Alberta Power Industry Consortium & University of Alberta
Professional Development Course
Understanding
Insulation Coordination
Organized
By Alberta Power Industry Consortium & University of Alberta
AESO AltaLink ATCO Enmax Epcor FortisAlberta
Instructed
By
Dr. David Peelo
May 13 & 15, 2014
Calgary & Edmonton, Alberta, Canada
i
Abstract
Insulation coordination is fundamental to the design and operation of power systems. In turn,
overvoltage limitation is an important part of insulation coordination. Means for overvoltage
limitation have evolved from rod gaps through gapped type surge arresters to the metal oxide
surge arresters of today. This course will discuss the basic principles of insulation coordination
and will then cover arrester application and selection. The course is intended for APIC company
staffs who are not specialized in insulation coordination but want to gain an adequate
understanding on the basics of insulation coordination and surge arrester application. It is hoped
that the knowledge will help them to better appreciate the challenges and requirements of
insulation coordination and equipment protection, which, in turn, will facilitate the execution of
engineering projects involving multiple technical subjects including insulation coordination for
T&D equipment.
ii
Confidentiality Requirement
This course material was prepared by the University of Alberta for the ultimate benefit of the
Alberta Power Industry Consortium members (hereinafter called “SPONSORS”). It may contain
confidential research findings, trade secrets, proprietary materials (collectively called
“Proprietary Information”). The term Proprietary Information includes, but is not limited to,
plans, drawings, designs, specifications, new teaching materials, trade secrets, processes,
systems, manufacturing techniques, model and mock-ups, and financial or cost data.
The document is made available to the sponsors only. The Sponsors will use all reasonable
efforts to treat and keep confidential, and cause its officers, members, directors, employees,
agents, contractors and students, if any, (“Representatives”) to treat and keep confidential, and
Proprietary Information in the document and the document itself. This course material shall not
be disclosed to any third party without the consent of the Alberta Power Industry Consortium.
Disclaimer
This document may contain reports, guidelines, practices that are developed by the University of
Alberta and the members of the Alberta Power Industry Consortium (APIC).
Neither the APIC members, the University of Alberta, nor any of other person acting on his/her
behalf makes any warranty or implied, or assumes any legal responsibility for the accuracy of any
information or for the completeness or usefulness of any apparatus, product or process disclosed,
or accept liability for the use, or damages resulting from the use, thereof. Neither do they
represent that their use would not infringe upon privately owned rights.
Furthermore, the APIC companies and the University of Alberta hereby disclaim any and all
warranties, expressed or implied, including the warranties of merchantability and fitness for a
particular purpose, whether arising by law, custom, or conduct, with respect to any of the
information contained in this document. In no event shall the APIC companies and the University
of Alberta be liable for incidental or consequential damages because of use or any information
contained in this document.
Any reference in this document to any specific commercial product, process or service by trade
name, trademark, manufacture, or otherwise does not necessarily constitute or imply its
endorsement or recommendation by the University of Alberta and/or the APIC companies.
iii
About the Alberta Power Industry Consortium:
The Alberta Power Industry Consortium consists of six Alberta utility companies (AESO,
AltaLink, ATCO, Enmax, Epcor and FortisAlberta) and the University of Alberta. Established in
the fall of 2007, its goal is to bring Alberta power companies together, with the University of
Alberta as the coordinating organization, to solve technical problems of common interest, to
produce more power engineering graduates, to support the professional development of current
employees, and to promote technical cooperation and exchange in Alberta’s power utility
community.
iv
About the instructor:
Dr. David Peelo, P.Eng., is an independent consultant. He graduated from University College
Dublin in 1965 and worked first for the ASEA Power Transmission Products Division in
Sweden. He joined BC Hydro in 1973 where he rose to the position of specialist engineer for
switchgear and switching and took early retirement in 2001 to pursue a second career as a
consultant. In 2004 the Eindhoven University of Technology awarded him a PhD for original
research on current interruption using air-break disconnect switches. He has published more than
60 papers on switching and surge arrester application and is actively involved with IEEE, CIGRE
and IEC. He is a past convener of IEC Maintenance Team 32 Inductive Load Switching and IEC
Maintenance Team 42 Capacitive Current Interrupting Capability of Disconnectors and a
member of the Canadian IEC National Committees for switching equipment and for surge
arresters. He is the author of a textbook on current interruption transients calculation and a co-
author of a textbook on switching in power systems both due for publication in 2014.
v
Course Outline
1. Basic principles of insulation coordination
Overvoltages in power systems
The concept of insulation levels
The role of surge arresters
Simplified approach to insulation coordination
2. Power system overvoltages
Origins of overvoltages: lightning, switching and temporary overvoltages
Characteristics of overvoltages in power systems
Traveling waves
3. Metal oxide surge arresters
Evolution of overvoltage protection devices
The design of metal oxide surge arrester
Characteristics and applications of metal oxide surge arrester
4. Surge arrester standards
Evolution of surge arrester standards
IEC versus IEEE standards
Which is the recommended standard to follow?
5. Arrester application in substations
Types and characteristics of incoming surges
Distance effects
Arrester selection
vi
3/6/2014
1
© DF Peelo & Associates 2014
APIC 2014
Understanding Insulation Coordination
David PeeloDF Peelo & Associates Ltd.
© DF Peelo & Associates 2014
APIC 2014
Basic principles of insulation coordination
• Overvoltages in power systems• Concept of insulation levels• Role of surge arresters• Simplified approach to insulation coordination
2
3/6/2014
2
© DF Peelo & Associates 2014
APIC 2014
3
What is insulation coordination?
IEEE definition: The selection of insulation strength consistent with expected overvoltages to obtain an acceptable risk of failure
IEC definition: The selection of dielectric strength of equipment in relation to voltages which can appear on systems for which the equipment is intended and taking into account the service environment and the characteristics of available protective devices
4
3/6/2014
3
5
Types of overvoltages and their causes:
6
Insulation types and strengths:
• External insulation
• Internal insulation
• Self-restoring insulation
• Non self-restoring insulation
3/6/2014
4
© DF Peelo & Associates 2014
APIC 2014
7
8
Internal insulation - transformers
3/6/2014
5
Insulation Coordination Course
9
Insulation strengths:
• Atmospheric air: statistical based on overvoltage type and insulation terminal configuration
• Liquids and gases: deterministic or statistical based on type of equipment
Insulation Coordination Course
10
Overvoltage limitation:
• Air gaps: dependent on electrode configuration and type of overvoltage
• Silicon carbide surge arresters: voltage limited rating basis
• Metal oxide surge arresters: energy absorption limited rating basis
3/6/2014
6
Insulation Coordination Course
11
Basic definitions:
Terms that we will encounter throughout the various part of the course
Insulation Coordination Course
12
Nominal voltage of a system: A suitable approximate value of voltage used to designate or identify a system: example 230 kV system.
