Date post: | 07-Apr-2015 |
Category: |
Documents |
Upload: | vasanth-kumar |
View: | 109 times |
Download: | 0 times |
Presentation of UVGI Systems Ltd.
By Adrian Ng Airgate Engineering (HK) Ltd
Presentation of UVGI Systems Ltd.
By Peter Hudsonand Barry Pollard
Presentation of UVGI Systems Ltd.ForCIBSE
By Peter Hudson [email protected], 07860 883 923Barry PollardAzael [email protected]; www.uvgi.com
?
Mission Statement
To provide a range of air sterilisation products capable of maximum efficiencyunder a full HEVAC range of conditions(i.e. air velocity, volume and temperature).
Further, to create a suite of products capable of modular assembly to provide a practical yet flexible total air sterilisation solution.
HOW CLEAN IS YOUR AIR?
Is outside air really “fresh air” ?
More than 20% of outdoor air contains harmful bacteria & Pathogens
HOW CLEAN IS YOUR AIR?
Is outside air really “fresh air” ?
More than 20% of outdoor air contains harmful bacteria & Pathogens
Current major concerns in the World
Poor Indoor Air QualityRe-circulated air ventilation
Healthcare Acquired Infections
TuberculosisMeningitis
MRSAC. Diff
InfluenzaH1N1 & Avian
SARS
HealthCare Acquired Infections(HCAI’s)
Effect:10% to 20% of all Patients
Claimed:20,000 deaths pa in Germany30,000 deaths pa in UK90,000 deaths pa in USA
Only a plane ride away!!!
H1N1 WHO declares Influenza pandemic• In less than 8 weeks it has spread to 75 countries,
causing death in 9.• 30,000 cases globally & 141 deaths.• Figures are rising daily. (updated 11.6.09)
• It is the first flu pandemic in 40 years- the last in 1968 killed about one million people.
• Two weeks later its risen to 60,000 cases & 263 deaths(update 29.6.09)
• In 6 weeks 5,500 people infected in 20 countries.
• This grew to 8,096 infected casesand 774 deaths in 4 months.
• Planes and hotels were empty, resulting in losses over $100 Billion.
SARS OUTBREAK in 2003
SARS: Severe Acute Respiratory Syndrome
Indoor Air Quality (IAQ) problems
Air ducts are places where microorganismscan grow and gather by cross contamination
Microorganisms can double every 20 minutesIn a single day one microorganism grows to4,700,000,000,000,000,000.
Resistance to Antibiotics – increases the threat to our health.
Micoorganisms becoming resistant to AntibioticsMRSASARSTBNoroBird FluLegionella
ULTRA CLEAN AIR - GUARANTEED
Removes airborne pathogens- including Bacteria & Viruses
MEASURABLE PERFORMANCEWITH GUARANTEED RESULTS
COMMERCIAL BENEFITS
Reduced energy operating costs by 20%
Reduces Ozone & Biological inter-action with VOC’s
Reduced absenteeism
COMMERCIAL BENEFITS
Reduce energy operating costs by 20% of fresh air
Reduces Ozone & Biological inter-action with VOC’s
Reduced absenteeism
M&S Plan ASocial conscience
Sustainable Environment
Sick Building Syndrome
Eco friendly
Reducing Energy Costs
Building Regulations Part L to be re-writtenA reduction in the ventilation rate from 10 l/sec down to 8 l/sec in line with ASHRAEWould result in:20% reduction in heating & cooling costs.
Microbial Filtration
Social conscience
Sustainable Environment
Sick Building Syndrome
Eco friendly
Reducing Energy Costs
20% reduction in heating & cooling costs.
UVC providesMicrobial Filtration
WHAT IS UVGI ?
Ultra Violet Germicidal Irradiation
@ 254 nm wavelength lethally damages airborne microorganisms
UVGI - recognised term throughout the world
HOW DOES UVGI WORK?
