13
Two-stage compressors At a glance Refrigeration circuit Operating limits and performance data R404A | R410 | R22 Technical data Dimensions and connections Scope of supply and accessories 170 171 173 176 177 180
Transcript
Page 1: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

Two-stage compressors

At a glanceRefrigeration circuit Operating limits and performance data R404A | R410 | R22 Technical data Dimensions and connections Scope of supply and accessories

170171173

176177180

Page 2: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

170 I www.bock.de

TypeDisplacement (50 Hz)

LP / HP

HGZX7/1620-4 R404A/R507

93,70 m³/h / 46,90 m³/hHGZX7/1620-4 R410A

HGZ7/1620-4 R22

HGZX7/1860-4 R404A/R507

107,60 m³/h / 53,80 m³/hHGZX7/1860-4 R410A

HGZ7/1860-4 R22

HGZX7/2110-4 R404A/R507

122,40 m³/h / 61,20 m³/hHGZX7/2110-4 R410A

HGZX7/2110-4 R22

A two-stage variant based on the Bock HG semi-hermetic 6 cylinder range is available for extended use in the domain of deep-freezing.

The two stage system consists of:Liquid subcooler -

Reinjection valve -

Solenoid valve -

Sight glass -

Filter drier -

The two possible designs of the HGZ7:

Medium-pressure mixed line mounted on the compressor and insulated liquid subcooler, expansion valve, solenoid valve, two sight glasses, fi lter drier everything enclosed separately for individual, external mounting

Standard Option

Special features:

6 cylinder design -

LP/HP stage ratio 2:1 -

2 stage operation with liquid subcooler -

Reinjection valve adapted to refrigerant and application -

Extremely reliable and economic compressor design -

Detailed descriptions and information on the HG7 basic compres-sor can be found in the chapter entitled “Series HG(HA)single-stage compressors“ starting on page 32.

Two-stage compressors - At a glance

Liquid subcooler, expansion valve, solenoid valve, two sight glasses, fi lter dryer mounted directly to the compressor, lined and insulated.

Available modelsfor refrigerants R404A, R410A, R507, R22

Type key | Two-stage compressors

HGZX7 / 2110 - 4 R410A

Refrigerant 3)

Number of poles Swept volume Size Ester oil fi lling 2)

Series 1)

1) HG = Hermetic Gas-cooled (suction gas-cooled), two stage2) X = Ester oil fi lling (HFC refrigerants R404A, R410A)3) Possible refrigerants are R404A, R410A, R22

Page 3: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

www.bock.de I 171

01

02

03

04

05

06

07

08

09

10

11

12

13

Two-stage compressors - At a glance

123456789

10111213141516

Refrigeration circuit and two-stage compressorSchematic Diagram

Explanations

Compressor Cylinder LP-stage Intermediate pressure chamber MP Intermediate pressure line MP Cylinder HP-stage Subcooler* Reinjection valve* Sight glass 1* Sight glass 2* Solenoid valve* Filter drier* Vibration damper, pressure line Oil separator Non-return valve Condenser Refrigerant receiver

Filter drier Solenoid valve Sight glass Expansion valve (evaporator) Evaporator Liquid separator Vibration damper, suction line Filter suction line

LP = Low pressureMP = Medium pressureHP = High pressureFUE = Liquid subcooler, inletFUA = Liquid subcooler, outlet

* Components for subcooling system as standard

1718192021222324

Page 4: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

172 I www.bock.de

Two-stage compressors - At a glance

Subcooling temperature

The design of the expansion valve on the compressor can be defined with the help of the diagram by approximately calcula-ting the subcooling temperature arising in the relevant operating conditions (to/tc).

