions 152mm(6”) wide x 127mm(5.0”)high x 229mm(9”)deepWeight 8.2kgs(18 lbs) 9kgs(20 lbs)
SafetySafety standards Designed to meet UL, cUL and IEC standards.
EnvironmentalAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Five year limited warranty .
(Replacement boards will be provided free of charge upon failure ~ board is the only part that can fail and can be easily replaced by the user).
groundsurge
protection and
noisefilter
acinput
hotfuse
neutral
hot
ground
neutral
four tap voltage regulator
powersupply
logic
-15%
+40%+20%
0%
154 to306vac
SLc-Be output230vac+/-10%
SLc-Be system architecture
SLc-BeSLc-Be
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
UPs and XUPs Series ~ IndoorUninterruptible Power Systems
131
and UPs UPs
Note: This section also includes some widetemperature UPS suitable for use in outdoor
enclosures. For self-contained Outdoor XUPs/UPs, please see the Outdoor section.
XUPs and UPs Series ~ Uninterruptible Power Systems
UPs and XUPs SeriesUninterruptible power systems
XUPs XUPsand
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
132 UPs and XUPs Series ~ IndoorUninterruptible Power Systems
This page intentionally left blank.
UPs-XUPs-Series-2006-10-16.pdf
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPs SeriesRack-mountable Uninterruptible Power System
133
XUPs-600/1000 ~ 600VA /1000VA, 420W/700W,120vac, UPS+AVR
XUPs model600
5 amps600 VA420 watts120 volts10 min @420W 25 min @ 210W
10008.3 amps1000 VA700 watts120 volts5 min @ 700W 12 min @ 350W
Pure sine wave Wide input voltage window Voltage regulation
These heavy-duty XUPs Series UPS are housed in a rugged steel rack-mountable enclosure. The XUPs offers line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.
Key XUPs benefitsThe XUPs design, with its microprocessor-controlled 15kHz sine wave inverter, reduces the number of solid-state devices required for power conversion, thereby yielding a high level of reliability. Built-in automatic voltage regulation enables a wide input voltage window within which the XUPs can deliver power without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics.Standard battery run-times for the XUPs-600are approximately 10 minutes at a 420 watts load, and 25 minutes with a 210 watts load; and for the XUPs-1000, approximately 5 minutes at a 700 watts load, and 12 minutes at a 350 watts load.A built-in Anderson SB50 connector enables adding extra battery cabinets for longer times.
How the XUPs worksThe XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, and also overvoltage protection with a threshold of 135vac, and undervoltage protection with a threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other electronic systems.A comprehensive array of power, battery level, voltage level, and inverter status LED indicators is provided for visual assessment of UPS status. A DB-9 port is provided for communication using RS-232 or relay dry contact signals. The power on/off switch is recessed to prevent accidental turn on or off.
Rack-mountable Sine Wave UPS with AVR and a Wide Input Voltage Window
Typical XUPs applications This heavy duty UPS system is ideal for protection of computers, WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key XUPs features• Pure sine wave inverter output• Over/under-voltage protection• Rack or wall mountable with
optional rack/wall-mount kit • Heavy-duty surge protection
and noise filtering• Automatic voltage regulation
with wide voltage input windowenhances long battery life
• Comprehensive array of status bargraphs for voltage,load and battery levels
• SNMP compatible via RS-232port with optional SNMP adapter
• Both RS-232 (via DB9)and relay contact signals are provided
• Two year warranty on electronics• One year warranty on batteries
XUPs XUPs
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
134 SpecificationsXUPs-600/1000
Specification XUPs-600 XUPs-1000Electrical
Capacity in VA (watts) 600VA (420W) 1000VA (700W)
UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter. Input
Nominal voltage 120 volts ac (95–135vac without using batteries)Input current 5A maximum @ 120 vac 8.3A maximum @ 120 vac
Operating voltage. Freq. 95 to 140 vac without using batteries. 47 to 63Hz.Input receptacle/plug IEC320 input receptacle. Line cord with NEMA 5-15P plug.
OutputNominal voltage 120 volts ac Voltage regulation 115vac +/-8% upon changes in line or load. Crest ratio 3:1Output waveform Pure sine wave, less than 3% THD with linear load. Power efficiency 97 %, under full load conditions. Power on/off switch Recessed on/off rocker style power switch. Transfer time <4 millisecondsBatteries 7 amp hours, 24vdc maintenance-free sealed lead-acid batteries. Battery backup time 10 minutes @ 420 watts load.
25 minutes @ 210 watts load. 5 minutes @ 700 watts load.
12 minutes @ 350 watts load. Recharge time Four hours to 95% capacity after full discharge.Optional extra battery pack(s) for longer backup time
Matching extra battery pack(s) available with SB50 connector,and separate battery charger for enabling faster recharge times.Please call for sizing assistance.
SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Surge protection Ac input surge/noise filter (using inductor, capacitor and MOV). Status indicators 5 LED load level indicator: 0 to 100% of rated load.
5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault and overload.
Output receptacles Eight standard NEMA 5-15R receptacles. For others please call. Physical
Dimensions 406mm(16”)wide x 381mm(15”)deep x 89mm(3.5”)high (2U high) Weights 15kg(32 lbs) 17kg(37 lbs)
Housing Painted steel enclosure with rubber feet. Rack or wall mountingkits (optional)
Front pair rack-mount kit: For a 19” rack: # MK-5019A For a 23” rack: #MK-5023A
Center pair rack-mount kit: For a 19” rack: # MK-5019F For a 23” rack: #MK=5023F
Wall or floor mount kit: use # MK-5000C Safety
Agency approvals Designed to meet UL, cUL and IEC safety standards. Environmental
Operating temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
XUPs XUPs
Rack-mountableheavy-dutyline-interactive UPS with automaticvoltage regulation
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPs SeriesRack-mountable Uninterruptible Power System
135
XUPs XUPsFront-right view
Rear view
dc circuit breaker output ac via eightNEMA 5-15R receptacles
DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)
input ac IEC 320 receptacle for 6 foot cord with NEMA 5-15P plug(also accepts other cord/plug sets)
input ac circuit breaker
recessed on/off switch
- ac input on LED lit- buck mode- boost mode- overload- inverter on/off- battery failure
output current: threeof five LEDs showingXUPs 60% loaded
battery voltage level:four of five LEDsshowing batteries at80% charge status
dc Anderson SB-50battery connector
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
136 XUPs SeriesXUPs-600/1000
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi XUPs-600-1000-2006-10-16.pdf
XUPs XUPs
utilityac
input heavy-dutyac surge
protection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
battery and
charger
hot
relay 2
regulated XUPs output 115vac +/-8%
neutrallogic
-10%
+10%0%
95 –135vac
chassis
relay 1
inverterac
dc
groundchassis
groundearth
XUPs-600/1000 system architecture
XUPs-600/1000 at a glanceRack or wall-mountable heavy-duty UPS with line-interactiveautomatic voltage regulation and wide input voltage window
• 10 minutes @ 420 watts load25 minutes @ 210 watts load with XUPs-600
• 5 minutes @ 700 watts load12 minutes @ 350 watts load with XUPs-1000
• A built-in Anderson SB50 connector enables adding extra battery packs for longer times
• Less than 4ms transfer time • 24vdc battery bus
• 115vac +/-8% output from 95 to 135vac inputwithout going to batteries
• Microprocessor-controlled 15kHz PWM sine wave inverter
• Rack-mountable metal cabinet allows for rack or wall mounting using optional mounting kits
• SNMP compatible with optional SNMP adapter
Anderson SB50 connector
dc circuitbreaker
ac circuitbreaker
XUPs SeriesRack-mountable Uninterruptible Power System
137
XUPs-600HV/1000HV ~ 600VA /1000VA, 420W/700W, 230vac, UPS+AVR
XUPs model600HV
2.5 amps600 VA420 watts230 volts10 min @420W 25 min @ 210W
1000HV4.2 amps1000 VA700 watts230 volts5 min @ 700W 12 min @ 350W
These heavy-duty XUPs Series UPS are housed in a rugged steel rack-mountable enclosure. The XUPs offers line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.
Key XUPs BenefitsThe XUPs design, with its microprocessor-controlled 15kHz sine wave inverter, reduces the number of solid-state devices required for power conversion, thereby yielding a high level of reliability. Built-in automatic voltage regulation enables a wide input voltage window within which the XUPs can deliver power without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics.Standard battery run-times for the 600HVare approximately 10 minutes at a 420 watts load, and 25 minutes with a 210 watts load; and for the 1000HV, approximately 5 minutes at a 700 watts load, and 12 minutes at a 350 watts load.A built-in Anderson SB50 connector enables adding extra battery cabinets for longer times.
How the XUPs WorksThe XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, and also overvoltage protection with a threshold of 270vac, and undervoltage protection with a threshold of 190vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other electronic systems.A comprehensive array of power, battery level, voltage level, and inverter status LED indica-tors is provided for visual assessment of UPS status. A DB-9 port is provided for communica-tion using RS-232 or relay dry contact signals. The power on/off switch is recessed to prevent accidental turn on or off.
Rack-mountable Sine Wave UPS with AVR and a Wide Input Voltage Window
XUPs XUPs
Typical XUPs applications This heavy duty UPS system is ideal for protection of computers, WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key XUPs features• Pure sine wave inverter output• Over/under-voltage protection• Rack or wall mountable with
optional rack/wall-mount kit • Heavy-duty surge protection
and noise filtering• Automatic voltage regulation
with wide voltage input windowenhances long battery life
• Comprehensive array of status bargraphs for voltage,load and battery levels
• SNMP compatible via RS-232port with optional SNMP adapter
• Both RS-232 and relay contact signals are provided
• Two year warranty on electronics• One year warranty on batteries
Pure sine wave Wide input voltage window Voltage regulation
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
138 SpecificationsXUPs-600HV/1000HV
Specification XUPs-600HV XUPs-1000HVElectrical
Capacity in VA (watts) 600VA (420W) 1000VA (700W)
UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter. Input
Nominal voltage 230 volts ac (190–270vac without going to batteries)Input current 2.5A maximum @ 230vac 4.2A maximum @ 230vac
Operating voltage. Freq. 190 to 270vac without using batteries. 47 to 63Hz. Input receptacle/plug IEC320 input receptacle. Line cord with IEC320P plug.
OutputNominal voltage 230 volts ac Voltage regulation 230vac +/-8% upon changes in line or load. Crest ratio 3:1Output waveform Pure sine wave, less than 3% THD with linear load. Power efficiency 97 %, under full load conditions. Power on/off switch Recessed on/off rocker style power switch. Transfer time <4 millisecondsBatteries 7 amp hours, 24vdc maintenance-free sealed lead-acid batteries. Battery backup time 10 minutes @ 420 watts load.
25 minutes @ 210 watts load. 5 minutes @ 700 watts load.
12 minutes @ 350 watts load. Recharge time Four hours to 95% capacity after full discharge.Optional extra battery pack(s) for longer backup time
Matching extra battery pack(s) available with SB50 connector,and separate battery charger for enabling faster recharge times.Please call for sizing assistance.
SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Surge protection Ac input surge/noise filter (using inductor, capacitor and MOV). Status indicators 5 LED load level indicator: 0 to 100% of rated load.
5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload.
Output receptacles Six standard IEC320 female outlets (receptacles). Others, please call. Physical
Dimensions 406mm(16”)wide x 381mm(15”)deep x 89mm(3.5”)high (2U high) Weights 15kg(32 lbs) 17kg(37 lbs)
Housing Painted steel enclosure with rubber feet. Rack or wall mountingkits (optional)
Front pair rack-mount kit: For a 19” rack: # MK-5019A For a 23” rack: #MK-5023A
Center pair rack-mount kit: For a 19” rack: # MK-5019F For a 23” rack: #MK=5023F
Wall or floor mount kit: use # MK-5000C Safety
Agency approvals Designed to meet UL, cUL and IEC safety standards. Environmental
Operating temperature 0o to 40oC (32° to 104°F). 10 to 90% relative humidity(non-condensing).Warranty
Warranty Two year limited warranty, parts and labor. One year battery warranty. TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
XUPs XUPs
Rack-mountableheavy-dutyline-interactive UPS with automaticvoltage regulation
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPs SeriesRack-mountable Uninterruptible Power System
139
XUPs XUPsFront-right view
Rear view
dc circuit breaker output ac via sixIEC320 femaleoutlets (receptacles) (NEMA 5-15R shown)
DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)
input ac IEC 320 male inlet for 6 foot cord with IEC320 female plug(also accepts other cord/plug sets)
input ac circuit breaker
recessed on/off switch
- ac input on LED lit- buck mode- boost mode- overload- inverter on/off- battery failure
output current: threeof five LEDs showingXUPs 60% loaded
battery voltage level:four of five LEDsshowing batteries at80% charge status
dc Anderson SB-50battery connector
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
140 XUPs SeriesXUPs-600HV/1000HV
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi XUPs-600HV-1000HV-2006-10-16.pdf
XUPs XUPs
utilityac
input heavy-dutyac surge
protection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
battery and
charger
hot
relay 2
regulated XUPs output 230vac +/-8%
neutrallogic
-10%
+10%0%
190to270vac
fuse
chassis
relay 1
inverterac
dc
groundchassis
groundearth
XUPs-600HV/1000HV system architecture
XUPs-600HV/1000HV at a glanceRack or wall-mountable heavy-duty UPS with line-interactiveautomatic voltage regulation and wide input voltage window
• 10 minutes @ 420 watts load25 minutes @ 210 watts load with XUPs-600HV
• 5 minutes @ 700 watts load12 minutes @ 350 watts load with XUPs-1000HV
• A built-in Anderson SB50 connector enables adding extra battery packs for longer times
• Less than 4ms transfer time • 24vdc battery bus
• 230vac +/-8% output from 190 to 270vac inputwithout going to batteries
• Six IEC320 female outlets• Microprocessor-controlled
15kHz PWM sine wave inverter• Rack-mountable metal cabinet
allows for rack or wall mounting using optional mounting kits
• SNMP compatible with optional SNMP adapter
Anderson SB50 connector
UPs Flexible SeriesUninterruptible Power System
141
Wide temperature battery Flexibility of adding extra battery cabinets
UPs-400Wtb ~ 400VA, 250W, 120vac, with wide temperature battery
TSi Power's Flexible Series wide temperature battery UPS is an excellent choice for those applications that require battery backup with good surge protection, a wide temperature battery for usage in more extreme environments, and the flexibility of being able to add additional battery cabinets for extended run-time.
Typical applications UPs-400Wtb is the ideal UPS for computer or telecommunications equipment in extreme wide temperature -20o to +60oC(-4o to +140 oF) environments where ac power delivery is unreliable and long battery backup times may be necessary. The UPs-400Wtb is suitable where power outages are a regular occurrence, or in areas where utilities need to conduct rolling blackouts.
Key benefitsThe UPs-400Wtb protects connected equipment from: power supply failure, erroring, system lockups and re-boots. It contributes to enhanced systems operation, greater reliability, improved repeatability, and extended operating life. Typical back-up time fully loaded is 8 minutes, but 20 minutes can be obtained when the unit is loaded to 50% of its capacity. Thus, an application requiring 200VA can be provided with 20 minutes of hold-up. The capability of adding extra EXt-400Wtb external battery packs also makes this a very cost-effective choice for enabling nearly unlimited holdup times. Custom Settings: DIP switches in the rear panel allow the user to set brownout sensitivity, inverter operating frequency, or alarm mode, for complete flexibility and control of the UPS.
UPs model400Wtb
400 VA250 watts120 volts8 min @ 250W20 min@ 125W
Key features• Wide temperature battery
-20o to +60oC (-4o to +140oF)• Add-on battery cabinet flexibility • User-selectable 50/60Hz frequency• Electronics ~ Two year warranty
Batteries ~ One year warranty
How the UPs-400WTB worksThe UPs-400Wtb continually provides surge protection with a capacitive element, and coordinated MOV surge protection. Upon loss of power, the audible alarm beeps about once a second, as the battery inverter kicks in within 8ms, which means equipment will continue to operate without interruption. When the battery level drops until only a few minutes of holdup time remain, the alarm will beep, and the LED will flash more rapidly, alerting of impending shutdown.A DB-9 female connector provides communications capability with monitoring software which can safely save open files and automatically shutdown your systems.
Wide Temperature Battery UPSwith the Flexibility of Adding Extra Battery Cabinets
Flexible
UPs UPs
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
142 SpecificationsUPs-400Wtb
UPs-400Wtb-2006-10-16.pdf
UPs-400Wtb system architecture
UPs-400Wtb with wide temperature battery and add-on battery cabinet flexibility
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
ground surge protection
acinput
hot
fuse
neutral
dc to acinverter
widetemp.
battery and
charger
hot
ground
relay
UPSoutput
neutral
Anderson SB50 external battery connector
Specifications
Specification UPs-400Wtb Electrical
Capacity in VA (watts) 400VA (250 watts)UPS type Single conversion standby with 4 to 8ms transfer time.
Input Nominal voltage 120 volts ac, single phase.
Operating voltage 95 to 135 volts ac. 47 to 63Hz, sinusoidal.Ac input cord 6 foot cord with 5-15P plug
OutputNominal voltage 120 volts ac, single phase, sine wave during normal operation.Nominal frequency 50/60Hz +/-3% (user-selectable)Power efficiency 98% or higher during ac operation,
80% or higher during battery inverter operation.Transfer time 4 to 8ms typical between ac and inverter.UPS inverter output 105 to 130VRMS, 50/60Hz +/-1%,
pulse-width-modulated, modified square wave.Battery backup time(for more time see below)
8 minutes @ full load (250 watts) 20 minutes @ half load (125 watts)
Recharge time 8 hours to return to 90% capacity after full discharge. Optional # EXt-400WtbExtra battery pack for longer back-up timew/Anderson SB50conn.
A matching extra battery cabinet with separate charger, supplying an additional 40 minutes @ full load, 90 minutes @ half load.
With a weight of 15.9kg(35 lbs), and same size as the UPs-400Wtb.EXt-400Wtb’s battery recharge time is 12 hours to 90% capacity.
Surge protection MOV spike/surge suppression. Surge test conditions ANSI/IEEE C62.41-1991 test pulse,
Category A3, ring wave, 6000V, 200A. Indicators and alarms LEDs and audible signals for ac, inverter, and battery status. Communications interface
DB-9 female connector provides communications capability with optional monitoring and automatic shutdown software.
Ac output receptacles Two NEMA 5-15R Physical
Dimensions 125mm(5”)wide x 178mm(7”)high x 394mm(16”)deepWeight 10.7 kg (23.5 lbs)
SafetySafety standards Designed to meet UL and cUL 1778 standards Safety and reliability External fuse protects all ac circuits. Internal fuses protect all dc circuits.
Durable, all-steel chassis withstands transport in hostile environments and operation in any indoor application.
EnvironmentalAmbient temperature -20o to +60oC(-4o to +140oF). 90% relative humidity, non-condensing at 25oC.
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
Flexible
UPs UPs
Rear view
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPs SeriesModular OEM Uninterruptible Power System
143
Typical OEM applications This heavy duty UPS system is ideal for protection of telecommunications systems, WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key XUPs 8022 features• Pure sine wave inverter output• Over/under-voltage protection• Suitable for use in outdoor rated
enclosures with OEM provided wide temperature batteries
• Heavy-duty surge protectionand noise filtering
• Automatic voltage regulationwith wide voltage input windowenhances long battery life
• Comprehensive array of status bargraphs for voltage,load and battery levels
• SNMP compatible via RS-232port with optional SNMP adapter
• RS-232 and relay contact signals• Temperature-compensated battery
charger maximizes battery lifetime• Two year warranty
XUPs-600/1000-8022 ~ 600VA /1000VA, 420W/700W, 115vac, OEM UPS+AVR
XUPs model600-8022
3.6 amps600 VA420 watts115 volts(OEM version, no batteries)
1000-80226 amps1000 VA700 watts115 volts(OEM version, no batteries)
These heavy-duty XUPs Series UPS are housed in a rugged aluminum enclosure and designed for OEMs wanting a modular UPS with wide temperature capabilities and suitable for use in existing OEM outdoor enclosures. The XUPs offers line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.
Key modular XUPs OEM benefitsThe XUPs design, with its microprocessor-controlled 15kHz sine wave inverter, reduces the number of solid-state devices required for power conversion, thereby yielding a high level of reliability. Built-in automatic voltage regulation enables a wide input voltage window within which the XUPs can deliver power without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect the electronics.This OEM system is designed for use with OEM supplied wide temperature batteries and includes a built-in battery charger for a recommended external battery bank size of from 50 to 280 Ah.
How the XUPs worksThe XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, and also overvoltage protection with a threshold of 140vac, and undervoltage protection with a threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other electronic systems.A comprehensive array of power, battery level, voltage level, and inverter status LED indicators is provided for visual assessment of UPS status. A DB-9 port is provided for communication using RS-232 or relay dry contact signals.
Modular OEM Sine Wave UPS with AVR and a Wide Temperature Design
XUPs XUPs Pure sine wave Wide input voltage window Voltage regulation
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
144 SpecificationsXUPs-600/1000-8022
Specification XUPs-600-8022 XUPs-1000-8022Electrical
Capacity in VA (watts) 600VA (420W) 1000VA (700W)
UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter. Input
Nominal voltage 115 volts ac (95 to 140vac without going to batteries)Input circuit breaker 7A maximum @ 115vac 10A maximum @ 115vac
Operating voltage. Freq. 95 to 140vac without using batteries. 47 to 63Hz. Input inlet Male IEC320-C14 inlet.
OutputNominal voltage 115 volts ac Voltage regulation 115vac +/-8% upon changes in line or load. Crest ratio 3:1Output waveform Pure sine wave, less than 3% THD with linear load. Power efficiency 97 %, under full load conditions. Power on/off switch On/off rocker style power switch. Transfer time <4 milliseconds Surge protection Ac input surge/noise filter (using inductor, capacitor and MOV).Designed for wide temperature batteries *batteries not included
Designed for 24 vdc gel-cell wide temperature gel-cell battery bank consisting of multiples of two 12V batteries. e.g. Two 12V batteries in series, or four batteries if two 24V battery banks are paralleled; or six batteries if three 24V battery banks are paralleled. 50 to 280Ah.
Battery charger Temperature compensated battery charger. 27V, 5A.
Temperature compensated battery charger. 27V, 10A.
Recharge time After full discharge, 24V, 30Ah battery will be recharged within 8 hours to 95% capacity, and a 24V, 100Ah battery bank within 24 hours.
Dc breaker 30A 40A
SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Status indicators 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload.
Alarm signals Relay contact signals for: ac good/ ac fail and battery ok/battery low. Low voltage alarm sounds when battery voltage drops below 22vdc, and low voltage disconnect will occur at 21vdc.
Output receptacles Two NEMA 5-15R receptacles/outlets. For HW or other, please call. Physical
Dimensions 300mm(12”)wide x 250mm(10”)deep x 150mm(6”)high Weights 8kg(18 lbs) 13kg(28 lbs)
Housing Aluminum enclosure with rubber feet. Safety
Agency approvals Designed to meet UL, cUL and IEC safety standards. Environmental
Operating temperature -20o to 60oC (-4° to 140°F). 10 to 90% relative humidity(non-condensing).Warranty
Warranty Two year limited warranty, parts and labor. TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
XUPs XUPs
Modular UPS designed for use in outdoor enclosures with OEM supplied wide temperature batteries
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPs SeriesModular OEM Uninterruptible Power System
145
XUPs XUPsfront view
rear view
dc circuit breaker
output ac via twoNEMA 5-15R receptacles
DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)
IEC320-C14 ac inlet *for OEM provided line cord and typical NEMA 5-15P plug
input ac circuit breaker
on/off switch - ac input on LED lit- buck mode- boost mode- overload- inverter on/off- battery failure
output current: threeof five LEDs showingXUPs 60% loaded
battery voltage level:four of five LEDsshowing batteries at80% charge status
shielded hardwire terminals for battery connection
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
146 XUPs SeriesXUPs-600/1000-8022
XUPs-600/1000-8022 at a glanceOEM design heavy-duty wide-temperature UPS with line-interactiveautomatic voltage regulation and wide input voltage window
• Temperature compensated battery charging voltage maximizes battery lifetime
• 115vac +/-8% output from 95 to 140vac inputwithout going to batteries
• Two 5-15R receptacles/outlets• Wide temperature design• Microprocessor-controlled
15kHz PWM sine wave inverter• Less than 4ms transfer time• Rugged aluminum enclosure • SNMP compatible
with optional SNMP adapter
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi XUPs-600-1000-8022-OEM-115V-2006-10-16.pdf
XUPs XUPs
batte
ry c
harg
ing
volta
ge
operating temperature (oC)
29V
28V
27V
26V-20 -10 0 10 20 30 40 50 60
XUPs-600/1000-8022 system architecture utility
acinput heavy-duty
ac surgeprotection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
temperaturecompensated
charger
hot
relay 2
regulated XUPs output 115vac +/-8%
neutrallogic
-10%
+10%0%
95 to 140vac
chassis
relay 1
inverterac
dc
groundchassis
groundearth
external 24 vdcbattery connector
accircuit
breaker
dc circuitbreaker
XUPs SeriesModular OEM Uninterruptible Power System
147
Typical OEM applications This heavy duty UPS system is ideal for protection of telecommunications systems, WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).
Key XUPs 8023 features• Pure sine wave inverter output• Over/under-voltage protection• Suitable for use in outdoor rated
enclosures with OEM provided wide temperature batteries
• Heavy-duty surge protectionand noise filtering
• Automatic voltage regulationwith wide voltage input windowenhances long battery life
• Comprehensive array of status bargraphs for voltage,load and battery levels
• SNMP compatible via RS-232port with optional SNMP adapter
• RS-232 and relay contact signals• Temperature-compensated battery
charger maximizes battery lifetime• Two year warranty
XUPs-600/1000-8023 ~ 600VA /1000VA, 420W/700W, 230vac, OEM UPS+AVR
XUPs model600-8023
1.8 amps600 VA420 watts230 volts(OEM version, no batteries)
1000-80233.0 amps1000 VA700 watts230 volts(OEM version, no batteries)
These heavy-duty XUPs Series UPS are housed in a rugged aluminum enclosure and designed for OEMs wanting a modular UPS with wide temperature capabilities and suitable for use in existing OEM outdoor enclosures. The XUPs offers line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.
Key modular XUPs OEM benefitsThe XUPs design, with its microprocessor-controlled 15kHz sine wave inverter, reduces the number of solid-state devices required for power conversion, thereby yielding a high level of reliability. Built-in automatic voltage regulation enables a wide input voltage window within which the XUPs can deliver power without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect the electronics.This OEM system is designed for use with OEM supplied wide temperature batteries and includes a built-in battery charger for a recommended external battery bank size of from 50 to 280 Ah.