Disrupts the microorganisms DNA- Causing cell death or incapable of multiplying
Nobel Prize foruse against TB
Key to performance - Light intensity & Dwell time
REASEACH & DEVELOPMENT
Patented technology> £14M Investment> 10 Yrs R&D
Measurable Performance & Guaranteed Results
PARTNERS IN DEVELOPMENT
Air movement & Acoustic specialists
UK Government HPA Porton Down Test HouseStaphyylococcus Epidermis – (MRSA)Aspergillus Niger – Aspergillus Fumigatus / AnthraxMycobacterium Vaccae – TBMS-2 Coliphage (Influenza / SARS / Coronavirus / E coli
Results - Average efficiency > 99.9%
PARTNERS IN DEVELOPMENT
Pathogen control departmentResults showed reduced concentrations by 99.9%
ON GOING RESEARCHProfessor Beggs of University of BradfordWorlds leading expert in prevention & control of healthcare associated infections
Basingstoke NHS Hospital2 Yr test in four high dependency roomsSignificant reduction in colony count
PARTNERS IN DEVELOPMENT
Pathogen control departmentResults showed reduced concentrations by 99.9%
ON GOING RESEARCHProfessor Kowalski - University of Penn State, USAWorlds leading expert in UVC SterilisationProfessor Noaks - University of Leeds Pathogen Control
Basingstoke NHS Hospital2 Yr test in four high dependency roomsSignificant reduction in colony count
CLINICAL TRIAL
Air Quality SamplingMeasured in Colony Forming Units (CFU's)
Room
With or without
UVGI device CFU/M3 CFU/FT3%
Improvement
Isolation Room 727 No UVGI 675 19.1
93%
With UVGI 50 1.4
A & E Room 7 No UVGI 1,770 50.0
84%*
With UVGI 287 8.1
* Air sample taken immediately after room occupancy
Sample Tests CFU/M3
Before 30.3.10 490
6 Hours after 90
22.4.10 A. By bench, centre of room
<7
22.4.10 B. by door 20
Hong Kong Stem Cell Laboratory TestASU 6000 Fee- Standing Unit
M3/Hr CFU/M3Before
CFU/M3After
%“Kill”
1500 12,340 24 99.82
2000 10,980 24 99.79
3000 7,600 0 100.00
National Bio Protection Engineering Centre ShanghaiCDC Test for ASU 3000 In-Duct Unit
Trial of UVGI Systems Air Sterilisation Equipment Using ASU 1000 In-Branch and Ceiling-Jet Units
DateColony Forming
Units / M3
Fungi present
15.03.10 680 Yes16.03.10 Installation19.03.10 32 No
95% improvement within 3 days.
Royal Hospital Sultanate of Oman
PROVENTEST RESULTS
pass the HEPA filters
pass a conventional
filter
Primary Target markets
• Healthcare
• Commercial Offices
• Hotels
• Entertainment venues
• Schools & Universities
Additional potential markets
• Leisure Centres
• Food Industries
• Pharmaceutical
• Aircraft
• Cruise Ships
Global Opportunities
PRODUCTS
To suit any air duty,room size or building layout…
….without compromising on air sterilisation efficiency.
In-Branch
In-DuctMulti-Assembly
Ceiling-Jet
Free-Standing
PRODUCTS
In-Duct Units
Sterilising poor outdoor air….
……and for servicing re-circulated indoor air systems
Multi Assembly In-Duct Units
PRODUCTS
ASU 1000In-Branch Unit
Designed to serve individual or isolated rooms
Balancing volume & velocity to create maximum dwell time
– to eliminate all harmful pathogens
ASU 1000In-Branch Unit
Technical DetailsDimensions W x H x L (mm) 175 x 175 x 750 Weight 10kgPower input 170 WattsPower supply 220 – 240 AC / 50 Hz / 1 Phase Lamp replacement 9000 HoursAir Volume @ 15 Pa 0.15 m3/s
318 CFM540 m3/Hr
Specifically designed to serveIndividual rooms
ASU 2000In-Duct Unit
Technical DetailsDimensions W x H x L (mm) 550 x 350 x 1200 Weight 35kgPower input 240 WattsPower supply 220 – 240 AC / 50 Hz / 1 Phase Lamp replacement 9000 HoursAir Volume @ 18 Pa 0.8 m3/s
1695 CFM2,880 m3/Hr
Designed for general Commercial applications & low to medium risk Medical situations
ASU 3000In-Duct Unit
Technical DetailsDimensions W x H x L (mm) 550 x 350 x 1200 Weight 40kgPower input 480 WattsPower supply 220 – 240 AC / 50 Hz / 1 Phase Lamp replacement 9000 HoursAir Volume @ 35 Pa 0.8 m3/s
1695 CFM2,880 m3/Hr
The most powerful andefficient air sterilisationunit of its type
Ideal for high risk medical applications
Sterilising poor outdoor air….
