LED Exit and Emergency LightImportant: Read all instructions prior to installation. SAVE THESE INSTRUCTIONS. XSCS-RW
4400 Earth City Expy, St. Louis, MO 63045 866-590-3533 superbrightleds.com
Included Parts
Specifications
XSCS-RWTotal Power Consumption 4 W (in maintenance mode)Operating Voltage Range 120/277 VACOperating Temperature 50°–104° F (10°–40° C)IP Rating damp or dry locationFixture Weight 7.3 lb (3.3 kg)Battery Type Ni-Cd AA 3.6 V 600 mAh (x2)
User Manual
1 - fixture1 - hardware kit1 - side mount bracket
Dimensional Diagram
Important Safeguards
Read and follow all safety instructions. When using electrical equipment, basic safety precautions should always be followed including the following:
• This product should be installed and serviced by a certified electrician in accordance with applicable national, state, and local building and electrical codes.
• Light must be maintained, tested, and serviced in accordance with all applicable National Fire Protection Association (NFPA) and local codes.
• To reduce the risk of electric shock, ensure that the main power source and circuit breakers are switched off before performing any installation or wiring procedures.
• Ensure fixture is securely mounted and mount will support weight of the fixture. Failure to properly support fixture may result in damage or injury, for which the manufacturer does not assume responsibility.
• Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
• Indoor use only—do not use outdoors.
• Do not mount near gas or electric heaters or any other radiant heat sources.
• Use caution when handling or servicing the battery pack.
• For conduit wiring installation, use flexible conduit only
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
• Do not use this equipment for anything other than its intended use.
Testing
Manual Test button can be held to illuminate lights for manual testing purposes.
Rev Date: V2 04/09/2020
14.56in369.89mm
2.37in60.07mm
16.45in417.94mm
3.21in
Conduit Cut-out
Mounting Plate
Mounting Bracket
81.57mm
.85in21.64mm
10.34in262.51mm
2.25in57.15mm
2.62in66.58mm
4.61in
117.01mm
7.75in196.85mm
.85in21.64mm
3.44in87.42mm
4.35in110.45mm
2.76in70.05mm
3.18in80.87mm
2.68in68.17mm
1 - CONDUIT BUSHING
3 - WIRE NUT
6 - M4 x 24 mm SCREW
2 - HEX NUT WITH LOCK WASHER
PARTS INCLUDED
.85in21.64mm
Conduit Cut-out
120 V Wiring 277 V Wiring
BLACK
WHITE
GREEN
ORANGE
120 V POWER
NEUTRAL
GROUND
N/C
BLACK
WHITE
GREEN
ORANGE
N/C
NEUTRAL
GROUND
277 V POWER
BLACK
WHITE
GREEN
ORANGE
120 V POWER
NEUTRAL
GROUND
N/C
BLACK
WHITE
GREEN
ORANGE
N/C
NEUTRAL
GROUND
277 V POWER
Wiring Diagram
¹
¹Limited 2-year warranty on battery.
LED Exit and Emergency LightXSCS-RW
4400 Earth City Expy, St. Louis, MO 63045 866-590-3533 superbrightleds.com
User Manual
Installation Instructions
1. Remove screw at bottom of case holding front cover in place. 2. Remove appropriate knockouts for wiring and mounting from
real and/or side panel.3. Using an appropriate strain relief (not included) or conduit,
run wiring through rear or side panel. Connect wiring and cap unused wire. (refer to wiring diagram) Note: Orange and black wires should never be connected at the same time.
4. Securely mount fixture to wall/junction box. 5. Slide internal component tray down and connect batteries.6. Slide tray back up until it is locked in place. Remove arrow
knockouts from front cover as needed, then slide front cover into place and reinstall capture screw.
7. Apply power and allow battery pack to charge for at least 24 hours before initial test.
8. After 24-hour period, press test button to make certain emergency lights are functioning as intended and are aimed correctly.
Wall Installation (rear)
To LED Spotlight
To LED Spotlight
Battery Connection
Wall Mounting Holes
Junction Box Mounting Holes
Battery
¹
¹Limited 2-year warranty on battery.
Rev Date: V2 04/09/2020
Important: Read all instructions prior to installation. SAVE THESE INSTRUCTIONS.
LED Exit and Emergency LightXSCS-RW
4400 Earth City Expy, St. Louis, MO 63045 866-590-3533 superbrightleds.com
User Manual
Installation Instructions
1. Remove screw at bottom of case holding front cover in place. Note: For two-sided viewing, the blank rear cover can be removed using the same process and replaced later with additional included “exit” panel.
2. Remove appropriate knockouts for wiring and mounting from side panel.
3. Attach mounting plate to junction box, then attach mounting bracket to mounting plate.
4. Using an appropriate strain relief (not included) run wiring through side panel. Connect wiring and cap unused wire. (refer to wiring diagram) Note: Orange and black wires should never be connected at the same time.
5. Securely mount fixture to mounting bracket.6. Slide internal component tray down and connect batteries.7. Slide tray back up until it is locked in place. Remove arrow
knockouts from cover(s) as needed, then slide cover(s) into place and reinstall capture screw(s).
8. Apply power and allow battery pack to charge for at least 24 hours before initial test.
9. After 24-hour period, press test button to make certain emergency lights are functioning as intended and are aimed correctly.
Wall Installation (side)
To LED Spotlight
To LED Spotlight
Battery Connection
Battery
¹
¹Limited 2-year warranty on battery.
Rev Date: V2 04/09/2020
Important: Read all instructions prior to installation. SAVE THESE INSTRUCTIONS.