How the XUPs worksThe XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, and also overvoltage protection with a threshold of 280vac, and undervoltage protection with a threshold of 190vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other electronic systems.A comprehensive array of power, battery level, voltage level, and inverter status LED indicators is provided for visual assessment of UPS status. A DB-9 port is provided for communication using RS-232 or relay dry contact signals.
Modular OEM Sine Wave UPS with AVR and a Wide Temperature Design
XUPs XUPs Pure sine wave Wide input voltage window Voltage regulation
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
148 SpecificationsXUPs-600/1000-8023
Specification XUPs-600-8023 XUPs-1000-8023Electrical
Capacity in VA (watts) 600VA (420W) 1000VA (700W)
UPS topology High efficiency line-interactive with 15kHz PWM sine wave inverter. Input
Nominal voltage 230 volts ac (190 to 280vac without going to batteries)Input circuit breaker 4A maximum @ 230vac 5A maximum @ 230vac
Operating voltage. Freq. 190 to 280vac without using batteries. 47 to 63Hz. Input inlet Male IEC320-C14 inlet.
OutputNominal voltage 230 volts ac Voltage regulation 230vac +/-8% upon changes in line or load. Crest ratio 3:1Output waveform Pure sine wave, less than 3% THD with linear load. Power efficiency 97 %, under full load conditions. Power on/off switch On/off rocker style power switch. Transfer time <4 millisecondsSurge protection Ac input surge/noise filter (using inductor, capacitor and MOV).Designed for wide temperature batteries *batteries not included
Designed for 24 vdc gel-cell wide temperature gel-cell battery bank consisting of multiples of two 12V batteries. e.g. Two 12V batteries in series, or four batteries if two 24V battery banks are paralleled; or six batteries if three 48V battery banks are paralleled. 50 to 280Ah.
Battery charger Temperature compensated battery charger. 27V, 5A.
Temperature compensated battery charger. 27V, 10A.
Recharge time After full discharge, 24V, 30Ah battery will be recharged within 8 hours to 95% capacity, and a 24V, 100Ah battery bank within 24 hours.
Dc breaker 30A 40A
SNMP interface for UPS monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
Status indicators 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload.
Alarm Signals Relay contact signals for: ac good/ ac fail and battery ok/battery low. Low voltage alarm sounds when battery voltage drops below 22vdc, and low voltage disconnect will occur at 21vdc.
Output receptacles Two standard IEC320-C13 female outlets. For HW/other, please call. Physical
Dimensions 300mm(12”)wide x 250mm(10”)deep x 150mm(6”)high Weights 8kg(18 lbs) 13kg(28 lbs)
Housing Aluminum enclosure with rubber feet. Safety
Agency approvals Designed to meet UL, cUL and IEC safety standards. Environmental
Operating temperature -20o to 60oC (-4° to 140°F). 10 to 90% relative humidity(non-condensing).Warranty
Warranty Two year limited warranty, parts and labor. TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
XUPs XUPs
Modular UPS designed for use in outdoor enclosures with OEM supplied wide temperature batteries
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XUPs SeriesModular OEM Uninterruptible Power System
149
XUPs XUPsfront view
rear view
dc circuit breaker
output ac via twostandard IEC320-C13 female outlets
DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)
IEC320-C14 ac inlet *for OEM provided line cord and plug
input ac circuit breaker
on/off switch - ac input on LED lit- buck mode- boost mode- overload- inverter on/off- battery failure
output current: threeof five LEDs showingXUPs 60% loaded
battery voltage level:four of five LEDsshowing batteries at80% charge status
shielded hardwire terminals for battery connection
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
150 XUPs SeriesXUPs-600/1000-8023
XUPs-600/1000-8023 at a glanceOEM design heavy-duty wide-temperature UPS with line-interactiveautomatic voltage regulation and wide input voltage window
• Temperature compensated battery charging voltage maximizes battery lifetime
• 230vac +/-8% output from 190 to 280vac inputwithout going to batteries
• Two IEC320-C13 female outlets• Wide temperature design• Microprocessor-controlled
15kHz PWM sine wave inverter• Less than 4ms transfer time• Rugged aluminum enclosure • SNMP compatible
with optional SNMP adapter
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi XUPs-600-1000-8023-OEM-230V-2006-10-16.pdf
XUPs XUPs
batte
ry c
harg
ing
volta
ge
operating temperature (oC)
29V
28V
27V
26V-20 -10 0 10 20 30 40 50 60
XUPs-600/1000-8023 system architecture utility
acinput heavy-duty
ac surgeprotection, noise filter
andovervoltage,undervoltagedisconnect
circuits
hot
neutral
temperaturecompensated
charger
hot
relay 2
regulated XUPs output 230vac +/-8%
neutrallogic
-10%
+10%0%
190 to 280vac
chassis
relay 1
inverterac
dc
groundchassis
groundearth
external 24 vdcbattery connector
accircuit
breaker
dc circuitbreaker
UPs Flexible SeriesUninterruptible Power System
151
UPs-600 ~ 600VA, 400W, 120vac
ModelUPs-600
600 VA400 watts120 volts8 min @ 400W 20 min@ 200W
TSi Power's Flexible Series UPS is an excellent choice for those applications that require battery backup with good surge protection, And the flexibility of being able to add additional battery cabinets for extended run-time.
Typical applications UPs-600 is the ideal UPS for computer or telecommunications equipment in environments where ac power delivery is unreliable and several hours of backup time are necessary.
Key benefitsThe UPs-600 protects connected equipment from power supply failure, erroring, system lockups and re-boots. It contributes to enhanced systems operation, greater reliability, improved repeatability, and extended operating life. Typical back-up time fully loaded is 8 minutes, but 20 minutes can be obtained when the unit is loaded to 50% of its capacity. Thus, an application requiring 300VA can be provided with 20 minutes of hold-up. The capability of adding extra EXt-400 external battery packs also makes this a very cost-effective choice for enabling nearly unlimited battery backup times. Custom settings: DIP switches in the rear panel allow the user to set brownout sensitivity, inverter operating frequency, or alarm mode, for complete flexibility and control of the UPS.
How the UPs-600 worksThe UPs-600 continually provides power protection with a capacitive element and a fast-acting MOV (metal oxide varistor).Upon loss of power, the audible alarm beeps as the unit transfers to the battery inverter in less than 8ms. When the battery level drops until only a few minutes of holdup time remain, the alarm will beep, and the LED will flash more rapidly, alerting of impending shutdown.A DB-9 connector provides communications with monitoring software which can safely save open files and automatically shut down your systems.
Key features of the UPs-600• Add-on battery cabinet flexibility • Surge protection is included• DB-9 female connector provides
communications capability with optional monitoring and automatic shutdown software
• Customizable brownout sensitivity• User-selectable 50 or 60Hz • 2 year warranty on electronic parts
1 year warranty on batteries
Basic UPS plus theFlexibility of Adding Extra Battery Cabinets
Flexible
UPs UPs Wide temperature battery Flexibility of adding extra battery cabinets
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
152 SpecificationsUPs-600
UPs-600-2006-10-16.pdf
TSi’s ongoing product improvement process makes these specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
ground surge protection
acinput
hot
fuse
neutral
dc to acinverter
widetemp.
battery and
charger
hot
ground
relay
UPsoutput
neutral
Anderson SB50 externalbattery connector
UPs-600 system architecture
Specifications
Specification UPs-600Electrical
Capacity in VA (watts) 600VA (400 watts)UPS type Single conversion standby with 4-8ms transfer time.
Input Nominal voltage 120 volts ac single phase
Operating voltage 95 to 135 volts ac. 47 to 63Hz, sinusoidalAc input cord 6 foot long ac cord with 5-15P plug
OutputNominal voltage 120 volts ac, single phase, sine wave during normal operation.Nominal frequency 50/60Hz +/-3% (user-selectable)Power efficiency 98% or higher during ac operation, 80% or higher/battery inverter oper. Transfer time 4 to 8ms typical between ac and inverter.Inverter output 105 to 130 vacRMS. 50/60 Hz+/-1%
Pulse-width-modulated, modified square wave. Battery backup time(for more time see below)
8 minutes @ full load (400 watts)20 minutes @ 1/2 load (200 watts)
Recharge time 8 hours to return to 90% capacity after full discharge.Optional # EXt-400extra battery pack for longer backup timew/Anderson SB50 conn
A matching extra battery cabinet with separate charger, supplying an additional 45 minutes @ full load, 110 minutes @ half load.
With a weight of 35 lbs (15.9kg), and same size as the UPs-600.EXt-400’s battery recharge time is 12 hours to 90% capacity.
Surge protection MOV spike/surge suppression. Surge test conditions ANSI/IEEE C62.41-1991 test pulse,
Category A3 ring wave, 6000V, 200A.Indicators and alarms LED indicators and audible signals for ac, inverter, and battery status. Communicationsinterface
DB-9 female connector provides communications capability with optional monitoring and automatic shutdown software.
Ac output receptacles Two (NEMA 5-15R)Physical
Dimensions 125mm(5”)wide x 178mm(7”)high x 394mm(16”)deepWeight 9.1 kg(22 lbs)Enclosure Durable, all-steel chassis designed for indoor applications.
SafetySafety standards Designed to meet UL and cUL 1778 standardsSafety and reliability External fuse protects all ac circuits. Internal fuses protect all dc circuits.
EnvironmentalAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing).
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
UPs-600 with add-on battery cabinet flexibility
Rear view
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
UPs Premium SeriesUninterruptible Power System
153
UPs-10000/16000/21000 ~ 1 /1.6/2.1kVA, 750/1000/1500W, 120vac
UPs UPs
TSi Power’s Premium Series UPS are constructed with a rugged, ferroresonant no-break design and a fully isolated sinewave output with neutral-to-ground bond. This series offers the best surge protection available, with excellent noise filtering, remote on/off control, and optional extended battery back-up.
Key benefitsThis rugged industrial-strength ferroresonant design reduces the number of solid-state devices required for power conversion and is suitable for use in severe environments. All models can be rack-mounted in 19, 23, or 24" racks. Standard battery run-time is about 30 minutes under typical 50% load. If additional battery runtime is required, EXt-8000 Battery Extension Units can be daisy-chained to the UPS unit to provide hours of battery runtime.
How the Premium Series worksThe constant output isolation transformer provides 100% isolation from the input ac line. The regulated output protects switchmode power supplies from failure caused by unstable ac mains. The secondary neutral is bonded to ground, thus eliminating all surge voltages between neutral and ground. This type of surge protection is superior to all other technologies and is further enhanced thanks to the built-in low-pass filter, which takes the edge off even very fast transients. UPS status is monitored by LED indicators, LED bargraph displays and audible signals for ac status, inverter status, output voltage, load, and battery status. Alarm interface: Upon loss of power, the audible alarm will beep. Because the Premium Series is a continuous sinewave ‘No-break’ UPS system, power to equipment loads will be completely unaffected. As the battery level drops until only a few minutes of holdup time remains, the audible alarm will change, warning of impending shutdown.Communications: A DB-9 female connector in the rear panel provides communications capability with most network operating systems such as Novell, Unix, Solaris, Windows, Linux, etc. Optional monitoring software may be needed for some operating systems.
ModelsUPs-10000
1000 VA750 watts120 vac10 min@ 750W 30 min@375W
UPs-16000 1600 VA1200 watts120 vac10min@1200W30 min@ 600W
UPs-210002100 VA1500 watts120 vac10min@1500W30 min@ 750W
Pure sine wave Ferroresonant voltage regulation Transformer isolated
Typical applications These heavy-duty UPS are ideal for backing up critical servers, routers, hubs, networks, factory/industrial process controls, systems going to export markets, critical telecom equipment, ISP’s and other areas where reliability is a must, extended back-up might be necessary, or the power source is unpredictable.
Key features of the TSi PowerPremium Series UPS
• Pure sine wave output• No-break UPS• Best surge protection available• Voltage regulation and
integral isolation transformer• Reduces harmonics from
Non-linear loads • Extended back-up modules
available • Rack-mount kits available• Remote shutdown, auto-restart
and alarm interface• Comprehensive array of
status bargraphs for voltage,load and battery levels
• Network compatible • Two year warranty on
electronic parts• One year warranty on batteries
Heavy-duty UPS with Ferroresonant Isolation Transformer Voltage Regulation
Premium
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
154 SpecificationsUPs-10000/16000/21000
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
UPs-16000/ 21000
Specification UPs-10000 UPs-16000 UPs-21000Electrical
Capacity in VA (watts) 1000VA (750watts) 1600VA (1200watts) 2100VA (1500 watts) Transformer type Ferroresonant constant voltage output isolation transformer. Isolation 100% input/output isolation & output neutral-ground bonding qualifies the
UPS output as a “separately derived ac power source” via NEC 250-5D. Input
Nominal voltage 120 volts acOperating voltage 90 to 140 volts ac without using batteries Nominal frequency 60Hz sinusoidal +/- 5% Ac input cord 6 foot line cord, 2.5mm2 (14AWG) SJT with NEMA 5-15P plug
OutputNominal voltage 120volts +/-3 vac Voltage regulation +/-3% upon changes in line or load Crest ratio 3 : 1 Output waveform Pure sine wave, less than 3% THD with linear load Power efficiency 90%, under full load conditions Power on/off switch On/off rocker style power switch Transfer time Zero (continuous no-break) Batteries Maintenance-free sealed lead-acid batteries Battery backup time 10 - 15 minutes of backup time @ full load (30min. under typical 1/2 load) Recharge time 8 hours to return to 90% capacity after full discharge.Optional # EXt-8000extra battery pack for longer backup timew/Anderson SB50 conn
A matching extra battery cabinet with separate charger, supplying an additional 35 to 45 minutes backup time (details - see EXt specs).
Weight is 70 lbs (32kg), size is the same as the UPs-10000.EXt-8000’s battery recharge time is 8 hours to 90% capacity.
Noise filtering Low-pass filter reduces noise over a wide frequency range.Surge protection A three-stage surge protection system consisting of
ferroresonant isolation transformer, capacitor and M.O.V. is included. Surge test conditions ANSI/IEEE C62.41-1991 test pulse. Category B3,
Combination wave, 6000volts, 3000amps.Surge let-throughvoltages
Test pulse injection: Line-Neutral, Line-Ground and Neutral-Ground. Combination wave: L-N: 35V, L-G: 35V, N-G: 0.5V
Indicators ‘10 LED’ bar-graph indicators: output voltage, battery voltage, and show the output load from 0 to 100% of rated power.
4 status LED’s indicating - ac power present; inverter status; output mode; ac load, and battery status.
Ac receptacles Four NEMA 5-15R Six NEMA 5-15R Six NEMA 5-15RPhysical
Dimensions 431.8x533.4x127mm(17”Wx21”Dx5”H)
431.8x533.4x165mm(17”Wx21”Dx6.5”H)
431.8x533.4x165mm(17”Wx21”Dx6.5”H)
Weight 31.8 kg(70 lbs) 49.9 kg(110 lbs) 59 kg(130 lbs)Rack mount options Please call for factory assistance on rack-mount kit options. Steel housing Durable, all-steel chassis withstands transport in hostile
environments and operation in any indoor application.Safety
Agency approvals Designed to meet UL, cUL and IEC safety standards. FET inverter circuit FET inverter circuit ensures efficiency and reliability.
EnvironmentalAmbient temperature 0° to 40°C (32° to 104°F). 10 to 90% relative humidity(non-condensing). Cooling method Forced air (fan cooled).
WarrantyWarranty Two year limited warranty, parts and labor. One year battery warranty.
Rear viewUPs-10000
UPs-10000
Specifications
Heavy-duty UPS with ferroresonantvoltage regulatingisolation transformerand add-on batterycabinet flexibility
UPs UPsPremium
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
UPs Premium SeriesUninterruptible Power System
155
UPs-10000-16000-21000-2006-10-16.pdf
acInput 3- way MOV
surge protection
hot
ground
neutral
EMI / RFInoise filter
fuse
solid-staterelay
inverter
batterycharger
ferroresonanttransformer
resonantcapacitor
neutral
hot
ground
fuse
+48vdc
logic ground
batte
ry
to optionalEXt-8000
extra batterycabinet
viaAnderson
SB-50 connector
UPSoutput
UPs Premium Series system architecture
UPS-16000/ 21000
• 48vdc battery bus• Anderson SB50 battery connector:
for optional single/multiple extra battery cabinets, or external 48vdc battery bank
• 1000VA / 750 watts rating1600VA / 1200 watts rating2100VA / 1500 watts rating
UPS-10000Heavy-duty UPS with ferroresonantvoltage regulatingisolation transformerand add-on batterycabinet flexibility
UPs UPsPremium
• ‘No-break’ zero transfer time
• Ferroresonant constantvoltage-regulating isolation transformer
• Rack-mountableTSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
156 UPs Premium SeriesUninterruptible Power System
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
UPs SeriesUPs Shutdown Instructions for Windows XP
157
Please Note: These instructions are for configuring Windows XP Profor TSi Power UPS. Other software may require different instructions, but the Power Fail, Low-Battery and UPS Shutdown signal polarities being positive will remain the same.
XUPs and UPs Automatic Shutdown Instructions for Windows XP Professional
ConfiguringWindows XP For TSi UPs
Windows XP Professional now has UPS based computer system automatic shutdown built-in.
Preparing for UPS configurationBefore you start the configuration in Windows XP, make sure your UPS communication cable is properly plugged into a COM port on your computer. To help prevent any possible damage, do this while both the computer and UPS are turned off, and both units have their plugs inserted into properly grounded outlets.
Setting up UPS power options1. Click Windows- Start > Control Panel
> Power Options, then the UPS tab.
2. Then, click on the Select button. This will open up the UPS selection dialog box.
3. Under Select Manufacturer, click on the drop-down menu button, and click on Generic.
4. Under Select model, click on Custom.
5. Check that the Default Port Setting is correct (probably COM 1). If your UPS is plugged into a different port, change it accordingly.
6. Click on the Next button.
UPs interface configuration7. Checkmark all three boxes for:
Power Fail/On Battery, Low Battery, and UPS Shutdown.
8. Select Positive polarity for all three.9. Then, click on the Finish button.
This will then open up the Power Options Properties dialog box again.
Instructions for Configuring System Auto-Shutdown in Windows XP Professional®
Auto-shutdown UPS signal polarities Hibernation
UPs UPsAutomaticShutdown
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
158 UPs SeriesUPs Shutdown Instructions for Windows XP
UPs-Shutdown-Instructions-Win-XP-2006-10-16.pdf
Defining UPS power options10. Click on the Hibernation tab.
11. Checkmark Enable hibernation if you want the system to be able to save your open files and conduct an orderly shut-down after a certain amount of time. Except for certain unusual situations, this is usually the preferred choice.
12. Next, click on the UPS tab again. Then,click on the Configure button.
Setting up your UPS configuration13. Now, set up the UPS Configuration.
14. Checkmark the Enable all notifica-tions box, and set for 30 seconds, or other time, depending on your needs. Generally, electric utilities have auto-matic “reclosure” operations which attempt to restore power up to 3 times, each time taking about 10 seconds. If power hasn’t been restored after 30 seconds, you usually are in a “hard down” situation, and most likely will be out of power for at least 30 minutes.
15. In the Critical alarm area, checkmark the Minutes on battery before critical alarm. To preserve battery life, once you are past 30 seconds during an outage, it is usually advisable to start hibernation/shutdown, or shutdown, as soon as possible. Two minutes is the fastest setting.
16. Checkmark the Finally turn off the UPS. With this checked, the system will then automatically turn off the UPS, and it will automatically come back up when the AC power is restored.
17. Click on the Okay button.This will return the Power Options Prop-erties dialog box with UPS tab.
18. Click on either OK or Apply to finish.19. Save any files you may have open.20. Open some test files.21. Test the system with some outages a
few times to ensure correct operation.Note: Use a circuit breaker or some other safe means to simulate the outages. Do not just unplug the UPS, as doing so disconnects the safety ground.
UPs UPsAutomaticShutdown
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
VRp Series - IndoorPrecision Automatic Voltage Regulators
159
VRp SeriesPrecision Automatic Voltage Regulators
VRp Series ~ Precision PWM Automatic Voltage Regulators
VRp VRp
Note: For Outdoor VRp/VRp-ILc units please see Outdoor Series section
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
160 VRp Series - IndoorPrecision Automatic Voltage Regulators
VRp-Series-2006-10-16.pdf
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
ILc-VRp SeriesIsolation Transformer Line Conditioner + Precision Voltage Regulator
161
Dual RangeILc-VRp
International Precision voltage regulator Isolation transformer
ILc-VRp
ILc-2000-VRp-Dual-Range ~ 2kVA, 1.8kW, 120+240vac
Continuous fast and no-break PWM voltage regulationThe ILc-VRp dual range automatic precision voltage regulator with built-in low-impedance isolation transformer allows trouble-free operation of electronic equipment over a very wide ac voltage range of 120 or 240vac +/-20% found in many developing countries. Output regulation responds in less than one line cycle and corrects output voltage to +/-2.5% with 20,000 corrections per second. There is no switching of taps or otherwise a break in the power path as continuous PWM (pulse-width-modulation) switching of the primary windingof a buck-boost transformer leaves the secondary power path intact.
Key features of the ILc-VRp Series dual range isolation line conditioner with precision PWM automatic voltage regulation
• Dual voltage input enables use with either 120vac or 240vac power
• Dual voltage output enables 115vac via two NEMA 5-15R receptacles, and/or 230vac via one BS1362 socket
• Outstanding voltage regulationunder normal input range of: +/- 20% of 120 or 240vac, output voltage will be a precision 115 or 230vac +/-2.5% (47~ 63Hz)
• No switching of power path and unit always starts up on sine wave zero crossing, reducing inrush currents
• Failsafe: automatic bypass • Coordinated surge protection
per IEC61312• Common-mode noise elimination• Advanced noise and interference
filter reduces dV/dt from 6kV/µS to less than 10V/µS
• Lightweight design• Two year warranty
Typical ILc-VRp applications Designed for applications where absolutely safe and precisely regulated ac power is required, such as mobile telecommunications, wireless, satellite and carrier equipment.
Isolation Line Conditioner with Precision PWM Automatic Voltage Regulation and 120vac or 240vac Input Capability
Dual Range
Power with a Precision Attitude™
ILc-VRp modelILc-2000-VRp-Dual Range
2000VA2000 watts input:120 or 240vacoutput:115 &/or 230vac
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
162 ILc-VRp SeriesILc-2000-VRp-Dual Range
Key ILc-2000-VRp-Dual Range system benefitsThe lightweight, high efficiency dual voltage range ILc-VRp is easy to install in indoor environments. The unit comes in a rack-mountable enclosure and has the ability to accept either 120vac or 240vac +/-20% input via either a IEC320 C-20 input connector for the 120vac, or an IEC320C-13 inlet connector for the 240vac. Power output is up to 1800watts, and can be drawn from Either/or Both 115vac and 230vac +/-2.5%, as long as total output power is not exceeded.115vac and 230vac outputs are provided via two standard NEMA 5-15R receptacles for the 115vac, and one UK BS1363 outlet connector for the 230vac.The automatic bypass assures that connected equipment will not shut down, even if the ILc-VRp unit were to fail. The ILc-VRp is compatible with all loads as it does not switch any components in the power path. ILc-VRp’s ultra-low impedance assures stability even with the most demanding loads.The isolation line conditioner components provide maximum equipment protection against surges, spikes and transients, for higher equipment reliability and maximum equipment operating life. In addition, improved repeatability, fewer reboots or system lock-ups. Also, a reduction in equipment down time and service costs can be expected.Maximum transformer and regulator performance, reliability and lifetime is achieved by a design with no moving mechanical parts other than a thermostatically controlled high reliability cooling fan to control the unit’s internal temperature.
How the ILc-VRp 2000VA Dual Range system worksThe ILc-VRp unit is comprised of an automatic precision voltage regulator, and an isolation line conditioner. Unit has a front panel key switch to select either 120vac or 240vac, with a safety interlock to prevent voltage from appearing on unused terminals. The high frequency IGBT driven converter microprocessor takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve precisely regulated 230 or 120vac output, cycle by cycle. Voltage correction times do not exceed 1 cycle, or 20 milliseconds for all mains ac voltage changes, even for instantaneous voltage changes from 96 to 144vac (when at the 120vac input setting) or from 192 to 288vac (when at the 240vac input setting). The ILc-VRp starts on sine wave zero voltage crossing point upon turn-on. This reduces potentially damaging inrush currents into difficult loads.The automatic bypass will be activated when there is a fault condition, and makes operation possible without regulation. Three LEDs display unit status, the Green LED indicates Normal (regulating protected mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition. (If Green LED is off, it means internal circuit board needs replacement).A low-impedance isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground. The leakage inductance of the isolation transformers, in combination with capacitive elements and MOVs, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.
Dual voltage range isolation transformer with precision PWM automatic voltage regulator
Dual RangeILc-VRpILc-VRpDual Range
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
SpecificationsIsolation Transformer Line Conditioner + Precision Voltage Regulator
163
Specification ILc-2000-VRp-Dual RangeElectrical
Capacity in VA (watts) 2kVA (2kW)Transformer type Isolation transformer with key-switched taps for dual range capability. Regulator engine High frequency 20kHz IGBT driven voltage regulation converter.
Pulse-width-modulated (PWM) ac to dc converter and dc to ac topology. Input
Nominal voltage 120 or 240 volts ac (User selectable via key switch with safety interlock to prevent voltage from appearing on the unused terminals).
Normal operating range 120 or 240vac +/-20%.Short duration (less than 5 minutes) operation +/-30%.
Nominal frequency 47 to 63Hz Input circuit breaker Input circuit breaker (150% overload capability for heavy start load).Circuit breaker rating 20 amps@120vac or 10 amps@240vac. Input 120vac IEC320C-20 inlet. 240vac IEC320C-13 inlet.
OutputNominal voltage 115vac and/or 230vac Power efficiency Better than 96%Voltage regulation 115vac+/-2.5%, or 230vac+/-2.5% Automatic bypass Automatic bypass will be activated when there is a fault condition. Safe start Unit starts on sine wave zero voltage crossing point upon turn-on.
Unit is fully functional/regulated within 5 seconds of mains restoration. System status indicators (per phase)
System status LED’s provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (non-regulated output); Red LED indicates Overload (system may shut down).
Surge protection A three-stage surge protection system consisting of isolation transformer, capacitor and MOV is included.
