Operating Instructions Radar sensor for continuous level measurement of bulk solids VEGAPULS 68 4 … 20 mA/HART - two-wire Document ID: 36535
Transcript
Page 1: Vegapuls 68

Operating InstructionsRadar sensor for continuous level measurement of bulk solids

VEGAPULS 684 … 20 mA/HART - two-wire

Document ID: 36535

Page 2: Vegapuls 68

2

Contents

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Contents1 About this document

1.1 Function ........................................................................................................................... 41.2 Target group ..................................................................................................................... 41.3 Symbols used................................................................................................................... 4

2 For your safety2.1 Authorised personnel ....................................................................................................... 52.2 Appropriate use ................................................................................................................ 52.3 Warning about incorrect use ............................................................................................. 52.4 General safety instructions ............................................................................................... 52.5 CE conformity ................................................................................................................... 62.6 NAMUR recommendations .............................................................................................. 62.7 Radio license for Europe .................................................................................................. 62.8 Radio license for USA/Canada ......................................................................................... 62.9 Environmental instructions ............................................................................................... 7

3 Product description3.1 Configuration .................................................................................................................... 83.2 Principle of operation........................................................................................................ 93.3 Packaging, transport and storage ................................................................................... 103.4 Accessories and replacement parts ............................................................................... 10

4 Mounting4.1 General instructions ....................................................................................................... 134.2 Mounting preparations ................................................................................................... 144.3 Mounting preparations - Parabolic antenna .................................................................... 154.4 Mounting instructions ..................................................................................................... 16

5 Connecting to power supply5.1 Preparing the connection ............................................................................................... 295.2 Connecting ..................................................................................................................... 305.3 Wiring plan, single chamber housing.............................................................................. 325.4 Wiring plan, double chamber housing ............................................................................ 325.5 Wiring plan, double chamber housing Ex d ia ................................................................ 345.6 Double chamber housing with DIS-ADAPT .................................................................... 355.7 Wiring plan - version IP 66/IP 68, 1 bar ........................................................................... 365.8 Switch-on phase............................................................................................................. 36

6 Set up with the display and adjustment module6.1 Insert display and adjustment module ............................................................................ 376.2 Adjustment system ......................................................................................................... 386.3 Measured value indication - Selection national language ............................................... 396.4 Parameter adjustment .................................................................................................... 406.5 Saving the parameter adjustment data ........................................................................... 59

7 Setup with PACTware7.1 Connect the PC .............................................................................................................. 607.2 Parameter adjustment .................................................................................................... 617.3 Saving the parameter adjustment data ........................................................................... 62

8 Set up with other systems8.1 DD adjustment programs ............................................................................................... 63

Page 3: Vegapuls 68

3

Contents

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

8.2 Field Communicator 375, 475 ........................................................................................ 63

9 Diagnosis, asset management and service9.1 Maintenance .................................................................................................................. 649.2 Measured value and event memory ............................................................................... 649.3 Asset Management function ........................................................................................... 659.4 Rectify faults ................................................................................................................... 699.5 Exchanging the electronics module ................................................................................ 729.6 Software update ............................................................................................................. 739.7 How to proceed if a repair is necessary .......................................................................... 73

10 Dismount10.1 Dismounting steps.......................................................................................................... 7410.2 Disposal ......................................................................................................................... 74

11 Supplement11.1 Technical data ................................................................................................................ 7511.2 Dimensions .................................................................................................................... 83

Safety instructions for Ex areasTakenoteoftheExspecificsafetyinstructionsforExapplications.These instructions are attached as documents to each instrument with Ex approval and are part of the operating instructions manual.

Editing status: 2015-06-17

Page 4: Vegapuls 68

4

1 About this document

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

1 About this document

1.1 FunctionThis operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc-tionsformaintenanceandfaultrectification.Pleasereadthisinforma-tion before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.

1.2 Target groupThis operating instructions manual is directed to trained specialist personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbols usedInformation, tip, noteThis symbol indicates helpful additional information.Caution: If this warning is ignored, faults or malfunctions can result.Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result.Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.

Ex applicationsThis symbol indicates special instructions for Ex applications.

• ListThe dot set in front indicates a list with no implied sequence.

→ ActionThis arrow indicates a single action.

1 Sequence of actionsNumbers set in front indicate successive steps in a procedure.

Battery disposalThis symbol indicates special information about the disposal of bat-teries and accumulators.

Page 5: Vegapuls 68

5

2 For your safety

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

2 For your safety

2.1 Authorised personnelAll operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.During work on and with the device the required personal protective equipment must always be worn.

2.2 Appropriate useVEGAPULS 68 is a sensor for continuous level measurement.Youcanfinddetailedinformationabouttheareaofapplicationinchapter "Product description".Operational reliability is ensured only if the instrument is properly usedaccordingtothespecificationsintheoperatinginstructionsmanual as well as possible supplementary instructions.

2.3 Warning about incorrect useInappropriate or incorrect use of the instrument can give rise to application-specifichazards,e.g.vesseloverfillordamagetosystemcomponents through incorrect mounting or adjustment. Also the pro-tectivecharacteristicsoftheinstrumentcanbeinfluenced.

2.4 General safety instructionsThis is a state-of-the-art instrument complying with all prevailing regulations and guidelines. The instrument must only be operated in a technicallyflawlessandreliablecondition.Theoperatorisresponsiblefor the trouble-free operation of the instrument.During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regula-tions.The safety instructions in this operating instructions manual, the na-tional installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user.For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi-traryconversionsormodificationsareexplicitlyforbidden.The safety approval markings and safety tips on the device must also be observed.Depending on the instrument version, the emitting frequencies are in the C, K or W band range. The low emitting frequencies are far below the internationally approved limit values. When used correctly, the device poses no danger to health.

Page 6: Vegapuls 68

6

2 For your safety

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

2.5 CE conformityThedevicefulfillsthelegalrequirementsoftheapplicableECguide-lines.ByaffixingtheCEmarking,weconfirmsuccessfultestingoftheproduct.YoucanfindtheCECertificateofConformityinthedownloadsectionof our homepage.

Electromagnetic compatibilityInstruments in four-wire or Ex-d-ia version are designed for use in an industrial environment. Nevertheless, electromagnetic interference from electrical conductors and radiated emissions must be taken into account, as is usual with class A instruments according to EN 61326-1.Iftheinstrumentisusedinadifferentenvironment,theelectromag-netic compatibility to other instruments must be ensured by suitable measures.

2.6 NAMUR recommendationsNAMUR is the automation technology user association in the process industry in Germany. The published NAMUR recommendations are acceptedasthestandardinfieldinstrumentation.ThedevicefulfillstherequirementsofthefollowingNAMURrecom-mendations:

• NE 21 – Electromagnetic compatibility of equipment• NE 43 – Signal level for malfunction information from measuring

transducers• NE53–Compatibilityoffielddevicesanddisplay/adjustment

components• NE107–Self-monitoringanddiagnosisoffielddevicesFor further information see www.namur.de.

2.7 Radio license for EuropeThe instrument is approved according to EN 302372-1/2 (2006-04) for use in closed vessels.

2.8 Radio license for USA/CanadaThe instrument is in conformity with part 15 of the FCC regulations. Take note of the following two regulations:

• This device may not cause interference, and• This device must accept any interference, including interference

that may cause undesired operation of the device

Modificationsnotexpresslyapprovedbythemanufacturerwillleadtoexpiry of the operating licence according to FCC/IC.The instrument is in conformity with RSS-210 of the IC regulations.The instrument may only be used in closed vessels made of metal, concrete,orfibre-reinforcedplastic.

Page 7: Vegapuls 68

7

2 For your safety

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

2.9 Environmental instructionsProtection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental pro-tection.Theenvironmentmanagementsystemiscertifiedaccordingto DIN EN ISO 14001.Pleasehelpusfulfillthisobligationbyobservingtheenvironmentalinstructions in this manual:

• Chapter "Packaging, transport and storage"• Chapter "Disposal"

Page 8: Vegapuls 68

8

3 Product description

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

3 Product description

3.1 ConfigurationThetypelabelcontainsthemostimportantdataforidentificationanduse of the instrument:

2

1

14

15

16

17

13

12

11

5

3

6

4

78910

Fig. 1: Layout of the type label (example)1 Instrument type2 Product code3 Approvals4 Power supply and signal output, electronics5 Protection rating6 Measuring range7 Process and ambient temperature, process pressure8 Material, wetted parts9 Hardware and software version10 Order number11 Serial number of the instrument12 Data-Matrix-Code for smartphone app13 Symbol of the device protection class14 ID numbers, instrument documentation15 Reminder to observe the instrument documentation16 NotifiedauthorityforCEmarking17 Approval directive

The type label contains the serial number of the instrument. With it youcanfindthefollowinginstrumentdataonourhomepage:

• Product code (HTML)• Delivery date (HTML)• Order-specificinstrumentfeatures(HTML)• Operating instructions and quick setup guide at the time of ship-

ment (PDF)• Order-specificsensordataforanelectronicsexchange(XML)• Testcertificate(PDF)-optionalGo to www.vega.com, "VEGATools" and "Instrument search". Enter the serial number.Alternatively, you can access the data via your smartphone:

Type label

Serial number - Instru-ment search

Page 9: Vegapuls 68

9

3 Product description

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

• Download the smartphone app "VEGATools" from the "Apple App Store" or the "GooglePlayStore"

• Scan the Data Matrix code on the type label of the instrument or• Enter the serial number manually in the app

This operating instructions manual applies to the following instrument versions:

• Hardware version from 2.1.0• Software version from 4.5.1

The scope of delivery encompasses:

• Radar sensor• Documentation

– Quick setup guide VEGAPULS 68 – Instructions for optional instrument features – Ex-specific"Safety instructions" (with Ex versions) – ifnecessary,furthercertificates

• DVD "Software & Documents", containing – Operating instructions – Safety instructions – PACTware/DTM Collection – Driver software

Information:In the operating instructions manual, the optional instrument features are described. The respective scope of delivery results from the order specification.

3.2 Principle of operationThe VEGAPULS 68 is a radar sensor for continuous measurement of bulk solids also under arduous process conditions and large measur-ing ranges. It the ideal solution for level measurement in high silos, largebunkers,stonecrushersandmeltingfurnaces.Withdifferentantenna versions and materials, this sensor is the optimum solution for virtually all applications and processes.The instrument is also suitable for applications in liquids.Dependentontheapplicationrange,differentversionsareused:

• Small silos and vessels, measurement of virtually all bulk solids: Horn antenna

• Largesilosandvessels,measurementofbulksolidswithlowεr value: Parabolic antenna

• Liquids: Parabolic antenna

Theinstrumentcanbeusedwithproductswithanεrvalue≥1.5.Theactually achievable value depends on the measuring conditions and the antenna system.

The antenna of the radar sensor emits short radar pulses with a durationofapprox.1ns.Thesepulsesarereflectedbytheproductand received by the antenna as echoes. The transit time of the radar

Scope of this operating instructions manual

Scope of delivery

Application area

Functional principle

Page 10: Vegapuls 68

10

3 Product description

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

pulses from emission to reception is proportional to the distance and hence to the level. The determined level is converted into an appropri-ate output signal and outputted as measured value.

3.3 Packaging, transport and storageYour instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test based on ISO 4180.The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.

Transport must be carried out in due consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.

The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or con-cealed defects must be appropriately dealt with.

Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.Unless otherwise indicated, the packages must be stored only under the following conditions:

• Not in the open• Dry and dust free• Not exposed to corrosive media• Protected against solar radiation• Avoiding mechanical shock and vibration

• Storage and transport temperature see chapter "Supplement - Technicaldata-Ambientconditions"

• Relative humidity 20 … 85 %

3.4 Accessories and replacement partsThe display and adjustment module PLICSCOM is used for measured value indication, adjustment and diagnosis. It can be inserted into the sensor or the external display and adjustment unit and removed at any time.Youcanfindfurtherinformationintheoperatinginstructions"Display and adjustment module PLICSCOM" (Document-ID 27835).

The interface adapter VEGACONNECT enables the connection of communication-capable instruments to the USB interface of a PC. For parameter adjustment of these instruments, the adjustment software PACTware with VEGA-DTM is required.Youcanfindfurtherinformationintheoperatinginstructions"Interface adapterVEGACONNECT" (Document-ID 32628).

Packaging

Transport

Transport inspection

Storage

Storage and transport temperature

PLICSCOM

VEGACONNECT

Page 11: Vegapuls 68

11

3 Product description

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

The VEGADIS 81 is an external display and adjustment unit for VEGA plics® sensors.For sensors with double chamber housing the interface adapter "DISADAPT" is also required for VEGADIS 81.Youcanfindfurtherinformationintheoperatinginstructions"VE-GADIS81" (Document-ID 43814).

The adapter "DISADAPT" is an accessory part for sensors with dou-ble chamber housings. It enables the connection of VEGADIS 81 to the sensor housing via an M12 x 1 plug.Youcanfindfurtherinformationinthesupplementaryinstructions"AdapterDISADAPT" (Document-ID 45250).

VEGADIS 82 is suitable for measured value indication and adjustment of sensors with HART protocol. It is looped into the 4 … 20 mA/HART signal cable.Youcanfindfurtherinformationintheoperatinginstructions"VE-GADIS82" (Document-ID 45300).

PLICSMOBILE T61 is an external GSM/GPRS radio unit for transmis-sion of measured values and for remote parameter adjustment of plics® sensors. Adjustment is carried out via PACTware/DTM and the integrated USB connection.Youcanfindfurtherinformationinthesupplementaryinstructions"PLICSMOBILET61" (Document-ID 37700).

PLICSMOBILE is an internal GSM/GPRS radio unit for transmission of measured values and for remote parameter adjustment of plics® sensors. Adjustment is carried out via PACTware/DTM and the inte-grated USB connection.Youcanfindfurtherinformationinthesupplementaryinstructions"PLICSMOBILEGSM/GPRSradiomodule" (Document-ID 36849).

The protective cover protects the sensor housing against soiling and intense heat from solar radiation.Youwillfindadditionalinformationinthesupplementaryinstructionsmanual "Protective cover" (Document-ID 34296).

