(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
UL LISTED ENCLOSURE AIR CONDITIONERS
FULLY INTEGRATED CONDENSATE EVAPORATION PACKAGE
PROGRAMMABLE DIGITAL CONTROLLER
THERMAL EXPANSION VALVE
NARROW DESIGN TO FIT ONTO A 12” ENCLOSURE
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
THERMAL EDGE ENCLOSURE AIR CONDITIONER’S FEATURES AND BENEFITS
DRIP-FREE CONDENSATE REMOVAL IS NOT OPTIONAL
Liquid Condensate is the by-product of every air conditioner. At Thermal Edge
we understand that a puddle next to your sensitive electronic enclosure may not be ideal. We eliminate this messy problem by changing the troublesome liquid
back into a vapor and venting it out of your way. That means no puddles,
stains or mess near your electrical enclosure, control system or production line. In addition, our condensate evaporation system precools the refrigerant which
lowers the running amps and thus lowers your energy usage.
CONDENSATE EVAPORATION IS STANDARD ON EVERY UNIT With Thermal Edge Units...NO DRAIN TUBE IS NEEDED .
THERMAL EXPANSION VALVE CONTROLS THE FLOW
All phase change refrigerant systems require an expansion device which controls
the flow of refrigerant in the evaporator. Two principal types of control are used: Thermal Expansion Valves or Capillary Tubes.
Thermal Expansion Valves balance and modulate the refrigerant flow to the
heat load by sensing the temperature of the refrigerant leaving the evaporator.
There are three major advantages to this refrigerant control method.
1. Maximum efficiency over a wide temperature and load range. 2. Improved refrigerant return to the compressor assures better cooling at
high temperatures and reduces the possibility of liquid slugging which can destroy the compressor.
3. Variations in refrigerant charge, particularly smaller units, are less critical.
WITH THERMAL EDGE, YOU HAVE A SMARTER ENCLOSURE AIR CONDITIONER
Digital, programmable controller:
Fully programmable
Built in alarms and alerts
Will operate heating & cooling
Standard on every unit
Ethernet, Modbus RTU and Ethernet/IP communication options
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
All information subject to change without notice
ODEL BTU/HOUR VOLTAGE/ PHASE/
HZ.
RUNNING AMPS
MAXIMUM AMBIENT TEMP.
MAXIMUM INTEGRATED
HEAT IN WATTS H X W X D
SHIP WEIGHT
NE010126 1,000 120/1/60 2.69 125°F NA 22” x 11.8” x 8.5” 67
NE010236 1,000 230/1/60 1.99 125°F NA 22” x 11.8” x 8.5” 67
CS011D48 1,000 48 VDC 3.70 125°F NA 17” x 7” x 7” 43
CS011126 1,000 120/1/60 2.70 131°F 350 17” x 7” x 7” 43
NE015126 1,500 120/1/60 3.44 125°F NA 22” x 11.8” x 8.5” 67
NE015236 1,500 230/1/60 2.67 125°F NA 22” x 11.8” x 8.5” 67
NE020126 2,000 120/1/60 3.76 125°F 1000 32“ x 11.8“ x 9.5“ 111
NE020236 2,000 230/1/60 3.07 125°F 1000 32“ x 11.8“ x 9.5“ 116
NE020486 2,000 480/1/60 0.93 125°F 1000 38” x 11.8” x 9.5” 141
CS020126 2,000 120/1/60 3.36 131°F 500 20” x 10” x 10” 56
CS020236 2,000 230/1/60 2.00 131°F 500 20” x 10” x 10” 59
NE030126 3,000 120/1/60 5.15 125°F 1000 32” x 11.8“ x 9.5” 111
NE030236 3,000 230/1/60 3.07 125°F 1000 32” x 11.8“ x 9.5” 116
NE030486 3,000 480/1/60 1.51 125°F 1000 38” x 11.8” x 9.5” 141
NE040D48 4,000 48 VDC 22.3 131°F NA 35.27” x 11.8“ x 9.5” 120
NE040126 4,000 120/1/60 5.53 125°F 1000 32” x 11.8“ x 9.5” 111
NE040236 4,000 230/1/60 3.07 125°F 1000 32” x 11.8“ x 9.5” 116
NE040486 4,000 480/1/60 1.51 125°F 1000 38” x 11.8“ x 9.5” 141
NE050126 5,000 120/1/60 7.26 125°F 1000 36“ x 11.8“ x 15.1” 139
NE050236 5,000 230/1/60 3.76 125°F 1000 36“ x 11.8“ x 15.1” 140
NE050486 5,000 480/1/60 1.44 125°F 1000 44.63” x 11.8” x 15.1” 189
NE060126 6,000 120/1/60 7.83 125°F 1000 36“ x 11.8“ x 15.1” 139
NE060236 6,000 230/1/60 4.80 125°F 1000 36“ x 11.8“ x 15.1” 140
NE060486 6,000 480/1/60 1.80 125°F 1000 44.63” x 11.8” x 15.1” 189
NE080126 8,000 120/1/60 7.83 125°F 1000 36“ x 11.8“ x 15.1” 139
NE080236 8,000 230/1/60 4.80 125°F 1000 36“ x 11.8“ x 15.1” 140
