LIGHTING FIXTURES
LINEAR FIXTURE• SQUARE = RECESSED• CIRCLE =SURFACE
DOWNLIGHT, SQUARE = RECESSED
WALL MOUNT
CEILING EXHAUST FAN
POLE MOUNT AREA LIGHT
ELECTRICAL LEGEND
DRAFTING NOTATIONS
KEY NOTE, SEE SCHEDULE
EQUIPMENT TAG, SEE SCHEDULE
REFERENCE TO A DETAIL VIEW "A" ON SHEET E-2
NEW ELECTRICAL
EXISTING ELECTRICAL OR DEMOLISHED WHERE NOTED
EXISTING DEVICE, TO REMAIN IN OPERATION
REMOVE DEVICE, KEEP REMAINDER OF CIRCUIT IN OPERATION
REMOVE, RELOCATE AND RECONNECT DEVICE ON EXISTING CIRCUIT, EXTEND CIRCUIT
N##
N##
A
E-2
FIXTURE NOTATIONS:A,(b),C-12 FIXTURE TYPE "A", SWITCH "b", CIRCUIT C-12
(e) (E)
(r) (R)
(RR)
ELECTRICAL POWER
ALL LINE VOLTAGE WIRING IN CONDUIT, SEE GENERAL NOTES TICKS = # OF #12 WIRE, SHORT = HOT, LONG = NEUTRAL, DOT = GROUND, UNLESS NOTED OTHERWISE
120V OUTLET, +18" TO BOTTOM OF BOX• S = SIGN• F = FLOOR• GFI = GROUND FAULT INTERUPTER
COUNTER OUTLET
QUADRUPLEX OUTLET
HALF SWITCHED OUTLETS
OUTLETS ON EMERGENCY SYSTEMS
DUCT SMOKE DETECTOR
JUCTION BOX
MOTOR / DISCONNECT
PANELBOARD TRANSFORMER / SWITCHBOARD AS NOTED
SD
DILLON & MURPHY
REV. NO.
DRAWN BY: BA
DESIGNED BY: RCS
CHECKED BY: RCS
AS BUILT BY:
SCALE: AS SHOWN BENCH MARK: EL:
JOB NO.
SHEET
OF - SHEETS
DESCRIPTION DATE
TWIC GATES2019 REHABILITATION PROJECT
STOCKTON, CALIFORNIA
SEPTEMBER, 2019
1872
SEE TITLE SHEETFOR BENCHMARK
ENGINEERING PLANNING SURVEYING
CONSULTING CIVIL ENGINEERS
847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613
HHHHTTTTIIII
MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH
CCCCIIIIRRRR
No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919
EEEE
LLLL EEEECCCCTTTTRRRR IIII CCCCAAAALLLL
RR RREEEEGGGGIIIISSSSTTTTEEEERRRR
EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL
EEEENNNNGGGGIIIINNNNEEEEEEEERR RR
EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF
OOOORRRRNNNN
IIIIAAAA
SSSSTTTTAAAATTTT
HCSEngineering
50 years
4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com
inc.
6/10/2019 9:14:01 PM
C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt
E1
ELECTRICAL NOTES, DETAILS AND INFORMATION
CONTRACTOR TO PROVIDE:
1. ALL NEW 14 FT GATES INCLUDING ALL NEW BEARING HINGES AND HARDWARE.2. DUAL LEVEL PEDESTALS FOR CARD READERS3. TIRE RIPPERS (SEE CIVIL)4. GATE MOTORS5. MAG LOCKS6. EXISTING CONDUITS MAYBE REUSED WHERE THE DEVICES ARE REINSTALLED AT THE SAME LOCATION. CONDUITS MUST BE 24" BELOW FINAL GRADE. NEW SLAB AND BASE TO BE 14" DEEP.7. PROVIDE FIBER FOC ENCLOSURE AND 24 OR 96 STRAND FIBER WHERE SHOWN.8. CONTRACTOR TO MAKE ALL CABLE TERMINATIONS AND TESTING9. ELECTRICAL QUALITY TESTING BY CONTACTOR
PORT TO PROVIDE FOR THE CONTRACTOR'S INSTALLATION:
A. CARD READERS,B. INTERCOMSC. KNOX BOXES (2 PER PEDESTAL).D. SECURITY CARDS (SHOWN ON TECHNOLOGY PLAN)
PORT TO PROVIDE THE FOLLOWING SERVICES:
i. PROGRAMMING OF THE TECHNOLOGY EQUIPMENTii. TECHNOLOGY EQUIPMENT FOR THE COMM'S BOXiii. SPLICE FIBER, TERMINATE FIBER AND TEST FIBER. iv. PORT TO TEST ALL COMMUNCATIONS CABLES.