Screwedflangesareavailableindifferentversionsaccordingtothefollowing standards: DIN 2501, EN 1092-1, BS 10, ASME B 16.5, JIS B 2210-1984, GOST 12821-80.Youcanfindadditionalinformationinthesupplementaryinstructionsmanual "FlangesaccordingtoDIN-EN-ASME-JIS" (Document-ID 31088).

Electronics module "VEGAPULS series 60" is a replacement part for radarsensorsofVEGAPULSseries60.Adifferentversionisavailablefor each type of signal output.Youcanfindfurtherinformationintheoperatinginstructions"Elec-tronicsmoduleVEGAPULSseries60" (Document-ID 36801).

VEGADIS 81

DISADAPT

VEGADIS 82

PLICSMOBILE T61

PLICSMOBILE

Protective cap

Flanges

Electronics module

Page 12: Vegapuls 68

12

3 Product description

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

The supplementary electronics is a replacement part for sensors with double chamber housing and 4 … 20 mA/HART - two-wire.Youcanfindfurtherinformationintheoperatinginstructions"Supple-mentaryelectronicsfor4…20mA/HART-two-wire" (Document-ID 42764).

The antenna impedance cone is a replacement part used for optimum transmission of microwaves and for sealing against the process.Youfindfurtherinformationintheoperatinginstructions"Antenna impedanceconeVEGAPULS62and68" (Document-ID 31381).

Supplementary electron-ics for double chamber housing

Antenna impedance cone

Page 13: Vegapuls 68

13

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

4 Mounting

4.1 General instructionsOninstrumentswithprocessfittingthread,thehexagonmustbetight-enedwithasuitablewrench.Fortheproperwrenchsizeseechapter"Dimensions".

Warning:The housing must not be used to screw the instrument in! Applying tightening force can damage internal parts of the housing.

Protect your instrument against moisture ingress through the following measures:

• Use the recommended cable (see chapter "Connecting to power supply")

• Tighten the cable gland• Whenmountinghorizontally,turnthehousingsothatthecable

gland points downward• Loop the connection cable downward in front of the cable gland

This applies particularly to:

• Outdoor mounting• Installations in areas where high humidity is expected (e.g. through

cleaning processes)• Installations on cooled or heated vessels

Make sure that all parts of the instrument exposed to the process are suitable for the existing process conditions.These are mainly:

• Active measuring component• Processfitting• Process seal

Process conditions are particularly:

• Process pressure• Process temperature• Chemical properties of the medium• AbrasionandmechanicalinfluencesYoucanfinddetailedinformationontheprocessconditionsinchapter"Technicaldata" as well as on the type label.

In the case of instrument housings with self-sealing NPT threads, it is not possible to have the cable entries screwed in at the factory. The free openings for the cable glands are therefore covered with red dust protection caps as transport protection.Prior to setup you have to replace these protective caps with ap-proved cable glands or close the openings with suitable blind plugs.

Screwing in

Protection against mois-ture

Suitability for the process conditions

Cable entries - NPT thread

Page 14: Vegapuls 68

14

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

4.2 Mounting preparationsThe instrument is also available in versions with an antenna whose diameterislargerthantheprocessfitting(thread,flange).Insuchcasestheantennamustbedisconnectedfromtheprocessfittingbefore mounting.

Proceed as follows:1. Loosen the hexagon socket screws (3) on the antenna socket

withanAllenwrench(size3)2. Remove the antenna (4)

Note:The plastic cone may not be pulled out of the antenna socket.

3. Insert the antenna from below into the vessel socket and secure it againstfallingoff

4. Retighten the antenna with hexagon screws to the antenna socket; torque max. 2.5 Nm (1.8 lbf ft)

Note:The radar sensor with rinsing air connection or with antenna exten-sionhasanotchontheantennasocketforpolarization.Thisnotchmustbealignedwiththemarkingontheprocessfitting.

43

5

1

2

Fig. 2: Dismounting of the horn antenna1 Markingontheprocessfitting2 Marking at the antenna socket3 Screw locking device4 Hexagon screws5 Antenna

Caution:A secure hold of the antenna is only ensured with the untwist guard. The untwist guards inserted on site must hence be used again. Depending on temperature range and antenna material, these are spring rings according to DIN 217 or wedge lock washers according to DIN 25 201.

Horn antenna

Page 15: Vegapuls 68

15

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Proceed as follows:1. ClampVEGAPULS68withtheflange,e.g.inabenchvice2. Holdtheconnectionpiece(1)withawrenchontheflatsurfaces

(widthacrossflats22mm)3. Loosen counter nut (3) completely with a wrench (width across

flats36mm)inthedirectionoftheantenna4. Loosen compression nut (2) completely with a wrench (width

acrossflats41mm)inthedirectionoftheantenna5. Remove the parabolic antenna (4) axially6. Mountsensorflangeontheadapterflangeandfastenittightly7. Check if the O-ring seal is present on the connection piece and

make sure it is not damaged.

Note:A damaged O-ring seal must be replaced: FKM (SHS FPM 70C3 GLT),FFKM(Kalrez6375)

8. Remount the parabolic antenna (4)9. Fastencompressionnut(2)withawrench(widthacrossflats41),

torque max. 50 Nm10. Fastencounternut(3)withawrench(widthacrossflats36),

torque max. 40 Nm

Note:On the version with rinsing air connection, make sure that the holes intheantennaandintheprocessfittingcoincide.Thisensuresasuf-ficientairflow(theairisledthroughtheholestothefeedsystem.Arinsing of the whole parabolic antenna is not intended).

1

23

4

Fig. 3: Dismounting, parabolic antenna1 Connection piece2 Compression nut3 Locknut4 Parabolic antenna

4.3 Mounting preparations - Parabolic antennaThe instrument is also available in versions where the antenna has adiameterlargerthantheprocessfitting(thread,flange).Withsuchversionstheantennamustbedisconnectedfromtheprocessfittingbefore mounting. Proceed as follows:

Parabolic antenna

Page 16: Vegapuls 68

16

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

1. ClampVEGAPULS68withtheflange,e.g.inabenchvice2. Holdtheconnectionpiece(1)withawrenchontheflatsurfaces

(widthacrossflats22mm)3. Loosen counter nut (3) completely with a wrench (width across

flats36mm)inthedirectionoftheantenna4. Loosen compression nut (2) completely with a wrench (width

acrossflats41mm)inthedirectionoftheantenna5. Remove the parabolic antenna (4) axially6. Mountsensorflangeontheadapterflangeandfastenittightly7. Check if the O-ring seal is present on the connection piece and

make sure it is not damaged.

Note:A damaged O-ring seal must be replaced: FKM (SHS FPM 70C3 GLT),FFKM(Kalrez6375)

8. Remount the parabolic antenna (4)9. Fastencompressionnut(2)withawrench(widthacrossflats41),

torque max. 50 Nm10. Fastencounternut(3)withawrench(widthacrossflats36),

torque max. 40 Nm

Note:On the version with rinsing air connection, make sure that the holes intheantennaandintheprocessfittingcoincide.Thisensuresasuf-ficientairflow(theairisledthroughtheholestothefeedsystem.Arinsing of the whole parabolic antenna is not intended).

1

23

4

Fig. 4: Dismounting, parabolic antenna1 Connection piece2 Compression nut3 Locknut4 Parabolic antenna

4.4 Mounting instructionsThe illustrations with the following mounting instructions show a radar sensor with horn antenna. The mounting instructions apply analo-gously also to the version with parabolic antenna.

Horn and parabolic antenna

Page 17: Vegapuls 68

17

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

The emitted radar impulses of the radar sensor are electromagnetic waves. The polarisation is the direction of the electrical wave compo-nent.Byturningtheinstrumentintheconnectionflangeormountingboss,thepolarisationcanbeusedtoreducetheeffectsoffalseechoes.Thepositionofthepolarisationismarkedontheprocessfittingoftheinstrument.

1 2

Fig. 5: Position of the polarisation1 Marking with screwed version2 Markingwithflangeversion

Mount the sensor at least 200 mm (7.874 in) away from the vessel wall.

200 mm(7.87")

Fig. 6: Mounting the radar sensor on the vessel top

If you cannot maintain this distance, you should carry out a false signal storage during setup. This applies particularly if buildup on the vessel wall is expected. In such cases, we recommend repeating the false signal storage at a later date with existing buildup.

Mountingshouldnotbetooclosetotheinflowingmaterialasthemicrowave signal will be interferred. The optimum mounting position is ontheoppositeofthefilling.Toavoidstrongpollution,thedistancetothefilterordustextractionmustbeasbigaspossible.

Polarisation

Installation position

Inflowingmedium

Page 18: Vegapuls 68

18

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Fig.7:Mountingoftheradarsensorwithinflowingmedium

Withbulksolidssiloswithlateralpneumaticfilling,mountingshouldnotbeinthefillingstreamasthemicrowavesignalwillbeinterferred.Theoptimummountingpositionisnexttothefilling.Toavoidstrongpollution,thedistancetothefilterordustextractionmustbeasbigaspossible.

Page 19: Vegapuls 68

19

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Fig.8:Mountingoftheradarsensorwithinflowingmedium

The socket piece should be dimensioned in such a way that the antenna end protrudes slightly out of the socket.

Socket

Page 20: Vegapuls 68

20

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

ca. 1

0 m

m

Fig. 9: Recommended socket mounting with horn antenna

> 10

mm

(0

.39"

)

Fig. 10: Recommended socket mounting with parabolic antenna

When using a swivelling holder, keep in mind that the distance between antenna and socket gets smaller as the inclination of the sensorincreases.Additionalfalsereflectionsmaybegeneratedwhichcaninfluencethemeasuringresultatcloserange.Max.torqueoftheterminal screws on the swivelling holder: 20 Nm (14.75 lbf)

Fig. 11: Distance between antenna and socket with horn antenna

Page 21: Vegapuls 68

21

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Fig. 12: Distance between antenna and socket with parabolic antenna

Ifthemediumhasgoodreflectiveproperties,VEGAPULS68withhorn antenna can also be mounted on a longer socket piece. Rec-ommendedvaluesforsocketheightsarespecifiedinthefollowingillustration. You must carry out a false echo storage afterwards.

d

hm

ax.

Fig. 13: Deviating socket dimensions

Socket diameter d Socket length h Recommended anten-na diameter

40 mm ≤100mm 40 mm

50 mm ≤150mm 48 mm

80 mm ≤250mm 75 mm

100 mm ≤500mm 95 mm

150 mm ≤800mm 95 mm

Socket diameter d Socket length h Recommended anten-na diameter

1½" ≤3.9in 1½"

2" ≤5.9in 2"

3" ≤9.8in 3"

4" ≤19.7in 4"

6" ≤31.5in 4"

Tip:The instrument is also optionally available with an antenna extension. The antenna length can be selected (either ex works or later) to allow the antenna to protrude slightly out of the end of the mounting socket. Duetotheantennaextensionhowever,disturbingreflectionsaregenerated in the close-up range. This can lead to an increase in the

Page 22: Vegapuls 68

22

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

requiredminimumdistance,especiallywithpoorlyreflectingmediasuch as plastic powder. In practice, a cleanly constructed mounting socket, if necessary with rounded edges, introduces fewer disturbing influencesthananantennaextension.

To measure as much of the vessel volume as possible, the sensor should be aligned so that the measuring beam reaches the lowest level in the vessel. In a cylindrical silo with conical outlet mounting is carried out on a socket. It should be positioned on one third up to the half of the vessel radius.

rrr.../1 3 /1 2

Fig. 14: Orientation

If mounting in the centre of the silo is not possible, the sensor can be directed to the vessel center by using the optional swivelling holder. The following description shows a simple way to determine the required angle of inclination.

Orientation

Page 23: Vegapuls 68

23

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

d

a

α

Fig.15:ProposalforinstallationafterorientationVEGAPULS68

The angle of inclination depends on the vessel dimensions. It can be easily checked with a suitable level or water leve on the sensor.Thefollowingchartspecifiesthedistance"a"betweeninstallationposition and vessel centre dependent on the measuring distance for inclination angles of 2° … 10°.

Distance d (m)

2° 4° 6° 8° 10°

2 0.1 0.1 0.2 0.3 0.4

4 0.1 0.3 0.4 0.6 0.7

6 0.2 0.4 0.6 0.8 1.1

8 0.3 0.6 0.8 1.1 1.4

10 0.3 0.7 1.1 1.4 1.8

15 0.5 1.0 1.6 2.1 2.6

20 0.7 1.4 2.1 2.8 3.5

25 0.9 1.7 2.6 3.5 4.4

30 1.0 2.1 3.2 4.2 5.3

35 1.2 2.4 3.7 4.9 6.2

40 1.4 2.8 4.2 5.6 7.1

45 1.6 3.1 4.7 6.3 7.9

50 1.7 3.5 5.3 7 8.8

Page 24: Vegapuls 68

24

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Distance d (m)

2° 4° 6° 8° 10°

55 1.9 3.8 5.8 7.7 9.7

60 2.1 4.2 6.3 8.4 10.6

65 2.3 4.5 6.8 9.1 11.5

70 2.4 4.9 7.4 9.8 12.3

75 2.6 5.2 7.9 1.0 13Example:In a vessel 20 m high, the installation position of the sensor is 1.4 m from the vessel centre.The necessary angle of inclination of 4° can be read out from this chart.Proceed as follows to adjust the angle of inclination with the swivelling holder:1. Loosen terminal screw of the swivelling holder with a fork spanner

SW 132. Align the sensor, check angle of inclination

Information:The max. angle of inclination of the swivelling holder is approx. 15°

3. Tighten the terminal screw, torque max. 20 Nm.

Information:The hexagon screws must not be loosened.

The mounting location of the radar sensor should be a place where no otherequipmentorfixturescrossthepathoftheradarsignals.Vessel installations, such as e.g. ladders, limit switches, heating spi-rals, struts, etc., can cause false echoes and impair the useful echo. Make sure when planning your measuring point that the radar sensor has a "clear view" to the measured product.In case of existing vessel installations, a false echo storage should be carried out during setup.If large vessel installations such as struts or supports cause false echoes, these can be attenuated through supplementary measures. Small,inclinedsheetmetalbafflesabovetheinstallationsscattertheradarsignalsandpreventdirectinterferingreflections.