NE080486 8,000 480/1/60 1.80 125°F 1000 44.63” x 11.8” x 15.1” 189
HC101126 10,000 120/1/60 19.4 131°F 1500 48” x 15.9” x 15.1” 183
HC101236 10,000 230/1/60 8.20 131°F 1500 48” x 15.9” x 15.1” 186
HC101486 10,000 480/1/60 3.93 131°F 1500 57.6” x 15.9” x 15.1” 244
HC121126 12,000 120/1/60 19.4 131°F 1500 48” x 15.9” x 15.1” 183
HC121236 12,000 230/1/60 8.20 131°F 1500 48” x 15.9” x 15.1” 186
HC121486 12,000 480/1/60 3.93 131°F 1500 57.6” x 15.9” x 15.1” 244
HC151236 15,000 230/1/60 11.3 131°F 1500 48” x 15.9” x 15.1” 191
HC151486 15,000 480/1/60 5.41 131°F 1500 57.6” x 15.9” x 15.1” 256
HC201236 20,000 230/1/60 15.3 131°F 1500 56.1” x 23” x 15” 226
HC201486 20,000 480/1/60 7.7 131°F 1500 65.7” x 23” x 15” 342
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Brochure #1
2016-02-22
The Legendary
Green Bay Packers Coach Vince Lombardi said:
“Winning is not a sometime
thing; it’s an all-the-time thing. You don’t win once in a while, you don’t do things right once in a while, you do them right
all the time. Winning is a habit. Unfortunately, so is losing.”
Condensate evaporation package
Fully programmable digital controller
Thermal expansion valve
Full product line available in NEMA Types 12, 4 & 4X
UL Listed under Standard 484, file number SA32252
On/off switch as mandated by UL Standard 484
Rigid chassis and seam welded shroud
Proudly manufactured in the U.S.A.
Inventory on Hand
Customer Service answer-
ing your calls
A website that is easy to
navigate AND solutions
that are easy to find
Equipment tested to
perform and built to last
Units designed with our
customer’s applications and
environments in mind
Systems engineered to
maintain lower running
amps and higher efficiency
Features and Accessories
designed to solve critical
applications as in Corrosive
or Hazardous Environments
NOTE: AIR CONDITIONERS ARE SHIPPED SEPARATELY FROM ENCLOSURES
S T A N D A R D O N E V E R Y T H E R M A L E D G E A I R C O N D I T I O N E R :
All information subject to change without notice
A I R C O N D I T I O N E R O P T I O N S :
Electrostatic Coil Coating to prevent corrosion caused by a salt or chemical laden
environment
Enclosure door kill switch
Integrated Heat Packages to provide total temperature control for your enclosure
not just from the heat of summer but from the cold of winter
Dry Contact Options to allow the use of alarms, lights and notifications
Remote monitoring options
External Heat Control to support use of an externally mounted heater in the
enclosure
Vibration Package allows for enclosure cooling on cranes, moving vehicles or
other difficult locations. These systems are available in two levels
2” Deep Extended Filter Media for applications like flour, cement or coal when a
standard filter will load too quickly
Remote Controller Option to place our digital controller inside the electrical enclo-
sure when the environment requires a more secure setting
The Universal Mounting Plate allows the mounting of the Thermal Edge Enclosure
Air Conditioner onto an enclosure that formerly held a different brand of air
conditioner.
UL Listed Hazardous Location option, Class 1, Div 2, Groups B, C, D
Contact Us Today for Your Cooling Solutions!! Phone: 1-888-580-0202
E-mail: [email protected]
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 12” enclosure Unit Efficiency
Temperature operated blower control reduces power inrush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity
over a broad ambient temperature range Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save
energy and increase compressor life
1000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available NE010
11.8” wide
Options: Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Packages
Remote Monitoring Options
Integrated Enclosure Heat System
Model BTU/
Hour Material
Voltage/
Hz.
Running
Amps
Max. Amb
Temperature
H x W x D
Weight (lbs.)
