+ All Categories
Home > Documents > Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project...

Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project...

Date post: 25-Sep-2020
Category:
Upload: others
View: 2 times
Download: 0 times
Share this document with a friend
88
Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing Damping of Oscillation Sobuj Kumar Ray Department of Electrical and Electronic Engineering Dhaka University of Engineering & Technology, Gazipur October 2017
Transcript
Page 1: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Tuning of PI and PID Controller withSTATCOM, SSSC and UPFC for

Minimizing Damping of Oscillation

Sobuj Kumar Ray

Department of Electrical and Electronic Engineering

Dhaka University of Engineering & Technology, Gazipur

October 2017

Page 2: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Tuning of PI and PID Controller withSTATCOM, SSSC and UPFC for

Minimizing Damping of Oscillation

A dissertation submitted in partial fulfilment of the requirements for thedegree of

Master of Engineering in Electrical and ElectronicEngineering

By

Sobuj Kumar Ray

Student No. 112261-P

Under Supervision of

Dr. Md. Raju AhmedProfessor and Head, Dept. of EEE, DUET, Gazipur

Department of Electrical and Electronic Engineering

Dhaka University of Engineering & Technology, Gazipur

October 2017

Page 3: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC andUPFC for Minimizing Damping of Oscillation” submitted by Sobuj Kumar Ray, Student ID:112261-P, Session: 2011-2012 has been accepted as satisfactory in partial fulfillment for thedegree of Master of Engineering in Electrical and Electronic Engineering on October 10,2017.

BOARD OF EXAMINIERS

…………………………………………………………..Prof. Dr. Md Raju Ahmed Head of the DepartmentDepartment of Electrical and Electronic EngineeringDhaka University of Engineering & Technology, Gazipur

Chairman(Supervisor)(Ex-officio)

…………………………………………………………..Dr. Md. Bashir UddinProfessorDepartment of Electrical and Electronic EngineeringDhaka University of Engineering & Technology, Gazipur

Member

…………………………………………………………..Dr. RumaProfessorDepartment of Electrical and Electronic EngineeringDhaka University of Engineering & Technology, Gazipur

Member

…………………………………………………………..Dr. Md. Arifur RahmanAssistant ProfessorDepartment of Electrical and Electronic EngineeringDhaka University of Engineering & Technology, Gazipur

Member

…………………………………………………………..Dr. Mohammad Jahangir AlamProfessorDepartment of Electrical and Electronic EngineeringBangladesh University of Engineering and Technology, Dhaka

Member(External)

Page 4: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Declaration

I declare that this thesis is my own work and has not been submitted in any form for another

degree or diploma at any university or other institute of tertiary education. Information

derived from the published and unpublished work of others has been acknowledged in the

text and a list of references is given.

Sobuj Kumar Ray Date: 10/10/2017

iii

Page 5: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Acknowledgements

All admiration is due to the Almighty, the creator of the universe who gave me theopportunity and strength to carry out this research work.

I would like to express my sincere gratitude to my honorable supervisor Prof. Dr. Md. RajuAhmed Head, Department of EEE, Dhaka University of Engineering and Technology,(DUET), Gazipur for his continuous and wholehearted support for my M. Engineering studyand research. His guidance helped me during all the time of my study and research. I amthankful to him for allowing me the freedom to pursue my own ideas and interests. I couldnot have imagined having a better advisor and mentor for my M. Engineering study.

I am obligated to pay my sincere gratitude to Dr. Md. Arifur Rahman, Assistant Professor,EEE, and DUET for his endless support in guiding me on my way during my M.Engineering thesis.

I am thankful to all the teachers and staffs of the Department of EEE of Dhaka University ofEngineering and Technology for their continuous support. I feel indebted to DhakaUniversity of Engineering and Technology, (DUET), Gazipur for providing a congenialenvironment for research as well as overall education.

My family members, specially my parents, wife and friends had a lot to do behind thisaccomplishment. I can never thank them enough for their sacrifice and appreciationthroughout my career.

Last but not the least, I am also thankful to the people, who have directly or indirectly helpedme and encouraged me to complete my thesis.

v

Page 6: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Abstract

In a power systems, when rotor step change is occurred then the voltage of the generator isreduced to a very low magnitude. When voltage magnitude falls below the desired voltagecalled voltage sag, which is one of the most severe problems to the power system and itcauses severe disruptions and results in substantial economic loss. To control andcompensate for the voltage drop, Flexible AC Transmission System (FACTs) is used.

This paper presents the comparative performance of PI and PID controller scheme withFlexible AC Transmission System (FACTs) devices, such as Static SynchronousCompensator (STATCOM), Static Synchronous Series Compensator (SSSC) and UnifiedPower Flow Controller (UPFC) in terms of improvements in transient stability, extenuationof system oscillations and furnishing voltage support in single machine infinite bus system(SMIB).

The performances of the system with PI and PID controllers which are the combination withSTATCOM, SSSC and UPFC are analyzed using matlab simulation software (Simulink).Rotor angle deviation and speed deviation has been analyzed for PI and PID with UPFC,SSSC and STATCOM. The performances of each combination are compared in term ofmaximum overshoot and settling time. Finally an optimal solution will be proposed based onthe simulation results.

vi

Page 7: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Abbreviations

PSS Power System Stabilizers

FACTs Flexible AC Transmission System

TSSC Thyristor Switched Series Capacitor

GTO Gate Turn-Off

ASD Aperiodic Small Disturbance

TSSC Thyristor Switched Series Capacitor

SVC Static Var Compensator

VSC Voltage Source Converters

TCSC Thyristor- Controlled Series Capacitor

TCPS Thyristor-Controlled Phase Shifter

STATCOM Static Synchronous Compensator

SSSC Static Synchronous Series Compensator

UPFC Unified Power Flow Controller

IPFC Interline Power Flow Controller

SMIBS Single Machine Infinite Bus System

PI Proportional Integral PID Proportional Integral and Derivative

DDC Direct Digital Control

DCS Distributed Control System

VSI Voltage Sourced Inverters

CSC Controlled Series Capacitor

TCR Thyristor Controlled Reactors

SSR Sub Synchronous Resonance

IPFC Interline Power Flow Controller

IPPC Inter Phase Power Controller

TCVL Thyristor-Controlled Voltage Limiter

vii

Page 8: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Contents

Acknowledgements v

Abstract viAbbreviations vii1 Introduction and Literature Review 1

1.1 Introduction 11.2 Literature Review 3

1.2.1 First Generation of FACTs 41.2.1.1 Static VAR Compensator (SVC) 41.2.1.2 Thyristor-Controlled Series Capacitor (TCSC) 41.2.1.3 Thyristor-Controlled Phase Shifter (TCPS) 51.2.2 Second Generation of FACTs 51.2.2 .1 A Static Compensator (STATCOM) 51.2.2 .2 Static Synchronous Series Compensator (SSSC) 51.2.2 .3 Unified Power Flow Controller (UPFC) 5

1.3 Objectives with Specific Aims and Possible Outcome 6 1.3.1 Objectives 6

1.3.2 Possible Outcomes 61.4 Outline of the Thesis 7

2 Optimizations of PI and PID Controllers 82.1 Introduction 82.2 PI Controller 82.3 PID Controller 92.4 Proportional Control 102.5 Integral Control 102.6 Derivative Control 112.7 Continuous PID 112.8 Tuning of PI Controller 122.9 Tuning of PID Controller 122.10 Conclusion 17

3 Single Machine Infinite Bus System for Stability Analysis 183.1 Introduction 183.2 Principle of Power Transmission 193.3 Power Flow Control Concepts 213.4 Single Machine Infinite Bus System 213.5 Stability Analysis 223.6 Swing Equation 233.7 Synchronous Machine Operation 233.8 Mathematical Representation of Single Machine Infinite Bus 253.9 Conclusion 26

4 Mathematical Representation of STATCOM 27

4.1 Introduction 274.2 Principle of Shunt Compensation 284.3 Static Synchronous Compensator 304.4 Mathematical Modeling of STATCOM 314.5 Block Diagram of STATCOM 33

Page 9: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

4.6 Conclusion 345 Mathematical Representation of SSSC 35

5.1 Introduction 355.2 Principle of series compensation 355.3 Static synchronous series compensator (SSSC) 375.4 Mathematical Modeling of SSSC 385.5 Block Diagram of SSSC 405.6 Conclusion 41

6 Unified Power Flow Controller 426.1 Introduction 426.2 UPFC Construction 436.3 Methodology 446.4 Phase-shifter transformer 476.5 Inter phase Power Controller (IPC) 476.6 Modeling of UPFC 48

6.6.1 Block Diagram of UPFC 496.7 Conclusion 50

7 Simulation Result of STATCOM, SSSC and UPFC with PI and PID Controller 517.1 Introduction 517.2 Simulation Result without FACTs Controller 517.3 Simulation Result with STATCOM, SSSC and UPFC 527.4 Simulation Result with STATCOM, SSSC, UPFC and PI 567.5 Simulation Result with STATCOM, SSSC, UPFC and PID 607.6 Comparison of Simulation Result 637.7 Comparison of Simulation with the Previous Work 647.8 Conclusion 64

8 Conclusion and Future Work 658.1 Conclusion 658.2 Recommendation 66

References 66

List of FiguresFigure 2.1: A typical PID control structure 9Figure 2.2: Schematic of the PID controller - non-interacting form 10Figure 2.3: Schematic of the PID controller - non-interacting form 11Figure 2.4: PID tuning with actuator constraints using matlab 13Figure 3.1: Two-machine power system 19Figure 3.2: Power against angle 20Figure 3.3: A single-machine infinite-bus power system 22Figure 3.4: Single machine infinite bus systems 25Figure 3.5: Equivalent circuit of single machine infinite bus system 25Figure 4.1: Transmission system with shunt compensation: simplified model 29Figure 4.2: Transmission system with shunt compensation: phase diagram 29Figure 4.3: Corresponding steady-state power exchange diagram. 30Figure 4.4: Schematic diagram of the SMIB system with STATCOM 31Figure 4.5: Equivalent circuit of SMIB system with STATCOM 31Figure 4.6: Simulation diagram with STATCOM. 33Figure 5.1: Transmission system with series compensation: simplified model. 36Figure 5.2: Phasor diagram of series compensator 36

Page 10: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Figure 5.3: A series compensated transmission line. 38Figure 5.4: Schematic diagram of the SMIB system with SSSC. 39Figure 5.5: Equivalent circuit of SMIB system with SSSC 39Figure 5.6: Simulation diagram with SSSC. 40Figure 6.1: Schematic diagram of three phases UPFC connected to a transmission line 43Figure 6.2: Single line diagram of UPFC and phasor diagram of voltage and current 44Figure 6.3: Simulink simulation model. 45Figure 6.4: Block diagram of lab scale model. 45Figure 6.5: Thyristor-controlled phase shifting transformer for transmission angle control 46Figure 6.6: Schematic diagram of the SMIB system with UPFC 48Figure 6.7: Equivalent circuit of SMIB system with UPFC 48Figure 6. 8: Simulation diagram with UPFC. 49Figure 7.1: Rotor angle deviation without FACTs device 51Figure 7.2: Simulation of STATCOM, SSSC and UPFC. 52Figure 7.3: Rotor angle deviation with SSSC, STATCOM and UPFC controller 53Figure 7.4: Rotor speed deviation with SSSC, STATCOM and UPFC controller 54Figure 7.5: Injected current and voltage by SSSC, STATCOM and UPFC controller 55Figure 7.6: Simulation Result with STATCOM, SSSC, UPFC with PI Controller. 56Figure 7.7: Rotor angle deviation of SSSC, STATCOM and UPFC with PI controller 57Figure 7. 8: Rotor speed deviation of SSSC, STATCOM and UPFC with PID controller 58Figure 7.9: Injected current and voltage by SSSC, STATCOM and UPFC with PI controller 58Figure 7.10: Simulations of STATCOM, SSSC, UPFC and PID 60Figure 7.11: Rotor angle deviation of SSSC, STATCOM and UPFC with PID controller 61Figure 7.12: Rotor speed deviation of SSSC, STATCOM and UPFC with PID controller 62Figure 7.13: Injected current and voltage by SSSC, STATCOM and UPFC with PID controller 63

List of Tables

Table -2.1: PI controller gain parameter 12Table -2.2: PID controller gain parameter 13Table -2.3: Tuning parameter of STATCOM 14Table -2.4: Tuning parameter of SSSC 15Table -2.5: Tuning parameter of UPFC 16Table -7.1: Rotor angle deviation with SSSC, STATCOM and UPFC controller 53Table -7.2: Rotor speed deviation SSSC, STATCOM and UPFC controller 54Table -7.3: Rotor angle deviation of SSSC, STATCOM and UPFC with PI controller 57Table -7.4: Rotor speed deviation of SSSC, STATCOM and UPFC with PI controller 58Table -7.5: Rotor angle deviation of SSSC, STATCOM and UPFC with PID controller 61Table -7.6: Rotor speed deviation of SSSC, STATCOM and UPFC with PID controller 62Table -7.7: Rotor angle deviation comparision 63Table -7.8: Rotor speed deviation comparision 64

Page 11: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Chapter 1

Introduction and Literature Review

1.1 Introduction

Power system low-frequency oscillations are the electromechanical oscillations which occurred

in systems with oscillation frequency up to a pair of Hz. The oscillations may persist for a

while and then disappear, or continuously grow to cause system collapse. A power system

fluctuation can be triggered by unrelenting faults of system operation, such as a three-phase to-

earth, short circuit or tripping of a transmission line. Power system large-disturbance rotor

angle stability or small-disturbance rotor angle stability [1] occurred due to collapse of power

system. The power system is unstable in terms of system oscillation stability if an oscillation is

of a sustained continuously or increasing magnitude. If the oscillation diminishes rapidly with a

damping ratio greater than 0.1, it is said that the power system is steady as far as oscillation

stability is concerned and the oscillation is of excellent damping. If the low-frequency

oscillation sustains for a certain time (several to tens of seconds) and sets eventually, it is

identified that the oscillation stability of the power system is maintained but with poor

oscillation damping. In October, 1964 power system oscillations were first reported in Northern

American power network during a trial of interconnection of the Northwest Power Pool and the

Southwest Power Pool [2]. After then the connection during tie line, a power oscillation of 0.1

Hz was examined on the tie line which was tripped out later. Since then power system

oscillation incident data has been reported in power transmission networks of many

countries.In late 1970s and early 1980s, power oscillations were investigated in the power

transmission arena from Scotland to England in Great Britain power network. Operational

result indicated that those oscillations were associated with relatively high level of power

transfer from Scotland to England. A series of tests carried out between 1980 and 1985

confirmed that the oscillations occurred when the power transfer from Scotland to England

reached a certain level andthe typical frequency of oscillations was around 0.5 Hz. This

difficulty of power oscillations was successfully solved by installing Power System Stabilizers

(PSS) at various power plants in Scotland [3].It is now well recognized that the cause of power

system oscillations is the poor damping of the so-called “electromechanical oscillation modes”

in the power system.

