+ All Categories
Home > Documents > V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is...

V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is...

Date post: 11-Oct-2020
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
25
Section 5.3 I Static Var Compensators: SVC and STATCOM 1.83 the fixed reference I/n* in order to obtain the desired effective (variable) reference signal Yfi", that closed-loop controls the terminal voltage V7.. In the following sections, some practical auxiliary control loops and the corresponding characteristics of the static compensator are described. 5.3.1 The Regulation Slope In many applications, the static compensator is not used as a perfect terminal voltage regulator, but rather the terminal voltage is allowed to vary in proportion with the compensating current. There are several reasons for this: The linear operating range of a compensator with given maximum capacitive and inductive ratings can be extended if a regulation "droop" is allowed. Regulation "droop" means that the terminal voltage is allowed to be smaller than the nominal no load value at full capacitive compensation and, conversely, it is allowed to be higher than the nominal value at full inductive compensation. Perfect regulation (zero droop or slope) could result in poorly defined op- erating point, and a tendency of oscillation, if the system impedance exhibited a "flat" region (low impedance) in the operating frequency range of interest. A regulation "droop" or slope tends to enforce automatic load sharing be- tween static compensators as well as other voltage regulating devices normally employed to control transmission voltage. The desired terminal voltage versus output current characteristic of the compensator can be established by a minor control loop using the previously defined auxiliary input as shown schematically in Figure 5.M. A signal proportional to the amplitude of the compensating current r1p with an ordered polarity (capacitive current is negative and L v7+Avrft) Av V Power system Figure 5.44 Implementation of the 7-l slope by a minor control loop changing the reference voltage in proportion to the line current. 1. 2. 3. Voltage measuring and processing circuits Z(ot,t) Perfect Regulator: VT=Vier:AVr=0 hlt=het-Kte Static var generator Current measuring and processing circuits G
Transcript
Page 1: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.3 I Static Var Compensators: SVC and STATCOM 1.83

the fixed reference I/n* in order to obtain the desired effective (variable) referencesignal Yfi", that closed-loop controls the terminal voltage V7.. In the following sections,some practical auxiliary control loops and the corresponding characteristics of thestatic compensator are described.

5.3.1 The Regulation Slope

In many applications, the static compensator is not used as a perfect terminalvoltage regulator, but rather the terminal voltage is allowed to vary in proportionwith the compensating current. There are several reasons for this:

The linear operating range of a compensator with given maximum capacitiveand inductive ratings can be extended if a regulation "droop" is allowed.Regulation "droop" means that the terminal voltage is allowed to be smallerthan the nominal no load value at full capacitive compensation and, conversely,it is allowed to be higher than the nominal value at full inductive compensation.Perfect regulation (zero droop or slope) could result in poorly defined op-erating point, and a tendency of oscillation, if the system impedance exhibiteda "flat" region (low impedance) in the operating frequency range of interest.

A regulation "droop" or slope tends to enforce automatic load sharing be-tween static compensators as well as other voltage regulating devices normallyemployed to control transmission voltage.

The desired terminal voltage versus output current characteristic of the compensatorcan be established by a minor control loop using the previously defined auxiliary inputas shown schematically in Figure 5.M. A signal proportional to the amplitude of thecompensating current r1p with an ordered polarity (capacitive current is negative and

L v7+Avrft)

Av

V

Power system

Figure 5.44 Implementation of the 7-l slope by a minor control loop changing thereference voltage in proportion to the line current.

1.

2.

3.

Voltagemeasuring

andprocessing

circuits

Z(ot,t)

Perfect Regulator:VT=Vier:AVr=0

hlt=het-Kte

Staticvar

generator

Currentmeasuring

andprocessing

circuits

G

Page 2: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM

inductive current is positive) is derived and summed to the reference Vp"1. The effectivereference Vfi"r controlling the terminal voltage thus becomes

Vfirt:VRri*xlg

In (5.I4), K, the regulation slope is defined by

_ AYr*u* _ LVt^*I r^u* I L^u*

(5.15)

where LVc^*is the deviation (decrease) of the terminal voltage from its nominal valueat maximum capacitive output current (Ig^u*: Is^o), LVy^ois the deviation (increase)

of the terminal voltage from its nominal value at maximum inductive output current(19^*:Ir,u*), /cr* is the maximum capacitive compensating current, and [,o is themaximum inductive compensating current.

Equation (5.14) indicates that Vfi"1is controlled to decrease from the nominal(set) value (no compensation) with increasing capacitive compensating current (as

determined by the selected slope rc), and, conversely, it is controlled to increase withincreasing inductive compensating current until the maximum capacitive or, respec-

tively, inductive compensating current is reached. Consequently, the amplitude of the

terminal voltage, V7, is regulated along a set linear slope over the control range ofthe compensator. For terminal voltage changes outside of the linear control range,

the output current of the compensator is determined by the basic V-.I characteristic

of the var generator used. That is, the compensating current will stay at the maximum

capacitive or inductive value in the case of a converter-based var generator (i.e., ifthe compensator considered is STATCOM) and, in contrast, it will change in the

manner of a fixed capacitor or inductor in the case of a variable impedance (TCR/TSC) type var generator (i.e., if the compensator is an SVC).

A typical terminal voltage versus output current characteristic of a static compen-

sator with a specific slope is shown in Figure 5.45, together with particular "load lines"(voltage versus reactive current characteristic) of the ac system. Load line 1 intersects

the compensator V-I characteristic at the nominal (reference) voltage, thus the outputcurent of the compensator is zero. Load line 2 is below load line 1 due to a decrease

in the power system voltage (e.g., generator outage). Its intersection with the compen-sator V-l characteristic calls for the capacitive compensating current lcz. Load line 3

is above load line 1 due to an increase in the power system voltage (e.g., load rejection).Its intersection with the compensator V-I characteristic defines the inductive compen-sating current [3. The intersection points of the load lines 2 and 3 with the vertical(voltage) axis define the terminal voltage variation without any compensation. Theterminal voltage variation with compensation, in the linear operating range understeady-state conditions and slow system changes is entirely determined by the regula-tion slope, independent of the type of var generator used, as observable in Figure5.45. Outside of the linear operating range the STATCOM and SVC act differently,as indicated in the figure. The dynamic performance of the two types of compensatoris also different.

5.3.2 Transfer Function and Dynamic Performance

The V-I characteristic of the static compensator shown in Figure 5.45 represents

a steady-state relationship. The dynamic behavior of the compensator in the normalcompensating range can be characterized by the basic transfer function block diagram

(s.14)

Page 3: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.3 t Static Var Compensators: SVC and STATCOM

Load line 3

Load line 1

Load line 2 Vr=Jnet

avan^[

18s

V7

t,,'With compensation

tfut

Withoutc,ompensation

TSTATCOM \

I

t _._ \r\+ --,.\

- \1,,

lan^*lcz*?rluIc lL

Figure 5.45 v-I characteristic of the SVC and the STATCOM.

lL*^*

shown in Figure 5.46. This block diagram is derived directly from the basic controlscheme shown in Figure 5.44 and the transfer functions established for the variableimpedance (FC-TCR and rSC-TCR) type and converter-based var generators inSections 5.2.1. and 5.2.2, respectively.