Fig.16:Coverflat,large-areaprofileswithdeflectors

Vessel installations

Page 25: Vegapuls 68

25

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

If there are agitators in the vessel, a false signal suppression should be carried out with the agitators in motion. This ensures that the interferingreflectionsfromtheagitatorsaresavedwiththebladesindifferentpositions.

Fig. 17: Agitators

Large material heaps are detected with several sensors, which can be mounted on e.g. traverse cranes. For this type of application, it is best to orient the sensor toward the solid surface. A mutual infuence of the sensors is not possible.

Fig. 18: Radar sensors on traverse crane

Information:Keep in mind that for these applications, the sensors are designed for relatively slow level changes. When using VEGAPULS 68 on a mov-able bracket, the max. measuring rate must be observed (see chapter "Technicaldata").

Instruments for a temperature range up to 250 °C or up to 450 °C haveadistancepiecebetweenprocessfittingandelectronicshous-ing. Ths distance piece is used for thermal decoupling of the electron-ics against high process temperatures.

Agitators

Material heaps

Mounting in the vessel insulation

Page 26: Vegapuls 68

26

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Information:The spacer may only be incorporated up to a maximum of 50 mm into the vessel insulation. Only then is a reliable temperature decoupling guaranteed.

max

. 50

mm

(1

.97"

)

12

3

Fig. 19: Mounting the instrument on insulated vessels.1 Electronicshousing2 Spacer3 Vessel insulation

For level measurements in concrete silos, the sensors are often mounted in protective boxes. These boxes can be for example metal-lic, closed subsurface enclosures.

1 2

Fig. 20: Mounting of the instrument in an subsurface enclosure1 Subsurface enclosure2 Concrete bottom

For this application, the minimal amounts of stray radiation from the sensorcanbereflectedandstrengthenedbythewallsofthesubsur-face enclosures. In the case of sensors with plastic housings, this can lead to coupling disturbances. This can be avoided by using a sensor with aluminium or stainless steel housing.

Installation in subsurface enclosures

Page 27: Vegapuls 68

27

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Thesilowallsofmultiplechambersilosareoftenmadeofprofilewalls,suchase.g.profilesheeting,toensuretherequiredstability.Ifthe radar sensor is mounted very close to a heavily structured vessel wall,considerablefalsereflectionscanbegenerated.Hencethesen-sor should be mounted at a large distance from the separating wall. The optimal mounting position is on the outer wall of the silo with the sensor directed towards the emptying aperture in the silo center.

Fig.21:MountingofVEGAPULS68inmultiplechambersilos

Fig.22:OrientationofVEGAPULS68foremptyinginthesilocenter

Mounting in multiple chamber silo

Page 28: Vegapuls 68

28

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

To avoid strong buildup and dust in the antenna system, the sensor should not be mounted directly at the dust extraction of the vessel.In case of extreme dust deposits in the antenna system, VEGAPULS 68 is available with a rinsing air connection. The air is distributed via channels in the antenna system and keeps it largely free of dust.

Fig. 23: Purging air connection with horn antenna

Fig. 24: Purging air connection with parabolic antenna

The practice has shown that a pressure of approx. 0.2 … 1 bar providesasufficientairflow(seediagraminchapter"Technicaldata", "Purging air connection".

Dust deposits

Page 29: Vegapuls 68

29

5 Connecting to power supply

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

5 Connecting to power supply

5.1 Preparing the connectionAlways keep in mind the following safety instructions:

Warning:Connect only in the complete absence of line voltage.

• The electrical connection must only be carried out by trained personnel authorised by the plant operator.

• If overvoltage surges are expected, overvoltage arresters should be installed.

Power supply and current signal are carried on the same two-wire cable.Theoperatingvoltagecandifferdependingontheinstrumentversion.Thedataforpowersupplyarespecifiedinchapter"Technicaldata".Provide a reliable separation between the supply circuit and the mains circuits according to DIN EN 61140 VDE 0140-1.Keepinmindthefollowingadditionalfactorsthatinfluencetheoperat-ing voltage:

• Lower output voltage of the power supply unit under nominal load (e.g. with a sensor current of 20.5 mA or 22 mA in case of fault)

• Influenceofadditionalinstrumentsinthecircuit(seeloadvaluesinchapter "Technicaldata")

The instrument is connected with standard two-wire cable without screen. If electromagnetic interference is expected which is above the test values of EN 61326-1 for industrial areas, screened cable should be used.Use cable with round cross section for instruments with housing and cablegland.Toensurethesealeffectofthecablegland(IPprotectionrating),findoutwhichcableouterdiameterthecableglandissuitablefor.Useacableglandfittingthecablediameter.We generally recommend the use of screened cable for HART multi-drop mode.

With plastic housing, the NPT cable gland or the Conduit steel tube must be screwed without grease into the threaded insert.Max. torque for all housings see chapter "Technicaldata".

If screened cable is required, we recommend connecting the cable screen on both ends to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal on the outside of the housing must be connected to the ground potential (low impedance).In Ex systems, the grounding is carried out according to the installa-tion regulations.

Safety instructions

Voltage supply

Connection cable

Cable gland ½ NPT

Cable screening and grounding

Page 30: Vegapuls 68

30

5 Connecting to power supply

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

In electroplating and CCP systems (cathodic corrosion protection) it mustbetakenintoaccountthatsignificantpotentialdifferencesexist.This can lead to unacceptably high currents in the cable screen if it is grounded at both ends.

Information:Themetallicpartsoftheinstrument(processfitting,transmitter,concentric tube, etc.) are connected with the inner and outer ground terminal on the housing. This connection exists either directly via con-necting metallic parts or, in case of instruments with external electron-ics, via the screen of the special connection cable.Youcanfindspecificationsonthepotentialconnectionsinsidetheinstrument in chapter "Technicaldata".

5.2 ConnectingThe voltage supply and signal output are connected via the spring-loaded terminals in the housing.Connection to the display and adjustment module or to the interface adapter is carried out via contact pins in the housing.

Information:The terminal block is pluggable and can be removed from the electronics. To do this, lift the terminal block with a small screwdriver and pull it out. When reinserting the terminal block, you should hear it snap in.

Proceed as follows:1. Unscrew the housing lid2. If a display and adjustment module is installed, remove it by turn-

ing it slightly to the left.3. Loosen compression nut of the cable entry gland4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.

1 cm (0.4 in) of insulation from the ends of the individual wires5. Insert the cable into the sensor through the cable entry

Connection technology

Connection procedure

Page 31: Vegapuls 68

31

5 Connecting to power supply

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Fig. 25: Connection steps 5 and 6 - Single chamber housing

Fig. 26: Connection steps 5 and 6 - Double chamber housing

6. Insert the wire ends into the terminals according to the wiring plan

Information:Solidcoresaswellasflexiblecoreswithwireendsleevesareinsert-eddirectlyintotheterminalopenings.Incaseofflexiblecoreswithoutend sleeves, press the terminal from above with a small screwdriver, the terminal opening is then free. When the screwdriver is released, the terminal closes again.Youcanfindfurtherinformationonthemax.wirecross-sectionunder"Technicaldata/Electromechanicaldata"

7. Check the hold of the wires in the terminals by lightly pulling on them

8. Connect the screen to the internal ground terminal, connect the outer ground terminal to potential equalisation

Page 32: Vegapuls 68

32

5 Connecting to power supply

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable

10. Reinsert the display and adjustment module, if one was installed11. Screw the housing lid back onTheelectricalconnectionisfinished.

5.3 Wiring plan, single chamber housingThe following illustration applies to the non-Ex as well as to the Ex-ia version.

51 2+( ) (-) 6 7 8

4...20mA

2

3

41

Fig.27:Electronicsandterminalcompartment,singlechamberhousing1 Voltage supply, signal output2 For display and adjustment module or interface adapter3 For external display and adjustment unit4 Groundterminalforconnectionofthecablescreen

5.4 Wiring plan, double chamber housingThe following illustrations apply to the non-Ex as well as to the Ex-ia version.

5 6 7 8

4...20mA

1 2+( ) (-)

2

1 1

Fig.28:Electronicscompartment,doublechamberhousing1 Internal connection to the terminal compartment2 For display and adjustment module or interface adapter

Electronics and terminal compartment

Electronics compartment

Page 33: Vegapuls 68

33

5 Connecting to power supply

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

51 2+( ) (-) 6 7 8

4...20mA Display

2

3

41

Fig.29:Terminalcompartment,doublechamberhousing1 Voltage supply, signal output2 For display and adjustment module or interface adapter3 For external display and adjustment unit4 Groundterminalforconnectionofthecablescreen

Information:Parallel use of an external display and adjustment unit and a display and adjustment module in the terminal compartment is not supported.

1

USB

Status

TestSIM-Card

1 2+( ) (-)

Fig.30:Terminalcompartment,radiomodulePLICSMOBILE1 Voltage supply

Youcanfinddetailedinformationonconnectioninthesupplementaryinstructions "PLICSMOBILEGSM/GPRSradiomodule".

Terminal compartment

Terminal compartment - Radio module PLICS-MOBILE

Page 34: Vegapuls 68

34

5 Connecting to power supply

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

5.5 Wiring plan, double chamber housing Ex d ia

31

2

5 6 7 81 2( ) (-)+

4...20mA

Fig.31:Electronicscompartment,doublechamberhousingExdia1 Internal connection to the terminal compartment2 For display and adjustment module or interface adapter3 Internal connection to the plug connector for external display and adjust-

ment unit (optional)

Note:HART multidrop mode is not possible when using an Ex-d-ia instru-ment.

4...20mA

1 2+( ) (-) 2

1

Fig.32:Terminalcompartment,doublechamberhousingExdia1 Voltage supply, signal output2 Groundterminalforconnectionofthecablescreen

34

1 2

Fig.33:Topviewoftheplugconnector1 Pin 12 Pin 23 Pin 34 Pin 4

Electronics compartment

Terminal compartment

Plug M12 x 1 for external display and adjustment unit

Page 35: Vegapuls 68

35

5 Connecting to power supply

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Contact pin Colour connection ca-ble in the sensor

Terminal, electronics module

Pin 1 Brown 5

Pin 2 White 6

Pin 3 Blue 7

Pin 4 Black 8

5.6 Double chamber housing with DIS-ADAPT

3

1

2

Fig.34:ViewtotheelectronicscompartmentwithDISADAPTforconnectionofthe external display and adjustment unit1 DISADAPT2 Internal plug connection3 Plug connector M12 x 1

34

1 2

Fig. 35: View to the plug connector M12 x 11 Pin 12 Pin 23 Pin 34 Pin 4

Contact pin Colour connection ca-ble in the sensor

Terminal, electronics module

Pin 1 Brown 5

Pin 2 White 6

Pin 3 Blue 7

Pin 4 Black 8

Electronics compartment

Assignment of the plug connector

Page 36: Vegapuls 68

36

5 Connecting to power supply

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

5.7 Wiring plan - version IP 66/IP 68, 1 bar

1

2

Fig. 36: Wire assignment in permanently connected connection cable1 brown (+) and blue (-) to power supply or to the processing system2 Shielding

5.8 Switch-on phaseAfter connecting the instrument to power supply or after a voltage recurrence, the instrument carries out a self-check for approx. 30 s:

• Internal check of the electronics• Indication of the instrument type, hardware and software version,

measurement loop name on the display or PC• Indication of the status message "F 105 Determine measured

value" on the display or PC• The output signal jumps to the set fault current

As soon as a plausible measured value is found, the corresponding current is outputted to the signal cable. The value corresponds to the actual level as well as the settings already carried out, e.g. factory setting.

Wire assignment, con-nection cable

Page 37: Vegapuls 68

37

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

6 Set up with the display and adjustment module

6.1 Insert display and adjustment moduleThe display and adjustment module can be inserted into the sensor andremovedagainatanytime.Youcanchooseanyoneoffourdiffer-ent positions - each displaced by 90°. It is not necessary to interrupt the power supply.Proceed as follows:1. Unscrew the housing lid2. Place the display and adjustment module on the electronics in the

desired position and turn it to the right until it snaps in.3. Screw housing lid with inspection window tightly back onDisassembly is carried out in reverse order.The display and adjustment module is powered by the sensor, an ad-ditional connection is not necessary.

Fig. 37: Installing the display and adjustment module in the electronics compart-ment of the single chamber housing

Page 38: Vegapuls 68

38

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

1 2

Fig. 38: Installing the display and adjustment module in the double chamber housing1 In the electronics compartment2 In the terminal compartment

Note:Ifyouintendtoretrofittheinstrumentwithadisplayandadjustmentmodule for continuous measured value indication, a higher lid with an inspection glass is required.

6.2 Adjustment system

1

2

Fig. 39: Display and adjustment elements1 LC display2 Adjustment keys

• [OK] key:Key functions

Page 39: Vegapuls 68

39

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

– Move to the menu overview – Confirmselectedmenu – Edit parameter – Save value

• [->] key: – Presentation, change measured value – Select list entry – Select menu items in the quick setup – Select editing position

• [+] key: – Change value of the parameter

• [ESC] key: – Interrupt input – Jump to next higher menu

You adjust the instrument via the four keys of the display and adjust-ment module. The individual menu items are shown on the LC display. Youcanfindthefunctionsoftheindividualkeysinthepreviousillustration.

By pushing the [+] and [->] keys once, the edited value or the cursor changes by one position. By pushing the keys longer than 1 s the change will be continuously.By pushing the [OK] and [ESC] keys simultaneously for more than 5 s, a return to the basic menu is caused. The menu language is then switched over to "English".Approx. 60 minutes after the last pressing of a key, an automatic reset tomeasuredvalueindicationistriggered.Anyvaluesnotconfirmedwith [OK] will not be saved.

6.3 Measured value indication - Selection national language

With the [->]keyyoumovebetweenthreedifferentindicationmodes.Inthefirstview,theselectedmeasuredvalueisdisplayedinlargedigits.In the second view, the selected measured value and a correspond-ing bar graph presentation are displayed.In the third view, the selected measured value as well as a second se-lectable value, e.g. the temperature of the electronics, are displayed.

