+ All Categories
Home > Documents > tutorial digsilent ingles

tutorial digsilent ingles

Date post: 01-Jun-2018
Category:
Upload: henry-michel
View: 242 times
Download: 2 times
Share this document with a friend

of 18

Transcript
  • 8/9/2019 tutorial digsilent ingles

    1/18

    Overcurrent Protection for the

    IEEE 34 Node Radial Test FeederHamed B. Funmilayo, James A. Silva and

    Dr. Karen L. Butler-PurryTexas A&M University

    Electrical and Computer Engineering Department

    1

    Po

    werSystemAu

    tomationLab

  • 8/9/2019 tutorial digsilent ingles

    2/18

    Introduction

    Major use of the benchmark radial test

    feeders -- provide load-flow data for validating

    load-flow results from existing/novel load-

    flow algorithms

    Extend Current IEEE 34 node test feeder

    Provide overcurrent protection, considering off-

    the-shelf protective devices

    Make available for studies under new scenarios

    (such as DG impact)

    2

  • 8/9/2019 tutorial digsilent ingles

    3/18

    Work Reported in This Paper

    Model of Test feeder in DIgSILENT

    PowerFactory 13.1 and conduct LF and

    SC studies

    Coordination studies for temporary and

    permanent faults for various fault

    situations

    Select OCP devices for the test feeder

    3

  • 8/9/2019 tutorial digsilent ingles

    4/18

  • 8/9/2019 tutorial digsilent ingles

    5/18

    Over Current Protective Devices

    Modeled in DIgSILENT

    1 recloser, 12 fuses

    Fuse saving for fuses 1, 2, 3, 4, 6, 7, 8, and 11

    5

  • 8/9/2019 tutorial digsilent ingles

    6/18

    Maximum and Minimum Fault Currents

    6

    Comparison of Maximum FaultCurrent to IEEE TF Results

    Faulted IEEE* DIgSILENT DIgSILENT

    Node (A) (A) % Error

    800 718.60 678.60 5.57

    808 526.50 510.20 3.10

    816 335.40 329.94 1.63

    824 313.00 310.50 0.80

    854 272.90 276.40 1.28

    832 223.10 217.70 2.42

    858 217.70 213.30 2.02

    834 211.30 208.40 1.37

    836 206.90 204.40 1.21840 206.10 203.61 1.21

    890 406.50 440.10 8.27

    Comparison of Minimum FaultCurrent to IEEE TF Results

    Faulted IEEE* DIgSILENT DIgSILENT

    Node (A) (A) % Error

    800 479.30 459.00 4.24

    808 309.40 322.26 4.16

    816 213.50 205.49 3.75

    824 195.10 194.06 0.53

    854 175.90 173.68 1.26

    832 146.20 140.55 3.86

    858 143.00 138.06 3.45

    834 139.30 135.19 2.95

    836 136.50 132.71 2.78840 136.00 132.27 2.74

    890 94.10 87.94 6.55

  • 8/9/2019 tutorial digsilent ingles

    7/18

    Recloser and Fuses Types

    Recloser

    Recloser's coordination range must provide adequate time to sense all

    downstream faults.

    Fuse Saving mode used

    A triple single-phase electronic recloser was used

    Load side fuses

    Similar types of fuse links were selected for all branches within the

    same nominal current range

    Voltage rating equal to or higher than the maximum bus voltage at thefuse location

    Interrupting current rating larger than the maximum symmetrical fault

    current at the fuse location

    Type K, T and X expulsion fuse links

    7

  • 8/9/2019 tutorial digsilent ingles

    8/18

    Step Down Transformer (XMF-1) Fusing

    A type T external expulsion cutout on the primary side

    The voltage rating equal to or greater than the voltage at transformer's

    location

    The ampere rating equal to or greater than the anticipated normal

    loading level The symmetrical short-circuit interrupting rating equal to or greater

    than the maximum fault current

    Be able to withstand the inrush current generated when

    transformer is energized

    Be able to protect against transformer faults and secondary

    side faults (through faults)

    Serve as backup device by coordinating with the OCP device

    downstream of the lateral

    8

  • 8/9/2019 tutorial digsilent ingles

    9/18

    Capacitor Bank Fusing

    Group fusing method is used. (One fuse

    protects the capacitor bank)

    Promptly isolate the failed capacitor unit on

    the line prior to any other protective device

    on the system

    1-phase grounded fault current without fault

    impedance is assumed as the capacitor fault

    value.