……and for servicing re-circulated indoor air systems
ASU 2000 / ASU 3000 Multi-Assembly In-Duct Modules
ASU 2000 / ASU 3000Multi-Assembly In-Duct Modules
To suit any air duty,room size or building layout…
….without compromising on air sterilisation efficiency.
For total design flexibility
SCALABLE
ASU 2000 / ASU 3000Multi-Assembly In-Duct Modulescan be added to any existing system and new build….….to suit any air duty, room size or building layout
To suit your requirements
ASU 2000 / ASU 3000 Multi-Assembly In-Duct Modules
ASU 5000Ceiling-Jet Unit
Sterilises indoor air through localised recirculation
Sized to replaces a single standard ceiling tile
Unique & Patented
CEILING-JET UNIT
Directional air jet dissipates air throughout the entire room, including areas of high bacterial concentration
ASU 5000Ceiling-Jet Unit
Technical DetailsDimensions W x H x L (mm) 595 x 595 x 345 Weight 30kgPower supply 220 – 240 AC / 50 Hz / 1 Phase Lamp replacement 9000 HoursOptimum room size 50 cu mFan In-line backward curve fan , EC rotor motor
with integrated electronic controlsSettings m3/s CFM dBA Amps Watts Air Changes / Hr*Standard 0.10 212 39 0.78 180 12 Boost 0.22 466 60 0.84 230 26
Using latest discharge technologyto maximise minimum air quantity
ASU 6000Free-Standing Unit
Portable device – used to sterilise specific spaces
“Standard flow”setting for general cleaning & “High Pulse” for roompurging
ASU 6000Free-Standing Unit
Technical DetailsDimensions W x D x H (mm) 400 x 400 x 880 Weight 20kgPower supply 220 – 240 AC / 50 Hz / 1 Phase Lamp replacement 9000 HoursFan Direct drive, rotor motor, forward curve DIDW
centrifugal fan with sealed bearings Optimum room size 50 cu m Settings m3/s CFM dBA Amps Watts Air Changes / Hr*Standard 0.10 212 40 1.16 270 12 Boost 0.21 445 57 1.28 288 25
Using latest discharge technologyto maximise minimum air quantity
ASU 4000Modular System
For large remote rooms not served by a central ductwork system
Comparison of the ASU 3000 with a traditional UV solution
Side Elevation – Irradiation Pattern Isometric – Irradiation Pattern
Traditional UV solution
Air flow
1200 Long dwell chamber
350
x 55
0
The traditional way to create a UV zone is by mounting a number ofUV lamps perpendicular to the airstream.
What determines the ability to killairborne pathogens?
1. UV intensity2. Dwell time (exposure)3. Resistance of pathogen to UV irradiation
UV lamp intensity reduces dramatically as the distance increases away from the lamp:
UV intensity factor in relation to distance from the lamp
0
50
100
150
200
250
300
350
400
0 100 200 300 400 500 600 700 800 900 1000
mm
uW/cm2
Distancefrom lampmm
LampIntensityFactor
0 354
25 127
50 69
100 32
150 20
200 14
250 14
380 6
500 4
635 3
760 2
890 1.4
1000 1
Only very close to the lamp is the irradiation intensity high enough to kill.
‘Blue light’ in itself does not kill.
Lamp irradiation comparison
87W / 28W UVC vs 48W / 13W UVC
Traditional lampUVGI lamp
Traditional 48 watt commercial single lamp
irradiation performance based
on manufacturers technical data.
