Date post: | 24-May-2018 |
Category: |
Documents |
Upload: | trinhtuyen |
View: | 223 times |
Download: | 4 times |
Lower Capital Cost Installed (vs Primary/Secondary)No secondary pumps/piping/valves/electrical to buy and install
Fewer piping and electrical connections – less field labor
No large common pipe, but smaller bypass pipe/valve/flow meter/controls
Lower CHW Pumping Energy
Potential Savings, may reduce pump horsepower and initial cost.Reference ARTI (Air Conditioning & Refrigeration Technology Institute)
Estimated energy savings of 3 to 8 percent
Estimating initial cost saving of 4 to 8 percent
Estimating life cycling saving cost 3 to 5 percent
Variable Primary Flow Only (VPF) Advantages
Smaller Footprint (vs Primary/Secondary)More space available for better access to the other equipment
Higher ReliabilityFewer mechanical components
Any pump can serve any chiller
Variable Primary Flow Only (VPF) Advantages
Potentially higher PSID rated 2-Way valves in systemRequires more robust (complex and calibrated) control systemRequires coordinated control of chillers, isolation valves, and pumpsin sequencingPotentially longer commissioning time and start-up (ref ASHRAETaylor article)Requires greater operator sophisticationSudden flow variation through the chiller
More of an issue when additional machines are staged on
More complexity with bypass control
Variable Primary Flow Only (VPF) Disadvantages
Primary/Secondary System
Constant SpeedPrimary Pumps
Variable SpeedSecondary Pumps
Common Pipe
Typicalloadwithtwowayvalves
Primary/Secondary System at Design
54.0°F
54.0°F
54.0°F
44.0°F
44.0°F
44.0°F
Primary Pumps
360 GPM Each
1080 GPM @ 54.0 °F
Secondary Pumps
1080 GPM @ 44.0 °F
TypicalCoil
No flow
44.0°F
54.0°F
150 ton chillers360 GPM Each54.0-44.0°F
1080 GPM @ 54.0 °F
Primary/Secondary System at Part Load
51.5°F
51.5°F
51.5°F
44.0°F
44.0°F
44.0°F
Primary Pumps
360 GPM Each
1080 GPM @ 51.5 °F
Secondary Pumps
810 GPM @ 44.0 °F
TypicalCoil
44.0°F
54.0°F
270 GPM @ 44.0 °F
810 GPM @ 54.0 °F
75% System Load
Primary/Secondary System
54.0°F
54.0°F
44.0°F
44.0°F
Primary Pumps
360 GPM Each
720 GPM @ 54.0 °F
Secondary Pumps
720 GPM @ 44.0 °F
TypicalCoil
44.0°F
54.0°F
No Flow
720 GPM @ 54.0 °F
OFF 67% System LoadClean Coils
Primary/Secondary System
53.0°F
53.0°F
44.0°F
44.0°F
Primary Pumps
360 GPM Each
720 GPM @ 53.0 °F
Secondary Pumps
792 GPM @ 44.8 °F
TypicalCoil
44.8°F
53.0°F
72 GPM @ 53.0 °F
792 GPM @ 53.0 °F
OFF 67% System LoadDirty Coils
Primary/Secondary System
51.9°F
51.9°F
44.0°F
44.0°F
Primary Pumps
360 GPM Each
720 GPM @ 51.9 °F
Secondary Pumps
900 GPM @ 44.8 °F
TypicalCoil
44.8°F
51.9°F
180 GPM @ 51.9 °F
900 GPM @ 51.9 °F
OFF 67% System LoadDirty Coils
Primary/Secondary System
Variable Primary System
Secondary Pumps
Primary Pumps
Primary Pumps
Flow Meter
BypassValve
Automatic Isolation Valve
Typical load with 2 way valve
Typical load with 2 way valve
Variable Primary System at Design
54.0°F
54.0°F
54.0°F
44.0°F
44.0°F
44.0°F
Primary Pumps
360 GPM Each
1080 GPM @ 56.0 °F
1080 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassClosed
150 ton chillers360 GPM Each54.0-44.0°F
Typicalloadwithtwowayvalves
Variable Primary System – Part Load
54.0°F
54.0°F
54.0°F
44.0°F
44.0°F
44.0°F
Primary Pumps
270 GPM Each
810 GPM @ 54.0 °F
810 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalve
75% System Load
810 GPM @ 54.0 °F
Variable Primary System – Part Load
54.0°F
54.0°F
44.0°F
44.0°F
Primary Pumps
180 GPM Each
540 GPM @ 54.0 °F
540 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalve
50% System LoadChiller off
540 GPM @ 54.0 °F
Variable Primary System – Min Flow (120 gpm each)
51.5°F
44.0°F
Primary Pumps
120 GPM (oneoperating)
120 GPM @ 51.5 °F
90 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassOpen
Typicalloadwithtwowayvalve
System flow below chillerminimum flow
Chiller off
Chiller off
Closed
Closed
30 GPM @ 44.0
90 GPM @ 54.0 °FFlow meter
Pumpsoff
Variable Primary System – Min Flow (120 gpm each)
51.5°F
44.0°F
Primary Pumps
120 GPM (oneoperating)
120 GPM @ 51.5 °F
90 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassOpen
Typicalloadwithtwowayvalve
Pumps maintain system pressure
Bypass maintains minimum flow
Chiller off
Chiller off
Closed
Closed
30 GPM @ 44.0
90 GPM @ 54.0 °FFlow meter
Pumpsoff
Designing a VPF Bypass
Size for minimum flow through one chiller
Valve head ratings must be higher than pump dead head
