93 801.0 Scope. The requirements of this chapter shall govern the venting of fuel-burning appliances. 801.1 Venting of Gas Appliances. Low-heat gas appliances shall be vented in accordance with this chapter. Other gas appliances shall be vented in accordance with NFPA 211 or other applicable stan- dards. 801.2 Appliances Fueled by Other Fuels. Appli- ances fueled by fuels other than gas shall be vented in accordance with NFPA 211 and the appliance manufacturer’s instructions. 802.0 Venting of Appliances. 802.1 General. This section recognizes that the choice of venting materials and the methods of installation of venting systems are dependent on the operating characteristics of the appliance. 802.1.1 Categories. The operating characteris- tics of vented appliances can be categorized with respect to positive or negative pressure within the venting system and whether or not the appli- ance generates flue or vent gases that can condense in the venting system. See Section 224.0 for the definition of these vented appliance categories. [NFPA 54:12.2.2] 802.1.2 Installation. Listed vents shall be installed in accordance with Chapter 8 and the manufacturer’s installation instructions. [NFPA 54:12.2.3] 802.1.3 Appliance vents shall not discharge into any space enclosed by screens having openings smaller than one-quarter (1/4) inch (6.4 mm) mesh. 802.2 Specification for Venting. 802.2.1 Connection to Venting Systems. Except as permitted in Section 802.2.2 through 802.2.6, all appliances shall be connected to venting systems. [NFPA 54:12.3.1] 802.2.2 Appliances Not Required to Be Vented. The following appliances shall not be required to be vented [NFPA 54:12.3.2]: 802.2.2.1 Listed ranges. [NFPA 54:12.3.2(1)] 802.2.2.2 Built-in domestic cooking units listed and marked for optional venting. [NFPA 54:12.3.2(2)] 802.2.2.3 Listed hot plates and listed laundry stoves. [NFPA 54:12.3.2(3)] 802.2.2.4 Listed Type 1 clothes dryers exhausted in accordance with Section 504.3.2. [NFPA 54:12.3.2(4)] 802.2.2.5 A single listed booster-type (auto- matic instantaneous) water heater, when designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the appliance is installed with the draft hood in place and unaltered, if a draft hood is required, in a commercial kitchen having a mechanical exhaust system; where installed in this manner, the draft hood outlet shall not be less than thirty-six (36) inches (910 mm) vertically and six (6) inches (150 mm) hori- zontally from any surface other than the appliance. [NFPA 54:12.3.2(5)] 802.2.2.6 Listed refrigerators. [NFPA 54:12.3.2(6)] 802.2.2.7 Counter appliances. [NFPA 54:12.3.2(7)] 802.2.2.8 Room heaters listed for unvented use (see Sections 924.1 and 924.2). [NFPA 54:12.3.2(8)] 802.2.2.9 Direct gas-fired makeup air heaters. [NFPA 54:12.3.2(9)] 802.2.2.10 Other appliances listed for unvented use and not provided with flue collars. [NFPA 54:12.3.2(10)] 802.2.2.11 Specialized appliances of limited input such as laboratory burners or gas lights. [NFPA 54:12.3.2(11)] Where any or all of the appliances in Sections 802.2.2.5 through 802.2.2.11 are installed so the aggregate input rating exceeds twenty (20) Btu/h/ft. 3 (207 W/m 3 ) of room or space in which it is installed, one or more shall be provided with venting systems or other approved means for removing the vent gases to the outside atmosphere so the aggregate input rating of the remaining unvented appliances do not exceed twenty (20) Btu/h/ft. 3 (207 W/m 3 ). Where the calculation includes the volume of an adjacent room or space, the room or CHAPTER 8 CHIMNEYS AND VENTS
Transcript
Page 1: Uniform Mechanical Code- 2009 Chapter 8

93

801.0 Scope.The requirements of this chapter shall govern theventing of fuel-burning appliances.801.1 Venting of Gas Appliances. Low-heat gasappliances shall be vented in accordance with thischapter. Other gas appliances shall be vented inaccordance with NFPA 211 or other applicable stan-dards.801.2 Appliances Fueled by Other Fuels. Appli-ances fueled by fuels other than gas shall be ventedin accordance with NFPA 211 and the appliancemanufacturer’s instructions.

802.0 Venting of Appliances.802.1 General. This section recognizes that thechoice of venting materials and the methods ofinstallation of venting systems are dependent on theoperating characteristics of the appliance.

802.1.1 Categories. The operating characteris-tics of vented appliances can be categorized withrespect to positive or negative pressure withinthe venting system and whether or not the appli-ance generates flue or vent gases that cancondense in the venting system. See Section224.0 for the definition of these vented appliancecategories. [NFPA 54:12.2.2]802.1.2 Installation. Listed vents shall beinstalled in accordance with Chapter 8 and themanufacturer’s installation instructions. [NFPA54:12.2.3]802.1.3 Appliance vents shall not discharge intoany space enclosed by screens having openingssmaller than one-quarter (1/4) inch (6.4 mm)mesh.

802.2 Specification for Venting.802.2.1 Connection to Venting Systems.Except as permitted in Section 802.2.2 through802.2.6, all appliances shall be connected toventing systems. [NFPA 54:12.3.1]802.2.2 Appliances Not Required to BeVented. The following appliances shall not berequired to be vented [NFPA 54:12.3.2]:

802.2.2.1 Listed ranges. [NFPA 54:12.3.2(1)]802.2.2.2 Built-in domestic cooking unitslisted and marked for optional venting.[NFPA 54:12.3.2(2)]

802.2.2.3 Listed hot plates and listedlaundry stoves. [NFPA 54:12.3.2(3)]802.2.2.4 Listed Type 1 clothes dryersexhausted in accordance with Section504.3.2. [NFPA 54:12.3.2(4)]802.2.2.5 A single listed booster-type (auto-matic instantaneous) water heater, whendesigned and used solely for the sanitizingrinse requirements of a dishwashingmachine, provided that the appliance isinstalled with the draft hood in place andunaltered, if a draft hood is required, in acommercial kitchen having a mechanicalexhaust system; where installed in thismanner, the draft hood outlet shall not beless than thirty-six (36) inches (910 mm)vertically and six (6) inches (150 mm) hori-zontally from any surface other than theappliance. [NFPA 54:12.3.2(5)]802.2.2.6 Listed refrigerators. [NFPA54:12.3.2(6)]802.2.2.7 Counter appliances. [NFPA54:12.3.2(7)]802.2.2.8 Room heaters listed for unventeduse (see Sections 924.1 and 924.2). [NFPA54:12.3.2(8)]802.2.2.9 Direct gas-fired makeup airheaters. [NFPA 54:12.3.2(9)]802.2.2.10 Other appliances listed forunvented use and not provided with fluecollars. [NFPA 54:12.3.2(10)]802.2.2.11 Specialized appliances of limitedinput such as laboratory burners or gaslights. [NFPA 54:12.3.2(11)]

Where any or all of the appliances inSections 802.2.2.5 through 802.2.2.11 areinstalled so the aggregate input ratingexceeds twenty (20) Btu/h/ft.3 (207 W/m3)of room or space in which it is installed, oneor more shall be provided with ventingsystems or other approved means forremoving the vent gases to the outsideatmosphere so the aggregate input rating ofthe remaining unvented appliances do notexceed twenty (20) Btu/h/ft.3 (207 W/m3).Where the calculation includes the volumeof an adjacent room or space, the room or

CHAPTER 8CHIMNEYS AND VENTS

Page 2: Uniform Mechanical Code- 2009 Chapter 8

space in which the appliance is installedshall be directly connected to the adjacentroom or space by a doorway, archway, orother opening of comparable size thatcannot be closed. [NFPA 54:12.3.2]

802.2.3 Ventilating Hoods. Ventilating hoodsand exhaust systems shall be permitted to beused to vent appliances installed in commercialapplications (see Section 802.3.5) and to ventindustrial appliance, particularly where theprocess itself requires fume disposal. [NFPA54:12.3.3]802.2.4 Well-Ventilated Spaces. The operationof industrial appliances such that its flue gasesare discharged directly into a large and well-ventilated space shall be permitted. [NFPA54:12.3.4]802.2.5 Direct-Vent Appliance. Listed direct-vent appliances shall be considered properlyvented where installed in accordance with theterms of its listing, the manufacturer’s instruc-tions, and Section 802.8.3. [NFPA 54:12.3.5]802.2.6 Appliances with Integral Vents. Appli-ances incorporating integral venting means shallbe considered properly vented where installedin accordance with its listing, the manufacturer'sinstructions, and Sections 802.8.1 and 802.8.2.[NFPA 54:12.3.6]

802.3 Design and Construction.802.3.1 Minimum Safe Performance. Aventing system shall be designed andconstructed so as to develop a positive flowadequate to remove flue or vent gases to theoutside atmosphere. [NFPA 54:12.1]802.3.2 Appliance Draft Requirements. Aventing system shall satisfy the draft require-ments of the appliance in accordance with themanufacturer's instructions. [NFPA 54:12.4.1]802.3.3 Design and Construction. Appliancesrequired to be vented shall be connected to aventing system designed and installed in accor-dance with the provisions of Sections 802.4through 802.15. [NFPA 54:12.4.2]802.3.4 Mechanical Draft Systems.

802.3.4.1 Mechanical draft systems shall belisted and shall be installed in accordance withthe terms of their listing and both the appli-ance and the mechanical draft system manu-facturer's instructions. [NFPA 54:12.4.3.1]802.3.4.2 Appliances requiring venting shallbe permitted to be vented by means ofmechanical draft systems of either forced orinduced draft design. [NFPA 54:12.4.3.2]

Exception: Incinerators.

802.3.4.3 Forced draft systems and allportions of induced draft systems underpositive pressure during operation shall bedesigned and installed so as to preventleakage of flue or vent gases into a building.[NFPA 54:12.4.3.3]802.3.4.4 Vent connectors serving appli-ances vented by natural draft shall not beconnected into any portion of mechanicaldraft systems operating under positive pres-sure. [NFPA 54:12.4.3.4]802.3.4.5 Where a mechanical draft systemis employed, provision shall be made toprevent the flow of gas to the main burnerswhen the draft system is not performing soas to satisfy the operating requirements ofthe appliance for safe performance. [NFPA54:12.4.3.5]802.3.4.6 The exit terminals of mechanicaldraft systems shall be not less than seven (7)feet (2,134 mm) above grade where locatedadjacent to public walkways and shall belocated as specified in Sections 802.8.1 and802.8.2. [NFPA 54:12.4.3.6]

802.3.5 Ventilating Hoods and ExhaustSystems.

802.3.5.1 Ventilating hoods and exhaustsystems shall be permitted to be used tovent appliances installed in commercialapplications. [NFPA 54:12.4.4.1]802.3.5.2 Where automatically operatedappliances are vented through a ventilatinghood or exhaust system equipped with adamper or with a power means of exhaust,provisions shall be made to allow the flow ofgas to the main burners only when thedamper is open to a position to properly ventthe appliance and when the power means ofexhaust is in operation. [NFPA 54:12.4.4.2]

802.3.6 Circulating Air Ducts and FurnacePlenums. No portion of a venting system shallextend into or pass through any circulating airduct or furnace plenum. [NFPA 54:12.4.5.1]

802.4 Type of Venting System to Be Used.802.4.1 The type of venting system to be usedshall be in accordance with Table 8-1. [NFPA54:12.5.1]802.4.2 Plastic Piping. Plastic piping used forventing appliances listed for use with suchventing materials shall be approved. [NFPA54:12.5.2]802.4.3 Plastic Vent Joints. Plastic pipe andfittings used to vent appliances shall be installedin accordance with the appliance manufacturer’s

UNIFORM MECHANICAL CODE802.2 – 802.4

94

Page 3: Uniform Mechanical Code- 2009 Chapter 8

installation instructions. Where primer isrequired, it shall be of a contrasting color.[NFPA 54-09:12.5.3]802.4.4 Special Gas Vent. A special gas ventshall be listed and installed in accordance withthe terms of the special gas vent listing and themanufacturer's instructions. [NFPA 54:12.5.3]

802.5 Masonry, Metal, and Factory-Built Chimneys.802.5.1 Listing or Construction.

802.5.1.1 Factory-built chimneys shall beinstalled in accordance with their listing andthe manufacturer's instructions. Factory-builtchimneys used to vent appliances thatoperate at positive vent pressure shall belisted for such application. [NFPA 54:12.6.1.1]802.5.1.2 Metal chimneys shall be built andinstalled in accordance with NFPA 211,Standard for Chimneys, Fireplaces, Vents, andSolid-Fuel-Burning Appliances. [NFPA54:12.6.1.2]802.5.1.3 Masonry chimneys shall be builtand installed in accordance with NFPA 211,Standard for Chimneys, Fireplaces, Vents, andSolid Fuel-Burning Appliances, and lined withan approved clay flue lining, a listedchimney lining system, or other approvedmaterial that will resist corrosion, erosion,softening, or cracking from vent gases attemperatures up to 1,800°F (982°C).

Exception:Masonry chimney flues linedwith a chimney lining system specifi-cally listed for use with listed gas appli-ances with draft hoods, Category Iappliances, and other gas applianceslisted for use with Type B vents shall bepermitted. The liner shall be installed inaccordance with the liner manufactur-er's instructions and the terms of thelisting. A permanent identifying labelshall be attached at the point where theconnection is to be made to the liner.The label shall read: "This chimney lineris for appliances that burn gas only. Donot connect to solid or liquid fuel-burning appliances or incinerators."[NFPA 54:12.6.1.3]

802.5.2 Termination.802.5.2.1 A chimney for residential-type orlow-heat appliances shall extend at leastthree (3) feet (914 mm) above the highestpoint where it passes through a roof of abuilding and at least two (2) feet (610 mm)higher than any portion of a building within

a horizontal distance of ten (10) feet (3,048mm). (See Figure 8-1.) [NFPA 54:12.6.2.1]802.5.2.2 A chimney for medium-heatappliances shall extend at least ten (10) feet(3,048 mm) higher than any portion of anybuilding within twenty-five (25) feet (7,620mm). [NFPA 54:12.6.2.2]802.5.2.3 A chimney shall extend at leastfive (5) feet (1,524 mm) above the highestconnected appliance draft hood outlet orflue collar. [NFPA 54:12.6.2.3]802.5.2.4 Decorative shrouds shall not beinstalled at the termination of factory-builtchimneys except where such shrouds arelisted and labeled for use with the specific

CHIMNEYS AND VENTS 802.4 – 802.5

95

TABLE 8-1Type of Venting System to Be Used

[NFPA 54: Table 12.5.1]Appliance Type of Venting System

Listed Category I applianceListed appliance equippedwith draft hood

Appliance listed for use withType B gas vent

Type B gas vent (802.6)Chimney (802.5)Single-wall metal pipe(802.7)Listed chimney liningsystem for gas venting(802.5.1.3)Special gas vent listed forthis appliance (802.4.4)

Listed vented wall furnaces Type B-W gas vent(802.6, 928.0)

Category II applianceCategory III applianceCategory IV appliance

As specified or furnishedby manufacturers of listedappliance (802.4.2, 802.4.4)

Incinerators, outdoors

Incinerators, indoorsAppliance that can beconverted to use of solid fuel

Single-wall metal pipe(802.7, 802.7.3.3)

Unlisted combination gas- andoil-burning appliance

Combination gas- and solid-fuel-burning appliance

Appliance listed for use withchimneys only

Unlisted applianceListed combination gas- andoil-burning appliance

Chimney (802.5)

Type L vent (802.6) orchimney (802.5)

Decorative appliance invented fireplace

Chimney [907.2]

Gas-fired toilets Single-wall metal pipe(802.7, 926.3)

Direct-vent appliance See 802.2.5Appliance with integral vent See 802.2.6

Page 4: Uniform Mechanical Code- 2009 Chapter 8

factory-built chimney system and areinstalled in accordance with manufacturer' sinstallation instructions. [NFPA 54:12.6.2.4]

802.5.3 Size of Chimneys. The effective area ofa chimney venting system serving listed gasappliances with draft hoods, Category I appli-ances, and other appliances listed for use withType B vents shall be in accordance with one ofthe following methods [NFPA 54:12.6.3.1]:(1) Section 803.0. [NFPA 54:12.6.3.1(1)](2) For sizing an individual chimney venting

system for a single appliance with a drafthood, the effective areas of the ventconnector and chimney flue shall be not lessthan the area of the appliance flue collar ordraft hood outlet or greater than seven timesthe draft hood outlet area. [NFPA54:12.6.3.1(2)]

(3) For sizing a chimney venting systemconnected to two (2) appliances with drafthoods, the effective area of the chimney flueshall be not less than the area of the largerdraft hood outlet plus 50 percent of the areaof the smaller draft hood outlet, or greaterthan seven (7) times the smallest draft hoodoutlet area. [NFPA 54:12.6.3.1(3)]

(4) Other approved engineering methods.[NFPA 54:12.6.3.1(5)]

(5) Chimney venting systems using mechanicaldraft shall be sized in accordance withapproved engineering methods. [NFPA54:12.6.3.1(4)]

802.5.4 Inspection of Chimneys.802.5.4.1 Before replacing an existing appli-ance or connecting a vent connector to achimney, the chimney passageway shall beexamined to ascertain that it is clear and freeof obstructions and shall be cleaned if previ-ously used for venting solid or liquid fuel-burning appliances or fireplaces. [NFPA54:12.6.4.1]802.5.4.2 Chimneys shall be lined in accor-dance with NFPA 211, Standard for Chim-neys, Fireplaces, Vents, and Solid Fuel-BurningAppliances. [NFPA 54:12.6.4.2]

Exception: Existing chimneys shall bepermitted to have their use continuedwhen an appliance is replaced by anappliance or similar type, input rating,and efficiency, where the chimneycomplies with 802.5.4, and the sizing ofthe chimney is in accordance with802.5.3.