Page | 1

Page 12: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Poor damping could be caused by

(1) Large amount of long-distance power transmission;

(2) Weak inter-connection of large power sub-networks;

(3) Negative damping provided by fast-acting high-gainAVR.

Oscillation modes are classified into two types:-

(1) Local oscillation modes (or local modes) ;

(2) Inter-area oscillation modes (or inter-area modes).

Power system oscillations associated with local oscillation modes are the power oscillations of

one or a group of local generators against a large power network. Usually local generators send

power over a long distance to load centers in the large power network. Frequency of

oscillations often is about one or several Hz. Power oscillations related to interarea oscillation

modes are the power oscillations between two or more sub-networks in a power system. A

typical inter-area oscillation is the tie-line power oscillation between two weakly connected

areas in the power system. Inter-are an oscillations could involve many sub-networks to

oscillate against each other’s (referred to as intra-area oscillations in some literature). A power

system oscillation could be engaged by one oscillation mode only (local or inter-area oscillation

mode), the so-called “single-mode oscillation”. It could also participate by many oscillation

modes, typically local modes plus inter-area modes. This is the case of so-called “multimode

oscillations”. The trend of development of modern power systems is towards open access,

customer-driven planning and operation. This requires the system operation and control more

flexible and reliable. At the same time, due to the environmental considerations, conventional

ways to reinforce power systems to achieve flexibility and reliability are significantly

constrained. Power system researchers and engineers havelooked for new alternatives of

strengthening system operation and control without, for example, constructing new

transmission lines.

The National grid of Bangladesh failed after the transmission line experienced a "technical

glitch" that led to a cascade of failures throughout the national power grid, with power plants

and substations shutting down on 1st November 2014. In the year 2003, North America and

Europe have experienced a number of series blackouts [4-5]. These blackouts call for a novel

algorithm of controlling mechanism and minimizing the effect of failure for a safe and more

reliable power system operation. Such types of blackouts usually occur due to the disturbance

of rotor angle and corresponding instability of the turbines of generators. In order to reduce the

Page | 2

Page 13: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

effect of aperiodic small disturbance (ASD) [6] and large disturbance of rotor angle instability

[7], a number of approaches have been already deployed in many times.

The closed loop control system stables the single machine operating condition due to impact of

loss of generating unit and large sudden change in load. For the FACTS damping controllers of

the feedback signals are realized by evaluating the modal residues of each feedback signal to

the system input [8]. To stabilize the power system by damping interarea power oscillations and

by improving the transient stability of the system a thyristor switched series capacitor (TSSC)

has been incorporated [9]. Flexible ac transmission system (FACTS) devices are being applied

to improve power transfer capability of ac transmission networks and to enhance the

controllability of power flow and voltage thus augmenting power system stability due to

continuing developments in power electronic technologies.

1.2 Literature Review

There are two generations of power electronics-based FACTS controllers: the first generation

was conventional thyristor-switched capacitors and reactors, and quadrature tap-changing

transformers, the second generation employs gate tum-off (GTO) thyristor switched converters

as voltage source converters (VSCs). The Static Var Compensator (SVC), the Thyristor-

Controlled Series Capacitor (TCSC), and the Thyristor-Controlled Phase Shifter (TCPS) are

commonly used in first generation. The second generation has incorporated the Static

Synchronous Compensator (STATCOM), the Static Synchronous Series Compensator (SSSC),

the Unified Power Flow Controller (UPFC), and the Interline Power Flow Controller (IPFC).

The two groups of FACTS controllers have particularly different operating and performance

characteristics.The potential benefits of FACTS equipment are now widely recognized by

the power systems engineering and T&D communities. With respect to FACTS

equipment, voltage sourced converter (VSC) technology, which utilizes self-commutated

thyristor /transistors such as GTOs, Ws, IGCTs, and IGBTs, has been successfully applied in a

number of installations world-wide for Static Synchronous Compensators (STATCOM)

[10-14].For power system stability improvement, FACT devices multifariously are used in [15-

17]. For transient stability improvement and to compare among them

different methodology have been used with PI and PID controller [18-20].

Page | 3

Page 14: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

1.2.1 First Generation of FACT

1.2.1.1 Static VAR Compensator (SVC)

SVCs enhance the dynamic stability performance ofa power system by injecting appropriate

portion of a signal.For providing appropriate reactive power compensation the shunt type of

FACTS Controllers are used to either absorb or inject Vars into the system. The output of

SVCis adjusted to interchange capacitive or inductive current so as to maintain or control

specific parameters of the electrical power system. This is a general term for a thyristor

controlled reactor, and/or thyristor-switched capacitor or combination of both. SVC is based on

thyristors without the gate turn-off capability. It includes separate equipment for leading and

lagging vars; the thyristor-controlled or thyristor switched reactor for absorbing the reactive

power and thyristor-switched capacitor for supplying the reactive power. Static var

Compensator (SVC) which provides for reactive power compensation both during the leading

and lagging power factor conditions, hence the term hybrid.

1.2.1.2 Thyristor-Controlled Series Capacitor (TCSC)

Too mitigate the power system stability problem, Thyristor controlled series compensator

(TCSC) is a significant device in FACTs arena which is widely renowned as an effective and

efficient devices. TCSC controller can regulate the line impedance through the introduction of a

thyristor-controlled capacitor in series with the transmission line [23-29]. Series capacitors

compromise assured major advantages over the shunt capacitors. With shuntcapacitors, the

reactive power is proportional to the square ofbus voltage, whereas with series capacitors, the

reactive powerrises as the square of line current. For accomplishing same system benefits as

those ofseries capacitors, shunt capacitors required are three to six times more reactive power

rated than series capacitors. Furthermore shunt capacitors typically must be connected at the

midpoint, whereas no such requirement exists for series capacitors. A series capacitor is capable

of compensating for the voltage drop of the series inductance in a transmission line. During low

loading the system voltage drop is lower and at the same time the series compensation voltage

is lower. When loading increases and the voltage drop becomes higher, the contribution of

series compensation increases and therefore system voltage will be regulated as desired.

Page | 4

Page 15: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

1.2.1.3 Thyristor-Controlled Phase Shifter (TCPS)

A capacitive reactance compensator which consists of a series capacitive bank shunted by a

thyristor controlled reactor in order to provide smooth variation of series capacitive reactance.

1.2.2 Second Generation of FACTS

1.2.2.1 A Static Compensator (STATCOM)

Among the FACTS devices, the Static Synchronous Compensator (STATCOM) is able to

improve the transfer capability of a power system by enhancing voltage regulation and stability.

These can significantly provide smooth and for improving both damping of power oscillations

[30-32] and transient stability and rapid reactive power compensation for voltage support [33].

In addition the STATCOM carries a reactive current to regulate the voltage independently [34,

35, 36, 37] and control grid fault [38, 39].

1.2.2.2 Static Synchronous Series Compensator (SSSC)

The Static Synchronous Series Compensator (SSSC) comprises of a voltage source converter in

series with coupling transformer in the line. SSSC can inject a voltage with controllable

magnitude and phase angle at the line frequency and found to be more capable of handling

power flow control, improvements of transient stability and damping of oscillations [40-42].

1.2.2.3 Unified Power Flow Controller (UPFC)

There are two solid state voltage source converters (VSCs) in the unified power flow controller

(UPFC). The VSCs are colligated via a common DC link capacitor. One of the VSCs is

STATCOM which is shunt connected and the other is SSSC which is series connected. Both

VSCs injects a nearly sinusoidal current of variable magnitude. STATCOM injects current in

quadrature with the line voltage and at the point of association whereas SSSC injects current in

quadrature with the line current. STATCOM and SSSC exchange solely reactive power at their

terminal when they operate as standalone controllers with open dc link switch. At the point

when both of the VSCs works together with the dc link switch, the injected voltage which lies

in series with the line can take any angle with respect to the line current. As a result, the power

that is exchanged at the terminals of SSSC can take any form either real or reactive. The real

power can be exchanged by the SSSC with the line flows bi-directionally to the line through thePage | 5

Page 16: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

STATCOM and the common dc link capacitor. The UPFC has been used widely to improve

damping and dynamic performance of the system [43-44]and also enhancing reliability of

power system [45]. To incorporate synchronous AC grid, UPFC is also used in the system [46]

1.3 Objectives with specific aims and possible outcome

1.3.1 Objectives

This paper presents the comparative performance of PI and PID controller scheme with

Flexible AC Transmission System (FACTS) devices, such as Static Synchronous Compensator

(STATCOM), Static Synchronous Series Compensator (SSSC) and Unified Power Flow

Controller (UPFC) in terms of improvements in transient stability, extenuation of system

oscillations and furnishing voltage support in single machine infinite bus system (SMIB).The

specific aims are summarized as follows:

(i) To study transient and steady-state behaviour of Flexible AC Transmission System

(ii) To analysis rotor angle deviation and speed deviation for PI and PID controller with

STATCOM, SSSC and UPFC.(iii) To compare the simulation results in term of maximum overshoot and settling time.

1.3.2 Possible Outcomes

This paper presents to enumerate the rotor angle deviation and speed deviation by using two-

step methodology. The suggested techniques first simulates the STATCOM, SSSC, and UPFC

and then incorporate PI and PID controller with STATCOM, SSSC and UPFC. The actions of

STATCOM, SSSC, and UPFC will improve transient performance of the power system but

combine effect of PI and PID controller will show tremendous improvement. The PID

controller will perform betterthan PI controllerin term of maximum overshoot and settling time.

Page | 6

Page 17: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

1.4 Outline of the Thesis

The thesis is organized in 8 chapters.

In chapter 1 a general overview of FACTS devices are presented with a briefdescription. In chapter 2 the fundamentals of PID and PI controller are discussed. In this chapter the

tuning parameters of PI and PID controllers obtained for the system. Based on this

tuning parameter 20 different cases have been analyzed to optimized the controller. In chapter 3 the single machine infinite bus system is studied. The principle of power

system, stability analysis, and swing equation also has been discussed. The

mathematical model of single machine infinite bus power system also develops for

controlling of the system. In chapter 4, 5 and 6 the principle and mathematical equation has been developed for

STATCOM, SSSC and UPFC respectively. In these chapters block diagram of

STATCOM, SSSC and UPFC with PI and PID controllers has been incorporated. In chapter 7 simulation using matlab software (Simulink) has been performed for PI and

PID controller with STATCOM, SSSC and UPFC. From the simulationresults the

comparative performances of the system have beenanalysis. Further, in chapter 8 superior controller have been proposed as conclusion.

Chapter 2

Page | 7

Page 18: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Optimizations of PI and PID Controllers

2.1 Introduction

The first controllers with proportional, integral, and derivative (PID) feedback control action

became commercially available during the 1930s. The 1940s saw widespread acceptance in

industry of pneumatic PID controllers, and their electronic counterparts entered the market in

the 1950s. Digital hardware has been routinely used since the 1980s with significant impact on

process control. Even several decades after three-mode controllers were introduced; the vast

majority of controllers used in the chemical process industry are based on PI/PID models [48].

The popularity of these controllers has led to research on tuning methods, resulting in hundreds

of publications on this topic. Ziegler-Nichols tuning relations and Cohen-Coon tuning rules are

among the earliest published methods. Tuning relations based on error criteria are more recent

model-based tuning rules, which offer improvements over earlier tuning methods. Tuning rules

also exist for unstable processes as well as for tuning in the presence of plant model mismatch

[49].

2.2 PI Controller

PI controller has been used in recent years with the purpose of improving the transient and the

steady-state performance and also for rejection of disturbances caused by operation events

throughout startup [50-52].It comprises of proportional action and integral action. The

proportional controller dimineshes the system error by using proportion of system error to

control the system. However, this incorporate an offset error into the system. The integral

controller output is proportional to the amount of time there is an error present in the system.

The integral action eliminates the offset which is introduced by the proportional control but

incorporates a phase lag into the system.

2.3 PID Controller

Page | 8

Page 19: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

A typical structure of a PID control system is shown in Figure 1.2,where it has been seen that in

a PID controller , the error signal e(t) is used to generate the proportional, integral, and

derivative actions, with the resulting signals weighted and summed to form the control signal

u(t) applied to the plant model [53].

Figure 2.1: A typical PID control structure

A mathematical description of the PID controller is [4]

u (t )=KP [e (t )+1T i∫0

t

e (τ )dτ+T dde(t )dt ] (1 .1)

Where u(t) is the input signal to the plant model, the error signal e(t) is defined as

e(t) =r(t) − y(t),and r(t) is the reference input signal.

PID controller consists of Proportional Action, Integral Action and Derivative Action. It is by

far the most common control algorithm. PID controller’s algorithm is mostly used in feedback

loops [48]. PID controllers can be implemented in many forms. It can be implemented as a

stand-alone controller or as part of Direct Digital Control (DDC) package or even Distributed

Control System (DCS). The latter is a hierarchical distributed process control system which is

widely used in process plants such as pharmaceutical or oil refining industries [54]. The

schematic of the PID controller is explained in the following figure 2.2. Such set up is known

as non- interacting form or parallel form.

Page | 9

Disturbance d(t)

PID Controlleru(t) y(t)

e(t)r(t) PlantModel

Controller

-

Measurementnoise

Page 20: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Plant

P

I

Figure 2.2 : Schematic of the PID controller.

The behavior of the proportional, integral, and derivative actions will be demonstrated

individually.

2.4 Proportional Control

Proportional control is denoted by the P-term in the PID controller. The proportional controller

output uses a ‘proportion’ of the system error to control the system. However, this introduces an

offset error into the system.

Pterm=K P×e( t) (2. 2)

Where, is the error signal and KP is the gain of the P controller.

2.5 Integral Control

Integral control is denoted by the I-term in the PID controller and is used when it is required

that the controller correct for any steady offset from a constant reference signal value. Integral

control overcomes the shortcoming of proportional control by eliminating offset without the

use of excessively large controller gain but introduces a phase lag into the system.

Page | 10

++

ErrorInput+

_ Output

D

)(te

Page 21: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

C(S)

)1

1( di

STST

K Plant

Iterm=K I×∫e (t )dt (2.3)

Where, KI is gain of the integral controller

2.6 Derivative Control

If a controller can use the rate of change of an error signal as an input, then this introduces an

element of prediction into the control action. Derivative control uses the rate of change of an

error signal and is the D-term in the PID controller. Derivative control is used to

reduce/eliminate overshoot and introduces a phase lead action that removes the phase lag

introduced by the integral action.

Dterm=K D×d {e( t)}dt (2. 4)

Where, KD is the gain of the derivative controller.

