Sheet 2 PLC-5Item Pt. no. Description Qty VA D.F Total Reference
1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H 2 7.5 1 15 Page 62 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE 4 0.77 1 3.08 Page 73 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY 2 20 1 40 Page 84 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 95 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 1 11 1 11 Page 106 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331 2 0.4 1 0.8 Page 117 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321 5 6.5 1 32.5 Page 128 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322 2 6.6 1 13.2 Page 139 6ES7197-1LA04 -0XA0 Y-Link for S7-400H SIMATIC S7-400H, Y-LINK 1 0 0 0 Page 1410 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical 42 0.5 1 21 Page 2514 FIT-201A/B Magnetic flow meters DN 500 2 15 1 30 Page 2615 LSH-201A/B Level switch for hazarouds 2 2.5 1 5 Page 2716 LIT-201A/B level indicator transmitter 2 23 1 46 Page 2817 PIT-201A/B/C/D/E/F Pressure transmitter 6 0.4 1 2.4 Page 29
232.70
232.7300
Al- Wefaq Control System
TOTAL IN VA
SummationAuxiliary Rate
UPS Load Calculation for Industrial Area Pumping Station PLC panelProject: -
Rev. 0
Page 1 of 43
Sheet 3,4 PLC-4Item Pt. no. Description Qty VA D.F Total Reference
1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H, CENTRAL UNIT 2 7.5 1 15 Page 62 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE FOR 4 0.77 1 3.08 Page 73 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY PS407: 10A, WIDERANGE, 120/230V UC 2 20 1 40 Page 84 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 95 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 2 11 1 22 Page 106 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331,OPTICALLY ISOLATED, 8 AI, 13 BIT 2 0.4 1 0.8 Page 117 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321,OPTICALLY ISOLATED 32DI 8 6.5 1 52 Page 128 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322,OPTICALLY ISOLATED, 3 6.6 1 19.8 Page 139 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical indicator 74 0.5 1 37 Page 2510 DLIT-301C Differential Level Indicator Transmitters 3 0.5 1 1.5 Page 3011 AIT-401 Hydrocarbon Analyzer 1 0.6 1 0.6 Page 3112 ASS-401 Auto Sampler 1 290 1 290 Page 3213 FIT-401 FIT-401B Open Channel Ultrasonic level type flowmeter 2 23 1 46 Page 28
540.50
540.5600
Al- Wefaq Control System
TOTAL IN VA
SummationAuxiliary Rate
UPS Load Calculation Inlet Works panelProject: -
Rev. 0
Page 2 of 43
Sheet 5,6,7 SBR-PLCItem Pt. no. Description Qty D.F Total Reference
1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H, CENTRAL UNIT 2 7.5 1 15 Page 62 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE FOR PATCH CABLES UP TO 10M 4 0.77 1 3.08 Page 73 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY PS407: 10A 2 20 1 40 Page 84 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 95 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 5 11 1 55 Page 106 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331 13 0.4 1 5.2 Page 117 6ES7332-5HF00-0AB0 SIMATIC S7-300, ANALOG OUTPUT SM 332 3 6 1 18 Page 158 6ES7321-1BH02-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321 25 3.5 1 87.5 Page 169 6ES7322-1BH01-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322 9 4.9 1 44.1 Page 1710 6ES7197-1LA04 -0XA0 Y-Link for S7-400H SIMATIC S7-400H, Y-LIN 1 0 0 0 Page 1411 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical indicator 104 0.5 1 52 Page 2512 PIT-501A/B PIT601A/B Pressure Transmitter 4 0.5 1 2 Page 3313 LIT-501A/B LIT-601A/B Level Indicator Transmitters 4 23 1 92 Page 2814 Viberation Sensor 10 0.5 1 5 Page 3415 FIT-701A/B Differential Pressure Type 2 0.5 1 1 Page 30
16
AIT-501A/B/C AIT-502A/B/C AIT-601A/B/C AIT-602A/B/C LIT-502A/B LIT-602A-B AIT-503
Analyzers 17 55 1 935 Page 35
1367.60
1367.61400
UPS Load Calculation SBR PLC panelAl- Wefaq Control System
TOTAL IN VA
SummationAuxiliary Rate
Project: -
Rev. 0
VA
Page 3 of 43
Item Pt. no. Description Qty VA D.F Total Reference
1 6ES7214-1AG31-0XB0 SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC 1 12 1 12 Page 372 6ES7221-1BH30-0XB0 SIMATIC S7-1200, DIGITAL INPUTSM 1221 , 16DI, 24 V DC, S 5 2.5 1 12.5 Page 383 6ES7222-1BH30-0XB0 SIMATIC S7-1200, DIGITAL OUTPUT SM 1222, 16 DO, 2 2.5 1 5 Page 394 6ES7231-4HF30-0XB0 SIMATIC S7-1200, ANALOG INPUT, SM 1231, 5 1.5 1 7.5 Page 405 6AV6647-0AB11-3AX0 SIMATIC HMI ,KTP600 BASIC ,MONO PN 1 6 1 6 Page 416 6GK7242-5DX30-0XE0 COMMUNICATION MODULE CM 1242-5 1 0.75 1 0.75 Page 427 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +m. indicator 21 0.5 0.6 6.3 Page 258 55.34.9.024.0040 Relay 24 VDC, 7A ,4 Pole, Lockable test button 14 1 0.6 8.4 Page 439 - Loop Powered Signal 3 0.576 1 1.728 not avaliable
60.178
10 6ES7214-1AG31-0XB0 SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC 1 12 1 1211 6ES7221-1BH30-0XB0 SIMATIC S7-1200, DIGITAL INPUTSM 1221 , 16DI, 24 V DC, S 5 2.5 1 12.512 6ES7222-1BH30-0XB0 SIMATIC S7-1200, DIGITAL OUTPUT SM 1222, 16 DO, 2 2.5 1 513 6ES7231-4HF30-0XB0 SIMATIC S7-1200, ANALOG INPUT, SM 1231, 5 1.5 1 7.514 6AV6647-0AB11-3AX0 SIMATIC HMI ,KTP600 BASIC ,MONO PN 1 6 1 615 6GK7242-5DX30-0XE0 COMMUNICATION MODULE CM 1242-5 1 0.75 1 0.7516 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +m. indicator 21 0.5 0.6 6.317 55.34.9.024.0040 Relay 24 VDC, 7A ,4 Pole, Lockable test button 14 1 0.6 8.418 - Loop Powered Signal 3 0.576 1 1.728
