+ All Categories
Home > Documents > Ventiladores Inyección Oficinas

Ventiladores Inyección Oficinas

Date post: 03-Jun-2018
Category:
Upload: gilto-plata
View: 223 times
Download: 0 times
Share this document with a friend

of 48

Transcript
  • 8/12/2019 Ventiladores Inyeccin Oficinas

    1/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 87 92 93 92 91 87 79 74 95 83 38

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    46

    2

    26.375

    42.5

    Model: SBPS-42-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 2

    Weight w/o Acc's (lb) 218

    Weight w/ Acc's (lb) 432

    Max T Motor Frame Size 184

    Optional Damper (in.) 42 x 42

    Wall Opening (in.) 47.625 x 47.625

    PerformanceRequested Volume (CFM) 12,954

    Actual Volume (CFM) 12,954

    External SP (in. wg) 0.48

    Total SP (in. wg) 0.48

    Fan RPM 934

    Operating Power (hp) 1.91

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 4.9

    Tip Speed (ft/min) 10,273

    Motor

    Motor Mounted Yes

    Size (hp) 3

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 4.8

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/201Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S2-1 yMark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 1 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    2/48

    Model: SBPS-42-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-42-S - Short, 42Damper: WD430-42X42 - Gravity

    10/10/201Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S2-1 yMark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 2 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    3/48DAMPER

    42

    42

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/201Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S2-1 yMark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 3 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    4/48

    46.125

    1.5

    46.125

    44

    Standard Construction Features:

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    10/10/201Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S2-1 yMark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 4 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    5/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 83 93 87 85 84 82 76 70 89 78 29

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    34

    1.25

    20

    30.375

    Model: SBPS-30-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 3

    Weight w/o Acc's (lb) 111

    Weight w/ Acc's (lb) 259

    Max T Motor Frame Size 184

    Optional Damper (in.) 31 x 31

    Wall Opening (in.) 35.625 x 35.625

    PerformanceRequested Volume (CFM) 7,436

    Actual Volume (CFM) 7,436

    External SP (in. wg) 0.46

    Total SP (in. wg) 0.46

    Fan RPM 1171

    Operating Power (hp) 1.1

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 5.9

    Tip Speed (ft/min) 9,199

    Motor

    Motor Mounted Yes

    Size (hp) 1 1/2

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 3

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/201Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S2-3,4 yMark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 5 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    6/48

    Model: SBPS-30-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-30-S - Short, 30Damper: WD430-31X31 - Gravity

    10/10/201Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S2-3,4 yMark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 6 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    7/48DAMPER

    31

    31

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/201Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S2-3,4 yMark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 7 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    8/48

    34.125

    1.5

    34.125

    38

    Standard Construction Features:

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    10/10/201Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S2-3,4 yMark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 8 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    9/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 86 91 85 82 80 78 73 69 86 74 25

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    28

    1.25

    18

    24.375

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 6

    Weight w/o Acc's (lb) 92

    Weight w/ Acc's (lb) 211

    Max T Motor Frame Size 145

    Optional Damper (in.) 25 x 25

    Wall Opening (in.) 29.625 x 29.625

    PerformanceRequested Volume (CFM) 4,688

    Actual Volume (CFM) 4,688

    External SP (in. wg) 0.52

    Total SP (in. wg) 0.52

    Fan RPM 1321

    Operating Power (hp) 0.83

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 6.6

    Tip Speed (ft/min) 8,302

    Motor

    Motor Mounted Yes

    Size (hp) 1

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 2.1

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S7-54 a 5Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 9 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    10/48

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-24-S - Short, 24Damper: WD430-25X25 - Gravity

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S7-54 a 5Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 10 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    11/48DAMPER

    25

    25

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S7-54 a 5Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 11 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    12/48

    28.125

    1.5

    28.125

    37

    Standard Construction Features:

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S7-54 a 5Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 12 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    13/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 87 90 85 81 79 77 72 68 85 73 24

