Nominal Cooling Capacity RangeR22: 139.5 kW1825 kW 119,970kcal/h1,569,500kcal/h 39.7 RT519.1 RT R407C: 130 kW1755 kW 111,800kcal/h1,509,300kcal/h 37 RT499.1 RT The HITACHI H series water-cooled water chillers are designed for all the conveniences of chilled water air-conditioning systems, especially for hotels, stores, hospitalsmodern building and process cooling applications of modern manufacturing industries. HITACHI water-cooled water chillers are equipped with newly-developed HITACHI A type semi-hermetic screw compressors, which feature higher precision and simplicity of construction by eliminating such items as pistons, connecting rods, valve plates, oil pumps and mechanical linkages for capacity controls in the reciprocating compressors. These features result in lower noise and lower vibration, reliable long period operation, and installation feasibility on any floor of the building. The units are composed of a compressor(s), a condenser(s),a direct-expansion water cooler, a electronic expansion valve(s),and auxiliary and control equipment. The units can be operated with the utmost simplicity. Twin Screw Compressor TypeHITACHI Water Cooled Water Chillers [H] SERIES— Technical Catalog I -Design Information- ModelsRCU(G)40WHYZ(-E) RCU(G)50WHYZ(-E) RCU(G)60WHYZ(-E) RCU(G)80WHYZ(-E) RCU(G)100WHYZ(-E) RCU(G)120WHYZ(-E) RCU(G)150WHYZ(-E) RCU(G)180WHYZ(-E) RCU(G)220WHYZ(-E) RCU(G)260WHYZ(-E) RCU(G)300WHYZ(-E) RCU(G)340WHYZ(-E) RCU(G)380WHYZ(-E) RCU(G)410WHYZ(-E) RCU(G)450WHYZ(-E) RCU(G)490WHYZ(-E) RCU(G)530WHYZ(-E) RCU(G)570WHYZ(-E)
Transcript

1

Nominal Cooling Capacity Range: R22: 139.5 kW~1825 kW

119,970kcal/h~1,569,500kcal/h 39.7 RT~519.1 RT

R407C: 130 kW~1755 kW 111,800kcal/h~1,509,300kcal/h

37 RT~499.1 RT

The HITACHI H series water-cooled water chillers are designed for all the conveniences of chilled water air-conditioning systems, especially for hotels, stores, hospitals、modern building and process cooling applications of modern manufacturing industries. HITACHI water-cooled water chillers are equipped with newly-developed HITACHI A type semi-hermetic screw compressors, which feature higher precision and simplicity of construction by eliminating such items as pistons, connecting

rods, valve plates, oil pumps and mechanical linkages for capacity controls in the reciprocating compressors. These features result in lower noise and lower vibration, reliable long period operation, and installation feasibility on any floor of the building. The units are composed of a compressor(s), a condenser(s),a direct-expansion water cooler, a electronic expansion valve(s),and auxiliary and control equipment. The units can be operated with the utmost simplicity.

—Twin Screw Compressor Type— HITACHI Water Cooled Water Chillers

— [H] SERIES—

Technical Catalog I -Design Information- Models:RCU(G)40WHYZ(-E)

RCU(G)50WHYZ(-E) RCU(G)60WHYZ(-E) RCU(G)80WHYZ(-E) RCU(G)100WHYZ(-E) RCU(G)120WHYZ(-E) RCU(G)150WHYZ(-E) RCU(G)180WHYZ(-E) RCU(G)220WHYZ(-E) RCU(G)260WHYZ(-E) RCU(G)300WHYZ(-E) RCU(G)340WHYZ(-E) RCU(G)380WHYZ(-E) RCU(G)410WHYZ(-E) RCU(G)450WHYZ(-E) RCU(G)490WHYZ(-E) RCU(G)530WHYZ(-E) RCU(G)570WHYZ(-E)

1

A micro-processor has been applied to the new models for following various functions. Alarm indication for each cycle by 7-segment Rotating control of compressor starting order Current limitation control Automatic start after instantaneous power failure. Remote /location switch. Communication adapter connecting the unit to BMS (Building Management System) is a optional accessory, for the details, please refer to technology catalog I.

Big colorful liquid crystal touch panel(option) Provides English and Chinese display interfaces. Message board function(for shift) Real time Information Return to factory setting Time starting function With RS485 physics connection ,communication

adapter provides communication to BMS. (Building Management System)

Inclines HITACHI Water-Cooled Water Chillers to be perfect.

FEATURES

The Combination of HITACHI Screw Compressor and Microcomputer

Micro-processor control for various functions

High Efficiency Precise Temperature Control

Various Functions

Liquid crystal screen display (Option)

Suction GasInlet

Discharged GasOutlet

Bearing

Slide Valve

Oil Separator

Motor for Compressor

Suction GasInlet

Discharged GasOutlet

Bearing

Slide Valve

Oil Separator

Motor for Compressor

English Interface

Chinese Interface

2

Easy for Maintenance Equipped with accessibility components such as Pressure Relief

Valve and Oil Sight Glass, easy maintenance is obtained.

Factory-Charged The refrigeration cycle is charged with refrigerant and sealed under the strict quality control, therefore installation and operation can be performed in a short period of time. Factory-Wires Only power wiring and water piping are required in the field. Most Reliable Protective and Ancillary Components The units are protected against any assumed failure of operation, based on the following components: Electronic Timer for Compressors, Three-Phase Quick Response Overcurrent Relay, Internal Thermostats for Compressor Motors, Freeze Protection Thermistors. Pressure Relief Valve, Oil Sight Glass, Oil Heater and Reverse-Phase Protection Relays for Compressors. Hour Meter This device indicates the operation hours of the screw compressor; therefore, accurate maintenance time can be checked with this hour meter.

Hitachi’s Semi-Hermetic Screw CompressorThe newly-developed HITACHI semi-hermetic screw compressors feature long life and quiet operation due to simplicity of construction when compared with the conventional reciprocating compressors. A Symmetrical Rotor Profile and Other Features. This profile of the compressor rotor, five-six (male and female) type, assures excellent efficiency even in high compression ranges, in addition to these uniquely-profile rotors, the following features are incorporated.

Use of special bearing, resulting in long life and high reliability Patented capacity control system, enabling simple control

system. High precision and high-grade finishing rotors, enabling no

oil-cooling system. Automatic Capacity Control An Automatic capacity control mechanism enables the unit to perform economical and energy-saving operation depending on various conditions. Additionally, two(2) independent refrigeration cycles are provided for model RCU(G)80WHYZ(-E)、RCU(G)100WHYZ(-E)、RCU(G)120WHYZ(-E)、RCU(G)220WHYZ(-E)、RCU(G)260WHYZ(-E)、RCU(G)300WHYZ(-E) 、RCU(G)340WHYZ(-E)、and RCU(G)380WHYZ(-E); Three(3) independent refrigeration cycles are provided for model RCU(G)150WHYZ(-E)、RCU(G)180WHYZ(-E)、RCU(G)410WHYZ(-E)、RCU(G)450WHYZ(-E) 、RCU(G)490WHYZ(-E)and RCU(G)530WHYZ(-E)、RCU(G)570WHYZ(-E) to avoid complete shutdown and ensure 50% of capacity provided at the less even in maintenance.

The following accessories are supplied with the unit: 1. Vibration-Proof Rubber Mats 2. Foundation Bolts

The combination of these mats and bolts effectively minimizes noise and vibration, and is coupled with facilitated installation procedures.

The following accessories are optional: 1. Communication adapter connecting the unit to BMS (Building Management System) is an optional accessory . ( LONWORKS or

RS485 option) 2. Big colorful liquid crystal screen display.( both English and Chinese can be supplied). Please get in touch with HITACHI or HITACHI distributor if required .

Lower Noise、 Lower Vibration and Reliable Long Period Operation…

FEATURES

The Hitachi Screw Water Chiller Can Meet Your Requirements!!

Standard Accessories

- 3 -

General Data (R22)

Notes: 1、The nominal cooling capacities are based on the GB/T18430.1-2007 (*1)

Chilled Water Inlet/Outlet Temperature 12/7℃ Condenser Water Inlet/Outlet Temperature 30/35℃

2、Applicable Power Supplies Main Power Source(3φ) Control Power Supplies(1φ)

380V 50Hz 220V 50Hz 415V 50Hz 240V 50Hz

3、Working range

Condense Water Outlet Temperature 22℃ to 40℃ Chilled Water Outlet Temperature 5℃ to 20℃

4. ( ) marked with *2 is available by selection switch. 5 The units greater than 220 WHYZ including 220 WHYZ consist of two modules or more

and are separately shipped(*3) 6、Communication adapter connecting the unit to BMS (Building Management System) is an

optional accessory, please get in touch with HITACHI or HITACHI distributor if required. 7、The unit with liquid crystal display differs from the unit with segment code display in electric

box , however, both have the same outer dimensions.

GE

NE

RA

L DATA

RCU40WHYZ RCU50WHYZ RCU60WHYZ RCU80WHYZ RCU100WHYZ RCU120WHYZ RCU150WHYZ RCU180WHYZ RCU220WHYZ

RCU40WHYZ -E

RCU50WHYZ -E

RCU60WHYZ -E

RCU80WHYZ -E

RCU100WHYZ -E

RCU120WHYZ -E

RCU150WHYZ -E

RCU180WHYZ -E RCU220WHYZ -E

kW 139.5 172 212.5 279 344 425 516 637 713

kcal/h 119,970 147,920 182,750 239,940 295,840 365,500 443,760 547,820 613,180

RT 39.7 48.9 60.4 79.4 97.8 120.9 146.8 181.2 202.8

m3/h 28.6 35.3 43.6 57.3 70.7 87.3 106.0 130.9 2 x 73.1

m3/h 24.0 29.6 36.5 48.0 59.2 73.1 88.7 109.5 2 x 61.3

kPa 47 51 55 42 44 48 40 54 2 x 69

kPa 50 54 58 81 73 87 74 92 2 x 106

% 100~15,(7.5) *2,0

Height mm 1,860

Width mm 2,622

Depth mm 1,922

Type —

Flow Control —

Number Of Circuits — 2

Type —

Model — 40ASCCW-Z 50ASCCW-Z 60ASCCW-Z 40ASCCW-Z 50ASCCW-Z 60ASCCW-Z 50ASCCW-Z 60ASCCW-Z 100ASCCW-Z

Quantity — 2

Inlet Rc 4 4 4

Outlet Rc 4 4 4

Inlet R 3 3 3

Outlet R 3 3 3

Height mm 2×2,150

Width mm 2×1,464

Depth mm 2×2,247

kg 1,072 1,142 1,212 1,800 1,980 2,070 3,010 3,220 2×2,726

kg 1,170 1,240 1,310 1,960 2,140 2,230 3,220 3,430 2×2,888

kW 27.0 33.5 41.5 54.0 67.0 83.0 101.0 124.0 137.0Input Power

2,960 3,320

Net Weight

Shipping Weight

Piping Connections forWater Cooler

Shipping*3

1,747 1,765

1,898

With φ142 Inner Diameter Companion Flange

1,998

1,146 1,250 1,358

Safety Devices Three-Phase Overcurrent Relay, High-Pressure Switch, Low-Pressure Switch, Oil Heater, Internal Thermostat for Compressor Motor, Freeze Protection Thermistor, Reverse PhaseProtection Relay, Discharge Gas Thermostat, Operation Hour-Meter and Pressure Relief Valve.

Piping Connections forCondenser

Withφ78 Inner Diameter Companion Flange With φ142 Inner Diameter CompanionFlange

2 x With φ116 Inner DiameterCompanion FlangeWithφ78 Inner Diameter Companion Flange

Condenser Shell-and-Tube Type

Water Cooler Shell-and-Tube Type,Dry Expansion Type

Compressor

Semi-Hermetic Screw Type

1 2 3

Refrigerant

R22

Electronic Expansion Valve

1 2 3

Outer Dimensions

1,506 1,495 1,685

950 1,070 1,220

1,764 2,759 3,170

Continuous Capacity Control

100~15,0 100~15,(7.5)*2,0 100~15,(5) *2,0

2 x With φ142 Inner DiameterCompanion Flange

ModelStandard

Liquid Crystal Display

Nominal Cooling Capacity*1

Condenser Water Flow Rate

Chilled Water Flow Rate

Condenser Pressure Drop

Water Cooler Pressure Drop

Cooling Capacity Control

3

- 4 -

General Data (R22)

Notes: 1、The nominal cooling capacities are based on the GB/T18430.1-2007 (*1)

Chilled Water Inlet/Outlet Temperature 12/7℃ Condenser Water Inlet/Outlet Temperature 30/35℃

2、Applicable Power Supplies Main Power Source(3φ) Control Power Supplies(1φ)

380V 50Hz 220V 50Hz 415V 50Hz 240V 50Hz

3、Working range

Condense Water Outlet Temperature 22℃ to 40℃ Chilled Water Outlet Temperature 5℃ to 20℃

4. ( ) marked with *2 is available by selection switch. 5 The units greater than 220 WHYZ including 220 WHYZ consist of two modules or more

and are separately shipped(*3) 6、Communication adapter connecting the unit to BMS (Building Management System) is an

optional accessory, please get in touch with HITACHI or HITACHI distributor if required. 7、The unit with liquid crystal display differs from the unit with segment code display in electric

box , however, both have the same outer dimensions.

RCU260WHYZ RCU300WHYZ RCU340WHYZ RCU380WHYZ RCU410WHYZ RCU450WHYZ RCU490WHYZ RCU530WHYZ RCU570WHYZRCU260WHYZ

-ERCU300WHYZ

-ERCU340WHYZ

-ERCU380WHYZ

-ERCU410WHYZ

-ERCU450WHYZ

-ERCU490WHYZ

-ERCU530WHYZ

-ERCU570WHYZ

-EkW 842 971 1,094 1,217 1,328 1,457 1,579 1,703 1,825

kcal/h 724,120 835,060 940,840 1,046,620 1,142,080 1,253,020 1,357,940 1,464,580 1,569,500RT 239.5 276.2 311.1 346.1 377.7 414.4 449.1 484.4 519.1

Condenser Water Flow Rate(No.1/No.2/No.3) m3/h 99.6 / 73.1 2 x 99.6 124.8 / 99.6 2 x 124.8 99.6 / 99.6 / 73.1 3 x 99.6 124.8 / 99.6 / 99.6 124.8 / 124.8 / 99.6 3 x 124.8

m3/h 83.5 / 61.3 2 x 83.5 104.6 / 83.5 2 x 104.6 83.5 / 83.5 / 61.3 3 x 83.5 104.6 / 83.5 / 83.5 104.6 / 104.6 / 83.5 3 x 104.6kPa 55 / 69 2 x 55 70 / 55 2 x 70 55 / 55 / 69 3 x 55 70 / 55 / 55 70 / 70 / 55 3 x 70

Water Cooler Pressure Drop(No.1/No.2/No.3) kPa 83 / 106 2 x 83 93 / 83 2 x 93 83 / 83 / 106 3 x 83 93 / 83 / 83 93 / 93 / 83 3 x 93—%

Height mmWidth mmDepth mmType —

Flow Control —Number Of Circuits —

Type —

Model(No.1/No.2/No.3) — 130/100ASCCW-Z

130/130ASCCW-Z

170 /130ASCCW-Z

170/170ASCCW-Z

130/130/100ASCCW-Z

130/130/130ASCCW-Z

170/130/130ASCCW-Z

170/170/130ASCCW-Z

170/170/170ASCCW-Z

Quantity —

——

Inlet —Outlet —Inlet —

Outlet —Height mmWidth mmDepth mm

kg 2,858 / 2,726 2,858 / 2,858 2,988 / 2,858 2 x 2,988 2,858 / 2,858 / 2,726 3 x 2,858 2,988 /2,858 / 2,858 2,988 / 2,988 /2,858 3 x 2,988kg 3,020 / 2,888 3,020 / 3,020 3,150/ 3,020 2 x 3,150 3,020 / 3,020 / 2,888 3 x 3,020 3,150 /3,020 / 3,020 3,150 / 3,150 / 3,020 3 x 3,150kW 162.0 187.0 211.0 234.0 256.0 280.0 304.0 328.0 351.0

3 x Withφ142 Inner Diameter Companion Flange3 x Withφ142 Inner Diameter Companion Flange

2 x Withφ142 Inner Diameter Companion Flange

ModelStandard

Liquid Crystal Display

Nominal Cooling Capacity*1

Chilled Water Flow Rate(No.1/No.2/No.3)Condenser Pressure Drop(No.1/No.2/No.3)

Cooling Capacity ControlContinuous Capacity Control

100~15,(7.5)*2,0 100~15,(5) *2,0

Outer Dimensions1,879 1,8792,622 3,9831,922 1,922

RefrigerantR22

Electronic Expansion Valve2 3

Compressor

Semi-Hermetic Screw Type

2 3

Condenser Shell-and-Tube TypeWater Cooler Shell-and-Tube Type,Dry Expansion Type

2×2,247 3×2,247

Safety Devices Three-Phase Overcurrent Relay, High-Pressure Switch, Low-Pressure Switch, Oil Heater, Internal Thermostat for Compressor Motor, Freeze Protection Thermistor, Reverse PhaseProtection Relay, Discharge Gas Thermostat, Operation Hour-Meter and Pressure Relief Valve.

Piping Connections forCondenser

2 x Withφ116 Inner Diameter Companion Flange2 x Withφ116 Inner Diameter Companion Flange

2 x Withφ142 Inner Diameter Companion Flange

3 x Withφ116 Inner Diameter Companion Flange3 x Withφ116 Inner Diameter Companion Flange

2×2,150 3×2,1502×1,464 3×1,464

Net Weight(No.1/No.2/No.3)

Shipping Weight*3(No.1/No.2/No.3)Input Power

Piping Connections forWater Cooler

Shipping*3

GE

NE

RA

L DATA

4

- 5 -

General Data (R407C)

Notes: 1、The nominal cooling capacities are based on the GB/T18430.1-2007 (*1)

Chilled Water Inlet/Outlet Temperature 12/7℃ Condenser Water Inlet/Outlet Temperature 30/35℃

2、Applicable Power Supplies Main Power Source(3φ) Control Power Supplies(1φ)

380V 50Hz 220V 50Hz 415V 50Hz 240V 50Hz

3、Working range Condense Water Outlet Temperature 22℃ to 37℃

Chilled Water Outlet Temperature 5℃ to 20℃

4. ( ) marked with *2 is available by selection switch. 5 The units greater than 220 WHYZ including 220 WHYZ consist of two modules or more

and are separately shipped(*3) 6、Communication adapter connecting the unit to BMS (Building Management System) is an

optional accessory, please get in touch with HITACHI or HITACHI distributor if required. 7、The unit with liquid crystal display differs from the unit with segment code display in electric

box , however, both have the same outer dimensions.

RCUG40WHYZ RCUG50WHYZ RCUG60WHYZ RCUG80WHYZ RCUG100WHYZ RCUG120WHYZ RCUG150WHYZ RCUG180WHYZ RCUG220WHYZ

RCUG40WHYZ -E

RCUG50WHYZ -E

RCUG60WHYZ -E

RCUG80WHYZ -E

RCUG100WHYZ-E

RCUG120WHYZ-E

RCUG150WHYZ-E

RCUG180WHYZ -E

RCUG220WHYZ -E

kW 130 162 197 260 324 394 486 591 688kcal/h 111,800 139,320 169,420 223,600 278,640 338,840 417,960 508,260 591,680

RT 37.0 46.1 56.0 73.9 92.2 112.1 138.2 168.1 195.7

m3/h 27.4 34.2 41.5 54.9 68.3 82.9 102.4 124.4 2 x 71.7

m3/h 22.4 27.9 33.9 44.7 55.7 67.8 83.6 101.6 2 x 59.2kPa 43 50 39 40 41 44 38 49 2 x 68kPa 44 50 71 33 65 75 66 80 2 x 100—% 100~15,(7.5) *2,0

Height mm 1,860Width mm 2,622Depth mm 1,922Type —

Flow Control —Number Of Circuits — 2

Type —Model — 40ASCCW-Z 50ASCCW-Z 60ASCCW-Z 40ASCCW-Z 50ASCCW-Z 60ASCCW-Z 50ASCCW-Z 60ASCCW-Z 100ASCCW-Z

Quantity — 2——

Inlet Rc 4 4 4

Outlet Rc 4 4 4

Inlet R 3 3 3Outlet R 3 3 3Height mm 2×2,150Width mm 2×1,464Depth mm 2×2,247

kg 1,072 1,142 1,212 1,800 1,980 2,070 3,010 3,220 2×2,726kg 1,170 1,240 1,310 1,960 2,140 2,230 3,220 3,430 2×2,888kW 29.5 36.7 44.3 59.1 73.1 88.1 109.7 132.4 146.1

ModelStandard

Liquid Crystal Display

Nominal Cooling Capacity*1

Condenser Water Flow RateChilled Water Flow Rate

Condenser Pressure DropWater Cooler Pressure Drop

Cooling Capacity ControlContinuous Capacity Control

100~15,0 100~15,(7.5)*2,0 100~15,(5) *2,0

Outer Dimensions1,506 1,495 1,685950 1,070 1,220

1,764 2,759 3,170

RefrigerantR407C

Electronic Expansion Valve1 2 3

CompressorSemi-Hermetic Screw Type

1 2 3

Safety Devices Three-Phase Overcurrent Relay, High-Pressure Switch, Low-Pressure Switch, Oil Heater, Internal Thermostat for Compressor Motor, Freeze Protection Thermistor, Reverse PhaseProtection Relay, Discharge Gas Thermostat, Operation Hour-Meter and Pressure Relief Valve.

Piping Connectionsfor Condenser

Withφ78 Inner Diameter Companion Flange With φ142 Inner Diameter CompanionFlange

2 x With φ116 Inner DiameterCompanion FlangeWithφ78 Inner Diameter Companion Flange

Condenser Shell-and-Tube TypeWater Cooler Shell-and-Tube,Dry Expansion Valve

2 x With φ142 Inner DiameterCompanion Flange

Shipping*3

1,747 1,765 1,9981,146 1,250 1,358

3,320

Piping Connectionsfor Water Cooler With φ142 Inner Diameter Companion Flange

Input Power

1,898 2,960Net Weight

Shipping Weight*3

GE

NE

RA

L DATA

5

6

General Data (R407C)

Notes: 1、The nominal cooling capacities are based on the GB/T18430.1-2007 (*1)

Chilled Water Inlet/Outlet Temperature 12/7℃ Condenser Water Inlet/Outlet Temperature 30/35℃

2、Applicable Power Supplies Main Power Source(3φ) Control Power Supplies(1φ)

380V 50Hz 220V 50Hz 415V 50Hz 240V 50Hz

3、Working range Condense Water Outlet Temperature 22℃ to37℃

Chilled Water Outlet Temperature 5℃ to 20℃

4. ( ) marked with *2 is available by selection switch. 5 The units greater than 220 WHYZ including 220 WHYZ consist of two modules or more

and are separately shipped(*3) 6、Communication adapter connecting the unit to BMS (Building Management System) is an

optional accessory, please get in touch with HITACHI or HITACHI distributor if required. 7、The unit with liquid crystal display differs from the unit with segment code display in electric

box , however, both have the same outer dimensions.