UNIFORM MECHANICAL CODEFigure 8-1 – 802.5

96

FIGURE 8-1 Typical Termination Locations forChimneys and Single-Wall Metal Pipes ServingResidential-Type and Low-Heat Appliance.[NFPA 54: Figure 12.6.2.1]

Page 5: Uniform Mechanical Code- 2009 Chapter 8

802.5.4.3 Cleanouts shall be examined todetermine that they will remain tightlyclosed when not in use. [NFPA 54:12.6.4.3]802.5.4.4 When inspection reveals that anexisting chimney is not safe for the intendedapplication, it shall be repaired, rebuilt,lined, relined, or replaced with a vent orchimney to conform to NFPA 211, Standardfor Chimneys, Fireplaces, Vents, and Solid-Fuel-Burning Appliances, and shall be suitable forthe appliance to be attached. [NFPA54:12.6.4.4]

802.5.5 Chimney Serving Appliances BurningOther Fuels.

802.5.5.1 Appliances shall not be connectedto a chimney flue serving a separate appli-ance designed to burn solid fuel. [NFPA54:12.6.5.1]802.5.5.2 Where one (1) chimney serves gasappliances and an appliance burning liquidfuel, the appliances shall be connectedthrough separate openings or shall beconnected through a single opening wherejoined by a suitable fitting located as close aspractical to the chimney. Where two (2) ormore openings are provided into one (1)chimney flue, they shall be at differentlevels. Where the appliance is automaticallycontrolled, it shall be equipped with a safetyshutoff device. [NFPA 54:12.6.5.2]802.5.5.3 A listed combination gas and solidfuel-burning appliance connected to a singlechimney flue shall be equipped with amanual reset device to shut off gas to themain burner in the event of sustained back-draft or flue gas spillage. The chimney flueshall be sized to properly vent the appliance.[NFPA 54: 12.6.5.3]802.5.5.4 A single chimney flue serving alisted combination gas- and oil-burningappliance shall be sized to properly vent theappliance. [NFPA 54:12.6.5.4]

802.5.6 Support of Chimneys. All portions ofchimneys shall be supported for the design andweight of the materials employed. Listedfactory-built chimneys shall be supported andspaced in accordance with their listings and themanufacturers' instructions. [NFPA 54:12.6.6]802.5.7 Cleanouts. Where a chimney thatformerly carried flue products from liquid orsolid fuel-burning appliances is used with anappliance using fuel gas, an accessible cleanoutshall be provided. The cleanout shall have atight-fitting cover and be installed so its upper

edge is at least six (6) inches (150 mm) below thelower edge of the lowest chimney inlet opening.[NFPA 54:12.6.7]802.5.8 Space Surrounding Lining or Vent.The remaining space surrounding a chimneyliner, gas vent, special gas vent, or plastic pipinginstalled within a masonry chimney flue shallnot be used to vent another appliance. [NFPA54:12.6.8.1]

Exception: The insertion of another liner orvent within the chimney as provided in thiscode and the liner or vent manufacturer'sinstructions.The remaining space surrounding a

chimney liner, gas vent, special gas vent, orplastic piping installed within a masonry, metalor factory-built chimney flue shall not be used tosupply combustion air. [NFPA 54:12.6.8.2]

Exception: Direct vent gas-fired appliancesdesigned for installation in a solid-fuel-burning fireplace where installed in accor-dance with the listing and the manufac-turer’s instruction.

802.6 Gas Vents.802.6.1 A gas vent passing through a roof shallextend through the entire roof flashing, roofjack, or roof thimble and be terminated with alisted termination cap. [NFPA 54:12.7.2(6)]

802.6.1.1 Type B or Type L vents shallextend in a generally vertical direction withoffsets not exceeding 45 degrees, except thata vent system having not more than one 60degree offset shall be permitted. Any anglegreater than 45 degrees from the vertical isconsidered horizontal. The total horizontaldistance of a vent plus the horizontal ventconnector serving draft hood equippedappliances shall not be greater than 75percent of the vertical height of the vent.[NFPA 54:12.7.3.2]

Exception: Systems designed and sizedas provided in Section 803.0 or in accor-dance with other approved engineeringmethods.

Vents serving Category I fan-assisted appliancesshall be installed in accordance with the appli-ance manufacturer's instructions and Section803.0 or other approved engineering methods.[NFPA 54:12.7.1(3)]802.6.2 A gas vent shall terminate in accordancewith one of the following:(1) Above the roof surface with a listed cap or

listed roof assembly. Gas vents twelve (12)inches (300 mm) in size or smaller withlisted caps shall be permitted to be termi-

CHIMNEYS AND VENTS 802.5 – 802.6

97

Page 6: Uniform Mechanical Code- 2009 Chapter 8

nated in accordance with Figure 8-2,provided they are at least eight (8) feet(2,438 mm) from a vertical wall or similarobstruction. All other gas vents shall termi-nate not less than two (2) feet (610 mm)above the highest point where they passthrough the roof and at least two (2) feet(610 mm) higher than any portion of abuilding within ten (10) feet (3,048 mm).[NFPA 54:12.7.2(1)(a) and (b)]

(2) Industrial appliance provided in Section802.2.4. [NFPA 54:12.7.2(1)(c)]

(3) Direct-vent systems as provided in Section802.2.5. [NFPA 54:12.7.2(1)(d)]

(4) Appliance with integral vents as provided inSection 802.2.6. [NFPA 54:12.7.2(1)(e)]

(5) Mechanical draft systems as provided inSection 802.3.4. [NFPA 54:12.7.2(1)(f)]

(6) Ventilating hoods and exhaust systems asprovided in Section 802.3.5. [NFPA54:12.7.2(1)(g)]802.6.2.1 A Type B or a Type L gas ventshall terminate at least five (5) feet (1,524mm) in vertical height above the highestconnected appliances draft hood or fluecollar. [NFPA 54:12.7.2(2)]

802.6.2.2 A Type B-W gas vent shall termi-nate at least twelve (12) feet (3,658 mm) invertical height above the bottom of the wallfurnace. [NFPA 54:12.7.2(3)]802.6.2.3 A gas vent extending through anexterior wall shall not terminate adjacent tothe wall or below eaves or parapets, exceptas provided in Sections 802.2.5 and 802.3.4.[NFPA 54:12.7.2(4)]802.6.2.4 Decorative shrouds shall not beinstalled at the termination of gas ventsexcept where such shrouds are listed for usewith the specific gas venting system and areinstalled in accordance with manufacturers'installation instructions. [NFPA 54:12.7.2(5)]802.6.2.5 Gas vents shall extend through theroof flashing, roof jack, or roof thimble andterminate with a listed cap or listed roofassembly. [NFPA 54:12.7.2(6)]802.6.2.6 A gas vent shall terminate at leastthree (3) feet (914 mm) above a forced airinlet located within ten (10) feet (3,048 mm).[NFPA 54:12.7.2(7)]

802.6.3 Size of Gas Vents. Venting systemsshall be sized and constructed in accordancewith Section 803.0 or other approved engi-neering methods and the gas vent and appliancemanufacturers' instructions. [NFPA 54:12.7.3]

802.6.3.1 Category I Appliances. Thesizing of natural draft venting systemsserving one (1) or more listed appliancesequipped with a draft hood or applianceslisted for use with Type B gas vent, installedin a single story of a building, shall be inaccordance with one of the followingmethods. [NFPA 54:12.7.3.1](1) The provisions of Section 803.0. [NFPA

54:12.7.3.1(1)](2) Vents serving fan-assisted combustion

system appliances, or combinations offan-assisted combustion system anddraft hood-equipped appliances shall besized in accordance with Section 803.0or other approved engineering methods.[NFPA 54:12.7.3.1(2)]

(3) For sizing an individual gas vent for asingle, draft hood-equipped appliance,the effective area of the vent connectorand the gas vent shall be not less than thearea of the appliance draft hood outlet orgreater than seven (7) times the drafthood outlet area. [NFPA 54:12.7.3.1(3)]

(4) For sizing a gas vent connected to two(2) appliances, with draft hoods, the

UNIFORM MECHANICAL CODE802.6

98

FIGURE 8-2 Gas Vent Termination Locations forListed Caps 12 in. (300 mm) or Less in Size atLeast 8 ft. (2.4 m) from a Vertical Wall. [NFPA 54:Figure 12.7.2]

Page 7: Uniform Mechanical Code- 2009 Chapter 8

effective area of the vent shall be notless than the area of the larger drafthood outlet plus 50 percent of the areaof the smaller draft hood outlet orgreater than seven (7) times the smallerdraft hood outlet area. [NFPA54:12.7.3.1(4)]

(5) Approved engineering practices. [NFPA54:12.7.3.1(5)]

802.6.3.2 Category II, Category III, andCategory IV Appliances. The sizing of gasvents for Category II, Category III, and Cate-gory IV appliances shall be in accordancewith the appliance manufacturer’s instruc-tions. [NFPA 54:12.7.3.3]802.6.3.3 Sizing. Chimney venting systemsusing mechanical draft shall be sized inaccordance with approved engineeringmethods. [NFPA 54:12.7.3.4]

802.6.4 Gas Vents Serving Appliances onMore Than One Floor. A common gas ventshall be permitted in multistory installations tovent Category I appliances located on more thanone floor level, provided the venting system isdesigned and installed in accordance withapproved engineering methods. For the purposeof this section, crawl spaces, basements, andattics shall be considered as floor levels. [NFPA54:12.7.4.1]

All appliances connected to the commonvent shall be located in rooms separated from ahabitable space. Each of these rooms shall haveprovisions for an adequate supply of combus-tion, ventilation, and dilution air that is notsupplied from a habitable space. (See Figure 8-3.) [NFPA 54:12.7.4.2]

The size of the connectors and commonsegments of multistory venting systems forappliances listed for use with Type B double-wall gas vent shall be in accordance with Table8-10, provided [NFPA 54:12.7.4.3]:(1) The available total height (H) for each

segment of a multistory venting system isthe vertical distance between the level of thehighest draft hood outlet or flue collar onthat floor and the centerline of the nexthighest interconnection tee. (See Figure 8-4.)[NFPA 54:12.7.4.3(1)]

(2) The size of the connector for a segment isdetermined from its appliance heat inputand available connector rise, and shall notbe smaller than the draft hood outlet or fluecollar size. [NFPA 54:12.7.4.3(2)]

(3) The size of the common vertical ventsegment, and of the interconnection tee atthe base of that segment, shall be based on

the total appliance heat input entering thatsegment and its available total height.[NFPA 54:12.7.4.3(3)]

802.6.5 Support of Gas Vents. Gas vents shallbe supported and spaced in accordance withtheir listings and the manufacturers' instruc-tions. [NFPA 54:12.7.5]802.6.6 Marking. In those localities where solidand liquid fuels are used extensively, gas ventsshall be permanently identified by a labelattached to the wall or ceiling at a point wherethe vent connector enters the gas vent. The labelshall read: "This gas vent is for appliances thatburn gas. Do not connect to solid or liquid-fuel-burning appliances or incinerators." TheAuthority Having Jurisdiction shall determinewhether its area constitutes such a locality.[NFPA 54:12.7.6]802.6.7 Screws, rivets, and other fasteners shallnot penetrate the inner wall of double wall gasvents, except at the transition from the appliancedraft hood outlet, flue collar or single wall metalconnector to a double wall vent.

