LIGHTING FIXTURES LINEAR FIXTURE SQUARE = RECESSED CIRCLE =SURFACE DOWNLIGHT, SQUARE = RECESSED WALL MOUNT CEILING EXHAUST FAN POLE MOUNT AREA LIGHT ELECTRICAL LEGEND DRAFTING NOTATIONS KEY NOTE, SEE SCHEDULE EQUIPMENT TAG, SEE SCHEDULE REFERENCE TO A DETAIL VIEW "A" ON SHEET E-2 NEW ELECTRICAL EXISTING ELECTRICAL OR DEMOLISHED WHERE NOTED EXISTING DEVICE, TO REMAIN IN OPERATION REMOVE DEVICE, KEEP REMAINDER OF CIRCUIT IN OPERATION REMOVE, RELOCATE AND RECONNECT DEVICE ON EXISTING CIRCUIT, EXTEND CIRCUIT N## N## A E - 2 FIXTURE NOTATIONS: A,(b),C - 12 FIXTURE TYPE "A", SWITCH "b", CIRCUIT C - 12 (e) (E) (r) (R) (RR) ELECTRICAL POWER ALL LINE VOLTAGE WIRING IN CONDUIT, SEE GENERAL NOTES TICKS = # OF #12 WIRE, SHORT = HOT, LONG = NEUTRAL, DOT = GROUND, UNLESS NOTED OTHERWISE 120V OUTLET, +18" TO BOTTOM OF BOX S = SIGN F = FLOOR GFI = GROUND FAULT INTERUPTER COUNTER OUTLET QUADRUPLEX OUTLET HALF SWITCHED OUTLETS OUTLETS ON EMERGENCY SYSTEMS DUCT SMOKE DETECTOR JUCTION BOX MOTOR / DISCONNECT PANELBOARD TRANSFORMER / SWITCHBOARD AS NOTED SD DILLON & MURPHY REV. NO. DRAWN BY: BA DESIGNED BY: RCS CHECKED BY: RCS AS BUILT BY: SCALE: AS SHOWN BENCH MARK: EL: JOB NO. SHEET OF - SHEETS DESCRIPTION DATE TWIC GATES 2019 REHABILITATION PROJECT STOCKTON, CALIFORNIA SEPTEMBER, 2019 1872 SEE TITLE SHEET FOR BENCHMARK ENGINEERING PLANNING SURVEYING CONSULTING CIVIL ENGINEERS 847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613 H H H H T T T I I I M M M S S S S C . C . C . C . D D D D R R R R A A A A H H H C C C I I I R R R R No. E14303 No. E14303 No. E14303 No. E14303 Exp. 6 Exp. 6 Exp. 6 Exp. 6- - -30 30 30 30- - -19 19 19 19 E E E L L L L E E E E C C C C T T T T R R R R I I I I C C C C A A A A L L L R R R R E E E E G G G G I I I I S S S S T T T T E E E R R R E E E D D D P P P P R R R R O O O O F F F F E E E E S S S S S S S S I I I I O O O O N N N N A A A A L L L E E E N N N G G G G I I I I N N N N E E E E E E E E R R R R E E E E O O O O F F F F C C C C A A A A L L L L I I I I F F F F O O O O R R R N N N I I I A A A S S S S T T T A A A T T T HCS Engineering 50 years 4512 Feather River Dr #F, Stockton, CA 95219 4512 Feather River Dr #F, Stockton, CA 95219 4512 Feather River Dr #F, Stockton, CA 95219 4512 Feather River Dr #F, Stockton, CA 95219 209 209 209 209- - -478 478 478 478- - -8270 | www.hcs 8270 | www.hcs 8270 | www.hcs 8270 | www.hcs- - -eng.com eng.com eng.com eng.com inc. 6/10/2019 9:14:01 PM C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt E1 ELECTRICAL NOTES, DETAILS AND INFORMATION CONTRACTOR TO PROVIDE: 1. ALL NEW 14 FT GATES INCLUDING ALL NEW BEARING HINGES AND HARDWARE. 2. DUAL LEVEL PEDESTALS FOR CARD READERS 3. TIRE RIPPERS (SEE CIVIL) 4. GATE MOTORS 5. MAG LOCKS 6. EXISTING CONDUITS MAYBE REUSED WHERE THE DEVICES ARE REINSTALLED AT THE SAME LOCATION. CONDUITS MUST BE 24" BELOW FINAL GRADE. NEW SLAB AND BASE TO BE 14" DEEP. 7. PROVIDE FIBER FOC ENCLOSURE AND 24 OR 96 STRAND FIBER WHERE SHOWN. 8. CONTRACTOR TO MAKE ALL CABLE TERMINATIONS AND TESTING 9. ELECTRICAL QUALITY TESTING BY CONTACTOR PORT TO PROVIDE FOR THE CONTRACTOR'S INSTALLATION: A. CARD READERS, B. INTERCOMS C. KNOX BOXES (2 PER PEDESTAL). D. SECURITY CARDS (SHOWN ON TECHNOLOGY PLAN) PORT TO PROVIDE THE FOLLOWING SERVICES: i. PROGRAMMING OF THE TECHNOLOGY EQUIPMENT ii. TECHNOLOGY EQUIPMENT FOR THE COMM'S BOX iii. SPLICE FIBER, TERMINATE FIBER AND TEST FIBER. iv. PORT TO TEST ALL COMMUNCATIONS CABLES. CUSTOM CONCRETE INTERCOM PEDESTAL NTS AUTO VEHICLE ACCESS HEIGHT SEMI CAB ACCESS HEIGHT 18" 12" FULL TRAFFIC RATED "H20" LID DUAL HEIGHT PEDESTAL ARM FINISH GRADE 8", 48" TALL REMOVABLE BOLLARD SIMILAR TO PG&E DETAILS PROVIDE 1/2"x3" HEXHEAD STAINLESS STEEL BOLTS. PROVIDE THREADED RECEIVER IN CONCRETE BOX. PROVIDE THREADED RECEIVED MIN 4" IN 6" OF REINFORCED CONC. PROVIDE SHOP DRAWINGS FOR A CUSTOM CONCRETE BOX WITH H20 FULL TRAFFIC RATED LID THROUGH BOLT PEDESTAL ARM TO H20 LID. VERIFY BOLT PATTERN WITH PEDESTAL INSTALLED. PLAN VIEW PEDSTAL ARM 18" CLEAN INSIDE DIM 30" CLEAR INSIDE DIM INTERCOM, FOB READER, KNOX BOX INTERACTION PLATE. IN PULLBOX BELOW ARM, PROVIDE POLARIS CONNECTORS FOR ALL THHN/ THWN CONNECTIONS AND WEATERTIGHT CAT 6 JUCTIONS FOR DATA CABLING
Transcript
Page 1: TWIC GATES ELECTRICAL - Port of Stockton...TWIC GATES 2019 REHABILITATION PROJECT STOCKTON, CALIFORNIA SEPTEMBER, 2019 1872 SEE TITLE SHEET FOR BENCHMARK ENGINEERING PLANNING SURVEYING