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    28

    1.25

    18

    24.375

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 6

    Weight w/o Acc's (lb) 92

    Weight w/ Acc's (lb) 211

    Max T Motor Frame Size 145

    Optional Damper (in.) 25 x 25

    Wall Opening (in.) 29.625 x 29.625

    PerformanceRequested Volume (CFM) 4,040

    Actual Volume (CFM) 4,040

    External SP (in. wg) 0.5

    Total SP (in. wg) 0.5

    Fan RPM 1252

    Operating Power (hp) 0.7

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 7.2

    Tip Speed (ft/min) 7,867

    Motor

    Motor Mounted Yes

    Size (hp) 1

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 2.1

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S7-60 a 6Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 13 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    14/48

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-24-S - Short, 24Damper: WD430-25X25 - Gravity

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S7-60 a 6Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 14 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    15/48DAMPER

    25

    25

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S7-60 a 6Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 15 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    16/48

    28.125

    1.5

    28.125

    37

    Standard Construction Features:

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-S7-60 a 6Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 16 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    17/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 86 91 85 82 80 78 73 69 85 74 24

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    28

    1.25

    18

    24.375

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 6

    Weight w/o Acc's (lb) 92

    Weight w/ Acc's (lb) 211

    Max T Motor Frame Size 145

    Optional Damper (in.) 25 x 25

    Wall Opening (in.) 29.625 x 29.625

    PerformanceRequested Volume (CFM) 4,660

    Actual Volume (CFM) 4,660

    External SP (in. wg) 0.48

    Total SP (in. wg) 0.48

    Fan RPM 1283

    Operating Power (hp) 0.76

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 6.9

    Tip Speed (ft/min) 8,062

    Motor

    Motor Mounted Yes

    Size (hp) 1

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 2.1

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-6 a Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 17 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    18/48

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-24-S - Short, 24Damper: WD430-25X25 - Gravity

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-6 a Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 18 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    19/48DAMPER

    25

    25

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-6 a Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 19 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    20/48

    28.125

    1.5

    28.125

    37

    Standard Construction Features:

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-6 a Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 20 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    21/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 87 90 84 81 79 77 72 67 85 73 23

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    28

    1.25

    18

    24.375

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 6

    Weight w/o Acc's (lb) 75

    Weight w/ Acc's (lb) 194

    Max T Motor Frame Size 145

    Optional Damper (in.) 25 x 25

    Wall Opening (in.) 29.625 x 29.625

    PerformanceRequested Volume (CFM) 4,012

    Actual Volume (CFM) 4,012

    External SP (in. wg) 0.48

    Total SP (in. wg) 0.48

    Fan RPM 1230

    Operating Power (hp) 0.67

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 7.3

    Tip Speed (ft/min) 7,729

    Motor

    Motor Mounted Yes

    Size (hp) 3/4

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 1.6

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-12 a Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 21 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    22/48

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-24-S - Short, 24Damper: WD430-25X25 - Gravity

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-12 a Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 22 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    23/48DAMPER

    25

    25

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-12 a Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 23 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    24/48

    28.125

    1.5

    28.125

    37

    Standard Construction Features:

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-12 a Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 24 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    25/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 86 91 85 82 80 78 73 69 85 74 24

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    28

    1.25

    18

    24.375

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 6

    Weight w/o Acc's (lb) 92

    Weight w/ Acc's (lb) 211

    Max T Motor Frame Size 145

    Optional Damper (in.) 25 x 25

    Wall Opening (in.) 29.625 x 29.625

    PerformanceRequested Volume (CFM) 4,660

    Actual Volume (CFM) 4,660

    External SP (in. wg) 0.48

    Total SP (in. wg) 0.48

    Fan RPM 1283

    Operating Power (hp) 0.76

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 6.9

    Tip Speed (ft/min) 8,062

    Motor

    Motor Mounted Yes

    Size (hp) 1

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 2.1

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-18 a 2Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 25 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    26/48

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-24-S - Short, 24Damper: WD430-25X25 - Gravity

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-18 a 2Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 26 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    27/48DAMPER

    25

    25

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-18 a 2Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 27 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    28/48