802.7 Single-Wall Metal Pipe.802.7.1 Construction. Single-wall metal pipeshall be constructed of galvanized sheet steel notless than 0.0304 inch (0.7 mm) thick or of otherapproved, noncombustible, corrosion-resistantmaterial. [NFPA 54:12.8.1]802.7.2 Cold Climate. Uninsulated single-wallmetal pipe shall not be used outdoors in coldclimates for venting appliances in regions wherethe 99 percent winter design temperature is lessthan 32ºF (0ºC). [NFPA 54:12.8.2]

CHIMNEYS AND VENTS 802.6 – 802.7

99

FIGURE 8-3 Plan View of Practical SeparationMethod for Multistory Gas Venting. [NFPA 54:Figure 12.7.4.2]

Page 8: Uniform Mechanical Code- 2009 Chapter 8

802.7.3 Termination. The termination of single-wall metal pipe shall comply with the followingrequirements: [NFPA 54:12.8.3]

802.7.3.1 Single-wall metal pipe shall termi-nate at least five (5) feet (1,524 mm) in verticalheight above the highest connected appliancedraft hood outlet or flue collar. [NFPA54:12.8.3(1)]802.7.3.2 Single-wall metal pipe shall extendat least two (2) feet (610 mm) above thehighest point where it passes through a roof ofa building and at least two (2) feet (610 mm)higher than any portion of a building within ahorizontal distance of ten (10) feet (3,048 mm).(See Figure 8-1.) [NFPA 54:12.8.3(2)]802.7.3.3 An approved cap or roof assemblyshall be attached to the terminus of a single-wall metal pipe. (Also see Section 802.7.4.4)[NFPA 54:12.8.3(3)]

802.7.4 Installation with Appliances Permittedby Section 802.4.1.

802.7.4.1 Prohibited Use. Single-wall metalpipe shall not be used as a vent in dwellingsand residential occupancies. [NFPA 54-09:12.8.4.1]

802.7.4.2 Single-wall metal pipe shall beused only for runs directly from the space inwhich the appliance is located through theroof or exterior wall to the outer air. A pipepassing through a roof shall extend withoutinterruption through the roof flashing, roofjacket, or roof thimble. [NFPA 54:12.8.4.1]802.7.4.3 Single-wall metal pipe shall notoriginate in any unoccupied attic or concealedspace and shall not pass through any attic,inside wall, concealed space, or floor. For theinstallation of a single-wall metal pipethrough an exterior combustible wall seeSection 802.10.14.2. [NFPA 54:12.8.4.2]802.7.4.4 Single-wall metal pipe used forventing an incinerator shall be exposed andreadily examinable for its full length andshall have suitable clearances maintained.[NFPA 54:12.8.4.3]802.7.4.5 Minimum clearances from single-wall metal pipe to combustible materialshall be in accordance with Table 8-2.Reduced clearances from single-wall metal

UNIFORM MECHANICAL CODETable 8-2 – 802.7

100

TABLE 8-2Clearance for Connectors[NFPA 54: Table 12.8.4.4]

Minimum Distance from Combustible MaterialListed Type B Listed Type L Single-Wall Factory-Built

Appliance Gas Vent Material Vent Material Metal Pipe Chimney Sections

Listed appliance As listed As listed 6 in. As listedwith draft hoods and -appliance listed foruse with Type B gas ventsResidential boilers and 6 in. 6 in. 9 in. As listedfurnaces with listed gasconversion burner andwith draft hoodResidential appliances Not permitted As listed 9 in. As listedlisted for use with TypeL ventsResidential incinerators Not permitted 9 in. 18 in. As listedListed gas-fired toilets Not permitted As listed As listed As listedUnlisted residential Not permitted 6 in. 9 in. As listedappliances with drafthoodResidential and low-heat Not permitted 9 in. 18 in. As listedappliance otherthan those aboveMedium-heat appliance Not permitted Not permitted 36 in. As listedNotes:These clearances shall apply unless the listing of an appliance or connector specifies clearances, in which case the listed clearancesshall apply.1 in.= 25.4 mm

Page 9: Uniform Mechanical Code- 2009 Chapter 8

pipe to combustible material shall be asspecified for vent connectors in Table 5-3.[NFPA 54:12.8.4.4]802.7.4.6 Where a single-wall metal pipepasses through a roof constructed ofcombustible material, a noncombustible,nonventilating thimble shall be used at thepoint of passage. The thimble shall extend atleast eighteen (18) inches (460 mm) aboveand six (6) inches (150 mm) below the roof,with the annular space open at the bottomand closed only at the top. The thimble shallbe sized in accordance with Section802.10.14.2. [NFPA 54:12.8.4.5]

802.7.5 Size of Single-Wall Metal Pipe. Single-wall metal piping shall comply with thefollowing requirements: [NFPA 54:12.8.5]

802.7.5.1 A venting system of a single-wallmetal pipe shall be sized in accordance withone of the following methods and the appli-ance manufacturer's instructions: [NFPA54:12.8.5(1)](1) For a draft hood–equipped appliance, in

accordance with Section 803.0. [NFPA54:12.8.5(1)(a)]

(2) For a venting system for a single appli-ance with a draft hood, the areas of theconnector and the pipe each shall not beless than the area of the appliance fluecollar or draft hood outlet, whichever issmaller. The vent area shall not begreater than seven times the draft hoodoutlet area. [NFPA 54:12.8.5(1)(b)]

(3) Other approved engineering methods.[NFPA 54:12.8.5(1)(c)]

802.7.5.2 Where a single-wall metal pipe isused and has a shape other than round, itshall have an equivalent effective area equalto the effective area of the round pipe forwhich it is substituted, and the minimuminternal dimension of the pipe shall be two(2) inches (50 mm). [NFPA 54:12.8.5(2)]802.7.5.3 The vent cap or a roof assemblyshall have a venting capacity not less thanthat of the pipe to which it is attached.[NFPA 54:12.8.5(3)]

802.7.6 Support of Single-Wall Metal Pipe. Allportions of single-wall metal pipe shall besupported for the design and weight of thematerial employed. [NFPA 54:12.8.6]802.7.7 Marking. Single-wall metal pipe shallcomply with the marking provisions of Section802.6.6. [NFPA 54:12.8.7]

802.8 Through-the-Wall Vent Termination.Through the wall vent termination’s shall be inaccordance with the following:

802.8.1 A mechanical draft venting system shallterminate at least three (3) feet (914 mm) aboveany forced air inlet located within ten (10) feet(3,048 mm). [NFPA 54:12.9.1]

Exception 1: This provision shall not applyto the combustion-air intake of a direct-ventappliance.Exception 2: This provision shall not applyto the separation of the integral outdoor-airinlet and flue gas discharge of listed outdoorappliances.

802.8.2 A mechanical draft venting system ofother than direct-vent type shall terminate at leastfour (4) feet (1,219 mm) below, four (4) feet (1,219mm) horizontally from, or one (1) foot (300 mm)above any door, operable window, or gravity airinlet into any building. The bottom of the ventterminal shall be located at least twelve (12)inches (300 mm) above grade. [NFPA 54:12.9.2]802.8.3 The vent terminal of a direct-vent appli-ance with an input of 10,000 Btu/h (3 kW) or lessshall be located at least six (6) inches (150 mm)from any air opening into a building, and suchan appliance with an input over 10,000 Btu/h (3kW) but not over 50,000 Btu/h (14.7 kW) shall beinstalled with a nine (9) inches (230 mm) venttermination clearance, and an appliance with aninput over 50,000 Btu/h (14.7 kW) shall have atleast a twelve (12) inches (300 mm) vent termina-tion clearance. The bottom of the vent terminaland the air intake shall be located at least twelve(12) inches (300 mm) above grade. [NFPA54:12.9.3]802.8.4 Through-the-wall vents for Category IIand Category IV appliances and noncategorizedcondensing appliances shall not terminate overpublic walkways or over an area where conden-sate or vapor could create a nuisance or hazardor could be detrimental to the operation of regu-lators, relief valves, or other equipment. Wherelocal experience indicates that condensate is aproblem with Category I and Category III appli-ances, this provision shall also apply. Drains forcondensate shall be installed in accordance withthe manufacturer’s installation instructions.[NFPA 54-09:12.9.4]802.8.5 Where vents, including those for direct-vent appliances, penetrate outside walls ofbuildings, the annular spaces around such pene-trations shall be permanently sealed usingapproved materials to prevent entry of combus-tion products into the building. [NFPA 54-09:12.9.6]

CHIMNEYS AND VENTS 802.7 – 802.8

101

Page 10: Uniform Mechanical Code- 2009 Chapter 8

802.9 Condensation Drain.802.9.1 Provision shall be made to collect anddispose of condensate from venting systemsserving Category II and Category IV appliancesand noncategorized condensing appliances inaccordance with Section 802.8.4. [NFPA54:12.10.1]802.9.2 Where local experience indicates thatcondensation is a problem, provision shall bemade to drain off and dispose of condensatefrom venting systems serving Category I andCategory III appliances in accordance withSection 802.8.4. [NFPA 54:12.10.2]

802.10 Vent Connectors for Category I Appli-ances.

802.10.1 Where Required. A vent connectorshall be used to connect appliances to a gas vent,chimney, or single-wall metal pipe, exceptwhere the gas vent, chimney, or single-wallmetal pipe is directly connected to the appliance.[NFPA 54:12.11.1]802.10.2 Materials.

802.10.2.1 A vent connector shall be made ofnoncombustible, corrosion-resistant materialcapable of withstanding the vent gas temper-ature produced by the appliance and of suffi-cient thickness to withstand physicaldamage. [NFPA 54:12.11.2.1]802.10.2.2 Where the vent connector usedfor appliances having a draft hood or aCategory I appliance is located in or passesthrough an unconditioned area, that portionof the vent connector shall be listed Type B,Type L, or listed vent material having equiv-alent insulation qualities. [NFPA54:12.11.2.2]

Exception: Single-wall metal pipelocated within the exterior walls of thebuilding and located in areas having alocal 99 percent winter design tempera-ture of 5ºF (-15ºC) or higher.

802.10.2.3 Where the vent connector usedfor appliances having a draft hood or aCategory I appliance is located in or passesthrough attics and crawl spaces, that portionof the vent connector shall be listed Type B,Type L, or listed vent material having equiv-alent insulation qualities. [NFPA54:12.11.2.3]802.10.2.4 Vent connectors for residential-type appliances shall comply with thefollowing: [NFPA 54:12.11.2.4](1) Vent connectors for listed gas appli-

ances having draft hoods and for appli-

ances having draft hoods and equippedwith listed conversion burners that arenot installed in attics, crawl spaces, orother unconditioned areas shall be oneof the following: [NFPA 54:12.11.2.4(1)](a) Type B or Type L vent material.(b) Galvanized sheet steel not less than

0.018 in. (0.46 mm) thick.(c) Aluminum (1100 or 3003 alloy or

equivalent) sheet not less than 0.027in. (0.69 mm) thick.

(d) Stainless steel sheet not less than0.012 in. (0.31 mm) thick.

(e) Smooth-interior-wall metal pipehaving resistance to heat andcorrosion equal to or greater thanthat of b, c, or d above.

(f) A listed vent connector.(2) Vent connectors shall not be covered

with insulation. [NFPA 54:12.11.2.4(2)]Exception: Listed insulated ventconnectors shall be installedaccording to the terms of theirlisting in accordance with themanufacturer’s installation instruc-tions.

802.10.2.5 A vent connector for non-residen-tial low-heat appliance shall be a factory-built chimney section or steel pipe havingresistance to heat and corrosion equivalent tothat for the appropriate galvanized pipe asspecified in Table 8-3. Factory-built chimneysections shall be joined together in accor-dance with the chimney manufacturer'sinstructions. [NFPA 54:12.11.2.5]802.10.2.6 Vent connectors for medium-heat appliances, commercial and industrialincinerators shall be constructed of factory-built, medium-heat chimney sections orsteel of a thickness not less than that speci-

UNIFORM MECHANICAL CODE802.9 – Table 8-3

102

TABLE 8-3Minimum Thickness for Galvanized Steel Vent

Connectors for Low-Heat Appliances[NFPA 54: Table 12.11.2.5]

Diameter of Connector (in.) Minimum Thickness (in.)Less than 66 to less than 1010 to 12 inclusive14 to 16 inclusiveOver 16

0.0190.0230.0290.0340.056

Notes: 1 in. = 25.4 mm, 1 in.2 = 645 mm2

Page 11: Uniform Mechanical Code- 2009 Chapter 8

fied in Table 8-4, and shall comply with thefollowing: [NFPA 54:12.11.2.6](1) A steel vent connector for appliances

with a vent gas temperature in excess of1,000°F (538°C) measured at theentrance to the connector shall be linedwith medium-duty fire brick (ASTM C64, Specification for Refractories for Incin-erators and Boilers, Type F) or the equiva-lent.

(2) The lining shall be at least two and one-half (2-1/2) inches (64 mm) thick for avent connector having a diameter orgreatest cross-sectional dimension ofeighteen (18) inches (460 mm) or less.

(3) The lining shall be at least four and one-half (4-1/2) inches (110 mm) thick laidon the four and one-half (4-1/2) inches(110 mm) bed for a vent connectorhaving diameter or greatest cross-sectional dimension greater than eigh-teen (18) inches (460 mm).

(4) Factory-built chimney sections, ifemployed, shall be joined together inaccordance with the chimney manufac-turer's instructions.

802.10.3 Size of Vent Connector.802.10.3.1 A vent connector for gas utiliza-tion appliances with a single draft hood orfor a Category I fan-assisted combustionsystem appliance shall be sized and installedin accordance with Section 803.0 or otherapproved engineering methods. [NFPA54:12.11.3.1]802.10.3.2 For a single appliance havingmore than one (1) draft hood outlet or fluecollar, the manifold shall be constructedaccording to the instructions of the appli-ance manufacturer. Where there are noinstructions, the manifold shall be designedand constructed in accordance withapproved engineering practices. As an alter-

nate method, the effective area of the mani-fold shall equal the combined area of theflue collars or draft hood outlets and thevent connectors shall have a minimum one(1) foot (305 mm) rise. [NFPA 54:12.11.3.2]802.10.3.3 Where two or more gas appli-ances are connected to a common vent orchimney, each vent connector shall be sizedin accordance with Section 803.0 or otherapproved engineering methods. As an alter-native method applicable only when all ofthe appliances are draft hood equipped,each vent connector shall have an effectivearea not less than the area of the draft hoodoutlet of the appliance to which it isconnected. [NFPA 54:12.11.3.3, 12.11.3.4]802.10.3.4Where two (2) or more gas appli-ances are vented through a common ventconnector or vent manifold, the commonvent connector or vent manifold shall belocated at the highest level consistent withavailable head-room and clearance tocombustible material and shall be sized inaccordance with Section 803.0 or otherapproved engineering methods. [NFPA54:12.11.3.5]

As an alternate method applicable onlywhere there are two (2) draft hood–equippedappliances, the effective area of the commonvent connector or vent manifold and all junc-tion fittings shall be not less than the area ofthe larger vent connector plus 50 percent ofthe areas of smaller flue collar outlets.[NFPA 54:12.11.3.6]802.10.3.5 Where the size of a ventconnector is increased to overcome installa-tion limitations and obtain connectorcapacity equal to the appliance input, thesize increase shall be made at the appliancedraft hood outlet. [NFPA 54:12.11.3.7]

802.10.4 Two or More Appliances Connectedto a Single Vent.

802.10.4.1 Where two (2) or more openingsare provided into one (1) chimney flue orvent, the openings shall either be at differentlevels, or the connectors shall be attached tothe vertical portion of the chimney or vent atan angle of 45 degrees or less relative to thevertical. [NFPA 54-09:12.11.4.1]802.10.4.2 Where two (2) or more ventconnectors enter a common gas vent,chimney flue, or single-wall metal pipe, thesmaller connector shall enter at the highestlevel consistent with the available headroomor clearance to combustible material. [NFPA54:12.11.4.1]

CHIMNEYS AND VENTS 802.10

103

TABLE 8-4Minimum Thickness for Steel Vent Connectorsfor Medium-Heat Appliances and Commercial

and Industrial Incinerators[NFPA 54: Table 12.11.2.6]

Vent Connector Size

Diameter (in.) Area (in.2)Minimum

Thickness (in.)Up to 14

Over 14 to 16Over 16 to 18Over 18

Up to 154154 to 201201 to 254

Larger than 254

0.0530.0670.0930.123

Notes: 1 in. = 25.4 mm, 1 in.2 = 645 mm2

Page 12: Uniform Mechanical Code- 2009 Chapter 8

802.10.4.3 Vent connectors serving Cate-gory I appliances shall not be connected toany portion of a mechanical draft systemoperating under positive static pressure,such as those serving Category III or Cate-gory IV appliances. [NFPA 54:12.11.4.2]

802.10.5 Clearance. Minimum clearances fromvent connectors to combustible material shall bein accordance with Table 8-2. [NFPA 54:12.11.5]

Exception: The clearance between a ventconnector and combustible material shall bepermitted to be reduced where thecombustible material is protected as speci-fied for vent connectors in Table 5-3.

802.10.6 Avoid Unnecessary Bends. A ventconnector shall be installed so as to avoid turnsor other construction features that create exces-sive resistance to flow of vent gases. [NFPA54:12.11.6]802.10.7 Joints. Joints between sections ofconnector piping and connections to flue collarsor draft hood outlets shall be fastened in accor-dance with one of the following methods:[NFPA 54:12.11.7](1) By sheet metal screws.(2) Vent connectors of listed vent material shall

be assembled and connected to flue collarsor draft hood outlets in accordance with themanufacturers' instructions.

