V2.44 Schleifenbauer PDU User manual
Page 1 of 50 V2.44_User manual Schleifenbauer PDU
Index
Lay out of this manual 3
What’s new 3
How to? ….taking a shortcut 4
Introduction 5
Power distribution meets intelligence 5
Interfaces 5
Accessories 5
<UC> Colored housing 6
Measurements 6
Part I - Installation of hardware 7
Safety warnings 7
Expert personnel 7
Technical installation requirements 7
Visual inspection 7
Testing 8
Cleaning 8
Contents of the package 8
Additionally needed tools 8
Mounting the PDU in cabinets 8
How to mount a PDU horizontally (19 inch)? 8
How to mount a PDU vertically (= 0U)? 9
How to install on a flat surface?...table top mount 9
How to prevent hot spots in a cabinet? …sunken installation
9
How to mount a PDU without tools? 9
How to achieve maximum mounting flexibility? ...mounting
with profile clamps 9
Cabling the PDU: ethernet, data bus and sensors 10
How to connect the PDU to LAN? 10
How to connect a data bus? 10
How to connect sensors to a PDU? 10
How to connect a NO/NC contact? 11
Part II - User manual 12
How to maintain a PDU? 12
How to be sure the status of switchable outlets will not
change during firmware upgrade or restarting of the
controller? 12
Life-Supporting Policy 12
Part IIA - Locally monitoring: device display 13
How to change settings locally via PDU display? 13
How to stop a blinking display? … local alert reset 14
Why do alerts occur? 14
How to check the load balance, the temperature / humidity
or the status of the NO/NC contact? 14
How to get back to the first display? 14
How to check an outlet status locally? 15
How to check input and/or outlet measurements? 15
How to read measurements of optional sensors and what
options are possible? 15
Option 1: load page 15
Option 2: sensor pages 16
How to read Branch Residual Current measurements? 16
Residual Current Monitoring vs Residual Current
Devices? 17
Where to measure residual current? 17
How to find unit address, tag, name or location of the PDU?
17
How to check the way the PDU is connected to the LAN? 17
How can I check in which mode and with what protocol the
PDU is running? 18
How to check the installed firmware version? 18
How to check for traceability information ? 18
Part IIB - Remote operating and monitoring: Web interface 19
Introduction 19
How to enlarge a pane in L sized screens? 20
How to select English or German language? 20
How to change and save settings in the web interface? 20
Dashboard – tab 21
System status 21
Load 23
Interfaces 23
Sensors – tab 24
Inputs – tab 25
Outlets – tab 26
System – tab 28
Identification 29
Configuration 30
Reset 30
Settings 31
Interfaces – tab 34
Part III - Administrator manual 35
Specific manuals 35
How to change SNMPv3 settings? 36
How to use the ‘connected devices’ section in the web
interface? 37
How about login profiles, usernames and passwords? 37
How to change factory passwords? 38
How to change the Ethernet link settings? 38
Network configurations 39
DHCP and default address 39
How to configure the IP settings manually? 39
How to setup IPv6? 40
IPv6 Autoconfigure (SLAAC) 40
Static IP 40
How to configure IPv6? 40
How to set up IPv6 address filtering? 41
How to send SNMP Traps with IPv6? 42
Firmware downgrade / upgrade 42
How to stop the alert signaling? ...auto reset alert 43
How to upgrade the firmware? ...using SPST 43
Schleifenbauer data bus: what is it? 44
How to prevent data losses because of cable cuts? ...ring
redundancy 45
How to make a data bus using Schleifenbauer Gateway? 46
How to connect the data bus to LAN without a Gateway?
...using a PDU! 47
PART IV - Problem Solving 48
How to perform a “Soware reset”? And why? 48
Remotely 48
Locally 48
How to perform a “Factory reset”? 48
How to reset peak current?.....and other dips or peaks 49
Recycling 50
PRODUCT SPECIFICATIONS 50
SERVICE AND SUPPORT 50
Page 2 of 50 V2.44_User manual Schleifenbauer PDU
L
This manual is split in three sections. You can focus on the section that fulfills your need when installing, operating and/or
managing the PDU.
The “How to....” section is meant to guide you directly to a solution for a problem you are faced with. It is not necessary to
read the complete manual.
Part I Installation manual Prepare PDU for use:
safety issues
mounting the PDU
cabling the PDU
Part II User manual Operator and user part:
operating/read out via the PDU-display
operating/read out via the webinterface
problem solving
Part III Administrator manual Admin part:
configure via the webinterface
set up via the webinterface
problem solving
Part IV Problem Solving In this chapter you can find the frequently asked questions
(FAQs)
W’
In the webinterface and manual the term “output” was used as in output from a channel. This was confusing so we
changed it to “outlet” were a physical outlet was meant.
IPv6 support
Firmware and mass configuration using SPST
Part IV Problem Solving
Page 3 of 50 V2.44_User manual Schleifenbauer PDU
H ? ….TAKING A SHORTCUT
The “How to....” section is meant to guide you directly to a solution for a problem you are faced with. It is not necessary to
read the complete manual.
Please read the “Safety Warnings” and “Expert Personnel” sections first !
Part I - Installation of hardware 7
How to mount a PDU horizontally (19 inch)? 8
How to mount a PDU vertically (= 0U)? 9
How to install on a flat surface?...table top mount 9
How to prevent hot spots in a cabinet? …sunken installation
9
How to mount a PDU without tools? 9
How to achieve maximum mounting flexibility? ...mounting
with profile clamps 9
How to connect the PDU to LAN? 10
How to connect a data bus? 10
How to connect sensors to a PDU? 10
How to connect a NO/NC contact? 11
Part II - User manual 12
How to maintain a PDU? 12
How to be sure the status of switchable outlets will not
change during firmware upgrade or restarting of the
controller? 12
Part IIA - Locally monitoring: device display 13
How to change settings locally via PDU display? 13
How to stop a blinking display? … local alert reset 14
How to check the load balance, the temperature / humidity
or the status of the NO/NC contact? 14
How to get back to the first display? 14
How to check an outlet status locally? 15
How to check input and/or outlet measurements? 15
How to read measurements of optional sensors and what
options are possible? 15
How to read Branch Residual Current measurements? 16
How to find unit address, tag, name or location of the PDU?
17
How to check the way the PDU is connected to the LAN? 17
How can I check in which mode and with what protocol the
PDU is running? 18
How to check the installed firmware version? 18
How to check for traceability information ? 18
Part IIB - Remote operating and monitoring: Web interface 19
How to enlarge a pane in L sized screens? 20
How to select English or German language? 20
How to change and save settings in the web interface? 20
Part III - Administrator manual 35
How to change SNMPv3 settings? 36
How to use the ‘connected devices’ section in the web
interface? 37
How about login profiles, usernames and passwords? 37
How to change factory passwords? 38
How to change the Ethernet link settings? 38
How to configure the IP settings manually? 39
How to setup IPv6? 40
How to configure IPv6? 40
How to set up IPv6 address filtering? 41
How to send SNMP Traps with IPv6? 42
How to stop the alert signaling? ...auto reset alert 43
How to upgrade the firmware? ...using SPST 43
How to prevent data losses because of cable cuts? ...ring
redundancy 45
How to make a data bus using Schleifenbauer Gateway? 46
How to connect the data bus to LAN without a Gateway?
...using a PDU! 47
PART IV - Problem Solving 48
How to perform a “Soware reset”? And why? 48
Remotely 48
Locally 48
How to perform a “Factory reset”? 48
How to reset peak current?.....and other dips or peaks 49
Page 4 of 50 V2.44_User manual Schleifenbauer PDU
I
P
The Schleifenbauer Intelligent Power Distribution Unit (PDU) is designed to distribute power for many years and without
problems. It is equipped with a Schleifenbauer data bus which makes it possible to read and manage many PDUs with a
single IP address. An ethernet port was added to the individual PDU’s so that alongside the advantages of a data bus, a
whole range of new options has become available.