60.178120.356
0
120.356200
Odor 1 PLC Panel
Odor 2 PLC Panel
The Same as Odor 1 PLC
Panel
UPS Load Calculation OCU PLC panelAl- Wefaq Control System
TOTAL IN VA
SummationAuxiliary Rate
Project: -
Rev. 0
Page 4 of 43
Item Pt. no. Description Qty VA D.F Total Reference1 6ES7405-0KA02-0AA0 SIMATIC S7-400 , PS 405 2 95 1 190 Page 182 6ES7412-3HJ14-0AB0 SIMATIC S7-400H, CPU412H 2 5.5 1 11 Page 193 6ES7960-1AA04-0XA0 SIMATIC S7-400H, SYNC SUB MODULE 2 0.0011 1 0.0022 Page 204 6EP1 333-3BA00 SITOP MODULAR 5A 2 18 1 36 Page 215 6ES7153-2AR03-0XA0 IM153-2 INTERFACE REDUND.BUNDLE 3 5.5 1 16.5 Page 226 6ES7321-1BL00-0AA0 32DI DIGITAL INPUT MODULE 9 6.5 1 58.5 Page 127 6ES7322-1BL00-0AA0 32DO DIGITAL OUTPUT MODULE 8 6.6 1 52.8 Page 138 6ES7331-1KF02-0AA0 8AI ANALOG INPUT MODULE, 4-20mA 4 0.4 1 1.6 Page 239 6GK1503-3CB00 OLM/G12 2 4.8 1 9.6 Page 2410 6ES7197-1LA04-0XA0 Y-Link 1 0 0 0 Page 1411 46.52.9.024.0040 2-CONTACT RELAY 24VDC 300 0.5 1 150 Page 2512 SCADA system computer 1 535 1 535 not avaliable13 Printer 1 70 1 70 not avaliable
14 FIT-1001A/B/C/D/E/F FIT-1002 FIT-1003A/B Magnetic flow meters DN 200/400/500 9 15 1 135 Page 26
15 AIT-1002 TUT-1001 Nitrate/Turbidity analyzers 2 55 1 110 Page 3516 AIT-1001 hydro-carbon analyzer 1 0.6 1 0.6 Page 3117 flow switch low 19 10 1 190 Page 3618 LIT-1001 level transmitter 1 23 1 23 Page 28
19 PIT-1001:6A/BPIT-1001:6C Pressure transmitter 20 0.5 1 10 Page 33
20 Solenoid valve of pneumatic 40 15 1 600 not avaliable
2199.60
2199.62200
UPS Load Calculation Ultrafilters PLC panelAl- Wefaq Control System
TOTAL IN VA
SummationAuxiliary Rate
Project: -
Rev. 0
Page 5 of 43
Power losses
Power loss, typ. 7.5 W
Backup battery
Battery operation
Backup current, typ. 180 μA ; Valid up to 40°C
Backup current, max. 1000 μA
Backup time, max. Dealt with in the module data manual with thesecondary conditions and the factors of influence
Feeding of external backup voltage to CPU 5 to 15 VDC
Feeding of external backup voltage to CPU 5 to 15 VDC
Memory
Work memory
integrated 4 Mbyte
integrated (for program) 2 Mbyte
integrated (for data) 2 Mbyte
expandable No
Load memory
expandable FEPROM Yes ; with Memory Card (FLASH)
expandable FEPROM, max. 64 Mbyte
integrated RAM, max. 512 kbyte
expandable RAM Yes
expandable RAM, max. 64 Mbyte
Backup
present Yes
with battery Yes ; all data
without battery No
CPU processing times
for bit operations, min. 18.75 ns
for word operations, min. 18.75 ns
for fixed point arithmetic, min. 18.75 ns
for floating point arithmetic, min. 37.5 ns
CPU-blocks
DB
Number, max. 6000 ; Number range: 1 - 16.000
6ES7414-5HM06-0AB0 Page 2
Date:07/27/2012
subject to modifications© Copyright Siemens AG 201232
Page 6 of 43
productdatablad 6ES7960-1AA06-0XA0
-
SIMATIC S7-400H,SYNC SUBMODULE V6 FOR PATCH CABLES UP TO 10M
Input current
from CPU, max. 220 mA
Power losses
Power loss, typ. 0,77 W
Dimensions
Breedte 13 mm
Hoogte 14 mm
Diepte 58 mm
Weight
Weight, approx. 14 g
Status 6-jul-2013
6ES7960-1AA06-0XA0Page 1/ 20.07.2013
subject to modifications© Copyright Siemens AG 20131
Page 7 of 43
Input current
Rated value at 110 V DC 1 A ; at 120 V DC
Rated value at 230 V DC 0.5 A
Rated value at 120 V AC 0.9 A
Rated value at 230 V AC 0.5 A
Inrush current, max. 63 A ; Full width at half maximum 1 ms
Output voltage
Rated value, 5 V DC Yes
Rated value, 24 V DC Yes
Output current
for backplane bus (5 V DC), max. 10 A ; no base load required
for backplane bus (24 V DC), max. 1 A ; idling-proof
Short-circuit protection Yes
Power
Power consumption, typ. 95 W
Power losses
Power loss, typ. 20 W
Backup battery
Backup battery
Backup battery (optional) Yes ; 2 x lithium AA; 3.6 V/2.3 Ah
Galvanic isolation
primary/secondary Yes
EMC
Compliance with line harmonic distortion limits
Observance of line harmonic distortion acc. to IEC61000-3-2, IEC 61000-3-3
Yes
Degree and class of protection
Protection class 1 ; with protective conductor
Standards, approvals, certificates
FM approval Yes ; Ta: 0 °C to 60 °C T4
Connection method
Connecting cables/cross sections 3 x 1.5 mm2, solid or stranded wire with end sleeve,external diameter 3 to 9 mm
Dimensions
6ES7407-0KA02-0AA0 Page 2
Date:06/28/2012
subject to modifications© Copyright Siemens AG 2012
26
Page 8 of 43
Attenuation / of fiber-optic cable transmission link / minimumnecessary
0 dB
Range / at the optical interface / depending on the optical fiber used 0 … 5 km
design of the removable storage / C-PLUG Yes
Inputs/outputs
Operating voltage / of signaling contacts / at DC / rated value 24 V
Operating current / of signaling contacts / at DC / maximum 0.1 A
Supply voltage, current consumption, power loss
Type of voltage / of supply voltage DC
Supply voltage / external 24 V
• minimum 18 V
• maximum 32 V
Product component / fusing at power supply input Yes
Type of fusing / at input for supply voltage 0,6 A / 60 V
Consumed current / maximum 0.265 A
Active power loss / at 24 V / for DC 6.36 W
Permitted ambient conditions
Ambient temperature
• during operating -40 … +60 °C
• during storage -40 … +70 °C
• during transport -40 … +70 °C
Relative humidity / at 25 °C / without condensation / during operating/ maximum
95 %
Protection class IP IP30
Design, dimensions and weight
Design compact
Width 60 mm
Height 125 mm
Depth 124 mm
Net weight 0.78 kg
Type of mounting
• 35 mm DIN rail mounting Yes
• wall mounting Yes
• S7-300 rail mounting Yes
Product properties, functions, components / general
