1STULZ THE NATURAL CHOICE
STULZThe natural choice
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
2/50
2STULZ THE NATURAL CHOICE
STULZ Headquarters in HamburgResearch & Development, Production and
International Marketing
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
3/50
3STULZ THE NATURAL CHOICE
STULZ International Production Sites
STULZ GmbH
Hamburg, Germany
STULZ
Air Technology Systems,
Frederick/MD, USA
STULZ S.p.A.,
Valeggio sul Mincio (VR),
Italy
STULZ
Air Technology Systems
(Shanghai), China
STULZ CHSPL (India) P.Ltd., India
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
4/50
4STULZ THE NATURAL CHOICE
STULZ Group of Companies
A/C Technology Plastics Technology
Turnover
Plastics Technology
400 MioA/C Technology
300 Mio
Total 700 Mio
Employees
Plastics Technology 2.500A/C Technology 1.800
Total 4.300
Manufacturer and Distributor of AirConditioning Products, Systems
Engineering, Service and Object
Management.
STULZ GmbH, Germany (P)
STULZ Pty Ltd., AustraliaSTULZ-ATS (Shanghai), China (P)STULZ France S.A.R.L., FranceSTULZ UK Ltd., Great BritainSTULZ CHSPL Pvt . Ltd., India (P)STULZ SpA, Italy (P)STULZ Pte. Ltd. SingaporeSTULZ Groep B.V., Netherlands
STULZ Ltd., New ZealandSTULZ Polska Sp. z o.o., PolandSTULZ Espaa S.A., SpainSTULZ-ATS Inc., USA (P)STULZ South Africa Pty. Ltd.
(P): Production Site
Development and Production ofTechnical Plastic Components for
automotive industry.
Montaplast GmbH, Germany
Montaplast of North America, Inc.,USAMontaplast (SIP) Co.,Ltd., China
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
5/50
5STULZ THE NATURAL CHOICE
STULZ Germany - Business Areas
As an air conditioning specialist STULZ
offers a wide range of customer
solutions for the high-tech sector IT,
telecommunications and automation.
Development and manufacture of
precision air conditioning and chillersystems, STULZ also manufactures
moreover equipment for control
cabinets and for industrial cooling.
Precision Air Condition Units Comfort A/C and Humidification
The wide range of products distributed
stretches from portable air conditioners
to complex VRF multisplit systems.
In Germany STULZ is the sole
distributor for air conditioning units
of MITSUBISHI HEAVY INDUSTRIESand HAIER and humidifiers of CAREL.
Ventilation and air conditioning system
engineering for high-tech and comfort
applications. From the analysis
of individual requirements through
concept preparation and system
planning to installation and
commissioning.
Since its founding in 1947, STULZ
has specialised in areas requiring
technological expertise and
entrepreneurial flexibility. We help
to maintain standards and create
optimal operating conditions in
rooms for people and plant.
Systems Engineering Customer Service
STULZ customer service ensures that
ventilation and precision air conditioning
systems work reliably 365 days
a year.
STULZ furthermore provides a complete
modular range of services for all
building-related aspects.