Highest voltage of a system: The highest value of operating voltage which occurs under normal operating conditions at any time and at any point in the system: 245 kV on 230 kV system.
Highest voltage for equipment (Um): The highest rms value of phase-to-phase voltage for which the equipment is designed in respect of its insulation as well as other characteristics which relate to this voltage in the relevant equipment Standards
3/6/2014
7
Insulation Coordination Course
13
Isolated neutral system: A system where the neutral point is not intentionally connected to earth (ground)
Solidly earthed (grounded) neutral system: A system where the neutral point or points are directly connected to earth (ground)
Impedance earthed (grounded) system: A system whose neutral points are earthed (grounded) through impedances to limit fault current
Insulation Coordination Course
14
Earth (ground) fault factor: The ratio of the highest power frequency voltage on an unfaulted phase during a line-to-earth (ground) fault to thephase-to-earth (ground) power frequency voltage without the fault
Overvoltage: Voltage, between one phase and earth (ground) or between two phases, having a crest value exceeding the corresponding crest of the highest voltage of the system. Overvoltages may be classified by shape or duration as either temporary or transient
3/6/2014
8
Insulation Coordination Course
15
Performance criterion: The basis on which the insulation is selected so as to reduce to an economically and operationally acceptable level the probability that the resulting voltage stresses imposed on the equipment will cause damage to the equipment insulation or affect continuity of service. This criterion is usually expressed in terms of an acceptable failure rate of the insulation configuration
Insulation Coordination Course
16
Examples of performance criteria
Transmission lines:
2 lightning flashovers per 100 km-years exposure
1 switching surge flashover per 100 switching operations
Substations:
Generally, station reliability criteria is 10 times line criteria
Also, transformers and other non-self restoring insulation equipment arrester protected due to failure consequences
Air insulated stations: MTBF of 50 to 200 years
Gas insulated stations: MTBF up to 800 years due to failure consequences
3/6/2014
9
Insulation Coordination Course
17
Withstand voltage: The value of the test voltage to be applied under specified conditions during which a specified number of disruptive discharges may be tolerated:
• conventional assumed withstand voltage: number of disruptive discharges tolerated is zero and corresponds to a probability of withstand Pw = 100%
• statistical withstand voltage: number of disruptive discharges tolerated is related to a specified withstand probability and is specified at Pw = 90%
Insulation Coordination Course
18
Representative overvoltages (Urp): Overvoltages assumed to produce the same dielectric effect on the insulation as overvoltages of a given class occurring in service due to various origins
Coordination withstand voltage (Ucw): For each class of voltage, the value of the withstand voltage of the insulation configuration, in actual service conditions, that meets the performance criterion
3/6/2014
10
Insulation Coordination Course
Insulation coordination procedure
19
Insulation Coordination Course
20
Required withstand voltage (Urw): The test voltage that the insulation must withstand in a standard withstand test to ensure that the insulation will meet the performance criterion when subjected to a given class of overvoltages in actual service conditions and for the whole service duration
Standard withstand voltage (Uw): The standard value of the test voltage applied in a standard withstand test. It is the rated value of the insulation and proves that the insulation complies with one or more required withstand voltages
3/6/2014
11
Insulation Coordination Course
21
Coordination factor (Kc): The factor by which the value of the representative overvoltage must be multiplied in order to obtain the value of the coordination withstand voltage
Atmospheric correction factor (Ka): The factor to be applied to the coordination withstand voltage to account for the difference between the average atmospheric conditions in service and the standard reference atmospheric conditions. The factor applies only to external insulation
Insulation Coordination Course
22
Standard reference atmospheric conditions: The standard reference atmospheric conditions are:
• temperature to = 20°C
• pressure bo = 101.3 kPA (1013 mbar)
• absolute humidity hao = 11 g/m³
3/6/2014
12
Insulation Coordination Course
23
Safety factor (Ks): The factor to be applied to the coordination withstand voltage, after application of the atmospheric correction factor (if required), to obtain the required withstand voltage, accounting for all the differences between the conditions in service and those in the standard withstand test
Test conversion factor (Kt): The factor to be applied to the required withstand voltage, in the case where the standard withstand voltage is selected of different shape, so as to obtain the lower limit of the standard withstand test voltage that can be assumed to prove it
Insulation Coordination Course
Insulation coordination procedure
24
3/6/2014
13
Insulation Coordination Course
25
Insulation Coordination Course
Insulation coordination simplified approach
26
3/6/2014
14
Insulation Coordination Course
27Source IEC 62271-1
Insulation Coordination Course
28Source IEC 62271-1
3/6/2014
15
Insulation Coordination Course
29
References:
1. IEC and IEEE insulation coordination standards noted earlier.
2. IEC 60099-4 Surge arresters – Part 4: Metal-oxide surge arresters without gaps for a.c. systems.
3. IEC 60099-5 Surge arresters – Part 5: Selection and application recommendations.
4. Insulation Coordination for Power Systems (Book), A.R. Hileman, Marcel Dekker, Inc 1999.
5. Insulation Coordination for High-Voltage Electric Power Systems (Book), W. Diesendorf, Butterworth & Co. 1974.
6. Surge arrester manufacturer websites: ABB and Siemens in particular have comprehensive selection and application guides.
Insulation Coordination Course
Power system overvoltages
• Lightning, switching and temporary overvoltages• Characteristics of overvoltages in power systems• Travelling wave basics• How do surge arresters work?
