TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger TZW Karlsruhe ZW Karlsruhe Prüfstelle Wasser
Transcript
Page 1: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

The Influence of Water Treatment

on Corrosion of Materials in Service

Lines

and Drinking Water Installations

Josef Klinger

TZW Karlsruhe

TZW Karlsruhe Prüfstelle Wasser

Page 2: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Why to change the Water Treatment?

Water quality problems

New raw water resources

Merger of small water utilities

Corrosion problems – desalination

Consumer complaints – central softening

Page 3: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Central Softening

Precipitation (NaOH, Ca(OH)2)

Addition of acids (cooling water)

Ion exchange

Membrane filtration (nanofiltration, reverse osmosis)

Page 4: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Membrane Filtration

Page 5: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Reverse Osmosis

1 Feed 3 Feed spacer 5 Membrane 7 Permeate header2 Permeate 4 Concentrate 6 Permeate spacer 8 Sealing to pressure pipe

Page 6: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Example out of the Practice

Raw water quality

Groundwater

Winter m³/d 500

Summer m³/d 4.000

Conductivity mS/m 165

pH - 7,3

KS4,3 mmol/L 5,1

Hardness °dH 26

Chloride mg/L 325

Sulfate mg/L 70

Arsenic mg/L 0,010

Selenium mg/L 0,030

Hardness

Corrosion

Limit value

Page 7: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Pilot Study for Water Treatment

Version A

Mixture of desalinated water and aeration

Version B

100 % RO and stabilisation of desalinated water with CaCO3

Page 8: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Parameters of the Test Waters in the Pilot Plant

El. ConductivitypH

Alkalinity (pH: 4.3)Acidity (pH: 8.2)

Ca2+ 2++ MgNa+

Cl-

SO42-

NO3-

PO43- (total)

SiDOC

S1

mS/m

mmol/Lmmol/Lmmol/L

mg/Lmg/Lmg/Lmg/Lmg/L

mg/L Simg/L C

Tap Waterwith Inhibitor

148 -1647.3 - 7.4

5.10.64.713031070301.2

50.6 - 1,8

2

SoftenedTap Water

55 - 597.6 - 7.9

1.60.051.645

1002010

0.012

0.42

RO Filtrate afterCaCO3 Filtration

13 - 188.2 - 8.5

1.20.020.6

63

< 12

0.010.1

0.2 - 0,4<< 1

Parameter Unit Test Water 1 Test Water 2 Test Water 3

Tap:30%, RO:70%

Page 9: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Closed Loop Device

for Corrosion Tests with Iron Pipes

Pump

Test PipeFlowMeter

CoolingSystem

Effluent Stopcock

Cooler

Valve

Fresh Water Effluent

T O2

pH

SamplingPoint, V2

V

Page 10: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Corrosion and Iron Migration Rates

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

Cor

rosi

on

Ra

te[g

/md

]Fe

2

0 50 100 150 200 250

Running Time [d]

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

Mig

ratio

nR

ate

[g/m

d]F

e2

0 50 100 150 200 250

Running Time [d]

a) b)

Testwater 1Testwater 2Testwater 3

Page 11: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Mechanical Stability and Iron Migration Rates

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

Mig

ratio

nR

ate

[g/m

d]F

e2

0 50 100 150 200 250

Running Time [d]

b)

Testwater 1Testwater 2Testwater 3

0

20

40

60

80

100

120

Sta

bilit

yP

aram

eter

[g/m

²d]

Fe

0 50 100 150 200 250

Running Time [d]

c)

Page 12: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Corrosion Rates with changed Water Quality

Page 13: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Example of a „Turner Diagram“

0

50

100

150

200

Chl

orid

eC

once

ntra

tion

[mg/

L]

300

0 1 2 3 4 5 6

Carbonate Hardness [mol/m ]3

No Dezincification

Borderlinefor MS 58

Borderline for CR Brass

Testwater 1: 310 m/L Cl

Testwater 3 Source: Seppelfricke

Testwater 2

Page 14: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Metallurgical Structure of Duplex Brass

CuZn39Pb3 (Wieland Z33)Source: Wieland-Werke AG

Page 15: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Metallographical Grindings of the test pieces

Running Time: 220 Days

200 µmCuZn40Pb2 Testwater 1

200 µmCuZn40Pb2 Testwater 2

200 µmCuZn40Pb2 Testwater 3

Page 16: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Tempered Brass Material: CuZn40Pb2Running Time: 220 DaysTest Water 3(100 % RO + stabilisation) 200 µmb) CuZn40Pb2(t) Testwater 3

111 µm

Tempered Brass Material: CuZn40Pb2Running Time: 220 DaysTest Water 1Tap Water with Inhibitor

200 µma) CuZn40Pb2(t) Testwater 1

422 µm

Metallographic Sections of the test pieces

Page 17: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

The new Treatment Plant

Page 18: TZW Karlsruhe Prüfstelle Wasser The Influence of Water Treatment on Corrosion of Materials in Service Lines and Drinking Water Installations Josef Klinger.

TZW Karlsruhe Prüfstelle Wasser

Summary

The influence of a changed water quality on corrosion processes was assessed in a pilot plant

Corrosion assessment tools are available

Treatment plant is in service since two years

Corrosion processes are controlled as predicted

Prediction based on pilot plant tests were successful


Recommended