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
6/50
6STULZ THE NATURAL CHOICE
Kami membangun Sistem yang melindungiTeknologi Informasi dan Telekomunikasi anda
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
7/50
7STULZ THE NATURAL CHOICE
www.stulz.com
STULZ-CHSPL (INDIA) PVT. LTD.006, Jagruti Industrial Estate . Mogul Lane, Mahim . Mumbai - 400 016Tel.: +91(22) 56 66 94 46 . Fax: +91(22) 56 66 94 48 . [email protected]
STULZ GROEP B. V.Postbus 75 . 1180 AB AmstelveenTel.: +31(20)54 51 111 . Fax: +31(20)64 58 764 . [email protected]
STULZ NEW ZEALAND LTD.Office 71, 300 Richmond Rd. . Grey Lynn .AucklandTel.: +64(9)360 32 32 . Fax: +64(9)360 21 80 . [email protected]
STULZ POLSKA SP. Z O.O.Budynek Mistral .Al. Jerozolimskie 162 . 02 342 WarszawaTel.: +48(22)883 30 80 . Fax: +48(22)824 26 78 . [email protected]
STULZ AIR TECHNOLOGY SYSTEMS (SATS), INC.1572 Tilco Drive . Frederick, MD 21704Tel.: +1(301)620 20 33 . Fax: +1(301)662 54 87 . [email protected]
STULZ SOUTH AFRICA PTY. LTD.P.O.Box 15687 . Lambton 1414 . GautengTel.: +27(11)873 68 06 . Fax: +27(11)873 31 36 [email protected]
STULZ Company HeadquarterSTULZ GmbHHolsteiner Chaussee 283 . 22457 HamburgTel.: +49(40)55 85-0 . Fax: +49(40)55 85-352 [email protected]
STULZ AUSTRALIA PTY. LTD.34 Bearing Road . Seven Hills NSW 21 47Tel.: +61(2)96 74 47 00 . Fax: +61(2)96 74 67 22 . [email protected]
STULZ AIR TECHNOLOGY and SERVICES(SHANGHAI) CO., LTD.No. 999 Shen Fu Road, Min Hang District . Shanghai 201108 . P.R. ChinaTel.: +86(21) 54 83 02 70 . Fax: +86(21)54 83 02 71 . [email protected]
STULZ ESPAA S.A.Avenida de los Castillos 1034 . 28918 Legans (Madrid)Tel.: +34(91)517 83 20 . Fax: +34(91)517 83 21 . [email protected]
STULZ FRANCE S. A. R. L.107, Chemin de Ronde . 78290 Croissy-sur-SeineTel.: +33(1)34 80 47 70 . Fax: +33(1)34 80 47 79 . [email protected]
STULZ U. K. LTD.First Quarter. Blenheim Rd. . Epsom . Surrey KT 19 9 QNTel.: +44(1372)74 96 66 . Fax: +44(1372)73 94 44 . [email protected]
STULZ S.P.A.Via Torricelli, 3 . 37067 Valeggio sul Mincio (VR)Tel.: +39(045)633 16 00 . Fax: +39(045)633 16 35 . [email protected]
STULZ SINGAPORE PTE. LTD.1 Kaki Bukit Road 1 #02-44 Enterprise One . Singapore 415934
Tel.: Tel: +65 96743772 . [email protected]
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
8/50
8STULZ THE NATURAL CHOICE
ULTIMATEEFFICIENCYfor Data Center Cooling
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
9/50
9STULZ THE NATURAL CHOICE
ULTIMATE EFFICIENCYMateri untuk ULTIMATE EFFICIENCY
The Technical Corridor
The Raised Floor The CRAC/CRAH System
Konsep Airflow Bagaimana mengeliminir Hot Spots
Service on Demand
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
10/50
10STULZ THE NATURAL CHOICE
Materi untuk ULTIMATE EFFICIENCY
The Raised Floor AirBooster for Hot SpotsAirModulator
High Density
Zone Separation
CyberRow for High
Density Zones
Technical Corridor
for CRAC/CRAH
Cold Aisle
Containment
CyberAir
CRAC/CRAH
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
11/50
11STULZ THE NATURAL CHOICE
The Technical CorridorTechnical Corridor
for CRAC/CRAH
Kendali pemisahanpendingin & peralatan IT Tidak ada air / Refrigerant di
dalam Data Center Tidak ada staff maintenance
di Data Center
Fleksibilitas tinggi untukdesain sistem pendingin
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
12/50
12STULZ THE NATURAL CHOICE
The Raised Floor I
Pasokan Udara Secara BersamaanDari Semua CRAC untuk semua Rak
Pasokan Tekanan Udara SecaraKeseluruhan
Meminimalkan kebocoran udara untukmemastikan ULTIMATE EFFICIENCY
The Raised Floor
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
13/50
13STULZ THE NATURAL CHOICE 13
Raised floor harus tertutup rapat!