Surge test conditions Class 2 & Class 3 simulated lightning surge (Combination wave) per ANSI/IEEE C62.41-1991, Cat. C test waveform: 6kV, 3kA, 8x20µS
Surge let-throughvoltages (system will continue to operate without interruption under these conditions)
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5VRing wave: L-N: 20V, L-G: 20V, N-G: 0.5VCombination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt) of the remnant waveformis less than 10V/µS with input test waveform dV/dt of 6kV/µS.
Common mode filtering Neutral-ground bond eliminates all noise or voltage on neutral (< 0.5V) Normal mode filtering A built-in inductor-capacitor filter attenuates EMI/RFI noise from output. Output receptacles Two NEMA 5-15R 120vac, and One UK BS1363 230vac socket.
PhysicalDimensions 436mm(17.2”)wide x 127mm(5”)high x 381mm(15”) deep Weight 22.7 kg(50 lbs)Rack-mountng (optional) For 19” Front mounting: MK-8019A. For 19” Rear mounting: MK-8019B.
SafetyStandards Design ready to meet UL, CUL and EMC standards.
EnvironmentalAmbient temperature -5o to +35oC(23o to 95oF)Cooling method Fan cooled.
WarrantyWarranty Two year limited warranty, parts and labor.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Dual voltage range isolation transformer with precision PWM automatic voltage regulator
Dual RangeILc-VRpILc-VRpDual Range
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
164 ILc-VRp SeriesILc-2000-VRp-Dual Range
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi ILc-2000-VRp-Dual-Range-2006-10-16.pdf
• Dual voltage range input: 120vac Or 240vac• Dual voltage range output: 115vac And/Or 230vac • Precision PWM automatic voltage regulator
with low-impedance isolation transformer
ground
circuit breaker
neutral
line
buck-boosttransformer
L
N
microprocessorcontrol
115vac and/or 230vac +/-2.5%
ILc-VRpac outputautomatic bypass
surge prot.and
noisefilter
dualrange
ac Input
120or240vac+/-20%
isolation transformer
ILc-2000-VRp-Dual Range system architecture
noisefilter
dcac
ground ground
Dual RangeILc-VRpILc-VRpDual Range
Power with a Precision Attitude™
VRp SeriesPrecision Automatic Voltage Regulator
165
VRp-3000/5000-120V ~ 3/5kVA, 3/5kW, 40/70A, 120vac
VRp model3000-120V
3 kVA3 kW120 volts
5000-120V5 kVA5 kW120 volts
Failsafe Automatic voltage regulator With precision
Key features • Outstanding voltage regulation.
under normal input range of: 95 to 145V (47 to 63Hz), output regulation will be: 120V+/ -3%.
• No switching of the power path• Fast regulation• Failsafe automatic bypass• Low impedance• Low weight• Quiet operation• Two year warranty
Precision PWM Automatic Voltage Regulator with Automatic Bypass
VRp VRp
Power with a Precision Attitude™
Precision fast-PWMac mains voltage correctionTSi Power’s VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies between 95 to 145vac. There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.
Typical applications Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: analytical equipment, radio and TV broadcast equipment, mobile broadcast vans, industrial controllers (PLC), milking machines, lithographic equipment, recording studio equipment and electrolysis equipment.
Key benefitsThe low weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRp’s ultra-low impedance assures stability even with the most demanding loads.
How the VRp Series worksThe high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve the nominal output voltage +/-3%. The automatic bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition.
(VRp-7500 shown)
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
166 SpecificationsVRp-3000/5000-120V
VRp-3000-5000-120V-2006-10-16.pdf
TSi Power’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Specification VRp-3000-120V VRp-5000-120VElectrical
Capacity in VA (watts) 3 kVA (3000W) 5 kVA (5000W) Regulator engine High frequency 20kHz IGBT driven voltage regulation converter
Input Nominal voltage 120 volts ac single phase
Operating voltage 95 to 145 volts ac Nominal frequency 47 to 63 Hz Overcurrent protection Single pole circuit breaker Circuit breaker rating 1 x 40 amps 1 x 70 amps
Input wire size 10mm2 (AWG 8) 15mm2 (AWG 6)Output
Nominal voltage 120 volts ac, single phase Power efficiency 96% (typical)Voltage regulation Combined 3% maximum under 0 to 100% load and input of 95 to 45V. Automatic bypass Automatic bypass will be activated when there is a fault condition. Status indicators System status LED’s provided as follows:
Green LED indicates Normal (regulating mode operation); Yellow LED indicates Bypass (non-regulated output);
Red LED indicates Fault.Surge test conditions Per ANSI/IEEE C62.41-1991 6kV normal-mode injection Surge let-throughvoltages
Category A3, Ring wave, 200A: L-N: 30VCat. B3, Combination wave, 3000A: L-N: 200V
Note: Unit should be installed as close as possible (within 30’) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neu-tral and ground. A separate isolation transformer is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond.
Ac output connection Hardwired output terminals (hot, neutral and ground) are standard. Optional input cord and output receptacles are available.
PhysicalDimensions 270mm(10.6”)wide x 159mm(6.25”)high x 368mm(14.5”)deepWeight 18.2kg(40 lbs) 22.7kg(50 lbs)Wall/Floor mounting kit MK-5019C (optional)
SafetyAgency approvals Designed to meet UL1950 and cUL1950 standards.
EnvironmentalAmbient temperature 0o to +40oC(32o to +104oF). 10 to 90% RH non-condensing.
WarrantyWarranty Two year limited depot warranty, parts and labor.
Precisionautomaticvoltage regulator
VRp VRp
ground noisefilter
acinput
hot single pole
circuit breaker
neutralL2
ground
L1
buck-boosttransformer
surge protection
andnoisefilter
L1
L2
micro-processor
control
95 to 145V
acdc
120 V+/- 3%
acoutput
automatic bypass
VRp system architecture
hot
neutral
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
VRp SeriesPrecision Automatic Voltage Regulator
167
VRp-3000/5500-0230 ~ 3/5.5kVA, 3/5.5kW, 208/220/230/240vac
Precision fast-PWM ac mains voltage correctionTSi Power’s VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies between 184 to 264vac. There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.
Typical applications Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: analytical equipment, radio and TV broadcast equipment, mobile broadcast vans, industrial controllers (PLC), milking machines, lithographic equipment, recording studio equipment and electrolysis equipment.
Key benefitsThe low-weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRp’s ultra-low impedance assures stability even with the most demanding loads.
How the VRp Series worksThe high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve the nominal output voltage +/-3%. The automatic bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), yellow LED indicates Bypass (non-regulated output), and the red LED indicates a Fault condition.
VRp model3000-0230
3 kVA3 kW208/220/230/240 volts
5500-02305.5 kVA5.5 kW208/220/230/240 volts
Failsafe Automatic voltage regulator With precision
Key features of the VRp Series• Outstanding voltage regulation:
under normal input range of 184 to 264V (47 to 63Hz), output regulation will be 208/220/230 or 240V+/ -3%.
• Failsafe: no switching of power path
• Fast regulation• Automatic bypass• Low- impedance• Low weight• Quiet operation• 2 Year warranty
Precision PWM Automatic Voltage Regulator with Automatic Bypass
VRp VRp
Power with a Precision Attitude™
(VRp-7500 shown)
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
168 SpecificationsVRp-3000/5500-0230
VRp-3000-5500-230V-2006-10-16.pdf
Precisionautomaticvoltage regulator
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
VRp VRp
ground noisefilter
acinput
two polecircuit
breaker
L2ground
L1
buck-boosttransformer
surge protection
andnoisefilter
L1
L2
micro-processor
control
184 to 264V ac
dc
208, 220, 230,240 V
+/- 3%ac
output
automatic bypass
VRp system architecture
Specification VRp-3000-0230 VRp-5500-0230Electrical
Capacity in VA (watts) 3 kVA (3000W) 5.5 kVA (5500W) Regulator engine High frequency 20kHz IGBT driven voltage regulation converter
Input Nominal voltage 208/220/230 or 240 volts ac, single phase
Operating voltage 184 to 264 volts ac Nominal frequency 47 to 63Hz Over-current protection Circuit breaker Circuit breaker rating 2 x 20 amps 2 x 40 amps
Input wire size 6mm2 (AWG 10) 10mm2 (AWG 8)Output
Nominal voltage 208/220/230 or 240 volts ac, single phase Power efficiency 96% (typical)Voltage regulation Combined 3% maximum under 0 to 100% load and input of 184 to 264V Automatic bypass Automatic bypass will be activated when there is a fault condition. Status indicators System status LEDs provided as follows: Green LED indicates Normal
(regulating mode operation); Yellow LED indicates Bypass (non-regulated output); Red LED indicates Fault.
Surge test conditions Per ANSI/IEEE C62.41-1991 6kV normal-mode injection. Surge let-throughvoltages
Category A3, Ring wave, 200A: L-N: 30VCat. B3, Combination wave, 3000A: L-N: 200VNote: Unit should be installed as close as possible (within 30’) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond.
Ac output connection Hardwired output terminals (L1, L2, and ground) are standard. Optional ac socket option is available(for slight extra charge).
PhysicalDimensions 270mm(10.6”)wide x 159mm(6.25”)high x 368mm(14.5”)deepWeight 18.2kg(40 lbs) 22.7kg(50 lbs)Wall/Floor mounting kit MK-5019C (optional)
SafetyAgency approvals Designed to meet UL1950 and cUL1950 standards.
EnvironmentalAmbient temperature 0o to +40oC(32o to +104oF). 10 to 90% RH non-condensing.
WarrantyWarranty Two year limited depot warranty, parts and labor.
Specifications
(VRp-7500 shown)
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
VRp SeriesPrecision Automatic Voltage Regulator
169
VRp-3500-0233 ~ 3.5kVA, 3.5kW, 208/220/230/240vac
Precision fast-PWM ac mains voltage correctionTSi Power’s VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies plus/minus 20%. There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.
Typical applications Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: MacDermid Colorspan® high-performance color wide format digital Inkjet printers, and copiers, analytical equipment, radio/TV broadcast equipment, and mobile broadcast vans, and other 230vac loads that are 3500VA or under.
Key VRp-3500-0233 benefitsThe light-weight, high efficiency VRp-3500-0233 is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRp’s ultra-low impedance assures stability even with the most demanding loads.
How the VRp Series worksThe high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve the nominal output voltage +/-3%. The Automatic Bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), and the Red LED indicates a Fault condition.
VRp model3500-0233
3500 VA3500 wattsinput: 208/220/ 230/240vacoutput: 230vac +/-3%
Failsafe Automatic voltage Regulator With precision
Key features of the VRp Series• Outstanding voltage regulation:
under normal input range of nominal 184 to 276vac, output regulation will be 230vac+/ -3%
• Failsafe: no switching of the power path
• Fast regulation• Automatic bypass• Low-impedance• Low weight• Quiet operation• Two year warranty
Precision PWM Automatic Voltage Regulator for MacDermid Colorspan® Inkjet Printers
VRp VRp
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
170 SpecificationsVRp-3500-0233
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi VRp-3500-0233-230vac-2006-10-16.pdf
Specification VRp-3500-0233Electrical
Capacity in VA (watts) 3.5 kVA (3500W) maximumRegulator engine High frequency 20kHz IGBT driven voltage regulation converter
Input Nominal voltage 230 volts ac, single phase
Operating voltage 184 to 276 volts ac Nominal frequency 47 to 63Hz Over-current protection magnetic circuit breaker
Circuit breaker rating two pole - 20 amps Inlet line, cord-plug 8 foot long cord with IEC60320 C-20 inlet- connector, and
NEMA L6 -20P plug. (May be ordered configured with hardwired input terminals L1, L2, and ground. Extra charge will apply).
OutputNominal voltage 230 vacCurrent and efficiency 16A (maximum) ~ 96% efficiency (typical)Voltage regulation Combined 3% maximum under to 100% load and input of 184 to 276V Automatic bypass Automatic bypass will be activated when there is a fault condition. Status indicators System status LED’s provided as follows: Green LED indicates Normal
(regulating mode operation); Red LED indicates Fault.Surge test conditions Per ANSI/IEEE C62.41-1991 6kV normal-mode injection Surge let-throughvoltages
Category A3, Ring wave, 200A: L-N: 30VCat. B3, Combination wave, 3000A: L-N: 200VNote: Unit should be installed as close as possible (within 30’) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond.
AC output connection One NEMA #L6-20R Receptacle (May be ordered configured with hardwired output terminals L1, L2, and ground. Extra charge will apply).
PhysicalDimensions 282mm(11.125”) wide x 162mm(6.375”)high x 377mm(14.875”)deep
Weight 21.8 kg(48 lbs) Wall/floor mounting kit MK-5019C (optional)
SafetyAgency approvals Designed to meet UL1950 and cUL1950 standards.
EnvironmentalAmbient temperature 0o to +40oC(32o to +104oF). 10 to 90% RH non-condensing.
WarrantyWarranty Two year limited warranty, parts and labor.
Precisionautomaticvoltage regulator
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Rear view*(VRp-4000 shown)
*Future models forthe EU will bepainted steel
VRp VRp
ground noisefilter
acinput
hot
two polecircuit
breaker
neutralL2
ground
L1
buck-boosttransformer
surge protection
andnoisefilter
L1
L2
micro-processor
control
184 to 276V ac
dc
230V+/- 3%
acoutput
automatic bypass
VRp system architecture
Front-right view(VRp-4000 shown)
Specifications
VRp SeriesPrecision Automatic Voltage Regulator
171
VRp-4000-0235 ~ 4kVA, 4 kW, 208/220/230 or 240vac, single phase
Precision fast-PWM mains voltage correctionTSi Power’s VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies plus/minus 15%. There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.
Typical applications Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: high-throughput color printers and copiers, analytical equipment, radio/TV broadcast equipment, and mobile broadcast vans.
Key VRp-4000-0235 benefitsThis light-weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRp’s ultra-low impedance assures stability even with the most demanding loads.
How the VRp Series worksThe high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 10,000 times per second, to achieve the nominal output voltage +/-3%. The automatic bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), and the Red LED indicates a Fault condition.
VRp model4000-0235
4000 VA (max.)4000 wattsinput: 208/220/230 or 240 vacoutput: 208/220/230 or 240 vac +/-3%
Fail-safe Automatic voltage regulator with PWM precision
Key features of the VRp Series• Outstanding voltage regulation:
under normal input range of nominal 184 to 264vac (60Hz), output regulation will be 208/220/ 230 or 240 vac+/ -3%.
• Failsafe: no switching of power path
• Fast regulation• Automatic bypass• Low-impedance• Low weight• Quiet operation• Two year warranty
Precision PWM Automatic Voltage Regulator for Copiers and Printers
VRp VRp
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
172 SpecificationsVRp-4000-0235
VRp-4000-0235-208vac-2006-10-16.pdf
Specification VRp-4000-0235Electrical
Capacity in VA (watts) 4 kVA (4000W) maximumRegulator engine High frequency 10kHz IGBT driven voltage regulation converter
Input Nominal voltage 208 volts ac single phase (220/230 or 240vac optional)
Operating voltage 184 to 264 volts ac Nominal frequency 47 to 63Hz Over-current protection Magnetic circuit breaker
Circuit breaker rating Two - 20 amps Input line cord/plug 6 foot long cord with NEMA 6-20P plug. (May be ordered configured with
hardwired input terminals L1, L2, and ground. Extra charge will apply). Output
Nominal voltage 208/220/230 or 240vac (Please specify at time of order).Current and efficiency 16A (maximum) ~ 96% efficiency (typical)Voltage regulation Combined 3% maximum under 0 to 100% load and input of 184 to 264V Automatic bypass Automatic bypass will be activated when there is a fault condition. Status indicators System status LEDs provided as follows: Green LED indicates Normal
(regulating mode operation); Red LED indicates Fault.Surge test conditions Per ANSI/IEEE C62.41-1991 6kV normal-mode injection Surge let-throughvoltages
Category A3, Ring wave, 200A: L-N: 30V Category B3, Combination wave, 3000A: L-N: 200VNote: Unit should be installed as close as possible (within 30’) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond.
Ac output connection One NEMA #6-20R Receptacle. (May be ordered configured with hardwired output terminals L1, L2, and Ground.Extra charge will apply).
PhysicalDimensions 282mm(11.125”)wide x 162mm(6.375”)high x 377mm(14.875”)deep
Weight 12 kg(27 lbs)Wall/Floor mounting kit MK-5019C (optional)
SafetyAgency approvals Designed to meet UL1950 and cUL1950 standards.
EnvironmentalAmbient temperature 0o to +40oC(32o to +104oF). 10 to 90% RH non-condensing.
WarrantyWarranty Two year limited warranty, parts and labor.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
VRp VRp
ground noisefilter
acinput
two polecircuit breaker
L2ground
L1
buck-boosttransformer
surge protection
andnoisefilter
L1
L2
micro-processor
control
184 to 264V ac
dc
208, 220, 230,240V
+/- 3%ac
output
automatic bypass
VRp system architecture
Specifications
Precisionautomaticvoltage regulator
Front-right view
Rear view**Future models for
the EU will bepainted steel
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
VRp SeriesPrecision Automatic Voltage Regulator
173
VRp-7500/10000 ~ 7.5/10kVA, 7.5/10kW, 208/220/230 or 240vac, single phase
Precision fast-PWM ac mains voltage correctionTSi Power’s VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies between 185 to 265VAC. There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.
Typical applications Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: analytical equipment, radio and TV broadcast equipment, mobile broadcast vans, industrial controllers (PLC), milking machines, lithographic equipment, recording studio equipment and electrolysis equipment.
Key benefitsThe low-weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRp’s ultra-low impedance assures stability even with the most demanding loads.
How the VRp Series worksThe high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per cycle, to achieve the nominal output voltage +/-3%. The Automatic Bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition.
VRp model 7500
7.5 kVA7.5 kWinput: 208/220/230 or 240 vacoutput: 208/220/230 or 240 vac +/-3%
1000010 kVAinput: 208/220/230 or 240 vacoutput: 208/220/230 or 240 vac +/-3%
Fail-safe Automatic voltage regulator with PWM precision
Key features of the VRp Series• Outstanding voltage regulation:
under normal input range of 185 to 265V (47 to 63Hz), output regulation will be:single phase208/220/230 or 240V +/-3%.
• Failsafe: no switching of power path
• Fast regulation• Automatic bypass• Low-impedance• Low weight• Quiet operation• Two year warranty
Precision, Light-weight, No-breakPWM Automatic Voltage Regulator Line Conditioner with Automatic Bypass
VRp VRp
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
174 VRp SeriesVRp-7500-10000
ground noisefilter
acinput
two polecircuit breaker
L2ground
L1
buck-boosttransformer
surge protection
andnoiseFilter
L1
L2
micro-processor
control
185 to 265 vac
acdc
208/220/230/240V +/- 3%
acoutputautomatic
bypass
Specification VRp-7500 VRp-10000Electrical
Capacity in VA (watts) 7.5kVA (7.5 kW) 10kVA (10kW) Regulator engine High frequency 20kHz IGBT driven voltage regulation converter
Input Nominal voltage 208/220/230 or 240 volts ac, single phase
Operating voltage 185 to 265 volts acMaximum operating range 160 to 300 volts ac (with reduced capacity, wider output regulation) Nominal frequency 47 to 63 HzOvercurrent protection Input circuit breaker Circuit breaker rating 40 amps 60 amps
Input wire size AWG 8 (8 square mm) AWG 6 (13 square mm) Ac connection Terminal block (for L1, L2, and ground wires) is provided.
OutputNominal voltage 208/220/230 or 240 volts ac, single phase. (factory adjusted) Power efficiency Better than 96% (under all load conditions) Voltage regulation Nominal +/-3% maximum under 0 to 100% load and 185 to 265 vac input Relaxed voltage regulation 192 to 240 volts ac over wider input range of 160 to 300 vac Automatic bypass Automatic bypass will be activated when there is a fault condition System status indicators
System status LED’s provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (non-regulated output); Red LED indicates Fault condition.
Surge test conditions Per ANSI/IEEE C62.41-1991 6kV normal-mode injection Surge let-through voltages
Category A3, Ring wave, 200A: L-N: 30V. L-G: 30VCategory B3, Combination wave, 3000A: L-N: 200V,L-G: 200VNote: Unit should be installed as close as possible (within 30’) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer (ILc) is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond. (customized built-in ILc option is available).
Ac connection Terminal block (for L1, L2, and ground wires) is provided. Physical
Dimensions 330mm(13”)wide x 216mm(8.5”)high x508mm(20”)deep Weight 36.3 kg(80 lbs) 40.8kg(90 lbs)
SafetyAgency approvals Designed to meet UL/cUL1950 and IEC 60950 standards.
EnvironmentalAmbient temperature 0o to +40oC(32o to +104oF). 10 to 90% RH non-condensing.
WarrantyWarranty Two year limited warranty, parts and labor.
VRp-7500-10000-230V-2006-10-16.pdf
Voltage regulation withprecision
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
VRp systemarchitecture
VRp VRp
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
VRp SeriesPrecision Automatic Voltage Regulator
175
VRp-9000/16500 ~ 9/16.5kVA, 9/16.5kW, 220/380V or 230/400vac wye, grey
Precision fast-PWM ac mains voltage correctionTSi Power’s VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies between 185 to 265 vac, per phase. There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.
Typical VRp applications Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: analytical equipment, radio and TV broadcast equipment, mobile broadcast vans, industrial controllers (PLC), milking machines, lithographic equipment, recording studio equipment and electrolysis equipment.
Key VRp benefitsThe low-weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRp’s ultra-low impedance assures stability even with the most demanding loads.
How the VRp Series worksThe high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 10,000 times per second, to achieve the nominal output voltage +/-3%. The automatic bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition.
VRp model9000
9 kVA9 kW220/380 or230/400 volts3 phase wye
1650016.5 kVA16.5 kW220/380 or230/400 volts3 phase wye
Fail-safe Automatic voltage regulator with PWM precision
Precision PWM Automatic Voltage Regulator with Automatic Bypass
VRp VRp
Key features of the VRp Seriesprecision voltage regulator
• Outstanding voltage regulation:under normal input range of 185 to 265V(47 to 63Hz) per phase, output regulation will be:nominal +/-3%
• Failsafe: no switching of power path
• Fast regulation• Automatic bypass• Low- impedance• Low weight• Quiet operation• Two year warranty
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
176 SpecificationsVRp-9000/16500
VRp-9000-16500-3ph-Gray-2006-10-16.pdf
ground noisefilter
acinput
hot
three phasecircuit breaker
neutral ground
L1
buck-boosttransformer
surge protection
andnoisefilter
L1
micro-processor
control
185V to
265Vper
phaseac
dc
220V or230V
per ph.+/- 3%
acoutput
automatic bypass
neut
Specification VRp-9000 VRp-16500Electrical
Capacity in VA (watts) 9kVA (9 kW) 16.5kVA (16.5kW) Regulator engine High frequency 10kHz IGBT driven voltage regulation converter
Input Nominal voltage 220/380V or 230/400 volts ac, three phase wye
Normal operating voltage Range: 185 to 265 volts ac Maximum operating range 160 to 300 volts ac (with reduced output capacity and wider regulation). Nominal frequency 47 to 63Hz Over-current protection Input circuit breaker Circuit breaker rating 3 x 20 amps (ganged) 3 x 40 amps (ganged)
Input wire size AWG 12 (3.3 square mm) AWG 8 (8 square mm) Ac connection Terminal block (L1, L2, L3, neutral and ground wires) provided.
OutputNominal voltage 220/380V or 230/400 volts ac (specify with PO), three phase wye. Power efficiency Better than 96% (under all load conditions)Voltage regulation Nominal +/-3% maximum under 0 to 100% load and input of 185 to 265 vac Relaxed voltage regulation 192 to 240 volts ac over wider input range of 160 to 300 vac Automatic bypass Automatic bypass will be activated when there is a fault condition. System status indicators
System status LED’s provided as follows: Green LED (blinking) indicates normal (regulating mode operation); Yellow LED (blinking) indicates bypass (non-regulated output); Red LED indicates fault condition.
Surge test conditions Per ANSI/IEEE C62.41-1991 6kV normal-mode injection. Surge let-throughvoltages
Category A3, Ring wave, 200A: L-N: 30V. L-G: 30VCategory B3, Combination wave, 3000A: L-N: 200V,L-G: 200VNote: Unit should be installed as close as possible (within 30’) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer(ILc) is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond. (Customized built-in ILc option is available).
Ac connection Terminal block (L1, L2, L3, neutral and ground wires) provided. Physical
Dimensions 610mm(24”)wide x 710mm(28”)high x 560mm(22”)deep Weight 73 kg(160 lbs) 86 kg(190 lbs)
SafetyAgency approvals Designed to meet UL/cUL1950 and IEC 60950 standards.
EnvironmentalAmbient temperature 0o to +40oC(32o to +104oF). 10 to 90% RH non-condensing.
WarrantyWarranty Two year limited warranty, parts and labor.
Voltage regulator withprecision
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
VRp system (per phase) architecture
VRp VRp
Power with a Precision Attitude™
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
VRp SeriesPrecision Automatic Voltage Regulator
177
VRp-9000/16500-0338 ~ 9/16.5kVA, 9/16.5kW, 220/380vac or 230/400vac wye
Precision fast-PWM ac mains voltage correctionTSi Power’s VRp automatic precision regulator allows trouble-free operation of electronic equip-ment over a very wide mains ac voltage range of 160 to 300V found in many developing countries. There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.
Typical applications Designed for applications where absolutely safe and precisely regulated ac power is required, such as mobile communication (GSM/satellite/wireless broadband), radio/TV broadcasting, industrial process controller (PLC), medical (mobile MRI, CT) and laboratory or analytical measurement equipment.
Key benefitsVRp is compatible with all loads as it does not switch any components in the power path. VRp’s ultra-low impedance assures stability even with the most demanding loads. The automatic bypass assures that connected equipment will not shut down, even if VRp fails.
How the VRp Series worksThe high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 10,000 times per second, to achieve precisely regulated 230vac output. The automatic bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition.
VRp model9000-0338
9 kVA9 kW230/400 volts3 phase wye
16500-033816.5 kVA16.5 kW230/400 volts3 phase wye
Fail-safe Automatic voltage regulator with PWM precision
Precision PWM Automatic Voltage Regulator with Automatic Bypass
VRp VRp
Key features of the VRp Seriesprecision voltage regulator
• Outstanding voltage regulation:under voltage input range of 185 to 265V (47 to 63Hz) per phase, output regulation will be:within +/-1%.
• No switching of power path and unit always starts up on sinewave zero crossing.
• Over-under voltage cutoff, with automatic restart when mains voltage decreases back to below 275 vac, or above 160 vac.