Unit / Ship
NE010-126-12 1000 Powder coated steel 120/1/60 2.69 125°F 22” x 11.8” x 8.5” 52 / 67
NE010-126-04 1000 Powder coated steel 120/1/60 2.69 125°F 22” x 11.8” x 8.5” 52 / 67
NE010-126-4X 1000 Stainless steel 120/1/60 2.69 125°F 22” x 11.8” x 8.5” 52 / 67
NE010-236-12 1000 Powder coated steel 230/1/60 1.99 125°F 22” x 11.8” x 8.5” 52 / 67
NE010-236-04 1000 Powder coated steel 230/1/60 1.99 125°F 22” x 11.8” x 8.5” 52 / 67
NE010-236-4X 1000 Stainless steel 230/1/60 1.99 125°F 22” x 11.8” x 8.5” 52 / 67
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2015-10-28
All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
UL File # SA32252
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like Telecom Outside Plant, Off-Grid Solar, Wind & other Battery Powered Electrical Cabinets.
Model BTU/H Material Volts Running Amps
Max. Ambient Temperature
H x W x D Weight (lbs.) Unit / Ship
CS011-D48-12 1000 Powder coated steel 48 VDC 3.7 125°F 17” x 7” x 7” 30 / 43
CS011-D48-04 1000 Powder coated steel 48 VDC 3.7 125°F 17” x 7” x 7” 30 / 43
CS011-D48-4X 1000 Stainless steel 48 VDC 3.7 125°F 17” x 7” x 7” 30 / 43
Digital Temperature Controller Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 7” enclosure Filter free design Unit Efficiency Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity
over a broad ambient temperature range Compressor Protection System High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor motor drive controller eliminates power
inrush, saves energy and increases compressor life
1,000 BTU/H 48 Volt DC Powered Air Conditioner Indoor/Outdoor, NEMA Types 12, 4 & 4X Available CS011-D48
Options: Dry Contact Alarm Remote Controller Open Door Kill Switch Corrosive Environment Package Remote Monitoring Options
THE CS011 USES A UNIQUE 3 COIL DESIGN PROVIDING HIGH CAPACITY COOLING WHILE UTILIZING AIR INTAKE FROM EITHER SIDE. DUAL INTAKE ALLOWS FOR MOUNTING ON A WALL MOUNTED ENCLOSURE ON THE RIGHT OR LEFT
SIDE OF YOUR ENCLOSURE.
7” wide
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2015-06-11
All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
UL File # SA32252
0
500
1000
1500
2000
2500
85 95 105 115 125
BTUH
Ambient Temperature (°F)
CS011D48
105
95
85
Return Air
Temperature
(°F)
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
Model BTU/H Material Volt./Hz. Running Amps
Max. Ambient Temperature
H x W x D Weight (lbs.) Unit / Ship
CS011-126-12 1000 Powder coated steel 120/1/60 2.7 131°F 17” x 7” x 7” 30 / 43
CS011-126-04 1000 Powder coated steel 120/1/60 2.7 131°F 17” x 7” x 7” 30 / 43
CS011-126-4X 1000 Stainless steel 120/1/60 2.7 131°F 17” x 7” x 7” 30 / 43
Digital Temperature Controller Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 8” enclosure Filter free design Unit Efficiency Temperature operated blower control reduces power
inrush and saves energy Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity
over a broad ambient temperature range Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save
energy and increase compressor life
1,000 BTU/H Indoor/Outdoor, NEMA Types 12, 4 & 4X Available CS011
Options: Dry Contact Alarm Capabilities Open Door Kill Switch Corrosive Environment Package Low Ambient Package Remote Monitoring Options Integrated Enclosure Heater System Redundant System
THE CS011 USES A UNIQUE 3 COIL DESIGN PROVIDING HIGH CAPACITY COOLING WHILE UTILIZING AIR INTAKE FROM EITHER SIDE. DUAL INPUT ALLOWS FOR MOUNTING ON A WALL MOUNTED ENCLOSURE ON THE RIGHT OR LEFT
SIDE OF YOUR ENCLOSURE.
7” wide
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2014-03-31
UL File # SA32252 All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
0
500
1000
1500
2000
2500
85 95 105 115 125 135
BTUH
Ambient Temperature (F)
CS011
105
95
85
Return air Temperature
( F)
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 12” enclosure Unit Efficiency
Temperature operated blower control reduces power inrush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity
over a broad ambient temperature range Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save
energy and increase compressor life
1500 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available NE015
11.8” wide
Options: Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Packages
Remote Monitoring Options
Model BTU/
Hour
Voltage/
Hz.
Running
Amps
Max. Ambient
Temperature
Weight (lbs.)