RCUG260WHYZ RCUG300WHYZ RCUG340WHYZ RCUG380WHYZ RCUG410WHYZ RCUG450WHYZ RCUG490WHYZ RCUG530WHYZ RCUG570WHYZ

RCUG260WHYZ-E

RCUG300WHYZ-E

RCUG340WHYZ-E

RCUG380WHYZ-E

RCUG410WHYZ-E

RCUG450WHYZ-E RCUG490WHYZ -E RCUG530WHYZ

-ERCUG570WHYZ

-EkW 820 952 1,061 1,170 1,296 1,428 1,537 1,646 1,755

kcal/h 705,200 818,720 912,460 1,006,200 1,114,560 1,228,080 1,321,820 1,415,560 1,509,300RT 233.2 270.8 301.8 332.8 368.6 406.1 437.1 468.1 499.1

Condenser Water Flow Rate(No.1/No.2/No.3) m3/h 99.2 / 71.7 2 x 99.2 121.8 / 99.2 2 x 121.8 99.1 / 99.1 / 71.7 3 x 99.1 121.8 / 99.1 / 99.1 121.8 / 121.8 / 99.1 3 x 121.8

m3/h 81.9 / 59.2 2 x 81.9 100.6 / 81.9 2 x 100.6 81.8 / 81.8 / 59.2 3 x 81.8 100.6 / 81.8 / 81.8 100.6 / 100.6 / 81.8 3 x 100.6kPa 55 / 68 2 x 55 68 / 55 2 x 68 55 / 55 / 68 3 x 55 68 / 55 / 55 68 / 68 / 55 3 x 68

Water Cooler Pressure Drop(No.1/No.2/No.3) kPa 80 / 100 2 x 80 87 / 80 2 x 87 80 / 80 / 100 3 x 80 87 / 80 / 80 87 / 87 / 80 3 x 87—%

Height mmWidth mmDepth mmType —

Flow Control —Number Of Circuits —

Type —

Model(No.1/No.2/No.3) — 130/100ASCCW-Z 130/130ASCCW-Z 170 /130ASCCW-Z 170/170ASCCW-Z 130/130/100

ASCCW-Z130/130/130ASCCW-Z

170/130/130ASCCW-Z

170/170/130ASCCW-Z

170/170/170ASCCW-Z

Quantity ———

Inlet —Outlet —Inlet —

Outlet —Height mmWidth mmDepth mm

kg 2,858 / 2,726 2,858 / 2,858 2,988 / 2,858 2 x 2,988 2,858 / 2,858 / 2,726 3 x 2,858 2,988 /2,858 / 2,858 2,988 / 2,988 /2,858 3 x 2,988

kg 3,020 / 2,888 3,020 / 3,020 3,150/ 3,020 2 x 3,150 3,020 / 3,020 / 2,888 3 x 3,020 3,150 /3,020 / 3,020 3,150 / 3,150 / 3,020 3 x 3,150

kW 174.1 201.7 224.3 246.3 275.2 302 324.9 348 369.5

Chilled Water Flow Rate(No.1/No.2/No.3)Condenser Pressure Drop(No.1/No.2/No.3)

ModelStandard

Liquid Crystal Display

Nominal Cooling Capacity*1

Cooling Capacity ControlContinuous Capacity Control

100~15,(7.5)*2,0 100~15,(5) *2,0

Outer Dimensions1,879 1,8792,622 3,9831,922 1,922

RefrigerantR407C

Electronic Expansion Valve2 3

Compressor

Semi-Hermetic Screw Type

2 3Condenser Shell-and-Tube Type

Water Cooler Shell-and-Tube,Dry Expansion Type

Safety Devices Three-Phase Overcurrent Relay, High-Pressure Switch, Low-Pressure Switch, Oil Heater, Internal Thermostat for Compressor Motor, Freeze Protection Thermistor, Reverse PhaseProtection Relay, Discharge Gas Thermostat, Operation Hour-Meter and Pressure Relief Valve.

Piping Connectionsfor Condenser

2 x Withφ116 Inner Diameter Companion Flange 3 x Withφ116 Inner Diameter Companion Flange2 x Withφ116 Inner Diameter Companion Flange 3 x Withφ116 Inner Diameter Companion Flange

Piping Connectionsfor Water Cooler

2 x Withφ142 Inner Diameter Companion Flange 3 x Withφ142 Inner Diameter Companion Flange2 x Withφ142 Inner Diameter Companion Flange 3 x Withφ142 Inner Diameter Companion Flange

3×1,464

Net Weight(No.1/No.2/No.3)

Shipping Weight*3(No.1/No.2/No.3)Input Power

Shipping*3

2×2,247 3×2,247

2×2,150 3×2,1502×1,464

GE

NE

RA

L DATA

6

7

RCU(G)40、50、60 WHYZ(-E) RCU(G)80、100、120WHYZ(-E)

NOTE:

For RCU80,100,120WHYZ(-E) and RCUG80,100,120WHYZ(-E)

The unit with the refrigerant R22 (RCU-) differs from the unit with R407C (RCUG-) in the location of the refrigerant inlet of

condenser , however, both have the same outer dimensions.

DIMENSIONAL DATA

8

RCU(G)150、180 WHYZ(-E)

Note: The unit with the refrigerant R22 (RCU-) differs from the unit with R407C(RCUG-) in the location of the refrigerant inlet of

condenser, however, both have the same outer dimensions.

RCU(G)220WHYZ(-E) Note: The R22(RCU-) and R407C (RCUG)units have the same outer dimensions and installation dimension .

DIMENSIONAL DATA

View from PNo.1 cycle No.2 cycle

( ) ( )

Front Face of Unit)P

( )

9

RCU(G)260、300、340、380WHYZ(-E)

Note: The R22 (RCU-)and R407C (RCUG-)units have the same outer dimensions and installation dimension .

RCU(G)410、450、490、530、570 WHYZ(-E) Note: The R22 (RCU-)and R407C (RCUG-)units have the same outer dimensions and installation dimension .

DIMENSIONAL DATA

No.1 cycle

View from P

Front Face of Unit)P

No.2 cycle No.3 cycle

PFront Face of Unit)

View from PNo.2 cycleNo.1 cycle

10

Operation Space

Note: * Rear side operation space

depends on connection of field-piping

Weight Distribution (kg) Center of Gravity (mm) Location Location Model

1 2 3 4 A B

Operation Weight (kg)

RCU (G)40 WHYZ(-E) 281 255 346 320 811 523 1202 RCU (G)50 WHYZ(-E) 289 259 370 340 811 523 1258 RCU (G)60 WHYZ(-E) 306 276 386 356 811 523 1324 RCU(G)80 WHYZ(-E) 545 446 576 468 1373 645 2035 RCU(G)100WHYZ(-E) 572 461 662 510 1373 645 2205 RCU(G)120WHYZ(-E) 588 489 678 528 1373 645 2283 RCU(G)150WHYZ(-E) 906 816 836 765 1496 540 3323 RCU(G)180WHYZ(-E) 964 864 894 823 1496 540 3545 RCU(G)220WHYZ(-E)-1,2 RCU(G)260WHYZ(-E)-2 ; RCU(G)410WHYZ(-E)-3

764 708 724 692 602 975 2888

RCU(G)260WHYZ(-E)-1 RCU(G)300WHYZ(-E)-1,2 RCU(G)340WHYZ(-E)-2 RCU(G)410WHYZ(-E)-1,2 RCU(G)450WHYZ(-E)-1,2,3; RCU(G)490WHYZ(-E)-2 , 3 ; RCU(G)530WHYZ(-E)-3

823 762 778 744 602 975 3107

RCU(G)340WHYZ(-E)-1; RCU(G)380WHYZ(-E)-1,2 RCU(G)490WHYZ(-E)-1; RCU(G)530WHYZ(-E)-1,2 RCU(G)570WHYZ(-E)-1,2,3

853 789 809 777 602 975 3228

Dimension(mm) Dimension(mm) Model

A B C D Mode

A B C D

RCU(G)40WHYZ(-E) 1200 600 600 600 RCU(G)260WHYZ(-E) 1200 600 600 1500

RCU(G)50 WHYZ(-E) 1200 600 600 600 RCU(G)300 WHYZ(-E) 1200 600 600 1500

RCU(G)60 WHYZ(-E) 1200 600 600 600 RCU(G)340 WHYZ(-E) 1200 600 600 1500

RCU(G)80 WHYZ(-E) 1200 600 600 600 RCU(G)380 WHYZ(-E) 1200 600 600 1500

RCU(G)100 WHYZ(-E) 1200 600 600 600 RCU(G)410 WHYZ(-E) 1200 600 600 1500

RCU(G)120 WHYZ(-E) 1200 600 600 600 RCU(G)450 WHYZ(-E) 1200 600 600 1500

RCU(G)190 WHYZ(-E) 1200 600 600 600 RCU(G)490 WHYZ(-E) 1200 600 600 1500

RCU(G)180 WHYZ(-E) 1200 600 600 600 RCU(G)530 WHYZ(-E) 1200 600 600 1500

RCU(G)220 WHYZ(-E) 1200 600 600 1500 RCU(G)570WHYZ(-E) 1200 600 600 1500

Dimensions(mm) Dimensions(mm) Model

L1 L2 L3 L4 L5 L6 L7 Model

L1 L2 L3 L4 L5 L6 L7

RCU(G)40 WHYZ(-E)

300 58 25 150 70 35 17 RCU(G)260 WHYZ(-E)

300 58 38 150 100 50 27

RCU(G)50

WHYZ(-E) 300 58 25 150 70 35 17

RCU(G)300

WHYZ(-E) 300 58 38 150 100 50 27

RCU(G)60

WHYZ(-E) 300 58 25 150 70 35 17

RCU(G)340

WHYZ(-E) 300 58 38 150 100 50 27

RCU(G)80 WHYZ(-E)

300 58 25 150 70 35 17 RCU(G)380 WHYZ(-E)

300 58 38 150 100 50 27

RCU(G)100

WHYZ(-E) 300 58 25 150 70 35 17

RCU(G)410

WHYZ(-E) 300 58 38 150 100 50 27

RCU(G)120

WHYZ(-E) 300 58 25 150 70 35 17

RCU(G)450

WHYZ(-E) 300 58 38 150 100 50 27

RCU(G)150 WHYZ(-E)

300 58 25 230 70 35 17 RCU(G)490 WHYZ(-E)

300 58 38 150 100 50 27

RCU(G)180

WHYZ(-E) 300 58 25 230 70 35 17

RCU(G)530

WHYZ(-E) 300 58 38 150 100 50 27

RCU(G)220

WHYZ(-E) 300 58 38 150 100 50 27

RCU(G)570

WHYZ(-E) 300 58 38 150 100 50 27

Weight Balance 、Center of Gravity and Operation Weight

Foundation Bolt and Rubber Mat

O: Location of Foundation Bolt

Rear Side of Unit Base

2

3

4

Front Face of Unit

A B

Center of gravity1

SELECTION DATA

DB

C

A

Rubber Bushing (with Holes)

11

The Field Piping Connection Fig. for RCU(G)220~380WHYZ(-E)

The Field Piping Connection Fig. for RCU(G)410~570WHYZ(-E)

SELECTION DATA

Chilled Water Outlet(With 269mm Flange)(With 269mm Flange)

Condenser Water Outlet

Hitachi StandardField Supplied

(With 269mm Flange)

(With 269mm Flange)Condenser Water Inlet

Chilled Water Inlet

NOTES:(1)The Piping Connection above-mentioned is suitable for the units of RCU(G)410-570WHYZ(-E) and just for reference . (2)Support the water pipes with stay not to give the weight of water pipes directly to the unit,if not, a severe damage may occur due to excessive weight of the piping side, specially while the unit is running .

Chilled Water Outlet(With 269mm Flange)(With 269mm Flange)

Condenser Water Outlet

Hitachi StandardField Supplied

(With 269mm Flange)

(With 269mm Flange)Condenser Water Inlet

Chilled Water Inlet

NOTES:(1)The Piping Connection above-mentioned is suitable for the units of RCU(G)410-570WHYZ(-E) and just for reference . (2)Support the water pipes with stay not to give the weight of water pipes directly to the unit,if not, a severe damage may occur due to excessive weight of the piping side, specially while the unit is running .

12

1.Determination the System Requirements.

Calculate the total Load under design conditions. Given conditions: Power Source Frequency 50Hz Cooling Load 420kW (361,200kcal/h) Condenser Water Inlet Temperature 30℃ Condenser Water Outlet Temperature 35℃ Chilled Water Inlet Temperature 12℃ Chilled Water Outlet Temperature 7℃ Fouling Factor of Water Cooler 0.018m2.℃/kW Fouling Factor of Condenser 0.044m2. ℃/kW

2.Select a Matching Model and Read Performance of the Unit

Select unit model RCU120WHYZ(-E) ,according to the conditions mentioned above :condenser water outlet temperature (CDOT) of 35℃ and chilled water outlet temperature (CLOT) of 7℃.

3.Read the Unit Performance of the Model.

The compressor Input (IPT), cooling capacity (CCAP),Chilled water flow rate (CFR), condenser flow rate (HFR) can directly be determined from the table and the figure. In the case where the data cannot directly be determined from the table, the data can be determined by interpolation. Compressor Input (IPT) 82.5kW Cooling Capacity(CCAP)

425kW (365,500 kcal/h) Chilled Water Flow Rate (CFR) 73.1m3/h Cooled Water Flow Rate (HFR) 87.3 m3/h Condenser Heat Discharge.(HCAP) 508 kW Cooler Pressure Drop (CPD) 87 kPa Condenser Pressure Drop (HPD) 48 kPa

4.Correct the Data

Flow Rate When the water temperature difference of condenser or water cooler is different from 5℃, please correct the water flow rater of condenser or water cooler by following formulas.

Corrected Flow = × Rate

or

Corrected Flow= × Rate

Cooling Capacity and Compressor Input When fouling factors are different from 0.018m2. ℃/kW(cooler) and 0.44 m2.℃/kW(condenser) ,the cooling capacity and compressor input will also be different from the value indicated in the cooling capacity table.

The correction formulas are as follow:

= ×

and = ×

Fouling Factor

m2. ℃/kW

Cooling Capacity

Compressor Input

Water Cooler 0.000 0.018

1.01 1.00

1.00 1.00

Condenser 0.000 0.044 0.086

1.01 1.00 0.99

0.99 1.00 1.01

5℃

Given Temperature Difference (℃)

Flow Rate From the Table

Water Flow Factor

Flow Rate from the Table

Corrected Cooling Capacity

Correction Factor

Cooling Capacity Indicated in Table

Corrected Compressor Input

Correction Factor

Compressor Input indicated in Table

Correction Factor for Cooling Capacity and Compressor Input Regarding Fouling Factor

Selection Example SELECTION DATA

13

SE

LEC

TION

DATA

13

14

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃)

HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h)

CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa)

Note:

1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser.

2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data”

Conversion Multiplier: 1kW = 860kcal/h = 3412Btu/h

1kPa = 0.102mAq

IPT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD5 19.4 146 25.1 55 166 28.5 46 21.2 136 23.4 48 157 27.1 426 19.7 151 25.9 58 170 29.3 49 21.5 140 24.1 51 162 27.8 457 20.0 154 26.6 60 174 30.0 51 21.8 144 24.8 53 166 28.5 478 20.3 159 27.3 64 179 30.8 54 22.2 148 25.5 56 170 29.3 499 20.5 163 28.0 67 183 31.5 56 22.4 152 26.1 58 174 29.9 51

10 20.8 167 28.7 70 188 32.3 59 22.7 156 26.8 61 179 30.7 5311 21.1 171 29.4 73 192 33.0 61 23.0 159 27.4 64 182 31.4 565 21.1 143 24.6 52 164 28.2 46 23.0 133 22.9 46 156 26.8 426 21.3 147 25.2 55 168 28.9 48 23.3 137 23.5 48 160 27.5 447 21.6 151 26.0 58 173 29.7 50 23.6 141 24.2 51 164 28.3 468 21.9 155 26.7 61 177 30.4 52 23.9 144 24.8 53 168 29.0 489 22.1 159 27.4 64 182 31.2 55 24.2 149 25.5 56 173 29.7 50

10 22.4 163 28.1 67 186 31.9 57 24.5 152 26.2 59 177 30.4 5211 22.7 168 28.8 70 190 32.7 60 24.8 156 26.9 62 181 31.1 555 23.8 136 23.4 48 160 27.5 44 26.0 127 21.8 42 153 26.3 406 24.0 141 24.2 51 165 28.3 46 26.2 131 22.5 45 157 27.0 427 24.3 144 24.8 53 169 29.0 48 26.6 135 23.2 47 161 27.7 448 24.6 149 25.6 57 173 29.8 51 26.9 139 23.9 50 166 28.5 469 24.8 153 26.3 59 178 30.5 53 27.1 142 24.5 52 170 29.1 49

10 25.1 157 27.0 62 182 31.4 56 27.4 147 25.2 55 174 29.9 5111 25.4 161 27.7 65 186 32.1 58 27.7 150 25.8 57 178 30.6 535 26.5 130 22.4 44 157 26.9 42 28.9 121 20.8 39 150 25.8 396 26.7 135 23.1 47 161 27.7 44 29.2 125 21.6 41 155 26.6 417 27.0 139.5 24.0 50 167 28.6 47 29.5 130 22.4 44 160 27.4 438 27.3 143 24.6 52 170 29.3 49 29.8 133 22.9 46 163 28.0 459 27.5 147 25.2 55 174 30.0 51 30.1 137 23.5 48 167 28.7 47

10 27.8 151 26.0 58 179 30.8 54 30.4 141 24.2 51 171 29.4 4911 28.1 155 26.7 61 183 31.5 56 30.7 144 24.8 53 175 30.1 525 27.5 128 22.0 43 155 26.7 41 30.1 119 20.5 37 149 25.7 386 27.8 132 22.7 45 160 27.4 43 30.4 123 21.1 40 153 26.3 407 28.1 136 23.4 48 164 28.2 46 30.7 127 21.8 42 158 27.1 428 28.4 140 24.1 50 168 29.0 48 31.0 131 22.4 44 162 27.8 449 28.6 144 24.8 53 173 29.8 50 31.3 135 23.2 47 166 28.5 47

10 28.9 148 25.5 56 177 30.5 53 31.6 138 23.8 49 170 29.2 4911 29.2 153 26.3 59 182 31.3 55 31.9 142 24.5 52 174 30.0 515 27.8 127 21.8 42 154 26.6 416 28.1 130 22.4 44 158 27.2 437 28.4 135 23.2 47 163 28.1 458 28.6 138 23.8 49 167 28.7 479 28.9 143 24.6 53 172 29.6 50

10 29.2 147 25.2 55 176 30.2 5211 29.5 151 26.0 58 181 31.1 55

IPT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD5 24.1 181 31.1 59 205 35.2 51 26.5 170 29.3 53 197 33.8 476 24.5 186 31.9 62 210 36.1 53 26.8 175 30.1 56 202 34.7 497 24.8 191 32.9 66 216 37.1 56 27.2 180 31.0 59 207 35.6 528 25.2 196 33.7 69 221 38.1 59 27.6 185 31.8 62 212 36.5 549 25.5 201 34.6 72 227 39.0 61 28.0 189 32.6 64 217 37.4 57

10 25.8 207 35.5 76 232 40.0 64 28.3 195 33.4 68 223 38.3 5911 26.2 211 36.4 79 238 40.9 67 28.7 199 34.2 71 228 39.2 625 26.2 176 30.2 56 202 34.7 50 28.7 166 28.5 50 194 33.4 466 26.5 181 31.2 60 208 35.7 52 29.0 171 29.4 53 200 34.4 497 26.8 186 32.0 63 213 36.6 55 29.4 175 30.2 56 205 35.2 518 27.2 191 32.9 66 218 37.5 57 29.8 180 31.0 59 210 36.1 539 27.5 197 33.8 69 224 38.5 60 30.1 185 31.9 62 215 37.0 56

10 27.8 202 34.7 72 229 39.5 63 30.5 190 32.7 65 220 37.9 5811 28.2 207 35.6 76 235 40.5 66 30.9 195 33.5 68 226 38.8 615 29.5 168 28.9 52 198 34.0 48 32.4 158 27.2 46 191 32.8 456 29.9 174 29.9 55 204 35.0 50 32.7 164 28.1 49 196 33.8 477 30.2 179 30.7 58 209 35.9 53 33.1 168 28.9 52 201 34.6 498 30.5 184 31.6 61 214 36.8 55 33.4 173 29.7 54 206 35.5 529 30.9 189 32.5 64 220 37.8 58 33.8 178 30.6 58 212 36.4 54

10 31.2 194 33.3 67 225 38.7 61 34.2 183 31.4 60 217 37.3 5711 31.5 199 34.2 71 230 39.6 63 34.5 187 32.2 63 222 38.1 595 32.9 160 27.6 48 193 33.3 46 36.0 151 26.0 43 187 32.2 436 33.2 166 28.5 51 199 34.3 48 36.4 156 26.9 45 193 33.1 457 33.5 172 29.6 54 206 35.3 51 36.8 162 27.9 48 199 34.2 488 33.9 176 30.2 56 210 36.1 53 37.1 166 28.5 50 203 34.9 509 34.2 181 31.2 60 216 37.1 56 37.5 171 29.4 53 208 35.8 52

10 34.5 186 32.0 63 221 38.0 58 37.8 175 30.2 56 213 36.7 5511 34.9 191 32.9 66 226 38.9 61 38.2 180 31.0 59 218 37.5 575 34.2 158 27.1 46 192 33.0 45 37.5 149 25.6 41 186 32.0 436 34.5 163 28.0 49 197 33.9 47 37.8 153 26.4 44 191 32.9 457 34.9 168 28.8 51 202 34.8 50 38.2 158 27.1 46 196 33.7 478 35.2 173 29.8 55 208 35.8 53 38.6 163 28.0 49 202 34.7 499 35.6 178 30.6 58 214 36.7 55 39.0 168 28.8 52 207 35.5 52

10 35.9 183 31.5 61 219 37.6 58 39.3 172 29.6 54 212 36.4 5411 36.2 188 32.4 64 225 38.6 60 39.7 177 30.5 57 217 37.3 575 34.6 156 26.8 45 191 32.8 456 34.9 161 27.7 48 196 33.7 477 35.2 166 28.5 50 201 34.6 498 35.6 171 29.5 54 207 35.6 529 35.9 176 30.3 56 212 36.5 54

10 36.3 181 31.2 60 218 37.4 5711 36.6 186 32.1 63 223 38.4 60

CDOT CLOTRCU40WHYZ(-E) RCUG40WHYZ(-E)

22

25

30

35

40

22

25

30

35

RCUG50WHYZ(-E)RCU50WHYZ(-E)

Cooling Capacities

37

37

40

CDOT CLOT

SELECTION DATA

15

SELECTION DATA

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃)

HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h)

CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa)

Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser.

2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data”

Conversion Multiplier: 1kW = 860kcal/h = 3412Btu/h 1kPa = 0.102mA

IPT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD5 29.7 223 38.4 63 253 43.5 55 31.9 207 35.6 55 239 41.0 496 30.1 229 39.4 67 259 44.6 57 32.3 213 36.5 58 245 42.1 527 30.5 235 40.5 70 266 45.7 60 32.7 218 37.5 61 251 43.2 548 31.0 242 41.6 74 273 47.0 63 33.2 224 38.6 64 258 44.3 579 31.4 248 42.7 78 280 48.1 65 33.6 230 39.6 67 264 45.4 59

10 31.8 254 43.7 82 286 49.2 68 34.1 236 40.5 71 270 46.4 6111 32.2 261 44.9 86 293 50.4 71 34.5 242 41.6 74 276 47.5 645 32.2 217 37.3 60 249 42.8 53 34.5 201 34.6 52 236 40.5 486 32.6 224 38.5 64 256 44.1 56 35.0 207 35.7 55 242 41.7 517 33.0 230 39.5 67 263 45.2 59 35.4 213 36.6 58 248 42.7 538 33.4 236 40.6 71 269 46.3 61 35.9 219 37.6 61 255 43.8 559 33.8 243 41.7 75 276 47.5 64 36.3 225 38.7 64 261 44.9 58

10 34.3 249 42.8 78 283 48.7 67 36.8 231 39.7 68 267 46.0 6011 34.7 255 43.8 82 290 49.8 70 37.2 236 40.6 71 273 47.0 635 36.3 207 35.7 55 244 41.9 51 38.9 192 33.1 48 231 39.8 476 36.7 214 36.8 59 251 43.1 54 39.4 199 34.1 51 238 40.9 497 37.1 220 37.9 62 257 44.3 57 39.8 204 35.1 54 244 42.0 518 37.6 226 38.9 65 264 45.4 59 40.3 210 36.1 57 250 43.0 549 38.0 233 40.1 69 271 46.6 62 40.7 216 37.2 60 257 44.2 56

10 38.4 239 41.1 73 278 47.7 65 41.2 222 38.1 63 263 45.2 5911 38.8 245 42.2 76 284 48.9 67 41.6 228 39.1 66 269 46.3 615 40.4 198 34.0 51 238 41.0 49 43.4 184 31.6 44 227 39.0 456 40.9 205 35.2 54 246 42.2 52 43.8 190 32.6 47 234 40.2 487 41.3 212.5 36.5 58 254 43.6 55 44.2 197 33.9 50 241 41.5 508 41.7 217 37.3 60 259 44.5 57 44.7 201 34.6 52 246 42.3 529 42.1 224 38.5 64 266 45.7 60 45.1 207 35.7 55 252 43.4 55

10 42.5 230 39.5 67 272 46.8 62 45.6 213 36.6 58 259 44.5 5711 42.9 236 40.6 71 279 47.9 65 46.0 219 37.6 61 265 45.5 595 42.1 195 33.5 49 237 40.7 49 45.1 180 31.0 42 226 38.8 456 42.5 201 34.5 52 243 41.8 51 45.6 186 32.0 45 232 39.9 477 42.9 207 35.6 55 250 43.0 54 46.0 192 33.0 48 238 40.9 498 43.3 214 36.7 58 257 44.2 56 46.5 198 34.1 51 245 42.0 529 43.7 220 37.8 62 263 45.3 59 46.9 204 35.0 53 251 43.1 54

10 44.2 226 38.8 65 270 46.4 61 47.4 209 36.0 56 257 44.2 5611 44.6 233 40.0 69 277 47.7 64 47.8 216 37.1 59 263 45.3 595 42.5 193 33.2 48 235 40.5 486 42.9 199 34.1 51 241 41.5 507 43.3 205 35.2 54 248 42.7 538 43.8 211 36.4 57 255 43.9 569 44.2 218 37.4 61 262 45.0 58

