+ All Categories
Home > Documents > User Manual - d114hh0cykhyb0.cloudfront.net · XSCS-RW 4400 Earth City Expy, St. Louis, MO 63045...

User Manual - d114hh0cykhyb0.cloudfront.net · XSCS-RW 4400 Earth City Expy, St. Louis, MO 63045...

Date post: 28-Jun-2020
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
3
LED Exit and Emergency Light Important: Read all instructions prior to installation. SAVE THESE INSTRUCTIONS. XSCS-RW 4400 Earth City Expy, St. Louis, MO 63045 866-590-3533 superbrightleds.com Included Parts Specifications XSCS-RW Total Power Consumption 4 W (in maintenance mode) Operating Voltage Range 120/277 VAC Operating Temperature 50°–104° F (10°–40° C) IP Rating damp or dry location Fixture Weight 7.3 lb (3.3 kg) Battery Type Ni-Cd AA 3.6 V 600 mAh (x2) User Manual 1 - fixture 1 - hardware kit 1 - side mount bracket Dimensional Diagram Important Safeguards Read and follow all safety instructions. When using electrical equipment, basic safety precautions should always be followed including the following: This product should be installed and serviced by a certified electrician in accordance with applicable national, state, and local building and electrical codes. Light must be maintained, tested, and serviced in accordance with all applicable National Fire Protection Association (NFPA) and local codes. To reduce the risk of electric shock, ensure that the main power source and circuit breakers are switched off before performing any installation or wiring procedures. Ensure fixture is securely mounted and mount will support weight of the fixture. Failure to properly support fixture may result in damage or injury, for which the manufacturer does not assume responsibility. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel. Indoor use only—do not use outdoors. Do not mount near gas or electric heaters or any other radiant heat sources. Use caution when handling or servicing the battery pack. For conduit wiring installation, use flexible conduit only The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. Do not use this equipment for anything other than its intended use. Testing Manual Test button can be held to illuminate lights for manual testing purposes. Rev Date: V2 04/09/2020 14.56in 369.89mm 2.37in 60.07mm 16.45in 417.94mm 3.21in Conduit Cut-out Mounting Plate Mounting Bracket 81.57mm .85in 21.64mm 10.34in 262.51mm 2.25in 57.15mm 2.62in 66.58mm 4.61in 117.01mm 7.75in 196.85mm .85in 21.64mm 3.44in 87.42mm 4.35in 110.45mm 2.76in 70.05mm 3.18in 80.87mm 2.68in 68.17mm 1 - CONDUIT BUSHING 3 - WIRE NUT 6 - M4 x 24 mm SCREW 2 - HEX NUT WITH LOCK WASHER PARTS INCLUDED .85in 21.64mm Conduit Cut-out 120 V Wiring 277 V Wiring BLACK WHITE GREEN ORANGE 120 V POWER NEUTRAL GROUND N/C BLACK WHITE GREEN ORANGE N/C NEUTRAL GROUND 277 V POWER Wiring Diagram ¹ ¹Limited 2-year warranty on battery.
Transcript
Page 1: User Manual - d114hh0cykhyb0.cloudfront.net · XSCS-RW 4400 Earth City Expy, St. Louis, MO 63045 866-590-3533 superbrightleds.com User Manual Installation Instructions 1. Remove screw

LED Exit and Emergency LightImportant: Read all instructions prior to installation. SAVE THESE INSTRUCTIONS. XSCS-RW

4400 Earth City Expy, St. Louis, MO 63045 866-590-3533 superbrightleds.com

Included Parts

Specifications

XSCS-RWTotal Power Consumption 4 W (in maintenance mode)Operating Voltage Range 120/277 VACOperating Temperature 50°–104° F (10°–40° C)IP Rating damp or dry locationFixture Weight 7.3 lb (3.3 kg)Battery Type Ni-Cd AA 3.6 V 600 mAh (x2)

User Manual

1 - fixture1 - hardware kit1 - side mount bracket

Dimensional Diagram

Important Safeguards

Read and follow all safety instructions. When using electrical equipment, basic safety precautions should always be followed including the following:

• This product should be installed and serviced by a certified electrician in accordance with applicable national, state, and local building and electrical codes.

• Light must be maintained, tested, and serviced in accordance with all applicable National Fire Protection Association (NFPA) and local codes.

• To reduce the risk of electric shock, ensure that the main power source and circuit breakers are switched off before performing any installation or wiring procedures.

• Ensure fixture is securely mounted and mount will support weight of the fixture. Failure to properly support fixture may result in damage or injury, for which the manufacturer does not assume responsibility.

• Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.

• Indoor use only—do not use outdoors.

• Do not mount near gas or electric heaters or any other radiant heat sources.