Schleifenbauer PDUs bring together or merges the interests between IT and infrastructures, making it a real bridge builder.
The PDU may contain:
metered outlets
switched outlets
metered and switched outlets
passive outlets
Monitoring capabilities will be described in detail within this manual in coming sections.
I
In the Admin part of this manual you will find information about the “Interfaces” with which we mean the technology to
communicate via your LAN with the Schleifenbauer data bus. There are several possibilities:
(embedded) web interface
Modbus/TCP
SNMP (Simple Network Management Protocol)
(SP)API (Schleifenbauer Products Application Programming Interface)
A
The following accessories can be purchased from Schleifenbauer, additionally. Please check the Installation Section for
more details regarding mounting brackets.
C14/C20 plugs if C13/C19 outputs are used
Different types of attachment brackets
o 19” rack mounting brackets
o Tabletop mounting brackets
o Mounting plates for sunken installation
o Profile clamps
o Toolless Mounts
Customer Specific solutions related tools
Please check www.schleifenbauer.eu for further details regarding the accessories.
Page 5 of 50 V2.44_User manual Schleifenbauer PDU
<UC> C
< UC> groen is veranderd. Moet plaatje ook aangepast worden. Is namelijk leger groen geworden
Standard the housing color of the Schleifenbauer PDUs is black. It is also possible to anodizing the housing in 5 other
colors.
01. black
02. green
03. orange
04. blue
05. red
06. Yellow
Note: actual colors may vary!
M
Measurements of the input and the outlet level can be found below:
Measurement Unit Remark
Energy (kWh) total & sub-total
Voltage (V) with voltage dip registration
Current (A) with peak value registration
Power factor (%)
Apparent power (VA)
Real power (W)
Temperature (°C) with optional sensor
Relative humidity (%) with optional sensor
NO/NC contact 0 or 1
Page 6 of 50 V2.44_User manual Schleifenbauer PDU
P I - I
Please use the information in this chapter to inspect, install and connect the Schleifenbauer Intelligent PDU and all
optional mentioned accessories.
The PDU must be installed in a restricted access location
Socket-outlet must be installed near the equipment
Socket-outlet must be easily accessible
Installation by expert personnel only
Aer installation: default passwords / RC4 keys MUST be changed (see: Part III - Administrator manual )
S
This manual contains important safety instructions that should be followed during installation and operation of the PDU.
Please read this manual carefully since there may be serious or fatal personal injury and damage to the equipment if the
safety instructions, warnings and directions are not followed. Please save this document for future use.
E
Installation, maintenance and inspection of the Schleifenbauer Intelligent PDU must be carried out by adequately trained
persons according to NEN EN 50110-1, with full observance of the specifications of NEN EN 50110-1 and NEN 3140.
T
Before installing and putting the system into operation, check whether the characteristics of the electrical system to which
connection is to be made correspond to the product specifications.
The Schleifenbauer Intelligent PDU has been designed for connection to electrical systems that comply with IEC
60364 or in the Netherlands, NEN 1010.
The voltage, maximum permitted current and the number of phases must be correct. This information is displayed
on the front side of the PDU.
The maximum permitted power must be taken into account with regard to the maximum length and the diameter
of the connecting lead.
The values and characteristics of the in-series protective devices must match the PDU and the protective elements
included in it.
The environmental factors must correspond to the product specifications.
V
Aer opening the cardboard box and removing the packaging material, the PDU should be checked visually. The PDU
should not be put into operation if damage is detected such that safe and proper operation cannot be guaranteed. In such
cases, please contact Schleifenbauer Products BV.
Note that, in the case of PDUs that are equipped with an over voltage protection, the overvoltage protection and the
respective overcurrent protection (if applicable) must be inspected on a regular basis.
Page 7 of 50 V2.44_User manual Schleifenbauer PDU
T
Each Schleifenbauer PDU is individually tested according to the NEN 3140 standard. Test reports are available on request.
For measurement of insulation resistance, the measuring voltage used must be lower than or equal to the
voltage according to the product specification.
C
The PDU may only be cleaned by wiping off the outside with a clean dry cloth.
C
The Schleifenbauer Intelligent PDUs are shipped in a GreenCart (rolling trolley) or are packaged in a cardboard box. Where
applicable, dispose the packaging material in a responsible manner, in accordance with local regulations. All of the
materials used for packaging can be recycled. Please contact Schleifenbauer Products BV to arrange return of your empty
GreenCart. Immediately aer receipt, check whether you have received all of the goods.
The following items are delivered for each PDU:
fixing materials: these can be attached to the PDU (19’’ or table-mounting brackets), or are delivered separately if
they have been ordered separately;
the installation manual (1 per shipment);
Please note that the PDU User Manual can be found online at http://schleifenbauer.eu
A
The following tools are needed to install the PDUs:
cage-nuts with bolts and washers
suitable screwdriver.
M PDU
How to mount a PDU horizontally (19 inch)? Each 19’’ rack bracket of a PDU has 4 holes for horizontal mounting in 19” racks. The holes are
positioned so that an appropriate fixing hole is always available for a PDU with a profile height of
1.5 U. Using one or two of the 4 holes allows mounting without wasting space.
Page 8 of 50 V2.44_User manual Schleifenbauer PDU
How to mount a PDU vertically (= 0U)? I n the case of a PDU for vertical mounting, the connection lead is fed through a hole in the upper, bottom or front face.
There are 4 options for horizontal mounting:
How to install on a flat surface?...table top mount Gives the profile possibility to be mounted to a flat surface (tabletop). This
arrangement is used for:
vertical mounting to the bracing beams in the 19” cabinet
fixing to a mounting plate
mounting between the 19” uprights: the profile attaches to the front
of the uprights
The holes on the brackets are located as far as possible to the outside so
that it can also fit and tighten the bolts if a swivel gland has been placed
on the short side.
How to prevent hot spots in a cabinet? …sunken installation When power leads might block the flow of hot exhaust air, especially in
case of a 600mm wide cabinet, it is necessary to create flow space. This
can be done by using the “sunken installation brackets”. Because of the
shape of the bracket, it is possible to ‘partially sink’ the profile into the
cabinet and save space.
These mounting plates can be used for many different cabinets.
How to mount a PDU without tools? Toolless mounting is created by making attachment points on the rear of
the PDU housing. There is a wide range of cabinet brackets available, all in
which you can hang the PDU without using tools.
Toolless Mounting can be done as single PDU or double PDUs (see photo).
Mounting brackets can be custom made by Schleifenbauer.
How to achieve maximum mounting flexibility? ...mounting with profile clamps The clamps, made of spring steel, can be installed in the position of your
choice. The clamp fits around the PDU profile and is secured with a
fastening screw. Best is to use one clamp for every 50 cm of profile length.
Page 9 of 50 V2.44_User manual Schleifenbauer PDU
C PDU: ,
How to connect the PDU to LAN? 10/100 Mbps LAN Ethernet port
Connecting the PDU to a Local Area Network (LAN) provides
communication through an Ethernet network, if the PDU is connected
exclusively, or simultaneously with the data bus.
The RJ45 connector for the network cable must be plugged into the
Ethernet port:
Connect the RJ45 Ethernet cable to the Ethernet port on the PDU
and to the Ethernet connector on the LAN device; when
connected, the orange LED – marked “lnk” - will blink
How to connect a data bus? There are three black communication ports. One is marked as sensorport,
the other two as databus ports (in and out).
The le databus port is the “incoming” databus port. The right databus
port is “outgoing”. This is especially important for devices in “bridge”
mode; a MUST HAVE for devices in bridge mode. For devices in hybrid
mode it is a NICE TO HAVE.
The serial data bus in the Schleifenbauer PDU uses CAT5 or (preferable)
patch cables.