- In the linear operating range of the compensator, the terminal voltage v7 canbe.expressed from Figure 5.46 in terms of the internal voltage V and the referencevoltage 7ps1 as follows:

rl -r, | ,,, G1G2Xvr- v T+ cGrHX+ vnetll@@fift (5.16)

Since the objective is to establish how well the terminal voltage is regulated

vr(-n)

Measurement

Figure 5.46 Basic transfer function block diagram of the static (var) compensator.

V7

V+AV

Page 4: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

186 Chapter 5 f Static Shunt Compensators: SVC and STATCOM

against the (varying) system voltage, let Vx"i : 0 and consider small variation only.Then the amplitude variation of the terminal voltage AVl against the amplitudevariation of the power system voltage LV can be expressed in the followingform:

LVr _AV L+GIG\HX I+GHX (5.17)

where

..\ rlrc(rl:1+fu

Gz: €-Tas

G-GrGr--\,1 2 €-rasl1- lt,S

(5.18)

(s.1e)

(5.20)

(5.21)H-1+Tzs

and ?r : main time constant of the PI controller (typically about 10*50 ms dependingon the var generator transport lag), T2: amplitude measuring circuit time constant(typically about 8-16 ms), Zd : transport lag of the var generator (typically 2.5 msfor TCR, 5.0 ms for TSC and 0.2-0.3 ms for converter), X : Im Z (reactive part ofthe system impedance), rc : regulation slope (typically L-5Vo) given by (5.15), ands: Laplace operator.

It should be pointed out that practical compensator controls often employ filtersin the signal processing circuits which may introduce additional time constants inthe transfer functions affected. Sometimes phase correcting (lead/lag) circuits arealso employed.

Under steady-state conditions (s -+ 0) (5.17) becomes

LV, 1(5.22)Lv r+

Equation (5.22) confirms that as the slope becomes smaller (rc -+ 0), the terminalvoltage remains constant, independent of the system voltage variation (LVrl LV --->

0). Similarly, with increasing slope (*> X) the terminal voltage becomes unregulated(avrtLV---> 1).

It is to be noted too that (5.17) defining the dynamic behavior of the compensatoris a function of the power systern impedance, that is, the system impedance is an integralpart of the feedback loop. This means that the time response, and thus the stabilityof the control, is dependent on the system impedance. For this reason, the controlis normally optimized for the maximum system impedance (minimum short-circuitcapacity) expected. This, of course, means that the response time of the system willbe somewhat longer if the system impedance is decreased (short-circuit capacity isincreased). With practical static compensators, the worst case response time is typicallyin the range of 30 to 70 ms (2 to 4 cycles at the power system frequency). The toleranceto system impedance variation and the attainable worst case response time are consid-erably dependent on the achievable frequency bandwidth of the compensator, whichis ultimately limited by the transport lag of the var generator employed.

XK

Page 5: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

'l

drru

ll

,

Section 5.3 r Static var compensators: Svc and srATCoM 187

In order to estimate the attainable bandwidth and the stability of the closedvoltage regulation loop of the two types of static comp".rruto, lsvc and STATCOM),consider the general expression given by (5.17). This equation equally characterizesboth-types, except for the^"tranJport lag'; time constant ?a in iransfer function G2,which is about an order of magnitude smaller for the STATCOM than it is for theSVC. Recognizing tl:I?-ridesirable phase characteristic of the e-ra, term, theimprovement the STATCoM offers is very significant from the st.anopoint of attainablefrequercy bandwidth. Refer to Figure 5-.47-where the phase angle characteristic ofthe e-ra'term (with t _:_io uor,r_r ft"quency for the pr;io;Jf estaulished transportlag delay times, za : 5.55 ms (TSC), Ti: z.il ms (TCir), andio: 0.5 -, 1"onu"ri*y,are plotted. As can be seen, the frequency at which the phase shift reaches 1g0 degrees(where the closed-loop gain of the- voltage regulator for stability must be less thanunity) is typically more than ten times gieater for the converter-based var genera-tor of the STATCoM than it is for thtTsc and rcR based var generator of theSVC.It follows from 5.17 that, if the system impedance varies (as it always does inpractice due to line switchings, generator outagei, etc.), the comfensator will remainstable only if the overall roop gain versus r*q""n"y, o"te.-i'n"o by the productG.G2HX, is less than unity withlhe maximum system impedance (weakest ;y*;ibefore the angle of G1G2HX versus frequency. rlaches 1gb degrees. This is usuany

achieved by setting the time constant of the main error amplifiei appropriately large.To illustrate this, consider the basic compensator-based uoltug" regulator shown inFigure 5'43, with the transfer function repiesentation and correlponding data definedin Figure 5.48. If the compensator is a STATCOM with Ii : 0'.5 -r, and thus withG2: s-''*,ss, then stable operation with a regulation bandwidth of 65 Hz (Tt : .14

ms) is maintained over the total two to one system impedance range. As the Bodeplots shown in Figures-5.49(a) and (b) ilrustrate,-with the strong system (x : 4.76r)the gain margin (i.e., the_gain at 1g0" phase angle) is almost -io ag and even withthe weak system (x : 9.522) acomfortable gain maigin of about - 10 dB is maintained.By contrast, as the Bode plots in Figures-5.50(a) ind (b) illustrate, the TSC/TCR_based SVC (Tz: 5.55 ms), even if the bandwiain is fimiied to 35 Hz (zr : 35 ms)would become unstable (the gain becomes positive at 1g0 degree phase angle) as

Angle [" ] 0

-90

*180

*270

\ \ \i-E;,ir.-l,.TM t]]I

\ \ \ \

s -+ ja - jZrrf

J^\ T-llll\rg'louuu")

10 f lHzl 100

Il9: thyristor-switched capacitorlUFt: thyristor-controlled reactorconv. : multipulse, voltage-sourced converter

Figure 5,47 Bode-plot representation of thetrolled elements of a static varthe converter.

transport lag characterizing the con_generator: the TSC, the TCR. and

Page 6: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

GtGrx-ffir-Et

t' - t-n= l+rrs

188 Chapter 5 I Static Shunt Compensators: SVC and STATCOM

Steady-state perfo rmance :

Xmin =Xrn"* =rc (s/p.)=

73rsc =Lconv =

Tz=

Data:

4.761 (strong system)9.522 (weak system)

0.846 (with strong system)

5.55 ms (TSC/TCR SVC)0.5 ms (STATCOM)

4msavrlav l"=o

= 0.1 511 + Gt GzHX 1 4.761I +

91946

Determine:

Maximum bandwidth for stable operation with both strong and weak systems, i.e.,

maximum fis6nufor STATCOM and lrsc for TSC/TCR type SVC

Figure 5.48 Compensation example to demonstrate the effect of transport lag onthe stability of voltage regulation in face of varying system impedance.

the system impedance approaches its maximum value. For acceptable stability, thebandwidth of the SVC would have to be reduced further, to about 2OHz. The reducedbandwidth would, of course, result in a reduced response to system disturbances. Ifthe wide impedance variation in the application is encountered, and fast response is

required, then the TSC/TCR-based SVC would have to be equipped with an automaticgain adjustment that would change the regulation gain either according to the prevail-ing system impedance or with the sensing of an oscillatory trend in the control.

