    UV Germicidal Systems

    PR0DUCT CATALOG

    A U V s o l u t i o n f o r e v e r y a p p l i c a t i o n

    Choose UV Systems for: healthier air

    energy savings

    reduced maintenance

    Clean coils in rooftop units or smaller AHUs

    Clean coils in AHUs

  • 8/9/2019 UV Germicidal System

    2/12

    P a g e 2 D R I S T E E M U V G e r m i c i d a l S y s t e m s

    W h y c l e a n c o i l s w i t h U V C l i g h t ?

    1 . H e a l t h i e r a i r

    Mold in buildings is a known health threat. Mold and other

    microorganisms grow on damp cooling coils and in drain pans.Air flowing through coils and across drainpans spreads mold spores and mycotoxinsthroughout buildings where they can landand multiply on moist surfaces. To do allyou can to eliminate this threat, kill moldand other microorganisms on cooling coilsand drain pans with ultraviolet light in theC bandwidth (UVC). Continuous UVC exposure, provided byDRISTEEMs UV Germicidal Systems, keeps coils and drain pansclean and keeps mold spores out of the airstream.

    2 . S a v e e n e r g y

    A coil with very small amounts of mold growth can significantlyblock airflow and decrease coil thermaltransfer. The coil may look clean to thenaked eye, but there still can be enoughmold coating a cooling coil to reducesystem efficiency. As mold growth on acoil increases, energy costs increase due toreduced coil efficiency.

    3 . R e d u c e m a i n t e n a n c e

    Cleaning coils by hand exposes maintenance staff to strongchemicals and mold mycotoxins, which can cause severe healthproblems. Pressure-washing coils can push mold into the coilinterior, reducing coil function or requiringcoil replacement. Removing coils tosubmerge them until clean sometimesworks; however, it is a very expensive wayto clean coils.

    Theres a much easier and more effectiveway to keep coils clean.

    UV Germicidal Systems clean dirty coils and drain pans and keepthem continuously clean. Just replace the lamps annually andeliminate the periodic need for cleaning toxic coils by hand. UVGermicidal Systems applied to new coils maintain operation at peakperformance.

    Where should you install UVC?Mold spores are everywhere in our homesand work places. We co-exist comfortablywith mold when their populations aresmall; however, when mold spores f ind afavorable environment, they multiply tothe point where they can cause healthproblems.

    To multiply, mold spores need moisture anda food source. While there are many placeswithin a building where mold can grow,mold thrives on damp cooling coils with

    dust as its food source.Good filtration helps, and prevents somemold growth, but will not eliminate it.

    And, its extremely important to kill moldon coils to prevent spores from spreadingthroughout the building via the airstream.This is why we recommend installing UVClights to illuminate all cooling coils.

    Q:What types of buildings need a UVGermicidal System?

    A:Any building with a damp or wetcooling coil.

    Coil cleaned at these points in time

    Peakcoil

    efficiency

    Reducedcoilefficiency

    Coil loses efficiencyin between manual cleanings

    Figure 2-1:Coil efficiency and manual cleaning

    Immediately after a coil is cleaned manuallyit begins to lose efficiency due to moldgrowth. DRISTEEMs UV Germicidal Systemskeep clean coils continuously clean,allowing coils to continuously operate atnear peak efficiency.

  • 8/9/2019 UV Germicidal System

    3/12

    D R I S T E E M U V G e r m i c i d a l S y s t e m s P a g e 3

    R e l y o n D R I S T E E M f o r . . .

    DRISTEEM performance and reliability

    Customers all over the world rely on DRISTEEM performance

    and reliability. Proven in thousands of installations, youllfind DRISTEEM humidifiers at NASA, high-tech facilities,world-famous museums, and the White House. Now, thatsame engineered performance and reliability is available inDRISTEEMs UV Germicidal Systems.

    Solutions that precisely fit your application

    DRISTEEM has a UV solution for every cooling coilapplication, including:

    Large AHUs Small AHUs Packaged rooftop units

    From systems installed right out of the box to systems designedfor a uniquely sized AHU, youll find the right UV solution atDRISTEEM.

    Efficient operation

    An effective ultraviolet treatment is a factor of intensity aswell as exposure time. Rely on DRISTEEMs UV GermicidalSystems to provide the required amount of ultraviolet light tokill microorganisms on coils. Polished aluminum reflectorson Model UVR enhance this efficiency by focusing ultravioletenergy at the coil and drain pan.