30
3/6/2014
16
Insulation Coordination Course
31
Spectrum of power system overvoltages:
Insulation Coordination Course
32
Overvoltage class: transient
3/6/2014
17
Insulation Coordination Course
33
Overvoltage class: low frequency continuous and temporary
Insulation Coordination Course
34
Temporary overvoltages: causes and characteristics
1. Ferranti effect:
Steady state voltage (V2) at the open receiving end of an uncompensated line (no shunt reactors) is always higher than the voltage (V1) at the sending end; occurs because the (leading) capacitive charging current flows through the series inductance of the line
where L is the line length in km and B the phase constant (7.2 degrees/100 km at 60 Hz)
)BLcos(1
VV
1
2 =
3/6/2014
18
Insulation Coordination Course
35
Ferranti effect
V1 and V2 sending and receiving end voltages.
1: no compensation 2: 50% series capacitor compensation 3: 50% series capacitor and 70% shunt reactor compensation.
Insulation Coordination Course
36
2. Faults:
A line to ground fault represents a typical example of a temporary undamped overvoltage that may be sustained on the unfaulted phases for up to hundreds of milliseconds
The magnitude of the overvoltages on the unfaulted phases depends on the shift of the electrical neutral caused by the fault – earth fault factors
3/6/2014
19
Insulation Coordination Course
37
SLG EFFs:
Maximum line to ground voltage at any fault location and under any fault condition for effectively grounded system. Numbers on curves are maximum line to ground voltages on any phase in percent of line-to-line voltage.
Insulation Coordination Course
38
Earth fault TOVs:
Category EFF (pu) Duration
Grounded• Network, high SC*• Line radial line, low SC
1.2 – 1.41.2 – 1.5
1 s1 s
Resonant grounded• Network or mesh• Long radial line
1.731.2 – 1.5
8 hours – 2 days1 s
Isolated/Ungrounded• Distribution with O/H lines• Industrial with cable
1.73 1 – 2 s(with fault clearing)
SC – short circuit
3/6/2014
20
Insulation Coordination Course
39
3. Load rejection:
Load rejection occurs when a remote circuit breaker on a transmission line carrying a substantial load is opened due to system condition or an error. A voltage rise follows because:
• the reduced current means a lower voltage drop across the internal system impedance
• generators tend to overspeed to produce higher voltages
Insulation Coordination Course
40
Load rejection overvoltages:
Category Magnitude Duration (s)
Load rejection• in a system• generator-transformer
− steam turbine− hydro
1.05
1.1 – 1.41.15 – 1.5
> 10
11
Note: Load rejection may be combined with the occurrence of a fault producing a combined effect
3/6/2014
21
Insulation Coordination Course
41
4. Resonance:
Resonance in power systems can take two forms:
• linear resonance when inductive and capacitive elements in series form a series resonant circuit; for example, an unsaturated transformer and a shunt capacitor bank
• ferroresonance when saturated iron-cored inductive and capacitive elements in series form a series circuit; for example, the grading capacitors on an open circuit breaker in series with a magnetic PT
Insulation Coordination Course
42
Overvoltages associated resonance situations can be very significant and rapid intervention is necessary
Resonance Magnitude (pu) Duration (s)
Unsaturated phenomena < 2 ≤ 0.5
Saturated phenomena 2 – 3+ 0.5 – 10
Coupled circuits 3 – 5+ 0.5 – 10
3/6/2014
22
Insulation Coordination Course
43
TOVs due to Magnitude (pu) Duration
Line energization and re-energization ≤ 1.5 < 1 s
Stuck breaker pole ≤ 2 Steady state
Backfeeding ≤ 2 Seconds
5. Other TOV situations:
Insulation Coordination Course
44
Interesting facts about TOVs:
1. TOVs DO NOT CONTRIBUTE TO INSULATION DESIGN…HOWEVER
2. TOVs DETERMINE THE VOLTAGE RATINGS OF THE METAL OXIDE ARRESTERS TO BE APPLIED ON THE SYSTEM
3/6/2014
23
Insulation Coordination Course
45
Slow front switching surges:
• Line switching
• Making and breaking reactive currents
• TRVs across circuit breakers
Insulation Coordination Course
46
Line switching:
Due to travelling wave effects, line switching can result in overvoltages of significant magnitude. Worst case is re-energization of a line with a full DC trapped charge
The resulting switching surges are slow-front with times to peak in the order of hundreds of microseconds
3/6/2014
24
Insulation Coordination Course
47
Switching surge overvoltage distribution with various control measures
Insulation Coordination Course
Voltage profile on line
48
3/6/2014
25
Insulation Coordination Course
49
Typical switching overvoltage magnitudes:
Condition Magnitude (pu)
Energizing discharged line 1.5 – 2.0
Re-energizing with no overvoltage control 3 – 3.4
Re-energizing with pre-insertion resistors 2 – 2.2
Re-energizing with controlled closing 1.2 – 1.7
Insulation Coordination Course
50
Making and breaking reactive currents:
• Inductive current switching
transformer magnetizing current
shunt reactors at EHV, HV and MV
• Capacitive current switching
shunt capacitor banks
lines and cables
3/6/2014
26
Insulation Coordination Course
51
Insulation Coordination Course
52
Fast front overvoltages:
Fast front overvoltages are those due to lightning and have the dimensioning role at system voltages below EHV levels (at EHV levels switching surges have the dimensioning role)
The overvoltages are characterized by fast rise times of 0.1 to 20 µs and associated in the range 5 to 200 kA.
3/6/2014
27
Insulation Coordination Course
53
Very fast front overvoltages:
Very fast front overvoltages are generally associated with gas insulated switchgear (GIS) applications and in particular with the live operation of disconnect switches
The overvoltage are not dimensioning with respect to the insulation coordination of GIS; however, present standards for disconnect switches now incorporate very severe tests to demonstrate that live operation of the switches does not compromise the GIS insulation structure
Insulation Coordination Course
54
What is lightning?