Cascading in the case of a redundant ring / at reconfiguration time of<\~0.3\~s
50
Cascading in cases of star structuring Any (depending only on signal propagation time)
Product function
• CLI Yes
6GK5204-2BB10-2AA3Page 2/ 12/03/2012
subject to modifications© Copyright Siemens AG 20124
108 Page 9 of 43
I²t 0.1 A²·s
Output voltage
Rated value, 5 V DC Yes
Output current
for backplane bus (5 V DC), max. 1.5 A
Power losses
Power loss, typ. 5.5 W
Address area
Addressing volume
Outputs 244 byte
Inputs 244 byte
Hardware configuration
Number of modules per DP slave interface, max. 12
Time stamping
Accuracy 1 ms ; 1ms at up to 8 modules; 10ms at up to 12modules
Number of message buffers 15
Messages per message buffer 20
Number of stampable digital inputs, max. 128 ; Max. 128 signals/station; max. 32 signals/slot
Time format RFC 1119
Time resolution 0.466 ns
Time interval for transmitting the message buffer if amessage is present
1000 ms
Time stamp on signal change rising / falling edge as signal entering or exiting
Interfaces
Interface physics, RS 485 Yes
Interface physics, FOC No
PROFIBUS DP
Node addresses 1 to 125 permitted
Automatic detection of transmission speed Yes
PROFIBUS DP, output current, max. 70 mA
Transmission procedure RS 485
Transmission rate, max. 12 Mbit/s
SYNC capability Yes
6ES7153-2BA02-0XB0 Page 2
Date:02/14/2012
subject to modifications© Copyright Siemens AG 2012
60
Page 10 of 43
Product data sheet 6ES7331-1KF02-0AB0
SIMATIC S7-300, ANALOG INPUT SM 331,OPTICALLY ISOLATED, 8 AI,13 BIT RESOLUTION,U/I/RESISTANCE/PT100, NI100, NI1000,LG-NI1000, PTC / KTY,66 MS MODULE UPDATE, 1 X 40 PIN
Input current
from backplane bus 5 V DC, max. 90 mA
Power losses
Power loss, typ. 0.4 W
Analog inputs
Number of analog inputs 8
Number of analog inputs for resistancemeasurement
8
permissible input voltage for voltage input(destruction limit), max.
30 V ; 12 V continuous, 30 V for max. 1 s
permissible input current for current input(destruction limit), max.
40 mA
Input ranges
Voltage Yes
Current Yes
Thermocouple No
6ES7331-1KF02-0AB0 Page 1
Date:01/09/2012
subject to modifications© Copyright Siemens AG 2012
73
6ES7331-1KF02-0AB0
Page 11 of 43
Product data sheet 6ES7321-1BL00-0AA0
SIMATIC S7-300, DIGITAL INPUT SM 321,OPTICALLY ISOLATED 32DI, 24 V DC,1 X 40 PIN
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 15 mA
Power losses
Power loss, typ. 6.5 W
Digital inputs
Number/binary inputs 32
Input characteristic curve acc. to IEC 61131, Type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
up to 40 °C, max. 32
6ES7321-1BL00-0AA0 Page 1
Date:01/29/2012
subject to modifications© Copyright Siemens AG 201265-1
6ES7321-1BL00-0AA0
Page 12 of 43
Product data sheet 6ES7322-1BL00-0AA0
SIMATIC S7-300, DIGITAL OUTPUT SM 322,OPTICALLY ISOLATED, 32DO, 24V DC, 0.5A,1 X 40 PIN,SUM OF OUTPUT CURRENTS 4A/GROUP(16A/MODULE)
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 160 mA
from backplane bus 5 V DC, max. 110 mA
Power losses
Power loss, typ. 6.6 W
Digital outputs
Number/binary outputs 32
Limitation of inductive shutdown voltage to L+ (-53 V)
Lamp load, max. 5 W
Load resistance range
6ES7322-1BL00-0AA0 Page 1
Date:01/29/2012
subject to modifications© Copyright Siemens AG 2012
69-1
6ES7322-1BL00-0AAAAA0
Page 13 of 43
Product data sheet 6ES7197-1LA04-0XA0
-
SIMATIC S7-400H,Y-LINK FOR CONNECTING SINGLE-CHANNEL DPSLAVES TO S7-400H BASED ON IM153-BA02 (NOT FITFOR PCS7 V6.1)
Dimensions
Width 40 mm
Height 125 mm
Depth 130 mm
Status Jul 1, 2013
6ES7197-1LA04-0XA0Page 1/ 07/20/2013
subject to modifications© Copyright Siemens AG 20131
Page 14 of 43
Product data sheet 6ES7332-5HF00-0AB0
SIMATIC S7-300, ANALOG OUTPUT SM 332,OPTICALLY ISOLATED, 8 AO, U/I;DIAGNOSTICS;RESOLUTION 11/12 BITS, 40 PIN,REMOVE/INSERT W. ACTIVE, BACKPLANE BUS
Supply voltage
Load voltage L+
Rated value (DC) 24 V
Input current
from load voltage L+ (without load), max. 340 mA
from backplane bus 5 V DC, max. 100 mA
Power losses
Power loss, typ. 6 W
Analog outputs
Number of analog outputs 8
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
0 to 10 V Yes
6ES7332-5HF00-0AB0 Page 1
Date:02/09/2012
subject to modifications© Copyright Siemens AG 2012
85
6ES7332-5HF00-0AB0
Page 15 of 43
Product data sheet 6ES7321-1BH02-0AA0
SIMATIC S7-300, DIGITAL INPUT SM 321,OPTICALLY ISOLATED, 16DI, 24 V DC,1 X 20 PIN
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 10 mA
Power losses
Power loss, typ. 3.5 W
Digital inputs
Number/binary inputs 16
Input characteristic curve acc. to IEC 61131, Type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
up to 60 °C, max. 16
6ES7321-1BH02-0AA0 Page 1
Date:02/12/2012
subject to modifications© Copyright Siemens AG 2012
66-1
6ES7321-1BH02-0AA0
Page 16 of 43
Product data sheet 6ES7322-1BH01-0AA0
SIMATIC S7-300, DIGITAL OUTPUT SM 322,OPTICALLY ISOLATED, 16 DO, 24V DC,0.5A,1 X 20 PIN SUM OF OUTPUT CURRENTS4A/GROUP (8A/MODULE)
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 80 mA
from backplane bus 5 V DC, max. 80 mA
Power losses
Power loss, typ. 4.9 W
Digital outputs
Number/binary outputs 16
Limitation of inductive shutdown voltage to L+ (-53 V)
Lamp load, max. 5 W
Load resistance range
6ES7322-1BH01-0AA0 Page 1
Date:02/12/2012
subject to modifications© Copyright Siemens AG 2012
70-1
6ES7322-1BH01-0AAAAA0
Page 17 of 43
for backplane bus (24 V DC), max. 1 A ; idling-proof
Short-circuit protection Yes
Power
Power consumption, typ. 95 W