    Easy installation and servicing

    DRISTEEM UV Germicidal Systems are easy to install andservice. Model UVR is pre-assembled and ready to mount onsupport channels. Just connect power to the terminal strips.Other models ship with mounting hardware. Model UVRfixtures rotate away from the coil for easy service access (seeFigure 4-1).

    M o r e a b o u t m o l d

    Mold spores are everywhere and grow where there is water and food such as dust, paper

    or wood. In buildings, molds thrive on dark, damp cooling coils and on moist paper orwood building materials such as wall board.

    All molds can cause allergic reactions in humans and many produce mycotoxins.

    Mycotoxins can be found in air, mold spores, within mold itself, and in the material where

    mold is growing. Some common indoor molds such as aspergillus and penicillium can

    cause a severe, sometimes toxic, reaction in humans. At low normal background levels,

    mold is only a minor issue for many. Unmanaged, mold can be a serious health issue.

    Ultraviolet light (C band) emitters

    shall be incorporated downstream of

    all cooling coils and above all drain

    pans to control airborne and surface

    microbial growth and transfer.

    U.S. Standard for Government Buildings

  • 8/9/2019 UV Germicidal System

    4/12

    P a g e 4 D R I S T E E M U V G e r m i c i d a l S y s t e m s

    Model UVRInternal mount rack system

    U V G e r m i c i d a l S y s t e m s o v e r v i e w

    Lamp fixture rotates away from coilfor service access (see Figure 4-1)

    Remove quickrelease pin torotate fixture

    Ballast

    Lamp

    Reflector

    Electrical enclosureTerminal strip

    Supportchannel

    Model selection

    This system can be configured to provide completeillumination of coils 4'-12' (1.2 m - 3.7 m) wide.See Pages 6-8 for more information.

    Keeping coils sanitary throughcleaning and the application of

    chemicals and/or UV lights is part

    of a system-wide approach, which

    can prevent spores from amplifying

    in the heating and air conditioning

    system. ACHR News

    Figure 4-1:Model UVR rotating lamp fixture

    In operating mode (top), Model UVRs lampfixture is positioned to directly illuminatethe coil. In service mode (bottom), the lampfixture rotates 90 away from the coil foreasy service access. To rotate the lampfixture, simply pull the quick release pinfrom the hinged bracket.

    Lamp fixture rotates90 away from coilfor easy lampreplacementaccess

    Lamp fixture inoperating mode

    Lamp

    Reflector

    Reflector

    Quick-release pin

    Quick-release pin

    Quick-releasepinremoved torotate fixture

    Lamp fixturein service mode

    OM-6355

    Convenientaccess to ballast

    Application

    For cleaning large AHU coils 4'-12' (1.2 m - 3.7 m) wide Completely assembled and ready to mount on support

    channels; just connect power to the terminal strips.Note: Support channels are provided by installer, or maybe ordered as a DRISTEEM option.

    Rotating lamp fixture and quick-release pin allow veryeasy access for maintenance (see Figure 4-1)

    Polished aluminum reflector focuses UV energy

    120, 208, 240, and 277 VAC available voltages

    OM-1130

  • 8/9/2019 UV Germicidal System

    5/12

    D R I S T E E M U V G e r m i c i d a l S y s t e m s P a g e 5

    Application

    For cleaning coils in packaged rooftop units Weather-resistant NEMA-4 housing 24" (610 mm; Model UV-W-1-24) and

    32" (813 mm; Model UV-W-1-32) lamps available NEMA-4 housing door interlock safety switch 120 to 277 VAC auto adjusting variable voltage ballast Electrical usage: 60 watts for Model UV-W-1-24,

    75 watts for Model UV-W-1-32

    Application

    For cleaning coils in packaged rooftop units or smallair handlers

    Internally mounted; requires no exterior penetrations 18" (458 mm) lamp 120 to 277 VAC auto adjusting variable voltage ballast Electrical usage: 55 watts

    U V G e r m i c i d a l S y s t e m s o v e r v i e w

    Coil area illumination by modelModel

    number

    Coil area illumination Lamp length

    in2 ft2 m2 inches mm

    UV-W-1-24 1008 7.0 0.65 24 610

    UV-W-1-32 1296 9.0 0.84 32 813

    Note: Combine fixtures to completely illuminate coil and drain pan.See Page 10 for more information.