2.7 Continuous PID

The three controllers when combined together have been represented by the following transfer

function.

Gc ( s )=K (1+1sT i

+sT d) (2. 5)

This has been illustrated in Figure 2.3 in the following block diagram

Figure 2.3: Block diagram of continuous PID controller

Page | 11

R(S) +_

Page 22: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

What the PID controller does is basically is to act on the variable to be manipulated through a

proper combination of the three control actions that is the P control action, I control action and

D control action. The P action is the control action that is proportional to the actuating error

signal, which is the difference between the input and the feedback signal. The I action is the

control action which is proportional to the integral of the actuating error signal. Finally, the D

action is the control action which is proportional to the derivative of the actuating error signal.

With the integration of all the three actions, the continuous PID has been realized. This type of

controller has been widely used in industries all over the world. In fact a lot of research, studies

and application have been discovered in the recent years.

2.8 Tuning of PI Controller

The PI controller tuning parameters and have been optimized by PID tuning with

actuator constraint.

Table 2.1PI Controller Gain Parameter

Parameters

Gain with actuator constraints for linear block 3.715 0.4762

Gain for simulation 3.715 0.4762

2.9 Tuning of PID Controller

The PID controller is a “three modes” controller. The value of three tuning parameters the

proportional, integral and derivative determine the performance and activity of these

controllers. The three control actions that are P control action, I control action and D control

action work together to get the continuous PID controller. PID controller has been developed in

order to improve transient performance and speed control of motor [56-57] generator. A

discrete PID controller is incorporated into the system for diminishing nonlinear damping [58].

The tuning value of gain (KP, KI, KD) may be obtained from Steepest Gradient Descent Method

(SDGM) [59] and as well as Genetic Algorithms Method [60] and also Ziegler–Nichols tuning

Page | 12

PK IK

PK IK

Page 23: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

method. In the proposed controller, the gain parameter ( , and ) of PID controller has

been tuned by PID tuning with actuator constraint as shown in figure 2.4. This gain parameters

have been manupulated due to non-linear block present in the system which have been shown

in Table 2.

Figure 2.4: PID Tuning with Actuator Constraints Using Matlab.

Table 2.2PID Controller Gain Parameter

Parameters

Gain with actuator constraints for linear block 1.646

0.7671 0.4633

Gain for Proposed Methodology 15 0.01083

0.4673

Tuning parameters for STATCOM, SSSC and UPFC are summarized in the following table 2.3,

2.4 and 2.5.

Page | 13

PK IK DK

PK IK DK

Page 24: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Table 2.3 Tuning Parameter of STATCOM

Page | 14

Page 25: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Sl.

No

Maximum Overshoot Setting Time

Angle Speed Angle Speed

1 55 0.25 0.25 4 43 0.23 0.27

2 20 0.1 0.50 1.25 38 0.45 0.4

3 15 0.2 0.1 5.625 49 0.40 0.30

4 10 1 0.6 0.375 23 0.57 0.62

5 11 0.3 0.4 1.25 29 0.43 0.45

6 12 0.35 0.8 1.25 22 0.52 0.4

7 30 1 0.7 0.5 44 0.30 0.39

8 40 0.9 0.8 0.3125 47 0.25 0.19

9 35 0.1 0.2 1.25 62 0.23 0.22

10 45 0.3 0.1 0.75 81 0.90 0.17

11 50 0.98 0.01 6.25 90 16 0.16

12 50 0.30 0.25 6.25 72 0.11 0.16

13 13 0.19 0.15 25.625 9.6 0.44 0.38

14 140 0.27 0.33 6.25 110 0.46 0.18

15 100 0.39 0.36 6.25 90 0.40 0.17

16 110 0.45 0.73 4.25 85 0.25 0.21

17 90 0.38 0.74 6.25 70 0.23 0.2

18 200 0.56 0.19 5.8 95 0.25 0.2

19 300 0.86 0.43 6.25 96 0.21 0.18

20 250 0.9 0.2 6.25 82 0.25 0.19

From the above table 2.3 it has been found that for STATCOM the values of KP,KIand KDare 55

0.25 and 0.25 respectively. For these tuning parameters, maximum overshoot and settlingtime

of rotor angle deviation are 0.001 and 0.11respectively. For the same tuning

parameters,maximum overshoot and settling time of rotor speed deviation are 0.72 and

0.16respectivelyPage | 15

PK IK DK

Page 26: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Table 2.4Tuning Parameter of SSSC

Sl

No

Maximum Overshoot Setting Time

Angle Speed Angle Speed

1 20 0.01083 0.4673 1.875 43 0.27 0.30

2 10 0.2 0.50 1.25 27 0.40 0.44

3 30 1 1.3 6.50 34 0.23 0.25

4 35 0.9 1 6.25 44 0.3 0.26

5 5 0.8 0.4 0.125 18 0.6 0.65

6 10 1 0.7 4.30 23 0.32 0.35

7 15 0.9 0.75 6.25 28 0.35 0.4

8 12 0.8 0.6 0.625 27 0.3 0.42

9 18 0.1 0.3 5.625 48 0.37 0.3

10 42 2.3 0.5 6.25 50 0.25 0.25

11 45 2 0.5 1.875 67 0.27 0.2

12 50 2.5 0.123 6.25 88 0.22 0.19

13 40 1 0.9 6.67 42 0.20 0.2

14 60 0.5 0.9 6.25 63 0.19 0.23

15 70 1.6 0.55 1.25 84 0.30 0.18

16 11.5 0.5 0.5 1.875 29 0.4 0.41

17 33 0.65 0.76 6.25 28 0.27 0.47

18 13 0.35 0.28 5.625 42 0.45 0.43

19 18 0.97 0.16 10.625 52 0.44 0.46

20 24 0.72 0.61 1.25 43 0.33 0.34

From the above table 2.4 it is found that for SSSC the best tuning values of and

are40, 1 and 0.09 respectively. For these tuning parameters, maximum overshoot and settling

Page | 16

PK IK DK

PK IK DK

Page 27: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

time ofrotor angle deviation are 0.001 and 0.25respectively. For the same tuning parameters,

maximum overshoot and settling time of rotor speed deviation are 0.50 and 0.25respectively.

Table 2.5 Tuning Parameter of UPFC

Sl

No

Maximum Overshoot Setting Time

Angle Speed Angle Speed

1 15 0.01083 0.4673 6.25 27 0.45 0.55

2 11 0.2 0.5 12.5 23 0.46 0.65

3 18 0.15 0.67 6.25 27 0.4 0.55

4 60 0.9 0.5 6.25 54 0.25 0.30

5 50 0.8 0.6 5.23 46 0.35 0.25

6 55 0.7 0.2 3.42 65 0.4 0.27

7 5 0.86 0.34 4.52 17 0.8 0.85

8 70 0.64 0.26 6.3 27 0.30 0.67

9 75 0.85 0.42 4.7 30 0.27 0.62

10 80 0.67 0.55 5.1 60 0.25 0.30

11 85 0.77 0.41 3.6 65 0.80 0.32

12 97 0.32 0.21 7.2 82 0.22 0.23

13 77 0.86 0.52 5.1 60 0.31 0.30

14 46 0.34 0.47 3 26 0.15 0.26

15 64 0.39 0.60 4.5 46 0.25 0.22

16 67 0.43 0.47 5.30 55 0.30 0.27

17 82 0.60 0.50 4.30 62 0.25 0.25

18 79 0.80 0.20 5.88 75 0.20 0.40

19 89 0.42 0.69 3.49 62 0.25 0.37

20 65 0.32 0.60 4.14 58 0.21 0.23

Page | 17

PK IK DK

Page 28: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

From the above table 2.5 it has been found that for UPFC the values of and are46

0.34 and 0.47 respectively. For these tuning parameters, maximum overshoot and settling time

of rotor angle deviation are 0.001 and 0.15respectively. For the same tuning parameters,

maximum overshoot and settling time of rotor speed deviation are 0.46 and 0.22respectively.

2.10Conclusion

This paper proposes novel approaches for data driven of nonlinear system. Tuning methods for

PI and PID controllers are proposed such that the response of the compensated system has

overshoot below a prescribed value. All the development of the methodologies is simple and

relies solely on concepts introduced in a frequency-domain-based control system. The tuning

values of controller achieved first for linear part of system using actuator constraint which is

the iterative tuning method. Based on the tuning values twenty iterations completed

comprehensively for STATCOM, SSSC and UPFC to get the tuning parameter of PID

controller.

Page | 18

PK IK DK

Page 29: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Chapter 3

Single Machine Infinite Bus System for Stability

Analysis

3.1 Introduction

Small signal stability investigation is vital as the system outage due small signal perturbation

being unknown to the system operators. The small signal disturbance may be initiating event

for large system outage. The Single Machine Infinite Bus (SMIB) power system helps in tuning

the controllers at one machine without considering the effect of other machines in the power

system. The effect of disturbance seen by the machine being 100%, whereas, in interconnected

power system the effect gets distributed among different machines. Therefore, the controller

tuning with SMIB remains valid for multi-machine power system as well. Small signal stability

investigations usually involve the analysis of the linearized system governing equations that

define the power system dynamics. Whereas, transient stability of the power system deals with

system analysis, following a severe disturbance, such as a single or multi-phase shorts circuit or

a generator loss. Under these conditions, the linearized power system model does not remain

valid. A third term, dynamic stability, has been widely used in the literature as a class of rotor

angle stability. The stability criterion with respect to synchronous machine equilibrium has

been presented. The mathematical model presented for small scale stability state is a set of

linear time invariant differential equations [61]. P.M. Anderson and A.A. Fouad, had

mentioned, the stability under the condition of small load changes has been called steady state

stability [62]. The concepts of synchronous machine stability as affected by excitation control

and the phenomenon of stability of synchronous machines under small perturbations in the case

of single machine connected to an infinite bus through external reactance has been presented by

F.P.demello and C. Concordia. The analysis also develops insights into effects of thyristor type

excitation systems and establishes understanding of the stabilizing requirements for systems

Page | 19

Page 30: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

[63]. These stabilizing requirements include the voltage regulator gain parameters as well as the

transfer function characteristics for a machine speed derived signal superposed on the voltage

regulator reference for providing damping machine oscillations [64]. Trends in design of power

system components have resulted in lower stability and led to increased reliance on the use of

excitation control to improve stability [62]. IEEE Committee Report (1981), the working group

of IEEE on computer modeling of excitation systems, in their report has discussed excitation

system models suitable for use in large scale stability studies [65]. Michael J. Basler Richard C.

Schaefer discusses power system instability and the importance of fast fault clearing

performance to aid in reliable production of power [66]. In the past decades, the utilization of

supplementary excitation control signals for improving the dynamic stability of power systems

has received much attention.

3.2 Principle of Power Transmission

To model the operation, a transmission line can be represented by a series reactance and with

the sending and receiving end voltages. This is shown in figure 3.1 for one phase of a three-

phase system. Therefore, all quantities such as voltages and currents are defined per phase.

V s and V r are the per-phase sending end voltage and receiving end voltage, respectively.

They represent Thevenin equivalents with respect to the midpoint. The equivalent impedance

(jX/2) of each Thevenin equivalent represents the ‘’short-circuit impedance’’ located on the

right or left side of that midpoint. For the sake for the simplicity, let us assume that the

magnitudes of the terminal voltages remain constant, equal to V. That is V s = V R =

V m =V [67].

Page | 20

IX/2X/2

2/ VVRMV2/ VVS

Page 31: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Figure 3.5: Two-machine power system

Figure 3.6: Power against angle

Active (real) power P is defined as

Equation 3-1

(3.1)

Reactive power Q is defined as(3.2)

Page | 21

Power

Angle

P

Q

2

MaxP

MaxQ

SinX

VP

2

)1(2

CosX

VQ

Page 32: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Active power P becomes the maximum at δ=900

, and reactive power Q becomes

the maximum at δ=1800

.The plots of the active power and reactive power Q

against the angle δ are shown in Figure 3.2. For a constant value of line reactance X, varying

angle δ can control the transmitted power P. However, any changes in active power also change

the reactive power demand on the sending and receiving ends. Power and current flow can be

controlled by one of the following means [67].

Applying a voltage in the midpoint can also increase or decrease the magnitude of power.

Applying a voltage in series with the line, and in phase quadrature with the current flow, can

increase or decrease the magnitude of current flow. Because the current flow lags the voltage

by 900

, there is injection of reactive power in series.

If a voltage with a variable magnitude and a phase is applied in series, then varying the

amplitude and phase angle can control both the active and reactive current flows. This requires

injection of active power and reactive power in series.

Increasing and decreasing the value of the reactance X cause a decrease and an increase of the

power height of the curves, respectively, as shown in Figure 3.2. For a given power flow,

varying X correspondingly varies the angle δ between the terminal voltages.

Power flow can also be controlled by regulating the magnitude of sending and receiving end

voltages V s and V r . The type of control has much more influence over the reactive power

flow than the reactive power flow.Therefore, we can conclude that the power flow in a

transmission line can be controlled by

(1) Applying a shunt voltage V m at the midpoint,

(2) Varying the reactance X, and

(3) Applying a voltage with a variable magnitude in series with line.

These are easily done by FACTS devices

Page | 22

X

VP

2

max

X

VQ

2

max 2

Page 33: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

3.3 Power Flow Control Concepts

To control power flow, it is necessary to be able to maintain or change line impedances, bus

voltage magnitudes, or phase angle differences. In this work, a power flow control device refers

to any device that changes or maintains one or more of these parameters. Power flow control

devices can be coordinated to affect system states in a way which attains some objective. There

are many power flow control devices, including the well-studied FACTS devices. Power flow

control devices often work by changing an effective admittance or impedance. Effective

impedance can either be changed through the use of physical capacitors and inductors or

through the use of a voltage source to perform active impedance injection.

3.4 Single Machine Infinite Bus System

The configuration of a power system has been shown in figure 3.3 where a generator sends

power to a large network. Capacity of the large network is much greater than that of the

generator such that operation of the large network is not affected at all by any changes in the

part of the power system on the left-hand side of bus bar b in figure 3.3. This effectively means

that the voltage and frequency at bus bar b are constant when the focus of the study is the part

of the left-hand side of the power system. Thus, from the point of view of operation of the part

of right-hand side of the power system, capacity of the large network is “infinite”. Hence, bus

bar b is called the “infinite bus bar”, and the part of the power system on the left-hand side of

bus bar b is a “single-machine infinite-bus” power system. The single-machine infinite-bus

power system is an approximate representation of a kind of real power systems, where a power

plant with a generator or a group of generators are connected by transmission lines to a very

large power network.