10 44.6 224 38.5 64 268 46.2 6111 45.0 230 39.6 67 275 47.3 64

IPT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD5 38.8 292 50.3 88 331 56.9 42 42.4 272 46.8 77 315 54.1 386 39.4 301 51.8 93 341 58.6 44 43.1 281 48.3 82 324 55.7 407 40.0 309 53.1 98 349 60.0 46 43.7 288 49.5 86 332 57.0 428 40.5 318 54.6 103 358 61.6 48 44.3 296 50.9 90 340 58.5 449 41.0 326 56.0 108 367 63.0 50 44.8 303 52.2 94 348 59.9 4610 41.6 334 57.5 113 376 64.7 53 45.4 312 53.6 99 357 61.4 4811 42.2 342 58.8 118 384 66.1 55 46.1 319 54.8 103 365 62.7 505 42.2 286 49.1 84 328 56.4 41 46.1 266 45.8 74 312 53.7 376 42.6 293 50.5 89 336 57.8 43 46.6 273 47.0 78 320 55.0 397 43.2 302 52.0 94 345 59.4 45 47.2 282 48.4 82 329 56.6 418 43.8 310 53.3 98 354 60.8 47 47.8 289 49.7 86 337 57.9 439 44.2 319 54.8 103 363 62.4 50 48.3 297 51.1 91 345 59.4 4510 44.8 327 56.2 108 371 63.9 52 49.0 304 52.3 95 353 60.8 4711 45.4 335 57.7 114 381 65.5 54 49.6 313 53.8 100 362 62.3 495 47.6 272 46.8 77 320 55.0 39 52.0 254 43.6 68 306 52.6 366 48.0 281 48.4 82 329 56.6 41 52.5 262 45.1 72 315 54.1 387 48.6 289 49.7 86 338 58.1 43 53.1 269 46.3 76 322 55.4 408 49.2 298 51.2 91 347 59.7 46 53.7 278 47.7 80 331 57.0 429 49.6 306 52.5 96 355 61.1 48 54.2 285 49.0 84 339 58.3 4410 50.2 314 54.1 101 365 62.7 50 54.9 293 50.4 88 348 59.8 4611 50.8 322 55.4 105 373 64.1 52 55.5 300 51.6 93 356 61.2 485 53.0 260 44.7 71 313 53.8 38 57.9 242 41.7 62 300 51.6 356 53.4 269 46.3 75 322 55.5 40 58.4 251 43.1 66 309 53.2 377 54.0 279 48.0 81 333 57.3 42 59.0 260 44.7 71 319 54.9 398 54.6 286 49.1 84 340 58.5 44 59.6 266 45.8 74 326 56.0 419 55.0 293 50.5 89 348 59.9 46 60.1 273 47.0 78 334 57.4 4210 55.6 302 52.0 94 358 61.5 48 60.8 282 48.4 82 342 58.9 4411 56.2 310 53.3 98 366 63.0 50 61.4 289 49.7 86 350 60.2 465 55.0 256 44.0 69 311 53.4 37 60.1 238 41.0 60 298 51.3 346 55.6 264 45.3 73 319 54.9 39 60.8 246 42.2 64 306 52.7 367 56.2 272 46.8 77 329 56.5 41 61.4 254 43.6 68 315 54.2 388 56.7 280 48.2 81 337 57.9 43 62.0 261 44.9 71 323 55.6 409 57.2 289 49.7 86 346 59.5 45 62.5 269 46.3 76 332 57.1 4210 57.8 297 51.0 91 355 61.0 47 63.1 277 47.6 79 340 58.4 4411 58.4 306 52.5 96 364 62.6 50 63.8 285 49.0 84 349 59.9 465 55.6 253 43.6 67 309 53.1 376 56.1 260 44.8 71 317 54.4 387 56.7 270 46.4 76 326 56.1 418 57.3 277 47.6 80 334 57.5 429 57.8 286 49.2 85 344 59.2 4510 58.3 293 50.5 89 352 60.5 4711 58.9 303 52.1 94 362 62.2 49

37

40

Cooling Capacities

22

25

30

35

37

40

CDOT CLOTRCU80WHYZ(-E) RCUG80WHYZ(-E)

22

25

30

35

CDOT CLOT RCU60WHYZ(-E) RCUG60WHYZ(-E)

16

SELECTION DATA

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃)

HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h)

CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa)

Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser.

2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data”

Conversion Multiplier: 1kW = 860kcal/h = 3412Btu/h

IPT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD5 48.3 362 62.2 80 410 70.5 44 52.9 341 58.6 71 393 67.7 416 49.0 371 63.9 84 420 72.3 46 53.6 350 60.2 75 403 69.4 437 49.6 382 65.8 88 432 74.3 48 54.4 360 61.9 79 414 71.3 458 50.4 392 67.4 93 443 76.1 51 55.2 369 63.5 83 425 73.0 479 51.0 402 69.1 97 453 77.9 53 55.9 379 65.1 87 435 74.7 49

10 51.7 413 71.0 102 465 79.9 55 56.6 389 66.9 91 446 76.6 5111 52.4 423 72.7 107 475 81.7 58 57.4 398 68.5 95 456 78.4 535 52.4 352 60.5 76 404 69.5 43 57.4 331 57.0 68 389 66.8 406 53.0 363 62.4 80 416 71.5 45 58.1 342 58.7 72 400 68.7 427 53.7 372 64.1 84 426 73.3 47 58.8 351 60.3 75 410 70.4 448 54.3 382 65.8 88 437 75.1 49 59.5 360 61.9 79 420 72.2 469 55.0 393 67.6 93 448 77.1 52 60.3 370 63.7 83 431 74.1 48

10 55.7 403 69.3 97 459 78.9 54 61.0 380 65.3 87 441 75.8 5011 56.3 414 71.2 102 470 80.9 57 61.7 390 67.1 92 452 77.7 525 59.1 336 57.8 70 395 68.0 41 64.7 317 54.5 62 381 65.6 386 59.7 347 59.7 74 407 70.0 43 65.4 327 56.3 66 393 67.5 407 60.4 357 61.4 78 418 71.8 45 66.2 336 57.8 70 403 69.2 428 61.0 367 63.1 82 428 73.6 48 66.9 346 59.4 73 413 70.9 449 61.7 378 65.0 86 440 75.6 50 67.6 356 61.2 77 424 72.8 47

10 62.4 388 66.7 91 450 77.4 52 68.3 365 62.8 81 434 74.6 4911 63.0 398 68.4 95 461 79.2 54 69.1 375 64.4 85 444 76.3 515 65.8 321 55.2 64 387 66.5 39 72.1 302 52.0 57 374 64.4 376 66.4 332 57.1 68 398 68.5 42 72.8 313 53.8 61 385 66.3 397 67.1 344 59.2 73 411 70.7 44 73.5 324 55.7 65 398 68.4 418 67.8 352 60.5 76 419 72.1 46 74.2 331 57.0 68 405 69.7 439 68.4 363 62.4 80 431 74.1 48 75.0 342 58.7 72 416 71.6 45

10 69.1 372 64.1 84 442 75.9 50 75.7 351 60.3 75 427 73.3 4711 69.7 382 65.8 88 452 77.7 53 76.4 360 61.9 79 437 75.1 495 68.4 316 54.3 62 384 66.0 39 75.0 297 51.1 55 372 64.0 376 69.1 325 56.0 66 394 67.8 41 75.7 306 52.7 59 382 65.7 397 69.7 335 57.7 69 405 69.6 43 76.4 316 54.3 62 392 67.4 408 70.5 346 59.5 73 417 71.7 45 77.2 326 56.1 66 403 69.4 439 71.2 356 61.2 77 427 73.5 47 78.0 335 57.7 69 413 71.1 45

10 71.8 366 62.9 81 438 75.3 50 78.7 345 59.3 73 423 72.8 4711 72.5 377 64.8 86 449 77.3 52 79.4 355 61.0 77 434 74.7 495 69.1 312 53.7 61 381 65.6 386 69.8 322 55.4 64 392 67.4 407 70.4 332 57.0 68 402 69.1 428 71.2 343 59.0 72 414 71.2 459 71.9 352 60.6 76 424 72.9 47

10 72.5 363 62.3 80 435 74.8 4911 73.2 373 64.1 84 446 76.7 51

IPT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD5 59.4 446 76.7 95 506 86.9 48 63.7 414 71.1 82 477 82.1 436 60.3 458 78.8 100 519 89.2 50 64.7 425 73.1 87 490 84.2 457 61.1 471 81.0 106 532 91.5 52 65.5 436 75.0 91 502 86.3 478 61.9 484 83.3 111 546 93.9 55 66.4 449 77.2 96 515 88.6 499 62.7 496 85.4 117 559 96.1 57 67.3 460 79.1 101 527 90.7 52

10 63.6 509 87.5 122 572 98.4 60 68.2 472 81.1 106 540 92.8 5411 64.4 522 89.8 129 586 100.8 62 69.0 484 83.2 111 553 95.1 565 64.4 434 74.6 90 498 85.7 47 69.0 402 69.2 78 471 81.0 426 65.2 447 76.9 96 513 88.1 49 70.0 415 71.3 83 485 83.3 447 66.0 460 79.0 101 526 90.4 51 70.8 426 73.3 87 497 85.4 468 66.9 472 81.1 106 539 92.6 54 71.7 437 75.2 92 509 87.6 489 67.7 485 83.4 112 553 95.1 56 72.6 450 77.4 97 522 89.8 51

10 68.5 498 85.6 117 566 97.3 58 73.5 461 79.3 102 535 92.0 5311 69.3 510 87.7 123 579 99.6 61 74.3 473 81.3 106 547 94.1 555 72.6 415 71.4 83 488 83.8 45 77.9 385 66.2 72 463 79.5 416 73.5 428 73.7 88 502 86.3 47 78.8 397 68.3 76 476 81.8 437 74.3 441 75.8 93 515 88.5 49 79.6 408 70.2 80 488 83.9 458 75.1 453 77.9 98 528 90.8 52 80.6 420 72.2 85 500 86.1 479 75.9 466 80.2 104 542 93.2 54 81.4 432 74.3 90 514 88.3 49

10 76.8 479 82.3 109 555 95.5 56 82.4 444 76.3 94 526 90.5 5111 77.6 491 84.4 114 568 97.7 59 83.2 455 78.2 99 538 92.6 535 80.9 396 68.1 76 477 82.0 43 86.7 367 63.1 66 454 78.0 406 81.7 409 70.4 81 491 84.5 45 87.7 380 65.3 70 467 80.3 427 82.5 425 73.1 87 508 87.3 48 88.5 394 67.8 75 482 83.0 448 83.4 434 74.6 90 517 89.0 50 89.4 402 69.2 78 492 84.6 469 84.2 447 76.9 96 531 91.4 52 90.3 415 71.3 83 505 86.8 48

10 85.0 460 79.0 101 545 93.7 55 91.2 426 73.3 87 517 89.0 5011 85.8 472 81.1 106 558 95.9 57 92.0 437 75.2 92 529 91.1 525 84.2 389 66.9 73 473 81.4 43 90.3 361 62.1 63 451 77.6 396 85.0 402 69.1 78 487 83.7 45 91.2 372 64.0 67 463 79.7 417 85.8 414 71.2 82 500 85.9 47 92.0 384 66.0 71 476 81.8 438 86.7 427 73.5 88 514 88.4 49 93.0 396 68.1 76 489 84.1 459 87.5 440 75.6 93 527 90.6 51 93.8 407 70.1 80 501 86.2 47

10 88.3 452 77.7 98 540 92.9 54 94.7 419 72.0 84 514 88.3 4911 89.1 465 80.0 103 554 95.3 56 95.6 431 74.2 89 527 90.6 515 85.0 386 66.3 72 471 81.0 426 85.9 397 68.3 76 483 83.1 447 86.7 409 70.4 81 496 85.3 468 87.5 423 72.7 86 510 87.8 499 88.3 435 74.9 91 524 90.1 51

10 89.2 448 77.0 96 537 92.3 5311 90.0 460 79.1 101 550 94.6 56

RCU120WHYZ(-E) RCUG120WHYZ(-E)

37

CDOT CLOT

40

Cooling Capacities 1kPa = 0.102mAq

22

25

30

35

37

40

22

25

30

35

CDOT CLOT RCU100WHYZ(-E) RCUG100WHYZ(-E)

17

SELECTION DATA

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃)

HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h)

CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa) Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser. 2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data”

Conversion Multiplier: 1kW = 860kcal/h = 3412Btu/h

IPT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD5 72.4 542 93.3 81 615 105.7 40 79.4 511 87.8 72 590 101.5 376 73.4 557 95.8 86 631 108.4 42 80.4 525 90.2 76 605 104.1 397 74.4 574 98.6 90 648 111.4 44 81.5 540 92.9 81 622 106.9 418 75.6 588 101.2 95 664 114.2 46 82.8 554 95.3 85 637 109.5 439 76.5 603 103.7 100 680 116.9 49 83.9 568 97.7 89 652 112.1 45

10 77.5 620 106.5 105 697 119.9 51 84.9 584 100.3 93 668 115.0 4711 78.5 634 109.1 110 713 122.6 53 86.0 597 102.7 98 683 117.5 495 78.5 528 90.7 77 606 104.2 39 86.0 497 85.4 69 583 100.2 366 79.5 544 93.5 82 623 107.2 41 87.1 512 88.1 73 599 103.1 387 80.5 559 96.1 86 639 109.9 43 88.2 526 90.5 77 614 105.7 408 81.5 574 98.6 90 655 112.6 45 89.3 540 92.9 81 629 108.2 429 82.5 590 101.5 95 672 115.6 48 90.4 556 95.6 85 646 111.1 44

10 83.5 605 104.0 100 688 118.4 50 91.5 570 98.0 89 661 113.7 4611 84.5 621 106.8 105 706 121.4 52 92.6 585 100.6 94 678 116.5 485 88.6 504 86.8 71 593 102.0 38 97.1 475 81.7 63 572 98.4 356 89.6 521 89.6 75 611 105.0 40 98.1 491 84.4 67 589 101.3 377 90.6 536 92.1 79 626 107.7 42 99.2 505 86.8 71 604 103.8 398 91.6 551 94.7 84 642 110.4 44 100.3 519 89.2 74 619 106.4 419 92.6 567 97.5 88 660 113.4 46 101.4 534 91.8 79 635 109.3 43

10 93.6 582 100.0 93 675 116.1 48 102.5 548 94.2 83 650 111.8 4511 94.6 597 102.6 98 691 118.8 50 103.6 562 96.6 87 665 114.4 475 98.7 481 82.8 65 580 99.8 36 108.1 453 78.0 58 562 96.6 346 99.7 498 85.6 69 598 102.8 38 109.2 469 80.6 61 578 99.4 367 100.6 516 88.7 74 617 106.0 40 110.3 486 83.6 66 596 102.5 388 101.6 528 90.7 77 629 108.2 42 111.3 497 85.4 69 608 104.6 399 102.6 544 93.5 82 647 111.2 44 112.4 512 88.1 73 625 107.4 41

10 103.6 559 96.1 86 662 113.9 46 113.5 526 90.5 77 640 110.0 4311 104.6 574 98.6 90 678 116.6 48 114.6 540 92.9 81 655 112.6 455 102.6 473 81.4 63 576 99.0 35 112.4 446 76.7 56 558 96.0 336 103.6 488 83.9 66 592 101.8 37 113.5 460 79.1 59 573 98.6 357 104.6 503 86.5 70 607 104.5 39 114.6 474 81.4 63 588 101.2 378 105.7 519 89.3 75 625 107.5 41 115.9 489 84.1 67 605 104.0 399 106.7 534 91.8 79 641 110.2 43 116.9 503 86.5 70 620 106.6 41

10 107.7 549 94.4 83 657 112.9 45 118.0 517 88.9 74 635 109.2 4311 108.7 565 97.2 88 674 115.9 48 119.1 532 91.6 78 652 112.0 455 103.7 468 78.1 58 572 98.3 356 104.7 484 80.6 61 588 101.2 377 105.6 497 83.2 65 603 103.7 398 106.8 514 85.7 69 621 106.8 419 107.8 528 88.2 73 636 109.4 43

10 108.8 544 90.8 77 653 112.2 4511 109.8 559 93.3 81 669 115.1 47

IPT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD5 89.1 669 115.1 101 758 130.4 53 95.6 620 106.7 88 716 123.1 486 90.4 688 118.3 106 778 133.8 56 97.0 638 109.6 92 735 126.3 507 91.6 706 121.4 112 798 137.2 58 98.2 655 112.6 97 753 129.5 538 92.9 726 124.9 118 819 140.9 61 99.6 673 115.8 102 773 132.9 559 94.1 745 128.0 124 839 144.2 64 100.9 690 118.7 107 791 136.1 57

10 95.4 763 131.2 130 858 147.6 66 102.3 707 121.6 112 810 139.2 6011 96.5 783 134.7 136 880 151.3 69 103.5 726 124.8 118 829 142.6 625 96.5 651 111.9 96 747 128.5 52 103.5 603 103.8 83 707 121.6 476 97.8 671 115.4 102 769 132.2 55 104.9 622 107.0 88 727 125.0 507 99.0 689 118.6 107 788 135.6 57 106.2 639 109.9 93 745 128.2 528 100.3 708 121.7 112 808 139.0 60 107.6 656 112.8 97 764 131.3 549 101.5 728 125.2 118 829 142.6 62 108.8 675 116.0 103 784 134.8 56

10 102.8 746 128.3 124 849 146.0 65 110.3 692 119.0 108 802 137.9 5911 104.0 765 131.5 130 869 149.4 67 111.5 709 121.9 113 820 141.1 615 108.9 622 107.0 88 731 125.8 50 116.8 577 99.2 76 694 119.3 466 110.2 643 110.5 94 753 129.4 53 118.2 596 102.4 81 714 122.8 487 111.4 661 113.7 99 772 132.8 55 119.5 613 105.4 86 732 125.9 508 112.7 679 116.8 104 792 136.2 58 120.9 630 108.3 90 751 129.1 529 113.9 699 120.3 110 813 139.9 60 122.1 648 111.5 95 771 132.5 55

10 115.2 718 123.4 115 833 143.2 63 123.5 665 114.4 100 789 135.7 5711 116.3 736 126.6 121 853 146.6 65 124.8 683 117.4 105 807 138.8 595 121.3 594 102.1 81 715 123.0 48 130.1 551 94.7 70 681 117.1 446 122.6 614 105.6 86 737 126.7 51 131.5 569 97.9 74 701 120.5 477 123.8 638 109.6 92 761 130.9 54 132.7 591 101.6 80 724 124.5 498 125.1 651 111.9 96 776 133.4 55 134.1 603 103.8 83 738 126.8 519 126.2 671 115.4 102 797 137.1 58 135.4 622 107.0 88 757 130.3 53

10 127.5 689 118.6 107 817 140.5 61 136.8 639 109.9 93 776 133.4 5511 128.7 708 121.7 112 836 143.8 63 138.0 656 112.8 97 794 136.6 585 126.2 584 100.4 78 710 122.1 48 135.4 541 93.1 68 677 116.4 446 127.5 602 103.6 83 730 125.5 50 136.8 558 96.0 72 695 119.6 467 128.7 621 106.8 88 749 128.9 52 138.0 575 99.0 76 714 122.7 488 130.0 641 110.2 93 771 132.6 55 139.5 594 102.2 81 734 126.1 509 131.2 659 113.4 98 790 135.9 57 140.7 611 105.1 85 752 129.3 53

10 132.5 678 116.5 103 810 139.3 60 142.1 628 108.0 90 770 132.5 5511 133.7 698 120.0 109 831 143.0 63 143.4 647 111.2 95 790 135.9 575 127.5 579 95.8 71 706 121.4 476 128.8 596 98.8 76 724 124.6 497 130.0 614 102.0 80 744 128.0 528 131.3 634 105.0 85 766 131.7 549 132.5 653 108.3 90 785 135.1 57

10 133.8 672 111.3 95 805 138.5 5911 135.0 690 114.4 100 825 141.9 62

Cooling Capacities

37

40

1kPa = 0.102mAq

22

25

30

35

37

40

CDOT CLOT RCU180WHYZ(-E) RCUG180WHYZ(-E)

22

25

30

35

CDOT CLOTRCU150WHYZ(-E) RCUG150WHYZ(-E)

18

NO.1 NO.2 NO.1 NO.2 NO.1 NO.2 NO.1 NO.25 104.2 765 65.7 65.7 119 119 869 74.7 74.7 72 726 104.9 786 67.6 67.6 124 124 891 76.6 76.6 74 747 105.6 808 69.4 69.4 130 130 913 78.5 78.5 77 778 106.3 829 71.3 71.3 135 135 935 80.4 80.4 80 809 107.1 850 73.1 73.1 141 141 957 82.3 82.3 83 83

10 107.8 872 75.0 75.0 147 147 980 84.2 84.2 86 8611 108.5 893 76.8 76.8 152 152 1002 86.1 86.1 88 885 111.3 744 63.9 63.9 114 114 855 73.5 73.5 70 706 112.1 765 65.7 65.7 119 119 877 75.4 75.4 73 737 112.9 785 67.5 67.5 124 124 898 77.2 77.2 75 758 113.6 806 69.3 69.3 129 129 920 79.1 79.1 78 789 114.4 827 71.1 71.1 135 135 942 81.0 81.0 81 81

10 115.2 848 72.9 72.9 140 140 963 82.8 82.8 83 8311 115.9 869 74.7 74.7 146 146 985 84.7 84.7 86 865 123.2 709 61.0 61.0 105 105 833 71.6 71.6 67 676 124.1 729 62.7 62.7 110 110 853 73.4 73.4 70 707 124.9 749 64.4 64.4 115 115 874 75.2 75.2 72 728 125.8 769 66.1 66.1 120 120 895 76.9 76.9 75 759 126.6 789 67.8 67.8 125 125 916 78.7 78.7 77 77

10 127.5 809 69.6 69.6 130 130 936 80.5 80.5 80 8011 128.3 829 71.3 71.3 135 135 957 82.3 82.3 83 835 135.1 675 58.1 58.1 97 97 810 69.7 69.7 65 656 136.1 694 59.7 59.7 102 102 830 71.4 71.4 67 677 137.0 713 61.3 61.3 106 106 850 73.1 73.1 69 698 137.9 732 62.9 62.9 111 111 870 74.8 74.8 72 729 138.9 751 64.6 64.6 115 115 890 76.5 76.5 74 74

10 139.8 770 66.2 66.2 120 120 910 78.2 78.2 77 7711 140.7 789 67.8 67.8 125 125 929 79.9 79.9 79 795 140.1 661 56.9 56.9 94 94 801 68.9 68.9 64 646 141.0 680 58.5 58.5 98 98 821 70.6 70.6 66 667 142.0 698 60.1 60.1 103 103 840 72.3 72.3 68 688 142.9 717 61.7 61.7 107 107 860 73.9 73.9 71 719 143.9 736 63.2 63.2 112 112 879 75.6 75.6 73 73

10 144.9 754 64.8 64.8 116 116 899 77.3 77.3 75 7511 145.8 773 66.4 66.4 121 121 918 79.0 79.0 78 785 150.5 641 55.1 55.1 90 90 791 68.0 68.0 62 626 151.5 659 56.6 56.6 94 94 810 69.7 69.7 65 657 152.5 677 58.2 58.2 98 98 829 71.3 71.3 67 678 153.6 695 59.7 59.7 102 102 848 72.9 72.9 69 699 154.6 713 61.3 61.3 106 106 867 74.6 74.6 72 72

10 155.6 731 62.8 62.8 111 111 886 76.2 76.2 74 7411 156.7 749 64.4 64.4 115 115 905 77.8 77.8 76 76

NO.1 NO.2 NO.1 NO.2 NO.1 NO.2 NO.1 NO.25 111.1 738 63.4 63.4 112 112 849 73.0 73.0 69 696 111.9 759 65.2 65.2 117 117 870 74.8 74.8 72 727 112.6 779 67.0 67.0 122 122 892 76.7 76.7 75 758 113.4 800 68.8 68.8 128 128 913 78.5 78.5 77 779 114.2 821 70.6 70.6 133 133 935 80.4 80.4 80 80

10 114.9 841 72.3 72.3 138 138 956 82.2 82.2 83 8311 115.7 862 74.1 74.1 144 144 978 84.1 84.1 85 855 118.7 718 61.7 61.7 107 107 836 71.9 71.9 68 686 119.6 738 63.4 63.4 112 112 857 73.7 73.7 70 707 120.4 758 65.2 65.2 117 117 878 75.5 75.5 73 738 121.2 778 66.9 66.9 122 122 899 77.3 77.3 75 759 122.0 798 68.6 68.6 127 127 920 79.1 79.1 78 78

10 122.8 818 70.4 70.4 132 132 941 80.9 80.9 81 8111 123.6 838 72.1 72.1 138 138 962 82.7 82.7 83 835 131.4 685 58.9 58.9 100 100 816 70.2 70.2 65 656 132.3 704 60.5 60.5 104 104 836 71.9 71.9 68 687 133.2 723 62.2 62.2 109 109 856 73.6 73.6 70 708 134.1 742 63.8 63.8 113 113 876 75.3 75.3 73 739 135.0 761 65.5 65.5 118 118 896 77.1 77.1 75 75

10 135.9 781 67.1 67.1 123 123 916 78.8 78.8 78 7811 136.8 800 68.8 68.8 128 128 937 80.5 80.5 80 805 144.1 651 56.0 56.0 92 92 796 68.4 68.4 63 636 145.1 670 57.6 57.6 96 96 815 70.1 70.1 65 657 146.1 688 59.2 59.2 100 100 834 71.7 71.7 68 688 147.1 706 60.7 60.7 105 105 853 73.4 73.4 70 709 148.1 725 62.3 62.3 109 109 873 75.0 75.0 72 72

10 149.1 743 63.9 63.9 113 113 892 76.7 76.7 75 7511 150.1 761 65.4 65.4 118 118 911 78.3 78.3 77 775 149.4 638 54.9 54.9 89 89 788 67.7 67.7 62 626 150.4 656 56.4 56.4 93 93 806 69.3 69.3 64 647 151.4 674 58.0 58.0 97 97 825 71.0 71.0 66 668 152.4 692 59.5 59.5 101 101 844 72.6 72.6 69 699 153.5 710 61.0 61.0 105 105 863 74.2 74.2 71 71

10 154.5 728 62.6 62.6 110 110 882 75.9 75.9 73 7311 155.5 746 64.1 64.1 114 114 901 77.5 77.5 76 76

Conversion Multiplier: 1kW = 860kcal/h = 3412Btu/h

CDOT

30

RCU220WHYZ(-E) 1kPa = 0.102mAq

HFR HPD

22

25

HCAP

CLOT

CLOT IPT CCAP CFR

Cooling Capacities

35

25

30

CPD

35

37

40

CDOT

37

RCUG220WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

22

SELECTION DATA

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃)

HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h)

CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa) Notes: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser. 2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data”.