(3) Other approved means.802.10.8 Slope. A vent connector shall beinstalled without any dips or sags and shallslope upward toward the vent or chimney atleast one-quarter (1/4) in./ft. (20 mm/m).[NFPA 54:12.11.8]

Exception: Vent connectors attached to amechanical draft system installed in accor-dance with the draft system manufacturers'instructions.

802.10.9 Length of Vent Connector.802.10.9.1 A vent connector shall be asshort as practical, and the appliance locatedas close as practical to the chimney or vent.[NFPA 54:12.11.9.1]802.10.9.2 The maximum horizontal lengthof a single-wall connector shall be 75 percentof the height of the chimney or vent exceptfor engineered systems. [NFPA 54:12.11.9.2]802.10.9.3 The maximum horizontal lengthof a Type B double-wall connector shall be100 percent of the height of the chimney orvent, except for engineered systems. Themaximum length of an individual connector

for a chimney or vent system servingmultiple appliances, from the applianceoutlet to the junction with the common ventor another connector, shall be 100 percent ofthe height of the chimney or vent. [NFPA 54:12.11.9.3]

802.10.10 Support. A vent connector shall besupported for the design and weight of thematerial employed to maintain clearances andprevent physical damage and separation ofjoints. [NFPA 54:12.11.10]802.10.11 Chimney Connection. Whereentering a flue in a masonry or metal chimney,the vent connector shall be installed above theextreme bottom to avoid stoppage. Where athimble or slip joint is used to facilitate removalof the connector, the connector shall be firmlyattached to or inserted into the thimble or slipjoint to prevent the connector from falling out.Means shall be employed to prevent theconnector from entering so far as to restrict thespace between its end and the opposite wall ofthe chimney flue. [NFPA 54:12.11.11]802.10.12 Inspection. The entire length of avent connector shall be readily accessible forinspection, cleaning, and replacement. [NFPA54:12.11.12]802.10.13 Fireplaces. A vent connector shallnot be connected to a chimney flue serving afireplace unless the fireplace flue opening ispermanently sealed. [NFPA 54:12.11.13]802.10.14 Passage Through Ceilings, Floors,or Walls.

802.10.14.1 A vent connector shall not passthrough any ceiling, floor, or fire-resistancerated wall. A single-wall metal pipeconnector shall not pass through any inte-rior wall.

Exception: Vent connectors made oflisted Type B or Type L vent materialand serving listed appliances with drafthoods and other appliances listed foruse with Type B gas vents that passthrough walls or partitions constructedof combustible material shall beinstalled with not less than the listedclearance to combustible material.

802.10.14.2 A vent connector made of asingle-wall metal pipe shall not passthrough a combustible exterior wall unlessguarded at the point of passage by a venti-lated metal thimble not smaller than thefollowing: [NFPA 54:12.11.14.2](1) For listed appliances equipped with

draft hoods and appliances listed for

UNIFORM MECHANICAL CODE802.10

104

Page 13: Uniform Mechanical Code- 2009 Chapter 8

use with Type B gas vents, the thimbleshall be a minimum of four (4) inches(100 mm) larger in diameter than thevent connector. Where there is a run ofnot less than six (6) feet (305 mm) ofvent connector in the opening betweenthe draft hood outlet and the thimble,the thimble shall be a minimum of two(2) inches (50 mm) larger in diameterthan the vent connector.

(2) For unlisted appliances having drafthoods, the thimble shall be a minimumof six (6) inches (150 mm) larger indiameter than the vent connector.

(3) For residential and low-heat appliances,the thimble shall be a minimum oftwelve (12) inches (300 mm) larger indiameter than the vent connector.

Exception: In lieu of thimble protec-tion, all combustible material in thewall shall be removed from the ventconnector a sufficient distance toprovide the specified clearancefrom such vent connector tocombustible material. Any materialused to close up such opening shallbe noncombustible.

802.10.14.3 Vent connectors for medium-heat appliances shall not pass through wallsor partitions constructed of combustiblematerial. [NFPA 54:12.11.14.3]

802.11 Vent Connectors for Category II, CategoryIII, and Category IV Appliances. (See Section 802.4.)[NFPA 54:12.12]802.12 Draft Hoods and Draft Controls.

802.12.1 Appliances Requiring Draft Hoods.Vented appliances shall be installed with drafthoods. [NFPA 54:12.13.1]

Exception: Dual oven–type combinationranges; incinerators; direct-vent appliances;fan-assisted combustion system appliances;appliances requiring chimney draft for oper-ation; single-firebox boilers equipped withconversion burners with inputs greater than400,000 Btu/h (117 kW); appliancesequipped with blast, power, or pressureburners that are not listed for use with drafthoods; and appliances designed for forcedventing.

802.12.2 Installation. A draft hood suppliedwith or forming a part of listed vented applianceshall be installed without alteration, exactly asfurnished and specified by the appliance manu-facturer. If a draft hood is not supplied by the

appliance manufacturer where one (1) is required,a draft hood shall be installed, be of a listed orapproved type, and, in the absence of otherinstructions, be of the same size as the applianceflue collar. Where a draft hood is required with aconversion burner, it shall be of a listed orapproved type. Where it is determined that adraft hood of special design is needed or prefer-able for a particular installation, the installationshall be in accordance with the recommenda-tions of the appliance manufacturer and shall bewith the approval of the Authority Having Juris-diction. [NFPA 54:12.13.2, 12.13.2.1, 12.13.2.2]802.12.3 Draft Control Devices. Where a draftcontrol device is part of the appliance or issupplied by the appliance manufacturer, it shallbe installed in accordance with the manufactur-er's instructions. In the absence of manufactur-er's instructions, the device shall be attached tothe flue collar of the appliance or as near to theappliance as practical. [NFPA 54:12.13.3]802.12.4 Additional Devices. Appliances(except incinerators) requiring controlledchimney draft shall be permitted to be equippedwith a listed double-acting barometric draftregulator installed and adjusted in accordancewith the manufacturers' instructions. [NFPA54:12.13.4]802.12.5 Location. Draft hoods and barometricdraft regulators shall be installed in the sameroom or enclosure as the appliance in such amanner as to prevent any difference in pressurebetween the hood or regulator and the combus-tion air supply. [NFPA 54:12.13.5]802.12.6 Positioning. Draft hoods and draftregulators shall be installed in the position forthat they were designed with reference to thehorizontal and vertical planes and shall belocated so that the relief opening is notobstructed by any part of the appliance or adja-cent construction. The appliance and its drafthood shall be located so that the relief opening isaccessible for checking vent operation. [NFPA54:12.13.6]802.12.7 Clearance. A draft hood shall belocated so that its relief opening is not less thansix (6) inches (150 mm) from any surface exceptthat of the appliance it serves and the ventingsystem to which the draft hood is connected.Where a greater or lesser clearance is indicatedon the appliance label, the clearance shall not beless than that specified on the label. Such clear-ances shall not be reduced. [NFPA 54:12.13.7]

CHIMNEYS AND VENTS 802.10 – 802.12

105

Page 14: Uniform Mechanical Code- 2009 Chapter 8

802.13 Manually Operated Dampers. A manuallyoperated damper shall not be placed in any appli-ance vent connector. Fixed baffles shall not be classi-fied as manually operated dampers. [NFPA 54:12.14]802.14 Automatically Operated Vent Dampers. Anautomatically operated vent damper shall be of alisted type. [NFPA 54:12.15]802.15 Obstructions. Devices that retard the flow ofvent gases shall not be installed in a vent connector,chimney, or vent. The following shall not be consid-ered as obstructions:(1) Draft regulators and safety controls specifically

listed for installation in venting systems andinstalled in accordance with the terms of theirlisting.

(2) Approved draft regulators and safety controlsdesigned and installed in accordance withapproved engineering methods.

(3) Listed heat reclaimers and automatically oper-ated vent dampers installed in accordance withthe terms of their listing.

(4) Vent dampers serving listed appliances installedin accordance with Sections 803.1 and 803.2.1 orother approved engineering methods.

(5) Approved economizers, heat reclaimers, andrecuperators installed in venting systems ofappliances not required to be equipped withdraft hoods, provided the appliance manufactur-er's instructions cover the installation of such adevice in the venting system and performance inaccordance with Sections 802.3.1 and 802.3.2 isobtained. [NFPA 54:12.16]

803.0 Sizing of Category I Venting Systems.803.1 These venting tables shall not be used whereobstructions (see Section 802.15) are installed in theventing system. The installation of vents servinglisted appliances with vent dampers shall be inaccordance with the appliance manufacturer’sinstructions or in accordance with the following:[NFPA 54:13.1.1](1) The maximum capacity of the vent system shall

be determined using the NAT Max column.(2) The minimum capacity shall be determined as if

the appliance were a fan-assisted appliance,using the FAN Min column to determine theminimum capacity of the vent system. Wherethe corresponding FAN Min is NA, the ventconfiguration shall not be permitted and analternative venting configuration shall beutilized.803.1.1 Where the vent size determined fromthe tables is smaller than the appliance draft

hood outlet or flue collar, the use of the smallersize shall be permitted provided that the instal-lation complies with all of the following require-ments: [NFPA 54:13.1.2](1) The total vent height (H) is at least ten (10)

feet (3,048 mm).(2) Vents for appliance draft hood outlets or

flue collars twelve (12) inches (300 mm) indiameter or smaller are not reduced morethan one table size.

(3) Vents for appliance draft hood outlets orflue collars larger than twelve (12) inches(300 mm) in diameter are not reduced morethan two table sizes.

(4) The maximum capacity listed in the tablesfor a fan-assisted appliance is reduced byten (10) percent (0.90 maximum tablecapacity).

(5) The draft hood outlet is greater than four (4)inches (100 mm) in diameter. Do not connecta three (3) inches (80 mm) diameter vent to afour (4) inches (100 mm) diameter drafthood outlet. This provision shall not applyto fan-assisted appliances.

803.1.2 Single-appliance venting configurationswith zero (0) lateral lengths in Tables 8-5, 8-6,and 8-9 shall not have elbows in the ventingsystem. For vent configurations with laterallengths, the venting tables include allowance fortwo (2) 90 degree turns. For each additionalelbow up to and including 45 degrees, themaximum capacity listed in the venting tablesshall be reduced by 5 percent. For each elbowgreater than 45 degrees up to and including 90degrees, the maximum capacity listed in theventing tables shall be reduced by 10 percent.Where multiple offsets occur in a vent, the totallateral length of all offsets combined shall notexceed that specified in Tables 8-5 through 8-9.[NFPA 54-09:13.1.3]803.1.3 Zero (0) lateral (L) shall apply only to astraight vertical vent attached to a top-outletdraft hood or flue collar. [NFPA 54:13.1.4]803.1.4 Sea level input ratings shall be usedwhen determining maximum capacity for high-altitude installation. Actual input (derated foraltitude) shall be used for determining minimumcapacity for high-altitude installation. [NFPA54:13.1.5]803.1.5 For appliances with more than one (1)input rate, the minimum vent capacity (FANMin) determined from the tables shall be lessthan the lowest appliance input rating, and themaximum vent capacity (FAN Max/NAT Max)determined from the tables shall be greater than

UNIFORM MECHANICAL CODE802.13 – 803.1

106

Page 15: Uniform Mechanical Code- 2009 Chapter 8

the highest appliance rating input. [NFPA54:13.1.6]803.1.6 Listed corrugated metallic chimney linersystems in masonry chimneys shall be sized byusing Table 8-5 or 8-6 for Type B vents, with themaximum capacity reduced by 20 percent (0.80maximum capacity) and the minimum capacityas shown in Table 8-5 or 8-6. Corrugated metallicliner systems installed with bends or offsets shallhave their maximum capacity further reduced inaccordance with Section 803.1.2. The 20 percentreduction for corrugated metallic chimney linersystems includes an allowance for one (1) longradius 90 degree turn at the bottom of the liner.[NFPA 54:13.1.7]803.1.7 Where the vertical vent has a largerdiameter than the vent connector, the verticalvent diameter shall be used to determine theminimum vent capacity, and the connectordiameter shall be used to determine themaximum vent capacity. The flow area of thevertical vent shall not exceed seven (7) times theflow area of the listed appliance categorized ventarea, flue collar area, or draft hood outlet areaunless designed in accordance with approvedengineering methods. [NFPA 54:13.1.9]803.1.8 Connection to Chimney Liners.Connections between chimney liners and listeddouble-wall connectors shall be made with listedadapters designed for such purpose. [NFPA54:13.1.8]

803.1.8.1 Tables 8-5 through 8-9 shall beused for chimneys and vents not exposed tothe outdoors below the roof line. A Type Bvent or listed chimney lining system passingthrough an unused masonry chimney flueshall not be considered to be exposed to theoutdoors. A Type B vent passing through anunventilated enclosure or chase insulated toa value of not less than R8 shall not beconsidered to be exposed to the outdoors.Table 8-7 in combination with Table 8-15shall be used for clay-tile-lined exteriormasonry chimneys, provided all of thefollowing are met:(1) The vent connector is Type B double wall.(2) The vent connector length is limited to

one and one-half (1-1/2) feet for eachinch (18 mm/mm) of vent connectordiameter.

(3) The appliance is draft hood equipped.(4) The input rating is less than the

maximum capacity given in Table 8-7.(5) For a water heater, the outdoor design

temperature shall not be less than 5°F(-15°C).

(6) For a space-heating appliance, the inputrating is greater than the minimumcapacity given by Table 8-15. [NFPA54:13.1.11]

803.1.9 Corrugated vent connectors shall not besmaller than the listed appliance categorizedvent diameter, flue collar diameter, or drafthood outlet diameter. [NFPA 54:13.1.12]803.1.10 Vent connectors shall not be upsizedmore than two (2) sizes greater than the listedappliance categorized vent diameter, flue collardiameter, or draft hood outlet diameter. [NFPA54:13.1.13]803.1.11 In a single run of vent or ventconnector, more than one diameter and typeshall be permitted to be used, provided that allthe sizes and types are permitted by the tables.[NFPA 54:13.1.14]803.1.12 Interpolation shall be permitted incalculating capacities for vent dimensions thatfall between table entries. (See Example 8-1 inSection 803.2.23.) [NFPA 54:13.1.15]803.1.13 Extrapolation beyond the table entriesshall not be permitted. [NFPA 54:13.1.16]803.1.14 For vent heights lower than six (6) feet(1,829 mm) and higher than shown in the tables,engineering methods shall be used to calculatevent capacities. [NFPA 54:13.1.17]803.1.15 Draft Hood Conversion Accessories.Draft hood conversion accessories for use withmasonry chimneys venting listed Category I fan-assisted appliances shall be listed and installedin accordance with the listed accessory manufac-turer’s installation instructions. [NFPA54:13.1.10]

803.2 Additional Requirements to Multiple Appli-ance Vent Tables 8-10 through 8-14 and Tables 8-16 through 8-19.

803.2.1 These venting tables shall not be usedwhere obstructions (see Section 802.15) areinstalled in the venting system. The installationof vents serving listed appliances with ventdampers shall be in accordance with the appli-ance manufacturer’s instructions or in accor-dance with the following:(1) The maximum capacity of the vent

connector shall be determined using theNAT Max column.

(2) The maximum capacity of the vertical ventor chimney shall be determined using theFAN+NAT column when the second appli-ance is a fan-assisted appliance, or the

CHIMNEYS AND VENTS 803.1 – 803.2

107

Page 16: Uniform Mechanical Code- 2009 Chapter 8

NAT+NAT column when the second appli-ance is equipped with a draft hood.