Page | 23

tV

bVtX

A large network

bItP

busbar b

Page 34: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Figure 3.7: A single-machine infinite-bus power system

3.5 Stability Analysis

The tendency of a power system to develop restoring forces equal to or greater than the

disturbing forces to maintain the state of equilibrium is known as “STABILITY”.

The problem of interest is one where a power system operating under a steady load condition is

perturbed, causing the readjustment of the voltage angles of the synchronous machines. If such

an occurrence creates an unbalance between the system generation and load, it results in the

establishment of a new steady-state operating condition, with the subsequent adjustment of the

voltage angles. The perturbation could be a major disturbance such as the loss of a generator, a

fault or the loss of a line, or a combination of such events. It could also be a small load or

random load changes occurring under normal operating conditions. Adjustment to the new

operating condition is called the transient period. The system behavior during this time is called

the dynamic system performance, which is of concern in defining system stability. The main

criterion for stability is that the synchronous machines maintain synchronism at the end of the

transient period. So we can say that if the oscillatory response of a power system during the

transient period following a disturbance is damped and the system settles in a finite time to a

new steady operating condition, we say the system is stable. If the system is not stable, it is

considered unstable. This primitive definition of stability requires that the system oscillations

be damped. This condition is sometimes called asymptotic stability and means that the system

contains inherent forces that tend to reduce oscillations. This is a desirable feature in many

systems and is considered necessary for power systems. The definition also excludes

continuous oscillation from the family of stable systems, although oscillators are stable in a

mathematical sense. The reason is practical since a continually oscillating system would be

undesirable for both the supplier and the user of electric power. Hence the definition describes a

practical specification for an acceptable operating condition. The stability problem is concerned

with the behavior of the synchronous machines after a disturbance. For convenience of

analysis, stability problems are generally divided into two major categories-steady state

stability and transient state stability.

3.6 Swing Equation

Page | 24

Page 35: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Under normal operating conditions, the relative position of the rotor axis and the resultant

magnetic field axis is fixed. The angle between the two is known as the power angle or torque

angle. During any disturbance, rotor will decelerate or accelerate with respect to the

synchronously rotating air gap mmf, a relative motion begins. The equation describing the

relative motion is known as the swing equation.

3.7 Synchronous Machine Operation

Consider a synchronous generator with electromagnetic torque Te running at synchronous speed

ωsm.

During the normal operation, the mechanical torque

A disturbance occur will result in accelerating/decelerating torque ( if

accelerating, if decelerating).

By the law of rotation

(3.3)

Where J is the combined moment of inertia of prime mover and generator

is the angular displacement of rotor with respect to stationery reference frame on the stator

is the constant angular velocity

Taking the derivative of we obtain

Page | 25

em TT

ema TTT 0aT

0aT

emam TTT

dt

dJ

2

2

m

msmm t sm

m

Page 36: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

(3.4)

Taking the second derivative of

(3.5)

Substituting into law of rotation-

Multiplying to obtain power equation (3.6)

(3.7)

Where and are mechanical power and electromagnetic power.

Swing equation in terms of inertial constant M

(3.6)

Relations between electrical power angle and mechanical power angle and electrical

speed and mechanical speed

Page | 26

dt

d

dt

d msm

m

m

2

2

2

2

dt

d

dt

d mm

emam TTT

dt

dJ

2

2

m

ememmmammm

m PPTTTdt

dM

dt

dJ

2

2

2

2

mP eP

eme

m PPdt

dM

2

2

m

Page 37: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

1 2

Where p is pole number

Swing equation in terms of electrical power angle

(3.7)

Converting the swing equation into per unit system

(3.8)

Where H is the inertia constant

3.8 Mathematical Representation of Single Machine Infinite Bus

A generator connected to a substation whose bus voltage and frequency are constant through a

very long transmission line. The characteristic of bus voltage remains constant through the

power supplied or consumed by any device connected to it.

Figure 3.8: Single machine infinite bus systems

Page | 27

m

p 2

m

p 2

eme

m PPdt

dM

P

2

22

)()(2

22puepum

es

PPdt

dH

L

1

L

3

V tm VV t

L

4

L

2 Infinite

bus

Page 38: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

The equivalent circuit of the system is shown in Figure 3, where represent the equivalent

reactance between machine internal bus and the impedance represent the equivalent

reactance between the bus m and the infinite bus.

Figure 3.5: Equivalent circuit of single machine infinite bus system

The magnitude of the machine internal voltage and the infinite bus voltage is represented by E’

and V, respectively. The equation describing the relative motion between rotor axis and the

magnetic field axis is known as the swing equation. Under normal condition, the rotor remains

to its original position but if the disturbance is created due to any fault or sudden load, the rotor

comes to a new operating power angle relative to the synchronous revolving field.

The swing equation can be express in term of inertia constant

(3.9)

(3.10)

Here δ= the rotor angle deviation,

= the rotor angle deviation,

M= moment of inertia,

Pm = input mechanical power, and

D= damping coefficient.

Page | 28

1X

2X

V m = V m <E’=E’<δV=V<0

jX

1

jX

2

dt

d

)(1

2

2

DPPMdt

d

dt

dem

Page 39: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

The simplified form of power flow equation in Figure 3 can be written as

(3.11)

Where

(3.12)

3.9 Conclusion

Power industries are modernized to provide effective operation to more consumers at lower

prices and better power efficiency. Due to interconnectivity of power system the complexity of

the power systems has been mounting. Load demand also increases linearly with the increase in

users. Since stability phenomenon limits the transfer capability of the system, there is a need to

confirm stability and reliability of the power system due to economic reasons. With these

conditions, authorities and researchers were continually tasked to find simple, effective and

economical strategy of achieving stabilization of the power system, which is considered of

highest priority. Thus, because of the importance of the stability of the power systems,

stabilizing control techniques have been used for the single-machine power system with the

help of intelligent methods. The optimal sequential design for single-machine power systems is

very essential. As a result, serious consideration is now being given on the concern of

stabilization control. In recent times, the utilization of optimization techniques becomes

possible to deal with control signals in power system.

Chapter 4

Mathematical Representation of STATCOM

4.1 Introduction

Static VAR compensator (STATCOM) is a device whose capacitive or inductive current can be

controlled independently without affecting ac system voltage.It is well established that the

steady-state transmittable power can be improved and the voltage profile along the line

controlled parameter by appropriate reactive shunt compensation. The methodology of this

reactive compensation isto create it more hormonal situation to prevail load demand of power

Page | 29

SinPPe max

21

'

max XX

VEP

Page 40: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

system. Thus, shunt connected, fixed or mechanically switched reactors are applied to minimize

line overvoltage under light load conditions, and shunt connected, fixed or mechanically

switched capacitors are applied to maintain voltage levels under heavy load conditions. To

maintain a constant DC voltagethe STATCOM capacitor bank is used for thevoltage-source

converter operation. Common STATCOM mayvary from six-pulse topologies up to forty-eight-

pulse topologies that consist of eight six-pulse converters operated froma common dc link

capacitor [68-69].TheSTATCOM is optimalsuitable device for voltage control since it may

swiftlyinject or absorb reactive power to stabilize voltage excursions [70-71] and has been

shown to perform very well inactual operation [69]. Several prototype STATCOM installations

are currently in operation [69], [72]. The ability of the STATCOMto maintain a pre-set voltage

magnitude with reactive powercompensation has also been shown to improve transient stability

[70] and sub synchronous oscillation damping [73-75].In this section, basic considerations to

enhance the transmittable power by ideal shunt-connected var compensation will be reviewed

in order to provide a foundation for power electronics-based compensation and control

techniques to meet specific compensation objectives. The ultimate objective of applying

reactive shunt compensation in a transmission system is to increase the transmittable power.

This may be prerequisite to develop the steady-state and transient transmission characteristics

as well as the stability of the system. The applications of reactive power compensators based on

voltage-sourced inverters (VSI), such as Static Synchronous Compensator (STATCOM) [76],

are increasing in different power levels.These devices have several advantages over

conventional thyristor-based converters solutions in terms of the speed of response, flicker

compensation, flexibility, and minimal interaction with the supply grid.

Reactive compensation has been used widely in the power industry in order to provide voltage

regulation as well as improve transient stability [77]. Compared with SVCs, the voltage

sourced converter (VSC) based STATCOM has better compensating capability, faster response,

less harmonics and smaller physical size, and thus becomes a serious competitive alternative to

conventional SVCs [78]. This is used for voltage regulation at a given bus against load

variations or voltage support during generation or line outages in power systems.

4.2 Principle of Shunt Compensation

The power system is connected in parallel with shunt FACT devices for shunt compensation.It

works as a controllable current source. Shunt compensation is of two types: Shunt capacitive

Page | 30

Page 41: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

compensation this method is used to improve the power factor. When an inductive load is

connected to power system, power factor lags because of lagging load current. To compensate,

a shunt capacitor is connected which draws current leading the source voltage. The net result is

improvement in power factor. Shunt inductive compensation this method is used either when

charging the transmission line, or, when there is very low load at the receiving end. Due to very

low or no load, very low current flows through the transmission line, shunt capacitance in the

transmission line causes voltage amplification (Ferranti Effect). The receiving end voltage may

significantly increasethan the sending end voltage. To compensate, shunt inductors are

connected across the transmission line.The objectives of STATCOM are to provide fast acting

dynamic reactive compensation for voltage support during contingency events, providing

dynamic and flexible voltage and reactive power support at their Substation, improving

power system and voltage stabilization to increase power transfer opportunities [79]. Shunt-

connected reactors are used to reduce the line over voltages by consuming the reactive power,

while shunt-connected capacitors are used to maintain the voltage levels by compensating the

reactive power to transmission line.

A simplified model of a transmission system with shunt compensation is shown in Figure 4.1.

The voltage magnitudes of the two buses and the phase angle may consider V andδ

respectively. The transmission line is assumed lossless and represented by the reactance X L .

At the midpoint of the transmission line, a controlled capacitor C is shunt-connected. The

voltage magnitude is maintained as V at the bus of transmission line.

Page | 31

j XL2

V<

δ2

j XL2

Bus 2Bus 1 V<

−δ2

I2I1

CIC

Page 42: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Figure 4.9: Transmission system with shunt compensation: simplified model

Figure 4.10: Transmission system with shunt compensation: phase diagram

As discussed previously, the active powers at bus 1 and bus 2 are equal.

(4.1)

The injected reactive power by the capacitor to regulate the voltage at the mid-point of the

transmission line is calculated as:

(4.2)

From the power angle curve shown in Figure 4.3 the transmitted power can be significantly

increased, and the peak point shifts from δ=90º to δ=180º. The shunt compensation can

improve operation margin of power system and also system stability effectively. The voltage

support function of the midpoint compensation can easily be extended to the voltage support at

the end of the radial transmission, which will be proven by the system simplification analysis in

a later section.

4.3 Static Synchronous Compensator (STATCOM)

Static synchronous compensator (STATCOM) is a fast acting device which is the representative

of FACTS family. A promising technology has been used comprehensively for reactive power

Page | 32

V c

V<

−δ2

V<

−δ2

I2I1

2sin

22

21

LX

VPP

)2

cos1(42 L

C X

VQ

Page 43: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

1 2

control of power system. It is also known as static synchronous condenser. It is a controlling

device used on AC electricity network. STATCOM is a power electronic device. If the SVS is

used strictly for reactive shunt compensation, like a conventional static var compensator, the dc

energy source can be a relatively small dc capacitor, as shown in Figure 4.4. By measuring the

ripple input current the specification or size of the capacitor of particular converter may design.

In this case, interchange of the steady-state power between the SVS and the alternating current

system can only be reactive. The converter maintains the voltage level by using reactive power

generation of SVS. This is accomplished by making the output voltages of the converter lag the

system voltage by a small angle. The convertor furnishes the desired voltage level by absorbing

real power form the ac system. For increasing and decreasing of the capacitor voltage similar

method can be used to control the var generation or absorption. The dc capacitor maintains an

energy balance during the dynamic fluctuation of the var output [79]

Figure 4.3: Corresponding steady-state power exchange diagram

4.4 Mathematical Modeling of STATCOM

STATCOM is a controlled shunt current source that current is in quadrature with its terminal

voltage.

Page | 33

At AC terminal

I qSupply Q

V> V TV AC

At DC terminal

I dc≅0+V dc≅0

Absorb QV> V T

L

3

L

1

VmV t

Page 44: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Figure 4.4: Schematic diagram of the SMIB system with STATCOM.

The STATCOM is placed in the bus m and is represented by a shunt reactive current source

as show in Figure 4 and Figure 5.

Figure 4.5: Equivalent circuit of SMIB system with STATCOM

Where

(4.3)

Positive and negative signs indicate for the inductive and capacitive respectively.

Here

Page | 34

Infinite bus

L

2

L

4

VSC

C

sI

V m = V m <E’=E’<δV=V<0

jX

1

jX

2

Is

)90( mjSS eII

Page 45: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

(4.4)

With the STATCOM the output power of the machine can be written as

(4.5)

Where

(4.6)

is positive when δ oscillates in between zero and π. Equation of suggests that it can be

modulated by modulating the shunt reactive current . For enhancement of power system

damping the shunt reactive current can be modulated in propagation to the rotor speed

deviation ω. With this control signal can be expressed as

, (4.7)

Where, K1 is a positive constant.

Putting all the values in equation (4.5)

(4.8)

From Equation (4.3) in setting value of

Page | 35

)cos

sin(tan

2'

1

21

XEVX

EXm

eP

Se IfPP )(sin 1max

)sin()(21

2'

1 mXX

XEf

mP

sI

sI

1KI S maxmaxSSS III

121

2'

21

'

)sin()(

sin)(

KXX

XE

XX

EP me

eP

Page 46: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Output

D ω

(4.9)

From equation (4.9) we may draw the block diagram of the system with STATCOM as depicted

the following in Figure 4.9.

4.5 Block Diagram of STATCOM

Figure 4.8: Simulation diagram with STATCOM

Figure 4.9 represents the simulation model for dynamic analysis of power system with

STATCOM. represents the shunt reactive current modulated by the STATCOM in

proportion to speed deviation of the machine,

PID: Proportional Integral Derivative Controller

Page | 36

})sin()(

sin)(

{1

121

2'

21

'

DK

XX

XE

XX

EP

Mdt

dmm

Pe = Pmax Sinδ+f1(δ)

-Pe

ω δPm

-

I s

1KI s

Page 47: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

: Step change in mechanical input to the turbine.

eP : Electrical power output of the machine.

M : Machine moment of inertia.

ω : Rotor speed deviation.

δ : Rotor angle deviation.

D : Damping coefficient.

4.6 Conclusion

In this paper, PID controller is proposed to control STATCOM for improving power system

transient stability and system damping. Input parameters of controller are chosen carefully to

provide to considerable damping of power system. The range of each controller chosen from

actuator constant for linear portion of controller and then the tuning parameter rectify for better

performance. The single machine infinite bus system has been controlled by above controllers.