CUSTOM CONCRETE INTERCOM PEDESTALNTS
AUTO VEHICLE ACCESS HEIGHT
SEMI CAB ACCESS HEIGHT
18"12"
FULL TRAFFIC RATED "H20" LID
DUAL HEIGHT PEDESTAL ARM
FINISH GRADE
8", 48" TALLREMOVABLE BOLLARDSIMILAR TO PG&E DETAILS
PROVIDE 1/2"x3" HEXHEAD STAINLESSSTEEL BOLTS. PROVIDE THREADED RECEIVER IN CONCRETE BOX.
PROVIDE THREADEDRECEIVED MIN 4" IN 6" OF REINFORCEDCONC.
PROVIDE SHOP DRAWINGSFOR A CUSTOM CONCRETEBOX WITH H20 FULL TRAFFICRATED LID
THROUGH BOLT PEDESTAL ARMTO H20 LID. VERIFY BOLT PATTERNWITH PEDESTAL INSTALLED.
PLAN VIEW
PEDSTAL ARM
18
" C
LE
AN
IN
SID
E D
IM
30" CLEAR INSIDE DIM
INTERCOM, FOB READER, KNOX BOXINTERACTION PLATE.
IN PULLBOX BELOW ARM, PROVIDEPOLARIS CONNECTORS FOR ALL THHN/THWN CONNECTIONS AND WEATERTIGHTCAT 6 JUCTIONS FOR DATA CABLING
2
2
2
2
2
4
5
6
ALTERNATE BID FOR NEW CANOPYSEE STRUCTURAL PLANS.
TYP3
TYP1
10
TYP12
14
17
2"CO FOR FUTURE SOLAR3/4"C-2#10+1#10 GND (LIGHTS)
7
TYP8
TYP8
TYP9
1117
STUB UP ANDCAP
PROVIDE 3/4"C FROM MOTORTO SECURITY PANELTYPICAL FOR ALL 5 GATESAND 3 TRAFFIC CONTROL ARMS.
STUB 6' PAST RAILINTO PULLBOX
11
13
TO PEDESTAL
2"C STUB FORFUTURE SOLAR,SEE SITE PLAN
PROVIDE FLUSH JUNCTIONBOX AND 3/4"C TO BUILDINGFOR FUTURE TRAFFICCONTROL LIGHTS
STUB CONDUITS FROM BACKWALL, UPTO CANOPY FORFUTURE TRAFFICCONTROL LIGHTS
DILLON & MURPHY
REV. NO.
DRAWN BY: BA
DESIGNED BY: RCS
CHECKED BY: RCS
AS BUILT BY:
SCALE: AS SHOWN BENCH MARK: EL:
JOB NO.
SHEET
OF - SHEETS
DESCRIPTION DATE
TWIC GATES2019 REHABILITATION PROJECT
STOCKTON, CALIFORNIA
SEPTEMBER, 2019
1872
SEE TITLE SHEETFOR BENCHMARK
ENGINEERING PLANNING SURVEYING
CONSULTING CIVIL ENGINEERS
847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613
HHHHTTTTIIII
MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH
CCCCIIIIRRRR
No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919
EEEE
LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL
RR RREEEEGGGGIIIISSSSTTTTEEEERRRR
EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL
EEEENNNNGGGGIIIINNNNEEEEEEEERR RR
EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF
OOOORRRRNNNN
IIIIAAAA
SSSSTTTTAAAATTTT
HCSEngineering
50 years
4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com
inc.
6/10/2019 9:14:05 PM
C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt
E2
WEST GATE ELECTRICAL PLANS
SCALE: 1" = 20'-0"
WEST COMPLEX ELECTRICAL DEMOLITION SITE PLAN1
SCALE: 1" = 20'-0"
WEST COMPLEX POWER PLAN2SCALE: 1" = 20'-0"
WEST COMPLEX COMMUNICATION PLAN3
ELECTRICAL PLAN NOTES (WEST GATE)
Note Number Note
1 PROVIDE EXIT LOOPS, SAFETY LOOPS, AND TRAFFIC CLEAR LOOPS FOR GATEMOTORS (TO REPLACE EXISTING LOOPS WITH THE REPLACEMENT OF THE ROADSURFACES). TIE INTO GATE MOTORS
2 EXISTING GATE MOTOR TO BE REMOVED. REMOVE WIRE TO SOURCE.
3 PROVIDE NEW GATE MOTOR (TO MATCH EXISTING), PROVIDE HEAVY DUTYDISCONNECT, NEMA 3R 30A FUSED. MAKE ALL CONNECTIONS (POWER, SAFETYAND EXIT LOOPS, REMOTE CONTROL, ETC.) PROVIDE 1"C-3#10+1#10 GND FROMMOTOR TO PANEL. PROVIDE 3/4"C-WIRE AS REQUIRED TO REMOTE GATECONTROL PANEL. PROVIDE 3/4"C TO SECURITY PANEL FOR REMOTE CONTROL.SEE GATE TECHNOLOGY PLAN. PROVIDE WIRE AS REQUIRED.