5.3.3 Transient Stability Enhancement and PowerOscillation Damping

As established in Section 5.1.5, transient stability enhancement and power oscilla-tion damping require the appropriate variation of the transmission line (terminal)voltage in order to control the transmitted power so as to counteract the prevailingacceleration or deceleration of the disturbed machine(s).

5.3,3.1 Transimt Stability Enhancement. The transient stability indicates thecapability of the power system to recover following a major disturbance. A majordisturbance, for example a severe fault on a heavily loaded line, can result in a largestep-like decrease in the transmitted electric power while the generators feeding theline receive constant mechanical input power. The difference between mechanicalinput and electrical output power causes the machines to accelerate. As explained inSection 5.1.3, transient stability at a given power level and fault clearing time isprimarily determined by the P versus 6 characteristic of the post-fault system thatcontrols the electric power transmission and thereby the rate of energy absorptionfrom the machine.

I

Iil

Page 7: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.3 t Static Var Compensators: SVC and STATCOM

Type of compensator: STATCOM (a) System: strong (X = 4.761')

Gain [dB]+o

2A

189

Tt = 0.014 sec (wideband)

0

-20

-40

Angle ["] 0

Gain tdBl 40

20

0

_20

_44

Angle ['] 0

1 000

-90

- 180

-274ff{zl 100 1 000

Tt = 0.014 sec (wideband)Type of compensator: STATCOM (b) System: weak (X = 9.522)

10 flHzl 100 1 000

-90

- 180

-270

I 1-lo.oooss;v1t_'1+0.004s

- l(GHl= l(GtGrHl

l-t+rr/1- 1+0.014s

ttltttttlS-----+ i, = j2rrf

t t|tl

10 fl{zl 100

10

tlHzl 100 1 000

Figure 5.49 Gain and angle versus frequency bode plots representing the case whenthe STATCOM regulates the voltage of a strong (low impedance)system (a) and a weak (high impedance) system (b).

As was shown in that section, a static compensator, controlled to regulate theterminal voltage, can increase the transient stability by maintaining the transmissionvoltage (at the midpoint or some appropriate intermediate point) in face of the in-creased power flow encountered immediately after fault clearing. However, the tran-sient stability can be increased further by temporarily increasing the voltage abovethe regulation reference for the duration of the first acceleration period of the machine.

10

'l 'inGHX| - n = 20 log X/SLP = 15 dBll'-wllllllll

ilil1QuoslGfixl

\..

r=r *T lfil

r (Zooooutl I

1l/-L 1+0.004s

- I (GH\=t(GtGrH)N /11 + 0"014 s

illiltl5 -"-, ja = i2

tltrnf

lttlttltlltt20 loglGHXlr=o= 20log X/SLP = 20 dB

20 toglGHXl

Page 8: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

190 Chapter 5 r Static Shunt Compensators: SVC and STATCOM

Type of compensator: SVC (TSC/TCR) (a) System: strong (X = 4.761) Tt = 0.035 sec

Gain tdBl 40

20

0

_24

_44

Angle ["] 0

Gain tdBl 40

20

0

_20

_40

Angle ['] 0

fl{zl 100

*90

- 180

-270flHzl 100

Type of compensator: SVC (TSC/TCR) (b) System: weak (X = 9.522)

10 1 000

1 000

Tt = 0.035 sec

10

100 1 000

-90

- 180

-27010 flHzl 100 1 000

Figure 5.50 Gain and angle versus frequency bode plots representing the case whenthe SVC regulates the voltage of a strong (low impedance) system (a)and a weak (high impedance) system (b).

The voltage increased above its nominal value will increase the electric power transmit-ted and thus will increase also the deceleration of the machine. This is illustrated inFigure 5.51, where the P versus 6'plots of a simple two-machine system with differentmidpoint compensations are shown. The plot marked V-: V represents the P versusD plot obtained with an ideal compensator holding the midpoint voltage constant(refer back to Figure 5.1). The plots marked STATCOM and SVC represent these

10 fl{zl

I I

20 loglGHXlr=a= 20 log X/SLP = 15 dB

20 toglGHXl+.Lt

:-.- h !1...-1+0.004s

-J-l-l.L'rr"'||ll

t1\ 1 + 0.035 slll\ \ \ ('="ofuu",

r il illS -----* i, = j2n f

llttrl

2A

+ogl

+GHXlr

=o = !0 log XSLP = 20 CB

|]l

-riK''

:J_ 1ffi t_'111

- 0.035 s

tltlt(GH)\ =l(G

\J

lt..]o1'),

{ \'2"]>55S; ||

S* ir=i',2 t

Page 9: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.3 t Static Var Compensators: SVC and STATCOM

P(p.u.)

2.0

vs- t/sin(arf * il vr = Vsin(arf *81

191.

Pt-)

x/2 -

x2

vm - Vrsin att

For uncompensated line: sin 6 Az = area with Vm = V (regulated voltage)

AAz = additional area with maximumcapacitive outp ut (V, > V )

Figure 5.5L Attainable enhancement of transient stability by the SVC and STAT-COM increasing temporarily the (midpoint) transmission voltage.

compensators with a given rating insufficient to maintain constant midpoint voltageover the total range of 6. Thus, these P versus 6'plots are identical to that of the idealcompensator up to a specific 6. (, : fl) at which the SVC becomes a fixed capacitorand the STATCOM a constant current source. In the interval between fl and n, theP versus 6 plots are those which correspond to a fixed midpoint capacitor and aconstant reactive current source. The continuations of these plots in the d; to zerointerval show the P versus 6 characteristic of the two-machine system with the maxi-mum capacitive admittance of the SVC and with the maximum capacitive outputcurrent of the STATCOM. That is, at angles smaller than 6; the transmission line isovercompensated (and, of course, for angles greater, it is undercompensated). Thisovercompensation capability of the compensator can be exploited to enhance thetransient stability by increasing the var output to the maximum value after faultclearing and thereby match the area of accelerating energy (,41) by that of the decelerat-ing energy (,4r) with a smaller d61, zrS indicated in the figure. Depending on therating of the compensator, and the allowed voltage increase, the attainable increasein transient stability margin (represented by AAr) can be significant.

The implementation of the transient stability enhancement in the basic controlscheme shown in Figure 5.43 can be accomplished simply by summing a signal dV tothe fixed voltage reference signal Vp,1, as illustrated in Figure 5.52. The signal 6V canbe derived from the rate of change of transmitted power, line current or systemfrequency, indicating the angular change of the disturbed machines.

5.3.3.2 PowerOscillationDamping. AsdiscussedinSection5.l.4,poweroscil-lation damping generally requires the variation of the voltage at the terminal of thecompensator in proportion to the rate of change of the effective rotor (or powertransmission) angle. Rotor angle changes, of course, result in frequency and real powervariations. In practice, usually the variation of the transmitted real power or the system

For V=V: reAA4\^ 7r 6

I I'diltI - 6.4, with V^ = const.| 6.r;, with /c = ffiax.

P= !'X

SVCI

Page 10: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Voltagemeasuring

andprocessing

c|rcu|ts

Z(a,t)

Staticvar

generator

Measuringprocessing

andactuatingcircuits

192 chapter 5 t Static Shunt compensators: SVC and 5TATC.M

Vr + AV,U)

fr+Afrft)

Av

V

Power system Perfect regulator:VT=hLt,JVT=O

hlt = het+DV

Figure 5.52 Implementation of the transient stability enhancement concept by in-creasing the reference voltage during the first swing of a major distur-bance.

frequency is measured and used for controlling the var output to produce the terminalvoltage variation desired.