The performance of comparison results depict that the STATCOM improves the stability of

power system consideration part but after incorporating PI and PID controllers’ improvement of

stability is tremendous.

Page | 37

mP

Page 48: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Chapter 5

Mathematical Representation of SSSC

5.1 Introduction

The ac power transmission over long transmission lines is primarily limited by the series

reactive impedance of the line. Though series capacitive compensation was used decades ago to

diminish a portion of the reactive line impedance and thereby increase the transmittable power.

Subsequently, within the FACTS initiative, it has been established that variable series

compensation is highly effective in both controlling power flow in the line and in improving

stability. Controllable series line compensation is a cornerstone of FACTS technology. It can be

used for proper utilization of transmission assets to control the power flow of transmission

lines. It can be applied to prevent loop flows, minimized the system disturbances and also

reduced stability requirement. The SSSC can be considered as an impedancecompensation

controller acting like a controlled seriescapacitor [80-82]. It contains a solid-state

voltagesource inverter (VSI) which can inject nearly sinusoidal voltage, of flexible magnitude,

in series with a transmissionline. It compensates the inductive voltage drop in theline by

inserting capacitive voltage in order to reducethe effective inductive reactance of the

transmission line. In compare to others series capacitor, the SSSC can maintain a continuous

Page | 38

Page 49: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

compensating voltage in case of variable line current or controls the amplitude of the injected

compensating voltage independent of amplitude of line current. In this section the basic

approach of reactive series compensation will be reviewed to provide the necessary foundation

for the treatment of power electronics based compensators. The effect of series compensation

on the basic factors, determining attainable maximal power transmission, steady-state power

transmission limit, transient stability, voltage stability and power oscillation damping, will be

examined.

5.2 Principle of Series Compensation

In series compensation, the FACTS are connected in series with the power system. It works as a

controllable voltage source. Series inductance occurs in long transmission lines, and when a

large current flow it causes a large voltage drop. To compensate, series capacitors are

connected. Series compensation aims to directly control the overall series line impedance of the

transmission line. Tracking back to Equations, the AC power transmission is primarily limited by

the series reactive impedance of the transmission line. A series-connected can add a voltage in

opposition to the transmission line voltage drop, therefore reducing the series line impedance.

A simplified model of a transmission system with series compensation is shown in Figure 5.1.

The voltage magnitudes of the two buses are assumed equal as V, and the phase angle between

them is δ. The transmission line is assumed lossless and represented by the reactance XL. A

controlled capacitor is series-connected in the transmission line with voltage addition Vinj. The

phase diagram is shown in Figure 5.2.

Figure 5.11: Transmission system with series compensation: simplified model

Page | 39

V<

δ2

Bus 2Bus 1jX LIC V<

−δ2

V L

V C

Page 50: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Figure 5.12: Phasor diagram of series compensator

Defining the capacitance of C as a portion of the line reactance,

(5.1)

The overall series inductance of the transmission line is,

(5.2)

The active power transmitted is,

(5.3)

The reactive power supplied by the capacitor is calculated as,

(5.3)

In Figure 5.3, shows the power angle curve from which it can be seen that the transmitted

active power increases with k.

5.3 Static Synchronous Series Compensator (SSSC)

A static synchronous generator operated without an external electric energy source as a series

compensator whose output voltage is in quadrature with, and controllable independently of, the

line current for the purpose of increasing or decreasing the overall reactive voltage drop across

Page | 40

V CV L

V<0

V<

δ2

LC kXX

LCL XkXXX )1(

sin)1(

2

LXk

VP

)cos1()1(

22

2

L

C Xk

kVQ

Page 51: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

the line and thereby controlling the transmitted electric power. The SSSC may include

transiently rated energy storage or energy absorbing devices to enhance the dynamic behavior

of the power system by additional temporary real power compensation, to increase or decrease

momentarily, the overall real (resistive) voltage drop across the line.

Series reactive power compensation is obtained by controlling the equivalent impedance of a

transmission line, as to regulate the power flow through the line. Series connection of

capacitors banks was the first method of series compensation. However, the impossibility to

control in real time the level of compensation and the risk of initiating potentially dangerous

resonances constitute serious drawbacks to this solution. As for shunt compensation, the

utilization of fully controllable devices based on power electronics converters, provides the

most flexible solution for series compensation. The SSSC can be defined as a static

synchronous generator which acts as a series compensator whose output voltage is fully

controllable, independent of line current and kept in quadrature with it, with the aim of

increasing or decreasing the voltage drop across the line, therefore controlling the power

flow.The basic structure of an SSSC and its connection with the network is reported in Figure

5.7.SSSC operation is illustrated by the equivalent circuit of a lossless transmission line of

power system.

Figure 5.3: A series compensated transmission line

Page | 41

V r =V

e− jδ /2

V S =V e jδ /2 V q V 1

Page 52: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

1 2

A series compensated transmission linecompensation if leads Iby π/2rad:or inductive

compensation if lags I by π/2 rad: A relatively small active power exchange is required to

compensate for coupling transformer and switching losses, and maintain the required DC

voltage. It can be concluded that the SSSC increases the voltage drop across line inductance

and hence power flow, if it emulates capacitive compensation. Differently from series

compensation achieved by means of either fixed or switched reactors, the SSSC can inject a

voltage that is independent of line current, whose amplitude can be fully controlled. Indeed, the

SSSC can be controlled in two different operation modes: constant reactance mode and

constant quadrature voltage mode. If SSSC is in constant reactance mode of operation, active

power transfer over the transmission line of Figure 5.7 is

(5.4)

SSSC is operated inconstant quadrature voltage mode, assuming active power

transfer.

5.4 Mathematical Modeling of SSSC

Synchronous Series Compensator (SSSC) is a solid-state voltage source inverter which absorbs

or produces reactive power when the line voltage is in phase quadrature with the line current.

The SSSC can interchange both active and reactive power with the ac system by controlling the

angular position of injected voltage with respect to line current. It may use to control the power

flow, to improve the transient stability, to diminish power system oscillation and to dampen

sub-synchronous resonance.

Page | 42

qV

qV

sin)1(1 sx

VVP rs

VVV rs

mL

3

L

1

V t

Page 53: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Figure 5.4: Schematic diagram of the SMIB system with SSSC.

Figure 5.5: Equivalent circuit of SMIB system with SSSC.

Consider that a SSSC is placed near bus m in the system as shown in Figure 5.6 and Figure 5.7.

The SSSC is represented by a series voltage source.

The series voltage injected by the SSSC is given by

(5.5)

Where � is the angle of the line current and is given by

(5.6)

With the SSSC the machine power can written as

(5.7)

Page | 43

Infinite

bus

L

4

L

2

VSC

C

E’=E’<δV=V<0

+jX

1

jX

2

)2( j

SS eVV

)sin

cos(tan

'

'

E

EV

eP

Se VfPP )(sin 2max

Page 54: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Where

(5.8)

f2 (δ) is positive when δ oscillates in between 0 and π.

can be modulated by properly controlling the value of

Vscan be expressed as

, (5.9)

K2 is a positive constant.

(5.10)

(5.11)

From equation (5.11) we may draw the block diagram of the system with SSSC.

5.5 Block Diagram of SSSC

Page | 44

)cos2

sin()(

''

max2 2

VEE

Pf

eP sV

2KVS maxmaxSSS VVV

2''

21

'

21

'

)cos2

sin))(

(

(sin)(

2 KVEE

XX

E

XX

EPe

})cos2

sin))(

(

(sin)(

{1

2''

21

'

21

'

2

DKVEE

XX

E

XX

EP

Mdt

dm

Pe = Pmax Sinδ+f2(δ)

-Pe

ω δ1M

Pm 1S Output

1S

-

V s

Page 55: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

D ω

Fig.5.6: Simulation diagram with SSSC

Figure 5.8 represents the simulation model for dynamic analysis of power system with SSSC.

represents the series voltage injected by the SSSC in proportion to speed deviation of

the machine,

: Step change in mechanical input to the turbine.

: Electrical power output of the machine.

M : Machine moment of inertia.

ω : Rotor speed deviation.

δ : Rotor angle deviation.

D : Damping coefficient.

5.6 Conclusion

The SSSC and PID controller’s devices not only damp the system oscillations

of the single machine system but also reduce the oscillations transient

periods accordingly. The transient state period of rotor speed responses is

longer than those of voltage responses hence. FACTS provide better

support to system voltages compared to other parameters like rotor angle.

To achieve steady state operating after disturbances, it’s evident that the

damping characteristics of the PID are superior to those of SSSC.

Page | 45

ss KV

mP

eP

Page 56: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Chapter 6

Unified Power Flow Controller

6.1 Introduction

A combination of static synchronous compensator (STATCOM) and a static series compensator

(SSSC) which are coupled via a common dc link, to allow bidirectional flow of real power

between the series output terminals of the SSSC and the shunt output terminals of the

STATCOM, and are controlled to provide concurrent real and reactive series line compensation

without an external electric energy source. The UPFC, by means of angularly unconstrained

series voltage injection, is able to control, concurrently or selectively, the transmission line

voltage, impedance, and angle or, alternatively, the real and reactive power flow in the line. The

UPFC may also provide independently controllable shunt reactive compensate

The previous two chapters deal with shunt compensation and series compensation technique.

The combination of shunt and series compensation technique provides more flexibility to the

transmission system. In this chapter, a particular type of shunt and series compensator, a unified

power flow controller (UPFC) will be discussed. Unified Power Flow Controller (UPFC) is

used to control the power flow in the transmission systems by controlling the impedance,

voltage magnitude and phase angle. The static and dynamic operation of power system can be

performed by this controller. The fundamental structure of the UPFC comprises of two voltage

source inverter (VSI); where each source connected series and parallel with the transmission

line.

Page | 46

Page 57: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

6.2 UPFC Construction

The UPFC is represented by of two ideal voltage sources converters; series and shunt

converter, which are connected to each other with a common dc link. Series converter or Static

Synchronous Series Compensator (SSSC) is used to add controlled voltage magnitude and

phase angle in series with the line, while shunt converter or Static Synchronous Compensator

(STATCOM) is used to provide reactive power to the ac system, besides that, it will provide the

dc power required for both inverter. The basic hardware employment of UPFC composed

of six valves, operated from a joint DC link is shown figure 6.1[85].

Therefore, active power absorb by the shunt converter could be equal to the active power

generated by the series converter. Figure 6.1 shows the schematic diagram of the three phases

UPFC connected to the transmission line [86].

Figure 6.13: Schematic diagram of three phases UPFC connected to a transmission line

Control of power flow is achieved by adding the series voltage, with a certain amplitude,

and phase shift, φ to . This will gives a new line voltage with different magnitude and

Page | 47

V 0V pqV 01

Transmission Line

P settingQ SettingMeasureDCvoltage

Ref

Parameter

V 01

V pq

V 0

ZZ

UPFC Control

i Series TransformerShunt Transformer

SV

1V 2V

Page 58: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

phase shift. As the angle φ varies, the phase shift δ between and also varies. Figure 6.2

shows the single line diagram of the UPFC and phasor diagram of voltage and current.

Figure 6.14: Single line diagram of UPFC and phasor diagram of voltage and current

With the presence of the two converters, UPFC not only can supply reactive power but also

active power. The equation for the active and reactive power is given as follows:-

(6.1)

(6.2)

6.3 Methodology

The focus of this work is to design a UPFC and simulate it using matlabsoftware (Simulink).

Based on the schematic diagram of the three phases UPFC in Figure 6.1, a simulation model of

a single phase UPFC is drawn in Simulink and is illustrated in Figure 6.3.

Page | 48

2V 3V

δV 2−V 3 cos¿

¿V 2¿

Q=¿

P=V 2V 3 sin δ

XV s

I

V 3

V 2

V 1

I

V dV q

- V S

VSC1

1

VSC1

1

I_SH transmission line

P ,QX

V 3V 2V 1

sin12

2112 X

VVP

cos12

2112 X

VVQ

Page 59: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Figure 6.15: Simulation model

A lab scale model is constructed using H-bridge voltage source inverter to act as SSSC. Figure

6.4 shows the block diagram of the lab scale model. Programmable Interface Controller (PIC)

is being programmed to generated PWM signals to the gate drive that will send the signals to

trigger the IGBTs. The comparator provides a reference signal to the PIC controller board to

generate triggering signals in synchronization with the supply voltage.

Figure 6.16: Block diagram of lab scale model

Page | 49

AC DC

Pulse

Load

SeriesTransformer

InverterRectifier

ShuntTransformer

AC supplyLoad

H-bridgeinverter

DCcapacitor

H-bridgerectifier TransformerTransformer

H-bridgeinverter

Comparator PIC

Page 60: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

A program is used to find zero crossing and to generate the required pulses. The program

generates a pulsed signal of 50Hz with a switching frequency of 1.22 kHz. The desired

frequency at the output of the H-bridge inverter is 50Hz which is equivalent to the supply

frequency. The program is written to start triggering when it detects zero crossing of the ac

supply. In order to get a delay at the output of the inverter in comparison to the supply, delay

instruction is added into the program before starting the triggering signals.

6.4 Phase-shifter transformer

Figure 6.5 shows a thyristor-controlled phase-shifter transformer arrangement. It contains a

shunt-connected excitation transformer and a series insertion transformer. The basic function of

a phase shifter is to provide a means to control power flow in a transmission line. It can modify

the voltage phase angle by injecting a variable quadrature voltage in series with the

transmission line in power system. The phase of the output voltage can be varied relative to that

of the input voltage by simply varying the magnitude of the series quadrature voltage.

Figure 6.17: Thyristor-controlled phase shifting transformer scheme for transmission angle

control.

Historically, this has been accomplished by specially connected mechanical regulating

transformers; because the power flow on the transmission line is proportional to the since of the

Page | 50

seriestransformer

Measuredvariables

Referenceinput

Parametersetting

Thyristorswitcharrangement

Excitation transformer

transmision line

Control

Page 61: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

angle across the line, the steady state power flow can he controlled by utilizing a phase-shifter

to vary the angle across the line. The effectiveness of traditional phase shifters in performing

this function is well demonstrated in practice. Just as traditional phase shifters can be employed

to alter steady-state power flow, they can be used to alter transient power flow during system

disturbances or outages, if the phase shifter angle can be changed rapidly. Rapid phase angle

control could be accomplished by replacing the mechanical tap changer of by a thyristor

switching network.

6.5 Inter phase Power Controller (IPC)

The Interphase Power Controller (IPC) controlled at high short-circuits environments. IPCs offer

passive solutions for normal andcontingency conditions. It is a series connected controller which has

inductive and capacitive branch to control active and reactive power. By adjusting phase shifter the

active and reactive power may set independently by IPC. In the specific situation where the inductive

and capacitive impedancemake a conjugate pair, the terminal of IPC acts as a current source

[87-88].This is a broad based concept of series Controller, which can be designed to provide

control of active and reactive power.