    28.125

    1.5

    28.125

    37

    Standard Construction Features:

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-18 a 2Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 28 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    29/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 87 90 84 81 79 77 72 67 85 73 23

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    28

    1.25

    18

    24.375

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 6

    Weight w/o Acc's (lb) 75

    Weight w/ Acc's (lb) 194

    Max T Motor Frame Size 145

    Optional Damper (in.) 25 x 25

    Wall Opening (in.) 29.625 x 29.625

    PerformanceRequested Volume (CFM) 4,012

    Actual Volume (CFM) 4,012

    External SP (in. wg) 0.48

    Total SP (in. wg) 0.48

    Fan RPM 1230

    Operating Power (hp) 0.67

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 7.3

    Tip Speed (ft/min) 7,729

    Motor

    Motor Mounted Yes

    Size (hp) 3/4

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 1.6

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-24 a 2Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 29 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    30/48

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-24-S - Short, 24Damper: WD430-25X25 - Gravity

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-24 a 2Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 30 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    31/48DAMPER

    25

    25

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-24 a 2Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 31 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    32/48

    28.125

    1.5

    28.125

    37

    Standard Construction Features:

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-24 a 2Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 32 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    33/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 86 91 85 82 80 78 73 69 85 74 24

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    28

    1.25

    18

    24.375

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 6

    Weight w/o Acc's (lb) 92

    Weight w/ Acc's (lb) 211

    Max T Motor Frame Size 145

    Optional Damper (in.) 25 x 25

    Wall Opening (in.) 29.625 x 29.625

    PerformanceRequested Volume (CFM) 4,660

    Actual Volume (CFM) 4,660

    External SP (in. wg) 0.48

    Total SP (in. wg) 0.48

    Fan RPM 1283

    Operating Power (hp) 0.76

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 6.9

    Tip Speed (ft/min) 8,062

    Motor

    Motor Mounted Yes

    Size (hp) 1

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 2.1

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-30 a 3Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 33 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    34/48

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-24-S - Short, 24Damper: WD430-25X25 - Gravity

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-30 a 3Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 34 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    35/48DAMPER

    25

    25

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-30 a 3Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 35 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    36/48

    28.125

    1.5

    28.125

    37

    Standard Construction Features:

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-30 a 3Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 36 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    37/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 87 90 84 81 79 77 72 67 85 73 23

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    28

    1.25

    18

    24.375

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 6

    Weight w/o Acc's (lb) 75

    Weight w/ Acc's (lb) 194

    Max T Motor Frame Size 145

    Optional Damper (in.) 25 x 25

    Wall Opening (in.) 29.625 x 29.625

    PerformanceRequested Volume (CFM) 4,012

    Actual Volume (CFM) 4,012

    External SP (in. wg) 0.48

    Total SP (in. wg) 0.48

    Fan RPM 1230

    Operating Power (hp) 0.67

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 7.3

    Tip Speed (ft/min) 7,729

    Motor

    Motor Mounted Yes

    Size (hp) 3/4

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 1.6

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-36 a 4Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 37 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    38/48

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-24-S - Short, 24Damper: WD430-25X25 - Gravity

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-36 a 4Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 38 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    39/48DAMPER

    25

    25

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-36 a 4Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 39 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    40/48

    28.125

    1.5

    28.125

    37

    Standard Construction Features:

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-36 a 4Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 40 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    41/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 86 91 85 82 80 78 73 69 86 74 24

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    28

    1.25

    18

    24.375

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 6

    Weight w/o Acc's (lb) 92

    Weight w/ Acc's (lb) 211

    Max T Motor Frame Size 145

    Optional Damper (in.) 25 x 25

    Wall Opening (in.) 29.625 x 29.625

    PerformanceRequested Volume (CFM) 4,660

    Actual Volume (CFM) 4,660

    External SP (in. wg) 0.5

    Total SP (in. wg) 0.5

    Fan RPM 1301

    Operating Power (hp) 0.79

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 6.8

    Tip Speed (ft/min) 8,173

    Motor

    Motor Mounted Yes

    Size (hp) 1

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 2.1

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-42 a 4Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 41 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    42/48

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-24-S - Short, 24Damper: WD430-25X25 - Gravity

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-42 a 4Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 42 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    43/48DAMPER

    25

    25

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-42 a 4Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 43 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    44/48

    28.125

    1.5

    28.125

    37

    Standard Construction Features:

    Notes: All dimensions shown are in units of in.