• Lightning is the breakdown of atmospheric air; in dry air at sea level breakdown voltage is 30 kV/cm but, at higher altitudes in a region filled with water droplets, it is about one-third this value
• Lightning strikes are not instantaneous starting as ‘local’ events and progressing in steps to the other electrode which could be earth (ground) or another cloud
• Lightning strikes are very statistical in terms of current magnitude, number of strokes per strike and striking point
3/6/2014
28
Insulation Coordination Course
55
Global electric circuit
Insulation Coordination Course
56
3/6/2014
29
Insulation Coordination Course
57
Insulation Coordination Course
58
3/6/2014
30
Insulation Coordination Course
59
Insulation Coordination Course
60
3/6/2014
31
Insulation Coordination Course
61
Insulation Coordination Course
62
Travelling wave basics:Fundamental circuit for travelling waves
Vi = incident voltageZi = surge impedance of ViZt = surge impedance of VtVr = reflected voltage = αVi where α = (Zt – Zi)/(Zt + Zi)Vt = transmitted voltage = βVi where β = 2Zt/(Zt + Zi)
3/6/2014
32
Insulation Coordination Course
63
Insulation Coordination Course
64
Voltage waves:
CaseSurge
Impedance
VrReflected Voltage
VtTransmitted
Voltage
No change Zi = Zt 0 Vi
Open circuit Zt >> Zi Vi 2 Vi
50% reduction Zt = 0.5 Zi -0.33 Vi 0.67 Vi
Short circuit Zt = 0 -Vi 0
3/6/2014
33
Insulation Coordination Course
65
Surge current (directional): I = V/Z
CaseSurge
ImpedanceIr
Reflected CurrentInet
(Zi side)
No change Zi = Zt 0 Ii
Open circuit Zt >> Zi Ii 0
50% reduction Zt = 0.5 Zi -0.33 Ii 0.67 Ii
Short circuit Zt = 0 -Ii 2 Ii
Insulation Coordination Course
66
CO operation on 100 km unloaded transmission line
Sending end
Receiving end
3/6/2014
34
Insulation Coordination Course
67
We can now consider the principle of overvoltage surge protection using arresters:
V1 V2
V3
Z1 Z2
Z3
I3
V2 = V3
Insulation Coordination Course
68
We can write:
32 VV =
32
32T ZZ
ZZZ where+
=
1T1
T VZZ
Z2
+
=
( )( )
++
+=
3221
32212 ZZ1ZZ
ZZ11ZV2V
3/6/2014
35
Insulation Coordination Course
69
If no arrester, Z3 = ∞
If Z2 also ∞ as at open-ended line or transformer
132 V2VV == (voltage doubling)
21
2132 ZZ
ZV2VV+
==
Insulation Coordination Course
70
We can also write:
If ideal arrester (short-circuit), Z3 = 0 and
113 ZV2I =
33323 ZVZVI ==
+
+
+
=32
321
32
21 ZZ
ZZZZZ
ZV2
3/6/2014
36
Insulation Coordination Course
71
We now have the two extreme points on the circuit load line:
( )31121
22 I ZV2
ZZZV −
+
=
V2
I3
2V1*Z2
Z1+Z2
2V1
Z1
Insulation Coordination Course
72
Add the arrester VI-characteristic:
( )ar1121
2ar I ZV2
ZZZV −
+
=
V2
I3
2V1*Z2
Z1+Z2
2V1
Z1
Var
Iar
Arrester VI-characteristic
3/6/2014
37
Insulation Coordination Course
73
Load line for transformer case: Z2 = ∞
ar11ar I ZV2V −=
V2
I3 2V1
Z1
Var
Iar
Arrester VI-characteristic
2V1
Insulation Coordination Course
74
Question: how does travelling wave theory treat the effect of a surge arrester in clamping the voltage to the protective level at its location?
3/6/2014
38
© DF Peelo & Associates 2014
APIC 2014
Metal oxide surge arresters
• Evolution of overvoltage protective devices• Design of metal oxide surge arresters• Characteristics and application of metal oxide surge
arresters
75
76
History of surge arresters:
• 1898 – rod gap design• 1908 – electrolyte arrester with non-linear resistive
element to limit follow current and enable arcinterruption
• 1930 – silicon carbide arresters with silicon carbideresistive elements in series with gaps
• 1957 – silicon carbide arresters with current limitinggaps
• 1976 – metal oxide surge arresters with extremenon-linear characteristics
3/6/2014
39
© DF Peelo & Associates 2014
APIC 2014
77
Structure of metal oxide surge arresters:
• Consist simply of zinc oxide varistor disks of varying sizes connected in series
• Zinc oxide varistors are ceramic semiconductor devices with verynon-linear voltage-current characteristics and very good energy absorption capability
© DF Peelo & Associates 2014
APIC 2014
78
Zinc oxide disks are about 90% zinc oxide (ZnO) by weight plus various other metal oxides to provide specific properties – for example:
bismuth + CaO, CoO, BaO, SrO, MnO:non-linearity of the VI characteristic
K2O: inhibits grain growth
Cr2O3: enhances thermal stability
Ga2O3: increases exponent (α) of VI characteristic
Sb2O3: grain grown enhancer
3/6/2014
40
© DF Peelo & Associates 2014
APIC 2014
79
Varistor microstructure key elements:
• Zinc oxide grains
• Bismuth-rich intergranular layer
• Spinel grains
80
Varistor microstructure:
Source: ABB
3/6/2014
41
81
VI characteristic: three conductive regions
0
0.5
1
1.5
2
2.5
1E-05 0.0001 0.001 0.01 0.1 1 10 100 1000 10000 100000
Current (A)
Per u
nit p
eak
rate
d vo
ltage
Region 1 Region 2 Region 3
LIPL
SIPLRated voltage
MCOV
25 C 150 C
Resistive leakage current
© DF Peelo & Associates 2014
APIC 2014
82
Region 1: pre-breakdown region is the low current region associated with steady state operation; material resistivity temperature dependent with negative temperature coefficient
Region 2: breakdown region is the highly non-linear region associated with TOVs and switching surges; very small temperature dependence and exponent α = 30 to 50
Region 3: high current region is the region associated impulse currents > 1 kA due to lightning;non-linearity much less than in the breakdown region
3/6/2014
42
83
Current conduction: equivalent circuit
© DF Peelo & Associates 2014
APIC 2014
84
Pre-breakdown: in this region current conduction is determined by the high “resistance” associated with grain boundaries with a significant temperature dependence
Breakdown: at a certain applied voltage across grain boundaries, the intergranular layer “resistance” drops allowing a large increase in current; energy is therefore being absorbed in the intergranular layer
High-current: the zinc oxide grain resistance dominates in this region
3/6/2014
43
© DF Peelo & Associates 2014
APIC 2014
85
Comparison: metal oxide versus gapped silicon carbide arresters – fundamentally different:
• Metal oxide arresters are rated on the basis of ability to absorb energy and maintain thermal stability at rated voltage followed by MCOV
• Gapped silicon carbide arresters are rated on the basis of ability to reseal – interrupt follow current – after discharging a lightning or switching surge
86
Grading resistors and capacitors
Active gaps
SiC resistors
SiC gapped arresterZnO arrester
Courtesy of ABB
3/6/2014
44
87
88
Rated voltage and energy considerations: metal oxide arresters are energy (temperature) limited
3/6/2014
45
89
Effects of aging: over lifetime
90
IEC 60099-4 specifies five (5) line classes:
0
1
2
3
4
5
6
7
1 1.5 2 2.5 3 3.5
Ures/Ur
Spec
ific
ener
gy (k
J/kV
Ur) Line class 1
Line class 2Line class 3Line class 4Line class 5
Former IEC rating basis now changed to a thermal energy rating and a repetitive charge transfer rating
3/6/2014
46
91
Former IEC rating basis now changed to a thermal energy rating and a repetitive charge transfer rating
© DF Peelo & Associates 2014
APIC 2014
Thermal Energy Rating Wth
• Maximum specified energy given in kJ/kV of Ur that may be injected into an arrester within 3 minutes time duration without causing thermal runaway.