6.6 Modeling of UPFC

The amalgamation of a static series compensator (SSSC) and static synchronous compensator

(STATCOM) which are combined via a common dc link, to permit bidirectional flow of active

power between the series output terminals of the SSSC and the shunt output terminals of the

STATCOM, and are controlled to provide concurrent active and reactive series line

compensation without an external electric energy source. The UPFC is able to control,

concurrently or selectively, the transmission line voltage, impedance, and angle or,

alternatively, the active and reactive power flow in the line.

Page | 51

Page 62: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

1 2

Figure 6.6: Schematic diagram of the SMIB system with UPFC

Figure 6.7: Equivalent circuit of SMIB system with UPFC.

The single line diagram and equivalent circuit are given in Figure 6.6. and Figure 6.7. The

mathematical expression of Static Synchronous Series Compensator (SSSC) and Static

Compensator (STATCOM) will be combined to show the damping improvement of the system

with UPFC. With the UPFC the machine power Pecan written as

(6.3)

Where, the value of Pmax, δ, f1 (δ) and f2 (δ) are given in

Page | 52

L

1L

3

V t

m

Infinite

bus

L

4

L

2

VSC

VSC

C

V=V<0V m = V m <E’=E’<δ

jX2jX1+

I

s

SSe VfIfPP )()(sin 21max

Page 63: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

(6.4)

(6.5)

From equation (6.5) we may draw the block diagram of the system with UPFC.

6.6.1 Block Diagram of UPFC

Figure 6.8: Simulation diagram with UPFC

Figure 6.8 represents the simulation model for dynamic analysis of power system with UPFC.

With UPFC both the loops (shunt current modulation) and (series voltage

modulation are present).

Page | 53

2''

21

'

121

2'

21

'

)cos2

sin))(

(()sin(

)(sin

)(2 K

VEE

XXE

KXX

XE

XX

EP me

))cos2

sin))(

(()sin(

)(sin

)((

12''

21

'

121

2'

21

'

2

DKVEE

XX

E

KXX

XE

XX

EP

Mdt

dmm

Pe = Pmax Sinδ+f1(δ) I s +f2(δ)

Pe

-Output

δω1M

Pm 1S

1S

-V sK 2 ω

K1 ωDI s

1K 2K

Page 64: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

6.7 Conclusion

The UPFC is the most adaptable and compound of the truths gadgets, joining the elements of

the STATCOM and the SSSC. The capacity of UPFC is to pass the genuine power stream bi-

directionally, supporting all around managed DC voltage, workability in the extensive variety

of working conditions and so on. One VSI is associated in arrangement to the transmission

framework by means of an arrangement transformer, while the other one is associated in shunt

through a shunt transformer. The DC terminals of the two VSCs are coupled and this makes a

way for dynamic power trade between the converters. Along these lines the dynamic power

provided to the line by the arrangement converter can be provided by the shunt converter.

Along these lines, a wide scope of control alternatives is accessible contrasted with STATCOM

or SSSC. The UPFC can be utilized to control the stream of dynamic and responsive power

through the transmission line and to control the measure of receptive power provided to the

transmission line at the purpose of establishment. To control dynamic and receptive power

streams on the transmission line, the arrangement inverter is utilized to infuse a symmetrical

three stage voltage arrangement of controllable greatness and stage. Thus, this inverter will

trade dynamic and responsive power with the line. The shunt inverter is actuated so as to

request this dc terminal power (positive or negative) from the line keeping the voltage over the

capacity capacitor steady. In this way, the net genuine power assimilated from the line by the

UPFC is equivalent just to the misfortunes of the inverters and their transformers. The rest of

the limit of the shunt inverter can be utilized to trade receptive power with the line so to give a

voltage direction at the association point. The two VSI's can work freely of each other by

isolating the dc side. So all things considered, the shunt inverter is working as a STATCOM

that produces or retains receptive energy to control the voltage size at the association point.

Rather, the arrangement inverter is working as SSSC that produces or ingests responsive energy

to direct the present stream, and henceforth the power streams on the transmission line. The

Page | 54

Page 65: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

UPFC can likewise give synchronous control of all essential power framework parameters, viz.,

transmission voltage, and impedance.

Chapter 7

Simulation Result of STATCOM, SSSC and UPFC

with PI and PID Controller

7.1 Introduction

This work ensures system stability, in order to provide faster responses over a wide range of

power system operation, power system stability (PSS) of single machine infinite bus system

(SMIB) is developed and its parameters are tuned by PI, PID, STATCOM, SSSC and UPFC.

For Transient State Response, a Synchronous generator is taken having a suitable inertia

constant and transient reactance which is connected to an infinite bus through a purely reactive

circuit where the reactance’s are marked on a common system base.

7.2 Simulation Result without FACT Controller

The simulation perform by using matlab software (simulink) and model has been chosen [89]

for step change in the turbine mechanical input, ∆pm = 0.1 p.u. From Figure 7.1, it is clear that

there are sustained rotor angle oscillations and speed deviation with poor damping.

Page | 55

Page 66: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Figure 7.18: Rotor angle deviation without FACTS device

7.3 Simulation Result with STATCOM, SSSCand UPFC

Page | 56

Page 67: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Pm

Pm

Pm

3Output1

2Out1

1Output

angle

-C- V*X2

1*0.15

V*X1

1.2602

V*V3

1 V*V2

1.2602

V*V1 1

V*V

sin

TrigonometricFunction7

sin

TrigonometricFunction6

cos

TrigonometricFunction5

sin

TrigonometricFunction4

sin TrigonometricFunction3

sin

TrigonometricFunction2

cos

TrigonometricFunction1

cos

TrigonometricFunction

t

To Workspace4

y

To Workspace2

y1

To Workspace1

Switch1

Switch

Speed1

Speed

Scope9

Scope8

Scope6

Scope5

Scope4

Scope3

Scope2

Scope12

Scope11

Scope10

Scope1Scope

Product9

Product8

Product7

Product6

Product5

Product4

Product3

Product2

Product15

Product14

Product13Product12

Product11

Product10

Product1

Product

-C- Pmax1

-C- Pmax

Pe5 Pe4

Pe3

Pe2

Pe1

Pe

sqrt

MathFunction1

sqrt

MathFunction

.2

K4

2

K3

.2

K2

2

K1

1s

Integrator5

1s

Integrator4

1s

Integrator3

1s

Integrator2

1s

Integrator1

1s

Integrator

180/pi

Gain3

180/pi

Gain2

-K-

Gain1

3.7419

EV/X3 -C- EV/X2

3.7419

EV/X12

3.7419

EV/X1

-C- E*X3

2.2452

E*X2

0.16839

E*X1

Divide3

Divide2

Divide1

Divide

atan

Delta_m1

atan

Delta_m

0

D2

0

D1

0

D

0

Constant1

0

Constant

Clock3

Clock1

Clock

Add7Add6

Add5

Add4Add3

Add2Add1

Add

2.2452 2E*X2

11

1/M2

15.5

1/M1

15.5

1/M

sin cos

Figure 7.19: Simulation of STATCOM, SSSC and UPFC

The figure 7.2 is depicted the simulation of STATCOM, SSSC and UPFC using parameters

from [89].

Page | 57

Page 68: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

0 1 2 3 4 5 6 7 8 90

0.5

1

1.5

2

2.5

3

Time (Second)

Rot

or A

ngle

Dev

iatio

n (D

egre

e)

STATCOMSSSCUPFC

Figure 7.20 Rotor angle deviation with SSSC, STATCOM and UPFC controller

Table 7.6Rotor angle deviationwith SSSC, STATCOM and UPFC controller

Devices Maximum Overshoot (%) Settling Time(Sec)

STATCOM80 7

SSSC66 3.4

UPFC53 3.20

Page | 58

Page 69: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

0 1 2 3 4 5 6 7 8 9-0.15

-0.1

-0.05

0

0.05

0.1

0.15

0.2

Time (Second)

Rot

or S

peed

Dev

iati

on P

er U

nit

STATCOMSSSCUPFC

Figure 7.4: Rotor speed deviation with SSSC, STATCOM and UPFC controller

Table 7.7Rotor speed deviationwith SSSC, STATCOM and UPFC controller

Devices Maximum Overshoot (%) Settling Time(Sec)

STATCOM18 7

SSSC17 4.5

UPFC15 3.5

Page | 59

Page 70: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

0 1 2 3 4 5 6 7 8 9-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

Time (Second)

Inje

cted

Vol

tage

/Cur

rent

Per

Uni

t

Injected Voltage by UPFC

Injected Voltage by SSSC

Injected Current by STATCOM

Injected Current by UPFC

Figure 7.5: Injected Current and Voltage by SSSC, STATCOM and UPFC Controller

From Figure 7.3 and Figure 7.4 the rotor angle deviation and speed deviation have been

demonstrated for STATCOM, SSSC and UPFC. We found that due to small disturbance of

turbine rotor angle oscillation overshoot varies 80, 66, 53 percent with settling time 7, 3.4 and

0.20 second respectively. Again, the rotor speed deviation diminishing within 7, 4.5, 3.5 second

respectively. From Figure 7.5 the maximum injected current by STATCOM is 0.3 per unit and

injected voltage by SSSC is 0.40 per unit. Again, the injected current and voltage by UPFC are

0.03 per unit.

Page | 60

Page 71: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

7.4 Simulation Result with STATCOM, SSSC, UPFC and PI

Pm

Pm

Pm

3Output1

2Out1

1Output

angle

-C- V*X2

1*0.15

V*X1

1.2602

V*V3

1 V*V2

1.2602

V*V1 1

V*V

sin

TrigonometricFunction7

sin

TrigonometricFunction6

cos

TrigonometricFunction5

sin

TrigonometricFunction4

sin TrigonometricFunction3

sin

TrigonometricFunction2

cos

TrigonometricFunction1

cos

TrigonometricFunction

t

To Workspace4

r

To Workspace3

y1

To Workspace2

Switch1

Switch

Speed

Scope9

Scope8

Scope7

Scope6

Scope5

Scope4

Scope3

Scope2

Scope12

Scope11

Scope10

Scope1

Scope

Product9

Product8

Product7

Product6

Product5

Product4

Product3

Product2

Product15

Product14

Product13Product12

Product11

Product10

Product1

Product

-C- Pmax1

-C- Pmax

Pe5 Pe4

Pe3

Pe2

Pe1

Pe

PID

PID Controller2

PID

PID Controller1

PID

PID Controller

sqrt

MathFunction1

sqrt

MathFunction

.2

K4

2

K3

.2

K2

2

K1

1s

Integrator5

1s

Integrator4

1s

Integrator3

1s

Integrator2

1s

Integrator1

1s

Integrator

180/pi

Gain3

180/pi

Gain2

-K-

Gain1

3.7419

EV/X3 -C- EV/X2

3.7419

EV/X12

3.7419

EV/X1

-C- E*X3

2.2452

E*X2

0.16839

E*X1

Divide3

Divide2

Divide1

Divide

atan

Delta_m1

atan

Delta_m

0

D2

0

D1

0

D

0

Constant1

0

Constant

Clock3Clock1

Clock

Add7Add6

Add5

Add4Add3

Add2Add1

Add

2.2452 2E*X2

11

1/M2

15.5

1/M1

15.5

1/M

sin cos

Figure 7.6: Simulation result with STATCOM, SSSC, and UPFC with PI controller

Page | 61

Page 72: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

The figure 7.6 is presented the simulation of STATCOM, SSSC and UPFC with PI Controller

using matlab software.

0 0.5 1 1.5 2 2.50

0.5

1

1.5

2

2.5

Time (Second)

Roto

r Ang

le D

evia

tion

(Deg

ree)

STATCOM

SSSC

UPFC

Figure 7.7: Rotor angle deviation of SSSC, STATCOM and UPFC with PI controller

Table 7.8Rotor angle deviation of SSSC, STATCOM and UPFC with PI controller

Devices Maximum Overshoot (%) Settling Time(Sec)

STATCOM60 1.5

SSSC46 1

UPFC36 0.90

Page | 62

Page 73: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

0 0.5 1 1.5 2 2.5-0.2

0

0.2

0.4

0.6

Time (Second)

Rot

or S

peed

Dev

iati

on P

er U

nit

SSSCSTATCOMUPFC

Figure 7.8: Rotor speed deviation of SSSC, STATCOM and UPFC with PI controller

Table 7.9Rotor speed deviation of SSSC, STATCOM and UPFC with PI controller

Devices Maximum Overshoot (%) Settling Time(Sec)

STATCOM33 1.5

SSSC32 0.90

UPFC27 0.70

Page | 63

Page 74: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

0 0.5 1 1.5 2 2.5-0.5

0

0.5

1

Time (Second)

Inje

cted

Cur

rent

/Vol

tage

Per

Uni

t

Injected Voltage by UPFCInjected Voltage by SSSCInjected Voltage by STATCOMInjected Current by UPFC

Figure 7.9 Injected current and voltage by SSSC, STATCOM and UPFC with PI controller

From Figure 7.7 and Figure 7.8, the rotor angle deviation and speed deviation have been

presented for STATCOM, SSSC and UPFC with PI controller. We analyzed that due to small

disturbance of turbine rotor angle oscillation overshoot varies 60, 46 and 36 percent with

settling time 1.50, 1.0 and 0.90 second respectively. Again, the rotor speed deviation

diminishing within 1.5 0.90 and 0.70 second with maximum overshoot33, 32, and

27respectively. From Figure 7.9, the maximum injected current by STATCOM is 0.50 per unit

and injected voltage by SSSC 0.70 per unit. Again, the injected current and voltage by UPFC

are 0.10 and 0.0.80 per unit respectively.