    Coil area illumination by modelModel

    number

    Coil area illumination Lamp length

    in2 ft2 m2 inches mm

    UV-I-1-18 792 5.5 0.5 18 458

    Note: Combine fixtures to completely illuminate coil and drain pan.See Page 9 for more information.

    Model UV-I-1-18Internal mount with mounting hardware

    Fixture with weather resistantNEMA-4 housing

    LampCooling coil

    24" (610 mm) lamp32" (813 mm) lamp

    NEMA-4 housing

    18" (458 mm) lamp

    Mounting hardware(provided by DRISTEEM)

    Blower

    Cooling coil

    UV fixture

    Models UV-W-1-24 and UV-W-1-32External mount with weather-resistant housing

    Blower

  • 8/9/2019 UV Germicidal System

    6/12

    P a g e 6 D R I S T E E M U V G e r m i c i d a l S y s t e m s

    Components (see Figure 6-1)

    1. Rotating lamp fixture

    The lamp fixture rotates away from the coil,allowing easy access for lamp replacement(see also Figure 4-1 on Page 4).

    2. Hinge with quick release pin

    To rotate the lamp fixture, simply pull thequick release pin from the hinged bracket(see also Figure 4-1).

    3. Ballast

    Program-start ballast provides precise lampfilament preheat, optimizing lamp life.Operates with the following voltages: 120,208, 240, and 277 VAC.

    4. Lamp

    High output ultraviolet (UVC) lamp killsmold, bacteria, and all other microorganismson coils and drain pans.

    5. Reflector

    Polished aluminum reflector focuses UVCenergy.

    6. Terminal strip

    The terminal strip, located behind the easilyremoved key-holed cover, provides accessfor quick field electrical connections.

    7. NEMA-12 electrical enclosure

    The electrical enclosure houses an electronic

    timer that monitors lamp usage andilluminates an indicator light after 9,000hours of use to signal required lampreplacement. A dry contact closes when thelamps need changing and sends a signalto a remote indicator light or buildingmanagement system (provided by installer).

    8. Support channel (optional)

    The lamp fixture attaches easily to standardhole-punched channel supports, which canbe provided by DRISTEEM if requested,shipped loose.

    9. Door interlock safety switch (optional;

    not shown)Recommended for installation on anydoor with access to a UVC lamp, the doorinterlock safety switch turns off the UVClamp when the door it is installed on opens,preventing accidental exposure. The switchrequires manual reset.

    M o d e l U V R :C o m p o n e n t s a n d c o n f i g u r a t i o n s

    Figure 6-1:Model UVR components

    1

    2

    3

    4

    5

    6

    8

    Model UVR configurations

    Model UVR Germicidal Systems are applied to chilled water orrefrigerant cooling coils.

    Available voltages for Model UVR include 120, 208, 240, and 277

    VAC.Model UVR fits inside unobstructed duct widths from 48" to 144"(from 1219 mm to 3657 mm); and fits inside unobstructed ductheights from 24" to 180" (from 610 mm to 4572 mm). Note: Contactyour DRISTEEM representative for ordering instructions to installaround obstructions.

    Model UVR can be ordered with an optional door interlocksafety switch (manual reset). Note: A safety switch is highlyrecommended.

    Model UVR can be ordered with optional standard hole-punchedchannel supports shipped unassembled in lengths equal to height of

    duct minus 1" (25 mm).

    For custom solutions such as pre-assembled systems, applicationsrequiring custom UV illumination intensities, or stainless steelcomponents, contact your DRISTEEM representative.

    7

    OM-1130

  • 8/9/2019 UV Germicidal System

    7/12

    D R I S T E E M U V G e r m i c i d a l S y s t e m s P a g e 7

    Table 7-1:Model UVR dimensions

    Dimension Description Inches (mm)

    AOverall width

    47.75" (1213)minimum to 119.75"(3042) maximum in 6"(152) increments

    B

    Center-to-center width ofsupport channelmounting holes

    44.625" (1133)minimum to 116.625"(2962) maximum in 6"(152) increments

    CActive lamparea width

    41.75" (1060)minimum to 113.75"(2889) maximum in 6"(152) increments

    M o d e l U V R :D i m e n s i o n s a n d p l a c e m e n t g u i d e l i n e s

    Figure 7-1:Model UVR dimensions

    OM-1132

    Reflector

    Elevation view Mountingbrackets

    Side view

    A

    2.1" (53 mm)

    B

    Lamp fixtureTop view

    4.46"(113 mm)

    Note:

    Electrical enclosure dimensions:10" (254 mm) high 8" (203 mm) wide 6" (152 mm) deep

    C

    Installing Model UVR

    Install Model UVR on the coils downstream side 12" to 24"(305 mm to 610 mm) from the coil (12" [305 mm] recommended).Placement on the coils downstream side produces the most

    effective results because the downstream side tends to be the wetterside, enabling mold growth. In addition, the coils downstream sidetypically has more access room, allowing easier servicing.

