Veris Differential Pressure Transducer Connection Instructions For use with HOBO® H22, U12, U30, UX120-006M, and RX3000 data loggers and HOBO ZW data nodes
Applies to these Veris Differential Pressure Transducers:
Onset Part No. Air Pressure Range Output Veris Part No.
T-VER-PXU-L 0-10” WC 4-20mA (or 0-5V/0-10V) representing 0 to 10” WC PXULX05S (LCD display)
T-VER-PXU-X 0-10” WC 4-20mA (or 0-5V/0-10V) representing 0 to 10” WC PXUXX05S (no display)
This document provides instructions on connecting the Veris Differential Pressure Transducers listed above to each of the following:
• FlexSmart™ Analog Module used with HOBO H22 series data loggers
• Analog Sensor Port/Module used with HOBO U30 and RX3000 series data loggers
• Voltage adapter used with the U12 and UX120-006M data loggers and ZW series data nodes
It also lists configuration values used by HOBOware® software to configure the logger for each transducer. Note: For information on connecting the differential pressure transducer to the pressure source, and other transducer details, refer to the documentation provided by Veris.
Required • Selected Veris Differential Pressure Transducer
• HOBO H22, U12, U30, UX120-006M, or RX3000 data logger, or HOBO ZW data node
• FlexSmart Analog Module, Onset Part No: S-FS-CVIA (for H22 series); Analog Sensor Port/Module option (for U30 and RX3000 series); voltage adapter, Onset Part No. CABLE-ADAP5 or CABLE-ADAP10 (for U12, UX120-006M, or ZW series)
• HOBOware software, version 2.2.1 or higher (2.4.0 or higher for U30 series; 3.6 or higher for UX120-006M); HOBOware Pro 3.0 or higher for ZW series
• HOBOlink (for RX3000 series data loggers)
• Customer-supplied length of 18 AWG, shielded, multi-conductor cable
Connecting the Differential Pressure Transducer to the Analog Module or Port
HOBO H22 Series Data Logger
S-FS-CVIAFlexSmart Analog Module
Customer-supplied 18 AWG shielded multi-conductor cable
Differential Pressure Transducer
Shl
dS
1+S
1-E
xc+
Exc
-S
2+S
2-
Conductor
Conductor
POWER/4-20mAOUT (0-10V)COM
Terminal Blockinside transducer housing
for 4-20mA Output
ZE
RO
N/CN/C
N/CConductor
Conductor
POWER/4-20mAOUT (0-10V)COM
for 0-5V/0-10V Output
ZE
RO
N/CN/C
Conductor
FlexSmart Analog Module
Terminal Blockinside transducer housing
Shl
dS
1+
S1-
Exc
+E
xc-
S2+
S2-
FlexSmart Analog Module
H22 Connection
Veris Differential Pressure Transducer(Onset Part No. T-VER-PXU-L shown)
Office: Jl. Radin Inten II No. 62 Duren Sawit, Jakarta 13440 - IndonesiaWorkshop: Jl. Pahlawan Revolusi No. 22B, Jakarta 13430 - IndonesiaPhone: 021-8690 6777 (Hunting)
Fax: 021-8690 6777Mobile: +62 816 1740 8925Fax: 021-8690 6771
Veris Differential Pressure Transducer Connection Instructions
Page 2 of 3
U30 or RX3000 Connection (U30 Shown)
Shi
eld
Ch1
Sig
nal
Ch1
Ret
urn
Exc
Out
Analog Sensor Port
Shi
eld
Ch2
Sig
nal
Ch2
Ret
urn
Ext
Re
turn
Conductor
Conductor
POWER/4-20mAOUT (0-10V)COM
for 4-20mA Output
ZE
RO
N/CN/C
N/C
for 0-5V/0-10V Output
Conductor
Conductor
POWER/4-20mAOUT (0-10V)COM
ZE
RO
N/CN/C
Conductor
Terminal Blockinside transducer housing
Terminal Blockinside transducer housing
Analog Sensor PortHOBO U30 Series Data Logger
Shi
eld
Ch1
Sig
nal
Ch1
Ret
urn
Exc
Out
Analog Sensor Port
Shi
eld
Ch2
Sig
nal
Ch2
Ret
urn
Ext
Re
turn
Differential Pressure Transducer
Customer-supplied 18 AWG shielded multi-conductor cable
ZW, U12, and UX120-006M Connection
Connect to analog port
HOBO ZW Series Wireless Data Node or U12 Series Data Logger(ZW shown)
AC-SENS-1*
*CAUTION: Polarity is very important! Before plugging AC-SENS-1 into AC power, make sure the correct polarity lead connections to device are made as shown!
POWER/4-20mAOUT (0-10V)COM
for 4-20mA Output
ZE
RO
for 0-5V/0-10V Output
Terminal Blockinside transducer housing
CABLE-4-20MA (for 4-20mA output) or CABLE-ADAP5 (for 0-5VDC output) orCABLE-ADAP10 (for 0-10VDC output)
Differential Pressure Transducer
AC-SENS-1*
(+)
(-)
Yellow (+)
Blue (-)
CABLE-4-20MA
POWER/4-20mAOUT (0-10V)COM
ZE
RO
Terminal Blockinside transducer housingAC-SENS-1*
(+)
(-)
White (+)
Black (-)
CABLE-ADAP5 or CABLE-ADAP10
(Red wire not used)
N/CN/C
N/CN/C
N/C
Use appropriate termination for connection (denoted with )
HOBO ZW Series Wireless Data Node; U12 or UX120-006M Logger
Veris Differential Pressure Transducer Connection Instructions
Configuring the Data Logger for the Differential Pressure Transducer using HOBOware Software
HOBOware software provides configuration files for the transducers. The table below lists the recommended configuration values that these files contain. For information on loading configuration files, refer to the software documentation.
Onset Part Nos. Channel Name
Warm-Up Measurement Type
Raw Value 1
Raw Value 2
Raw Units
Scaled Value 1
Scaled Value 2
Scaled Units
T-VER-PXU-L and T-VER-PXU-X
Diff Pressure 20 sec Current 4 20 mA 0 0.1 (or 0.25, 0.5, 1, 2.5, 5, or 10)
in WC
Voltage 0 5 (or 10) V
Notes: • Excitation power provided by the FlexSmart Analog Module (Onset Part No. S-FS-CVIA) with H22; by the Analog
Sensor Port/Module with U30 and RX3000; and by power adapter (Onset Part No. AC-SENS-1) with ZW, U12, or UX120-006M.
• Both differential pressure transducer models have switch-selectable ranges and scales, as listed.