UVGI System 87 watt single lamp
irradiation performance based
on manufacturers technical data,
UVGI lamps 4 times larger “killzone”
ASU 3000
Average irradiation value 70,000 µJ/cm2
Air flow
@ 0.15 seconds dwell time & 5.8 m/s optimum velocity
ASU 3000
Average Dose value 25,000 µJ/cm2 - URV 20
Air flow
@ 0.15 seconds dwell time & 5.8 m/s optimum velocity
Perpendicular to airflow
using traditional lamps (40W / 5W UVC per lamp)
Air flow
350
x 55
0 m
m
To achieve the same minimum UV irradiation as ASU 3000
a) 55 No. lamps requiredb) Increase in air velocity/reduction in dwell timec) High radiated heat 2.2 Kw & 2.3 ºC temp raise. d) Remote ballast likely due to congested lamp configuration.
0
10000
20000
30000
40000
50000
60000
70000
80000
90000
100000
0 200 400 600 800 1000 1200
Lamp Irradiation Pattern
uW/c
m2
Irradiation performance ofUVGI Systems ASU3000 unit (Depth of UVfield 550 x 350 mm)
Irradiation performance of4 lamp set up with samespec as ASU 3000 lamps(Restricted depth of UVfield: 280 mm dia)
Irradiation performance of4 lamp traditional set upperpendicular to airflow(Restricted depth of UVfield: 75 mm dia)
1
2
3
1
2
3
UV field comparison using :
ASU 3000 = 70,000 uJ/cm2 average blanket irradiation.
1) ASU 3000 unit – lamps parallel to airflow.
2) 4 x 90W lamp stab-in unit – lamps perpendicular to airflow.
3) 4 x 40W lamp traditional stab-in unit – lamps perpendicular to the airflow
350 x 550 mm
duct
850 mm Dwell time
mm mm
0
10000
20000
30000
40000
50000
60000
70000
80000
90000
100000
0 200 400 600 800 1000 1200
Lamp Irradiation Pattern
uW/c
m2
Irradiation performance ofUVGI Systems ASU3000 unit (Depth of UVfield 550 x 350 mm)
Irradiation performance of4 lamp set up with samespec as ASU 3000 lamps(Restricted depth of UVfield: 280 mm dia)
Irradiation performance of4 lamp traditional set upperpendicular to airflow(Restricted depth of UVfield: 75 mm dia)
1
2
3
1
2
3
UV field comparison using :
ASU 3000 = 25,000 uJ/cm2 average blanket Dose.
1) ASU 3000 unit – lamps parallel to airflow.
2) 4 x 90W lamp stab-in unit – lamps perpendicular to airflow.
3) 4 x 40W lamp traditional stab-in unit – lamps perpendicular to the airflow
350 x 550 mm
duct
850 mm Dwell time
mm mm
UVGI Systems additional advantages• Lamps parallel to airstream – most efficient use of power.
• Prevent dust build up.
• 2.5 times less Power consumption.
• Easy to install and maintain, including when retrofitting existing HVAC installations.
• Investment is 40-60% lower.
• UVGI guaranteed performance throughindependent test data.
• Lower annual maintenance costs.
Room Type Description Sterilisation Guide URV µW/cm2 Risk Level
Domestic Influenza 45 - 80%
10
11
12
500
1,000
1,500
Low
Commercial Influenza 81 - 95%
13
14
2,000
3,000
Low /Medium
High spec commercial / Low Medical
Influenza 99%
15
16
4,000
5,000
Medium
Medium Medical
Influenza 99.99%
Adenovirus 90 - 98%
17
18
6,000
8,000
Medium /High
High Medical Adenovirus 99.99%
19
20
10,000
20,000
High
URV = Ultraviolet Rating Value / µW/cm2 = UV dose required for sterilisation.
