Think future. Switch to greenThink future. Switch to green.
Efficient solutions for motor control
New Products CatalogueIndustrial Switchgear | 2006
The complete range of
contac-tors, efficient motor-
starters and variable speed
drives for the motor circuit.
New simple to install
solutions based on clever
communication.
DIL contactors
PKZ motor-protec-tive circuit-breakers
MSC motor-starters
DS 4 softstarters
DF & DV Drives
Rapid Link
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 2/130
New Products Catalogue
Industrial Switchgear
Switching and Control 1 Contactor relaysDILA
2 ContactorsDILM7 – DILM150
3 Overload relaysZB12 – ZB150
Switching and Protection 4 Motor-protective circuit-breakersPKZM01, PKZM0, PKZM4
5 Fuseless motor-startercombinations
MSC-D, MSC-R
Information 6 Part number list,Alphabetical index
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 3/130
1/1
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r r e l a y s
D I L A
Contents, system overviewContactor relays DILA
Page
System overview 1/1
Contactor relays DILA 1/1
Contactor relays 1/2
Basic units DILA 1/2
Auxiliary contact modules 1/4
Accessories 1/6
Actuating voltages 1/9
Contactor relays DILA 1/9
Characteristic curves, contact travel diagrams 1/10
Contactor relays 1/10
Technical data 1/11Contactor relays DILA 1/11
Amplifier module, electronic timer module 1/14
Dimensions 1/17
Contactor relays 1/17
Electronic timer module 1/17
DILA Basic units 1
AC or DC operated
Magnet systemsAC 12 – 600 V, 50, 60, 50/60 Hz
0.8 – 1.1ϫ Uc24 VA/4 VA
DC 12 – 220 V DC0.8 – 1.1ϫ Uc
at 24 V:0.7 – 1.3ϫ Uc without extra auxiliary contact moduleAmbient temperature +40 °C3 W/3 W
Can be extended to 8 contacts
Interlocked opposing contacts
Modular system
Screw and snap fitting
Finger proof
Screw terminals
Spring-loaded terminals
a 1/3
Suppressors 2
All DC contactor relays have integral suppressor circuits
Suppressor circuits for AC contactor relays
a 1/6
Auxiliary contact modules 3, 4
2 or 4 pole
Overlapping contacts
Interlocked opposing contacts
a 1/5
1
4
3
2
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 4/130
Moeller NK1210+2100+2300-1153GB-INT
1/2
Moeller NK1210+2100+2300-1153GB-INT
Contactor relays Basic units DILA
AC operation DC
Connection technique Contacts Rated operationalcurrent
Conventionalcurrent,open at 60 °C
Code number Contact sequence Can be combinedwith auxiliarycontact module
Part no.Article no.
Pricesee pricelist
ParArti
N/O = Normally openN/C = Normally closed
AC–15
220 V230 V240 V
380 V400 V415 V
I e I e I th
A A A
Base units with interlocked opposing contacts
Screw terminals 4 N/O – 6 4 16 40E DILA-XHI(V)... DILA-40(230V50HZ)276329
DIL276
3 N/O 1 N/C 31E DILA-31(230V50HZ)276364
DIL276
2 N/O 2 N/C 22E DILA-22(230V50HZ)276399
DIL276
Spring-loadedterminals
4 N/O – 6 4 16 40E DILA-XHIC(V)... DILAC-40(230V50HZ)276441
DIL276
3 N/O 1 N/C 31E DILAC-31(230V50HZ)276473
DIL276
2 N/O 2 N/C 22E DILAC-22(230V50HZ)276505
DIL276
14
13 33
34
43
44
A1
A2
23
24
14
1 3 2 1
22
33
34
43
44
A1
A2
14
1 3 2 1
22
31
32
43
44
A1
A2
14
13 33
34
43
44
A1
A2
23
24
14
1 3 2 1
22
33
34
43
44
A1
A2
14
1 3 2 1
22
31
32
43
44
A1
A2
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 5/130
Moeller NK1210+2100+2300-1153GB-INT
1/4
Moeller NK1210+2100+2300-1153GB-INT
Contactor relays Auxiliary contact modules
Connectiontechnique
Contacts Rated operationalcurrent
Conventionalcurrent,open at 60 °C
Contactsequence
Code number and version of combination Part no.Article no.
N/O = Normally openN/OE = Normally open, early makeN/C = Normally closedN/CL = Normally closed, late break
AC–15 DILA(C)-40 DILA(C)-31 DILA(C)-22
220 V230 V240 V
380 V400 V415 V
I e I e I th
A A A
DILA auxiliary contact modules
With interlocked opposing contacts (exception: ...XHI(C)V...)
Screwterminals 2 pole – 2 N/C 6 3 16 42 E 33 24 DILA-XHI02276420
1 N/O 1 N/C 51E 42 33 DILA-XHI11276421
2 N/O – 60E 51 42 DILA-XHI20276422
1 N/OE 1 N/CL 51 42 33 DILA-XHIV11276423
4 pole – 4 N/C 44E 35 26 DILA-XHI04276424
1 N/O 3 N/C 53E 44 35 DILA-XHI13276425
2 N/O 2 N/C 62E 53 44 DILA-XHI22276426
3 N/O 1 N/C 71E 62 53 DILA-XHI31276427
4 N/O – 80E 71 62 DILA-XHI40
276428
1 N/O, 1 N/OE 1 N/C, 1 N/CL 62 53 44 DILA-XHIV22276429
Spring-loadedterminals
2 pole – 2 N/C 42 E 33 24 DILA-XHIC02276526
1 N/O 1 N/C 51E 42 33 DILA-XHIC11276527
2 N/O – 60E 51 42 DILA-XHIC20276528
1 N/OE 1 N/CL 51 42 33 DILA-XHICV11276529
4 pole – 4 N/C 44E 35 26 DILA-XHIC04276530
1 N/O 3 N/C 53E 44 35 DILA-XHIC13276531
2 N/O 2 N/C 62E 53 44 DILA-XHIC22
276532
3 N/O 1 N/C 71E 62 53 DILA-XHIC31276533
4 N/O – 80E 71 62 DILA-XHIC40276534
1 N/O, 1 N/OE 1 N/C, 1 N/CL 62 53 44 DILA-XHICV22276535
51
52
61
62
54
53 61
62
54
63
64
53
58
5 7 6 5
66
51
52
61
62
71
7 2 8 2
81
53 61 71 81
82726254
54
53 61
62
71
72
83
84
54
5 3 6 1
62
73
74
83
84
54
63 73
64 74
53 83
84
58
57 65
66
71
72
83
84
51
52
61
62
54
53 61
62
54
63
64
53
58
5 7 6 5
66
51
52
61
62
71
72 82
81
53 61 71 81
82726254
54
53 61
62
71
72
83
84
54
5 3 6 1
62
73
74
83
84
54
63 73
64 74
53 83
84
58
57 65
66
71
72
83
84
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 6/130
Moeller NK1210+2100+2300-1153GB-INT
D I L A
1/6 Accessories
Actuatingvoltage
Contact sequence For use with Part no.Article no.
Pricesee pricelist
Std. pack Notes
V
SuppressorVaristor suppressor
24 – 48 AC DILM7 – DILM15DILMP20DILA
DILM12-XSPV48281208
10 off For AC operated contactors50 – 60 Hz.On DC operated contactor relaysand on DILM115 and DILM150 thesuppressor circuit is built-in.Note drop-out delay
48 – 130 AC DILM12-XSPV130281209
130 – 240 AC DILM12-XSPV240281210
240 – 500 AC DILM12-XSPV500281211
Varistor with LED
24 – 48 AC DILM7 – DILM15DILMP20DILADILM7 – DILM15
DILMP20DILA
DILM12-XSPVL48281220
10 off For AC operated contactors50 – 60 Hz.On DC operated contactor relaysand on DILM115 and DILM150 the
suppressor circuit is built-in.Note drop-out delay
130 – 240 AC DILM12-XSPVL240281221
10 off
RC suppressor
24 – 48 AC DILM7 – DILM15DILMP20DILA
DILM12-XSPR48281199
10 off For AC operated contactors50 – 60 Hz.On DC operated contactor relaysand on DILM115 and DILM150 thesuppressor circuit is built-in.Note drop-out delay
110 – 240 AC DILM12-XSPR240281200
240 – 500 AC DILM12-XSPR500281201
Free-wheel diode suppressor
12 – 250 DC DILM7 – DILM15DILMP20DILA
DILM12-XSPD101672
10 off In addition to the built-insuppressor circuit for DC-actuatedcontactors.Prevents negative breaking voltagewhen contactors are used incombination with a safety PLC.
Voltage indicators
12 – 48 DC DILM7 – DILM15DILMP20DILA
DILM12-XSPI48285251
10 off For DC actuated contactors.
48 – 130 DC DILM12-XSPI130285252
110 – 250 DC DILM12-XSPI250285253
Connector
– – DILM7 – DILM65DILA
DILM32-XVB281227
50 off For mechanically arrangingcontactors in combinations.Distance between contactors 0 mm
Mechanical interlock
– – DILM7 – DILM15DILMP20DILA
DILM12-XMV281196
1 off For two contactors with AC or DCoperated magnet system which arehorizontally or vertically mounted,distance between contactors 0 mmMechanical lifespan 2.5x 106 operationsAdditional auxiliary contactmodules possiblea 1/5Including 2 contactor connectors.
A2
A1
A1
A2
A1
A2
A1
A2
A1
A2
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 7/130
1/7
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r r e l a y s
D I L A
Accessories
Actuating voltage For use with Contact sequence Part no.Article no.
Pricesee pricelist
Std. pack Notes
Electronic timer modules
on-delayed
24 V AC/DC DILM7 – DILM32DILMP20DILA
DILM32-XTEE11(RA24)101440
1 off Cannot be combined with:• DILM32-XHI...• DILM12-XSP...• DILM32-XSP...
Availability 12/05.
100 – 130 V AC DILM32-XTEE11(RAC130)101441
200 – 240 V AC DILM32-XTEE11(RAC240)101442
off-delayed
24 V AC/DC DILM7 – DILM32DILMP20DILA
DILM32-XTED11(RA24)101443
1 off Cannot be combined with:• DILM32-XHI...• DILM12-XSP...
• DILM32-XSP...
Availability 02/06.
100 – 130 V AC DILM32-XTED11(RAC130)101444
200 – 240 V AC DILM32-XTED11(RAC240)101445
For star-delta applications
24 V AC/DC DILM7 – DILM32DILMP20DILA
DILM32-XTEY20(RA24)101446
1 off Cannot be combined with:• DILM32-XHI...• DILM12-XSP...• DILM32-XSP...
Availability 02/06.
100 – 130 V AC DILM32-XTEY20(RAC130)101447
200 – 240 V AC DILM32-XTEY20(RAC240)101448
Sealable shrouds
Transparent
– DILM32-XTE... – DILM32-XTEPLH101449
1 off –
57
58
65
66
A1
A2
57
58
65
66
A1
A2
57
58
67
68
A1
A2
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 8/130
Moeller NK1210+2100+2300-1153GB-INT
D I L A
1/8 Accessories
Rated operational current Actuatingvoltage
Actuatingcurrent
Contact sequence For use with Part no.Article no.
Pricesee pricelist
Std. pack
AC-15 DC1) Us I
240V 415V 220V V DC mA
I e
I e
I e
A A A
Amplifier modules2)
Input with integral suppressor for overvoltage limit
2 2 0.03 24 25 As required ETS4-VS3083094
1 off
Notes 1) Making and breaking requirements in accordance with DC-11, L/R 300 ms2) Contactor coils with rated operational currents > 2 A must be energized via the contactor relay DILA.
13
14
21
22
For use with Part no.Article no.
Pricesee price list
Std. pack Notes
Device labelling
Sheet of adhesive labels
Inscription using laser printer, plotter,marker pen, copier
XGKE-GE207517
25 off 1 off = 1 sheet240 labels per sheet
1 sheet = DIN A4Can be split into two DIN A5 sheets
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 9/130
1/9
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r r e l a y s
D I L A
Actuating voltagesContactor relays DILA
With screw terminals: With spring-loaded terminals:
DILA-40(...) DILA-31(...) DILA-22(...) DILAC-40(...) DILAC-31(...) DILAC-22(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list
12V50Hz 276315 276350 276385 276430 276462 276494
24V50Hz 276316 276351 276386 276431 276463 276495
48V50Hz 276317 276352 276387 276432 276464 276496
240V50Hz 276318 276353 276388 276433 276465 276497
500V50Hz 276319 276354 276389 281415 281418 281421
24V60Hz 276320 276355 276390 276434 276466 276498
110V60Hz 276321 276356 276391 276435 276467 276499
115V60Hz 276322 276357 276392 276436 276468 276500
208V60Hz 276323 276358 276393 281416 281419 281422
600V60Hz 276324 276359 276394 281417 281420 281423
42V50Hz48V60Hz
276325 276360 276395 276437 276469 276501
110V50Hz120V60Hz
276326 276361 276396 276438 276470 276502
190V50Hz220V60Hz
276327 276362 276397 276439 276471 276503
220V50Hz240V60Hz
276328 276363 276398 276440 276472 276504
230V50Hz240V60Hz
276329 276364 276399 276441 276473 276505
380V50Hz440V60Hz
276330 276365 276400 276442 276474 276506
400V50Hz440V60Hz
276331 276366 276401 276443 276475 276507
415V50Hz480V60Hz
276332 276367 276402 276444 276476 276508
24V50Hz/60Hz 276333 276368 276403 276445 276477 276509
42V50Hz/60Hz 276334 276369 276404 276446 276478 276510110V50Hz/60Hz 276335 276370 276405 276447 276479 276511
220V50Hz/60Hz 276336 276371 276406 276448 276480 276512
230V50Hz/60Hz 276337 276372 276407 276449 276481 276513
380V50Hz/60Hz 276338 276373 276408 276450 276482 276514
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list
...V50Hz(12-500V) 276341 276376 276411 276453 276485 276517
...V60Hz(12-600V) 276342 276377 276412 276454 276486 276518
DC With screw terminals: With spring-loaded terminal:
DILA-40(...) DILA-31(...) DILA-22(...) DILAC-40(...) DILAC-31(...) DILAC-22(...)
Article no.1)
Article no.1)
Article no.1)
Article no.1)
Article no.1)
Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list
12 V DC 276343 276378 276413 276455 276487 276519
24 V DC 276344 276379 276414 276456 276488 276520
48 V DC 276345 276380 276415 276457 276489 276521
60V DC 276346 276381 276416 276458 276490 276522
110 V DC 276347 276382 276417 276459 276491 276523
220V DC 276348 276383 276418 276460 276492 276524
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list
...VDC (12-250V) 276349 276384 276419 276461 276493 276525
Notes 1) To obtain the article number for ordering, read under selected type and actuating voltage from the table.2) For non-standard voltages, state the actuating voltage selected from the range (...–...V) shown.
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 10/130
Moeller NK1210+2100+2300-1153GB-INT
D I L A
1/10 Characteristic curves, contact travel diagramsContactor relays
DILA (AC-15)
Component lifespan (operations) I e = Rated operational current
DILA (DC-131))
Component lifespan (operations) I e = Rated operational current
AC-15
240 V
0.01 0.050.02 20.1 0.5 10.2 5 10 A
20
10
5
2
1
0.5
0.2
0.1
x 106
I e
0.01 0.050.02 20.1 0.5 10.2 5 10 A
20
10
5
2
1
0.5
0.2
0.1
X 106
L
R
DC-13
24 V
Q 50 ms
I e
The diagrams show the closing and opening travel of the contact of the contactor relays and auxiliary contacts at no load.Tolerances are not taken into consideration.
DILA-....AC DILA-....DC
Normally open contact Normally open contact
Normally closed contact Normally closed contact
DILA-XHI(C)..AC DILA-XHI(C)..DC
Normally open contact Normally open contact
Normally closed contact Normally closed contact
DILA-XHI(C)V..AC DILA-XHI(C)V..DC
Normally open contact (early make) Normally open contact (early make)
Normally closed contact (late make) Normally closed contact (late make)
Notes 1) Making and breaking conditions to DC-13, time constant as stated.
4.5
4.53.30
0 1.0 2.9
2.92.10
0 0.7
4.5
4.53.20
01.6 2.9
2.92.30
00.7
4.5
4.52.00
0 2.8 2.9
2.91.10
0 1.9
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 11/130
1/11
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r r e l a y s
D I L A
Technical dataContactor relays DILA
DILA DILA...XHI
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operated Operations x 106 20 10
DC operated Operations x 106 20 10
Maximum operating frequency
Maximum operating frequency Operations/h 9000 9000
Climatic proofing Damp heat, constant, to IEC 60068-2-78;Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -25 – 60 -25 – 60
Enclosed °C -25 – 40 -25 – 40
Ambient temperature, storage °C -40/80 -40/80
Mounting position
Mounting position
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Basic unit with auxiliary contact module
N/O contact g 7 7
N/C contact g 5 5
Protection type IP20 IP20
Protection against direct contact when actuated from front(IEC 536)
Finger- and back-of-hand proof
Weight
AC operated kg 0.23 0.05
DC operated kg 0.28 0.05
Terminal capacities
Screw terminals
Solid mm2 1x (0,75 – 4)2x (0,75 – 2,5)
1x (0,75 – 4)2x (0,75 – 2,5)
Flexible with ferrule mm2 1x (0.75 – 2.5)2x (0.75 – 2.5)
1x (0.75 – 2.5)2x (0.75 – 2.5)
Solid or stranded AWG 18 – 14 18 – 14
Terminal screw M3.5 M3.5
Pozidriv screwdriver Size 2 2
Standard screwdriver mm 0.8x 5.51x 6
0.8x 5.51x 6
Max. tightening torque Nm 1.2 1.2
Spring-loaded terminalsSolid mm2 1x (0.75 – 2.5)
2x (0.75 – 2.5)1x (0.75 – 2.5)2x (0.75 – 2.5)
Flexible with or without ferrule DIN 46228 mm2 1x (0,75 – 1.5)2x (0,75 – 1.5)
1x (0,75 – 1.5)2x (0,75 – 1.5)
Solid or stranded AWG 18 – 14 18 – 14
Standard screwdriver mm 0.6x 3.5 0.6x 3.5
1 8 0 ˚
9 0 ˚ 9 0 ˚ 9 0
˚
30˚
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 12/130
Moeller NK1210+2100+2300-1153GB-INT
D I L A
1/12 Technical dataContactor relays DILA
DILA DILA...XHI
Contacts
Interlocked opposing contacts to ZH 1/457,including auxiliary contact module
Yes Yes
Rated impulse withstand voltage Uimp V AC 6000 6000Overvoltage category/pollution degree III/3 III/3
Rated insulation voltage Ui V AC 690 690
Rated operational voltage Ue V AC 690 500
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between coil and auxiliary contacts V AC 400 400
between the auxiliary contacts V AC 400 400
Rated operational current
AC–15
220/240 V I e A 6 6
380/415 V I e A 4 3
500 V I e A 1.5 –
DV-13
DC-13 L/R – 15 msContacts in series:
1 24 V A 10 10
1 60 V A 6 6
2 60 V A 10 10
1 110 V A 3 3
3 110 V A 6 6
1 220 V A 1 1
3 220 V A 5 5
DC-13 L/R – 50 ms
Contacts in series:
3 24 V A 4 –
3 60 V A 4 –
3 110 V A 2 –3 220 V A 1 –
Control circuit reliability(at Ue = 24 V DC, Umin = 17 V, I min= 5.4 mA)
Failure rate l <10-8, < one failure at 100 million operations
Conventional thermal current I th A 16 16
Short-circuit rating without welding
Maximum overcurrent protective device
220/240 V PKZM0 4 –
380/415 V PKZM0 4 –
Short-circuit protection maximum fuse
500 V A gG/gL 10 10
Current heat loss at I th
AC operated W 0.3 0.3
DC operated W 0.3 0.3
Notes 1) Making and breaking conditions to DC-13, time constant as stated2) See transparent overlay "Fuses" for time/current characteristics (please enquire)
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 13/130
1/13
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r r e l a y s
D I L A
Technical dataContactor relays DILA
DILA DILA...XHI
Magnet systems
Voltage tolerance
AC operated
Pick-up x Uc 0.8 – 1.1 –
DC operated
Pick-up x Uc 0.8 – 1.1 –
at 24 V: without auxiliary contact component (40 °C) Pick-up x Uc 0.7 – 1.3 –
Power consumption
50 Hz Pick-up VA 24 –
50 Hz Sealing VA 3.4 –
50 Hz Sealing W 1.2 –
60 Hz Pick-up VA 30 –
60 Hz Sealing VA 4.4 –
60 Hz Sealing W 1.4 –
50/60 Hz Pick-up VA 2725
–
50/60 Hz Sealing VA 4.23.3
–
50/60 Hz Sealing W 1.41.2
–
DC operated Pull-in = sealing W 3 –
Duty factor % DF 100 –
Switching times at 100 % Uc (approximate values)
AC operated closing delay ms 15 – 21 –
AC operated N/O contact opening delay ms 9 – 18 –
DC operated closing delay ms 31 –
DC operated N/O contact opening delay ms 12 –
Notes 1) Pure DC voltage, three-phase current bridge rectifier orsmoothed double-pulse bridge rectification
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 14/130
Moeller NK1210+2100+2300-1153GB-INT
D I L A
1/14 Technical dataAmplifier module, electronic timer modules
ETS4-VS3 DILM32-XTE
General
Standards IEC/EN 60947, VDE 0660, UL,CSA
DIN EN 61812, IEC/EN 60947,VDE 0660, UL, CSA
Lifespan, mechanicalAC operated Operations x 106 – 3
DC operated Operations x 106 30 3
Maximum operating frequency
220 V 230 V Operations x 106 72000 –
Climatic proofing Damp heat, constant, to IEC 60068-2-78;Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Storage °C – -40/80
Open °C -25 – 60 -25 – 60
Enclosed °C -25 – 45 -25 – 40
Mounting position As required As required, not suspended
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 20 msN/O contact g 10 –
Half-sinusoidal shock, 10 ms
N/O contact g – 6
N/C contact g – 6
Protection type IP20 IP20
Protection against direct contact when actuated from front(IEC 536)
Finger and back-of-hand proof
Weight kg 0.09 0.08
Terminal capacities
Solid mm2 1x (0.75 – 2.5)2x (0.75 – 2.5)1)
1x (0.75 – 2.5)2x (0.75 – 1.5)
Flexible with ferrule mm2 1x (0.75 – 2.5)2x (0.75 – 1.5)1)
1x (0.75 – 1.5)2x (0.75 – 1.5)
Solid or stranded AWG 16 – 14 18 – 14Terminal screw M3.5 M3.5
Pozidriv screwdriver Size 2 2
Standard screwdriver mm 0.8x 5.51x 6
0.8x 5.51x 6
Max. tightening torque Nm 1.2 1.2
Notes 1) Use only equal cross-sections
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 15/130
1/15
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r r e l a y s
D I L A
Technical dataAmplifier module, electronic timer modules
ETS4-VS3 DILM32-XTE
Contacts
Rated impulse withstand voltage Uimp V AC 6000 6000
Overvoltage category/pollution degree III/2 III/3
Rated insulation voltage Ui V AC 440 600
Rated operational voltage Ue V AC 440 400
Rated operational current
AC–15
220/240 V I e A 2 please enquire
380/415 V I e A 2 please enquire
DC-131)
DC-13 L/R – 15 ms
Contacts in series:
1 24 V A 2.6 –
1 60 V A 1 –
1 110 V A 0.6 –
1 220 V A 0.2 –
DC-13 L/R – 50 ms
Contacts in series:
1 24 V A 2 –
1 60 V A 0.6 –
1 110 V A 0.08 –
1 220 V A 0.08 –
DC-13 L/R – 300 ms
Contacts in series:
1 24 V A 0.6 –
1 60 V A 0.2 –
1 110 V A 0.08 –
1 220 V A 0.03 –
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between coil and auxiliary contacts V AC – 250
between the auxiliary contacts V AC – 250
Control circuit reliability(at Ue = 24 V DC, Umin = 17 V, I min= 5.4 mA)
Failure rate l <10-8, < one failure at100 million operations
–
Conventional thermal current I th A 6 6
Component lifespan
AC-15
230 V, I e = 0.1 A Operations x 106 7 –
230 V, I e = 1.2 A Operations x 106 1 –
Short-circuit rating without welding
Short-circuit protection Maximum fuse2)
500 V A gG/gL – 6
500 V A fast 4 –
Notes 1) Making and breaking conditions to DC-13, time constant as stated2) See transparent overlay "Fuses" for time/current characteristics (please enquire)
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 16/130
Moeller NK1210+2100+2300-1153GB-INT
D I L A
1/16 Technical dataAmplifier module, electronic timer modules
ETS4-VS3 DILM32-XTE
Magnet systems
Voltage tolerance
Pick-up voltage
AC operated
Pick-up x Uc – 0.85 – 1.1
DC operated
Pick-up x Uc 0.85 – 1.2 0.7 – 1.2
Power consumption
AC Sealing VA – 2
DC Sealing W – 1.8
DC operated Pull-in = sealing W 0.6 –
Duty factor % DF 100 100
Switching times at 100 % Uc (approximate values)
DC operated closing delay ms 7 –
DC operated, opening delay ms 3 –
Maximum operating frequency
Max. operating frequency Ops/h – 3600
6 A/250 V Ops./h – 360
Minimum contact closing time
On-delayed ms – < 50
Off-delayed ms – < 200
Repetition accuracy (with constant parameters) Deviation % – < 5
Recovery time (after 100% time delay) ms – 70
contact changeover time
DILM32-XTEE11/DILM32-XTED11 t ms – 10
DILM32-XTEY20 t ms – 50
Notes 1) Pure DC voltage, three-phase current bridge rectifier or smoothed double-pulse bridge rectification
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 17/130
1/17
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r r e l a y s
D I L A
DimensionsContactor relays
Contactor relays
DILA-...-XHI...
DILA-...(-C)-XHI...
Electronic timer moduleDILM32-XTE
DILA with DILM...XMV mechanical interlock
DILM12-XSPR...DILM12-XSPV(L)...DILM12-XSPI...
1 8
4 5
6.5
75
117
6 8
45
18
2 6 .
4
5 2 .