During the initial setup of an instrument shipped Ex works,use the "OK" key to get to the menu "National language".

Adjustment system

Time functions

Measured value indica-tion

Page 40: Vegapuls 68

40

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

This menu item is used to select the national language for further pa-rameter adjustment. You can change the selection via the menu item "Setup - Display, Menu language".

With the "OK" key you move to the main menu.

6.4 Parameter adjustmentThe instrument is adapted to the application conditions via the pa-rameter adjustment. The parameter adjustment is carried out with an adjustment menu.

Themainmenuisdividedintofivesectionswiththefollowingfunc-tions:

Setup: Settings, e.g., for measurement loop name, medium, applica-tion, vessel, adjustment, signal outputDisplay: Settings, e.g., for language, measured value display, lightingDiagnosis: Information, e.g. on instrument status, pointer, measure-ment certainty, simulation, echo curveFurther settings: Instrument unit, false signal suppression, linearisa-tion curve, reset, date/time, reset, copy functionInfo: Instrument name, hardware and software version, date of manu-facture, instrument features

Information:Inthisoperatinginstructionsmanual,theinstrument-specificparam-eters in the menu sections "Setup", "Diagnosis" and "Additional set-tings" are described. The general parameters in these menu section are described in the operating instructions manual "Indicating and adjustment module".Youcanfindintheoperatinginstructionsmanual"Display and adjust-ment module" also the description of the menu sections "Display" and "Info".

In the main menu point "Setup", the individual submenu points should be selected one after the other and provided with the correct parameters to ensure optimum adjustment of the measurement. The procedure is described in the following.

In the menu item "SensorTAG" you edit a twelve digit measurement loop designation label.You can enter an unambiguous designation for the sensor, e.g. the measurement loop name or the tank or product designation. In digital systems and in the documentation of larger plants, a singular desig-

Selection of national language

Main menu

Setup - Measurement loop name

Page 41: Vegapuls 68

41

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

nationmustbeenteredforexactidentificationofindividualmeasuringpoints.The available digits comprise:

• Letters from A … Z• Numbers from 0 … 9• Special characters +, -, /, -

Eachmediumhasdifferentreflectionproperties.Withliquids,furtherinterferingfactorsarefluctuationproductsurfaceandfoamgenera-tion. With bulk solids, these are dust generation, material cone and additional echoes from the vessel wall.Toadaptthesensortothesedifferentmeasuringconditions,theselection "Liquid" or "Bulk solid" should be made in this menu item.

Through this selection, the sensor is adapted perfectly to the product andmeasurementreliability,particularlyinproductswithpoorreflec-tive properties, is considerably increased.Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.

In addition to the medium, also the application, i.e. the measuring site, caninfluencethemeasurement.With this menu item, the sensor can be adapted to the applications. The adjustment possibilities depend on the selection "Liquid" or "Bulk solid" under "Medium".

The following options are available when "Liquid" is selected:

Setup - Medium

Setup - Application

Page 42: Vegapuls 68

42

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

The selection "Standpipe" opens a new window in which the inner diameter of the applied standpipe is entered.

The following features form the basis of the applications:

Storage tank:• Setup: large-volumed, upright cylindrical, spherical• Productspeed:slowfillingandemptying• Process/measurement conditions:

– Condensation – Smooth product surface – High requirements to the measurement accuracy

• Properties, sensor: – Slight sensitivity against sporadic false echoes – Stable and reliable measured values through averaging – High accuracy – Short reaction time of the sensor not required

Storage tank with product circulation:• Setup: large-volumed, upright cylindrical, spherical• Productspeed:slowfillingandemptying• Installations: small laterally mounted or large top mounted stirrer• Process/measurement conditions:

– Relatively smooth product surface – High requirements to the measurement accuracy – Condensation – Slight foam generation – Overfillingpossible

• Properties, sensor: – Slight sensitivity against sporadic false echoes – Stable and reliable measured values through averaging – High accuracy because not adjusted for max. speed – False signal suppression recommended

Storage tank on ships (Cargo Tank):• Productspeed:slowfillingandemptying• Vessel:

– Installations in the bottom section (bracers, heating spirals) – High sockets 200 … 500 mm, also with large diameters

• Process/measurement conditions: – Condensation, buildup by movement – Max. requirement on measurement accuracy from 95 %

• Properties, sensor: – Slight sensitivity against sporadic false echoes – Stable and reliable measured values through averaging

Page 43: Vegapuls 68

43

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

– High accuracy – False signal suppression required

Stirrer vessel (reactor):• Setup:allvesselsizespossible• Product speed:

– Fasttoslowfillingpossible – Vesselisveryoftenfilledandemptied

• Vessel: – Socket available – Large agitator blades of metal – Vortex breakers, heating spirals

• Process/measurement conditions: – Condensation, buildup by movement – Strong spout generation – Very agitated surface, foam generation

• Properties, sensor: – Higher measurement speed through lower averaging – Sporadic false echoes are suppressed

Dosing vessel:• Setup:allvesselsizespossible• Product speed:

– Fastfillingandemptying – Vesselisveryoftenfilledandemptied

• Vessel: narrow installation situation• Process/measurement conditions:

– Condensation, buildup on the antenna – Foam generation

• Properties, sensor: – Measurementspeedoptimizedbyvirtuallynoaveraging – Sporadic false echoes are suppressed – False signal suppression recommended

Standpipe:• Productspeed:veryfastfillingandemptying• Vessel:

– Vent hole – Joinslikeflanges,weldjoints – Shifting of the running time in the tube

• Process/measurement conditions: – Condensation – Buildup

• Properties, sensor: – Measurementspeedoptimizedthroughlittleaveraging – Entering the tube inside diameter takes the running time shift

into consideration – Echo detection sensitivity reduced

Bypass:• Product speed:

– Fastuptoslowfillingwithshortuptolongbypasstubepossible – Often the level is hold via a control facility

Page 44: Vegapuls 68

44

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

• Vessel: – Lateral outlets and inlets – Joinslikeflanges,weldjoints – Shifting of the running time in the tube

• Process/measurement conditions: – Condensation – Buildup – Separation of oil and water possible – Overfillingintotheantennapossible

• Properties, sensor: – Measurementspeedoptimizedthroughlittleaveraging – Entering the tube inside diameter takes the running time shift

into consideration – Echo detection sensitivity reduced – False signal suppression recommended

Plastic tank:• Vessel:

– Measurementfixmountedorintegrated – Measurement depending on the application through the vessel

top – With empty vessel, the measurement can be carried out

through the bottom• Process/measurement conditions:

– Condensation on the plastic ceiling – In outside facilities water and snow on the vessel top possible

• Properties, sensor: – False signals outside the vessel are not taken into consideration – False signal suppression recommended

Transportable plastic tank:• Vessel:

– Materialandthicknessdifferent – Measurement through the vessel top

• Process/measurement conditions: – Measured value jump with vessel change

• Properties, sensor: – Quickadaptationtochangingreflectionconditionsthrough

vessel change – False signal suppression required

Open water (gauge measurement):• Gauge rate of change: slow gauge change• Process/measurement conditions:

– Distance sensor to water surface to big – Extreme damping of output signal due to wave generation – Ice and condensation on the antenna possible – Spiders and insect nestle in the antennas – Floating material and animals sporadically on the water surface

• Properties, sensor: – Stable and reliable measured values through high averaging – Insensitive in the close range

Page 45: Vegapuls 68

45

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Openflume(flowmeasurement):• Gauge rate of change: slow gauge change• Process/measurement conditions:

– Ice and condensation on the antenna possible – Spiders and insect nestle in the antennas – Smooth water surface – Exact measurement result required – Distance to the water surface normally relatively high

• Properties, sensor: – Stable and reliable measured values through high averaging – Insensitive in the close range

Rain water overfall (weir):• Gauge rate of change: slow gauge change• Process/measurement conditions:

– Ice and condensation on the antenna possible – Spiders and insect nestle in the antennas – Turbulent water surface – Sensorfloodingpossible

• Properties, sensor: – Stable and reliable measured values through high averaging – Insensitive in the close range

Demonstration:• Adjustment for all applications which are not typically level meas-

urement – Instrument demonstration – Object recognition/monitoring (additional settings required)

• Properties, sensor: – Sensor accepts all measured value changes within the measur-

ing range immediately – High sensitivity against interferences, because virtually no

averaging

Caution:Ifliquidswithdifferentdielectricconstantsseparateinthevessel,forexample through condensation, the radar sensor can detect under certain circumstances only the medium with the higher dielectric constant. Keep in mind that layer interfaces can cause faulty meas-urements.If you want to measure the total height of both liquids reliably, please contact our service department or use an instrument specially de-signed for interface measurement.

The following options are available when "Bulk solid" is selected:

The following features form the basis of the applications:

Page 46: Vegapuls 68

46

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Silo (slender and high):• Vessel of metal: weld joints• Process/measurement conditions:

– Filling aperture too close to the sensor – System noise in completely empty silo increased

• Properties, sensor: – Stable measured values through higher averaging – False signal suppression during setup recommended, required

for automatic false signal suppression – Automaticfalsesignalsuppressionwithpartlyfilledvessel

Bunker (large-volume):• Vessel of concrete or metal:

– Structured vessel walls – Installations present

• Process/measurement conditions: – Large distance to the medium – Large angles of repose

• Properties, sensor: – Mean averaging – High measured value jumps are accepted

Bunkerwithfastfilling:• Vessel of concrete or metal, also multiple chamber silo:

– Structured vessel walls – Installations present

• Process/measurement conditions: – Measured value jumps, e.g. through truck loading – Large distance to the medium – Large angles of repose

• Properties, sensor: – Lower averaging – Very high measured value jumps are accepted

Heap:• Sensor mounting on movable conveyor belts• Detectionoftheheapprofile• Heightdetectionduringfilling• Process/measurement conditions:

– Measuredvaluejumps,e.g.bytheprofileoftheheaportrav-erses

– Large angles of repose – Measurementnearthefillingstream

• Properties, sensor: – Mean averaging – High measured value jumps are accepted

Crusher:• Vessel: installations, wear and protective facilities available• Process/measurement conditions:

– Measured value jumps, e.g. through truck loading – Fast reaction time – Large distance to the medium

Page 47: Vegapuls 68

47

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

• Properties, sensor: – Little averaging – Max. reaction speed, very high measured value jumps are

accepted

Demonstration:• Adjustment for all applications which are not typically level meas-

urement – Instrument demonstration – Object recognition/monitoring (additional settings required)

• Properties, sensor: – Sensor accepts all measured value changes within the measur-

ing range immediately – High sensitivity against interferences, because virtually no

averaging

Through this selection, the sensor is adapted optimally to the applica-tion or the location and measurement reliability under the various basic conditions is increased considerably.Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.

Alsothevesselformcaninfluencethemeasurementapartfromthemedium and the application. To adapt the sensor to these measure-mentconditions,thismenuitemoffersyoudifferentoptionsforvesselbottom and ceiling in case of certain applications.

Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.

With this selection, the operating range of the sensor is adapted to thevesselheightandthereliabilitywithdifferentframeconditionsisincreased considerably.The min. adjustment must be carried out independently of this.

Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.

Since the radar sensor is a distance measuring instrument, the distance from the sensor to the product surface is measured. For indication of the real level, an allocation of the measured distance to the percentage height must be carried out.

Setup - Vessel form

Setup - Vessel height, measuring range

Setup - Adjustment

Page 48: Vegapuls 68

48

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

To perform the adjustment, enter the distance with full and empty ves-sel, see the following example:

100%

0%

0,5

m(1

9.68

")5

m(1

96.9

")

2

1

3

Fig.40:Parameteradjustmentexamplemin./max.adjustment1 Min. level = max. measuring distance2 Max. level = min. measuring distance3 Reference plane

If these values are not known, an adjustment with the distances of for example 10 % and 90 % is possible. Starting point for these distance specificationsisalwaysthesealsurfaceofthethreadorflange.Youcanfindspecificationsofthereferenceplaneinchapter"Technicaldata". By means of these settings, the real level will be calculated.The real product level during this adjustment is not important, be-cause the min./max. adjustment is always carried out without chang-ing the product level. These settings can be made ahead of time without the instrument having to be installed.

Proceed as follows:1. Select the menu item "Setup" with [->]andconfirmwith[OK].

Now select with [->] the menu item "Min. adjustment"andconfirmwith [OK].

2. Edit the percentage value with [OK] and set the cursor to the requested position with [->].

Setup - Min. adjustment

Page 49: Vegapuls 68

49

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

3. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value.

4. Enter the suitable distance value in m for the empty vessel (e.g. distance from the sensor to the vessel bottom) corresponding to the percentage value.

5. Save settings with [OK] and move with [ESC] and [->] to the max. adjustment.

Proceed as follows:1. Select with [->]themenuitemMax.adjustmentandconfirmwith

[OK].

2. Prepare the percentage value for editing with [OK] and set the cursor to the requested position with [->].

3. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value.

4. Enter the appropriate distance value in m (corresponding to the percentage value) for the full vessel. Keep in mind that the max. level must lie below the min. distance to the antenna edge.

5. Save settings with [OK]

Todampprocess-dependentmeasuredvaluefluctuations,setanintegration time of 0 … 999 s in this menu item.

Depending on the sensor type, the factory setting is 0 s or 1 s.

Setup - Max. adjustment

Setup - Damping

Page 50: Vegapuls 68

50

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

In the menu item "Current output mode" you determine the output characteristics and reaction of the current output in case of failure.

The default setting is output characteristics 4 … 20 mA, failure mode < 3.6 mA.

In the menu item "CurrentoutputMin./Max.", you determine the reac-tion of the current output during operation.

The default setting is min. current 3.8 mA and max. current 20.5 mA.

In this menu item, the PIN is activated/deactivated permanently. Enteringa4-digitPINprotectsthesensordataagainstunauthorizedaccessandunintentionalmodifications.IfthePINisactivatedperma-nently, it can be deactivated temporarily (i.e. for approx. 60 min.) in any menu item.

Only the following functions are permitted with activated PIN:

• Select menu items and show data• Read data from the sensor into the display and adjustment mod-

ule.