Unit / Ship
H x W x D
Material
NE015-126-12 1500 120/1/60 3.44 125°F 52 / 67 22” x 11.8” x 8.5” Powder coated steel
NE015-126-04 1500 Powder coated steel 120/1/60 3.44 125°F 22” x 11.8” x 8.5” 52 / 67
NE015-126-4X 1500 Stainless steel 120/1/60 3.44 125°F 22” x 11.8” x 8.5” 52 / 67
NE015-236-12 1500 230/1/60 2.67 125°F 52 / 67 22” x 11.8” x 8.5” Powder coated steel
NE015-236-04 1500 Powder coated steel 230/1/60 2.67 125°F 22” x 11.8” x 8.5” 52 / 67
NE015-236-4X 1500 Stainless steel 230/1/60 2.67 125°F 22” x 11.8” x 8.5” 52 / 67
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2015-10-28
All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
UL File # SA32252
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 12” enclosure Unit Efficiency
Temperature operated blower control reduces power inrush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity
over a broad ambient temperature range Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save
energy and increase compressor life
2000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available NE020
Options: Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Packages
Remote Monitoring Options
Integrated Enclosure Heat System
Hazardous Location Units
Redundant Systems
11.8” wide
Model BTU/H Material Volt./Hz. Running
Amps
Max. Ambi-
ent Temper-ature
H x W x D
Weight
(lbs.)Unit / Ship
NE020-126-12 2000 Powder coated steel 120/1/60 3.76 125°F 32” x 11.8” x 9.5” 94 / 111
NE020-126-04 2000 Powder coated steel 120/1/60 3.76 125°F 32” x 11.8” x 9.5” 94 / 111
NE020-126-4X 2000 Stainless steel 120/1/60 3.76 125°F 32” x 11.8” x 9.5” 94 / 111
NE020-236-12 2000 Powder coated steel 230/1/60 3.07 125°F 32” x 11.8” x 9.5” 99 / 116
NE020-236-04 2000 Powder coated steel 230/1/60 3.07 125°F 32” x 11.8” x 9.5” 99 / 116
NE020-236-4X 2000 Stainless steel 230/1/60 3.07 125°F 32” x 11.8” x 9.5” 99 / 116
NE020-486-12 2000 Powder coated steel 480/1/60 0.93 125°F 38” x 11.8” x 9.5” 123 /141
NE020-486-04 2000 Powder coated steel 480/1/60 0.93 125°F 38” x 11.8” x 9.5” 123 / 141
NE020-486-4X 2000 Stainless steel 480/1/60 0.93 125°F 38” x 11.8” x 9.5” 123 / 141
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2013-10-30
UL File # SA32252 All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Management System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 10” enclosure Unit Efficiency
Pressure operated blower control reduces power inrush and saves energy
Highly efficient Rotary Compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity
over a broad ambient temperature range Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save
energy and increase compressor life
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
Model BTU/
Hour Material
Voltage/
Hz.
Running
Amps
Max.
Ambient Temp
H x W x D
Weight (lbs.)
Unit / Ship
CS020-126-12 2000 Powder coated steel 120V/1/60 3.36 131°F 20” x 10” x 10” 42 / 56
CS020-126-04 2000 Powder coated steel 120V/1/60 3.36 131°F 20” x 10” x 10” 42 / 56
CS020-126-4X 2000 304 Stainless 120V/1/60 3.36 131°F 20” x 10” x 10” 42 / 56
CS020-236-12 2000 Powder coated steel 230V/1/60 2.0 131°F 20” x 10” x 10” 45 / 59
CS020-236-04 2000 Powder coated steel 230V/1/60 2.0 131°F 20” x 10” x 10” 45 / 59
CS020-236-4X 2000 304 Stainless 230V/1/60 2.0 131°F 20” x 10” x 10” 45 / 59
Options: Dry Contact Alarm Capabilities Open Door Kill Switch Corrosive Environment Package Low Ambient Packages Remote Monitoring Options Integrated Enclosure Heater System
2000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available CS020
10” wide
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2015-01-15
UL File # SA32252 All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
0
500
1000
1500
2000
2500
3000
3500
4000
85 90 95 100 105 110 115 120 125 130
BTUH
Ambient Temperature
CS020
105
95
85
Evaporator Temperature
(°F)
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 12” enclosure Unit Efficiency
Temperature operated blower control reduces power inrush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity
over a broad ambient temperature range Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save
energy and increase compressor life
3000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available NE030
Options: Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Packages
Remote Monitoring Options
Integrated Enclosure Heat System
Hazardous Location Units
Redundant Systems
11.8” wide
Model BTU/H Material Volt./Hz. Running Max. Ambient H x W x D Weight (lbs.) Unit / Ship
NE030-126-12 3000 Powder coated steel 120/1/60 5.15 125°F 32” x 11.8” x 9.5” 94 / 111