3
45
36 6.5
75
125
6 8
3 8
2 5
7045
4 5
6 8
6.5
75
4 5
6 8
90
DILM12-XSPR...DILM12-XSPV...DILM12-XSPI...
a 25a1 9.2
b 25.9
b1 28
b2 Q32
c 9a1 c
a
b 1
b 2
b
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 18/130
2/1
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Contents
Page
Technical overview 2/2
Contactors DILM 2/2
System overview 2/4
Contactors DILM7 – DILM150 2/4
Contactors 2/6
Basic units DILM 2/6
Complete units DILM 2/10
Auxiliary contact modules for DILM7 to DILM32 2/12
Auxiliary contact modules for DILM40 – DILM150 2/14
Contactors for three-phase capacitors 2/16
Engineering notes 2/17
Contactors for power factor correction 2/17
Contactor combinations 2/18
Star-delta combination 2/18
Reversing combination 2/20
Accessories 2/22
DILM contactors 2/22
Actuating voltages 2/27
Contactors screw terminals DILM 2/27
Contactors with springloaded terminals DILMC 2/30
Complete units DILM 2/33Individual coils DILM 2/36
Contactors for three-phase capacitors 2/37
Contactor combination SDAINLM 2/38
Contactor combination DIULM 2/40
Contact travel diagrams 2/42
Contactors DILM 2/42
Tripping characteristics 2/43
Contactors DILM 2/43
Engineering notes 2/44
Contactors for resistive load 2/44
Contactors, enclosure 2/46
Contactors DILM 2/47Technical data 2/48
Contactors DILM7 to DILM150 2/48
Contactor for capacitors DILMK 2/56
Auxiliary contacts 2/57
Dimensions 2/58
Contactors DILM 2/58
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 19/130
Moeller NK1210+2100+2300-1153GB-INT
2/2
Moeller NK1210+2100+2300-1153GB-INT
Technical overviewContactors DILM
Contactors DILE(E)M a Main catalogue for industrial switchgear
Contactors DILM3 pole
DIL M7 M9 M12 M15 M17 M25 M32 M40
Basic units Page a 2/7 a 2/7 a 2/7 a 2/7 a 2/7 a 2/7 a 2/7 a 2/7
Complete units Page a 2/11 a 2/11 a 2/11 – a 2/11 a 2/11 a 2/11 a 2/11
Rated operational voltage kW kW kW kW kW kW kW kW
AC-3Rated powerof three-phase motor 50 – 60 Hz
220 V – 230 V 2.2 2.5 3.5 4 5 7.5 10 12.5
380 V –400 V 3 4 5.5 7.5 7.5 11 15 18.5
440 V 4.5 5.5 7.5 8.4 10.5 15.5 20 25
500 V 3.5 4.5 7 7.5 12 17.5 23 28
660 V/690 V 3.5 4.5 6.5 7 11 14 17 23
1000 V – – – – – – – –
AC-4Rated powerof three-phase motor 50 – 60 Hz
i Increased life span of DILM7 – DILM150 to 200.000 operations
220 V – 230 V 1 1.5 2 2 2.5 3.5 4 5
380 V –400 V 2.2 2.5 3 3 4.5 6 7 9
440 V 2.4 3 3.6 3.6 5.5 7 8 10500 V 2.5 2.8 3.5 3.5 6 8 9 11
660 V/690 V 2.9 3.6 4.4 4.4 6.5 8.5 10 12
1000 V – – – – – – – –
AC-1Rated powerwith resistive load, 40 °C
220 V – 230 V 8 8 8 8 15 17 17 22
380 V –400 V 14 14 14 14 26 29 29 39
440 V 16 16 16 16 30 34 34 45
500 V 19 19 19 19 34 38 38 51
660 V/690 V 25 25 25 25 45 51 51 68
1000 V – – – – – – – –
Conventional thermalfree air current I th = I e open at 40 °C A A A A A A A A
up to 690 V 22 22 22 22 40 45 45 60
1000 V – – – – – – – –
Notes 1) on request
Contactors DILMP
4 pole
DIL MP20
Rated operational voltage Page a 2/7
AC-1Conventional free air thermal current I th = I e open, at 40 °C A
up to 690 V 22
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 20/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/4 System overviewContactors DILM7 – DILM150
6 6
54
4 55
1
3
3
1
11
3
32
2
5
6
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 21/130
2/5
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
System overviewContactors DILM7 – DILM150
Contactor up to 75 kW(AC-3/400 V)
1
Magnet systems:
AC: 12 – 600 V, 50, 60, 50/60 Hz
0.8 – 1.1x
U
cDC: 12 – 250 VDILM7 – DILM15: 0,8 – 1,1 x Uc
DILM17 – DILM150: 0,7 – 1,2 x Uc
bei 24 V: 0,7 – 1,3 x Uc without additional auxiliary contacts andambient temperature +40 °C
Coils for special voltages
“Safe isolation” to IEC 536between coil andcontacts
a 2/7
Suppressors 2RC suppressor
Varistor suppressorFree-wheel diode suppressor
a 2/22
Overload relays 3
Can be mounted directly
Separate mounting, possible
Protection of EEx e motors
EU prototype test certificate number
a 3/3
Auxiliary contact modules 4
2 pole, plug-in type
a 2/12
Auxiliary contact modules 5
4 pole, plug-in type
Overlapping contacts
a 2/12
Auxiliary contact modules 6
2 pole, side mounting
a 2/13
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 22/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 23/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 24/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 25/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/12 ContactorsAuxiliary contact modules for DILM7 to DILM32
Connectiontechnique
Conventional free airthermal current I th = I e AC-1 at 60 °C
Contacts Contactsequence
Can becombined withbasic unit
Part no.Article no.
Pricesee pricelist
Std. pack
Open N/O = Normally openN/OE = Normally open, early make
N/C = Normally closedN/CL = Normally closed, late break
I th = I e
A
Auxiliary contact modules
With positively driven contacts; except XHIV and XHICV
Top-mounting auxiliary switches
Screwterminals
2 pole 16 1 N/O 1 N/C DILM(C)7-10...DILM(C)9-10...DILM(C)12-10...DILM(C)15-10...DILM(C)17-10...DILM(C)25-10...DILM(C)32-10...
DILM32-XHI11277376
5 off
2 pole – 2 N/C DILM32-XHI02277375
4 pole 2 N/O 2 N/C DILM32-XHI22277377
spring-loadedterminals
2 pole 16 1 N/O 1 N/C DILM32-XHIC11277751
2 pole – 2 N/C DILM32-XHIC02277750
4 pole 2 N/O 2 N/C DILM32-XHIC22277752
Screwterminals
2 pole 16 2 N/O – DILM(C)7...DILM(C)9...DILM(C)12...DILM(C)15...DILM(C)17...DILM(C)25...DILM(C)32...
DILA-XHI20276422
1 N/O 1 N/C DILA-XHI11276421
– 2 N/C DILA-XHI02276420
1 N/OE 1 N/CL DILA-XHIV11276423
4 pole 16 4 N/O – DILA-XHI40276428
3 N/O 1 N/C DILA-XHI31276427
2 N/O 2 N/C DILA-XHI22276426
1 N/O 3 N/C DILA-XHI13276425
– 4 N/C DILA-XHI04276424
1 N/O,1 N/OE
1 N/C,1 N/CL
DILA-XHIV22276429
spring-loadedterminals
2 pole 16 2 N/O – DILA-XHIC20276528
1 N/O 1 N/C DILA-XHIC11276527
– 2 N/C DILA-XHIC02276526
1 N/OE 1 N/CL DILA-XHICV11276529
Notes • Interlocked opposing contacts, to IEC/EN 60947-5-1 Annex L, within the auxiliary contact modules(not N/O (early make) and N/C (late break) contacts) and for the built-in auxiliary contacts of the DILM7 – DILM32
• Auxiliary break contact can be used as mirror contact to IEC/EN 60947-4-1 Annex F (not N/C (late break) contact)• No auxiliary contacts can be fitted between 2 contactors.
21
22
33
34
21
22
31
32
21
22
31
32
43
44
53
54
21
22
33
34
21
22
31
32
21
22
31
32
43
44
53
54
54
63
64
53
54
53 61
62
51
52
61
62
58
5 7 6 5
66
54
63 73
64 74
53 83
84
54
53 61
62
73
74
83
84
54
53 61
62
71
72
83
84
53 61 71 81
82726254
51
52
61
62
71
72 82
81
58
57 65
66
71
72
83
84
54
63
64
53
54
53 61
62
51
52
61
62
58
5 7 6 5
66
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 26/130
2/13
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
ContactorsAuxiliary contact modules for DILM7 to DILM32
Connectiontechnique
Conventional free airthermal current I th = I e AC-1 at 60 °C
Contacts Contactsequence
Can becombined withbasic unit
Part no.Article no.
Pricesee pricelist
Std. pack
Open N/O = Normally openN/OE = Normally open, early make
N/C = Normally closedN/CL = Normally closed, late break
I th = I e
A
Auxiliary contact modules
With positively driven contacts; except XHIV and XHICV
Top-mounting auxiliary switches
spring-loadedterminals
4 pole 16 4 N/O – DILM(C)7...DILM(C)9...DILM(C)12...DILM(C)15...DILM(C)17...DILM(C)25...DILM(C)32...
DILA-XHIC40276534
5 off
3 N/O 1 N/C DILA-XHIC31276533
2 N/O 2 N/C DILA-XHIC22276532
1 N/O 3 N/C DILA-XHIC13276531
– 4 N/C DILA-XHIC04276530
1 N/O,1 N/OE
1 N/C,1 N/CL
DILA-XHICV22276535
High version
Screwterminals
2 pole 16 2 N/O – DILM7...DILM9...DILM12...DILM15...
DILA-XHIT20101042
5 off
1 N/O 1 N/C DILA-XHIT11101043
– 2 N/C DILA-XHIT02101041
4 pole 2 N/O 2 N/C DILA-XHIT22101044
Side mounting auxiliary contacts2)
Screwterminals
2 pole 10 1 N/O 1 N/C DILM17...DILM25...DILM32...
DILM32-XHI11-S101371
1 off
Notes 1) Suitable for combination with electrical wire jumpers in tool-less plug connection;for use with:DILM12-XSLDILM12-XRLDILM12-XS1
PKZM0-XDM12PKZM0-XRM12PKZM0-XSM12
1 PKZM02 DILM7 – DILM153 DILA-XHIT4 PKZM0-XDM12
2) Can be fitted only to the left of the contactor; can not be combined with top-mounting auxiliary contacts or mechanical interlocks
• Interlocked opposing contacts, to IEC/EN 60947-5-1 Annex L, within the auxiliary contact modules(not N/O (early make) and N/C (late break) contacts) and for the built-in auxiliary contacts of the DILM7 – DILM32
• Auxiliary break contact can be used as mirror contact to IEC/EN 60947-4-1 Annex F (not N/C (late break) contact)• No auxiliary contacts can be fitted between 2 contactors.
54
63 73
64 74
53 83
84
54
53 61
62
73
74
83
84
54
53 61
62
71
72
83
84
53 61 71 81
82726254
51
52
61
62
71
72 82
81
58
57 65
66
71
72
83
84
54
63
64
53
54
5 3 6 1
62
51
52
61
62
54
53 61
62
71
72
83
84
54
53 61
62
1
2
3
4
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 27/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/14 ContactorsAuxiliary contact modules for DILM40 to DILM150
Connectiontechnique
Conventionalthermal current I th = I e AC-1 at 50 °C
Contacts Contactsequence
Can becombinedwith basicunit
Part no.Article no.
Pricesee pricelist
Std. pack
Open N/O = Normally openN/OE = Normally open, early make
N/C = Normally closedN/CL = Normally closed, late break
I th = I e
A
Auxiliary contact modules
With positively driven contacts; except XHIV and XHICV
Screwterminals
2 pole 10 2 N/O – DILM40...DILM50...DILM65...DILM80...DILM95...DILM115...DILM150...
DILM150-XHI20277945
5 off
10 1 N/O 1 N/C DILM150-XHI11277946
10 1 N/O 1 N/C DILM150-XHIA11283463
10 – 2 N/C DILM150-XHI02277947
Screwterminals 4 pole 10 4 N/O – DILM150-XHI40277948
10 3 N/O 1 N/C DILM150-XHI31277949
10 2 N/O 2 N/C DILM150-XHI22277950
10 2 N/O 2 N/C DILM150-XHIA22283464
10 1 N/O 3 N/C DILM150-XHI13277951
10 – 4 N/C DILM150-XHI04277952
10 1 N/O,
1 N/OE
1 N/C,
1 N/CL
DILM150-XHIV22
277953
spring-loadedterminals
4 pole 10 4 N/O – DILMC40...DILMC50...DILMC65...DILMC80...DILMC95...DILMC115...DILMC150...
DILM150-XHIC40278044
10 3 N/O 1 N/C DILM150-XHIC31278045
10 2 N/O 2 N/C DILM150-XHIC22278046
10 2 N/O 2 N/C DILM150-XHIAC22283465
10 1 N/O 3 N/C DILM150-XHIC13278047
10 – 4 N/C DILM150-XHIC04
278048
10 1 N/O,1 N/OE
1 N/C,1 N/CL
DILM150-XHICV22278049
Side mounting auxiliary contacts
Screwterminals
2 pole 10 1 N/O 1 N/C DILM40 –DILH2000
DILM1000-XHI11-SI278425
1 off
10 1 N/OE 1 N/CL DILM40 –DILH2000
DILM1000-XHIV11-SI278426
10 1 N/O 1 N/C DILM80 –DILH2000
DILM1000-XHI11-SA278427
spring-loaded
terminals
10 1 N/O 1 N/C DILMC40 –DILMC500-S
DILM1000-XHIC11-SI278428
10 1 N/O 1 N/C DILMC80 –DILMC500-S
DILM1000-XHIC11-SA278430
14 24
13 23
14
13 21
22
54
53 61
62
12
11 21
22
14
13 23
24
33
34
43
44
14
13 21
22
33
34
43
44
14
13 21
22
31
32
43
44
54
53 61
62
71
72
83
84
14
13 21
22
31
32
41
42
12
11 21
22
31
32
41
42
14
13 21
22
35
36
47
48
14
13 23
24
33
34
43
44
14
13 21
22
33
34
43
44
14
13 21
22
31
32
43
44
54
53 61
62
71
72
83
84
14
13 21
22
31
32
41
42
12
11 21
22
31
32
41
42
14
1 3 2 1
22
35
36
47
48
134 4
144 3
213 2
3 122
17 4 8
184 7
25 3 6
263 5
53 8 4
54 62
61 7 2
7 1 8 3
134 4
144 3
213 2
3 122
53 8 4
54 62
61 7 2
7 1 8 3
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 28/130
2/15
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
ContactorsAuxiliary contact modules for DILM40 – DILM150
DILM1000-XHI(V)(C)11-SI DILM1000-XHI(V)(C)11-SA DILM150-XHI(C)20
DILM150-XHI(C)11DILM150-XHI(C)02
DILM150-XHI(C)40
DILM150-XHI(C)31DILM150-XHI(C)(V)22DILM150-XHI(C)13DILM150-XHI(C)04
DILM150-XHIA11 DILM150-XHIA(C)22
DILM40...DILM65
2x – – – 1x –
– 2x 1x – – –
1x – – – – 1x
– 1x – 1x – –
DILM80...DILM150
2x 2x – – – –
2x – – – – 1x
2x – – – 1x –
– 2x – 1x – –
– 2x 1x – – –
Notes Side mounted auxiliary contacts
a DILM40 – DILM65b DILM80 – DILM150
• Forced operation contact to IEC/EN 60947-5-1 Appendix L, inside the auxiliary contact unit (not early close and late opening).• Auxiliary normally closed contact can be used as mirror contact to IEC/EN 60947-4-1 Appendix F (not late opening).• No auxiliary contacts can be fitted between 2 contactors.
DILM1000-XHI(C)..
+ a +
DILM1000-XHI(C)..-SI
DILM1000-XHI(C)..-SA
b+ + ++
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 29/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/16 Contactors for three-phase capacitors
Three-phase capacitors 50 – 60 Hz Contact sequence Part no.Article no.
Pricesee pricelist
Std. pack
Open
230 V 400 V420 V440 V
525 V 690 V
kvar kvar kvar kvar
With series resistors without quick-discharge resistor
Basic units
7.5 12.5 16.7 20 DILK12-11(230V50HZ)293988
1 off
11 20 25 33.3 DILK20-11(230V50HZ)294010
15 25 33.3 40 DILK25-11(230V50HZ)294032
20 33.3 40 55 DILK33-10(230V50HZ)294054
25 50 65 85 DILK50-10(230V50HZ)294076
Notes Availability on request.
In the case of group compensation multi-stage capacitor banks are connected to the mains, as required. In the process, transient currents of upto 180x I e can flow between the capacitors.The capacitors are pre-charged via the early-make auxiliary contacts and the fitted wire resistors, thereby reducing the inrush current. The maincontacts then close after a time lag and carry the uninterrupted current.The contactors for capacitors are weld-resistant with inrush current peaks up to 180 x I e due to their special contacts.For switching reactive-power compensation equipment with chokes, observe design notes.
For switching of power factor correction with reactors please observe engeneering notes a 2/17
1 3 5
2 4 6
13 21
14 22
A1
A2
1 3 5
2 4 6
13
14
A1
A2
Weld-resistant for capacitors with inrush current peaks up to 180 x I N
Accessories
Enclosure
Accessories a 2/22
Further actuating voltages a 2/37
R11 R11
R11
C1
L 1 L 2 L 3
1 3 5
642A2
A1
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 30/130
2/17
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Engineering notesContactors for power factor correction
Ordering data Switching duty230 V 400 V
420 V440 V
525 V 690 V
Part no. Page kvar kvar kvar kvar
Individual compensation, open versionDILM7 a 2/7 1.5 3 3.5 5
DILM9 a 2/7 2 4 4.5 6
DILM12 a 2/7 2.5 4.5 5.5 7
DILM15 a 2/7 2.5 4.5 5.5 7
DILM17 a 2/7 6.5 12 14.5 19
DILM25 a 2/7 7 13.5 16 21
DILM32 a 2/7 7.5 14.5 17 22.5
DILM40 a 2/7 11 20.5 24.5 32
DILM50 a 2/7 11.5 22 26 34.5
DILM65 a 2/7 12.5 23.5 28 37
DILM80 a 2/7 16 30.5 36.5 48
DILM95 a 2/7 18 34 41 54
DILM115 a 2/7 24 46 54.5 72DILM150 a 2/7 28 53 63.5 83.5
DILM185 Main catalogue forindustrialswitchgeara 5/30
87 150 190 150
DILM300 115 200 265 200
DILM580 175 300 400 300
Group compensation, with reactor, open version
DILM7 a 2/7 4 7 7.5 12
DILM9 a 2/7 5 8 10 14
DILM12 a 2/7 5.5 10 12 16
DILM15 a 2/7 5.5 10 12 16
DILM17 a 2/7 7.5 16 20 28
DILM25 a 2/7 9 18 23 30
DILM32a
2/7 10 20 24 32DILM40 a 2/7 13 25 30 40
DILM50 a 2/7 16 30 36 48
DILM65 a 2/7 19 36 43 57
DILM80 a 2/7 30 58 68 90
DILM95 a 2/7 34 66 79 104
DILM115 a 2/7 44 80 100 125
DILM150 a 2/7 50 97 115 152
DILM185 Main catalogue forindustrialswitchgeara 5/30
80 150 200 260
DILM225 100 175 230 300
DILM250 110 190 260 340
DILM300 130 225 290 390
DILM400 160 280 370 480
DILM500 220 390 500 680
Group compensation, without reactor, open version
DILK12 a 2/16 7.5 12.5 16.7 20
DILK20 a 2/16 11 20 25 33.3
DILK25 a 2/16 15 25 33.3 40
DILK33 a 2/16 20 33.3 40 55
DILK50 a 2/16 25 50 65 85
DILM185 Main catalogue forindustrialswitchgeara 5/30
66 115 145 115
DILM300 85 150 195 150
DILM580 145 250 333 250
Notes Use of the contactors DILM without series resistor for centralised power factor correctionWhen using contactors for group compensation, a minimum inductance of approx. 6 µH per capacitor must be availableto limit the high inrush current peaks. This corresponds to an air-cored coil with 5 windings and a coil diameter of
approximately ∅ 140 mm. The conductor cross-section must be selected according to the rated current per phase.
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 31/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 32/130
Moeller NK1210+2100+2300-1153GB-INT
2/20
Moeller NK1210+2100+2300-1153GB-INT
Contactor Combinations Reversing combination
AC operation
Ratedoperationalcurrent
Max. rating for three-phase motors, 50 – 60 Hz Part no.Article no.
Pricesee price list
Std. pack Individual components of the combination Spare auxiliary contac
AC-3 AC-3 AC-4 Contactor Q11 Contactor Q12 Q11 Q12 Meint
400 V 220/230 V
380/400 V
660 V690 V
220/230 V
380/400 V
660 V690 V
I e P P P P P P Part No. Part No.
A kW kW kW kW kW kW
Reversing contactors
7 2.2 3 3.5 1 2.2 2.9 DIULM7/21(230V50HZ)278061
1 off DILM7-01+ DILA-XHI20
DILM7-01+ DILA-XHI20
+
9 2.5 4 4.5 1.5 2.5 3.6 DIULM9/21(230V50HZ)278086
DILM9-01+ DILA-XHI20
DILM9-01+ DILA-XHI20
+
12 3.5 5.5 6.5 2 3 4.4 DIULM12/21(230V50HZ)278111
DILM12-01+ DILA-XHI20
DILM12-01+ DILA-XHI20
+
18 5 7.5 11 2.5 4.5 6.5 DIULM17/21(230V50HZ)278136
DILM17-01+ DILA-XHI20
DILM17-01+ DILA-XHI20
+
25 7.5 11 14 3.5 6 8.5 DIULM25/21(230V50HZ)278161
DILM25-01+ DILA-XHI20
DILM25-01+ DILA-XHI20
+
32 10 15 17 4 7 10 DIULM32/21(230V50HZ)278186
DILM32-01+ DILA-XHI20
DILM32-01+ DILA-XHI20
+
40 12.5 18.5 23 5 9 12 DIULM40/11(230V50HZ)278211
1 off DILM40+ DILM150-XHI11
DILM40+ DILM150-XHI11
– – +
50 15.5 22 30 6 10 14 DIULM50/11(230V50HZ)278236
DILM50+ DILM150-XHI11
DILM50+ DILM150-XHI11
– – +
65 20 30 35 7 12 17 DIULM65/11(230V50HZ)278261
DILM65+ DILM150-XHI11
DILM65+ DILM150-XHI11
– – +
80 25 37 63 12 20 26 DIULM80/11(230V50HZ)
239799
DILM80
+ DILM150-XHI11
DILM80
+ DILM150-XHI11
– – +
95 30 45 75 16 26 35 DIULM95/11(230V50HZ)239841
DILM95+ DILM150-XHI11
DILM95+ DILM150-XHI11
– – +
115 37 55 90 17 28 43 DIULM115/11(RAC240)239862
DILM115+ DILM150-XHI11
DILM115+ DILM150-XHI11
– – +
150 48 75 96 20 33 48 DIULM150/11(RAC240)239880
DILM150+ DILM150-XHI11
DILM150+ DILM150-XHI11
– – +
64
63
64
63
64
63
64
63
64
63
64
63
64
63
64
63
64
63
64
63
64
63
64
63
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 33/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/22 AccessoriesContactors DILM
Voltage For use with Contact sequence Part no.Article no.
Pricesee pricelist
Std. pack Notes
V
Suppressors
RC suppressors
24 – 48 AC DILM7 – DILM15DILMP20DILA
DILM12-XSPR48281199
10 off For AC operated contactors 50 – 60 Hz.On DC operated contactor relays and onDILM115 and DILM150 the suppressorcircuit is built-in.Note drop-out delay
110 – 240 AC DILM12-XSPR240281200
240 – 500 AC DILM12-XSPR500281201
24 – 48 AC DILM17 – DILM32 DILM32-XSPR48281202
110 – 240 AC DILM32-XSPR240281203
240 – 500 AC DILM32-XSPR500281204
24 – 48 AC DILM40 – DILM95 DILM95-XSPR48281205
110 – 240 AC DILM95-XSPR240281206
240 – 500 AC DILM95-XSPR500281207
Varistor suppressors
24 – 48 AC DILM7 – DILM15DILMP20DILA
DILM12-XSPV48281208
10 off For AC operated contactors 50 – 60 Hz.On DC operated contactor relays and onDILM115 and DILM150 the suppressorcircuit is built-in.Note drop-out delay
48 – 130 AC DILM12-XSPV130281209
130 – 240 AC DILM12-XSPV240281210
240 – 500 AC DILM12-XSPV500281211
24 – 48 AC DILM17 – DILM32 DILM32-XSPV48281212
48 – 130 AC DILM32-XSPV130281213
130 – 240 AC DILM32-XSPV240281214
240 – 500 AC DILM32-XSPV500281215
24 – 48 AC DILM40 – DILM95 DILM95-XSPV48281216
48 – 130 AC DILM95-XSPV130281217
130 – 240 AC DILM95-XSPV240281218
240 – 500 AC DILM95-XSPV500281219
Varistor suppressors with integated LED
24 – 48 AC DILM7 – DILM15DILMP20DILA
DILM12-XSPVL48281220
10 off For AC operated contactors 50 – 60 Hz.On DC operated contactor relays and onDILM115 and DILM150 the suppressorcircuit is built-in.Note drop-out delay
130 – 240 AC DILM12-XSPVL240281221
24 – 48 AC DILM17 – DILM32 DILM32-XSPVL48281222
130 – 240 AC DILM32-XSPVL240281223
24 – 48 AC DILM40 – DILM95 DILM95-XSPVL48281224
130 – 240 AC DILM95-XSPVL240281225
A1
A2
A2
A1
A1
A2
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 34/130
2/23
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
AccessoriesContactors DILM
Voltage For use with Contactsequence
Part no.Article no.
Pricesee pricelist
Std. pack Notes
V
Free-wheel diode suppressor
12 – 250 DC DILM7 – DILM15DILMP20DILA
DILM12-XSPD101672
10 off In addition to the built-in suppressorcircuit for DC actuated contactors.Prevents negative breaking voltage whencontactors are used in combination with asafety PLC.
Voltage indicators
12 – 48 DC DILM7 – DILM15DILMP20DILA
DILM12-XSPI48285251
10 off For DC actuated contactors.
48 – 130 DC DILM12-XSPI130285252
110 – 250 DC DILM12-XSPI250285253
RDC24 DILM17 – DILM32 DILM32-XSPI48285254
RDC60,RDC130
DILM32-XSPI130285255
RDC240 DILM32-XSPI250285256
RDC24,RAC24, RAC48
DILM40 – DILM150 DILM150-XSPI48285257
For DC operated contactors DILM40 – DILM95and contactors DILM115 and DILM150
RDC120,RAC60,RAC130
DILM150-XSPI130285258
RDC240,RAC240
DILM150-XSPI250285259
A1
A2
A1
A2
For use with Part no.Article no.