The terms IN and OUT are arguable. Data will be send and received
by both ports but to close the data bus ring, it is necessary to follow the
connection diagram. See it as the best way to daisy chain PDUs.
How to connect sensors to a PDU? The PDU has a RJ12 connector sensor port for connecting a digital
temperature sensor, a combined sensor for temperature/humidity or a dry
switch contact
Plug and play
The PDU registers which sensor is connected and automatically adapts the
menu in the display to the sensor(s) that it has detected.
Use Schleifenbauer sensors only.
Page 10 of 50 V2.44_User manual Schleifenbauer PDU
How to connect a NO/NC contact? The sensor port makes use of the RJ12 6P6C standard (= 6 position, 6 conductor). To connect a NO/NC contact on the PDU
sensor port, you have to make use of pin 1 and pin 6 ; as shown in the figure below.
Note that on a PDU only 1 NO/NC contact can be connected.
Status of the contact will be displayed. It is not possible to send a command.
Classic PDUs (= without ethernet port) do not support a NO/NC contact
Page 11 of 50 V2.44_User manual Schleifenbauer PDU
P II - U
How to maintain a PDU? Internal maintenance is not an option
A Schleifenbauer Intelligent PDU may not be opened by unauthorized persons . In the event of malfunction or faults in
the PDU, please refer to the warranty conditions. Schleifenbauer Products BV will not accept warranty claims if the PDU has
been opened or alterations have been made.
⇒ Please pay attention to the operation conditions before installation and operation of the Schleifenbauer PDU. ⇒ The Schleifenbauer PDU has to be protected according to the valid installation guidelines.
The rated value of the in-series protective device may not exceed the maximum value indicated on the product. ⇒ The Schleifenbauer PDU may not be used in: a humid environment, a seriously contaminated environment or
outdoors. ⇒ The manufacturer’s warranty on the Schleifenbauer PDU becomes invalid when the QC sticker on the side of the
profile is broken. ⇒ Before turning on the PDU for the first time, make sure that it has been allowed to acclimatize to the ambient
temperature for at least 24 hours. Major temperature fluctuations can lead to the formation of condensation in the PDU if this guideline is not followed.
⇒ Please keep in mind that maximum allowed temperature for a metal enclosure is 70 °C for installation in a normal location and 90 °C for installation in a restricted access location.
How to be sure the status of switchable outlets will not change during firmware upgrade or restarting of the controller? There are no extra safety precautions necessary. Power distribution and the control over measuring and switching is
separated. This means that while updating or restarting the (controller of the) PDUs, power distribution is not interrupted.
See the section “ Power distribution meets intelligence ”
L-S P
The Schleifenbauer PDU has been designed and built for use in data centers. The Intelligent PDU may not be applied in
surroundings where a malfunction in the PDU can have consequences for life support systems. Life support systems
include any devices designated as “critical” by the U.S. FDA. Such systems are found not only in medical environments such
as hospitals, but also on offshore platforms, in petrochemical plants, in air traffic control centers, etc.
Page 12 of 50 V2.44_User manual Schleifenbauer PDU
P IIA - L :
The intelligent PDU features a display with scroll buttons, LEDs and some ports for connecting accessories. Please keep in
mind that PDUs may differ in configuration and may not have a display.
(1) PDUs without an Ethernet port are called Classic PDUs. Firmware for Classic PDUs are in the FW1xxx - range (2) This option is called “Local alert reset” and must be activated via the interfaces
How to change settings locally via PDU display?
Changing settings locally via the PDU itself is not possible! You have to use one of the interfaces.
See the Administrator part of this manual how to changes the settings
Page 13 of 50 V2.44_User manual Schleifenbauer PDU
How to stop a blinking display? … local alert reset
Why do alerts occur?
Alerts are signal flags aer an event occurred. For example, if you measure temperature and the environmental conditions
exceeded a configured level - threshold - the PDU will generate an alert. This resolves in:
- SNMP trap
- the screen of the PDU will start blinking.
Aer the temperature has dropped, the event is cleared but the alert still exists. The display will blink until you “reset”
(=clear) the alert.
The LCD display only flashes when an alert is active.
Actions: press any button to stop blinking for a short period: blinking will stop so you can read the display
resetting the alert can be done by pressing both scroll buttons simultaneously; when cleared the
display will stop blinking (Note: this possibility must be activated on your device; see Admin part of
this manual)
Remember: you can reset the alert but by doing so, you do not resolve the cause of the alert!
How to check the load balance, the temperature / humidity or the status of the NO/NC contact?
In the picture you see 3 phases (L1, 2 and 3). The actual information is given in
Amperes but also graphically displayed. The higher the load, the more the bar is
filled.
The graphical bar is related to the maximum PDU rating (in the picture it is 32A).
There is nearly no load, only on L3 there is a small 0,1A.
DS = status of NO/NC contact [ 0 = open; 1 = closed ]
Te = temperature [degrees C]
RH = relative humidity [%]
How to get back to the first display?
No alerts (= no blinking display) => shortly press both the scroll buttons. You will see
the first screen in the display.
If there are alerts, first clear these (see: “ How to stop blinking display? … local alert
reset ” ) then shortly press both the scroll buttons to jump to the first page
Page 14 of 50 V2.44_User manual Schleifenbauer PDU
How to check an outlet status locally?
Note: every row on the display shows the
state of 9 outlets. So the first ends with
outlet 9, the second row starts with outlet
10
In the “outlets” display you can see how many outlets the PDU has and what their
individual state is.
An overview of the possible states:
0 = off
1 = on
s = scheduled to go off
S = scheduled to go on
p = power cycling
How to check input and/or outlet measurements?
Example: input page
Note: “Input x” shows the name of the
Input. This information can be configured
from the Web Interface, Inputs tab or from
the other interfaces.
Example: outlet page
With the scroll buttons you can scroll through the pages. The total amount of
pages varies and depends on the configuration of the PDU. For example: the more
outlets the higher the total amount of pages.
In the upper example you see that page 4 of 29 is displayed.
In the lower le corner of the displayed page, you see the subject of the shown
information. In this example: input measurements of L2.
So, when you search for outlets, you need to scroll through the pages until you
reach the “outlet” sections. See lower example
Displayed information can be:
I = current [A]
P = power [W]
U = voltage [V]
Pf = power factor [%] (= real power ÷ apparent power) Et = energy total [kW]
Es = subtotal energy [kW]
How to read measurements of optional sensors and what options are possible?
Option 1: load page
Sensors are displayed on the "Load" screen whenever there are less than 3 sensors in use. When adding more sensors, one
or more pages are added to the LCD screen to show the sensors readout as shown in the images below:
DS = status of NO/NC contact [ 0 = open; 1 = closed ]
Te = temperature [degrees C]
RH = relative humidity [%]
Page 15 of 50 V2.44_User manual Schleifenbauer PDU
Option 2: sensor pages
The sensor measurements are displayed in the following format:
< channel number > < sensor type > = < value >
The sensor type is indicated by a letter. The letters are abbreviations for the sensor type as follows:
Example: sensor page 1 of 2
Example: sensor page 2 of 2
Analog :
T = temperature [°C]
H = humidity [%]
R = residual current [mA]
A = AC residual current [mA]
D = DC residual current [mA]
B = Branch residual current [mA]
Digital :
I = dry switch contact
S = error status
Y = activity
For all optional sensors see www.schleifenbauer.eu
How to read Branch Residual Current measurements?
L1 + L2 + L3 + N > 0 mA …. THERE MIGHT BE FAULT IN YOUR SYSTEM !
When the PDU is equipped with a Residual Current Sensor (RCS), measurements of
the residual current are shown in the sensors pages.
( See “Example: sensor pages x of 2” in the previous chapter “Option 2: sensor pages” ).
In most parts of Europe, electrical installations must incorporate devices designed to protect people and prevent fires. Most
common among these is the residual current device, or RCD for short, which disconnects the circuit if the total for the
incoming and outgoing currents in the monitored phases and their neutral conductor does not equal 0.