Linear characteristic - valve position % equals flow %
Fast actuator
Valve control range 100:1
Flow meter controls bypass to maintain chiller minimum flow
Selecting a VPF Flow Meter for Small Tonnage Systems
Best accuracy job can afford
Minimum +/- 5% at evaporator minimum flow
Set bypass to open when flow equals minimum plus 2 times flowmeter accuracy rating
Example: 120 gpm minimum, flow meter +/- 5%, set minimum flowat 120 + 120*10% = 132 gpm
Calibrate flow meter at least as often as manufacturer recommends
Buy the best
Selecting VPF AHU Control Valves
All valve pressure ratings greater than pump dead head
Sized by pressure
% valve position equals % coil capacity
Control range 200:1
Selecting VPF Chiller Isolation Valves
All valve pressure ratings greater than pump dead head
Linear characteristic - valve position % equals flow %
Modulating valve with slow actuator
Variable Primary System (1 chiller running)
54.0°F
44.0°F
Primary Pumps
120 GPM Each
360 GPM @ 546.0 °F
360 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalve360 GPM
Variable Primary System (Staging on secondchiller)
54.0°F
45.0°F
Primary Pumps
132 GPM Each
396 GPM @ 55.0 °F
396 GPM @ 45.0 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalve396 GPM
Need to add chiller
Variable Primary System (Open isolation valve)
55.0°F
35.0°F
Primary Pumps
132 GPM Each
396 GPM @ 55.0 °F
396 GPM @ 45.0 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalve198 GPM
198 GPM55.0°F55.0
°F
Variable Primary System (Open isolation valve)
55.0°F
35.0°F
Primary Pumps
132 GPM Each
396 GPM @ 55.0 °F
396 GPM @ 45.0 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalve198 GPM
198 GPM55.0°F55.0
°F
LCHWT approaches 35F
LWT Cutout at 40F
Off goes chiller 1
Variable Primary System (Open isolation valve)
55.0°F
40.0°F
Primary Pumps
132 GPM Each
396 GPM @ 55.0 °F
396 GPM @ 45.0 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalve264 GPM
132 GPM55.0°F55.0
°F
Open slowly
Chiller 2 comes on when flowexceeds minimum
Chiller 1 unloads to maintain setpoint
Variable Primary System (Open isolation valve)
55.0°F
42.0°F
Primary Pumps
132 GPM Each
396 GPM @ 55.0 °F
396 GPM @ 45.9 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalve276 GPM
120 GPM55.0°F55.0
°F
Open to change flow 36gpm/min
Chiller 2 comes on when flow is120gpm – in 3 min 20 sec
Chiller 1 is still producing 100%capacity
Variable Primary System (Open isolation valve)
54.0°F
44.0°F
Primary Pumps
132 GPM Each
396 GPM @ 54.0 °F
396 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalve198 GPM
198 GPM44.0°F54.0
°F
Both valves fully open
Flow equalizes
Chillers modulate to maintainchilled water set point
Staging on Chiller 2 in VPF Systems
Maintain minimum flow through the operating chiller
Avoid sudden changes in flow anywhere in the system
Prefer schemes that work when bringing on any chiller
Setting Flow Rate of Change
Start with 10% of design flow per minute
Most small tonnage chillers can handle faster changes
If the project requires rapid flow changes, contact applicationengineering
If problems occur during operation, adjust the rate
Variable Primary System – Handling RapidlyDecreasing Loads
54.0°F
54.0°F
54.0°F
44.0°F
44.0°F
44.0°F
Primary Pumps
360 GPM Each
1080 GPM @ 56.0 °F
1080 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassClosed
150 ton chillers360 GPM Each54.0-44.0°F
Typicalloadwithtwowayvalves
Variable Primary System – Handling RapidlyDecreasing Loads
54.0°F
54.0°F
54.0°F
44.0°F
44.0°F
44.0°F
Primary Pumps
360 GPM Each
1080 GPM @ 44.0 °F
0 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassOpen
150 ton chillers360 GPM Each54.0-44.0°F
Typicalloadwithtwowayvalves
Variable Primary System – Handling RapidlyDecreasing Loads
54.0°F
54.0°F
54.0°F
44.0°F
44.0°F
44.0°F
Primary Pumps
324 GPM Each
972 GPM @ 44.0 °F
972 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalves
Close the closest valve first
Variable Primary System – Handling RapidlyDecreasing Loads
54.0°F
54.0°F
54.0°F
44.0°F
44.0°F
44.0°F
Primary Pumps
288 GPM Each
864 GPM @ 44.0 °F
864 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalves
Close the next closest valve
Variable Primary System – Handling RapidlyDecreasing Loads
54.0°F
54.0°F
54.0°F
44.0°F
44.0°F
44.0°F
Primary Pumps
252 GPM Each
756 GPM @ 44.0 °F
756 GPM @ 44.0 °F
AutomaticIsolation Valve
BypassClosed
Typicalloadwithtwowayvalves
Close the next closest valve