Caution:With active PIN, adjustment via PACTware/DTM as well as other systems is also blocked.

In delivery status, the PIN is "0000".

This menu item enables the setting of the requested national lan-guage.

Setup - Current output mode

Setup - Current output Min./Max.

Lock setup - adjustment

Display - Language

Page 51: Vegapuls 68

51

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

In the delivery status, the sensor is set to the ordered national lan-guage.

Inthismenuitemyoucandefinetheindicationofthemeasuredvalueon the display.

The default setting for the indication value is e.g. distance with radar sensors.

The optionally integrated background lighting can be adjusted via the adjustment menu. The function depends on the level of the supply voltage, see operating instructions of the respective sensor.

In delivery status, the lighting is switched on.

In this menu item, the device status is displayed.

The respective min. and max. measured value is saved in the sensor. The values are displayed in the menu item "Peak values".

Display - Displayed value

Display - Backlight

Diagnostics - Device status

Diagnosis - Peak value

Page 52: Vegapuls 68

52

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

The respective min. and max. measured value of the electronics temperature is saved in the sensor. These values as well as the actual temperature value are displayed in the menu item "Peak values".

When non-contact level sensors are used, the measurement can be influencedbytherespectiveprocessconditions.Inthismenuitem,the measurement reliability of the level echo is displayed as dB value. The measurement reliability equals signal strength minus noise. The higher the value, the more reliable the measurement. With a function-ing measurement, the values are > 10 dB.

In this menu item you can simulate measured values via the current output. This allows the signal path to be tested, e.g. through down-stream indicating instruments or the input card of the control system.

How to start the simulation:1. Push [OK]2. Select the requested simulation variable with [->]andconfirm

with [OK].3. With [OK]youstartthesimulation,firstofalltheactualmeasured

value is displayed in %4. Start the editing mode with [OK]5. Set the requested numerical value with [+] and [->].6. Push [OK]

Note:During simulation, the simulated value is outputted as 4 … 20 mA cur-rent value and digital HART signal.

Diagnosis - Electronics temperature

Diagnosis - Measurement reliability

Diagnosis - Simulation

Page 53: Vegapuls 68

53

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

How to interrupt the simulation:

→ Push [ESC]

Information:The simulation is automatically terminated 10 minutes after the last pressing of a key.

The "Echocurve" shows the signal strength of the echoes over the measuring range in dB. The signal strength enables an evaluation of the quality of the measurement.

The "False signal suppression" displays the saved false echoes (see menu "Additional settings") of the empty vessel with signal strength in "dB" over the measuring range.A comparison of echo curve and false signal suppression allows a more detailed statement of the reliability.

Theselectedcurveiscontinuouslyupdated.Asubmenuwithzoomfunctions is opened with the [OK] key:

• "X-Zoom":Zoomfunctionforthemeas.distance• "Y-Zoom":1,2,5and10xsignalmagnificationin"dB"• "Unzoom":Resetthepresentationtothenominalmeasuringrange

withoutmagnification

With the function "Echocurvememory" the echo curve can be saved at the time of setup. This is generally recommended; for using the As-set Management functions it is absolutely necessary. If possible, the curve should be saved with a low level in the vessel.With the adjustment software PACTware and the PC, the high resolu-tionechocurvecanbedisplayedandusedtorecognizesignalchanges over the operating time. In addition, the echo curve of the setup can be also displayed in the echo curve window and compared with the actual echo curve.

In this menu item you select the measured variable of the system and the temperature unit.

Diagnoses - Curve indica-tion

Diagnostics - Echo curve memory

Additional adjustments - Device units

Page 54: Vegapuls 68

54

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Thefollowingcircumstancescauseinterferingreflectionsandcaninfluencethemeasurement:

• High sockets• Vessel installations such as struts• Agitators• Buildup or welded joints on vessel walls

Note:A false signal suppression detects, marks and saves these false signals so that they are no longer taken into account in the level measurement.

This should be done with a low level so that all potential interfering reflectionscanbedetected.Proceed as follows:1. Select with [->] the menu item "False signal suppression" and

confirmwith[OK].

2. Confirmagainwith[OK].

3. Confirmagainwith[OK].

4. Confirmagainwith[OK] and enter the actual distance from the sensor to the product surface.

5. All interfering signals in this section are detected by the sensor andstoredafterconfirmingwith[OK].

Note:Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as a false signal. The level would then no longer be detectable in this area.

Additional adjustments - False signal suppression

Page 55: Vegapuls 68

55

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

If a false signal suppression has already been saved in the sensor, the following menu window appears when selecting "False signal suppression":

Delete: An already created false signal suppression will be com-pletely deleted. This is useful if the saved false signal suppression no longer matches the metrological conditions in the vessel.Extend: is used to extend an already created false signal suppres-sion. This is useful if a false signal suppression was carried out with a too high level and not all false signals could be detected. When selecting "Extend", the distance to the product surface of the created false signal suppression is displayed. This value can now be changed and the false signal suppression can be extended to this range.

Alinearizationisnecessaryforallvesselsinwhichthevesselvolumedoesnotincreaselinearlywiththelevel-e.g.ahorizontalcylindri-cal or spherical tank - and the indication or output of the volume is required.Correspondinglinearizationcurvesarepreprogrammedfor these vessels. They represent the correlation between the level percentage and vessel volume.By activating the appropriate curve, the volume percentage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set in the menu item "Display".

Enter the requested parameters via the appropriate keys, save your settings and jump to the next menu item with the [ESC] and [->] key.

Caution:Note the following if instruments with appropriate approval are used aspartofanoverfillprotectionsystemaccordingtoWHG:If a linearisation curve is selected, the measuring signal is no longer necessarilylineartothefillingheight.Thismustbeconsideredbytheuser especially when adjusting the switching point on the limit signal transmitter.

Enteringa4-digitPINprotectsthesensordataagainstunauthorizedaccessandunintentionalmodification.Inthismenuitem,thePINisdisplayed or edited and changed. However, this menu item is only available if adjustment is enabled in the menu "Setup".

Additional adjustments - Linearization curve

Additional settings - PIN

Page 56: Vegapuls 68

56

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

In delivery status, the PIN is "0000".

In this menu item, the internal clock of the sensor is adjusted.

With a reset, certain parameter adjustments carried out by the user are reset.

The following reset functions are available:Delivery status: Restoring the parameter settings at the time of ship-mentfromthefactoryincl.theorder-specificsettings.Acreatedfalsesignalsuppression,user-programmablelinearizationcurveaswellasthe measured value memory will be deleted.Basic settings: Resetting of the parameter settings, incl. special parameters, to the default values of the respective instrument. Any stored false signal suppression or user programmable linearisation curve, as well as the measured value memory, is deleted.Setup: Resetting of the parameter settings to the default values of the respective instrument in the menu item Setup. User-generated false signal suppression, user-programmed linearisation curve, measured value memory as well as event memory remain untouched. The linearisation is set to linear.False signal suppression: Deleting a previously created false signal suppression. The false signal suppression created in the factory remains active.Peak values, measured value: Resetting of the measured min. and max. distances to the actual measured value.The following table shows the default values of the instrument. De-pending on the instrument version, not all menu items are available or somemaybedifferentlyassigned:

Additional adjustments - Date/Time

Additional adjustments - Reset

Page 57: Vegapuls 68

57

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Menu Menu item Default value

Setup Measurement loop name

Sensor

Medium Liquid/WaterBulk solids/Crushed stones, gravel

Application Storage tankSilo

Vessel form Vessel bottom, dished boiler endVessel top, dished boiler end

Vessel height/Measuring range

Recommended measuring range, see "Technicaldata" in the supplement

Min. adjustment Recommended measuring range, see "Technicaldata" in the supplement

Max. adjustment 0,000 m(d)

Damping 0.0 s

Current output mode

4 … 20 mA, < 3.6 mA

Current output Min./Max.

Min. current 3.8 mA, max. current 20.5 mA

Lock adjustment Released

Display Language Like order

Displayed value Distance

Display unit m

Scalingsize Volumel

Scaling 0.00 lin %, 0 l100.00 lin %, 100 l

Backlight Switched on

Additional adjust-ments

Distance unit m

Temperature unit °C

Probe length Length of the standpipe Ex factory

Linearisation curve

Linear

HART mode StandardAddress 0

ThesensorofferstheHARTmodesstandardandMultidrop.Inthismenu item you determine the HART modes and enter the address with Multidrop.

Additional adjustments - HART mode

Page 58: Vegapuls 68

58

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Themodestandardwiththefixedaddress0meansoutputofthemeasured value as 4 … 20 mA signal.In Multidrop mode, up to 63 sensors can be operated on one two-wire cable. An address between 1 and 63 must be assigned to each sen-sor.1)

The default setting is standard with address 0.

The instrument settings are copied with this function. The following functions are available:

• Store data from the sensor into the indicating/adjustment module.• Store data from the display and adjustment module in the sensor

The following data or settings for adjustment of the display and ad-justment module are saved:

• All data of the menu "Setup" and "Display"• In the menu "Additional settings" the items "Distance unit, tem-

perature unit and linearization"• Thevaluesoftheuserprogrammablelinearizationcurve

The copied data are permanently saved in an EEPROM memory in the display and adjustment module and remain there even in case of power failure. From there, they can be written into one or more sen-sors or kept as backup for a possible sensor exchange.The type and the volume of the copied data depend on the respective sensor.

Note:Before the data are stored in the sensor, a check is carried out to determineifthedatafitthesensor.Ifthedatadonotfit,afaultsignalis triggered or the function is blocked. When data are being written into the sensor, the display shows which instrument type the data originate from and which TAG-no. this sensor had.

In this menu, you read out the instrument name and the instrument serial number:

In this menu item, the hardware and software version of the sensor is displayed.

Additional adjustments - Copy instrument settings

Info - Instrument name

Info - Instrument version

1) The4…20mAsignaloftheHARTsensorisswitchedoff.Thesensorconsumes a constant current of 4 mA. The measuring signal is transmitted exclusively as digital HART signal.

Page 59: Vegapuls 68

59

6 Set up with the display and adjustment module

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

In this menu item, the date of factory calibration of the sensor as well as the date of the last change of sensor parameters are displayed via the display and adjustment module or via the PC.

In this menu item, the features of the sensor such as approval, pro-cessfitting,seal,measuringrange,electronics,housingandothersare displayed.

6.5 Saving the parameter adjustment dataWe recommended noting the adjusted data, e.g. in this operating instructions manual, and archiving them afterwards. They are thus available for multiple use or service purposes.If the instrument is equipped with a display and adjustment module, the data in the sensor can be saved in the display and adjustment module. The procedure is described in the operating instructions manual "Display and adjustment module" in the menu item "Copy sensor data". The data remain there permanently even if the sensor power supply fails.The following data or settings for adjustment of the display and ad-justment module are saved:

• All data of the menu "Setup" and "Display"• In the menu "Additional settings" the items "Sensor-specificunits,

temperature unit and linearization"• ThevaluesoftheuserprogrammablelinearizationcurveThe function can also be used to transfer settings from one instru-ment to another instrument of the same type. If it is necessary to exchange a sensor, the display and adjustment module is inserted into the replacement instrument and the data are likewise written into the sensor via the menu item "Copy sensor data".

Info - Date of manufacture

Instrument features

Page 60: Vegapuls 68

60

7 Setup with PACTware

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

7 Setup with PACTware

7.1 Connect the PC

3

1

2

Fig. 41: Connection of the PC directly to the sensor via the interface adapter1 USBcabletothePC2 InterfaceadapterVEGACONNECT3 Sensor

1

5

2 4

3 OPEN

TWIST

USB

LOCK

Fig.42:ConnectingthePCviaHARTtothesignalcable1 Sensor2 HARTresistance250Ω(optionaldependingonprocessing)3 Connection cable with 2 mm pins and terminals4 Processingsystem/PLC/Voltagesupply5 Interfaceadapter,forexampleVEGACONNECT4

Note:With power supply units with integrated HART resistance (internal resistanceapprox.250Ω),anadditionalexternalresistanceisnotnecessary. This applies, e.g. to the VEGA instruments VEGATRENN 149A, VEGAMET 381, VEGAMET 391. Common Ex separators are alsousuallyequippedwithasufficientcurrentlimitationresistance.In

Via the interface adapter directly on the sensor

Via the interface adapter and HART

Page 61: Vegapuls 68

61

7 Setup with PACTware

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

such cases, the interface converter can be connected parallel to the 4 … 20 mA cable (dashed line in the previous illustration).

7.2 Parameter adjustmentFor parameter adjustment of the instrument via a Windows PC, the configurationsoftwarePACTwareandasuitableinstrumentdriver(DTM) according to FDT standard are required. The latest PACTware version as well as all available DTMs are compiled in a DTM Collec-tion. The DTMs can also be integrated into other frame applications according to FDT standard.

Note:To ensure that all instrument functions are supported, you should always use the latest DTM Collection. Furthermore, not all described functionsareincludedinolderfirmwareversions.Youcandownloadthe latest instrument software from our homepage. A description of the update procedure is also available in the Internet.

Further setup steps are described in the operating instructions manu-al "DTMCollection/PACTware" attached to each DTM Collection and which can also be downloaded from the Internet. Detailed descrip-tions are available in the online help of PACTware and the DTMs.

Fig.43:ExampleofaDTMview

All device DTMs are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already included. An assistant for simpleprojectconfigurationsimplifiestheadjustmentconsiderably.Saving/printing the project as well as import/export functions are also part of the standard version.In the full version there is also an extended print function for complete project documentation as well as a save function for measured value

Prerequisites

Standard/Full version

Page 62: Vegapuls 68

62

7 Setup with PACTware

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

and echo curves. In addition, there is a tank calculation program as well as a multiviewer for display and analysis of the saved measured value and echo curves.The standard version is available as a download under www.vega.com/downloads and "Software". The full version is avail-able on CD from the agency serving you.

7.3 Saving the parameter adjustment dataWe recommend documenting or saving the parameter adjustment data via PACTware. That way the data are available for multiple use or service purposes.