4 GATE SERVICE PEDESTAL TO BE USED FOR POWER FOR ALL GATES.
5 EXISTING ELECTRICAL PANEL ON SERVICE POLE FEEDS SOUTH SIDE EXIT GATES.THIS PANEL WILL BE ABANDONED AFTER THIS PROJECT.
6 REMOTE GATE OPERATOR STATION WITH OPEN CLOSE CONTROLS. THIS PANEL ISTO BE REPLACED AND RELOCATED TO THE FRONT OF THE GUARD HOUSE.
7 VERIFY LOCATION OF EXISTNG SECURITY SYSTEM PANEL, TIE NEW GATEPEDESTALS INTO CONTROLLER. SEE GATE TECHNOLOGY PLAN FOR CARDS ANDCONNECTIONS
8 ON ALL IN-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN), FORHIGH AND LOW CARD SCANNERS, AND KNOX BOX.) PROVIDE NEW PEDESTALBOLT DOWN BOX TO ALLOW FOR PEDESTAL REMOVAL FOR MAINT.
9 ON ALL OUT-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN),FOR HIGH AND LOW CARD SCANNERS) PROVIDE NEW PEDESTAL BOLT DOWNBOX TO ALLOW FOR PEDESTAL REMOVAL FOR MAINT.
10 PROVIDE NEW REMOTE GATE CONTROLLER CONSOL WITH OPEN / CLOSECONTROLS FOR ALL 5 GATES AND 3 TRAFFIC CONTROL ARMS. ALSO PROVIDE 1"CFROM CONTROL CONSOL TO SECURITY PANEL WITH WIRE AS REQUIRED TO TIEOPERATORS INTO SECURITY SYSTEM
11 PROVIDE (2) SPARE 2"C STUB TO LANDSCAPING FOR FUTURE DATA. STUBCONDUITS INTO CHRISTY N24 PULLBOX WITH 2 EXTENSIONS. MARK LID "DATA".AT GUARD HOUSE, STUB UP AND CAP CONDUITS.
12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THE GATES TOBE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE AN ADDITIONAL 2#12 TOTHE ELECTRICAL PANEL (WITH AN ADDITIONAL 20A CB IN PANEL PROVIDED BYTHE CONTRACTOR), THROUGH A RELAY AT THE SECURITY PANEL.
13 UNDER AN ALTERNATE BID, PROVIDE A LUMINAIRE LIGHTING VPF84 LED FIXTUREABOVE EACH LANE, TIE TO ELECTRICAL PANEL THROUGH A PHOTOCELL.
14 EXISTING SERVICE PEDESTAL, USE EXISTING CIRCUIT BREAKERS TO POWER THEGATE MOTORS, ADD BREAKERS FOR ELECTROMAGNETIC LOCKS IF ALTERNATEBID IS ACCEPTED.
15 MOUNT NEW NEMA 3R TRANSFER SWITCH ON UNISTRUT POSTS, INTERCONNECTWITH PEDESTAL PER ONE LINE DIAGRAM.
16 PROVIDE NEW PORTABLE GENERATOR. CONNECT TO ATS WITH TWISTLOCKS ASSHOWN IN ONE LINE DIAGRAM. CONNECT TO PEDESTAL (PROVIDE NEW CIRCUITBREAKERS), FOR POWER TO BLOCK HEATER AND BATTERY CHARGER(1"C-4#10+1#10 GND). GROUND GENERATOR TO INDEPEDANT 3/4"x10' GND RODWITH #4.
17 PROVIDE TRAFFIC CONTROL ARM GATE, PROVIDE LOCAL DISCONNECT, PROVIDE1"C-CONTROL CABLES PER TECH PLANS, 1"C-2#10+1#10 GND TO SERVICEPEDESTAL
SCALE: 1" = 20'-0"
WEST COMPLEX CANOPY PLAN4
PROVIDECHRISTY N36PULLBOX
TYP3
TYP1
TYP8
9
TYP12
PORT TO PROVIDE CALTRANS IIIAF PEDESTAL120/208V, 3PH, 4W, 100A MAIN, UNMETERED(2)30A3P CB FOR GATES, (1)30A1P CB CONTROL(1)20A1P FOR GFI IN PEDESTAL, (1)20A2P FORSTREET LIGHTINGPROVIDE CALTRANS STANDARD GROUNDINGAND CONCRETE PEDESTAL.