mengurang semua kebocoran raised floor,e.g. menggunakan grommets untuk jalur kabel,
Hindari / hilangkan bukaan yang tidak perlu,
Damper harus memiliki kebocoran yang minimalketika tertutup sepenuhnya
Penyesuaian harus di capai dengan cara yangakurat dengan cara memperbaiki peredam
Damper harus bisa di sesuaikan dari atas
raised floor
The Raised Floor I
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
14/50
14STULZ THE NATURAL CHOICE
The Raised Floor IIDifferential Pressure Control untuk
memastikan aliran udara di raised floor
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
15/50
15STULZ THE NATURAL CHOICE 15
The Challenge: Pemerataan udara untuk rak
Low air volume Right air volume High air volume
Source: Intel15
The Raised Floor II
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
16/50
16STULZ THE NATURAL CHOICE
The CRAC/CRAH SystemCooling System yang biasa digunakan untuk DC :
DFC - Direct Free Cooling
DFC Dynamic (indirect) Free Cooling Dual Fluid Systems ACW, GCW Tradisional Cooling Systems A, G or CW/CW2 Semua sistem dilengkapi dengan teknologi EC fan Redundancy design sesuai dengan kebutuhan
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
17/50
17STULZ THE NATURAL CHOICE
CyberAir 3
energy efficiencyin seven sizes
The CRAC/CRAH System
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
18/50
18STULZ THE NATURAL CHOICE
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
19/50
19STULZ THE NATURAL CHOICE
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
20/50
20STULZ THE NATURAL CHOICE
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
21/50
21STULZ THE NATURAL CHOICE
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
22/50
22STULZ THE NATURAL CHOICE
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
23/50
23STULZ THE NATURAL CHOICE
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
24/50
24STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
EC is much more than efficiency Tidak ada in-rush current
Produksi fan speed, tidak pernah lebih dari F.L.Amps
Tidak ada delay / penundaan untuk starting
EC current ramps up to F.L.A.AC inrush current 3.5 times F.L.A.
Inrush
F.L.A.
F.L.A.
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
25/50
25STULZ THE NATURAL CHOICE
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
26/50
26STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres 26
Definisi PAC or CRAC:
Definidi Close control units, konstan dan kondisi suhu dan kelembaban didalam ruangan yang presisi. Toleransi untuk suhu dan kelembaban ruangandikontrol dengan band yang kecil.
Unit harus memiliki:
CoolingReheatHumidify
Dehumidify
Udara di saring oleh air filter yang high grade.
Cooling capacity biasanya tipikal di >90% (sensible cooling capacity) Posri ini adalah total cooling capacity yang mampu me-reduce temperature
Latent cooling capacity biasanya tipikal
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
27/50
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
28/50
28STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
Strategi Pemil ihan data centre
Sistem yang efisien energi dengan biaya
operasional yang rendah
atau
Sistem yang biayanya rendah tetapi denganbiaya operasi yang tinggi
Ingat:
Data centre membutuhkan energi setiap saat,
sepanjang tahun.
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
29/50
29STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
System Selection in depending on the Heat Load
Hot Aisle Cold Aisle Concept
Cold Aisle Containment
In Row Hot Aisle Containment
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
30/50
30STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
Air- conditioning Concept Selection 1Pengaturan rak dalam Cold/Hot Aisles
Designated Power Range
< 2000 W/m
< 8 kW / Rack
Solusi yang lebih diminati = 1,44 kW /m
heat load !!!!
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
31/50
31STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
Air- conditioning Concept Selection 2Pengaturan rak dalam Cold Aisle Enclosures
Designated Power Range
< 2000 to 5000 W/m
< 8 to 20 kW / Rack
Alternatife biaya, Solusi
yang efisien!
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
32/50
32STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
Return temperatur udara yang rendah tanpa Cold Corridor
22C
35C
13C
22C
35C
13C
13C
35C
0 6 3 1 7 4 0..
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
33/50
33STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
Return temperatur yang tinggi dengan menggunakan ColdCorridor = Pendinginan lebih efisien
35C
35C
22C
0 6 5 2 7 9 8..
Boat Meeting 2009
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
34/50
34STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
Design Temperatures
31-39C
18-24C
0 5 8 9 6 2 4..
Boat Meeting 2009
ASHRAE:Thermal Guidelines for dataProcessing Environments
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
35/50
35STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
Air- conditioning Concept Selection 3In Row Cooling
Designated Power Range< 20 to 40 kW / Rack
Solusi alternatif untuk
kasus yang High
Density !