NE030-126-04 3000 Powder coated steel 120/1/60 5.15 125°F 32” x 11.8” x 9.5” 94 / 111
NE030-126-4X 3000 Stainless steel 120/1/60 5.15 125°F 32” x 11.8” x 9.5” 94 / 111
NE030-236-12 3000 Powder coated steel 230/1/60 3.07 125°F 32” x 11.8” x 9.5” 99 / 116
NE030-236-04 3000 Powder coated steel 230/1/60 3.07 125°F 32” x 11.8” x 9.5” 99 / 116
NE030-236-4X 3000 Stainless steel 230/1/60 3.07 125°F 32” x 11.8” x 9.5” 99 / 116
NE030-486-12 3000 Powder coated steel 480/1/60 1.51 125°F 38” x 11.8” x 9.5” 123 / 141
NE030-486-04 3000 Powder coated steel 480/1/60 1.51 125°F 38” x 11.8” x 9.5” 123 / 141
NE030-486-4X 3000 Stainless steel 480/1/60 1.51 125°F 38” x 11.8” x 9.5” 123 / 141
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2013-10-30
UL File # SA32252 All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 12” enclosure Unit Efficiency
Highly efficient rotary compressor Temperature operated condenser blower control saves
energy Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity
over a broad ambient temperature range Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection
Compressor motor drive controller eliminates power inrush, saves energy and increases compressor life
4000 BTUH 48 VDC Powered Air Conditioner Indoor/Outdoor, NEMA Types 12, 4 & 4X Available NE040-D48
Options: Dry Contact Alarm
Remote Controller
Open Door Kill Switch
Corrosive Environment Packages
Remote Monitoring Options
Redundant Systems
Tamper Resistant Filters
11.8” wide
Model BTU/Hour
Material Voltage/
Hz. Running
Amps Maximum Ambient
H x W x D
Weight (lbs.) Unit / Ship
NE040-D48-12 4000 Powder coated steel 48 VDC 22.3 131°F 35.27” x 11.8” x 9.5” 103 / 120
NE040-D48-04 4000 Powder coated steel 48 VDC 22.3 131°F 35.27” x 11.8” x 9.5” 103 / 120
NE040-D48-4X 4000 Stainless steel 48 VDC 22.3 131°F 35.27” x 11.8” x 9.5” 103 / 120
4000 BTUH 48 VDC Powered Air Conditioner Indoor/Outdoor, NEMA Types 12, 4 & 4X Available
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like Telecom Outside Plant, Off-Grid Solar, Wind & other Battery Powered Electrical Cabinets.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2015-06-11
All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
0
1000
2000
3000
4000
5000
6000
85 90 95 100 105 110 115 120 125 130
BT
UH
Ambient Temperature (°F)
NE040-D48
105
95
85
Return Air Temperature
(°F)
UL File # SA32252
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 12” enclosure Unit Efficiency
Temperature operated blower control reduces power inrush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity
over a broad ambient temperature range Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save
energy and increase compressor life
4000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available
NE040
Options: Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Packages
Remote Monitoring Options
Integrated Enclosure Heat System
Hazardous Location Units
Redundant Systems
11.8” wide
Model BTU/Hour
Voltage/Hz.
Running Amps
Maximum Ambient
H x W x D
Weight (lbs.) Unit / Ship
Material
NE040-126-12 4000 120/1/60 5.53 125°F 32” x 11.8” x 9.5” 94 / 111 Powder coated steel
NE040-126-04 4000 120/1/60 5.53 125°F 32” x 11.8” x 9.5” 94 / 111 Powder coated steel
NE040-126-4X 4000 120/1/60 5.53 125°F 32” x 11.8” x 9.5” 94 / 111 Stainless steel
NE040-236-12 4000 230/1/60 3.07 125°F 32” x 11.8” x 9.5” 99 / 116 Powder coated steel
NE040-236-04 4000 230/1/60 3.07 125°F 32” x 11.8” x 9.5” 99 / 116 Powder coated steel
NE040-236-4X 4000 230/1/60 3.07 125°F 32” x 11.8” x 9.5” 99 / 116 Stainless steel
NE040-486-12 4000 480/1/60 1.51 125°F 38” x 11.8” x 9.5” 123 / 141 Powder coated steel
NE040-486-04 4000 480/1/60 1.51 125°F 38” x 11.8” x 9.5” 123 / 141 Powder coated steel
NE040-486-4X 4000 480/1/60 1.51 125°F 38” x 11.8” x 9.5” 123 / 141 Stainless steel
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2013-10-30
UL File # SA32252 All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 12” enclosure Unit Efficiency
Temperature operated blower control reduces power in-rush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity over
a broad ambient temperature range Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save
energy and increase compressor life
5000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available NE050
Options: Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Packages
Remote Monitoring Options
Integrated Enclosure Heat System
Hazardous Location Units
Redundant Systems
11.8” wide
Model BTU/Hour
Voltage Phase
Hz.