3. NO.1, NO.2 at the title row means No.1, No.2 module of the unit separately.

19

Conversion Multiplier: 1kW = 860kcal/h = 3412Btu/h

NO.1 NO.2 NO.1 NO.2 NO.1 NO.2 NO.1 NO.25 123.2 903 89.5 65.7 95 119 1026 101.8 74.7 57 726 124.1 928 92.1 67.6 100 124 1052 104.4 76.6 59 747 124.9 954 94.6 69.4 105 130 1079 107.0 78.5 62 778 125.7 979 97.1 71.3 110 135 1105 109.6 80.4 64 809 126.6 1004 99.6 73.1 115 141 1131 112.1 82.3 67 83

10 127.4 1030 102.1 75.0 120 147 1157 114.7 84.2 69 8611 128.3 1055 104.6 76.8 126 152 1183 117.3 86.1 72 885 131.7 878 87.1 63.9 90 114 1010 100.2 73.5 56 706 132.6 903 89.5 65.7 95 119 1035 102.7 75.4 58 737 133.5 928 92.0 67.5 99 124 1061 105.2 77.2 60 758 134.4 952 94.4 69.3 104 129 1087 107.8 79.1 63 789 135.3 977 96.9 71.1 109 135 1112 110.3 81.0 65 81

10 136.2 1001 99.3 72.9 114 140 1138 112.8 82.8 67 8311 137.1 1026 101.7 74.7 119 146 1163 115.3 84.7 70 865 145.7 838 83.1 61.0 83 105 984 97.5 71.6 53 676 146.7 861 85.4 62.7 87 110 1008 100.0 73.4 56 707 147.7 885 87.7 64.4 91 115 1033 102.4 75.2 58 728 148.7 908 90.1 66.1 96 120 1057 104.8 76.9 60 759 149.7 932 92.4 67.8 100 125 1081 107.3 78.7 62 77

10 150.7 955 94.7 69.6 105 130 1106 109.7 80.5 64 8011 151.7 979 97.1 71.3 110 135 1130 112.1 82.3 67 835 159.8 797 79.1 58.1 76 97 957 94.9 69.7 51 656 160.9 820 81.3 59.7 79 102 981 97.2 71.4 53 677 162.0 842 83.5 61.3 83 106 1004 99.6 73.1 55 698 163.1 864 85.7 62.9 87 111 1027 101.9 74.8 57 729 164.2 887 87.9 64.6 92 115 1051 104.2 76.5 59 74

10 165.3 909 90.1 66.2 96 120 1074 106.5 78.2 61 7711 166.4 931 92.4 67.8 100 125 1098 108.9 79.9 64 795 165.6 781 77.4 56.9 73 94 947 93.9 68.9 50 646 166.8 803 79.6 58.5 76 98 970 96.2 70.6 52 667 167.9 825 81.8 60.1 80 103 993 98.5 72.3 54 688 169.0 847 84.0 61.7 84 107 1016 100.7 73.9 56 719 170.2 869 86.1 63.2 88 112 1039 103.0 75.6 58 73

10 171.3 891 88.3 64.8 92 116 1062 105.3 77.3 60 7511 172.4 912 90.5 66.4 96 121 1085 107.6 79.0 62 785 177.9 757 75.0 55.1 69 90 935 92.7 68.0 49 626 179.2 778 77.1 56.6 72 94 957 94.9 69.7 51 657 180.4 799 79.2 58.2 76 98 980 97.2 71.3 53 678 181.6 820 81.4 59.7 80 102 1002 99.4 72.9 55 699 182.8 842 83.5 61.3 83 106 1025 101.6 74.6 57 72

10 184.1 863 85.6 62.8 87 111 1047 103.8 76.2 59 7411 185.3 884 87.7 64.4 91 115 1069 106.1 77.8 61 76

NO.1 NO.2 NO.1 NO.2 NO.1 NO.2 NO.1 NO.25 132.4 879.4 87.8 63.4 91 112 1012 101.0 73.0 56 696 133.3 904.1 90.2 65.2 96 117 1037 103.5 74.8 59 727 134.2 928.7 92.7 67.0 101 122 1063 106.1 76.7 61 758 135.1 953.4 95.2 68.8 106 128 1089 108.6 78.5 63 779 136.0 978.1 97.6 70.6 111 133 1114 111.2 80.4 66 80

10 137.0 1002.7 100.1 72.3 116 138 1140 113.7 82.2 68 8311 137.9 1027.4 102.6 74.1 121 144 1165 116.3 84.1 71 855 141.5 855.3 85.4 61.7 87 107 997 99.5 71.9 55 686 142.5 879.3 87.8 63.4 91 112 1022 102.0 73.7 57 707 143.4 903.3 90.2 65.2 96 117 1047 104.5 75.5 60 738 144.4 927.3 92.6 66.9 101 122 1072 107.0 77.3 62 759 145.4 951.3 95.0 68.6 105 127 1097 109.4 79.1 64 78

10 146.4 975.3 97.4 70.4 110 132 1122 111.9 80.9 67 8111 147.3 999.3 99.8 72.1 115 138 1147 114.4 82.7 69 835 156.6 815.9 81.4 58.9 80 100 973 97.0 70.2 53 656 157.7 838.8 83.7 60.5 84 104 996 99.4 71.9 55 687 158.8 861.7 86.0 62.2 88 109 1020 101.8 73.6 57 708 159.8 884.5 88.3 63.8 92 113 1044 104.2 75.3 59 739 160.9 907.4 90.6 65.5 97 118 1068 106.6 77.1 62 75

10 162.0 930.3 92.9 67.1 101 123 1092 109.0 78.8 64 7811 163.1 953.2 95.2 68.8 106 128 1116 111.4 80.5 66 805 171.7 776.5 77.5 56.0 73 92 948 94.6 68.4 51 636 172.9 798.2 79.7 57.6 77 96 971 96.9 70.1 53 657 174.1 820.0 81.9 59.2 80 100 994 99.2 71.7 55 688 175.3 841.8 84.0 60.7 84 105 1017 101.5 73.4 57 709 176.5 863.5 86.2 62.3 88 109 1040 103.8 75.0 59 72

10 177.6 885.3 88.4 63.9 92 113 1063 106.1 76.7 61 7511 178.8 907.1 90.6 65.4 97 118 1086 108.4 78.3 63 775 178.0 760.6 75.9 54.9 70 89 939 93.7 67.7 50 626 179.2 781.9 78.1 56.4 74 93 961 95.9 69.3 52 647 180.4 803.3 80.2 58.0 77 97 984 98.2 71.0 54 668 181.7 824.6 82.3 59.5 81 101 1006 100.4 72.6 56 699 182.9 845.9 84.4 61.0 85 105 1029 102.7 74.2 58 71

10 184.1 867.3 86.6 62.6 89 110 1051 104.9 75.9 60 7311 185.3 888.6 88.7 64.1 93 114 1074 107.2 77.5 62 76

Cooling Capacities 1kPa = 0.102mAq

CDOT CLOTRCU260WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

CLOT

22

25

30

35

25

30

35

37

40

CDOT

37

RCUG260WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

22

SELECTION DATA

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃)

HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h)

CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa) Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser. 2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data”.

3. NO.1, NO.2 at the title row means No.1, No.2 module of the unit separately.

20

SELECTION DATAConversion Multiplier: 1kW = 860kcal/h

= 3412Btu/h

NO.1 NO.2 NO.1 NO.2 NO.1 NO.2 NO.1 NO.25 142.2 1041 89.5 89.5 95 95 1184 101.8 101.8 57 576 143.2 1071 92.1 92.1 100 100 1214 104.4 104.4 59 597 144.2 1100 94.6 94.6 105 105 1244 107.0 107.0 62 628 145.2 1129 97.1 97.1 110 110 1274 109.6 109.6 64 649 146.1 1158 99.6 99.6 115 115 1304 112.1 112.1 67 67

10 147.1 1187 102.1 102.1 120 120 1334 114.7 114.7 69 6911 148.1 1217 104.6 104.6 126 126 1365 117.3 117.3 72 725 152.0 1013 87.1 87.1 90 90 1165 100.2 100.2 56 566 153.0 1041 89.5 89.5 95 95 1194 102.7 102.7 58 587 154.1 1070 92.0 92.0 99 99 1224 105.2 105.2 60 608 155.1 1098 94.4 94.4 104 104 1253 107.8 107.8 63 639 156.2 1126 96.9 96.9 109 109 1283 110.3 110.3 65 65

10 157.2 1155 99.3 99.3 114 114 1312 112.8 112.8 67 6711 158.2 1183 101.7 101.7 119 119 1342 115.3 115.3 70 705 168.2 966 83.1 83.1 83 83 1134 97.5 97.5 53 536 169.4 993 85.4 85.4 87 87 1163 100.0 100.0 56 567 170.5 1020 87.7 87.7 91 91 1191 102.4 102.4 58 588 171.7 1047 90.1 90.1 96 96 1219 104.8 104.8 60 609 172.8 1075 92.4 92.4 100 100 1247 107.3 107.3 62 62

10 174.0 1102 94.7 94.7 105 105 1276 109.7 109.7 64 6411 175.1 1129 97.1 97.1 110 110 1304 112.1 112.1 67 675 184.5 919 79.1 79.1 76 76 1104 94.9 94.9 51 516 185.7 945 81.3 81.3 79 79 1131 97.2 97.2 53 537 187.0 971 83.5 83.5 83 83 1158 99.6 99.6 55 558 188.3 997 85.7 85.7 87 87 1185 101.9 101.9 57 579 189.5 1023 87.9 87.9 92 92 1212 104.2 104.2 59 59

10 190.8 1048 90.1 90.1 96 96 1239 106.5 106.5 61 6111 192.1 1074 92.4 92.4 100 100 1266 108.9 108.9 64 645 191.2 901 77.4 77.4 73 73 1092 93.9 93.9 50 506 192.5 926 79.6 79.6 76 76 1118 96.2 96.2 52 527 193.8 951 81.8 81.8 80 80 1145 98.5 98.5 54 548 195.1 976 84.0 84.0 84 84 1172 100.7 100.7 56 569 196.4 1002 86.1 86.1 88 88 1198 103.0 103.0 58 58

10 197.7 1027 88.3 88.3 92 92 1225 105.3 105.3 60 6011 199.1 1052 90.5 90.5 96 96 1251 107.6 107.6 62 625 205.4 873 75.0 75.0 69 69 1078 92.7 92.7 49 496 206.8 897 77.1 77.1 72 72 1104 94.9 94.9 51 517 208.2 922 79.2 79.2 76 76 1130 97.2 97.2 53 538 209.6 946 81.4 81.4 80 80 1156 99.4 99.4 55 559 211.0 971 83.5 83.5 83 83 1182 101.6 101.6 57 57

10 212.5 995 85.6 85.6 87 87 1208 103.8 103.8 59 5911 213.9 1020 87.7 87.7 91 91 1233 106.1 106.1 61 61

NO.1 NO.2 NO.1 NO.2 NO.1 NO.2 NO.1 NO.25 153.4 1021 87.8 87.8 91 91 1174 101.0 101.0 56 566 154.5 1050 90.2 90.2 96 96 1204 103.5 103.5 59 597 155.5 1078 92.7 92.7 101 101 1234 106.1 106.1 61 618 156.6 1107 95.2 95.2 106 106 1263 108.6 108.6 63 639 157.6 1135 97.6 97.6 111 111 1293 111.2 111.2 66 66

10 158.7 1164 100.1 100.1 116 116 1323 113.7 113.7 68 6811 159.7 1193 102.6 102.6 121 121 1352 116.3 116.3 71 715 163.9 993 85.4 85.4 87 87 1157 99.5 99.5 55 556 165.1 1021 87.8 87.8 91 91 1186 102.0 102.0 57 577 166.2 1049 90.2 90.2 96 96 1215 104.5 104.5 60 608 167.3 1077 92.6 92.6 101 101 1244 107.0 107.0 62 629 168.4 1104 95.0 95.0 105 105 1273 109.4 109.4 64 64

10 169.6 1132 97.4 97.4 110 110 1302 111.9 111.9 67 6711 170.7 1160 99.8 99.8 115 115 1331 114.4 114.4 69 695 181.4 947 81.4 81.4 80 80 1129 97.0 97.0 53 536 182.7 974 83.7 83.7 84 84 1156 99.4 99.4 55 557 183.9 1000 86.0 86.0 88 88 1184 101.8 101.8 57 578 185.2 1027 88.3 88.3 92 92 1212 104.2 104.2 59 599 186.4 1053 90.6 90.6 97 97 1240 106.6 106.6 62 62

10 187.7 1080 92.9 92.9 101 101 1268 109.0 109.0 64 6411 188.9 1107 95.2 95.2 106 106 1296 111.4 111.4 66 665 199.0 901 77.5 77.5 73 73 1100 94.6 94.6 51 516 200.3 927 79.7 79.7 77 77 1127 96.9 96.9 53 537 201.7 952 81.9 81.9 80 80 1154 99.2 99.2 55 558 203.1 977 84.0 84.0 84 84 1180 101.5 101.5 57 579 204.4 1003 86.2 86.2 88 88 1207 103.8 103.8 59 59

10 205.8 1028 88.4 88.4 92 92 1234 106.1 106.1 61 6111 207.2 1053 90.6 90.6 97 97 1260 108.4 108.4 63 635 206.2 883 75.9 75.9 70 70 1089 93.7 93.7 50 506 207.6 908 78.1 78.1 74 74 1115 95.9 95.9 52 527 209.0 933 80.2 80.2 77 77 1142 98.2 98.2 54 548 210.5 957 82.3 82.3 81 81 1168 100.4 100.4 56 569 211.9 982 84.4 84.4 85 85 1194 102.7 102.7 58 58

10 213.3 1007 86.6 86.6 89 89 1220 104.9 104.9 60 6011 214.7 1032 88.7 88.7 93 93 1246 107.2 107.2 62 62

22

25

30

35

37

CDOTRCUG300WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

40

IPT CCAP CFR

35

37

25

30

CLOT

1kPa = 0.102mAq

Cooling Capacities

CDOT

22

HCAP HFR HPDCPDCLOTRCU300WHYZ(-E)

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃) HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h) CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa) Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser. 2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data” .

3. NO.1, NO.2 at the title row means No.1, No.2 module of the unit separately.

21

SELECTION DATA Conversion Multiplier: 1kW = 860kcal/h

= 3412Btu/h 1kPa = 0.102mAq

NO.1 NO.2 NO.1 NO.2 NO.1 NO.2 NO.1 NO.25 160.1 1173 112.2 89.5 105 95 1333 127.5 101.8 72 576 161.2 1206 115.4 92.1 110 100 1367 130.8 104.4 75 597 162.3 1239 118.5 94.6 115 105 1401 134.0 107.0 78 628 163.4 1272 121.7 97.1 120 110 1435 137.3 109.6 81 649 164.5 1305 124.8 99.6 125 115 1469 140.5 112.1 83 67

10 165.6 1338 128.0 102.1 131 120 1503 143.8 114.7 86 6911 166.7 1371 131.1 104.6 136 126 1537 147.0 117.3 89 725 171.1 1141 109.2 87.1 100 90 1312 125.5 100.2 71 566 172.3 1173 112.2 89.5 105 95 1345 128.7 102.7 73 587 173.4 1205 115.3 92.0 110 99 1379 131.9 105.2 76 608 174.6 1237 118.3 94.4 115 104 1412 135.0 107.8 79 639 175.8 1269 121.4 96.9 120 109 1445 138.2 110.3 81 65

10 177.0 1301 124.5 99.3 125 114 1478 141.4 112.8 84 6711 178.1 1333 127.5 101.7 130 119 1511 144.5 115.3 87 705 189.4 1089 104.1 83.1 92 83 1278 122.2 97.5 68 536 190.7 1119 107.0 85.4 97 87 1310 125.3 100.0 70 567 192.0 1150 110.0 87.7 101 91 1342 128.3 102.4 73 588 193.3 1180 112.9 90.1 106 96 1373 131.4 104.8 75 609 194.6 1211 115.8 92.4 110 100 1405 134.4 107.3 78 62

10 195.9 1241 118.7 94.7 115 105 1437 137.4 109.7 81 6411 197.2 1272 121.6 97.1 120 110 1469 140.5 112.1 83 675 207.6 1036 99.1 79.1 85 76 1244 118.9 94.9 65 516 209.1 1065 101.9 81.3 89 79 1274 121.8 97.2 68 537 210.5 1094 104.6 83.5 93 83 1305 124.8 99.6 70 558 211.9 1123 107.4 85.7 97 87 1335 127.7 101.9 72 579 213.4 1152 110.2 87.9 102 92 1365 130.6 104.2 75 59

10 214.8 1181 113.0 90.1 106 96 1396 133.5 106.5 77 6111 216.2 1210 115.8 92.4 110 100 1426 136.4 108.9 80 645 215.2 1015 97.1 77.4 82 73 1230 117.6 93.9 64 506 216.7 1043 99.8 79.6 86 76 1260 120.5 96.2 66 527 218.2 1072 102.5 81.8 90 80 1290 123.4 98.5 69 548 219.6 1100 105.2 84.0 94 84 1320 126.2 100.7 71 569 221.1 1129 108.0 86.1 98 88 1350 129.1 103.0 74 58

10 222.6 1157 110.7 88.3 102 92 1380 132.0 105.3 76 6011 224.1 1186 113.4 90.5 107 96 1410 134.8 107.6 78 625 231.2 983 94.1 75.0 78 69 1214 116.2 92.7 63 496 232.8 1011 96.7 77.1 81 72 1244 118.9 94.9 65 517 234.4 1038 99.3 79.2 85 76 1273 121.7 97.2 67 538 236.0 1066 102.0 81.4 89 80 1302 124.5 99.4 70 559 237.6 1094 104.6 83.5 93 83 1331 127.3 101.6 72 57

10 239.2 1121 107.2 85.6 97 87 1360 130.1 103.8 74 5911 240.7 1149 109.9 87.7 101 91 1389 132.9 106.1 77 61

NO.1 NO.2 NO.1 NO.2 NO.1 NO.2 NO.1 NO.25 170.6 1137.9 107.9 87.8 98 91 1308 124.0 101.0 69 566 171.8 1169.8 110.9 90.2 103 96 1342 127.1 103.5 72 597 172.9 1201.7 113.9 92.7 107 101 1375 130.3 106.1 75 618 174.1 1233.6 117.0 95.2 112 106 1408 133.4 108.6 77 639 175.3 1265.5 120.0 97.6 117 111 1441 136.5 111.2 80 66

10 176.4 1297.4 123.0 100.1 122 116 1474 139.7 113.7 83 6811 177.6 1329.3 126.0 102.6 128 121 1507 142.8 116.3 85 715 182.3 1106.7 104.9 85.4 93 87 1289 122.1 99.5 68 556 183.5 1137.8 107.9 87.8 98 91 1321 125.2 102.0 70 577 184.8 1168.8 110.8 90.2 103 96 1354 128.3 104.5 73 608 186.1 1199.8 113.8 92.6 107 101 1386 131.3 107.0 75 629 187.3 1230.9 116.7 95.0 112 105 1418 134.4 109.4 78 64

10 188.6 1261.9 119.7 97.4 117 110 1450 137.5 111.9 81 6711 189.8 1292.9 122.6 99.8 122 115 1483 140.5 114.4 83 695 201.8 1055.7 100.1 81.4 86 80 1257 119.1 97.0 65 536 203.2 1085.3 102.9 83.7 90 84 1288 122.1 99.4 68 557 204.5 1114.9 105.7 86.0 95 88 1319 125.0 101.8 70 578 205.9 1144.5 108.5 88.3 99 92 1350 128.0 104.2 73 599 207.3 1174.1 111.3 90.6 103 97 1381 130.9 106.6 75 62

10 208.7 1203.7 114.1 92.9 108 101 1412 133.8 109.0 78 6411 210.1 1233.3 116.9 95.2 112 106 1443 136.8 111.4 80 665 221.3 1004.7 95.3 77.5 79 73 1226 116.2 94.6 63 516 222.8 1032.8 97.9 79.7 83 77 1256 119.0 96.9 65 537 224.3 1061.0 100.6 81.9 87 80 1285 121.8 99.2 68 558 225.8 1089.2 103.3 84.0 91 84 1315 124.6 101.5 70 579 227.3 1117.3 105.9 86.2 95 88 1345 127.4 103.8 72 59

10 228.9 1145.5 108.6 88.4 99 92 1374 130.2 106.1 75 6111 230.4 1173.7 111.3 90.6 103 97 1404 133.0 108.4 77 635 229.3 984.2 93.3 75.9 77 70 1213 115.0 93.7 62 506 230.9 1011.8 95.9 78.1 80 74 1243 117.7 95.9 64 527 232.5 1039.4 98.5 80.2 84 77 1272 120.5 98.2 66 548 234.0 1067.0 101.2 82.3 88 81 1301 123.3 100.4 69 569 235.6 1094.6 103.8 84.4 92 85 1330 126.0 102.7 71 58

10 237.2 1122.2 106.4 86.6 96 89 1359 128.8 104.9 73 6011 238.8 1149.7 109.0 88.7 100 93 1389 131.6 107.2 76 62

37

RCUG340WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

22

25

30

35

37

40

CDOT CLOT

CLOTRCU340WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

Cooling Capacities

CDOT

30

35

22

25

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃) HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h) CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa) Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser. 2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data” .