There is significant potential for this scenario to occur at data centres. One example is when a switching power supply
within a computer or network equipment gives up the ghost. This in turn causes the RCD to trip and shut down operations
either entirely or for large sections. In view of this, the usual approach at data centres is to avoid RCDs and use continuous
monitoring instead. Typically, a suitable residual current monitoring device, of Type A, is used in the main distribution or
the sub-distribution system.
Standards define various types of residual current devices. The devices concerned are characterised by the types of
currents detected and their tripping behaviour under classes AC, A, F, and B.
By way of example, Type A RCDs only detect alternating currents and pulsating direct currents.
Devices sensitive to all currents, namely Type B ones, are prescribed for environments where inverters or frequency
converters are used (such as in the UPS systems found in data centres). The superimposed DC residual currents which may
occur during fault scenarios would pre-magnetize or saturate the traducers used in Type A monitoring devices, thereby
rendering measurement inaccurate or even impossible.
The residual current monitoring devices which meet the measurement criteria for Type B are based on the principle of
using special transducers for measurement purposes and recording even DC currents with real precision
Page 16 of 50 V2.44_User manual Schleifenbauer PDU
Residual Current Monitoring vs Residual Current Devices?
Many devices inside a datacenter operate a switching power supply. These power supplies usually leak a bit of energy to
the protective earth, so even without failing hardware some residual current will occur.
In order to discriminate a single dangerous fault from a sum of harmless smaller faults, one needs to set up a network of
RC-sensors and monitor permanently. RC-monitoring can take place in many forms. The Schleifenbauer RC-sensor offers
Class B metering, thus enabling our customers to set-up an RC-monitoring system that prevents dangerous situations
inside the datacenter.
Where to measure residual current?
When monitoring residual current at a single location it is not possible to determine whether the measured value is a sum
of many small currents or a single larger (dangerous) one. For that reason it contributes to the safety of the personnel
inside a datacentre when residual currents are metered at many points. It makes sense to have one or more RC-sensors
inside each PDU. The search of an RC-fault can thus be limited to a single PDU or segment of that PDU.
How to find unit address, tag, name or location of the PDU?
You will find all customer specific information about the PDU in the “Custom”
display.
Adr = address of this unit on the data bus
Tag = vanity tag
Nme = device name
Loc = location of the device
How to check the way the PDU is connected to the LAN?
Information screen about how the PDU is connected to the network:
Lnk = current Ethernet link status of the device
St = IP status:
DHCP: Acquiring/Bound, Static, Static fallback ‘-‘ when there is no link
IP = IP address of the device
NM = subnet mask of the device
GW = IP address of the Gateway or Router
MAC = MAC address of the device
Page 17 of 50 V2.44_User manual Schleifenbauer PDU
How can I check in which mode and with what protocol the PDU is running?
In the “IP Interfaces” display you can find information about the device mode in
which the PDU is working:
Mode = hybrid, data bus , bridge, colocation, …
See the chapter “ Schleifenbauer data bus: what is it ?” in this manual
for explanations of the term hybrid, bridge, ….
In the display you can read the status, which protocol and port number is shown
for:
HTTP
API
Modbus
SNMP
IPMode (IPv4, IPv6 or both)
When there is active communication with the PDU, the interface
which is running will turn white. In this example “HTTP”.
How to check the installed firmware version?
In the “About” display you can find the installed firmware version of the device. In
this example it is FW02.33.
It is important that the most recent firmware version is running on
the devices. This to ensure good working of the device and data bus.
Firmware and service tools can be found on “downloads” page of the
Schleifenbauer website
How to check for traceability information ?
In the “About” display you can find information regarding serial number, product
information and Schleifenbauer order number.
ID = unique hardware address of this device’s controller
SN = serial number (also found on the PDU housing)
Prt = product identification (also found on the PDU housing)
Ord = order number for internal Schleifenbauer uses
Ph = number of phases of this device
O = total number of outlets on this device
S = number of switchable outlets on this device.
M = number of metered and/or switched outlets on this device
Page 18 of 50 V2.44_User manual Schleifenbauer PDU
P IIB - R :
W
I
Connected devices
(ONLY FOR BRIDGE MODE)
In the le pane (part of the screen) a list of connected devices in the data bus is shown.
Also the data bus management functions can be found in this section such as:
Scan data bus
Initialise zero addresses to sequence
Reset all alerts
Device information Aer selecting a connected device, you see measurements/information and get access
to the remote operating functions, in the right pane.
Connected device -> <- Device information
There are three window sizes: S for smartphones, M for tablets and L for monitor screens.
Size of the shown screen is automatically set to the device you are working on.
Using the web interface means using capacity of the data bus and slowing down the performance of other
interfaces. Therefore it is NOT advisable to open too many web interfaces in order to prevent “hammering”
the data bus.
Classic PDUs don’t have a device type register. That is why some things do not work using SNMP: - input subtotal reset per phase, not working -> try multiple times, reset is often delayed. - outlet reboot, not working - Power (W) and Power (VA), invalid value (0.0)
Page 19 of 50 V2.44_User manual Schleifenbauer PDU
How to enlarge a pane in L sized screens?
There are two possibilities:
Using the pane separator: the thin line between < and > sign:
Using or
How to select English or German language?
The login screen makes it also possible to select English or German as language
Note: in this manual, only the English screens will be shown.
How to change and save settings in the web interface?
The web interface is protected against accidentally changing settings. Related to your
profile, you might have permission to change information: see the “Permission model”.
To open protected cells, you first have to click the “Locked” sign and the status will
change to “Editable”.
When ready, click “Editable” or click the “Save changes” icon if shown, and the sign will
turn into “Locked”.
Page 20 of 50 V2.44_User manual Schleifenbauer PDU
D –
System status
This section gives you a quick view of the actual status of the PDU: are there any alerts? And if yes, what kind of alerts?
The number following aer “drops” and “overcurrent” show the OUTLET NUMBER of the last alert. In this example the is an “outlet current drop” at outlet number 6 When enabled “Auto reset alert”, alerts will be automatically cleared aer the chosen time without active alert conditions.
Device status code The code shows the status of the device in terms of errors:
0 OK Device status is OK.
1 Alert flagged One or more alerts have been flagged. Please check the other alert fields to see the cause
of the alert. It can be one of the following sources:
temperature alert
input current alert
output current alert
input voltage alert
output current drop alert
input current drop alert
sensor change alert
2 Setting(s) initialized Some settings have been reset to default values. This may occur aer a factory reset or a
firmware upgrade.
4 Power-on reset The device booted aer a power loss. It can be one of the following reasons:
because of inserting the PDU power plug (mostly intentional. It can be
unintentional if someone removed the power plug accidentally)
because of a power outage (unintentional),
because of a defect in the internal power supply.
8 External reset The device has been reset by pressing the reset button on the unit.
16 Watchdog timer The device rebooted due to an internal error.
32 Brownout detected Device rebooted because a voltage drop has been detected. This may indicate a defect in
the internal power supply or a dip in external power supply.
64 Controller error A hardware error has been detected.
128 Slave reset A communication issue has been detected with an outlet slave module.
Page 21 of 50 V2.44_User manual Schleifenbauer PDU
temperature alert (1) Temperature alert raises for temperatures, which exceed the user’s maximum temperature
setting.
‘0’ is the indication of everything's all right.
input overcurrent
alert (1)
Input current alert raises for inputs/lines/phases, which exceed the user’s maximum current
setting for that input.
In case multiple inputs are in alert state, only the alert which appeared first is shown..
0 = OK , “3” means that there was an input/line/phase current alert at phase 3
outlet overcurrent
alert (1)
Outlet OVER CURRENT alert raises for outlet number ..n.. .