• Use caution when handling or servicing the battery pack.

• For conduit wiring installation, use flexible conduit only

• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.

• Do not use this equipment for anything other than its intended use.

Testing

Manual Test button can be held to illuminate lights for manual testing purposes.

Rev Date: V2 04/09/2020

14.56in369.89mm

2.37in60.07mm

16.45in417.94mm

3.21in

Conduit Cut-out

Mounting Plate

Mounting Bracket

81.57mm

.85in21.64mm

10.34in262.51mm

2.25in57.15mm

2.62in66.58mm

4.61in

117.01mm

7.75in196.85mm

.85in21.64mm

3.44in87.42mm

4.35in110.45mm

2.76in70.05mm

3.18in80.87mm

2.68in68.17mm

1 - CONDUIT BUSHING

3 - WIRE NUT

6 - M4 x 24 mm SCREW

2 - HEX NUT WITH LOCK WASHER

PARTS INCLUDED

.85in21.64mm

Conduit Cut-out

120 V Wiring 277 V Wiring

BLACK

WHITE

GREEN

ORANGE

120 V POWER

NEUTRAL

GROUND

N/C

BLACK

WHITE

GREEN

ORANGE

N/C

NEUTRAL

GROUND

277 V POWER

BLACK

WHITE

GREEN

ORANGE

120 V POWER

NEUTRAL

GROUND

N/C

BLACK

WHITE

GREEN

ORANGE

N/C

NEUTRAL

GROUND

277 V POWER

Wiring Diagram

¹

¹Limited 2-year warranty on battery.

Page 2: User Manual - d114hh0cykhyb0.cloudfront.net · XSCS-RW 4400 Earth City Expy, St. Louis, MO 63045 866-590-3533 superbrightleds.com User Manual Installation Instructions 1. Remove screw

LED Exit and Emergency LightXSCS-RW

4400 Earth City Expy, St. Louis, MO 63045 866-590-3533 superbrightleds.com

User Manual

Installation Instructions

1. Remove screw at bottom of case holding front cover in place. 2. Remove appropriate knockouts for wiring and mounting from

real and/or side panel.3. Using an appropriate strain relief (not included) or conduit,

run wiring through rear or side panel. Connect wiring and cap unused wire. (refer to wiring diagram) Note: Orange and black wires should never be connected at the same time.

4. Securely mount fixture to wall/junction box. 5. Slide internal component tray down and connect batteries.6. Slide tray back up until it is locked in place. Remove arrow

knockouts from front cover as needed, then slide front cover into place and reinstall capture screw.

7. Apply power and allow battery pack to charge for at least 24 hours before initial test.

8. After 24-hour period, press test button to make certain emergency lights are functioning as intended and are aimed correctly.

Wall Installation (rear)

To LED Spotlight

To LED Spotlight

Battery Connection

Wall Mounting Holes

Junction Box Mounting Holes

Battery

¹

¹Limited 2-year warranty on battery.

Rev Date: V2 04/09/2020

Important: Read all instructions prior to installation. SAVE THESE INSTRUCTIONS.

Page 3: User Manual - d114hh0cykhyb0.cloudfront.net · XSCS-RW 4400 Earth City Expy, St. Louis, MO 63045 866-590-3533 superbrightleds.com User Manual Installation Instructions 1. Remove screw

LED Exit and Emergency LightXSCS-RW

4400 Earth City Expy, St. Louis, MO 63045 866-590-3533 superbrightleds.com

User Manual

Installation Instructions

1. Remove screw at bottom of case holding front cover in place. Note: For two-sided viewing, the blank rear cover can be removed using the same process and replaced later with additional included “exit” panel.

2. Remove appropriate knockouts for wiring and mounting from side panel.

3. Attach mounting plate to junction box, then attach mounting bracket to mounting plate.

4. Using an appropriate strain relief (not included) run wiring through side panel. Connect wiring and cap unused wire. (refer to wiring diagram) Note: Orange and black wires should never be connected at the same time.

5. Securely mount fixture to mounting bracket.6. Slide internal component tray down and connect batteries.7. Slide tray back up until it is locked in place. Remove arrow

knockouts from cover(s) as needed, then slide cover(s) into place and reinstall capture screw(s).

8. Apply power and allow battery pack to charge for at least 24 hours before initial test.

9. After 24-hour period, press test button to make certain emergency lights are functioning as intended and are aimed correctly.

Wall Installation (side)

To LED Spotlight

To LED Spotlight

Battery Connection

Battery

¹

¹Limited 2-year warranty on battery.

Rev Date: V2 04/09/2020

Important: Read all instructions prior to installation. SAVE THESE INSTRUCTIONS.


Recommended