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
36/50
36STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
Design dari CRAC unit: Membangun Efisiensi EnergiKonsumsi power yang rendah.
Fan menggunakan teknoligi
EC-Fans Resistan udara yang rendah
dengan Heat Exchanger
Resistan Filter udara yang
rendah dengan permukaan
yang meningkat
Casing lebih besar
Bebas dari biaya heater
dengan opsi penggunaan hot
gas Ultrasonic Humidifier
eksternal kontrol
...Tetapi footprint masi tetap tercapai
!
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
37/50
37STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
Return Air24 C; 65 % R. H.
Room Air22 C; 50 % R. H.
Inside Air18 C; 50 % r. H.
Heater
1
1
3
2
1
22
Dehumidifikasi mungkin memerlukan pemanas
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
38/50
38STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
Hot gas reheat(Free energy cost heater)
Hot gas Reheat (sampai 80% dari cooling capacity, dengan hot gas = 0 kw konsumsi power)Rata-rata runtime dari CRAC dalam mode dehumidifikasi di Jakarta sebesar 20 %
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
39/50
39STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
A. Total cooling capacity
B. Total sensible capacity
C. Net sensible capacity
Bagaimana ukuran kapasitas PAC?
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
40/50
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
41/50
41STULZ THE NATURAL CHOICE Energy efficient Precision Air Conditioning and Chilled Water Systems for Data Centres
Belted drive technologyEC fan direct driven technology
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
42/50
42STULZ THE NATURAL CHOICE Product overview 42
Air Modulator untuk pendinginan yang efisien dalam cold aisle
Posisi Damper sesuai kebutuhan
mengcover kebutuhanpendinginan yang sudah di
versifikasi ???
Area Aplikasi: Data center yang rasio
pressure nya homogen
Cold aisle containment dikombinasi dengan suplai
udara yang terkontrol dari unit
PAC
The Airflow Concept
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
43/50
43STULZ THE NATURAL CHOICE Product overview 43
Air Modulator
Fungsi: Dua temperature sensors
yang menghasilkan nilai
rata-rata dibandingkan
dengan set point???
Peningkatan T damperdibuka untuk pendinginan
yang lebih baik
The Airflow Concept
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
44/50
44STULZ THE NATURAL CHOICE Product overview 44
AirBooster
Penyesuaian kecepatan kipas untuk
memastikan pedinginan denganberbagai permintaan
Peningkatan T penyesuaiankecepatan dari EC-fan
Opsional: Differential pressurecontrol untuk aplikasi cold
containment.
max. airflow: 2650 m/h
Bagaimana mengeliminir HotSpots
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
45/50
45STULZ THE NATURAL CHOICE Product overview 45
AirBooster Pro
Airflow dapat di arahkan ke area load
head yang paling tinggi
Konfigurasi AirBooster plus saluransirip udara yang dapat di sesuaikan
max. airflow: 2500 m/h
Bagaimana mengeliminir HotSpots
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
46/50
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
47/50
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
48/50
48STULZ THE NATURAL CHOICE
Steam humidifier Ultrasonic humidifier Infrared humidifier
Biaya investasi
Konsumsi power
Biaya maintenance
Kebersihan properti
Keselamatan
Ketersediaan ukuran
Pengontrolan
Technical comparison humidification systems
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
49/50
49STULZ THE NATURAL CHOICE
Menghitung Load DC
Head Load Server : 300000 BTU/h
Ruangan : 15m x 9m = 135m
135 x 75 w = 10.125 kW (34546 BTU/h)Lampu (TL) Kurang lebih : 70 pcs x 36 w = 2520 w x 125% = 315 kW
3.15 kW = 10747 BTU/h
PIC kurang lebih : 10 org x 720 = 7200 BTU/h
Total Head Load adalah:
300000 + 34546 + 10747 + 7200 = 352493 BTU/h ( 103.31 kW )
Jadi kebutuhan PCU adalah :
2 unit dengan kapasitas 180000 BTU/h per unit
8/11/2019 Ultimate Efficiency Indo 02.2012 (Rev.1)
50/50
50STULZ THE NATURAL CHOICE
...thank you