+ All Categories
Home > Documents > UK Cables – the only way to be sure! · A 450/750 Volt industrial fi xed wiring cable with Low...

UK Cables – the only way to be sure! · A 450/750 Volt industrial fi xed wiring cable with Low...

Date post: 22-Sep-2018
Category:
Upload: ngodan
View: 216 times
Download: 0 times
Share this document with a friend
3
UK Cables the only way to be sure! www.ukcables.co.uk Aberdeen Birmingham Glasgow Gateshead Manchester London T: 01224 898114 T: 0121 565 7040 T: 0141 779 7804 T: 0191 487 2000 T: 0161 653 6789 T: 01708 86446 F: 01224 898900 F: 0121 565 7050 F: 0141 779 7801 F: 0191 487 2022 F: 0161 653 7184 F: 01708 865385 [email protected] [email protected] [email protected] [email protected] [email protected] [email protected] Cores x mm 2 Nom OD mm Weight kg / km 1.5 3.0 22 2.5 3.6 34 4.0 4.1 50 6.0 4.7 70 10.0 5.8 114 16.0 6.8 175 25.0 8.6 272 35.0 10.2 377 50.0 11.9 510 70.0 12.8 698 95.0 15.0 960 120.0 16.6 1205 150.0 16.6 1510 185.0 20.8 1855 240.0 25.4 2450 300.0 28.1 3030 400.0 31.6 3898 500.0 35.2 4894 630.0 39.1 6244 LSOH 6491B DIMENSIONS A 450/750 Volt industrial fixed wiring cable with Low Smoke Zero Halogen (LSOH) insulation, for use in conduit or trunking. May also be used inside fixed protected installations such as light fittings, appliances and switchgear. LSOH cables are installed where smoke and acid gas emission in the event of a fire would pose a hazard to the public. CONSTRUCTION Single core plain copper conductor solid or stranded, LSOH cross linked polyethylene (XLPE) 90 degree compound insulated only. Insulation colours Brown, Blue, Black, Green/Yellow, Grey. TECHNICAL DATA BS EN 50525-3-41 H07Z-R Nominal Voltage 450/750V Test Voltage 3000V Operating Temperature -15ºC to +90ºC Bending Radius 10mm 2 3 times O/D 10mm 2 - 25mm 2 4 times O/D 25mm 2 + 5 times O/D Flame Propagation BS EN 60332-1-2 Smoke Density BS EN 61034-2 Halogen Emission BS EN 60754-2 Current Rating Table 4E1A & 4E1B Note - Minimum installation temperature 5 º C When installed in an earthed metal enclosure, cables are suitable for voltages up to 1000V A.C or up to 750V to earth D.C When a conductor operates at a temperature above 70ºC it should be ascertained that the equipment is suitable. CONDUIT WIRING CABLE LSOH 6491B
Transcript
Page 1: UK Cables – the only way to be sure! · A 450/750 Volt industrial fi xed wiring cable with Low Smoke Zero Halogen (LSOH) insulation, for use in conduit or trunking. May also ...

UK Cables – the only way to be sure!

www.ukcables.co.uk

Aberdeen Birmingham Glasgow Gateshead Manchester London

T: 01224 898114 T: 0121 565 7040 T: 0141 779 7804 T: 0191 487 2000 T: 0161 653 6789 T: 01708 86446

F: 01224 898900 F: 0121 565 7050 F: 0141 779 7801 F: 0191 487 2022 F: 0161 653 7184 F: 01708 865385

[email protected] [email protected] [email protected] [email protected] [email protected] [email protected]

Cores x mm2

Nom ODmm

Weight kg / km

1.5 3.0 222.5 3.6 344.0 4.1 506.0 4.7 70

10.0 5.8 11416.0 6.8 17525.0 8.6 27235.0 10.2 37750.0 11.9 51070.0 12.8 69895.0 15.0 960

120.0 16.6 1205150.0 16.6 1510185.0 20.8 1855240.0 25.4 2450300.0 28.1 3030400.0 31.6 3898500.0 35.2 4894630.0 39.1 6244

LSOH 6491B DIMENSIONS

A 450/750 Volt industrial fi xed wiring cable with Low Smoke Zero Halogen (LSOH) insulation, for use in conduit or trunking. May also be used inside fi xed protected installations such as light fi ttings, appliances and switchgear. LSOH cables are installed where smoke and acid gas emission in the event of a fi re would pose a hazard to the public.

CONSTRUCTION

Single core plain copper conductor solid or stranded, LSOH cross linked polyethylene (XLPE) 90 degree compound insulated only. Insulation colours Brown, Blue, Black, Green/Yellow, Grey.

TECHNICAL DATA

BS EN 50525-3-41 H07Z-R

Nominal Voltage 450/750V

Test Voltage 3000V

Operating Temperature -15ºC to +90ºC

Bending Radius≤10mm2 3 times O/D10mm2 - 25mm2 4 times O/D25mm2+ 5 times O/D

Flame Propagation BS EN 60332-1-2

Smoke Density BS EN 61034-2

Halogen Emission BS EN 60754-2

Current Rating Table 4E1A & 4E1B

Note - Minimum installation temperature 5ºC

When installed in an earthed metal enclosure, cables are suitable for voltages up to 1000V A.C or up to 750V to earth D.C

When a conductor operates at a temperature above 70ºC it should be ascertained that the equipment is suitable.