Power losses
Power loss, typ. 20 W
Battery
Backup battery
Backup battery
Backup battery (optional) Yes ; 2 x lithium AA; 3.6 V/2.3 Ah
Galvanic isolation
primary/secondary Yes
Degree and class of protection
Protection class 1 ; with protective conductor
Standards, approvals, certificates
FM approval Yes ; Ta: 0 °C to 60 °C T4
Connection method
Connecting cables/cross sections 3 x 1.5 mm2, solid or stranded wire with end sleeve, externaldiameter 3 to 9 mm
Dimensions
Width 50 mm
Height 290 mm
Depth 217 mm
Required slots 2
Weight
Weight, approx. 1200 g
Status Jul 11, 2013
6ES7405-0KA02-0AA0Page 2/ 07/16/2013
subject to modifications© Copyright Siemens AG 20132
Page 18 of 43
Product data sheet 6ES7412-3HJ14-0AB0
-
SIMATIC S7-400H,CPU 412-3H CENTRAL UNIT FOR S7-400H AND S7-400F/FH,3 INTERFACES: 1 MPI/DP AND 2 FOR SYNC MODULES768 KB MEMORY (256 KB DATA/512 KB CODE)
General information
Hardware product version 1
Firmware version V4.5
Engineering with
Programming package STEP7 V 5.3 SP2 or higher with HW update
CiR - Configuration in RUN
CiR synchronization time, basic load 150 ms
CiR synchronization time, time per I/O slave 40 μs
Supply voltage
24 V DC No ; Power supply via system power supply
Input current
from backplane bus 5 V DC, typ. 1.2 A
from backplane bus 5 V DC, max. 1.5 A
from backplane bus 24 V DC, max. 150 mA ; Per DP interface
from interface 5 V DC, max. 90 mA ; At each DP interface
Power losses
Power loss, typ. 5.5 W
Memory
6ES7412-3HJ14-0AB0Page 1/ 07/16/2013
subject to modifications© Copyright Siemens AG 201310
Page 19 of 43
Product data sheet 6ES7960-1AA04-0XA0
-
SIMATIC S7-400H,SYNC SUBMODULE V4 FOR PATCH CABLES UP TO 10M
Input current
from CPU, max. 210 mA
Power losses
Power loss, typ. 1.1 mW
Dimensions
Width 25 mm
Height 53 mm
Depth 140 mm
Weight
Weight, approx. 65 g
Status Jul 6, 2013
6ES7960-1AA04-0XA0Page 1/ 07/16/2013
subject to modifications© Copyright Siemens AG 20131
Page 20 of 43
• Note > 60 °C Derating
delivered active power / typ. 120 W
constant overload current / at short-circuit during run-up / typical
5.5 A
short-term overload current / at short-circuit duringoperation / typical
15 A
Duration of overloading ability for excess current / onshort-circuiting during the operational phase
25 ms
Parallel switching for enhanced performance Yes
• Note switchable characteristic
Numbers of parallel switchable units for enhancedperformance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 87 %
Power loss at Vout rated, Iout rated, approx. 18 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max. 0.1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ±typ.
3 %
Load step setting time 50 to 100%, typ. 2 ms
Load step setting time 100 to 50%, typ. 2 ms
Setting time / maximum 5 ms
Protection and monitoring
Output overvoltage protection < 35 V
Current limitation, typ. 5.5 A
Characteristic feature of the output / short-circuitprotected
Yes
Short-circuit protection Alternatively, constant current characteristic approx.5.5 A or latching shutdown
Enduring short circuit current / Effective level / typical 5.5 A
Overload/short-circuit indicator LED yellow for "overload", LED red for "latchingshutdown"
Safety
Primary/secondary isolation Yes
Potential separation Safety extra low output voltage Vout according to EN60950-1 and EN 50178
6EP1333-3BA00 Page 3
Date:02/09/2012
subject to modifications© Copyright Siemens AG 2012
12
Page 21 of 43
I²t 0.1 A²·s
Output voltage
Rated value, 5 V DC Yes
Output current
for backplane bus (5 V DC), max. 1.5 A
Power losses
Power loss, typ. 5.5 W
Address area
Addressing volume
Outputs 244 byte
Inputs 244 byte
Hardware configuration
Number of modules per DP slave interface, max. 12
Time stamping
Accuracy 1 ms ; 1ms at up to 8 modules; 10ms at up to 12modules
Number of message buffers 15
Messages per message buffer 20
Number of stampable digital inputs, max. 128 ; Max. 128 signals/station; max. 32 signals/slot
Time format RFC 1119
Time resolution 0.466 ns
Time interval for transmitting the message buffer if amessage is present
1000 ms
Time stamp on signal change rising / falling edge as signal entering or exiting
Interfaces
Interface physics, RS 485 Yes
Interface physics, FOC No
PROFIBUS DP
Node addresses 1 to 125 permitted
Automatic detection of transmission speed Yes
PROFIBUS DP, output current, max. 70 mA
Transmission procedure RS 485
Transmission rate, max. 12 Mbit/s
SYNC capability Yes
6ES7153-2BA02-0XB0 Page 2
Date:02/14/2012
subject to modifications© Copyright Siemens AG 2012
60
Page 22 of 43
73
Page 23 of 43
• for glass FOC with 50/125 μm / at 3 dB/km / maximum 10 dB
• for glass FOC with 62.5/125 μm
• at 3.5 dB/km / maximum 12 dB
Signal delay time in bit time 6.5 bit
Injectable optical power relating to 1 mW
• for glass FOC with 50/125 μm / at 3 dB/km -16 dB
• for glass FOC with 62.5/125 μm
• at 3.5 dB/km -13 dB
Optical sensitivity relating to 1 mW
• for glass FOC with 50/125 μm / at 3 dB/km -28 dB
• for glass FOC with 62.5/125 μm
• at 3.5 dB/km -28 dB
Wavelength
• for glass FOC with 50/125 μm / compatible with interface / at 3dB/km
860 nm
• for glass FOC with 62.5/125 μm / compatible with interface
• at 3.5 dB/km 860 nm
Cable length
• for glass FOC with 50/125 μm / at 3 dB/km / maximum 3 km
• for glass FOC with 62.5/125 μm at 3.5 dB/km maximum
• 3 km
Inputs/outputs
Operating voltage / of signaling contacts / at DC / rated value 24 V
Operating current / of signaling contacts / at DC / maximum 0.1 A