Pricesee pricelist
Std. pack Notes
Links
DILM7 – DILM65DILA
DILM32-XVB281227
50 off For mechanically arranging contactorsin combinations.Distance between contactors 0 mm
DILM7 – DILM150 DILM150-XVB281226
10 off
Mechanical interlock including contactor connector
DILM7 – DILM15DILMP20DILA
DILM12-XMV281196
1 off For two contactors with AC or DC operatedmagnet system which are horizontally or verticallymounted, distance between contactors 0 mmMechanical lifespan 2.5x 106 operationsAdditional auxiliary contact modules possiblea 2/12DIL 150-XMV including mounting plate forcontactors
DILM17 – DILM32 DILM32-XMV281197
DILM40 – DILM65 DILM65-XMV281198
DILM80 – DILM150 DILM150-XMV240081
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 35/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/24 AccessoriesContactors DILM
For use with Part no.Article no.
Pricesee pricelist
Std. pack Notes
Set of paralleling links
Consisting of two paralleling links
DILM7 – DILM15 DILM12-XP1281193
5 off 4th pole can be broken off AC-1 current carrying capacity of the open contactorincreases by a factor of 2.5.Protected against accidental contact in accordancewith IEC 536.Terminal capacity for DILM..-XP1 a 2/60DILM17 – DILM32 DILM32-XP1
2811945 off
DILM40 – DILM65 DILM65-XP1281195
1 off
DILM80 – DILM150 DILM150-XP1284769
1 off
Star-point bridges
DILM7 – DILM15 DILM12-XS1281190
20 off • Tool-less plug connection type• As auxiliary contactor use DILA-XHIT... a 2/13
DILM17 – DILM32 DILM32-XS1281191
20 off –
DILM40 – DILM65 DILM65-XS1281192
10 off –
DILM80 – DILM150 DILM150-XS1284768
1 off –
Star-delta wiring kits
Main current wiring for star-delta combination– including star-point bridge
DILM7/9/12/15 mains contactorDILM7/9/12/15 delta contactorDILM7/9/12/15 star contactor
DILM12-XSL283130
1 off • Tool-less plug connection type• as auxiliary contactor use DILA-XHIT... a 2/13The following control cables are integrated in addition
to electrical interlock:• Q13: A1 – Q15: 21• Q13: 21 – Q15: A1• Q13: A2 – Q15: A2
DILM17/25/32 mains contactorDILM17/25/32 delta contactorDILM17/25/32 star contactor
DILM32-XSL283131
–
DILM40/50/65 mains contactorDILM40/50/65 delta contactorDILM40/50/65 star contactors
DILM65-XSL101058
–
Reversing starter wiring kits
Main current wiring for reversing combinationDILM7DILM9DILM12
DILM12-XRL283108
1 off • Tool-less plug connection type• as auxiliary contactor use DILA-XHIT... a 2/13The following control cables are integrated in additionto electrical interlock:• Q11: A1 – Q12: 21• Q11: 21 – Q12: A1• Q11: A2 – Q12: A2
DILM17DILM25DILM32
DILM32-XRL283109
–
DILM40DILM50DILM65
DILM65-XRL101057
–
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 36/130
2/25
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
AccessoriesContactors DILM
For use with Contact sequence Part no.Article no.
Pricesee pricelist
Std. pack Notes
Three-phase commoning links
Protected against accidental contact, short-circuit proof,Ue = 690 V, I u = 63 ACan be extended by rotated mountig.
DILM7DILM9DILM12DILM15
– DILM12-XDSB0/3240084
5 off Suitable for 3 contactors,length 135 mm
– DILM12-XDSB0/4240085
Suitable for 4 contactors,length 180 mm
– DILM12-XDSB0/5240086
Suitable for 5 contactors,length 225 mm
4th pole
Only for AC 1 load, up to two auxiliary contacts can be fitted; suitable forisolating non-earthed and poorly earthed neutral conductors.
DILM40 NDIL0M062006
1 off I e AC-1 Open/Enclosed 35 A/30 A
DILM40 NDIL1M060243
I
e AC-1 Open/Enclosed 55 A/44 A
DILM50DILM65
NDIL2M060264
I e AC-1 Open/Enclosed 75 A/60 A
Electronic timer modules
on-delayed
24 V AC/DC DILM7 – DILM32DILMP20DILA
DILM32-XTEE11(RA24)101440
1 off Cannot be combined with:• DILM32-XHI...• DILM12-XSP...• DILM32-XSP...
Availability 12/05.
100 – 130 V AC DILM32-XTEE11(RAC130)101441
200 – 240 V AC DILM32-XTEE11(RAC240)101442
off-delayed
24 V AC/DC DILM7 – DILM32DILMP20DILA
DILM32-XTED11(RA24)101443
1 off Cannot be combined with:• DILM32-XHI...• DILM12-XSP...• DILM32-XSP...
Availability 02/06.
100 – 130 V AC DILM32-XTED11(RAC130)101444
200 – 240 V AC DILM32-XTED11(RAC240)101445
For star-delta applications
24 V AC/DC DILM7 – DILM32DILMP20DILA
DILM32-XTEY20(RA24)101446
1 off Cannot be combined with:• DILM32-XHI...• DILM12-XSP...• DILM32-XSP...
Availability 02/06.
100 – 130 V AC DILM32-XTEY20(RAC130)101447
200 – 240 V AC DILM32-XTEY20(RAC240)101448
Sealable shroudsTransparent
DILM32-XTE... – DILM32-XTEPLH101449
1 off –
Device labelling
Sheet of adhesive labels
Inscription usinglaser printer,plotter, markerpen, copier
– XGKE-GE207517
25 off 1 off = 1 sheet240 labels per sheet
1 sheet = DIN A4Can be split into two DIN A5sheets
8 7
7 8
57
58
65
66
A1
A2
57
58
65
66
A1
A2
57
58
67
68
A1
A2
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 37/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/26 AccessoriesContactors DILM
Rated operational current Actuatingvoltage
Actuatingcurrent
Contact sequence For use with Part no.Article no.
Pricesee pricelist
Std. pack
AC-15 DC
240V 415V 220V
I e I e I e Us I
A A A V DC mA
Amplifier modules
Separate mountingInput with integral suppressor for overvoltage limit
2 2 0.03 24 25 As required ETS4-VS3083094
1 off
Notes Contactor coils with rated operational currents > 2 A must be energized via the contactor relay DILA.Making and breaking conditions for ETS4-VS3 to DC-11, L/R 300 ms
13
14
21
22
AC DC
For use with Part no.Article no.
Pricesee pricelist
Part no.Article no.
Pricesee pricelist
Std. pack Notes
Individual coils
DILM17DILM25DILM32
DILM32-XSP(230V50HZ)281141
DILM32-XSP(RDC24)281155
1 off Other actuating voltagesa 2/36
DILM40DILM50DILM65
DILM65-XSP(230V50HZ)281171
DILM65-XSP(RDC24)281185
DILM80DILM95
DILM95-XSP(230V50HZ)230062
DILM95-XSP(RDC24)230080
DILM115DILM150
DILM150-XSP(RAC240)1)
230112DILM150-XSP(RDC24)230115
Notes 1) Including electronics module
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 38/130
2/27
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Actuating voltagesContactors DILM screw terminals
AC DILM7-10
(...)
DILM7-01
(...)
DILM9-10
(...)
DILM9-01
(...)
DILM12-10
(...)
DILM12-01
(...)
DILM15-10
(...)
DILM15-01
(...)
DILMP20
(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list See price list See price list See price list
12 V 50 Hz 276536 276571 276676 276711 276816 276851 290044 290079 276956
24 V 50 Hz 276537 276572 276677 276712 276817 276852 290045 290080 276957
48 V 50Hz 276538 276573 276678 276713 276818 276853 290046 290081 276958
240V 50Hz 276539 276574 276679 276714 276819 276854 290047 290082 276959
500 V 50Hz 276540 276575 276680 276715 276820 276855 290048 290083 276960
24 V 60 Hz 276541 276576 276681 276716 276821 276856 290049 290084 276961
110 V 60 Hz 276542 276577 276682 276717 276822 276857 290050 290085 276962
115 V 60 Hz 276543 276578 276683 276718 276823 276858 290051 290086 276963
208 V 60 Hz 276544 276579 276684 276719 276824 276859 290052 290087 276964
600 V 60 Hz 276545 276580 276685 276720 276825 276860 290053 290088 276965
42V 50Hz48V 60Hz
276546 276581 276686 276721 276826 276861 290054 290089 276966
110V 50Hz
120V 60Hz
276547 276582 276687 276722 276827 276862 290055 290090 276967
190V 50Hz220V 60Hz
276548 276583 276688 276723 276828 276863 290056 290091 276968
220V 50Hz240V 60Hz
276549 276584 276689 276724 276829 276864 290057 290092 276969
230V 50Hz240V 60Hz
276550 276585 276690 276725 276830 276865 290058 290093 276970
380V 50Hz440V 60Hz
276551 276586 276691 276726 276831 276866 290059 290094 276971
400V 50Hz440V 60Hz
276552 276587 276692 276727 276832 276867 290060 290095 276972
415V 50Hz480V 60Hz
276553 276588 276693 276728 276833 276868 290061 290096 276973
24V 50Hz/60Hz 276554 276589 276694 276729 276834 276869 290062 290097 276974
42V 50Hz/60Hz 276555 276590 276695 276730 276835 276870 290063 290098 276975
110V 50Hz/60Hz 276556 276591 276696 276731 276836 276871 290064 290099 276976
220V 50Hz/60Hz 276557 276592 276697 276732 276837 276872 290065 290100 276977
230V 50Hz/60Hz 276558 276593 276698 276733 276838 276873 290066 290101 276978
380V 50Hz/60Hz 276559 276594 276699 276734 276839 276874 290067 290102 276979
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list See price list See price list See price list
...V 50Hz (12 – 600V) 276562 276597 276702 276737 276842 276877 290070 290105 276982
...V 60Hz (12 – 600V) 276563 276598 276703 276738 276843 276878 290071 290106 276983
DC DILM7-10
(...)
DILM7-01
(...)
DILM9-10
(...)
DILM9-01
(...)
DILM12-10
(...)
DILM12-01
(...)
DILM15-10
(...)
DILM15-01
(...)
DILMP20
(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list See price list See price list See price list
12 V DC 276564 276599 276704 276739 276844 276879 290072 290107 276984
24 V DC 276565 276600 276705 276740 276845 276880 290073 290108 276985
48 V DC 276566 276601 276706 276741 276846 276881 290074 290109 276986
60V DC 276567 276602 276707 276742 276847 276882 290075 290110 276987
110 V DC 276568 276603 276708 276743 276848 276883 290076 290111 276988
220V DC 276569 276604 276709 276744 276849 276884 290077 290112 276989
Non-standard voltages with theexception of the previously statedstandard voltages1)
See price list See price list See price list See price list See price list See price list See price list See price list See price list
...VDC (12-250V) 276570 276605 276710 276745 276850 276885 290078 290113 276990
Notes 1) The article no. is formed from the combination of part no. and actuating voltage.Devices with dual-voltage coils must be ordered using one order number.
2) With non-standard voltages the required actuating voltage from the defined range (...–...V) must be stated.
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 39/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/28 Actuating voltagesContactors DILM screw terminals
AC DILM17-10
(...)
DILM17-01
(...)
DILM25-10
(...)
DILM25-01
(...)
DILM32-10
(...)
DILM32-01
(...)
DILM40
(...)
DILM50
(...)
DILM65
(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard voltages See price list See price list See price list See price list See price list See price list See price list See price list See price list
24 V 50 Hz 276991 277023 277119 277151 277247 277279 277753 277817 277881
48 V 50Hz 276992 277024 277120 277152 277248 277280 277754 277818 277882
240V 50Hz 276993 277025 277121 277153 277249 277281 277755 277819 277883
500 V 50Hz 276994 277026 277122 277154 277250 277282 277756 277820 277884
24 V 60 Hz 276995 277027 277123 277155 277251 277283 277757 277821 277885
110 V 60 Hz 276996 277028 277124 277156 277252 277284 277758 277822 277886
115 V 60 Hz 276997 277029 277125 277157 277253 277285 277759 277823 277887
208 V 60 Hz 276998 277030 277126 277158 277254 277286 277760 277824 277888
600 V 60 Hz 276999 277031 277127 277159 277255 277287 277761 277825 277889
42V 50Hz48V 60Hz
277000 277032 277128 277160 277256 277288 277762 277826 277890
110V 50Hz120V 60Hz
277001 277033 277129 277161 277257 277289 277763 277827 277891
190V 50Hz220V 60Hz 277002 277034 277130 277162 277258 277290 277764 277828 277892
220V 50Hz240V 60Hz
277003 277035 277131 277163 277259 277291 277765 277829 277893
230V 50Hz240V 60Hz
277004 277036 277132 277164 277260 277292 277766 277830 277894
380V 50Hz440V 60Hz
277005 277037 277133 277165 277261 277293 277767 277831 277895
400V 50Hz440V 60Hz
277006 277038 277134 277166 277262 277294 277768 277832 277896
415V 50Hz480V 60Hz
277007 277039 277135 277167 277263 277295 277769 277833 277897
24V 50Hz/60Hz 277008 277040 277136 277168 277264 277296 277770 277834 277898
42V 50Hz/60Hz 277009 277041 277137 277169 277265 277297 277771 277835 277899
110V 50Hz/60Hz 277010 277042 277138 277170 277266 277298 277772 277836 277900
220V 50Hz/60Hz 277011 277043 277139 277171 277267 277299 277773 277837 277901230V 50Hz/60Hz 277012 277044 277140 277172 277268 277300 277774 277838 277902
380V 50Hz/60Hz 277013 277045 277141 277173 277269 277301 277775 277839 277903
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list See price list See price list See price list
...V 50Hz (24 – 600V) 277016 277048 277144 277176 277272 277304 277778 277842 277906
...V 60Hz (24 – 600V) 277017 277049 277145 277177 277273 277305 277779 277843 277907
DC DILM17-10
(...)
DILM17-01
(...)
DILM25-10
(...)
DILM25-01
(...)
DILM32-10
(...)
DILM32-01
(...)
DILM40(...) DILM50(...) DILM65(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard voltages See price list See price list See price list See price list See price list See price list See price list See price list See price list
RDC 243) 277018 277050 277146 277178 277274 277306 277780 277844 277908
RDC 604) 277019 277051 277147 277179 277275 277307 277781 277845 277909
RDC 1305) 277020 277052 277148 277180 277276 277308 277782 277846 277910
RDC 2406) 277021 277053 277149 277181 277277 277309 277783 277847 277911
Notes 1) The article no. is formed from the combination of part no. and actuating voltage.Devices with dual-voltage coils must be ordered using one order number.
2) With non-standard voltages the required actuating voltage from the defined range (...–...V) must be stated.3) 24 – 27 V DC4) 48 – 60 V DC5) 110 – 130 V DC6) 200 – 240 V DC
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 40/130
2/29
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Actuating voltagesContactors DILM screw terminals
AC DILM80
(...)
DILM95
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
24 V 50 Hz 235904 239467
48 V 50Hz 235909 239468
240V 50Hz 235910 239469
500 V 50Hz 235911 239470
24 V 60 Hz 239377 239471
110 V 60 Hz 239378 239472
115 V 60 Hz 239379 239473
208 V 60 Hz 239384 239474
600 V 60 Hz 239389 239475
42V 50Hz48V 60Hz
239394 239476
110V 50Hz120V 60Hz
239399 239477
190V 50Hz220V 60Hz 239400 239478
220V 50Hz240V 60Hz
239401 239479
230V 50Hz240V 60Hz
239402 239480
380V 50Hz440V 60Hz
239403 239481
400V 50Hz440V 60Hz
239404 239482
415V 50Hz480V 60Hz
239405 239483
24V 50Hz/60Hz 239406 239484
42V 50Hz/60Hz 239407 239485
110V 50Hz/60Hz 239408 239486
220V 50Hz/60Hz 239409 239487230V 50Hz/60Hz 239410 239488
380V 50Hz/60Hz 239411 239489
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list
...V 50Hz (24 – 600V) 239414 239504
...V 60Hz (24 – 600V) 239415 239509
DC DILM80
(...)
DILM95
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
RDC 243) 239416 239510
RDC 604) 239417 239511
RDC 1305) 239418 239512
RDC 2406) 239419 239513
AC DILM115
(...)
DILM150
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
RAC 247) 239545 239585
RAC 488) 239546 239586
RAC 1209) 239547 239587
RAC 24010) 239548 239588
RAC 44011) 239549 239589
RAC 50012) 239550 239590
DC DILM115
(...)
DILM150
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
RDC 243) 239555 239591RDC 604) 239560 239592
RDC 1305) 239567 239593
RDC 2406) 239572 239594
Notes 1) The article no. is formed from the combinationof part no. and actuating voltage.Devices with dual-voltage coils must be orderedusing one order number.
2) When ordering non-standard voltages, statethe required actuating voltage from the selectedrange (...-...V).
3) 24 – 27 V DC4) 48 – 60 V DC5) 110 – 130 V DC6) 200 – 240 V DC7) 24 V 50/60 Hz8) 42 – 48 V 50/60 Hz9) 100 – 120 V 50/60 Hz10) 190 – 240 V 50/60 Hz11) 380 – 440 V 50/60 Hz12) 480 – 500 V 50/60 Hz
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 41/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/30 Actuating voltagesContactors DILMC with spring-loaded terminals
AC DILMC7-10(...) DILMC7-01(...) DILMC9-10(...) DILMC9-01(...) DILMC12-10(...) DILMC12-01(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list
12 V 50 Hz 277378 277410 277442 277474 277506 27753824 V 50 Hz 277379 277411 277443 277475 277507 277539
48 V 50Hz 277380 277412 277444 277476 277508 277540
240V 50Hz 277381 277413 277445 277477 277509 277541
500 V 50Hz 281424 281427 281430 281433 281436 281439
24 V 60 Hz 277382 277414 277446 277478 277510 277542
110 V 60 Hz 277383 277415 277447 277479 277511 277543
115 V 60 Hz 277384 277416 277448 277480 277512 277544
208 V 60 Hz 281425 281428 281431 281434 281437 281440
600 V 60 Hz 281426 281429 281432 281435 281438 281441
42V 50Hz48V 60Hz
277385 277417 277449 277481 277513 277545
110V 50Hz120V 60Hz
277386 277418 277450 277482 277514 277546
190V 50Hz220V 60Hz
277387 277419 277451 277483 277515 277547
220V 50Hz240V 60Hz
277388 277420 277452 277484 277516 277548
230V 50Hz240V 60Hz
277389 277421 277453 277485 277517 277549
380V 50Hz440V 60Hz
277390 277422 277454 277486 277518 277550
400V 50Hz440V 60Hz
277391 277423 277455 277487 277519 277551
415V 50Hz480V 60Hz
277392 277424 277456 277488 277520 277552
24V 50Hz/60Hz 277393 277425 277457 277489 277521 277553
42V 50Hz/60Hz 277394 277426 277458 277490 277522 277554
110V 50Hz/60Hz 277395 277427 277459 277491 277523 277555220V 50Hz/60Hz 277396 277428 277460 277492 277524 277556
230V 50Hz/60Hz 277397 277429 277461 277493 277525 277557
380V 50Hz/60Hz 277398 277430 277462 277494 277526 277558
Non-standard voltages withthe exception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list
...V 50Hz (12 – 600V) 277401 277433 277465 277497 277529 277561
...V 60Hz (12 – 600V) 277402 277434 277466 277498 277530 277562
DC DILMC7-10(...) DILMC7-01(...) DILMC9-10(...) DILMC9-01(...) DILMC12-10(...) DILMC12-01(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list
12 V DC 277403 277435 277467 277499 277531 277563
24 V DC 277404 277436 277468 277500 277532 277564
48 V DC 277405 277437 277469 277501 277533 277565
60V DC 277406 277438 277470 277502 277534 277566
110 V DC 277407 277439 277471 277503 277535 277567
220V DC 277408 277440 277472 277504 277536 277568
Non-standard voltages withthe exception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list
...VDC (12 – 250V) 277409 277441 277473 277505 277537 277569
Notes 1) The article no. is formed from the combination of part no. and actuating voltage.Devices with dual-voltage coils must be ordered using one order number.
2) When ordering non-standard voltages, state the required actuating voltage from the selected range (...-...V).
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 42/130
2/31
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Actuating voltagesContactors DILMC with spring-loaded terminals
AC DILMC17-10
(...)
DILMC17-01
(...)
DILMC25-10
(...)
DILMC25-01
(...)
DILMC32-10
(...)
DILMC32-01
(...)
DILMC40
(...)
DILMC50
(...)
DILMC65
(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list See price list See price list See price list
24 V 50 Hz 277570 277600 277630 277660 277690 277720 277954 277984 278014
48 V 50Hz 277571 277601 277631 277661 277691 277721 277955 277985 278015
240V 50Hz 277572 277602 277632 277662 277692 277722 277956 277986 278016
500 V 50Hz 277573 277603 277633 277663 277693 277723 277957 277987 278017
24 V 60 Hz 277574 277604 277634 277664 277694 277724 277958 277988 278018
110 V 60 Hz 277575 277605 277635 277665 277695 277725 277959 277989 278019
115 V 60 Hz 277576 277606 277636 277666 277696 277726 277960 277990 278020
208 V 60 Hz 281442 281444 281446 281448 281450 281452 281454 281456 281458
600 V 60 Hz 281443 281445 281447 281449 281451 281453 281455 281457 281459
42V 50Hz48V 60Hz
277577 277607 277637 277667 277697 277727 277961 277991 278021
110V 50Hz120V 60Hz
277578 277608 277638 277668 277698 277728 277962 277992 278022
190V 50Hz220V 60Hz
277579 277609 277639 277669 277699 277729 277963 277993 278023
220V 50Hz240V 60Hz
277580 277610 277640 277670 277700 277730 277964 277994 278024
230V 50Hz240V 60Hz
277581 277611 277641 277671 277701 277731 277965 277995 278025
380V 50Hz440V 60Hz
277582 277612 277642 277672 277702 277732 277966 277996 278026
400V 50Hz440V 60Hz
277583 277613 277643 277673 277703 277733 277967 277997 278027
415V 50Hz480V 60Hz
277584 277614 277644 277674 277704 277734 277968 277998 278028
24V 50Hz/60Hz 277585 277615 277645 277675 277705 277735 277969 277999 278029
42V 50Hz/60Hz 277586 277616 277646 277676 277706 277736 277970 278000 278030
110V 50Hz/60Hz 277587 277617 277647 277677 277707 277737 277971 278001 278031
220V 50Hz/60Hz 277588 277618 277648 277678 277708 277738 277972 278002 278032
230V 50Hz/60Hz 277589 277619 277649 277679 277709 277739 277973 278003 278033
380V 50Hz/60Hz 277590 277620 277650 277680 277710 277740 277974 278004 278034
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list See price list See price list See price list
...V 50Hz (24 – 600V) 277593 277623 277653 277683 277713 277743 277977 278007 278037
...V 60Hz (24 – 600V) 277594 277624 277654 277684 277714 277744 277978 278008 278038
DC DILMC17-10
(...)
DILMC17-01
(...)
DILMC25-10
(...)
DILMC25-01
(...)
DILMC32-10
(...)
DILMC32-01
(...)
DILMC40
(...)
DILMC50
(...)
DILMC65
(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list See price list See price list See price list
RDC 243) 277595 277625 277655 277685 277715 277745 277979 278009 278039
RDC 604) 277596 277626 277656 277686 277716 277746 277980 278010 278040
RDC 1305) 277597 277627 277657 277687 277717 277747 277981 278011 278041
RDC 2406) 277598 277628 277658 277688 277718 277748 277982 278012 278042
Notes 1) The article no. is formed from the combination of part no. and actuating voltage.Devices with dual-voltage coils must be ordered using one order number.
2) With non-standard voltages the required actuating voltage from the defined range (...–...V) must be stated.3) 24 – 27 V DC4) 48 – 60 V DC5) 110 – 130 V DC6) 200 – 240 V DC
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 43/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/32 Actuating voltagesContactors DILMC with spring-loaded terminals
AC DILMC80
(...)
DILMC95
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
24 V 50 Hz 239605 239656
48 V 50Hz 239606 239657
240V 50Hz 239607 239658
500 V 50Hz 239608 239662
24 V 60 Hz 239609 239666
110 V 60 Hz 239610 239672
115 V 60 Hz 239611 239676
208 V 60 Hz 239612 239679
600 V 60 Hz 239613 239680
42V 50Hz48V 60Hz
239614 239681
110V 50Hz120V 60Hz
239615 239682
190V 50Hz220V 60Hz 239616 239683
220V 50Hz240V 60Hz
239617 239684
230V 50Hz240V 60Hz
239618 239685
380V 50Hz440V 60Hz
239619 239686
400V 50Hz440V 60Hz
239620 239687
415V 50Hz480V 60Hz
239621 239688
24V 50Hz/60Hz 239622 239692
42V 50Hz/60Hz 239627 239696
110V 50Hz/60Hz 239632 239702
220V 50Hz/60Hz 239639 239706230V 50Hz/60Hz 239644 239709
380V 50Hz/60Hz 239647 239710
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list
...V 50Hz (24 – 600V) 239650 239713
...V 60Hz (24 – 600V) 239651 239714
DC DILMC80
(...)
DILMC95
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
RDC 243) 239652 239715
RDC 604) 239653 239716
RDC 1305) 239654 239717
RDC 2406) 239655 239718
AC DILMC115
(...)
DILMC150
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
RAC 247) 239722 239745
RAC 488) 239726 239746
RAC 1209) 239732 239747
RAC 24010) 239736 239751
RAC 44011) 239739 239755
RAC 50012) 239740 239761
DC DILM115
(...)
DILM150
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
RDC 243) 239741 239765RDC 604) 239742 239768
RDC 1305) 239743 239769
RDC 2406) 239744 239770
Notes 1) The article no. is formed from the combinationof part no. and actuating voltage.Devices with dual-voltage coils must be orderedusing one order number.
2) When ordering non-standard voltages, statethe required actuating voltage from the selectedrange (...-...V).