Ultra violet germicidal irradiation Rating Value (URV)Level of Sterilisation by room type
ASU 1000
ASU 6000
ASU 2000 / 7000
ASU 5000
ASU 3000 / 8000
Room Type Description Sterilisation Guide URV µW/cm2 Risk Level
Domestic Influenza 45 - 80%
10
11
12
500
1,000
1,500
Low
Commercial Influenza 81 - 95%
13
14
2,000
3,000
Low /Medium
High spec commercial / Low Medical
Influenza 99%
15
16
4,000
5,000
Medium
Medium Medical
Influenza 99.99%
Adenovirus 90 - 98%
17
18
6,000
8,000
Medium /High
High Medical Adenovirus 99.99%
19
20
10,000
20,000
High
URV = Ultraviolet Rating Value / µW/cm2 = UV dose required for sterilisation.
Ultra violet germicidal irradiation Rating Value (URV)Level of Sterilisation by room type
ASU 1000
ASU 6000
ASU 2000 / 7000
ASU 5000
ASU 3000 / 8000
NoTraditional Solution Available
NoTraditional Solution Available
Introduction
1. UV intensity2. Dwell time (exposure)3. Resistance of pathogen to UV irradiation
UVGI Systems of the UK has developed the most effective solution toremove airborne pathogens in a single pass.
This analysis explains why UVGI Systems is more effective thantraditional UV solutions.
What determines the ability to kill airborne pathogens?
UV intensity
UVGI uses ultra high power UV lamps.
The UV intensity is a result of the power of the lamp in combination with its optimum field of irradiation –The closer the pathogen passes to the lamp the greater the UV exposure level.
Traditional UVGILength (mm) 406 842Power (Watt) 40 87Yielding UV (Watt) 5.3 28
UVGI Systems lamps produce more than 5 times the irradiation of atraditional UV lamp (as used in most UV sterilisation equipment or installations).
Lamp irradiation comparison
87W / 28W UVC vs 48W / 13W UVC
Traditional lampUVGI lamp
Traditional 48 watt commercial single lamp
irradiation performance based
on manufacturers technical data.
UVGI System 87 watt single lamp
irradiation performance based
on manufacturers technical data,
UVGI lamps create a 4 times larger killzone than traditional UV lamps
Dwell time (exposure)
In order to kill a pathogen, it needs to be exposed to UV irradiation fora certain period within a consistant UV field.
Practical air volumes in HVAC installations are 0.8 m3/sec (1695 CFM).
Standard ducting at cross sectional size of 350 mm x 550 mm results in anairspeed of 5.8 m/sec.
This means that a particle travels a distance of 1200 mm in 0.15 sec.
Objective:To kill effectively airborne pathogens in a single pass, maximising velocitywithin practical HVAC applications.
End Elevation – Irradiation Pattern
( = Internal reflective surface )Side Elevation – Irradiation Pattern / Dwell Time
Isometric – Irradiation Pattern
ASU 3000 UV Irradiation Pattern – Average irradiation value 70,000 µJ/cm2@ 0.15 seconds dwell time & 5.8 m/s optimum velocity.
850 mm contact time = 0.15 secs dwell timeAir
flow
UVGI System 87 watt single lamp irradiation performance based on manufacturers technical data,
1200mm Long dwell chamber
350
x 55
0 m
m
550mm Wide Duct
350m
m D
eep
Duc
t
Power: 45 lamps x 40W = 1,800 watts total (ASU 3000 – 696 W)
UVC: 45 lamps x 5W = 225 watts UVC total (ASU 3000 – 224 W)
(Internal reflective liner assumed)
Alternative lamp configuration perpendicular to airflow using traditional lamp selection.
(40W / 5W UVC per lamp)
Air flow
850mm Dwell Time
A) Same UVC Output as ASU 3000
Air flow
350
x 55
0 m
m35
0 x
550
mm
B) Same UV irradiation as ASU 3000
a) Lowest irradiation value of 3,750 µW/cm2 against 5,600 µW/cm2 for ASU 3000. ie. less efficient use of UVC in perpendicular
configuration.
b) Non-standard lamp length required to cover full 550 mm wide duct.
c) High radiated heat output from lamps – 1.8 Kw / 1.9 ºC temp raise. (ASU 3000 – 0.6 ºC)
d) Remote ballast likely due to congested lamp configuration.
a) 55 No. lamps required to provide matching minimum irradiation value to ASU 3000 of 5,600 µW/cm2.
b) Increase in air velocity/reduction in dwell time through unit due to congested lamp grouping.
c) High radiated heat output from lamps – 2.2 Kw / 2.3 ºC temp raise. (ASU 3000 – 0.6 ºC)
d) Remote ballast likely due to congested lamp configuration.