Supply voltage, current consumption, power loss
Type of voltage / of supply voltage DC
Supply voltage / for DC
• rated value 24 V
• minimum 18.8 V
• maximum 28.8 V
Product component / fusing at power supply input Yes
Consumed current / At 24 V / with DC / maximum 0.2 A
Permitted ambient conditions
Ambient temperature
• during operating 0 … 60 °C
• during storage -40 … +70 °C
• during transport -40 … +70 °C
Relative humidity
• at 25 °C / without condensation / during operating / maximum 95 %
Protection class IP IP40
6GK1503-3CB00Page 2/ 07/16/2013
subject to modifications© Copyright Siemens AG 20133
0.2 AAt 24 V
Page 24 of 43
32.8
29 12.4
20
4.75 0.5 4.75
6.5
46.52 46.61
• 2 Pole CO, 8 A• Plug-in/Solder terminals
2 CO (DPDT)
8/15
250/440
2,000
350
0.37
6/0.5/0.15
300 (5/5)
AgNi
1.2/0.5
(0.8...1.1)UN
(0.73...1.1)UN
0.8UN /0.4UN
0.2UN /0.1UN
10 · 106
100 · 103
10/3
6 (8 mm)
1,000
–40 ... +70
RT II
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage/Maximum switching voltage V AC
Rated load AC1 VA
Rated load AC15 (230 V AC) VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Standard contact material
Coil specification
Nominal voltage (UN) V AC (50/60 Hz)
V DC
Rated power VA/W
Operating range AC
DC
Holding voltage AC/DC
Must drop-out voltage AC/DC
Technical data
Mechanical life AC/DC cycles
Electrical life at rated load AC1 cycles
Operate/release time ms
Insulation between coil and contacts (1.2/50 μs)kV
Dielectric strength between open contacts V AC
Ambient temperature range °C
Environmental protection
Approvals (according to type)
Features1 & 2 Pole relay range
46.52 - 2 Pole 8 A46.61 - 1 Pole 16 A
• Socket mount or direct connection via Fastonconnectors
• AC coils & DC coils• Available with: lockable test button,
mechanical indicator & LED indicator• 8 mm, 6 kV (1.2/50 μs) isolation, coil-contacts• Cadmium Free contacts
• 1 Pole CO, 16 A• Plug-in/Faston 187
1 CO (SPDT)
16/25
250/440
4,000
750
0.55
12/0.5/0.15
300 (5/5)
AgNi
1.2/0.5
(0.8...1.1)UN
(0.73...1.1)UN
0.8UN /0.4UN
0.2UN /0.1UN
10 · 106
100 · 103
15/5
6 (8 mm)
1,000
–40 ... +70
RT II
12 - 24 - 48 - 110 - 120 - 230 - 240
12 - 24 - 48 - 110 - 125
1
46.52
46.61
FOR UL HORSEPOWER AND PILOT DUTY RATINGSSEE “General technical information” page V
46 Series - Miniature industrial relays 8 - 16 A
138
46.52
2 Pole CO, 8 A•
Plug-in/Solder terminals•
/0.5
Page 25 of 43
Proline Promag 50W, 53W
10 Endress+Hauser
A0003194
a Signal cableb Coil current cable
1 Core2 Core insulation3 Core shield4 Core jacket5 Core reinforcement6 Cable shield7 Outer jacket
Operation in zones of severe electrical interference
The measuring device complies with the general safety requirements in accordance with EN 61010 and
the EMC requirements of IEC/EN 61326 and NAMUR recommendation NE 21.
" Caution!
Grounding is by means of the ground terminals provided for the purpose inside the connection housing.
Ensure that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible.
Power consumption • AC: < 15 VA (incl. sensor)
• DC: < 15 W (incl. sensor)
Switch-on current:
• Max. 3 A (< 5 ms) for 260 V AC
• Max. 13.5 A (< 50 ms) for 24 V DC
Power supply failure Lasting min. ½ cycle frequency: EEPROM saves measuring system data
• EEPROM or T-DAT (Promag 53 only) retain the measuring system data in the event of a power supply failure
• S-DAT: exchangeable data storage chip which stores the data of the sensor (nominal diameter, serial number,
calibration factor, zero point etc.)
1234567
a b
Page 26 of 43
Nivotester FTL 325 N
8 Endress+Hauser
Power supplyElectrical connection Terminal blocks
The removable terminal blocks are separated into intrinsically safe connections (at top of the instrument) and non-instrinsically safe connections (at bottom of the instrument). Also, the terminal blocks have different colours to make them more easily recognisable. Blue for the intrinsically safe section and grey for the non-intrinsically safe section. This difference helps to ensure safe wiring.
Connecting the measuring sensor
(at upper, blue terminal blocks)The two-wire connecting line between the Nivotester FTL 325 N and the Liquiphant, Nivopuls or Soliphant measuring sensor can be either a commercially available installation cable or wires in a multi-wire cable for measuring purposes. Line resistance may be a maximum of 25 Ω per wire.If strong electromagnetic interference is expected, e.g. from machines or radio devices, a screened cable must be used. Only connect the screen to the ground connection, and not to the Nivotester.
Using the measuring sensor in explosion hazardous areas
Please observe all local regulations on explosion protection concerning the type and installation of intrinsically safe signal cabling. Please refer to the Safety Instructions XA 134F for maximum permissible values of capacitance and inductance.
Connecting signal and control devices
(at lower, grey terminal blocks)The relay function is dependent on the level and fail-safe circuit.If an instrument is connected at high inductance (e.g. contactor, solenoid valve etc.), a spark suppressor must be installed to protect the relay contact.
Connecting the supply voltage
(at lower, grey terminal blocks)For voltage variants, see the Ordering Information on page 14.A fuse is built into the supply current circuit. This obviates the need to connect a fine-wire fuse in series. The Nivotester is equipped with reverse polarity protection.