    Notes:

    Obstructions between lamps and the coil will block illuminationand reduce Model UVRs effectiveness.

    Contact DRISTEEM for instructions when placing a dispersionunit downstream of a UV Germicidal System.

    Figure 7-2:Installing Model UVR in an AHU airflow

    OM-1134

    Top viewCooling coil

    Airflow

    Model UVR Heating coil

    Position Model UVR with lamp(s)horizontal and facing cooling coil

    12" (305 mm) recommended;maximum 24" (610 mm)

    UV lamp

    11.75"(298 mm)

    8.76"(223 mm)

    Figure 7-3:Dimensions of support channel foot

    OM-6354

    1.6875" (43 mm)

    3.5"(89 mm)

    9.1875"(233 mm)

    3.875"(98 mm)

  • 8/9/2019 UV Germicidal System

    8/12

    P a g e 8 D R I S T E E M U V G e r m i c i d a l S y s t e m s

    M o d e l U V R :A m p d r a w s , f i x t u r e s p a c i n g

    Table 8-2:Model UVR fixture row vertical spacing

    AHU, duct, or coil height Number offixture rows

    Spacing between fixture rows (S)S = AHU or duct height number of fixture rows

    Spacing between fixture andAHU/duct floor or ceiling (S)

    ft m inches mm inches mm

    2 to 5 0.6 to 1.52 1 Center vertically Center vertically

    5 to 6 1.52 to 1.83 2 30 to 36 762 to 914 15 to 18 381 to 457

    6 to 7 1.83 to 2.13 2 36 to 42 914 to 1067 18 to 21 457 to 533

    7 to 8 2.13 to 2.44 2 42 to 48 1067 to 1219 21 to 24 533 to 610

    8 to 9 2.44 to 2.74 2 48 to 54 1219 to 1372 24 to 27 610 to 686

    9 to 10 2.74 to 3.05 2 54 to 60 1372 to 1524 27 to 30 686 to 762

    10 to 11 3.05 to 3.35 3 40 to 44 1016 to 1118 20 to 22 508 to 559

    11 to 12 3.35 to 3.66 3 44 to 48 1118 to 1219 22 to 24 559 to 610

    12 to 13 3.66 to 3.96 3 48 to 52 1219 to 1321 24 to 26 610 to 66013 to 14 3.96 to 4.27 3 52 to 56 1321 to 1422 26 to 28 660 to 711

    14 to 15 4.27 to 4.57 3 56 to 60 1422 to 1524 28 to 30 711 to 762

    Notes:Center entire assembly within coil height and width.Follow fixture row spacing guidelines in this table; however, positioning does not need to be exact.If AHU or duct height is significantly more than coil height, use coil height for calculating S.

    Figure 8-1:Typical installation, Model UVR (elevation view)

    OM-1135

    Coilwidth

    AHU or duct

    AHU or ductwidth

    Coilheight

    AHU or duct height

    Space between AHU

    or duct ceiling andfixture row (S)

    Space betweenfixture rows (S).See Table 8-2

    Space between AHU orduct floor andfixture row (S)

    Table 8-1:Amps per fixture row by lamp fixture width

    Supplyvoltage(single-phase)

    Lamp fixture width in ft (m)* Amps*per

    electrical

    enclosure

    4.0(1.22)

    4.5(1.37)

    5.0(1.52)

    5.5(1.68)

    6.0(1.83)

    6.5(1.98)

    7.0(2.13)

    7.5(2.29)

    8.0(2.44)

    8.5(2.59)

    9.0(2.74)

    9.5(2.90)

    10.0(3.05)

    10.5(3.20)

    11.0(3.35)

    11.5(3.50)

    12.0(3.66)

    120 1.014 1.208 1.229 1.423 1.638 1.639 2.027 2.027 2.242 2.457 2.457 2.846 2.846 2.846 2.652 2.652 3.061 0.210