Alternative 40 watt commercial single lamp irradiation performance based on manufacturers technical data.
Notes
850mm Dwell Time
Power: 55 lamps x 40W = 2,200 watts total (ASU 3000 – 696 W)
UVC: 55 lamps x 5W = 275 watts UVC total (ASU 3000 – 224 W)
(Internal reflective liner assumed)
Power: 20 lamps x 48W = 960 watts total (ASU 3000 – 696 W)
UVC: 20 lamps x 13W = 260 watts UVC total (ASU 3000 – 224 W)
(Internal reflective liner assumed)
Alternative lamp configuration perpendicular to airflow using traditional lamp selection.
(48W / 13W UVC per lamp)
Air flow
850mm Dwell Time
A) Same UVC Output & Irradiation as ASU 3000
350
x 55
0 m
m
a) 20 No. lamps required to provide matching minimum irradiationvalue
to ASU 3000 of 5,600 µW/cm2.
b) Non-standard lamp length required to cover full 550 mm wide duct.
c) Higher radiated heat output from lamps – 0.96 Kw / 1 ºC temp raise.
(ASU 3000 – 0.6 ºC)
d) Possible remote ballast required due to congested lamp configuration
Notes
Alternative 48 watt high output lamp irradiation performance based on manufacturers technical data.
Isometric – Irradiation Pattern
Power: 8 lamps x 90W = 720 watts total (ASU 3000 – 696 W)
UVC: 8 lamps x 27W = 216 watts UVC total (ASU 3000 – 224 W)
(Internal reflective liner assumed)
Alternative lamp configuration perpendicular to airflow using compact lamp selection.
(90W / 27W UVC per lamp)
850mm Dwell Time
Air flow
350
x 55
0 m
m35
0 x
550
mm
B) Same UV irradiation as ASU 3000
a) Lowest irradiation value of 4,500 µW/cm2 against 5,600 µW/cm2 for ASU 3000. ie. less efficient kill chamber in perpendicular
configuration.
b) Non-standard lamp length required to cover full 550 mm wide duct.
c) Higher radiated heat output from lamps – 0.72 Kw / 0.75 ºC temp raise.
(ASU 3000 – 0.6 ºC)
a) 12 No. lamps required to provide matching minimum irradiation value to ASU 3000 of 5,600 µW/cm2.
b) Higher radiated heat output from lamps – 1.08 Kw / 1.1 ºC temp raise. (ASU 3000 – 0.6 ºC)
Alternative 90 watt high output lamp irradiation performance based on manufacturers technical data.
Notes
850mm Dwell Time
Power: 12 lamps x 90W = 1,080 watts total (ASU 3000 – 696 W)
UVC: 12 lamps x 27W = 324 watts UVC total (ASU 3000 – 224 W)
Air flow
A) Same UVC Output as ASU 3000
Summary
– Perpendicular lamp positioning against parallel ASU 3000 configuration:
To match the performance of the ASU 3000 unit the following equivalent lamp numbers are required:
Option 1: 55 No UVC lamps x 40 W
Option 2: 20 No UVC lamps x 48 W
Option 3: 12 No UVC lamps x 90 W
=
Airborne UV “Kill rates”.
• HVAC airborne pathogen resistance higher than water borne by factor of 4 to 10. (Dr kowalski 2000 & Lukiersh 1946)
• Leeds University tests show a 5 x’s factor to guarantee sterilisation of 99.9%.
• e.g Tuberculosis 10,000 micro joules /cm2 for water borne UV kill rate. 50,000 micro joules /cm2 for air borne UV kill rate.
