SEPTEMBER 5 - 7, 2018
Understanding the Value of Electrical Testing for Power Transformers
Charles Sweetser - OMICRON
SEPTEMBER 5 - 7, 2018
Transformers
SEPTEMBER 5 - 7, 2018
Diagnostic Testing - OVERALL
• DGA
• Oil Screen
• Power Factor / Capacitance
• Exciting Current
• Transformer Turns Ratio
• Leakage Reactance
• DC Winding Resistance
• SFRA (Sweep Frequency Response Analysis)
• DFR (Dielectric Frequency Response)
• Thermal Imaging
• Insulation Resistance
• Partial Discharge
SEPTEMBER 5 - 7, 2018
Transformer Tests
Dielectric Thermal Mechanical
DGA DGA SFRAOil Screen Oil Screen Leakage ReactancePF/TD CAP IR PF/TD CAPExciting Ima DC Winding RES Exciting ImaTurns Ratio Tests DC Winding RESDFRInsulation Resistance
SEPTEMBER 5 - 7, 2018
Transformer Test Protocol
1. Overall Power Factor and Capacitance
2. Bushings (C1, C2, Hot Collar)
3. Exciting Current
4. Surge Arresters
5. Insulating Fluids
6. Leakage Reactance
7. Turns Ratio Test
8. Insulation Resistance
9. IR
10. DFR
11. SFRA
12. DC Winding Resistance
SEPTEMBER 5 - 7, 2018
1. Overall Power Factor and Capacitance2. Bushing Power Factor and Capacitance3. Exciting Current Test4. TTR – Transformer Turns Ratio5. Leakage Reactance (3-Phase Equivalent and
Per Phase)6. DC Winding Resistance
Diagnostic Tests
SEPTEMBER 5 - 7, 2018
• IEEE C57.152-2013, "IEEE Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors".
• ANSI/NETA MTS-2015, "Standard for Maintenance Testing Specifications for Electrical Power Equipment and Systems".
• IEEE C57.149-2012, "IEEE Guide for the Application and Interpretation of Frequency Response Analysis for Oil-Immersed Transformers".
Industry Guides and Standards
SEPTEMBER 5 - 7, 2018
Delta-Wye (Dyn1)
SEPTEMBER 5 - 7, 2018
Two-Winding Transformer Model
• Windings are short-circuited to remove unwanted inductance• CH, CL and CHL insulation systems• CH includes H-C1• CL includes X-C1
SEPTEMBER 5 - 7, 2018
1) Ensure that the transformer tank and core are solidly grounded, also connect both the test instrument and power source ground to this point. We will refer to this point as the “GROUND” node.
2) Ensure that all bushing surfaces are clean and dry.3) Completely isolate the transformer terminals; remove external
connections and buswork from H1, H2, H3, X1, X2, X3 and X0.4) Bond/short the H1, H2, and H3, making sure that they are isolated. We
will refer to this point as the “HV” node.5) Bond/short the X1, X2, X3, and X0 making sure that they are isolated. We
will refer to this point as the “LV” node.6) Document tap-positions, temperatures, humidity, fluid levels, and
pressures.
Overall Power Factor - Test Preparation
SEPTEMBER 5 - 7, 2018
Overall Power Factor - Test Procedure
Test Insulation Test Voltage * Test Mode Energize Red LV Lead1 CH + CHL 10 kV GST HV LV
2a CH 10 kV GST-gA HV LV2b CH(f) 2 kV (15-400 Hz) GST-gA HV LV3a CHL 10 kV UST-A HV LV3b CHL(f) 2 kV (15-400 Hz) UST-A HV LV
4 CL + CLH 7 kV GST LV HV5a CL 7 kV GST-gA LV HV5b CL(f) 2 kV (15-400 Hz) GST-gA LV HV6a CLH 7 kV UST-A LV HV6b CLH(f) 2 kV (15-400Hz) UST-A LV HV
• The test voltages will be limited and should not exceed the line-to-ground rating of the insulation system.
• When convenient, Variable Frequency Power Factor Tests will be performed on CH, CL, and CHL insulation components, along with Power Factor Tip-Up measurements.
SEPTEMBER 5 - 7, 2018
IEEE C57.152
• PF < 0.5% at 20 °C for “new” liquid filled power transformers rated under 230kV• PF < 0.4% at 20 °C for “new” liquid filled power transformers rated over 230kV • PF < 1.0% at 20 °C for “service aged” liquid filled power transformers• PFs between 0.5% and 1.0% at 20 °C warrant additional testing and investigation
NETA MTS
• PF < 1.0% for liquid filled power transformers• PF < 2.0% for liquid field distribution transformers• PF < 2.0% for dry-type power transformers (CHL insulation)• PF < 5.0% for dry-type distribution transformers (CHL insulation)• PF Tip-Up for dry-type insulation should be < 1.0%
Note: Measured values should also be compared to the manufacturer’s published data.