• This rating is verified in the revised operating duty test –above injection preceded by conditioning consisting of two high current impulses only.
• The rating is strictly thermal and no longer relates rated energy to protective levels; temperature coefficient for metal oxide material 0.33 ⁰C/J/cm3.
92
3/6/2014
47
Insulation Coordination Course
Repetitive Charge Transfer Rating Qrs
• Maximum specified charge transfer capability of an arrester in the form of a single event or group of surges that may transferred through an arrester without causing mechanical failure or unacceptable electrical degradation to the MO resistors.
• The charge is calculated as the absolute value of current integrated over time. This is the charge that is accumulated in a single event or a group of surges lasting for no more than 2 seconds and which may be followed by a subsequent event at a time interval not shorter than 60 seconds.
93
94
TOV versus time curves:
0.7
0.8
0.9
1
1.1
1.2
1.3
0.1 1 10 100 1000 10000
Time (s)
TOV
fact
or k
tov
With prior energyWithout prior energyMCOV
3/6/2014
48
95
Overvoltages: types and shapes
Source: IEC 60071-1
© DF Peelo & Associates 2014
APIC 2014
96
Energy absorption:
• TOVs: system is a voltage source
• lightning and switching surges: system is a current source
• For energy absorption studies, the minimum VI characteristics should be used
3/6/2014
49
97
Overvoltages and associated energies:
Type/Cause Magnitude Waveshape
EnergykJ/kV rated
voltage
Atmospheric Overvoltages:Lightning strikes or induced by lightning (multiple strikes may occur)
> 5 pu Front: 1 – 6 µsTail @ 50%: 50 µs 0.5
Switching Overvoltages:Line autoreclosing, switching capacitor banks, shunt reactors, issue more at EHV
2 – 4 pu Front: 30 – 300 µsTail @ 50%: 100 – 2000 µs 3 – 5
Temporary Overvoltages:SLG faults in ungrounded systems, Ferranti effect, loading shedding++ 1 – 1.5 pu Power frequency
(may be distorted)
Very high(fast remedial
action required)
98
Protective and related characteristics: 192 kV arrester
0
100
200
300
400
500
600
700
1E-05 1E-04 0.001 0.01 0.1 1 10 100 1000 10000 1E+05Current (A)
Vol
tage
(kV
peak
)
MCOV 218 kV peakRated voltage 272 kV peak
SIPL 384 kV peak
LIPL 470 kV peak
3/6/2014
50
© DF Peelo & Associates 2014
APIC 2014
99
Because we are dealing with a VI characteristic, the respective protective levels are defined at standard normal discharge currents. For lightning protection:
System voltageStandard nominal discharge current*
(8/20 µs)
Distribution 5 kASub-transmission up to 72.5 kV 5 or 10 kA
72.5 to 245 kV 10 kA245 kV and up 10 kA or 20 kA≥ 500 kV 20 kA
* values also define so-called Arrester Classification
© DF Peelo & Associates 2014
APIC 2014
100
For switching surges:
Arrester classification Peak currents*(A)
20 kA 500 and 2000
10 kA 250 and 1000
10 kA distribution class 125 and 500
* in switching impulse residual voltage test, higher numbers used to define the protective level
3/6/2014
51
101
VI characteristic: switching and lightning currents
0.60.70.80.9
11.11.21.31.41.5
1 10 100 1000 10000 100000
Current (A)
Volta
ge (p
u of
10
kA v
alue
)
4/10micros8/20micros36/90micros
102
Extract from ABB surge arrester catalog:
Guaranteed protective characteristics
Recommended for system
voltageRated
voltage
Max. cont. operating voltage (COV)
MCOV as per ANSI
testsTOV
capability for
Maximum residual voltage with current wave
Switching surges 8/20 µs
kVrms kVrms kVrms kVrms
1 skVrms
10 skVrms
1 kAkVcrest
2 kAkVcrest
3 kAkVcrest
5 kAkVcrest
10 kAkVcrest
20 kAkVcrest
40 kAkVcrest
EXLIM P-A and P-B245 180 144 144 209 198 351 362 371 392 414 452 497
192 154 154 223 211 374 386 396 418 442 482 530
198 156 160 230 218 386 398 408 431 456 497 547
210 156 170 244 231 409 423 433 457 483 528 580
219 156 177 254 241 426 441 452 477 504 550 605
228 156 180 264 251 444 459 470 496 525 573 630
3/6/2014
52
Insulation Coordination Course
103
Energy absorption:
• TOVs: system is a voltage source
• lightning and switching surges: system is a current source
• For energy absorption studies, the minimum VI characteristics should be used
Insulation Coordination Course
104
Selection procedure:• Electrical characteristics
Rated voltage and MCOVNominal discharge currentThermal energy rating Wth
Repetitive charge transfer rating Qrs
Lightning and switching surge protection levels• Mechanical characteristics
Strike and creepage distancesShort-circuit withstandSeismic and tensile loads
3/6/2014
53
Insulation Coordination Course
105
Selecting the housing: briefly the following applies
• Arresters are self-protecting and the housings do not require the same withstand capability as other station equipment
• Creepage distances should be the same as for all station equipment
• Pollution or exposure to salt contamination can require longer creepage distances but consideration should also be given to using higher rated voltage arresters or more appropriate arrester designs
Insulation Coordination Course
106
• Short-circuit testing is required on all arrester types over a range of current; for example, an arrester with a ratedshort-circuit current rating of 50 kA would also be tested at 25 kA, 12 kA and 600 kA
• Selection of the short-circuit current rating should be based on the maximum expected short-circuit current magnitude at the arrester location
3/6/2014
54
Insulation Coordination Course
107
Insulation coordination – iterative process
Insulation Coordination Course
108
Station layout considerations:
• Location of the arrester relative to the protected equipment is important and will be discussed later
• Location of the arrester relative to other energized equipment on the same phase also requires attention
• Question: how does the protected equipment ‘know’ that the arrester is ahead of it?