3) 24 – 27 V DC4) 48 – 60 V DC5) 110 – 130 V DC6) 200 – 240 V DC7) 24 V 50/60 Hz8) 42 – 48 V 50/60 Hz9) 100 – 120 V 50/60 Hz10) 190 – 240 V 50/60 Hz11) 380 – 440 V 50/60 Hz12) 480 – 500 V 50/60 Hz
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 44/130
2/33
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Actuating voltagesComplete unit DILM
AC DILM7-21(...) DILM7-32(...) DILM9-21(...) DILM9-32(...) DILM12-21(...) DILM12-32(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list
12 V 50 Hz 276606 276641 276746 276781 276886 27692124 V 50 Hz 276607 276642 276747 276782 276887 276922
48 V 50Hz 276608 276643 276748 276783 276888 276923
240V 50Hz 276609 276644 276749 276784 276889 276924
500 V 50Hz 276610 276645 276750 276785 276890 276925
24 V 60 Hz 276611 276646 276751 276786 276891 276926
110 V 60 Hz 276612 276647 276752 276787 276892 276927
115 V 60 Hz 276613 276648 276753 276788 276893 276928
208 V 60 Hz 276614 276649 276754 276789 276894 276929
600 V 60 Hz 276615 276650 276755 276790 276895 276930
42V 50Hz48V 60Hz
276616 276651 276756 276791 276896 276931
110V 50Hz120V 60Hz
276617 276652 276757 276792 276897 276932
190V 50Hz220V 60Hz
276618 276653 276758 276793 276898 276933
220V 50Hz240V 60Hz
276619 276654 276759 276794 276899 276934
230V 50Hz240V 60Hz
276620 276655 276760 276795 276900 276935
380V 50Hz440V 60Hz
276621 276656 276761 276796 276901 276936
400V 50Hz440V 60Hz
276622 276657 276762 276797 276902 276937
415V 50Hz480V 60Hz
276623 276658 276763 276798 276903 276938
24V 50Hz/60Hz 276624 276659 276764 276799 276904 276939
42V 50Hz/60Hz 276625 276660 276765 276800 276905 276940
110V 50Hz/60Hz 276626 276661 276766 276801 276906 276941220V 50Hz/60Hz 276627 276662 276767 276802 276907 276942
230V 50Hz/60Hz 276628 276663 276768 276803 276908 276943
380V 50Hz/60Hz 276629 276664 276769 276804 276909 276944
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list
...V 50Hz (12 – 600V) 276632 276667 276772 276807 276912 276947
...V 60Hz (12 – 600V) 276633 276668 276773 276808 276913 276948
DC DILM7-21(...) DILM7-32(...) DILM9-21(...) DILM9-32(...) DILM12-21(...) DILM12-32(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list
12 V DC 276634 276669 276774 276809 276914 276949
24 V DC 276635 276670 276775 276810 276915 276950
48 V DC 276636 276671 276776 276811 276916 276951
60V DC 276637 276672 276777 276812 276917 276952
110 V DC 276638 276673 276778 276813 276918 276953
220V DC 276639 276674 276779 276814 276919 276954
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list
...VDC (12 – 250V) 276640 276675 276780 276815 276920 276955
Notes 1) The article no. is formed from the combination of part no. and actuating voltage.Devices with dual-voltage coils must be ordered using one order number.
2) With non-standard voltages the required actuating voltage from the defined range (...–...V) must be stated.
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 45/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/34 Actuating voltagesComplete unit DILM
AC DILM17-21
(...)
DILM17-32
(...)
DILM25-21
(...)
DILM25-32
(...)
DILM32-21
(...)
DILM32-32
(...)
DILM40-22
(...)
DILM50-22
(...)
DILM65-22
(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list See price list See price list See price list
24 V 50 Hz 277055 277087 277183 277215 277311 277343 277785 277849 277913
48 V 50Hz 277056 277088 277184 277216 277312 277344 277786 277850 277914
240V 50Hz 277057 277089 277185 277217 277313 277345 277787 277851 277915
500 V 50Hz 277058 277090 277186 277218 277314 277346 277788 277852 277916
24 V 60 Hz 277059 277091 277187 277219 277315 277347 277789 277853 277917
110 V 60 Hz 277060 277092 277188 277220 277316 277348 277790 277854 277918
115 V 60 Hz 277061 277093 277189 277221 277317 277349 277791 277855 277919
208 V 60 Hz 277062 277094 277190 277222 277318 277350 277792 277856 277920
600 V 60 Hz 277063 277095 277191 277223 277319 277351 277793 277857 277921
42V 50Hz48V 60Hz
277064 277096 277192 277224 277320 277352 277794 277858 277922
110V 50Hz120V 60Hz
277065 277097 277193 277225 277321 277353 277795 277859 277923
190V 50Hz220V 60Hz
277066 277098 277194 277226 277322 277354 277796 277860 277924
220V 50Hz240V 60Hz
277067 277099 277195 277227 277323 277355 277797 277861 277925
230V 50Hz240V 60Hz
277068 277100 277196 277228 277324 277356 277798 277862 277926
380V 50Hz440V 60Hz
277069 277101 277197 277229 277325 277357 277799 277863 277927
400V 50Hz440V 60Hz
277070 277102 277198 277230 277326 277358 277800 277864 277928
415V 50Hz480V 60Hz
277071 277103 277199 277231 277327 277359 277801 277865 277929
24V 50Hz/60Hz 277072 277104 277200 277232 277328 277360 277802 277866 277930
42V 50Hz/60Hz 277073 277105 277201 277233 277329 277361 277803 277867 277931
110V 50Hz/60Hz 277074 277106 277202 277234 277330 277362 277804 277868 277932
220V 50Hz/60Hz 277075 277107 277203 277235 277331 277363 277805 277869 277933
230V 50Hz/60Hz 277076 277108 277204 277236 277332 277364 277806 277870 277934
380V 50Hz/60Hz 277077 277109 277205 277237 277333 277365 277807 277871 277935
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list See price list See price list See price list
...V 50Hz (24 – 600V) 277080 277112 277208 277240 277336 277368 277810 277874 277938
...V 60Hz (24 – 600V) 277081 277113 277209 277241 277337 277369 277811 277875 277939
DC DILM17-21(...)
DILM17-32(...)
DILM25-21(...)
DILM25-32(...)
DILM32-21(...)
DILM32-32(...)
DILM40-22(...)
DILM50-22(...)
DILM65-22(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list See price list See price list See price list
RDC 243) 277082 277114 277210 277242 277338 277370 277812 277876 277940
RDC 604) 277083 277115 277211 277243 277339 277371 277813 277877 277941
RDC 1305) 277084 277116 277212 277244 277340 277372 277814 277878 277942
RDC 2406) 277085 277117 277213 277245 277341 277373 277815 277879 277943
Notes 1) The article no. is formed from the combination of part no. and actuating voltage.Devices with dual-voltage coils must be ordered using one order number.
2) With non-standard voltages the required actuating voltage from the defined range (...–...V) must be stated.3) 24 – 27 V DC4) 48 – 60 V DC5) 110 – 130 V DC6) 200 – 240 V DC
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 46/130
2/35
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Actuating voltagesComplete unit DILM
AC DILM80-22
(...)
DILM95-22
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
24 V 50 Hz 239420 239514
48 V 50Hz 239421 239515
240V 50Hz 239422 239516
500 V 50Hz 239423 239517
24 V 60 Hz 239424 239518
110 V 60 Hz 239425 239519
115 V 60 Hz 239426 239520
208 V 60 Hz 239427 239521
600 V 60 Hz 239428 239522
42V 50Hz48V 60Hz
239429 239523
110V 50Hz120V 60Hz
239434 239524
190V 50Hz220V 60Hz 239439 239525
220V 50Hz240V 60Hz
239444 239526
230V 50Hz240V 60Hz
239449 239527
380V 50Hz440V 60Hz
239450 239528
400V 50Hz440V 60Hz
239451 239529
415V 50Hz480V 60Hz
239452 239530
24V 50Hz/60Hz 239453 239531
42V 50Hz/60Hz 239454 239532
110V 50Hz/60Hz 239455 239533
220V 50Hz/60Hz 239456 239534230V 50Hz/60Hz 239457 239535
380V 50Hz/60Hz 239458 239536
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list
...V 50Hz (24 – 600V) 239461 239539
...V 60Hz (24 – 600V) 239462 239540
DC DILM80-22
(...)
DILM95-22
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
RDC 243) 239463 239541
RDC 604) 239464 239542
RDC 1305) 239465 239543
RDC 2406) 239466 239544
AC DILM115-22
(...)
DILM150-22
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
RAC 247) 239575 239595
RAC 488) 239576 239596
RAC 1209) 239577 239597
RAC 24010) 239578 239598
RAC 44011) 239579 239599
RAC 50012) 239580 239600
DC DILM115-22
(...)
DILM150-22
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
RDC 243) 239581 239601RDC 604) 239582 239602
RDC 1305) 239583 239603
RDC 2406) 239584 239604
Notes 1) The article no. is formed from the combinationof part no. and actuating voltage.Devices with dual-voltage coils must be orderedusing one order number.
2) When ordering non-standard voltages, statethe required actuating voltage from the selectedrange (...-...V).
3) 24 – 27 V DC4) 48 – 60 V DC5) 110 – 130 V DC6) 200 – 240 V DC7) 24 V 50/60 Hz8) 42 – 48 V 50/60 Hz9) 100 – 120 V 50/60 Hz10) 190 – 240 V 50/60 Hz11) 380 – 440 V 50/60 Hz12) 480 – 500 V 50/60 Hz
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 47/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/36 Actuating voltagesIndividual coils DILM
AC DILM32-XSP
(...)
DILM65-XSP
(...)
DILM95-XSP
(...)
Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list
24 V 50 Hz 281130 281160 229984
48 V 50Hz 281131 281161 229985
240V 50Hz 281132 281162 229986
500 V 50Hz 281133 281163 229987
24 V 60 Hz 281134 281164 229988
110 V 60 Hz 281135 281165 229989
115 V 60 Hz 281136 281166 229990
208 V 60 Hz 283377 283379 229991
600 V 60 Hz 283378 283380 229993
42V 50Hz48V 60Hz
281137 281167 229994
110V 50Hz120V 60Hz
281138 281168 230058
190V 50Hz220V 60Hz
281139 281169 230059
220V 50Hz240V 60Hz
281140 281170 230061
230V 50Hz240V 60Hz
281141 281171 230062
380V 50Hz440V 60Hz
281142 281172 230063
400V 50Hz440V 60Hz
281143 281173 230064
415V 50Hz480V 60Hz
281144 281174 230065
24V 50Hz/60Hz 281145 281175 230066
42V 50Hz/60Hz 281146 281176 230067
110V 50Hz/60Hz 281147 281177 230068
220V 50Hz/60Hz 281148 281178 230073
230V 50Hz/60Hz 281149 281179 230074
380V 50Hz/60Hz 281150 281180 230075
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list
...V 50Hz (24 – 600V) 281153 281183 230078
...V 60Hz (24 – 600V) 281154 281184 230079
DC DILM32-XSP
(...)
DILM65-XSP
(...)
DILM95-XSP
(...)
Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list
RDC 243) 281155 281185 230080
RDC 604) 281156 281186 230081
RDC 1305) 281157 281187 230082
RDC 2406) 281158 281188 230107
AC DILM150-XSP
(...)
Article no.1)
Standard voltages See price list
RAC 247) 230109
RAC 488) 230110
RAC 1209) 230111
RAC 24010) 230112
RAC 44011) 230113
RAC 50012) 230114
DC DILM150-XSP
(...)
Article no.1)
Standard voltages See price list
RDC 243) 230115RDC 604) 230116
RDC 1305) 230117
RDC 2406) 230122
Notes 1) The article no. is formed from the combinationof part no. and actuating voltage.Devices with dual-voltage coils must be orderedusing one order number.
2) When ordering non-standard voltages, statethe required actuating voltage from the selectedrange (...-...V).
3) 24 – 27 V DC4) 48 – 60 V DC5) 110 – 130 V DC6) 200 – 240 V DC7) 24 V 50/60 Hz8) 42 – 48 V 50/60 Hz9) 100 – 120 V 50/60 Hz10) 190 – 240 V 50/60 Hz11) 380 – 440 V 50/60 Hz12) 480 – 500 V 50/60 Hz
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 48/130
2/37
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Actuating voltagesContactors for three-phase capacitors
AC DILK12-11
(...)
DILK20-11
(...)
DILK25-11
(...)
DILK33-10
(...)
DILK50-10
(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list
24 V 50 Hz 293967 293999 294021 294043 294065
48 V 50Hz 293968 294000 294022 294044 294066
240V 50Hz 293969 294001 294023 294045 294067
500 V 50Hz 293980 294002 294024 294046 294068
24 V 60 Hz 293981 294003 294025 294047 294069
110 V 60 Hz 293982 294004 294026 294048 294070
115 V 60 Hz 293983 294005 294027 294049 294071
42V 50Hz,48V 60Hz
293984 294006 294028 294050 294072
110V 50Hz,120V 60Hz
293985 294007 294029 294051 294073
190V 50Hz,220V 60Hz
293986 294008 294030 294052 294074
220V 50Hz,240V 60Hz 293987 294009 294031 294053 294075
230V 50Hz,240V 60Hz
293988 294010 294032 294054 294076
380V 50 Hz,440V 60 Hz
293989 294011 294033 294055 294077
400V 50 Hz,440V 60 Hz
293990 294012 294034 294056 294078
415V 50Hz,480V 60Hz
293991 294013 294035 294057 294079
24 V 50/60 Hz 293992 294014 294036 294058 294080
42V 50/60Hz 293993 294015 294037 294059 294081
110 V 50/60 Hz 293994 294016 294038 294060 294082
230 V 50/60Hz 293995 294017 294039 294061 294083
380 V 50/60 Hz 293996 294018 294040 294062 294084
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list
…V 50Hz (24 – 600V) 293997 294019 294041 294063 294085
…V 60Hz (24 – 600V) 293998 294020 294042 294064 294086
Notes 1) The article no. is formed from the combination of part no. and actuating voltage.Devices with dual-voltage coils must be ordered using one order number.
2) With non-standard voltages the required actuating voltage from the defined range (...–...V) must be stated.
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 49/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/38 Actuating voltagesContactor combination SDAINLM
AC SDAINLM12
(...)
SDAINLM16
(...)
SDAINLM22
(...)
SDAINLM30
(...)
SDAINLM45
(...)
SDAINLM55
(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list
24 V 50 Hz 278276 278301 278326 278351 278376 278401
48 V 50Hz 278277 278302 278327 278352 278377 278402
240V 50Hz 278278 278303 278328 278353 278378 278403
400 V 50 Hz 101380 101381 101382 101383 101384 101385
24 V 60 Hz 278279 278304 278329 278354 278379 278404
110 V 60 Hz 278280 278305 278330 278355 278380 278405
115 V 60 Hz 278281 278306 278331 278356 278381 278406
208 V 60 Hz 283366 283368 283370 283372 283374 283376
42V 50Hz48V 60Hz
278282 278307 278332 278357 278382 278407
110V 50Hz120V 60Hz
278283 278308 278333 278358 278383 278408
190V 50Hz
220V 60Hz
278284 278309 278334 278359 278384 278409
220V 50Hz240V 60Hz
278285 278310 278335 278360 278385 278410
230V 50Hz240V 60Hz
278286 278311 278336 278361 278386 278411
24V 50Hz/60Hz 278290 278315 278340 278365 278390 278415
42V 50Hz/60Hz 278291 278316 278341 278366 278391 278416
110V 50Hz/60Hz 278292 278317 278342 278367 278392 278417
220V 50Hz/60Hz 278293 278318 278343 278368 278393 278418
230V 50Hz/60Hz 278294 278319 278344 278369 278394 278419
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list
...V 50Hz (24 – 240V) 278298 278323 278348 278373 278398 278423
...V 60Hz (24 – 240V) 278299 278324 278349 278374 278399 278424DC SDAINLM12
(...)
SDAINLM16
(...)
SDAINLM22
(...)
SDAINLM30
(...)
SDAINLM45
(...)
SDAINLM55
(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list
24 V DC 100416 100417 100418 – – –
RDC 243) – – – 100419 100420 100421
Notes 1) The article no. is formed from the combination of part no. and actuating voltage.2) With non-standard voltages the required actuating voltage from the defined range (...–...V) must be stated.3) 24 – 27 V DC
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 50/130
2/39
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Actuating voltagesContactor combination SDAINLM
AC SDAINLM70
(...)
SDAINLM90
(...)
SDAINLM115
(...)
SDAINLM140
(...)
SDAINLM165
(...)
SDAINLM200
(...)
SDAINLM260
(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list See price list
24 V 50 Hz 239883 239909 239951 239977 240023 100999 101020
48 V 50Hz 239884 239910 239952 239978 240024 101000 101021
240V 50Hz 239885 239911 239953 239983 240025 101001 101022
400 V 50 Hz 101386 101387 101388 101389 101390 101391 101392
24 V 60 Hz 239887 239913 239955 239995 240027 101002 101023
110 V 60 Hz 239888 239914 239956 240000 240028 101003 101024
115 V 60 Hz 239889 239915 239957 240003 240029 101004 101025
208 V 60 Hz 239890 239916 239958 240004 240030 101005 101026
42V 50Hz48V 60Hz
239891 239917 239959 240005 240031 101006 101027
110V 50Hz120V 60Hz
239892 239922 239960 240006 240032 101007 101028
190V 50Hz
220V 60Hz
239893 239927 239961 240007 240033 101008 101029
220V 50Hz240V 60Hz
239894 239932 239962 240008 240034 101009 101030
230V 50Hz240V 60Hz
239895 239937 239963 240009 240035 101010 101031
24V 50Hz/60Hz 239899 239941 239967 240013 240039 101011 101032
42V 50Hz/60Hz 239900 239942 239968 240014 240040 101012 101033
110V 50Hz/60Hz 239901 239943 239969 240015 240041 101013 101034
220V 50Hz/60Hz 239902 239944 239970 240016 240042 101014 101035
230V 50Hz/60Hz 239903 239945 239971 240017 240043 101015 101036
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list
...V 50Hz (24 – 240V) 239907 239949 239975 240021 240047 – –
...V 60Hz (24 – 240V) 239908 239950 239976 240022 240048 – –
Notes 1) The article no. is formed from the combination of part no. and actuating voltage.2) With non-standard voltages the required actuating voltage from the defined range (...–...V) must be stated.
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 51/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/40 Actuating voltagesContactor combination DIULM
AC DIULM7/21
(...)
DIULM9/21
(...)
DIULM12/21
(...)
DIULM17/21
(...)
DIULM25/21
(...)
DIULM32/21
(...)
DIULM40/11
(...)
DIULM50/11
(...)
DIULM65/11
(...)
Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1) Article no.1)
Standard coils See price list See price list See price list See price list See price list See price list See price list See price list See price list
12 V 50 Hz 278050 278075 278100 – – – – – –
24 V 50 Hz 278051 278076 278101 278126 278151 278176 278200 278225 278250
48 V 50Hz 278052 278077 278102 278127 278152 278177 278201 278226 278251
240V 50Hz 278053 278078 278103 278128 278153 278178 278202 278227 278252
500 V 50Hz 283350 283352 283354 283356 283358 283360 278203 278228 278253
24 V 60 Hz 278054 278079 278104 278129 278154 278179 278204 278229 278254
110 V 60 Hz 278055 278080 278105 278130 278155 278180 278205 278230 278255
115 V 60 Hz 278056 278081 278106 278131 278156 278181 278206 278231 278256
208 V 60 Hz 283351 283353 283355 283357 283359 283361 283362 283363 283364
600 V 60 Hz – – – – – – – – –
42V 50Hz48V 60Hz
278057 278082 278107 278132 278157 278182 278207 278232 278257
110V 50Hz
120V 60Hz
278058 278083 278108 278133 278158 278183 278208 278233 278258
190V 50Hz220V 60Hz
278059 278084 278109 278134 278159 278184 278209 278234 278259
220V 50Hz240V 60Hz
278060 278085 278110 278135 278160 278185 278210 278235 278260
230V 50Hz240V 60Hz
278061 278086 278111 278136 278161 278186 278211 278236 278261
380V 50Hz440V 60Hz
278062 278087 278112 278137 278162 278187 278212 278237 278262
400V 50Hz440V 60Hz
278063 278088 278113 278138 278163 278188 278213 278238 278263
415V 50Hz480V 60Hz
278064 278089 278114 278139 278164 278189 278214 278239 278264
24V 50Hz/60Hz 278065 278090 278115 278140 278165 278190 278215 278240 278265
42V 50Hz/60Hz 278066 278091 278116 278141 278166 278191 278216 278241 278266
110V 50Hz/60Hz 278067 278092 278117 278142 278167 278192 278217 278242 278267
220V 50Hz/60Hz 278068 278093 278118 278143 278168 278193 278218 278243 278268
230V 50Hz/60Hz 278069 278094 278119 278144 278169 278194 278219 278244 278269
380V 50Hz/60Hz 278070 278095 278120 278145 278170 278195 278220 278245 278270
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list See price list See price list See price list See price list See price list See price list See price list
...V 50Hz (12 – 600V) 278073 278098 278123 – – – – – –
...V 60Hz (12 – 600V) 278074 278099 278124 – – – – – –
...V 50Hz (24 – 600V) – – – 278148 278173 278198 278223 278248 278273
...V 60Hz (24 – 600V) – – – 278149 278174 278199 278224 278249 278274
Notes 1) The article no. is formed from the combination of part no. and actuating voltage.2) With non-standard voltages the required actuating voltage from the defined range (...–...V) must be stated.
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 52/130
2/41
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Actuating voltagesContactor combination DIULM
AC DIULM80/11
(...)
DIULM95/11
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
24V 50HZ 239771 239829
48V 50HZ 239772 239830
240V 50HZ 239773 239831
500V 50HZ 239774 239832
24V 60HZ 239775 239833
110V 60HZ 239776 239834
115V 60HZ 239777 239835
208V 60HZ 239782 239836
42V 50HZ,48V 60HZ
239787 239837
110V 50HZ,120V 60HZ
239792 239838
190V 50HZ,
220V 60HZ
239797 239839
220V 50HZ,240V 60HZ
239798 239840
230V 50HZ,240V 60HZ
239799 239841
380V 50HZ,440V 60HZ
239800 239842
400V 50HZ,440V 60HZ
239801 239843
415V 50HZ,480V 60HZ
239802 239844
24V 50/60HZ 239803 239845
42V 50/60HZ 239804 239846
110V 50/60HZ 239805 239847
220V 50/60HZ 239806 239848
230V 50/60HZ 239807 239849
380V 50/60HZ 239812 239850
Non-standard voltages with theexception of the previously statedstandard voltages2)
See price list See price list
...V 50Hz (24 – 600V) 239827 239853
...V 60Hz (24 – 600V) 239828 239854
AC DIULM115/11
(...)
DIULM150/11
(...)
Article no.1) Article no.1)
Standard voltages See price list See price list
RAC 243) 239855 239877
RAC 484) 239856 239878
RAC 1205) 239857 239879
RAC 2406) 239862 239880
RAC 4407) 239867 239881
RAC 5008) 239872 239882
Notes 1) The article no. is formed from the combinationof part no. and actuating voltage.Devices with dual-voltage coils must be orderedusing one order number.
2) When ordering non-standard voltages, statethe required actuating voltage from the selectedrange (...-...V).
3) 24 V 50/60 Hz
4) 42 – 48 V 50/60 Hz5) 100 – 120 V 50/60 Hz6) 190 – 240 V 50/60 Hz7) 380 – 440 V 50/60 Hz8) 480 – 500 V 50/60 Hz
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 53/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/42 Contact travel diagramsContactors DILM
Contactor contact travel diagramsThe diagrams indicate the closing and opening travel of the contacts of the contactors and auxiliary contacts at no-load.Tolerances are not taken into consideration.
DILM(C)7/9/12/15/P20-...AC DILM(C)7/9-...DC DILM(C)12/15/P20-...DC
N/O contact
N/C contact
N/O contact
N/C contact
N/O contact
N/C contact
DILM32-XHI(C)... DILM32-XHI(C)... DILM32-XHI(C)...
N/O contact
N/C contact
N/O contact
N/C contact
N/O contact
N/C contact
DILA-XHI(C)V... DILA-XHI(C)V... DILA-XHI(C)V...
N/O contact
N/C contact
N/O contact
N/C contact
N/O contact
N/C contact
DIL(C)17/25/32 DILM(C)40/50/65 DILM(C)80/95/115/150
N/O contact
Auxiliary N/C
Auxiliary N/O
N/O contact N/O contact
DILM150-XHI(C)... DILM150-XHI(C)...
N/O contact
N/C contact
N/O contact
N/C contact
DILM32-XHI(C)...,DILA-XHI(C)...
N/O contact
N/C contact DILM150-XHI(C)V... DILM150-XHI(C)V...
N/O contact
N/C contact
N/O contact
N/C contact
DILA-XHI(C)V...
N/O contact
N/C contact DILM1000-XHI(C)... DILM1000-XHI(C)...
N/O contact
N/C contact
N/O contact
N/C contact
DILM1000-XHI(C)V... DILM1000-XHI(C)V...
N/O contact
N/C contact
N/O contact
N/C contact
4.5
4.53.30
0 1.0 2.9
2.92.10
0 0.7 4.4
4.43.30
0 1.0
4.5
4.53.20
0 1.6 2.9
2.92.30
0 0.7 4.4
4.43.20
0 1.6
4.5
4.52.00
0 2.8 2.9
2.91.10
0 1.9 4.4
4.42.00
0 2.8
6.040
1.8
3.2
7.55.10 1180
7.5
7.55.7
3.9
0
0
11
11
9.20
0 7.4
6
63.20
0 1.6
7.55.40
7.53.80 11
11
7.30
0 8.9
6
62.00
0 2.8
7.5
7.55.45
3.6
0
0
11
11
8.950
0 7.1
7.54.950
7.54.10 11
11
7.60
0 8.45
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 54/130
2/43
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Tripping characteristicsContactors DILM
Normal switching duty
Squirrel-cage motor
Operating characteristics
Starting: From rest
Stopping: After attaining full running speed
Electrical characteristics
Starting: Up to 6ϫ rated motor current
Break: up to 1ϫ rated motor current
Utilization category
100 % AC-3
Typical applications
Compressors Lifts Mixers
Pumps Escalators Agitators
Fans Conveyor belts Centrifuges
Hinged flaps/valves Bucket-elevators Air-conditioningsystems
General drives in manufacturing and processing machines
Extreme switching duty
Squirrel-cage motor
Operating characteristics
Inching, plugging, reversing
Electrical characteristics
Starting: Up to 6ϫ rated motor current
Stopping: bis 6ϫ rated motor current
Utilization category
100 % AC-4
Typical applications
Printing presses Wire drawing Centrifuges
Special drives for manufacturing and processing machines
AkW
150
115958065
504032
25
18
12
9
7
54
3
2
AC-3/400V
7555
45373022
18.515
11
7.5
5.5
4
3
0.01 0.02 0.04 0.06 0.1 0.2 0.4 0.6 1 2 4 6 10
DILM32
DILM50
DILM25
DILM15
DILM40
DILM65DILM80
DILM115DILM95
DILM150
DILM17
DILM12
DILM9DILM7
R a t e
d o u t p u t o
f t h r e e - p
h a s e m o t o r s 5 0 –
6
0 H z
R a t e
d o p e r a t i o n a
l c u r r e n t
I e
5 0 –
6 0 H z
Component lifespan [millions of operations]
AkW
100908066
403532
2017
13
98.3
6.5
52474133
191715
97.5
5.5
43.5
2.5
5
4
3
2
AC-4/400V
0.01 0.02 0.04 0.06 0.1 0.2 0.4 0.6 1 2 4 6 10
DILM150
DILM95
DILM65
DILM40
DILM32
DILM12.15
DILM7
DILM115
DILM80
DILM50
DILM25
DILM9
R a t e
d o u t p u
t o
f t h r e e - p
h a s e m o t o r s 5 0 –
6 0 H z
R a t e
d o p e r a t i o n a
l c u r r e n t I e
5 0 –
6 0 H z
Component lifespan [millions of operations]
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 55/130
Moeller NK1210+2100+2300-1153GB-INT
2/44
Moeller NK1210+2100+2300-1153GB-INT
Engineering notesContactors for resistive load
Rating data Part no. Orderingdata
AccessoriesrequiredParallelinglink
Notes
Single-phase rating AC-1 Three-phase rating AC-1 Three-phase rating AC-1
Voltage in V Ratedoperationalcurrent I e = I th
or I the
Voltage in V Rated operationalcurrent I e = I th
or I the
Voltage in V Ratedoperationalcurrent I e = I th
or I the
220230240
380400440
660690
220230240
380400440
660690
220230240
380400440
660690
kW kW kW A kW kW kW A kW kW kW A Page Part no.