Overall Power Factor - Expected Results
SEPTEMBER 5 - 7, 2018
Bushing Power Factor
Condenser Bushing with Potential Tap
Condensers Bushing with TestTap Non Condenser
Visual Inspection Visual Inspection Visual Inspection
C1 Power Factor (60 Hz) C1 Power Factor (60 Hz) Energize Collar Test
C1 Capacitance (60 Hz) C1 Capacitance (60 Hz) Infrared Test
C2 Power Factor (2.0 kV) C2 Power Factor (0.5 kV)
C2 Capacitance (2.0 kV) C2 Capacitance (0.5kV)
Advance Power Factor Measurements
Advance Power Factor Measurements
Power Factor Tip Up Test Power Factor Tip Up Test
Infrared Test Infrared Test
SEPTEMBER 5 - 7, 2018
Bushing Power Factor – Test Connections
C2C1
Hot Collar
SEPTEMBER 5 - 7, 2018
• Bushings shall remain shorted, similar to the overall power factor test. Failure to short the bushing terminals, may result in compromised measurements.
• Hot Collar tests are optional; they will not be performed if test taps or potential taps are available.
• Test taps and potential taps can be identified, based on the bushing rating, as follows:
– Test Taps <= 350 kV BIL– Potential Taps > 350 kV BIL
• C2 tests must be performed carefully, ensuring that the “hook” is in the clear, completely.
• The C1 results should compare well with the nameplate data. C1 Power Factor values should not exceed 1.5X to 2.0X nameplate data. C1 capacitance should not exceed +/- 5% of nameplate data.
• C2 values should compare well with the nameplate or amongst similar bushings.
• The hot collar results are analyzed from watts loss. We expect less than 100 mW loss.
Bushing Power Factor - Expected Results
SEPTEMBER 5 - 7, 2018
Transformer Exciting Current Test
Vs
1. Apply Voltage Vs on on primary phase, secondary winding left floating2. Measure currurent Iex3. The current required to force ``transformer action´´ (the use of one
winding to induce a voltage in the second winding).
SEPTEMBER 5 - 7, 2018
Exciting Currents - Analysis Strategy
• Confirm Expected Phase Pattern
• Confirm Expected LTC Pattern(For load tap changing transformers)
• Compare to Previous Results
SEPTEMBER 5 - 7, 2018
Exciting Current - Analyzing ResultsConfirming the Expected Phase Pattern:
1. High – Low – High (HLH) Pattern Expected for a 3-legged core type transformer. Expected for a 5-legged core (or shell) type transformer with a Delta
connected secondary winding.
2. Low – High – Low (LHL) Pattern Will be obtained on a 3-legged core type transformer if the traditional
test protocals are not followed.Neutral on high side Wye-configured transformer is inaccessibleForget to ground 3rd terminal on a Delta-connected transformer
Expected for a 4-legged core type transformer.
3. All 3 Similar Pattern Expected for a 5-legged core (or shell) type transformer with a non-
delta secondary winding.
SEPTEMBER 5 - 7, 2018
Exciting Current Test Results
Transformer: Delta – Wye (Dyn1)
X1
X2
X3
X0
H1 H3
H2
Test HV Lead LV Lead Ground Float Mode Measure Result
1 H1 H3 H2, X0 X1,X2,X3 UST H1-H3 63.8 mA
2 H2 H1 H3, X0 X1,X2,X3 UST H2-H1 48.6 mA
3 H3 H2 H1, X0 X1,X2,X3 UST H3-H2 64.2 mA
SEPTEMBER 5 - 7, 2018
Turn Ratio - Expected Results
SEPTEMBER 5 - 7, 2018
Turn Ratio - Expected Results
The turn ratio measurement results should be within 0.5% of nameplate markings.
SEPTEMBER 5 - 7, 2018
Leakage Reactance
SEPTEMBER 5 - 7, 2018
Leakage Reactance
• Short circuit LV winding or “winding pairs”• Inject 0.5 - 1.0% of rated current 60 Hz (Line-to-Line)• A variable 280 VAC source is recommended• Measure Series Current and Terminal Voltage• RESULT - ZΩ, RΩ, and XΩ
• There are two ways to perform the measurement1. 3 Phase Equivalent2. Per Phase
SEPTEMBER 5 - 7, 2018
Leakage Reactance - Example
Phase V I Z R X L
H1-H3 55.22 1.05 51.59 4.38 51.41 136.4H2-H1 54.68 1.05 51.15 4.37 50.96 135.2H3-H2 54.46 1.05 50.96 4.46 50.76 134.2
Nameplate: 6.85% 69 kV 12.5 MVA
SEPTEMBER 5 - 7, 2018
DC Winding Resistance - Failure Modes
A change greater than the criteria mentioned can be indicative of the following:
1. Shorted Circuited Turns
2. Open Turns
3. Defective DETC or LTC (contacts)
4. A Poor Connection Between Terminals Measured
SEPTEMBER 5 - 7, 2018
DC Winding Resistance - Case Study
SEPTEMBER 5 - 7, 2018
Conclusion
• When performed properly, electrical diagnostic testing can provide useful and in depth information regarding the condition of the power transformer. Dielectric, thermal, and mechanical incipient failure modes can be identified.
• Care should be taken to ensure useful results. The test data is only as good as the technician performing the tests. The technician should always know what to expect; utilizing invalid test data can lead to an undesired result in the decision-making process.
• NETA and IEEE standards and guides provide comprehensive information regarding test plans test procedures test preparations, and analysis of the results.