(3) The minimum capacity shall be determinedas if the appliance were a fan-assisted appli-ance.(a) The minimum capacity of the vent

connector shall be determined using theFANMin column.

(b) The FAN+FAN column shall be usedwhen the second appliance is a fan-assisted appliance, and the FAN+NATcolumn shall be used when the secondappliance is equipped with a drafthood, to determine whether the verticalvent or chimney configuration is notpermitted (NA). Where the vent config-uration is NA, the vent configurationshall not be permitted, and an alterna-tive venting configuration shall beutilized. [NFPA 54:13.2.1]

803.2.2 The maximum vent connector horizontallength shall be 18 in./in. (18 mm/mm) ofconnector diameter (see the Vent ConnectorMaximum Length Table). [NFPA 54:13.2.2]

803.2.3 The vent connector shall be routed to thevent utilizing the shortest possible route.Connectors with longer horizontal lengths thanthose listed in Section 803.2.2 are permittedunder the following conditions: [NFPA 54:13.2.3]

(A) The maximum capacity (FAN Max or NATMax) of the vent connector shall be reduced10 percent for each additional multiple ofthe length listed in 803.2.2. For example, themaximum length listed for a four (4) inches(100 mm) connector is six (6) feet (1,829mm). With a connector length greater thansix (6) feet (1,829 mm) but not exceedingtwelve (12) feet (3,658 mm), the maximumcapacity must be reduced by 10 percent(0.90 maximum vent connector capacity).With connector length greater than twelve(12) feet (3,658 mm) but not exceeding eigh-teen (18) feet (5,486 mm), the maximumcapacity must be reduced by 20 percent(0.80 maximum vent capacity). [NFPA54:13.2.3(1)]

(B) For a connector serving a fan-assisted appli-ance, the minimum capacity (FAN Min) ofthe connector shall be determined by refer-ring to the corresponding single-appliancetable. For Type B double-wall connectors,Table 8-5 shall be used. For single-wallconnectors, Table 8-6 shall be used. Theheight (H) and lateral (L) shall be measuredaccording to the procedures for a single-appliance vent, as if the other applianceswere not present. [NFPA 54:13.2.3(2)]

803.2.4Where the vent connectors are combinedprior to entering the vertical portion of thecommon vent to form a common vent manifold,the size of the common vent manifold and thecommon vent shall be determined by applying a10 percent reduction (0.90 x maximum commonvent capacity) to the Common Vent Capacitypart of the common vent tables. The length ofthe common vent connector manifold (LM) shallnot exceed 18 in./in. (18 mm/mm) of commonvent connector manifold diameter (D). (SeeFigure 8-4.) [NFPA 54:13.2.4]803.2.5 Where the common vertical vent isoffset, the maximum capacity of the commonvent shall be reduced in accordance with Section803.2.6, and the horizontal length of the commonvent offset shall not exceed 18 in./in. (18mm/mm) of common vent diameter. Wheremultiple offsets occur in a common vent, thetotal horizontal length of all offsets combinedshall not exceed 18 in./in. (18 mm/mm) ofcommon vent diameter. [NFPA 54-09:13.2.5]803.2.6 For each elbow up to and including 45degrees in the common vent, the maximumcommon vent capacity listed in the ventingtables shall be reduced by 5 percent. For each

UNIFORM MECHANICAL CODE803.2

108

Vent Connector Maximum Length[NFPA 54: Table 13.2.2]

Connector Connector HorizontalDiameter Maximum Length

(in.) (ft.)3 4-1/24 65 7-1/26 97 10-1/28 129 13-1/210 1512 1814 2116 2418 2720 3022 3324 36

Notes: 1 in. = 25.4 mm, 1 ft. = 0.305 m

Page 17: Uniform Mechanical Code- 2009 Chapter 8

elbow exceeding 45 degrees up to and including90 degrees, the maximum common vent capacitylisted in the venting tables shall be reduced by10 percent. [NFPA 54:13.2.6]803.2.7 Common Vent Minimum Size. Thecross-sectional area of the common vent shall beequal to or greater than the cross-sectional areaof the largest connector. [NFPA 54:13.2.8]803.2.8 Tee and Wye Fittings. Tee and wyefittings connected to a common gas vent shall beconsidered as part of the common gas vent andconstructed of materials consistent with that ofthe common gas vent. [NFPA 54-09:13.2.9]

803.2.8.1 At the point where tee or wyefittings connect to a common vent, theopening size of the fitting shall be equal tothe size of the common vent. Such fittingsshall not be prohibited from having reducedsize openings at the point of connection ofappliance vent connectors. [NFPA 54:13.2.10]

803.2.9 Sea level input ratings shall be usedwhen determining maximum capacity for high-altitude installation. Actual input (derated foraltitude) shall be used for determining minimumcapacity for high-altitude installation. [NFPA54:13.2.11]803.2.10 The connector rise (R) for each appli-ance connector shall be measured from the drafthood outlet or flue collar to the centerline wherethe vent gas streams come together. [NFPA54:13.2.12]803.2.11 For multiple units of appliances alllocated on one (1) floor, available total height (H)shall be measured from the highest draft hoodoutlet or flue collar up to the level of the outletof the common vent. [NFPA 54:13.2.13]

803.2.12 For multistory installations, availabletotal height (H) for each segment of the systemshall be the vertical distance between the highestdraft hood outlet or flue collar entering thatsegment and the centerline of the next higherinterconnection tee. (See Figure 8-5.) [NFPA54:13.2.14]

803.2.13 The size of the lowest connector and ofthe vertical vent leading to the lowest intercon-nection of a multistory system shall be in accor-dance with Table 8-5 or 8-6 for available totalheight (H) up to the lowest interconnection. (SeeFigure 8-6.) [NFPA 54:13.2.15]803.2.14 Where used in multistory systems,vertical common vents shall be Type B double-wall and shall be installed with a listed vent cap.[NFPA 54:13.2.16]803.2.15 Offsets in multistory common ventsystems shall be limited to a single offset in eachsystem, and systems with an offset shall complywith all of the following:(1) The offset angle shall not exceed 45 degrees

from vertical.

CHIMNEYS AND VENTS Figure 8-4 – 803.2

109

FIGURE 8-4 Use of Manifolded Common VentConnector. [NFPA 54: Figure G.1(k)]

FIGURE 8-5 Multistory Gas Vent Design Proce-dure for Each Segment of System.[NFPA 54: Figure G.1(m)]

Page 18: Uniform Mechanical Code- 2009 Chapter 8

(2) The horizontal length of the offset shall notexceed eighteen (18) inches for each inch(180 mm/mm) of common vent diameter ofthe segment in that the offset is located.

(3) For the segment of the common vertical ventcontaining the offset, the common ventcapacity listed in the common venting tablesshall be reduced by 20 percent (0.80 xmaximum common vent capacity).

(4) A multistory common vent shall not bereduced in size above the offset. [NFPA54:13.2.17]

803.2.16 Where two or more appliances areconnected to a vertical vent or chimney, the flowarea of the largest section of vertical vent orchimney shall not exceed seven times thesmallest listed appliance categorized vent areas,flue collar area, or draft hood outlet area, unlessdesigned in accordance with approved engi-neering methods. [NFPA 54:13.2.18]

803.2.17 For appliances with more than oneinput rate, the minimum vent connector capacity(FAN Min) determined from the tables shall beless than the lowest appliance input rating, andthe maximum vent connector capacity (FANMax or NAT Max) determined from the tablesshall be greater than the highest appliance inputrating. [NFPA 54:13.2.19]803.2.18 Listed, corrugated metallic chimneyliner systems in masonry chimneys shall besized by using Table 8-10 or 8-11 for Type Bvents, with the maximum capacity reduced by20 percent (0.80 maximum capacity) and theminimum capacity as shown in Table 8-10 or 8-11. Corrugated metallic liner systems installedwith bends or offsets shall have their maximumcapacity further reduced in accordance withSections 803.2.5 and 803.2.6. The 20 percentreduction for corrugated metallic chimney linersystems includes an allowance for one longradius 90 degree turn at the bottom of the liner.[NFPA 54:13.2.20]803.2.19 Tables 8-10 and 8-11 shall be used forchimneys and vents not exposed to the outdoorsbelow the roof line. A Type B vent passingthrough an unventilated enclosure or chase insu-lated to a value of not less than R 8 shall not beconsidered to be exposed to the outdoors. Tables8-16 through 8-19 shall be used for clay-tile-linedexterior masonry chimneys, provided all of thefollowing conditions are met:(1) Vent connector is Type B double-wall.(2) At least one appliance is draft hood-

equipped.(3) The combined appliance input rating is less

than the maximum capacity given by Table8-16 (for NAT+NAT) or Table 8-18 (forFAN+NAT).

(4) The input rating of each space-heatingappliance is greater than the minimuminput rating given by Table 8-17 (forNAT+NAT) or Table 8-19 (for FAN+NAT).

(5) The vent connector sizing is in accordancewith Table 8-12. [NFPA 54:13.2.22]

803.2.20 Vent connectors shall not be increasedmore than two sizes greater than the listed appli-ance categorized vent diameter, flue collar diam-eter, or draft hood outlet diameter. Vent connec-tors for draft hood-equipped appliances shallnot be smaller than the draft hood outlet diam-eter. Where a vent connector size(s) determinedfrom the tables for a fan-assisted appliance(s) issmaller than the flue collar diameter, the use ofthe smaller size(s) shall be permitted provided

UNIFORM MECHANICAL CODE803.2

110

FIGURE 8-6 Principle of Design of MultistoryVents Using Vent Connector and Common VentDesign Tables. [NFPA 54: Figure G.1(n)]

Page 19: Uniform Mechanical Code- 2009 Chapter 8

that the installation complies with all of thefollowing:(1) Vent connectors for fan-assisted appliance

flue collars twelve (12) inches (300 mm) indiameter or smaller are not reduced by morethan one table size [e.g., 12 in. to 10 in. (300mm to 250 mm) is a one-size reduction] andthose larger than twelve (12) inches (300mm) in diameter are not reduced more thantwo table sizes [e.g., 24 in. to 20 in. (610 mmto 510 mm) is a two-size reduction].

(2) The fan-assisted appliance(s) is commonvented with a draft hood equipped appli-ance(s).

(3) The vent connector has a smooth interiorwall. [NFPA 54:13.2.24]

803.2.21 All combinations of pipe sizes andsingle-wall and double-wall metal pipe shall beallowed within any connector run(s) or withinthe common vent provided ALL of the appro-priate tables permit ALL of the desired sizes andtypes of pipe, as if they were used for the entirelength of the subject connector or vent. Wheresingle-wall and Type B double-wall metal pipesare used for vent connectors within the sameventing system, the common vent must be sizedusing Table 8-11 or 8-13, as appropriate. [NFPA54:13.2.25]803.2.22 Where a table permits more than one(1) diameter of pipe to be used for a connector orvent, all the permitted sizes shall be permitted tobe used. [NFPA 54:13.2.26]803.2.23 Interpolation shall be permitted incalculating capacities for vent dimensions thatfall between table entries. (See Example 8-1.)[NFPA 54:13.2.27]Example 8-1: Interpolating between TableValues. An installer has an 80,000 Btu/h. inputappliance with a four (4) inch diameter drafthood outlet that needs to be vented into a twelve(12) foot high Type B vent. The vent connectorhas a five (5) foot lateral length and is also TypeB. Can this appliance be vented using a four (4)inch diameter vent?SolutionTable 8-5 is used in the case of an all Type B ventsystem. However, since there is no entry inTable 8-5 for a height of 12 ft., interpolation mustbe used. Read down the 4 in. diameter NAT Maxcolumn to the row associated with 10 ft. heightand 5 ft. lateral to find the capacity value of77,000 Btu/h. Read further down to the 15 ft.height, 5 ft. lateral row to find the capacity valueof 87,000 Btu/h. The difference between the 15

ft. height capacity value and the 10 ft. heightcapacity value is 10,000 Btu/h. The capacity for avent system with a 12 ft. height is equal to thecapacity for a 10 ft. height plus 2/5 of the differ-ence between the 10 ft. and 15 ft. height values,or 77,000 + 2/5 x 10,000 = 81,000 Btu/h. There-fore, a 4 in. diameter vent can be used in theinstallation.803.2.24 Extrapolation beyond the table entriesshall not be permitted. [NFPA 54:13.2.28]803.2.25 For vent heights lower than six (6) feetand higher than shown in the tables, engineeringmethods shall be used to calculate vent capaci-ties. [NFPA 54:13.2.29]

CHIMNEYS AND VENTS 803.2

111

Page 20: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-5

112

Number of Appliances: SingleAppliance Type: Category I

Appliance Vent Connection: Connected Directly to VentVent Diameter – D (in.)

3 4 5 6 7Appliance Input Rating in Thousands of Btu per Hour

HeightH(ft)

LateralL(ft)

FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 0246

0132125

78514946

46363452

0183036

152979491

86676461

0273947

251157153149

141105103100

0325059

375232227223

205157153149

0446678

524321316310

285217211205

8 0258

0122328

84575349

50403835

0163239

16510910398

94757166

0254251

276178171164

155120115109

0285364

415263255247

235180173165

0427084

583365356347

320247237227

10 02510

0122330

88615751

53424036

0173241

175118113104

100817770

0234154

295194187176

166129124115

0265267

447289280267

255195188175

0406888

631402392376

345273263245

15 0251015

011222935

9469655953

5848454137

015304048

191136130121112

11293878276

020395161

327226219206195

187150142135128

022496476

502339330315301

285225217208198

038648498

716475463445429

390316300288275

20 025101520

01021283448

977571645852

615148444035

01429384655

202149143133124116

11910096898478

01838505969

349250242229217206

202166160150142134

02047627384

540377367351337322

307249241228217206

033628194107

776531519499481464

430346337321308295

30 02510152030

0921273356NA

1008177706458NA

64565450NANANA

0132837445373

213166160150141132113

1281121081029690NA

0143648576688

374283275262249237214

220185176171163154NA

01845597080104

587432421405389374346

336280273261249237219

027587790102131

853613600580560542507

475394385371357343321

50 02510152030

08202659NANA

10186827670NANA

6761NANANANANA

0112735425069

216183177168158149131

134122119114NANANA

0143545546384

397320312299287275250

232206200190180169NA

0154356667699

633497487471455440410

363314308298288278259

02255738597123

932715702681662642605

518445438426413401376

100 0251015203050

NANANANANANANANA

NANANANANANANANA

NANANANANANANANA

01026334047NANA

218194189182174166NANA

NANANANANANANANA

0123343505978NA

407354347335321311290NA

NANANANANANANANA

0134053627192147

665566557542528513483428

400375369361353344NANA

01852688090115180

997831820801782763726651

560510504493482471449405

Table 8-5Type B Double-Wall Gas Vent [NFPA 54: Table 13.1(a)]

Page 21: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-5 continued

113

Number of Appliances: SingleAppliance Type: Category I

Appliance Vent Connection: Connected Directly to VentVent Diameter – D (in.)