LIGHTING FIXTURES

LINEAR FIXTURE• SQUARE = RECESSED• CIRCLE =SURFACE

DOWNLIGHT, SQUARE = RECESSED

WALL MOUNT

CEILING EXHAUST FAN

POLE MOUNT AREA LIGHT

ELECTRICAL LEGEND

DRAFTING NOTATIONS

KEY NOTE, SEE SCHEDULE

EQUIPMENT TAG, SEE SCHEDULE

REFERENCE TO A DETAIL VIEW "A" ON SHEET E-2

NEW ELECTRICAL

EXISTING ELECTRICAL OR DEMOLISHED WHERE NOTED

EXISTING DEVICE, TO REMAIN IN OPERATION

REMOVE DEVICE, KEEP REMAINDER OF CIRCUIT IN OPERATION

REMOVE, RELOCATE AND RECONNECT DEVICE ON EXISTING CIRCUIT, EXTEND CIRCUIT

N##

N##

A

E-2

FIXTURE NOTATIONS:A,(b),C-12 FIXTURE TYPE "A", SWITCH "b", CIRCUIT C-12

(e) (E)

(r) (R)

(RR)

ELECTRICAL POWER

ALL LINE VOLTAGE WIRING IN CONDUIT, SEE GENERAL NOTES TICKS = # OF #12 WIRE, SHORT = HOT, LONG = NEUTRAL, DOT = GROUND, UNLESS NOTED OTHERWISE

120V OUTLET, +18" TO BOTTOM OF BOX• S = SIGN• F = FLOOR• GFI = GROUND FAULT INTERUPTER

COUNTER OUTLET

QUADRUPLEX OUTLET

HALF SWITCHED OUTLETS

OUTLETS ON EMERGENCY SYSTEMS

DUCT SMOKE DETECTOR

JUCTION BOX

MOTOR / DISCONNECT

PANELBOARD TRANSFORMER / SWITCHBOARD AS NOTED

SD

DILLON & MURPHY

REV. NO.

DRAWN BY: BA

DESIGNED BY: RCS

CHECKED BY: RCS

AS BUILT BY:

SCALE: AS SHOWN BENCH MARK: EL:

JOB NO.

SHEET

OF - SHEETS

DESCRIPTION DATE

TWIC GATES2019 REHABILITATION PROJECT

STOCKTON, CALIFORNIA

SEPTEMBER, 2019

1872

SEE TITLE SHEETFOR BENCHMARK

ENGINEERING PLANNING SURVEYING

CONSULTING CIVIL ENGINEERS

847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613

HHHHTTTTIIII

MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919

EEEE

LLLL EEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

HCSEngineering

50 years

4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com

inc.

6/10/2019 9:14:01 PM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt

E1

ELECTRICAL NOTES, DETAILS AND INFORMATION

CONTRACTOR TO PROVIDE:

1. ALL NEW 14 FT GATES INCLUDING ALL NEW BEARING HINGES AND HARDWARE.2. DUAL LEVEL PEDESTALS FOR CARD READERS3. TIRE RIPPERS (SEE CIVIL)4. GATE MOTORS5. MAG LOCKS6. EXISTING CONDUITS MAYBE REUSED WHERE THE DEVICES ARE REINSTALLED AT THE SAME LOCATION. CONDUITS MUST BE 24" BELOW FINAL GRADE. NEW SLAB AND BASE TO BE 14" DEEP.7. PROVIDE FIBER FOC ENCLOSURE AND 24 OR 96 STRAND FIBER WHERE SHOWN.8. CONTRACTOR TO MAKE ALL CABLE TERMINATIONS AND TESTING9. ELECTRICAL QUALITY TESTING BY CONTACTOR

PORT TO PROVIDE FOR THE CONTRACTOR'S INSTALLATION:

A. CARD READERS,B. INTERCOMSC. KNOX BOXES (2 PER PEDESTAL).D. SECURITY CARDS (SHOWN ON TECHNOLOGY PLAN)

PORT TO PROVIDE THE FOLLOWING SERVICES:

i. PROGRAMMING OF THE TECHNOLOGY EQUIPMENTii. TECHNOLOGY EQUIPMENT FOR THE COMM'S BOXiii. SPLICE FIBER, TERMINATE FIBER AND TEST FIBER. iv. PORT TO TEST ALL COMMUNCATIONS CABLES.