Subcooling temperature calculation diagram for the intermedi-ate cooler outlet.

tU = Subcooling temperature at the intermediate cooler outlet (FUA)tO = Evaporation temperature (°C)

Page 5: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

www.bock.de I 173

01

02

03

04

05

06

07

08

09

10

11

12

13

-30-40-50-60-7020

30

40

50

6058

t (°C)o

t (°C)c

∆toh<10K

-20-30-40-50-6020

30

40

50

60

t (°C)o

t (°C)c

66

∆toh<10K

Operating limits

R404A/R507 R410A

R22

Application range

tO Evaporating temperature (°C)tC Condensing temperature (°C)∆tOh Suction gas superheat (K)

Max. permissible operating pressure (LP/MP/HP) 1): 19/19/28 bar

1) LP = low pressure MP = middle pressure HP = high pressure

Notes

Operating limits

Compressor operation is possible within the limits shown on the application diagrams. Compressor application limits should not be chosen for design purposes or continuous operation.

Performance data

The stated performance values are based on 10 K suction gas superheat with liquid subcooling, operating at 50 Hz.

Performance data were compiled for R404A and R507.The base values are the data for R404A.

Conversion factor for 60 Hz = 1,2Performance data for other operating points, see Bock software.

Two-stage compressors - Operating limits

Page 6: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

174 I www.bock.de

Type Cond.temp.

°C

Cooling capacity QO [W] Power consumption Pe [kW]

Evaporating temperature °C

-35 -40 -45 -50 -55 -60 -65

HGZX7/1620-430

QP

2535422,89

1996720,80

1528518,67

1139616,43

838514,00

40QP

1913122,87

1463020,63

1086818,25

793015,68

HGZX7/1860-430

QP

2918226,28

2285923,89

1753021,44

1313618,87

961416,08

40QP

2195926,26

1677423,68

1250820,96

910118,00

HGZX7/2110-430

QP

3319529,90

2600327,17

1994124,39

1494321,46

1093718,29

40QP

2498029,87

1908226,94

1422923,84

1035220,48

R410A Performance data 50 Hz

Two-stage compressors - Performance data

Type Cond.temp.

°C

Cooling capacity QO [W] Power consumption Pe [kW]

Evaporating temperature °C

-30 -35 -40 -45 -50 -55 -60 -65 -70

HGZX7/1620-4

30QP

3486921,17

2847119,41

2309817,63

1862815,84

1493614,05

1189912,31

939410,61

72968,99

54827,46

40QP

3343723,42

2731521,42

2218119,40

1791017,39

1438015,41

1146713,48

904711,61

69979,84

51928,17

50QP

2586023,49

2095021,24

1686619,02

1348416,84

1068014,72

833212,68

631510,75

HGZX7/1860-4

30QP

4004224,31

3269422,29

2652520,24

2139118,18

1715216,14

1366514,13

1078712,19

837810,32

62948,56

40QP

3839726,90

3136724,60

2547122,28

2056719,97

1651417,70

1316915,48

1039013,34

803511,30

59629,38

50QP

2969626,98

2405724,39

1936721,84

1548419,33

1226516,90

956814,56

725212,35

HGZX7/2110-4

30QP

4555027,66

3719125,36

3017323,03

2433420,69

1951118,36

1554416,08

1227113,86

953011,74

71609,74

40QP

4367930,60

3568127,98

2897425,34

2339622,72

1878520,13

1498017,61

1181915,17

914012,85

678210,67

50QP

3378030,69

2736627,75

2203124,84

1761421,99

1395219,23

1088416,57

824914,04

R404A/R507 Performance data 50 Hz

Page 7: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

www.bock.de I 175

01

02

03

04

05

06

07

08

09

10

11

12

13

Performance data 50 Hz relative to 10 K suction gas superheat with liquid subcooling

Type Cond.temp.

°C

Cooling capacity QO [W] Power consumption Pe [kW]

