one quarter inch = one foot
0
one eighth inch = one foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
three quarters inch = one foot
F
04
three eighths inch = one foot
80
E 4
one half inch = one foot
0
D 46"
02
one inch = one foot
C
6"
0
one and one half inches = one foot
2
B
6"
01
A
three inches = one foot
6"
0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE
100% SUBMITTAL 11/21/14
BID DOCUMENTS 12/19/146/10
/201
5 10
:57:
23 A
MF
ile N
ame G0.1
RNLPSH
COVER SHEET
11/21/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
GENERAL
G0.1 COVER SHEET
ARCHITECTURAL
A0.1 ABBREVIATIONS AND SYMBOLSA0.2 SECOND FLOOR LIFE SAFETY PLANA0.3 FINISH AND DOOR SCHEDULESA1.1 DEMOLITION FLOOR PLANA1.2 DEMOLITION RCP PLANA2.1 NEW WORK FLOOR PLANA2.2 NEW WORK RCP PLANA3.1 INTERIOR ELEVATIONSA4.1 INTERIOR DETAILS
DRAWING SHEET INDEX
Project Number: 539-15-103REMODEL 2nd FLOOR LABS, BLDG. 15
Prepared For:DEPARTMENT OF VETERANS AFFAIRSCINCINNATI VA MEDICAL CENTER3200 Vine StreetCincinnati, Ohio 45220
Prepared By:App Architecture615 Woodside DriveEnglewood, Ohio 45322
Heapy Engineering1400 West Dorothy LaneDayton, Ohio 45409
VICINITY MAP
PROJECT LOCATION
BID DOCUMENTS
FIRE PROTECTION
FX0.1 LEGENDS AND SYMBOLSFX1.2 SECOND FLOOR PLAN - NEW WORK
PLUMBING
P0.1 LEGENDS AND SYMBOLSP0.2 SCHEDULES AND DIAGRAMSP1.2 SECOND FLOOR PLAN - REMOVALSP2.2 SECOND FLOOR PLAN - NEW WORK
MECHANICAL
M0.1 INDEX, LEGEND, AND GENERAL NOTESM0.2 SCHEDULES AND DETAILSM0.3 CONTROLS AND DETAILSM1.1 SECOND FLOOR PLAN - REMOVALSM2.1 SECOND FLOOR PLAN - NEW WORK
ELECTRICAL
E0.1 LEGEND AND SYMBOLSE0.2 SINGLE LINE DIAGRAME0.3 PANELBOARD SCHEDULESE0.4 LIGHTING DETAILSE0.5 TECHNOLOGY SYMBOLS AND DETAILSE0.6 EXISTING SIGNALS CLOSET DETAILSE1.1 BASEMENT FLOOR PLAN - REMOVALSE1.2 SECOND FLOOR PLAN - REMOVALSE2.1 SECOND FLOOR PLAN - NEW WORK - LIGHTINGE2.2 SECOND FLOOR PLAN - NEW WORK - POWERE2.3 SECOND FLOOR - NEW WORK - SIGNALS
COPYRIGHT © 2014GOOGLE MAPS
AABVA/CAPCADJAFFAHUALALTANODANCHAPAPPOXARCHATTENAUTOAUXAVG
@&LØC[OP
BCBLDGBDBLKBLKGBMBOTBRGBSMTBUR
CCABCBC/CCEMCFCGCIRCJCLGCLOSCLRCMTCMUCOCOLCONCCONSTCONTCPUCRSCY
DBLDEMODEVDFDIADIMDISPDIVDSDRDRWGDET
EEAECEIFSEJELECELEVEMERGEPEPTEQEQUIPEWCEXIST OR EXEXPEXT
FABFDFEFECFFFINFLRFNDFTFTGFTWFURFVFOW
F
A
B
C
D
E
SYMBOL