CUSTOM CONCRETE INTERCOM PEDESTALNTS

AUTO VEHICLE ACCESS HEIGHT

SEMI CAB ACCESS HEIGHT

18"12"

FULL TRAFFIC RATED "H20" LID

DUAL HEIGHT PEDESTAL ARM

FINISH GRADE

8", 48" TALLREMOVABLE BOLLARDSIMILAR TO PG&E DETAILS

PROVIDE 1/2"x3" HEXHEAD STAINLESSSTEEL BOLTS. PROVIDE THREADED RECEIVER IN CONCRETE BOX.

PROVIDE THREADEDRECEIVED MIN 4" IN 6" OF REINFORCEDCONC.

PROVIDE SHOP DRAWINGSFOR A CUSTOM CONCRETEBOX WITH H20 FULL TRAFFICRATED LID

THROUGH BOLT PEDESTAL ARMTO H20 LID. VERIFY BOLT PATTERNWITH PEDESTAL INSTALLED.

PLAN VIEW

PEDSTAL ARM

18

" C

LE

AN

IN

SID

E D

IM

30" CLEAR INSIDE DIM

INTERCOM, FOB READER, KNOX BOXINTERACTION PLATE.

IN PULLBOX BELOW ARM, PROVIDEPOLARIS CONNECTORS FOR ALL THHN/THWN CONNECTIONS AND WEATERTIGHTCAT 6 JUCTIONS FOR DATA CABLING

Page 2: TWIC GATES ELECTRICAL - Port of Stockton...TWIC GATES 2019 REHABILITATION PROJECT STOCKTON, CALIFORNIA SEPTEMBER, 2019 1872 SEE TITLE SHEET FOR BENCHMARK ENGINEERING PLANNING SURVEYING

2

2

2

2

2

4

5

6

ALTERNATE BID FOR NEW CANOPYSEE STRUCTURAL PLANS.

TYP3

TYP1

10

TYP12

14

17

2"CO FOR FUTURE SOLAR3/4"C-2#10+1#10 GND (LIGHTS)

7

TYP8

TYP8

TYP9

1117

STUB UP ANDCAP

PROVIDE 3/4"C FROM MOTORTO SECURITY PANELTYPICAL FOR ALL 5 GATESAND 3 TRAFFIC CONTROL ARMS.

STUB 6' PAST RAILINTO PULLBOX

11

13

TO PEDESTAL

2"C STUB FORFUTURE SOLAR,SEE SITE PLAN

PROVIDE FLUSH JUNCTIONBOX AND 3/4"C TO BUILDINGFOR FUTURE TRAFFICCONTROL LIGHTS

STUB CONDUITS FROM BACKWALL, UPTO CANOPY FORFUTURE TRAFFICCONTROL LIGHTS

DILLON & MURPHY

REV. NO.

DRAWN BY: BA

DESIGNED BY: RCS

CHECKED BY: RCS

AS BUILT BY:

SCALE: AS SHOWN BENCH MARK: EL:

JOB NO.

SHEET

OF - SHEETS

DESCRIPTION DATE

TWIC GATES2019 REHABILITATION PROJECT

STOCKTON, CALIFORNIA

SEPTEMBER, 2019

1872

SEE TITLE SHEETFOR BENCHMARK

ENGINEERING PLANNING SURVEYING

CONSULTING CIVIL ENGINEERS

847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613

HHHHTTTTIIII

MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

HCSEngineering

50 years

4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com

inc.

6/10/2019 9:14:05 PM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt

E2

WEST GATE ELECTRICAL PLANS

SCALE: 1" = 20'-0"

WEST COMPLEX ELECTRICAL DEMOLITION SITE PLAN1

SCALE: 1" = 20'-0"

WEST COMPLEX POWER PLAN2SCALE: 1" = 20'-0"

WEST COMPLEX COMMUNICATION PLAN3

ELECTRICAL PLAN NOTES (WEST GATE)

Note Number Note

1 PROVIDE EXIT LOOPS, SAFETY LOOPS, AND TRAFFIC CLEAR LOOPS FOR GATEMOTORS (TO REPLACE EXISTING LOOPS WITH THE REPLACEMENT OF THE ROADSURFACES). TIE INTO GATE MOTORS

2 EXISTING GATE MOTOR TO BE REMOVED. REMOVE WIRE TO SOURCE.

3 PROVIDE NEW GATE MOTOR (TO MATCH EXISTING), PROVIDE HEAVY DUTYDISCONNECT, NEMA 3R 30A FUSED. MAKE ALL CONNECTIONS (POWER, SAFETYAND EXIT LOOPS, REMOTE CONTROL, ETC.) PROVIDE 1"C-3#10+1#10 GND FROMMOTOR TO PANEL. PROVIDE 3/4"C-WIRE AS REQUIRED TO REMOTE GATECONTROL PANEL. PROVIDE 3/4"C TO SECURITY PANEL FOR REMOTE CONTROL.SEE GATE TECHNOLOGY PLAN. PROVIDE WIRE AS REQUIRED.

4 GATE SERVICE PEDESTAL TO BE USED FOR POWER FOR ALL GATES.

5 EXISTING ELECTRICAL PANEL ON SERVICE POLE FEEDS SOUTH SIDE EXIT GATES.THIS PANEL WILL BE ABANDONED AFTER THIS PROJECT.

6 REMOTE GATE OPERATOR STATION WITH OPEN CLOSE CONTROLS. THIS PANEL ISTO BE REPLACED AND RELOCATED TO THE FRONT OF THE GUARD HOUSE.