Running Amps
Max. Ambient Temperature
Weight (lbs.) Unit / Ship
H x W x D
Material
NE050-126-12 5000 120V/1/60 7.26 125°F 121 / 139 36” x 11.8” x 15.02” Powder coated steel
NE050-126-04 5000 120V/1/60 7.26 125°F 121 / 139 36” x 11.8” x 15.02” Powder coated steel
NE050-126-4X 5000 120V/1/60 7.26 125°F 36” x 11.8” x 15.02” 121 / 139 Stainless steel
NE050-236-12 5000 230V/1/60 3.76 125°F 36” x 11.8” x 15.02” 122 / 140 Powder coated steel
NE050-236-04 5000 230V/1/60 3.76 125°F 36” x 11.8” x 15.02” 122 / 140 Powder coated steel
NE050-236-4X 5000 230V/1/60 3.76 125°F 36” x 11.8” x 15.02” 122 / 140 Stainless steel
NE050-486-12 5000 480V/1/60 1.44 125°F 44.63” x 11.8” x 15.02” 170 / 189 Powder coated steel
NE050-486-04 5000 480V/1/60 1.44 125°F 44.63” x 11.8” x 15.02” 170 / 189 Powder coated steel
NE050-486-4X 5000 480V/1/60 1.44 125°F 44.63” x 11.8” x 15.02” 170 / 189 Stainless steel
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2015-01-22
UL File # SA32252 All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 12” enclosure Unit Efficiency
Temperature operated blower control reduces power in-rush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity over
a broad ambient temperature range Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save
energy and increase compressor life
6000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available NE060
Options: Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Packages
Remote Monitoring Options
Integrated Enclosure Heat System
Hazardous Location Units
Redundant Systems
11.8” wide
Model BTU/Hour
Voltage Phase
Hz.
Running Amps
Max. Ambient Temperature
Weight (lbs.) Unit / Ship
H x W x D
Material
NE060126-12 6000 120V/1/60 7.83 125°F 121 / 139 36” x 11.8” x 15.02” Powder coated steel
NE060126-04 6000 120V/1/60 7.83 125°F 121 / 139 36” x 11.8” x 15.02” Powder coated steel
NE060126-4X 6000 120V/1/60 7.83 125°F 36” x 11.8” x 15.02” 121 / 139 Stainless steel
NE060236-12 6000 230V/1/60 4.80 125°F 36” x 11.8” x 15.02” 122 / 140 Powder coated steel
NE060236-04 6000 230V/1/60 4.80 125°F 36” x 11.8” x 15.02” 122 / 140 Powder coated steel
NE060236-4X 6000 230V/1/60 4.80 125°F 36” x 11.8” x 15.02” 122 / 140 Stainless steel
NE060486-12 6000 480V/1/60 1.80 125°F 44.63” x 11.8” x 15.02” 170 / 189 Powder coated steel
NE060486-04 6000 480V/1/60 1.80 125°F 44.63” x 11.8” x 15.02” 170 / 189 Powder coated steel
NE060486-4X 6000 480V/1/60 1.80 125°F 44.63” x 11.8” x 15.02” 170 / 189 Stainless steel
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2014-07-15
UL File # SA32252 All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication & keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Narrow body style fits on 12” enclosure Unit Efficiency
Temperature operated blower control reduces power in-rush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity over
a broad ambient temperature range Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save
energy and increase compressor life
8000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available
NE080
Options: Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Packages
Remote Monitoring Options
Integrated Enclosure Heat System
Hazardous Location Units
Redundant Systems
11.8” wide
Model BTU/Hour
Voltage Phase
Hz.