3/6/2014
55
Insulation Coordination Course
109
Testing:
• Type testing is covered in great detail in IEC 60099-4 as is basic routine testing
• As noted earlier routine testing is at least as important as type testing; in making comparisons between arresters from different manufacturers, compare the tests performed on each block before considering award
Insulation Coordination Course
Surge arrester standards
• Evolution of surge arrester standards• IEC versus IEEE standards• Which is the recommended standard to use
110
3/6/2014
56
Insulation Coordination Course
111
IEEE and IEC differ in approaches:
• IEEE: rated voltage is the duty cycle ratingwhich is a holdover from gappedsilicon carbide arresters and has norelationship to absorbed energy
• IEC: rated voltage is a TOV to be withstoodfollowing absorption of defined energyunder specific circumstances
Insulation Coordination Course
112
IEEE rating basis: from IEEE C62.11-2005
3.29 duty cycle voltage rating: The designated maximum permissible voltage between its terminals at which an arrester is designed to perform its duty cycle.
8.14 Duty-cycle test
The purpose of the duty-cycle test is verify that the arrester can withstand multiple lightning type impulses without causing thermal instability or dielectric failure.
3/6/2014
57
Insulation Coordination Course
113
Insulation Coordination Course
114
3/6/2014
58
Insulation Coordination Course
115
Former IEC rating basis now changed to a thermal energy absorption rating
Insulation Coordination Course
116
Importance of routine testing:
• Absolutely no redundancy in metal oxide surge arresters: one bad block and the arrester will fail –guaranteed!
• Routine testing has therefore equal or arguably greater importance than type testing
3/6/2014
59
© DF Peelo & Associates 2014
APIC 2014
Arrester application in stations
• Type and characteristic of incoming surges• Distance effects• Arrester selection
117
Insulation Coordination Course
118
Stations: insulation coordination
• Transmission lines are normally shielded except where the soil resistivity is such that it is not possible to achieve low tower footing impedances at a justifiable cost
• Lines, however, are typically shielded about 1 km or more out from the station in order to limit the occurrence, magnitude and steepness of incoming surges
• Two types of lightning related failures are of interest: shielding failures where a lightning strike occurs directly to the line conductor and back flashover (also known as a backflash) where the tower or ground wire is struck and a flashover then occurs to a phase conductor.
3/6/2014
60
Insulation Coordination Course
119
Insulation Coordination Course
120
Lightning strike to a phase conductor
Only close-in strikes are of interest because of the damping effect of corona on the traveling wave.
3/6/2014
61
Insulation Coordination Course
121
Travelling wave damping due to corona
Conductors Zo(ohms) Kc (km-kV/us)
Single 450 700
2 Conductor Bundle 350 1000
3 or 4 Conductor Bundle 320 1700
6 or 8 Conductor Bundle 300 2500
Insulation Coordination Course
122
-500000
0
500000
1000000
1500000
0 10 20 30 40
Voltage Surge Distortion Due to Corona
Electrotek Concepts® TOP, The Output Pro
Vol
tage
(V
)
Time (us)
V@ 3.0 km V@ 4.0 km V@ 0.5 km V@ 1.0 km V@ 2.0 km
0.5 km1.0 km
2.0 km3.0 km
4.0 km
3/6/2014
62
Insulation Coordination Course
123
Back flashover
Insulation Coordination Course
124
Lightning currents
Shielding failure: 4 kA or greater at 89% probability: 20 kA or greater at 80% probability.
Back flashover: 20 kA or greater at probability of 80%; 90 kA or greater at probability of 5%
Median current: 32 kA
3/6/2014
63
Insulation Coordination Course
125
Station insulation coordination: determine the representative incoming lightning overvoltage.
Two approaches are possible:
1. Comprehensive approach: requires a computer study because of the complexity of the calculations.
2. Deterministic approach: a more general approach but does take into account the lightning stress severity of the station under study.
Insulation Coordination Course
126
Comprehensive approach flow diagram:
3/6/2014
64
Insulation Coordination Course
127
Comprehensive approach - need to consider:
• Statistical (stochastic) variation of the lightning flash and stroke parameters
• Dependence of the flash strike point on these parameters• Response of the line to the lightning flash including the tower
footing impedance current dependence• Propagation of the surge from the strike point to the station
and the deformation effect of corona
Insulation Coordination Course
128
Station insulation coordination: deterministic approach
1. Determine the lightning performance of incoming transmission line based on parameters discussed earlier –ground flash density, line height etc.
2. Determine steepness of incoming surge based on the above and system fault tolerance.
3. Determine the protective zones based on selected arrester locations; may need a number of iterations and this type of study is usually done using EMTP simulations.