7 VERIFY LOCATION OF EXISTNG SECURITY SYSTEM PANEL, TIE NEW GATEPEDESTALS INTO CONTROLLER. SEE GATE TECHNOLOGY PLAN FOR CARDS ANDCONNECTIONS

8 ON ALL IN-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN), FORHIGH AND LOW CARD SCANNERS, AND KNOX BOX.) PROVIDE NEW PEDESTALBOLT DOWN BOX TO ALLOW FOR PEDESTAL REMOVAL FOR MAINT.

9 ON ALL OUT-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN),FOR HIGH AND LOW CARD SCANNERS) PROVIDE NEW PEDESTAL BOLT DOWNBOX TO ALLOW FOR PEDESTAL REMOVAL FOR MAINT.

10 PROVIDE NEW REMOTE GATE CONTROLLER CONSOL WITH OPEN / CLOSECONTROLS FOR ALL 5 GATES AND 3 TRAFFIC CONTROL ARMS. ALSO PROVIDE 1"CFROM CONTROL CONSOL TO SECURITY PANEL WITH WIRE AS REQUIRED TO TIEOPERATORS INTO SECURITY SYSTEM

11 PROVIDE (2) SPARE 2"C STUB TO LANDSCAPING FOR FUTURE DATA. STUBCONDUITS INTO CHRISTY N24 PULLBOX WITH 2 EXTENSIONS. MARK LID "DATA".AT GUARD HOUSE, STUB UP AND CAP CONDUITS.

12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THE GATES TOBE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE AN ADDITIONAL 2#12 TOTHE ELECTRICAL PANEL (WITH AN ADDITIONAL 20A CB IN PANEL PROVIDED BYTHE CONTRACTOR), THROUGH A RELAY AT THE SECURITY PANEL.

13 UNDER AN ALTERNATE BID, PROVIDE A LUMINAIRE LIGHTING VPF84 LED FIXTUREABOVE EACH LANE, TIE TO ELECTRICAL PANEL THROUGH A PHOTOCELL.

14 EXISTING SERVICE PEDESTAL, USE EXISTING CIRCUIT BREAKERS TO POWER THEGATE MOTORS, ADD BREAKERS FOR ELECTROMAGNETIC LOCKS IF ALTERNATEBID IS ACCEPTED.

15 MOUNT NEW NEMA 3R TRANSFER SWITCH ON UNISTRUT POSTS, INTERCONNECTWITH PEDESTAL PER ONE LINE DIAGRAM.

16 PROVIDE NEW PORTABLE GENERATOR. CONNECT TO ATS WITH TWISTLOCKS ASSHOWN IN ONE LINE DIAGRAM. CONNECT TO PEDESTAL (PROVIDE NEW CIRCUITBREAKERS), FOR POWER TO BLOCK HEATER AND BATTERY CHARGER(1"C-4#10+1#10 GND). GROUND GENERATOR TO INDEPEDANT 3/4"x10' GND RODWITH #4.

17 PROVIDE TRAFFIC CONTROL ARM GATE, PROVIDE LOCAL DISCONNECT, PROVIDE1"C-CONTROL CABLES PER TECH PLANS, 1"C-2#10+1#10 GND TO SERVICEPEDESTAL

SCALE: 1" = 20'-0"

WEST COMPLEX CANOPY PLAN4

PROVIDECHRISTY N36PULLBOX

Page 3: TWIC GATES ELECTRICAL - Port of Stockton...TWIC GATES 2019 REHABILITATION PROJECT STOCKTON, CALIFORNIA SEPTEMBER, 2019 1872 SEE TITLE SHEET FOR BENCHMARK ENGINEERING PLANNING SURVEYING

TYP3

TYP1

TYP8

9

TYP12

PORT TO PROVIDE CALTRANS IIIAF PEDESTAL120/208V, 3PH, 4W, 100A MAIN, UNMETERED(2)30A3P CB FOR GATES, (1)30A1P CB CONTROL(1)20A1P FOR GFI IN PEDESTAL, (1)20A2P FORSTREET LIGHTINGPROVIDE CALTRANS STANDARD GROUNDINGAND CONCRETE PEDESTAL.

PROVIDE 36x36x12"NEMA 3R ENCLOSUREFOR PORT SECURITYELECTRONICS. SEE TECHNOLOGY DRAWINGFOR BACKBOARD DESIGN.PROVIDE 120V, 20A GFI OUTLET AND 120, 30A TWIST LOCK OUTLET TOMATCH OTHER SITES

1"C-4#10+1#10 GND

PORT TO PROVIDE LIGHT STANDARD

1"C-2#10+1#10GND

2"C-CAT 6 CAMERA CABLE

15

16

(E)FIBER CONDUIT TO PULLBOX DOWNEMBARCADERO

EXTEND 12-STRAND SINGLE MODE FIBER, FROM COMMS ENCLOSURE INCL. 20FT STORAGE, NORTHWARDS THRU NEW )2_2" CONDUITS TO (E)VAULT ON EMBARCADERO, AND THEN EASTWARDS THRU (E)CONDUIT TO (E)VAULT WITH SPLICE ENCLOSURE ADJACENT TO GILMORE GATE INCL. 100FT STORAGE IN EACH VAULT. SPLICING, TERMINATIONS, AND OTDR QA/TESTING BY PORT.