3. NO.1, NO.2 at the title row means No.1, No.2 module of the unit separately.

22

SELECTION DATA

NO.1 NO.2 NO.1 NO.2 NO.1 NO.2 NO.1 NO.25 178.0 1305 112.2 112.2 105 105 1483 127.5 127.5 72 726 179.2 1342 115.4 115.4 110 110 1521 130.8 130.8 75 757 180.4 1378 118.5 118.5 115 115 1559 134.0 134.0 78 788 181.6 1415 121.7 121.7 120 120 1597 137.3 137.3 81 819 182.9 1452 124.8 124.8 125 125 1634 140.5 140.5 83 83

10 184.1 1488 128.0 128.0 131 131 1672 143.8 143.8 86 8611 185.3 1525 131.1 131.1 136 136 1710 147.0 147.0 89 895 190.2 1269 109.2 109.2 100 100 1460 125.5 125.5 71 716 191.5 1305 112.2 112.2 105 105 1497 128.7 128.7 73 737 192.8 1341 115.3 115.3 110 110 1533 131.9 131.9 76 768 194.1 1376 118.3 118.3 115 115 1570 135.0 135.0 79 799 195.4 1412 121.4 121.4 120 120 1607 138.2 138.2 81 81

10 196.7 1447 124.5 124.5 125 125 1644 141.4 141.4 84 8411 198.0 1483 127.5 127.5 130 130 1681 144.5 144.5 87 875 210.5 1211 104.1 104.1 92 92 1421 122.2 122.2 68 686 211.9 1245 107.0 107.0 97 97 1457 125.3 125.3 70 707 213.4 1279 110.0 110.0 101 101 1492 128.3 128.3 73 738 214.8 1313 112.9 112.9 106 106 1528 131.4 131.4 75 759 216.3 1347 115.8 115.8 110 110 1563 134.4 134.4 78 78

10 217.7 1381 118.7 118.7 115 115 1598 137.4 137.4 81 8111 219.2 1415 121.6 121.6 120 120 1634 140.5 140.5 83 835 230.8 1152 99.1 99.1 85 85 1383 118.9 118.9 65 656 232.4 1185 101.9 101.9 89 89 1417 121.8 121.8 68 687 234.0 1217 104.6 104.6 93 93 1451 124.8 124.8 70 708 235.6 1249 107.4 107.4 97 97 1485 127.7 127.7 72 729 237.2 1282 110.2 110.2 102 102 1519 130.6 130.6 75 75

10 238.8 1314 113.0 113.0 106 106 1553 133.5 133.5 77 7711 240.3 1346 115.8 115.8 110 110 1587 136.4 136.4 80 805 239.2 1129 97.1 97.1 82 82 1368 117.6 117.6 64 646 240.9 1161 99.8 99.8 86 86 1401 120.5 120.5 66 667 242.5 1192 102.5 102.5 90 90 1435 123.4 123.4 69 698 244.2 1224 105.2 105.2 94 94 1468 126.2 126.2 71 719 245.8 1255 108.0 108.0 98 98 1501 129.1 129.1 74 74

10 247.4 1287 110.7 110.7 102 102 1535 132.0 132.0 76 7611 249.1 1319 113.4 113.4 107 107 1568 134.8 134.8 78 785 257.0 1094 94.1 94.1 78 78 1351 116.2 116.2 63 636 258.8 1125 96.7 96.7 81 81 1383 118.9 118.9 65 657 260.6 1155 99.3 99.3 85 85 1416 121.7 121.7 67 678 262.3 1186 102.0 102.0 89 89 1448 124.5 124.5 70 709 264.1 1217 104.6 104.6 93 93 1481 127.3 127.3 72 72

10 265.9 1247 107.2 107.2 97 97 1513 130.1 130.1 74 7411 267.6 1278 109.9 109.9 101 101 1545 132.9 132.9 77 77

NO.1 NO.2 NO.1 NO.2 NO.1 NO.2 NO.1 NO.25 187.3 1255 107.9 107.9 98 98 1442 124.0 124.0 69 696 188.6 1290 110.9 110.9 103 103 1479 127.1 127.1 72 727 189.9 1325 113.9 113.9 107 107 1515 130.3 130.3 75 758 191.2 1360 117.0 117.0 112 112 1552 133.4 133.4 77 779 192.5 1396 120.0 120.0 117 117 1588 136.5 136.5 80 80

10 193.8 1431 123.0 123.0 122 122 1624 139.7 139.7 83 8311 195.0 1466 126.0 126.0 128 128 1661 142.8 142.8 85 855 200.2 1220 104.9 104.9 93 93 1421 122.1 122.1 68 686 201.6 1255 107.9 107.9 98 98 1456 125.2 125.2 70 707 202.9 1289 110.8 110.8 103 103 1492 128.3 128.3 73 738 204.3 1323 113.8 113.8 107 107 1527 131.3 131.3 75 759 205.7 1357 116.7 116.7 112 112 1563 134.4 134.4 78 78

10 207.1 1392 119.7 119.7 117 117 1599 137.5 137.5 81 8111 208.4 1426 122.6 122.6 122 122 1634 140.5 140.5 83 835 221.6 1164 100.1 100.1 86 86 1386 119.1 119.1 65 656 223.1 1197 102.9 102.9 90 90 1420 122.1 122.1 68 687 224.6 1229 105.7 105.7 95 95 1454 125.0 125.0 70 708 226.1 1262 108.5 108.5 99 99 1488 128.0 128.0 73 739 227.6 1295 111.3 111.3 103 103 1522 130.9 130.9 75 75

10 229.2 1327 114.1 114.1 108 108 1557 133.8 133.8 78 7811 230.7 1360 116.9 116.9 112 112 1591 136.8 136.8 80 805 243.0 1108 95.3 95.3 79 79 1351 116.2 116.2 63 636 244.6 1139 97.9 97.9 83 83 1384 119.0 119.0 65 657 246.3 1170 100.6 100.6 87 87 1416 121.8 121.8 68 688 248.0 1201 103.3 103.3 91 91 1449 124.6 124.6 70 709 249.6 1232 105.9 105.9 95 95 1482 127.4 127.4 72 72

10 251.3 1263 108.6 108.6 99 99 1515 130.2 130.2 75 7511 253.0 1294 111.3 111.3 103 103 1547 133.0 133.0 77 775 251.8 1085 93.3 93.3 77 77 1337 115.0 115.0 62 626 253.5 1116 95.9 95.9 80 80 1369 117.7 117.7 64 647 255.3 1146 98.5 98.5 84 84 1401 120.5 120.5 66 668 257.0 1177 101.2 101.2 88 88 1434 123.3 123.3 69 699 258.7 1207 103.8 103.8 92 92 1466 126.0 126.0 71 71

10 260.5 1237 106.4 106.4 96 96 1498 128.8 128.8 73 7311 262.2 1268 109.0 109.0 100 100 1530 131.6 131.6 76 76

Conversion Multiplier: 1kW = 860kcal/h

RCUG380WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

25

30

35

37

40

CDOT CLOT

22

RCU380WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

37

= 3412Btu/h 1kPa = 0.102mAq

Cooling Capacities

30

35

CDOT

22

25

CLOT

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃) HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h) CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa)

Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser.

2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data” .

3. NO.1, NO.2 at the title row means No.1, No.2 module of the unit separately.

23

NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.35 194.3 1424 89.5 89.5 65.7 95 95 119 1618 101.8 101.8 74.7 57 57 726 195.7 1464 92.1 92.1 67.6 100 100 124 1659 104.4 104.4 76.6 59 59 747 197.0 1504 94.6 94.6 69.4 105 105 130 1701 107.0 107.0 78.5 62 62 778 198.3 1543 97.1 97.1 71.3 110 110 135 1742 109.6 109.6 80.4 64 64 809 199.7 1583 99.6 99.6 73.1 115 115 141 1783 112.1 112.1 82.3 67 67 83

10 201.0 1623 102.1 102.1 75.0 120 120 147 1824 114.7 114.7 84.2 69 69 8611 202.3 1663 104.6 104.6 76.8 126 126 152 1866 117.3 117.3 86.1 72 72 885 207.7 1385 87.1 87.1 63.9 90 90 114 1592 100.2 100.2 73.5 56 56 706 209.1 1424 89.5 89.5 65.7 95 95 119 1633 102.7 102.7 75.4 58 58 737 210.5 1462 92.0 92.0 67.5 99 99 124 1673 105.2 105.2 77.2 60 60 758 211.9 1501 94.4 94.4 69.3 104 104 129 1713 107.8 107.8 79.1 63 63 789 213.4 1540 96.9 96.9 71.1 109 109 135 1753 110.3 110.3 81.0 65 65 81

10 214.8 1579 99.3 99.3 72.9 114 114 140 1794 112.8 112.8 82.8 67 67 8311 216.2 1618 101.7 101.7 74.7 119 119 146 1834 115.3 115.3 84.7 70 70 865 229.8 1321 83.1 83.1 61.0 83 83 105 1551 97.5 97.5 71.6 53 53 676 231.4 1358 85.4 85.4 62.7 87 87 110 1589 100.0 100.0 73.4 56 56 707 233.0 1395 87.7 87.7 64.4 91 91 115 1628 102.4 102.4 75.2 58 58 728 234.6 1432 90.1 90.1 66.1 96 96 120 1667 104.8 104.8 76.9 60 60 759 236.1 1469 92.4 92.4 67.8 100 100 125 1705 107.3 107.3 78.7 62 62 77

10 237.7 1506 94.7 94.7 69.6 105 105 130 1744 109.7 109.7 80.5 64 64 8011 239.3 1543 97.1 97.1 71.3 110 110 135 1782 112.1 112.1 82.3 67 67 835 252.0 1257 79.1 79.1 58.1 76 76 97 1509 94.9 94.9 69.7 51 51 656 253.8 1292 81.3 81.3 59.7 79 79 102 1546 97.2 97.2 71.4 53 53 677 255.5 1328 83.5 83.5 61.3 83 83 106 1583 99.6 99.6 73.1 55 55 698 257.2 1363 85.7 85.7 62.9 87 87 111 1620 101.9 101.9 74.8 57 57 729 259.0 1398 87.9 87.9 64.6 92 92 115 1657 104.2 104.2 76.5 59 59 74

10 260.7 1433 90.1 90.1 66.2 96 96 120 1694 106.5 106.5 78.2 61 61 7711 262.4 1468 92.4 92.4 67.8 100 100 125 1731 108.9 108.9 79.9 64 64 795 261.2 1231 77.4 77.4 56.9 73 73 94 1493 93.9 93.9 68.9 50 50 646 263.0 1266 79.6 79.6 58.5 76 76 98 1529 96.2 96.2 70.6 52 52 667 264.8 1300 81.8 81.8 60.1 80 80 103 1565 98.5 98.5 72.3 54 54 688 266.6 1335 84.0 84.0 61.7 84 84 107 1602 100.7 100.7 73.9 56 56 719 268.4 1369 86.1 86.1 63.2 88 88 112 1638 103.0 103.0 75.6 58 58 73

10 270.2 1404 88.3 88.3 64.8 92 92 116 1674 105.3 105.3 77.3 60 60 7511 272.0 1439 90.5 90.5 66.4 96 96 121 1711 107.6 107.6 79.0 62 62 785 280.6 1193 75.0 75.0 55.1 69 69 90 1474 92.7 92.7 68.0 49 49 626 282.6 1227 77.1 77.1 56.6 72 72 94 1509 94.9 94.9 69.7 51 51 657 284.5 1260 79.2 79.2 58.2 76 76 98 1545 97.2 97.2 71.3 53 53 678 286.4 1294 81.4 81.4 59.7 80 80 102 1580 99.4 99.4 72.9 55 55 699 288.4 1327 83.5 83.5 61.3 83 83 106 1615 101.6 101.6 74.6 57 57 72

10 290.3 1360 85.6 85.6 62.8 87 87 111 1651 103.8 103.8 76.2 59 59 7411 292.2 1394 87.7 87.7 64.4 91 91 115 1686 106.1 106.1 77.8 61 61 76

NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.35 209.3 1389.4 87.8 87.8 63.4 91 91 112 1599 100.9 100.9 73.0 56 56 696 210.7 1428.3 90.2 90.2 65.2 96 96 117 1639 103.5 103.5 74.8 59 59 727 212.2 1467.3 92.7 92.7 67.0 101 101 122 1679 106.0 106.0 76.7 61 61 758 213.6 1506.3 95.1 95.1 68.8 106 106 128 1720 108.6 108.6 78.5 63 63 779 215.1 1545.2 97.6 97.6 70.6 111 111 133 1760 111.1 111.1 80.4 66 66 80

10 216.5 1584.2 100.1 100.1 72.3 116 116 138 1801 113.7 113.7 82.2 68 68 8311 217.9 1623.1 102.5 102.5 74.1 121 121 144 1841 116.2 116.2 84.1 71 71 855 223.7 1351.3 85.4 85.4 61.7 87 87 107 1575 99.4 99.4 71.9 55 55 686 225.2 1389.2 87.7 87.7 63.4 91 91 112 1614 101.9 101.9 73.7 57 57 707 226.7 1427.1 90.1 90.1 65.2 96 96 117 1654 104.4 104.4 75.5 60 60 738 228.3 1465.0 92.5 92.5 66.9 101 101 122 1693 106.9 106.9 77.3 62 62 759 229.8 1502.9 94.9 94.9 68.6 105 105 127 1733 109.4 109.4 79.1 64 64 78

10 231.3 1540.8 97.3 97.3 70.4 110 110 132 1772 111.9 111.9 80.9 66 66 8111 232.9 1578.7 99.7 99.7 72.1 115 115 138 1812 114.4 114.4 82.7 69 69 835 247.6 1289.0 81.4 81.4 58.9 80 80 100 1537 97.0 97.0 70.2 53 53 656 249.3 1325.2 83.7 83.7 60.5 84 84 104 1574 99.4 99.4 71.9 55 55 687 251.0 1361.3 86.0 86.0 62.2 88 88 109 1612 101.8 101.8 73.6 57 57 708 252.7 1397.5 88.3 88.3 63.8 92 92 113 1650 104.2 104.2 75.3 59 59 739 254.4 1433.6 90.6 90.6 65.5 97 97 118 1688 106.6 106.6 77.1 61 61 75

10 256.1 1469.8 92.8 92.8 67.1 101 101 123 1726 108.9 108.9 78.8 64 64 7811 257.8 1505.9 95.1 95.1 68.8 106 106 128 1764 111.3 111.3 80.5 66 66 805 271.5 1226.7 77.5 77.5 56.0 73 73 92 1498 94.6 94.6 68.4 51 51 636 273.3 1261.1 79.7 79.7 57.6 77 77 96 1534 96.9 96.9 70.1 53 53 657 275.2 1295.5 81.8 81.8 59.2 80 80 100 1571 99.1 99.1 71.7 55 55 688 277.1 1329.9 84.0 84.0 60.7 84 84 105 1607 101.4 101.4 73.4 57 57 709 278.9 1364.3 86.2 86.2 62.3 88 88 109 1643 103.7 103.7 75.0 59 59 72

10 280.8 1398.7 88.3 88.3 63.9 92 92 113 1680 106.0 106.0 76.7 61 61 7511 282.7 1433.1 90.5 90.5 65.4 97 97 118 1716 108.3 108.3 78.3 63 63 775 281.4 1201.7 75.9 75.9 54.9 70 70 89 1483 93.6 93.6 67.7 50 50 626 283.3 1235.4 78.0 78.0 56.4 74 74 93 1519 95.9 95.9 69.3 52 52 647 285.2 1269.1 80.2 80.2 58.0 77 77 97 1554 98.1 98.1 71.0 54 54 668 287.1 1302.8 82.3 82.3 59.5 81 81 101 1590 100.4 100.4 72.6 56 56 699 289.1 1336.5 84.4 84.4 61.0 85 85 105 1626 102.6 102.6 74.2 58 58 71

10 291.0 1370.2 86.5 86.5 62.6 89 89 110 1661 104.9 104.9 75.9 60 60 7311 292.9 1403.9 88.7 88.7 64.1 93 93 114 1697 107.1 107.1 77.5 62 62 76

CCAP

40

35

Cooling Capacities = 3412Btu/hConversion Multiplier: 1kW = 860kcal/h

22

1kPa = 0.102mAq

CDOTRCU410WHYZ(-E)

IPT

25

30

35

37

HPD

22

25

CFR CPD HCAP HFR

CLOTCDOT

CLOT

37

RCUG410WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

30

SELECTION DATA

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃) HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h) CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa) Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser. 2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data” . 3. NO.1, NO.2, NO.3 at the title row means No.1, No.2, No.3 module of the unit separately.

24

SELECTION DATA

NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.35 213.3 1562 89.5 89.5 89.5 95 95 95 1775 101.8 101.8 101.8 57 57 576 214.8 1606 92.1 92.1 92.1 100 100 100 1821 104.4 104.4 104.4 59 59 597 216.3 1650 94.6 94.6 94.6 105 105 105 1866 107.0 107.0 107.0 62 62 628 217.7 1693 97.1 97.1 97.1 110 110 110 1911 109.6 109.6 109.6 64 64 649 219.2 1737 99.6 99.6 99.6 115 115 115 1956 112.1 112.1 112.1 67 67 6710 220.7 1781 102.1 102.1 102.1 120 120 120 2002 114.7 114.7 114.7 69 69 6911 222.1 1825 104.6 104.6 104.6 126 126 126 2047 117.3 117.3 117.3 72 72 725 228.0 1519 87.1 87.1 87.1 90 90 90 1747 100.2 100.2 100.2 56 56 566 229.5 1562 89.5 89.5 89.5 95 95 95 1791 102.7 102.7 102.7 58 58 587 231.1 1604 92.0 92.0 92.0 99 99 99 1836 105.2 105.2 105.2 60 60 608 232.7 1647 94.4 94.4 94.4 104 104 104 1880 107.8 107.8 107.8 63 63 639 234.2 1690 96.9 96.9 96.9 109 109 109 1924 110.3 110.3 110.3 65 65 6510 235.8 1732 99.3 99.3 99.3 114 114 114 1968 112.8 112.8 112.8 67 67 6711 237.4 1775 101.7 101.7 101.7 119 119 119 2012 115.3 115.3 115.3 70 70 705 252.3 1449 83.1 83.1 83.1 83 83 83 1702 97.5 97.5 97.5 53 53 536 254.1 1490 85.4 85.4 85.4 87 87 87 1744 100.0 100.0 100.0 56 56 567 255.8 1530 87.7 87.7 87.7 91 91 91 1786 102.4 102.4 102.4 58 58 588 257.5 1571 90.1 90.1 90.1 96 96 96 1829 104.8 104.8 104.8 60 60 609 259.3 1612 92.4 92.4 92.4 100 100 100 1871 107.3 107.3 107.3 62 62 6210 261.0 1652 94.7 94.7 94.7 105 105 105 1913 109.7 109.7 109.7 64 64 6411 262.7 1693 97.1 97.1 97.1 110 110 110 1956 112.1 112.1 112.1 67 67 675 276.7 1379 79.1 79.1 79.1 76 76 76 1656 94.9 94.9 94.9 51 51 516 278.6 1418 81.3 81.3 81.3 79 79 79 1696 97.2 97.2 97.2 53 53 537 280.5 1457 83.5 83.5 83.5 83 83 83 1737 99.6 99.6 99.6 55 55 558 282.4 1495 85.7 85.7 85.7 87 87 87 1778 101.9 101.9 101.9 57 57 579 284.3 1534 87.9 87.9 87.9 92 92 92 1818 104.2 104.2 104.2 59 59 5910 286.2 1573 90.1 90.1 90.1 96 96 96 1859 106.5 106.5 106.5 61 61 6111 288.1 1611 92.4 92.4 92.4 100 100 100 1899 108.9 108.9 108.9 64 64 645 286.8 1351 77.4 77.4 77.4 73 73 73 1638 93.9 93.9 93.9 50 50 506 288.7 1389 79.6 79.6 79.6 76 76 76 1678 96.2 96.2 96.2 52 52 527 290.7 1427 81.8 81.8 81.8 80 80 80 1717 98.5 98.5 98.5 54 54 548 292.7 1465 84.0 84.0 84.0 84 84 84 1757 100.7 100.7 100.7 56 56 569 294.6 1503 86.1 86.1 86.1 88 88 88 1797 103.0 103.0 103.0 58 58 5810 296.6 1540 88.3 88.3 88.3 92 92 92 1837 105.3 105.3 105.3 60 60 6011 298.6 1578 90.5 90.5 90.5 96 96 96 1877 107.6 107.6 107.6 62 62 625 308.1 1309 75.0 75.0 75.0 69 69 69 1617 92.7 92.7 92.7 49 49 496 310.2 1346 77.1 77.1 77.1 72 72 72 1656 94.9 94.9 94.9 51 51 517 312.3 1383 79.2 79.2 79.2 76 76 76 1695 97.2 97.2 97.2 53 53 538 314.5 1419 81.4 81.4 81.4 80 80 80 1734 99.4 99.4 99.4 55 55 559 316.6 1456 83.5 83.5 83.5 83 83 83 1772 101.6 101.6 101.6 57 57 5710 318.7 1493 85.6 85.6 85.6 87 87 87 1811 103.8 103.8 103.8 59 59 5911 320.8 1529 87.7 87.7 87.7 91 91 91 1850 106.1 106.1 106.1 61 61 61

NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.35 229.7 1531 87.8 87.8 87.8 91 91 91 1761 100.9 100.9 100.9 56 56 566 231.3 1574 90.2 90.2 90.2 96 96 96 1805 103.5 103.5 103.5 59 59 597 232.8 1617 92.7 92.7 92.7 101 101 101 1850 106.0 106.0 106.0 61 61 618 234.4 1660 95.1 95.1 95.1 106 106 106 1894 108.6 108.6 108.6 63 63 639 236.0 1703 97.6 97.6 97.6 111 111 111 1939 111.1 111.1 111.1 66 66 6610 237.6 1746 100.1 100.1 100.1 116 116 116 1983 113.7 113.7 113.7 68 68 6811 239.2 1789 102.5 102.5 102.5 121 121 121 2028 116.2 116.2 116.2 71 71 715 245.4 1489 85.4 85.4 85.4 87 87 87 1734 99.4 99.4 99.4 55 55 556 247.1 1531 87.7 87.7 87.7 91 91 91 1778 101.9 101.9 101.9 57 57 577 248.8 1573 90.1 90.1 90.1 96 96 96 1821 104.4 104.4 104.4 60 60 608 250.5 1614 92.5 92.5 92.5 101 101 101 1865 106.9 106.9 106.9 62 62 629 252.2 1656 94.9 94.9 94.9 105 105 105 1908 109.4 109.4 109.4 64 64 6410 253.9 1698 97.3 97.3 97.3 110 110 110 1952 111.9 111.9 111.9 66 66 6611 255.6 1740 99.7 99.7 99.7 115 115 115 1995 114.4 114.4 114.4 69 69 695 271.7 1420 81.4 81.4 81.4 80 80 80 1692 97.0 97.0 97.0 53 53 536 273.5 1460 83.7 83.7 83.7 84 84 84 1734 99.4 99.4 99.4 55 55 557 275.4 1500 86.0 86.0 86.0 88 88 88 1775 101.8 101.8 101.8 57 57 578 277.3 1540 88.3 88.3 88.3 92 92 92 1817 104.2 104.2 104.2 59 59 599 279.1 1580 90.6 90.6 90.6 97 97 97 1859 106.6 106.6 106.6 61 61 6110 281.0 1620 92.8 92.8 92.8 101 101 101 1901 108.9 108.9 108.9 64 64 6411 282.9 1659 95.1 95.1 95.1 106 106 106 1942 111.3 111.3 111.3 66 66 665 297.9 1352 77.5 77.5 77.5 73 73 73 1650 94.6 94.6 94.6 51 51 516 300.0 1390 79.7 79.7 79.7 77 77 77 1690 96.9 96.9 96.9 53 53 537 302.0 1428 81.8 81.8 81.8 80 80 80 1730 99.1 99.1 99.1 55 55 558 304.0 1465 84.0 84.0 84.0 84 84 84 1769 101.4 101.4 101.4 57 57 579 306.1 1503 86.2 86.2 86.2 88 88 88 1809 103.7 103.7 103.7 59 59 5910 308.1 1541 88.3 88.3 88.3 92 92 92 1849 106.0 106.0 106.0 61 61 6111 310.2 1579 90.5 90.5 90.5 97 97 97 1889 108.3 108.3 108.3 63 63 635 308.8 1324 75.9 75.9 75.9 70 70 70 1633 93.6 93.6 93.6 50 50 506 310.9 1361 78.0 78.0 78.0 74 74 74 1672 95.9 95.9 95.9 52 52 527 313.0 1398 80.2 80.2 80.2 77 77 77 1711 98.1 98.1 98.1 54 54 548 315.1 1436 82.3 82.3 82.3 81 81 81 1751 100.4 100.4 100.4 56 56 569 317.2 1473 84.4 84.4 84.4 85 85 85 1790 102.6 102.6 102.6 58 58 5810 319.4 1510 86.5 86.5 86.5 89 89 89 1829 104.9 104.9 104.9 60 60 6011 321.5 1547 88.7 88.7 88.7 93 93 93 1868 107.1 107.1 107.1 62 62 62

35

22

CDOT

25

30

CLOT

HCAP HFR HPDCLOTRCU450WHYZ(-E)

IPT CCAP CFR CPD

25

30

35

37

40

CDOT

37

RCUG450WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

22

Cooling Capacities = 3412Btu/h Conversion Multiplier: 1kW = 860kcal/h

1kPa = 0.102mAq

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃) HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h) CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa) Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser. 2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data” . 3. NO.1, NO.2, NO.3 at the title row means No.1, No.2, No.3 module of the unit separately.