CONDUIT WIRING CABLE LSOH 6491B

Page 2: UK Cables – the only way to be sure! · A 450/750 Volt industrial fi xed wiring cable with Low Smoke Zero Halogen (LSOH) insulation, for use in conduit or trunking. May also ...

UK Cables – the only way to be sure!

www.ukcables.co.uk

Aberdeen Birmingham Glasgow Gateshead Manchester London

T: 01224 898114 T: 0121 565 7040 T: 0141 779 7804 T: 0191 487 2000 T: 0161 653 6789 T: 01708 86446

F: 01224 898900 F: 0121 565 7050 F: 0141 779 7801 F: 0191 487 2022 F: 0161 653 7184 F: 01708 865385

[email protected] [email protected] [email protected] [email protected] [email protected] [email protected]

Current Rating Table

Table 4E1ASingle core cables having thermosetting 90º insulator, non armoured with or without sheath (copper conductors)

CURRENT-CARRYING CAPACITY (amperes): Ambient temperature : 30°C Conductor operating temperature:90°C

Permission to reproduce extracts from BS 7671:2008+A1:2011 is granted by the British Standards Institution (BSI) and the Institution of Engineering and Technology (IET). No other use of this material is permitted. BS 7671:2008 Incorporating Amendment No 1: 2011 can be purchased from the IET website http://electrical.theiet.org/ and the BSI online shop: http://shop.bsigroup.com

Conductorcross-sectional area

Reference Method 100# (above a plaster-board ceiling covered by thermal insulation not exceeding 100mm in thickness)

Reference Method 101# (above a plasterboard ceiling covered by thermal insulation exceeding 100mm in thickness)

Reference Method 102# (in a stud wall with thermal insulation with cable touching the inner wall surface)

Reference Method 103#(in a stud wall with thermal insulation with cable not touching the inner wall surface)

Reference Method A*(enclosed in conduit in an insulated wall)

2 cablessinglephasea.c or d.c.

3 or 4cablesthreephase a.c..

2 cablessinglephasea.c or d.c

3 or 4cablesthreephase a.c.

2 cablessinglephasea.c. or d.c. fl at andtouching

3 or 4cablesthreephase a.c.fl at andtouchingor trefoil

2 cablessinglephasea.c. or d.c. fl at

3 cablesthreephase a.c. fl at

3 cablesthreephasea.c. trefoil

2 cables single phasea.c. or d.c.or 3 cablesthree phase a.c. fl at

Horizontal Vertical

1 2 3 4 5 6 7 8 9 10 11 12

(mm²) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)1 14 13 17 15 19 17.5 - - - - -

1.5 19 17 23 19 25 23 - - - - -2.5 26 23 31 26 34 31 - - - - -4 35 31 42 35 46 41 - - - - -6 45 40 54 45 59 54 - - - - -

10 61 54 75 63 81 74 - - - - -16 81 73 100 85 109 99 - - - - -25 106 95 133 111 143 130 161 141 135 182 16135 131 117 164 138 176 161 200 176 169 226 20150 158 141 198 168 228 209 242 216 207 275 24670 200 179 253 214 293 268 310 279 268 353 31895 241 216 306 259 355 326 377 342 328 430 389

120 278 249 354 299 413 379 437 400 383 500 454150 318 285 393 328 476 436 504 464 444 577 527185 362 324 449 370 545 500 575 533 510 661 605240 424 380 500 433 644 590 679 634 607 781 719300 486 435 573 493 743 681 783 736 703 902 833400 - - 683 584 868 793 940 868 823 1085 1008500 - - 783 666 990 904 1083 998 946 1253 1169630 - - 900 764 1130 1033 1254 1151 1088 1454 1362800 - - - - 1288 1179 1358 1275 1214 1581 1485

1000 - - - - 1443 1323 1520 1436 1349 1775 1671

NOTES:1. Where a conductor operates at a temperature exceeding 70°C it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see Regulation 512.1.2)

2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70°C, the current ratings given in the equivalent table for 70°C thermoplastic insulated cables (Table 4D1A) must be used (see Reg 523.1)

Page 3: UK Cables – the only way to be sure! · A 450/750 Volt industrial fi xed wiring cable with Low Smoke Zero Halogen (LSOH) insulation, for use in conduit or trunking. May also ...