• UVGI ASU 3000 produces 70,000 micro joules /cm2.
• Excess lamp power leading to more expensive running costs.
• Higher radiated heat output – add to cooling load of central station air handler.
Additional cost for internal reflective liner to maximise 3 fold averaging factor(Reference paper: Kowalski 2000).
Higher maintenance cost due to increased lamp numbers.
Remote ballast / controls likely due to restricted space between lamps – To increase lamp centres will reduce overall irradiation level thereby reduce efficiency of steriliser.
Additional cost for safety interlocks to access doors on air handling unit to shut down UV lamps.
Summary cont– Perpendicular lamp positioning against
parallel ASU 3000 configuration:
Additional costs for interconnecting wiring between lamps & remote ballast location.
Dense grouping of low watt lamps (40W & 48W) creates higher velocity through killzone thereby reducing overall dwell time –
To increase dwell time further lamp rows necessary.
Re-design of current stab-in product necessary to include both improved lamp specification & associated ballast / controls upgrade.
Additional cost for safety interlocks to access doors on air handling unit to shut down UV lamps.
Summary cont– Perpendicular lamp positioning against
parallel ASU 3000 configuration:
UV BULB SAFETY
• High Efficiency
• High Wattage
• Quartz Shrouded
• BMS Compatibility
• *Guaranteed lamp life 13,000 hours – 1.5 years 24/7
• Full Warranty for 1 year.
Certificates of ConformityCE & EMC ISO 9001:2
Design, Manufacture & Installation
BESPOKE SOLUTIONS
Designed to serve any air given duty, any type of ventilation…..
…and suitable for both new build and existing developments
BESPOKE SOLUTIONS
ASU 2000 / ASU 3000 Multi-Assembly In-Duct Modules
Installation – quick and simple
• To suit any air duty, room size or building layout,
• Can be added to existing system or new build
Maintenance
• Annually
Availability
• 6 – 8 weeks
Installation – quick and simple
• To suit any air duty, room size or building layout,
• Can be added to existing system or new build
Maintenance• 9 Months
Mid Term
• 18 MonthsFull Service
Availability• 6 – 8 weeks
Cost Benefit Analysis
1 in 10 patients contract an infection whilst in hospital (HCAI). Costing an additional £12,000 each.
Even with only a 10% reduction…
PAYBACK in < 7 months
Increased occupancy ratesReduced patient costsPublic confidenceStaff moral
Cost Benefit Analysis
1 in 10 patients contract an infection whilst in hospital (HCAI). Costing an additional AED 66,000 each.
Even with only a 10% reduction…
PAYBACK in < 7 months
Increased occupancy ratesReduced patient costsPublic confidenceStaff moral
Cost Benefit Analysis
1 in 10 patients contract an infection whilst in hospital (HCAI). Costing an additional Qrs 72,000 each.
Even with only a 10% reduction…
PAYBACK in < 7 months
Increased occupancy ratesReduced patient costsPublic confidenceStaff moral
Cost Benefit Analysis
1 in 10 patients contract an infection whilst in hospital (HCAI). Costing an additional AUS $ 23,000 each.
Even with only a 10% reduction…
PAYBACK in < 7 months
Increased occupancy ratesReduced patient costsPublic confidenceStaff moral
Cost Benefit Analysis
1 in 10 patients contract an infection whilst in hospital (HCAI). Costing R 160,800 each.
Even with only a 10% reduction…
PAYBACK in < 7 months
Increased occupancy ratesReduced patient costsPublic confidenceStaff moral
Cost Benefit Analysis
1 in 10 patients contract an infection whilst in hospital (HCAI). Costing HK $153,600 each.
Even with only a 10% reduction…
PAYBACK in < 7 months
Increased occupancy ratesReduced patient costsPublic confidenceStaff moral
Cost Benefit Analysis
1 in 10 patients contract an infection whilst in hospital (HCAI). Costing SG $ 28,800 each.
Even with only a 10% reduction…
PAYBACK in < 7 months
Increased occupancy ratesReduced patient costsPublic confidenceStaff moral
Cost Benefit Analysis
1 in 10 patients contract an infection whilst in hospital (HCAI). Costing 7,600 Omani Rials each.