Open version Accessorie
Paralleling EnclosureAccessories
Auxiliarycontact mo
10 18 31 50 7 13 22 20 18 31 54 50 DILM7 a 2/7 DILM12-XP1
13 22 38 60 – – – – 22 38 65 60 DILMP20 a 2/7 DILM12-XP1
18 32 55 88 13 22 38 35 32 55 95 88 DILM17 a 2/7 DILM32-XP1
21 36 63 100 14 25 43 40 36 63 109 100 DILM25 a 2/7 DILM32-XP1
26 45 78 125 18 31 54 50 45 78 136 125 DILM40 a 2/7 DILM65-XP1
34 59 102 163 24 41 71 65 59 102 176 163 DILM50 a 2/7 DILM65-XP1
42 72 125 200 29 50 87 80 72 125 217 200 DILM65 a 2/7 DILM65-XP1
47 81 141 225 33 56 98 90 81 141 244 225 DILM80 a 2/7 DILM150-XP1
57 99 172 275 40 69 119 110 100 172 299 275 DILM95 a 2/7 DILM150-XP1
68 117 204 325 47 81 141 130 118 203 353 325 DILM115 a 2/7 DILM150-XP1
84 144 251 400 58 100 174 160 145 250 434 400 DILM150 a 2/7 DILM150-XP1
7 )11 3 5
8642
1 3 5
2 4 6
7 )11
2
3 5 7
4 6 8
1 3 5 7
2 4 6 8
1 3 5
2 4 6 8
Notes1)
Contact 7 – 8 only with DILMP20
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 56/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/46 Engineering notesContactors, enclosure
Components
Contactor selection
With top mountingauxiliary contacts
With side mountingauxiliary contacts
With overload relays
Part no. Insulated enclosures
DILM7 – DILM15 K – – CI-K2-145-TS
DILM7 – DILM15 K – K CI-K3-160-TS
DILM17 – DILM32 – – – CI-K2-145-TS
DILM17 – DILM32 K – K CI23E-150
DILM40 – DILM65 – K – CI-K3-160-TS
DILM40 – DILM65 K K K CI43E-150
DILM80 – DILM150 K K – CI43E-200
DILM80 – DILM150 K K K CI44E-200
DIULM7 – DIULM12 K – – CI-K4-160-TS
DIULM17 – DIULM32 K – – CI23E-150DIULM40 – DIULM65 K – – CI43E-200
SDAINLM12 – SDAINLM22 K – – CI-K5-160-TS
SDAINLM30 – SDAINLM65 K – – CI23E-150
SDAINLM70 – SDAINLM115 K – – CI43E-200
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 57/130
2/47
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Engineering notesContactor DILM
Determination of the maximum number of operations per hour in relation to the rating and utilization category (approximate values) at 400 V
P N = max. motor rating (kW) of the relevant contactor a page 5/2
S/h = max. operation per hour
Part no. Characteristic
curveAC-1
AC–-3 AC-2AC-4
DILM7, 9, 12, 15 3 1 5DILM17, 25, 32 3 2 5DILM40, 50, 65 3 2 5DILM80, 95, 115, 150 3 4 5
6000
4000
2000
1000
800
600
400
200
100
0 10 20 30 40 50 60 70 80 90 100 %
[kW]N
a
b
e
c
d
S/h
Switching DC current
– – – – – Conductor to beinstalled by customer to suitrequirement
DILM7 – DILM150 Without overload relayϹ 60 V DC Ͼ 60 V DC
With overload relayϾ 60V DC
1 pole
2 pole
DILMP20
1 pole
2 pole
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 58/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 59/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 60/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 61/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 62/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/56 Technical DataContactor for capacitors DILMK
DILK12 DILK20 DILK25 DILK33 DILK50
General
Standards IEC/EN 60947
Ambient temperature
open °C -25 – 60 -25 – 60 -25 – 60 -25 – 60 -25 – 60
enclosed °C -25 – 40 -25 – 40 -25 – 40 -25 – 40 -25 – 40
Mounting position
Mounting position
Protection type IP20 IP00 IP00 IP00 IP00
Protection against direct contact
when actuated from front (IEC 536)
Finger and back-of-hand proof
Weight Basic unit
AC operated kg 0.41 0.55 0.55 1 1
Terminal capacity main cable
Solid mm2 1x (0.75 – 4) 1x (0.75 – 16) 1x (0.75 – 16) 1x (2.5 – 16) 1x (2.5 – 16)
Flexible with ferrule mm2 1x (0.75 – 2.5) 1x (0.75 – 16) 1x (0.75 – 16) 1x (2.5 – 35) 1x (2.5 – 35)
Stranded mm2 – 1x 16 1x 16 1x (16 – 50) 1x (16 – 50)
Solid or stranded AWG 18 – 14 18 – 6 18 – 6 12 – 2 12 – 2
Flat conductor Number of segmentsx widthx thickness
mm – – – 1x (6x 9x 0.8)
1x (6x 9x 0.8)
Group compensation
Motor rating of three-phase capacitors
230 V kvar 7.5 11 15 20 25
400 V kvar 12.5 20 25 33.3 50
525 V kvar 16.7 25 33.3 40 65
690 V kvar 20 33.3 40 55 85
Rated operational current I e of three-phase capacitors
open
230 V Ie A 18 29 38 50 72
400 V Ie A 18 29 38 50 72
525 V Ie A 18 29 38 50 72
690 V Ie A 18 29 38 50 72
enclosed
230 V Ie A 16 26 34 45 65
400 V Ie A 16 26 34 45 65
525 V Ie A 16 26 34 45 65690 V Ie A 16 26 34 45 65
Making capacity (i-peak value) without damping x I e 180 180 180 180 180
Component lifespan Operations x 106 0.15 0.15 0.15 0.15 0.15
Maximum operating frequency
Max. operating frequency Ops/h 120 120 120 120 120
1 8 0 °
9 0 ° 9 0 ° 9 0
˚
30˚ 30˚30˚
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 63/130
2/57
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
Technical DataAuxiliary contacts
DILM7-... –DILM32-...
DILA(C)-XHI...
DILM(C)32-XHI...
DILM(C)150-XHI...
DILM(C)1000-XHI...
Auxiliary contacts
Interlocked opposing contacts within an auxiliary contact module
(to IEC 60947-5-1 Annex L)1)
– Yes Yes Yes Yes
N/C contact (not late-break contact) suitable as a mirror contact(to IEC/EN 60947-4-1 Annex F)
DILM7 –DILM32
DILM7 –DILM32
DILM7 –DILM32
DILM40 –DILM65
DILM40 – DILM150,DILM185 – DILM1000
Rated impulse withstand voltage Uimp V AC 6000 6000 6000 6000 6000
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3
Rated insulation voltage
AC Ui V AC 690 690 690 690 690
Rated operational voltage Ue V AC 500 500 500 500 500
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between coil and auxiliary contacts V AC 400 400 400 440 440
between the auxiliary contacts V AC 400 400 400 440 440
Rated operational current
AC–15
230 V I e A 6 6 6 6 6
380/415 V I e A 4 3 4 4 4
500 V I e A 1.5 – 1.5 1.5 1.5
DC-13 L/R – 15 ms2)
24 V I e A 10 10 10 10 10
60 V I e A 6 6 6 6 6
110 V I e A 3 3 3 3 3
220 V I e A 1 1 1 1 1
Conv. thermal current I th A 10 10 10 10 10
Control circuit reliability(at Ue = 24 V DC, Umin = 17 V, I min= 5.4 mA)
Failure rate l <10-8, < 1 one failure at 100 million operations
Component lifespan
at Ue = 230 V, AC-15, 3 A Operations x 106 1.3 1.3 1.3 1.3 1.3
Short-circuit rating without welding3)
max. fuse A gG/gL 10 10 10 16 16
Notes 1) not with DIL...-XHIV and DIL...-XHICV2) Making and breaking conditions to DC-13, time L/R constant as stated3) See transparent overlay "Fuses" for time/current characteristics (please inquire)
DILM12-XP1 DILM32-XP1 DILM65-XP1 DILM150-XP1
Parallel link
Terminal capacities
Solid mm2 1 – 16 16 16 –
Flexible with ferrule mm2 1x (0.5 – 25)2x (0.5 – 16)
1x (16 – 35) 1x (16 – 120) –
Stranded mm2 1x (0.5 – 25)2x (0.5 – 16)
1x (16 – 50) 1x (16 – 120) 1x (35 – 300)2x (35 – 120)
Flat conductor Number of segmentsx widthx thickness
mm 6x 9x 0.8 – – 2x (11x 21x 1)
Tightening torque Nm 4 4 14 –
Tool
Pozidriv screwdriver Size 2 2 – –
Hexagon socket-head spanner SW mm – – 5 6
Conventional thermal current
3 pole I th A 50 100 180 400
4 pole I th A 60 – – –
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 64/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/58 DimensionsContactors DILM
Contactors
DILM7DILM9DILM12DILM15
DILMC7DILMC9DILMC12
DILM(C)17DILM(C)25DILM(C)32
1 8
4 5
6 8
45
36
8.7 8.7 8.7 8.7 (5.1)
6.5
75
c
3.235
2x M4
6 0
Type c
DILM32-XHI 117
DILA-XHI 117
DILA-XHI..T 125
6 8
6.5
3.2
75
125
2 6 .
4
5 2 . 3
45
8.7 8.7 8.7 8.7 (5.1)
1.8
1.8
11.6 11.6
4.5
17.7
10.6(6.4)
3 8
7 1
6 0 .
4
8 5
45
4.8
138
6.5
97.4
4.5 35
2x M4
7 5
Sideways distance to earthed parts:6 mm
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 65/130
2/59
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
DimensionsContactors DILM
DILM(C)40DILM(C)50DILM(C)65
Sideways distanceto earthed parts: 6 mm
DILM80DILM95DILM115DILM150
Sideways distanceto earthed parts: 10 mm
6.9
4.734.4
114
132.1
147
55
5 7
8 6 .
4
1 0 4
1 1 5
45
2x M4
1 0 5
90
111
82.5
85.5
142
160
7 6 .
5
5 7
1 7 0
1 5 6
4x M6
1 5 6
70
a1 c
a
b 1
b 2
b
DILM12-XSPR...DILM12-XSPV...DILM12-XSPI...DILM12-XSPD...
DILM32-XSPR...DILM12-XSPV...DILM12-XSPI...
DILM95-XSPR...DILM12-XSPV...DILM12-XSPI...
a 25 25 25
a1 9.2 9.2 20
b 25.9 16 18.5
b1 28 28 28
b2 Q32 Q32 Q32
c 9 9 9
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 66/130
Moeller NK1210+2100+2300-1153GB-INT
D I L M 7 – D I L M 1 5
0
2/60 DimensionsContactor DIL
SDAINLM... star-delta combination
SDAINLM140 – SDAINLM260
Reversing combination
b
ca
SDAINLM12 –SDAINLM22
SDAINLM30 –SDAINLM55
SDAINLM70 –SDAINLM115
a 158 158 188
b 68 85 115
c 117 138 147
144 144 M 6
308
3 1 4
2 9 9
183
b
ca
DIULM7/21 –DIULM12/21
DIULM17/21 –DIULM32/21
DIULM40/11 –DIULM65/11
a 90 90 110
b 68 85 115
c 117 138 147
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 67/130
2/61
Moeller NK1210+2100+2300-1153GB-INT
C o n t a c t o r s
D I L M 7 – D I L M 1 5
0
DimensionsContactor DILM
DIULM80 – DIULM150
176
196
183M 6
3 1 4
2 9 9
Three phase commoning link
DILM12-XDSB0/3
DILM12-XDSB0/4DILM12-XDSB0/5
Contactors for capacitors with series resistor
DILK12DILK20DILK25
DILK33DILK50
1 3 .
1a
1 8 .
1
12.5
DILM12-XDSB0/3 DILM12-XDSB0/4 DILM12-XDSB0/5
a 112 157 202
b
ca
a1
b 1
d
DILK12 DILK20 DILK25 DILK33 DILK50abc
45120118
45135138
45135138
55190147
55190147
a1 35 35 35 45 45
b1 60 75 75 105 105
d 2x M4 2x M4 2x M4 2x M4 2x M4
Amplifier module
ETS4-VS3
103
98
7 8
22.5
8 2
. 5
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 68/130
3/1
Moeller NK1210+2100+2300-1153GB-INT
O v e r l o a d
r e l a y
Z B 1 2
– Z B 1 5 0
Contents, rating overviewOverload relay ZB
Page
Technical overview 3/1
Overload relay ZB 3/1
Overload relays 3/2
Overload relay ZB 3/2
Accessories 3/6
Technical data 3/7
Engineering 3/7
Overload relays 3/8
Dimensions 3/10
Overload relay ZB 3/10
Setting ranges (A)
(Note max. currentof the contactor)
DILM7DILM9DILM12DILM15
DILM17DILM25DILM32
DILM40DILM50DILM65
DILM80DILM95DILM115DILM150
Overload relays
ZB120,1 – 16
ZB32
0,1 – 32
ZB656 – 65
ZB15025-150
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 69/130
Moeller NK1210+2100+2300-1153GB-INT
3/2
Moeller NK1210+2100+2300-1153GB-INT
Overload relays Overload relay ZB
Setting rangeOverload releases
Contact sequence Auxiliary contacts For use with Short-circuit protection Part no.Article no.
Pricesee price list
Std. pack
N/O = Normally openN/C = Normally closed
Type “1”coordination
Type “2”coordination
I r gG/gL gG/gL
A A A
ZB12 overload relays
Phase failure sensitivity to IEC/EN60947, VDE 0660 Part 102
For direct mounting0.1 – 0.16 1 N/O 1 N/C DILM7, DILM9,
DILM12,DILM15,DIULM7,DIULM9,DIULM12,SDAINLM12,SDAINLM16,SDAINLM22
25 0.5 ZB12-0,16278431
1 off Overload relShort-circuitmaximum pewith direct d
Suitable for EC prototype
PTB 04 ATEX
Observe man
0.16 – 0.24 1 ZB12-0,24278432
0.24 – 0.4 2 ZB12-0,4278433
0.4 – 0.6 4 ZB12-0,6278434
0.6 – 1 4 ZB12-1278435
1 – 1.6 6 ZB12-1,6278436
1.6 – 2.4 10 ZB12-2,4278437
2.4 – 4 16 ZB12-4278438
4 – 6 20 ZB12-6278439
6 – 10 50 25 ZB12-10278440
9 – 12 ZB12-12278441
12 – 16 ZB12-16290168
ZB32 overload relays
Phase failure sensitivity to IEC/EN60947, VDE 0660 Part 102For direct mounting
0.1 – 0.16 1 N/O 1 N/C DILM17,DILM25,DILM32,DIULM17,DIULM25,DIULM32,SDAINLM30,SDAINLM45,SDAINLM55
25 0.5 ZB32-0,16278442
1 off Overload relShort-circuitmaximum pewith direct d
Suitable for EC prototype
PTB 04 ATEX
Observe man
0.16 – 0.24 1 ZB32-0,24278443
0.24 – 0.4 2 ZB32-0,4278444
0.4 – 0.6 4 ZB32-0,6278445
0.6 – 1 4 ZB32-1278446
1 – 1.6 6 ZB32-1,6278447
1.6 – 2.4 10 ZB32-2,4278448
2.4 – 4 16 ZB32-4278449
4 – 6 20 ZB32-6278450
6 – 10 50 25 ZB32-10278451
10 – 16 63 35 ZB32-16278452
16 – 24 100 35 ZB32-24278453
24 – 32 125 63 ZB32-32278454
2 4 6 9 8 9 6 A 2 1 4/
22
97 95
2 4 6 98 96 14/
22
97 95
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 70/130
Moeller NK1210+2100+2300-1153GB-INT
3/4
Moeller NK1210+2100+2300-1153GB-INT
Overload relays Overload relay ZB
Overload releases Contact sequence Auxiliary contacts For use with Short-circuit protection Part no.Article no.
Pricesee price list
Std. pack
I r N/O = Normally openN/C = Normally closed
Type “1”coordination
Type “2”coordination
A gG/gL gG/gL
A A
ZB65, ZB150 Overload relays
Phase failure sensitivity to IEC/EN 60947For direct mounting
6 – 10 1 N/O 1 N/C DILM40,DILM50,DILM65,DIULM40,DIULM50,DIULM65,SDAINLM70,SDAINLM90,SDAINLM115
50 25 ZB65-10278455
1 off Overload relShort-circuitmaximum pewith direct d
Suitable for EC prototype
PTB 04 ATEX
Observe man
10 – 16 63 35 ZB65-16278456
16 – 24 63 50 ZB65-24278457
24 – 40 125 63 ZB65-40278458
40 – 57 160 80 ZB65-57278459
50 – 65 160 100 ZB65-65278460
25 – 35 DILM80,DILM95,DILM115,DILM150,DIULM80,DIULM95,DIULM115,DIULM150,SDAINLM140,SDAINLM165,
SDAINLM200,SDAINLM260
125 100 ZB150-35278461
35 – 50 160 125 ZB150-50278462
50 – 70 250 160 ZB150-70278463
70 – 100 315 200 ZB150-100278464
95 – 125 315 250 ZB150-125278465
120 – 150 315 250 ZB150-150278466
Separate mounting
25 – 35 1 N/O 1 N/C 125 100 ZB150-35/KK278467
1 off Overload relShort-circuitmaximum pewith direct d
Suitable for EC prototype
PTB 04 ATEX
Observe man
35 – 50 160 125 ZB150-50/KK278468
50 – 70 250 160 ZB150-70/KK278469
70 – 100 315 200 ZB150-100/KK278470
95 – 125 315 250 ZB150-125/KK278471
120 – 150 315 250 ZB150-150/KK278472
2 4 6 98 96
97 95
2 4 6 98 96
97 95
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 71/130
Moeller NK1210+2100+2300-1153GB-INT
Z B 1 2
– Z B 1 5 0
3/6 Overload relaysAccessories
For use with Part no.Article no.
Pricesee pricelist
Std. pack Notes
Documentation
Overload relaysOverload monitoring of EEx emotors
– ZB12...ZB32...
AWB2300-1527D/GB284910
1 off German/English
ZB65...ZB150...
AWB2300-1545D/GB102065
1 off German/English
Bases
For separate mounting ZB32 ZB32-XEZ278473
5 off Can be snap fitted on a top-hat rail toIEC/EN 60715 or can be screw fitted.
ZB65 ZB65-XEZ278474
1 off
Push-buttons
For enclosed overload relaysMounting diameter: 22.3 mm
External reset button IP65 ZW7...
ZB12ZB32ZB65ZB150
M22-DZ-B
254833
10 off Blue button plate
M22-DZ-B-GB14254834
Blue button plate: RESET
Off button, IP65 M22-DZ-X254835
Without button plate, button platemust be added
Button plates – M22-DZ-X M22-XD-R216423
Red legend plate
M22-XD-R-X0218153
Button plate, red with white circle
M22-XD-R-GB0218194
Red legend plate STOP
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 72/130
3/7
Moeller NK1210+2100+2300-1153GB-INT
O v e r l o a d
r e l a y s
Z B 1 2
– Z B 1 5 0
Technical dataEngineering
Selection data ZB12, ZB32, ZB65, ZB150
Phase-failure sensitivity b
Temperature compensation b
Auxiliary switch N/O + N/C b
Test/off button b
Reset button manual/auto b
Separate mounting b
Protection of EEx e-motors (PTB) b
Protection with heavy starting duty –
Trip-free release b
b standard features
EC prototype test certification number
ZB12ZB32ZB65ZB150
PTB 04 ATEX 3022PTB 04 ATEX 3022PTB 04 ATEX 3022PTB 04 ATEX 3022
Protection of single-phase and DC current motors: Mounting position:1 pole 2 pole ZB12, ZB32, ZB65, ZB150
These tripping characteristics are mean values of the spread at 20 °C ambient temperature in a cold state. Tripping time depends on response current. With devices atoperating temperature the tripping time of the overload relay reduces to approx. 25 % of the read off value. Specific characteristics for each individual setting range canbe found in the manual on page 3/6.
100
60
40
20
10
6
4
2
1
40
20
10
6
4
2
1
0.6
ZB12, ZB32,
ZB65,
64 108 15 2031 21.5
x Setting current
2-phase
S e c o n d s
M i n u t e s
3-phase
2 h
100 ZB150
60
40
20
10
6
4
2
1
40
20
10
6
4
2
1
0.664 108 15 2031 21.5
x Setting current
2-phase
S e c o n d s
M i n u t e s
3-phase
2 h
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 73/130
Moeller NK1210+2100+2300-1153GB-INT
Z B 1 2
– Z B 1 5 0
3/8 Technical dataOverload relays
ZB12, ZB32 ZB65 ZB150(KK)
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Climatic proofing Damp heat, constant, to IEC 60068-2-78;
Damp heat, cyclic, to IEC 60068-2-30Ambient temperature
Open1) °C -25 – 55 -25 – 55 -25 – 55
Enclosed1) °C -25 – 40 -25 – 40 -25 – 40
Temperature compensation Continuous
Mounting position 3/7 3/7 3/7
Weight kg 0.15 0.25 1.64
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC g 10 10 10
Protection type IP20 IP00 IP00
Protection against direct contact when actuated from front(IEC 536)
Finger- and back-of-hand proof
Main conducting paths
Rated impulse withstand voltage Uimp V AC 6000 6000 6000
Overvoltage category/pollution degree III/3 III/3 III/3Rated insulation voltage
AC Ui V AC 690 690 690
Rated operational voltage Ue V AC 690 690 690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between auxiliary contacts and main contacts V AC 440 440 440
Between main circuits V AC 440 440 440
Overload release setting range A 0.1 – 32 6 – 75 25 – 150
Temperature compensation residual error > 40ºC %/K F 0.25 F 0.25 F 0.25
Short-circuit protection maximum fuse a 3/3 a 3/5 a 3/5
Current heat loss (3 conductors)
Lower value of the setting range W 2.5 3 16
Maximum setting W 6 7.5 28
Terminal capacitiesSolid mm2 2x (1 – 6) 2x (1 – 16) 2x (4 – 16)
Flexible with ferrule mm2 2x (1 – 4)2x (1 – 6)3)
1x 252x (1 – 10)2)
1x (4 – 70)2x (4 – 50)
Stranded mm2 – 1x 352x 10
–
Solid or stranded AWG 14 – 8 14 – 2 2/0
Terminal screw M4 M6 M10
Tightening torque Nm 1.8 3.5 10
Tools
Pozidriv screwdriver Size 2 2 –
Standard screwdriver mm 1x 6 1x 6 –
Hexagon socket-head spanner SW mm – – 5
Notes 1) ambient temperature to IEC/EN 60947, PTB: -5°C to +55°C2) when using 2 conductors of the same cross section3) 6 mmB flexible with ferrule to DIN 46228
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 74/130
3/9
Moeller NK1210+2100+2300-1153GB-INT
O v e r l o a d
r e l a y s
Z B 1 2
– Z B 1 5 0
Technical dataOverload relays
ZB12, ZB32 ZB65 ZB150(KK)
Auxiliary and control circuits
Rated impulse withstand voltage Uimp V 6000 6000 6000
Overvoltage category/pollution degree III/3 III/3 III/3
Terminal capacities
Solid mm2 2x (0.75 – 4) 2x (0.75 – 4) 2x (0.75 – 2.5)
Flexible with ferrule mm2 2x (0.75 – 2.5) 2x (0.75 – 2.5) 2x (0.5 – 1.5)
Solid or stranded AWG 2x (18 – 12) 2x (18 – 12) 2x (18 – 12)
Terminal screw M3.5 M3.5 M3.5
Tightening torque Nm 0.8 – 1.2 0.8 – 1.2 0.8 – 1.2
Tools
Pozidriv screwdriver Size 2 2 2
Standard screwdriver mm 1x 6 1x 6 1x 6
Rated insulation voltage Ui V AC 500 500 500
Rated operational voltage Ue V AC 500 500 500
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between the auxiliary contacts V AC 240 240 240
Conventional thermal current I th A 6 6 6
Rated operational current
AC–15
Make contact
120 V I e A 1.5 1.5 1.5
240 V I e A 1.5 1.5 1.5
415 V I e A 0.5 0.5 0.5
500 V I e A 0.5 0.5 0.5
Break contact
120 V I e A 1.5 1.5 1.5
240 V I e A 1.5 1.5 1.5
415 V I e A 0.9 0.9 0.9
500 V I e A 0.8 0.8 0.8
DC-13 L/R – 15 ms1)
24 V I e A 0.9 0.9 0.9
60 V I e A 0.753) 0.753) 0.753)
110 V I e A 0.4 0.4 0.4
220 V I e A 0.2 0.2 0.2
Short-circuit rating without welding
max. fuse2) A gG/gL 6 6 6
Notes 1) Rated operating current on and off switching conditions to DC-13, L/R constant to details2) Short-circuit rating: Time/current curve as transparent overlay "fuses" (please enquire)3) Rated operational current DC-13, 60 V: auxiliary NO contact 0.6 A
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 75/130
Moeller NK1210+2100+2300-1153GB-INT
Z B 1 2
– Z B 1 5 0
3/10 DimensionsOverload relay ZB
Overload relays
ZB12/ZB32
ZB65
ZB32-XEZZB65-XEZ
45 83
65
4 8
3 5 . 5
3 9 . 5 2
9 . 5
60 102
95.5
51.5
7 9 . 2
20.3
5
b
16.5
c2
b 1
a
c
c1 ZB32 ZB65
a 45 60
b 85 86
b1 42.5 42.5
c 90.5 112
c1 58.3 80.5
c2 3.8 4.7
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 76/130
3/11
Moeller NK1210+2100+2300-1153GB-INT
O v e r l o a d
r e l a y s
Z B 1 2
– Z B 1 5 0
DimensionsOverload relay ZB
ZB150
ZB150KK
M22-DZ-... external reset buttonOFF button M22-DZ-...