• Failsafe: automatic bypass• Low- impedance• Lightweight• Wall fixing kit is included• Quiet operation• Two year warranty
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
178 SpecificationsVRp-9000/16500-0338
VRp-9000-16500-0338-3ph-2006-10-16.pdf
Specification VRp-9000-0338 VRp-16500-0338Electrical
Capacity in VA (watts) 9kVA (9 kW) 16.5kVA (16.5kW) Regulator engine High frequency 10kHz IGBT driven voltage regulation converter
Input Nominal voltage 230/400 volts ac, three phase wye
Normal operating voltage Range: 160 to 300 volts ac Maximum operating range 160 to 300 volts ac(with reduced output capacity and wider regulation) Nominal frequency 47 to 63Hz Overcurrent protection Input circuit breaker and over-under voltage cutoff (>300vac or <160vac) Circuit breaker rating 3 x 20 amps (ganged) 3 x 30 amps (ganged)
Input wire size AWG 10 (4 square mm) AWG 8 (8 square mm) Ac connection Terminal block (L1, L2, L3, Neutral and ground wires) provided.
OutputNominal voltage 230/400 volts ac, three phase wye Power efficiency Better than 96% (with 20-100% load conditions) Voltage regulation Factory set at 1%, long-term stability: <2%. Relaxed voltage regulation 192 to 240 volts ac over wider input range of 160 to 300 volts ac Automatic bypass Automatic bypass will be activated when there is a fault condition. System status indicators
Status LED’s provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (non-regulated output); Red LED indicates Overload (system may shut down).
Surge test conditions Per Class 2 and Class 3 simulated lightning surge (Combination wave) Surge let-throughvoltages
Class 2 and 3, 4000V, 3000A: L-N: 200V, L-G: 200VNote: For maximum protection of the VRp and connected load equipment, TSi Power recommends that a matching isolation power conditioner (ILc) be placed adjacent to the VRp.
Matching ILc (mandatory) ILc-9000-0338 ILc-16500-0338Ac connection Terminal block (L1, L2, L3, neutral and ground wires) provided.
PhysicalDimensions 610mm(24”)wide x 610mm(24”)high x 305mm(12”)deep Weight 80 kg(176 lbs) 100 kg(220 lbs)
SafetyAgency approvals Designed to meet IEC 60950 standards. Protection class IP20.
EnvironmentalAmbient temperature 0o to +40oC(32o to +104oF). 10 to 90% RH non-condensing. Cooling method Fan cooled.
WarrantyWarranty Two year limited warranty, parts and labor.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
VRp system (per phase) architecture
VRp VRpVoltage regulator withprecision
Power with a Precision Attitude™
Left side- front view
ground noisefilter
acinput
hot
three phasecircuit breaker
neutral ground
L1
buck-boosttransformer
surge protection
andnoisefilter
L1
micro-processor
control
185V to 265Vper
phaseac
dc
230Vper ph.+/- 1%
acoutput
automatic bypass
neut
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
VRp SeriesPrecision Automatic Voltage Regulator
179VRp-15000/20000-0230 ~ 15/20kVA, 15/20kW, 208/220/230 or 240vac, single phase
VRp model15000-0230
15 kVA15 kW208/220/230or 240 voltssingle phase
20000-023020 kVA20 kW208/220/230or 240 voltssingle phase
VRp VRp
Power with a Precision Attitude™
Precision fast-PWM ac mains voltage correctionTSi Power’s VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies between 185 to 265VAC. There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.
Typical applications Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: analytical equipment, radio and TV broadcast equipment, mobile broadcast vans, industrial controllers (PLC), milking machines, lithographic equipment, recording studio equipment and electrolysis equipment.
Key benefitsThe low-weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRp’s ultra-low impedance assures stability even with the most demanding loads.
How the VRp Series worksThe high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per cycle, to achieve the nominal output voltage +/-3%. The Automatic Bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition.
Precision, Light-weight, No-breakPWM Automatic Voltage Regulator Line Conditioner with Automatic Bypass
Key features of the VRp Series• Outstanding voltage regulation:
under normal input range of 185 to 265V (47 to 63Hz), output regulation will be:single phase208/220/230 or 240V +/-3%.
• Failsafe: no switching of power path
• Fast regulation• Automatic bypass• Low-impedance• Low weight• Quiet operation• Two year warranty
Fail-safe Automatic voltage regulator with PWM precision
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
180 SpecificationsVRp-15000/20000-0230
Specification VRp-15000-0230 VRp-20000-0230Electrical
Capacity in VA (watts) 15kVA (15 kW) 20kVA (20kW) Regulator Engine High frequency 20kHz IGBT driven voltage regulation converter
Input Nominal Voltage 208/220/230 or 240 volts ac, single phase
Operating Voltage 185 to 265 volts acMaximum OperatingRange 160 to 300 volts ac (with reduced capacity, wider output regulation) Nominal Frequency 47 to 63 HzOvercurrent Protection Input circuit breaker Circuit Breaker Rating 80 amps 100 amps
Input Wire Size AWG 4 AWG 2 AC Connection Input wire terminal block (L1, L2, and ground wires) is provided.
OutputNominal voltage 208/220/230 or 240 volts ac, single phase. (factory adjusted) Power efficiency Better than 96% (under all load conditions) Voltage regulation Nominal +/-3% maximum under 0 to 100% load and 185 to 265 vac input Relaxed voltage regulation 192 to 240 volts ac over wider input range of 160 to 300 vac Automatic bypass Automatic bypass will be activated when there is a fault condition System status indicators
System status LED’s provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (non-regulated output); Red LED indicates Fault condition.
Surge test conditions Per ANSI/IEEE C62.41-1991 6kV normal-mode injection Surge let-throughvoltages
Category A3, Ring wave, 200A: L-N: 30V. L-G: 30VCategory B3, Combination wave, 3000A: L-N: 200V,L-G: 200VNote: Unit should be installed as close as possible (within 30’) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer (ILc) is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond. (customized built-in ILc option is available).
Ac connection Terminal block (for L1, L2, and ground wires) is provided. Physical
Dimensions 610mm(24”)wide x 710mm(28”)high x 560mm(22”)deep Weight 82 kg(180 lbs) 91 kg (200 lbs)
SafetyAgency approvals Designed to meet UL/cUL1950 and IEC 60950 standards.
EnvironmentalAmbient temperature 0o to +40oC(32o to +104oF). 10 to 90% RH non-condensing.
WarrantyWarranty Two year limited warranty, parts and labor.
VRp-15000-20000-230V-2006-10-16.pdf
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
VRp VRp
Voltage regulator withprecision
Power with a Precision Attitude™
ground noisefilter
acinput
two polecircuit breaker
L2ground
L1
buck-boosttransformer
surge protection
andnoiseFilter
L1
L2
micro-processor
control
185 to 265 vac
acdc
208/220/230/240V +/- 3%
acoutputautomatic
bypassVRp systemarchitecture
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
VRp SeriesPrecision Automatic Voltage Regulator
181
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
VRp-22500/30000-0338 ~ 22.5/ 30kVA, 22.5/30kW, 220/380V or 230/400vac wye
VRp model22500-0338
22.5 kVA22.5 kW230/400 volts3 phase wye
30000-033830 kVA30 kW230/400 volts3 phase wye
VRp VRp
VRp-22500
Fail-safe Automatic voltage regulator with PWM precision
Precision fast-PWM ac mains voltage correctionTSi Power’s VRp automatic precision regulator allows trouble-free operation of electronic equip-ment over a very wide mains ac voltage range of 160 to 300V found in many developing countries. There is no switching of taps or otherwise a break in the power path thanks to continuous pulsed-width-modulation (PWM) switching of a buck-boost transformer.
Typical applications Designed for applications where absolutely safe and precisely regulated ac power is required, such as mobile communications (GSM/satellite/wireless broadband), radio base stations (RBS)/base transmitter stations (BTS), radio/TV broad-casting, transmission sites for backhaul (including microwave links) industrial process controller (PLC), medical (mobile MRI, CT) and laboratory or analytical measurement equipment.
Key benefitsVRp is compatible with all loads as it does not switch any components in the power path. VRp’s ultra-low impedance assures stability even with the most demanding loads. The automatic bypass assures that connected equipment will not shut down, even if VRp fails.
How the VRp Series worksThe high frequency insulated gate bi-polar transistor (IGBT) driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve precisely regulated 230vac output. The automatic bypass will be activated when there is a fault condition. Green LEDs are used to indicate Normal (regulating mode) operation).
Precision PWM Automatic Voltage Regulator with Automatic Bypass
Key features of the VRp Seriesprecision voltage regulator
• Outstanding voltage regulation:under voltage input range of 185 to 265V (47 to 63Hz) per phase, output regulation will be:within +/-1%.
• No switching of power path and unit always starts up on sine wave zero crossing.
• Over-under voltage cutoff, with automatic restart when mains voltage decreases back to below 275 vac, or above 160 vac.
• Failsafe: automatic bypass• Low- impedance• Lightweight• Wall fixing kit is included• Quiet operation• Two year warranty
182 SpecificationsVRp-22500/30000-0338
VRp-22500-30000-0338-3ph-2006-10-16.pdf
Specification VRp-22500-0338 VRp-30000-0338Electrical
Capacity in VA (watts) 22.5kVA (22.5 kW) 30kVA (30kW)Regulator engine High frequency 20kHz IGBT driven voltage regulation converter
Input Nominal voltage 230/400 volts ac, three phase wye
Normal operating voltage Range: 160 to 300 volts ac Maximum operating range 160 to 300 volts ac (with reduced output capacity and wider regulation) Nominal frequency 47 to 63Hz Input circuit breaker and overcurrent protection
Input circuit breaker (with limited inrush current capability) and over-under voltage cutoff (at greater than 300vac or less than160vac)
Circuit breaker rating 3 x 40 amps (ganged) 3 x 60 amps (ganged) Input wire size 10mm2 (AWG 8) 15mm2 (AWG 6)
Ac connection Terminal block (L1, L2, L3, neutral and ground wires) provided. Output
Nominal voltage 230/400 volts ac, three phase wye Power efficiency Better than 96% (with 20-100% load conditions) Voltage regulation Factory set at 1%, long-term stability: <2%. Relaxed voltage regulation 192 to 240 volts ac over wider input range of 160 to 300 volts ac Automatic bypass Automatic bypass will be activated when there is a fault condition. System status indicator Green LED (ON) indicates Normal (regulating mode) operation.
Surge test conditions Per Class 2 and Class 3 simulated lightning surge (Combination wave) Surge let-throughvoltages
Class 2 and 3, 4000V, 3000A: L-N: 200V, L-G: 200VNote: For maximum protection of the VRp and connected load equipment, TSi Power recommends that a matching isolation power conditioner (ILc) be placed adjacent to the VRp.
Matching ILc (mandatory) ILc-22500-0338 ILc-30000-0338Ac connection Terminal block (L1, L2, L3, neutral and ground wires) provided.
PhysicalDimensions 610mmW x 610mmH x 305mmD
24”wide x 24”high x 12”deep 610mm W x 863mm H x 305mm
24”wide x 34”high x 12”deep Weight 89kg(196 lbs) 110kg(243 lbs)
SafetyStandards Designed to meet IEC 60950 standards. Protection class IP20.
EnvironmentalAmbient temperature -5° to +35°C (23° to 95°F). 10 to 90% RH non-condensing. Cooling method Fan cooled.
WarrantyWarranty Two year limited warranty, parts and labor.
Precision PWMautomaticvoltage regulator
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
VRp VRp
Power with a Precision Attitude™
VRp system (per phase) architecture
ground noisefilter
acinput
hot
three phasecircuit breaker
neutral ground
L1
buck-boosttransformer
surge protection
andnoisefilter
L1
micro-processor
control
185V to
265Vper
phaseac
dc
230Vper ph.+/- 1%
acoutput
automatic bypass
neut
Specifications
Lifting ears shown
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
VRp-ILc SeriesPrecision Voltage Regulator + Isolation Transformer Line Conditioner
183
VRp-ILc-16500-0338 ~ 16.5kVA, 16.5kW, 400vac delta to 230/400vac wye
Continuous fast andno-break PWM regulationTSi Power’s VRp-ILc automatic precision voltage regulator with built-in low-impedance isolation transformer allows trouble-free operation of electronic equipment over a very wide mains ac voltage range of 400V +/-20% (+/-30% for short durations) found in many developing countries. There is no switching of taps or otherwise a break in the power path thanks to continuous PWM (Pulse-Width-Modulation) switching of a buck-boost transformer primary winding.
Typical VRp-ILc applications Designed for applications where absolutely safe and precisely regulated ac power is required, such as outdoor mobile tele-communication, TV/radio broadcasting or industrial equipment.
International Precision voltage regulator Isolation transformer
Precision PWM Automatic Voltage Regulator with Isolation Transformer,Automatic Bypass and Automatic Cutoff
Key features of the VRp-ILc Series precision automatic voltage regulator with isolation transformer
• Outstanding voltage regulation:under normal input range of 400vac +/- 20%, output voltage will be 230vac +/-1% (47 to 63Hz)
• No switching of power path and unit always starts up on sine wave zero crossing
• Over and under voltage cutoff, with automatic restart when ac mains voltage returns to normal (safe) condition
• Failsafe: automatic bypass (even during bypass, the over/under voltage protection is active)
• Lightweight design
• Three separate low-impedance isolation transformers (one per phase) are used for maximum reliability
• Coordinated surge protection per IEC61312
• Common-mode noise elimination• Advanced noise and interference
filter reduces dV/dt from 6kV/µS to less than 10V/µS
• IP20 rated enclosure with two separate compartments
• Two year warranty
VRp-ILc model16500-0338
16.5 kVA16.5 kW input - 4 wires400vac deltaoutput - 5 wires230/400vac wyethree phase
VRp-ILcVRp-ILc
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
184 VRp-ILc SeriesVRp-ILc-16500-0338
Key VRp-ILc benefitsThe lightweight, high efficiency VRp-ILc is easy to install in indoor environments. The unit comes in a specially designed IP20 rated enclosure with thermostatically controlled fans and has removable lifting eyes to enable use of lifting equipment.The automatic bypass assures that connected equipment will not shut down, even if VRp-ILc fails. VRp-ILc is compatible with all loads as it does not switch any components in the power path. VRp-ILc’s ultra-low impedance assures stability even with the most demanding loads.The automatic over-voltage/under-voltage cutoff with automatic restart ensures that operation is off-line during serious over-voltage or under-voltage situations that could damage the system and/or load, and then restarts without intervention when the ac mains voltage becomes within the operating range. The ILc isolation line conditioner components provide maximum equipment protection against surges, spikes and transients, for higher equipment reliability and maximum equipment operating life. In addition, improved repeatability, fewer reboots or system lock-ups. In addition, a reduction in equipment down time and service costs can be expected.TSi’s use of three separate transformers, one per phase, minimizes the dangers associated with single phasing or lost phase problems associated with a three phase transformer built on a common (single) core.Maximum transformer and regulator performance, reliability and lifetime is achieved by a design with no moving mechanical parts other than cooling fans.
VRp-ILcVRp-ILc
How the VRp-ILc Series worksThe VRp-ILc unit is comprised of a VRp section - an automatic precision voltage regulator, and an ILc section - an isolation line conditioner, each in its own separate compartment.The high frequency IGBT driven converter microprocessor takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve precisely regulated 230/400 vac three phase output, cycle by cycle. Voltage correction times do not exceed 1 cycle, or 20 milliseconds for all mains ac voltage changes, even for instantaneous voltage changes from 160 to 300vac or from 300 to 160vac. The automatic bypass will be activated when there is a fault condition. Three LEDs display unit status, the Green LED indicates Normal (regulating protected mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition.The over-voltage and under-voltage cutoff is activated whenever the ac mains input voltage becomes dangerously high or low (>300vac or <160vac). It automatically restarts whenever ac mains voltage is restored within <300vac and >160vac.Three separate low-impedance isolation transformers provide complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground. The leakage inductance of the isolation transformers, in combination with capacitive elements and MOVs, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.High reliability cooling fans control the unit’s internal temperature, with intake and exhaust through vents on sides of the unit.
PrecisionPWM voltage regulatorwith isolationtransformer
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
SpecificationsPrecision Voltage Regulator + Isolation Transformer Line Conditioner
185
Front-right side view
Specification VRp-ILc-16500-0338Electrical
Capacity in VA (watts) 16.5kVA (16.5kW)Regulator technology High frequency 20kHz IGBT driven voltage regulation converter.
Pulse width modulated (PWM) ac to dc converter and dc to ac topology. Transformer type Three separate isolation transformers are used (one per phase).
Input Nominal voltage Three phase delta: 400 volts ac
Normal operating range Range: 400 vac, +/-20%. Short duration (less than 5 minutes) operation 400vac, +/-30%.
Nominal frequency 47 to 63 Hz Input circuit breaker Input circuit breaker (150% overload capability for heavy start load). Over-under voltage cutoff with auto-restart
Over-under voltage cutoff activated when >300vac or <160vac, with automatic restart when voltage becomes <300vac and >160vac.
Circuit breaker rating 3 x 40 amps (ganged) Input wire size 10mm2 (8AWG) Ac connection Terminal block (L1, L2, L3 and ground wires) provided.
OutputNominal voltage Three phase wye: 230/400 volts acPower efficiency Better than 93% (at 400V input) Voltage regulation Factory set at 1%, long-term stability: <2%. Relaxedvoltageregulation 230/400vac +/-10% (over input range of 400vac +/- 30%) Automatic bypass Automatic bypass will be activated when there is a fault condition. Safe start Unit starts on sine wave zero voltage crossing point upon turn-on.
Unit is fully functional/regulated within 5 seconds of mains restoration. System status indicators (per phase)
System status LED’s provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (non-regulated output); Red LED indicates Overload (system may shut down).
Surge protection A three-stage surge protection system consisting of isolation transformer, capacitor and MOV is included.
Surge test conditions Class 2 and Class 3 simulated lightning surge (Combination wave) Per ANSI/IEEE C62.41-1991, Cat. C test waveform: 6kV, 3kA, 8x20µS
Surge let-throughvoltages (system will continue to operate without interruption under these conditions)
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt of the remnant waveform is less than 10V/µS with input test waveform dV/dt of 6kV/µS
Common mode filtering Neutral-ground bond eliminates all noise or voltage on neutral (< 0.5V) Normal mode filtering A built-in inductor-capacitor filter attenuates EMI/RFI noise from output. Ac connection Terminal block (L1, L2, L3, neutral and round wires) provided.
PhysicalDimensions 800mm(32”)wide x 1300mm(51”)high x 300mm(12”)deep Weight 276 kg(242 lbs) Enclosure IP20. Painted metal.
SafetyStandards Design ready to meet EMC standards.
EnvironmentalAmbient temperature -5o to +35oC(23o to 95oF) (Air conditioned). Cooling method Fan cooled (Ball bearing).
WarrantyWarranty Two year limited warranty, parts and labor.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may betrademarks of their respective companies.
VRp-ILcVRp-ILc
Power with a Precision Attitude™
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
186 VRp-ILc SeriesVRp-ILc-16500-0338
VRp-ILc-16500-0338-2006-10-16.pdf
VRp-ILcVRp-ILc
Precision PWM automatic voltage regulatorwith low-impedance isolation transformer
Power with a Precision Attitude™
ground
3 phasecircuit breaker
L2 G
L1
buck-boosttransformer
L
N
microprocessorcontrol
230vac+/-2%
VRp-ILcoutputautomatic bypass
over/undervoltage cutoff
surge prot.and
noisefilter
Input400vac-20%+30%
isolation transformer
noisefilter
dcac
ground
VRp-ILc-16500-0338 system architecture (per phase)
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv SeriesDc to Ac Inverters
187
XINvXINv
XINv SeriesDc to Ac Inverters
XINv Series ~ Rack-mountable PWM Dc to Ac Inverters with Transformer Isolation
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
188 XINv SeriesDc to Ac Inverters
XINv-Series-2006-10-16.pdf
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv SeriesRack-mountable 24vdc to 115vac Inverter
189
XINv-600/900-24V ~ 600/900VA, 600/900W, 24vdc to 115vac
XINv model600-24V
600 VA600 watts+/-24 vdc input115 vac output
900-24V 900 VA900 watts+/-24 vdc input115 vac output
Pure sine wave PWM dc to ac inverter Voltage regulation + isolation
These heavy-duty XINv Series dc to ac inverters are housed in a 2U rack-mountable enclosure. XINv PWM inverters feature a transformer isolated sine wave output. They are designed for all applications requiring continuous pure sine wave power. They produce 115 volts ac from 24volts dc.
Key XINv benefitsXINv uses high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuits for high efficiency and low input dc ripple currents. They also feature high dc to ac power conversion efficiency, pure sine wave output and long MTBF. XINv also provides precision automatic voltage regulation: of 115vac +/-3% and less than 5% THD. XINv’s 2U high construction with optional wall or rack-mounting kits provides maximum flexibility for telecom and industrial users. XINv offers a hardwire terminal block battery connection with a dc circuit breaker for external 24vdc battery banks.
How the XINv worksA rugged, high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuit takes the dc input and converts it into a pure sine wave. The circuitry automatically adjusts the duty cycle of the output for all loads and inputs. XINv delivers a stable 60Hz +/-0.5% frequency. A dc circuit breaker protects all dc circuits, and an overload shutdown feature protects the inverter from overload. When the input dc voltage drops below 21volts, a DB9 connector in the rear of the inverter sends signals for inverter output failure and low dc input voltage. A comprehensive array of output current, battery charge levels, and status LED indicators are provided for visual assessment of inverter status. A DB-9 port is provided for communication using RS-232 or dry relay contact signals.
Rack-mountable Dc to Ac Inverter
Typical XINv applications Applications include all waveshape sensitive equipment such as telecommunications systems, industrial, measurement and other mission-critical, harmonic-sensitive electronics. They are also ideal for use in facilities with 24vdc rectifier/battery power plants, where the inverter can be used to provide the function of a double-conversion on-line UPS.
Key XINv features• Pure sine wave inverter output• Eight NEMA 5-15R receptacles• Rack or wall mountable
with optional rack/wall-mount kits • Unipolar PWM inverter• Ac output is isolated from dc • +/-3% voltage regulation• Comprehensive array of
status LEDs/bargraphs • SNMP compatible via RS-232
port with optional SNMP adapter• Both RS-232 and relay
contact signals are provided• Very low audible noise• Rugged construction supports
mobile and portable applications• Two year limited warranty
parts and labor
XINv XINv
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
190 SpecificationsXINv-600/900-24vdc-115vac
Specification XINv-600-24V XINv-900-24V Electrical Capacity in VA (watts) 600VA (600W) 900VA (900W)
Inverter type Pulse-width-modulated (PWM) with isolation transformer. Input Nominal voltage -24 volts dc or +24 volts dc
Operating voltage 21 to 29 volts dc Maximum input current 35 amps 50 amps
Dc input connector 3 screw terminal block for earth ground, (+), (-) dc Inputs. Recommended wire 10mm2(8 AWG) 15mm2(6 AWG) Output
Ac output voltage 115 volts +/-3% ac (factory settable to 100, 110 or 120 vac) Frequency stability 60Hz +/- 0.5%Output waveform Pure sine wave. Less than 5% maximum THD for 0 to 100% loads. Load compatibility All linear and non-linear loads from -0.6 (leading) to +0.6 (lagging)
power factor, including new power-factor corrected switchmode power supplies and older non-power-factor corrected power supplies.
Load crest factor Up to 3:1 crest factor loads can be powered by the inverter. Surge current capability
Up to 300% surge power is available from the inverter to power loadequipment with high starting/stopping surge currents for a few ac cycles.
Overload capability 1 minute @ 120% overcurrent. Power efficiency Greater than 85% under all load and dc input voltage conditions. Power on/off switch Recessed on/off rocker style power switch. Communications Rear-mounted DB-9 female signal port. Status indicators Dc input voltage indicator: 5 green LEDs (20% per each LED).
Ac output current: 5 green LEDs (20% per each LED). Inverter On: 1 yellow LED illuminates during normal inverter operation. Overload: 1 red LED illuminates if overload condition exists.
Ac receptacles Eight standard NEMA 5-15R female receptacles. Audible noise <45dBA @ 1m under all operating conditions. Isolation and grounding 100% isolation between input dc and output ac (isolation transformer
included). Metal enclosure is bonded to dc input terminal block earth ground input.
PhysicalDimensions 406mm(16”)wide x 381mm(15”)deep x 89mm(3.5”)high (2U high)
Weight 12 kg(26 lbs) 18 kg(38 lbs) Rack or wall mountingkits (optional),23/24” also available
19 Inch Front rack-mount kit: MK-5019A 19 Inch Center rack-mount kit: MK-5019F Wall or Floor mount kit: MK-5000C
SafetyAgency approvals Designed to meet IEC 60950 safety standards. Dc breaker Protection against shorts or misapplication of inverter current. Low voltage disconnect Inverter turns off automatically if input dc voltage drops below 21vdc. Overload shutdown Inverter turns off automatically if overload is >120% for over 1 minute.
EnvironmentalAmbient temperature -20o to +40oC(-4o to +104oF). 10 to 95% relative humidity
(non-condensing). Storage temp. -20o to +60oC(-4o to +140oF).Cooling method Forced air (internal hot air exhaust fan is included). Elevation 0 to 4000 meters (0 to 12,400 feet) above sea level.
WarrantyWarranty Two year limited depot warranty, parts and labor.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Rack-mountableheavy-duty PWMdc to ac inverter
XINv XINv
Power with a Precision Attitude™
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv SeriesRack-mountable 24vdc to 115vac Inverter
191
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv XINv
dc input circuit breaker
output ac via eight standard NEMA 5-15R receptacles
DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)
dc input terminalblock connector
recessed on/off switch
dc input voltagelevel: 20% per LED
rear view
output current level: 20% per LED
inverter On
overload condition
L
N
XINv output115vac +/-3%
dc input21–29vdc isolation transformer
ground
ac
dc
chassis groundearth groundgnd
neutral-ground bondon transformer output
N
dc to ac inverter
microprocessor
DB9 port forcommunications
dc circuit breaker
XINv-600/900-24V system architecture
front-right view
192 XINv SeriesXINv-600/900-24vdc-115vac
XINv-600-900-24vdc-115vac-Inverter-2006-10-16.pdf
XINv-600/900-24V at a glanceRack or wall-mountable heavy-duty PWM dc to ac inverterwith isolation transformer and 115vac +/- 3% voltage regulation
• High performance microprocessor-controlled PWM sine wave output+/-24vdc to 115vac inverter
• Pure sine wave output• Isolation transformer• Rack-mountable 2U high metal
cabinet allows for rack or wall mounting using optional mounting kits
• 115vac +/-3% standard output can be set to a 100, 110 or 120vac output at the factory
• Eight NEMA 5-15R receptacles• +/-24vdc terminal block
connection with dc circuit breaker• DB-9 signal port with RS-232
and relay contact signals• SNMP compatible
with optional SNMP adapter
Specification Connector pin Switching condition DB9 port function (Please note: relay contact is rated for 48vac/vdc, 1A maximum).