PROVIDE 36x36x12"NEMA 3R ENCLOSUREFOR PORT SECURITYELECTRONICS. SEE TECHNOLOGY DRAWINGFOR BACKBOARD DESIGN.PROVIDE 120V, 20A GFI OUTLET AND 120, 30A TWIST LOCK OUTLET TOMATCH OTHER SITES
1"C-4#10+1#10 GND
PORT TO PROVIDE LIGHT STANDARD
1"C-2#10+1#10GND
2"C-CAT 6 CAMERA CABLE
15
16
(E)FIBER CONDUIT TO PULLBOX DOWNEMBARCADERO
EXTEND 12-STRAND SINGLE MODE FIBER, FROM COMMS ENCLOSURE INCL. 20FT STORAGE, NORTHWARDS THRU NEW )2_2" CONDUITS TO (E)VAULT ON EMBARCADERO, AND THEN EASTWARDS THRU (E)CONDUIT TO (E)VAULT WITH SPLICE ENCLOSURE ADJACENT TO GILMORE GATE INCL. 100FT STORAGE IN EACH VAULT. SPLICING, TERMINATIONS, AND OTDR QA/TESTING BY PORT.
IN BOUND
OUT BOUND
PROVIDE CHRISTY N16PULLBOX
1"C FROM GATE MOTORS TOSECURITY ENCLOSURE WITH 2#14 (REMOTE OPEN SIGNAL)
SAFETYLOOP
DILLON & MURPHY
REV. NO.
DRAWN BY: BA
DESIGNED BY: RCS
CHECKED BY: RCS
AS BUILT BY:
SCALE: AS SHOWN BENCH MARK: EL:
JOB NO.
SHEET
OF - SHEETS
DESCRIPTION DATE
TWIC GATES2019 REHABILITATION PROJECT
STOCKTON, CALIFORNIA
SEPTEMBER, 2019
1872
SEE TITLE SHEETFOR BENCHMARK
ENGINEERING PLANNING SURVEYING
CONSULTING CIVIL ENGINEERS
847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613
HHHHTTTTIIII
MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH
CCCCIIIIRRRR
No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919
EEEE
LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL
RR RREEEEGGGGIIIISSSSTTTTEEEERRRR
EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL
EEEENNNNGGGGIIIINNNNEEEEEEEERR RR
EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF
OOOORRRRNNNN
IIIIAAAA
SSSSTTTTAAAATTTT
HCSEngineering
50 years
4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com
inc.
6/10/2019 9:14:08 PM
C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt
E3
BOONE DRIVE GATE ELECTRICAL
SCALE: 1" = 10'-0"
BOONE ROAD GATE ELECTRICAL1
ELECTRICAL PLAN NOTES (BOONE)
Note Number Note
1 PROVIDE EXIT LOOPS, SAFETY LOOPS, AND TRAFFIC CLEAR LOOPS FORGATE MOTORS (TO REPLACE EXISTING LOOPS WITH THE REPLACEMENTOF THE ROAD SURFACES). TIE INTO GATE MOTORS
3 PROVIDE NEW GATE MOTOR (TO MATCH EXISTING), PROVIDE HEAVYDUTY DISCONNECT, NEMA 3R 30A FUSED. MAKE ALL CONNECTIONS(POWER, SAFETY AND EXIT LOOPS, REMOTE CONTROL, ETC.) PROVIDE1"C-3#10+1#10 GND FROM MOTOR TO PANEL. PROVIDE 3/4"C-WIRE ASREQUIRED TO REMOTE GATE CONTROL PANEL. PROVIDE 3/4"C TOSECURITY PANEL FOR REMOTE CONTROL. SEE GATE TECHNOLOGYPLAN. PROVIDE WIRE AS REQUIRED.
8 ON ALL IN-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECHPLAN), FOR HIGH AND LOW CARD SCANNERS, AND KNOX BOX.)PROVIDE NEW PEDESTAL BOLT DOWN BOX TO ALLOW FOR PEDESTALREMOVAL FOR MAINT.
9 ON ALL OUT-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECHPLAN), FOR HIGH AND LOW CARD SCANNERS) PROVIDE NEW PEDESTALBOLT DOWN BOX TO ALLOW FOR PEDESTAL REMOVAL FOR MAINT.
12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THEGATES TO BE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE ANADDITIONAL 2#12 TO THE ELECTRICAL PANEL (WITH AN ADDITIONAL 20ACB IN PANEL PROVIDED BY THE CONTRACTOR), THROUGH A RELAY ATTHE SECURITY PANEL.
15 MOUNT NEW NEMA 3R TRANSFER SWITCH ON UNISTRUT POSTS,INTERCONNECT WITH PEDESTAL PER ONE LINE DIAGRAM.
16 PROVIDE NEW PORTABLE GENERATOR. CONNECT TO ATS WITHTWISTLOCKS AS SHOWN IN ONE LINE DIAGRAM. CONNECT TOPEDESTAL (PROVIDE NEW CIRCUIT BREAKERS), FOR POWER TO BLOCKHEATER AND BATTERY CHARGER (1"C-4#10+1#10 GND). GROUNDGENERATOR TO INDEPEDANT 3/4"x10' GND ROD WITH #4.
TYP3
TYP1
7
TYP8
TYP9
10
TYP12
TIE INTO EXISTINGPANEL
(e)PEDESTAL TO BEABANDONED. REMOVEAND RETURN TO PORT
EXISTING GATE MOTORS TO BE REMOVED. THIS MOTORLOCATION IS BEING RELOCATEDTO THE GATE HOUSE
17
TYP2
TYP2
1"C POWER (GATE & LOCK)1"C-2#14 TO SECURITY FOR REMOTE OPENTYPICAL FOR ALL GATE MOTORS
DILLON & MURPHY
REV. NO.
DRAWN BY: BA
DESIGNED BY: RCS
CHECKED BY: RCS
AS BUILT BY:
SCALE: AS SHOWN BENCH MARK: EL:
JOB NO.
SHEET
OF - SHEETS
DESCRIPTION DATE
TWIC GATES2019 REHABILITATION PROJECT
STOCKTON, CALIFORNIA
SEPTEMBER, 2019
1872
SEE TITLE SHEETFOR BENCHMARK
ENGINEERING PLANNING SURVEYING
CONSULTING CIVIL ENGINEERS
847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613
HHHHTTTTIIII
MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH
CCCCIIIIRRRR
No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919
EEEE
LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL
RR RREEEEGGGGIIIISSSSTTTTEEEERRRR
EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL
EEEENNNNGGGGIIIINNNNEEEEEEEERR RR
EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF
OOOORRRRNNNN
IIIIAAAA
SSSSTTTTAAAATTTT
HCSEngineering
50 years
4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com
inc.
6/10/2019 9:14:10 PM
C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt
E4
EAST GATE ELECTRICAL PLAN
SCALE: 1" = 10'-0"
EAST GATE ELECTRICAL SITE PLAN1
ELECTRICAL PLAN NOTES (EAST GATE)
Note Number Note
1 PROVIDE EXIT LOOPS, SAFETY LOOPS, AND TRAFFIC CLEAR LOOPS FOR GATEMOTORS (TO REPLACE EXISTING LOOPS WITH THE REPLACEMENT OF THE ROADSURFACES). TIE INTO GATE MOTORS
2 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THE GATES TOBE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE AN ADDITIONAL 2#12 TO THEELECTRICAL PANEL (WITH AN ADDITIONAL 20A CB IN PANEL PROVIDED BY THECONTRACTOR), THROUGH A RELAY AT THE SECURITY PANEL.
3 PROVIDE NEW GATE MOTOR (TO MATCH EXISTING), PROVIDE HEAVY DUTYDISCONNECT, NEMA 3R 30A FUSED. MAKE ALL CONNECTIONS (POWER, SAFETY ANDEXIT LOOPS, REMOTE CONTROL, ETC.) PROVIDE 1"C-3#10+1#10 GND FROM MOTORTO PANEL. PROVIDE 3/4"C-WIRE AS REQUIRED TO REMOTE GATE CONTROL PANEL.PROVIDE 3/4"C TO SECURITY PANEL FOR REMOTE CONTROL. SEE GATETECHNOLOGY PLAN. PROVIDE WIRE AS REQUIRED.
7 VERIFY LOCATION OF EXISTNG SECURITY SYSTEM PANEL, TIE NEW GATEPEDESTALS INTO CONTROLLER. SEE GATE TECHNOLOGY PLAN FOR CARDS ANDCONNECTIONS
8 ON ALL IN-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN), FORHIGH AND LOW CARD SCANNERS, AND KNOX BOX.) PROVIDE NEW PEDESTAL BOLTDOWN BOX TO ALLOW FOR PEDESTAL REMOVAL FOR MAINT.
9 ON ALL OUT-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN), FORHIGH AND LOW CARD SCANNERS) PROVIDE NEW PEDESTAL BOLT DOWN BOX TOALLOW FOR PEDESTAL REMOVAL FOR MAINT.
10 PROVIDE NEW REMOTE GATE CONTROLLER CONSOL WITH OPEN / CLOSE CONTROLSFOR ALL 4 GATES AND 2 TRAFFIC CONTROL ARMS. ALSO PROVIDE 1"C FROMCONTROL CONSOL TO SECURITY PANEL WITH WIRE AS REQUIRED TO TIEOPERATORS INTO SECURITY SYSTEM
12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THE GATES TOBE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE AN ADDITIONAL 2#12 TO THEELECTRICAL PANEL (WITH AN ADDITIONAL 20A CB IN PANEL PROVIDED BY THECONTRACTOR), THROUGH A RELAY AT THE SECURITY PANEL.