The functional control scheme for damping power oscillations (and for providinglerminal voltage regulation when power oscillation is absent) is shown in Figure 5.5iIn this scheme, the same general idea of modifying the fixed voltage reference by anauxiliary control signal to derive the effective voltage reference that controls theterminal voltage is followed again. Accordingly, a signal corresponding to the variation

W+avrft)fr + A rrft)

Av

V

Power system

Af r = d(A6)ldt

Figure 5.53 Implementation of power oscillation damping by modulating the refer-ence voltage according to frequency or power flow variations.

hltr

Voltagemeasunng

andprocessing

ctrcu[s

Z(a,t)

dt = d(Aa)ldtPower flow or

frequencyvariation

measuringcircuits

Page 11: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.3 I Static Var Compensators: SVC and STATCOM 193

of the real power or that of the system frequency is summed to the flxed referencevoltage signal 7p"1. The added signal causes the output current of the compensator tovary (oscillate) around the fixed operating point to control the terminal voltage so as

to aid system damping. That is, the terminal voltage is increased when, for example,the frequency deviation Af = d(LA)ldr is positive (in order to increase the transmittedelectrical power and thereby to oppose the acceleration of the generators) and it isdecreased when A/is negative (to reduce the transmitted electrical power and therebyoppose the deceleration of the generators).

Effective power oscillation damping can be achieved also by the alternativecontrol scheme shown in Figure 5.54. In this scheme, the signal representing poweroscillation is fed directly to the input of the static var generator. This may be doneto avoid the time constants associated with the terminal voltage regulator loop andto improve the overall response time, or to simplify the control system if the solepurpose of the compensator is power oscillation damping. This arrangement is particu-larly suitable to the implementation of the "bang-bang" type control strategy thatalternates the var output between the attainable maximum positive and negative values.

The control scheme shown in Figure 5.54 can also be used successfully to dampensubsynchronous oscillations encountered with transmission lines employing series ca-pacitive compensation. The frequency of subsynchronous oscillation is normally sig-nificantly higher than that of normal power oscillation. For subsynchronous oscillationdamping, the angular velocity of the generator is usually measured directly by using,for example, a toothed-wheel magnetic transducer located at the shaft of the rotor.

5.3.4 Var Reserve (operating point) Control

As evident from the previous sections, a static compensator has the functionalcapability to handle dynamic system conditions, such as transient stability and poweroscillation damping in addition to providing voltage regulation. Even in the area of

Vr + AVrU)

fr + Atrft) Vr+ AVr

Av

V /onet

Power systemPerfect Regulator:VT=het,AV7=Q

o vR.f

For coordination

Alternative method of power oscillation damping by modulating thereference current to the static var generator according to frequency orpower flow variations.

I---->Z(u,t)

Afr = d(Aa)l

Staticvar

generator

Power flow orf requencyvariation

measuringcircuits

Figure 5.54

Page 12: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

194 Chapter 5 I Static Shunt Compensators: SVC and STATCOM

voltage regulation, the static compensator is viewed primarily as a fast var source tocounteract rapid and unexpected voltage disturbances due to faults, line and loadswitching, generator outages, etc. In order to fulfill these applications requirements itis necessary to ensure that the compensator will have sufficient var capacity to handleunpredictable dynamic disturbances. This is often accomplished with an automaticcontrol that maintains predetermined var reserve by adjusting the operating point ofthe compensator.

The objective of this control is to limit the steady-state reactive power outputof the compensator to a given reference value. The basic concept is to allow thecompensator to change its output rapidly to counteract transient disturbances. How-ever, when a disturbance results in a new operating point, with a steady var output,the var reserve control effectively changes the voltage reference in order to bringback the var output slowly to the set reference value, and thereby activating "slow"var sources (e.g., mechanically-switched capacitors) and other compensating means(e.g., generator excitation) to pick up the steady-state var load. The response time ofthis control loop is slow in order not to interfere with the rapid voltage regulation orany fast stabilizing or auxiliary functions that might be included in the overall varoutput control.

A possible scheme to implement a basic var reserve control is shown in Figure5.55. The magnitude of the output current of the compensator is measured and com-pared against the reference I$. The error signal A1p is processed by an integrator oflarge time constant and added to the fixed voltage reference Vp"1. This forces the inputsignal to the voltage regulator to change until the difference between the actual outputcurrent of the compensator and the steady-state output current reference I$ be-come equal.

The operation of the simple var reserve control described is illustrated in Figure5.56. Assume that the compensator is operating at point 1 (/o : 1g1) on the V-l curvewhen a disturbance in the form of a sudden A[ drop in the amplitude of the terminalvoltage occurs. The voltage change A[ forces, via the fast voltage regulating loop,

vr + Avrft)

Av

V

Power System

td

Voltagemeasunng

andprocessing

circuits

Z(a,t)

/enet I pr IAV-

Perfect Regulator:

VnLt =VR"f - k.i Ltqdt

Staticvar

generator

Currentmeasuring

andprocessing

circuits

Slowerror

integrator

Figure 5.55 Implementation of the var reserve control.

Page 13: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.3 I Static Var Compensators: SVC and STATCOM

Figure 5.56 Diagrammatic illustration of theconcept of var reserve control.

195

the output current to increase from the steady-state value 1[ to 162 and the compensatorassumes working point 2 on the V-l curve. However, since 162 > I$, an error signal

A1q is generated within the var reserve control loop, which, via the slow integrator,changes the reference signal to the voltage regulator, forcing the compensator toreduce slowly its output current. The compensator finally assumes a new steady state

in working point 3 on the V-I cuwe.

5.3.5 Summary of Compensator Gontrol

The structure of static compensator control illustrating the underlying principleof superimposing auxiliary input signals on the basic voltage reference, to carry outspecific compensation functions automatically as required by system conditions, is

shown in Figure 5.57. With this principle, the compensator, within its MVA ratingand operating frequency band, acts as a perfect amplifier forcing the magnitude ofthe regulated terminal voltage to follow the effective voltage refetence, which is thesum of the fixed voltage magnitude reference and auxiliary signals. The effectivereference thus defines the operating modes and characteristics (e.g., voltage regulationwith the corresponding steady-state operating point and regulation slope) as well as

the desired actions in response to dynamic changes of selected system variables (e.g.,

transient stability enhancement and oscillation damping).Apart from the real-time control functions illustrated in Figure 5.57, the total

control system of a modern static compensator has many other elements to managethe proper and safe operation of the equipment with high reliability and availability,as well as to accommodate proper interface with local and remote operators, as shownin a glossary manner in Figure 5.58. The main elements of this overall compensatorcontrol system include:

L. Interface between high-power, high-voltage semiconductor valves of theoverall switching converter and/or TSC and TCR structure and a highly-sophisticated real-time control required for the internal operation of the vargenerator and for the desired system compensation functions. This interface,

STATCOM

Page 14: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

196 Chapter 5 I Static Shunt Compensators: SVC and STATCOM

Vr + AVrft)f r+ afrft)

Voltageregulation loop

hJt'

VT

aanag)

(Arr{o)Aux. Input

het

ls

V7

ioafrPafrP

Figure 5.57 Structure of the basic compensator control for multifunctional powersystem compensation.

Auxiliary equipment andsystem status input

SCADA

Figure 558 Main elements of the complete control operating a static compensator.

transmitting gating commands from the control to the valves and status infor-mation from the valves to the control is usually implemented by optical links.

2. Signal measuring and processing circuits for system and equipment variables.The real-time control and protection relays (and operator displays) need asinputs certain system variables, such as terminal voltage and compensatoroutput current, as well as appropriate internal voltages and currents of theequipment, from which magnitude, phase, frequency, and other relevant infor-mation can be derived to follow in real-time system conditions and monitorequipment operation.

3. Supervisory control and status monitor which interfaces with the all parts of

Voltagemeasuring

andprocessing

circuitsJORefStatic

var.generator

Vllqdroopcharacter.

Overvoltagelimitation

Transientstab. enhnc.

Power osc.

SVGpowercircuit

SVGinternalcontrol

Compensatorinternalcontrol

Controlpanel and

CRT monitor

Supervisory control andstatus monitor

Page 15: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.4 r compensation between sTATCOM and svc 197

the compensator, including all essential components of the compensatorproper and its support equipment (e.g., cooling system, power suppliei, break-ers, switches, interlocks, etc.). It collects status information from every partof the system, usually via serial communication links, organizes and inteipietsthe status data to determine the operational integrity of the compensatoi andto provide diagnostics for possible malfunctions and failures. Ii also carriesout the start-up and shutdown sequencing and other operating routines ofthe compensator and provides appropriate communication linkJfor the localand remote operators.

I 4. User interface with CRT graphical displays is usually provided by a stand-alone computer with an appropriate CRT monitor, keyboard, and pointingdevice for data entry. This computer usually has a serial link to the statusprocessor and runs a graphical display and control software. Through theinterface a large amount of information is available for the operation, diignos-tic, and maintenance purposes in graphical and numerical form. The informa-tion includes: status information from the valves, identifying failed powersemiconductors and other components and associated circuiti; selected op-erating modes of the compensator and associated control and operationalparameter settings; control operating and redundancy; and status of supportequipment such as cooling system, auxiliary power supplies, breakers, swifches,etc., and building climate status (temperature, humidity, etc.).

5.4 COMPARISON BETWEEN STATCOM AND SVC

On the basis of explanations provided in the previous sections it should be clear tothe reader that, on the one hand, in the linear operating range the V-1 characteristicand functional compensation capability of the STATCOM and the SVC are similar.However, the basic operating principles of the STATCOM, which, with a converter-based var generator, functions as a shunt-connected synchronous voltage source, arefundamentally different from those of the SVC, which, with thyristor-co-ntrolled reac-tors and thyristor-switched capacitors, functions as a shunt-connected, controlled reac-tive admittance. This basic operational difference (voltage source versus reactive ad-mittance) accounts for the STATCOM's overall superior functional characteristics,better performance, and greater application flexibility than those attainable with theSVC. These operational and performance characteristics are summarized here, withthe underlying physical reasons behind them, and with the corresponding applica-tion benefits.

5.4.1 V-l and t/-O Characteristics

The STATCOM is essentially an alternating voltage source behind a couplingreactance with the correspondingV-I andV-Q chancteristics shown in Figures S.Se1a)and 5.60(a), respectively. These show that the STATCOM can be operated ou", it.full output current range even at very low (theoretically zero), typicaliy about 0.2 p.u.system voltage levels. In other words, the maximum capacitive or inductive outputcurrent of the STATCOM can be maintained independently of the ac system voltage,and the maximum var generation or absorption changes linearly with the ac systJmvoltage.

In contrast to the STATCOM, the SVC, being composed of (thyristor-switchedcapacitors and reactors, becomes a fixed capacitive admittance at full output. Thus,

Page 16: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

198

(a) STATCOM

Chapter 5 t

Transientrating (f<1sec)

Static Shunt Compensators: SVC and STATCOM

(b) svcTransient

rating (f<1sec)//./i/___ --7Transient

rating

lc lc^^^

Capacitive

Transientrating

Q6 Qcrn"* o

Capacitive

lL^^* lL

Inductive

(a) sTATcoM rransient

rating (f<1sec)

(b) svc ,",1i3??l?31.r

vr

1.0

vr

Figure 5.59 V-I characteristic of the STATCOM (a) and of the (SVC) (b).

the maximum attainable compensating current of the SVC decreases linearly with acsystem voltage, and the maximum var output decreases with the square of this voltage,as shown in Figures 5.59(b) and 5.60(b), respectively. The STATCOM is, therefore,superior to the SVC in providing voltage support under large system disturbancesduring which the voltage excursions would be well outside of the linear operatingrange of the compensator. The capability of providing maximum compensating currentat reduced system voltage enables the STATCOM to perform in a variety of applica-tions the same dynamic compensation as an SVC of considerably higher rating.

As Figures 5.59(a) and 5.60(a) illustrate, the STATCOM may, depending on thepower semiconductors used, have an increased transient rating in both the inductive

lc lcrn^^

Capacitive Inductive

QLr"* Qy

Inductive

VT

1.0

-ri_ _l--ii-/

t'r'i,,'

.---

-

- i

QLrn"* Qy

lnductive

Q6 Qcp,1u*

Capacitive

a"'

Figure 5.60 V-Q characteristic of the STATCOM (a) and of the (SVC) (b).

Page 17: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.4 I Compensation between STATCOM and SVC L99

and capacitive operating regions. (The SVC has no means to increase transiently thevar generation since the maximum capacitive current it can draw is strictly determinedby the size of the capacitor and the magnitude of the system voltage.) The maximumattainable transient overcurrent of the STATCOM in the capacitive region is deter-mined by the maximum current turn-off capability of the power semiconductors (e.g.,GTO thyristors) employed. As shown in Chapter 3, in the inductive operating regionthe power semiconductors of an elementary converter, switched at the fundamentalfrequency, are naturally commutated. This means that the transient current rating ofthe STATCOM in the inductive range is, theoretically, limited only by the maximumpermissible GTO junction temperature, which would in principle allow the realizationof a higher transient rating in this range than that attainable in the capacitive range.However, it should be pointed out that this possibility would generally not exist if theconverter poles were operated to produce a pulse-width modulated waveform, whenthe current conduction between the upper and lower valves is transferred severaltimes during each fundamental half cycle. Even with non-PWM converters, abnormaloperating conditions should be carefully considered in the implementation of transientratings above the peak turn-off current capability of the semiconductors employed,because if an expected natural commutation would be missed for any reason, converterfailure requiring a forced shutdown would likely occur.

5.4.2 Transient Stability

The ability of the STATCOM to maintain full capacitive output current at lowsystem voltage also makes it more effective than the SVC in improving the transient(first swing) stability. The effectiveness of the STATCOM in increasing the transmitta-ble power is illustrated in Figure 5.61(a), where the transmitted power P is shown

(a) STATOOM (b) svc

4 2.s

2

1.5

1

0.5

0

2

Figure 5.6L Transmitted power versus transmission angle of a two-machine system

with a midpoint STATCOM (a) and a midpoint SVC (b) obtained withdifferent var ratings.

Page 18: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

200 Chapter 5 I Static Shunt Compensators: SVC and STATCOM

against the transmission angle dfor the usual two-machine model at various capacitiveratings defined by the maximum capacitive output current 16,o. For comparison, anequivalent P versus 6 relationship is shown for an SVC in Figure 5.61(b). It can beobserved that the STATCOM, just like the SVC, behaves like an ideal midpoint shuntcompensator with P versus 6 relationship as defined by (5.2b), P : (2V2lX) sin(d/2)until the maximum capacitive output current /6.,u* is reached. From this point, theSTATCOM keeps providing this maximum capacitive output current (instead of afixed capacitive admittance like the SVC), independent of the further increasing angle6'and the consequent variation of the midpoint voltage. As a result, the sharp decreaseof transmitted power P in the n 12 < 6 < n region, characterizing the power transmissionof an SVC supported system, is avoided and the obtainable I faa area representingthe improvement in stability margin is significantly increased.

The increase in stability margin obtainable with a STATCOM over a conventionalthyristor-controlled SVC of identical rating is clearly illustrated with the use of thepreviously explained equal-area criterium (Section 5.1.3) in Figures 5.62(a) and (b).The simple two-machine system, discussed at the review of the basic shunt compensa-tion principles [Figure 5.1(a)], is compensated at the midpoint by a STATCOM andan SVC of the same var rating. For the sake of clarity, it is assumed that the systemtransmitting steady-state electric power Py at angle fi, is subjected to a fault for aperiod of time during which Pr becomes zero. During the fault, the sending-endmachine accelerates (due to the constant mechanical input power), absorbing thekinetic energy represented by the shaded area below the constant P1 line, and increasing& to 6. (6. > 6,). Thus, when the original system is restored after fault clearing, thetransmitted power becomes much higher than P1 due to the larger transmission angle6". As a result, the sending-end machine starts to decelerate, but 6 increases furtheruntil the machine loses all the kinetic energy it gained during the fault. The recoveredkinetic energy is represented by the shaded area between the P versus d curve and

(a) STATCOM (b) svc

P z.sPo

2

1.5

1

Pt

Pg

0.5

0

P 2.sPo

2

1.5

1

Pl

Pg

61 6c t,

Figure 5.62 Improvement of transient stabilityCOM (a) and a midpoint SVC (b)

o 61 6c;

obtained with a midpoint STAT-of a given var rating.

Page 19: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.4 I Compensation between STATCOM and SVC 20I

the constant power line Pr. The remaining unshaded area below the P versus E curveand above the constant power line Pr provides the transient stability margin. As canbe observed, the transient stability margin obtained with the srATCoM, due to thebetter support of the midpoint voltage, is significantly greater than that attainablewith the SVC of identical var rating. This of course means that the transmittablepower can be increased if the shunt compensation is provided by a STATCOM ratherthan by an SVC, or, for the same stability margin, the rating of the STATCOM canbe decreased below that of the SVC.

5.4.3 Response Time

As demonstrated in Section 5.3.2,the attainable response time and the bandwidthof the closed voltage regulation loop of the STATCOM are also significantly betterthan those of the SVC. Although the closedloop voltage regulation of both compensa-tors can be expressed by the formula given in (5.17), i.e., LVTILV : ll(I + G1G2HX),the time constant Za in the transfer function G2 (which characterizes the inherent"transport lag" in the power circuits of the STATCoM and of the SVC) is about anorder of magnitude smaller for the STATCOM than it is for the SVC, i.e., it is typicallyfrom less than 200 g,s to 350 g.s for the STATCoM and between 2.5 and 5.0 ms forthe SVC. Considering the rapidly changing angle versus frequency characteristic ofthe e-ra'term, this improvement is important from the standpoint of attainable fre-quency bandwidth. The practical importance of wide frequency bandwidth cannot beoverstated for applications requiring fast response, but even in typical transmissionapplications the STATCOM can provide stable operation with respectable responseover a much wider variation of the transmission network impedance than is possiblewith an SVC.

5.4.4 Capability to Exchange Real Power

For applications requiring active (real) power compensation it is clear that theSTATCOM, in contrast to the SVC, can interface a suitable energy storage with theac system for real power exchange. That is, the STATCoM is capable of drawingcontrolled real power from an energy source (large capacitor, battery, fuel cell, super-conducting magnetic storage, etc.) at its dc terminal and deliver it as ac power tothe system. It can also control energy absorption from the ac system to keep the stor-age device charged. This potential capability provides a new tool for enhancingdynamic compensation, improving power system efficiency and, potentially, prevent-ing power outages.

The reactive and real power exchange between the STATCOM and the ac systemcan be controlled independently of each other and any combination of real powergeneration and absorption with var generation and absorption is achievable. Thus, byequipping the STATCOM with an energy storage device of suitable capacity, extremelyeffective control strategies for the modulation of the reactive and real output powercan be executed for the improvement of transient stability and the damping of poweroscillation. It should be noted that for short-term dynamic disturbances an energyconsuming device (".g., a switched resistor) may be effectively used in place of themore expensive energy storage to absorb power from the ac system via the STATCOM.with this simple scheme, the STATCoM would transfer energy from the ac systemto the dc terminals where it would be dissipated by the energy-consuming device that

Page 20: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

202 Chapter 5 t Static Shunt Compensators: SVC and STATCOM

would be switched on whenever surplus energy at those terminals is detected (by, e.g.,the increase of dc voltage).

5.4.5 Operation With Unbalanced AG System

The ac system voltages are normally balanced (maximum unbalance does notusually exceed 1.Vo) and therefore compensators normally control all three phases oftheir output current together. This for the SVC normally means that its control estab-lishes three identical shunt admittances, one for each phase. Consequently, with unbal-anced system voltages the compensating currents in each phase would become differ-ent. It is possible to control the three compensating admittances individually byadjusting the delay angle of the TCRs so as to make the three compensating currentsidentical. However, in this case the triple-n harmonic content would be different ineach phase and their normal cancellation through delta connection would not takeplace. This operation mode thus would generally require the installation of the usuallyunneeded third harmonic fllters. For this reason, individual phase control for SVCsin transmission line compensation is rarely employed.

The operation of the STATCOM under unbalanced system conditions is differentfrom that of the SVC, but the consequences of such operation are similar. The STAT-COM operation is governed by the fundamental physical law requiring that the netinstantaneous power at the ac and dc terminals of the voltage-sourced converteremployed must always be equal. This is because the converter has no internal energystorage and thus energy transfer through it is absolutely direct, and consequently thenet instantaneous power at its ac and dc terminals must be equal.

Assume that the dc terminal voltage of the STATCOM is supported entirely byan appropriately charged dc capacitor (i.e., there is no source or sink of power attachedto this terminal), and that the losses of the converter are zero and its pulse numberis infinite (ideal converter). With perfectly balanced sinusoidal ac terminal voltages(provided by the ac power system), the STATCOM will draw a set of balanced,sinusoidal currents in quadrature with the system voltages, but the dc capacitor willexperience no charging current because no real power is exchanged with the ac systemand, furthermore, because the net instantaneous power remains invariably zero at theac terminals of the converter. However, if the ac system voltages become unbalanced,then an alternating power component at twice the fundamental frequency will appearat the ac terminals of the STATCOM converter and this will be matched by analternating second harmonic charging current in the dc terminals, producing in turnan associated alternating voltage component of the same frequency across the capacitorshunting the dc terminals. If the converter control ignores this ac voltage component,that is, if it is operated to produce the ac output voltage as if the dc terminal voltagewas constant, then the second harmonic voltage component from the dc terminalwill be transformed (by the converter switching operation) as a negative sequencefundamental component and a positive sequence third harmonic component to theac terminals. As a result, the STATCOM will, in general, draw a negative sequencefundamental current component (in proportion to the difference between its internallygenerated negative sequence voltage and the negative sequence component of the acsystem voltage) as well as a (positive sequence) third harmonic current component.

Out of the two voltage components, generated in the output of the STATCOMas a result of system unbalance, the third harmonic is clearly "unwanted." Whereasthe negative sequence fundamental voltage, generated "naturally" by the converterwith properly sized dc capacitor, reduces significantly the negative sequence current

Page 21: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.4 I Compensation between STATCOM and SVC

that would otherwise be forced to flow by the negative sequence systemcould be very large during single-phase faults), the third harmonicuseful function.

The "natural" behavior of the STATCOM is illustrated in Figure 5.63 whererelevant voltage and current waveforms records, representing a TNA simulated powersystem with precisely scaled 48-pulse STATCOM hardware model that was subjectedto a severe line to ground fault. The traces in the figure show (from top to bottom):line to line voltages up6 zr.d u"6 (phase a is faulted to ground); the three currents drawnby the STATCOM, io, ib, l.; the dc capacitor voltage u6; and the reactive currentreference 1pn.r (limited to 2 p.u.). In steady state, the STATCOM was producing 1.0p.u. capacitive current, when it was subjected to a line to ground fault lasting for aboutfive cycles. It can be observed that, due to the internally generated negative sequenceconverter voltage (that largely matched the negative sequence voltage of the unbal-anced ac system), the STATCOM was providing during the fault substantially balanced,capacitive compensating currents with the maximum magnitude of 2.0 p.u., but withconsiderable third harmonic distortion. Flowever, the harmonics, present only duringthe five cycle fault period are, arguably, of no significant consequence (since, presum-ably, under this condition significantly more distortion is generated by various static

vab 0

vcb 0

ibo

ic0

vdc

Figure 5.63 Waveforms illustrating the operation of a STATCOM (without individ-ual phase voltage control) during and following a line to ground faultat the regulated bus.

203

voltage (whichhas clearly no

/oR"t

Page 22: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

244 Chapter 5 I Static Shunt Compensators: SVC and STATCOM

and rotating electromagnetic components present in the system). On the other hand,the STATCOM, as evidenced in the figure by the capacitive compensation maintained,can provide strong system support during the fault. This, with the STATCOM's fastresponse at fault clearing, could greatly contribute to system stability. (It should benoted that in practice the over-current limit of the STATCOM, for economic reasons,would normally be set lower than 2.0 p.u. used in this illustrative example.)

The natural behavior of the STATCOM characterized above is related to theoperating mode in which the three output voltages are controlled together; that is,single-phase voltage control is not applied. This operating mode provides the best VAutilization of the converter and generally the lowest harmonic generation obtainableunder normal system conditions with a given method of waveform synthesis employed.However, in special applications where considerable system unbalance exists, or wherelarge unbalanced loads. are to be compensated, the STATCOM converter with appro-priate pole structure and waveform synthesis method can be operated to control eachof the output phases individually, that is, to control the positive and negative sequencecompensating currents independently. However, this type of operation is usually associ-ated with some amount of fluctuating ac power and, therefore, it requires a larger dccapacitor than typically used in a transmission system STATCOM to accommodatethe consequent second harmonic ripple current at the dc terminals.

5.4.6 Loss Versus Var Output Gharacteristic

As shown in Figures 5.38 and 5.27 the overall loss versus reactive output charac-teristic, as well as the actual operating losses, of the srATCoM are comparableto those of the SVC using both thyristor-controlled reactors and thyristor-switchedcapacitors. Both types of compensator have relatively low losses (about 0.1to 0.27o)at and in the vicinity of zero var output. On the average, the losses in both casesincrease with increasing var output reaching about 1.0Vo at rated output. This type ofloss versus output characteristic is generally considered favorable for transmissionapplications where the average var output demand is normally low and the compensa-tor is primarily applied to handle dynamic events, system contingencies, and possiblythe coordination of the overall area var control.

The loss contribution of power semiconductors and related components to thetotal compensator losses is higher for the STATCOM than for the SVC. This is becausepresently available power semiconductor devices with internal turn-off capability havehigher conduction losses than conventional thyristors. Also switching losses with forcedcurrent interruption tend to involve more losses than natural commutation. However,it is reasonable to expect that the historically rapid semiconductor developments willreduce the device losses in the coming years, whereas the losses of conventionalpower components, such as reactors, are not likely to change significantly. Thus, thetechnological advances probably will have help to reduce the overall losses of theSTATCOM more than those of the SVC.

5.4.7 Physical Size and Installation

From the standpoint of physical installation, because the STATCOM not onlycontrols but also internally generates the reactive output power (both capacitive andinductive), the large capacitor and reactor banks with their associated switchgear andprotection, used in conventional thyristor-controlled SVCs, are not needed. This resultsin a significant reduction in overall size (about 30to 40Vo), as well as in installation

Page 23: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.5 t Static VAR Svstems

labor and cost. The small physical size of the STATCOMfor installations in areas where land cost is at a premium,anticipated system changes may require the relocation of

5.4.8 Merits of Hybrid Compensator

20s

makes it eminently suitableand for applications wherethe installation.

From the V-I characteristics shown in Figures 5.39 through 5.40 for hybrid vargenerators employing a switching power converter with thyristor-switched clpacitorsand thyristor-controlled reactors the obvious deduction can be made that, in general,the operating and performance advantages attainable with the STATCOM will also beexhibited by a hybrid compensator, in direct proportion to the rating of the STATCOMrelative to the total controllable var range of the hybrid compensator.

In considering hybrid compensator schemes, a particuiarly good case can bemade for the replacement of the TCR with a converter-based vai generator in thepresently used TCR-TSC compensator arrangements. This replacement would resultin a number of signiflcant operating and performance advantiges, including:

L. Faster response, since the converter can immediately provide capacitive outputbefore the TSCs could be switched in. (The TCR can only absorb ,"u"tru"power.)

2. Reduced harmonic generation and the possible elimination of filters, sincethe converter can be designed to have very low harmonic generation. (TCRis the harmonic source in the SVC.)

3. Greater flexibility to optimize for loss evaluation criteria, since the convertercan generate and absorb reactive power, which makes it possible to switchthe capacitors with either a net var output surplus or a net var output shortagethat the converter then needs to absorb or generate. (The TCR can onlyabsorb reactive power, making it necessary to switch the capacitors with anet var surplus. For example, even at very small capacitive output demandthe first TSC must be switched in, which forces the TCR to absorb a verylarge surplus capacitive vars, causing significant internal losses at that op-erating point of the compensator.)

It should be also noted that, in contrast to the TCR and mechanically-switched capaci-tor (MSC) arrangement, the combination of a STATCOM with trriSCr may providea good and economical solution for many applications. This is because the STATCOMwould be able to provide capacitive var output immediately upon demand and onlythe additional capacitive output would be delayed by the MSC operation. By contrast,in the TCR-MSC arrang"*"ot, there would be no clmpensation before the first MSCwould be switched in.

5.5 STATIC VAR SYSTEMS

A static var system is, per CIGRE/IEEE definition, a combination of static compensa-tors and mechanically-switched capacitors and reactors whose operation is coordinated.A static var system is thus not a well-defined compensating arrangement because itdoes not have a uniform V-I characteristic and its overall t"rpori" time is greatlydependent on the mechanical switching devices used.

The emphasis in a static var system is on coordination. The major objective isusually to ensure that the static compensator, having a well-define d, V-I chaiacteristic

Page 24: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

2M Chapter 5 I Static Shunt Compensators: SVC and STATCOM

and fast speed of response, is available for dynamic compensation and other elementsof the overall var system handle the steady-state var demands. Another reason forcoordination is to minimize the steady-state losses in the compensator and the overallpower system.

The var output coordination may follow different strategies. In the simplest form,it may be nothing more than the previously described var reserve control, which forcesthe output of the static compensator to return to a specific (or adjustable) var referenceafter each significant var demand change in the power system. With this arrangement,the availability of a specific amount of fast compensation capacity is enforced by anautomatic control action, but the steady var demand is left for unidentified "othermeans" in the power system (which may include generator voltage regulators, synchro-nous compensators (condensers), and mechanically-switched capacitor and reactorbanks activated by under- and over-voltage relays) to provide.

An equally simple, but philosophically opposite, policy is to let the static compen-sator pick up the reactive compensation as required, but provide an alarm signal tothe power system dispatcher if a specific var output is exceeded. It is left to thedispatcher to determine whether the compensator should keep providing the compen-sation or other available means should be brought in operation.

In a more rigorous coordination scheme, the compensator would control a num-ber of dedicated capacitor and reactor banks within the overall static var system. Thatis, if the capacitive output of the compensator would exceed a preset level for a

specified time duration, then the compensator control would activate, in a predeter-mined sequence, the mechanically-switched capacitor banks until the output of thecompensator is reduced below that level. Similarly, an excess in inductive var outputwould initiate the systematic disconnection of capacitor banks and, if required, actuatean appropriate number of mechanically-switched reactor banks.

In providing automatic coordination, due attention must be paid to the capabili-ties of the mechanical switches with regard to the frequency of operation and, also,the limitation of possible surge currents. A microprocessor-based control is usuallythe most convenient for monitoring switch status, storing switching history, and ef-fecting overall coordination according to established priorities and compensation pol-icies.

REFERENCES

Bergmann, K., et al., "Application of GTO-Based SVCs for Improved Use of the Rejsby HedeWindfarm," Ninth National Power System Conference, Kanpur NPSC '96, vol. 2,pp.39L-395.

Edwards, C. W., et al., "Advanced Static Var Generator Employing GTO Thyristors," IEEE/PES Winter Power Meeting Paper No. 38WM109-1, L988.

Erinmez, I. A., ed., "Static Var Compensators," Working Group 38-01, Task Force No. 2 onSVC, CIGRE,1986.

Erinmez, L A., and Foss, A. M., eds., "Static Synchronous Compensator (STATCOM)," Work-ing Group 14.19, CIGRE Study Committee 1.4, Document No. 144, August 1999.

Gyugyi, L., "Power Electronics in Electric Utilities: Static Var Compensators," Proceeding ofIEEE, vol.76, no.4, April 1988.

Gyugyi, L., "Reactive Power Generation and Control by Thyristor Circuits," Paper SPCC 77-

29 presented at Power Electronics Specialist Conference, Cleveland, OH, June 8-10, t976.

Reprinted in the IEEE Trans. Ind. Appl., voI. IA-15, no. 5, September lOclober 1979.

Gyugyi, L., et al., "Advanced Static Var Compensator Using Gate Turn-off Thyristors forUtility Applications," CIGRE paper 23-203, 1990.

Page 25: V7.. of · 184 Chapter 5 I Static Shunt Compensators: SVC and STATCOM inductive current is positive) is derived and summed to the reference Vp"1.The effective reference Vfi"r controlling

Section 5.5 I Static VAR Systems 247

Gyugyi, L., "Dynamic Compensation of AC Transmission Lines by Solid-State SynchronousVoltage Sources," IEEE/PES Summer Meeting, Paper No. 93SM431-1PWRD, 1993.

Gyugyi, L., and Taylor, E. R., "Characteristics of Static Thyristor. Controlled Shunt Compensa-tors for Power Transmission System Applications," IEEE Trans. PAS, vol. PAS-99, no. 5,pp. 1795-1804, September/October 1980.

Gyugyi, L., et al., "Principles and Applications of Static, Thyristor-Controlled Shunt Compensa-tors," IEEE Trans. PAS, vol. PAS-97, no. 5, September/October 1978.

Hauth, R. L., and Moran, R. J., "Basics of Applying Static Var Systems on HVAC PowerNetworks," EPRI Seminar on Transmission Static Var Systems, Duluth, MN, October24,1978.

Kimbark, E. W., "How to Improve System Stability without Risking Subsynchronous Reso-nance," IEEE Trans. PAS-96, no. 5, SeptemberlOctober 1977.

Larsen E., et al., "Benefits of GTO-Based Compensation Systems for Electric Utility Applica-tions," IEEE/PES Summer Power Meeting Paper No. 9L SM 397-0 TWRD, 1991.

Mathur, R. M., ed., Static Compensators for Reactiue Power Control The Committee on StaticCompensation, Canadian Electrical Association (CEA), 1984.

Miller, T. J. E., ed., Reactiue Power Contol in Electric Systems, John Wiley & Sons, NewYork, L982.

Mori, S., et al., "Development of Large Static Var Generator Using Self-Commutated Convertersfor Improving Power System Stability," IEEE/PES Winter Power Meeting Paper No.92W}lI65-1, t992.

Povh, D., and Weinhold, M., "Efficient Computer Simulation of STATCON," InternationalConference on Power System Transients, Lisbon, pp. 397 -402, September 1.995.

Schauder, C. D., et al. "Development of a -f 100 MVAR Static Condenser for Voltage Controlof Transmission Systems," IEEE/PES Summer Meetlng, Paper No. 94SM479-6 PWRD, 1994.

Schauder, C. D., and Mehta, H., "Vector Analysis and Control of Advanced Static Var Compen-sators," IEE Fifth International Conference on AC and DC Transmission, Conference Publica-tion No. 345, pp.266-272,1991.

Schauder, C. D., et al., "Operation of 1100 MVAR TVA STATCON," IEEE/PES WinterMeeting, Paper No. PE-509-PWRD-0-01-1997.

Schweickardt, H. W., et al., "Closed Loop Control of Static Var Sources (SVC) on EHVTransmission Lines," IEEE/PES Winter Meeting, Paper A 78 135-6, 1978.

Sen, K. K., "STATCOM-STATic synchronous COMpensator: Theory, Modeling, and Applica-tions," 99WM706, Proceedings of IEEE/PES Winter Meeting, New York, 1999.

Sumi, Y., et al., "New Static Var Control Using Force-Commutated Converters," IEEE/PESWinter Power Meeting Paper No. 81WM228-6, 1981.

.:--::-:- --


Recommended