Evaporating temperature °C

-30 -35 -40 -45 -50 -55 -60

HGZ7/1620-4

30QP

2971118,26

2421416,81

1944815,40

1536514,03

1192112,70

907011,41

676510,16

40QP

2905920,23

2363018,52

1893016,86

1491415,23

1153713,64

875312,10

50QP

2835522,30

2299220,33

1836018,41

1441116,53

1110014,69

60QP

2759824,47

2230222,25

1773620,07

1385417,93

HGZ7/1860-4

30QP

3008820,97

2788119,31

2240817,69

1766916,11

1366414,58

1039313,10

785511,67

40QP

3329623,23

2718121,27

2180019,36

1715317,49

1324015,67

1006113,89

50QP

3243425,60

2641123,35

2112221,14

1656718,98

1274616,68

60QP

3150328,09

2557225,54

2037523,04

1591220,59

HGZ7/2110-4

30QP

3881123,86

3163221,96

2540620,12

2007218,33

1557316,59

1184814,91

883713,27

40QP

3796026,43

3086824,20

2472922,02

1948319,89

1507117,82

1143315,80

50QP

3704029,13

3003526,56

2398424,05

1882521,59

1450019,18

60QP

3605031,96

2913329,06

2316926,21

1809723,42

R22 Performance data 50 Hz

Two-stage compressors - Performance data

Page 8: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

176 I www.bock.de

HGZ

Type

Numberof

cylinders

Displacement Electrical data 3 Weight Oil charge

50 Hz(1450 1/min)

LP HP

60 Hz(1740 1/min)

LP HP

Voltage

1

Max.working current

2

Max. powerconsumption

2

Startingcurrent

(rotor locked)

m³/h m³/h A kW A kg Ltr.

* PW 1+2 * PW1 / PW 1+2

HGZX7/1620-4 R404A

6 93,70 / 46,90 112,50 / 56,20 4 50 27,0 185 / 278 294 4,8HGZX7/1620-4 R410A

HGZ7/1620-4 R22

HGZX7/1860-4 R404A

6 107,60 / 53,80 129,10 / 64,60 4 55 30,0 185 / 278 291 4,8HGZX7/1860-4 R410A

HGZ7/1860-4 R22

HGZX7/2110-4 R404A

6 122,40 / 61,20 146,90 / 73,50 4 65 36,0 191 / 286 289 4,8HGZX7/2110-4 R410A

HGZ7/2110-4 R22

LP = low pressureHP = high pressure

Oil sump heater 230V -1- 50/60 Hz 140 WPermanently set version, installation in immersion sleeve

* PW = Part Winding, motors for part winding start 1 = 1. part winding 2 = 2. part winding

Explanations:

Tolerance (± 10%) relates to the mean value of the voltagerange. Other voltages and current types on request.

Take account of the max. operating current / max. powerconsumption when designing contactors, leads and fuses.Switches: Service category AC3

All data are based on the mean value of the voltage range.

380-420 V∆/YYY - 3 - 50 Hz PW440-480 V∆/YYY - 3 - 60 Hz PWPW = Part Winding, motors for part winding start(no start unloaders required) Winding ratios: 60% / 40%

1

2

3

4

Two-stage compressors - Technical data

Page 9: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

www.bock.de I 177

01

02

03

04

05

06

07

08

09

10

11

12

13

Dimensions in mm Centre of gravity

HGZ7 Standard Liquid subcooler with accessories supplied separately

HGZ7 Option Liquid subcooler with complete accessories directly mounted onto the compressor

Connections see page 178 -Rigid fixing without anti-vibration pad -Dimensions for view X see page 179 -

ca.285

ca.2

30

FÖV

J

P

D

B1

B

KO

D1H

SVX

CE

L

A1WDV

Q4xØ11

ca.630

576

290

340

ca.6

35

A

A3

A2

15,5

139

ca.825

472

189X

Z

RZ

Two-stage compressors - Dimensions and connections

ca.670

U

FS

FUE

FS

T

N FUA

X

260ca.

ca.950

ÖV1

V

R1

D

L1

3

2

1

Liquid subcooler with accessories Oil service valve Oil pressure safety switch 1 2 3

Page 10: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

178 I www.bock.de

Two-stage compressors - Dimensions and connections

Connections Connections

DV Discharge line Ø 35 mm / 1 3/8 " J Oil sump heater M 22 x 1,5

SV Suction line Ø 54 mm / 2 1/8 " K Sight glass 3 hole M 6

FUELiquid subcooler ON

Ø 16 mm - 5/8 " LConnection thermalprotection thermostat

1/8 " NPTF

FUALiquid subcooler OFF

Ø 16 mm - 5/8 " L1 Thermal protection thermostat 1/8 " NPTF

AConnection suction side,not lockable

1/8 " NPTF N Filter drier Ø 12 mm

A1Connection suction side,lockable

7/16 " UNF OConnection oil level regulator

1

A2Connection intermediate pressure, not lockable

1/8 " NPTF ÖVConnection oil service valve

1/4 " NPTF 1)