17 PROVIDE TRAFFIC CONTROL ARM GATE, PROVIDE LOCAL DISCONNECT, PROVIDE1"C-CONTROL CABLES PER TECH PLANS, 1"C-2#10+1#10 GND TO SERVICE PEDESTAL
8
9
TYP12
(e)MOTORS AND SAFETYLOOPS TO REMAIN
15
16
7
14
PULL WIRE TO PANEL AND CONTROLLERTHROUGH EXISTING CONDUITS. TYPICAL
8
9
VERIFY LOCATIONIN FIELD WITH PORT
IN BOUND
OUT BOUND
TYP3
8
9
TYP12
(e)MOTORS AND SAFETYLOOPS TO REMAIN
15
16
714
PULL WIRE TO PANEL AND CONTROLLERTHROUGH EXISTING CONDUITS. TYPICAL
REPLACE WIRE IN EXISTING CONDUITS
DILLON & MURPHY
REV. NO.
DRAWN BY: BA
DESIGNED BY: RCS
CHECKED BY: RCS
AS BUILT BY:
SCALE: AS SHOWN BENCH MARK: EL:
JOB NO.
SHEET
OF - SHEETS
DESCRIPTION DATE
TWIC GATES2019 REHABILITATION PROJECT
STOCKTON, CALIFORNIA
SEPTEMBER, 2019
1872
SEE TITLE SHEETFOR BENCHMARK
ENGINEERING PLANNING SURVEYING
CONSULTING CIVIL ENGINEERS
847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613
HHHHTTTTIIII
MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH
CCCCIIIIRRRR
No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919
EEEE
LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL
RR RREEEEGGGGIIIISSSSTTTTEEEERRRR
EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL
EEEENNNNGGGGIIIINNNNEEEEEEEERR RR
EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF
OOOORRRRNNNN
IIIIAAAA
SSSSTTTTAAAATTTT
HCSEngineering
50 years
4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com
inc.
6/10/2019 9:14:12 PM
C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt
E5
EMBARCADERO & ROAD 13 GATE ELECTRICAL PLAN
SCALE: 1" = 10'-0"
ROAD 131
ELECTRICAL PLAN NOTES (ROAD 13)
Note Number Note
3 PROVIDE NEW GATE MOTOR (TO MATCH EXISTING), PROVIDE HEAVYDUTY DISCONNECT, NEMA 3R 30A FUSED. MAKE ALL CONNECTIONS(POWER, SAFETY AND EXIT LOOPS, REMOTE CONTROL, ETC.)RECONNECT EXIST FEEDER. PROVIDE 3/4"C TO SECURITY PANEL FORREMOTE CONTROL. SEE GATE TECHNOLOGY PLAN. PROVIDE WIRE ASREQUIRED.
7 VERIFY LOCATION OF EXISTNG SECURITY SYSTEM PANEL, TIE NEWGATE PEDESTALS INTO CONTROLLER. SEE GATE TECHNOLOGY PLANFOR CARDS AND CONNECTIONS
8 ON ALL IN-BOUND GATES, REUSE EXIST CONDUIT PROVIDE 2 SETS OFCABLES (SEE TECH PLAN), FOR HIGH AND LOW CARD SCANNERS, ANDKNOX BOX.) PROVIDE NEW PEDESTAL BOLT DOWN BOX TO ALLOW FORPEDESTAL REMOVAL FOR MAINT.
9 ON ALL OUT-BOUND GATES, REUSE EXISTING CONDUITS PROVIDE 2SETS OF CABLES (SEE TECH PLAN), FOR HIGH AND LOW CARDSCANNERS) PROVIDE NEW PEDESTAL BOLT DOWN BOX TO ALLOW FORPEDESTAL REMOVAL FOR MAINT.
12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THEGATES TO BE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE ANADDITIONAL 2#12 TO THE ELECTRICAL PANEL (WITH AN ADDITIONAL 20ACB IN PANEL PROVIDED BY THE CONTRACTOR), THROUGH A RELAY ATTHE SECURITY PANEL.
14 EXISTING SERVICE PEDESTAL, USE EXISTING CIRCUIT BREAKERS TOPOWER THE GATE MOTORS, ADD BREAKERS FOR ELECTROMAGNETICLOCKS IF ALTERNATE BID IS ACCEPTED.
15 MOUNT NEW NEMA 3R TRANSFER SWITCH ON UNISTRUT POSTS,INTERCONNECT WITH PEDESTAL PER ONE LINE DIAGRAM.
16 PROVIDE NEW PORTABLE GENERATOR. CONNECT TO ATS WITHTWISTLOCKS AS SHOWN IN ONE LINE DIAGRAM. CONNECT TOPEDESTAL (PROVIDE NEW CIRCUIT BREAKERS), FOR POWER TO BLOCKHEATER AND BATTERY CHARGER (1"C-4#10+1#10 GND). GROUNDGENERATOR TO INDEPEDANT 3/4"x10' GND ROD WITH #4.