Page | 64

Page 75: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

7.5 Simulation Result with STATCOM, SSSC, UPFC and PID

Page | 65

Page 76: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Pm

Pm

Pm

3Output1

2Out1

1Output

angle

-C- V*X2

1*0.15

V*X1

1.2602

V*V3

1 V*V2

1.2602

V*V1 1

V*V

sin

TrigonometricFunction7

sin

TrigonometricFunction6

cos

TrigonometricFunction5

sin

TrigonometricFunction4

sin TrigonometricFunction3

sin

TrigonometricFunction2

cos

TrigonometricFunction1

cos

TrigonometricFunction

t

To Workspace4

r

To Workspace3

y1

To Workspace2

Switch1

Switch

Speed

Scope9

Scope8

Scope7

Scope6

Scope5

Scope4

Scope3

Scope2

Scope12

Scope11

Scope10

Scope1

Scope

Product9

Product8

Product7

Product6

Product5

Product4

Product3

Product2

Product15

Product14

Product13Product12

Product11

Product10

Product1

Product

-C- Pmax1

-C- Pmax

Pe5 Pe4

Pe3

Pe2

Pe1

Pe

PID

PID Controller2

PID

PID Controller1

PID

PID Control ler

sqrt

MathFunction1

sqrt

MathFunction

.2

K4

2

K3

.2

K2

2

K1

1s

Integrator5

1s

Integrator4

1s

Integrator3

1s

Integrator2

1s

Integrator1

1s

Integrator

180/pi

Gain3

180/pi

Gain2

-K-

Gain1

3.7419

EV/X3 -C- EV/X2

3.7419

EV/X12

3.7419

EV/X1

-C- E*X3

2.2452

E*X2

0.16839

E*X1

Divide3

Divide2

Divide1

Divide

atan

Delta_m1

atan

Delta_m

0

D2

0

D1

0

D

0

Constant1

0

Constant

Clock3Clock1

Clock

Add7Add6

Add5

Add4Add3

Add2Add1

Add

2.2452 2E*X2

11

1/M2

15.5

1/M1

15.5

1/M

sin cos

Figure 7.10: Simulation result with STATCOM, SSSC, and UPFC with PID controller

Page | 66

Page 77: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

0 0.1 0.2 0.3 0.4 0.5 0.6 0.70

0.5

1

1.5

2

Time (Second)

Rot

or A

ngle

Dev

iatio

n (D

egre

e)

UPFC with PID

SSSC with PID

STATCOM with PID

Figure 7.11: Rotor angle deviation of SSSC, STATCOM and UPFC with PID controller

Table 7.5Rotor angle deviation of SSSC, STATCOM and UPFC with PID controller

Page | 67

Devices Maximum Overshoot (%) Settling Time(Sec)

STATCOM4 0.23

SSSC6.67 0.20

UPFC3.30 0.15

Page 78: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7-0.1

0

0.1

0.2

0.3

0.4

0.5

0.6

Time (Second)

Rot

or S

peed

Dev

iatio

n Pe

r U

nit

STATCOM with PID

SSSC with PID

UPFC with PID

Figure 7.12: Rotor speed deviation of SSSC, STATCOM and UPFC with PID

Table 7.6Rotor speed deviation of SSSC, STATCOM and UPFC with PID

Page | 68

Devices Maximum Overshoot (%) Settling Time(Sec)

STATCOM43 0.27

SSSC42 0.20

UPFC26 0.26

Page 79: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7-0.2

0

0.2

0.4

0.6

0.8

1

1.2

Time (Second)

Inje

cted

Cur

rent

/Vol

tage

Per

Uni

t

Injected Voltage by UPFC

Injected Voltage by SSSC

Injected Current by STATCOM

Injected Current by UPFC

Figure 7.13: Injected Current and Voltage by SSSC, STATCOM and UPFC with PIDcontroller

From Figure 7.11 and Figure 7.12, the rotor angle deviation and speed deviation have been

depicted for STATCOM, SSSC and UPFC with PID controller at non-linear feedback path. We

found that due to small disturbance of turbine rotor angle oscillation overshoot varies 4, 6.67,

3.3 percent with settling time 0.23, 0.20 and 0.15 second respectively. Again, the rotor speed

deviation diminishing within 0.27, 0.20, 0.26 second respectively. From Figure 7.13, the

maximum injected current by STATCOM is 0.0.055 per unit and injected voltage by SSSC

0.088 per unit. Again, the injected current and voltage by UPFC are 0.09 and 0.03 per unit

respectively.

7.6 Comparison of Simulation Result

Table 7.10Rotor angle deviation comparision

Devices

FACT Devices

FACT Devices

with PI Controller

FACT Devices

with PID Controller

Maximum

Overshoot

(%)

Settling

Time

Maximum

Overshoot

(%)

Settling

Time

Maximum

Overshoot

(%)

Settling

Time

Page | 69

Page 80: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

STATCOM 80 7 60 1.5 4 0.23

SSSC 66 3.4 46 1 6.67 0.20

UPFC 53 3.20 36 0.90 3.30 0.15

Table 7.8Rotor Speed Deviation

Devices

FACT Devices

FACT Devices

with PI Controller

FACT Devices

with PID Controller

Maximum

Overshoot

(%)

Settling

Time

Maximum

Overshoot

(%)

Settling

Time

Maximum

Overshoot

(%)

Settling

Time

STATCOM 18 7 33 1.5 43 0.27

SSSC 17 4.5 32 0.90 42 0.20

UPFC 15 3.5 27 0.70 26 0.26

7.7 Comparison of Simulation with the Previous Work

In [19], rotor speed deviation is analyzed and it has been settle in 2 to 2.2 sec. In this thesis,

rotor angle deviation as well as speed deviation is analyzed. From table 7.7, rotor angle

deviation settles in 0.15 to 0.23 sec. Again, from table 7.8, rotor speed deviation settle in 0.20

to 0.27 sec. So, we may summarize that UPFC with PID controller perform superior than other

controller.

7.8 Conclusion

At first the system is simulated with STATCOM, SSSC, and UPFC for step response. For step

change of mechanical input, UPFC quickly damps the oscillations compared to the SSSC and

STATCOM. Then PI and PID controller have been incorporated with the system including

STATCOM, SSSC and UPFC controller.

Page | 70

Page 81: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Chapter 8Conclusion and Future Work

8.1 Conclusion

This paper presents a systematic method of designing of PI and PID controllers for the FACTS

devices in single machine infinite bus system. The performance of the system is analyzed in

term of power handling capacity, improvement in transient stability and damping of oscillations

and compared for different types of controllers.

Initially the system is simulated with STATCOM, SSSC, and UPFC for step response. For step

change of mechanical input, UPFC quickly damps the oscillations compared to the SSSC and

STATCOM. Then PI and PID controller have been incorporated with the system including

STATCOM, SSSC and UPFC controller.

STATCOM, SSSC, and UPFC improved the transient performance of the power system, when

PI and PID controller is incorporated with STATCOM, SSSC, and UPFC the performance is

improved tremendously. However, the UPFC with PID controller diminished the maximum

overshoot and as well as minimized the settling time to stable the system more rapidly as

compared to the STATCOM and SSSC.

In previous works [20] PI, PID and fuzzy logic controllers have been used with SSSC for

power transmission line performance evaluation. In [12] only PI controller and STATCOM

have been used for only power factor improvement. In [19], STATCOM, SSSC and UPFC

Controllers have been demonstrated for transient stability

improvement.Very few researchers analyzed the power system stability using PI and PID

controller with SSSC, STATOM and UPFC thoroughly.

In this thesis the transient performance of power system is analyzed for change of mechanical

input power with STATCOM, SSSC and UPFC using PI and PID controller rigorously. It is

Page | 71

Page 82: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

found that the UPFC with PID controller stabilized the system more rapidly than STATCOM

and SSSC.

In [19], rotor speed deviation is analyzed and it has been settle in 2 to 2.2 sec. In this thesis,

rotor angle deviation as well as speed deviation is analyzed. Rotor angle deviation settles in

0.15 to 0.23 sec. Again, Rotor speed deviation settle in 0.20 to 0.27 sec. So, we may summarize

that UPFC with PID controller perform superior than other controller.

8.2 Future Works

In this thesis, PI and PID controller are simulated with STATCOM, SSSC and UPFC for change

of mechanical input power. In future, further simulation can be performed for sudden load

change and during faulty condition forminimizing maximum overshoot and settling time. In

future, Lag-lead compensator, lag compensator can be used for more reliability and quick

damping of the system. It is seen that it would be better if the peak overshoot and the settling

time can be reduced to a lower value. For this purpose, some modern controller like fuzzy logic

controller can be added with FACTS devices for desired operation.

References[1] IEEE/CIGRE Joint Task Force on Stability Terms and Definitions, “Definition and

classification of power system stability”, IEEE Trans. Power Syst., Vol.19, No. 2, 2004,pp1387-1401.

[2] F. R. S chleif and J. H. White, “Damping for the northwest-southwest tie lineoscillations an analogue study,” IEEE Trans. Power Appar. Syst., Vol.85, No.12, pp1239-1247, Dec 1966.

[3] C. M. Gibson, “Application of power system stabilizers on the Anglo Scottish interconnection-Programme of system proving tests and operational experience,” IEEE Proc. Part C, Vol.135,No. 3, 1988, pp255-260.

[4] S. Larsson and E. Ek, “The black-out in southern Sweden and eastern Denmark,” inProc. IEEE Power Engineering Society General Meeting, 2004, vol. 2, pp. 1668–1672.

[5] G. Andersson, P. Donalek, R. Farmer, N. Hatziargyriou, I. Kamwa, P. Kundur, N.Martins, J. Paserba, P. Pourbeik, J. Sanchez-Gasca, R. Schulz, A. Stankovic, C. Taylor,and V. Vittal, “Causes of the 2003 Major Grid Blackouts in North America and Europe,and Recommended Means to Improve System Dynamic Performance,”IEEE Trans.Power Syst., vol. 20, no. 4, pp. 1922–192, Feb. 2005.

[6] E. Dmitrova, M. L. Wittrock, H. Jóhannsson and A.H Nielsen, “Early PreventionMethod for Power System Instability,” IEEE Trans. Power Syst, vol. 30, No.4, pp-1784-1792, July 2015.

[7] R. Preece, and J.V. Milanović, “Probabilistic Risk Assessment of Rotor Angle Instability UsingFuzzy Inference Systems,” IEEE Trans. Power Syst., vol. 30, no.4, pp-1747-1757, July, 2015.

Page | 72

Page 83: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

[8] J. Deng, C. Li, and X. P. Zhang, “Coordinated Design of Multiple Robust FACTSDamping Controllers: A BMI-Based Sequential Approach with Multi-Model Systems,”IEEE Trans. Power Syst., vol. 30, no. 6, pp-3150-3159, Nov, 2015.

[9] N. Johansson, L. Ängquist, and H.P. Nee, “An Adaptive Controller for Power SystemStability Improvement and Power Flow Control by Means of a Thyristor SwitchedSeries Capacitor (TSSC),” IEEE Trans. Power Syst. vol. 25, no. 1, pp-381-391,February, 2010.

[10] S. Mori, K. Matsuno, T. Hasegawa, S. Ohnishi, M. Takeda, M. Seto, S. Murakami, F.Ishiguro, “Development of a Large Static Var Generator Using Self-CommutatedInverters for Improving Power System Stability,” IEEE Trans. Power Syst., vol. 8, no.1, ,pp.371-377. February, 1993.

[11] A. Ghafouri, M.R. Zolghadri M. Ehsan,O. Elmatboly, and A. Homaifar “Fuzzy Controlled STATCOM for Improving the Power System Transient Stability,” IEEE, North American Power Symposium, , pp-212-216, 2007.

[12] J. Moharana, M. Sengupta,.and A. Sengupta, “Design and implementation of a PI-controller on a 10 kVA STATCOM prototype,” Int. J. Power and Energy Conversion,vol. 6, no. 1,. pp 85–106, 2015.

[13] C. Schauder, “STATCOM for Compensation of Large Electric Arc FurnaceInstallations,” Proceedings of the IEEE PES Summer Power Meeting, Edmonton,Alberta, July 1999, pp. 1109-1112.

[14] D.J. Hanson, C. Horwill, B.D. Gemmell, D.R. Monkhouse, “ASTATCOM-Based Relocatable SVC Project in the UK for National Grid,” Proceedings of the IEEE PES Winter Power Meeting, New York, January 2002.

[15] L. Zhang; C. Shen; Z. Yang; M. Crow; A. Arsoy; Yilu Liu; S. Atcitty “A comparison ofthe dynamic performance of FACTS with energy storage to a unified power flowcontroller,” Columbus, OH, USA, , pp-611-616, Jan.-1 Feb. 2001.

[16] L. Dong, M. L. Crow, Z. Yang, C. Shen, L. Zhangand S. Atcitty “A reconfigurable FACTSsystem for university laboratories vol. 19, no. 1, pp-120-128, February 2004.

[17] A. Kumar; G. Priya “Power system stability enhancement using FACTS controllers,”Emerging Trends in Electrical Engineering and Energy Management (ICETEEEM),Chennai, India, , pp-84-87, 2012.

[18] P. Dash, L.C. Saikiaand N. Sinha “AGC of a multi - area interconnected system withFACTS and firefly optimized 2DOF PID controller,” Control, Instrumentation, Energyand Communication (CIEC), ,Calcutta, India, pp-397-401, 2014.

[19] V.K. Chandrakar and A.G .Kothari “Comparison of RBFN based STATCOM, SSSCand UPFC Controllers for Transient Stability improvement,” Power SystemsConference and Exposition, PSCE '06. 2006 IEEE PES, Atlanta, GA, USA, pp-784-791, 2006.

[20] H. Zenk; A. S. Akpinar, “PI, PID and fuzzy logic controlled SSSC connected to apower transmission line, voltage control performance comparison,” IEEE, Istanbul,Turkey, pp-1493-1497, 2013.

[21] G. Reed, J. Paserba, T. Croasdaile, M. Takeda, Y. Hamasaki, T. Aritsuka,N. Morishima,S. Jochi, I. Iyoda, M. Nambu, N. Toki, L. Thomas, G.Smith, D. LaForest, W. Allard, D.Haas, “The VELCO STATCOM-based transmission system project,” Proceedings ofthe IEEE PES Winter Power Meeting, Columbus, OH, January/February 2001.

[22] G. Reed, J. Paserba, T. Croasdaile, M. Takeda, N. Morishima, Y.Hamasaki, L. Thomas, W.

Page | 73

Page 84: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Allard, “STATCOM application at VELCO essex substation,” Proceedings of the IEEE PES T&D Conference and Exposition, Atlanta, Georgia, October/November 2001.

[23] V. Mahajan “Power system stability improvement with Flexible A.C. TransmissionSystem (FACTs) controller”, Power System Technology and IEEE Power IndiaConference, 2008. POWERCON 2008. Joint International Conference on, New Delhi,India, pp-978-99883, 2009.

[24] A. Edris, "FACTS technology development: An update", IEEE Power EngineeringReview, pp. 4 - 11. March 2000.

[25] B. M. Zhang, Q. F. Ding, "The Development of FACTS and Its Control," Proceedings of The 4th Conference on APSCOM 97, Hong Kong, , pp. 48 - 53. Nov. 1997.

[26] "FACTS For Cost Effective and Reliable Transmission of Electrical Energy", ww.worldbank.org/html/fpd/em/transmission/facts sielmens.pdf.

[27] L. D. Colvara, S. C. B. Araujo, E. B. Festraits, "Stability Analysis of Power SystemIncluding FACTS (TCSC) Effects by Direct Method Approach", Electrical Power andEnergy Systems , pp. 1 – 11, 2005.