    9

  • 8/9/2019 tutorial digsilent ingles

    10/18

    Settings for Recloser and Load Side Fuses

    10

    Minimum Fault Current Observed at the Recloser

    For The Minimum Fault At Each Lateral

    Recloser Faulted Lateral If recloser (A)

    Node Node number DIgSILENT

    800 810 1 321.79

    800 822 2 168.90

    800 826 3 218.89

    800 856 4 179.82

    800 888 5 61.08

    800 864 6 126.36

    800 848 7 165.82

    800 838 8 166.88800 Cap- 844 7 167.93

    800 Cap- 848 7 165.82

    800 840 11 165.88

    No. of Instantaneous Trips 1

    No. of Delay Trips 2

    Nominal Voltage 14.4 kV, L-N

    Minimum trip rating 100 A

    Instantaneous trip curve type 103

    Delay trip curve type 134

    Recloser Settings

    Nominal Voltage Rating24.9 kV, L-L or

    4.16 kV, L-L

    Nominal Current Rating of Each

    Fuse

    Based on each

    branchs current

    Load Side Fuse Settings

  • 8/9/2019 tutorial digsilent ingles

    11/18

    Coordination Studies

    Two terms for OCP operation

    Primary device

    Near to the fault and first to clear the fault

    Secondary (backup device)

    Backup of the primary device

    Coordination between recloser and fuse

    For temporary fault, K factor is used

    For permanent fault, fuse operates prior to reclosersdelay trip

    Coordination between fuse and fuse Max clearing time of primary fuse will not exceed 0.75 times the

    minimum melting time of the secondary fuse

    11

  • 8/9/2019 tutorial digsilent ingles

    12/18

    Fault Case Studies

    Fault on main feeder

    Fault on ordinary laterals

    Fault on laterals with reactive compensation Faults on laterals with step-down transformer

    12

  • 8/9/2019 tutorial digsilent ingles

    13/18

    Fault on ordinary laterals

    Recloser operates on its

    instantaneous trip for

    temporary fault

    For permanent fault,

    fuse operates to clear

    the fault and isolates the

    lateral

    13

    Instantaneous trip of recloser

    Fuse melting time

    Delayed curve of recloser (backup)

    Recloser-Fuse coordination for min fault at 810

  • 8/9/2019 tutorial digsilent ingles

    14/18

    Discussion of Results

    RECLOSER-FUSE COORDINATION TIME INTERVALS FROM DIGSILENT

    14

  • 8/9/2019 tutorial digsilent ingles

    15/18

    OPD List for the Test Feeder

    15

  • 8/9/2019 tutorial digsilent ingles

    16/18

    Summary/Conclusions

    16

    A conventional overcurrent protection and

    coordination scheme was implemented on IEEE 34

    Node Test Feeder computer model in DIgSILENT

    The final list of selected OCP was provided Coordination was achieved for different cases

    This may be used for easy comparison and

    assessment of future overcurrent protection studiesregarding radial distribution system with or without

    additions such as DG

  • 8/9/2019 tutorial digsilent ingles

    17/18

    Acknowledgement

    The authors would like to thank F. J. Verdeja

    Perez, J. Mendoza, S. Duttagupta, M. Marotti,

    K. Mansfield, T. Djokic, and H. E. Leon for their

    contributions, along with the assistance ofProf. W. H. Kersting.

    This work was supported in part by the U.S.

    National Science Foundation under Grant ECS-02-18309.

    Paper no. TPWRD-00792-2007.

    17

  • 8/9/2019 tutorial digsilent ingles

    18/18

    18

    Contact information:

    Dr. Karen L. Butler-Purry

    Email: [email protected]


Recommended