    208 0.574 0.680 0.702 0.808 0.936 0.936 1.148 1.148 1.276 1.404 1.404 1.616 1.616 1.616 1.510 1.510 1.744 0.121

    240 0.501 0.604 0.604 0.707 0.810 0.803 1.009 1.009 1.112 1.215 1.215 1.414 1.414 1.414 1.311 1.311 1.517 0.105

    280 0.439 0.523 0.532 0.616 0.710 0.710 0.878 0.878 0.971 1.064 1.064 1.233 1.233 1.233 1.149 1.149 1.326 0.091

    * Amp values listed by fixture width are for one row only. To calculate total Amps per rack system, multiply the Amp value by the number of fixture rows and addamperage for one electrical enclosure. For example: Total amps for a 120 V system with three 12-foot rows = (3 3.061) + 0.21 = 9.393 Amps.

  • 8/9/2019 UV Germicidal System

    9/12

    D R I S T E E M U V G e r m i c i d a l S y s t e m s P a g e 9

    M o d e l U V - I - 1 - 1 8 :D i m e n s i o n s , i n s t a l l a t i o n g u i d e l i n e s

    Figure 9-2:Model UV-I-1-18

    Figure 9-1:Typical installation, Model UV-I-1-18

    Figure 9-3:Model UV-I-1-18 components

    Figure 9-4:Model UV-I-1-18 dimensions

    Table 9-1:Guidelines for number of fixtures by coil area

    Coil areaRecommended

    number of fixtures

    in2 ft2 m2 Model UV-I-1-18

    750 5.2 0.48 1

    1000 6.9 0.64 2

    1250 8.7 0.80 2

    1500 10.4 0.97 21750 12.2 1.13 3

    2000 13.9 1.29 3

    2250 15.6 1.45 3

    2500 17.4 1.62 4

    2750 19.1 1.77 4

    3000 20.8 1.93 4

    3250 22.6 2.10 5

    3500 24.3 2.25 5

    Notes: Model UV-I-1-18 covers approximately 792 in2 (5.5 ft2, 0.5 m2) of coil area. Use this table as a guideline only. The most important requirement for an effective UV

    Germicidal System installation is complete coil and drain pan illumination. Install fixturesas required to fully illuminate the coil and drain pan. The above guidelines are based on the following assumptions:

    UV lamps installed 3 to 12 inches (76 mm to 305 mm) from coil Coil thickness in the range of 2 to 4 inches (51 mm to 102 mm)

    As distance from the coil increases, light intensity illuminating the coil decreases,requiring more time for organisms to be killed by UV light.

    Coolingcoil

    Model UV-I-1-18

    Mountinghardware as shown

    provided byDRISTEEM

    Blower

    Wiring access cover

    Lamp socket

    Lamp

    Mountingbrackets

    18.25" (404 mm)

    4.50" (114 mm)

    17" (432 mm)

    3"(76 mm)

    2.77"(70 mm)

  • 8/9/2019 UV Germicidal System

    10/12

    P ag e 1 0 D RI ST EE M U V G er mi ci da l S ys te ms

    BlowerLampCooling coil

    Fixture base and cabinet

    Figure 10-1:Models UV-W-1-32 and UV-W-1-24

    M o d e l s U V - W - 1 - 2 4 a n d U V - W - 1 - 3 2 :D i m e n s i o n s , i n s t a l l a t i o n g u i d e l i n e s

    Figure 10-4:Typical installation

    OM-1131

    Figure 10-2:Components

    Ballast

    Fuse

    Lamp retainingbracket

    Lamp base

    Lamp socket

    Lamp

    Internal switch

    Figure 10-3:Dimensions

    OM-1133

    Side view

    Front view

    10" (254 mm)

    4.25" (108 mm)

    23" (584 mm)or

    32.25" (819 mm)

    8"(203 mm)

    Table 10-1:Guidelines for number of fixtures by coil area

    Coil area Recommended number of fixtures

    in2 ft2 m2Model UV-W-1-24

    24" lampModel UV-W-1-32

    32" lamp

    750 5.2 0.48 1 11000 6.9 0.64 1 1

    1250 8.7 0.80 2 1

    1500 10.4 0.97 2 2

    1750 12.2 1.13 2 2

    2000 13.9 1.29 2 2

    2250 15.6 1.45 3 2

    2500 17.4 1.62 3 2

    2750 19.1 1.77 3 3

    3000 20.8 1.93 3 3

    3250 22.6 2.10 4 3

    3500 24.3 2.25 4 3Notes: Model UV-W-1-24 covers approximately 1008 in2 (7 ft2, 0.65 m2) of coil area. Model UV-W-1-32 covers approximately 1296 in2 (9 ft2, 0.87 m2) of coil area. Use this table as a guideline only. The most important requirement for an effective UV

    Germicidal System installation is complete coil and drain pan illumination. Install fixturesas required to fully illuminate the coil and drain pan.