8 9 10 12 14Appliance Input Rating in Thousands of Btu per Hour

HeightH(ft)

LateralL(ft)

FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 0246

0537993

698425419413

370285279273

06393110

897543536530

470370862354

075110128

1121675668661

570455445435

0103147171

1645982975967

850650640630

0138191219

2267134613381330

1170890880870

8 0258

0508399

780483473463

415322313303

06099117

1006619607596

537418407396

071115137

1261770758746

660515503490

098154180

1858112411101097

970745733720

0130199231

2571154315281514

1320102010101000

10 02510

04881104

847533522504

450355346330

05795122

1096684671651

585457446427

068112142

1377852839817

720560547525

093149187

2036124412291204

1060850829795

0124192238

2825171316961669

1450113011051080

15 0251015

0457699115

970633620600580

525414403386373

05390116134

1263815800777755

682544529507491

063105135155

159610191003977953

840675660635610

086140177202

23801495147614461418

1240985967936905

0114182227257

33232062204120091976

17201350132712891250

20 025101520

0417395111125

1057711697675654634

575470460443427410

05086112129145

1384917902877853830

752612599576557537

059101130150167

175611501133110510781052

930755738710688665

081135172195217

263716941674164116091578

13501100107910451018990

0107174220248273

370123432320228222452210

190015201498146014251390

30 02510152030

0336991105119149

1173826811788765743702

650535524507490473444

04282107124139171

15481072105510281002977929

855700688668648628594

05496125143160195

1977135113321301127212431189

1060865851829807784745

074127164187207246

3004200419811944190818731807

1550131012891254122011851130

098164209237260305

4252278627592716267426332555

2170180017751733169216501585

50 02510152030

0266586100113141

1297975960935911888844

708615605589572556522

03377101117131161

1730127612591230120311761125

952813798773747722670

04190118136151183

2231162016001567153615051446

11951010996972948924876

066118154177195232

3441243124062366232722882214

1825151314951466143714081349

086151196222244287

4034340933803332328532393150

2550212521022064202619871910

100 0251015203050

021608093105131197

1411115511411118109510731029944

770700692679666653627575

0257194109122149217

19081536151914921465143813871288

1040935926910895880849787

03082108126141170241

24911975195519231892186118021688

13101170115911421124110710711000

044107142163181215292

39253027300229612920288028032657

20501820180317751747171916631550

072136180206226265350

57294313428242314182413340373856

29502550253125002469243823752250

Table 8-5Type B Double-Wall Gas Vent [NFPA 54: Table 13.1(a)] (continued)

Page 22: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-5 continued

114

Number of Appliances: SingleAppliance Type: Category I

Appliance Vent Connection: Connected Directly to VentVent Diameter – D (in.)

16 18 20 22 24Appliance Input Rating in Thousands of Btu per Hour

HeightH(ft)

LateralL(ft)

FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 0246

0178242276

2983176917611753

1530117011601150

0225300341

3802225022422235

1960148014751470

0296390437

4721278227742767

2430185018351820

0360469523

5737337733703363

2950222022152210

0426555618

6853403040234017

3520267026602650

8 0258

0168251289

3399203020132000

1740134013301320

0212311354

4333258425632552

2220170016851670

0278398450

5387319631803163

2750211020902070

0336476537

6555388238633850

3360256025452530

0401562630

7838463446124602

4010305030403030

10 02510

0161243298

3742225622382209

1925148014611430

0202300364

4782286828492818

2450189018711840

0264382459

5955355635363504

3050234023182280

0319458546

7254432243014268

3710284028182780

0378540641

8682515351325099

4450339033713340

15 0251015

0147229283318

44232719269626592623

22701770174817121675

0186283346385

56783467344234023363

29002260223521932150

0239355432479

70994304427842344192

36202800277727392700

0290426510564

86655232520451595115

44103410338533433300

0346501599665

10,3936251622261756129

53004080405740193980

20 025101520

0139219273306335

494830973071302929882948

252020001978194019101880

0175270334372404

637639553926388038353791

325025702544250024652430

0220337413459495

798849164885483547864737

406032003174313030903050

0269403489541585

978559835950589658445792

498039103880383037953760

0321475573631689

11,75371547119706370076953

600047004662460045754550

30 02510152030

0127206259292319369

5725369636663617357035233433

2920238023502300225022002130

0159252316354384440

7420473447014647459445424442

3770305030202970292028702785

0199312386431467540

9341590058635803574456865574

4750381037833739369536503565

0241373456507548635

11,483719471557090702669646842

5850465046224574452744804375

0285439535590639739

13,848861785748505843783708239

7060560055525471539153105225

50 02510152030

0113191243274300347

6711455445204464440943564253

3440284028132767272126752631

0141234295330361412

8774586458265763570156415523

4460367036393585353434813431

0171283355396433494

11,129733972957224715570866953

5635463045974542451144794421

0209336419465506577

13,767898089338855877987048557

6940569556545585554655065444

0251394491542586672

16,69410,78810,73710,65210,57010,48810,328

8430686068186749671066706603

100 0251015203050

095172223252277319415

79145834579757375678561955055289

40503500347534343392335132673100

0120208268304330378486

10,4857591754874787409734172096956

53004600456645094451439442794050

0138245318358387446572

13,4549577952894479367928991368841

67005800576957175665561355095300

0169293374418452514659

16,81711,80311,74811,65811,56911,48211,31010,979

86007200716271007037697568506600

0204341436487523592752

20,57814,26414,20414,10514,00713,91013,72013,354

10,3008800875686838610853783918100

Table 8-5Type B Double-Wall Gas Vent [NFPA 54: Table 13.1(a)] (continued)

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 23: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-6

115

Number of Appliances: SingleAppliance Type: Category I

Appliance Vent Connection: Single-Wall Metal ConnectorVent Diameter – D (in.)

3 4 5 6 7Appliance Input Rating in Thousands of Btu per Hour

HeightH(ft)

LateralL(ft)

FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 0246

3839NANA

7751NANA

45363331

59607483

151969289

85666360

8585102114

249156152147

14010410299

126123146163

373231225220

204156152148

165159187207

522320313307

284213208203

8 0258

3739NANA

8356NANA

50393733

58597790

16410810295

93756964

8383107122

273176168161

154119114107

123121151175

412261252243

234179171163

161155193223

580363352342

319246235225

10 02510

373952NA

876156NA

53413934

57597697

174117111100

99807668

8282105132

293193185171

165128122112

120119148188

444287277261

254194186171

158153190237

628400388369

344272261241

15 0251015

363851NANA

936963NANA

57474439NA

56577595NA

190136128116NA

11193867972

8080102128158

325225216201186

186149140131124

116115144182220

499337326308290

283224217203192

153148182228272

713473459438418

388314298284269

20 025101520

353750NANANA

967468NANANA

60504741NANA

54567393NANA

200148140129NANA

11899948680NA

7878100125155186

346248239223208192

201165158146136126

114113141177216254

537375363344325306

306248239224210196

149144178222264309

772528514491469448

428344334316301285

30 02510152030

343749NANANANA

998074NANANANA

635652NANANANA

53557291115NANA

211164157144131NANA

12711110698NANANA

767698122151181NA

372281271255239223NA

219183173168157NANA

110109136171208246NA

584429417397377357NA

334279271257242228NA

144139171213255298389

849610595570547524477

472392382367349333305

50 02510152030

333648NANANANA

998480NANANANA

6661NANANANANA

51537089112NANA

213181174160148NANA

133121117NANANANA

737394118145176NA

394318308292275257NA

230205198186174NANA

105104131136199236315

629495482461441420376

361312305292280267NA

138133164203244285373

928712696671646622573

515443435420405389NA

100 0251015203050

NANANANANANANANA

NANANANANANANANA

NANANANANANANANA

49516785132NANANA

214192186175162NANANA

NANANANANANANANA

697090113138168231NA

403351342324310295264NA

NANANANANANANANA

10098125153188224301NA

659563551532511487448NA

395373366354343NANANA

131125156191230270355540

991828813789764739685584

555508501486473458NANA

Table 8-6Type B Double-Wall Gas Vent [NFPA 54: Table 13.1(b)]

Page 24: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-6 continued

116

Number of Appliances: SingleAppliance Type: Category I

Appliance Vent Connection: Single-Wall Metal ConnectorVent Diameter – D (in.)

8 9 10 12Appliance Input Rating in Thousands of Btu per Hour

HeightH(ft)

LateralL(ft)

FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max

6 0246

211201237263

695423416409

369284277271

267251295327

894541533526

469368360352

371347409449

1118673664656

569453443433

537498584638

1639979971962

849648638627

8 0258

206197245280

777482470458

414321311300

258246305344

1002617604591

536417404392

360339418470

1257768754740

658513500486

521486598665

1852112011041080

967743730715

10 02510

202193241296

844531518497

449354344325

253242299363

1093681667643

584456443423

351332409492

1373849834808

718559544520

507475584688

2031124212241194

1057848825788

15 0251015

195187231284334

966631616592568

523413400381367

244232287349404

1259812795768742

681543526501484

336319392470540

15911015997966937

838673657628601

488457562664750

23741491146914331399

1237983963928894

20 025101520

190182224277325374

1053708692666640616

573468457437419400

238227279339393448

1379914896866838810

750611596570549526

326309381457526592

175111461126109210601028

927754734702677651

473443547646730808

263116891665162615871550

13461098107410371005973

30 02510152030

184175215265312360461

1168823806777750723670

647533521501481461426

229219269327379433541

1542106910491017985955895

852698684662638615574

312296366440507570704

1971134613241287125112161147

1056863846821794768720

454424524620702780937

2996199919711927188418411759

1545130812831243120511661101

50 02510152030

176168204253299345442

1292971953923894866809

704613602583562543502

220209257313363415521

1724127312521217118311501086

948811795765736708649

295280347418481544674

2223161515911551151214731399

11891007991963934906848

428401496589668741892

3432242623962347229922512159

1818150914901455142113871318

100 0251015203050

166158194238281325418617

140411521134110410751046988866

765698688672656639NANA

207196240293342391491711

19001532151114771443141013431205

1033933921902884864824NA

273259322389447507631895

24791970194519051865182517471591

1300116811531133111010871041NA

3953714605476186908341138

39123021299029382888283827392547

20421817179617631730169616271489

Table 8-6Type B Double-Wall Gas Vent [NFPA 54: Table 13.1(b)] (continued)

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 25: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-7

117

Number of Appliances: SingleAppliance Type: Category I

Appliance Vent Connection: Type B Double-Wall ConnectorType B Double-Wall Connector Diameter – D (in.)

To be used with chimney areas within the size limits at bottom3 4 5 6 7

Appliance Input Rating in Thousands of Btu per HourHeight

H(ft)

LateralL(ft)

FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 25

NANA

NANA

2825

NANA

NANA

5249

NANA

NANA

8682

NANA

NANA

130117

NANA

NANA

180165

8 258

NANANA

NANANA

292624

NANANA

NANANA

555248

NANANA

NANANA

938883

NANANA

NANANA

145134127

NANANA

NANANA

198183175

10 2510

NANANA

NANANA

312825

NANANA

NANANA

615730

NANANA

NANANA

1039687

NANANA

NANANA

162148139

NANANA

NANANA

221204191

15 251015

NANANANA

NANANANA

353528NA

NANANANA

NANANANA

67625548

NANANANA

NANANANA

1141079789

NANANANA

NANANANA

179164153141

53NANANA

475NANANA

250231216201

20 25101520

NANANANANA

NANANANANA

3836NANANA

NANANANANA

NANANANANA

746860NANA

NANANANANA

NANANANANA

1241161079783

NANANANANA

NANANANANA

201184172159148

5180NANANA

522503NANANA

274254237220206

30 2510152030

NANANANANANA

NANANANANANA

41NANANANANA

NANANANANANA

NANANANANANA

827667NANANA

NANANANANANA

NANANANANANA

13712811510791NA

NANANANANANA

NANANANANANA

216198184171159NA

4775NANANANA

581561NANANANA

303281263243227188

50 2510152030

NANANANANANA

NANANANANANA

NANANANANANA

NANANANANANA

NANANANANANA

92NANANANANA

NANANANANANA

NANANANANANA

161131138127NANA

NANANANANANA

NANANANANANA

251230215199185NA

NANANANANANA

NANANANANANA

351323304282264NA

Minimuminternalarea of

chimney(in.2)

12 19 28 38 50

Maximuminternalarea of

chimney(in.2)

Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet area.

Table 8-7Masonry Chimney [NFPA 54-09: Table 13.1(c)]

Page 26: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-7 continued

118

Number of Appliances: SingleAppliance Type: Category I

Appliance Vent Connection: Type B Double-Wall ConnectorType B Double-Wall Connector Diameter – D (in.)

To be used with chimney areas within the size limits at bottom8 9 10 12

Appliance Input Rating in Thousands of Btu per HourHeight

H(ft)

LateralL(ft)

FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max

6 25

NANA

NANA

247231

NANA

NANA

320298

NANA

NANA

401376

NANA

NANA

581561

8 258

NANANA

NANANA

266247239

84NANA

590NANA

350328318

100149173

728711695

446423410

139201231

10241007990

651640623

10 2510

68NANA

519NANA

298277263

82124155

655638610

388365347

98146182

810791762

491466444

136196240

114411241093

724712668

15 251015

6499126NA

613594565NA

336313296281

77118148171

779759727698

441416394375

92139173198

968946912880

562533567485

127186229259

1376135213151280

841828777742

20 25101520

6195122NANA

678658627NANA

375350332314296

73113143165186

867845811780750

491463440418397

87133167191214

108310591022987955

627597566541513

121179221251277

15481523148214431406

953933879840807

30 2510152030

5790115NANANA

762741709NANANA

421393373353332288

68106135156176NA

985962927893860NA

558526500476450416

81125158181203249

124012161176113911031035

717683648621592555

111169210239264318

179317661721167916381560

111210941025981940877

50 2510152030

5183NANANANA

840819NANANANA

477445424400376327

6198126146165NA

1106108310471010977NA

633596567539511468

72116147170190233

141313871347130712691196

812774733702669623

99155195222246295

208020522006196119161832

12431225114710991050984

Minimuminternalarea of

chimney(in.2)

63 78 95 132

Maximuminternalarea of

chimney(in.2)

Seven times the listed appliance categorized vent area, flue collar area, or draft hoodoutlet area.

Table 8-7Masonry Chimney [NFPA 54-09: Table 13.1(c)] (continued)

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 27: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-8

119

Table 8-8Masonry Chimney [NFPA 54-09: Table 13.1(d)]

Number of Appliances: SingleAppliance Type: Category I

Appliance Vent Connection: Single-Wall Metal ConnectorSingle-Wall Metal Connector Diameter – D (in.)

To be used with chimney areas within the size limits at bottom3 4 5 6 7

Appliance Input Rating in Thousands of Btu per HourHeight

H(ft)

LateralL(ft)

FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 25

NANA

NANA

2825

NANA

NANA

5248

NANA

NANA

8681

NANA

NANA

130116

NANA

NANA

180164

8 258

NANANA

NANANA

292623

NANANA

NANANA

555147

NANANA

NANANA

938782

NANANA

NANANA

145133126

NANANA

NANANA

197182174

10 2510

NANANA

NANANA

312824

NANANA

NANANA

615649

NANANA

NANANA

1029586

NANANA

NANANA

161147137

NANANA

NANANA

220203189

15 251015

NANANANA

NANANANA

353227NA

NANANANA

NANANANA

67615446

NANANANA

NANANANA

1131069687

NANANANA

NANANANA

178163151138

166NANANA

473NANANA

249230214198

20 25101520

NANANANANA

NANANANANA

3835NANANA

NANANANANA

NANANANANA

736759NANA

NANANANANA

NANANANANA

1231151059580

NANANANANA

NANANANANA

200183170156144

163NANANANA

520NANANANA

273252235217202

30 2510152030

NANANANANANA

NANANANANANA

41NANANANANA

NANANANANANA

NANANANANANA

817566NANANA

NANANANANANA

NANANANANANA

13612711310588NA

NANANANANANA

NANANANANANA

215196182168155NA

158NANANANANA

578NANANANANA

302279260240223182

50 2510152030

NANANANANANA

NANANANANANA

NANANANANANA

NANANANANANA

NANANANANANA

91NANANANANA

NANANANANANA

NANANANANANA

160149136124NANA

NANANANANANA

NANANANANANA

250228212195180NA

NANANANANANA

NANANANANANA

350321301278258NA

Minimuminternalarea of

chimney(in.2)

12 19 28 38 50

Maximuminternalarea of

chimney(in.2)

Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet area.