L
L2
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
ABBREVIATIONS
ATANDANGLEDIAMETERCENTER LINECHANNELOXYGENPLATE
AIR (MEDICAL)ABOVEAIR CONDITIONINGACOUSTICAL PANEL CEILINGADJACENT OR ADJUSTABLEABOVE FINISHED FLOORAIR HANDLER UNITALUMINUMALTERNATEANODIZEDANCHORACCESS PANELAPPROXIMATELYARCHITECT OR ARCHITECTURALATTENUATEDAUTOMATICAUXILIARYAVERAGE
BASE CABINETSBUILDINGBOARDBLOCKBLOCKINGBEAMBOTTOMBEARINGBASEMENTBUILT-UP ROOF
CARPETCABINETCATCH BASINCENTER TO CENTERCEMENTCUBIC FOOTCORNER GUARDCIRCLECONTROL JOINTCEILINGCLOSETCLEARCERAMIC MOSAIC TILECONCRETE MASONRY UNITCLEAN OUTCOLUMNCONCRETECONSTRUCTIONCONTINUOUS OR CONTINUECENTRAL PROCESSING UNIT (COMPUTER)COURSE OR COURSINGCUBIC YARD
DOUBLEDEMOLISH, DEMOLITIONDEVELOPMENTDRINKING FOUNTAINDIAMETERDIMENSIONDISPENSERDIVISIONDOWNSPOUTDOORDRAWINGDETAIL
EASTEACHELECTRICAL CONTRACTOREXTERIOR INSULATION AND FINISH SYSTEMEXPANSION JOINTELECTRIC OR ELECTRICALELEVATION OR ELEVATOREMERGENCYELECTRICAL PANELEPOXY PAINTEQUALEQUIPMENTELECTRIC WATER COOLEREXISTINGEXPANSIONEXTERIOR
FABRICATED OR FABRICATINGFLOOR DRAINFIRE EXTINGUISHERFIRE EXTINGUISHER CABINETFINISH FLOORFINISH OR FINISHEDFLOORFOUNDATIONFOOT OR FEET OR FULLY TEMPEREDFOOTINGFIRE TREATED WOODFURRINGFIELD VERIFYFACE OF WALL
GAGALVGBGCGDGENGLGNDGYPGWBGWT
GUAGE OR GAGEGALVANIZEDGRAB BARGENERAL CONTRACTORGRADE OR GRADINGGENERALGLASS OR GLAZINGGROUNDGYPSUMGYPSUM WALLBOARDGLAZED WALL TILE
HBHDHDWHMHORIZHPDLHRHTHVACHWD
HOSE BIBBHEADHARDWAREHOLLOW METALHORIZONTALHIGH PRESSURE DECORATIVE LAMINATEHOURHEIGHTHEATING, VENTILATING & AIR CONDITIONHARDWARE
IDIGININCLINTINVIV
INSIDE DIAMETERINSULATED GLASSINCHINCLUDE (D) (ING)INTERIORINVERTINTRAVENOUS
JBJC
JUNCTION BOXJANITOR CLOSET
KKT
KIPSKITCHEN
LLAVLBSLCDLHLINLLLLHLLVLTLTLLVR
LONGLAVATORYPOUNDSLIQUID CRYSTAL DISPLAY (MONITOR)LEFT HANDLINEARLIVE LOADLONG LEG HORIZONTALLONG LEG VERTICALLIGHTLINTELLOUVER
MMASMATMAXMCMECHMEDMFRMHMILMMMINMISCMOMTDMTGMTL
MEN OR METERMASONRYMATERIAL OR WALKOFF MATMAXIMUMMECHANICAL CONTRACTORMECHANICALMEDICINEMANUFACTURERMOUNTING HEIGHT, MANHOLETHOUSANDTHS OF AN INCHMILLIMETERMINIMUMMISCELLANEOUSMASONRY OPENINGMOUNTEDMOUNTINGMETAL
NNATNCNICNONOMNRCNTS
NORTH OR NITROGENNATURALNURSE CALLNOT IN CONTRACTNUMBER OR NITROUS OXIDENOMINALNOISE REDUCTION COEFFICIENTNOT TO SCALE