In case multiple outlets are in alert state, the highest outlet will be indicate
0 = OK , “22” means that there was a current drop at outlet “22”
input voltage drop
alert (1)
This alert raises in case the voltage on an input/line/phase drops below normal operating range,
even if the drop is very short.
In case multiple inputs are in alert state, only the alert which appeared first is shown.
0 = OK , “3” means that there was an input/line/phase voltage alert at phase 3
outlet current drop
alert (1)
Outlet drop alert raises for outlet number ..n.. .
In case multiple outlets are in alert state, the highest outlet will be indicated.
0 = OK , “22” means that there was a current drop at outlet “22”
input current drop
alert (1)
Input current drop alert raises due to a sudden current drop for an input. In case multiple inputs
are in alert state, the highest input will be indicated.
‘0’ is the indication of everything's all right.
sensor change
alert (1)
Sensor change alert raises when a sensor type has been changed. If multiple sensor types have
been changed the lowest sensor channel will be shown.
‘0’ is the indication of everything's all right.
outlet voltage drop
alert (1)
Outlet voltage drop alert raises for outlet number ..n.. .
In case multiple outlets are in alert state, the highest outlet will be indicated.
The threshold is hard coded on 118V.
0 = OK , “22” means that there was a current drop at outlet “22” (1) For the alert setting please check System Tab > Settings section > Sensor Change Alert.
Page 22 of 50 V2.44_User manual Schleifenbauer PDU
Load
Shows the name, load and alert threshold of each input.
The way loads are visualised depend on the configuration of your PDU
Default, the name has 8 characters. With the “extended name”-option enabled, you can make use
of 18 characters
See also chapter: System tab > Settings
In a graphical bar the load is presented.
As long as the load is under the “alert threshold” the bar will be green
The alert threshold is visualised as a yellow, horizontal line.
The
See also chapter: System tab > Settings
However, when the load passes the alert threshold, the bar will turn red. In the meantime 2 things
will happen:
1) an alert occurs in the “System status” block
See also chapter: Web Interface > Dashboard tab > System status
2) at the same time the display of the PDU will blink
See also chapter: Operating the PDU > Alerts: blinking display
Interfaces
Data shown is read-only and gives an overview of the statuses of the interfaces.
This block is only shown for devices in BRIDGE mode
Page 23 of 50 V2.44_User manual Schleifenbauer PDU
S –
name Default, the name has 8 characters. With the “extended name”-option enabled, you can make use
of 18 characters
See also chapter: System tab > Settings
type Shows the type of sensor. This is auto detect
See also chapter: Operating the PDU > description of display screens > Sensor page(s)
value Shows the actual sensor value
Page 24 of 50 V2.44_User manual Schleifenbauer PDU
I –
# This indicates the number of input phases. In this example, you see 3 lines because a 3 phase PDU
is shown. A single phase PDU will show only 1 line
name Default, the name has 8 characters. With the “extended name”-option enabled, you can make use
of 18 characters. If you are allowed to change the names, depends on your role according to the
“permission model”
See also chapter: “web interface > permission model” & “System tab > Settings”
kWh total Total amount of energy per line: value cannot be reset during the lifetime of the devices!
subtotal / reset Total amount of energy per line since the last reset. Resetting aer “unlocking” and clicking the
“reset” button
power [VA] Apparent power per line
power [W] Real power per line
PF Power factor per line [%] = real power [W] / apparent power [VA]
current Actual current [A] per line
peak current Highest current per line since the last “reset peaks and dips”
See also chapter: System tab > Reset
voltage Actual voltage [V] per line
min voltage Lowest measured voltage (dip) [V since the last “reset peaks and dips”
See also chapter: System tab > Reset
alert current Field in which the maximum current [A] is configured for this line, what the actual current is
allowed to reach. Crossing this limit will lead to an alert
See also chapter: System tab > Reset & Settings
Page 25 of 50 V2.44_User manual Schleifenbauer PDU
O –
# This tab gives an overview of the configuration of the PDU.
In this example, there are 18 outlets in total of which 18 are both switchable and metered.
The example shows only the first 5 lines, in reality the screen shows 18 lines because 18 outlets!
name Default, the name has 8 characters. With the “extended name”-option enabled, you can make use
of 18 characters. If you are allowed to change the names, depends on your role according to the
“permission model”
See also chapter: “web interface > permission model” & “System tab > Settings”
kWh total Total amount of energy per line: value cannot be reset during the lifetime of the devices!
subtotal / reset Total amount of energy per line since the last reset. Resetting aer “unlocking” and clicking the
“reset” button
power [VA] Apparent power per outlet
Note: not available on Classic PDU (= without Ethernet port) or DPM27
power [W] Real power per outlet
Note: not available on Classic PDU (= without Ethernet port) or DPM27
PF Power factor per outlet [%] = real power [W] / apparent power [VA]
current Actual current [A] per line
peak current Highest current per line since the last “reset peaks and dips”
See also chapter: System tab > Reset
voltage Actual voltage [V] per outlet
alert current Field in which the maximum current [A] is configured for this outlet, what the actual current is
allowed to reach. Crossing this limit will lead to an alert
See also chapter: System tab > Reset & Settings
delay This functionality makes it possible to switch outlets in a row during startup (if configured). So,
one-by-one and not all at once. You can configure the time of switching in seconds.
Page 26 of 50 V2.44_User manual Schleifenbauer PDU
power cycle time Configurable downtime when an outlet is power cycled. Which means that aer the command to
power cycle (shut outlet of and start again) is given, the outlet will be switched on again aer the
configured downtime has passed.
See “Unlock” at the end of this table
state Shows the configured OR actual outlet statet. There are several possibilities:
See “Unlock” at the end of this table
Devices built up and including January 2018: the displayed outlet state is the user configured state. For devices built from February 2018 on: the displayed outlet state is the ACTUAL state because of the implementation of 6-channel outlet prints. These prints send information to the controller print about the actual state of the outlets. Depending the “power up/down outlet behaviour” you can see changes in the overview.
unlock Aer the “unlock” sign is clicked, a confirmation is needed to change the state of the outlet.
There are 2 possibilities:
Switch off
Power cycle ( See “power cycle time” in this table)
Aer you have made a choice, the state of the outlet is changing ( See “state” in this table)
While the given command is running, a status bar shows the progression of the action.
Page 27 of 50 V2.44_User manual Schleifenbauer PDU
S –
On the next pages the different sections of this tab are described.
Page 28 of 50 V2.44_User manual Schleifenbauer PDU
Identification Identification and allocation information of the device
firmware version Actual firmware version on the device
Please check the website for the latest version: www.schleifenbauer.eu
SPDM version The actual version of the Schleifenbauer Products Data Model
sales order
number
Reference of initial Schleifenbauer sales order number
product ID Product identification tag of the device
serial number Unique, sequential production number
hardware address Unique MAC-address of the device controller
unit address Address of the device on the data bus. Number can be between 1 and 65535.
(When using Modbus, number can be between 1 and 247)
device name Configurable device name, which has a maximum of 16 characters
Note: this field is not connected with the “extended name support” and always max 16 characters
device location Configurable location name, which has a maximum of 16 characters
Note: this field is not connected with the “extended name support” and always max 16 characters
vanity tag Configurable vanity tag, which has maximal 20 characters
Note: this field is not connected with the “extended name support” and always max 20 characters
Page 29 of 50 V2.44_User manual Schleifenbauer PDU
Configuration
Configuration information of the device
number of phases Number of input phases/lines
number of outlets Total number of outlets
number of
switchable outlets
Total number of switchable outlets
number of
metered outlets
Total number of metered outlets
maximum load [A]
Maximum current of the loads
number of sensors Shows the total number of sensors detected
Note: this is autoconfig so aer sensors are added or taken out, the system recognizes this and change the information
Reset Restart controller and resetting alerts (manually / automatically)
restart CPU This is a reboot of the controller of the PDU. Aer restarting all alerts and peak registrations will
be erased. Be assured: power distribution will NOT BE INTERRUPTED during this restart !
reset alerts Clears all the alerts on the device.