Remote shutdown 1 For Remote Shutdown A +5vdc to +12vdc signal sent to pin#1 for three full seconds will shut down the inverter remotely. Note: this operation requires manual restart.
Transmit data 2 TXD RS-232 Signal RS-232 signal line
Receive data 3 RXD RS-232 Signal RS-232 signal line
Custom or future use 4 Unused For future use.
Ground 5 Ground Logic ground for pins 1 through 4.
Inverter On 6 + 7 Inverter On/Off (Relay contact)
Closed when inverter is On, Open when inverter is Off.
Low battery alarm 8 + 9 Low Battery Alarm (Relay contact)
Open when dc is okay. Closed when input source (battery voltage) drops below 21.5vdc.
RS-232C serial communication for inverter status communicationcompatible with MEGATEC Communication Protocol, Part 1
Baud rate 2400bps
Data length 8 bits
Stop bit 1 bit
Parity None
SNMP interface (optional)SNMP interface for inverter monitoring andautomatic shutdown configuration (Optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the inverter can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external inverter monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
XINv XINv
Rack-mountableheavy-duty PWMdc to ac inverter
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv SeriesRack-mountable 24vdc to 230vac Inverter
193
XINv-600E/900E-24V ~ 600/900 VA, 600/900 W, 24vdc to 230vac
XINv model600E-24V
600 VA600 watts+/-24 vdc input230 vac output
900E-24V 900 VA900 watts+/-24 vdc input230 vac output
Pure sine wave PWM dc to ac inverter Voltage regulation + isolation
These heavy-duty XINv Series dc to ac inverters are housed in a 2U rack-mountable enclosure. XINv PWM inverters feature a transformer isolated sine wave output. They are designed for all applications requiring continuous pure sine wave power. They produce 230 volts ac from 24volts dc.
Key XINv benefitsXINv uses high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuits for high efficiency and low input dc ripple currents. They also feature high dc to ac power conversion efficiency, pure sine wave output and long MTBF. XINv also provides precision automatic voltage regulation of: 230vac +/-3% and less than 5% THD. XINv’s 2U high construction with optional wall or rack-mounting kits provides maximum flexibility for telecom and industrial users.XINv offers a hardwire terminal block battery connection with a dc circuit breaker for external 24vdc battery banks.
How the XINv worksA rugged, high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuit takes the dc input and converts it into a pure sine wave. The circuitry automatically adjusts the duty cycle of the output for all loads and inputs. XINv delivers a stable 50Hz +/-0.5% frequency. A dc circuit breaker protects all dc circuits, and an overload shutdown feature protects the inverter from overload. When the input dc voltage drops below 21volts, a DB9 connector in the rear of the inverter sends signals for inverter output failure and low dc input voltage. A comprehensive array of output current, battery charge levels, and status LED indicators are provided for visual assessment of inverter status. A DB-9 port is provided for communication using RS-232 or dry relay contact signals.
Rack-mountable Dc to Ac Inverter
Typical XINv applications Applications include all waveshape sensitive equipment such as telecommunications systems, industrial, measurement and other mission-critical, harmonic-sensitive electronics. They are also ideal for use in facilities with 24vdc rectifier/battery power plants, where the inverter can be used to provide the function of a double-conversion on-line UPS.
Key XINv features• Pure sine wave inverter output• Four IEC320-C13 receptacles• Rack or wall mountable
with optional rack/wall-mount kits • Unipolar PWM inverter• Ac output is isolated from dc • +/-3% voltage regulation• Comprehensive array of
status LEDs/bargraphs • SNMP compatible via RS-232
port with optional SNMP adapter• Both RS-232 and relay
contact signals are provided• Very low audible noise• Rugged construction supports
mobile and portable applications• Two year limited warranty
parts and labor
XINv XINv
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
194 SpecificationsXINv-600E/900E-24V
Specification XINv-600E-24V XINv-900E-24V Electrical Capacity in VA (watts) 600VA (600W) 900VA (900W)
Inverter type Pulsed-width-modulated (PWM) with isolation transformer. Input Nominal voltage -24 volts dc / +24 volts dc
Operating voltage 21 to 29 volts dc Maximum input current 35 amps 50 amps
Dc input connector 3 screw terminal block for earth ground, (+), (-) dc Inputs. Recommended wire 10mm2(8 AWG) 15mm2(6 AWG) Output
Ac output voltage 230volts +/-3% ac (factory settable to 200, 220 or 240vac) Frequency stability 50Hz +/- 0.5%Output waveform Pure sine wave. Less than 5% maximum THD for 0 to 100% loads. Load compatibility All linear and non-linear loads from -0.6 (leading) to +0.6 (lagging)
power factor, including new power-factor corrected switchmode power supplies and older non-power-factor corrected power supplies.
Load crest factor Up to 3:1 crest factor loads can be powered by the inverter. Surge current capability
Up to 300% surge power is available from the inverter to power load equipment with high starting/stopping surge currents for a few ac cycles.
Overload capability 1 minute @ 120% overcurrent. Power efficiency Greater than 85% under all load and dc input voltage conditions. Power on/off switch Recessed on/off rocker style power switch. Communications Rear-mounted DB-9 female signal port. Status indicators Dc input voltage indicator: 5 green LEDs (20% per each LED).
Ac output current: 5 green LEDs (20% per each LED). Inverter On: 1 yellow LED illuminates during normal inverter operation. Overload: 1 red LED illuminates if overload condition exists.
Ac receptacles Four standard IEC320-C13 female outlets (receptacles). Audible noise <45dBA @ 1m under all operating conditions. Isolation and grounding 100% isolation between input dc and output ac
(isolation transformer included). Metal enclosure is bonded to dc input terminal block Earth Ground input.
PhysicalDimensions 406mm(16”)wide x 381mm(15”)deep x 89mm(3.5”)high (2U high)
Weight 12 kg(26 lbs) 18 kg(38 lbs) Rack or wall mountingkits (optional),23/24” also available
19 Inch Front rack-mount kit: MK-5019A 19 Inch Center rack-mount kit: MK-5019F Wall or Floor mount kit: MK-5000C
SafetyAgency approvals Designed to meet IEC 60950 safety standards. Dc breaker Protection against shorts or misapplication of inverter current. Low voltage disconnect Inverter turns off automatically if input dc voltage drops below 21vdc. Overload shutdown Inverter turns off automatically if overload is >120% for over 1 minute.
EnvironmentalAmbient temperature -20o to +40oC(-4o to +104oF). 10 to 95% relative humidity
(non-condensing). Storage temp. -20o to +60oC(-4o to +140oF).Cooling method Forced air (internal hot air exhaust fan is included). Elevation 0 to 4,000 meters (0 to 12,400 feet) above sea level.
WarrantyWarranty Two year limited depot warranty, parts and labor.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Rack-mountableheavy-duty PWMdc to ac inverter
XINv XINv
Power with a Precision Attitude™
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv SeriesRack-mountable 24vdc to 230vac Inverter
195
L
N
XINv output230vac +/-3%
microprocessor
dc input21–29vdc isolation transformer
ground
ac
dc
dc to ac inverter
chassis groundearth groundgnd
neutral–ground bondon transformer output
DB9 port forcommunications
dc circuit breaker
output ac via four standard IEC320-C13 female outlets(receptacles)(115V NEMA 5-15R receptacles shown)
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv XINv
dc input circuit breaker
DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)
dc input terminalblock connector
recessed on/off switch
dc input voltagelevel: 20% per LED
rear view
output current level: 20% per LED
inverter On
overload condition
XINv-600E/900E-24V system architecture
front-right view
196 XINv SeriesXINv-600E/900E-24vdc-230vac
XINv-600E-900E-24vdc-230vac-Inverter-2006-10-16.pdf
XINv-600E/900E-24V at a glanceRack or wall-mountable heavy-duty PWM dc to ac inverterwith isolation transformer and +/- 3% voltage regulation
• High performance microprocessor-controlled PWM sine wave output24vdc to 230vac inverter
• Pure sine wave output• Isolation transformer• Rack-mountable 2U high metal
cabinet allows for rack or wall mounting using optional mounting kits
• 230vac +/-3% standard output can be set to a 200, 220 or 240vac output at the factory
• Four IEC320-C13 female outlets• +/-24vdc terminal block
connection with dc circuit breaker • DB-9 signal port with RS-232
and relay contact signals• SNMP compatible
with optional SNMP adapter
Specification Connector pin Switching condition DB9 port function (Please note: relay contact is rated for 48vac/vdc, 1A maximum).
Remote shutdown 1 For remote shutdown A +5vdc to +12vdc signal sent to pin#1 for three full seconds will shut down the inverter remotely. Note: this operation requires manual restart.
Transmit data 2 TXD RS-232 signal RS-232 signal line
Receive data 3 RXD RS-232 signal RS-232 signal line
Custom or future use 4 Unused For future use.
Ground 5 Ground Logic ground for pins 1 through 4.
Inverter On 6 + 7 Inverter on/off (Relay Contact)
Closed when inverter is on, Open when inverter is off.
Low battery alarm 8 + 9 Low battery alarm (relay contact)
Open when dc is okay. Closed when input source (battery voltage) drops below 21.5vdc.
RS-232C serial communication for inverter status communicationcompatible with MEGATEC Communication Protocol, Part 1
Baud rate 2400bps
Data length 8 bits
Stop bit 1 bit
Parity None
SNMP interface (optional)SNMP interface for inverter monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the inverter can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external inverter monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
XINv XINv
Rack-mountableheavy-duty PWMdc to ac inverter
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv SeriesRack-mountable 48vdc to 115vac Inverter
197
XINv-400/700/1400-48V ~ 400/700/1400VA, 400/700/1400W, 48vdc to 115vac
XINv model400-48V
400 VA400 watts+/-48 vdc input115 vac output
700-48V 700 VA700 watts+/-48 vdc input115 vac output
1400-48V 1400 VA1400 watts+/-48 vdc input115 vac output
Pure sine wave PWM dc to ac inverter Voltage regulation + isolation
These heavy-duty XINv Series dc to ac inverters are housed in a 2U rack-mountable enclosure. XINv PWM inverters feature a transformer isolated sine wave output. They are designed for all applications requiring continuous pure sine wave power. They produce 115 volts ac from 48 volts dc.
Key XINv benefitsXINv uses high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuits for high efficiency and low input dc ripple currents. They also feature high dc to ac power conversion efficiency, pure sine wave output and long MTBF. XINv also provides precision automatic voltage regulation with 115vac +/-3% and less than 5% THD. XINv’s 2U high construction with optional wall or rack-mounting kits provides maximum flexibility for telecom and industrial users. XINv offers a hardwire terminal block battery connection with a dc circuit breaker for external 48vdc battery banks.
How the XINv WorksA rugged, high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuit takes the dc input and converts it into a pure sine wave. The circuitry automatically adjusts the duty cycle of the output for all loads and inputs. XINv delivers a stable 60Hz +/-0.5% frequency. A dc circuit breaker protects all dc circuits, and an overload shutdown feature protects the inverter from overload. If the input dc voltage drops below 42vdc, a DB9 connector in the rear of the inverter sends signals for inverter output failure & low dc input voltage. A comprehensive array of output current, battery charge levels, and status LED indicators are provided for visual assessment of inverter status. A DB-9 port is provided for communication using RS-232 or dry relay contact signals.
Rack-mountable Dc to Ac Inverter
Typical XINv applications Applications include all waveshape sensitive equipment such as telecommunications systems, industrial, measurement and other mission-critical, harmonic-sensitive electronics. They are also ideal for use in facilities with 48vdc rectifier/battery power plants, where the inverter can be used to provide the function of a double-conversion on-line UPS.
Key XINv features• Pure sine wave inverter output• Eight NEMA 5-15R receptacles• Rack or wall mountable
with optional rack/wall-mount kits • Unipolar PWM inverter• Ac output is isolated from dc • +/-3% voltage regulation• Comprehensive array of
status LEDs/bargraphs • SNMP compatible via RS-232
port with optional SNMP adapter• Both RS-232 and relay
contact signals are provided• Very low audible noise• Rugged construction supports
mobile and portable applications• Two year limited warranty
parts and labor
XINv XINv
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
198 SpecificationsXINv-400/700/1400-48vdc-115vac
Specification XINv-400-48V XINv-700-48V XINv-1400-48V Electrical
Capacity in VA (watts) 400VA (400W) 700VA (700W) 1400VA (1400W)Inverter type Pulsed-width-modulated (PWM) with isolation transformer.
Input Nominal voltage -48 volts dc or +48 volts dc
Operating voltage 42 to 56 volts dc Maximum input current 25 amps 40 amps 75 amps
Dc input connector 3 screw terminal block for earth ground, (+), (-) dc Inputs. Recommended wire 10mm2(8 AWG) 15mm2(6 AWG) 25mm2(4 AWG) Output
Ac output voltage 115 volts +/-3% ac (factory settable to 100, 110 or 120vac) Frequency stability 60Hz +/- 0.5%Output waveform Pure sine wave. Less than 5% maximum THD for 0 to 100% loads. Load compatibility All linear and non-linear loads from -0.6 (leading) to +0.6 (lagging)
power factor, including new power-factor corrected switchmode power supplies and older non-power-factor corrected power supplies.
Load crest factor Up to 3:1 crest factor loads can be powered by the inverter. Surge current capability
Up to 300% surge power is available from the inverter to power load equipment with high starting/stopping surge currents for a few ac cycles.
Overload capability 1 minute @ 120% overcurrent. Power efficiency Greater than 85% under all load and dc input voltage conditions. Power on/off switch Recessed on/off rocker style power switch. Communications Rear-mounted DB-9 female signal port. Status indicators Dc input voltage indicator: 5 green LEDs (25% per each LED).
Ac output current: 5 green LEDs (25% per each LED). Inverter On: 1 yellow LED illuminates during normal inverter operation. Overload: 1 red LED illuminates if overload condition exists.
Ac receptacles Eight standard NEMA 5-15R female receptacles. Audible noise <45dBA @ 1m under all operating conditions. Isolation and grounding 100% isolation between input dc and output ac
(isolation transformer included). Metal enclosure is bonded to dc input terminal block earth ground input.
PhysicalDimensions 406mm(16”)wide x 381mm(15”)deep x 89mm(3.5”)high (2U high)Weight 10 kg(22 lbs.) 12 kg(26 lbs.) 18 kg(38 lbs.)Rack or wall mountingkits (optional)
19 Inch Front or Rear rack-mount kit: MK-5019A 19 Inch Center rack-mount kit: MK-5019F Wall or Floor mount kit: MK-5000C
SafetyAgency approvals Designed to meet IEC 60950 Safety Standards. Dc breaker Protection against shorts or misapplication of inverter current. Low voltage disconnect Inverter turns off automatically if input dc voltage drops below 42vdc. Overload shutdown Inverter turns off automatically if overload is >120% for over 1 minute.
EnvironmentalAmbient temperature 0o to +40oC(32o to +104oF). 5 to 95% RH non-condensing.
Storage temp. -20o to +60oC(-4o to +140oF). Cooling method Forced air (internal hot air exhaust fan is included). Elevation -200 to 3000 meters (-656’ to 9842’) with respect to sea level.
WarrantyWarranty Two year limited depot warranty, parts and labor.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Rack-mountableheavy-duty PWMdc to ac inverter
XINv XINv
Power with a Precision Attitude™
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv SeriesRack-mountable 48vdc to 115vac Inverter
199
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv XINv
dc input circuit breaker
output ac via eight standard NEMA 5-15R receptacles
DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)
dc input terminalblock connector
recessed on/off switch
dc input voltagelevel: 20% per LED
rear view
output current level: 20% per LED
inverter On
overload condition
L
N
XINv output115vac +/-3%
dc input42–56vdc isolation transformer
ground
ac
dc
chassis groundearth groundgnd
neutral-ground bondon transformer output
N
dc to ac inverter
microprocessor
DB9 port forcommunications
dc circuit breaker
XINv-400/700/1400-48v system architecture
front-right view
200 XINv SeriesXINv-400/700/1400-48vdc-115vac
XINv-400-700-1400-48vdc-115vac-Inverter-2006-10-16.pdf
XINv-400-700-1400-48V at a glanceRack or wall-mountable heavy-duty PWM dc to ac inverterwith isolation transformer and 115vac +/- 3% voltage regulation
• High performance microprocessor-controlled PWM sine wave output+/-48vdc to 115vac inverter
• Pure sine wave output• Isolation transformer• Rack-mountable 2U high metal
cabinet allows for rack or wall mounting using optional mounting kits
• 115vac +/-3% standard output can be set to a 100, 110 or 120vac output at the factory
• Eight NEMA 5-15R receptacles• +/-48vdc terminal block
connection with dc circuit breaker • DB-9 signal port with RS-232
and relay contact signals• SNMP compatible
with optional SNMP adapter
Specification Connector pin Switching condition DB9 Port Function (Please note: relay contact is rated for 48vac/vdc, 1A maximum).
Remote shutdown 1 For remote shutdown A +5vdc to +12vdc signal sent to pin#1 for three full seconds will shut down the inverter remotely. Note: this operation requires manual restart.
Transmit data 2 TXD RS-232 signal RS-232 signal line
Receive data 3 RXD RS-232 signal RS-232 signal line
Custom or future use 4 Unused For future use.
Ground 5 Ground Logic ground for pins 1 through 4.
Inverter On 6 + 7 Inverter On/Off (Relay contact)
Closed when inverter is On, Open when inverter is Off.
Low battery alarm 8 + 9 Low battery alarm (Relay contact)
Open when dc is okay. Closed when input source (battery voltage) drops below 43vdc.
RS-232C serial communication for inverter status communicationcompatible with MEGATEC Communication Protocol, Part 1
Baud rate 2400bps
Data length 8 bits
Stop bit 1 bit
Parity None
SNMP interface (optional)SNMP interface for inverter monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the inverter can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external inverter monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
XINv XINv
Rack-mountableheavy-duty PWMdc to ac inverter
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv SeriesRack-mountable 48vdc to 230vac Inverter
201
XINv-400E/700E/1400E-48V ~ 400/700/1400VA, 400/700/1400W, 48vdc to 230vac
XINv model400E-48V
400 VA400 watts+/-48 vdc input230 vac output
700E-48V 700 VA700 watts+/-48 vdc input230 vac output
1400E-48V 1400 VA1400 watts+/-48 vdc input230 vac output
Pure sine wave PWM dc to ac inverter Voltage regulation + isolation
These heavy-duty XINv Series dc to ac inverters are housed in a 2U rack-mountable enclosure. XINv PWM inverters feature a transformer isolated sine wave output. They are designed for all applications requiring continuous pure sine wave power. They produce 230 volts ac from 48volts dc.
Key XINv benefitsXINv uses high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuits for high efficiency and low input dc ripple currents. They also feature high dc to ac power conversion efficiency, pure sine wave output and long MTBF. XINv also provides precision automatic voltage regulation: of 230vac +/-3% and less than 5% THD. XINv’s 2U high construction with optional wall or rack-mounting kits provides maximum flexibility for telecom and industrial users. XINv offers a hardwire terminal block battery connection with a dc circuit breaker for external 48vdc battery banks.
How the XINv worksA rugged, high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuit takes the dc input and converts it into a pure sine wave. The circuitry automatically adjusts the duty cycle of the output for all loads and inputs. XINv delivers a stable 50Hz +/-0.5% frequency. A dc circuit breaker protects all dc circuits, and an overload shutdown feature protects the inverter from overload. If the input dc voltage drops below 42vdc, a DB9 connector in the rear of the inverter sends signals for inverter output failure and low dc input voltage. A comprehensive array of output current, battery charge levels, and status LED indicators are provided for visual assessment of inverter status. A DB-9 port is provided for communication using RS-232 or dry relay contact signals.
Rack-mountable Dc to Ac Inverter
Typical XINv applications Applications include all waveshape sensitive equipment such as telecommunications systems, industrial, measurement and other mission-critical, harmonic-sensitive electronics. They are also ideal for use in facilities with 48vdc rectifier/battery power plants, where the inverter can be used to provide the function of a double-conversion on-line UPS.
Key XINv features• Pure sine wave inverter output• Eight IEC320 receptacles• Rack or wall mountable
with optional rack/wall-mount kits • Unipolar PWM inverter• Ac output is isolated from dc • +/-3% voltage regulation• Comprehensive array of
status LEDs/bargraphs • SNMP compatible via RS-232
port with optional SNMP adapter• Both RS-232 and relay
contact signals are provided• Very low audible noise• Rugged construction supports
mobile and portable applications• Two year limited warranty
parts and labor
XINv XINv
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
202 SpecificationsXINv-400E/700E/1400E-48vdc-230vac
Specification XINv-400E-48V XINv-700E-48V XINv-1400E-48V Electrical
Capacity in VA (watts) 400VA (400W) 700VA (700W) 1400VA (1400W)Inverter type Pulse-width-modulated (PWM) with isolation transformer.
Input Nominal voltage -48 volts dc / +48 volts dc
Operating voltage 42 to 56 volts dc Maximum input current 25 amps 40 amps 75 amps
Dc input connector 3 Screw Terminal Block for Earth Ground, (+), (-) dc Inputs. Recommended wire 10mm2(8 AWG) 15mm2(6 AWG) 25mm2(4 AWG) Output
Ac output voltage 230 volts +/-3% ac (Factory settable to 200, 220 or 240vac) Frequency stability 50 Hz +/- 0.5% Output waveform Pure sine wave. Less than 5% maximum THD for 0 to 100% loads. Load compatibility All linear and non-linear loads from -0.6 (leading) to +0.6 (lagging)
power factor, including new power-factor corrected switchmode power supplies and older non-power-factor corrected power supplies.
Load crest factor Up to 3:1 crest factor loads can be powered by the inverter. Surge current capability
Up to 300% surge power is available from the inverter to power load equipment with high starting/stopping surge currents for a few ac cycles.
Overload capability 1 minute @ 120% overcurrent. Power efficiency Greater than 85% under all load and dc input voltage conditions. Power On/Off switch Recessed On/off rocker style power switch. Communications Rear-mounted DB-9 female signal port. Status indicators Dc input voltage indicator: 5 green LEDs (25% per each LED).
Ac output current: 5 green LEDs (25% per each LED). Inverter On: 1 yellow LED illuminates during normal inverter operation. Overload: 1 red LED illuminates if overload condition exists.
Ac receptacles Four standard IEC320-C13 female outlets (receptacles). Audible noise <45dBA @ 1m under all operating conditions. Isolation and grounding 100% isolation between input dc and output ac
(isolation transformer included). Metal enclosure is bonded to dc input terminal block Earth Ground input.
PhysicalDimensions 406mm(16”)wide x 381mm(15”)deep x 89mm(3.5”)high (2U high)Weight 10 kg(22 lbs.) 12 kg(26 lbs.) 18 kg(38 lbs.)Rack or wall mountingkits (optional)
19 Inch Front or Rear rack-mount kit: MK-5019A 19 Inch Center rack-mount kit: MK-5019F Wall or Floor mount kit: MK-5000C
SafetyAgency approvals Designed to meet IEC 60950 Safety Standards. dc breaker Protection against shorts or misapplication of inverter current. Low voltage disconnect Inverter turns off automatically if input dc voltage drops below 42vdc. Overload shutdown Inverter turns off automatically if overload is >120% for over 1 minute.
EnvironmentalAmbient temperature 0o to +40oC(32o to +104oF). 5 to 95% RH non-condensing.
Storage temp. -20o to +60oC(-4o to +140oF). Cooling method Forced air (internal hot air exhaust fan is included). Elevation -200 to 3000 meters (-656’ to 9842’) with respect to sea level.
WarrantyWarranty Two year limited depot warranty, parts and labor.
TSi’s ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.
Rack-mountableheavy-duty PWMdc to ac inverter
XINv XINv
Power with a Precision Attitude™
Specifications
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
XINv SeriesRack-mountable 48vdc to 230vac Inverter
203
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
L
N
XINv output230vac +/-3%
microprocessor
dc input42–56vdc isolation transformer
ground
ac
dc
dc to ac inverter
chassis groundearth groundgnd
neutral–ground bondon transformer output
DB9 port forcommunications
dc circuit breaker
output ac via four standard IEC320-C13 female outlets(receptacles)(115V NEMA 5-15R receptacles shown)
XINv XINv
dc input circuit breaker
dc input terminalblock connector
recessed on/off switch
dc input voltagelevel: 20% per LED
rear view
output current level: 20% per LED
inverter On
overload condition
XINv-400E/700E/1400E-48V system architecture
front-right view
DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)
204 XINv SeriesXINv-400E/700E/1400E-48vdc-230vac
XINv-400E-700E-1400E-48vdc-230vac-Inverter-2006-10-16.pdf
XINv-400E/700E/1400E-48V at a glanceRack or wall-mountable heavy-duty PWM dc to ac inverterwith isolation transformer and +/- 3% voltage regulation
• High performance microprocessor-controlled PWM sine wave output+/-48vdc to 230vac inverter
• Pure sine wave output• Isolation transformer• Rack-mountable 2U high metal
cabinet allows for rack or wall mounting using optional mounting kits
• 230vac +/-3% standard output can be set to a 200, 220 or 240vac output at the factory
• Four IEC 320-C13 female outlets• +/-48vdc terminal block
connection with dc circuit breaker • DB-9 signal port with RS-232
and relay contact signals• SNMP compatible
with optional SNMP adapter
Specification Connector pin Switching condition DB9 port function (Please note: relay contact is rated for 48vac/vdc, 1A maximum).
Remote shutdown 1 For remote shutdown A +5vdc to +12vdc signal sent to pin#1 for three full seconds will shut down the inverter remotely. Note: this operation requires manual restart.
Transmit data 2 TXD RS-232 signal RS-232 signal line
Receive data 3 RXD RS-232 signal RS-232 signal line
Custom or future use 4 Unused For future use.
Ground 5 Ground Logic ground for pins 1 through 4.
Inverter on 6 + 7 Inverter On/Off (Relay Contact)
Closed when inverter is On, Open when inverter is Off.
Low battery alarm 8 + 9 Low battery alarm (Relay contact)
Open when dc is okay. Closed when input source (battery voltage) drops below 43vdc.
RS-232C serial communication for inverter status communicationcompatible with MEGATEC Communication Protocol, Part 1
Baud rate 2400bps
Data length 8 bits
Stop bit 1 bit
Parity None
SNMP interface (optional)SNMP interface for inverter monitoring andautomatic shutdown configuration (optional)
Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the inverter can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external inverter monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).