25

NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.35 231.2 1694 112.2 89.5 89.5 105 95 95 1925 127.5 101.8 101.8 72 57 576 232.8 1741 115.4 92.1 92.1 110 100 100 1974 130.8 104.4 104.4 75 59 597 234.4 1789 118.5 94.6 94.6 115 105 105 2023 134.0 107.0 107.0 78 62 628 236.0 1836 121.7 97.1 97.1 120 110 110 2072 137.3 109.6 109.6 81 64 649 237.6 1884 124.8 99.6 99.6 125 115 115 2122 140.5 112.1 112.1 83 67 67

10 239.1 1931 128.0 102.1 102.1 131 120 120 2171 143.8 114.7 114.7 86 69 6911 240.7 1979 131.1 104.6 104.6 136 126 126 2220 147.0 117.3 117.3 89 72 725 247.1 1648 109.2 87.1 87.1 100 90 90 1895 125.5 100.2 100.2 71 56 566 248.8 1694 112.2 89.5 89.5 105 95 95 1943 128.7 102.7 102.7 73 58 587 250.5 1740 115.3 92.0 92.0 110 99 99 1990 131.9 105.2 105.2 76 60 608 252.2 1786 118.3 94.4 94.4 115 104 104 2038 135.0 107.8 107.8 79 63 639 253.9 1832 121.4 96.9 96.9 120 109 109 2086 138.2 110.3 110.3 81 65 65

10 255.6 1879 124.5 99.3 99.3 125 114 114 2134 141.4 112.8 112.8 84 67 6711 257.3 1925 127.5 101.7 101.7 130 119 119 2182 144.5 115.3 115.3 87 70 705 273.5 1572 104.1 83.1 83.1 92 83 83 1845 122.2 97.5 97.5 68 53 536 275.3 1616 107.0 85.4 85.4 97 87 87 1891 125.3 100.0 100.0 70 56 567 277.2 1660 110.0 87.7 87.7 101 91 91 1937 128.3 102.4 102.4 73 58 588 279.1 1704 112.9 90.1 90.1 106 96 96 1983 131.4 104.8 104.8 75 60 609 281.0 1748 115.8 92.4 92.4 110 100 100 2029 134.4 107.3 107.3 78 62 62

10 282.9 1792 118.7 94.7 94.7 115 105 105 2075 137.4 109.7 109.7 81 64 6411 284.7 1836 121.6 97.1 97.1 120 110 110 2121 140.5 112.1 112.1 83 67 675 299.9 1496 99.1 79.1 79.1 85 76 76 1795 118.9 94.9 94.9 65 51 516 301.9 1538 101.9 81.3 81.3 89 79 79 1839 121.8 97.2 97.2 68 53 537 304.0 1580 104.6 83.5 83.5 93 83 83 1884 124.8 99.6 99.6 70 55 558 306.1 1621 107.4 85.7 85.7 97 87 87 1928 127.7 101.9 101.9 72 57 579 308.1 1663 110.2 87.9 87.9 102 92 92 1972 130.6 104.2 104.2 75 59 59

10 310.2 1705 113.0 90.1 90.1 106 96 96 2016 133.5 106.5 106.5 77 61 6111 312.2 1747 115.8 92.4 92.4 110 100 100 2060 136.4 108.9 108.9 80 64 645 310.8 1465 97.1 77.4 77.4 82 73 73 1776 117.6 93.9 93.9 64 50 506 312.9 1506 99.8 79.6 79.6 86 76 76 1819 120.5 96.2 96.2 66 52 527 315.1 1547 102.5 81.8 81.8 90 80 80 1862 123.4 98.5 98.5 69 54 548 317.2 1588 105.2 84.0 84.0 94 84 84 1906 126.2 100.7 100.7 71 56 569 319.3 1629 108.0 86.1 86.1 98 88 88 1949 129.1 103.0 103.0 74 58 58

10 321.5 1671 110.7 88.3 88.3 102 92 92 1992 132.0 105.3 105.3 76 60 6011 323.6 1712 113.4 90.5 90.5 107 96 96 2035 134.8 107.6 107.6 78 62 625 333.9 1420 94.1 75.0 75.0 78 69 69 1754 116.2 92.7 92.7 63 49 496 336.2 1459 96.7 77.1 77.1 81 72 72 1796 118.9 94.9 94.9 65 51 517 338.5 1499 99.3 79.2 79.2 85 76 76 1838 121.7 97.2 97.2 67 53 538 340.8 1539 102.0 81.4 81.4 89 80 80 1880 124.5 99.4 99.4 70 55 559 343.1 1579 104.6 83.5 83.5 93 83 83 1922 127.3 101.6 101.6 72 57 57

10 345.4 1619 107.2 85.6 85.6 97 87 87 1964 130.1 103.8 103.8 74 59 5911 347.7 1659 109.9 87.7 87.7 101 91 91 2006 132.9 106.1 106.1 77 61 61

NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.35 247.1 1648.4 107.9 87.8 87.8 98 91 91 1895 124.0 100.9 100.9 69 56 566 248.8 1694.6 110.9 90.2 90.2 103 96 96 1943 127.1 103.5 103.5 72 59 597 250.5 1740.8 113.9 92.7 92.7 107 101 101 1991 130.2 106.0 106.0 75 61 618 252.2 1787.0 116.9 95.1 95.1 112 106 106 2039 133.4 108.6 108.6 77 63 639 253.9 1833.3 120.0 97.6 97.6 117 111 111 2087 136.5 111.1 111.1 80 66 66

10 255.6 1879.5 123.0 100.1 100.1 122 116 116 2135 139.6 113.7 113.7 83 68 6811 257.3 1925.7 126.0 102.5 102.5 128 121 121 2183 142.8 116.2 116.2 85 71 715 264.1 1603.2 104.9 85.4 85.4 93 87 87 1867 122.1 99.4 99.4 68 55 556 265.9 1648.2 107.9 87.7 87.7 98 91 91 1914 125.2 101.9 101.9 70 57 577 267.7 1693.2 110.8 90.1 90.1 102 96 96 1961 128.2 104.4 104.4 73 60 608 269.5 1738.1 113.7 92.5 92.5 107 101 101 2008 131.3 106.9 106.9 75 62 629 271.3 1783.1 116.7 94.9 94.9 112 105 105 2054 134.4 109.4 109.4 78 64 64

10 273.1 1828.0 119.6 97.3 97.3 117 110 110 2101 137.4 111.9 111.9 81 66 6611 274.9 1873.0 122.6 99.7 99.7 122 115 115 2148 140.5 114.4 114.4 83 69 695 292.3 1529.3 100.1 81.4 81.4 86 80 80 1822 119.1 97.0 97.0 65 53 536 294.3 1572.2 102.9 83.7 83.7 90 84 84 1866 122.1 99.4 99.4 68 55 557 296.3 1615.1 105.7 86.0 86.0 95 88 88 1911 125.0 101.8 101.8 70 57 578 298.3 1658.0 108.5 88.3 88.3 99 92 92 1956 127.9 104.2 104.2 73 59 599 300.3 1700.9 111.3 90.6 90.6 103 97 97 2001 130.9 106.6 106.6 75 61 61

10 302.3 1743.7 114.1 92.8 92.8 108 101 101 2046 133.8 108.9 108.9 78 64 6411 304.3 1786.6 116.9 95.1 95.1 112 106 106 2091 136.7 111.3 111.3 80 66 665 320.5 1455.4 95.2 77.5 77.5 79 73 73 1776 116.1 94.6 94.6 63 51 516 322.7 1496.2 97.9 79.7 79.7 83 77 77 1819 118.9 96.9 96.9 65 53 537 324.9 1537.0 100.6 81.8 81.8 87 80 80 1862 121.8 99.1 99.1 68 55 558 327.1 1577.8 103.2 84.0 84.0 91 84 84 1905 124.6 101.4 101.4 70 57 579 329.3 1618.6 105.9 86.2 86.2 95 88 88 1948 127.4 103.7 103.7 72 59 59

10 331.5 1659.4 108.6 88.3 88.3 99 92 92 1991 130.2 106.0 106.0 74 61 6111 333.7 1700.3 111.3 90.5 90.5 103 97 97 2034 133.0 108.3 108.3 77 63 635 332.2 1425.7 93.3 75.9 75.9 77 70 70 1758 114.9 93.6 93.6 62 50 506 334.4 1465.7 95.9 78.0 78.0 80 74 74 1800 117.7 95.9 95.9 64 52 527 336.7 1505.6 98.5 80.2 80.2 84 77 77 1842 120.5 98.1 98.1 66 54 548 339.0 1545.6 101.1 82.3 82.3 88 81 81 1885 123.2 100.4 100.4 69 56 569 341.3 1585.6 103.8 84.4 84.4 92 85 85 1927 126.0 102.6 102.6 71 58 58

10 343.6 1625.6 106.4 86.5 86.5 96 89 89 1969 128.8 104.9 104.9 73 60 6011 345.9 1665.6 109.0 88.7 88.7 100 93 93 2011 131.5 107.1 107.1 76 62 62

Conversion Multiplier: 1kW = 860kcal/h = 3412Btu/h

1kPa = 0.102mAq

Cooling Capacities

37

RCUG490WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

22

25

30

35

37

40

CDOT CLOT

22

25

30

35

CDOT CLOTRCU490WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃) HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h) CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa) Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser. 2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data” . 3. NO.1, NO.2, NO.3 at the title row means No.1, No.2, No.3 module of the unit separately.

SELECTION DATA

26

NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.35 249.1 1826 112.2 112.2 89.5 105 105 95 2075 127.5 127.5 101.8 72 72 576 250.8 1877 115.4 115.4 92.1 110 110 100 2128 130.8 130.8 104.4 75 75 597 252.5 1928 118.5 118.5 94.6 115 115 105 2181 134.0 134.0 107.0 78 78 628 254.2 1979 121.7 121.7 97.1 120 120 110 2234 137.3 137.3 109.6 81 81 649 255.9 2031 124.8 124.8 99.6 125 125 115 2287 140.5 140.5 112.1 83 83 67

10 257.6 2082 128.0 128.0 102.1 131 131 120 2339 143.8 143.8 114.7 86 86 6911 259.3 2133 131.1 131.1 104.6 136 136 126 2392 147.0 147.0 117.3 89 89 725 266.2 1776 109.2 109.2 87.1 100 100 90 2042 125.5 125.5 100.2 71 71 566 268.0 1826 112.2 112.2 89.5 105 105 95 2094 128.7 128.7 102.7 73 73 587 269.8 1875 115.3 115.3 92.0 110 110 99 2145 131.9 131.9 105.2 76 76 608 271.7 1925 118.3 118.3 94.4 115 115 104 2197 135.0 135.0 107.8 79 79 639 273.5 1975 121.4 121.4 96.9 120 120 109 2249 138.2 138.2 110.3 81 81 65

10 275.3 2025 124.5 124.5 99.3 125 125 114 2300 141.4 141.4 112.8 84 84 6711 277.1 2075 127.5 127.5 101.7 130 130 119 2352 144.5 144.5 115.3 87 87 705 294.6 1694 104.1 104.1 83.1 92 92 83 1989 122.2 122.2 97.5 68 68 536 296.6 1741 107.0 107.0 85.4 97 97 87 2038 125.3 125.3 100.0 70 70 567 298.6 1789 110.0 110.0 87.7 101 101 91 2088 128.3 128.3 102.4 73 73 588 300.7 1836 112.9 112.9 90.1 106 106 96 2137 131.4 131.4 104.8 75 75 609 302.7 1884 115.8 115.8 92.4 110 110 100 2187 134.4 134.4 107.3 78 78 62

10 304.7 1931 118.7 118.7 94.7 115 115 105 2236 137.4 137.4 109.7 81 81 6411 306.7 1979 121.6 121.6 97.1 120 120 110 2286 140.5 140.5 112.1 83 83 675 323.1 1612 99.1 99.1 79.1 85 85 76 1935 118.9 118.9 94.9 65 65 516 325.3 1657 101.9 101.9 81.3 89 89 79 1983 121.8 121.8 97.2 68 68 537 327.5 1703 104.6 104.6 83.5 93 93 83 2030 124.8 124.8 99.6 70 70 558 329.7 1748 107.4 107.4 85.7 97 97 87 2077 127.7 127.7 101.9 72 72 579 331.9 1793 110.2 110.2 87.9 102 102 92 2125 130.6 130.6 104.2 75 75 59

10 334.2 1838 113.0 113.0 90.1 106 106 96 2172 133.5 133.5 106.5 77 77 6111 336.4 1883 115.8 115.8 92.4 110 110 100 2220 136.4 136.4 108.9 80 80 645 334.8 1579 97.1 97.1 77.4 82 82 73 1914 117.6 117.6 93.9 64 64 506 337.1 1623 99.8 99.8 79.6 86 86 76 1961 120.5 120.5 96.2 66 66 527 339.4 1668 102.5 102.5 81.8 90 90 80 2007 123.4 123.4 98.5 69 69 548 341.7 1712 105.2 105.2 84.0 94 94 84 2054 126.2 126.2 100.7 71 71 569 344.0 1756 108.0 108.0 86.1 98 98 88 2100 129.1 129.1 103.0 74 74 58

10 346.3 1801 110.7 110.7 88.3 102 102 92 2147 132.0 132.0 105.3 76 76 6011 348.6 1845 113.4 113.4 90.5 107 107 96 2194 134.8 134.8 107.6 78 78 625 359.7 1530 94.1 94.1 75.0 78 78 69 1890 116.2 116.2 92.7 63 63 496 362.2 1573 96.7 96.7 77.1 81 81 72 1935 118.9 118.9 94.9 65 65 517 364.7 1616 99.3 99.3 79.2 85 85 76 1981 121.7 121.7 97.2 67 67 538 367.1 1659 102.0 102.0 81.4 89 89 80 2026 124.5 124.5 99.4 70 70 559 369.6 1702 104.6 104.6 83.5 93 93 83 2071 127.3 127.3 101.6 72 72 57

10 372.1 1745 107.2 107.2 85.6 97 97 87 2117 130.1 130.1 103.8 74 74 5911 374.6 1788 109.9 109.9 87.7 101 101 91 2162 132.9 132.9 106.1 77 77 61

NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.35 264.7 1764.7 107.9 107.9 87.8 98 98 91 2029 124.0 124.0 100.9 69 69 566 266.5 1814.2 110.9 110.9 90.2 103 103 96 2081 127.1 127.1 103.5 72 72 597 268.3 1863.7 113.9 113.9 92.7 107 107 101 2132 130.2 130.2 106.0 75 75 618 270.1 1913.2 116.9 116.9 95.1 112 112 106 2183 133.4 133.4 108.6 77 77 639 271.9 1962.7 120.0 120.0 97.6 117 117 111 2235 136.5 136.5 111.1 80 80 66

10 273.8 2012.2 123.0 123.0 100.1 122 122 116 2286 139.6 139.6 113.7 83 83 6811 275.6 2061.7 126.0 126.0 102.5 128 128 121 2337 142.8 142.8 116.2 85 85 715 282.8 1716.4 104.9 104.9 85.4 93 93 87 1999 122.1 122.1 99.4 68 68 556 284.8 1764.6 107.9 107.9 87.7 98 98 91 2049 125.2 125.2 101.9 70 70 577 286.7 1812.7 110.8 110.8 90.1 102 102 96 2099 128.2 128.2 104.4 73 73 608 288.7 1860.8 113.7 113.7 92.5 107 107 101 2149 131.3 131.3 106.9 75 75 629 290.6 1909.0 116.7 116.7 94.9 112 112 105 2200 134.4 134.4 109.4 78 78 64

10 292.5 1957.1 119.6 119.6 97.3 117 117 110 2250 137.4 137.4 111.9 81 81 6611 294.5 2005.2 122.6 122.6 99.7 122 122 115 2300 140.5 140.5 114.4 83 83 695 313.0 1637.3 100.1 100.1 81.4 86 86 80 1950 119.1 119.1 97.0 65 65 536 315.2 1683.2 102.9 102.9 83.7 90 90 84 1998 122.1 122.1 99.4 68 68 557 317.3 1729.1 105.7 105.7 86.0 95 95 88 2046 125.0 125.0 101.8 70 70 578 319.5 1775.0 108.5 108.5 88.3 99 99 92 2095 127.9 127.9 104.2 73 73 599 321.6 1820.9 111.3 111.3 90.6 103 103 97 2143 130.9 130.9 106.6 75 75 61

10 323.8 1866.9 114.1 114.1 92.8 108 108 101 2191 133.8 133.8 108.9 78 78 6411 325.9 1912.8 116.9 116.9 95.1 112 112 106 2239 136.7 136.7 111.3 80 80 665 343.3 1558.1 95.2 95.2 77.5 79 79 73 1901 116.1 116.1 94.6 63 63 516 345.6 1601.8 97.9 97.9 79.7 83 83 77 1947 118.9 118.9 96.9 65 65 537 348.0 1645.5 100.6 100.6 81.8 87 87 80 1994 121.8 121.8 99.1 68 68 558 350.4 1689.2 103.2 103.2 84.0 91 91 84 2040 124.6 124.6 101.4 70 70 579 352.7 1732.9 105.9 105.9 86.2 95 95 88 2086 127.4 127.4 103.7 72 72 59

10 355.1 1776.6 108.6 108.6 88.3 99 99 92 2132 130.2 130.2 106.0 74 74 6111 357.4 1820.3 111.3 111.3 90.5 103 103 97 2178 133.0 133.0 108.3 77 77 635 355.8 1526.3 93.3 93.3 75.9 77 77 70 1882 114.9 114.9 93.6 62 62 506 358.2 1569.1 95.9 95.9 78.0 80 80 74 1927 117.7 117.7 95.9 64 64 527 360.7 1611.9 98.5 98.5 80.2 84 84 77 1973 120.5 120.5 98.1 66 66 548 363.1 1654.8 101.1 101.1 82.3 88 88 81 2018 123.2 123.2 100.4 69 69 569 365.6 1697.6 103.8 103.8 84.4 92 92 85 2063 126.0 126.0 102.6 71 71 58

10 368.0 1740.4 106.4 106.4 86.5 96 96 89 2108 128.8 128.8 104.9 73 73 6011 370.4 1783.2 109.0 109.0 88.7 100 100 93 2154 131.5 131.5 107.1 76 76 62

Conversion Multiplier: 1kW = 860kcal/h = 3412Btu/h

1kPa = 0.102mAq

Cooling Capacities

37

RCUG530WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

22

25

30

35

37

40

CDOT CLOT

CPD HCAPCDOT

35

30

CLOTRCU530WHYZ(-E)

IPT HFR HPD

22

25

CCAP CFR

SELECTION DATA

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃) HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h) CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa) Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser. 2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data” . 3. NO.1, NO.2, NO.3 at the title row means No.1, No.2, No.3 module of the unit separately.

27

NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.35 267.0 1958 112.2 112.2 112.2 105 105 105 2225 127.5 127.5 127.5 72 72 726 268.8 2013 115.4 115.4 115.4 110 110 110 2281 130.8 130.8 130.8 75 75 757 270.6 2068 118.5 118.5 118.5 115 115 115 2338 134.0 134.0 134.0 78 78 788 272.5 2122 121.7 121.7 121.7 120 120 120 2395 137.3 137.3 137.3 81 81 819 274.3 2177 124.8 124.8 124.8 125 125 125 2452 140.5 140.5 140.5 83 83 83

10 276.1 2232 128.0 128.0 128.0 131 131 131 2508 143.8 143.8 143.8 86 86 8611 278.0 2287 131.1 131.1 131.1 136 136 136 2565 147.0 147.0 147.0 89 89 895 285.3 1904 109.2 109.2 109.2 100 100 100 2189 125.5 125.5 125.5 71 71 716 287.2 1958 112.2 112.2 112.2 105 105 105 2245 128.7 128.7 128.7 73 73 737 289.2 2011 115.3 115.3 115.3 110 110 110 2300 131.9 131.9 131.9 76 76 768 291.1 2064 118.3 118.3 118.3 115 115 115 2356 135.0 135.0 135.0 79 79 799 293.1 2118 121.4 121.4 121.4 120 120 120 2411 138.2 138.2 138.2 81 81 81

10 295.1 2171 124.5 124.5 124.5 125 125 125 2466 141.4 141.4 141.4 84 84 8411 297.0 2225 127.5 127.5 127.5 130 130 130 2522 144.5 144.5 144.5 87 87 875 315.7 1816 104.1 104.1 104.1 92 92 92 2132 122.2 122.2 122.2 68 68 686 317.9 1867 107.0 107.0 107.0 97 97 97 2185 125.3 125.3 125.3 70 70 707 320.1 1918 110.0 110.0 110.0 101 101 101 2238 128.3 128.3 128.3 73 73 738 322.2 1969 112.9 112.9 112.9 106 106 106 2291 131.4 131.4 131.4 75 75 759 324.4 2020 115.8 115.8 115.8 110 110 110 2345 134.4 134.4 134.4 78 78 78

10 326.6 2071 118.7 118.7 118.7 115 115 115 2398 137.4 137.4 137.4 81 81 8111 328.7 2122 121.6 121.6 121.6 120 120 120 2451 140.5 140.5 140.5 83 83 835 346.2 1729 99.1 99.1 99.1 85 85 85 2075 118.9 118.9 118.9 65 65 656 348.6 1777 101.9 101.9 101.9 89 89 89 2126 121.8 121.8 121.8 68 68 687 351.0 1826 104.6 104.6 104.6 93 93 93 2177 124.8 124.8 124.8 70 70 708 353.4 1874 107.4 107.4 107.4 97 97 97 2227 127.7 127.7 127.7 72 72 729 355.8 1922 110.2 110.2 110.2 102 102 102 2278 130.6 130.6 130.6 75 75 75

10 358.1 1971 113.0 113.0 113.0 106 106 106 2329 133.5 133.5 133.5 77 77 7711 360.5 2019 115.8 115.8 115.8 110 110 110 2380 136.4 136.4 136.4 80 80 805 358.8 1693 97.1 97.1 97.1 82 82 82 2052 117.6 117.6 117.6 64 64 646 361.3 1741 99.8 99.8 99.8 86 86 86 2102 120.5 120.5 120.5 66 66 667 363.8 1788 102.5 102.5 102.5 90 90 90 2152 123.4 123.4 123.4 69 69 698 366.2 1836 105.2 105.2 105.2 94 94 94 2202 126.2 126.2 126.2 71 71 719 368.7 1883 108.0 108.0 108.0 98 98 98 2252 129.1 129.1 129.1 74 74 74

10 371.2 1931 110.7 110.7 110.7 102 102 102 2302 132.0 132.0 132.0 76 76 7611 373.6 1978 113.4 113.4 113.4 107 107 107 2352 134.8 134.8 134.8 78 78 785 385.5 1641 94.1 94.1 94.1 78 78 78 2026 116.2 116.2 116.2 63 63 636 388.2 1687 96.7 96.7 96.7 81 81 81 2075 118.9 118.9 118.9 65 65 657 390.8 1733 99.3 99.3 99.3 85 85 85 2124 121.7 121.7 121.7 67 67 678 393.5 1779 102.0 102.0 102.0 89 89 89 2172 124.5 124.5 124.5 70 70 709 396.1 1825 104.6 104.6 104.6 93 93 93 2221 127.3 127.3 127.3 72 72 72

10 398.8 1871 107.2 107.2 107.2 97 97 97 2270 130.1 130.1 130.1 74 74 7411 401.4 1917 109.9 109.9 109.9 101 101 101 2318 132.9 132.9 132.9 77 77 77

NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.3 NO.1 NO.2 NO.35 281.0 1882 107.9 107.9 107.9 98 98 98 2163 124.0 124.0 124.0 69 69 696 283.0 1934 110.9 110.9 110.9 103 103 103 2217 127.1 127.1 127.1 72 72 727 284.9 1987 113.9 113.9 113.9 107 107 107 2272 130.2 130.2 130.2 75 75 758 286.8 2040 116.9 116.9 116.9 112 112 112 2327 133.4 133.4 133.4 77 77 779 288.7 2093 120.0 120.0 120.0 117 117 117 2381 136.5 136.5 136.5 80 80 80

10 290.7 2145 123.0 123.0 123.0 122 122 122 2436 139.6 139.6 139.6 83 83 8311 292.6 2198 126.0 126.0 126.0 128 128 128 2491 142.8 142.8 142.8 85 85 855 300.3 1830 104.9 104.9 104.9 93 93 93 2130 122.1 122.1 122.1 68 68 686 302.4 1881 107.9 107.9 107.9 98 98 98 2184 125.2 125.2 125.2 70 70 707 304.4 1933 110.8 110.8 110.8 102 102 102 2237 128.2 128.2 128.2 73 73 738 306.5 1984 113.7 113.7 113.7 107 107 107 2291 131.3 131.3 131.3 75 75 759 308.6 2035 116.7 116.7 116.7 112 112 112 2344 134.4 134.4 134.4 78 78 78

10 310.6 2087 119.6 119.6 119.6 117 117 117 2397 137.4 137.4 137.4 81 81 8111 312.7 2138 122.6 122.6 122.6 122 122 122 2451 140.5 140.5 140.5 83 83 835 332.4 1746 100.1 100.1 100.1 86 86 86 2078 119.1 119.1 119.1 65 65 656 334.7 1795 102.9 102.9 102.9 90 90 90 2129 122.1 122.1 122.1 68 68 687 336.9 1844 105.7 105.7 105.7 95 95 95 2181 125.0 125.0 125.0 70 70 708 339.2 1893 108.5 108.5 108.5 99 99 99 2232 127.9 127.9 127.9 73 73 739 341.5 1942 111.3 111.3 111.3 103 103 103 2283 130.9 130.9 130.9 75 75 75

10 343.8 1991 114.1 114.1 114.1 108 108 108 2334 133.8 133.8 133.8 78 78 7811 346.1 2039 116.9 116.9 116.9 112 112 112 2386 136.7 136.7 136.7 80 80 805 364.5 1661 95.2 95.2 95.2 79 79 79 2026 116.1 116.1 116.1 63 63 636 367.0 1708 97.9 97.9 97.9 83 83 83 2075 118.9 118.9 118.9 65 65 657 369.5 1755 100.6 100.6 100.6 87 87 87 2124 121.8 121.8 121.8 68 68 688 372.0 1801 103.2 103.2 103.2 91 91 91 2173 124.6 124.6 124.6 70 70 709 374.5 1848 105.9 105.9 105.9 95 95 95 2222 127.4 127.4 127.4 72 72 72

10 377.0 1894 108.6 108.6 108.6 99 99 99 2271 130.2 130.2 130.2 74 74 7411 379.5 1941 111.3 111.3 111.3 103 103 103 2320 133.0 133.0 133.0 77 77 775 377.8 1627 93.3 93.3 93.3 77 77 77 2005 114.9 114.9 114.9 62 62 626 380.4 1673 95.9 95.9 95.9 80 80 80 2053 117.7 117.7 117.7 64 64 647 382.9 1719 98.5 98.5 98.5 84 84 84 2102 120.5 120.5 120.5 66 66 668 385.5 1764 101.1 101.1 101.1 88 88 88 2150 123.2 123.2 123.2 69 69 699 388.1 1810 103.8 103.8 103.8 92 92 92 2198 126.0 126.0 126.0 71 71 71

10 390.7 1856 106.4 106.4 106.4 96 96 96 2246 128.8 128.8 128.8 73 73 7311 393.3 1901 109.0 109.0 109.0 100 100 100 2295 131.5 131.5 131.5 76 76 76

Conversion Multiplier: 1kW = 860kcal/h= 3412Btu/h

1kPa = 0.102mAq

Cooling Capacities

RCUG570WHYZ(-E)

IPT CCAP CFR CPD HCAP HFR HPD

25

30

35

37

40

CDOT CLOT

22

37

HCAP HFR HPD

22

CDOT CLOTRCU570WHYZ(-E)

IPT CCAP CPD

25

30

35

CFR

SELECTION DATA

CDOT: Condenser Water Outlet Temperature (℃) CFR: Chilled Water Flow Rate (m3/h) CLOT: Chilled Water Outlet Temperature (℃) HCAP: Condenser Heat Ejection (kW) IPT: Compressor Power Input (kW) HFR: Condenser Water Flow Rate (m3/h) CCAP: Cooling Capacity (kW) CPD: Cooler Pressure Drop (kPa) HPD: Condenser Pressure Drop (kPa) Note: 1 The chilled water flow rate and the condenser water flow rate are based on 5℃ of temperature difference between the outlet and inlet of the water cooler or the condenser. 2 The data circled by lines at 35℃ of CDOT and 7℃ of CLOT are based on the condition indicated in the “General Data” . 3. NO.1, NO.2, NO.3 at the title row means No.1, No.2, No.3 module of the unit separately.