UK Cables – the only way to be sure!

www.ukcables.co.uk

Aberdeen Birmingham Glasgow Gateshead Manchester London

T: 01224 898114 T: 0121 565 7040 T: 0141 779 7804 T: 0191 487 2000 T: 0161 653 6789 T: 01708 86446

F: 01224 898900 F: 0121 565 7050 F: 0141 779 7801 F: 0191 487 2022 F: 0161 653 7184 F: 01708 865385

[email protected] [email protected] [email protected] [email protected] [email protected] [email protected]

Current Rating Table

Table 4E1B

CURRENT-CARRYING CAPACITY (amperes): Conductor operating temperature:90°C

Permission to reproduce extracts from BS 7671:2008+A1:2011 is granted by the British Standards Institution (BSI) and the Institution of Engineering and Technology (IET). No other use of this material is permitted. BS 7671:2008 Incorporating Amendment No 1: 2011 can be purchased from the IET website http://electrical.theiet.org/ and the BSI online shop: http://shop.bsigroup.com

*spacings larger than one cable diameter will result in a larger voltage drop

Con-ductorCross-Sec-tionalarea

2cablesd.c

2 cables, single phase a.c. 3 or 4 cables, three-phase a.c.

Reference MethodsA & B (enclosed inconduit or trunking)

Reference Methods C, F & G(clipped direct, on tray or in free air)

Reference MethodsA & B (enclosed inconduit or trunking)

Reference Methods C, F & G(clipped direct, on tray or in free air)

cables touching cables spaced* cables touching,trefoil

cables touching,fl at

cables spaced*fl at

1 2 3 4 5 6 7 8 9

(mm²)(mV/A/m)

(mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m)

1 46 46 46 46 40 40 40 40

1.5 31 31 31 31 27 27 27 27

2.5 19 19 19 19 16 16 16 16

4 12 12 12 12 10 10 10 10

6 7.9 7.9 7.9 7.9 6.8 6.8 6.8 6.8

10 4.7 4.7 4.7 4.7 4.0 4.0 4.0 4.0

16 2.9 2.9 2.9 2.9 2.5 2.5 2.5 2.5

r x z r x z r x z r x z r x z r x z r x z

25 1.85 1.85 0.31 1.90 1.85 0.190 1.85 1.85 0.28 1.85 1.60 0.27 1.65 1.60 0.165 1.60 1.60 0.190 1.60 1.60 0.27 1.65

35 1.35 1.35 0.29 1.35 1.35 0.180 1.35 1.35 0.27 1.35 1.15 0.25 1.15 1.15 0.155 1.15 1.15 0.180 1.15 1.15 0.26 1.20

50 0.99 1.00 0.29 1.05 0.99 0.180 1.00 0.99 0.27 1.00 0.87 0.25 0.90 0.86 0.155 0.87 0.86 0.180 0.87 0.86 0.26 0.89

70 0.68 0.70 0.28 0.75 0.68 0.175 0.71 0.68 0.26 0.73 0.60 0.24 0.65 0.59 0.150 0.61 0.59 0.175 0.62 0.59 0.25 0.65

95 0.49 0.51 0.27 0.58 0.49 0.170 0.52 0.49 0.26 0.56 0.44 0.23 0.50 0.43 0.145 0.45 0.43 0.170 0.46 0.43 0.25 0.49

120 0.39 0.41 0.26 0.48 0.39 0.165 0.43 0.39 0.25 0.47 0.35 0.23 0.42 0.34 0.140 0.37 0.34 0.165 0.38 0.34 0.24 0.42

150 0.32 0.33 0.26 0.43 0.32 0.165 0.36 0.32 0.25 0.41 0.29 0.23 0.37 0.28 0.140 0.31 0.28 0.165 0.32 0.28 0.24 0.37

185 0.25 0.27 0.26 0.37 0.26 0.165 0.30 0.25 0.25 0.36 0.23 0.23 0.32 0.22 0.140 0.26 0.22 0.165 0.28 0.22 0.24 0.33

240 0.190 0.21 0.26 0.33 0.20 0.160 0.25 0.195 0.25 0.31 0.185 0.22 0.29 0.170 0.140 0.22 0.170 0.165 0.24 0.170 0.24 0.29

300 0.155 0.175 0.25 0.31 0.160 0.160 0.22 0.155 0.25 0.29 0.150 0.22 0.27 0.140 0.140 0.195 0.135 0.160 0.21 0.135 0.24 0.27

400 0.120 0.140 0.25 0.29 0.130 0.155 0.20 0.125 0.24 0.27 0.125 0.22 0.25 0.110 0.135 0.175 0.110 0.160 0.195 0.110 0.24 0.26

500 0.093 0.120 0.25 0.28 0.105 0.155 0.185 0.098 0.24 0.26 0.100 0.22 0.24 0.090 0.135 0.160 0.088 0.160 0.180 0.085 0.24 0.25

630 0.072 0.100 0.25 0.27 0.086 0.155 0.175 0.078 0.24 0.25 0.088 0.21 0.23 0.074 0.135 0.150 0.171 0.160 0.170 0.068 0.23 0.24

800 0.056 0.072 0.150 0.170 0.064 0.24 0.25 0.062 0.130 0.145 0.059 0.155 0.165 0.055 0.23 0.24

1000 0.045 0.063 0.150 0.165 0.054 0.24 0.24 0.055 0.130 0.140 0.050 0.155 0.165 0.047 0.23 0.24


Recommended