IN BOUND

OUT BOUND

PROVIDE CHRISTY N16PULLBOX

1"C FROM GATE MOTORS TOSECURITY ENCLOSURE WITH 2#14 (REMOTE OPEN SIGNAL)

SAFETYLOOP

DILLON & MURPHY

REV. NO.

DRAWN BY: BA

DESIGNED BY: RCS

CHECKED BY: RCS

AS BUILT BY:

SCALE: AS SHOWN BENCH MARK: EL:

JOB NO.

SHEET

OF - SHEETS

DESCRIPTION DATE

TWIC GATES2019 REHABILITATION PROJECT

STOCKTON, CALIFORNIA

SEPTEMBER, 2019

1872

SEE TITLE SHEETFOR BENCHMARK

ENGINEERING PLANNING SURVEYING

CONSULTING CIVIL ENGINEERS

847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613

HHHHTTTTIIII

MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

HCSEngineering

50 years

4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com

inc.

6/10/2019 9:14:08 PM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt

E3

BOONE DRIVE GATE ELECTRICAL

SCALE: 1" = 10'-0"

BOONE ROAD GATE ELECTRICAL1

ELECTRICAL PLAN NOTES (BOONE)

Note Number Note

1 PROVIDE EXIT LOOPS, SAFETY LOOPS, AND TRAFFIC CLEAR LOOPS FORGATE MOTORS (TO REPLACE EXISTING LOOPS WITH THE REPLACEMENTOF THE ROAD SURFACES). TIE INTO GATE MOTORS

3 PROVIDE NEW GATE MOTOR (TO MATCH EXISTING), PROVIDE HEAVYDUTY DISCONNECT, NEMA 3R 30A FUSED. MAKE ALL CONNECTIONS(POWER, SAFETY AND EXIT LOOPS, REMOTE CONTROL, ETC.) PROVIDE1"C-3#10+1#10 GND FROM MOTOR TO PANEL. PROVIDE 3/4"C-WIRE ASREQUIRED TO REMOTE GATE CONTROL PANEL. PROVIDE 3/4"C TOSECURITY PANEL FOR REMOTE CONTROL. SEE GATE TECHNOLOGYPLAN. PROVIDE WIRE AS REQUIRED.

8 ON ALL IN-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECHPLAN), FOR HIGH AND LOW CARD SCANNERS, AND KNOX BOX.)PROVIDE NEW PEDESTAL BOLT DOWN BOX TO ALLOW FOR PEDESTALREMOVAL FOR MAINT.

9 ON ALL OUT-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECHPLAN), FOR HIGH AND LOW CARD SCANNERS) PROVIDE NEW PEDESTALBOLT DOWN BOX TO ALLOW FOR PEDESTAL REMOVAL FOR MAINT.

12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THEGATES TO BE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE ANADDITIONAL 2#12 TO THE ELECTRICAL PANEL (WITH AN ADDITIONAL 20ACB IN PANEL PROVIDED BY THE CONTRACTOR), THROUGH A RELAY ATTHE SECURITY PANEL.

15 MOUNT NEW NEMA 3R TRANSFER SWITCH ON UNISTRUT POSTS,INTERCONNECT WITH PEDESTAL PER ONE LINE DIAGRAM.

16 PROVIDE NEW PORTABLE GENERATOR. CONNECT TO ATS WITHTWISTLOCKS AS SHOWN IN ONE LINE DIAGRAM. CONNECT TOPEDESTAL (PROVIDE NEW CIRCUIT BREAKERS), FOR POWER TO BLOCKHEATER AND BATTERY CHARGER (1"C-4#10+1#10 GND). GROUNDGENERATOR TO INDEPEDANT 3/4"x10' GND ROD WITH #4.

Page 4: TWIC GATES ELECTRICAL - Port of Stockton...TWIC GATES 2019 REHABILITATION PROJECT STOCKTON, CALIFORNIA SEPTEMBER, 2019 1872 SEE TITLE SHEET FOR BENCHMARK ENGINEERING PLANNING SURVEYING

TYP3

TYP1

7

TYP8

TYP9

10

TYP12

TIE INTO EXISTINGPANEL

(e)PEDESTAL TO BEABANDONED. REMOVEAND RETURN TO PORT

EXISTING GATE MOTORS TO BE REMOVED. THIS MOTORLOCATION IS BEING RELOCATEDTO THE GATE HOUSE

17

TYP2

TYP2

1"C POWER (GATE & LOCK)1"C-2#14 TO SECURITY FOR REMOTE OPENTYPICAL FOR ALL GATE MOTORS

DILLON & MURPHY

REV. NO.

DRAWN BY: BA

DESIGNED BY: RCS

CHECKED BY: RCS

AS BUILT BY:

SCALE: AS SHOWN BENCH MARK: EL:

JOB NO.

SHEET

OF - SHEETS

DESCRIPTION DATE

TWIC GATES2019 REHABILITATION PROJECT

STOCKTON, CALIFORNIA

SEPTEMBER, 2019

1872

SEE TITLE SHEETFOR BENCHMARK

ENGINEERING PLANNING SURVEYING

CONSULTING CIVIL ENGINEERS

847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613

HHHHTTTTIIII

MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

HCSEngineering

50 years

4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com

inc.

6/10/2019 9:14:10 PM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt

E4

EAST GATE ELECTRICAL PLAN

SCALE: 1" = 10'-0"

EAST GATE ELECTRICAL SITE PLAN1

ELECTRICAL PLAN NOTES (EAST GATE)

Note Number Note

1 PROVIDE EXIT LOOPS, SAFETY LOOPS, AND TRAFFIC CLEAR LOOPS FOR GATEMOTORS (TO REPLACE EXISTING LOOPS WITH THE REPLACEMENT OF THE ROADSURFACES). TIE INTO GATE MOTORS

2 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THE GATES TOBE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE AN ADDITIONAL 2#12 TO THEELECTRICAL PANEL (WITH AN ADDITIONAL 20A CB IN PANEL PROVIDED BY THECONTRACTOR), THROUGH A RELAY AT THE SECURITY PANEL.