Supply voltage AC version:
• Voltage ranges: 85...253 V AC, 50/60 Hz
DC version:
• Voltage ranges: 20...30 V AC / 20...60 V DC• DC supply: max. 60 mA (1-channel)• DC supply: max. 115 mA (3-channel)• Permissible residual ripple within tolerance: Uss = max. 2 V
The Nivotester is equipped with reverse polarity protection.
Power consumption AC
1-channel: max. 1.75 W3-channel: max. 2.75 W
DC
1-channel: max. 1.2 W (bei Umin 20 V)3-channel: max. 2.25 W (bei Umin 20 V)
Page 27 of 43
Prosonic S FMU90
10 Endress + Hauser
PROFIBUS DP interface
Auxiliary energy
Supply voltage/Power consumption/Current consumption
Galvanic isolation The following terminals are galvanically isolated from each other:
• auxiliary energy
• sensor inputs
• analogue output 1
• analogue output 2
• relay outputs
• bus connection (PROFIBUS DP)
Fuse • 2 A T /DC
• 400 mA T /AC
accesible in the terminal compartment
Profile 3.0
Transmittable values • main value (level or flow, depending on the instrument version)
• distances
• counters
• temperatures
• average/difference/sum
• relay states
• rake control
• pump control
Function blocks • 10 Analog Input Blocks (AI)
• 10 Digital Input Blocks (DI)
• 10 Digital Output Blocks (DO)
Supported baud rates • 9.6 kbaud
• 19.2 kbaud
• 45,45 kbuad
• 93.75 kbaud
• 187.5 kbaud
• 500 kbaud
• 1.5 Mbaud
• 3 Mbaud
• 6 Mbaud
• 12 Mbaud
Service Access Points (SAPs) 1
ID number 1540 (hex) 1540 (hex) = 5440 (dec)
GSD file EH3x1540.gsd
Addressing via dip switches at the instrument or via software (e.g. FieldCare)
Default address: 126 per software
Termination can be activated/deactivated in the instrument
Locking The device can be locked by hardware or software.
Instrument version Supply voltage Power consumption Current consumption
AC voltage
(FMU90 - ****A****)90 ... 253 VAC (50/60 Hz) max. 23 VA max. 100 mA at 230 VAC
DC voltage
(FMU90 - ****B****)10,5 ... 32 VDC max. 14 W (typically 8 W) max. 580 mA at 24 VDC
Page 28 of 43
Cerabar M PMC51, PMP51, PMP55
Endress+Hauser 19
FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC
Start-up current HART 12 mA or 22 mA (selectable)
Current consumption • PROFIBUS PA: 11 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 16 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
Cable entry ä 75 ff, feature 50 "Electrical connection".
Cable specification • Endress+Hauser recommends using twisted, shielded two-wire cables.
• Terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in)
Residual ripple No influence on 4 to 20 mA signal up to 5 % residual ripple within the permitted voltage range [according to
HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]
Influence of power supply 0.001% of URL/1 V
Page 29 of 43
Deltabar S
18 Endress+Hauser
Supply voltage Note!
• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions or Installation or Control Drawings.
• All explosion protection data are given in separate documentation which is available upon request. The
Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
ä 85, "Safety Instructions" and "Installation/Control Drawings" sections.
4 to 20 mA HART
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position
(delivery status): 11.5 to 45 V DC
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position:
10.5 to 45 V DC
PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 VDC
FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC
Current consumption • PROFIBUS PA: 13 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 15 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
Cable entry ä 69 ff, feature 30 "Housing; Cable entry; Protection".
Cable specification • Endress+Hauser recommends using shielded, twisted-pair two-wire cables.
• Terminals for core cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in)
Residual ripple Without influence on 4 to 20 mA signal up to 5 % residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]
Influence of power supply 0.0006% of URL/1 V
Page 30 of 43
Power requirement 220 VAC Power consumption: 0.48 Watts Analog outputs: 4-20mA isolated Analog loop resistance: 500 Ohms, nominally @ 24V Alarms: Optional Certification: Available upon request
Mechanical
Transmitter weight: 3 lbs. Enclosure: Extruded aluminum (optional NEMA or purged enclosures) 8" H x 3-7/8" W x 1-1/2" D
UV Lamp
Type: Xenon flash lamp Wavelength range: 200 - 650 nm Lamp Life: Typically 3 years Size: 2" H x 4" W x 1-1/2" D Power requirements: 24 VDC (9-32 VDC)
6650 UVF Probe
Materials: 316SS Max temperature rating: 315.5° C (600° F) Max pressure rating: 5000 psig
Sample Conditioning System
All wetted parts of SCS components will be SS316 Ultrasonic Homogenizer for sample mix Sample shut off valve Sample and fast loop bypass Pressure regulator with viewing gauge Sample flow meter with precision needle valves Extra Cuno filter
Mounting:
NEMA 4 (IP65) free standing enclosure
Area Class
Ex”d” certified Enclosure for Class 1 Div 2
Page 31 of 43
Liquistation CSF34
22 Endress+Hauser
Mains fuse Optional fuses on DIN rail• T10A (for 24V power supply)• T3.15A (for 230V power supply)• T10A (fuse for battery backup)
Power consumption • Version with vacuum pump: 290 VA• Version with peristaltic pump: 290 VA
Power failure • Power supply via battery (optional): 2 x 12 V, 7.2 Ah, with additional charge controller
Replace batteries with battery type Panasonic LC-R127R2PG1.
• Real-time clock: lithium battery, type CR2032
Performance characteristicsSampling methods Vacuum pump / peristaltic pump:
• Event sampling• Single and multiple samples• Sampling table
Vacuum pump:• In proportion to time• In proportion to volume
Peristaltic pump:• In proportion to time• In proportion to volume• In proportion to flow
Dosing volume • Vacuum pump:20 to 350 ml (0.7 to 12 fl.oz.)
• Peristaltic pump:10 to 10,000 ml (0.3 to 340 fl.oz.)
A sample volume < 20 ml can vary in dosing accuracy and repeatability, depending on the application.
Dosing accuracy • Vacuum pump:±5 ml (0.17 fl.oz.) or 5 % of the set volume
• Peristaltic pump:±5 ml (0.17 fl.oz.) or 5 % of the set volume
Repeatability • Vacuum pump: 5 %• Peristaltic pump: 5 %
Intake speed > 0.5 m/s (> 1.6 ft/s) for 13 mm (1/2") ID, in accordance with EN 25667, ISO 5667> 0.6 m/s (> 1.9 ft/s) for 10 mm (3/8") ID, in accordance with Ö 5893 (Austrian standard); US EPA
Suction height Max. 8 m (26 ft)
Hose length Max. 30 m (98 ft)
Page 32 of 43
Cerabar S
18 Endress+Hauser
Supply voltage Note!
• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions or Installation or Control Drawings.
• All explosion protection data are given in separate documentation which is available upon request. The
Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
ä 89 ff, "Safety Instructions" and "Installation/Control Drawings" sections.
4 to 20 mA HART
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position
(delivery status): 11.5 to 45 V DC
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position:
10.5 to 45 V DC
PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 V DC
FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC
Current consumption • PROFIBUS PA: 13 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 15 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
Cable entry ä 76 ff, feature 30 "Housing; Cable entry; Protection".
Cable specification • Endress+Hauser recommends using shielded, twisted-pair two-wire cables.
• Terminals for core cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in)
Residual ripple Without influence on 4 to 20 mA signal up to 5 % residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]
Influence of power supply 0.0006% of URL/1 V
Page 33 of 43
Page 34 of 43
Liquiline CM442
10 Endress+Hauser
Cable specification
Power consumption Depending on supply voltage
• 100 to 230 V AC and 24 V AC:
Max. 55 VA
• 24 V DC:
Max. 22 W
Fuse For all versions:5x20 mm, 250 V, 4.0 A, slow-blow (T4.0A)
Performance characteristics
Response time Current outputs
t90 = max. 500 ms for an increase from 0 to 20 mA
Reference temperature 25 C (77 F)
Maximum measured error of inputs
--> Documentation of the connected sensor
Maximum measured error of current outputs
< 20 A at 4 mA
< 50 A at 20 mA
at 25 C (77 F) each
Additional measured error depending on the temperature:
< 1.5 A/K
Resolution of current output < 5 A
Repeatability --> Documentation of the connected sensor
Cable gland Permitted cable diameter
M16x1.5 mm 4 to 8 mm (0.16 to 0.32")
M12x1.5 mm 2 to 5 mm (0.08 to 0.20")
M20x1.5 mm 6 to 12 mm (0.24 to 0.48")
NPT3/8" 4 to 8 mm (0.16 to 0.32")
G3/8 4 to 8 mm (0.16 to 0.32")
NPT1/2" 6 to 12 mm (0.24 to 0.48")
G1/2 7 to 12 mm (0.28 to 0.47")
Page 35 of 43
Limit reed switch ZE 951 for DFM 165 - 350bistable
Advantage• reliable limit value determination using reed switches• direct power control of consumers with contact protection relay
ZE 3061• 2-point control for monostable switches with ZE 3060• freely adjustable flow limit value - fastened with a clamping
piece to the measuring tube dovetail guide• reliable, simple installation, easy to retrofit in existing plants
Description• The limit reed switch ZE 951 serves as signal transmitters of the
flow values. They are clamped to the dovetail guides and signalwhen the magnetic float in the measuring tube has reached orexceeded the signal transmitter position. As soon as thishappens, a contact in the signal transmitter, as the actualswitching element (reed switch), opens or closes.
Function• Type ZE 951 bistable (normally open contact/normally closed
contact) The contact is closed (normally open contact) or opened(normally closed contact), as soon as the magnetic float movesup from below or is at the direct height of the signal transmitter.If the float goes above the signal transmitter, the switching stateremains unaffected. The switching state is only cancelled if thefloat goes below the signal transmitter.
Body• ABS
Connector Plug• according to DIN EN 175301-803
Voltage• 2 V C
Switching Current• max. 0,5 A
Electric Switching Capacity• max. 10 VA
Resistance• < 150 mOhm
Insulation Resistance• > 1010 Ohm
Ambient Temperature• 0°C to +55°C
Hysteresis• 10 mm
Type Of Protection• IP 65 with mounted connector plug
Connection Cable• nominal cross-section: 1.5 mm²• cable outside diameter: 4…6 mm
Pin Assignment• the polarity of the connections has no influence on the function
Colour• anthracite grey
Accessories• 2-Point Control Unit ZE 3060 (Article number 136245, 1326244)• Contact Protection Relay ZE 3061 (Article number 136240,
136239)
1All rights for technical modifications withheld> data sheet no.: 330207 - 2010/05/05ASV Stübbe GmbH & Co. KG · Hollwieser Str. 5 · D-32602 Vlotho · Tel. +49(0)5733. 799-0 · Fax +49(0)5733. 799-5000 · [email protected] · www.asv-stuebbe.de
• 22 VV C
ZE 951 for DFM 165 - 350
Page 36 of 43
Current output to backplane bus (DC 5 V), max. 1600 mA ; Max. 5 V DC for SM and CM
Power losses
Power loss, typ. 12 W
Memory
Usable memory for user data 75 kbyte
Work memory
integrated 75 kbyte
expandable No
Load memory
integrated 4 Mbyte
Backup
present (maintenance-free)
without battery Yes
CPU processing times
for bit operations, typ. 0.085 µs ; / instruction
for word operations, typ. 1.7 µs ; / instruction
for floating point arithmetic, typ. 2.5 µs ; / instruction
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number ofaddressable blocks ranges from 1 to 65535. There is no restriction,the entire working memory can be used
OB
Number, max. Limited only by RAM for code
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max. 10 kbyte
Flag
Number, max. 8 kbyte ; Size of bit memory address area
Address area
I/O address area
I/O address area, overall 1024 bytes for inputs / 1024 bytes for outputs
Process image
Inputs, adjustable 1 kbyte
Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
Hardware clock (real-time clock) Yes
6ES7214-1AG31-0XB0Page 2/ 07/20/2013
subject to modifications© Copyright Siemens AG 20138
Page 37 of 43
Product data sheet 6ES7221-1BH30-0XB0
-
SIMATIC S7-1200, DIGITAL INPUT SM 1221,16 DI, 24VDC, SINK/SOURCE INPUT
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 130 mA
Digital inputs
from load voltage L+ (without load), max. 4 mA ; per channel
Output voltage
Power supply to the transmitters
present Yes
Power losses
Power loss, typ. 2.5 W
Digital inputs
Number/binary inputs 16
In groups of 4
Input characteristic curve acc. to IEC 61131, Type 1 Yes
Number of simultaneously controllable inputs
6ES7221-1BH30-0XB0Page 1/ 07/20/2013
subject to modifications© Copyright Siemens AG 20133
Page 38 of 43
Product data sheet 6ES7222-1BH30-0XB0
-
SIMATIC S7-1200,DIGITAL OUTPUT SM 1222, 16 DO, 24V DC,TRANSISTOR 0.5A
Supply voltage
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 140 mA
Power losses
Power loss, typ. 2.5 W
Digital inputs
Number/binary inputs 0
Digital outputs
Number/binary outputs 16
In groups of 1
Functionality/short-circuit strength No ; to be provided externally
Limitation of inductive shutdown voltage to typ. (L+) -48 V
Switching capacity of the outputs
with resistive load, max. 0.5 A
on lamp load, max. 5 W
Output voltage
6ES7222-1BH30-0XB0Page 1/ 07/20/2013
subject to modifications© Copyright Siemens AG 20133
Page 39 of 43
Product data sheet 6ES7231-4HF30-0XB0
-
SIMATIC S7-1200, ANALOG INPUT, SM 1231,8 AI, +/-10V, +/-5V, +/-2.5V,OR 0-20 MA 12 BIT + SIGN OR (13 BIT ADC)
Supply voltage
24 V DC Yes
Input current
Current consumption, typ. 45 mA
from backplane bus 5 V DC, typ. 90 mA
Power losses
Power loss, typ. 1.5 W
Analog inputs
Number of analog inputs 8 ; Current or voltage differential inputs
permissible input frequency for current input (destruction limit),max.