28

Working Range Power Supply The applicable voltage range for each unit is given in the electrical data. The working voltage among the three phases must be balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the Rated voltage. Temperature Range

Condenser Water Outlet Temperature R22 : 22℃ to 40℃ R407C : 22℃ to 37℃ Chilled Water Outlet Temperature 5 ℃ to 20℃

Maximum Water Flow Rate and Minimum Water Flow Rate (m3/h)

MCF: Maximum Condenser Water Flow Rate, (m3/h) MEF: Maximum Chilled Water Flow Rate (m3/h) mef: Minimum Chilled Water Flow Rate (m3/h)

Internal Water Volume of Water Cooler (m3)

Model Volume(m3) Model Volume(m3)

(No.1/No.2) Model Volume(m3)

(No.1/No.2/No.3) RCU(G)40WHYZ(-E) 0.08 RCU(G)150WHYZ(-E) 0.21 RCU(G)380WHYZ(-E) 0.16 / 0.16

RCU(G)50WHYZ(-E) 0.07 RCU(G)180WHYZ(-E) 0.20 RCU(G)410WHYZ(-E) 0.19 / 0.19 / 0.11

RCU(G)60WHYZ(-E) 0.07 RCU(G)220WHYZ(-E) 0.11 / 0.11 RCU(G)450WHYZ(-E) 0.19 / 0.19 / 0.19

RCU(G)80WHYZ(-E) 0.16 RCU(G)260WHYZ(-E) 0.19 / 0.11 RCU(G)490WHYZ(-E) 0.16 / 0.19 / 0.19

RCU(G)100WHYZ(-E) 0.14 RCU(G)300WHYZ(-E) 0.19 / 0.19 RCU(G)530WHYZ(-E) 0.16 / 0.16 / 0.19

RCU(G)120WHYZ(-E) 0.13 RCU(G)340WHYZ(-E) 0.16 / 0.19 RCU(G)570WHYZ(-E) 0.16 / 0.16 / 0.16 Minimum Internal System Water Volume (m3)

Model Volume(m3

) Model Volume(m3)

(No.1/No.2) Model Volume(m3)

(No.1/No.2/No.3)RCU(G)40WHYZ(-E) 0.5 RCU(G)150WHYZ(-E) 1.85 RCU(G)380WHYZ(-E) 2.18 / 2.18

RCU(G)50WHYZ(-E) 0.62 RCU(G)180WHYZ(-E) 2.28 RCU(G)410WHYZ(-E) 1.74 / 1.74 / 1.28

RCU(G)60WHYZ(-E) 0.76 RCU(G)220WHYZ(-E) 1.28 /1.28 RCU(G)450WHYZ(-E) 1.74 / 1.74 / 1.74

RCU(G)80WHYZ(-E) 1.00 RCU(G)260WHYZ(-E) 1.74 / 1.28 RCU(G)490WHYZ(-E) 2.18 / 1.74 / 1.74

RCU(G)100WHYZ(-E) 1.23 RCU(G)300WHYZ(-E) 1.74 / 1.74 RCU(G)530WHYZ(-E) 2.18 / 2.18 / 1.74

RCU(G)120WHYZ(-E) 1.52 RCU(G)340WHYZ(-E) 2.18 / 1.74 RCU(G)570WHYZ(-E) 2.18 / 2.18 / 2.18 Note: The above minimum internal system water volume is based on the setting of the neutral zone temperature。In case of changing the

setting, minimum internal system water volume shall be increased as follows.

Neutral Zone Temperature Setting Minimum System Water Volume

2℃(Standard) 100%

1.5℃ 130%

1℃ 200%

WORKING RANGE

Model MCF MEF mef Model MCF(No.1/No.2/No.3) MEF(No.1/No.2/No.3) mef(No.1/No.2/No.3)

RCU(G)40WHYZ(-E) 38 42 15 RCU(G)220WHYZ(-E) 87.5 / 87.5 73.5 / 73.5 30.5 / 30.5

RCU(G)50WHYZ(-E) 49 49 17 RCU(G)260WHYZ(-E) 119.5 / 87.5 100 / 73.5 42 / 30.5

RCU(G)60WHYZ(-E) 55 53 17 RCU(G)300WHYZ(-E) 119.5 / 119.5 100 / 100 42 / 42

RCU(G)80WHYZ(-E) 76 83 29 RCU(G)340WHYZ(-E) 152.5 / 119.5 125.5 / 100 52.5 / 42

RCU(G)100WHYZ(-E) 94 97 33 RCU(G)380WHYZ(-E) 152.5 / 152.5 125.5 / 125.5 52.5 / 52.5

RCU(G)120WHYZ(-E) 110 105 33 RCU(G)410WHYZ(-E) 119.5 / 119.5 / 87.5 100 / 100 /73.5 42 / 42 / 30.5

RCU(G)150WHYZ(-E) 144 127 52 RCU(G)450WHYZ(-E) 119.5 / 119.5 / 119.5 100 / 100 / 100 42 / 42 / 42

RCU(G)180WHYZ(-E) 170 143 52 RCU(G)490WHYZ(-E) 152.5 / 119.5 / 119.5 125.5 / 100 / 100 52.5 / 42 / 42

RCU(G)530WHYZ(-E) 152.5 / 152.5 / 119.5 125.5 / 125.5 / 100 52.5 / 52.5 / 42

RCU(G)570WHYZ(-E) 152.5 / 152.5 / 152.5 125.5 / 125.5 / 125.5 52.5 / 52.5 / 52.5

29

Electrical Data

(For working voltage:380V) Notes: 1. The data above are based on the following conditions: Chilled Water Inlet Temperature : 12℃ Chilled Water Outlet Temperature : 7℃ Condenser Water Inlet Temperature : 30℃ Condenser Water Outlet Temperature : 35℃

ELECTRICAL DATA

2. The mentioned above in the “maximum Unit Current” indicates the total running current of the unit under the following conditions .The design of power supply line should be decided referring to these current: Supplied Voltage : 90% of Rated Voltage Condenser Water Outlet Temperature : 40 ℃(R407C:37℃) Chilled Water Outlet Temperature : 20℃ Capacity Control :100%

VOL: Unit Power Supply (Rated) Hz: Frequency (Hz) STC: Starting Current (A) (For each cycle) RNC: Running Current (A) IPT: Input (kW)

Maximum Unit Current

VOL Hz Max. Min. STC(No.1/No.2/No.3)

RNC(No.1/No.2/No.3)

IPT(No.1/No.2/No.3)

Maximum(No.1/No.2/No.3)

RCU 40WHYZ(-E) 380 50 418 342 114 46 27 68

RCUG40WHYZ(-E) 380 50 418 342 114 50 29.5 75

RCU 50WHYZ(-E) 380 50 418 342 148 57 33.5 85

RCUG50WHYZ(-E) 380 50 418 342 148 62 36.7 93

RCU 60WHYZ(-E) 380 50 418 342 178 70 41.5 105

RCUG60WHYZ(-E) 380 50 418 342 178 75 44.3 112

RCU 80WHYZ(-E) 380 50 418 342 114 / 114 46/46 27/27 68/68

RCUG80WHYZ(-E) 380 50 418 342 114 / 114 50/50 29.5/29.5 75/75

RCU 100WHYZ(-E) 380 50 418 342 148 / 148 57/57 33.5/33.5 85/85

RCUG100WHYZ(-E) 380 50 418 342 148 / 148 62/62 36.7/36.7 93/93

RCU 120WHYZ(-E) 380 50 418 342 178 / 178 70/70 41.5/41.5 105/105

RCUG120WHYZ(-E) 380 50 418 342 178 / 178 75/75 44.3/44.3 112/112

RCU 150WHYZ(-E) 380 50 418 342 148 / 148 / 148 57/57/57 33.5/33.5/33.5 85/85/85

RCUG150WHYZ(-E) 380 50 418 342 148 / 148 / 148 62/62/62 36.7/36.7/36.7 93/93/93

RCU 180WHYZ(-E) 380 50 418 342 178 / 178 / 178 70/70/70 41.5/41.5/41.5 105/105/105

RCUG180WHYZ(-E) 380 50 418 342 178 / 178 / 178 75/75/75 44.3/44.3/44.3 112/112/112

RCU 220WHYZ(-E) 380 50 418 342 226 / 226 116 / 116 68.5 / 68.5 165 / 165

RCUG220WHYZ(-E) 380 50 418 342 226 / 226 123 / 123 73.1 / 73.1 182 / 182

RCU 260WHYZ(-E) 380 50 418 342 336 / 226 158 / 116 93.5 / 68.5 225 / 165

RCUG260WHYZ(-E) 380 50 418 342 336 / 226 170 / 123 100.9 / 73.1 242 / 182

RCU 300WHYZ(-E) 380 50 418 342 336 / 336 158 / 158 93.5 / 93.5 225 / 225

RCUG300WHYZ(-E) 380 50 418 342 336 / 336 170 / 170 100.9 / 100.9 242 / 242

RCU 340WHYZ(-E) 380 50 418 342 392 / 336 198 / 158 117 / 93.5 270 / 225

RCUG340WHYZ(-E) 380 50 418 342 392 / 336 208 / 170 123.2 / 100.9 291 / 242

RCU 380WHYZ(-E) 380 50 418 342 392 / 392 198 / 198 117 / 117 270 / 270

RCUG380WHYZ(-E) 380 50 418 342 392 / 392 208 / 208 123.2 / 123.2 291 / 291

RCU 410WHYZ(-E) 380 50 418 342 336 / 336 / 226 158 / 158 / 116 93.5 / 93.5 / 68.5 225 / 225 / 165

RCUG410WHYZ(-E) 380 50 418 342 336 / 336 / 226 170 / 170 / 123 100.9 / 100.9 / 73.1 242 / 242 / 182

RCU 450WHYZ(-E) 380 50 418 342 336 / 336 / 336 158 / 158 / 158 93.5 / 93.5 / 93.5 225 / 225 / 225

RCUG450WHYZ(-E) 380 50 418 342 336 / 336 / 336 170 / 170 / 170 100.9 / 100.9 / 100.9 242 / 242 / 242

RCU 490WHYZ(-E) 380 50 418 342 392 / 336 / 336 198 / 158 / 158 117 / 93.5 / 93.5 270 / 225 / 225

RCUG490WHYZ(-E) 380 50 418 342 392 / 336 / 336 208 / 170 / 170 123.2 / 100.9 / 100.9 291 / 242 / 242

RCU 530WHYZ(-E) 380 50 418 342 392 / 392 / 336 198 / 198 / 158 117 / 117 / 93.5 270 / 270 / 225

RCUG530WHYZ(-E) 380 50 418 342 392 / 392 / 336 208 / 208 / 170 123.2 / 123.2 / 100.9 291 / 291 / 242

RCU 570WHYZ(-E) 380 50 418 342 392 / 392 / 392 198 / 198 / 198 117 / 117 / 117 270 / 270 / 270

RCUG570WHYZ(-E) 380 50 418 342 392 / 392 / 392 208 / 208 / 208 123.2 / 123.2 / 123.2 291 / 291 / 291

Unit Main Power Application Voltage Compressor(Three-phase)

Model

30

Electrical Data (For working voltage:415V) Notes: 1. The data above are based on the following conditions: Chilled Water Inlet Temperature : 12℃ Chilled Water Outlet Temperature : 7℃ Condenser Water Inlet Temperature : 30℃ Condenser Water Outlet Temperature : 35℃

ELECTRICAL DATA

VOL: Unit Power Supply (Rated) Hz: Frequency (Hz) STC: Starting Current (A) (For each cycle) RNC: Running Current (A) IPT: Input (kW)

2. The mentioned above in the “maximum Unit Current” indicates the total running current of the unit under the following conditions .The design of power supply line should be decided referring to these current: Supplied Voltage : 90% of Rated Voltage Condenser Water Outlet Temperature : 40 ℃(R407C:37℃) Chilled Water Outlet Temperature : 20℃ Capacity Control :100%

Maximum Unit Current

VOL Hz Max. Min. STC(No.1/No.2/No.3)

RNC(No.1/No.2/No.3)

IPT(No.1/No.2/No.3)

Maximum(No.1/No.2/No.3)

RCU 40WHYZ(-E) 415 50 456 374 125 42 27 63

RCUG40WHYZ(-E) 415 50 456 374 125 46 29.5 68

RCU 50WHYZ(-E) 415 50 456 374 161 52 33.5 78

RCUG50WHYZ(-E) 415 50 456 374 161 57 36.7 85

RCU 60WHYZ(-E) 415 50 456 374 195 64 41.5 96

RCUG60WHYZ(-E) 415 50 456 374 195 68 44.3 103

RCU 80WHYZ(-E) 415 50 456 374 125 / 125 42/42 27/27 63/63

RCUG80WHYZ(-E) 415 50 456 374 125 / 125 46/46 29.5/29.5 68/68

RCU 100WHYZ(-E) 415 50 456 374 161 / 161 52/52 33.5/33.5 78/78

RCUG100WHYZ(-E) 415 50 456 374 161 / 161 57/57 36.7/36.7 85/85

RCU 120WHYZ(-E) 415 50 456 374 195 / 195 64/64 41.5/41.5 96/96

RCUG120WHYZ(-E) 415 50 456 374 195 / 195 68/68 44.3/44.3 103/103

RCU 150WHYZ(-E) 415 50 456 374 161 / 161 / 161 52/52/52 33.5/33.5/33.5 78/78/78

RCUG150WHYZ(-E) 415 50 456 374 161 / 161 / 161 57/57/57 36.7/36.7/36.7 85/85/85

RCU 180WHYZ(-E) 415 50 456 374 195 / 195 / 195 64/64/64 41.5/41.5/41.5 96/96/96

RCUG180WHYZ(-E) 415 50 456 374 195 / 195 / 195 68/68/68 44.3/44.3/44.3 103/103/103

RCU 220WHYZ(-E) 415 50 456 374 247 / 247 106 / 106 68.5 / 68.5 151 / 151

RCUG220WHYZ(-E) 415 50 456 374 247 / 247 113 / 113 73.1 / 73.1 167 / 167

RCU 260WHYZ(-E) 415 50 456 374 367 / 247 145 / 106 93.5 / 68.5 206 / 151

RCUG260WHYZ(-E) 415 50 456 374 367 / 247 156 / 113 100.9 / 73.1 222 / 167

RCU 300WHYZ(-E) 415 50 456 374 367 / 367 145 / 145 93.5 / 93.5 206 / 206

RCUG300WHYZ(-E) 415 50 456 374 367 / 367 156 / 156 100.9 / 100.9 222 / 222

RCU 340WHYZ(-E) 415 50 456 374 428 / 367 181 / 145 117 / 93.5 247 / 206

RCUG340WHYZ(-E) 415 50 456 374 428 / 367 190 / 156 123.2 / 100.9 266 / 222

RCU 380WHYZ(-E) 415 50 456 374 428 / 428 181 / 181 117 / 117 247 / 247

RCUG380WHYZ(-E) 415 50 456 374 428 / 428 190 / 190 123.2 / 123.2 266 / 266

RCU 410WHYZ(-E) 415 50 456 374 367 / 367 / 247 145 / 145 / 106 93.5 / 93.5 / 68.5 206 / 206 / 151

RCUG410WHYZ(-E) 415 50 456 374 367 / 367 / 247 156 / 156 / 113 100.9 / 100.9 / 73.1 222 / 222 / 167

RCU 450WHYZ(-E) 415 50 456 374 367 / 367 / 367 145 / 145 / 145 93.5 / 93.5 / 93.5 206 / 206 / 206

RCUG450WHYZ(-E) 415 50 456 374 367 / 367 / 367 156 / 156 / 156 100.9 / 100.9 / 100.9 222 / 222 / 222

RCU 490WHYZ(-E) 415 50 456 374 428 / 367 / 367 181 / 145 / 145 117 / 93.5 / 93.5 247 / 206 / 206

RCUG490WHYZ(-E) 415 50 456 374 428 / 367 / 367 190 / 156 / 156 123.2 / 100.9 / 100.9 266 / 222 / 222

RCU 530WHYZ(-E) 415 50 456 374 428 / 428 / 367 181 / 181 / 145 117 / 117 / 93.5 247 / 247 / 206

RCUG530WHYZ(-E) 415 50 456 374 428 / 428 / 367 190 / 190 / 156 123.2 / 123.2 / 100.9 266 / 266 / 222

RCU 570WHYZ(-E) 415 50 456 374 428 / 428 / 428 181 / 181 / 181 117 / 117 / 117 247 / 247 / 247

RCUG570WHYZ(-E) 415 50 456 374 428 / 428 / 428 190 / 190 / 190 123.2 / 123.2 / 123.2 266 / 266 / 266

ModelUnit Main Power Application Voltage Compressor(Three-phase)

31

SOUND DATA

Note: 1、 The above uses (SPL-A) A scale sound pressure level data (dB)。

2、 The measuring point is 1.0 meter from the center of the machine surface and 1.5 meter from the floor level。

3、 The units are operating under a standard working conditions。

4、 The sound data are measured on the flat, so the influence of the resonance should be considered while the unit

is located in a rounding wall.

Component Detailed Data Compressor

Compressor Model 40ASCC

W-Z 50ASCC

W-Z 60ASCC

W-Z 100ASCC

W-Z 130ASCC

W-Z 170ASCC

W-Z Compressor Type — Semi-hermetic Type

Q’ty of Rotor set 1 1 1 1 1 1

Rotating Speed 50Hz r/min. 2,880 2,880 2,880 2,880 2,880 2,880

Exhaust Rate 50HZ m3/h 137.4 169.5 208.7 343.8 468.3 586.8

Cooling Capacity Control

Continuous Capacity Control % 100~15,0

Discharge MPa 3.0 3.0 3.0 3.0 3.0 3.0 Air-Tight Pressure Suction MPa 2.0 2.0 2.0 2.0 2.0 2.0

Type — Three-Phase Asynchronism Motor

Starting Method — Star-Delta Starting

Number of Poles — 2

Insulation Class — F Motor

Nominal Rated Output Power kW 30 37 45 75 98 128

Type — UX300 UX300 UX300 UX300 UX300 UX300 Lubrication

Oil Volume liters 6 6 6 10 13 15

Unit Power Supply Frequency:50Hz Frequency Band(Hz)

Model

45 ~ 90

90 ~

180

180 ~

355

355 ~

710

710 ~

1400

1400 ~

2800

2800 ~

5600

5600 ~

11200 Overall

RCU(G) 40WHYZ(-E) 48.7 50.2 58.9 56.4 57.5 58.8 51.8 36 63.2 RCU(G) 50WHYZ(-E) 47.3 50.9 58.4 58.6 59.1 60.5 48.9 38 64.5 RCU(G) 60WHYZ(-E) 52.2 53.3 61.3 58.7 60.7 61.1 55.3 39 65.9 RCU(G) 80WHYZ(-E) 52.4 53.6 63.1 60.9 62.8 63.1 55.8 39.9 67.8 RCU(G)100WHYZ(-E) 52.2 56.2 63.4 66.6 64.3 66.8 54.4 43.6 70.7 RCU(G)120WHYZ(-E) 52.4 55.7 60.8 53.2 67.8 67.2 56.5 39.9 71.4 RCU(G)150WHYZ(-E) 56.2 59.8 62.8 66.8 60.1 71.6 57.9 46.9 73.7 RCU(G)180WHYZ(-E) 54.7 60.2 62.8 64.5 65.5 71.4 61.3 46.9 74.0 RCU(G)220WHYZ(-E) 53.4 60.5 63.2 64.5 65 73.1 61.2 45.7 75.2 RCU(G)260WHYZ(-E) 53.7 60.8 63.5 64.8 65.4 73.4 61.5 45.9 75.6 RCU(G)300WHYZ(-E) 54.0 61.2 64.0 65.3 65.9 73.5 61.9 46.2 75.7 RCU(G)340WHYZ(-E) 54.4 61.6 64.5 65.8 66.4 73.8 62.3 46.5 76.1 RCU(G)380WHYZ(-E) 55.2 62.6 65.6 66.9 67.6 73.6 63.3 47.3 76.2 RCU(G)410WHYZ(-E) 55.7 63.2 66.2 67.6 68.3 73.8 63.9 47.7 76.5 RCU(G)450WHYZ(-E) 56.2 63.7 66.8 68.2 68.9 73.6 64.4 48.1 76.6 RCU(G)490WHYZ(-E) 56.4 63.9 67.0 68.4 69.2 73.9 64.7 48.3 76.9 RCU(G)530WHYZ(-E) 56.6 64.2 67.3 68.7 69.5 73.9 64.9 48.5 77.0 RCU(G)570WHYZ(-E) 56.9 64.5 67.7 69.1 69.9 74.0 65.3 48.7 77.2

SOUND DATA and COMPONENT DATA

32

Condenser

Model RCU(G)40 WHYZ(-E)

RCU(G)50 WHYZ(-E)

RCU(G)60WHYZ(-E)

RCU(G)80WHYZ(-E)

RCU(G)100WHYZ(-E)

RCU(G)120WHYZ(-E)

RCU(G)150 WHYZ(-E)

RCU(G)180WHYZ(-E)

RCU(G)220WHYZ(-E)

Outer Diameter mm 355.6 355.6 355.6 355.6 355.6 355.6 406.4 406.4 508

Length mm 1200 1200 1200 2409 2409 2409 2838 2838 1372

Thickness mm 6 6 6 6 6 6 6 6 6

Material — Copper

Q’ty — 76 92 112 2×76 2×92 2×112 3×138 3×168 328

Number of Water Pass 2 2 2 2 2 2 2 2 4

Ref. Side 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) Maximum Permissible

Pressure Water Side 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

Model RCU(G)260 WHYZ(-E)

RCU(G)300 WHYZ(-E)

RCU(G)340WHYZ(-E)

RCU(G)380WHYZ(-E)

RCU(G)410WHYZ(-E)

RCU(G)450WHYZ(-E)

RCU(G)490 WHYZ(-E)

RCU(G)530WHYZ(-E)

RCU(G)570WHYZ(-E)

Outer Diameter mm 508 508 508 508 508 508 508 508 508

Length mm 1372 1372 1372 1372 1372 1372 1372 1372 1372

Thickness mm 6 6 6 6 6 6 6 6 6

Material — Copper

Number — 383 438 494 550 602 657 713 769 825

Number of Water Pass 4 4 4 4 4 4 4 4 4

Ref. Side 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) 2.2(2.5) Maximum Permissible

Pressure Water Side 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

NOTE: The data 2.5 in the “( )” is for the R407C units .