3 PROVIDE NEW GATE MOTOR (TO MATCH EXISTING), PROVIDE HEAVY DUTYDISCONNECT, NEMA 3R 30A FUSED. MAKE ALL CONNECTIONS (POWER, SAFETY ANDEXIT LOOPS, REMOTE CONTROL, ETC.) PROVIDE 1"C-3#10+1#10 GND FROM MOTORTO PANEL. PROVIDE 3/4"C-WIRE AS REQUIRED TO REMOTE GATE CONTROL PANEL.PROVIDE 3/4"C TO SECURITY PANEL FOR REMOTE CONTROL. SEE GATETECHNOLOGY PLAN. PROVIDE WIRE AS REQUIRED.

7 VERIFY LOCATION OF EXISTNG SECURITY SYSTEM PANEL, TIE NEW GATEPEDESTALS INTO CONTROLLER. SEE GATE TECHNOLOGY PLAN FOR CARDS ANDCONNECTIONS

8 ON ALL IN-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN), FORHIGH AND LOW CARD SCANNERS, AND KNOX BOX.) PROVIDE NEW PEDESTAL BOLTDOWN BOX TO ALLOW FOR PEDESTAL REMOVAL FOR MAINT.

9 ON ALL OUT-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN), FORHIGH AND LOW CARD SCANNERS) PROVIDE NEW PEDESTAL BOLT DOWN BOX TOALLOW FOR PEDESTAL REMOVAL FOR MAINT.

10 PROVIDE NEW REMOTE GATE CONTROLLER CONSOL WITH OPEN / CLOSE CONTROLSFOR ALL 4 GATES AND 2 TRAFFIC CONTROL ARMS. ALSO PROVIDE 1"C FROMCONTROL CONSOL TO SECURITY PANEL WITH WIRE AS REQUIRED TO TIEOPERATORS INTO SECURITY SYSTEM

12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THE GATES TOBE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE AN ADDITIONAL 2#12 TO THEELECTRICAL PANEL (WITH AN ADDITIONAL 20A CB IN PANEL PROVIDED BY THECONTRACTOR), THROUGH A RELAY AT THE SECURITY PANEL.

17 PROVIDE TRAFFIC CONTROL ARM GATE, PROVIDE LOCAL DISCONNECT, PROVIDE1"C-CONTROL CABLES PER TECH PLANS, 1"C-2#10+1#10 GND TO SERVICE PEDESTAL

Page 5: TWIC GATES ELECTRICAL - Port of Stockton...TWIC GATES 2019 REHABILITATION PROJECT STOCKTON, CALIFORNIA SEPTEMBER, 2019 1872 SEE TITLE SHEET FOR BENCHMARK ENGINEERING PLANNING SURVEYING

8

9

TYP12

(e)MOTORS AND SAFETYLOOPS TO REMAIN

15

16

7

14

PULL WIRE TO PANEL AND CONTROLLERTHROUGH EXISTING CONDUITS. TYPICAL

8

9

VERIFY LOCATIONIN FIELD WITH PORT

IN BOUND

OUT BOUND

TYP3

8

9

TYP12

(e)MOTORS AND SAFETYLOOPS TO REMAIN

15

16

714

PULL WIRE TO PANEL AND CONTROLLERTHROUGH EXISTING CONDUITS. TYPICAL

REPLACE WIRE IN EXISTING CONDUITS

DILLON & MURPHY

REV. NO.

DRAWN BY: BA

DESIGNED BY: RCS

CHECKED BY: RCS

AS BUILT BY:

SCALE: AS SHOWN BENCH MARK: EL:

JOB NO.

SHEET

OF - SHEETS

DESCRIPTION DATE

TWIC GATES2019 REHABILITATION PROJECT

STOCKTON, CALIFORNIA

SEPTEMBER, 2019

1872

SEE TITLE SHEETFOR BENCHMARK

ENGINEERING PLANNING SURVEYING

CONSULTING CIVIL ENGINEERS

847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613

HHHHTTTTIIII

MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

HCSEngineering

50 years

4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com

inc.

6/10/2019 9:14:12 PM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt

E5

EMBARCADERO & ROAD 13 GATE ELECTRICAL PLAN

SCALE: 1" = 10'-0"

ROAD 131

ELECTRICAL PLAN NOTES (ROAD 13)

Note Number Note

3 PROVIDE NEW GATE MOTOR (TO MATCH EXISTING), PROVIDE HEAVYDUTY DISCONNECT, NEMA 3R 30A FUSED. MAKE ALL CONNECTIONS(POWER, SAFETY AND EXIT LOOPS, REMOTE CONTROL, ETC.)RECONNECT EXIST FEEDER. PROVIDE 3/4"C TO SECURITY PANEL FORREMOTE CONTROL. SEE GATE TECHNOLOGY PLAN. PROVIDE WIRE ASREQUIRED.

7 VERIFY LOCATION OF EXISTNG SECURITY SYSTEM PANEL, TIE NEWGATE PEDESTALS INTO CONTROLLER. SEE GATE TECHNOLOGY PLANFOR CARDS AND CONNECTIONS

8 ON ALL IN-BOUND GATES, REUSE EXIST CONDUIT PROVIDE 2 SETS OFCABLES (SEE TECH PLAN), FOR HIGH AND LOW CARD SCANNERS, ANDKNOX BOX.) PROVIDE NEW PEDESTAL BOLT DOWN BOX TO ALLOW FORPEDESTAL REMOVAL FOR MAINT.