Even with only a 10% reduction…
PAYBACK in < 7 months
Increased occupancy ratesReduced patient costsPublic confidenceStaff moral
Cost Benefit Analysis
1 in 10 patients contract an infection whilst in hospital (HCAI). Costing 75,500 Saudi Riyals each.
Even with only a 10% reduction…
PAYBACK in < 7 months
Increased occupancy ratesReduced patient costsPublic confidenceStaff moral
Cost Benefit Analysis
1 in 10 patients contract an infection whilst in hospital (HCAI). Costing CNY 136,000 each.
Even with only a 10% reduction…
PAYBACK in < 7 months
Increased occupancy ratesReduced patient costsPublic confidenceStaff moral
Cost R’000 / per Patient
ICU 105 73 44 37
HC 102 49 40 34
GW 46 37 31
Patients / room 1 4 10 15
ICU* 43
ICU* No ventilation system – Ceiling-Jet onlyBased on 50m3 room with 2 patients
Cost R / Day per Patient in Year 1
ICU 288 200 120 101
HC 279 134 110 93
GW 126 101 85
Patients / room 1 4 10 15
ICU* 118
ICU* No ventilation system – Ceiling-Jet onlyBased on 50m3 room with 2 patients
Cost R ‘000 / Annum per Patient Yr 2
ICU 10.5 7.3 4.4 3.6
HC 10.2 4.7 4.0 3.3
GW 4.7 3.6 2.9
Patients / room 1 4 10 15
ICU* 4.0
ICU* No ventilation system – Ceiling-Jet only
Managed Service Contract
Cost R / Day per Patient Yr 2
ICU 29 20 12 10
HC 28 13 11 9
GW 13 10 8
Patients / room 1 4 10 15
ICU* 11
ICU* No ventilation system – Ceiling-Jet only
Managed Service Contract
Cost per Patient in Year 2 & beyond
Number of ASU’s per Room Type
Room Type ASU Patients per Room
30m3 30m3 70m3 70m3 175m3 250m3
Room # Air Ind’v Int’g Ind’v Int’g Int’g Int’g
Type Changes Type 1 1 4 4 10 15
ICU 15 I-B 1 2
I-D 0.15 0.36 1 1.3
C-J 1 1 3 3 4 5
ICU – Intensive Care Unit Ind’v – Individual room treated.Int’g – One of several rooms served by AHU
Number of ASU’s per Room Type
Room Type ASU Patients per Room
30m3 30m3 70m3 70m3 175m3 250m3
Room # Air Ind’v Int’g Ind’v Int’g Int’g Int’g
Type Changes Type 1 1 4 4 10 15
HCU 10 I-B 1 2
I-D 0.10 0.24 0.60 0.90
C-J 1 1 2 2 4 5
HCU – High Care Unit Ind’v – Individual room treated.Int’g – One of several rooms served by AHU
Number of ASU’s per Room Type
Room Type ASU Patients per Room
30m3 30m3 70m3 70m3 175m3 250m3
Room # Air Ind’v Int’g Ind’v Int’g Int’g Int’g
Type Changes Type 1 1 4 4 10 15
GW 5 I-D 0.12 0.30 0.40
C-J 2 3 5
ICU* 12 C-J 1
GW – General Ward.ICU* - No existing ventilation.
Ind’v – Individual room treated.Int’g – One of several rooms served by AHU.
Reduced Absenteeism
Average absence from work is 4% equivalent to 9 days.
1/3 is due to flu like cough’s & colds.
Assuming only a 10% reduction…
PAYBACK in < 4 months
Reduced Energy Costs
PAYBACK in ? months
To be completed
Removes Airborne Pathogens
Measurable Performance
Guaranteed Results
Removes Airborne Pathogens
Measurable Performance
Guaranteed Results
UVGI Systems delivers the mostpowerful, efficient and economical
Air Sterilisation Units in live HVAC applications
The solution….
Thank you for your attention
Any questions?