Page 63: Vegapuls 68

63

8 Set up with other systems

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

8 Set up with other systems

8.1 DD adjustment programsDevice descriptions as Enhanced Device Description (EDD) are available for DD adjustment programs such as, for example, AMS™ and PDM.Thefilescanbedownloadedatwww.vega.com/downloads under "Software".

8.2 Field Communicator 375, 475Device descriptions for the instrument are available as EDD for pa-rameter adjustment with the Field Communicator 375 or 475.For the integration of the EDD in the Field Communicator 375 or 475, the software "Easy Upgrade Utility" is required which is available from the manufacturer. This software is updated via the Internet and new EDDs are automatically taken over into the device catalogue of this software after they are released by the manufacturer. They can then be transferred to a Field Communicator.

Page 64: Vegapuls 68

64

9 Diagnosis, asset management and service

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

9 Diagnosis, asset management and service

9.1 MaintenanceIf the device is used correctly, no maintenance is required in normal operation.Insomeapplications,buildupontheantennasystemcaninfluencethe measuring result. Depending on the sensor and application, make arrangements to avoid strong pollution of the antenna system. If nec-essary, clean the antenna system in certain intervals.

9.2 Measured value and event memoryThe instrument has several memories which are available for diagno-sis purposes. The data remain even with voltage interruption.

Up to 100,000 measured values can be stored in the sensor in a ring memory. Each entry contains date/time as well as the respective measured value. Storable values are for example:

• Distance• Filling height• Percentage value• Lin. percent• Scaled• Current value• Meas. reliability• Electronics temperature

When the instrument is shipped, the measured value memory is active and stores distance, measurement certainty and electronics temperature every 3 minutes.The requested values and recording conditions are set via a PC with PACTware/DTM or the control system with EDD. Data are thus read out and also reset.

Up to 500 events are automatically stored with a time stamp in the sensor (non-deletable). Each entry contains date/time, event type, event description and value. Event types are for example:

• Modificationofaparameter• Switch-onandswitch-offtimes• Status messages (according to NE 107)• Error messages (according to NE 107)

The data are read out via a PC with PACTware/DTM or the control system with EDD.

The echo curves are stored with date and time and the corresponding echo data. The memory is divided into two sections:Echo curve of the setup: This is used as reference echo curve for the measurement conditions during setup. Changes in the measure-ment conditions during operation or buildup on the sensor can thus berecognized.Theechocurveofthesetupisstoredvia:

Measured value memory

Event memory

Echo curve memory

Page 65: Vegapuls 68

65

9 Diagnosis, asset management and service

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

• PC with PACTware/DTM • Control system with EDD • Display and adjustment module

Further echo curves: Up to 10 echo curves can be stored in a ring bufferinthismemorysection.Furtherechocurvesarestoredvia:

• PC with PACTware/DTM • Control system with EDD

9.3 Asset Management functionThe instrument features self-monitoring and diagnostics according to NE 107 and VDI/VDE 2650. In addition to the status messages in the following tables, detailed error messages are available under menu item "Diagnostics" via the display and adjustment module, PACTware/DTM and EDD.

The status messages are divided into the following categories:

• Failure• Function check• Outofspecification• Maintenance requirement

and explained by pictographs:

41 2 3Fig. 44: Pictographs of the status messages1 Failure - red2 Outofspecification-yellow3 Function check - orange4 Maintenance - blue

Failure: Due to a malfunction in the instrument, a failure message is outputted.This status message is always active. It cannot be deactivated by the user.Function check: The instrument is in operation, the measured value is temporarily invalid (for example during simulation).This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD.Outofspecification: The measured value is unstable because the instrumentspecificationisexceeded(e.g.electronicstemperature).This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD.

Status messages

Page 66: Vegapuls 68

66

9 Diagnosis, asset management and service

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Maintenance:Duetoexternalinfluences,theinstrumentfunctionislimited.Themeasurementisaffected,butthemeasuredvalueisstill valid. Plan in maintenance for the instrument because a failure is expected in the near future (e.g. due to buildup).This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD.

The following table shows the error codes in the status message "Failure"andgivesinformationonthereasonandrectification.Keepin mind that some information is only valid with four-wire instruments.

CodeText message

Cause Rectification DevSpec State in CMD 48

F013no measured value available

– Sensor does not detect an echo during operation

– Antenna system dirty or defective

– Check or correct installation and/or parameter adjust-ment

– Clean or exchange process compo-nent or antenna

Bit 0 of Byte 0…5

F017Adjustment span too small

– Adjustment not withinspecification

– Change adjust-ment accord-ing to the limit values(differencebetween min. and max.≥10mm)

Bit 1 of Byte 0…5

F025Error in the lin-earizationtable

– Index markers are not continuously rising, for example illogical value pairs

– Checklineariza-tion table

– Delete table/Cre-ate new

Bit 2 of Byte 0…5

F036No operable software

– Failed or inter-rupted software update

– Repeat software update

– Check electronics version

– Exchanging the electronics

– Send instrument for repair

Bit 3 of Byte 0…5

F040Error in the electronics

– Hardware defect – Exchanging the electronics

– Send instrument for repair

Bit 4 of Byte 0…5

F080General soft-ware error

– General software error

– Disconnect operat-ingvoltagebriefly

Bit 5 of Byte 0…5

Failure

Page 67: Vegapuls 68

67

9 Diagnosis, asset management and service

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

CodeText message

Cause Rectification DevSpec State in CMD 48

F105Determine measured value

– The instrument is still in the start phase, the measured value could not yet be determined

– Wait for the end of the switch-on phase

– Duration depend-ing on the version and parameter adjustment up to approximately 3 min.

Bit 6 of Byte 0…5

F113Communica-tion error

– EMC interference – Transmission error

with the external communication with 4-wire power supply unit

– Remove EMC influences

– Exchange 4-wire power supply unit or electronics

Bit 12 of Byte 0…5

F125Impermissi-ble electronics temperature

– Temperature of the electronics in thenon-specifiedrange

– Check ambient temperature

– Isolate electronics – Use instrument

with higher tem-perature range

Bit 7 of Byte 0…5

F260Error in the cal-ibration

– Error in the calibra-tion carried out in the factory

– Error in the EEPROM

– Exchanging the electronics

– Send instrument for repair

Bit 8 of Byte 0…5

F261Error in the instrument set-tings

– Error during setup – False signal sup-

pression faulty – Error when carry-

ing out a reset

– Repeat setup – Carry out a reset

Bit 9 of Byte 0…5

F264Installation/Set-up error

– Adjustment not within the vessel height/measuring range

– Max. measuring range of the instru-mentnotsufficient

– Check or correct installation and/or parameter adjust-ment

– Use an instrument with bigger meas-uring range

Bit 10 of Byte 0…5

F265Measurement function dis-turbed

– Sensor no longer carries out a measurement

– Operating voltage too low

– Check operating voltage

– Carry out a reset – Disconnect operat-ingvoltagebriefly

Bit 11 of Byte 0…5

The following table shows the error codes and text messages in the status message "Function check" and provides information on causes as well as corrective measures.

Function check

Page 68: Vegapuls 68

68

9 Diagnosis, asset management and service

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

CodeText message

Cause Rectification DevSpec State in CMD 48

C700Simulation active

– A simulation is active – Finish simulation – Wait for the automatic end

after 60 mins.

"Simulation Active" in"StandardizedSta-tus 0"

The following table shows the error codes and text messages in the status message "Outofspecification" and provides information on causes as well as corrective measures.

CodeText message

Cause Rectification DevSpec State in CMD 48

S600Impermissible elec-tronics temperature

– Temperature of the electron-icsinthenon-specifiedrange

– Check ambient temperature – Isolate electronics – Use instrument with higher

temperature range

Bit 5 of Byte 14…24

S601Overfilling

– Dangerofvesseloverfilling – Make sure that there is no furtherfilling

– Check level in the vessel

Bit 6 of Byte 14…24

The following table shows the error codes and text messages in the status message "Maintenance" and provides information on causes as well as corrective measures.

CodeText message

Cause Rectification DevSpec State in CMD 48

M500Error with the reset de-livery status

– With the reset to delivery status, the data could not be restored

– Repeat reset – LoadXMLfilewithsensor

data into the sensor

Bit 0 of Byte 14…24

M501Error in the non-active linearizationtable

– Hardware error EEPROM – Exchanging the electronics – Send instrument for repair

Bit 1 of Byte 14…24

M502Error in the diagnosis memory

– Hardware error EEPROM – Exchanging the electronics – Send instrument for repair

Bit 2 of Byte 14…24

M503Meas. reliability too low

– The echo/noise ratio is too small for reliable measure-ment

– Check installation and process conditions

– Clean the antenna – Change polarisation direc-

tion – Use instrument with higher

sensitivity

Bit 3 of Byte 14…24

M504Error on an device in-terface

– Hardware defect – Check connections – Exchanging the electronics – Send instrument for repair

Bit 4 of Byte 14…24

Outofspecification

Maintenance

Page 69: Vegapuls 68

69

9 Diagnosis, asset management and service

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

CodeText message

Cause Rectification DevSpec State in CMD 48

M505No echo available

– Level echo can no longer be detected

– Clean the antenna – Use a more suitable

antenna/sensor – Remove possible false

echoes – Optimizesensorposition

and orientation

Bit 7 of Byte 14…24

9.4 Rectify faultsThe operator of the system is responsible for taking suitable meas-ures to rectify faults.

Thefirstmeasuresare:

• Evaluation of fault messages, for example via the display and adjustment module

• Checking the output signal• Treatment of measurement errors

Further comprehensive diagnostics options are available with a PC with PACTware and the suitable DTM. In many cases, the reasons can bedeterminedinthiswayandfaultsrectified.

Connect a multimeter in the suitable measuring range according to the wiring plan. The following table describes possible errors in the current signal and helps to eliminate them:

Error Cause Rectification

4 … 20 mA signal not stable

– Fluctuations of the measured variable

– Set damping appropriate to the instrument via the display and adjustment module or PACTware/DTM

4 … 20 mA signal missing

– Electrical con-nection faulty

– Check connection according to chapter "Connection steps" and if necessary, correct according to chapter "Wiring plan"

– Voltage supply missing

– Check cables for breaks; repair if necessary

– Operating volt-age too low or load resistance too high

– Check, adapt if necessary

Current sig-nal greater than 22 mA or less than 3.6 mA

– Electronics module in the sensor defec-tive

– Exchange the instrument or send it in for repair

The below tables show typical examples of application-related measurement errors with bulk solids. A distinction is made between measurement errors during:

Reaction when malfunc-tion occurs

Procedure for fault recti-fication

Check the 4 … 20 mA signal

Treatment of measure-ment errors with bulk solids

Page 70: Vegapuls 68

70

9 Diagnosis, asset management and service

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

• Constant level• Filling• Emptying

The images in column "Errorpattern" show the real level as a broken line and the level displayed by the sensor as a continuous line.

12

Leve

l

time0

1 Real level2 Level displayed by the sensor

Notes:

• Whenever the sensor displays a constant value, the reason could also be that the fault setting of the current output is set to "Hold value"

• If the level indication is too low, the reason could be a line resist-ance that is too high

Measurement error with constant level

Fault description Error pattern Cause Rectification

1. Measured value shows a too low or too high level

Leve

l

time0

– Min./max. adjustment not correct

– Adapt min./max. adjustment

– Incorrectlinearizationcurve – Adaptlinearizationcurve

2. Measured value jumps towards 100 % Le

vel

time0

– Due to the process, the amplitude of the product echo decreases

– A false signal suppression was not carried out

– Carry out a false signal sup-pression

– Amplitude or position of a false signal has changed (e.g. con-densation, buildup); false signal suppression no longer matches actual conditions

– Determine the reason for the changed false signals, carry out false signal suppression, e.g. with condensation

Page 71: Vegapuls 68

71

9 Diagnosis, asset management and service

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Measurementerrorduringfilling

Fault description Error pattern Cause Rectification

3. Measured value jumps towards 0 % duringfilling

Leve

l

time0

– Amplitude of a multiple echo (vessel top - product surface) is larger than the level echo

– Check parameter "Application", especially vessel top, type of medium, dished bottom, high dielectric constant, and adapt if necessary

– The level echo cannot be distin-guished from the false signal at a false signal position (jumps to multiple echo)

– Remove/reduce false signal: minimizeinterferinginstalla-tionsbychangingthepolariza-tion direction

– Chose a more suitable installa-tion position

– Transversereflectionfromanextraction funnel, amplitude of thetransversereflectionlargerthan the level echo

– Direct sensor to the opposite funnel wall, avoid crossing with thefillingstream

4. Measured val-uefluctuatesaround10 … 20 %

Leve

l

time0

– Various echoes from an uneven product surface, e.g. a material cone

– Check parameter "Type of medium" and adapt, if neces-sary

– Optimizeinstallationpositionand sensor orientation

– Reflectionsfromtheproductsurface via the vessel wall (deflection)

– Select a more suitable installa-tionposition,optimizesensororientation, e.g. with a swivel-ling holder

5. Measured value jumps sporadically to 100%duringfilling

Level

time0

– Changing condensation or con-tamination on the antenna

– Carry out a false signal sup-pression or increase false signal suppression with con-densation/contamination in the close range by editing

– With bulk solids use radar sen-sor with purging air connection orflexibleantennacover

Measurement error during emptying

Fault description Error pattern Cause Rectification

6. Measured value re-mains unchanged in the close range during emptying

Leve

l

time0

– False signal larger than the level echo

– Level echo too small

– Eliminate false signals in the close range. Check: Antenna must protrude out of the socket

– Remove contamination on the antenna

– Minimizeinterferinginstal-lations in the close range by changingthepolarizationdirection

– After eliminating the false sig-nals, the false signal suppres-sion must be deleted. Carry out a new false signal suppression

Page 72: Vegapuls 68

72

9 Diagnosis, asset management and service

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Fault description Error pattern Cause Rectification

7. Measured value jumps sporadically to-wards 100 % during emptying

Leve

l

time0

– Changing condensation or con-tamination on the antenna

– Carry out false signal suppres-sion or increase false signal suppression in the close range by editing

– With bulk solids use radar sen-sor with purging air connection orflexibleantennacover

8. Measured val-uefluctuatesaround10 … 20 %

Leve

l

time0

– Various echoes from an uneven product surface, e.g. an extrac-tion funnel

– Check parameter "Type of medium" and adapt, if neces-sary

– Optimizeinstallationpositionand sensor orientation

– Reflectionsfromtheproductsurface via the vessel wall (deflection)

Depending on the reason for the fault and the measures taken, the steps described in chapter "Setup" must be carried out again or must be checked for plausibility and completeness.

Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550.The hotline is also available outside normal working hours, seven days a week around the clock.Sinceweofferthisserviceworldwide,thesupportisprovidedinEnglish. The service itself is free of charge, the only costs involved are the normal call charges.

9.5 Exchanging the electronics moduleIf the electronics module is defective, it can be replaced by the user.In Ex applications, only instruments and electronics modules with ap-propriate Ex approval may be used.

If there is no electronics module available on site, the electronics module can be ordered through the agency serving you. The electron-icsmodulesareadaptedtotherespectivesensoranddifferinsignaloutput or voltage supply.The new electronics module must be loaded with the default settings of the sensor. These are the options:

• In the factory• Or on site by the user

In both cases, the serial number of the sensor is needed. The serial numbers are stated on the type label of the instrument, on the inside of the housing as well as on the delivery note.Whenloadingonsite,firstofalltheorderdatamustbedownloadedfrom the Internet (see operating instructions manual "Electronicsmodule").

Caution:Alluser-specificsettingsmustbeenteredagain.Hence,youhavetocarry out a new setup after the electronics exchange.

Reaction after fault recti-fication

24 hour service hotline

Page 73: Vegapuls 68

73

9 Diagnosis, asset management and service

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

If you have stored the data of the parameter adjustment during the firstsetupofthesensor,youcantransferthesetothereplacementelectronics module. A new setup is no more necessary.

9.6 Software updateThe following components are required to update the instrument software:

• Instrument• Voltage supply• Interface adapter VEGACONNECT• PC with PACTware• CurrentinstrumentsoftwareasfileYoucanfindthecurrentinstrumentsoftwareaswellasdetailedinformation on the procedure under "www.vega.com/downloads" and "Software".

Caution:Instruments with approvals can be bound to certain software versions. Thereforemakesurethattheapprovalisstilleffectiveafterasoftwareupdate is carried out.Youcanfinddetailedinformationatwww.vega.com/downloads and "Approvals".

9.7 How to proceed if a repair is necessaryYoucanfindarepairformaswellasdetailedinformationonhowtoproceed at www.vega.com/downloads and "Formsandcertificates".By doing this you help us carry out the repair quickly and without hav-ing to call back for needed information.If a repair is necessary, please proceed as follows:

• Printandfilloutoneformperinstrument• Clean the instrument and pack it damage-proof• Attach the completed form and, if need be, also a safety data

sheet outside on the packaging• Please contact the agency serving you to get the address for

thereturnshipment.Youcanfindtheagencyonourhomepagewww.vega.com.

Page 74: Vegapuls 68

74

10 Dismount

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

10 Dismount

10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel or pipeline, high temperatures, cor-rosive or toxic products etc.

Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order.

10.2 DisposalThe instrument consists of materials which can be recycled by spe-cialised recycling companies. We use recyclable materials and have designed the parts to be easily separable.Correctdisposalavoidsnegativeeffectsonhumansandtheenviron-ment and ensures recycling of useful raw materials.Materials: see chapter "Technicaldata"If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal.

WEEE directive 2002/96/EGThis instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws. Pass the instrument directly on to a spe-cialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive.

Page 75: Vegapuls 68

75

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

11 Supplement

11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts

Ʋ Processfitting 316L, Alloy C22 (2.4602), Alloy 400 (2.4360) Ʋ Process seal On site (instruments with thread: Klingersil C-4400 is

attached) Ʋ Antenna 316L,Alloy C22 (2.4602), Tantalum, 316L electropol-

ished, stainless steel investment casting 1.4848, Alloy 400 (2.4360), 316L Safecoat coated

Ʋ Antenna impedance cone PTFE TFM 1600 or PTFE INOFLON M290, PP, PEEK, ceramic (99.7 % Al2O3)

Ʋ seal, antenna system FKM(SHSFPM70C3GLT),FFKM(Kalrez6375),FFKM(Kalrez6230-FDA),graphite(99.9%)

Materials, non-wetted parts Ʋ Plastic housing plastic PBT (Polyester) Ʋ Aluminium die-casting housing Aluminium die-casting AlSi10Mg, powder-coated - basis:

Polyester Ʋ Stainless steel housing 316L Ʋ Seal between housing and housing cover

NBR (stainless steel housing, precision casting), silicone (aluminium/plastic housing; stainless steel housing, electropolished)

Ʋ Inspection window in housing cover (optional)

Polycarbonate

Ʋ Ground terminal 316LOhmic contact Betweengroundterminal,processfittingandantennaProcessfittings

Ʋ Pipe thread, cylindrical (ISO 228 T1) G1½ according to DIN 3852-A Ʋ American pipe thread, conically 1½ NPT, 2 NPT Ʋ Flanges DIN from DN 25, ASME from 1"

Weights Ʋ Instrument (depending on housing, processfittingandantenna)

approx. 2 … 17.2 kg (4.409 … 37.92 lbs)

Ʋ Antenna extension 1.6 kg/m (1.157 lbs/ft)Length antenna extension max. 5.85 m (19.19 ft)Torque for NPT cable glands and Conduit tubes

Ʋ Plastic housing max. 10 Nm (7.376 lbf ft) Ʋ Aluminium/Stainless steel housing max. 50 Nm (36.88 lbf ft)

Page 76: Vegapuls 68

76

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Input variableMeasured variable The measured quantity is the distance between process

fittingofthesensorandproductsurface.Thereferenceplane is the seal surface on the hexagon or the lower sideoftheflange.

3

42

1

Fig. 54: Data of the input variable1 Reference plane2 Measured variable, max. measuring range3 Antenna length4 Usefulmeasuringrange

Max. measuring range 75 m (246.1 ft)Recommended meas. range depending on the antenna diameter

Ʋ ø 40 mm (1.575 in) up to 15 m (49.21 ft) Ʋ ø 48 mm (1.89 in) up to 20 m (65.62 ft) Ʋ ø 75 mm (2.953 in) up to 40 m (131.2 ft) Ʋ ø 95 mm (3.74 in) up to 50 m (164 ft) Ʋ Parabolic antenna up to 75 m (246.1 ft)

Output variableOutput signal 4 … 20 mA/HARTRange of the output signal 3.8 … 20.5 mA/HART (default setting)Signal resolution 0.3 µAResolution, digital < 1 mm (0.039 in)Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mAMax. output current 22 mA

Page 77: Vegapuls 68

77

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Starting current ≤3.6mA;≤10mAfor5msafterswitchingonLoad see load diagram under Power supplyDamping (63 % of the input variable), adjustable

0 … 999 s

HART output values according to HART 7.02)

Ʋ PV (Primary Value) Lin. percent Ʋ SV (Secondary Value) Distance Ʋ TV (Third Value) Meas. reliability Ʋ QV (Fourth Value) Electronics temperature

FulfilledHARTspecification 7.0Further information on Manufacturer ID, Device ID, Device Revision

See website of HART Communication Foundation

Accuracy (according to DIN EN 60770-1)Process reference conditions according to DIN EN 61298-1

Ʋ Temperature +18 … +30 °C (+64 … +86 °F) Ʋ Relative humidity 45 … 75 % Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions Ʋ Min. distance to internal installations > 200 mm (7.874 in) Ʋ Reflector Flatplatereflector Ʋ Falsereflections Biggest false signal, 20 dB smaller than the useful signal

Deviation with liquids See following diagrams

1,0 m (3.28 ft)

10 mm (0.394 in)

2 mm (0.079 in)

- 2 mm (- 0.079 in)

- 10 mm (- 0.394 in)

0

1 2 3

Fig. 55: Deviation under reference conditions1 Reference plane2 Antenna edge3 Recommended measuring range

Repeatability ≤±1mmDeviation with bulk solids The values depend to a great extent on the application.

Bindingspecificationsarethusnotpossible.DeviationunderEMCinfluence ≤±30mm

2) Default values, can be assigned individually

Page 78: Vegapuls 68

78

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

VariablesinfluencingmeasurementaccuracySpecificationsapplytothedigitalmeasuredvalueTemperature drift - Digital output ±3mm/10K,max.10mmAdditional deviation through electromag-netic interference acc. to EN 61326

<±50mm

SpecificationsapplyalsotothecurrentoutputTemperature drift - Current output ±0.03%/10Krelatingtothe16mAspanmax.±0.3%Deviation on the current output through analogue/digital conversion

<±15µA

Deviation in the current output due to strong, high-frequency electromagnetic fieldsacc.toEN61326

<±150µA

Characteristics and performance dataMeasuring frequency K-band(26GHztechnology)Measuring cycle time approx. 700 msStep response time3) ≤3sBeam angle4)

Ʋ Horn antenna ø 40 mm (1.575 in) 20° Ʋ Horn antenna ø 48 mm (1.89 in) 15° Ʋ Horn antenna ø 75 mm (2.953 in) 10° Ʋ Horn antenna ø 95 mm (3.74 in) 8° Ʋ Parabolic antenna 3°

Emitted HF power (depending on the parameter adjustment)5)

Ʋ Average spectral transmission power density

-14dBm/MHzEIRP

Ʋ Max. spectral transmission power density

+43dBm/50MHzEIRP

Ʋ Max. power density at a distance of 1 m

< 1 µW/cm²

Ambient conditionsAmbient, storage and transport tempera-ture

-40 … +80 °C (-40 … +176 °F)

Process conditionsFortheprocessconditions,pleasealsonotethespecificationsonthetypelabel.Thelowestvaluealways applies.

3) Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk solidsapplications,untiltheoutputsignalhastakenforthefirsttime90%ofthefinalvalue(IEC61298-2).

4) Outsidethespecifiedbeamangle,theenergyoftheradarsignalisreducedby50%(-3dB).5) EIRP: Equivalent Isotropic Radiated Power.

Page 79: Vegapuls 68

79

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Seal Antenna impedance cone

Process temperature (measured on the process fitting)

FKM (SHS FPM 70C3 GLT)

PTFE -40 … +130 °C (-40 … +266 °F)

PTFE6) -40 … +200 °C (-40 … +392 °F)

PEEK7) -40 … +200 °C (-40 … +392 °F)

FFKM(Kalrez6375) PTFE -20 … +130 °C (-4 … +266 °F)

PEEK -20 … +250 °C (-4 … +482 °F)

FFKM(Kalrez6230) PTFE -15 … +130 °C (5 … +266 °F)

PEEK -15 … +250 °C (5 … +482 °F)

Graphite Ceramic -196 … +450 °C (-321 … +842 °F)

Graphite(processfittingAlloy C22)

Ceramic -196 … +400 °C (-321 … +752 °F)

Vessel pressure - horn antenna Ʋ Antenna impedance cone PTFE -1 … 40 bar (-100 … 4000 kPa/-14.5 … 580 psig) Ʋ Antenna impedance cone PP -1 … 3 bar (-100 … 300 kPa/-14.5 … 43.5 psig) Ʋ Antenna impedance cone PEEK -1 … 100 bar (-100 … 10000 kPa/-14.5 … 1450 psig) Ʋ Antenna impedance cone ceramic -1 … 160 bar (-100 … 16000 kPa/-14.5 … 2320 psig)

Vessel pressure - parabolic antenna -1 … 6 bar (-100 … 6000 kPa/-14.5 … 870 psig)Vessel pressure with swivelling holder -1 … 1 bar (-100 … 100 kPa/-14.5 … 14.5 psig)Vesselpressurerelatingtotheflangenominal pressure stage

see supplementary instructions manual "Flanges ac-cordingtoDIN-EN-ASME-JIS"

Vibration resistance Ʋ Horn antenna 4gat5…200HzaccordingtoEN60068-2-6(vibration

with resonance) Ʋ Parabolic antenna 1gat5…200HzaccordingtoEN60068-2-6(vibration

with resonance)Shock resistance

Ʋ Horn antenna 100 g, 6 ms according to EN 60068-2-27 (mechanical shock)

Ʋ Parabolic antenna 25 g, 6 ms according to EN 60068-2-27 (mechanical shock)

Data on rinsing air connectionMax. permissible pressure 6 bar (87.02 psig)Air volume with horn antenna, depending on pressure (recommended area)

Pressure Withoutrefluxvalve Withrefluxvalve

0.5 bar (7.25 psig) 3.3 m3/h 1.2 m3/h

0.6 bar (8.70 psig) 3.5 m3/h 1.4 m3/h

0.7 bar (10.15 psig) 3.7 m3/h 1.7 m3/h

6) Not with steam7) Not with steam

Page 80: Vegapuls 68

80

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Pressure Withoutrefluxvalve Withrefluxvalve

0.8 bar (11.60 psig) 3.9 m3/h 1.8 m3/h

0.9 bar (13.05 psig) 4.0 m3/h 2.1 m3/h

1 bar (14.5 psig) 4.2 m3/h 2.2 m3/h

1.5 bar (21.76 psig) 5.0 m3/h 3.2 m3/h

2 bar (29.0 psig) 5.5 m3/h 4.5 m3/h

Air volume with parabolic antenna, depending on pressure (recommended area)

Pressure Withoutrefluxvalve Withrefluxvalve

0.5 bar (7.25 psig) 3.0 m3/h 1.2 m3/h

0.6 bar (8.70 psig) 3.2 m3/h 1.4 m3/h

0.7 bar (10.15 psig) 3.4 m3/h 1.7 m3/h

0.8 bar (11.60 psig) 3.5 m3/h 1.9 m3/h

0.9 bar (13.05 psig) 3.6 m3/h 2.0 m3/h

1 bar (14.5 psig) 3.8 m3/h 2.2 m3/h

1.5 bar (21.76 psig) 4.3 m3/h 3.5 m3/h

2 bar (29.0 psig) 4.8 m3/h 4.0 m3/h

Thread G⅛Closure with

Ʋ Non-Ex Dust protection cover of PE Ʋ Ex Threaded plug of 316Ti

Refluxvalve-unmounted(asoptionwithnon-Exversion,includedinthescopeofdeliverywithExversion)