9 ON ALL OUT-BOUND GATES, REUSE EXISTING CONDUITS PROVIDE 2SETS OF CABLES (SEE TECH PLAN), FOR HIGH AND LOW CARDSCANNERS) PROVIDE NEW PEDESTAL BOLT DOWN BOX TO ALLOW FORPEDESTAL REMOVAL FOR MAINT.

12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THEGATES TO BE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE ANADDITIONAL 2#12 TO THE ELECTRICAL PANEL (WITH AN ADDITIONAL 20ACB IN PANEL PROVIDED BY THE CONTRACTOR), THROUGH A RELAY ATTHE SECURITY PANEL.

14 EXISTING SERVICE PEDESTAL, USE EXISTING CIRCUIT BREAKERS TOPOWER THE GATE MOTORS, ADD BREAKERS FOR ELECTROMAGNETICLOCKS IF ALTERNATE BID IS ACCEPTED.

15 MOUNT NEW NEMA 3R TRANSFER SWITCH ON UNISTRUT POSTS,INTERCONNECT WITH PEDESTAL PER ONE LINE DIAGRAM.

16 PROVIDE NEW PORTABLE GENERATOR. CONNECT TO ATS WITHTWISTLOCKS AS SHOWN IN ONE LINE DIAGRAM. CONNECT TOPEDESTAL (PROVIDE NEW CIRCUIT BREAKERS), FOR POWER TO BLOCKHEATER AND BATTERY CHARGER (1"C-4#10+1#10 GND). GROUNDGENERATOR TO INDEPEDANT 3/4"x10' GND ROD WITH #4.

SCALE: 1" = 10'-0"

EMBARCADERO GATE2

ELECTRICAL PLAN NOTES (EMBARCADERO)

Note Number Note

7 VERIFY LOCATION OF EXISTNG SECURITY SYSTEM PANEL, TIE NEWGATE PEDESTALS INTO CONTROLLER. SEE GATE TECHNOLOGY PLANFOR CARDS AND CONNECTIONS

8 ON ALL IN-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECHPLAN), FOR HIGH AND LOW CARD SCANNERS, AND KNOX BOX.)PROVIDE NEW PEDESTAL BOLT DOWN BOX TO ALLOW FOR PEDESTALREMOVAL FOR MAINT.

12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THEGATES TO BE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE ANADDITIONAL 2#12 TO THE ELECTRICAL PANEL (WITH AN ADDITIONAL 20ACB IN PANEL PROVIDED BY THE CONTRACTOR), THROUGH A RELAY ATTHE SECURITY PANEL.

14 EXISTING SERVICE PEDESTAL, USE EXISTING CIRCUIT BREAKERS TOPOWER THE GATE MOTORS, ADD BREAKERS FOR ELECTROMAGNETICLOCKS IF ALTERNATE BID IS ACCEPTED.

15 MOUNT NEW NEMA 3R TRANSFER SWITCH ON UNISTRUT POSTS,INTERCONNECT WITH PEDESTAL PER ONE LINE DIAGRAM.

16 PROVIDE NEW PORTABLE GENERATOR. CONNECT TO ATS WITHTWISTLOCKS AS SHOWN IN ONE LINE DIAGRAM. CONNECT TOPEDESTAL (PROVIDE NEW CIRCUIT BREAKERS), FOR POWER TO BLOCKHEATER AND BATTERY CHARGER (1"C-4#10+1#10 GND). GROUNDGENERATOR TO INDEPEDANT 3/4"x10' GND ROD WITH #4.

Page 6: TWIC GATES ELECTRICAL - Port of Stockton...TWIC GATES 2019 REHABILITATION PROJECT STOCKTON, CALIFORNIA SEPTEMBER, 2019 1872 SEE TITLE SHEET FOR BENCHMARK ENGINEERING PLANNING SURVEYING

2"C-4#1+1#6 GND

(e)PORT COMMUNICATIONVAULT

OBTAIN RAILROAD CLEARANCEAND BORE (2)4"C, 6' BELOW RAILBED

PROVIDE (2) FULLY TRAFFICRATED CHRISTY N48 PULLBOXES WITH H20 LIDS ONEITHER SIDE OF RAIL

STUB CONDUITS INTO PULLBOXAND COIL 50' OF SPARE CABLE

COIL 25' OF SPARECABLE FOR PORT

(2)4"C, (1)12 PAIR SINGLE MODEGEL FILLED FIBER, TO MATCHEXISTING ON SITE, (1) SPARECONDUIT

(e)PORT ELECTRICAL SERVICEADD 100A3P CB

PROVIDE (2)CHRISTY N24PULLBOXES

EXTEND 12-STRAND SINGLE MODE FIBER, FROM COMMS ENCLOSURE INCL. 20FT STORAGE, NORTHWARDS THRU (2)2" NEW CONDUITS TO (E)VAULT ON PORT ROAD A, AND THEN EASTWARDS THRU (E)CONDUIT TO (E)VAULT WITH SPLICE ENCLOSURE ADJACENT TO WAREHOUSE 5 INCL. 100FT STORAGE IN EACH VAULT. SPLICING, TERMINATIONS, AND OTDR QA/TESTING BY PORT.