    Short Wall Housing

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-42 a 4Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 44 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    45/48

    Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 87 90 84 81 79 77 72 67 85 73 23

    SUPPLY FANS CAN CARRY RAIN

    OR SNOW INTO THE BUILDING

    AIR FLOW

    See the Assembly Drawing For

    Selected Accessories

    28

    1.25

    18

    24.375

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    DimensionalQuantity 6

    Weight w/o Acc's (lb) 75

    Weight w/ Acc's (lb) 194

    Max T Motor Frame Size 145

    Optional Damper (in.) 25 x 25

    Wall Opening (in.) 29.625 x 29.625

    PerformanceRequested Volume (CFM) 4,012

    Actual Volume (CFM) 4,012

    External SP (in. wg) 0.48

    Total SP (in. wg) 0.48

    Fan RPM 1230

    Operating Power (hp) 0.67

    Elevation (ft) 7,347

    Airstream Temp.(F) 70

    Air Density (ft3) 0.057

    Drive Loss (%) 7.3

    Tip Speed (ft/min) 7,729

    Motor

    Motor Mounted Yes

    Size (hp) 3/4

    V/C/P 460/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 1.6

    Notes:All dimensions shown are in units of in..

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighed sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5.0 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5.0 ft

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-48 a 5Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 45 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    46/48

    Model: SBPS-24-3H

    Sidewall Belt Drive Supply Fan

    Standard Construction Features:Model SBPS is belt driven with fabricated steel or cast aluminum blades

    depending on the level of construction. Model SBPS is suitable for supply in clean

    air applications including factories and warehouses. Propellers are available in

    three levels of construction from commercial to industrial. Multiple blade designs

    for low sound and optimum efficiency. The "L-type" design is for low static

    pressures and low sound levels. The "H-type" design is for higher static

    pressures. Fans feature adjustable motor pulleys to allow for final system

    balancing.

    - Die formed, galvanized steel drive frame assembly - Level 1: galvanized steel

    blades - Level 2: reinforced galvanized steel blades - Level 3: cast aluminum

    blades - Assembled motor and drives - Static-resistant belts - Adjustable motor

    pulley - Ball bearing motors - Fan shaft mounted in ball bearing pillow blocks -

    Corrosion-resistant fasteners - UL/cUL 705 Electrical (Model SBP)

    Options & Accessories:

    Wall Housing: HSG-24-S - Short, 24Damper: WD430-25X25 - Gravity

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-48 a 5Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 46 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    47/48DAMPER

    25

    25

    Standard Construction Features:

    Damper WD430 is used in vertical mount systems to allow airflow in one direction and prevent airflow in the opposite

    direction.Available as gravity backdraft, WD430 is constructed of galvanized steel with aluminum blades. WD430 (flange on

    ntake) can be used in vertical supply applications and is recommended for velocities up to 2,500 fpm or 2 in. wg.

    Damper Configuration:

    Actuator Type: Gravity

    Notes: All dimensions shown are in units of in.

    Width And height furnished approximately 0.125 in. undersize

    Vertical Mount Intake Damper

    Model: WD430

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-48 a 5Mark:

    CAPS 4.12.1241 I:\Jobs\MASTER PLAN II REINGENIERIA SOTANOS.gfcj Page 47 of

  • 8/12/2019 Ventiladores Inyeccin Oficinas

    48/48

    28.125

    1.5

    28.125

    37

    Standard Construction Features:

    Short Wall Housing

    10/10/20Printed Date:MASTER PLAN II REINGENIERIA SOTANOJob:

    VIO-ST-48 a 5Mark:


Recommended