[28] U. Gabrijel, R. Mihalic, "Assessment of Transient Stability in Power Systems withFACTS," EUROCON, Vol. 2, 22 - 24 pp. 230 -234, Sept 2003.

[29] A. M. Sharaf, M. Z. El - Sadek, F. N. Abd - Elbar, A.M. Hemeida, "Transient StabilityEnhancement Using Self Adjusting Flexible Variable Series Capacitor compensation",Electrical Power and Energy Systems, Vol. 50, pp. 219 – 225, 1999.

[30] Y Gui, W. Kim, and C.C. Chung “Passivity-Based Control With Nonlinear Dampingfor Type 2 STATCOM Systems,” IEEE Trans. Power Syst., vol. 31, no. 4, pp., pp-2824-2833, July, 2016.

[31] K.R. Padiyar, and N. Prabhu, “Design and Performance Evaluation of Sub synchronousDamping Controller With STATCOM,” IEEE Transactions on Power Delivery, Vol. 21,No. 3, pp-1398-1405, July, 2006.

[32] R. K. Varma, S.A. Rahman, and T. Vanderheide, “New Control of PV Solar Farm asSTATCOM (PV-STATCOM) for Increasing Grid Power Transmission Limits duringNight and Day,” IEEE Transactions on Power Delivery, Vol. 30, No. 2, pp-755-763,April, 2015.

[33] A. Kanchanaharuthai, V. Chankong, and K.A. Loparo, “Transient Stability and VoltageRegulation in Multi-machine Power Systems Vis-à-Vis STATCOM and Battery EnergyStorage,” IEEE Transactions on Power Systems, Vol. 30, No.5, pp-2404-2016.September, 2015.

[34] H. Chen., Y. Wang, and R. Zhou, “Transient and voltage stability enhancement viacoordinated excitation and UPFC control,” IEE Proc. Gen. Tran. & Distr. Vol. 148,No.3, pp. 201-208, May, 2001.

[35] K.K. Sen, and A.J.F. Keri, “Comparison of field results and digital simulation results ofvoltage – sourced converter based FACTS controllers,” Trans. on Power Delivery , Vol.18 No.1, pp.300-306, 2004, January.

[36] Kumkratug, and M.H. Haque, “Versatile model of a unified power flow controller insimple power system,” IEE Proc. Gene. Trans. & Dist. Vol.150, No.2, pp.155-161,March, 2003.

[37] N. Tambey, and M.L. Kothari, “Damping of power system oscillations with unifiedpower flow controller (UPFC) “, IEE Proc. Gen. Tran. & Distr., Vol.150, No.2, pp 129-140. March, 2003.

Page | 74

Page 85: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

[38] W. Song, and A.Q. Huang, “Fault-Tolerant Design and Control Strategy for CascadedH-Bridge Multilevel Converter-Based STATCOM”, IEEE Transactions on IndustrialElectronics, 2010, August, Vol. 57, No. 8,pp-2700-2708.

[39] C.Wessels, M. Molinas, and F.W Fuchs, “StatCom Control at Wind Farms With Fixed-Speed Induction Generators Under Asymmetrical Grid Faults”, IEEE Transactions onIndustrial Electronics, 2013, July, Vol. 60, No. 7,pp-2864-2873.

[40] L. Gyugyi, C. Schauder, and K. Sen, “Static Synchronous Series Compensator: A solidstate approach to the series compensation of transmission lines”, IEEE Trans. on PowerDelivery, 1997, January, Vol.12, No. 1, pp-406-417.

[41] M. Bongiorno, J. Svensson, and L. Ängquist, “Single-Phase VSC Based SSSC for Subsynchronous Resonance Damping”, IEEE Transactions on Power Delivery, 2008, July,Vol. 23, No. 3, pp-1544-1552.

[42] D. Rai, S.F. Faried, G. Ramakrishna, and A. A Edris “An SSSC-Based Hybrid SeriesCompensation Scheme Capable of Damping Sub synchronous Resonance,” IEEETransactions on Power Delivery, Vol. 27, No. 2, pp-531-540, April, 2012.

[43] S. Jiang, A.M. Gole, U.D. Annakkage, and D.A. Jacobson, “Damping PerformanceAnalysis of IPFC and UPFC Controllers Using Validated Small-Signal Models,” IEEETransactions on Power Delivery, Vol. 26, No. 1, pp-446-454, Jan, 2011.

[44] L.H. Hassan, M. Moghavvemi, H. A. F. Almurib, and K.M. Muttaqi, “A CoordinatedDesign of PSSs and UPFC-based Stabilizer Using Genetic Algorithm,” IEEETransactions on Industry Applications, Vol. 50, No. 5, pp-2957-2966 , Sept, 2014.

[45] A. R. Ghahnavieh, M.F Firuzabad, M. Shahidehpour, and R. Feuillet, “UPFC forEnhancing Power System Reliability,” IEEE Transactions on Power Delivery, Vol. 25,No. 4, pp-2881-2890, Oct, 2016.

[46] Y. Liu, S. Yang, X.. Wang, D. Gunasekaran, U. Karki,. and F.Z. Peng, “Application ofTransformer-Less UPFC for Interconnecting Two Synchronous AC Grids With LargePhase Difference,” IEEE Transactions on Power Electronics, Vol. 31, No. 9,pp-6092-6103,Sept. 2016

[47] S.K., Ray, P. C. Sarker, M.C. Ahsan, M.M.S.S Seddiqe, “Novel Approach of PIDControl Scheme with UPFC for Damping of Oscillations”, International Journal ofComputer and Electrical Engineering, Vol.4, No.2, pp-104.109, April, 2012.

[48] K. T. Hagglund, “PID Controllers; Theory, Design and Tuning”, Instrument Society ofAmerica, Research Triangle Park, 1995.

[49] A. O’Dwyer, “Handbook of PI and PID Controller Tuning Rules,” Imperial CollegePress, London, 2003.

[50] S.S. Khorramabadi, and A. Bakhshai, “Critic-Based Self-Tuning PI Structure for Activeand Reactive Power Control of VSCs in Microgrid Systems,” IEEE Transactions onSmart Grid, Vol. 6, No. 1, pp.92-103, Jan, 2015.

[51] A.V. Sant, K. R. Rajagopal, and N. K. Sheth “Permanent Magnet Synchronous MotorDrive Using Hybrid PI Speed Controller With Inherent and Non inherent SwitchingFunctions”, IEEE Transactions on Magnetics, , Vol. 47, No. 10,pp.4088-4090, Oct,2011.

[52] A. R. Martinez, R.G. Ramirez, and L.G. Vela-Valdes, “PI Fuzzy Gain-SchedulingSpeed Control at Startup of a Gas-Turbine Power Plant,” IEEE Transactions on EnergyConversion, Vol. 26, No. 1,pp-310-317. Mar, 2011.

Page | 75

Page 86: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

[53] D. Xue, Y. Quan Chen and D. P. Atherton, “Linear Feedback Control,” Chapter six,Copyright by ‘The Society of Industrial and Applied Mathematics,’ 2007.

[54] S. B. M. Ibrahim, “The PID Controller Design Using Genetic Algorithm,” Universityof Southern Queensland Faculty of Engineering and Surveying, 2005.

[55] Z. L. Gaing, “A Particle Swarm Optimization Approach for Optimum Design of PIDController in AVR System,” IEEE Transactions on Energy Conversion, Vol. 19, No. 2,pp.384~391, 2004.

[56] L. Angle and J. Viola “Design and Statistical Robustness Analysis of FOPID, IOPIDand SIMC PID Controllers Applied to a Motor Generator System,” IEEE LatinAmerica Transactions, Vol. 13, No. 12, and pp-3724-3734, Dec, 2015.

[57] K. H. Ang, G. Chong, and Y. Li, “PID Control System Analysis, Design, andTechnology , IEEE Transactions on Control Systems Technology, Vol. 13, No. 4, pp-‟559-576. July, 2005.

[58] J.Y. Lee, M. Jin, and P.H. Chang “Variable PID Gain Tuning Method Using Backstepping Control With Time-Delay Estimation and Nonlinear Damping,” IEEETransactions on Industrial Electronics, Vol. 61, No. 12, pp-6975-6985, Dec, 2014.

[59] M.M.I.S Seddiqe, S. K. Ray, “Application of SDGM to Digital PID and PerformanceComparison with Analog PID Controller,” International Journal of Computer andElectrical Engineering, Vol. 3, No. 5, , pp-634-638. Oct, 2011.

[60] S. K. Ray, and D. Paul “Performance Comparison of Electronic Printwheel System byPI and PID Controller Using Genetic Algorithms,” International Journal of ComputerScience & Emerging Technologies, , Vol. 1, No.4, 2010 pp-200-207 Dec, 2010.

[61] P. Kundur, “Power system stabiliy and control” New York: Tata McGraw-Hill, 1994.[62] P. M Anderson and A. A. Fouad, “Power System Control and Stability”, VolumeI, Iowa

State University Press, Ames, Iowa, 1977.[63] F. P. demello, C. Concordia, “Concepts of Synchronous Machine Stability as Affected

by Excitation Control,” IEEE Trans. On Power system and apparatus, Vol PAS- 88,No.4, pp. 316-329, April 1969.

[64] IEEE Committee Report: “Computer representation of excitation systems”, IEEETrans., 1968, PAS-87, pp 1460-1464.

[65] W.G. Heffron, and R.A. Phillips, “Effects of modern amplifying voltage regulator on under-excited operation of large turbine generators”, AIEE Trans., , PAS-71, pp. 692-697, Aug, 1952.

[66] M. J. Basler and R. C. Schaefer, “Understanding Power System Stability”, IEEE Trans.On Industry Application, Vol. 44, No. 2, pp 463-474. April, 2008.

[67] M. H. Rashid, Power Electronics Circuits, Devices and Applications, Third Edition,2007.

[68] C. Schauderet al., “Development of a 100 MVAR static condenser for voltage controlof transmission systems,” IEEE Trans. on Power Delivery, vol. 10, no. 3, July 1995.

[69] C. Schauderet al., “Operation of 100 MVAR TVA StatCom,” IEEE Trans. on PowerDelivery, vol. 12, no. 4, Oct. 1997.

[70] P. W. Lehn and M. R. Iravani, “Experimental evaluation of StatCom closed loopdynamics,” IEEE Trans. on Power Delivery, vol. 13, no. 4, Oct. 1998.

[71] P. Rao, M. L. Crow, and Z. Yang, “StatCom control for power system voltage controlapplications,” IEEE Trans. on Power Delivery, vol. 15, no. 4, Oct, 2000.

Page | 76

Page 87: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

[72] C. Schauderet al., “AEP UPFC project: Installation, Commissioning and Operation ofthe 160 MVA StatCom (phase I),” IEEE Trans. On Power Delivery, vol. 13, no. 4, Oct.1998.

[73] K. V. Patilet, J. Senthil, J. Jiang and M.R. Mathur “Application of StatCom fordamping Torsional oscillations in series compensated AC systems,” IEEE Trans. onEnergy Conversion, vol. 13, no. 3, Sept. 1998.

[74] B. M. Han, G. Karady, J. Park, and S. Moon, “Interaction analysis model fortransmission static compensator with EMTP,” IEEE Trans. on Power Delivery, vol. 13,no. 4, Oct. 1998.

[75] R. Koessler, B. Fardanesh, M. Henderson, and R. Adapa, “Feasibility studies forStatCon application in New York state,” FACTS Applications, pp. 8.52–8.58, 1996.

[76] Facts Applications: IEEE press, vol. 96-TP-116, 1996.[77] L.Gyugyi, “Dynamic compensation of AC Transmission lines by solid-state

synchronous voltage sources,” IEEE Trans. Power Delivery, , 9, (2), pp. 904-911, 1994[78] K. S. Jeong, Y. S. Baek, J. S. Yoon, B. H. Chang, H. C. Lee, G. J. Lee, “EMTP

Simulation of a STATCOM Shunts-OLTC Coordination for Local Voltage Control,”IEEE Transmission & Distribution Conference in Asia, pp. 1-4, October, 2009.

[79] N.G. Hingorani, L. Gyugyi, “Understanding FACTS, Concepts and Technology ofFlexible AC Transmission systems,” IEEE Press 2000.

[80] S. Ganjefar, M. Alizadeh, “On-line self-learning PID controller design of SSSC usingself-recurrent wavelet neural networks. In,” TurkishJournal of Electrical Engineering &ComputerSciences, pp. 1-22, 2013.

[81] M.S. Castro, H.M. Ayres, V.F. da Costa, and L.C.P. daSilva, “Impacts of the SSSCcontrol modes on small signal and transient stability of a power system,” ElectricPower Systems Research 77, pp. 1–9, 2007.

[82] D. Murali, M. Rajaram, “Intelligent Control Schemes for SSSC Based DampingControllers in Multi-Machine Power Systems,” International Journal of EngineeringScience and Technology Vol. 2(8), pp.3788-3796, 2010.

[83] R. Adapa, "Summary of EPRFs FACTS System Studies," CIGRE SC14 InternationalColloquiumon HVDC & FACTS, Montreal, September 1995.

[84] T. Larsson A. Edris, D. Kidd, F. Aboytes, “Eagle Pass Back-to-Back Tie:a DualPurpose Application of Voltage Source Converter Technology, “Proceedings of the2001 IEEE PES Summer Power Meeting, Vancouver, BC, July 2001.

[85] L. Xu and V.G. Agelidis, “Flying Capacitor Multilevel PWM Converter Based UPFC’,IEE Proc. Of Electronic Power Application, Vol. 149, No. 4, July 2003. Page(s) 304-310.

[86] N. G. Hingorani and L. Gyugyi, “Understanding FACTS”, IEEE Press, 2000.[87] E. Uzunovic, C. A. Canizares, J. Reeve, “Fundamental Frequency Model of Unified

Power Flow Controller,” North American Power Symposium (NAPS), Cleveland,Ohio, October 1998, pp 294-299.

[88] M. Toufan, U.D. Annakkage, “Simulation of the Unified Power Flow ControllerPerformance Using PSCAD/EMTDC,” Electrical Power System Research Vol. 46, pp67-75. 1998.

[89] H.Saadat, Power System Analysis, 3rd ed., New York. 1999.

Page | 77

Page 88: Tuning of PI and PID Controller with STATCOM, SSSC and UPFC … · 2020. 2. 3. · The project report entitled “Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing

Publication

[1] S. K. Ray, M. A, Rahman and M. R. Ahmed “Tuning of PI and PID Controller with STATCOM,

SSSC andUPFC for Minimizing Damping of Oscillation”, IOSR Journal of Electrical and

Electronics Engineering (IOSR-JEEE), Volume 12, Issue 1 Ver. II PP 30-44, Jan, 2017.

Page | 78


Recommended