    The above guidelines are based on the following assumptions: UV lamps installed 3 to 12 inches (76 mm to 305 mm) from coil Coil thickness in the range of 2 to 4 (51 mm to 102 mm) inches

    As distance from the coil increases, light intensity illuminating the coil decreases,requiring more time for organisms to be killed by UV light.

  • 8/9/2019 UV Germicidal System

    11/12

    D R I S T E E M U V G e r m i c i d a l S y s t e m s P a g e 1 1

    S p e c i f i c a t i o n s

    Model UVR

    UV Germicidal System shall kill bacteria, fungi, and mold thatcan grow on the cooling coil and drain pan.

    UV Germicidal System shall be factory-assembled and tested.It shall consist of a galvanized steel hinged rotating housing toallow easy access for maintenance, power source, lamp sockets,lamp, reflector, and control cabinet. All components shall beconstructed to withstand typical HVAC environments.

    Unit shall be mounted to standard hole-punched channelsupports and secured within air handling unit.

    The UV ballast shall be an electronic, high frequency, program-type with auto-adjusting, variable voltage, high output ballast

    with a voltage range of 120-277 VAC, 50/60 Hz, high outputlamp, fuse protection, and mounting flanges.

    Lamp connectors shall be circline-type sockets and constructedof a UVC-resistant polycarbonate.

    Lamp shall be a high output, hot cathode, T5 diameter, four-pin single-ended type that produces germicidal UV-C energy at254 nm. Each lamp shall produce the specified output at 500 fpmand air temperatures of 55 F (13 C).

    Reflector shall be constructed of specular polished aluminum tomaximize usage of all ultraviolet energy.

    The unit shall have terminal strips for quick field electricalconnections.

    UV Germicidal System shall be complete with NEMA-12electrical housing, shipped loose, containing: power block, 24volt step down transformer, electronic timer indicating hoursof usage, relay for dry contact for remote indication to replacelamps, door mounted indication lights for power (red) and

    replace lamps (green).

    Control option: The unit shall have a door interlock safety switch,auto-off, manual reset. The unit shall not produce ozone. The unit shall be independently tested to verify conformance to

    ETL per UL Standard 1598. The unit shall be EPA listed. Unit warranty shall be two years; the lamp warranty shall be one

    year.

    Model UV-I-1-18

    Ultraviolet Germicidal System shall kill bacteria, fungi, and moldthat can grow on the cooling coil.

    Unit shall be designed for installation inside a rooftop HVAC

    unit.

    Germicidal UV-C energy measured at a distance of 1 meterperpendicular to the center of the lamp shall be greater than 270W/cm2 at 253.7 nm when measured in a galvanized steel ductwith 70 F air moving at 400 fpm.

    Germicidal UV-C energy measured at a distance of 18 inchesperpendicular to the center of the lamp shall be greater than 560W/cm2 at 253.7 nm when measured in a galvanized steel ductwith 70 F air moving at 400 fpm.

    Unit shall be complete with stainless steel housing containing:auto-adjusting, variable voltage, high output ballast with a

    voltage range of 120-277 VAC, 50/60 Hz, high output lamp, fuse

    protection, and mounting flanges. Unit shall be housed completely inside of the HVAC equipment

    and not require any type of penetration of the equipmentcasing.

    Unit shall incorporate electrical knockouts on both ends of theunit to accommodate convenient supply wiring.

    Unit shall not exceed 55 watts. Unit shall not produce ozone. The unit shall ship complete with mounting hardware to assist

    in installation. Lamp life shall be one year when operated continuously. The unit shall be EPA listed. Unit shall be UL and C-UL classified. Unit warranty shall be two years; the lamp warranty shall be one

    year.

    Models UV-W-1-24 and UV-W-1-32

    Ultraviolet Germicidal Lamps shall kill bacteria, fungi, andmold that can grow on the cooling coil.