Running Amps
Max. Ambient Temperature
Weight (lbs.) Unit / Ship
H x W x D
Material
NE080-126-12 8000 120V/1/60 7.83 125°F 121 / 139 36” x 11.8” x 15.02” Powder coated steel
NE080-126-04 8000 120V/1/60 7.83 125°F 121 / 139 36” x 11.8” x 15.02” Powder coated steel
NE080-126-4X 8000 120V/1/60 7.83 125°F 36” x 11.8” x 15.02” 121 / 139 Stainless steel
NE080-236-12 8000 230V/1/60 4.80 125°F 36” x 11.8” x 15.02” 122 / 140 Powder coated steel
NE080-236-04 8000 230V/1/60 4.80 125°F 36” x 11.8” x 15.02” 122 / 140 Powder coated steel
NE080-236-4X 8000 230V/1/60 4.80 125°F 36” x 11.8” x 15.02” 122 / 140 Stainless steel
NE080-486-12 8000 480V/1/60 1.80 125°F 44.63” x 11.8” x 15.02” 170 / 189 Powder coated steel
NE080-486-04 8000 480V/1/60 1.80 125°F 44.63” x 11.8” x 15.02” 170 / 189 Powder coated steel
NE080-486-4X 8000 480V/1/60 1.80 125°F 44.63” x 11.8” x 15.02” 170 / 189 Stainless steel
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2014-07-15
UL File # SA32252 All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Model BTU/Hour
Voltage Phase
Hz.
Running Amps
Max Ambient
H x W x D Weight (lbs) Unit / Ship
Material
HC101-126-12 10,000 120/1/60 19.40 131°F 48” x 15.86” x 15” 162 / 183 Powder coated steel
HC101-126-04 10,000 120/1/60 19.40 131°F 48” x 15.86” x 15” 162 / 183 Powder coated steel
HC101-126-4X 10,000 120/1/60 19.40 131°F 48” x 15.86” x 15” 162 / 183 Stainless steel
HC101-236-12 10,000 230/1/60 8.20 131°F 48” x 15.86” x 15” 165 / 186 Powder coated steel
HC101-236-04 10,000 230/1/60 8.20 131°F 48” x 15.86” x 15” 165 / 186 Powder coated steel
HC101-236-4X 10,000 230/1/60 8.20 131°F 48” x 15.86” x 15” 165 / 186 Stainless steel
HC101-486-12 10,000 480/1/60 3.93 131°F 56.6” x 15.86” x 15” 222 / 244 Powder coated steel
HC101-486-04 10,000 480/1/60 3.93 131°F 56.6” x 15.86” x 15” 222 / 244 Powder coated steel
HC101-486-4X 10,000 480/1/60 3.93 131°F 56.6” x 15.86” x 15” 222 / 244 Stainless steel
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication with keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant
Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Unit Efficiency
Pressure operated blower control reduces power inrush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity over a
broad ambient temperature range
Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save energy
and increase compressor life
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
10,000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available
Options:
Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Package
Remote Monitoring Options
Integrated Enclosure Heater System
Hazardous Location Package
Redundant System
HC101
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2013-10-30
All information subject to change without notice
0
2000
4000
6000
8000
10000
12000
14000
16000
18000
85 90 95 100 105 110 115 120 125 130
BTU
H
Ambient Temperature
HC101
105
95
85
Evaporator Temperature
(°F)
Testing done under controlled conditions. Actual performance may vary
UL File # SA32252
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication with keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant
Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Unit Efficiency
Pressure operated blower control reduces power inrush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity over a
broad ambient temperature range
Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save energy
and increase compressor life
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
12,000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available
Options:
Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Package
Remote Monitoring Options
Integrated Enclosure Heater System
Hazardous Location Package
Redundant System
HC121
Model BTU/Hour
Voltage Phase Hz.
Running Amps
Max. Ambient Temperature
H x W x D
Weight (lbs.) Unit / Ship
Material
HC121-126-12 12,000 120/1/60 19.40 131°F 48” x 15.86” x 15.03” 162 / 183 Powder coated steel
HC121-126-04 12,000 120/1/60 19.40 131°F 48” x 15.86” x 15.03” 162 / 183 Powder coated steel
HC121-126-4X 12,000 120/1/60 19.40 131°F 48” x 15.86” x 15.03” 162 / 183 Stainless steel
HC121-236-12 12,000 230/1/60 8.20 131°F 48” x 15.86” x 15.03” 165 / 186 Powder coated steel
HC121-236-04 12,000 230/1/60 8.20 131°F 48” x 15.86” x 15.03” 165 / 186 Powder coated steel
HC121-236-4X 12,000 230/1/60 8.20 131°F 48” x 15.86” x 15.03” 165 / 186 Stainless steel
HC121-486-12 12,000 480/1/60 3.93 131°F 56.6” x 15.86” x 15.03” 222 / 244 Powder coated steel
HC121-486-04 12,000 480/1/60 3.93 131°F 56.6” x 15.86” x 15.03 222 / 244 Powder coated steel
HC121-486-4X 12,000 480/1/60 3.93 131°F 56.6” x 15.86” x 15.03 222 / 244 Stainless steel
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2013-10-30
All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
0
2000
4000
6000
8000
10000
12000
14000
16000
18000
20000
22000
85 90 95 100 105 110 115 120 125 130
BTU
H
Ambient Temperature (°F)
HC121
105
95
85
Return Air Temperature
UL File # SA32252
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication with keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant
Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Unit Efficiency
Pressure operated blower control reduces power inrush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity over a
broad ambient temperature range
Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save energy
and increase compressor life
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
15,000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available
Options:
Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Package
Remote Monitoring Options
Integrated Enclosure Heater System
Hazardous Location Package
Redundant System
HC151
Model BTU/Hour Voltage
Phase/Hz.