1 3 8
63
129100
134
7 4
118
99
80
95
73
1 2 1 7
4
63
129
134
100
118
99
95
100
19
2 – 5
8
2.5
2 4 .
1
22.3
3.2
o 2
9 .
5
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 77/130
4/1
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
Contents
Page
Technical overview 4/3
System overview 4/4
Motor-protective circuit-breakers
Motor-protective circuit-breakers PKZM01 4/6
Motor-protective circuit-breakers PKZM0 4/8
Motor-protective circuit-breakers PKZM4 4/8
Motor-protective circuit-breakers for starter combinations 4/10
Transformer-protective circuit-breakers PKZM0-T 4/10Accessories
Standard auxiliary contact 4/12
Trip-indicating auxiliary contact 4/14
Early-make auxiliary contacts 4/14
Current limiters CL-PKZ0 4/14
Shunt release 4/14
Undervoltage release 4/14
Insulated enclosure engineering notes 4/16
Surface mounting enclosure 4/18
Installation enclosure 4/19
Accessories 4/21
Busbar adapter 4/22
Wiring sets 4/243 phase busbar block 4/26
Actuating voltages 4/29
Tripping characteristics 4/30
Technical data 4/32
Dimensions 4/39
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 78/130
4/3
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
Technical overviewMotor-protective circuit-breakers
Motor-protectivecircuit-breaker
PKZM01 PKZM0 PKZM4 PKZ2
Page a 4/ 6 a 4/ 8 a 4/ 8 a Main catalogue forindustrial switchgear
Setting rangeoverload releaseIr
0.1 – 16 A 0.1 – 32 A 10 – 65 A 0.4 – 40 A
Motor dataat 400 V
Motor ratingP
kW
Ratedoperationalcurrent I eA
Motor ratingP
kW
Ratedoperationalcurrent I eA
Motor ratingP
kW
Ratedoperationalcurrent I eA
Motor ratingP
kW
Ratedoperationalcurrent I eA
0.06 0.21 0.06 0.210.09 0.31 0.09 0.31
0.12 0.41 0.12 0.41 0.12 0.41
0.18 0.6 0.18 0.6 0.18 0.6
0.25 0.8 0.25 0.8 0.25 0.8
0.37 1.1 0.37 1.1 0.37 1.1
0.55 1.5 0.55 1.5 0.55 1.5
0.75 1.9 0.75 1.9 0.75 1.9
1.1 2.6 1.1 2.6 1.1 2.6
1.5 3.6 1.5 3.6 1.5 3.6
2.2 5 2.2 5 2.2 5
3 6.6 3 6.6 3 6.6
4 8.5 4 8.5 4 8.5
5.5 11.3 5.5 11.3 5.5 11.3 5.5 11.37.5 15.2 7.5 15.2 7.5 15.2 7.5 15.2
9 18.2 9 18.2 9 18.2
11 21.7 11 21.7 11 21.7
12.5 25 12.5 25 12.5 25
15 29.3 15 29.3 15 29.3
18.5 36 18.5 36
20 40 20 40
22 41
30 55
34 63
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 79/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/4 System overviewMotor-protective circuit-breakers PKZM01, PKZM0, PKZM4
Motor protection, transformer protection, conductor and cable protection
66
2
1
5
4
6
3
27
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 80/130
4/5
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
System overviewMotor-protective circuit-breakers PKZM01, PKZM0, PKZM4
Basic units
Motor-protective circuit-breakers PKZM01 1
Rated operational current up to 16 A
Switching capacity 50 kA/415 VShort-circuit release,fixed setting to 14X I uOverload release, adjustable 0.6 – 1 X I u
Single-phasing sensitive
a 4/6
Motor-protective circuit-breakers PKZM0 2
Rated operational current up to 32 A
Switching capacity 150/50 kA/415 V
Short-circuit release,
fixed setting to 14X I
uOverload release, adjustable 0.6 – 1 X I u
Single-phasing sensitive
With screws or spring-loaded terminals
a 4/8
Motor-protective circuit-breakers PKZM4 3
Rated operational current up to 65 A
Switching capacity 50 kA/400 V
Short-circuit release,fixed setting to 14X I uOverload release, adjustable 0.6 – 1 X I u
Single-phasing sensitive
a 4/8
Add-on functions
Standard auxiliary contact 6
ON/OFF indication of motor-protective circuit-
breakerDifferential fault indication overload/short-circuit release
ON/OFF for (high-capacity) contact module
ON/OFF for starter combination
With early-make contacts
With screws or spring-loaded terminals
a 4/12
Voltage releases 5
Undervoltage release
Shunt releaseWith screws or spring-loaded terminals
a 4/14
Current limiter 7
Increases the switching capacity of thePKZM0-16, 20, 25 motor-protective circuit-breakers to 100 kA/440 V
Can be used for individual and groupprotection.
a 4/15
Mounting accessories
Door coupling rotary handle IP65 4
ON/OFF/Tripped switch position indication
Lockable with 3 padlocksIntegrated door/cover interlock
Extendable by plug fit extension shaft
Handle latched in switch positions
Optionally also without locking and doorinterlock function
a 4/20
Insulated enclosures
Surface mounting enclosures, IP40, IP55 andIP65
IP40 and IP55 front flush mounting enclosure
a 4/18
Mounting/wiring
Component adapter for busbar mounting
Three phase commoning link forside-by-side mounting
Mounting kits for rapid mounting of direct-on-line, reversing and star-deltastarters
a 4/22
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 81/130
Moeller NK1210+2100+2300-1153GB-INT
4/6
Moeller NK1210+2100+2300-1153GB-INT
Motor-protective circuit-breakers PKZM01 Motor-protective circuit-breakers
Screw terminals
220 – 240 V Rateduninterruptedcurrent
Setting range Part no.Article no.
Pricesee pricelist
Std. pack Notes
AC-3 Overloadreleases
Short-circuitreleases220 V
230 V240 V
380 V400 V415 V
440 V 500 V 660 V690 V
P P P P P I u I r I rm
kW kW kW kW kW A A A
Motor-protective circuit-breakers, Type "1" and Type "2" coordination
– – – – 0.06 0.16 0.1 – 0.16 2.2 PKZM01-0,16278475
1 off
– 0.06 0.06 0.06 0.12 0.25 0.16 – 0.25 3.5 PKZM01-0,25278476
0.06 0.09 0.12 0.12 0.18 0.4 0.25 – 0.4 5.6 PKZM01-0,4278477
0.09 0.12 0.18 0.25 0.25 0.63 0.4 – 0.63 8.8 PKZM01-0,63278478
0.12 0.25 0.25 0.37 0.55 1 0.63 – 1 14 PKZM01-1278479
0.25 0.55 0.55 0.75 1.1 1.6 1 – 1.6 22 PKZM01-1,6278480
0.37 0.75 1.1 1.1 1.5 2.5 1.6 – 2.5 35 PKZM01-2,5278481
0.75 1.5 1.5 2.2 3 4 2.5 – 4 56 PKZM01-4278482
1.1 2.2 3 3 4 6.3 4 – 6.3 88 PKZM01-6,3278483
2.2 4 4 4 7.5 10 6.3 – 10 140 PKZM01-10278484
3 5.5 5.5 5.5 11 12 8 – 12 168 PKZM01-12278485
4 7.5 9 9 12.5 16 10 – 16 224 PKZM01-16283390
L
T
I >
Accessories Page
3 Standard auxiliary contact a 4/13
5 Trip-indicating auxiliary contact a 4/15
6 Shunt release, undervoltage release a 4/15
Single-phasing sensitivity to IEC/EN 60947-4-1
Can be snap-fit to IEC/EN 60715 top-hat rail with 7.5 or 15 mm he
6
3
53
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 82/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 83/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 84/130
Moeller NK1210+2100+2300-1153GB-INT
4/12
Moeller NK1210+2100+2300-1153GB-INT
Motor-protective circuit-breakers PKZM0, PKZM4 MoStandard auxiliary contacts
Contacts Contact diagram Contact sequence For use with Part no. suffixOrder number fororders with basicunit
Pricesee pricelist
Std. pack Part no.Order number forseparate orders
Pricesee pricelist
Std. pack
N/O = Normally openN/C = Normally closed
Standard auxiliary contacts
For motor-protective circuit-breakers and (high-capacity) compact starters
1 N/O 1 N/C Screwterminals
PKZM01PKZM0PKZM4
PKZM0-TPKM0
+NHI11-PKZ0073233
1 off NHI11-PKZ0072896
5 off Can be fitted to thecircuit-breakers, trancircuit-breakers, mo
for starter combinatCan be combined wAGM, NHI-E-... trip-i
1 N/O 1 N/C Spring-loadedterminals
+NHI11-PKZ0-C232151
5 off NHI11-PKZ0-C229680
1 N/O 2 N/C Screwterminals
+NHI12-PKZ0073234
1 off NHI12-PKZ0072895
2 N/O 1 N/C +NHI21-PKZ0073235
NHI21-PKZ0072894
1 N/O 1 N/C +NHI-E-11-PKZ0082883
NHI-E-11-PKZ0082882
Can be fitted to mottransformer-protectiprotective circuit-brefrom Serial No. 01.The 45 mm (PKZM0of the motor-protectunchanged.
1 N/O – +NHI-E-10-PKZ0082885
NHI-E-10-PKZ0082884
1 N/O – Spring-loadedterminals
+NHI-E-10-PKZ0-C232152
5 off NHI-E-10-PKZ0-C229681
– 1 N/C Spring-loadedterminals
+NHI-E-01-PKZ0-C232153
5 off NHI-E-01-PKZ0-C229682
NHI11
L1L2L3
1.14 1.22
1.13 1.21
I >
NHI11
L1L2L3
1.14 1.22
1.13 1.21
I >
L1L2L3
NHI12
1.13
1.14 1.22
1.21 1.31
1.32
I >
L1L2L3
AGM
On/Off 1.13 1.21 1.33
1.14 1.22 1.34
I >
L1L2L3
NHI-E-11
1.53
1.54
1.61
1.62
I >
L1L2L3
NHI-E-10
1.53
1.54
I >
L1L2L3
NHI-E-10
1.53
1.54
I >
L1L2L3
NHI-E-01
1.51
1.52
I >
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 85/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 86/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/16 EngineeringAccessories for motor-protective circuit-breakers in enclosure
Enclosure Accessories
Part no. Part no. Degree of protection
Handlecolour
NHI..-PKZ0
AGM2-..-PKZ0
NHI-E..-PKZ0
VHI..-PKZ0 VHI..-PKZ01
U-PKZ0orA-PKZ0
L-PKZ0
Surface mounting enclosure
Motor-protective circuit-breakers PKZM01
CI-PKZ01 IP40 – – – ● – – ● ●
– – – – ● ● ●
● – ● – – – ●
● – – – ● – ●
CI-PKZ01-G IP65 – – – ● – – ● ●
– – – – ● ● ●
● – ● – – – ●
● – – – ● – ●
CI-PKZ01-PVTCI-PKZ01-PVS
IP65 Red-yellow
– – ● – – ● ●
– – – – ● ● ●
CI-PKZ01-SVB IP65 – – – ● – – ● ●
CI-PKZ01-SVB-V IP65 – – – – – K 1) ● ●
Motor-protective circuit-breakers PKZM0
CI-K2-PKZ0 IP41 – ● – ● – – ● ●
– ● ● – – ● ●
CI-K2-PKZ0-G IP65 Black ● – ● – – ● ●
– ● ● – – ● ●
CI-K2-PKZ0-GR IP65 Red-yellow
● – ● – – ● ●
– ● ● – – ● ●
CI-PKZ0-M IP40 – ● – ● – – – ●
– – ● – – ● ●
CI-PKZ0-GM IP55 Black ● – ● – – – ●
– – ● – – ● ●
CI-PKZ0-GRM IP55 Red-yellow
● – ● – – – ●
– – ● – – ● ●
Motor-protective circuit-breakers PKZM0 +
early-make auxiliary contact VHI-PKZ0CI-K2-PKZ0-GV IP65 Black ● – – ● – ● ●
– ● – ● – ● ●
CI-K2-PKZ0-GRV IP65 Red-yellow
● – – ● – ● ●
– ● – ● – ● ●
CI-K2-PKZ0-GVM IP55 Black ● – – ● – – ●
– – – ● – ● ●
CI-K2-PKZ0-GRVM IP55 Red-yellow
● – – ● – – ●
– – – ● – ● ●
Notes The combination possibilities of circuit-breakers in an enclosure withaccessory modules are identified by a ●1) always necessary
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 87/130
4/17
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
EngineeringAccessories for motor-protective circuit-breaker in enclosure
Enclosure Accessories
Part no. Part no. Degree of protection
Handlecolour
NHI..-PKZ0
AGM2-..-PKZ0
NHI-E..-PKZ0
VHI..-PKZ0 VHI..-PKZ01
U-PKZ0orA-PKZ0
L-PKZ0
Surface mounting enclosure
Motor-protective circuit-breakers PKZM4
CI-K4-PKZ4-G IP65 Black ● ● ● – – ● ●
● ● – ● – ● ●
CI-K4-PKZ4-GR IP65 Red-yellow
● ● ● – – ● ●
● ● – ● – ● ●
Installation enclosure
Motor-protective circuit-breakers PKZM01
E-PKZ01 IP40 – – – ● – – ● ●
– – – – ● ● ●
● – ● – – – ●
● – – – ● – ●
E-PKZ01-G IP65 – – – ● – – ● ●
– – – – ● ● ●
● – ● – – – ●
● – – – ● – ●
E-PKZ01-PVTE-PKZ01-PVS
IP65 Red-yellow
– – ● – – ● ●
– – – – ● ● ●
E-PKZ01-SVB IP65 – – – ● – – ● ●
E-PKZ01-SVB-V IP65 – – – – – K 1) ● ●
Motor-protective circuit-breakers PKZM0
E-PKZ0 IP40 – ● – – – – – ●
– – – – – ● ●
E-PKZ0-G IP55 Black ● – ● – – – ●
– – ● – – ● ●
E-PKZ01-GR IP55 Red-
yellow
● – ● – – – ●
– – ● – – ● ●
Notes The combination possibilities of circuit-breakers in an enclosure with accessory modules are identified by a ●1) always necessary
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 88/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/18 Motor-protective circuit-breakers PKZM01, PKZM0, PKZM4Insulated enclosures
Protectiontype
For use with Part no.Article no.
Pricesee pricelist
Std. pack
Insulated enclosures for surface mounting
For PKZM01 motor-protective circuit-breakers
IP40 PKZM01+NHI-Eor VHI-PKZ01+U or A or NHI+L(2 off)
CI-PKZ01281403
1 off Integrated terminal for PE(N)connection, two M25 cable entryknockouts at top and at bottom.
With actuation membrane IP65 CI-PKZ01-G281404
Lockable in off position PKZM01+NHI-E or+U or A+L (2 off)
CI-PKZ01-SVB281405
Lockable in off position incombination with VHI-PKZ01 PKZM01+NHI-E orVHI-PKZ01+U or A+L (2 off)
CI-PKZ01-SVB-V281944 1 off
With emergency-stop pushbutton actuator, stay-put
CI-PKZ01-PVT281406
1 off
With emergency-stop pushbutton actuator, release withkey
CI-PKZ01-PVS281407
1 off
For PKZM0 motor-protective circuit-breakers
Cover with aperturedimensioned to accommodatefront of breaker. IP40, whenmounted turned through 90°toleft/right
IP41whenmountedvertically
PKZM0-...+NHI or AGM+U or A+NHI-E+L-PKZ0 (2 off)
CI-K2-PKZ0219653
1 off M25 metric cable entry knockout,top and bottomPush-through cable entrydiaphragm top, bottom, in theback plate and for control cableentry.CI-K2 insulated enclosure
includes N and PE terminal.
With black/grey rotary handle IP65 CI-K2-PKZ0-G219654
With red/yellow rotary handle foruse as emergency-stop switchesto IEC/EN 60204
IP65 CI-K2-PKZ0-GR219655
Cover with aperturedimensioned to accommodatefront of breaker
IP40 PKZM0-...+NHI or U or A+L-PKZ0 (2 off)
CI-PKZ0-M267083
Integrated terminal for PE(N)connection, two M25 cable entryknockouts at top and at bottom.
With black/grey rotary handle IP55 PKZM0-...+NHI-E+NHI or U or A+L-PKZ0 (2 off)
CI-PKZ0-GM260089
1 off
With red/yellow rotary handle foruse as emergency-stop switchesto IEC/EN 60204
IP55 CI-PKZ0-GRM260104
1 off
For PKZM0 motor-protective circuit-breakers with early-make VHI auxiliary contacts
With black/grey rotary handle IP65 PKZM0-... VHI+NHI or AGM+U or A+L-PKZ0 (2 off)
CI-K2-PKZ0-GV219657
1 off M25 metric cable entry knockout,top and bottomPush-through cable entrydiaphragm top, bottom, in the backplate and for control cable entry.CI-K2 insulated enclosureincludes N and PE terminal.
With red/yellow rotary handle foruse as emergency-stop switchesto IEC/EN 60204
IP65 CI-K2-PKZ0-GRV219656
1 off
With black/grey rotary handle IP55 PKZM0-... and VHI+U or A+L-PKZ0 (2 off)
CI-PKZ0-GVM263526
1 off Integrated terminal for PE(N)connection, two M25 cable entryknockouts at top and at bottom.With red/yellow rotary handle for
use as emergency-stop switchesto IEC/EN 60204
IP55 CI-PKZ0-GRVM263525
1 off
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 89/130
4/19
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
Motor-protective circuit-breakers PKZM01, PKZM0, PKZM4Insulated enclosures
Protectiontype
For use with Part no.Article no.
Pricesee pricelist
Std.pack
For PKZM4 motor-protective circuit-breakers
With black/grey rotary handle IP65 PKZM4-...+VHI or NHI-E+NHI or AGM+U or A+L-PKZ0 (2 off)
CI-K4-PKZ4-G225524
1 off Metric knockout:top and bottom: M25/M32in the back plate: M25/M32Control cable entry: M20CI-K4 insulated enclosureincluding insulated PE terminal
With red/yellow rotary handlefor use as Emergency-Stopswitches to IEC/EN 60204
IP65 CI-K4-PKZ4-GR225525
1 off
Padlocking featureFor up to 3 padlocks with3 – 6 mm hasp thickness,for use as main switch toIEC/EN 60204
CI-K2-PKZ0-G(R)(V)CI-PKZ0-G(R)(V)M
SVB-PKZ0-CI035129
3 off Lockable in the 0-posit ion of thePKZM0 or PKZM4 motor-protective circuit-breaker.CI-K4-PKZ4-G(R) SVB-PKZ4-CI
2255261 off
Neutral terminalsFor connection of a 5th conductor
Flexible, 1 – 4 mmB
– CI-K2-PKZ0-... K-CI-K1/2207451
20 off –
63 A, flexible,6 – 16 mm2
– CI-K4-PKZ4-G(R) K25/1096200
10 off –
Insulated enclosures for flush mounting
For PKZM01 motor-protective circuit-breakers
– Front IP40 PKZM01+NHI-Eor VHI-PKZ01+U or A or NHI+L (2 off)
E-PKZ01281633
1 off Integrated terminal for PE(N)connection.
With actuation membrane Front IP65 E-PKZ01-G281634
Lockable in off position PKZM01+NHI-E+U or A+L (2 off)
E-PKZ01-SVB281635
Lockable in off position incombination with VHI-PKZ01
PKZM01+NHI-Eor VHI-PKZ01+U or A+L (2 off)
E-PKZ01-SVB-V281943
With Emergency-Stop pushbutton actuator, stay-put
E-PKZ01-PVT281636
With Emergency-Stop pushbutton actuator, release withkey
E-PKZ01-PVS281637
For PKZM0 motor-protective circuit-breakers
Cover with aperturedimensioned to accommodate
front of breaker
Front IP40 PKZM0-. ..+NHI
or U or A+L-PKZ0 (2 off)
E-PKZ0072906
1 off Integrated terminal for PE(N)connection.
With black/grey rotary handle Front IP55 PKZM0-...+NHI or U or A+NHI-E+L-PKZ0 (2 off)
E-PKZ0-G072907
With red/yellow rotary handlefor use as Emergency-Stopswitches to IEC/EN 60204
Front IP55 E-PKZ0-GR072908
Padlocking featureFor up to 3 padlocks with3 – 6 mm hasp thickness,for use as main switch toIEC/EN 60204
E-PKZ0-G(R) SVB-PKZ0-E035127
3 off Lockable in the Off positionof the PKZM0 motor-protectivecircuit-breaker
Neutral terminalFor connection of a 5th conductor
E-PKZ0(-G)(-GR)E-PKZ01(-G) N-PKZ0082160 20 off –
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 90/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/20 Motor-protective circuit-breakers PKZM01, PKZM0, PKZM4Accessories
Cable entry Hole diameter External diameterof cable
Part no.Article no.
Pricesee pricelist
Std. pack
mm mm
Metric cable glands to EN 50262
• With lock nut and integral strain relief • IP68 up to 5 bar, halogen free
M20 20.5 613 V-M20206910
20 off
M25 25.5 917 V-M25206911
20 off
M32 32.5 1321 V-M32206912
10 off
M32 32.5 1825 V-M32G226156
10 off
Metric diaphragm grommets
• IP65• With integral push-through diaphragm
M20 20.5 113 KT-M20
207602
100 off
M25 25.5 118 KT-M25207603
M32 32.5 124 KT-M32207604
Colour For use with Part no.Article no.
Pricesee pricelist
Std. pack
Door coupling handle IP651)
Can be used with PKZM0 and PKZM4
For use on main switches
to IEC/EN 60204
black – H-PKZ0
056320
1 off The plug-fit A-H-PKZ0 extension
shaft can be cut to any requiredlength for mounting depths of 100 – 240 mm.Driver pin and extension shaftsupplied with door couplinghandle.With On/Off and „+” (Tripped)switch positionswith 3 padlocks, hasp thickness4 – 8 mm. Can be locked in the Onposition if required.
For use on main switcheswith Emergency-Stop functionto IEC/EN 60204
red/yellow – RH-PKZ0056321
For use on main switchesto IEC/EN 60204 in MCC boardswhere the PKZM0 is mounted at90° from vertical.
black – H-PKZ0-MCC201454
For use on main switcheswith Emergency-Stop functionto IEC/EN 60204 in MCCdistribution boards with fittedPKZM0 turned through 90°.
red/yellow – RH-PKZ0-MCC201455
For straightforward actuationfrom outside, without doorinterlock and locking facility
Black – HSOV-PKZ0203598
The plug-fit A-H-PKZ0 extensionshaft can be cut to any requiredlength for mounting depths of 100 – 240 mm.Driver pin and extension shaftsupplied with door couplinghandle.
Terminal shroud
For enhancement of thedegree of protection of thePKZM4 to IP2x
– PKZM4 HB-PKZ4256581
1 off –
Notes 1) Additional front labels:ZFS...-T0 or ZFS...-P317 x 48 mm or 27 x 88 mma Main Catalogue Industrial Switchgearand ZFS60-NZM7For use with 17 x 64 mma Main Catalogue Industrial Switchgear
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 91/130
4/21
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
Motor-protective circuit-breakers PKZM01, PKZM0, PKZM4Accessories
Part no.Article no.
Pricesee pricelist
Std. pack
Telescopic adapters
With 45 mm top-hat rail to IEC/EN 60715, for compensating of the mountingdepth of rear mounted devices in CI-K.. enclosures and cabinets.
Telescopic adapter M22-TA226161
1 off Steplessly adjustableby means of a scale,from 75 – 115 mm.
Lockable rotary handle
For connection of the motor-protective circuit-breakerPKZM0 and PKZM4 as a main switch to EN 60204.Can be padlocked in the “0” position with a padlock.Hasp thickness: 3 – 6.35 mm
AK-PKZ0030851
5 off –
Sealing facilityTo prevent tampering with the overload release and thetest function, it can be sealed using industry standard sealingwireFor use with motor-protective circuit-breakers PKZM0 andPKZM4
PL-PKZ0203599
5 off –
Documentation
PKZM0 motor-protective circuit-breakers, overloadmonitoring of EEx e motors
AWB1210-1458D/GB266164
1 off German/English
PKZM4 motor-protective circuit-breakers, overloadmonitoring of EEx e motors
AWB1210-1457D/GB266165
1 off German/English
Blade terminal to DIN 46244
For connection of insulated ferrules for:main cables up to 25 A, 1 x 6.3 mm (DIN 46245)
control circuit cables up to 6 A, 2x
2.8 mm (DIN 46247)BT483059904
100 off Use insulated ferrules toDIN 46245.
Colour Voltage Part no.Article no.
Pricesee pricelist
Std. pack
V
Indicator lights with neon bulb
CI-K2-PKZ0-...
CI-K4-PKZ4E-PKZ0-...CI-PKZ01E-PKZ01
white 110 – 230 L-PKZ0(230V)
082151
10 off –
230 – 400 L-PKZ0(400V)082152
10 off –
415 – 500 L-PKZ0(500V)082153
5 off –
CI-K2-PKZ0-...CI-K4-PKZ4E-PKZ0-...CI-PKZ01E-PKZ01
green 110 – 230 L-PKZ0-GN(230V)082154
10 off –
230 – 400 L-PKZ0-GN(400V)082155
10 off –
415 – 500 L-PKZ0-GN(500V)082156
5 off –
CI-K2-PKZ0-...CI-K4-PKZ4E-PKZ0-...CI-PKZ01
E-PKZ01
red 110 – 230 L-PKZ0-RT(230V)082157
10 off –
230 – 400 L-PKZ0-RT(400V)082158
10 off –
415 – 500 L-PKZ0-RT(500V)082159
5 off –
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 92/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/22 Motor-protective circuit-breakers PKZM0, PKZM4Accessories
Ratedoperational voltage
Ratedoperational current
Terminalcapacity
Adapterwidth
Adapterlength
DIN rail For use with Part no.Article no.