XINv XINv
Rack-mountableheavy-duty PWMdc to ac inverter
Power with a Precision Attitude™
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
White Paper SeriesTSi Power White Papers On Power Protection
205
White Paper SeriesTSi White Papers on Power Protection
White Paper Series ~ TSi Power White Papers on Power Protection
Power with a Precision Attitude™
WhiteWhitePaperPaper
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
206 White Paper SeriesTSi Power White Papers On Power Protection
WP-White-Paper-Series-2006-10-16.pdf
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
White Paper SeriesCoordination of Telecommunications Surge Protective Devices In Countries With
207
Coordination of TelecommunicationsSurge Protective Devices in Countries with Unstable Ac Power
ZONED PROTECTION STRATEGY
AbstractThe rapid growth of the world market for telecommunications equipment will continue for the next several years. Manufacturers of radio infrastructure and switching equipment are based in the USA, Europe and Japan with some minor exceptions. Yet, these manufacturers are often not familiar with power quality in places far away from their home countries. The needs for surge protective devices vary from market to market and are especially challenging in the emerging countries. Why? Surge protection in the USA and Europe is based on the assumption that the ac power-line voltage is relatively stable. Developing countries, however, often have inadequate infrastructures for the generation and distribution of electric power. The lack of stable ac power complicates the selection and coordination of surge protective devices considerably. This paper will review the new IEC surge protection standards and discuss how to achieve coordination of surge protective devices in accordance with IEC 1312 principles.
Coordination of Telecommunications SPDs in Countries with Unstable Power
WhiteWhitePaperPaper
Power Protection in Countries with Unstable Ac Mains Voltages
AuthorPeter NystromPresidentTSi Power Corp
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
208 White Paper SeriesCoordination of Telecom Surge Protective Devices In Countries With
IntroductionIEC standards are used throughout Europe and in many other parts of the world. CE marking is based on such IEC standards. CE marking involves both equipment safety and electromagnetic compatibility while UL only involves safety. Thus, all electronic equip-ment that carry the CE label should have been tested to withstand static electricity, electric fast transients and surge voltages. This paper will focus on the surge voltage aspects.
IEC 1000-4-5 is a Combination Wave consisting of a voltage waveform of 1.2/50 µs with an amplitude of 2000 V in normal mode and 4000 V in common mode, and a current wave form of 8/20 µs at 2000 A. The Combination Wave is identical to the U.S. ANSI/IEEE C62.41-1991 Combination Wave with the following exceptions: the ANSI/IEEE voltage is 6000 V and the current is 3000 A.
In the IEC standard, the equipment that is tested for surge immunity is referred to as the "vulnerable equipment." Hence, the term "vulnerable equipment" will be used in this paper. All "vulnerable equipment" must be able to withstand IEC 1000-4-5 without upset, thus guaranteeing a certain level of surge immunity, which will be sufficient for most office environments. IEC has developed a series of standards that apply to enhanced surge protection of equipment and structures in cases where built-in equipment surge immunity is not sufficient. Telecom installations in outdoor shelters and enclosures are good examples of when enhanced surge immunity is required.
This paper will review key aspects of the following IEC standards:
• IEC 1024-1: 1990 Protection of Structures Against Lightning -- Part 1: General Principles
• IEC 1312-3: Protection Against Electromagnetic Impulse -- Part 3: Requirements of Surge Protective Devices.
SPECIAL PROBLEMS IN DEVELOPING COUNTRIES
Fluctuating power line voltageCauses
Overloaded, inadequate power generation and distribution systems, particularly when large step load changes are present, result in large voltage sags and surges. Voltage fluctuations between 155V to more than 310V have been observed in the field. Differences between day- and night-time voltage of 40V have also been observed.
Such conditions are common in Africa, India, Pakistan and China, but can be found in many other areas. Additional power plants and distribution infrastructure is needed in many developing countries. Timely power plant expansion is prevented by political and economic issues, which means the problem is here to stay for the foreseeable future.
Effects• Sags and undervoltages can cause component overheating or destruction,
which reduces the life and deteriorates the real reliability as opposed to the estimated reliability, based on steady-state conditions of the power supply
• Swells and overvoltages can cause component overheating and destruction of MOVs, SCRs and input capacitors that are rated too close to the line voltage. It is fairly common for power supply and telecom rectifier manufacturers to rate
White Paper SeriesCoordination of Telecom Surge Protective Devices In Countries With Unstable Ac
209
input MOVs at 275Vrms with the apparent objective of reducing the surge remnant voltage, thus providing better surge immunity of the power supply. The author of this paper has observed still-functioning telecom rectifiers where the input MOVs had been completely destroyed by high line voltage.Boost converters can be destroyed by voltage swells that cause increased energy storage in the input filter, which charges the output capacitor to an unsafe level. The charge level is dependent on the value of the output capacitor and the load levels for the dc to dc converter connected to the output of the boost converter.
• Poorly damped EMI filters can dramatically magnify the effects of voltage disturbances. The result can be oscillations inside the EMI filter during transi-tional conditions. Severe voltage surges may result from energy released when saturated inductors are looking for a path to release energy.
Frequent lightning conditionsReview of IEC 1024-01This standard relates to the protection of structures against lightning. A structure can be anything from a high rise building to an outdoor shelter containing telecommunica-tions equipment. IEC 1024 introduces the concept of Lightning Protection Zones (LPZ). Figure 1 below illustrates the basic zone concept.
Figure 1
The purpose of LPZs is to divert the surge energy from lightning and other disturbances away from the "vulnerable equipment." The majority of the energy should be diverted at the lowest zone boundaries. The number of required zones is determined by the physi-cal properties of the structure and the sensitivity of the "vulnerable equipment."
210 White Paper SeriesCoordination of Telecom Surge Protective Devices In Countries With
Sensitive equipment installed in outdoor shelters, particularly when a poor physical ground is present, require a higher number of zones. Basic Lightning Protection Zones and surge current waveforms are explained below:
LPZ 0A
This zone is subject to direct lightning strokes and may have to carry the full lightning current. The unattenuated electromagnetic field occurs here.
100 kA, 10/350 µs 200 A, 0.5 s 25 kA, 0.25/100 µs
Figure 2 shows a comparison between the 10 x 350 µs test waveform and lower-energy Combination Wave.
Figure 2
LPZ 0B
This zone is not subject to direct lightning strokes. The unattenuated electromagnetic field occurs here.
10 kV, 1.2/50 µs 5 kA, 8/20 µs
LPZ 1This zone is not subject to direct lightning strokes and currents on all conductive parts within this zone are further reduced from previous zones. The electromagnetic field may also be attenuated depending on the screening measures.
White Paper SeriesCoordination of Telecom Surge Protective Devices In Countries With Unstable Ac
211
LPZ 2When a further reduction of conducted currents and/or magnetic field is required, subsequent zones can be introduced.
In general, the higher the number of zones, the lower the electromagnetic environment parameters.
LPZ 3According to the author’s interpretation of IEC standards, this zone should contain the protected equipment. The requirement for Zone 3 is that the remnant surge voltage does not exceed the test levels specified in IEC 1000-4-5:
Combination Wave, 1.2/50 µs, 8/20 µs 2000 A
Normal-Mode Voltage: 2000 V
Common-Mode Voltage: 4000 V
Review of IEC 1312-3
Lightning surges contain significant amounts of energy which needs to be diverted away from the "vulnerable equipment." Electronic equipment, if CE marked, is designed with a certain built-in surge voltage immunity in accordance with IEC 1000-4-5 — this level of immunity will be sufficient for the majority of office buildings when the "vulnerable equipment" is located far away from the electric service entrance. Thus, equipment that carries the CE mark will work well without surge protection in many environments.
However, when the "vulnerable equipment" is installed close to the electric service entrance, or in an outdoor enclosure, particularly in areas with a poor physical ground (dry sand, rock, etc.), it is often necessary to add external surge protective devices (SPDs). IEC recommends (IEC 1024) that lightning protection zones (LPZ) be established to successively reduce lightning currents, in stages, down to the built-in immunity of the "vulnerable equipment." The number of zones required depends on the structure containing the installation and the "vulnerable equipment." IEC 1024 requires that an SPD be installed at each zone boundary. The surge current and voltage ratings of individual SPDs must not be exceeded.
Purpose of coordinationTo progressively reduce the lightning threat, in stages (SPD 1, 2 & 3) down to the surge withstand capability of the "vulnerable equipment," without exceeding surge current and voltage ratings of individual SPDs.
Coordination conceptsIEC 1312 defines four coordination "variants." The first three utilize individual single-port SPDs while the fourth variant is a two-port hybrid design.
Variant IShown in figure 3, the rated voltage of SPDs is identical and coordination is achieved by separating each SPD by means of series impedance.
212 White Paper SeriesCoordination of Telecom Surge Protective Devices In Countries With
Figure 3
Variant I is not recommended by the IEC, probably because it would require approximately 30’ (10 m) of wire or separate inductors between each SPD, which is not practical when installing equipment close to the electric service entrance or in outdoor enclosures.
Variant IIShown in figure 4, the rated voltages of SPD's are stepped so that the SPD in the "vulnerable equipment" has the highest rated voltage and SPD 3, 2 & 1 have progressively lower rated voltages, thus assuring that each upstream SPD would divert progressively higher currents.
Figure 4
Variant II is difficult to implement as most power supplies, uninterruptible power systems and telecom rectifiers, rated for 230 Vac, use input SPDs with a 275 Vrms rating. Thus, stepping down rated voltage, would cause SPD 1 and 2 to be destroyed by normal line voltage fluctuations-experience has shown that fluctuations of plus 10% resulting in 250V is not unusual.
White Paper SeriesCoordination of Telecom Surge Protective Devices In Countries With Unstable Ac
213
Variant IIIShown in figure 5, includes a component with a non-linear current/voltage characteristic, such as a spark gap. The SPD 1 spark gap would divert the majority of the surge current and output a Combined Wave, similar to ANSI/IEEE C62.41-1991, Category B3, Combination Wave, 3000 A, 6000 V, to downstream SPDs 2 and 3. The voltage ratings of SPD 2 and 3 are identical, but each device will handle considerably less current due to the much higher energy handling capability of spark gap SPD 1.
Figure 5
Variant III is a better choice than I or II as the spark gap is insensitive to fluctuations in line voltage. However, spark gap follow-on, short-circuit current may be an issue, and MOVs will still be sensitive to line voltage fluctuations.
Variant IV
Figure 6
Figure 6 shows a two-port hybrid device that incorporates cascaded stages of SPDs internally coordinated with series impedance.
214 White Paper SeriesCoordination of Telecom Surge Protective Devices In Countries With
A hybrid device can be designed to maximize performance while reducing the undesirable characteristics of spark gaps and SPDs based on varistor or silicon-avalanche-diode technology. The use of a hybrid device eliminates the need to coordinate surge protective devices, but does not eliminate sensitivity to prolonged ac overvoltage.
Proposed hybrid device in accordance with Variant IVThe purpose of the circuit shown in figure 7 below is to provide, in a condensed space, the critical functions required for a universal ac power interface used in outdoor shelters for cellular, fixed wireless and other telecom equipment. The major functions required are out-lined below:
• Surge protective device coordination for successive reduction of surge currents,• High energy handling capability,• Tolerance against high line voltage,• Adjustment for local nominal voltage variation,• Low dv/dt rise time,• Function not dependent on performance of internal protection of "vulnerable
equipment."
Figure 7
Discussion of circuit features shown in figure 7The protection scheme is designed to work with an outdoor equipment shelter even when "vulnerable equipment" uses 275V MOVs as internal protection. In this case it is impossible to provide coordination in accordance with Variant II and Variant I is not practical, because the required wiring distances of 30’ between SPD's are too short in an outdoor equipment shelter.
The spark gap is designed to provide primary protection within LPZ 0 and ignites when the surge voltage reaches approximately 2000V. The series inductance provided introduces the necessary coordination and reliable ignition of the spark gap. The output of the spark gap is a Combination Wave and is easily handled by the circuits in LPZ 1 and 2. Spark gaps can handle considerably more energy than MOV or SAD arrays and are not sensitive to line voltage fluctuations and are also more cost effective. The major disadvantage of a spark gap is the follow-on current which can cause tripping of upstream circuit protection devices. However, new-technology spark gaps based on the arc-chopping principle provide significant performance improvements.
White Paper SeriesCoordination of Telecom Surge Protective Devices In Countries With Unstable Ac
215
The new spark gap technology shown in figure 8 consists of two electrodes positioned opposite each other, held in place by a barrier and separated by a baffle. This arrange-ment and spacing of electrodes is called "arc chopping" and provides reliable ignition of the arc, which is then chopped by the baffle into several smaller arcs. Special versions with reduced follow-on current are available for branch circuits and services up to 75 kVA.
The neutral-to-ground bond provided at the service entrance or by a separate isolation transformer eliminates all surge voltages between neutral and ground and the requirement for SPD's between power carrying conductors and ground.
The series inductor with primary buck-boost windings provides static adjustment for different nominal voltages that can range from 200 to 250 V. The buck-boost windings can also be controlled automatically if the line voltage is chronically unstable. The series inductor also forms a two-pole filter together with the shunt capacitor. The filter reduces the surge voltage rise time (dv/dt) from 6 kV/µs to 10 V/µs thus providing considerable relief for the "vulnerable equipment." The filter which starts conduction well before MOV 1 also provides protection against electric fast transients and other line noise.
MOV 1, located within LPZ 2, is a 40-mm device rated for 275 Vrms, which is made possible due to the voltage adjustment provided by the buck-boost windings on the primary of the series inductor. In other words, MOV 1 is well-protected against premature failure caused by high nominal voltages. Now available in attractive packaging, easy-to-replace MOVs provide thermal disconnect and alarms in case of failure.
Figure 8
216 White Paper SeriesCoordination of Telecom Surge Protective Devices In Countries With
WP-Coordination-Telecom-SPDs-Unstable-Power-2006-10-16.pdf
SummaryThis paper has reviewed IEC 1024 and 1312 standards for protection of structures against lightning and for coordination of surge protective devices (SPDs). Line voltage fluctuations outside of the typical regulation window of most power supplies have been observed in many developing countries. Methods for designing an economical power interface which provides hybrid surge protection for demanding international applications have been discussed. The hybrid circuit provides full coordination of SPDs while being tolerant to line voltage fluctuations.
About the Author:
Mr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation (located in the state of Wisconsin, USA), a manufacturer of UPS, line conditioner, automatic voltage regulator, automatic transfer switches and dc to ac inverter systems designed to meet the challenging international power conditions.
Copyright held by Intertec International, Inc. Originally published in the Power Quality ‘97/Power Value ’97 Proceeding for the POWER SYSTEMS WORLD ’97 Conference held in Baltimore, MD September 1997.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
White PaperTSi Power Case Studies: Mission-Critical Solutions
217
TSi Power Case Studies
Mission-critical solutions
TSi UPS systems back-up signal transmitters that send critical flight information to all airplanes approaching any airport for landing.
TSi Power supplies Federal Aviation Administration with UPSSince 1991, TSi Power has been providing the Federal Aviation Administration (FAA) with UPS systems designed to provide 6 to 8 hours of battery back-up time in hostile environments. The TSi UPS systems back-up signal transmitters that send critical flight information to all airplanes approaching any airport for landing. The transmitters & UPS systems are housed in unmanned and non- air-condi-tioned equipment huts that are subject to extreme temperature swings between winter and summer. Several hundred systems were installed nationwide and have been operational since 1991 with minimal field problems. The FAA was so impressed with their performance that they have continued to install our UPS systems at hundreds of sites. So if you have a system that is exposed to harsh conditions, then a rugged TSi UPS is your solution!
TSi Power backs up White House telecommunications system with UPS and ARm-1000 automatic transfer switches
There is no more mission critical communications system than the Presidential telecommunications system run by the State Department. It is responsible for rout-ing and tracking all telecommunications between the White House and the world. This system is backed up with both a TSi Power UPS system and a large genera-tor UPS system to provide back-up power redundancy. In case of a problem with the primary ac source, TSi Power’s ARM-1000 Automatic Redundancy Module automatically detects the failed ac line and seamlessly transfers to another ac source without interruption. In the most unlikely event that even the back-up ac source is also defective, a second ARM-1000 can automatically select the second back-up ac source. There is no limit to the levels of redundancy that can be applied to these mission critical systems. By using multiple ARM-1000 units, as many layers of independent power back-up can be achieved as there are power sources available. Independent power sources include battery back-up, alternate utility circuit (from a different power grid), and emergency ac generator sets to name a few. If your system is truly mission critical, then TSi Power has the solu-tion!
TSi Power ~ Case Studies Of Mission-Critical Solutions
Author Nam Paik TSi Power Corp
WhiteWhitePaperPaper
TSi Power Case Studies ~ Mission-critical Solutions
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
218 White PaperTSi Power Case Studies: Mission-Critical Solutions
The drugs stores’ point-of-sale (POS) computers equipped with these UPS systems continued to operate and record unprecedented sales because all the other drug stores were shut down.
The United States Army relies on TSi Power ac line conditioners for demanding international applications in the field
Having access to accurate and timely information is the key to success in any field in the world, and the Armed Forces are no exception. In 1997, the U.S. Army was dispatched to Bosnia to serve as part of a peacekeeping force to help end the brutal conflict engulfing that region. Army Intelligence, which was responsible for gathering, disseminating and forwarding vast quantities of information to the peacekeeping forces, ran into some problems. During much of their operation, utility power was unavailable. They also found that their UPS technology was not capable of handling the large numbers of spikes, surges, sags and brownouts that were present on the AC line. As a result, the back-up UPS systems they relied on to maintain their computer networks were actually burning out. When all their UPS were gone, they hooked their computers directly into the field generators set up in their camps. This caused catastrophic computer failure. Since an army with no information is no army at all, the U.S. Army turned to TSi Power to create a quick solution. Within a few weeks, the U.S. Army Intelligence was up and running without fear of burning up their UPS systems or their computers after installation of rugged, generator compatible line conditioners from TSi Power.
Major drug store chain powers through an earthquake with TSi UPSIn 1989, a significant earthquake hit the San Francisco area causing millions of dollars in damage and interrupting the basic utilities for the area residents. Panic gripped many of the residents who immediately went to buy emergency food supplies, candles, flashlights, batteries, etc. TSi Power’s UPS systems were backing up three drug stores in San Francisco at the time of the earthquake. These drug stores were open a full eight hour business day entirely on TSi back-up power. The drugs stores’ point-of-sale (POS) computers equipped with these UPS systems continued to operate and record unprecedented sales because all the other drug stores were shut down. This incident convinced the drug store’s corporate executives that extended battery UPS systems were a necessity for uninterrupted operation of retail stores during emergency situations. TSi has the solution for all retail and service industry power protection and back-up power problems!
Medical equipment manufacturer utilizes TSi Power UPS and battery extension units for patient respirators
A leading manufacturer of medical technologies for critical care patients. Since 1990, a leading intensive patient care respirator manufacturer has been using a customized version of TSi Power’s UPS and Battery Extension Units to provide continuous ac power to respirators of critically ill patients. The respirator and UPS system are attached to the patient’s portable bed and moved around inside the hospital (e.g. from the operating room to the recovery room) by simply unplugging the UPS from the ac socket. In order to meet the stringent European medical equipment safety standards, TSi Power’s engineers worked closely with manufacturer’s engineers to implement the necessary modifications to the existing models.
Applied Energy Concepts, a partner of TSi Power, solves telecommunication problems in emerging markets
In January 1998, TSi Power joined with Applied Energy Concepts to increase its range of power quality products and applications on the market today. Applied Energy Con-cepts develops solutions that control electrical surges and regulate voltage for mis-sion-critical electronic systems.
White PaperTSi Power Case Studies: Mission-Critical Solutions
219
These international applications have included protection for switchmode rectifiers, power supplies and uninterruptible power systems. A major cellular infrastructure supplier’s experience has revealed that conventional surge protection devices have little impact on equipment failures and often fail themselves as a result of inadequate power generation and distribution infrastructures. In thousands of installations worldwide, AEC equipment has proven to consistently reduce high failure rates of telecom rectifiers, UPS, and other equipment connected to the power line. Critical loads such as base transceiver stations (BTS) and nodes for wireless-in-the-local-loop applications as well as other outdoor enclosure installations often require this additional protection.
Constant voltage and isolation of TSi Premium Series UPS key to smooth manufacturing control systems
In 1996, TSi Power was asked to assist a large farming product manufacturer in the middle of Georgia. Nearly one hundred cabinets that control the automated manufacturing equipment had to be manually reset after each power outage (even though they were protected by a well-known, national brand UPS). Each manual reset operation meant a down-time of over one hour for the entire plant and financial losses were piling up quickly, especially during summer months when a number of power outages can occur in a week.
After careful analysis of the problem, TSi engineers concluded that the problem was caused by a lack of voltage regulation, lack of isolation, power conditioning, and long transfer time (to 8 milliseconds) of existing standby UPS units. They recommended the Premium Series UPS-16000 with built in CVT (constant voltage transformer with 100% input/output isolation) and zero transfer time. The result was spectacular. The controller cabinet protected by the TSi Power Premium Series no longer required a manual reset after a power outage while the identical control cabinet powered by the original standby UPS needed a manual reset after each power outage.
By the middle of 1997, the manufacturing plant management decided to replace all of their existing UPS units with TSi Power Premium Series UPS-16000 units. TSi Power is also helping in the disposal of the old standby UPS units that are being replaced since the lead-acid batteries inside the old UPS units must be recycled properly.
Internet service provider keeps the world connected with TSi Power rack-mounted UPS and battery extension units backing them up
In 1996, a leading Internet Service Provider (ISP) began to realize that with increasing frequency of power outages and transients damaging the sensitive equipment in one of their Cisco 7513 routers and other critical communications equipment, it was time to take action. After careful evaluation, they chose TSi Power’s Premium Series rack-mounted UPS, Battery Extension Unit and Automatic/Manual Bypass Unit. In 1998, the ISP is in the process of installing several hundred Premium Series UPS systems in equipment rooms located in all of the major cities in the U.S. This again proves that for Premium Power Protection, customers turn to TSi Power.
About the authorNam Paik ~ Director of Engineering, TSi Power Corporation Mr. Paik has over 15 years experience in the power electronics industry. He was with Northern Telecom (now Nortel Networks) for 4 years prior to joining TSi Power in 1988. Nam has focused on UPS, Line Conditioner and dc to ac inverter products and most recently has developed a number of customized power protection and conversion systems for several U.S. government agencies and international applications.
WP-Case-Studies-TSi-Rev1-2006-10-16.pdf
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
220 White PaperTSi Power Case Studies: Mission-Critical Solutions
This page intentionally left blank.
White Paper SeriesChoosing UPS Protection For Underdeveloped Countries
221
Choosing UPS Protection for Underdeveloped Countries
Facing Unusual Challenges
Problems include: Frequent blackouts & ac mains voltages frequently fluctuate beyond the IEC assumed standard of a 184 to 264vac input range.
I. INTRODUCTION
All electrical and electronic equipment users in underdeveloped countries face unusual difficulties in trying to cope with ac power problems. Among the problems are:
1. Frequent blackouts due to inadequate generation capacity;
2. Wide ac mains voltage variation due to inadequate distribution infrastructure;
3. Generally poor quality of the power, in areas such as distortion, spike/noise, frequency, sags/surges and dropouts, especially when generators are used to supplement utility power.
Of course, these problems also exist in developed countries. However, in underdeveloped countries in Africa, South America and Asia, such power problems can occur so often as to cause unacceptable levels of system down time and catastrophic equipment failures. Also, uninterruptible power supply (UPS) systems, which are installed to mitigate the above-mentioned ac power problems, often exhibit unacceptably high failure rates. Standard UPS systems are designed to meet IEC specifications for a mains ac voltage window of 184 to 264vac, while actual mains voltages quite often vary between 160 to 330vac in many developing countries.
Operating a UPS system outside of its specified ac mains voltage window is one of the pri-mary reasons for premature UPS failure. When the other common power quality problems such as surges, spikes, noise, sags, and frequency problems are also considered, designing a reliable UPS system for underdeveloped countries poses a special challenge to UPS manufacturers.
Choosing UPS Protection for Underdeveloped Countries
Choosing UPS Protection for Underdeveloped Countries
Author Nam Paik Director of EngineeringTSi Power
WhiteWhitePaperPaper
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
222 White Paper SeriesChoosing UPS Protection For Underdeveloped Countries
II. DIFFERENCES IN UPS REQUIREMENTS
Challenges include:Deep and numerous battery discharges, frequency of power disturbances, small generator aberrant output, wide temperature swings, and non-coordinated systems unable to handle lightning.
A standard UPS designed for use in a developed country (such as in the USA) might encounter the following difficulties when installed in underdeveloped countries:
1. Because of frequent blackouts, the batteries in the UPS, whether online or standby, will be discharged and charged very often. Furthermore, because the duration of the blackout is usually longer than in developed countries, the batteries will be more deeply discharged. These two factors combine to drastically reduce the expected lifetime of the battery. For example, a typical lead-acid battery will last for about 1,200 discharge/charge cycles when the depth discharge is 30% of battery capacity. However, when the depth of discharge is 50%, this number is reduced to 450. And when the depth of discharge is 100%, the number is reduced to below 200. A UPS in the U.S. may experience a 100% discharge/charge cycle about 5 to 10 times a year. In underdeveloped countries, this may occur almost every day, reducing the expected life of the UPS to less than a year.
2. Because of the frequency of power disturbances, the power electronic circuitry in the UPS must work far more often and under greater stress. This is especially true for standby UPS systems, which must make the transfer to battery backup every time there is a power disturbance. Even in double-conversion online UPS systems (where transfer to battery is not required), the power transistors and transformers must operate at higher current and voltage levels during brownout and overvoltage conditions, resulting in a shorter-than-normal operating lifetime of the UPS.
3. The batteries cannot be charged fully when the power disturbances occur so frequently. Consequently, the UPS cannot provide the rated backup time during each power disturbance. This can cause severe problems with mission-critical computers or telecommunications equipment that depend on the UPS to provide the 99.99% (or higher) system availability.
4. Small emergency power generators can cause special problems for when they are used to power a UPS system. They are known to produce wide frequency/voltage fluctuations, surges/spikes, and highly distorted (often non-sinusoidal) outputs which can cause continuous mains/inverter transfer operations, shutdowns, and even catastrophic UPS failure.
5. For sites subject to frequent lightning strikes, absence of a coordinated surge protection system based on IEC Technical Specification 61312-3 "Requirement of Surge Protective Devices" may cause premature failure of UPS due to unmitigated surges and spikes induced on incoming ac power line(s).