Of course resetting alerts does not mean that the reason of the alert is taken away. So, an alert
can occur directly aer resetting.
Reset peaks and
dips
Clears all the registered peaks and dips on the device.
Local alert reset
allowed
Provides possibility to clear alerts while standing next to the PDU by pressing both
“Page up” and “Page down” buttons at the same time
Page 30 of 50 V2.44_User manual Schleifenbauer PDU
Auto reset alert (s) In this drop-down menu, you can select how much time it will take to
automatically clear alerts aer the alert condition disappeared.
Be sure that alerts are registered by your management soware.
Settings
For devices built from February 2018 and equipped with 6-channel outlet prints have a new feature
display backlight
timeout
Setting for switching off display backlight aer certain set time:
display orientation Setting for the orientation of the LCD display. It can be set as:
peak duration
[msec]
Configurable time in milliseconds that a current overload can occur before an alert is given.
Note: do not make this time too short because otherwise alerts keep on raising!
current drop
detection
In this drop-down menu, you can select what kind of current drops
must be detected.
Please note that current drop detection is working in the following
way: When the actual current of a channel (can be input or metered
outlet) is greater than 0.5A (500mA) and drops with more than 50% of its value, then an input/
outlet current drop alert is raised.
For example:
Actual current = 0.4A, drops to 0A -> no alert
Actual current = 1A, drops to 0.6A -> no alert
Actual current = 1A, drops to 0.4A -> alert is raised
Page 31 of 50 V2.44_User manual Schleifenbauer PDU
system-wide outlet
delay [msec]
Setting for delay time between 2 switch actions in milliseconds. Default value is 100 milliseconds
and values below 100 milliseconds are not accepted.
power up/down
outlet behaviour
Auto shut down is standard/default on Schleifenbauer PDUs. This means that when power
distribution to the PDU fails, all outlets will shutdown; which of course leads to shut down of
connected servers and other equipment .
The reason for the auto shut down is is to prevent peak currents damaging equipment when
power loss is solved and power distribution restarts. As a customer you are able to set the power
up mode of the outlets.
Outlet behaviour can be set as:
no switching on power up
- at power up, all outlets are kept in the off state
use system-wide outlet delay
- at power up, all the outlets are set to their last known state by respecting the fixed system-wide outlet delay
use individual outlet delay
- at power up, all the outlets are set to their last known state, but delayed by the individual outlet delay
For PDU’s built from February 2018 and equipped with 6-channel outlet prints, there is an
extra option:
no switching on power down
- in this state outlets are not turned of on power loss. If you can not select this option, you are using a 9-channel outlet pcb.
outlet unlock
override
Setting for overriding the outlet unlock registers. When this setting is enabled outlets can be
switched or power cycled without unlocking them first.
Note that this makes it easier for the user to switch outlets using SNMP, Modbus and API, but also makes it easier to switch the wrong outlet. Please keep in mind that this setting isn’t valid for the web interface. To be able to make a change through web interface, the relevant part has to be unlocked first.
Page 32 of 50 V2.44_User manual Schleifenbauer PDU
maximum
temperature [ o C]
Shows the value of the upper limit that the maximum temperature is allowed to reach in degrees
Celsius. An alert will be raised if the temperature of any connected temperature sensor exceeds
the set value.
It can be disabled by setting it to ‘0’.
sensor change
alert
Informs about the change in sensors such as new sensor, disconnected sensor or broken sensor
for this device.
extended name
support
A feature allowing the use of longer names for inputs, outlets and sensors when viewing the web
interface or using SNMP when it is enabled. This setting also affects the names shown on the LCD
display.
limited to 18 characters
setting is valid for SNMP, the web interface and the LCD display
for API and Modbus, both the original and extended name registers can be used
simultaneous and independent of each other.
when the device is configured in bridge mode, all connected devices should support the
extended name feature to work properly.
When using both Classic and ethernet PDUs in a databus, the extended name suport may lead to conflicting situations.
Page 33 of 50 V2.44_User manual Schleifenbauer PDU
I –
The sections of this screen are described in specific manuals. These can be downloaded from our website:
www.schleifenbauer.eu
Page 34 of 50 V2.44_User manual Schleifenbauer PDU
P III - A
S
The specific manuals can be found on our download page: http://documentation.schleifenbauer.eu/Documentation/
Subject Purpose
WebAPI documentation Describe the WebAPI custom authentication and resource requests
SPDM 2.xx
(Schleifenbauer Products Data Model)
List of all registers and their settings. These must be used when the API’s
SPBUS_protocol Provide a concrete and clear description for developers who intend to
integrate the SPBUS (Schleifenbauer Products BUS) protocol into their
(custom) soware solutions.
SPAPI
(Schleifenbauer Products application
programming interface)
Describe a high-level API for SPBUS devices such that (1) users using the
API understand how to use it and (2) developers of any API implementation
understand the API’s intentions, structure, and design such that they can
easily implement, maintain, and extend it where necessary.
APIs tutorial
“Getting started with SPBUS” Guide a developer to one of the SPBUS device interfaces most fit for their
purpose.
Modbus Address scheme, testfile and example can be found on our website
Page 35 of 50 V2.44_User manual Schleifenbauer PDU
How to change SNMPv3 settings?
SNMPv3 user settings can be configured in the web interface: tab
“Interfaces”, block “User management”.
To change the settings of a specific user click the ‘edit’ button. Then check
the ‘change snmpv3 settings’ checkbox to edit the snmpv3 settings. When
finished, click the ‘save user’ button.
Classic PDU, so without ethernet connector and running on firmware 1.xx , don’t have a device type register. That is why some things do not work using SNMP Not working using SNMP on a Classic PDU - input subtotal reset per phase - outlet reboot - Power (W) and Power (VA), invalid value (0.0)
Page 36 of 50 V2.44_User manual Schleifenbauer PDU
How to use the ‘connected devices’ section in the web interface? When the PDU is configured in Bridge mode the web interface will show a list of all devices connected to the bridge-PDU on
the le pane (or below the blue header when using narrower displays).
Initially this list is empty but will be filled while the web interface is loading data from the bridge-PDU. A selected device is
marked - yellow line - in the device list (le pane). You can switch to another device just by clicking the row in the device
list. Information and settings about the currently selected device can be seen on the right pane.
How about login profiles, usernames and passwords? The PDU user authentication model provides 5 different accounts which can be used to access the web interface and
SNMPv3.
In the web interface the user accounts are in decreasing order of access rights: super, admin, power, user and viewer.It
should be noted that super is only intended for use by Schleifenbauer personnel. The access rights of the different user
accounts, together with data bus and unauthenticated ethernet, are shown in the following table.
The default password for each profile initially equals the username of the profile. For example the default password for the
‘admin’ user profile is “admin”.
Each user can change all lesser user passwords, in addition to their own password.
Please fill the ‘User Name’ and ‘Password’ fields accordingly and then click login or press enter.
Page 37 of 50 V2.44_User manual Schleifenbauer PDU
How to change factory passwords?
All user profile passwords MUST be changed at the first connection by the administrator !
In tab “Interfaces”, block “User management” passwords can be changed.
There are five login profiles:
1. Viewer = viewing only
2. User = Viewer + resetting alerts and switching outlets
3. Power = User + resetting subtotals
4. Admin = all administrator rights
And the ”factory profile”: 5. Super.
Please keep in mind that ‘super’ user profile should never be used since it allows
changing the configuration of PDU.
How to change the Ethernet link settings? By default the “ethernet link speed and duplex mode”-setting is set to autonegotiation . With this setting the link speed
and duplex mode are automatically configured with the link partner (e.g. Network Switch).