Pricesee pricelist
Std.pack
Notes
Ue I e
V A mm mm Quantity
Busbar adapter, 3 pole
For mounting on CU flat busbars with 60 mm interval between busbar centres, suitable for 5 mmand 10 mm busbar thickness.
For direct-on-line starters
690 25 AWG 12(4 mmB)
45 200 1 PKZM0 + DILM7PKZM0 + DILM9PKZM0 + DILM12PKZM0 + DILM15MSC-D-0,25-M7...toMSC-D-16-M15...
BBA0-25101451
4 off Use in combinat ion withindividual components PKZM0and DILM DOL starter setPKZM0-XDM12.MSC-... available as acomplete unit on busbaradapters.
690 32 AWG 10(6 mmB)
45 200 2 PKZM0 + DILM17PKZM0 + DILM25PKZM0 + DILM32MSC-D-16-M17...toMSC-D-32-M32...
BBA0-32101452
Can be used incombination with individualcomponents PKZM0 and DILMelectric contact modulePKZM0-XM32DE.MSC-... available as acomplete unit on busbaradapters.
690 63 AWG 8(10 mmB)
55 260 2 PKZM4 + DILM17PKZM4 + DILM25PKZM4 + DILM32PKZM4 + DILM40PKZM4 + DILM50PKZM4 + DILM65
BBA4L-63101459
For electrical connection forPKZM4 + DILM17 – DILM32:MVS-LB0-0M-GPKZM4 + DILM40 – DILM65:PKZM4-XM65DEcan be used.
690 63 AWG 8(10 mmB)
72 260 2 PKZ2 + DILM7PKZ2 + DILM9PKZ2 + DILM12PKZ2 + DILM15PKZ2 + DILM17PKZ2 + DILM25PKZ2 + DILM32PKZ2 + DILM40
BBA2L-63101480
2 off For electrical connection forPKZ2 + DILM7 – DILM12:MVS-LB0-00M-GPKZ2 + DILM15 – DILM32:MVS-LB0-0M-Gcan be used.
For reversing starters
690 25 AWG 12(4 mmB)
90 200 1 PKZM0+ 2 x DILM7-01PKZM0+ 2 x DILM9-01PKZM0+ 2 x DILM12-01MSC-R-0,25-M7...
toMSC-R-12-M12...
BBA0R-25101453
2 off Use in combinat ion withindividual components PKZM0and DILM reversing starter setPKZM0-XRM12.MSC-... available as acomplete unit on busbaradapters.
690 32 AWG 10(6 mmB)
90 200 2 PKZM0+ 2 x DILM17-01PKZM0+ 2 x DILM25-01PKZM0+ 2 x DILM32-01MSC-R-16-M17...toMSC-R-32-M32...
BBA0R-32101454
2 off Can be used incombination with individualcomponents PKZM0 andDILM electric contact modulePKZM0-XM32DE andreversing wiring kitDILM32-XRL.MSC-... available as acomplete unit on busbaradapters.
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 93/130
4/23
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
Motor-protective circuit-breakers PKZM0, PKZM4Accessories
Ratedoperationalvoltage
Ratedoperationalcurrent
Terminalcapacity
Adapterwidth
Adapterlength
DIN rail For use with Part no.Article no.
Pricesee pricelist
Std. pack Notes
Ue I e
V A mm mm Quantity
Busbar adapter, 3 pole
For mounting on CU flat busbars with 60 mm interval between busbar centres, suitable for 5 mm and10 mm busbar thickness.
For starters with springloaded terminals
690 16 AWG 14(2.5 mmB)
45 200 2 PKZM0-C + DILMC7PKZM0-C + DILMC9PKZM0-C + DILMC12
BBA0C-16101455
4 off –
690 16 AWG 14
(2.5 mmB)
90 200 2 PKZM0-C
+ 2x
DILMC7-01PKZM0-C+ 2 x DILMC9-01PKZM0-C+ 2 x DILMC12-01
BBA0RC-16
101456
2 off –
Motor-protective circuit-breakers
690 63 AWG 8(10 mmB)
54 200 1 PKZM4 BBA4-63101457
4 off –
690 63 AWG 8(10 mmB)
72 200 1 PKZ2 BBA2-63101458
4 off –
Universal adapterFor universal use
690 25 AWG 12(4 mmB)
45 200 2 – BBA0-25/2TS101481
4 off Mounting rail canbe offset on 1.25 mmgrid.
Empty moduleWithout electrical contacts
– – – 45 200 2 – BBA0/2TS-L101482
4 off Mounting rail can beoffset on 1.25 mmgrid.For use withimplementation of reversing and star-delta starters.
– – – 54 200 2 – BBA4/2TS-L101483
4 off
Side mounted moduleCan be plugged into both sides
– – – 9 200 – – BBA-XSM101484
10 off Can be grouped onbusbar adapters forexpansion of themounting width.
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 94/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/24 Motor-protective circuit-breakers PKZM0, PKZM4Accessories
For use with Part no.Article no.
Pricesee pricelist
Std.pack
Notes
Wiring set
DOL starters
PKZM0 + DILM7PKZM0 + DILM9PKZM0 + DILM12PKZM0 + DILM15
PKZM0-XDM12283149
1 off Comprised of:• Mechanical connection element for PKZM0 and contactor• Main current wiring between PKZM0 and contactor in tool-less plug
connection• Cable guidanceUse as contactor auxiliary switch DILA-XHIT...a 2/13Control cable guidance: max. 6 cables up to 2.5 mm2 external diameteror 4 cables up to 3.5 mm2 external diameter
PKZM0 + DILM17PKZM0 + DILM25PKZM0 + DILM32
PKZM0-XDM32283153
1 off Comprised of:• Top-hat rail adapter plate• Main current wiring between PKZ and contactor
PKZM4 + DILM40PKZM4 + DILM50PKZM4 + DILM65
PKZM4-XDM65101053
1 off
Reversing starters
PKZM0 + DILM7-01PKZM0 + DILM9-01PKZM0 + DILM12-01
PKZM0-XRM12283185
1 off Comprised of:• Mechanical connection element for PKZM0 and contactor• Reversing starter main current wiring in tool-less plug connection• Control cables for electrical interlocking in tool-less plug connection:
– K1M: A1 – K2M: 21– K1M: 21 – K2M: A1– K1M: A2 – K2M: A2
• Cable guidanceUse as contactor auxiliary switch DILA-XHIT...a 2/13Control cable guidance: max. 6 cables up to 2.5 mm2 external diameteror 4 cables up to 3.5 mm2 external diameter
PKZM0 + DILM17PKZM0 + DILM25PKZM0 + DILM32
PKZM0-XRM32283189
1 off Comprised of:• Top-hat rail adapter plate• Reversing starter main current wiring
Star-delta starter
PKZM0 + DILM7PKZM0 + DILM9PKZM0 + DILM12PKZM0 + DILM15
PKZM0-XSM12239346
1 off Comprised of:• Top-hat rail adapter plate• Main current wiring between PKZM0 and contactor• Electrical interlock between delta and star contactor• Use as contactor auxiliary switch DILA-XHIT...a 2/13
PKZM0 + DILM17PKZM0 + DILM25PKZM0 + DILM32
PKZM0-XSM32239347
1 off Comprised of:• Top-hat rail adapter plate• Main current wiring between PKZM0 and contactor
Electric contact module
PKZM0 + DILM17PKZM0 + DILM25PKZM0 + DILM32
PKZM0-XM32DE239349
5 off • Main current wiring between PKZM0 and contactor• Use only in combination with busbar adapter
PKZM4 + DILM40PKZM4 + DILM50PKZM4 + DILM65
PKZM4-XM65DE101056
5 off • Main current wiring between PKZM4 and contactor• Use only in combination with busbar adapter
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 95/130
4/25
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
Motor-protective circuit-breakers PKZM0, PKZM4Accessories
For use with Part no.Article no.
Pricesee pricelist
Std. pack Notes
Top-hat rail adapter plate
PKZM0-XDM12PKZM0-XRM12
PKZM0-XC45283132
4 off Comprised of:• 45 mm wide adapter plate• Connection element for side-by-side positioning of further
plates
PKZM4 + DILM40PKZM4 + DILM50PKZM4 + DILM65
PKZM4-XC55/2101054
4 off Comprised of:• 55 mm wide adapter plate• Connection cams for further plates• For use with reversing and star-delta starters
Side mounted module
– PKZM0-XS
239354
10 off Can be grouped on the top-hat rail adapter
Expansion of the mounting width by 9 mm.Connection element
– PKZM0-XCM239359
50 off For connection of several top-hat rail adapter
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 96/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/26 Motor-protective circuit-breakers PKZM0Accessories
Circuit-breaker/compact starter
Length Unit width Part no.Article no.
Pricesee pricelist
Std. pack Notes
Number mm mm
Three phase commoning link, power feed to terminals 1, 3, 5
Protection against direct contact (touch-proof),U e = 690 V, I u = 63 Acan be lengthened by rotated mounting
For PKZM0-... without side mounted auxiliary contacts or voltage releases
2 90 45 B3.0/2-PKZ0063961
10 off For parallel power feed to severalmotor-protective circuit-breakers onterminals 1, 3, 53 135 45 B3.0/3-PKZ0
232289
4 180 45 B3.0/4-PKZ0063960
5 225 45 B3.0/5-PKZ0232290
For motor-protective circuit-breaker each with an auxiliary contact or
trip-indicating auxiliary contact fitted on the right2 99 45 + 9 B3.1/2-PKZ0
04494510 off For parallel power feed to several
motor-protective circuit-breakers onterminals 1, 3, 53 153 45 + 9 B3.1/3-PKZ0
044946
4 207 45 + 9 B3.1/4-PKZ0044947
5 261 45 + 9 B3.1/5-PKZ0044948
For PKZM0-... with one auxiliary contact each and a trip-indicating auxiliarycontact fitted on right or a voltage release fitted on left
2 108 45 + 18 B3.2/2-PKZ0063963
10 off For parallel power feed to severalmotor-protective circuit-breakers onterminals 1, 3, 54 234 45 + 18 B3.2/4-PKZ0
06395910 off
Shroud for unused terminals
Protection against direct contact.For closing off non-used connections on the three phase commoning linkB3...-PKZ0
– – – H-B3-PKZ0032721
20 off –
Incoming terminal
– – – BK25/3-PKZ0032720
5 off For three-phase commoning link,protected against accidental contact,U e = 690 V, I u = 63 AFor conductor cross-sections:2.5 – 25 mm2 stranded2.5 – 16 mm2 flexible with ferrulesAWG 14 – 6, for use on terminals 1, 3, 5
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 97/130
4/27
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
Motor-protective circuit-breakers PKZM0Accessories
Circuit-breaker/compact starter
Length Unit width Part no.Article no.
Pricesee pricelist
Std. pack Notes
Number mm mm
Three phase commoning link, power feed to terminals 2, 4, 6
Protection against direct contact (touch-proof),U e = 690 V, I u = 63 Acan be lengthened by rotated mounting
For PKZM0-... without side mounted auxiliary contacts or voltage releases
2 90 45 B3.0/2-PKZ0-U292387
5 off For parallel power feed to severalmotor-protective circuit-breakers onterminals 2, 4, 63 135 45 B3.0/3-PKZ0-U
292388
4 180 45 B3.0/4-PKZ0-U292389
5 225 45 B3.0/5-PKZ0-U292880
For motor-protective circuit-breaker each with an auxiliary contact or
trip-indicating auxiliary contact fitted on the right2 99 45 + 9 B3.1/2-PKZ0-U
2928815 off For parallel power feed to several
motor-protective circuit-breakers onterminals 2, 4, 63 153 45 + 9 B3.1/3-PKZ0-U
292882
4 207 45 + 9 B3.1/4-PKZ0-U292883
5 261 45 + 9 B3.1/5-PKZ0-U292884
Shroud for unused terminals
Protection against direct contact.For closing off non-used connections on the three phase commoning linkB3...-PKZ0-U
– – – H-B3-PKZ0-U
292885
10 off –
Incoming terminal
– – – BK25/3-PKZ0-U292886
10 off For three-phase commoning link,protected against accidental contact,U e = 690 V, I u = 63 AFor conductor cross-sections:2.5 – 25 mm2 stranded2.5 – 16 mm2 flexible with ferrulesFor use on the terminals 2, 4, 6
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 98/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/28 Motor-protective circuit-breakers PKZM4Accessories
Circuit-breaker/compact starter
Length Unit width Part no.Article no.
Pricesee price list
Std. pack
Number mm mm
Three-phase commoning link
Protection against direct contact (touch-proof), U e = 690 V, I u = 128 A
For motor-protective circuit-breakers/(high-capacity) compact starters without side-fitted auxiliary contact or
2 110 55 B3.0/2-PKZ4220220
1 off
3 165 B3.0/3-PKZ4220221
4 220 B3.0/4-PKZ4220222
For motor-protective circuit-breakers/starters each with an auxiliary contact ortrip-indicating auxiliary contact fitted on the right, and with a DIL1(A)M contactor
2 119 55 + 9 B3.1/2-PKZ4
220223
1 off
3 183 B3.1/3-PKZ4220224
4 247 B3.1/4-PKZ4220225
For PKZM4 with one auxiliary contact each ortrip-indicating auxiliary contact fitted on right or a voltage release fitted on left
2 128 55 + 18 B3.2/2-PKZ4220226
1 off
4 274 55 + 18 B3.2/4-PKZ4220227
1 off
Shroud for unused terminals
Protection against direct contact.To cover unused terminals on three-phase commoning link
– – – H-B3-PKZ4220228
10 off
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 99/130
4/29
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
Actuating voltagesMotor-protective circuit-breakers PKZM0, PKZM4
Shunt releases, undervoltage releases
When ordered with basic unit When ordered separately
AC +A-PKZ0(...) +U-PKZ0(...) A-PKZ0(...) U-PKZ0(...)
Article no.1) Article no.1) Article no.1) Article no.1)
Standard voltage See price list See price list See price list See price list
24 V 50 Hz 073305 073253 073181 073129
48 V 50Hz 073313 073262 073183 073131
110 V 50 Hz 073292 073240 073184 073132
220 V 50 Hz 073300 073248 073186 073134
230 V 50 Hz 073302 073250 073187 073135
240V 50Hz 073303 073251 073188 073136
380 V 50 Hz 073308 073256 073189 073137
400 V 50 Hz 073309 073257 073190 073138
415 V 50 Hz 073310 073258 073191 073139
120 V 60 Hz 073295 073243 073195 073143
240 V 60 Hz 073304 073252 073198 073146
440 V 60 Hz 082192 082193 082164 082161480 V 60 Hz 051492 073261 073199 073147
Non-standard voltages with the exceptionof the given standard voltages2).
See price list See price list See price list See price list
...V 50Hz (24 – 500V) 914740 914742 982165 982162
...V 60Hz (24 – 600V) 914739 914741 982166 982163
DC
Standard voltage See price list See price list See price list See price list
24 V DC 073306 – 073200 –
48V DC 073314 – 073201 –
60V DC 073315 – 073202 –
110V DC 073294 – 073203 –125 V DC 073296 – 073204 –
220V DC 073301 – 073205 –
250V DC 073307 – 073206 –
Notes 1) The article no. is formed from the combination of part no. and actuating voltage.2) With non-standard voltages the required actuating voltage from the defined range (...–...V) must be stated.
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 100/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/30 Tripping characteristicsMotor-protective circuit-breakers PKZM0, PKZM01, PKZM4
Tripping characteristics for motor-protective circuit-breakers PKZM0-...T (not for PKM0-...), PKZM01
Let-through characteristics, motor-protective circuit-breaker, transformer-protective circuit-breaker,circuit-breaker for starter combinations
PKZM0...-T
PKZM0-...,PKZM01
2
5
20
50
200
1
2
5
10
20
40
1
2
5
10
202 h
1.5 2 3 4 6 8 10 15 20 30
x Rated operational current
S e c o n d s
M i l l i - s e c o n
d s
M i n u t e s
2
5
20
50
200
1
2
5
10
20
40
1
2
5
10
202 h
1.5 2 3 4 6 8 10 15 20 30
PKZM4-...
x Rated operational current
S e c o n d s
M i l l i - s e c o n d s
M i n u t e s
1
2
3
6
4
8
10
4.0 A
6.3 A
2.5 A
1.6 A
0.25 A
10 A/12 A
0.1
0.2
0.3
0.4
0.6
0.8
0.01
0.02
0.015
0.03
0.04
0.06
0.08
1 21.5 3 4 6 8 10 2015 30 40 60 80 100
Ue = 400 V
[kA]16 A20 A25 A32 A
1 A
0.4 A
0.63 A
2 · I c c
x DPKZM0-....
PKZM01-....
PKM0-....
I cc rms [kA]
Ue = 400 V
PKZM01PKZM0-....PKM0-....
104
1.5
2
3
6
4
8105
4.0 A
6.3 A
2.5 A
1.6 A
1.0 A
10 A/12 A
103
2
1.5
3
4
6
8
102
2
1.5
3
4
6
8
1 21.5 3 4 6 8 10 2015 30 40 60 80 100
16 A20 A
25 A32 A
[kA]
[A2 s]
y Z
1 s t h
a l f - w a
v e
I cc rms
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 101/130
4/31
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
Tripping characteristicsMotor-protective circuit-breakers PKZM01, PKZM0, PKZM4
Motor-protective circuit-breaker let-through characteristics
Ue = 400 V
10
10 100
[kA]
63/58 A50/40/32 A
25 A
16 A
PKZM4
11
100
2 · I c
c
DÎ
I cc rms [kA]
105
106
104
102
1 10 100
y
[kA]
103
[A2 s]
Ue = 400 V
63/58 A50/40/32 A
25 A
16 A
PKZM4Z
I cc rms
1 s t h a
l f - w a v
e
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 102/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/32 Technical dataMotor-protective circuit-breakers PKZM01, PKZM4
Circuit-breaker switching capacity
Rated uninterrupted current I u
Rated conditional short-circuit current I q IEC/EN 60947-4-1
Rated ultimate short-circuit breaking capacity I cuIEC/EN 60947-2
Rated operational short-circuit breaking capacity I cs
230 V 400 V 440 V 500 V 690 V
I u I q I cu I cs I q I cu I cs I q I cu I cs I q I cu I cs I q I cu I cs
A kA kA kA A1) kA kA kA A1) kA kA kA A1) kA kA kA A1) kA kA kA A1)
PKZM01 with coordination Type “1” and “2”
0.16 – 1 50 50 50 50 50 50 50 50 50 50 50 50
1.6 50 50 50 50 50 50 50 50 50 50 50 50
2.5 50 50 50 50 50 50 50 50 50 50 50 50
4 50 50 50 50 50 50 50 50 50 50 50 50
6.3 50 50 50 50 50 50 50 50 50 50 50 50
10 50 50 50 50 50 50 50 50 42 42 10 50
12 50 50 10 50 50 50 10 50 15 15 10 50
PKZM4 with coordination Type “1” and “2”
16 150 150 25 N 150 150 25 N 45 45 25 100 15 15 100 8 8 2.5 100
25 150 150 25 N 150 150 25 N 45 45 25 100 15 15 100 8 8 2.5 100
32 50 50 25 100 50 50 25 100 45 45 25 100 15 15 100 5 5 2.5 100
40 50 50 25 100 50 50 25 100 45 45 25 100 15 15 100 5 5 2.5 100
50 50 50 25 100 50 50 25 100 45 45 25 100 15 15 100 5 5 2.5 100
58 50 50 25 160 50 50 25 160 45 45 25 160 15 15 160 5 5 2.5 160
63 50 50 25 160 50 50 25 160 45 45 25 160 15 15 160 5 5 2.5 160
Notes
N
No upstream protective device re-quired, as it is the auto-protected range(150 kA)
Not required
1) Fuse (A gG/gL) for enhancingthe switching capacity of themotor-protective circuit-breaker
to 100 kA
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 103/130
4/33
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
Technical dataMotor-protective circuit-breakers PKZM0
Circuit-breaker switching capacity from serial no. 04
Rated uninterrupted current I u
Rated conditional short-circuit current I q IEC/EN 60947-4-1
Rated ultimate short-circuit breaking capacity I cuIEC/EN 60947-2
Rated operational short-circuit breaking capacity I cs
230 V 400 V 440 V 500 V 690 V
I u I q I cu I cs I q I cu I cs I q I cu I cs I q I cu I cs I q I cu I cs
A kA kA kA A1) kA kA kA A1) kA kA kA A1) kA kA kA A1) kA kA kA A1)
PKZM0, PKZM0...-T, PKM0 with coordination Type “1” and “2”
0.16 – 1 150 150 150 N 150 150 150 N N N N
1.6 150 150 150 N 150 150 150 N N N N
2.5 150 150 150 N 150 150 150 N N N 5 5 5 50
4 150 150 150 N 150 150 150 N N N 3 3 3 50
6.3 150 150 150 N 150 150 150 N N 42 42 6 50 3 3 2 50
10 150 150 150 N 150 150 150 N 42 42 10 50 42 42 6 50 3 3 2 50
12 50 50 10 50 50 50 10 50 15 15 10 50 15 15 6 50 3 3 2 50
16 50 50 10 50 50 50 10 50 15 15 10 50 15 15 6 50 3 3 2 50
20 50 50 10 50 50 50 10 50 10 10 10 50 6 6 6 50 3 3 2 50
25 50 50 10 50 50 50 10 50 10 10 10 50 6 6 6 50 3 3 2 50
32 50 50 10 50 50 50 10 50 10 10 10 50 6 6 6 50 3 3 2 50
PKZM0 (PKZM0...-T, PKM0) + CL-PKZ0
0.16 – 1 N N N N 20 N
1.6 N N N N 20 N
2.5 N N N N 20 20 20 N
4 N N N N 20 20 20 N
6.3 N N N 50 N 20 20 20 N
10 N N N 20 N 20 20 20 N
12 N N N 20 N 5 5 2,5 N16 N N N 20 N 5 5 2,5 N
20 N N N 10 10 10 N 5 5 2,5 N
25 N N N 10 10 10 N 5 5 2,5 N
32 N N N 10 10 10 N 5 5 2,5 N
PKZM0 (PKZM0...-T, PKM0) + 2 CL-PKZ0
0.16 – 1 N N N N 20 N
1.6 N N N N 20 N
2.5 N N N N 40 40 20 N
4 N N N N 40 40 20 N
6.3 N N N 50 N 20 20 20 N
10 N N N 40 N 20 20 20 N
12 N N N 40 N 10 10 2,5 N
16 N N N 40 N 10 10 2,5 N
20 N N N 20 20 20 N 10 10 2,5 N
25 N N N 20 20 20 N 10 10 2,5 N
32 N N N 20 20 20 N 10 10 2,5 N
Notes
N
No upstream protective devicerequired, as it is the auto-protected range (100/150 kA)
Not required
1) Required back-up fuse if the short-circuit current exceedsthe rated conditional short-circuit current of the devices ( I cc Ͼ I q).
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 104/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 105/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/36 Technical DataAuxiliary contact PKZM...
NHI...PKZ0 NHI-E-...PKZ0 VHI...PKZ0 AGMtrip indication
Auxiliary contacts
Rated impulse withstand voltage Uimp V AC 6000 4000 4000 6000
Overvoltage category/pollution degree III/3 III/3 III/3 III/3
Rated operational voltage Ue V AC 500 440 440 500
Ue V DC 250 250 250 250
Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between auxiliary contacts and main contacts V AC 690 690 690 690
Rated operational current
AC–15
220 – 240 V I e A 3.5 1 1 3.5
380 – 415 V I e A 2 – – 2
440 – 500 V I e A 1 – – 1
DC-13 L/R – 100 ms
24 V I e A 2 2 2 2
60 V I e A 1.5 – – 1.5
110 V I e A 1 – – 1
220 V I e A 0.25 – – 0.25
Lifespan
Lifespan, mechanical Operations x 106 0.1 0.1 0.1 0.01
Lifespan, electrical Operations x 106 0.05 0.1 0.1 0.005
Control circuit reliability(at Ue = 24 V DC, Umin = 17 V, I min= 5.4 mA)
Failure rate l < 10-8 < 1 failure at 1 x 108 operations
Interlocked opposing contacts to ZH 1/457 Yes – – –
Short-circuit rating without welding
Fuseless FAZ-B4/1-HI – – FAZ-B4/1-HI
Fuse A gG/gL 10 10 10 10
Terminal capacities
Solid or flexible conductor with ferrule mm2 0.75 – 2.5 0.75 – 1.5 0.75 – 1.5 0.75 – 2.5
Solid or stranded AWG 18 – 14 18 – 16 18 – 16 18 – 14
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 106/130
4/37
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
Technical dataVoltage releases
U-PKZ...
Undervoltage release
Terminal capacities Solid or flexible conductor with ferrule mm2 1 x (0.75 – 2.5)2 x (0.75 – 2.5)
Solid or stranded AWG 1 x (18 – 14)2 x (18 – 14)
Main conducting paths
Rated operating voltage Ue V AC 42 – 480
Rated operating voltage Ue V DC 24 – 250
Pick-up voltage x Us 0.85 – 1.1
Drop-out voltage x Us 0.7 – 0.35
Power consumption Pick-up AC Pick-up VA 5
Sealing AC Sealing VA 3
A-PKZ...
Shunt release
Terminal capacities Solid or flexible conductor with ferrule mm2 1 x (0.75 – 2.5)2 x (0.75 – 2.5)
Solid or stranded AWG 1 x (18 – 14)2 x (18 – 14)
Main conducting paths
Rated operating voltage Ue V AC 42 – 480
Rated operating voltage Ue V DC 24 – 250
Operating range AC x Us 0.7 – 1.1
DC voltage (intermittent operation 5 s) x Us 0.7 – 1.1
Power consumption
AC Pick-up AC Pick-up VA 5
Sealing AC Sealing VA 3
DC Pick-up DC Pick-up W 3
Sealing DC Sealing W 3
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 107/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/38 Technical dataMotor-protective circuit-breakers PKZM...
PKZM0, PKZM4 in 1 and 2 pole circuits with AC/DC
Protection of PVC insulated cables against thermal overload with short-circuits
The table indicates which minimum cable cross-sections are protected bymotor-protective circuit-breakers PKZ(M) up to their rated conditional short-circuit current I q.
Fuseless installation with PKZ(M), back-up-protection diagrams
1 3 5
2 4 6
I > I > I >
1 3 5
2 4 6
I > I > I >
Min. cross-section protected
380 – 415 V, 50 Hz, Cu mm2
Device
Type
4 2,5 1,5 1 0,75
PKZM0-0,16
.
.
.