6. If the ambient temperature is outside of the optimum 10 to 25 degree C range, standard sealed lead-acid batteries cannot be used. Standard batteries are rated to work only when temperature is above 0 degree C, and sudden bat-tery failure can occur when operating temperature goes above 40 degree C. Even at 30 degrees C, expected battery lifetime is reduced by 50% compared to the expected battery lifetime at 20 degrees C.
White Paper SeriesChoosing UPS Protection For Underdeveloped Countries
223
III. SOLUTIONS FOR RELIABLE AND COST-EFFECTIVE UPS PROTECTION
TSi Power has developed 4 distinct UPS topologies to handle the challenging problem of reliability in underdeveloped countries.
The above-mentioned international power quality problems provide UPS manufactur-ers with a difficult challenge in trying to design UPS systems for underdeveloped countries. It must be recognized that no UPS system can provide foolproof protection against all types of power problems, especially at a reasonable cost. To provide the best solution to power problems in underdeveloped countries requires an intelligent application of technology, coupled with an intimate familiarity with the nature of the problems. Involved in international ac power protection since 1990, TSi Power has developed a family of UPS systems which are particularly useful in underdeveloped countries, with the following features:
1. A Voltage Range Extended UPS (VRe-UPs) provides an input voltage range of 160 to 330vac for a nominal 230vac in/output UPS system. Battery lifetime is maximized since battery discharge takes place during blackouts only (and not for brownout or overvoltage periods). The up-time percentage of a VRe-UPS is significantly higher than a standard UPS since the battery is always kept fully charged even during deep brownouts or overvoltage conditions.
2. Since only regulated 230vac is supplied to transistors and transformers in a VRe-UPs, they are not subjected to excessive voltage, current, or heat even during brownouts or overvoltage periods. Thus, the maximum lifetime of tran-sistors and transformers can be expected, thus increasing the reliability (and up-time percentage) of the VRe-UPS and the connected equipment.
3. When a small emergency power generator is used to power a UPS, the Precision Voltage Regulated UPS (VRp-UPs) should be used. The VRp circuit constantly regenerates a clean sine wave even from a highly distorted and non-sinusoidal output typical of a small power generator. By providing only high-quality, regulated sinewave input to the UPS, the VRp-UPs provides maximum UPS up-time percentage as well as maximum UPS and connected equipment lifetime.
4. When a site is subject to frequent and severe lightning strikes, an Isolation Line Conditioned (ILc-UPs) should be used. By providing transformer isolation, a new neutral-to-ground bond, surge protection at the output side of isolation transformer, and excellent noise filtering between incoming ac and the UPS, a coordinated protection system based on IEC Technical Specifica-tion 61312-3 is included. Therefore, the maximum level of surge protection for the mission-critical equipment is provided by the ILc-UPs.
5. If the ambient temperature is expected to be outside of the recommended 10 to 25 degree C window, a special class of wide-temperature rated batteries (which are guaranteed to work from -20 to +55 degrees C) must be used in order to obtain 5 years (or longer) of battery lifetime.
224 White Paper SeriesChoosing UPS Protection For Underdeveloped Countries
IV. CONCLUSION
A UPS manufacturer must be knowledgeable in handling all the possible power quality problems in the country where the UPS must be installed.
There are special challenges in designing a UPS system which can provide the requisite ac power protection and backup in underdeveloped countries. A UPS manufacturer must be knowledgeable in handling all the possible power quality problems in the country where the UPS must be installed.
Armed with this knowledge of actual conditions in underdeveloped countries, it is possible to provide an enhanced-performance, yet cost-effective UPS system that can withstand hostile conditions and fully protect the connected equipment against the following problems:
1. Wide ac mains voltage variation from 160 to 330vac.
2. Distortion, spike/noise, frequency, sags/surges and dropouts produced by small emergency power generators in wide use in underdeveloped countries due to the shortage of adequate power generation and distribution infrastructures.
3. Surges and spikes caused by frequent lightning strikes nearby.
4. Ambient temperature outside of the 10 to 25 degree C range.
Since 1992, TSi Power has developed several special optional modules, which can be added to the standard UPS, which extend the operating voltage range significantly and maximize the equipment protection level, up-time percentage and the lifetime of the UPS.
In order to ensure reliable UPS operation in an underdeveloped country, a specially modified UPS might be required. TSi Power’s experienced technical staff can work with customers to arrive at the best UPS design for underdeveloped countries.
ABOUT THE AUTHOR
Nam Paik ~ Director of Technology, TSi Power CorporationMr. Paik has over 15 years experience in the power electronics industry. He was with Northern Telecom (now Nortel Networks) for 4 years prior to joining TSi Power in 1988. Nam has focused on UPS, Line Conditioner and dc to ac inverter products and most recently has developed a number of customized power protection and conversion systems for several U.S. government agencies and international applications.
Choosing-UPS-Underdeveloped-Countries-2006-10-16.pdf
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
White Paper SeriesDesigning For Surge Immunity In International Markets
225
Designing for Surge Immunityin International Markets
Facing Hostile Environments
Surge immunity means the ability of electronic equipment to operate properly, with a low rate of failure, in the presence of abnormal line voltages and surge voltages from load switching and lightning.
BACKGROUND
Systems integrators in telecommunications and other industries that export to markets all over the world have to design equipment that will operate in electrical environments that may be more hostile than those found in North America or most parts of Western Europe. Power supplies, uninterruptible power systems and telecommunications rectifiers, for international applications, are typically designed to accept an input voltage window of 170 to 270 Vac. In addition, the equipment will have built-in surge withstand capability in accordance with IEC 1000-4-5, if CE marked. It is fairly safe to assume that power supplies and electronic equipment, designed in accordance with IEC standards, will be reasonably reliable in markets with stable power and minor lightning activity. However, conditions encountered in parts of Latin America, Asia, Africa and eastern Europe are often severe enough to cause power supply and sometimes system malfunction. The principals of TSi Power have identified three factors that drastically reduce system reliability:
• Inadequate infrastructure for the generation and distribution of electricity, causing frequent power outages and large voltage fluctuations.
• Inconsistent wiring and installation practices, locations without TN-S grounding systems (TN-S is the international term for three-phase with grounded neutral).
• Frequent lightning activity, especially when combined with a poor ground, thus causing lightning currents to find a path to ground through the power lines.
Designing for surge immunity requires careful attention to a number of factors that may be more or less difficult to control. Surge immunity, in the context of this paper, means the ability of electronic equipment to operate properly, with a low rate of failure, in the presence of abnormal line voltages and surge voltages from load switching and lightning. This paper will discuss factors that may necessitate enhanced surge immunity.
Designing for Surge Immunity in International Markets
WhiteWhitePaperPaper
Designing for Surge Immunity in International Markets
AuthorPeter NystromPresidentTSi Power Corp
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
226 White Paper SeriesDesigning For Surge Immunity In International Markets
FACTORS AFFECTING EQUIPMENT IMMUNITY
Fluctuating power line voltage
Causes• Overloaded , inadequate power generation and distribution systems,
particularly when large step load changes are present, result in large voltage sags and surges. Voltage fluctuations between 155 to more than 310 V have been observed in the field. Differences between day and night-time voltage of 40 V have also been observed.
• Such conditions are common in Africa, India, Pakistan and China, but can be found in many other areas. Additional power plants and distribution infrastruc-ture is needed in many developing countries. Timely power plant expansion is prevented by political and economic issues, which means the problem is here to stay for the foreseeable future.
Most power supplies, telecom rectifiers and UPS for international applications are designed for a nominal voltage of 230V with an input range of 176 to 270V
Effects
Power supplies can fail for a variety of reasons related to voltage fluctuations, the most common ones are listed below:
• Sags and undervoltages can cause component overheating or destruction, which reduces the life and deteriorates the real reliability as opposed to the estimated reliability, based on steady-state conditions of the power supply.
• Swells and overvoltages can cause component overheating and destruction of MOVs, SCR's and input capacitors that are rated too close to the line voltage. It is fairly common for power supply and telecom rectifier manufacturers to rate input MOVs at 275 Vrms with the apparent objective of reducing the surge remnant voltage, thus providing better surge immunity of the power supply. The author of this paper has observed still-functioning telecom rectifiers where the input MOVs had been completely destroyed by high line voltage.
• Typical EMI filters are not well damped, which can dramatically magnify the effects of voltage disturbances. The result can be oscillations inside the EMI filter during transitional conditions. Severe voltage surges may result from energy release where saturated inductors are looking for a path to release energy.
• Boost converters can be destroyed by voltage swells that cause increased energy storage in input filter, which charges the output capacitor to an unsafe level. The charge level is dependent on the value of the output capacitor and the load levels for the DC/DC converter connected to the output of the boost converter.
Remedies
Most power supplies, telecom rectifiers and UPS for international applications are designed for a nominal voltage of 230V with an input range of 176 to 270V. As previously mentioned, input MOVs are typically rated for 275Vrms to reduce surge remnant voltage. Experience suggests that the standard specifications for 230V power supplies are adequate for the majority of installations in major industrial countries. What to do if the supply voltage falls outside of the standard parameters? One possible solution is to specify telecom rectifiers and UPS that can withstand an expanded input range. The drawback is increased cost for the enhanced equipment and limited competitive selection, thus resulting in higher cost. Specifying equipment with enhanced input voltage range is only economical for new installations, not for retrofitting existing sites.
White Paper SeriesDesigning For Surge Immunity In International Markets
227
Another possibility is to add external voltage regulation devices, which can be cost-effective if the regulation device is sized and installed correctly. Modern voltage regulators can be both cost-effective and reliable, if applied properly. The use of an external voltage regulator makes it possible for the user to specify the best possible equipment without worrying about input voltage range specifications. This approach might be more cost-effective, particularly for existing installations.
Look for the following when specifying voltage regulators:
• Dynamic stability with all kinds of loads including power-factor-corrected,• Input voltage range should be at least 160 to 300 V,• Over voltage cut-off circuit,• Low heat loss,• Low wave form distortion,• By-pass switch to be used when unit fails,• Internal MOVs and capacitors should be sized to withstand 400 Vrms.
Electrical installations are affected by both direct and indirect lightning. A direct hit to a structure may produce 100 kA or more of a 10 x 350 µs wave form according to IEC 1024
Lightning surges
Causes
There are a number of areas in the world that experience a higher-than-average number of lightning days. Such areas are easily identified from an isokeraunic map.
• Electrical installations are affected by both direct and indirect lightning. A direct hit to a structure may produce 100 kA or more of a 10 x 350 µs wave form according to IEC 1024.
• Equipment installed close to the electric service entrance is exposed to considerably higher amounts of energy and may be subjected to the IEC 1024 wave shape above. Equipment installed more than 30’ (10 m) from the service entrance is subjected to the much milder ANSI/IEEE C62.41-1991, Category B3, Combination Wave, 3000A, 6000V, as the energy has dissipated some-what before reaching the equipment.A poor physical ground such as rock or dry sand causes lightning current to divert to the power line in order to find a path to ground.
• Incorrectly implemented site grounding may result in lightning current seeking a path to ground through equipment frames and power supplies.
• Use of non-TN-S grounding systems (TN-S is equivalent to three-phase with grounded neutral) can contribute to excessive surge voltages between power carrying conductors and ground.
EffectsPower supplies and the semiconductors used in electronic equipment can fail for a variety of reasons related to surge voltages from lightning and load switching—the most common threats are listed below:
• Destruction of power supply front end including EMI filter, MOVs, fuse holders and other components. Damage to chassis components and equipment frames that carried lightning current. The damaged equipment is usually located close to the electric service entrance and is installed in a region with a high number of lightning days. Typical wave shapes and currents are defined in the IEC 1024 standard.
• Surge voltages can cause damage or destruction to power semiconductors in the power supply.
• Surge voltages can cause false triggering of power supply SCRs and other components, thus causing short circuits that destroy components.
228 White Paper SeriesDesigning For Surge Immunity In International Markets
• Nuisance alarm tripping can result from surge voltages triggering detection circuits in the power supply.
• Semiconductor damage can occur as a result of surge voltages getting past the power supply, on to the logic board. The majority of semiconductor devices are intolerant to surge voltages that exceed their voltage ratings. Semiconductor damage occurs when a high reverse voltage is applied to a PN junction that is in the non-conducting state. Semiconductor junctions may avalanche at small points because of the non-uniformity of the electric field. Thermal runaway may result due to localized heat build up, thus causing the melt-through that leads to the destruction of the junction. Note, even a fast surge of a few microseconds may cause a semiconductor to fail catastrophically or cause degradation that shortens its useful life.
• System malfunctions including error messages, reboots, lock-ups, disk drive read/write errors are well known symptoms of surge voltage disturbances.
• A higher-than-average number of service calls and circuit board replacements is the definite confirmation that a system may be exposed to surge voltages that exceed the built-in system immunity.
Remedies
Power supplies, telecommunications rectifiers, UPS and other electronic equipment carrying the CE label have a certain built in level of surge immunity. What factors indicate the need for enhanced surge immunity? The presence of one or all of the following factors should warrant external surge protection in order to strengthen system immunity:
• Critical loads such as base transceiver stations (BTS) and nodes for wireless-in-the-local-loop applications as well as other outdoor enclosure installations often require additional protection,
• Inadequate infrastructure for the generation and distribution of power causing frequent power interruptions and unstable line voltages,
• High nominal line voltage,• Non-TN-S grounding systems,• High number of lightning days,• Poor physical grounding conditions,• Geographic locations where service calls are very expensive.
Look for the following when specifying external surge protection devices:• A primary protection device is required to handle the primary lightning threat that
is defined by IEC 1024.• A secondary protection device is required to divert the remnant of the primary
device.• Surge protective devices (SPD's) need to be coordinated in accordance with the
requirements of IEC 1312. Coordination is essential for proper performance of SPD's. Incorrect coordination can result in the "vulnerable equipment" absorbing most of the energy created by the surge.
• The clamping voltages of SPD's must not be rated too close to the power line voltage. This is especially important in locations with large voltage fluctuations.
• SPD's should have an internal disconnect to take them off line in case of failure. Failure conditions should generate an alarm.
• SPD's should be easy to replace in the field.• Protection should be provided between line and neutral as well as neutral to
ground.
White Paper SeriesDesigning For Surge Immunity In International Markets
229
• An isolation transformer should be added for non-TN-S systems in order to provide the neutral-to-ground bond that is essential for good surge protection.
• Spark-gap and gas-discharge-tube devices cause follow-on short-circuit current, which requires careful control not to cause problems. Careful attention should be given to ensure that follow-on currents do not cause disruption of the "vulnerable equipment." Proper down-stream inductance is required to ensure that spark gaps fire at the correct voltage level.
• A hybrid SPD may be used if it meets the above requirements.
The U.S. and Canada have consistent rules for grounding and bonding at the service entrance, but these vary between countries throughout the world. Some grounding systems actually contribute to surge voltage problems.
Installation and wiring practices
Causes
Installation and wiring practices are very important to ensure a reliable installation. Electrical installations in the U.S. have to conform to the National Electric Code and local inspectors enforce these and, in some cases, additional local requirements before approving a particular installation. It is often difficult, even in the U.S. and Western Europe where similar requirements exist, to ensure consistent quality practices. The U.S. and Canada have consistent rules for grounding and bonding at the service entrance, but these vary between countries throughout the world. Some grounding systems actually contribute to surge voltage problems. Some common problems are listed below:
• Inadequate wire size or type,• Long overloaded wire runs,• Too many loads on a branch circuit,• Incorrect circuit breakers,• Poor connections,• Ground currents due to incorrect wiring,• Poor ground and conduit connections,• Systems that do not have a clear path to ground for fault currents have to rely on
ground fault detection that sometimes malfunctions,• Mixing electrical equipment that is designed for different standards,• Incorrect grounding of distribution/isolation transformers,• Overloaded utility transformers,• Incorrectly applied surge protection devices.
Effects
The effects on the "vulnerable equipment" can vary from insignificant to major, sometimes intermittent malfunction. It can be very time consuming and costly to diagnose and correct problems, especially when the installation is far away in a country with different languages and customs. Those with experience from solving similar problems in North America will attest that fixing electrical problems can be a challenge even where one is familiar with language and customs. Some typical effects are listed below:
• Load induced voltage changes can cause equipment lock ups,• Load induced over voltage can cause failure of surge protective devices,• Incorrect grounding can cause excessive surge voltages, particularly from
lightning,• Poor wiring connections can create surge voltages that damage or upset
equipment.
230 White Paper SeriesDesigning For Surge Immunity In International Markets
Remedies• The following is suggested when planning site power:• Develop universal wire size recommendations in both AWG and square mm,• Develop one set of recommendations for countries that do not use
North-American-style metallic conduits,• Do not use conduit as ground,• Provide dedicated circuits to the "vulnerable equipment,"• Use breakers that are rated for universal use (UL, CSA and IEC),• Make sure that terminations and connections are properly checked before
approving the installation,• Establish a TN-S grounding system.• Ideally, design and build a power distribution module that can be used anywhere
in the world and that is approved by the major safety agencies. Develop simple installation instructions in the appropriate languages.
SUMMARY• Many equipment malfunctions can be traced back to inadequate infrastructure for
power generation and distribution, inadequate installation practices and significant lightning activity coupled with poor grounding systems.
• Installation and grounding practices vary from country to country and are not always enforced.
• Surge-immunity enhancement is often required for installations per above.• The selection and coordination of surge protective devices require careful
attention and planning.• A standardized approach is the best way to ensure consistent system
performance.
About the Author:
Mr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation ( located in Wisconsin, USA), a manufacturer of UPS, line conditioner, automatic voltage regulator, and dc to ac inverter systems designed to meet the challenging international power conditions.
WP-Designing-Surge-Immunity-Intl-Markets-2006-10-16.pdf
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
White Paper SeriesIEC 1312 Surge Protective Device Coordination
231
IEC 1312 SurgeProtective DeviceCoordination
FOUR COORDINATION VARIANTS
The purpose of SPD coordination is to successively reduce the lightning threat, in stages (SPD 1, 2 & 3) down to the surge withstand capability of the "vulnerable equipment," without exceeding surge current and voltage ratings of individual SPDs.
BackgroundLightning surges contain significant amounts of energy that needs to be diverted away from the "vulnerable equipment" (system that is to be protected from surges). Electronic equipment, if CE marked, is designed with a certain built-in surge voltage immunity in accordance with IEC 1000-4-5—this level of immunity will be sufficient for the majority of office buildings where the "vulnerable equipment" is located far away from the electric service entrance. Thus, equipment that carries the CE mark will work well without surge protection in many environments.However, when the "vulnerable equipment" is installed close to the electric service entrance, or in an outdoor enclosure, particularly in areas with a poor physical ground (dry sand, rock, etc.), it is often necessary to add external surge protective devices (SPDs). IEC recommends (IEC 1024) that lightning protection zones (LPZ) are established to successively reduce lightning currents, in stages, down to the built-in immunity of the "vulnerable equipment." The number of zones required depends on the structure containing the installation and the "vulnerable equipment." IEC 1024 requires that an SPD is installed at each zone boundary? the surge current and voltage ratings of individual SPDs must not be exceeded.
This paper explains the purpose and concept of surge protective device (SPD) coordination in accordance with the IEC 1312 standard.
Purpose of coordinationTo successively reduce the lightning threat, in stages (SPD 1, 2 & 3) down to the surge withstand capability of the "vulnerable equipment," without exceeding surge current and voltage ratings of individual SPDs.
IEC 1312 Surge Protective Device Coordination
WhiteWhitePaperPaper
IEC 1312 Surge Protective Device Coordination
Author Peter Nystrom President TSi Power Corp
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
232 White Paper SeriesIEC 1312 Surge Protective Device Coordination
Variant I
Figure 1
Variants I, II & III utilize individual single-port SPD’s. Variant IV is a two-port hybrid design.
Coordination conceptsIEC 1312 defines four coordination "variants." The first three utilize individual single-port SPDs while the fourth variant is a two-port hybrid design.
Variant I
Shown in Figure 1, the rated voltage of SPDs is identical and coordination is achieved by separating each SPD by means of series impedance. Variant I is not recommended by the IEC, probably because it would require approximately 30’ (10 m) of wire or separate inductors between each SPD, which is not practical when installing equipment close to the electric service entrance, or in outdoor enclosures.
Variant II
Shown in Figure 2, the rated voltages of SPDs are stepped so that the SPD in the "vulnerable equipment" has the highest rated voltage and SPD 3, 2 & 1 have progressively lower rated voltages, thus assuring that each upstream SPD would divert progressively higher currents. Variant II is difficult to implement as most power supplies, uninterruptible power systems and telecom rectifiers, rated for 230vac, use input SPDs with a 275Vrms rating. Thus, stepping down rated voltage, would cause SPD 1 and 2 to be destroyed by normal line voltage fluctuations—experience has shown that fluctuations of plus 10% resulting in 250V is not unusual.
White Paper SeriesIEC 1312 Surge Protective Device Coordination
233
Variant II
Figure 2
Variant III is a better choice than I or II as the spark gap is insensitive to fluctuations in line voltage.
Variant IIIShown in Figure 3, includes a component with a non-linear current/voltage character-istic, such as a spark gap. The SPD 1 spark gap would divert the majority of the surge current and output a combined wave, similar to ANSI/IEEE C62.41-1991, Category B3, Combination Wave, 3000A, 6000V, to downstream SPDs 2 and 3. The voltage ratings of SPD 2 and 3 are identical, but each device will handle considerably less current thanks to the much higher energy handling capability of spark gap SPD 1. Variant III is a better choice than I or II as the spark gap is insensitive to fluctuations in line voltage. However, spark gap follow-on, short-circuit current may be an issue, and MOVs will still be sensitive to line voltage fluctuations.
Figure 3
234 White Paper SeriesIEC 1312 Surge Protective Device Coordination
WP-IEC-1312-SPD-Coordination-2006-10-16.pdf
Variant IV
Figure 4 shows a two-port hybrid device that incorporates cascaded stages of SPDs internally coordinated with series impedances. A hybrid device can be designed to maximize performance while reducing the undesirable characteristics of spark gaps and SPDs based on varistor or silicon-avalanche-diode technology. The use of a hybrid device eliminates the need to coordinate surge protective devices, but does not eliminate sensitivity to prolonged line over voltage.
Figure 4
SummaryEquipment designed to conform to CE requirements has a built-in surge immunity level that is sufficient in most office applications. However, equipment installed close to the electric service entrance or in an outdoor enclosure, particularly in areas with a large number of lightning days, requires additional protection—especially if the physical ground is poor. Surge protective devices require coordination to perform well. The remnant voltage of the SPD closest to the "vulnerable equipment," shall not exceed its built-in immunity level. Coordination of surge protective devices is not always easy and the best solution may be a two-port, hybrid device, which will simplify the planning and installation process. High line voltage will destroy varistor and silicon-avalanche devices that are rated too close to the line voltage and must be considered when planning for protection in areas with unstable power lines.
About the AuthorMr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation (located in Wisconsin, USA), a manufacturer of UPS, line conditioner, automatic voltage regulator, and dc to ac inverter systems designed to meet the challenging international power conditions.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
White Paper SeriesThe Benefits of UPS and Line Conditioners with an Isolation Transformer
235
The Benefits Provided by UPS and Line Conditioners with an Isolation Transformer
DEDICATION AND ISOLATION
With the recent proliferation of low-cost standby UPS products which claim to "solve all the ac power problems", a false sense of security seems to exist among users who purchased and installed these basic non-isolated UPS for their PCs, fileservers, network/telecommunication equipment, point-of-sale terminals, etc.
Such a false sense of security and confidence is often rudely challenged by equipment glitches, crashes, and malfunctions that persist even after installation of these non-isolated UPS products. The answer to this unexplainable failure of UPS to provide 100% protection against ac power problems can be found in an "Isolation Transformer" based UPS or Line Conditioner.
Experienced electrical engineers have known this limitation of non-isolated UPS, line conditioners, surge protection devices and EMI/RFI noise filters for a long time - and their answer has been a "dedicated circuit" which is a separate ac wire run all the way to the main electrical panel located next to the building’s power transformer. Since the high neutral line voltage and high levels of spikes and transients are caused by devices such as air conditioners, heaters, elevators, copiers, laser printers, etc., bypassing all the sub-panels that feed these "dirty" devices by installing and using a "dedicated circuit" usually solved the problems.However, installation of a dedicated circuit can be very expensive and time-consuming, especially when it is a large or high-rise building. Installation of a dedicated circuit also requires an approval and permit from a licensed professional engineer (PE.), the building wiring diagram and the final drawing and work must be inspected and approved by a local county or city electrical inspector. The cost of a single dedicated circuit can be several thousand dollars and may require several weeks (or months) from start to finish.
The high cost and long installation time of installing a dedicated circuit can be eliminated by using an isolation line conditioner or isolation UPS system, however. Because of the integral isolation transformer, each isolation line conditioner or UPS qualifies as a "Separately derived power source" under National Electrical Code 250-5D. Isolation conditioner and UPS also complies with the U.S. federal government’s FIPS Publication 94 requirement of neutral and ground bonding for elimination of any problems caused by the presence of neutral voltage or common-mode noise/transients.
Benefits Provided by UPS and Line Conditioners with an Isolation Transformer
Author Nam Paik Director of EngineeringTSi Power
WhiteWhitePaperPaper
Benefits Provided by UPS/Line Conditioners with Isolation Transformers
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
236 White Paper SeriesThe Benefits of UPS and Line Conditioners with an Isolation Transformer
Additional benefits provided by an isolation line conditioner (or UPS with isolation transformer):
1. Regeneration of power using the isolation transformer at the point of use means that it is a truly ideal power source (It is like moving the building transformer to within a few feet of sensitive equipment). The power from an isolation transformer is both DEDICATED and ISOLATED.
2. Multi-stage surge protectors and EMI/RFI noise filters are also built-in.
3. Isolation conditioner sizes ranging from 90 VA to 5.5 kVA allows optimized performance vs. cost product selection. UPS size ranges from 400VA to 2100 VA.
4. Installation is immediate and no permit or approval is required. (Conditioners are also available in sizes up to 36 kVA, and it is recommended they be installed by a licensed electrician).
5. Cost of the unit is only a small fraction of a dedicated circuit installation cost.
About the author
Nam Paik ~ Director of Engineering, TSi Power Corporation Mr. Paik has over 15 years experience in the power electronics industry. He was with Northern Telecom (now Nortel Networks) for 4 years prior to joining TSi Power in 1988. Nam has focused on UPS, Line Conditioner and dc to ac inverter products and most recently has developed a number of customized power protection and conver-sion systems for several U.S. government agencies and international applications.