You can also configure the link speed and duplex mode to a fixed setting. You can choose from the following options:
Autonegotiation
10 Mbps Full Duplex
10 Mbps Half Duplex
100 Mbps Full Duplex
100 Mbps Half Duplex
When changing this setting you must also configure the link partner correctly! Otherwise you will not be able
to connect to the PDU remotely.
If this setting is changed in the wrong way and you are not able to connect, change the setting of the link
partner to be able to access the PDU again. If this doesn’t work you can try a factory reset .
Page 38 of 50 V2.44_User manual Schleifenbauer PDU
N
DHCP and default address
In general, the Dynamic Host Configuration Protocol (DHCP) protocol can dynamically configure the:
IP address
subnet mask
gateway address
Domain Name System (DNS) servers
By default, the PDU is configured to get the IP address from DHCP automatically. If the PDU does not receive an IP address
within a set time, it will proceed using the default address:
192.168.1.220
(subnet mask: 255.255.255.0)
How to configure the IP settings manually? The IP settings can be manually configured by using the web interface:
Actions: go to the <web interface> , tab < Interface >, block < Network Configuration >
disable DHCP
Fill in the “Static IP Settings”
Restart the CPU: go to tab < System >, block “Reset”
When using ‘DHCP fallback to static IP’, it is recommended to enter a unique IP address for each PDU. This
approach prevents all of the PDUs from being assigned the same IP address in the event of a faulty DHCP
server.
Page 39 of 50 V2.44_User manual Schleifenbauer PDU
How to setup IPv6? Since firmware version FW2.44, IPv6 support has been introduced in the Schleifenbauer PDU. This feature is disabled by
default.
An IPv6 address consists of 8 blocks of 4 hexadecimal digits separated by columns ( : ). Consecutive blocks of zeroes can 1 2
be substituted with a double column ( :: ) and leading zeroes can be omitted. By default the static IP is "::" which translates
to 0000:0000:0000:0000:0000:0000:0000:0000.
IPv6 Autoconfigure (SLAAC)
By default the PDU will try to obtain its IPv6 address through a process called "stateless local address auto configuration"
(SLAAC). This setting can be turned off in the web interface by setting "IPV6 Autoconfigure" to "disabled".
The PDU will try to find a router by sending router solicitation packets via ICMP6 using its link-local address. This means
that a IPv6-enabled router must be available on the network and it must send ICMP6 router advertisement packets in order
for the PDU to obtain a valid IP6 address.
When "IPV6 fallback to static IP" is set to enabled in the web interface, the PDU will use it's configured static addresses as
fallback when a router cannot be found.
Static IP
To use static IPv6 addresses the PDU must either have it's "IPV6 Autoconfigure" setting disabled or "IPV6 fallback to static
IP" enabled in the web interface.
These settings can be found under " interfaces → network configuration".
To change the static IPv6 addresses, fill in a valid IPv6 into fields "IP6 address 1" and/or "IP6 address 2" as shown in Image
1.
How to configure IPv6? The IPv6 settings can be found in the PDUs web interface under " interfaces → network configuration". The PDU will
always generate a Link-local address which starts with "FE80::". This address is auto-generated and loses its scope at the
first encountered network node. 3
The IP6 addresses can be found on the web interface or on the "IPv6 Link" page on the PDU's built-in LCD screen as shown
in Image 2.
To enable it the user must login to the PDU using the ipv4 address presented on the display. Aer logging in onto the web
page of the PDU, select the tab " interfaces". Under network configuration there's a drop-down box called "IP Protocol 4
select" as seen in Image 1. By default this will be set to "IPv4 only". To enable IPv6 set this to either "IPv6 only" or
"IPv4/IPv6 dual-stack".
Note that selecting "IPv4 only" or "IPv6 only" requires one of the filtering ranges to be all zero (allow all addresses). This is
to prevent users from locking themselves out. Naturally filtering can be configured aerwards when the user has
connected to the bridged and/or hybrid PDU using the protocol previously specified.
1 https://en.wikipedia.org/wiki/IPv6_address 2 https://en.wikipedia.org/wiki/Hexadecimal 3 https://en.wikipedia.org/wiki/Linklocal_address#IPv6 4 See part IIB Remote operating and monitoring
Page 40 of 50 V2.44_User manual Schleifenbauer PDU
Image 1: ipv6 settings in web interface
Enabling IPv6 will also add an additional page on the PDUs display: see image 2. The current IP Mode is also displayed on
the display; screen "IP INTERFACES".
I mage 2: ipv6 page on PDU display
How to set up IPv6 address filtering? As with IPv4, IPv6 address filtering settings can be found under
" interfaces → network Access control" from within the web interface.
The web interface shown in image 3 will allow you to specify 3 IP ranges which grant access, anything outside of these IP
ranges will be blocked. If you wish to configure only a single range, you should fill in this range 3 times.
All "allowed IP6 range" fields must be filled, in order for the filter(s) to have effect. Setting any address with prefix "0" will allow any address to access the PDU web interface, SNMP, modbus etc. Setting the
address to "::" (all zero's) and the prefix to a number between 0 and 128, will limit the allowed IP scope to the network the
PDU is connected to. Filtering will then
Page 41 of 50 V2.44_User manual Schleifenbauer PDU
Example:
Setting a filter of A76F::D222:12FF:FEB0:F48/64 will allow any address starting with A76F:0000:0000:0000: (A76F::) but other
addresses such as A76A::32D4:731B:F17B:6 will be blocked. for more detailed explanation see the wikipedia page on IPv6
subnetting. 5
Image 3: IPv6 filtering ranges
Image 4: PDUs current IPv6 addresses.
How to send SNMP Traps with IPv6? The PDU allows you to set 2 SNMP trap destinations. traps are fired when an alert has been generated within the PDU.
These destinations can be found under " interfaces → SNMP" in the PDU web interface. The "trap destination address"
fields can be set to any destination including an IPv4 address (when IPv4 is enabled) and an IPv6 address as seen in Image
5.
Image 5: IPv6 traps
F /
The development of the PDU firmware is an ongoing process. With every new release not only issues are fixed, but new
features appear and the data bus will be more stable and speed will be increased. Not installing the newest firmware
means that you do not make use of the latest technology.
Because of the data bus ring, upgrading of all attached devices can be done remotely! During the upgrade process the
power distribution will not be interrupted. Our firmware, firmware tools and manual are cost free: both download and in
use.
When a Schleifenbauer Gateway is in the data bus you need to upgrade the Gateway firmware first. This firmware can be
found on the documentation page of the Schleifenbauer website.
The latest firmware, manual and updater tool can be found on the downloads page of our website www.schleifenbauer.eu .
5 https://en.wikipedia.org/wiki/IPv6_subnetting_reference
Page 42 of 50 V2.44_User manual Schleifenbauer PDU
How to stop the alert signaling? ...auto reset alert From firmware 2.40 on it will be possible to select a duration time aer which the alert will be cleared aer the cause of the
alert is not present anymore. It will be no longer necessary to clear the alert on the PDU or via an interface aer the event
which led to an alert is gone
But remember: an alert does not occur without a reason. So it is important that the alerts are recorded/logged in an
management system.
How to upgrade the firmware? ...using SPST
SPST stands for "Schleifenbauer Products Service Tool”. This is a program which aims to aid customers in analyzing and
maintaining their network of Schleifenbauer PDUs and DPM-energy meters. It does so by offering the following features:
You are able to “quick scan” the status of your databusses
You can upgrade/ downgrade firmware in a very easy and simple way
You can remotely mass configure your databus devices
You will decrease problem solving lead time
You can download SPST from www.schleifenbauer.eu where you also can find the SPST-manual. Please read the manual
before you start using SPST and you will find out that this tool will make firmware updating and mass configuration a lot
easier.
Page 43 of 50 V2.44_User manual Schleifenbauer PDU
S : ?
The intelligence of Schleifenbauer PDUs (and DPM
energy meters) makes it possible to read and manage
devices remotely over IP. You can for example enter the
data bus via the web interface, MODBUS and SNMP.