COMPONENT DATA

33

Component Detailed Data (Continuous) Cooler

Cooler Dimensions

Model RCU(G)40 WHYZ(-E)

RCU(G)50 WHYZ(-E)

RCU(G)60 WHYZ(-E)

RCU(G)80 WHYZ(-E)

RCU(G)100WHYZ(-E)

RCU(G)120 WHYZ(-E)

RCU(G)150 WHYZ(-E)

RCU(G)180WHYZ(-E)

RCU(G)220WHYZ(-E)

Shell Material — Steel

Outer Diameter mm 356.2 356.2 356.2 356.2 356.2 356.2 431.8 431.8 429 Water Side

Length mm 1276 1276 1276 2296 2296 2296 2400 2400 1314

Shell Material — Steel

Outer Diameter mm 420 420 420 420 420 420 500 500 498

Length mm 101 101 101 101 101 101 101 101 140 Ref. Side

Thickness mm 10 10 10 10 10 10 12 12 10

Tube material — Copper

Outer Diameter mm 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7

Number of Tube — 220 272 310 220 272 310 408 437 932

Number of Pass — 4 4 4 2 2 2 2 2 4

Ref. Side MPa 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 Maximum Permissible

Pressure Water Side MPa 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05

Insulation Polyethylene(25mm)

Model RCU(G)260 WHYZ(-E)

RCU(G)300 WHYZ(-E)

RCU(G)340WHYZ(-E)

RCU(G)380WHYZ(-E)

RCU(G)410WHYZ(-E)

RCU(G)450 WHYZ(-E)

RCU(G)490WHYZ(-E)

RCU(G)530WHYZ(-E)

RCU(G)570WHYZ(-E)

Shell Material — Steel

Outer Diameter mm 541/429 541 541 541 541/429 541 541 541 541 Water Side

Length mm 1314 1314 1314 1314 1314 1314 1314 1314 1314

Shell Material — Steel

Outer Diameter (No.1/No.2) mm 611/498 611 611 611 611/498 611 611 611 611

Length mm 140 140 140 140 140 140 140 140 140

Ref. Side

Thickness mm 10 10 10 10 10 10 10 10 10

Tube material — Copper

Outer Diameter mm 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7

Number of Tube — 1100 1268 1416 1564 1734 1902 2050 2198 2346

Number of Pass — 4 4 4 4 4 4 4 4 4

Ref. Side MPa 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 Maximum

Permissible Pressure Water Side MP

a 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05

Insulation Polyethylene(25mm)

COMPONENT DATA

34

6. Control System Standard Operation Sequence for RCU(G)40、50、60WHYZ(-E)

Standard Operation Sequence for RCU(G) 80、100、120、220、260、300、340、380WHYZ(-E)

CONTROL SYSTEM

OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF — OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF — OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF — — — ON — — — — — — — — — — — — — — OFF — OFF —

Load-up — — — — — — — — — — — — — — — — — —Neutral — — — — — — — — — — — — — — — — — —Load-down — — — — — — — — — — — — — — — — — — —No.1 CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS OPN OPN CLS CLS CLS CLSNo.2 CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS OPN CLS CLS CLS CLS

Power Supply Lamp OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFFOperation Lamp OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF ON OFF OFFAlarm Lamp OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF ON OFF OFF

CH1 OFF ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF ON ON ON ON ON OFFCH2 OFF ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON OFF OFF ON ON ON ON OFF

STA DLT STA DLT DLT DLT DLT DLT DLT DLT DLT DLT(ULD) (ULD)(ULD) (ULD) (ULD) (FLD) (FLD) (ULD) (ULD) (ULD) (ULD) (FLD)15% 15% 15% 15% 15%-99% 100% 100% 15%-99% 15%-99% 15% 15%-99% 100%

STA DLT DLT DLT DLT DLT DLT DLT DLT DLT DLT(ULD) (ULD) (ULD) (FLD) (FLD) (ULD) (ULD) (ULD) (ULD) (ULD) (FLD)15% 15% 15%-99% 100% 100% 15%-99% 15%-99% 15% 15%-99% 15%-99% 100%

SV11 OFF OFF OFF ON ON ON ON ON OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFFSV12 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF OFF OFF OFF OFFSV13 OFF OFF OFF OFF OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFFSV21 OFF OFF OFF ON ON ON ON ON OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFFSV22 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF OFF OFF OFF OFFSV23 OFF OFF OFF OFF OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF

OFF OFFOFF OFF

Time Schedule

CLS:Close; OPN:Open; STA:Star; DLT:Delta ULD: Unload; FLD: Fullload;FLK:Flank

OFF

Solenoid Valve

OFF OFF OFFOFF

OFFOFF OFF OFF OFF

OFFOFF OFF OFF OFF

Controller

MC1 OFF

Safety Devices

Oil Heater

Motor forCompressor

MC2 OFF

Main Power SwitchChilled Water Pump Condenser Water PumpOperation Switch(ON/OFF)

Control StageControl Switch

Starting Control Capacity Control Safety Devices Shut Down

3min.

5 sec.

60sec.Minimum: 3min.

The compressor which started finally will be started first

5sec.

30sec.

OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF

— OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF

— OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF

— — — ON — — — — — — — — — — — OFF — OFF —

Load up — — — — — — — — — — — — — — — — —

Neutral — — — — — — — — — — — — — —

Load down — — — — — — — — — — — — — — — —

Safety Devices No.1 CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS OPN CLS CLS CLS CLS

Power Supply Lamp OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF

Operation Lamp OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON OFF ON OFF OFF

Alarm Lamp OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF

Oil Heater CH1 OFF ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON OFF ON ON ON ON OFF

STA DLT DLT DLT DLT DLT DLT DLT DLT DLT

(ULD) (ULD) (ULD) (FLD) (FLD) (ULD) (ULD) (ULD) (ULD) (FLD)

15% 15% 15%-99% 1 1 15%-99% 15%-99% 15% 15%-99% 1

SV11 OFF OFF OFF ON ON ON OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF OFF

SV12 OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF OFF OFF OFF

SV13 OFF OFF OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF

CLS:Close; OPN:Open; STA:Star; DLT:Delta

Shut Down

Main Power Switch

Chilled Water Pump

Condenser Water Pump

Control StageControl Switch

Starting Control Capacity Control Safety Devices

Controller

Motor of Comprssor MC1 OFF OFF

Operation Switch(ON/OFF)

OFFOFF OFF OFF OFF OFF

Solenoid Valve

Time Schedule

ULD: Unload; FLD: Fullload;FLK:Flank

OFF

5 Sec.3 Min.

30 Sec.Minimum: 3 Min.

35

OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF — OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF — OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF OFF — — — ON — — — — — — — — — — — — — — — — — OFF — OFF —

Load-up — — — — — — — — — — — — — — — — — — — — —Neutral — — — — — — — — — — — — — — — — — — — —Load-down — — — — — — — — — — — — — — — — — — — — — —No.1 CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS OPN OPN OPN CLS CLS CLS CLSNo.2 CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS OPN OPN CLS CLS CLS CLSNo.3 CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS OPN CLS CLS CLS CLS

Power Supply Lamp OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFFOperation Lamp OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF ON OFF OFFAlarm Lamp OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON OFF ON OFF OFF

CH1 OFF ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF ON ON ON ON OFF ON OFFCH2 OFF ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF OFF ON ON ON OFF ON OFFCH3 OFF ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF OFF OFF ON ON OFF ON OFF

STA DLT DLT DLT DLT DLT DLT DLT DLT DLT DLT DLT DLT DLT(ULD) (ULD) (ULD) (ULD) (ULD) (ULD) (ULD) (FLD) (FLD) (ULD) (ULD) (ULD) (ULD) (FLD)

15% 15% 15% 15% 15% 15% 15%-99% 100% 100% 15%-99% 15%-99% 15% 15%-99% 100%STA DLT DLT DLT DLT DLT DLT DLT DLT DLT DLT DLT DLT

(ULD) (ULD) (ULD) (ULD) (ULD) (FLD) (FLD) (ULD) (ULD) (ULD) (ULD) (ULD) (FLD)

15% 15% 15% 15% 15%-99% 100% 100% 15%-99% 15%-99% 15% 15%-99% 15%-99% 15%00%

STA DLT DLT DLT DLT DLT DLT DLT DLT DLT DLT DLT(ULD) (ULD) (ULD) (FLD) (FLD) (ULD) (ULD) (ULD) (ULD) (ULD) (ULD) (FLD)

15% 15% 15%-99% 100% 100% 15%-99% 15%-99% 15% 15%-99% 15%-99% 15%-99% 100%SV11 OFF OFF OFF ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFF OFFSV12 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFFSV13 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFFSV21 OFF OFF OFF ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFF OFFSV22 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFFSV23 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFFSV31 OFF OFF OFF ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFF OFFSV32 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFFSV33 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF

Time Schedule

CLS:Close; OPN:Open; STA:Star; DLT:Delta

OFF

OFF

OFF

OFF OFF

OFF OFF

MC1

Capacity Control Safety Devices

OFF OFF OFF OFF

OFF OFF OFF OFF

Shut Down

Controller

Safety Devices

Oil Heater

Main Power SwitchChilled Water PumpCondenser Water PumpOperation Switch(ON/OFF)

Control StageControl Devices Starting Capacity

OFF OFF OFF

OFF OFF OFF

OFF OFF OFF

MC2 OFF OFF OFF

OFF OFF

OFF OFF OFF

ULD: Unload FLD: Fullload; FLK:Flank

MC3

Motor forComperssor

Solenoid Valve

OFFOFF OFF

OFF

3min.Minimum:3min.

5sec.

60sec.

5sec.

60sec.

5sec.

30sec.

The compressor which started finally will be started first

Standard Operation Sequence for R

CU

(G)

150、

180、

410、

450、

490、

530、

570WH

YZ(-E)

CO

NTR

OL SYSTEM

35

36

1、Pump Operation Control 2、Pump and Cooling Tower Interlock Notes: 1.Select A or B for the desired operation method and perform the wiring according to the above wiring diagram.

A : for build-in operation switch B: for remote push button switch.

2. In case of applying the remote indication as shown in the above figure, shielded wires shall be used in order to avoid misguiding .

3.The maximum current value for contactor ”APp1”shall be lower than 5 A.

Tool and Instruments—One Set of Wiring Tools and Electrical Tester (Clamp Meter) Schedule Check--Confirm that the field-selected electrical components (main power switch, fuses, wires, conduit connections and wire terminals) are properly selected according to the “Electrical Data” in Technical Catalog I and ensure that they comply with national and local codes. It is recommended that the main power switch be locked on the “OFF” position, to prevent against accidental supply of power during unit servicing.

Main Power Wiring Procedures— Confirm that electrical power is not being supplied to the installation location prior to any electrical installation work.

1.Install the field-supplied main switch box in the properly selected location.

2. Install conduit connectors in the hole for power wiring.3. Lead main power wires and earthing wire through

connector to the screw terminals for main power and earthing in the electrical box. The neutral wire for 380v and 415V power supplies should also be led through the connector.

4. Firmly connect the wires with wire terminals to unit screw terminals T,S and T(and also Mp for 380V and 415V power supply) according to the following figures.

Control Wiring—Connect the interlock wiring among the unit terminals 、the water pump and the cooling tower starter according to the following figures or the wiring labels.

Electrical Wiring

Control Wiring

CONTROL SYSTEM

★CPUE——Magnetic Switch for Chilled Water Pump ★CPUC——Magnetic Switch for Condenser Water Pump★CPUT——Magnetic Switch for Water Cooling Tower ★PBSP1,2——ON/OFF Button for Pump Control ★CS —— Changeover Switch for Field-Wiring ★ARp —— Assistant Breaker for Operation Check ★ORP1,2,3——Overcurrent Relay for Pump Motor

Printed

Circuit Board) PBSp2

(STOP)

PBSp1

(START)

★ ★ ★★★★

★ ★ ★ ★★ ★

Factory WiringField WiringEarth WiringField-Supplied

Power supply for pump Power supply for pump

37

3、Remote Control and Remote Indication(if Required)

RCU(G)40WHYZ(-E)~RCU(G)570WHYZ(-E)

Mark Name ★PBS ON.OFF

Bush-Button Switch for Remote Unit

★PLR Pilot Lamp for Remote Operation ★PLO Pilot Lamp for Remote Alarm ★PLP pilot Lamp for Remote Pump

★PLO1-3 pilot Lamp for Remote Alarm 1-3

Main Power Wiring

Factory WiringField WiringEarth WiringField-Supplied★

CONTROL SYSTEM

(Remote Control SW Wiring)Start/Stop

Removed Wiring

38

Safety and Control Devices Setting

NOTE: *CCP: Compressor Cycle Protection CCP hour-meter has a range from 1 minute to 10 minutes , but the adjustment should be less than 3 minutes to avoid frequent unit starting, this function extends machine life. * The data in the “( )” is for the R407C units.

CONTROL SYSTEM

RCU(G)40WHYZ(-E)

RCU(G)50WHYZ(-E)

RCU(G)60WHYZ(-E)

RCU(G)80WHYZ(-E)

RCU(G)100WHYZ(-E)

High Pressure controlCut-out MPa 2.15(2.4) 2.15(2.4) 2.15(2.4) 2.15(2.4) 2.15(2.4)

Low Pressure controlCut-out MPa 0.05 0.05 0.05 0.05 0.05

Internal thermostatCut-out ℃ 115 115 115 115 115

Cut-in ℃ 93 93 93 93 93Electric Overcurrent Relay

Setting for R22 380V 50Hz A 42 50 64 42 50415V 50Hz A 42 50 64 42 50

Setting for R407C 380V 50Hz A 42 58 64 42 58415V 50Hz A 42 58 64 42 58

Oil Heater Capacity W 150 150 150 150 150Electric Timer

CCP(1*)Star—Delta Sec. 5 5 5 5 5

Unloading duringStarting

Control Wiring Fuse Capacity A 4 4 4 4 4Freezing Protection Thermistor

Cut-out ℃ 2.5 2.5 2.5 2.5 2.5Cut-in ℃ 6.5 6.5 6.5 6.5 6.5

Discharge Gas Thermistor Cut-out ℃ 140 140 140 140 140

Cut-in ℃ 110 110 110 110 110Pressure Relief Valve

Starting OpenRCU(G)120WHYZ

(-E)RCU(G)150WHY

Z(-E)RCU(G)180WHY

Z(-E)RCU(G)220WHY

Z(-E)RCU(G)260WHY

Z(-E)High Pressure Control

Cut-out MPa 2.15(2.4) 2.15(2.4) 2.15(2.4) 2.15(2.4)  2.15(2.4)

Cut-out MPa 0.05 0.05 0.05 0.05 0.05Internal Thermostat

Cut-out ℃ 115 115 115 115 115Cut-in ℃ 93 93 93 93 93

Electric Overcurrent RelaySetting for R22 380V 50Hz A 42 50 64 1.9 / 1.9 2.6 / 1.9

415V 50Hz A 42 50 64 1.7 / 1.7 2.4 / 1.7Setting for R407C 380V 50Hz A 42 58 64 2.1 / 2.1 2.8 / 2.1

415V 50Hz A 42 58 64 1.9 / 1.9 2.6 / 1.9D-Time S — — — 5 5O-Time S — — — 1 1

Oil Heater Power W 150 150 150 150 150Electric Timer

CCP(1*)Star—Delta Sec. 5 5 5 5 5

Unloading during starting Sec. 30 30 30 30 30Control Wiring Fuse Capacity A 4 4 4 6 6

Freezing Protection Thermistor Cut-out ℃ 2.5 2.5 2.5 2.5 2.5

Cut-in ℃ 6.5 6.5 6.5 6.5 6.5Discharge Gas Thermistor

Cut-out ℃ 140 140 140 140 140Cut-in ℃ 110 110 110 110 110

Pressure Relief Valve StartingOpen MPa 2.4(2.76) 2.4(2.76) 2.4(2.76) 2.4(2.76) 2.4(2.76)

Manual Reset Non-Adjustable Manual Reset Adjustable

Automatic Reset Non-Adjustable

Automatic Reset Non-Adjustable

3/4/5 3/4 3/4

Model

Compressor(No.1/No.2/No.3)

Manual Reset Adjustable

Low Pressure Control Shut Down and Give an Alarm

  Automatic Reset Non-Adjustable

Min. 3/4 3/4/5

 Automatic Reset Non-Adjustable

 Automatic Reset Non-Adjustable

MPa 2.4(2.76) 2.4(2.76) 2.4(2.76) 2.4(2.76) 2.4(2.76)

3

Refrigerantcycle system

3/4 3/4

Sec. 30 30 30 30 30

Refrigerant CycleSystem

Model

Compressor(No.1/No.2)

Manual Reset Adjustable

Shut Down and Give an Alarm

 Automatic Reset Non-Adjustable

Manual Reset Non-Adjustable

Min. 3 3

39

Safety and Control Devices Setting

NOTE:

*CCP: Compressor Cycle Protection CCP hour-meter has a range from 1 minute to 10 minutes , but the adjustment should be less than 3 minutes to avoid frequent unit starting, this function extends machine life. * The data in the “( )” is for the R407C units.

CONTROL SYSTEM

RCU(G)300WHYZ(-E) RCU(G)340WHYZ(-E) RCU(G)380WHYZ(-E) RCU(G)410WHYZ(-E)

High Pressure ControlCut-out MPa 2.15(2.4) 2.15(2.4) 2.15(2.4) 2.15(2.4)

Low Pressure ControlCut-out MPa 0.05 0.05 0.05 0.05

Internal ThermostatCut-out ℃ 115 115 115 115

Cut-in ℃ 93 93 93 93 Electric Overcurrent RelaySetting for R22 380V 50Hz A 2.6/2.6 2.6/2.6 2.6/2.6 2.6/2.6/1.9

415V 50Hz A 2.4/2.4 2.4/2.4 2.4/2.4 2.4/2.4/1.7Setting for R407C 380V 50Hz A 2.8/2.8 2.8/2.8 2.8/2.8 2.8/2.8/2.1

415V 50Hz A 2.6/2.6 2.6/2.6 2.6/2.6 2.6/2.6/1.9D-Time SO-Time S

Oil Heater Power W 150 150 150 150 Electric Timer

CCP(1*) Star — Delta Sec. 5 5 5 5

Unloading during starting Sec. 30 30 30 30Fuse Capacity A 6 6 6 6

Freezing Protection Thermistor Cut-out ℃ 2.5 2.5 2.5 2.5

Cut-in ℃ 6.5 6.5 6.5 6.5Discharge Gas Thermistor

Cut-out ℃ 140 140 140 140Cut-in ℃ 110 110 110 110

Pressure Relief ValveStarting Open

RCU(G)450WHYZ(-E) RCU(G)490WHYZ(-E) RCU(G)530WHYZ(-E) RCU(G)570WHYZ(-E)

High Pressure ControlCut-out MPa 2.15(2.4) 2.15(2.4) 2.15(2.4) 2.15(2.4)

Low Pressure ControlCut-out MPa 0.25 0.25 0.25 0.25

Cut-in MPa 0.5 0.5 0.5 0.5Internal Thermostat

Cut-out ℃ 115 115 115 115Cut-in ℃ 93 93 93 93

Electric Overcurrent RelaySetting for R22 380V 50Hz A 2.6/2.6/2.6 2.6/2.6/2.6 2.6/2.6/2.6 2.6/2.6/2.6

415V 50Hz A 2.4/2.4/2.4 2.4/2.4/2.4 2.4/2.4/2.4 2.4/2.4/2.4Setting for R407C 380V 50Hz A 2.8/2.8/2.8 2.8/2.8/2.8 2.8/2.8/2.8 2.8/2.8/2.8

415V 50Hz A 2.6/2.6/2.6 2.6/2.6/2.6 2.6/2.6/2.6 2.6/2.6/2.6D-Time SO-Time S

Oil Heater Power W 150 150 150 150 Electric Timer

CCP(1*) Star — Delta Sec. 5 5 5 5

Unloading during starting Sec. 30 30 30 30Control Wiring Fuse Capacity A 6 6 6 6

Freezing Protection Thermistor Cut-out ℃ 2.5 2.5 2.5 2.5

Cut-in ℃ 6.5 6.5 6.5 6.5Discharge Gas Thermistor

Cut-out ℃ 140 140 140 140Cut-in ℃ 110 110 110 110

Pressure Relief ValveStarting Open

Model

Compressor(No.1/No.2/No.3)

Manual Reset Adjustable

Shut Down and Give an Alarm

Automatic Reset Non-Adjustable

Manual Reset Adjustable

51

Min. 3/4 3/4 3/4 3/4/5

Automatic Reset Non-Adjustable

Automatic Reset Non-Adjustable

3/4/5

2.4(2.76)

Model

Compressor(No.1/No.2/No.3)

Manual Reset Adjustable

 Automatic Reset Non-Adjustable

Automatic Reset Non-Adjustable

Manual Reset Adjustable

51

RefrigerantCycle System

3/4/5 3/4/5 3/4/5Min.

MPa 2.4(2.76) 2.4(2.76) 2.4(2.76)

RefrigerantCycle System

Automatic Reset Non-Adjustable

Automatic Reset Non-Adjustable

MPa 2.4(2.76) 2.4(2.76) 2.4(2.76) 2.4(2.76)

40

Fig.3-1 Recommended Concrete Curbs

Fig.3-2 Recommended Concrete Curbs

Fig.3-3 Recommended Concrete Curbs

Recommended Concrete Curbs For Models : RCU(G)40、50、60WHYZ(-E)

For Models :RCU(G)80、100、120WHYZ(-E)

For Models : RCU(G)150、180WHYZ(-E)

INSTALLATION

4-M20 300

100

41

Fig.3-4 Recommended Concrete Curbs

Fig.3-5 Recommended Concrete Curbs

Recommended Concrete Curbs For Models : RCU(G)220、260、300、340、380WHYZ(-E)

For Models : RCU(G)410、450、490、530、570WHYZ(-E)

INSTALLATION

42

CONTROL SYSTEM

42

43

CONTROL SYSTEM

- 43 -

43

44

CONTROL SYSTEM

44

45

CONTROL SYSTEM

- 45 -

45

46

CONTROL SYSTEM

46

47

CONTROL SYSTEM

DIP SWITCH SETTING Models:RCU(G)40~570WHYZ

47

48

Unit-The unit shall be a water-cooled screw water chiller for application with R22/R-407C refrigerant, and shall be composed of a refrigerant cycle(s) and electrical components. Optional accessories shall also be provided upon customer request. The unit shall be for indoor installation. The unit shall be properly assembled, internally piped and wired, thoroughly tested and operation-charged with refrigerant at the factory. Capacity-the cooling capacity of the unit shall be greater ——kW(kcal/h) or greater under the following conditions: ——m3/h chilled water flow rate ——℃ chilled water inlet temperature ——℃ chilled water outlet temperature ——m3/h condenser cooling water flow rate ——℃ condenser water inlet temperature ——℃ condenser water outlet temperature Water cooler and condenser fouling factors of ——m2.℃/kW or greater. Refrigerant Cycle- The refrigerant cycle shall be provided with HITACHI-SRW semi-hermetic screw compressor(s), a water-cooled condenser(s), a direct expansion type water cooler, electronic expansion valve(s), liquid line strainer(s), and a check joint of low pressure. Compressor- The compressor shall be a HITACHI semi-hermetic screw compressor of the same manufacture. The starting method shall be the star-delta type. The compressor shall be equipped with an oil separator in one piece and shall be the serviceable type

Water-Cooler- The water cooler shall be the dry expansion type with a horizontal welded steel construction shell, containing inside tubes. The seamless copper tube shall be the thermofin cargated tube, in order to obtain the optimum heat transfer coefficient .Refrigerant side of the water cooler shall be cleaned, dried and tested for leakage, and water side be tested for leakage. Condenser-The condenser shall be the shell –and-tube type. Seamless copper tubes used shall be the high-flux heat transfer surfaces type. Refrigerant side of the condenser shall be cleaned, dried and tested for leakage, and water side be tested for leakage Compressor Protection-The compressor protection system of each compressor shall include a quick response overcurrent relay, a gas discharge thermistor, a high pressure switch, a low pressure sensor, a timer relay and an internal thermostat embedded in the motor winding. Control –All control devices should be enclosed in the unit. In addition to the compressor protection devices, the water cooler shall be equipped with a freezing protection thermistor to protect against freezing. The control devices shall include operation sequence and capacity control . Accessories- The factory-supplied standard accessories shall include vibration-proof rubber mats and foundation bolts.

APPLICATION DATA and SPECIFICATION

Maintenance Maintenance These units are equipped with HITACHI semi-hermetic screw compressor so periodical maintenance is necessary. Refer to the “HITACHI SEMI-HERMETIC SCREW COMPRESSOR -Service Handbook.

Standard Specification

49

Hitachi specifications in this catalogue are subject to change without notice in order that HITACHI may bring the latest innovations to their customers.

URL:http://www.hitachiacs.co.ip

Printed in china

Z0011134-IX-A


Recommended