Running
Amps
Max. Ambi-
ent Temper-ature
H x W x D
Weight
Unit / Ship Material
HC151-236-12 15,000 230/1/60 11.30 131°F 48” x 15.86” x 15.03” 170 / 191 Powder coated steel
HC151-236-04 15,000 230/1/60 11.30 131°F 48” x 15.86” x 15.03” 170 / 191 Powder coated steel
HC151-236-4X 15,000 230/1/60 11.30 131°F 48” x 15.86” x 15.03” 170 / 191 Stainless steel
HC151-486-12 15,000 480/1/60 5.41 131°F 56.6” x 15.86” x 15.03” 234 / 256 Powder coated steel
HC151-486-04 15,000 480/1/60 5.41 131°F 56.6” x 15.86” x 15.03” 234 / 256 Powder coated steel
HC151-486-4X 15,000 480/1/60 5.41 131°F 56.6” x 15.86” x 15.03” 234 / 256 Stainless steel
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2013-10-30
All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
0
5000
10000
15000
20000
25000
85 90 95 100 105 110 115 120 125 130
BTU
H
Ambient Temperature
HC151
105
95
85
Evaporator Temperature
(°F)
UL File # SA32252
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
Digital Temperature Controller
Programmable set point and temperature controls Visible Error and/or alarm messaging System status indication with keypad lockout function Active Condensate Evaporation System
Constant elimination of condensate Increases unit efficiency by pre-cooling refrigerant
Key Design Features Sloped top to allow for water runoff Designed with rigid chassis and seam welded shroud Thoughtful interior design for easy maintenance Unit Efficiency
Pressure operated blower control reduces power inrush and saves energy
Highly efficient rotary compressor Fully insulated & sealed cabinet Thermal Expansion Valve to maintain cooling capacity over a
broad ambient temperature range
Compressor Protection System
High & Low refrigerant cutouts with fault indication Compressor anti short cycle protection Compressor run capacitors reduce power inrush, save energy
and increase compressor life
Engineered & manufactured to endure the most difficult of environments and applications. Thermal Edge air conditioners will exceed environmental requirements in applications like
Steel, Food Processing, Petro-Chemical, Cement, Paper & Pulp and Plastics.
20,000 BTUH Indoor/Outdoor, NEMA Types 12, 4 & 4X Available HC201
Options:
Dry Contact Alarm Capabilities
Open Door Kill Switch
Corrosive Environment Package
Low Ambient Package
Remote Monitoring Options
Integrated Enclosure Heater System
Hazardous Location Package
Redundant System
Model BTU/Hour
Voltage/ Phase/Hz.
Running Amps
Max. Ambient Temperature
H x W x D
Weight (lbs.) Unit / Ship
Material
HC201-236-12 20,000 230/1/60 15.3 131°F 56.09” x 23” x 15.03” 205 / 226 Powder coated steel
HC201-236-04 20,000 Powder coated steel 230/1/60 15.3 131°F 56.09” x 23” x 15.03” 205 / 226
HC201-236-4X 20,000 Stainless steel 230/1/60 15.3 131°F 56.09” x 23” x 15.03” 205 / 226
HC201-486-12 20,000 Powder coated steel 480/1/60 7.7 131°F 65.7” x 23” x 15.03” 320 / 342
HC201-486-04 20,000 Powder coated steel 480/1/60 7.7 131°F 65.7” x 23” x 15.03” 320 / 342
HC201486-4X 20,000 480/1/60 7.7 131°F 65.7” x 23” x 15.03” 320 / 342 Stainless steel
(972) 580-0200 or (888) 580-0202 • www.thermal-edge.com • [email protected]
2015-03-13
UL File # SA32252 All information subject to change without notice
Testing done under controlled conditions. Actual performance may vary
ATTENTION: If ordering a replacement for a Thermal Edge air conditioner, please include the part number and serial number of the unit being replaced in your order. This will assure that we ship a replacement that is compatible with the cutout dimensions and power connection features of the older model.
0
5000
10000
15000
20000
25000
85 90 95 100 105 110 115 120 125 130
BTU
H
Ambient Temperature
HC201
105
95
85
Return Air Temperature
(°F)