There are all kinds of possibilities using the data bus:
whatever configuration you want to build, with the data
bus it is possible.
Data bus and power distribution are two separate
functions of the Schleifenbauer PDU. This means that all
actions done via the data bus do NOT interfere the
distribution of power to the IT equipment in the racks.
Advantages of the data bus:
easy to build: just pick a PDU and connect it to
your LAN, daisy chain the rest of the PDUs and
you have made a data bus
remote updating of the firmware
Explanation of the figure:
the PDU/DPM-energy meter that is connected
to the LAN must be in “ BRIDGE ” mode; this is
the MASTER device
all “daisy chained” devices must be in “ HYBRID ”
mode; these are the followers: the BRIDGED
devices
Page 44 of 50 V2.44_User manual Schleifenbauer PDU
How to prevent data losses because of cable cuts? ...ring redundancy Normally the advantage of an IP solution per PDU is that a cable cut will not affect the other PDUs on the bus. This could happen in a normal daisy chained serial bus topology.
However, Schleifenbauer has made their bus redundant so that a single cable cut will not affect the readout or control of the PDUs; it will try and get access via the alternative route on the ring. A cable cut is detected by our firmware and an error message will be submitted to the database. The disadvantage of a serial bus topology is therefore covered in the Schleifenbauer system.
See Part I “How to connect a data bus” on the PDU
Page 45 of 50 V2.44_User manual Schleifenbauer PDU
How to make a data bus using Schleifenbauer Gateway?
In the figure above you see a small data bus-ring with
four PDUs connected to the Schleifenbauer Gateway.
The Classic PDU has NO ethernet port, so a
(Schleifenbauer) Gateway is needed in order to get PDUs
connected to your LAN.
The sequence of devices does not affect the performance
of the Gateway or the data bus. Though the more devices
you place in the data bus, the slower data transmission
will be.
It is advised to close your data bus-ring. To do so, you
connect the last device in the data bus also to the
Gateway (blue lines in the figure). In a closed data bus
ring the Gateway can reach all connected devices via IN
and OUT data bus-ports (clockwise and anti-clockwise).
Advantage : with one IP-address you can collect data
from a number of connected Schleifenbauer-devices (not
only PDUs but also the Schleifenbauer DPM-range
(=energy meters)
Disadvantage : Gateway uses 1U
Problem solving: when the Gateway fails, you can
change to the next configuration: using the “bridge”
mode
Data bus communication is 0,2 seconds per
query (e.g. input measures block). Therefore
we advice to make rings with a maximum of 50
devices which means that querying each
device once will last appr. 10 seconds
Page 46 of 50 V2.44_User manual Schleifenbauer PDU
How to connect the data bus to LAN without a Gateway? ...using a PDU!
In the figure you see a small data bus-ring with only four
devices connected to a LAN: a Classic PDU and PDU with
ethernet port. The device connected to the LAN must
have an ethernet port and be in "BRIDGE" mode. All
other devices should be in "Hybrid" mode. The BRIDGED
device takes over the function of the Schleifenbauer
Gateway.
You can connect numerous of Schleifenbauer devices to
the device which is in BRIDGE mode: PDUs and DPM3's (=
3 channel energy meter) as well as Classic PDUs and
DPM27 (= 27 channel energy meter). The sequence of
devices does not affect the performance of the data
bus-ring. But, the more devices you place in the data
bus-ring, the slower data transmission will be. The
scheme shows that you can use different kind of
Schleifenbauer devices in a ring which makes the system
easily scalable to your needs. It is advised to close your
data bus ring. So it is best to connect the last device in
the data bus to the device which is in BRIDGE-mode. In a
closed data bus ring you can reach all connected devices
via IN and OUT data bus ports (clockwise and
anti-clockwise).
Advantages : (1) when only using devices with ethernet
port: only the device in BRIDGE mode uses one
IP-address. (2) you can select any device connected to
your LAN as long as you place it in BRIDGE mode, (3)
investment in a Schleifenbauer Gateway is not
necessary, (4) the system is easily scalable
Disadvantage : MySQL can not be used
Data bus communication is 0,2 seconds per
query (e.g. input measures block). Therefore
we advice to make rings with a maximum of 50
devices which means that querying each
device once will last appr. 10 seconds
Page 47 of 50 V2.44_User manual Schleifenbauer PDU
PART IV - P S
How to perform a “Soware reset”? And why? When Interface-settings are changed the CPU has to be started. In the webinterface a pop up will appear when needed:
Remotely
Soware reset can be done via the web interface. It is important to understand that a soware reset has no impact on
power distribution of the PDU. So a reset can be performed at any time without having to interrupt the power supply and
without losing the settings in the PDU.
Locally
The soware can be reset using a paperclip or some other kind of thin and rigid rod to press the reset button. This button is
mounted behind the hole labelled as ‘rst’ on the PDU which is next to the Ethernet connection port.
How to perform a “Factory reset”? If the PDU can no longer be accessed via the LAN, for example, because settings have been changed, restoring IP access
may be needed. The following procedure causes the PDU to adopt various default values, which allows it to be detected on
the network again without losing any of the other settings in the PDU. However, the power supply must be interrupted in
order to perform this restore procedure! The procedure is described in five steps:
1. Interrupt the power supply to the PDU.
2. Restore the power supply.
3. Wait for one second and aerwards press the reset button using a paper clip.
4. Wait for a further second and press the reset button again.
5. Wait for a further second and press the reset button again.
The PDU has now adopted the default values for the IP settings. The access control fields and the web server settings have
also been returned to the standard values.
Please note that because the power is removed, outlets will also be out of power. Hence, during this process there won’t be
any measuring.
Please keep in mind that kWh totals will NOT be reset during this process.
Page 48 of 50 V2.44_User manual Schleifenbauer PDU
How to reset peak current?.....and other dips or peaks Example: you have set the “overcurrent alert at” on 5.00A in the < input > tab. At a certain moment you see an alert in the
webinterface dashboard. You check the Inputs-tab and see a peak current of 8.30A:
You can clear the alert as you already know locally or by the reset button in the <Reset> block in the System-tab but the
peak current will not be cleared. You have to do this by clicking the <reset peaks and dips> button in the <Reset> block of
the System-tab:
Page 49 of 50 V2.44_User manual Schleifenbauer PDU
R
Schleifenbauer Products aims to be a socially responsible corporation. Therefore, it makes great effort to minimise the
impact of our products to our planet during production as well as during operation. Packaging consists of recyclable
materials and Schleifenbauer asks you to save them for later use or dispose them with applicable regulations.
PRODUCT SPECIFICATIONS
OPERATING
Temperature 0° to 60° Celsius
Height -30 to +2000 m
Relative humidity 10 to 90% NC
Level of pollution 2
Environment Indoors IP20
Installation category II
Protective rating II
Conditions of use Continuous
Voltage: single-phase 100-230 VAC; three-phase 230/400 VAC
Frequency: 50/60 Hz
Permitted load: see product information on your PDU
Accuracy: EN 50470-1/3 class B
EN 62053-21: class 1, ± 1%
Wire colour code: L1 = BROWN
L2 = BLACK
L3 = GREY
N (neutral) = BLUE
PE = YELLOW/GREEN
SERVICE AND SUPPORT
In case you have any questions regarding our products, please contact us from the following addresses:
T: +31 73 5230256
F: +31 73 5212383
E-mail: [email protected]
Website: http://schleifenbauer.eu/en
When an email is sent, a case is created automatically with a unique case number. The request will be investigated in detail
and proper actions will be taken. Correspondence about the case will be done with the unique number as reference.
© Schleifenbauer is a registered trademark.
This publication is protected by copyright.
No part of it may be reproduced or transmitted in any form,
without prior consent in writing from Schleifenbauer Products BV.
Page 50 of 50 V2.44_User manual Schleifenbauer PDU