4. Transformer protection tends to get most attention but open breaker protection is also a consideration
3/6/2014
65
Insulation Coordination Course
129
Insulation Coordination Course
130
Insulation Coordination 101
3/6/2014
66
Insulation Coordination Course
131
Basic case: arrester at transformer onlyCASE1>B-B1 (Type 1)
0.03300 0.03400 0.03500 0.03600 -200000
0
200000
400000
600000
800000
1000000
Time (mS)
Voltage (V)
VB-B1V-CBV-JTN VSA-1 VTX
Insulation Coordination Course
132
-200000
0
200000
400000
600000
800000
1000000
33 35 37 39 41
Entrance Bus Voltages : Normal, Wih Ccvt, With SA2 & Ccvt
Electrotek Concepts® TOP, The Output Processor®
Vol
tage
(V)
Time (us)
Vb: normal Vb: With Ccvt Vb: With SA2 & Ccvt
3/6/2014
67
Insulation Coordination Course
133
-200000
0
200000
400000
600000
800000
1000000
33 35 37 39 41
Transformer Voltages: Normal, With Ccvt, With SA2 & CCVT
Electrotek Concepts® TOP, The Output Processor®
Vol
tage
(V)
Time (us)
Vtxc: normal Vtx: With Ccvt Vtx: With SA2 & Ccvt
Insulation Coordination Course
134
0
200000
400000
600000
33 35 37 39 41
Vsa : Normal, With Ccvt, With SA2 & Ccvt
Electrotek Concepts® TOP, The Output Processor®
Vol
tage
(V)
Time (us)
Vsa: normal Vsa: With Ccvt Vsa: With SA2 & Ccvt
3/6/2014
68
Insulation Coordination Course
135
0
2000
4000
6000
8000
10000
33 35 37 39 41
SA Currents: Normal, With Ccvt, With SA2 & Ccvt
Electrotek Concepts® TOP, The Output Processor®
Cur
rent
(A)
Time (us)
Isa: normal Isa: Ccvt Isa: SA2 & Ccvt
Insulation Coordination Course
136
Surge arrester application:
• Arrester selection – recap
• Arrester location relative to protected equipment
• Clearances associated with arresters
3/6/2014
69
Insulation Coordination Course
137
Arrester selection based on:
• system voltage and grounding
• temporary overvoltages
• desired safety factor relative to the equipment withstand voltage
but its physical location relative to the protected equipment is also a consideration (why?)
Insulation Coordination Course
138
whereUpl = lightning impulse protective level of the
arrester (kV)S = steepness of incoming surge (kV/µs)L = d1 + dA + d2 + d (m)c = velocity of light (300 m/µs)
Simple estimation of protective distance:
cSL2UU plrp +=
3/6/2014
70
Insulation Coordination Course
139
Example: 245 kV transformer, LIWL 850 kV192 kV rated surge arrester, Upl 440 kV, 1000 kV/µs
L = d1 + dA + d2 + d= 2 + 2.5 + 2.6 + d= 7.1 + d
Urp =
= 440 + 6.67 (7.1 + d)( )d1.7
30010002440 +⋅+
Insulation Coordination Course
140
0
100
200
300
400
500
600
700
800
900
0 10 20 30 40 50Distance d (m)
Urp
(kV)
Voltage attransformer850*0.85
850*0.6375
3/6/2014
71
Insulation Coordination Course
141
Let’s take a look at what is really happening when a surge approaches a transformer protected at a certain distance by an arrester:
•Incoming surge steepness 1000 kV/μs
•Arrester with protective level of 800 kV installed at distance of 75 m from the transformer
•Remember the questions: how does traveling wave deal with arresters and their voltage limiting effect and how does the transformer know there is an arrester ahead of it?
Insulation Coordination Course
142
Arrester at distance 75 m and surge 1000 kV/µs
3/6/2014
72
© DF Peelo & Associates 2014
APIC 2014
EMTP study result same case
143
Insulation Coordination Course
144
What conclusions can we draw?
Urp = Upl + 2ST for Upl > or = 2ST
Urp = 2Upl for Upl < 2ST
where T is the travel time of the lightning surge L/c.
Actual voltage at the transformer oscillates due the ‘arrival’ and ‘departure’ of the traveling waves but the maximum value is Urp.
3/6/2014
73
Insulation Coordination Course
145
Disadvantages of simplified method:
1. Does not take the capacitance of transformers or reactors into account
2. Real VI characteristic of the arrester is not used
3. Does not take the effect of the power frequency voltage into account
Insulation Coordination Course
146
Switching surges within stations:
• Are ‘man-made’ events and generally more an issue for lines than for stations; however, station equipment and clearances must be capable of withstanding the applicable rated switching surge withstand voltages and surge arresters must provide the corresponding overvoltage protection. Equipment standards fix a certain ratio between rated lightning and switching impulse voltages as we have seen earlier.
• Surge arresters are applied to limit switching overvoltages within stations for the switching of shunt capacitor banks. This is a special case usually requiring a computer study to determine energy requirements in particular but some generalization is possible. Key parameters are discussed in the following.
3/6/2014
74
Insulation Coordination Course
147
Clearances: two types of clearances to consider
• Station air clearances
• Surge arrester clearances
to ground
to energized equipment on same phase
Insulation Coordination Course
148
Statistical nature of electrical breakdown
3/6/2014
75
Insulation Coordination Course
149
Statistical nature of electrical breakdown (cont/d)
• Applied voltage must exceed critical value (field strength) where cumulative ionization is possible
• Statistical time lag ts from application of voltage to the time of creation of the first free electron – time lag decreases with increasing voltage
• Once electron found must further generate a streamer, then streamer converts to a spark – formative time lag tf
Insulation Coordination Course
150
Statistical nature of electrical breakdown (cont/d)
• Vs must be high enough for ionization to occur and sustained for duration longer than the total time lag
• Total time lag ts+tf not the same for each voltage application – same voltage waveform may or may not cause breakdown and therefore it is a probabilistic event
• Question: what does this mean for lightning impulses and switching surges?