SCALE: 1" = 10'-0"
EMBARCADERO GATE2
ELECTRICAL PLAN NOTES (EMBARCADERO)
Note Number Note
7 VERIFY LOCATION OF EXISTNG SECURITY SYSTEM PANEL, TIE NEWGATE PEDESTALS INTO CONTROLLER. SEE GATE TECHNOLOGY PLANFOR CARDS AND CONNECTIONS
8 ON ALL IN-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECHPLAN), FOR HIGH AND LOW CARD SCANNERS, AND KNOX BOX.)PROVIDE NEW PEDESTAL BOLT DOWN BOX TO ALLOW FOR PEDESTALREMOVAL FOR MAINT.
12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THEGATES TO BE CONTROLLED BY THE SECURITY SYSTEM, PROVIDE ANADDITIONAL 2#12 TO THE ELECTRICAL PANEL (WITH AN ADDITIONAL 20ACB IN PANEL PROVIDED BY THE CONTRACTOR), THROUGH A RELAY ATTHE SECURITY PANEL.
14 EXISTING SERVICE PEDESTAL, USE EXISTING CIRCUIT BREAKERS TOPOWER THE GATE MOTORS, ADD BREAKERS FOR ELECTROMAGNETICLOCKS IF ALTERNATE BID IS ACCEPTED.
15 MOUNT NEW NEMA 3R TRANSFER SWITCH ON UNISTRUT POSTS,INTERCONNECT WITH PEDESTAL PER ONE LINE DIAGRAM.
16 PROVIDE NEW PORTABLE GENERATOR. CONNECT TO ATS WITHTWISTLOCKS AS SHOWN IN ONE LINE DIAGRAM. CONNECT TOPEDESTAL (PROVIDE NEW CIRCUIT BREAKERS), FOR POWER TO BLOCKHEATER AND BATTERY CHARGER (1"C-4#10+1#10 GND). GROUNDGENERATOR TO INDEPEDANT 3/4"x10' GND ROD WITH #4.
2"C-4#1+1#6 GND
(e)PORT COMMUNICATIONVAULT
OBTAIN RAILROAD CLEARANCEAND BORE (2)4"C, 6' BELOW RAILBED
PROVIDE (2) FULLY TRAFFICRATED CHRISTY N48 PULLBOXES WITH H20 LIDS ONEITHER SIDE OF RAIL
STUB CONDUITS INTO PULLBOXAND COIL 50' OF SPARE CABLE
COIL 25' OF SPARECABLE FOR PORT
(2)4"C, (1)12 PAIR SINGLE MODEGEL FILLED FIBER, TO MATCHEXISTING ON SITE, (1) SPARECONDUIT
(e)PORT ELECTRICAL SERVICEADD 100A3P CB
PROVIDE (2)CHRISTY N24PULLBOXES
EXTEND 12-STRAND SINGLE MODE FIBER, FROM COMMS ENCLOSURE INCL. 20FT STORAGE, NORTHWARDS THRU (2)2" NEW CONDUITS TO (E)VAULT ON PORT ROAD A, AND THEN EASTWARDS THRU (E)CONDUIT TO (E)VAULT WITH SPLICE ENCLOSURE ADJACENT TO WAREHOUSE 5 INCL. 100FT STORAGE IN EACH VAULT. SPLICING, TERMINATIONS, AND OTDR QA/TESTING BY PORT.
TYP3
TYP1
TYP8
9
TYP12
PORT TO PROVIDE CALTRANS IIIAF PEDESTAL120/208V, 3PH, 4W, 100A MAIN, UNMETERED(2)30A3P CB FOR GATES, (1)30A1P CB CONTROL(1)20A1P FOR GFI IN PEDESTAL, (1)20A2P FORSTREET LIGHTINGPROVIDE CALTRANS STANDARD GROUNDINGAND CONCRETE PEDESTAL.
PROVIDE 36x36x12"NEMA 3R ENCLOSUREFOR PORT SECURITYELECTRONICS. SEE TECHNOLOGY DRAWINGFOR BACKBOARD DESIGN.PROVIDE 120V, 20A GFI OUTLET AND 120, 30A TWIST LOCK OUTLET TOMATCH OTHER SITES
1"C-4#10+1#10 GND
PORT TO PROVIDE LIGHT STANDARD
1"C-2#10+1#10GND
2"C-CAT 6 CAMERA CABLE
15
16
DILLON & MURPHY
REV. NO.
DRAWN BY: BA
DESIGNED BY: RCS
CHECKED BY: RCS
AS BUILT BY:
SCALE: AS SHOWN BENCH MARK: EL:
JOB NO.
SHEET
OF - SHEETS
DESCRIPTION DATE
TWIC GATES2019 REHABILITATION PROJECT
STOCKTON, CALIFORNIA
SEPTEMBER, 2019
1872
SEE TITLE SHEETFOR BENCHMARK
ENGINEERING PLANNING SURVEYING
CONSULTING CIVIL ENGINEERS
847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613
HHHHTTTTIIII
MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH
CCCCIIIIRRRR
No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919
EEEE
LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL
RR RREEEEGGGGIIIISSSSTTTTEEEERRRR
EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL
EEEENNNNGGGGIIIINNNNEEEEEEEERR RR
EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF
OOOORRRRNNNN
IIIIAAAA
SSSSTTTTAAAATTTT
HCSEngineering
50 years
4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com
inc.