PKZM0-6,3PKZM0-10
PKZM0-16
PKZM0-20
PKZM0-25
PKZM4-16
PKZM4-25
PKZM4-32
PKZM4-40
PKZM4-50
PKZM4-58
PKZM4-63
I c c
I c n
PKZM0
PKZM0
415 V AC
I n h e r e n t l y s h o r t - c i r c u i t p r o o f
I
c c r m s
[ k A ]
Back-upprotectionrangewith CL-PKZ 0
Ratedshort-circuitbreakingcapacityrange
100
50
30
20
16
10
6
0.16... 10 16 20 25
P K Z M 0 - . . .
+ C L - P K Z 0
P K Z M 0 - . . .
PKZM0
Ratedcurrent I n [A]
Inherentlyshort-circuit-proof
I c c
I c n
PKZM4
PKZM4
415 V AC
I n h e r e n t l y s h o r t - c i r c u i t p r o o f
I
c c r m s
[ k A ]
Back-upprotectionrangewith CL-PKZ 0
Ratedshort-circuitbreakingcapacityrange
100
50
30
20
16
10
6
16... 3225 40 50 63 I n [A]
PKZM4-... +CL-PKZ0
PKZM4-...
Ratedcurrent
I n h e r e n t l y
s h o r t - c i r c u i t - p r o o f
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 108/130
4/39
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
DimensionsMotor-protective circuit-breakers PKZM0, PKZM01
Motor-protective circuit-breakers
PKZM01
Motor-protective circuit-breakers, transformer-protective circuit-breakers
PKZM0-...(+NHI-E-..-PKZ0)PKZM0-...TPKM0-...
Motor-protective circuit-breakers with lockable rotary handles
PKZM0-... +AK-PKZ0
Current limiter
CL-PKZ
a IEC/EN 60715 top-hat rail
Motor-protective circuit-breakers with early-make auxiliary contacts
PKZM0-...+VHI-...-PKZ0
Standard auxiliary contact
NHI...-PKZ0
trip-indicating auxiliary contacts
AGM2-...-PKZ0
Voltage releases
U/A-PKZ0
5.545
4 5
9 3
44
74
85
NHI-E-..-PKZ0 NHI-E-..-PKZ0
70
5 5
45
25
9 3
50
76
68
4 5
4 . 5
45
AK-PKZ 0
AK-PKZ 0
9 3
50
88
94
4 5
70
7.5
49.5
447.5
45
28
9 0
7 3
9 3
a
VHI...-PKZ0
80
5 5
45
9 3
50
86
68
4 5
VHI...-PKZ0
9 2668
4 5
9 0
3 6
9 2668
4 5
9 0 3
6
18 4968
3 6
4 5
9 0
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 109/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/40 DimensionsMotor-protective circuit-breakers PKZ0
Three-phase commoning link
B3.0/4-PKZ0B3.0/2-PKZ0
Three-phase commoning link
B3.2/4-PKZ0B3.2/2-PKZ0
Three-phase commoning link
B3.1/5-PKZ0B3.1/4-PKZ0B3.1/3-PKZ0B3.1/2-PKZ0
Incoming terminal
BK25/3-PKZ0
Three-phase commoning link
B3.0/5-PKZ0-UB3.0/4-PKZ0-U
B3.0/3-PKZ0-UB3.0/2-PKZ0-U
Three-phase commoning link
B3.1/5-PKZ0-UB3.1/4-PKZ0-U
B3.1/3-PKZ0-UB3.1/2-PKZ0-U
Type a Type a
B3.0/5-...B3.0/4-...B3.0/3-...B3.0/2-...
21517012580
B3.1/5-...B3.1/4-...B3.1/3-...B3.1/2-...
25219814489
180 (90)
H-B3-PKZ 0
27
45
234 (108)
H-B3-PKZ 0
27
63
H-B3-PKZ 0
27
261 (207, 153, 99)
54
Overlapping mountingto extend the three-phasecommoning link
BK25/3-PKZ0
F 41
7 3
7.5 31
4 8
F 56
B3...-PKZ0
1 3 . 2
a
2 7 . 5
13.6 1 3 . 2
a
2 7 . 5
13.6
Incoming terminalBK25-PKZ0-U
1 5
4 2
44 33.5
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 110/130
4/41
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
DimensionsMotor-protective circuit-breakers PKZM01
Insulated enclosures for surface mounting
CI-PKZ01/CI-PKZ01-G CI-PKZ01-PVT/CI-PKZ01-PVS
CI-PKZ01-SVB(-V)
Insulated enclosures for flush mounting
E-PKZ01(-G) E-PKZ01-PVT/E-PKZ01-PVS
E-PKZ01-SVB(-V)
80
1 5 8
116.5 80
1 5 8
116.5
177.2
80
1 5 8
116.5
129.5
69
90.2 93
115.2
1 2 9
69
90.2 93
115.2
175.9
1 2 9
69
90.2 93
115.2
1 2 9
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 111/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/42 DimensionsMotor-protective circuit-breakers PKZM0
Insulated enclosures for surface mounting
CI-PKZ0 CI-PKZ0-G(R)(V)
CI-PKZ0-G(R)(V)ϩSVB-PKZ0-CI
Drilling dimensionsCI-PKZ0…
CI-K2-PKZ0 CI-K2-PKZ0G(R)(V)
CI-K2-PKZ0-G(R)(V)ϩSVB-PKZ0-CI
Drilling dimensionsCI-K2-PKZ0…
80
1 5 8
90
100
7 0
80
1 5 8
97.5
125.5
98
30
4 4
5 5
SVB-PKZ0-CI
80
1 5 8
28
3 3
97.5
4 . 5
1 5 3
8
30
4.5
100
1 6 0
47.5
104
1 8 1
100
1 6 0
47.5
103
130
1 8 1
98
30
4 4
5 5
SVB-PKZ0-CI
97
1 8 1
28
3 3
114
1 7 1
M4
M4
30
1 6 0
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 112/130
4/43
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
DimensionsMotor-protective circuit-breakers PKZM0
Door coupling handle
(R)H-PKZ0, HSOV-PKZ0
Insulated enclosures for flush mounting
E-PKZ0E-PKZ0-G(R)
Mounting apertureE-PKZ0…
6 2
1 9 .
5
+l
o
64
6 4
48
4 8
7.5
4 3
At least 100 mm
up to cover hinge
Mounting depth: 100 to 240 mm fromthe top edgeof the mounting rail to the frontedge of the panel door/cover
69
85
1 2 9
96
80
124
5 5
98
30
5 8
5 5
80
96
124
E-PKZ0-G(R)ϩSVB-PKZ0-E
85
1 2 9
30
28
2 1
R4
70–72
1 1 6
–
1 1 8
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 113/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/44 DimensionsMotor-protective circuit-breakers PKZM4
Motor-protective circuit-breakers
PKZM4
Motor-protective circuit-breakers with lockable rotary handles
PKZM4...+AK-PKZ0
Auxiliary contact and trip-indicating auxiliary contact dimensions a 4/39
30 NHI-E... 7.5
118
127
145
160
55
1 3 0
1 4 0
1 2 5
6 5
5 3 4
5
;; ;; ;
4
NHI-E...
30 7.5
118
127
145
171
55
1 3 0
1 4 0
1 2 5
6 5
4 5
4
AK-PKZ0
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 114/130
4/45
Moeller NK1210+2100+2300-1153GB-INT
M o t o r - p r o t e c t i v
e c i r c u i t - b r e a k e r s
P K Z M 0 1 ,
P K Z M 0
, P K Z M 4
DimensionsMotor-protective circuit-breakers PKZM4
Insulated enclosures for surface mounting
CI-K4-PKZ4-G(R)
CI-K4-PKZ4-G(R)ϩSVB-PKZ4-CI
Drilling dimensionsCI-K4-PKZ4-G(R)
160
2 4 0
134
181
197
32
98
SVB-PKZ4-CI
7 2
3
160 186 28
30
2 4 0
2 4 0
1 9 3
142
o 5.6
7 2
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 115/130
Moeller NK1210+2100+2300-1153GB-INT
P K Z M 0 1 , P K Z M 0
, P K Z M 4
4/46 DimensionsMotor-protective circuit-breakers PKZM4
Three-phase commoning linkB3.0/4-PKZ4
Three-phase commoning linkB3.2/4-PKZ4
B3.0/3-PKZ4 B3.2/2-PKZ4
B3.0/2-PKZ4
Three-phase commoning linkB3.1/4-PKZ4
B3.1/3-PKZ4
B3.1/2-PKZ4
1 4
205
3 6
33 33
1 4
260
3 6
1 4
151
3 6
33
1 4
115
3 6
33
1 4
98
3 6
33
33
1 4
232
3 6
33
1 4
170
3 6
33
1 4
117
3 6
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 116/130
5/1
Moeller NK1210+2100+2300-1153GB-INT
F u s e l e s s m o t o r - s t a r t e r c o m b i n a t i o n s
M S C - D ,
M S C - R
Contents
Conditions for fulfilling Type “1” coordination (IEC/EN 60947-4-1)
• The stated short-circuit current I q must be safely interrupted.• The starter must not endanger personnel or equipment in the event of
a short-circuit.• The starter does not have to be usable for continued use without repairs
or parts replacements.• Damage to the starter or its components is permissible.
Conditions for fulfilling Type “2” coordination (IEC/EN 60947-4-1)
• The stated short-circuit current I q must be safely interrupted.• The starter must not endanger personnel or equipment in the event of a
short-circuit.• The starter must be suitable for continued use.• No damage may occur to the starter – with the exception of
welding of the contactor contacts – provided they can be easily separated(e.g. with a screwdriver) without any significant deformation.
Page
Technical overview 5/2
DOL starters 5/2
Reversing starters 5/3
Direct-on-line starters 400/415 V 5/4
Complete device Type “1” coordination 5/4Complete device Type “2” coordination 5/6
Module Type “1” and Type “2” coordination 5/8
Module Type “1” coordination 5/10
Reversing starter 400/415 V 5/12
Complete device Type “1” coordination 5/12
Complete device Type “2” coordination 5/14
Module Type “1” and Type “2” coordination 5/16
Technical data 5/18
Dimensions 5/18
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 117/130
Moeller NK1210+2100+2300-1153GB-INT
M S C - D , M S C - R
5/2 Technical overviewDOL starters
DOL starters
Complete units Modules Modules Modules
PKZM0 and DILM PKZM0 and DILM completeunits
PKZM4 and DILM PKM0, DILM and ZB
Coordination type “1” “2“ “1” “2“ “1” “2“ “1”
Voltage 400/415 V 400/415 V 400/415 V 400/415 V 400/415 V 400/415 V 400/415 V
Motor ratingP/kW
0.06 0.06 0.06 0.06 0.06
0.09 0.09 0.09 0.09 0.09
0.12 0.12 0.12 0.12 0.12
0.18 0.18 0.18 0.18 0.18
0.25 0.25 0.25 0.25 0.25
0.37 0.37 0.37 0.37 0.37
0.55 0.55 0.55 0.55 0.55
0.75 0.75 0.75 0.75 0.75
1.1 1.1 1.1 1.1 1.1
1.5 1.5 1.5 1.5 1.5
2.2 2.2 2.2 2.2 2.2
3 3 3 3 3
4 4 4 4 4
5.5 5.5 5.5 5.5 5.5 5.5 5.5
7.5 7.5 7.5 7.5 7.5 7.5 7.5
11 11 11 11 11 11 11
15 15 15 15 15 15 15
18.5 18.5
22 22
30 30
34 34
Page a 5/4 a 5/8 a 5/8 a 5/10
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 118/130
5/3
Moeller NK1210+2100+2300-1153GB-INT
F u s e l e s s m o t o r - s t a r t e r c o m b i n a t i o n s
M S C - D ,
M S C - R
Technical overviewReversing starters
Reversing starters
Complete units Modules Modules
PKZM0 and DILM complete units PKZM0 and DILM complete units PKZM4 and DILM
Coordination type “1” “2“ “1” “2“ “1” “2“
Voltage 400/415 V 400/415 V 400/415 V 400/415 V 400/415 V 400/415 V
Motor ratingP/kW
0.06 0.06 0.06 0.06
0.09 0.09 0.09 0.09
0.12 0.12 0.12 0.12
0.18 0.18 0.18 0.18
0.25 0.25 0.25 0.25
0.37 0.37 0.37 0.37
0.55 0.55 0.55 0.55
0.75 0.75 0.75 0.75
1.1 1.1 1.1 1.1
1.5 1.5 1.5 1.5
2.2 2.2 2.2 2.2
3 3 3 3
4 4 4 4
5.5 5.5 5.5 5.5 5.5 5.5
7.5 7.5 7.5 7.5 7.5 7.5
11 11 11 11 11 11
15 15 15 15 15 15
18.5 18.5
22 22
30 30
34 34
Page a 5/12 a 5/16 a 5/16
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 119/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 120/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 121/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 122/130
Moeller NK1210+2100+2300-1153GB-INT
5/10
Moeller NK1210+2100+2300-1153GB-INT
DOL starters 400/415 V Modules Type “1” coordination
Motor ratings Setting range Base unitPart no.
ContactorPart no.
OverloPart nMotor rating Rated operational
current 400 VRated short-circuitcurrent 380 – 415 V
Overload releases Short-circuit releases
AC-3
380 V400 V415 V
P I e I q I r I rm
kW A kA A A
Modules PKM0, DILM and ZB with/without automatic reset
0.06 0.21 100 0.16 – 0.24 3.5 PKM0-0,25 DILM7-.. .(... ) ZB12-0
0.09 0.31 100 0.24 – 0.4 5.6 PKM0-0,4 DILM7-...(...) ZB12-0
0.12 0.41 100 0.4 – 0.6 8.82 PKM0-0,63 DILM7-...(...) ZB12-0
0.18 0.6 100 0.4 – 0.6 8.82 PKM0-0,63 DILM7-...(...) ZB12-0
0.25 0.8 100 0.6 – 1 14 PKM0-1 DILM7-...(...) ZB12-1
0.37 1.1 100 0.1 – 1.6 22.4 PKM0-1,6 DILM7-...(...) ZB12-1
0.55 1.5 100 0.1 – 1.6 22.4 PKM0-1,6 DILM7-...(...) ZB12-1
0.75 1.9 100 1.6 – 2.4 35 PKM0-2,5 DILM7-...(...) ZB12-2
1.1 2.6 100 2.4 – 4 56 PKM0-4 DILM7-...(...) ZB12-4
1.5 3.6 100 2.4 – 4 56 PKM0-4 DILM7-...(...) ZB12-4
2.2 5 100 4 – 6 88.2 PKM0-6,3 DILM7-...(...) ZB12-6
3 6.6 100 6 – 10 140 PKM0-10 DILM9-...(...) ZB12-1
4 8.5 100 6 – 10 140 PKM0-10 DILM9-...(...) ZB12-1
5.5 11.3 50 8 – 12 168 PKM0-12 DILM12-...(...) ZB12-1
7.5 15.2 50 10 – 16 224 PKM0-16 DILM17-...(...) ZB32-1
11 21.7 50 16 – 24 350 PKM0-25 DILM25-...(...) ZB32-2
15 29.3 50 20 – 32 448 PKM0-32 DILM32-...(...) ZB32-3
M
3 ~
I >
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 123/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 124/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 125/130
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 126/130
Moeller NK1210+2100+2300-1153GB-INT
M S C - D , M S C - R
5/18 Technical data, dimensions
General
Standards IEC/EN 60947-4-1, VDE 0660
UL 508CSA C 22.2 No. 14 on request
Mounting position
Main contacts
Rated impulse withstand voltage U imp V 6000
Overvoltage category/pollution degree
III/3
Rated operational voltage Ue V 230 – 415
Further technical data
PKZM0 motor-protective circuit-breakers a 4/34
DILM contactor a 2/48
DILET, ETR4 timing relay a Main catalogue for industrial switchgear
9 0 º
9 0 º
DOL starters
MSC-D-...-M7(...15) MSC-D-...-M17(...32)
Reversing starters
MSC-R-...-M7(...12) MSC-R-...-M17(...32)
95 45
67
6
4 6
1 8 0
45
1 8 0
97.4
67
6
4 6
95 90
67
6
4 6
1 1 4
1 8 0
90
1 8 0
97.4
67
6
4 6
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 127/130
6/1
Moeller NK1210+2100+2300-1153GB-INT
P a r t n u m b e r l i s t
,
A l p h a b e t i c a l i n d
e x
Type Device Page Type Device Page
Part number list
AA-PKZ0... Shunt release 4/15
AK-PKZ0 Lockable rotary handle 4/21
AWB... Manuals 3/6, 4/21
BB3...-PKZ0 Three-phase commoning links PKZ0 4/26
B3...-PKZ0-U Three-phase commoning links PKZ0 4/27
B3...-PKZ4 Three-phase commoning links PKZ4 4/28
BBA... Busbar adapter 4/22
BK25/3-PKZ0 Incoming terminal 4/26
BK25/3-PKZ-U Incoming terminal 4/27
C
CI.. .PKZ0(1)(4).. . Insulated enclosure 4/18
D
DILA(C)... Contactor relays 1/3
DILA...XHI... Auxiliary contact modules 1/4, 2/12DILK... Contactors for capacitors 2/16
DILM(C)... Contactors 2/9
DILM...-... Complete units 2/11
DILMP20... Contactors 2/7
DILM...XDSB Three-phase commoning links 2/25
DILM...XHI... Auxiliary contact modules 2/12
DILM...XMV Mechanical interlock 1/6, 2/23
DILM...XP1 Paralleling link 2/24
DILM...XRL Reversing starter wiring kits 2/24
DILM...XSP... Suppressor circuits 1/6, 2/22, 26
DILM...XS1 Star-point bridge 2/24
DILM...XSL Star-delta wiring kits 2/24
DILM...XTE Electronic timer modules 1/7, 2/25
DILM...XTEPLH Sealing flap 1/7
DILM...XVB Spacer 1/6, 2/23
DIULM... Reversing contactors 2/20
E
E-PKZ0 Insulated enclosures 4/19
E-PKZ01 Insulated enclosures 4/19
ETS4-VS3 Amplifier modules 1/8
H
H-B3-PKZ0-U Shroud for unused terminals 4/27
H-B3-PKZ0 Shroud for unused terminals 4/26
H-B3-PKZ4 Shroud for unused terminals 4/28
H-PKZ0 Door coupling handle 4/20
HB-PKZ4 Terminal shroud 4/20
LL-PKZ0-... Indicator light 4/21
M
MSC-D... Direct-on-line starter 5/4
MSC-R... Reversing starter 5/12
N
NDIL...M 4th pole 2/25
NHI...-PKZ0 Standard auxiliary contact 4/13
N-PKZ0 N-terminal 4/19
P
PKM0... Motor-protective circuit-breakersfor starter combinations 4/10
PKZM01... Motor-protective circuit-breakers 4/6
PKZM0-... Motor-protective circuit-breakers 4/8, 24
PKZM0(4)-XC... Top-hat rail adapter plate 4/25
PKZM0(4)-XM... Electric contact module 4/24PKZM0-XDM... Wiring set for direct-on-line starters 4/24
PKZM0-XRM.. . Wiring set for revers ing starters 4/24
PKZM0-XSM... Wiring set for star-delta starters 4/24
PKZM4-... Motor-protective circuit-breakers 4/8, 24
R
RH-PKZ0 Door coupling handle 4/20
S
SDAINLM... Star-delta contactors 2/18
SVB-PKZ0-... Padlocking feature 4/19
U
U-PKZ0 Undervoltage release 4/15
Z
ZB... Overload relays 3/3
ZB...-XEZ Bases for ZB32(65) 3/6
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 128/130
Moeller NK1210+2100+2300-1153GB-INT
A l p h a b e t i c a l i n d
e x
6/2 Alphabetical index
A
Amplifier module 1/8
Auxiliary contact modules 1/4, 2/12
Auxiliary contact modules 2/12
BBases for ZB32(65) 3/6
Busbar adapter 4/22
C
Complete units 2/11
Contactor relays 1/3
Contactors 2/9, 2/7
Contactors for capacitors 2/16
D
DOL starters 5/4
Door coupling handle 4/20 , 4/20
E
Electric contact module 4/24
Electronic timer modules 1/7, 2/25
I
Incoming terminals 4/26, 4/27
Indicator lights 4/21
Insulated enclosure 4/18
Insulated enclosure 4/19 , 4/19
L
Lockable rotary handle 4/21
M
Manuals 3/6, 4/21
Mechanical interlock 1/6, 2/23
Motor-protective circuit-breakers 4/8, 24, 4/8, 24
Motor-protective circuit-breakers 4/6
Motor-protective circuit-breakers for starter combinations 4/10
NN-terminal 4/19
O
Overload relays 3/3
P
Padlocking feature 4/19
Paralleling link 2/24
R
Reversing contactors 2/20
Reversing starter wiring kits 2/24
Reversing starters 5/12 V
S
Sealing flap 1/7
Shroud for unused terminals 4/27, 4/26, 4/28
Shunt release 4/15Spacer 1/6, 2/23
Standard auxiliary contact 4/13
Star-delta contactors 2/18
Star-delta wiring kits 2/24
Star-point bridge 2/24
Suppressor circuits 1/6, 2/22, 26
T
Terminal shroud 4/20
Three-phase commoning links 2/25
Three-phase commoning links PKZ0 4/26 , 4/27
Three-phase commoning links PKZ4 4/28
Top-hat rail adapter plate 4/25
U
Undervoltage releases 4/15
W
Wiring set for direct-on-line starters 4/24
Wiring set for reversing starters 4/24
Wiring set for star-delta starters 4/24
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 129/130
Minimum fuse size for the protection of three-phase motorsThe maximum size is governed by the requirements of the associated switchgear or overload relay
Motor rating 230 V 400 V 500 V 690 V
Ratedmotorcurrent
Fuse
Startingdirect Y/∆
Ratedmotorcurrent
Fuse
Startingdirect Y/∆
Ratedmotorcurrent
Fuse
Startingdirect Y/∆
Ratedmotorcurrent
Fuse
Startingdirect Y/∆
kW cos ϕ η (%) A A A A A A A A A A A A
0.06 0.7 58 0.37 2 – 0.21 2 – 0.17 2 – 0.12 2 –
0.09 0.7 60 0.54 2 – 0.31 2 – 0.25 2 – 0.18 2 –
0.12 0.7 60 0.72 4 2 0.41 2 – 0.33 2 – 0.24 2 –
0.18 0.7 62 1.04 4 2 0.6 2 – 0.48 2 – 0.35 2 –
0.25 0.7 62 1.4 4 2 0.8 4 2 0.7 2 – 0.5 2 –
0.37 0.72 66 2 6 4 1.1 4 2 0.9 2 2 0.7 2 –0.55 0.75 69 2.7 10 4 1.5 4 2 1.2 4 2 0.9 4 2
0.75 0.79 74 3.2 10 4 1.9 6 4 1.5 4 2 1.1 4 2
1.1 0.81 74 4.6 10 6 2.6 6 4 2.1 6 4 1.5 4 2
1.5 0.81 74 6.3 16 10 3.6 6 4 2.9 6 4 2.1 6 4
2.2 0.81 78 8.7 20 10 5 10 6 4 10 4 2.9 10 4
3 0.82 80 11.5 25 16 6.6 16 10 5.3 16 6 3.8 10 4
4 0.82 83 14.8 32 16 8.5 20 10 6.8 16 10 4.9 16 6
5.5 0.82 86 19.6 32 25 11.3 25 16 9 20 16 6.5 16 10
7.5 0.82 87 26.4 50 32 15.2 32 16 12.1 25 16 8.8 20 10
11 0.84 87 38 80 40 21.7 40 25 17.4 32 20 12.6 25 16
15 0.84 88 51 100 63 29.3 63 32 23.4 50 25 17 32 20
18.5 0.84 88 63 125 80 36 63 40 28.9 50 32 20.9 32 25
22 0.84 92 71 125 80 41 80 50 33 63 32 23.8 50 25
30 0.85 92 96 200 100 55 100 63 44 80 50 32 63 32
37 0.86 92 117 200 125 68 125 80 54 100 63 39 80 50
45 0.86 93 141 250 160 81 160 100 65 125 80 47 80 63
55 0.86 93 173 250 200 99 200 125 79 160 80 58 100 63
75 0.86 94 233 315 250 134 200 160 107 200 125 78 160 100
90 0.86 94 279 400 315 161 250 200 129 200 160 93 160 100
110 0.86 94 342 500 400 196 315 200 157 250 160 114 200 125
132 0.87 95 401 630 500 231 400 250 184 250 200 134 250 160160 0.87 95 486 630 630 279 400 315 224 315 250 162 250 200
200 0.87 95 607 800 630 349 500 400 279 400 315 202 315 250
250 0.87 95 – – – 437 630 500 349 500 400 253 400 315
315 0.87 96 – – – 544 800 630 436 630 500 316 500 400
400 0.88 96 – – – 683 1000 800 547 800 630 396 630 400
450 0.88 96 – – – 769 1000 800 615 800 630 446 630 630
500 0.88 97 – – – – – – – – – 491 630 630
560 0.88 97 – – – – – – – – – 550 800 630
630 0.88 97 – – – – – – – – – 618 800 630
Notes The rated motor currents apply to normal, internally-ventilated andenclosed fan-cooled three-phase motors at 1500 rpm.D.O.L. starting: Maximum starting current 6× rated motor current.
Maximum starting time 5 seconds.Y/∆starting: Maximum starting current 2 × rated motor current.
Maximum starting time 15 seconds.Set the overload relay in the phase leadto 0.58 × rated motor current.
Rated fuse currents for Y/∆ starting also apply to three-phasemotors with slip-ring rotors.Use a larger fuse if the rated current or starting current is higherand/or if the starting time is longer.The table applies to “slow” or “gL” fuses (VDE 0636)
LV h.b.c. fuses with aM characteristics,select fuse size to match rated current.
Technical DataRated currents of three-phase motors (guidelines for squirrel-cage motors)
8/22/2019 U1_GB-INT
http://slidepdf.com/reader/full/u1gb-int 130/130
Moeller addresses worldwide:www.moeller.net/address
E-Mail: [email protected]: www.moeller.net
Issued by Moeller GmbH
Hein-Moeller-Str. 7-11
D-53115 Bonn
© 2005 by Moeller GmbH
Subject to alterations
NK1210+2100+2300-1153GB-INT MDS/Doku/DFS 09 /05
Printed in the Federal Republic of Germany (02 /06)
Article No.: 104731
Xtra Combinations
Xtra Combinations from Moeller offers a range of products
and services, enabling the best possible combination options
for switching, protection and control in power distribution
and automation.
Using Xtra Combinations enables you to find more efficient
solutions for your tasks while optimising the economic
viability of your machines and systems.
It provides: