G-1www.sbt.siemens.com/hvp/components
Variable Frequency Drives Table of Contents
Product Resource Documents
Important Note: VFD products are only available throught authorized distribution channels. To locate an authorized distributor, please contact a Siemens Building Tech-nologies representative at: 1.888.593.7876.
To lookup products and accessories:
1. Locate the appropri-ate application using the table of contents.
2. Find the desired product and page number.
3. Reference any accessories or service kits quickly in the colored pages at the back of the section.
Indexes are located at the front of the catalog organized alphabetically by application or product, or alpha- numerically by part number.
For more information:
For technical or instal-lation instructions and locations, visit the web site at: www.sbt. siemens.com/hvp/ components.
Ordering &Information
Varia
ble
Freq
uenc
y D
rives
Variable Frequency Drives
Introduction G-3
Variable Frequency Drives G-5 SED2 154-042
Variable Frequency Drives with Conventional Bypass Options G-9 SED2 154-044
Variable Frequency Drives with Electronic (E) Bypass Options G-13 SED2 154-051
Variable Frequency Drives NEMA Type 3R Bypass Options G-17 SED2 154-062
Accessories & Service Kits G-21–G-24
Page # Product Code
G-2
Varia
ble
Freq
uenc
y D
rives
Visit us on the web at: www.sbt.siemens.com/hvp/ componentsYou can:• search for products by part
number or description.• link directly to the product
information from the index.• print out product information
for submittals.• link to technical documentation.• locate a distributor near you.
G-3www.sbt.siemens.com/hvp/components
Varia
ble
Freq
uenc
y D
rives
Variable Frequency DrivesIntroduction
From a global leader in drives technology comes a drive specifically configured for HVAC applications, the SED2 Vari-able Frequency drives from Siemens. Incorporating the latest advancements in IGBT technology, the SED2 is a PWM drive packed with standard features expected in a drive designed for HVAC variable torque applications. Unique design features make this Variable Frequency Drive (VFD) truly advanced.
G-4
Varia
ble
Freq
uenc
y D
rives
Visit us on the web at: www.sbt.siemens.com/hvp/ componentsYou can:• search for products by part
number or description.• link directly to the product
information from the index.• print out product information
for submittals.• link to technical documentation.• locate a distributor near you.
feat
ure
s
G-5www.sbt.siemens.com/hvp/components
Description Applications
Varia
ble
Freq
uenc
y D
rives
Variable Frequency DrivesSED2
The SED2 Variable Frequency Drives are designed specifically for HVAC applications. The SED2 supports a wide variety of digital and analog I/O for diverse control capability. Built-in PID features control pumps and fans, and an integral system protocol can interface P1/N2 networks. Using the SED2 multi-level parameter access, operators can quickly pinpoint relevant data.
• Built-in SBT P1 and JCI N2 (Metasys®) building automation system protocols for easy network integration
• LON Interface and Modbus Interface op-tional
• Low harmonics design reduces noises and interference eliminates need for filters/reac-tors in most installations
• Built-in PID for fast and accurate pressure control
• Pump staging for open loop, constant pres-sure, and constant flow-type applications
• Multi-level program access
• Belt failure detection with or without an external sensor
SED2 Variable Frequency Drives Family.
• Service mode for applications requiring continuous, uninterruptible operation
• Accepts a wide variety of digital and analog I/O types, including direct Siemens Ni 1000 RTD sensor level inputs
• One common interface throughout all power ranges
• Optional Advanced Operator Panel for uploading/downloading parameters
• Full form C relay contacts for digital outputs
Important Note: VFD products are only available throught authorized distribution channels. To locate an authorized distributor, please contact a Siemens Building Technologies representative at: 1.888.593.7876.
Options
• LON Interface • Modbus Interface
• Advanced Operator Panel (AOP) Module
G-6
Specifications/Product OrderingVa
riabl
e Fr
eque
ncy
Driv
es
Page22
Page22
Input Voltage and Power Ranges (3 phase) 200V to 240V, 3 ac±10%. .............................................. 1/2 hp to 60 hp 380V to 480V, 3 ac ±10% ............................................. 1/2 hp to 125 hp 500V to 600V, 3 ac ±10% ................................................ 1 hp to 125 hp
Input Frequency .................................................................47 Hz to 63 Hz
Output Frequency ..............................................................0 Hz to 150 Hz
Total Power Factor ............................................................................ ≥0.9
Displacement Power Factor ........................................................... ≥0.98
VFD Degree of Efficiency ...................................................... 96% to 97%
Switch-on Current .................................. Less than nominal input current
Auxiliary Supply 24V ....................... Glavanically separated, unregulated auxiliary supply (18V to 32V) 100 mA
Overload Capacity ...................................................110% for 60 secondsControl Method ......................... Linear, parabolic and programmable V/f;
and flux current control low-power mode
PWM Frequency ...........2k Hz to 16k Hz (adjustable in 2k Hz increments)
Fixed Frequencies ........................................................ 15 programmable
Skip Frequency Bands ................................................... 4 programmable
Setpoint Resolution ............................................................0.01 Hz digital 0.01 Hz serial 10 bit analog
Digital Inputs (sink/source) ............................6: fully programmable and scalable isolated digital inputs, switchable
Analog Inputs ...............................................2: 0 to 10 Vdc, 0/4 to 20 mA, can also be configured as digital inputs or Siemens Ni 1000 input
Relay Outputs .................................2: configurable 30 Vdc/5A (resistive), 250 Vac/2A (inductive)
Analog Outputs ................................ 2: programmable (0/4 mA to 20 mA, or 0 Vdc to 10 Vdc)
Serial Interface .................................................RS-485 transmission rate: Up to 38.4k baud Protocols: USS, P1 and N2
Protection Level ................................................................................ IP20 NEMA Type 1 with protective shield and gland plate installed IP54/NEMA Type 12
Temperature Ranges .............Operating: 14°F to 104°F (-10°C to +40°C) Storage: -40°F to +158°F (-40°C to +70°C)
Humidity ........................................................... 95% RH, non-condensing
Operational Altitudes ................. Up to 3280 ft. (1000m) above sea level without derating
Protection Features • Under-voltage • Over-voltage • Overload • Ground fault • Short circuit • Stall prevention • Locked motor • Over-temperature • Parameter PIN protection
Standards ................................................................... UL, cUL, CE, C-tick
Options • LON Interface • Modbus Interface
Model
SED2 = VFD Only
kW 0.37, 0.55, 0.75, 1.1, 1.5, 2.2, 3, 4, 5.5, 7.5, 11, 15, 18.5, 22, 30, 37, 45, 55, 75, 90
Voltage 2 = 200 to 240V 3 = 380 to 480V 4 = 500 to 600V
NEMA 2 (IP20) 1 NEMA Type 1 5 NEMA Type 12 (IP54) Placeholder X = Included with all part numbers.
Example Product Number S E D 2 - 0 . 7 5 / 2 2 X
Table Note*Available with Voltage Codes 3 and 4.
Example ShownSED2-0.75/22X = SED2 only, 0.75 kW (1hp), 200V to 240V, open type IP20.
(Uses 2 to 4 spacesplus “/” divider)
G-7www.sbt.siemens.com/hvp/components
Dimensions
Varia
ble
Freq
uenc
y D
rives
Frame Sizes
SED2 IP20 and NEMA Type 1 Frame Sizes and Power Ranges
SED2 IP54 and NEMA Type 12 Frame Sizes and Power Ranges
HP 4321.51.7.5 5 7.5 403025201510 125100756050
kW 32.21.51.1.75.5.37 4 5.5 30221915117.5 9075554537240V
480V
575V
A B C D E
F
F
CED
A B C
VFD0163R1
HP 4321.51.7.5 5 7.5 403025201510 125100756050
kW 32.21.51.1.75.5.37 4 5.5 30221915117.5 9075554537
480V
575V C
BE
CD F
VFD0164R1
Dimensions shown in inches (mm).
G-8
Specifications/Product OrderingVa
riabl
e Fr
eque
ncy
Driv
es
Frame Weight Size Height Width Depth lb. (kg)
A 6.8 (173) 2.9 (73) 5.9 (149) 2.9 (1.3)
B 8.0 (202) 5.9 (149) 6.8 (172) 7.5 (3.4)
C 9.6 (245) 7.3 (185) 7.7 (195) 12 (5.5)
D 20.5 (520) 10.8 (275) 9.6 (245) 35 (16)
E 25.6 (650) 10.8 (275) 9.6 (245) 44 (20)
F 33.5 (850) 13 (350) 12.6 (320) 116 (53)
Frame Weight Size Height Width Depth lb. (kg)
A 9.1 (231) 2.9 (73) 5.9 (149) 3.2 (1.5)
B 11.8 (300) 5.9 (149) 6.8 (172) 8.3 (3.8)
C 13.8 (351) 7.3 (185) 7.7 (195) 13.6 (6.2)
D 24.6 (625) 10.8 (275) 9.6 (245) 37.5 (17)
E 29.7 (754) 10.8 (275) 9.6 (245) 46.4 (21)
F 54.5 (1384) 16.0 (406) 14.0 (356) 200 (91)
Frame Weight Size Height Width Depth lb. (kg)
B 15.2 (385) 10.6 (270) 10.6 (268) 10 (22)
C 23.9 (606) 13.8 (350) 11.2 (284) 42 (19)
D 27.0 (685) 14.2 (360) 13.9 (353) 77 (35)
E 34.8 (885) 14.2 (360) 17.8 (453) 105 (48)
IP20 SED2 VFDs
NEMA Type 1 SED2 VFDs Assembled with Protective Shield and Gland Plate
IP54/NEMA Type 12 SED2 VFDs
Dimensions/Weights
Tables expressed in inches (mm).
feat
ure
s
G-9www.sbt.siemens.com/hvp/components
Description Applications
Varia
ble
Freq
uenc
y D
rives
Variable Frequency Driveswith Conventional Bypass Options
SED2
Conventional Bypass Options are companion packages for the family of SED2 Variable Frequency Drives.
Bypass Power2-Contactor: Output & Bypass• Overload protection in bypass mode.
• Step-down transformer with fused primary and secondary.
• Contactors electrically and mechanically interlocked.
3-Contactor (optional): Input, Output, & BypassIn addition to the 2-contactor features, 3-contactor features provide:• Drive test function
• Complete electrical isolation of drive
Input Device• Disconnect
• Fused disconnect (optional)
• Circuit breaker (optional)
• All doors are interlocked and padlockable
Reactor Options• Line reactor mounted in bypass option
enclosure.
• Line reactor (in NEMA 1 enclosure) supplied separately.
• Load reactor mounted in bypass option enclosure.
• Load reactor (in NEMA 1 enclosure) supplied separately.
SED2 Variable Frequency Drives with Conventional Bypass Options Family.
Bypass ControlAu to Bypass
• Relay logic allows user to send the motor to bypass mode based on the drive’s programmable relay.
• The drive’s programmable relay, typically set to fault, can be set up for applications that run full speed for an extended period of time.
Enable Input• Generally used for safety tie-ins; the motor will not
operate the drive or bypass when open.
Common Remote Start/Stop• Common remote start/stop can be used in both drive
and bypass mode.
Essential Services Mode• Typically used for smoke purge; the motor goes to
bypass regardless of the selected mode.
• No call to stop will have an effect, including open safety or stop commands.
• Only turning the power off or opening this contact will stop the motor.
Bypass – Door Mounted Control Devices2-Contactor Units• Drive-Off-Bypass selector
• Bypass pilot light
3-Contactor Units• Drive-Off-Bypass selector
• Bypass pilot light
• Drive Test on/off selector
Important Note: VFD products are only available throught authorized distribution channels. To locate an authorized distributor, please contact a Siemens Building Technologies representative at: 1.888.593.7876.
Options
• LON Interface • Modbus Interface
• Advanced Operator Panel (AOP) Module
G-10
Specifications/Product OrderingVa
riabl
e Fr
eque
ncy
Driv
es
Conventional BypassInput Voltage (3-phase)
208V, 3 AC±10%. .................. 1/2 hp to 60 hp (2.3 amps to 154 amps)
230V, 3 AC±10%. .................. 1/2 hp to 60 hp (2.3 amps to 154 amps)
460V, 3 AC ±10%. ............... 1/2 hp to 125 hp (1.2 amps to 178 amps)
575V, 3 AC ±10%. .................. 1 hp to 125 hp (2.3 amps to 125 amps)
Temperature
Operating ..................................................... 14 to 104°F (-10 to +40°C)
Storage ......................................................-40 to +158°F (-40 to +70°C)
Humidity .................................................... 0 to 95% RH, non-condensing
Drive Specifications
Input Voltage and Power Ranges (3 phase), amps
200V to 240V, 3 ac ± 10%. .... 1/2 hp to 60 hp (2.3 amps to 154 amps)
380V to 480V, 3 ac ± 10%. .. 1/2 hp to 125 hp (1.2 amps to 178 amps)
500V to 600V, 3 ac ± 10%. ..... 1 hp to 125 hp (2.3 amps to 125 amps)
Input Frequency .................................................................47 Hz to 63 Hz
Output Frequency ..............................................................0 Hz to 150 Hz
Total Power Factor ............................................................................ ≥0.9
Displacement Power Factor ........................................................... ≥0.98
VFD Degree of Efficiency ...................................................... 96% to 97%
Switch-on Current .................................. Less than nominal input current
Auxiliary Supply 24V ....................... Glavanically separated, unregulated auxiliary supply (18V to 32V) 100 mA
Overload Capacity ...................................................110% for 60 seconds
Control Method ......................... Linear, parabolic and programmable V/f; and flux current control low-power mode
PWM Frequency ...........2k Hz to 16k Hz (adjustable in 2k Hz increments)
Fixed Frequencies ........................................................ 15 programmable
Skip Frequency Bands ................................................... 4 programmable
Setpoint Resolution ............................................................0.01 Hz digital 0.01 Hz serial 10 bit analog
Digital inputs (sink/source) ............................6: fully programmable and scalable isolated digital inputs, switchable
Analog inputs ................................ 2: 0 to 10 Vdc, 0/4 to 20 mA, can also be configured as digital inputs or Ni 1000 input
Relay Outputs .................................2: configurable 30 Vdc/5A (resistive), 250 Vac/2A (inductive)
Analog Outputs ..................................2: programmable (0/4 mA to 20 mA or 0 Vdc to 10 Vdc)
Serial Interface .................................................RS-485 transmission rate: Up to 38.4k baud
Protocols: Siemens Building Technologies, Inc., P1 and Johnson, N2
Protection Level
IP20 ............NEMA Type 1 with protective shield and gland plate installed
IP54 ......................................NEMA Type 12 (400V and 500V series only)
Temperature Ranges
Operating ................................................. 14°F to 104°F (-10 to +40°C)
Storage ......................................................-40 to +158°F (-40 to +70°C)
Humidity ........................................................... 95% RH, non-condensing
Operational Altitudes ................ Up to 3280 ft. (1000 m) above sea level without derating
Protection Features Under-voltage .................................................................Stall prevention Over-voltage ......................................................................Locked motor Overload ..............................................Motor overtemperature l2 t, PTC Ground fault ............................................................... Over-temperature Short circuit ....................................................Parameter PIN protection
Agency Standards ................................................................................UL cUL
CE Conformity ............................................................Conformity with EC Low Voltage Directive 73/23/EECOptions • LON Interface • Modbus Interface • AOP Module
Specifications
Page22
Page22
G-11www.sbt.siemens.com/hvp/components
Dimensions
Varia
ble
Freq
uenc
y D
rives
Example Shown VBA340.F120X = VFD with bypass, 480V, 40 hp, fused disconnect, NEMA 1, 2 contactors, and no reactors.
Product Ordering
V B A 3 4 0 . F 1 2 0 XExample Product Number
Model
VB = VFD with Bypass
Series
A = Conventional Bypass (Standard)
Voltage 1 = 208V 2 = 230 to 240V 3 = 380 to 480V 4 = 500 to 600V
HP Rating 0.5, 0.7, 1.0, 1.5, 2.0, 3.0, 4.0 5.0, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125
Disconnect
D = Disconnect F = Fused Connect
NEMA 1 = NEMA Type 1 Contractors 2 = 2 Contractors 3 = 3 Contractors Reactor 0 = None 3 = Line Reactor* L = Load Reactor* Placeholder X = Included with all part numbers. Options HA1 = High Amp rating
Table Note*Only one can be installed in bypass option enclosure.
If both are required, a separate enclosed reactor is required.
G-12
Specifications/Product OrderingVa
riabl
e Fr
eque
ncy
Driv
es
VFD0007R3
= Protective Shield
Depth8.3
(211)
12.0(305)
11.0(279)
11.0(279)
17.0(432)
36.0(914) 24.0
(610)
49.0(1245)
Depth9.7
(244)
12.0(305)
18.0(457)
Depth11.3 (287)
57.5(1461)
Depth11.3 (287)
66.5(1689)
48.0(1219)
12.0(305)
9.5(241)
12.0(305)
12.0(305)
18.0(457)
17.0(432)
Frame SizeA and B
Frame Size C
Frame Size D
Frame Size FFrame Size E
12.0(305)
12.0(305)
9.5(241)
12.0(305)
12.0(305)
12.0(305)
5.5(140)
12.0(305)
12.0(305)
12.0(305)
12.0(305)
5.5(140)
36.0(914)
36.0(914)
57.5(1460)
45.5(1156)
Depth17.4(442)
Dimensions shown
in inches (mm).
Dimensions
Dimensions
Frame Sizes/Weights
HP 321.51.7.5 5 7.5 403025201510 125100756050
kW 2.21.51.1.75.5.37 4 5.5 30221915117.5 9075554537
208/
230V
480V
575V FABC
HA1
- -
ABC
ABC
DE
F
F
DE
DE
SED2 Frame Sizes and Power Ranges
Frame Weights Sizes lb. (kg)
A 55 25
B 65 29
C 100 45
D 170 77
E 200 91
F 500 227
Weights by Frame Size
feat
ure
s
G-13www.sbt.siemens.com/hvp/components
Description Applications
Varia
ble
Freq
uenc
y D
rives
Variable Frequency Driveswith Electronic (E) Bypass Option
SED2
The E-Bypass Options are companion packages for the family of SED2 Variable Frequency Drives (VFDs).
E-Bypass • Enhanced visual interface for improved
monitoring and diagnostics
• E-Bypass guarantees continuous operation even if SED2 fails
• Electronic touch-sensitive keypad
• Standard built-in networking compatibility
• Service mode isolates drive from the control scheme
• Six relay outputs for indication of operation
• Fourteen LEDs indicate monitoring and operation
• Six digital inputs
• Remote start via networking
• Contactors electrically and mechanically interlocked.
2-Contactor: Output & Bypass• Overload protection in bypass mode
3-Contactor (optional): Input, Output, & Bypass 3-Contactor features provide:
• Drive test function
• Complete electrical isolation of drive
Input Device• Disconnect
• Fused disconnect (optional)
• Circuit breaker (optional)
• All doors are interlocked and padlockable
SED2 Variable Frequency Drives with Electronic (E) Bypass family.
Reactor Options
• Line reactor mounted in bypass option enclosure
• Line reactor (in NEMA 1 enclosure) supplied separately
• Load reactor mounted in bypass option enclosure
• Load reactor (in NEMA 1 enclosure) supplied separately
E-Bypass ControlAuto Bypass• Relay logic allows user to send the motor to bypass
mode based on the drive’s programmable relay.
• The drive’s programmable relay, typically set to fault, can be set up for applications that run full speed for an extended period of time.
Enable Input• Generally used for safety tie-ins; the motor will not
operate the drive or bypass when open.
Common Remote Start/Stop• Common remote start/stop can be used in both drive
and bypass mode.
Essential Services Mode• Also used for smoke purge; the motor goes to bypass
regardless of the selected mode.
• No call to stop will have an effect, including open safety or stop commands.
• Only turning the power off or opening this contact will stop the motor.
Important Note: VFD products are only available throught authorized distribution channels. To locate an authorized distributor, please contact a Siemens Building Technologies representative at: 1.888.593.7876.
Options
• LON Interface • Modbus Interface
• Advanced Operator Panel (AOP) Module
G-14
Specifications/Product OrderingVa
riabl
e Fr
eque
ncy
Driv
es
Electronic BypassInput Voltage (3-phase)
208V, 3 AC±10%. .................. 1/2 hp to 60 hp (2.3 amps to 154 amps)
230V, 3 AC±10%. .................. 1/2 hp to 60 hp (2.3 amps to 154 amps)
460V, 3 AC ±10%. ............... 1/2 hp to 125 hp (1.2 amps to 178 amps)
575V, 3 AC ±10%. .................. 1 hp to 125 hp (2.3 amps to 125 amps)
Digital Inputs
• Six Digital Inputs as follows:
• Remote start input
• Remote safety 1
• Remote safety 2
• Interlock start
• Essential services
• Overload trigger
Inputs require a contact closure capable of providing a low impedance path at currents less than 20 mA.
Relay/Digital Outputs
• Six Relay/Digital Outputs as follows:
• VFD fault
• Programmable output
• Drive select
• Bypass select
• Running on bypass
• Overload fault
Each relay has a maximum rating of 2A at 120V ac.
Temperature
Operating ..................................................... 14 to 104°F (-10 to +40°C)
Storage ......................................................-40 to +158°F (-40 to +70°C)
Humidity .................................................... 0 to 95% RH, non-condensing
Drive Specifications
Input Voltage and Power Ranges (3 phase), amps
200V to 240V, 3 ac ± 10%. .... 1/2 hp to 60 hp (2.3 amps to 154 amps)
380V to 480V, 3 ac ± 10%. .. 1/2 hp to 125 hp (1.2 amps to 178 amps)
500V to 600V, 3 ac ± 10%. ..... 1 hp to 125 hp (2.3 amps to 125 amps)
Input Frequency .................................................................47 Hz to 63 Hz
Output Frequency ..............................................................0 Hz to 150 Hz
Total Power Factor ............................................................................ ≥0.9
Displacement Power Factor ........................................................... ≥0.98
VFD Degree of Efficiency ...................................................... 96% to 97%
Switch-on Current .................................. Less than nominal input current
Auxiliary Supply 24V ....................... Glavanically separated, unregulated auxiliary supply (18V to 32V) 100 mA
Overload Capacity ...................................................110% for 60 seconds
Control Method ......................... Linear, parabolic and programmable V/f; and flux current control low-power mode
PWM Frequency ...........2k Hz to 16k Hz (adjustable in 2k Hz increments)
Fixed Frequencies ........................................................ 15 programmable
Skip Frequency Bands ................................................... 4 programmable
Setpoint Resolution ............................................................0.01 Hz digital 0.01 Hz serial 10 bit analog
Digital inputs (sink/source) ............................6: fully programmable and scalable isolated digital inputs, switchable
Analog inputs ................................ 2: 0 to 10 Vdc, 0/4 to 20 mA, can also be configured as digital inputs or Ni 1000 input
Relay Outputs .................................2: configurable 30 Vdc/5A (resistive), 250 Vac/2A (inductive)
Analog Outputs ..................................2: programmable (0/4 mA to 20 mA or 0 Vdc to 10 Vdc)
Serial Interface .................................................RS-485 transmission rate: Up to 38.4k baud
Protocols: Siemens Building Technologies, Inc., P1 and Johnson, N2
Protection Level
IP20 ............NEMA Type 1 with protective shield and gland plate installed
IP54 ......................................NEMA Type 12 (400V and 500V series only)
Temperature Ranges
Operating ................................................. 14°F to 104°F (-10 to +40°C)
Storage ......................................................-40 to +158°F (-40 to +70°C)
Humidity ........................................................... 95% RH, non-condensing
Operational Altitudes ................ Up to 3280 ft. (1000 m) above sea level without derating
Protection Features Under-voltage .................................................................Stall prevention Over-voltage ......................................................................Locked motor Overload ..............................................Motor overtemperature l2 t, PTC Ground fault ............................................................... Over-temperature Short circuit ....................................................Parameter PIN protection
Agency Standards ................................................................................UL cUL
CE Conformity ............................................................Conformity with EC Low Voltage Directive 73/23/EECOptions • LON Interface • Modbus Interface • AOP Module
Specifications
Page22
Page22
G-15www.sbt.siemens.com/hvp/components
Dimensions
Varia
ble
Freq
uenc
y D
rives
Example Product Number V B E 3 4 0 . F 1 2 0 X
Model
VB = VFD with Bypass
Series E = Electronic Bypass
Voltage 1 = 208V 2 = 230 to 240V 3 = 380 to 480V 4 = 500 to 600V
HP Rating 0.5, 0.7, 1.0, 1.5, 2.0, 3.0, 4.0, 5.0, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75,100, 125 Disconnect B = Circuit Breaker D = Disconnect F = Fused Disconnect
NEMA 1 = NEMA Type 1 Contactors 2 = 2 Contactors 3 = 3 Contactors Reactor 0 = None 3 = Line Reactor* L = Load Reactor* Placeholder X = Included with all part numbers. Options HA1 = High Amp Rating
Product Ordering
Example Shown VBE340.F120X = SED2 with E-Bypass, 480V, 40 hp, fused disconnect, NEMA 1, 2 contactors, and no reactors.
Table Notes*Only one reactor type can be installed in the bypass enclosure.
If both are required, a separate enclosed reactor is required.
HA1 option is a bypass package rated to 178 amps at 480 Vac. Though it does not meet NEC for 150 hp at 180 amps, the package will control a high percentage of 150 hp motors.
G-16
Specifications/Product OrderingVa
riabl
e Fr
eque
ncy
Driv
esDimensions
Dimensions shown in inches (mm).
DepthWith
Handle9.6 (24)
DepthWith
Handle12.2 (31)
DepthWith
Handle9.6 (24)
13.2(34)
34(86)
48(122)
11.5(29)
Frame SizeA and B
Frame Size C
12.4(31)
10.5 TYP(27)
10.6(27)
11 TYP(28)
20.8(53)
DepthWith
Handle10.4 (26)
57.5(146)
Frame Size D
19.9(51)
11.5 TYP(29)
1.5(3.8)
1.5(3.8)
2(5)
2(5)
4(10)
3.4(8.6)
57.5(146)
45.5(116)
Depth17.4(44)
Frame Size FFrame Size E
20.8(53)
58.5(149)
19.9(51)
10 TYP(25)
5.5(14)
3(7.6)
2.9(7.4)
2.9(7.4)
1(2.5)
VFD0127R1
= Protective Shield
Dimensions
Dimensions
Frame Sizes/Weights
HP 321.51.7.5 5 7.5 403025201510 125100756050
kW 2.21.51.1.75.5.37 4 5.5 30221915117.5 9075554537
208/
230V
480V
575V FABC
HA1
- -
ABC
ABC
DE
F
F
DE
DE
SED2 Frame Sizes and Power Ranges
Frame Weights Sizes lb. (kg)
A 45 20
B 55 25
C 75 34
D 150 68
E 180 82
F 470 213
Weights by Frame Size
feat
ure
s
G-17www.sbt.siemens.com/hvp/components
Description Applications
Varia
ble
Freq
uenc
y D
rives
Variable Frequency DrivesNEMA Type 3R Bypass
SED2
The NEMA Type 3R Bypasses are companion packages for the family of SED2 Variable Frequency Drives. NEMA Type 3R enclosed bypasses are manufactured for outdoor locations that are not in direct sunlight. The 3R rating provides a degree of protection to the enclosed SED2 VFD and electrical control components. A heater is supplied to protect against condensation. The standard package is rated to 104°F (40°C). A high temperature package, rated to 122°F (50°C), is available.
Bypass Power2-Contactor: Output and Bypass• Overload protection in bypass mode.
• Step-down transformer with fused primary and secondary.
• Contactors electrically and mechanically interlocked.
3-Contactor (optional): Input, Output, and Bypass In addition to the 2-contactor features, 3-contactor features provide:
• Drive test function.
• Complete electrical isolation of drive.
Input Device• Disconnect switch.
• Fused disconnect (optional).
• All doors are interlocked and padlockable.
Reactor Options• Line reactor mounted in bypass enclosure.
• Line reactor supplied separately (in NEMA Type 3R enclosure).
• Load reactor (in NEMA Type 3R enclosure) supplied separately.
SED2 Variable Frequency Drives NEMA Type 3R Bypass Family.
Bypass ControlAuto Bypass• Relay logic allows user to send the motor to bypass
mode based on the drive’s programmable relay.
Enable Input
• Generally used for safety tie-ins; the motor will not operate the drive or bypass when open.
Common Remote Start/Stop• Can be used in both drive and bypass mode.
Essential Services Mode• Typically used for smoke purge; the motor goes to
bypass regardless of the selected mode.
• No call to stop will have an effect, including open safety or stop commands.
• Only turning the power off or opening this contact will stop the motor.
Bypass – Door Mounted Control Devices2-Contactor Units• Drive-Off-Bypass selector and Bypass pilot light
3-Contactor Units• Drive-Off-Bypass selector
• Bypass pilot light
• Drive Test On-Off selector
The SED2 is designed specifically for HVAC applications and supports a variety of digital and analog I/O and pro-vides built-in PID features to control pumps and fans.
Important Note: VFD products are only available throught authorized distribution channels. To locate an authorized distributor, please contact a Siemens Building Technologies representative at: 1.888.593.7876.
Options
• LON Interface • Modbus Interface
• Advanced Operator Panel (AOP) Module
G-18
Specifications/Product OrderingVa
riabl
e Fr
eque
ncy
Driv
es
NEMA Type 3R Bypass
Input Voltage (3 phase) ............................................... 208V, 3 AC ±10% 230V, 3 AC ±10% 460V, 3 AC ±10% 575V, 3 AC ±10%
Temperature
Operating ...............14°F to 104°F (-10 to +40°C), HT1 to 122°F (50°C)
Storage .................................................. -40°F to +158°F (-40 to +70°C)
High-Temperature Model
Operating ..................................................... 14 to 122°F (-10 to +50°C)
Storage ......................................................-40 to +158°F (-40 to +70°C)
Humidity .................................................... 0 to 95% RH, non-condensing
Drive Specifications
Input Voltage and Power Ranges (3 phase), amps
200V to 240V, 3 ac ± 10%. .... 1/2 hp to 60 hp (2.3 amps to 154 amps)
380V to 480V, 3 ac ± 10%. .. 1/2 hp to 125 hp (1.2 amps to 178 amps)
500V to 600V, 3 ac ± 10%. ..... 1 hp to 125 hp (2.3 amps to 125 amps)
Input Frequency .................................................................47 Hz to 63 Hz
Output Frequency ..............................................................0 Hz to 150 Hz
Total Power Factor ............................................................................ ≥0.9
Displacement Power Factor ........................................................... ≥0.98
VFD Degree of Efficiency ...................................................... 96% to 97%
Switch-on Current .................................. Less than nominal input current
Auxiliary Supply 24V ....................... Glavanically separated, unregulated auxiliary supply (18V to 32V) 100 mA
Overload Capacity ...................................................110% for 60 seconds
Control Method ......................... Linear, parabolic and programmable V/f; and flux current control low-power mode
PWM Frequency ...........2k Hz to 16k Hz (adjustable in 2k Hz increments)
Fixed Frequencies ........................................................ 15 programmable
Skip Frequency Bands ................................................... 4 programmable
Setpoint Resolution ............................................................0.01 Hz digital 0.01 Hz serial 10 bit analog
Digital inputs (sink/source) ............................6: fully programmable and scalable isolated digital inputs, switchable
Analog inputs ................................ 2: 0 to 10 Vdc, 0/4 to 20 mA, can also be configured as digital inputs or Ni 1000 input
Relay Outputs .................................2: configurable 30 Vdc/5A (resistive), 250 Vac/2A (inductive)
Analog Outputs ..................................2: programmable (0/4 mA to 20 mA or 0 Vdc to 10 Vdc)
Serial Interface .................................................RS-485 transmission rate: Up to 38.4k baud
Protocols: Siemens Building Technologies, Inc., P1 and Johnson, N2
Protection Level
IP20 ............NEMA Type 1 with protective shield and gland plate installed
IP54 ......................................NEMA Type 12 (400V and 500V series only)
Temperature Ranges
Operating ................................................. 14°F to 104°F (-10 to +40°C)
Storage ......................................................-40 to +158°F (-40 to +70°C)
Humidity ........................................................... 95% RH, non-condensing
Operational Altitudes ................ Up to 3280 ft. (1000 m) above sea level without derating
Protection Features Under-voltage .................................................................Stall prevention Over-voltage ......................................................................Locked motor Overload ..............................................Motor overtemperature l2 t, PTC Ground fault ............................................................... Over-temperature Short circuit ....................................................Parameter PIN protection
Agency Standards ................................................................................UL cUL
CE Conformity ............................................................Conformity with EC Low Voltage Directive 73/23/EECOptions • LON Interface • Modbus Interface • AOP Module
Specifications
Page22
Page22
G-19www.sbt.siemens.com/hvp/components
Dimensions
Varia
ble
Freq
uenc
y D
rives
Product Ordering
Example Product Number V B A 4 4 0 . D 3 2 0 X H T 1
Model
VB = VFD with Bypass
Series A = Conventional Bypass (Standard)
Voltage 1 = 208V* 2 = 230 to 240V 3 = 380 to 480V 4 = 500 to 600V
HP Rating 0.5, 0.7, 1.0, 1.5, 2.0, 3.0, 4.0, 5.0, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75,100, 125 Disconnect D = Disconnect F = Fused Disconnect
NEMA 3 = NEMA Type 3R Contactors 0 = None 2 = 2 Contactors 3 = 3 Contractors Reactor 0 = None 3 = Line Reactor* L = Load Reactor* Placeholder X = Included with all part numbers. Options HA1 = High Amp Rated HT1 = High Temperature Rating (NEMA 3R only)**
Table Note*208 Vac and 230/240 Vac to 3 hp are all HT1. 480 Vac to 5 hp are all HT1
**HT1 (122°F, 50°C) not available for all ratings.
G-20
Specifications/Product OrderingVa
riabl
e Fr
eque
ncy
Driv
es
Dimensions shown in inches (mm).
Dimensions
Depth = 11-1/2 (292)
Enclosure ABC Enclosure DE
Depth = 12-1/2 (318)
Enclosure F
Depth = 16-1/2 (419)
Mounting clearance for properairflow: leave 1 foot (305 mm) betweenthe NEMA Type 3R bypass and any adjacentsolid structure that is not used for mounting purposes.
Leave 3 feet (914 mm) between the NEMA Type 3R bypassand any other NEMA Type 3R Bypass or VFD.
34 (864)
75(1905)
74-1/8(1882)
58 (1473)
42 (1067)
46 (1169)
57(1448)
56-1/8(1425)
30 (762)
18 (457)
28-1/2 (724)
30 (762)
DimensionsDimensions
Dimensions
Frame Sizes/Weights
HP 321.51.7.5 5 7.5 403025201510 125100756050
kW 2.21.51.1.75.5.37 4 5.5 30221915117.5 9075554537
208/
230V
480V
575V FABC
HA1
- -
ABC
ABC
DE
F
F
DE
DE
Non-HT1 Enclosure Sizes and Power Ranges
HT1 Enclosure Sizes and Power Ranges
HP 4321.51.7.5 5 7.5 403025201510 125100756050
kW 32.21.51.1.75.5.37 4 5.5 30221915117.5 9075554537
480V
575V ABC
ABC
DE
208/
230V ABC F
DE F
DE F
VFD0180R1
Frame Weights Sizes lb. (kg)
ABC 130 59
DE 300 136
F 550 249
Weights by Frame Size
G-21www.sbt.siemens.com/hvp/components
Ordering & InformationThis section contains important ordering information, including:
• Mounting Hardward
• Filter Kits
• Accessories
• Options
to complement its complete line of VFDs.
To lookup and order acces-sories or service kits:
1. Use the table of contents to locate the correct product.
2. Turn to that page and locate the product using the left hand tab and the type of device using the right-hand tab on the table.
3. Locate the product needed and the appropriate part number.
For technical or instal-lation instructions and locations, visit the web site at: www.sbt. siemens.com/hvp/components.
For further assistance, please contact a Siemens Building Technologies representative at: 1.888.593.7876.
Variable Frequency Drives Accessories & Service Kits
ProductProduct Page #
Varia
ble
Freq
uenc
y D
rives
SED2
Software G-22
Mounting Hardware G-22
Filter Kits G-22
Accessories/Options G-22
G-22
Accessories and Service KitsVa
riabl
e Fr
eque
ncy
Driv
es
Description Quantity Part No.
SED
2 Software
Filter Kits
Gland Plates. (included with NEMA Type 1)
• Frame A 1 SED2-GL-A
• Frame B 1 SED2-GL-B
• Frame C 1 SED2-GL-C
Protection Shield. (included with NEMA Type 1)
• Frame A 1 SED2-PS-A
• Frame B 1 SED2-PS-B
• Frame C 1 SED2-PS-C
• Frames D, E 1 SED2-PS-DE
NEMA Type 1 and 3R Enclosed Reactors. Contact Sales Partners.
NEMA Type 3R Floor Mounting Kit. 1 994-809
• Frames A, B, C
BOP/AOP Door Mounting Kits.
• BOP/AOP Single Inverter 1 SED2-DOOR-KIT1
• AOP Multi-Inverter 1 SED2-DOOR-KIT2
EMC Filter Kit.
• For use with E-Bypass Frames A & B 1 994-975
• For use with E-Bypass Frame C 1 994-976
• For use with E-Bypass Frames D & E 1 994-977
• For use with E-Bypass Frame F 1 994-978
• For use with NEMA 3R Frame A, B, C 1 994-830
• For use with NEMA 3R Frames D, E, F 1 994-831
Operator Panel.
• Basic Operator Panel (included with all SED2s) 1 SED2-BOP1
• Advanced Operator Panel (AOP) 1 SED2-AOP1
LON Interface Option. 1 SED2-LONI/F
Modbus Interface Cable. 1 SED2-MODBUS1
Converts VFD’s USS bus to Modbus RTU.
Accessories/ O
ptions
PC Kit. 1 SED2-PC-KIT EasyComm Drive 1 SED2-EASYCOMM Programming Software.
Mounting H
ardware
G-23www.sbt.siemens.com/hvp/components
Varia
ble
Freq
uenc
y D
rives
Notes
G-24
Varia
ble
Freq
uenc
y D
rives
Notes