WP-Isolation-Transformer-Benefits-2006-10-16.pdf
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
White Paper SeriesThe Merits of a Standby UPS with a Modified Sinewave Output
237
The Merits of aStandby UPS with a Modified Sinewave Output
Of the 3 major UPS architectures (e.g. Standby, Ferroresonant On-Line, and Double-Conversion On-Line), the Standby UPS features the following advantages:
About the AuthorNam Paik ~ Director of Engineering, TSi Power Corporation Mr. Paik has over 15 years experience in the power electronics industry. He was with Northern Telecom (now Nortel Networks) for 4 years prior to joining TSi Power in 1988. Nam has focused on UPS, Line Conditioner and dc to ac inverter products and most recently has developed a number of customized power protection and conversion systems for several U.S. government agencies and international applications.
Features Benefits1. Extremely high power efficiency,
typically above 97%.Lowest operating cost in terms of electric use – only 1/10 of double-conversion on-line UPS.
2. Air exhaust fan is normally off since very little heat is generated.
Quiet operation. Does not add to air conditioning loads.
3. The inverter circuit is normally off. Very quiet operation and the highest MTBF (mean-time-between failure) due to the lowest voltage, current and temperature of its internal parts.
4. Cooler internal operating temperature. Battery lifetime is approximately twice that of an on-line type UPS.
5. Output waveform is normally a sinewave. The inverter waveform is a modified square-wave, generated only during power outages.
The pulse-width-modified and optimized peak-voltage modified square waveform is actually more beneficial for switchmode power supplies.
6. Simplest and most economical UPS design.
Simple design with the lowest parts count. Means lowest purchase price and maintenance costs. Repair procedures are quick and easy.
7. The switchover time of some high-quality Standby UPS is less than 1ms.
The ride-through of a typical switchmode power supply is 10 to 20 ms. A fast 1 ms switchover time guarantees glitch-free transfers.
The Merits of a Standby UPS with a Modified Sine WaveOutput
Author Nam Paik Director of EngineeringTSi Power
WhiteWhitePaperPaper
The Merits of a Standby UPS with a Modified Sine Wave Output
WP-Merits-of-Standby-UPS-2006-10-16.pdf
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
238 White Paper SeriesThe Benefits of UPS and Line Conditioners with an Isolation Transformer
This page intentionally left blank.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
White Paper SeriesPower Primer ~ A Guide to UPS and Power Terms
239
Power Primer
A Guide to Power and UPS Terms
The reliability of PC’s and the Internet comes nowhere near the telephone system.
Power quality is an issue that all serious computer users should be concerned with. Why? The world is becoming more dependent on computers than ever before. The Internet is changing everything in ways that could not have been imagined just a few years ago. We are now using the Web to make travel reservations, buy and sell stocks, upload and download large files and to purchase many different products. Yet the reliability of PCs and the Internet comes nowhere near the telephone system. We are always expecting dial tone when we pick up the receiver to make a telephone call, and we would be quite surprised if the telephone company would have to reboot the digital switch used in the central office. We certainly would not accept if the telephone didn’t work when there was a power outage. Somehow we seem to accept much less when we log on to the Web. In time the computer industry will figure out how to design reliable software, computers and data communications equipment. The good news is that it is quite inexpensive to do something about computer crashes caused by power interruptions. Most PCs can be adequately protected for less than $285.00 with a Flexible Series UPS from TSi Power Corporation.
The purpose of the Power Primer is to provide some basic information about the quality of utility power and how it affects the average computer user. First, a list of power anomalies and their effect on computers:
• Power outage (also known as blackout or power failure)—a complete loss of power, which causes the computer to crash and shut down.
• Surge voltage (also known as spike, transient or impulse)—a short-duration overvoltage, which can cause computer malfunction or failure, depending on the severity of the surge.
• Sag (also known as brownout or undervoltage)—a longer-term abnormal deviation from the nominal voltage of 120V (230V in many countries outside North-America), which can cause the computer to shut down or cause overheating of its internal power supply if the sag continues for a long time.
• Swell (also known as overvoltage)—a longer-term overvoltage, which can cause failure of the computers internal power supply or possible shut down for some computers.
Power Primer ~ A Guide to UPS and Power Terms
WhiteWhitePaperPaper
Author Peter Nystrom President TSi Power Corp
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
Power Primer and Guide to UPS Terms
240 White Paper SeriesPower Primer ~ A Guide to UPS and Power Terms
What is the cause of the above problems? The power provided by the local Power Company has to be generated and distributed to the user. This process and natural events like lightning cause most problems.
Using generators that are powered by hydro, fossil fuel or nuclear fission generates power. Future supply of power will be affected by the lack of available sources of hydro and concerns over pollution caused by the burning of fossil fuel—the situation will worsen because of the lack of enthusiasm for any expansion of nuclear plants. A number of US nuclear plants are being decommissioned while countries like Swe-den have decided to decommission most of its nuclear plants. Thus, it is possible that there will not be enough power to satisfy future demand in the US. Many devel-oping countries are already experiencing severe shortages of power and have been unable to arrange the financing necessary to build more power plants. A shortage of power will cause all of the above problems, as some users will be subject to momentary power outages when there is not enough power to satisfy demand.
Power is distributed over long distances using high-voltage overhead power lines— distribution voltages can be as high as one million volts. Power is distributed locally via lower voltages provided through a series of step-down transformers. Some local distribution networks are unable to provide the power required when many users demand power at the same time, which may cause local distribution transformers to fail and hence cause power outages. Many local distribution sys-tems in the US use overhead power lines that are very sensitive to tree branches falling and thus causing power interruptions. Additionally, surge voltages will occur when power fails as the rapid interruption of power results in a surge voltage.
The deregulation trend may compound power interruptions and stability problems in the future as switching between different power grids becomes more frequent as sellers and buyers exchange power.
Power problems can also be caused by thunderstorms when surge voltages from lightning strikes are delivered via the power line to the computer. Additionally, light-ning arresters on utility distribution lines can cause brief power interruptions as the momentarily short the power while diverting lightning voltages to ground.
Surge voltages can result as electrical equipment turns on and off inside buildings.
Helpful terminology when selecting a UPSAll computers and telecommunications key systems and PBXs have a voltage and current rating and requirement. Typically, such information is printed on the back planes of equipment (near serial number and product model information) and is also included in the User’s Manual. Uninterruptible Power Systems are rated in Volt Amperes or "VA." It is a simple task to determine what size UPS a particular system requires just: (Note, the information provided applies to equipment connected to a regular 120V or 230V outlet)
• Determine required VA rating for each piece of equipment to be con-nected to the UPS (e.g. computer, monitor, modem, etc). Multiply volts (V) and amps (A) for each piece of equipment and obtain VA per device. Then add the total and obtain total VA rating. Example: Computer 120V x 2A = 240 VA; Monitor 120V x 1A = 120 VA; Modem 120V x 0.1A = 12 VA. Thus, total VA is 240VA + 120VA + 12VA = 372 VA. Note, if only watts are given: multiply watts by 1.35 to obtain VA rating.
• Select a UPS that is the same rating or larger than the above calculated load. For example, a UPs-400 provides 400 VA of power and would provide at least 8 minutes of backup. If more backup is required or if more equip-ment will be connected to the UPS in the future, a larger UPS should be selected. A UPs-600 would provide longer backup than a UPs-400, typically 15 minutes or more. TSi Power Quality Products can provide longer backup times.
White Paper SeriesPower Primer ~ A Guide to UPS and Power Terms
241
A Guide to UPS TermsTransfer timeThis describes the amount of time it takes from the initial loss of ac power to the time the UPS takes over the load. The importance of time for the computer translates into the computer locking up or freezing and thereby losing any unsaved information. Instantaneous transfer time means that the computer would not even notice that its power source had switched from one input to another.
Isolation from lineA characteristic of a UPS in which the output is completely electrically disconnected from the input. Power is coupled from input to output by magnetic fields in a trans-former. Because there is no connection from input to output, transients cannot cross the magnetics thereby eliminating any transients in the ac output.
Neutral to ground bondThe neutral to ground bond provides protection from transients on the neutral line which could feedback into sensitive electronic equipment.
EMI/RFI noise filteringEMI refers to electro-magnetic interference which is unwanted electrical noise present on the power line. This noise may "leak" from the power lines and affect equipment that is not even connected to the power line. Such "leakage" is called a magnetic field. Magnetic fields are formed when unwanted noise voltages give rise to noise currents. Such noise may adversely affect electronic equipment and cause intermittent data problems. EMI protection is provided by noise filters placed on the ac power line. The filter reduces the noise voltage on the protected line, and by doing so eliminates the magnetic fields of noise generated by the protected line. Noise signals that act over a significant distance are called Radio Frequency Interference (RFI). Equipment power cords and building wiring often act as antennas to receive RFI and convert it to EMI.
Surge/spike protectionThis category is fairly self explanatory. The higher your protection, the better your equipment is insulated from momentary increases in voltage on the ac line.
Output voltage regulationVoltage regulation, especially in areas where the power quality is low, is essential to equipment performance. Computer equipment will identify if the voltage is within the operating parameters and if it falls below those parameters, the computer will shut down and will lose any unsaved information. Furthermore, with a constant voltage, the internal components in the computer will run more efficiently and will extend the life of the computer’s hardware substantially.
Inverter WaveformSine wave inverter waveform is the best. Pseudo-sine wave (typically modified square wave) is suitable for computers and other switchmode power supply driven equipment, but not motors or fans.
Energy efficiencyThe ratio of output power to input power as expressed as a percent. For example, if a UPS has an efficiency of 80%, then 20% of the input energy in lost as heat.
Source impedanceSmall engine generators (1kW to 10kW range) have very high source impedance, which means output voltage will drop as more load is connected to the output. This is the reason for oversizing a generator.
242 White Paper SeriesPower Primer ~ A Guide to UPS and Power Terms
WP-Power-Primer-UPS-Terms-2006-10-16.pdf
Operating environmentAn overall description of the ac environment which includes in its definition frequency of transients (i.e. surges, spikes, sags), blackouts, and voltage fluctuations to name a few. Often contributing factors can be industrial growth, poor utility maintenance, poor power management or erratic weather. The areas in which your computers are operating are easily described as poor ac environments.
Unit surge voltage withstandThis denotes the amount of voltage surge the UPS itself can handle before damage and failure of the unit. If the UPS fails, the computer equipment becomes vulnerable to the transients on the ac line.
PriceThe range of prices, as you’ve discovered, is widely disparate because the standby UPS is using the cheapest but least reliable technology, whereas the ferroresonant, and on-line technologies are very high quality and durable.
About the AuthorMr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation (located in Wisconsin, USA), a manufacturer of indoor and outdoor UPS, isolation transformer line conditioners, precision automatic voltage regulators, and dc to ac inverter systems designed to meet the challenging international power conditions.
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
White Paper SeriesWhy Power Supplies and Semiconductors Fail
243
Why Power Supplies and Semiconductors Fail
Causes and results of power disturbances
A power disturbance can be defined as unwanted excess energy that is presented to the load.
Comments regarding power disturbances• Power quality varies significantly from one area to another. Some countries
have very stable power grids while others are extremely short on capacity.• Power disturbances are caused by the generation, distribution and use of
power; and lightning.• A power disturbance can be defined as unwanted excess energy that is
presented to the load.
Causes of power disturbances• Power disturbance originate both outside and inside customer facilities.• Load switching causes surges because of collapsing fields (-e = l * di/dt).• Over loaded power distribution systems can cause significant voltage variations
between peak and off-peak hours.• Significant momentary load changes, such as heavy inrush currents can cause
severe voltage variations.• Black-outs can cause severe voltage surges both on loss and return of power.• Circuit-breaker tripping and fuse blowing can cause severe surge voltages.• Large ups and variable-speed drives can cause various surge voltages inside
buildings.
Results of power disturbances• Sags and under voltages can cause component overheating or destruction.• Surges and over voltages can cause component overheating, destruction or can
trigger other electronic components such as SCR's.• Component overheating reduces the life and deteriorates the real reliability as
opposed to the estimated reliability based on steady-state conditions of the product.
• False triggering of other components can create nuisance alarm tripping or, worse, can cause overheating or destruction of other electronic components.
Why Power Supplies and Semiconductors Fail
WhiteWhitePaperPaper
Why Power Supplies and Semiconductors Fail
Author Peter Nystrom President TSi Power Corp
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
244 White Paper SeriesWhy Power Supplies and Semiconductors Fail
Why semiconductors fail• Most semiconductor devices are intolerant to surge voltages in excess of their
voltage ratings.• Even a fast surge of a few microseconds can cause the semiconductor to fail
catastrophically or may degrade it so as to shorten its useful life.• Damage occurs when a high reverse voltage is applied to a non-conducting
pn junction.• The junction may avalanche at a small point due to the non-uniformity of the
electric field. In this case, thermal runaway can occur because of localized heat build up and cause a melt-through which destroys the junction.
Problems with current solutions• Common-mode voltage disturbances can be amplified in non-tn-s ac distribution
systems.• Typical emi filters are not well damped. This has a dramatic effect on any voltage
disturbances, resulting in oscillations inside the emi filter under any transitional conditions. Severe voltage surges may result from fly-back from saturated inductors looking for a path to release energy.
• Boost converters can be destroyed by surges causing increased energy storage in input filter, the output capacitor (c) is charged to an unsafe level depending on capacitance value and load levels for the dc/dc converter connected to the output of the boost.
Limitations of commercial UPS equipment• The industry is driven by lowest cost.• Users normally don't care about power quality.• Users really care about saving data which means that they are satisfied with
orderly shut down to protect data files.• Most UPS do not have quality battery chargers and chargers are nor designed
for long-term back-up.• Most UPS equipment does not provide real power conditioning (there are
exceptions).• Some UPS equipment is poorly protected against surge voltages.• Extended back-up requires the addition of expensive rectifier/chargers and
battery packs.
About the authorMr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation (located in Wisconsin, USA), a manufacturer of UPS, line conditioner, automatic voltage regulator, and dc to ac inverter systems designed to meet the challenging international power conditions.
WP-Power-Supply-Failure-2006-10-16.pdf
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
White Paper SeriesProtection of Telecom Sites in Countries with Unstable Ac Mains
245
Protection of Telecom Sites in Countries withUnstable Ac Mains
Ac mains voltages frequently fluctuate beyond the IEC assumed standard of a 184 to 264vac input range.
BACKGROUND
Developing countries often have weak power generation and distribution systems: Frequently resulting in mains voltage fluctuations beyond the 184 to 264vac input range mandated by the European Norm. The underlying IEC standards assume that power generation and distribution are fairly stable and that voltage excursions will not be outside the specified input window of 184 to 264vac. Unfortunately, that is not the case in many developing countries throughout the world. Even industrialized nations have their share of problems with ac mains availability. Mains voltages frequently fluctuate beyond the assumed 184 to 264vac input range.
In the U.S. State of California for example, a failed deregulation scheme coupled with the lack of corrective political will led to rolling blackouts that cut power to millions in early 2001. The desired expansion of generation and distribution capacity in developing countries is also constrained by a shortage of capital and, in some cases, political factors as well. Thus, it appears that the quality of ac mains, for developing countries, is at best uncertain into the foreseeable future.
The expansion of communications networks, such as cellular radio, direct radio access telephony (wireless in the local loop), paging networks, land mobile radio and satellite telephony stations, has led to a rapid increase of installed sites to support these networks. The proliferation of sites sometimes makes it difficult to place a particular site in an ideal location. The site might then be installed in a remote or difficult-to-access location.
The author of this article has worked with infrastructure manufacturers and operators to address power-related reliability problems, which can be very expensive if not addressed properly--especially for remote and hard-to-reach locations. This paper aims to give readers some helpful hints when addressing their own power-related reliability concerns.
Protection of Telecom Sites in Countries with Unstable Ac Mains
WhiteWhitePaperPaper
AuthorPeter NystromPresidentTSi Power Corp
Power Protection in Countries with Unstable Ac Mains Voltages
TSi Power CorporationRepresented byCareBaseMichael GibsonPost Office Box 2987Glenwood Springs, CO81602-2987 USAPhone +1 970 945 2770800 430 2770 (USA.CAN)[email protected] © 2006 TSi
246 White Paper SeriesProtection of Telecom Sites in Countries with Unstable Ac Mains
THE PROBLEM
The power converters used in modern ac-dc rectifiers, UPS and ac-dc switchmode power supplies, are typically based on the IEC input range of 184 to 264vac. Ac induction motors are sensitive to both high and low mains voltage, where low voltage can cause rotor lockup following a dip in mains voltage; and to saturation causing tripping of circuit breakers, as a result of high mains voltage. Transformers and other 50/60Hz magnetics can easily get saturated when exposed to high input voltage, particularly at 50Hz, when the magnetization curve of steel becomes non-linear much quicker than for 60Hz.
Ac induction motors are sensitive to both high and low mains voltage.
Causes of power supply failure• Sags and under-voltages can cause component overheating and
destruction of MOS-FETs from over-current.• Surges and over-voltages can cause component overheating, destruction of
MOS-FETs, or can trigger other electronic components such as SCRs, MOVs and input capacitors may be destroyed if they are rated too close to the line voltage.
• Component overheating reduces the life and deteriorates the real reliability as opposed to the estimated reliability based on steady-state conditions of the product.
• False triggering of other components can create nuisance alarm tripping or, worse, can cause overheating or destruction of other components.
• Typical EMI filters are not well damped. This has a dramatic effect on anyvoltage disturbances, resulting in oscillations inside the EMI filter under anytransitional conditions. Severe voltage surges may result from fly-back from saturated inductors looking for a path to release energy.
• Boost converters can be destroyed by surges causing increased energy storage in the input filter, when the output capacitor is charged to an unsafe level, depending on capacitance value and the load levels for the dc to dc converter connected to the output of the boost converter.
Causes of semiconductor failure• Most semiconductor devices are intolerant to surge voltages in excess of their
voltage ratings.• A fast surge (high dv/dt) of a few kV per microsecond can cause a semicon-
ductor to fail catastrophically or may degrade it so as to shorten its useful life.• Damage occurs when a high reverse voltage is applied to a non-conducting
PN junction.• The PN junction may avalanche at a small point due to the non-uniformity of
the electric field. In this case, thermal runaway can occur because of localized heat buildup and cause a melt-through which destroys the junction.
Mains voltages varying between 160 to 330 vac are common in countries like India and Pakistan.
Mains voltages varying between 160 to 330 vac are common in countries like India and Pakistan, but are also found in many other areas. In such cases, installation of unprotected power systems and equipment can lead to an abnormally high failure rate and loss of revenue for both suppliers and users of telecom hardware.
White Paper SeriesProtection of Telecom Sites in Countries with Unstable Ac Mains
247
Mains voltage anomalies can be caused by the following:• Fault clearing: where a short circuit occurs on the line and a protection
device clears the fault, typically in around 3 cycles. The clearing of a fault results in a short dip and voltage recovers rapidly if the mains are stable. However, recovery can take much longer if the mains are weak, resulting in a protracted voltage sag.
• Chronic instability: caused by interaction of voltage stabilizing devices. A good example would be an industrial area with an inadequate incoming power line, thus resulting in unstable mains as loads cycle on and off. Users of power may then install a voltage stabilizer that will draw more current to provide a higher voltage for one facility, with the higher current draw causing a voltage drop for adjacent facilities that in turn draw more power when regulators attempt to correct the mains voltage. The end result can be a total loss of power when current draw exceeds the substation’s capability to deliver the required current.
• Weak generation capacity: will also result in fluctuating mains when utility customers compete for available power.
• Rolling brownouts: can result when the power utility reduces the mains voltage by 10% or more in order to limit power consumption. This approach may work for fixed-resistance loads such as light bulbs, but will not for computer and telecom equipment utilizing switchmode power supplies, as these compensate for low voltage by increasing current draw. The increased current is capable of generating increased internal heat that can lead to power supply failure.
• Blackouts: can result when the electric utility cuts off power to selected areas in an attempt to protect major parts of the distribution system from interruptions.
Mitigation devices are often applied as a “bandage,” in the hope that things will get better quickly, to the satisfaction of both the telecom operator and the equipment provider. Unfortunately, applying mitigation devices without understanding the basics can actually aggravate the problem. This is especially true for power-factor-corrected power supplies, as these are more sensitive to mains disturbances than their simpler siblings with rectifier/capacitor inputs. It is the author’s experience that power-factor-corrected rectifiers can trip internal protection devices when exposed to rapidly changing mains voltages.
Over-voltage protection (surge protection) against surge voltages, and from load switching and lightning, is governed by rational principles, first outlined by IEC-1312 in the early 1990s. The applicable IEC-Standard: IEC Technical Specification 61312-3 “Requirements of Surge Protective Devices (SPDs)” describes clearly how to coordinate SPDs to ensure that upstream devices (Figure 1) progressively handle more energy than the SPD found on the front-end of a power supply, typically a metal oxide varistor. These sensible coordination principles are not always adhered to, which sometimes results in a lack of coordination between SPDs used in a system. This can lead to the destruction of down stream SPDs that clamp before the upstream SPDs, which in turn causes the destruction of the metal oxide varistors in the power supply itself.
248 White Paper SeriesProtection of Telecom Sites in Countries with Unstable Ac Mains
FIGURE 1. Coordination of surge protection devices.
Safety earthing systems
Many different earthing systems are in use throughout the world and need to be understood before primary surge protection is implemented. The most common earthing systems are shown below:
TN-S A separate neutral and ground conductor are run throughout.
TN-S
A separate neutral and ground conductor are run throughout. The ground conductor can be the metallic sheath of the power distribution cable or a separate conductor. All exposed-conductive-parts of the installation are connected to ground.
TT
One point of the source of energy is grounded and the exposed-conductive-parts of the installation are connected to independent grounded electrodes.
TN-C
Neutral and ground conductors combine in a single conductor throughout the system. All exposed-conductive-parts are connected to the combined N-G conductor.
IT
A system that has no direct connection between live parts and ground. All exposed-conductive-parts of the installation are connected to independent grounding electrodes.
TN-C-S
Neutral and ground combine in a single conductor. This system is also known as multiple earthed neutral (MEN). The protective conductor is referred to as the combined neutral and ground conductor. The supply N-G conductor is grounded at a number of points throughout the network and generally as close to the consumer’s service entrance as possible. All exposed-conductive-parts are connected to the combined N-G conductor.
I0 I1
R1 L1
I2
R2 L2 L3
I3
equipmentto be
protected
UC(SPD1)=UC(SPD2)=UC(SPD3)
LPZ 1 LPZ 2 LPZ 3LPZ 0
SPD 3SPD 2SPD 1
R3
White Paper SeriesProtection of Telecom Sites in Countries with Unstable Ac Mains
249
POSSIBLE SOLUTIONS
The most obvious solution is to design power supplies to withstand a much wider input voltage range.
The most obvious solution is to design power supplies to withstand a much wider input voltage range, to prevent saturation and resulting energy impulses that cause damage to switching transistors and other circuits. Such changes require more steel in inductors, capacitors with higher voltage ratings, possibly larger circuit boards with greater trace separation, as well as transistors with higher voltage and current ratings. This is not likely, as manufacturers would have to offer special versions with a wide input voltage range or, as a second option, make only power systems that can handle all worldwide markets, regardless of mains quality. This second option is not realistic since customers in countries with a stable mains infrastructure would be penalized.
Designing a protection device that can handle an entire power plant, or racks of power systems, is probably a more economical solution that can be used whenever increased immunity is required. Such a solution can also be used to address problems that occur in the field after installation.
Considerations for mitigation devices
Mitigation devices may include a complete solution, or components thereof, if system analysis reveals that essential elements already exist. We will present here a complete solution for the readers’ consideration.
Input range of 160 to 330 vac at 50/60Hz without saturation at 50Hz
Requirements:1. Input range of 160 to 330 vac at 50/60Hz without saturation at 50Hz2. Output range of 184 to 264 vac3. Over-voltage protection (OVP) with cut-off if output exceeds 264 vac4. Automatic bypass in case of electronics failure5. Low impedance6. Coordinated surge protection7. Conversion to TN safety earthing system8. Low weight9. Reasonable cost10. High power efficiency and low heat loss
FIGURE 1. An example of a power system for a cellular base station follows on the next page
250 White Paper SeriesProtection of Telecom Sites in Countries with Unstable Ac Mains
White Paper SeriesProtection of Telecom Sites in Countries with Unstable Ac Mains
251
Limitations of existing technologiesSeveral technologies are available for mitigation devices, each with a distinct set of advantages and drawbacks. Table 1 below provides a summary:
Table 1: Limitations of existing technologies
Technology Advantages DrawbacksFerroresonant transformer with isolation
• Reliability• Surge protection• Tight regulation• Fast regulation• Bypass is not required
• Price• Stability• High impedance• Limited voltage input
range• Frequency sensitive• Low efficiency• Incompatible with power-
factor-corrected power supplies
• High weight• Bulky
Tap-switched auto-transformer
• Lowest cost• High efficiency• Low impedance
• Slow response• Limited voltage input
range• Automatic bypass not
available• Requires added isolation
transformer to achieve proper surge protection
PWM-regulated buck-boost transformer
• Very tight regulation• Low impedance• Excellent stability• Low weight• Small size• Very high efficiency• Some have automatic
bypass
• Medium reliability• Limited voltage input
range• Most do not have OVP• Requires added isolation
transformer to achieve proper surge protection
Relay-switched buck-boost transformer with autobypass and OVP
• Very wide input voltage range of 160–330vac
• Low impedance• Excellent stability• Low weight• Small size• Very high efficiency• Automatic bypass
• Requires addedisolation transformer to achieve proper surge protection
Variable transformer with buck-boost transformer
• Very tight regulation• Low impedance• Excellent stability• Very high efficiency• Some have automatic
bypass
• Very slow• High weight• Bulky• Slow regulation• Can produce excessive
voltage following restart after mains failure
• Some do not have OVP• Requires added isolation
transformer to achieve proper surge protection
252 White Paper SeriesProtection of Telecom Sites in Countries with Unstable Ac Mains
WP-Protection-Telecom-Sites-Unstable-Ac-Mains-2006-10-16.pdf
Summary
Many equipment malfunctions can be traced back to inadequate infrastructure for power generation and distribution and inadequate installation practices.
The risk of system failure is greater at 50Hz, especially for high mains voltages.
A plethora of safety earthing systems and supply voltages make it difficult to create a simple standard for field installation.
A standardized system of mitigation devices with ac mains stabilization that also meet the requirements of IEC Technical Specification 61312-3 may be the best way to ensure consistent system performance.
About the Author:
Mr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation (located in the state of Wisconsin, USA), a manufacturer of indoor and outdoor UPS, line conditioners, precision automatic voltage regulator, automatic transfer switches and dc to ac inverter systems designed to meet the challenging international power conditions.