6/10/2019 9:14:14 PM
C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt
E6
STORK GATE
SCALE: 1" = 30'-0"
STORK AREA SITE PLAN1
SCALE: 1" = 10'-0"
STORK ROAD GATE ELECTRICAL2
ELECTRICAL PLAN NOTES (STORK)
Note Number Note
1 PROVIDE EXIT LOOPS, SAFETY LOOPS, AND TRAFFIC CLEAR LOOPS FOR GATE MOTORS(TO REPLACE EXISTING LOOPS WITH THE REPLACEMENT OF THE ROAD SURFACES). TIEINTO GATE MOTORS
3 PROVIDE NEW GATE MOTOR (TO MATCH EXISTING), PROVIDE HEAVY DUTYDISCONNECT, NEMA 3R 30A FUSED. MAKE ALL CONNECTIONS (POWER, SAFETY ANDEXIT LOOPS, REMOTE CONTROL, ETC.) PROVIDE 1"C-3#10+1#10 GND FROM MOTOR TOPANEL.PROVIDE 3/4"C TO SECURITY PANEL FOR REMOTE CONTROL. SEE GATETECHNOLOGY PLAN. PROVIDE WIRE AS REQUIRED.
8 ON ALL IN-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN), FOR HIGHAND LOW CARD SCANNERS, AND KNOX BOX.) PROVIDE NEW PEDESTAL BOLT DOWNBOX TO ALLOW FOR PEDESTAL REMOVAL FOR MAINT.
9 ON ALL OUT-BOUND GATES, PROVIDE 2"C-2 SETS OF CABLES (SEE TECH PLAN), FORHIGH AND LOW CARD SCANNERS) PROVIDE NEW PEDESTAL BOLT DOWN BOX TOALLOW FOR PEDESTAL REMOVAL FOR MAINT.
12 AS AN ALTERNATE BID, PROVIDE FOR ELECTROMAGNET LOCK FOR THE GATES TO BECONTROLLED BY THE SECURITY SYSTEM, PROVIDE AN ADDITIONAL 2#12 TO THEELECTRICAL PANEL (WITH AN ADDITIONAL 20A CB IN PANEL PROVIDED BY THECONTRACTOR), THROUGH A RELAY AT THE SECURITY PANEL.
15 MOUNT NEW NEMA 3R TRANSFER SWITCH ON UNISTRUT POSTS, INTERCONNECT WITHPEDESTAL PER ONE LINE DIAGRAM.
16 PROVIDE NEW PORTABLE GENERATOR. CONNECT TO ATS WITH TWISTLOCKS ASSHOWN IN ONE LINE DIAGRAM. CONNECT TO PEDESTAL (PROVIDE NEW CIRCUITBREAKERS), FOR POWER TO BLOCK HEATER AND BATTERY CHARGER (1"C-4#10+1#10GND). GROUND GENERATOR TO INDEPEDANT 3/4"x10' GND ROD WITH #4.
DILLON & MURPHY
REV. NO.
DRAWN BY: BA
DESIGNED BY: RCS
CHECKED BY: RCS
AS BUILT BY:
SCALE: AS SHOWN BENCH MARK: EL:
JOB NO.
SHEET
OF - SHEETS
DESCRIPTION DATE
TWIC GATES2019 REHABILITATION PROJECT
STOCKTON, CALIFORNIA
SEPTEMBER, 2019
1872
SEE TITLE SHEETFOR BENCHMARK
ENGINEERING PLANNING SURVEYING
CONSULTING CIVIL ENGINEERS
847 N. CLUFF AVENUE, SUITE A2, LODI, CALIFORNIA 95240 (209) 334-6613
HHHHTTTTIIII
MMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHH
CCCCIIIIRRRR
No. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----19191919
EEEE
LLLLEEEECCCCTTTTRRRR IIII CCCCAAAALLLL
RR RREEEEGGGGIIIISSSSTTTTEEEERRRR
EEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLL
EEEENNNNGGGGIIIINNNNEEEEEEEERR RR
EEEEOOOOFFFF CCCCAAAALLLL IIIIFFFF
OOOORRRRNNNN
IIIIAAAA
SSSSTTTTAAAATTTT
HCSEngineering
50 years
4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.com
inc.
6/10/2019 9:14:14 PM
C:\Users\RichardSmith\HCS ENGINEERING\Projects - Documents\Add to 2018\DillonMurphy TWIC\TWIC GATES ELECTRICAL.rvt
E7
TECHNOLOGY PLAN