Ʋ Material 316Ti Ʋ Seal FKM(SHSFPM70C3GLT),FFKM(Kalrez6375) Ʋ for tube diameter 6 mm Ʋ opening pressure 0.5 bar (7.25 psig) Ʋ Nominal pressure stage PN 250

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable gland M20 x 1.5 or ½ NPTWire cross-section (spring-loaded terminals)

Ʋ Massive wire, stranded wire 0.2 … 2.5 mm² (AWG 24 … 14) Ʋ Stranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16)

Electromechanical data - version IP 66/IP 68 (1 bar)Options of the cable entry

Ʋ Cable gland with integrated connec-tion cable

M20 x 1.5 (cable: ø 5 … 9 mm)

Ʋ Cable entry ½ NPT

Page 81: Vegapuls 68

81

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Ʋ Blind plug M20 x 1.5; ½ NPTConnection cable

Ʋ Wire cross-section 0.5 mm² (AWG 20) Ʋ Wire resistance <0.036Ω/m Ʋ Tensile strength < 1200 N (270 lbf) Ʋ Standard length 5 m (16.4 ft) Ʋ Max. length 180 m (590.6 ft) Ʋ Min. bending radius 25 mm (0.984 in) with 25 °C (77 °F) Ʋ Diameter approx. 8 mm (0.315 in) Ʋ Colour - Non-Ex version Black Ʋ Colour - Ex-version Blue

Display and adjustment moduleDisplay element Display with backlightMeasured value indication

Ʋ Number of digits 5 Ʋ Sizeofdigits W x H = 7 x 13 mm

Adjustment elements 4 keysProtection rating

Ʋ unassembled IP 20 Ʋ mounted in the housing without lid IP 40

Materials Ʋ Housing ABS Ʋ Inspection window Polyester foil

Interface to the external display and adjustment unitData transmission Digital (I²C-Bus)Connection cable Four-wire

Sensor version Configuration,connectioncable

Cable length Standard cable Special cable Screened

4 … 20 mA, 4 … 20 mA/HART 50 m ● – –

ProfibusPA,Founda-tion Fieldbus 25 m – ● ●

Integrated clockDate format Day.Month.YearTime format 12 h/24 hTimezoneExfactory CETRate deviation max. 10.5 min/year

Page 82: Vegapuls 68

82

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Measurement electronics temeratureResolution 0.1 °C (1.8 °F)Accuracy ±1°C(1.8°F)Permissible temperature range -40 … +85 °C (-40 … +185 °F)

Voltage supplyOperating voltage UB

Ʋ Non-Ex instrument 9.6 … 35 V DC Ʋ Ex ia instrument 9.6 … 30 V DC Ʋ Ex-d-ia instrument 14 … 35 V DC Ʋ Ex-d-ia instrument with ship approval 15 … 35 V DC

Operating voltage UB - illuminated display and adjustment module Ʋ Non-Ex instrument 16 … 35 V DC Ʋ Ex ia instrument 16 … 30 V DC Ʋ Ex-d-ia instrument No lighting (integrated ia barrier)

Reverse voltage protection IntegratedPermissible residual ripple - Non-Ex, Ex-ia instrument

Ʋ for 9.6 V< UB < 14 V ≤0.7Veff(16…400Hz) Ʋ for 18 V< UB < 36 V ≤1.0Veff(16…400Hz)

Permissible residual ripple - Ex-d-ia instrument Ʋ for 18 V< UB < 36 V ≤1Veff(16…400Hz)

Load resistor Ʋ Calculation (UB - Umin)/0.022 A Ʋ Example - Non-Ex instrument with UB= 24 V DC

(24V-9.6V)/0.022A=655Ω

Electrical protective measuresProtection rating

Housing material Version IP-protection class NEMA protection

Plastic Single chamber IP 66/IP 67 NEMA4X

Double chamber IP 66/IP 67 NEMA4X

Aluminium Single chamber IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA 6PNEMA 6P

Double chamber IP 66/IP 67IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA4XNEMA 6PNEMA 6P

Stainless steel, electro-polished

Single chamber IP 66/IP 68 (0.2 bar) NEMA 6P

Page 83: Vegapuls 68

83

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Housing material Version IP-protection class NEMA protection

Stainless steel, precision casting

Single chamber IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA 6PNEMA 6P

Double chamber IP 66/IP 67IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA4XNEMA 6PNEMA 6P

Protection rating (IEC 61010-1) III

ApprovalsInstrumentswithapprovalscanhavedifferenttechnicalspecificationsdependingontheversion.For that reason the associated approval documents of these instruments have to be carefully noted. They come with the delivery or can be downloaded under www.vega.com, "VEGATools" and "Instrument search" as well as under www.vega.com/downloads and "Approvals".

11.2 DimensionsThe following dimensional drawings represent only an extract of all possible versions. Detailed dimensional drawings can be downloaded at www.vega.com/downloads under "Drawings".

Plastic housing~ 69 mm(2.72")

ø 79 mm(3.11")

112

mm

(4.4

1")

M20x1,5/½ NPT

~ 84 mm(3.31")

M16x1,5

112

mm

(4.4

1")

M20x1,5/½ NPT1 2

ø 79 mm(3.11")

Fig.56:HousingversionswithprotectionratingIP66/IP67-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version2 Double chamber version

Page 84: Vegapuls 68

84

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

Aluminium housing

21

ø 86 mm(3.39")

~ 116 mm(4.57")

116

mm

(4.5

7")

M20x1,5M20x1,5/½ NPT

~ 87 mm(3.43")

M16x1,5

ø 86 mm(3.39")

120

mm

(4.7

2")

M20x1,5/½ NPT

Fig.57:HousingversionswithprotectionratingIP66/IP68(0.2bar)-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version2 Double chamber version

Aluminium housing with protection rating IP 66/IP 68 (1 bar)

120

mm

(4.7

2")

~ 105 mm(4.13")

116

mm

(4.5

7")

~ 150 mm(5.91")

ø 86 mm(3.39")

ø 86 mm(3.39")

M20x1,5/½ NPT

M16x1,5

2

M20x1,5M20x1,5

1

Fig.58:HousingversionwithprotectionratingIP66/IP68(1bar)-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version2 Double chamber version

Page 85: Vegapuls 68

85

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

Stainless steel housing~ 69 mm(2.72")

ø 79 mm(3.11")

117

mm

(4.6

1")

M20x1,5/½ NPT

~ 59 mm(2.32")

ø 80 mm(3.15")

112

mm

(4.4

1")

M20x1,5/½ NPT

~ 87 mm(3.43")

ø 86 mm(3.39")

120

mm

(4.7

2")

M20x1,5/½ NPT

M16x1,5

321

Fig.59:HousingversionswithprotectionratingIP66/IP68(0.2bar)-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version, electropolished2 Single chamber version, precision casting3 Double chamber version, precision casting

Stainless steel housing with protection rating IP 66/IP 68, 1 bar11

7 m

m(4

.61"

)

~ 103 mm(4.06") ø 79 mm

(3.11")

120

mm

(4.7

2")

~ 105 mm(4.13") ø 86 mm

(3.39")

M20x1,5

M20x1,5/½ NPT

M16x1,5

~ 93 mm(3.66") ø 80 mm

(3.15")

112

mm

(4.4

1")

M20x1,5/½ NPT

321

Fig.60:HousingversionwithprotectionratingIP66/IP68(1bar)-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version, electropolished2 Single chamber version, precision casting3 Double chamber version, precision casting

Page 86: Vegapuls 68

86

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

VEGAPULS 68, horn antenna in threaded version

mm

inch

38 m

m (1

.50"

)

22 m

m (0

.87"

)

22 m

m (0

.87"

)

SW 46 mm(1.81")

8.50"16.93"

3.94" ø1.58"ø1.89"ø2.95"ø3.74"

4.72"

x y 100 ø40 120 ø48 216 ø75 430 ø95

1½" 2" 3" 4"

x y 1½" 2" 3" 4"

x

yG1½A / 1½ NPT

x

y

2 1

144

mm

(5.6

7")

Fig.61:VEGAPULS68,hornantennainthreadedversion1 Standard2 With temperature adapter up to 250 °C

Page 87: Vegapuls 68

87

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

VEGAPULS68,hornantennainflangeversion

x

y

21

165

mm

(6.5

")60 m

m(2

.36"

)

mm inch

8.50"16.93"

3.94" ø1.58"ø1.89"ø2.95"ø3.74"

4.72"

xy100 ø40120 ø48216 ø75430 ø95

1½"2"3"4"

xy1½"2"3"4"

Fig.62:VEGAPULS68,hornantennainflangeversion1 Standard2 With temperature adapter up to 250 °C

Page 88: Vegapuls 68

88

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

VEGAPULS68,hornantennainflangeversionwithpurgingairconnection

x

y

x

y

21

3 4

3 4

41,5

mm

(1.6

3")

83 m

m(3

.27"

)

190

mm

(7.4

8")

49 mm(1.93")

41 mm(1.61")

mm inch

8.50"16.93"

3.94" ø1.58"ø1.89"ø2.95"ø3.74"

4.72"

xy100 ø40120 ø48216 ø75430 ø95

1½"2"3"4"

xy1½"2"3"4"

45,5

mm

(1.7

9")

49 mm(1.93")

41 mm(1.61")

Fig.63:VEGAPULS68,hornantennainflangeversionwithpurgingairconnection1 Standard2 With temperature adapter up to 250 °C3 Blind plug4 Refluxvalve

Page 89: Vegapuls 68

89

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

VEGAPULS68,hornantennainflangeversion450°C

y

x

inch

8.50"11.30"

ø 1.89"ø 2.95"ø 3.74"

4.72"

mm xy120 ø 48216 ø 75287 ø 95

2"3"4"

xy2"3"4"

260

mm

(10.

24")

Fig.64:VEGAPULS68,hornantennainflangeversionwithtemperatureadapterupto450°C

Page 90: Vegapuls 68

90

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

VEGAPULS 68, horn antenna and swivelling holder

20 m

m(0

.79"

)

20 m

m(0

.79"

)

max. 15°(0.59")

40 m

m(1

.58"

)

146

mm

(5.7

5")

x

y

x

y

3.94" ø 1.58"ø 1.89"ø 2.95"ø 3.74"

4.72"8.50"

16.93"

x y 100 ø 40120 ø 48216 ø 75430 ø 95

1½" 2" 3" 4"

x y 1½"2"3"4"

mm

inch

21

Fig.65:VEGAPULS68,hornantennaandswivellingholder1 Standard2 With temperature adapter up to 250 °C

Page 91: Vegapuls 68

91

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

VEGAPULS68,hornantennaandswivellingholder,threadedfitting

max. 10°(0.39")

53,6

mm

(2.1

1")

159,

6 m

m(6

.28"

)

102,

2 m

m(4

.02"

)

ø 40 / 48 mm(1.57" / 1.89")

G2 / 2NPT

SW 70 mm(2.76")10

2,2

mm

(4.0

2")

ø 40 / 48 mm(1.57" / 1.89")

21

Fig.66:VEGAPULS68,hornantennaandswivellingholder,threadedfitting1 Standard2 With temperature adapter up to 250 °C

Page 92: Vegapuls 68

92

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

VEGAPULS 68, parabolic antenna and swivelling holder

130

mm

(5.1

2")

ø 243 mm (9.57")

1

40 m

m(1

.58"

)

max. 15°(0.59")

120

mm

(4.7

2")

2

Fig.67:VEGAPULS68,parabolicantennaandswivellingholder1 Standard2 With temperature adapter up to 200 °C

Page 93: Vegapuls 68

93

11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

11.3 Industrial property rightsVEGA product lines are global protected by industrial property rights. Further information see www.vega.com.Only in U.S.A.: Further information see patent label at the sensor housing.VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte.Nähere Informationen unter www.vega.com.Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec-tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com.VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus-trial. Para mayor información revise la pagina web www.vega.com.Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную собственность. Дальнейшую информацию смотрите на сайте www.vega.com.VEGA系列产品在全球享有知识产权保护。进一步信息请参见网站<www.vega.com。

11.4 TrademarkAll the brands as well as trade and company names used are property of their lawful proprietor/originator.

Page 94: Vegapuls 68

94

INDEX

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-150625

INDEX

AAdjustment 48, 49Agitator 25Application

– Bulk solid 45 – Liquid 41 – Standpipe 42

BBacklight 51

CCable entry 13Check output signal 69Connecting

– Electrically 30 – To the PC 60

Connection – Cable 29 – Steps 30 – Technology 30

Copy sensor settings 58Current output Min./Max. 50Current output mode 50Curve indication

– Echo curve 53 – False signal suppression 53

DDamping 49Date/Time 56Default values 56Deviation 69Device units 53

EEcho curve memory 64Echo curve of the setup 53EDD (Enhanced Device Description) 63Electronics and terminal compartment, single chamber housing 32Electronics temperature 52Error codes 67, 68Event memory 64

FFalse signal suppression 54Faultrectification69Functional principle 9

GGrounding 29

HHART

– Resistor 60HART mode 57

IIndication of the measured value 51Instrument version 58

LLanguage 50Linearisation curve 55Lock adjustment 50

MMain menu 40Meas. reliability 52Measured value memory 64Measurement loop name 40

NNAMUR NE 107 66, 68

OOperation

– System 39OverfillprotectionaccordingtoWHG55

PPeak value indicator 51PIN 50, 55Polarisation 17

RRead out info 58Reflectionproperties41Repair 73Reset 56

SSensor status 51Service hotline 72Simulation 52Socket 19Status messages - NAMUR NE 107 65Subsurface enclosure 26

Page 95: Vegapuls 68

95

INDEX

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

3653

5-EN

-150

625

TType label 8

VVessel form 47Vessel height 47Vessel installations 24Vessel insulation 25

Page 96: Vegapuls 68

Printing date:

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany

3653

5-E

N-1

5062

5

All statements concerning scope of delivery, application, practical use and operat-ing conditions of the sensors and processing systems correspond to the information available at the time of printing.Subject to change without prior notice

© VEGA Grieshaber KG, Schiltach/Germany 2015