    Unit shall be designed for installation on a rooftop HVAC unit. Germicidal UV-C energy measured at a distance of 1 meter

    perpendicular to the center of the lamp shall be greater than 270W/cm2 at 253.7 nm when measured in a galvanized steel ductwith 70 F air moving at 400 fpm.

    Germicidal UV-C energy measured at a distance of 18 inchesperpendicular to the center of the lamp shall be greater than 560W/cm2 at 253.7 nm when measured in a galvanized steel ductwith 70 F air moving at 400 fpm.

    Unit shall be complete with NEMA-4 electrical housing

    containing: auto-adjusting, variable voltage, high output ballastwith a voltage range of 120-277 VAC, 50/60 Hz, high outputlamp, fuse protection, and NEMA-4 housing door interlocksafety switch.

    NEMA-4 electrical housing shall be complete with mountingflanges, door weather gasket, and surface gasket to seal the unitto the HVAC equipment.

    Unit shall incorporate an electrical knock-out on the sameside of the box that the lamp protrudes from to accommodatesupply wiring from within the rooftop unit without requiring anadditional electrical penetration in the electrical housing.

    The unit shall allow for the installation of weather resistantconduit fittings on any side of the electrical housing whenwiring is external to the HVAC equipment.

    Unit electrical shall not exceed 60 watts for 24" units or 75 wattsfor 32" units.

    Unit shall allow for annual service to be conducted from the

    outside of the rooftop unit. Unit shall produce no ozone. Unit shall be UL and C-UL classified. Lamp life shall be one year when operated continuously. The unit shall be EPA listed. Unit warranty shall be two years; the lamp warranty shall be one

    year.

  • 8/9/2019 UV Germicidal System

    12/12

    Important safety statement

    DRISTEEMs UV Germicidal Systems use lampsthat emit ultraviolet light in the UVC bandwidthwhen energized. Direct or reflected exposure toUVC light can cause severe bodily injury and/orburns to eyes and skin. To reduce personalinjury risk, install UV Germicidal Systems only inapplications providing adequate protection toarea occupants. To prevent accidental exposure,DRISTEEM strongly recommends installingdoor interlock safety switches on all doorsaccessible to UV lamps. More detail about safetyprecautions is in the UV Germicidal SystemsInstallation, Operation, and Maintenance Manual.

    DRISTEEM CorporationAn ISO 9001:2000 certified corporationand a subsidiary of Research ProductsCorporation

    Continuous product improvement is a policyof DRISTEEM Corporation; therefore, productfeatures and specifications are subject tochange without notice.

    U.S. Headquarters:14949 Technology DriveEden Prairie, MN 55344800-328-4447952-949-2415952-229-3200 (fax)

    European office:Bell Place, Bell LaneSyresham, Brackley

    NN13 5HP, UK+44 1280 850122 (voice)+44 1280 850124 (fax)E-mail: [email protected]

    DRISTEEM, GTS, and Ultra-sorb are registeredtrademarks of DRISTEEM Corporation.

    2005 DRISTEEM Corporation

    Model UVR is ETL listed.Models UV-I-1-18, UV-W-1-24, andUV-W-1-32 are UL classified.

    For more information

    [email protected]

    Your DRISTEEM representative is:

    Form No. UV-CAT-0305

    Proven humidification systems designed for your HVAC project

    In addition to manufacturing UV Germicidal Systems, DRISTEEM

    also designs and manufactures industrial and commercialhumidification systems for customers around the world. Someof our humidification products are showcased here. For moreinformation, contact your DRISTEEM representative or visit ourweb site at www.dristeem.com

    Easy-to-operateelectric humidifier

    The new VT Serieshumidifier is an af-fordable, reliable andeasy-to-operate electrichumidifier. Simply setthe humidistat, pressthe on button, and walkaway. And, the humidi-fier is maintenance-freefor the first three yearswhen operated with

    softened water.

    Redesigned gas-to-steam humidifier

    DRISTEEM has improvedthe functionality, reliability,and cost-efficiency ofthe industrys first gashumidifier. Now all thecomponents are containedwithin the cabinet, makingthe GTS humidifier easierto maintain and install.What hasnt changed is theproven energy-efficiency ofgas humidification.

    Guaranteed steamabsorption within inchesUltra-sorb steam dispersionpanels provide guaranteeddrip-free absorption, forinstallation within inchesof downstream devices eliminating condensationworries. Panels can beinstalled in ducts or air-handling units and operatewith any steam pressure.