TYP3

TYP1

TYP8

9

TYP12

PORT TO PROVIDE CALTRANS IIIAF PEDESTAL120/208V, 3PH, 4W, 100A MAIN, UNMETERED(2)30A3P CB FOR GATES, (1)30A1P CB CONTROL(1)20A1P FOR GFI IN PEDESTAL, (1)20A2P FORSTREET LIGHTINGPROVIDE CALTRANS STANDARD GROUNDINGAND CONCRETE PEDESTAL.

PROVIDE 36x36x12"NEMA 3R ENCLOSUREFOR PORT SECURITYELECTRONICS. SEE TECHNOLOGY DRAWINGFOR BACKBOARD DESIGN.PROVIDE 120V, 20A GFI OUTLET AND 120, 30A TWIST LOCK OUTLET TOMATCH OTHER SITES

1"C-4#10+1#10 GND

PORT TO PROVIDE LIGHT STANDARD

1"C-2#10+1#10GND

2"C-CAT 6 CAMERA CABLE

15

16

DILLON & MURPHY

REV. NO.

DRAWN BY: BA

DESIGNED BY: RCS

CHECKED BY: RCS

AS BUILT BY:

SCALE: AS SHOWN BENCH MARK: EL:

JOB NO.

SHEET

OF - SHEETS

DESCRIPTION DATE

TWIC GATES2019 REHABILITATION PROJECT

STOCKTON, CALIFORNIA

SEPTEMBER, 2019

1872

SEE TITLE SHEETFOR BENCHMARK

ENGINEERING PLANNING SURVEYING

CONSULTING CIVIL ENGINEERS

847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613

HHHHTTTTIIII

MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

HCSEngineering

50 years

4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com

inc.

6/10/2019 9:14:14 PM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt

E6

STORK GATE

SCALE: 1" = 30'-0"

STORK AREA SITE PLAN1

SCALE: 1" = 10'-0"

STORK ROAD GATE ELECTRICAL2

ELECTRICAL PLAN NOTES (STORK)

Note Number Note

1 PROVIDE EXIT LOOPS, SAFETY LOOPS, AND TRAFFIC CLEAR LOOPS FOR GATE MOTORS(TO REPLACE EXISTING LOOPS WITH THE REPLACEMENT OF THE ROAD SURFACES). TIEINTO GATE MOTORS

3 PROVIDE NEW GATE MOTOR (TO MATCH EXISTING), PROVIDE HEAVY DUTYDISCONNECT, NEMA 3R 30A FUSED. MAKE ALL CONNECTIONS (POWER, SAFETY ANDEXIT LOOPS, REMOTE CONTROL, ETC.) PROVIDE 1"C-3#10+1#10 GND FROM MOTOR TOPANEL.PROVIDE 3/4"C TO SECURITY PANEL FOR REMOTE CONTROL. SEE GATETECHNOLOGY PLAN. PROVIDE WIRE AS REQUIRED.

8 ON ALL IN-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN), FOR HIGHAND LOW CARD SCANNERS, AND KNOX BOX.) PROVIDE NEW PEDESTAL BOLT DOWNBOX TO ALLOW FOR PEDESTAL REMOVAL FOR MAINT.

9 ON ALL OUT-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN), FORHIGH AND LOW CARD SCANNERS) PROVIDE NEW PEDESTAL BOLT DOWN BOX TOALLOW FOR PEDESTAL REMOVAL FOR MAINT.

12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THE GATES TO BECONTROLLED BY THE SECURITY SYSTEM, PROVIDE AN ADDITIONAL 2#12 TO THEELECTRICAL PANEL (WITH AN ADDITIONAL 20A CB IN PANEL PROVIDED BY THECONTRACTOR), THROUGH A RELAY AT THE SECURITY PANEL.

15 MOUNT NEW NEMA 3R TRANSFER SWITCH ON UNISTRUT POSTS, INTERCONNECT WITHPEDESTAL PER ONE LINE DIAGRAM.

16 PROVIDE NEW PORTABLE GENERATOR. CONNECT TO ATS WITH TWISTLOCKS ASSHOWN IN ONE LINE DIAGRAM. CONNECT TO PEDESTAL (PROVIDE NEW CIRCUITBREAKERS), FOR POWER TO BLOCK HEATER AND BATTERY CHARGER (1"C-4#10+1#10GND). GROUND GENERATOR TO INDEPEDANT 3/4"x10' GND ROD WITH #4.

Page 7: TWIC GATES ELECTRICAL - Port of Stockton...TWIC GATES 2019 REHABILITATION PROJECT STOCKTON, CALIFORNIA SEPTEMBER, 2019 1872 SEE TITLE SHEET FOR BENCHMARK ENGINEERING PLANNING SURVEYING

DILLON & MURPHY

REV. NO.

DRAWN BY: BA

DESIGNED BY: RCS

CHECKED BY: RCS

AS BUILT BY:

SCALE: AS SHOWN BENCH MARK: EL:

JOB NO.

SHEET

OF - SHEETS

DESCRIPTION DATE

TWIC GATES2019 REHABILITATION PROJECT

STOCKTON, CALIFORNIA

SEPTEMBER, 2019

1872

SEE TITLE SHEETFOR BENCHMARK

ENGINEERING PLANNING SURVEYING

CONSULTING CIVIL ENGINEERS

847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613

HHHHTTTTIIII

MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH

CCCCIIIIRRRR

No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919

EEEE

LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL

RR RREEEEGGGGIIIISSSSTTTTEEEERRRR

EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL

EEEENNNNGGGGIIIINNNNEEEEEEEERR RR

EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF

OOOORRRRNNNN

IIIIAAAA

SSSSTTTTAAAATTTT

HCSEngineering

50 years

4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com

inc.

6/10/2019 9:14:14 PM

C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt

E7

TECHNOLOGY PLAN