Page 28: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-8 continued

120

Table 8-8Masonry Chimney [NFPA 54-09: Table 13.1(d)] (continued)

Number of Appliances: SingleAppliance Type: Category I

Appliance Vent Connection: Single-Wall Metal ConnectorSingle-Wall Metal Connector Diameter – D (in.)

To be used with chimney areas within the size limits at bottom8 9 10 12

Appliance Input Rating in Thousands of Btu per HourHeight

H(ft)

LateralL(ft)

FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max

6 25

NANA

NANA

247230

NANA

NANA

319297

NANA

NANA

400375

NANA

NANA

580560

8 258

NANANA

NANANA

265246237

NANANA

NANANA

349327317

382NANA

725NANA

445422408

549673747

10211003985

650638621

10 2510

216NANA

518NANA

297276261

271334NA

654635NA

387364345

373459547

808789758

490465441

536657771

114211211088

722710665

15 251015

211261NANA

611591NANA

335312294278

264325392452

776755722692

440414392372

362444531606

965942907873

560531504481

520637749841

1373134813091272

840825774738

20 25101520

206255312NANA

675655622NANA

374348330311292

258317382442NA

864842806773NA

490461437414392

252433517591663

107910551016979944

625594562539510

508623733823911

15441518147514341394

950930875835800

30 2510152030

200245300NANANA

759737703NANANA

420391370349327281

249306370428NANA

982958920884NANA

556524496471445408

340417500572643NA

12371210116811281089NA

715680644615585544

4896007087988831055

178917601713166816241539

111010901020975932865

50 2510152030

191NANANANANA

837NANANANANA

475442420395370318

238293355NANANA

110310781038NANANA

631593562533504458

323398447546616NA

14081381133712941251NA

810770728695660610

4635716747618441009

207620441994194518981805

12401220114010901040970

Minimuminternalarea of

chimney(in.2)

63 78 95 132

Maximuminternalarea of

chimney(in.2)

Seven times the listed appliance categorized vent area, flue collar area, or draft hoodoutlet area.

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 29: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-9

121

Number of Appliances: SingleAppliance Type: Draft Hood-Equipped

Appliance Vent Connection: Connected Directly to Pipe or Vent

HeightH(ft)

LateralL(ft)

Diameter – D (in.)To be used with chimney areas within the size limits at bottom

3 4 5 6 7 8 10 12Appliance Input Rating in Thousands of Btu per Hour

Maximum Appliance Input Rating in Thousands of Btu per Hour6 0

25

393128

705551

1169488

170141128

232194177

312260242

500415390

750620600

8 02510

42322924

76615649

1261029586

185154141131

252210194180

340284264250

542451430406

815680648325

10 0251015

45353227NA

8467615446

1381111049484

202168153143130

279233215200186

372311289274258

606505480455432

912760724700666

15 025101520

49393530NANA

9172675850NA

1511221101039382

223186170158144132

312260240223207195

420350325308291273

684570540514488466

1040865825795760726

20 025101520

53423832NANA

10180746555NA

16313612311510491

252210192178163149

342286264246228214

470392364345326306

770641610571550525

1190990945910870832

30 02510152030

5644NANANANANA

108847868NANANA

18314813712511399NA

276230210196177163NA

384320296274258240192

529441410388366344395

878730694656625596540

13701140108010501000960890

50 02510152030

NANANANANANANA

12095NANANANANA

210171159146NANANA

310260234221200185NA

443370342318392276222

590492474456407384330

980820780730705670605

1550129012301190113010801010

Table 8-9Single-Wall Metal Pipe or Type B Asbestos Cement Vent [NFPA 54: Table 13.1(e)]

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 30: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-10

122

Number of Appliances: Two or MoreAppliance Type: Category I

Appliance Vent Connection: Type B Double-Wall ConnectorVent Connector Capacity

VentHeight

H(ft)

ConnectorRise

R(ft)

Type B Double-Wall Vent and Connector Diameter – D (in.)3 4 5 6 7

Appliance Input Rating in Thousands of Btu per HourFAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 123

222324

374144

263135

353738

667581

465562

464849

106121132

728696

586062

164183199

104124139

777982

225253275

142168189

8 123

222324

404447

273236

353637

728087

485764

495153

114128139

7690101

646667

176195210

109129145

848688

243269290

148175198

10 123

222324

434750

283337

343637

788692

505967

495152

123136146

7893104

656769

189206220

113134150

899194

257282303

154182205

15 123

212224

505355

303540

333536

8996102

536371

474951

142153163

8399111

646668

220235248

120142160

889193

298320339

163193218

20 123

212223

545760

313742

333435

99105110

566674

464850

157167176

87104116

626466

246259271

125149168

868991

334354371

171202228

30 123

202122

626466

333944

313334

113118123

597079

454748

181190198

93110124

606264

288299309

134158178

838588

391408423

182215242

50 123

192122

717375

364348

303233

133137141

647686

434546

216223229

101119134

575961

349358366

145172194

788183

477490502

197234263

100 123

181920

828384

374450

283031

158161163

667989

404244

262267272

104123138

535557

442447452

150178200

737578

611619627

204242272

Common Vent Capacity

VentHeight

H(ft)

Type B Double-Wall Common Vent Diameter – D (in.)4 5 6 7 8

Combined Appliance Input Rating in Thousands of Btu per HourFAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

681015203050100

92101110125136152167175

819097112123138153163

65737991102118134NA

140155169195215244279311

116129141164183210244277

103114124144160185214NA

204224243283314361421489

161178194228255297353421

147163178206229266310NA

309339367427475547641751

248275299352394459547658

200223242280310360423479

4044444775566217208541025

314348377444499585706873

260290315365405470550625

Table 8-10Type B Double-Wall Vent [NFPA 54: Table 13.2(a)]

Page 31: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-10 continued

123

Number of Appliances: Two or MoreAppliance Type: Category I

Appliance Vent Connection: Type B Double-Wall ConnectorVent Connector Capacity

VentHeight

H(ft)

ConnectorRise

R(ft)

Type B Double-Wall Vent and Connector Diameter – D (in.)8 9 10 12 14

Appliance Input Rating in Thousands of Btu per HourFAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 123

929597

296333363

185220248

109112114

376424463

237282317

128131134

466526575

289345386

174180NA

764897NA

496616NA

223230NA

10461231NA

653827NA

8 123

100103105

320356384

194230258

118121123

408454492

248294330

138141143

507564612

303358402

186192198

8229521050

516644772

238244252

112613071445

6968841072

10 123

106109111

341374402

200238268

125128131

436479515

257305342

146149152

542596642

314372417

196201207

8709971095

536664792

249256263

119513711509

7309241118

15 123

110112115

389419445

214253286

134137140

493532565

273323365

162165167

609658700

333394444

214221228

96710851181

568712856

272279286

133414991632

79010061222

20 123

107110113

436463486

224265300

131134137

552587618

285339383

158161164

681725764

347414466

223230237

105111621253

596748900

291298307

144315971726

84010641288

30 123

103105108

512534555

238282317

125129132

649679706

305360405

151155158

802840874

372439494

216223231

121713161400

632792952

286294303

166418021920

91011601410

50 123

97100103

627645661

257306343

120123126

797820842

330392441

144148151

98410141043

403478538

206213221

147915611631

6898601031

273281290

202321392242

100712911575

100 123

919497

810822834

266316355

112115118

103810541069

341405455

135139142

128513061327

417494555

192200208

192319842035

7128881064

254263272

264427312811

105013461642

Common Vent Capacity

VentHeight

H(ft)

Type B Double-Wall Common Vent Diameter – D (in.)9 10 12 14 16

Combined Appliance Input Rating in Thousands of Btu per HourFAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

681015203050100

54760264975384297911641408

4344805226126888089771215

335378405465523605705800

6727408009241035120914511784

52057762773382697511881502

410465495565640740860975

900994107612471405165820242569

6967738419861116132716402131

588652712825916102512801670

12841423154217942006237329113732

9901103120014101588189223473076

81591299511581290152518632450

17351927209324402722322039645125

13361491162519102147255831834202

10651190130015101690199024303200

Table 8-10Type B Double-Wall Vent [NFPA 54: Table 13.2(a)] (continued)

Page 32: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-10 continued

124

Number of Appliances: Two or MoreAppliance Type: Category I

Appliance Vent Connection: Type B Double-Wall ConnectorVent Connector Capacity

VentHeight

H(ft)

ConnectorRise

R(ft)

Type B Double-Wall Vent and Connector Diameter – D (in.)16 18 20 22 24

Appliance Input Rating in Thousands of Btu per HourFAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 123

281287NA

13711617NA

8531081NA

346352NA

17722069NA

10801370NA

NANANA

NANANA

NANANA

NANANA

NANANA

NANANA

NANANA

NANANA

NANANA

8 123

298305313

147817191902

91011501390

365372380

192022112434

115014601770

NA471478

NA27373018

NA18002180

NA560568

NA33193665

NA21802640

NA662669

NA39574373

NA25903130

10 123

311318325

157018041989

95512051455

379387395

204923322556

120515351865

NA486494

NA28873169

NA18902290

NA581589

NA35023849

NA22802760

NA686694

NA41754593

NA27103270

15 123

336344351

176019782157

103013201610

408416424

231725792796

130516652025

NA523533

NA31973470

NA20602510

NA624634

NA38814216

NA24903030

NA734743

NA46315035

NA29603600

20 123

357365373

191121162287

109513951695

430438450

253327782984

138517652145

NA554567

NA34473708

NA21802650

NA661671

NA41904511

NA26303190

NA772785

NA50055392

NA31303790

30 123

367376384

218323662524

119015101830

461474485

289131103299

154019202340

NA619632

NA38404080

NA23652875

NA728741

NA48614976

NA28603480

NA847860

NA56065961

NA34104150

50 123

350359369

265928142951

131516852055

435447461

354837303893

166521352605

NA580594

NA46014808

NA26333208

NA709724

NA55695826

NA31853885

NA851867

NA66336943

NA37904620

100 123

326336346

349036063714

137017602150

402414426

470748424968

174022202700

NA523539

NA59826143

NA27503350

NA639654

NA72547453

NA33304070

NA769786

NA86508892

NA39504810

Common Vent Capacity

VentHeight

H(ft)

Type B Double-Wall Common Vent Diameter – D (in.)18 20 22 24

Combined Appliance Input Rating in Thousands of Btu per HourFAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

681015203050100

22532507272731843561419751846749

17321936211324842798332641495509

13451510164519102140252030754050

28383162344440264548530365678597

21802439266531333552419352406986

16601860203023602640311038005000

348838904241497155736539811610,681

26772998327838624352515764588648

19702200240027903120368045005920

420646955123601667497940983713,004

322636163957467052616247781310,499

23902680292034003800448054757200

Table 8-10Type B Double-Wall Vent [NFPA 54: Table 13.2(a)] (continued)

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 33: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-11 continued

125

Number of Appliances: Two or MoreAppliance Type: Category I

Appliance Vent Connection: Single-Wall Metal ConnectorVent Connector Capacity

VentHeight

H(ft)

ConnectorRise

R(ft)

Single-Wall Metal Vent Connector Diameter – D (in.)3 4 5 6 7

Appliance Input Rating in Thousands of Btu per HourFAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 123

NANANA

NANANA

263134

NANANA

NANANA

465562

NANA121

NANA131

718595

NA168175

NA182198

102123138

207215222

223251273

140167188

8 123

NANANA

NANANA

273235

NANANA

NANANA

485764

NA125130

NA126138

7589100

NA184191

NA193208

106127144

226234241

240266287

145173197

10 123

NANANA

NANANA

283336

NA8489

NA8591

505967

119124129

121134144

7791102

182189197

186203217

110132148

240248257

253278299

150183203

15 123

NANANA

NANANA

293439

798387

8794100

526270

116121127

138150160

8197109

177185193

214230243

116138157

238246255

291314333

158189215

20 123

495255

565962

303640

788287

97103107

546472

115120125

152163172

84101113

175182190

238252264

120144164

233243252

325346363

165197223

30 123

475154

606264

313742

778185

110115119

576776

112117122

175185193

89106120

169177185

278290300

129152172

226236244

380397412

175208235

50 123

464952

697172

344045

757983

128132136

607282

109114119

207215221

96113123

162170178

336345353

137164186

217226235

460473486

188223252

100 123

454851

798081

344146

717579

150153157

617385

104110114

249255260

98115129

153160168

424428433

140167190

205212222

585593603

192228256

Table 8-11Type B Double-Wall Vent [NFPA 54: Table 13.2(b)]

Common Vent Capacity

VentHeight

H(ft)

Type B Double-Wall Common Vent Diameter – D (in.)4 5 6 7

Combined Appliance Input Rating in Thousands of Btu per HourFAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

681015203050100

NANANA121131145159166

788794108118132145153

6471768898113128NA

NANA163189208236268297

113126137159177202233263

99111120140156180208NA

200218237275305350406469

158173189221247286337398

144159174200223257296NA

304331357416463533622725

244269292343383446529633

196218236274302349410464

Page 34: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-11 continued

126

Number of Appliances: Two or MoreAppliance Type: Category I

Appliance Vent Connection: Single-Wall Metal ConnectorVent Connector Capacity

VentHeight

H(ft)

ConnectorRise

R(ft)

Single-Wall Metal Vent Connector Diameter – D (in.)8 9 10

Appliance Input Rating in Thousands of Btu per HourFAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max

6 123

262271279

293331361

183219247

325334344

373422463

234281316

447458468

463524574

286344385

8 123

285293302

316253381

191228256

352360370

403450489

244292328

481492501

502560609

299355400

10 123

302311320

335369398

196235265

372381391

429473511

252302339

506517528

534589637

308368413

15 123

312321331

380411438

208248281

397407418

482522557

266317360

556568579

596646690

324387437

20 123

306317326

425453476

217259294

390400412

538574607

276331375

546558570

664709750

336403457

30 123

296307316

497521542

230274309

378389400

630662690

294349394

528541555

779819855

358425482

50 123

284294304

604623640

245293331

364376387

768793816

314375423

507520535

9519831013

384458518

100 123

269279289

774788801

249299339

345358368

99310111027

321383431

476490506

123612591280

393469527

Common Vent Capacity

VentHeight

H(ft)

Type B Double-Wall Common Vent Diameter – D (in.)8 9 10

Combined Appliance Input Rating in Thousands of Btu per HourFAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

681015203050100

398436467544606703833999

310342369434487570686846

257285309357395459535606

54159263873882495811391378

4294735125996737909541185

332373398456512593689780

6657307879051013118314181741

51556961771880895211571459

407460487553626723838948

Table 8-11Type B Double-Wall Vent [NFPA 54: Table 13.2(b)] (continued)

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 35: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-12

127

Number of Appliances: Two or MoreAppliance Type: Category I

Appliance Vent Connection: Type B Double-Wall ConnectorVent Connector Capacity

VentHeight

H(ft)

ConnectorRise

R(ft)

Type B Double-Wall Vent Connector Diameter – D (in.)3 4 5 6 7

Appliance Input Rating in Thousands of Btu per HourFAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 123