± 35 V
permissible input voltage for voltage input (destruction limit), max. 35 V
permissible input current for voltage input (destruction limit), max. 40 mA
permissible input current for current input (destruction limit), max. 40 mA
Cycle time (all channels) max. 625 µs
Input ranges
Voltage Yes ; ±10 V, ±5 V, ±2.5 V
Current Yes ; 0 to 20 mA
Thermocouple No
6ES7231-4HF30-0XB0Page 1/ 07/20/2013
subject to modifications© Copyright Siemens AG 20134
Page 40 of 43
Alphanumeric keyboard Yes ; Onscreen keyboard
Touch operation
Design as touch screen Yes
Installation type/mounting
Mounting in portrait format possible Yes
Mounting in landscape format possible Yes
Supply voltage
Type of supply voltage DC
Rated voltage/DC 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Input current
Current consumption (rated value) 0.24 A
Inrush current A²s 0.5 A²·s
Power
Power consumption, typ. 6 W
Processor
Processor type
X86 No
ARM Yes ; RISC 32-bit
Memory
Flash Yes
RAM Yes
Usable memory for user data 1 Mbyte
Type of output
Acoustics
Buzzer Yes
Speaker No
Time of day
Clock
Hardware clock (real-time clock) No
Software clock Yes
Battery-backed No
Synchronizable Yes
Interfaces
Number of RS 485 interfaces 0
Number of USB interfaces 0
Number of SD card slots 0
6AV6647-0AB11-3AX0Page 2/ 07/20/2013
subject to modifications© Copyright Siemens AG 20139
Page 41 of 43
Product data sheet 6GK7242-5DX30-0XE0
Product-type designation CM 1242-5
COMMUNICATION MODULE CM 1242-5;FOR CONNECTION OF SIMATIC S7-1200 TO PROFIBUSAS DP SLAVE MODULE
Transmission rate
Transmission rate / at interface 1 / in accordance with PROFIBUS 9.6 kbit/s … 12 Mbit/s
Interfaces
Number of electrical connections
• at interface 1 / in accordance with PROFIBUS 1
• for power supply 0
Design of electrical connection
• at interface 1 / in accordance with PROFIBUS 9-pin Sub-D socket (RS485)
Supply voltage, current consumption, power loss
Type of voltage / of supply voltage DC
Supply voltage
• 1 / from backplane bus 5 V
Consumed current
• from backplane bus / at 5 V / for DC / Typical 0.15 A
Resistive loss 0.75 W
Permitted ambient conditions
Ambient temperature
• for vertical installation / during operating phase 0 … 45 °C
• for horizontal installation / during operating phase 0 … 55 °C
• during storage -40 … +70 °C
6GK7242-5DX30-0XE0Page 1/ 07/20/2013
subject to modifications© Copyright Siemens AG 20132
Page 42 of 43
55.32 55.33 55.34
2 CO (DPDT) 3 CO (3PDT) 4 CO (4PDT)
10/20 10/20 7/15
250/400 250/400 250/250
2,500 2,500 1,750
500 500 350
0.37 0.37 0.125
10/0.25/0.12 10/0.25/0.12 7/0.25/0.12
300 (5/5) 300 (5/5) 300 (5/5)
AgNi AgNi AgNi
6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240
6 - 12 - 24 - 48 - 60 - 110 - 125 - 220
1.5/1 1.5/1 1.5/1
(0.8…1.1)UN (0.8…1.1)UN (0.8…1.1)UN
(0.8…1.1)UN (0.8…1.1)UN (0.8…1.1)UN
0.8 UN/0.5 UN 0.8 UN/0.5 UN 0.8 UN/0.5 UN
0.2 UN/0.1 UN 0.2 UN/0.1 UN 0.2 UN/0.1 UN
20 · 106/50 · 106 20 · 106/50 · 106 20 · 106/50 · 106
200 · 103 200 · 103 150 · 103
10/5 10/5 11/3
4 4 4
1,000 1,000 1,000
–40…+85 –40…+85 –40…+85
RT I RT I RT I
2
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage/Maximum switching voltage V AC
Rated load AC1 VA
Rated load AC15 (230 V AC) VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Standard contact material
Coil specification
Nominal voltage (UN) V AC (50/60 Hz)
V DC
Rated power AC/DC VA (50 Hz)/W
Operating range AC
DC
Holding voltage AC/DC
Must drop-out voltage AC/DC
Technical data
Mechanical life AC/DC cycles
Electrical life at rated load AC1 cycles
Operate/release time ms
Insulation between coil and contacts (1.2/50 μs) kV
Dielectric strength between open contacts V AC
Ambient temperature range °C
Environmental protection
Approvals (according to type)
FeaturesPlug-in mount, general purpose 2, 3 & 4 Pole relays
55.32 - 2 Pole 10 A55.33 - 3 Pole 10 A 55.34 - 4 Pole 7 A
• Lockable test button and mechanical flagindicator as standard on 2 & 4 pole types
• AC coils & DC coils• UL Listing (certain relay/socket combinations)• Cadmium Free contacts (preferred version)• Contact material options• 94 series sockets• Coil EMC suppression• Timer accessories 86 series• European Patent
• 2 pole, 10 A• Plug-in 94 series sockets
• 3 pole, 10 A• Plug-in 94 series sockets
• 4 pole, 7 A• Plug-in 94 series sockets
FOR UL RATINGS SEE: “General technical information” page V
55.32 55.33 55.34
55 Series - General purpose relays 7 - 10 A
VII-2
012,
ww
w.fi
nder
net.c
om