3/6/2014
76
Insulation Coordination Course
151
Influencing factors on breakdown:
• Waveshape: breakdown voltage dependent on impulse voltage and its profile over time
• Gap configuration: more of an influence on switching impulses than lightning impulses
• Polarity: breakdown voltage lowest for positive impulses
Insulation Coordination Course
152
Influence of waveshape: lightning impulses:
• Lightning impulses represented by a standard1.2/50 µs waveshape
• Duration of voltage around the peak does not give enough time for leaders to develop and breakdown is dependent on streamers only
• Breakdown (aka sparkover) voltage Vs given by:
Vs = Esd
where Es is the electric field gradient and d is the gap length
3/6/2014
77
Insulation Coordination Course
153
• Rod-plane gaps have the lowest breakdown voltages for all gap configurations; for positive standard lightning impulses for such gaps 1 to10 m (IEC 60071-2):
U50RP = 530d
U50RP is the 50% probability of flashover voltage in kV crest
d is the gap spacing in m
Insulation Coordination Course
154
• For other gap configurations such as rod-rod, U50 can be as high as 700d (rod-plane and rod-rod gaps tend to represent two extremes)
• For rod-plane gaps up to 6 m and negative standard lightning impulses:
U50RP = 950d0.8
and can be as low as 700d0.8 for other gaps
3/6/2014
78
Insulation Coordination Course
155
0
1000
2000
3000
4000
5000
6000
7000
8000
0 2 4 6 8 10
Gap length (m)
U50
flas
hove
r val
ue (k
V cr
est)
Rod-plane positiveRod-rod positiveRod-plane negative
Insulation Coordination Course
156
Important notes for lightning impulses:1. Gap factors (to be discussed for switching impulses) are
generally not directly applicable
2. Because positive impulses give the lowest breakdown values does not mean that negative impulses can be ignored; most lightning surges have negative polarity and internal insulation (e.g. in a transformer) has lower withstand for negative impulses
3. Above-noted equations apply at sea level
3/6/2014
79
Insulation Coordination Course
157
Influence of waveshape: switching impulses• Switching impulses represented by a standard rise time of
250 µs and a time to half-value of 2500 µs
• Breakdown is dependent on gap configuration and hence the use of gap factor
• Breakdown also dependent on voltage rise time giving so-called U-curves
Insulation Coordination Course
158
Rod-plane gaps: K = 1
0
500
1000
1500
2000
2500
3000
3500
4000
0 5 10 15 20 25
Gap length (m)
U50
flas
hove
r val
ue (k
V cr
est)
EdF
H arbec-M enemeniis
IEC 60071
M eek-C raggs
3/6/2014
80
Insulation Coordination Course
159
So what is the gap factor? The gap factor represents the influence of the electrode configuration
* dependent on length of grounded rod (5 m in this case)
Configuration Gap factor
Rod-plane 1
Conductor-plane 1.15
Vertical rod-rod 1.4*
Insulation Coordination Course
160
* IEC 60071-2
Configuration α = 0.5 α = 0.33Ring-ring 1.8 1.7
Crossed conductors 1.65 1.53Conductor-conductor 1.62 1.52
Supported busbars (including fittings) 1.5 1.4
Gap factors for phase-to-phase configurations*:
3/6/2014
81
Insulation Coordination Course
161
Lightning versus switching impulse: rod-plane and rod-rod gaps:
0
500
1000
1500
2000
2500
0 1 2 3 4 5
Gap length (m)
U50
flas
hove
r val
ues
(kV
cres
t)
IEC 60071
Meek-CraggsIEC*1.4Meek-Craggs*1.4Lightning
Insulation Coordination Course
162
0
500
1000
1500
2000
2500
0 0.5 1 1.5 2 2.5 3
Gap length (m)
U50
flas
hove
r val
ues
(kV
cres
t)
IEC 60071Meek-CraggsIEC*1.4Meek-Craggs*1.4
Lightning
3/6/2014
82
Insulation Coordination Course
163
Arrester minimum clearances phase to ground:
• Because arresters are self-protecting lower minimum clearances than station minimum clearances can be used
• Consult the appropriate manufacturer catalog or instruction manual for their recommended minimum clearances
Insulation Coordination Course
164
Arrester rated voltage(kV rms)
Minimum clearance phase-to-ground (mm)for
Mfr 1 Mfr 2 Mfr 3 Mfr 4 Mfr 512 92 115 216 127 9215 118 115 216 147 12221 168 165 229 190 15424 168 165 279 216 18260 448 505 483 407 41666 499 505 - 457 45872 549 505 508 508 500
120 829 870 914 813 832132 905 1140 965 889 916144 981 1140 1168 991 998192 1270 1345 1448 1334 1198216 1473 1465 1854 1611 1292258 1599 1925 2337 1842 1612396 - 2270 3530 2921 2475
Surge Arrester ManufacturerRecommended Minimum Clearances Phase-to-Ground
3/6/2014
83
Insulation Coordination Course
165
Surge arrester clearances to energized equipment on the same phase:
• Energized equipment on the same phase includes transformer bushings (arrester on an outrigger), CVTs or PTs, post insulators and so on
• Arrester voltage distribution determined by grading rings and proximity to other equipment on same phase really only an issue where pollution is a consideration; however what about tight fit scenarios?
Insulation Coordination Course
166
Distribution system arrester practices:
• On overhead systems arresters applied at the cable riser pole from substation and possibly on pole-top transformers in very lightning prone areas
• On underground systems, arresters applied at the cable riser pole and at open points in the underground circuit; other measures may include paralleling arresters at the riser pole or applying a surge arrester at next pole with or without a groundwire
3/6/2014
84
Insulation Coordination Course
167
TWENTY-ONE QUESTIONS
1. What are the voltages considered in insulation coordination?
2. Which overvoltage determines the rated voltage of the surge arrester to be used?
3. Metal oxide material consists of zinc oxide plus various additives: which additive gives the non-linear VI characteristic?
Insulation Coordination Course
168
4. Which four points are used to define the VI characteristic of the required surge arrester?
5. Which quantities define arrester energy handling capability?
6. Which test defines the relationship between arrester rated voltage and rated thermal energy?
3/6/2014
85
Insulation Coordination Course
169
7. What determines the withstand capability of the arrester housing?
8. How is the required creepage distance for the arrester housing selected?
9. How should the required pressure relief capability for the arrester be selected?
Insulation Coordination Course
170
10. With respect to lightning, what representative quantity is used for station insulation coordination?
11. If the required protective levels are not met, what additional measures can be applied to resolve it?
12. Why is there no distance effect for switching surges?
3/6/2014
86
Insulation Coordination Course
171
13. What determines the required clearances for surge arrester installation?
14. Why is the separation distance arrester to transformer so important?
15. What is the effect on added capacitance on incoming surges?
Insulation Coordination Course
172
16. What are the characteristic waveshapes for lightning and switching surges?
17. What is a gap factor?
18. Which electrode configuration has the lowest switching surge withstand capability?
3/6/2014
87
Insulation Coordination Course
173
19. Rated lightning withstand capability for a transformer is deterministic: what is the expected probability of withstand?
20. Rated lightning withstand capability for a circuit breaker is probabilistic: what is the expected probability of failure?
21. More questions?
Insulation Coordination Course
Thanks for listening!
174