242627

334349

212834

394142

627992

405261

525355

106133155

678597

656769

194230262

101124143

878991

274324369

141173203

8 123

242627

394752

222934

394042

728797

415362

555759

117140159

698698

717375

213246269

105127145

949799

304350383

148179206

10 123

242627

425055

222935

384041

8093105

425463

555758

130153170

7187100

747678

232261284

108129148

101103106

324366397

153184209

15 123

242526

485559

233135

383941

93105115

445564

545657

154174189

7489102

727476

277299319

114134153

100103105

384419448

164192215

20 123

242526

525863

243135

373940

102114123

465665

535557

172190204

7791104

717375

313335353

119138157

98101104

437467493

173199222

30 123

242526

546064

253236

373840

111122131

485866

525456

192208221

8295107

697274

357376392

127145163

9699101

504531554

187209233

50 123

232426

515964

253236

363739

116127135

516169

515355

209225237

89102115

677072

405421435

143161180

929598

582604624

213235260

100 123

232425

465359

243135

353738

108120130

506068

495153

208224237

92105118

656769

428444458

155174193

889294

640660679

237260285

Common Vent Capacity

VentHeight

H(ft)

Minimum Internal Area of Masonry Chimney Flue (in.2)12 19 28 38 50

Combined Appliance Input Rating in Thousands of Btu per HourFAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

681015203050100

NANANANANANANANA

748084NANANANANA

2528313641NANANA

NANANANANANANANA

119130138152NANANANA

4653566775NANANA

NANANANANANANANA

178193207233250270NANA

718290106122137NANA

NANANANANANANANA

257279299334368404NANA

103119131152172198NANA

NANANA523565615NANA

351384409467508564620NA

143163177212243278328348

Table 8-12Masonry Chimney [NFPA 54: Table 13.2(c)]

Page 36: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-12 continued

128

Number of Appliances: Two or MoreAppliance Type: Category I

Appliance Vent Connection: Single-Wall Metal ConnectorVent Connector Capacity

VentHeight

H(ft)

ConnectorRise

R(ft)

Type B Double-Wall Vent Connector Diameter – D (in.)8 9 10

Appliance Input Rating in Thousands of Btu per HourFAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max

6 123

104107109

370436491

201232270

124127129

479562633

253300349

145148151

599694795

319378439

8 123

113116119

414473517

210240276

134137139

539615672

267311358

156160163

682776848

335394452

10 123

120123126

444498540

216247281

142145147

582652705

277321366

165168171

739825893

348407463

15 123

125128131

511558597

229260292

153156159

658718760

297339382

184187190

824900960

375432486

20 123

123126129

584625661

239270301

150153156

752805851

312354396

180184187

94310111067

397452505

30 123

119122125

680715746

255287217

145149152

883928968

337378418

175179182

111511711220

432484535

50 123

115118121

798827854

294326357

140143147

104910851118

392433474

168172176

133413791421

506558611

100 123

109113116

907933956

334368399

134138141

122212531282

454497540

161165169

158916261661

596651705

Common Vent Capacity

VentHeight

H(ft)

Minimum Internal Area of Masonry Chimney Flue (in.2)63 78 113

Combined Appliance Input Rating in Thousands of Btu per HourFAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

681015203050100

NANA606682742816879NA

458501538611668747831NA

188218236283325381461499

NA72477687495510621165NA

5826366867818589691089NA

246278302365419496606669

10411144122613741513170219052053

853937101011561286147316921921

NA4084545466487499221058

Table 8-12Masonry Chimney [NFPA 54: Table 13.2(c)] (continued)

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 37: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-13

129

Number of Appliances: Two or MoreAppliance Type: Category I

Appliance Vent Connection: Single-Wall Metal ConnectorVent Connector Capacity

VentHeight

H(ft)

ConnectorRise

R(ft)

Single-Wall Metal Vent Connector Diameter – D (in.)3 4 5 6 7

Appliance Input Rating Limits in Thousands of Btu per HourFAN NAT FAN NAT FAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max

6 123

NANANA

NANANA

212834

NANANA

NANANA

395261

NANA134

NANA153

668497

179186193

191227258

100123142

231239247

271321365

140172202

8 123

NANANA

NANANA

212834

NANANA

NANANA

405262

NA137143

NA139156

688598

195202210

208240264

103125145

250258266

298343376

146177205

10 123

NANANA

NANANA

222934

NANA97

NANA102

415362

130136143

151150166

708699

202210217

225255277

106128147

267276284

316358389

151181207

15 123

NANANA

NANANA

233034

NA9296

NA103112

435463

129135141

151170185

7388101

199207215

271295315

112132151

268277286

376411439

161189213

20 123

NANANA

NANANA

233035

879196

99111119

455564

128134140

167185199

7690103

197205213

303325343

117136154

265274282

425455481

169195219

30 123

NANANA

NANANA

243135

869195

108119127

475765

126132138

187203216

8093105

193201209

347366381

124142160

259269277

492518540

183205229

50 123

NANANA

NANANA

243135

858994

113123131

506068

124130136

204218231

87100112

188196205

392408422

139158176

252262271

567588607

208230255

100 123

NANANA

NANANA

233034

848893

104115124

495967

122127133

200215228

89102115

182190199

410425438

151169188

243253262

617636654

232254279

Common Vent Capacity

VentHeight

H(ft)

12 19 28 38 50Combined Appliance Input Rating in Thousands of Btu per Hour

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

681015203050100

NANANANANANANANA

NANANANANANANANA

25283136NANANANA

NANANANANANANANA

118128136NANANANANA

4552566674NANANA

NANANANANANANANA

176190205230247NANANA

718189105120135NANA

NANANANANANANANA

255276295335362398NANA

102118129150170195NANA

NANANANANANANANA

348380405400503558612NA

142162175210240275325NA

Table 8-13Masonry Chimney [NFPA 54: Table 13.2(d)]

Page 38: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-13 continued

130

Number of Appliances: Two or MoreAppliance Type: Category I

Appliance Vent Connection: Single-Wall Metal ConnectorVent Connector Capacity

VentHeight

H(ft)

ConnectorRise

R(ft)

Single-Wall Metal Vent Connector Diameter – D (in.)8 9 10

Appliance Input Rating Limits in Thousands of Btu per HourFAN NAT FAN NAT FAN NAT

Min Max Max Min Max Max Min Max Max

6 123

292301309

366432491

200231269

362373381

474557634

252299348

499509519

594696793

316376437

8 123

313323332

407465509

207238274

387397407

530607663

263309356

529540551

672766838

331391450

10 123

333343352

434489530

213244279

410420430

571640694

273317363

558569580

727813880

343403459

15 123

349359368

502548586

225256289

445456466

646706755

291334378

623634646

808884945

366424479

20 123

345355365

569610644

235266298

439450461

734787831

306348391

614627639

9219861042

387443496

30 123

338348358

665699729

250282312

430442452

864908946

330372412

600613626

108911451193

421473524

50 123

328339349

778806831

287320351

417429440

102210581090

383425466

582596610

130213461386

492545597

100 123

315326337

875899921

328361392

402415427

118112101238

444488529

560575589

153715701604

580634687

Common Vent Capacity

VentHeight

H(ft)

Minimum Internal Area of Masonry Chimney Flue (in.2)63 78 113

Combined Appliance Input Rating in Thousands of Btu per HourFAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

FAN+FAN

FAN+NAT

NAT+NAT

681015203050100

NANANA677765808NANA

455497532602661739821NA

187217234280321377456494

NANA77186694710521152NA

5796336807728499571076NA

245277300360415490600663

NA1136121613591495168218792006

846928100011391264144716721885

NA4054505406407409101046

Table 8-13Masonry Chimney [NFPA 54: Table 13.2(d)] (continued)

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 39: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-14 continued

131

Number of Appliances: Two or MoreAppliance Type: Draft Hood-Equipment

Appliance Vent Connection: Direct to Pipe or VentVent Connector Capacity

Total Vent HeightH(ft)

ConnectorRise

R(ft)

Vent Connector Diameter – D (in.)3 4 5 6 7 8

Maximum Appliance Input Rating in Thousands of Btu per Hour6-8 1

23

212834

405361

688698

102124147

146178204

205235275

15 123

233035

445664

7792102

117134155

179194216

240265298

30and up

123

253136

495868

8497107

129145164

190211232

270295321

Common Vent Capacity

Total Vent HeightH(ft)

Common Vent Diameter – D (in.)4 5 6 7 8 10 12

Combined Appliance Input Rating in Thousands ofBtu per Hour

681015203050

4855597180NANA

788995115129147NA

111128136168186215NA

155175190228260300360

205234250305340400490

320365395480550650810

NA5055606907909401190

Table 8-14Single-Wall Metal Pipe or Type B Asbestos Cement Vent [NFPA 54: Table 13.2(e)]

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 40: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-15

132

Number of Appliances: SingleAppliance Type: NAT

Appliance Vent Connection: Type B Double-Wall ConnectorINTENDED USE: Minimum allowable Input Rating of Space-Heating Appliance in Thousands of Btu per Hour

Vent HeightH (ft)

Internal Area of chimney (in.2)12 19 28 38 50 63 78 113

Local 99% winter design temperature: 37ºF or lower681015203050

000

NANANANA

0000

NANANA

0000

123NANA

0000

190NANA

0000

249NANA

0000

184393NA

00000

334NA

000000

579Local 99% winter design temperature: 27ºF to 36ºF

681015203050

000

NANANANA

0051NANANANA

688297NANANANA

116127141NANANANA

156167183233NANANA

180187201253307419NA

212214225274330445NA

266263265305362485763

Local 99% winter design temperature: 17ºF to 26ºF681015203050

NANANANANANANA

NANANANANANANA

NANANANANANANA

NANANANANANANA

NA197214NANANANA

215226245296352NANA

259264278331387507NA

349352358398457581NA

Local 99% winter design temperature: 5ºF to 16ºF681015203050

NANANANANANANA

NANANANANANANA

NANANANANANANA

NANANANANANANA

NANANANANANANA

NANA289NANANANA

NA312331393450NANA

416423430485547682972

Local 99% winter design temperature: -10ºF to 4ºF681015203050

NANANANANANANA

NANANANANANANA

NANANANANANANA

NANANANANANANA

NANANANANANANA

NANANANANANANA

NANANANANANANA

4844945135866508051003

Local 99% winter design temperature -11ºF or lowerNot recommended for any vent configurations

Table 8-15Exterior Masonry Chimney [NFPA 54: Table 13.1(f)]

For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, ºC = (ºF - 32)/1.8Note: See Figure G.2.4 for a map showing local 99 percent winter design temperatures in the United States.

Page 41: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-16

133

Number of Appliances: Two or MoreAppliance Type: NAT + NAT

Appliance Vent Connection: Type B Double-Wall ConnectorINTENDED USE: Combined Appliance Maximum Input Rating in Thousands of Btu per Hour

Vent HeightH(ft)

Internal Area of Chimney (in.2)

12 19 28 38 50 63 78 113

681015203050100

252831NANANANANA

46535667NANANANA

718290106NANANANA

103119131152NANANANA

143163177212NANANANA

188218236283325NANANA

246278302365419496NANA

NA408454546648749922NA

Table 8-16Exterior Masonry Chimney [NFPA 54: Table 13.2(f)]

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 42: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-17

134

Number of Appliances: Two or MoreAppliance Type: NAT + NAT

Appliance Vent Connection: Type B Double-Wall ConnectorINTENDED USE: Minimum Allowable Input Rating of Space-Heating Appliance in Thousands of Btu per Hour

Vent HeightH(ft)

Internal Area of Chimney (in.2)

12 19 28 38 50 63 78 113

Local 99% winter design temperature: 37ºF or greater681015203050100

000NANANANANA

0000NANANANA

0000NANANANA

0000NANANANA

0000NANANANA

0000184393NANA

00000334NANA

NA00000579NA

Local 99% winter design temperature: 27ºF to 36ºF681015203050100

000NANANANANA

0051NANANANANA

6882NANANANANANA

NANANANANANANANA

NANANANANANANANA

180187201253307NANANA

212214225274330445NANA

NA263265305362485763NA

Local 99% winter design temperature: 17ºF to 26ºF681015203050100

NANANANANANANANA

NANANANANANANANA

NANANANANANANANA

NANANANANANANANA

NANANANANANANANA

NANANANANANANANA

NA264278331387NANANA

NA352358398457581862NA

Local 99% winter design temperature: 5ºF to 16ºF681015203050100

NANANANANANANANA

NANANANANANANANA

NANANANANANANANA

NANANANANANANANA

NANANANANANANANA

NANANANANANANANA

NANANANANANANANA

NANA430485547682NANA

Local 99% winter design temperature: 4ºF or lowerNot recommended for any vent configurations

Table 8-17Exterior Masonry Chimney [NFPA 54: Table 13.2(g)]

For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, ºC = (ºF - 32)/1.8Note: See Figure G.2.4 for a map showing local 99 percent winter design temperatures in the United States.

Page 43: Uniform Mechanical Code- 2009 Chapter 8

CHIMNEYS AND VENTS Table 8-18

135

Number of Appliances: Two or MoreAppliance Type: FAN + NAT

Appliance Vent Connection: Type B Double-Wall ConnectorINTENDED USE: Combined Appliance Maximum Input Rating in Thousands of Btu per Hour

Vent HeightH(ft)

Internal Area of Chimney (in.2)

12 19 28 38 50 63 78 113

681015203050100

748084NANANANANA

119130138152NANANANA

178193207233250NANANA

257279299334368404NANA

351384409467508564NANA

458501538611668747831NA

5826366867818589691089NA

853937101011561286147316921921

Table 8-18Exterior Masonry Chimney [NFPA 54: Table 13.2(h)]

For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1 in.2 = 645 mm2, 1,000 Btu/hr = 0.293 kW

Page 44: Uniform Mechanical Code- 2009 Chapter 8

UNIFORM MECHANICAL CODETable 8-19

136

Number of Appliances: Two or MoreAppliance Type: FAN + NAT

Appliance Vent Connection: Type B Double-Wall ConnectorINTENDED USE: Minimum Allowable Input Rating of Space-Heating Appliance in Thousands of Btu per Hour

Vent HeightH(ft)

Internal Area of Chimney (in.2)

12 19 28 38 50 63 78 113

Local 99% winter design temperature: 37ºF or greater681015203050100

000NANANANANA

0000NANANANA

0000123NANANA

0000190334NANA

0000249398NANA

0000184393714NA

00000334707NA

0000005791600

Local 99% winter design temperature: 27ºF to 36ºF681015203050100

000NANANANANA

0051111NANANANA

688297142187NANANA

116127141183230330NANA

156167183233284319NANA

180187210253307419672NA

212214225274330445705NA

2662632653053624857631554

Local 99% winter design temperature: 17ºF to 26ºF681015203050100

052NANANANANANA

557490NANANANANA

99111125167212NANANA

141154169212258362NANA

182197214263316429NANA

215226245296352470723NA

259264278331387507766NA

3493523583984575818621669

Local 99% winter design temperature: 5ºF to 16ºF681015203050100

NANANANANANANANA

7894111NANANANANA

121135149193NANANANA

166182198247293377NANA

214230250305360450NANA

252269289346408531797NA

301312331393450580853NA

4164234304855476829721833

Local 99% winter design temperature: -10ºF to 4ºF681015203050100

NANANANANANANANA

NANANANANANANANA

145159175NANANANANA

196213231283333NANANA

249269292351408NANANA

296320339404468603NANA

349371397457528667955NA

4844945135866508051003NA

Local 99% winter design temperature: -11ºF or lowerNot recommended for any vent configurations

Table 8-19Exterior Masonry Chimney [NFPA 54: Table 13.2(i)]

For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW .Note: See Figure G.2.4 for a map showing local 99 percent winter design temperatures in the United States.


Recommended