A3Connection intermediate pressure, not lockable

1/4 " NPTF ÖV1 Oil service valve 7/16 " UNF

BConnection discharge side,not lockable

1/8 " NPTF PConnection oil pressuredifferential sensor

M 20 x 1,5

B1Connection discharge side,lockable

7/16 " UNF QConnectionoil temperature sensor

1/8 " NPTF 1)

CConnection oil pressuresafety switch OIL

7/16 " UNF RConnectionequalizer for injection valve

7/16 " UNF

DConnection oil pressuresafety switch LP

7/16 " UNF R1 Equalizer for injection valve Ø 6 mm

D1Connection oil return fromoil separator

1/4 " NPTF T Solenoid valve Ø 12 mm

EConnection oil pressure gauge

7/16 " UNF UReinjection valve -dependent on refrigerant

Ø 12 mm

F Oil drain M 22 x 1,5 V Oil pressure safety switch MP 54 -

FSSight glassliquid line

Ø 12 mm WConnectionrefrigerant injection

M 22 x 1,5

H Oil charge plug M 22 x 1,5 XConnection for Schrader valve for intermediate pressure manometer

7/16 " UNF

1 Dimensions see view X page 179

Page 11: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

www.bock.de I 179

01

02

03

04

05

06

07

08

09

10

11

12

13

View X

Dimensions in mm

Possibility to connect to oil level regulator

Three-hole connection for oil level regulator make ESK, AC+R, CARLY (3x M6, 10 deep)

Two-stage compressors - Dimensions and connections

Page 12: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

180 I www.bock.de

Scope of supply

Semi-hermetic six cylinder reciprocating compressor with drive motor for part winding start380-420 V ∆/YYY - 3 - 50 Hz440-480 V ∆/YYY - 3 - 60 HzSingle-section compressor housing with hermetically integrated electric motor

Cylinder design in W form, LP/HP stage ratio 2:1

1 Intermediate pressure line mounted and insulated

2 Liquid subcooler, reinjection valve, solenoid valve, two sight glasses, fi lter drier. Supplied separately for individual, external installation

3 Winding protection with PTC sensors and Bock MP10 electronic motor protection

4 Oil pump cover with screw connection for oil differential pressure sensor (∆p switch Kriwan make)

5 Direct connection possibility for oil level regulators ESK, AC+R or CARLY

6 Oil sump heater 230 V - 1 - 50/60 Hz, 140 WPermanently set version, installation in immersion sleeve

Oil charge:HGZ: FUCHS Reniso SP 46HGZX: FUCHS Reniso Triton SE 55

7 Three sight glasses

Decompression valve

8 9

Suction and discharge line shut off valve

Inert gas charge

1 2 3

4 5

7 98

Two-stage compressors - Scope of supply

6

Page 13: Two-stage compressors - bock.de · PDF fileTwo-stage compressors - Dimensions and connections Connections Connections DV Discharge line Ø 35 mm / 1 3/ 8" J Oil sump heater M 22 x

www.bock.de I 181

01

02

03

04

05

06

07

08

09

10

11

12

13

1 2 3

4 65

Accessories

1 Liquid subcooler, reinjection valve, solenoid valve, two sight glasses, fi lter drier, directly mounted onto the compressor,fully assembled and insulated with pipes ready for connection

2 Oil pressure safety switch MP 54 230 V - 1 - 50/60 Hz, IP20, including installation

3 Oil differential pressure sensor (∆p switch Kriwan make)220-240 V - 1 - 50/60 Hz

4 Oil service valve

5 Thermal protection thermostat (PTC sensor) IP67

6 Bock Compressor Management BCM2000 including oil pressure control,oil temperature control (NTC), thermal protection thermostat (PTC) on HD side

Two-stage compressors - Accessories


Recommended