ODOHOHDOPNGOPPOX
OUTSIDE DIAMETEROVERHEADOVERHEAD DOOROPENINGOPPOSITEOXYGEN
PARPCPCFPLPLASPLAMPLBGPLWDPMEPNLPRPSFPSIPPVC
PARALLELPLUMBING CONTRACTORPOUNDS PER CUBIC FOOTPLATE OR PROPERTY LINEPLASTERPLASTIC LAMINATEPLUMBINGPLYWOODPLUMBING, MECHANICAL & ELECTRICALPANELPAIRPOUNDS PER SQUARE FOOTPOUNDS PER SQUARE INCHPAINTPOLYVINYL CHLORIDE
QTQUANT
QUARRYQUANTITY
RRARBRDRECEPTREFREFRIGREGREINFREMREQDRETREVRHRMROROW
RADIUS OR RISERRETURN AIRRUBBER BASEROOF DRAINRECEPTACLEREFERENCEREFRIGERATORREGISTRATIONREINFORCEREMOVEREQUIREDRETURNREVISIONRIGHT HANDROOMROUGH OPENINGRIGHT OF WAY
SSASANSBSCSCHEDSEALSECTSFSGSHSHTSHTGSIMSPECSPKSQSRVSSSSMSTSTCSTDSTLSTORSTRSUSPSVSWDSYMSYS
SOUTHSUPPLY AIRSANITARYSINK BASESOLID CORESCHEDULESEALANTSECTIONSQUARE FEETSAFETY GLASSSPRINKLER HEAD OR SHOWER HEADSHEETSHEATHINGSIMILARSPECIFICATION(S)SPEAKERSQUARESERVICESTAINLESS STEELSOLID SURFACING MATERIALSTREETSOUND TRANSMISSION CLASSIFICATIONSTANDARDSTEELSTORAGESTRUCTURALSUSPENDEDSHEET VINYLSOFTWOODSYMMETRICALSYSTEM
TT & GTBT&BTELTHKTKBDTOCTOSTOMTOWTPDTRANSTVTYP
TREADTONGUE & GROOVETOWEL BAR OR TACKBOARDTOP AND BOTTOMTELEPHONETHICKTACKBOARDTOP OF CONCRETETOP OF STEELTOP OF MASONRYTOP OF WALLTOILET PAPER DISPENSERTRANSFORMERTELEVISIONTYPICAL
UCUCRUHULUNOUTILUR
UNDER CABINET OR COUNTERUNDER COUNTER REFRIGERATORUNIT HEATERUNDERWRITERS LABORATORYUNLESS NOTED OTHERWISEUTILITYURINAL
VVARVBVCTVERTVJVSVWBVWCVYL
VACUUMVARNISHVAPOR BARRIERVINYL COMPOSITION TILEVERTICALV-JOINT (ED)VACUUM SLIDEVINYL WALL BORDERVINYL WALL COVERINGVINYL
WW/W/OWBWCWDWFWGWHWINWPWPTWRGBWTWWF
WIDE OR WEST OR WOMENWITHWITHOUTWOOD BASEWATER CLOSET OR WALL CABINETWOODWIDE FLANGEWIRE GLASSWALL HUNG OR WATER HEATERWINDOWWEATHERPROOFWOOD PRESERVATIVE TREATMENTWATER RESISTANT GYPSUM BACKING BOARDWEIGHTWELDED WIRE FABRIC
REFERENCE SYMBOLS DRAWING SYMBOLS
DRAWING TITLE
ROOMNAME
BUILDING/DETAIL SECTION
ENLARGED DETAIL
EXTERIOR ELEVATIONS
MATCH LINE
MATERIAL SYMBOLS IN SECTION
COLUMN CENTER LINES
ROOM SYMBOL
PLAN SYMBOLS
ELEVATION SYMBOLS
TYPICAL WALL CONVENTIONS
INTERIOR ELEVATION SYMBOLS
REFLECTED CEILING SYMBOLS
B1
A1.1
B1
A1.1
1 ¼ = 1'-0"
A1.1 2
1
3
4
A1
A1.1
DRAWING TITLE
SCALE OF DRAWING
DRAWING REFERENCE NUMBER
DRAWING REFERENCE NUMBER
DRAWING SHEET NUMBER
DRAWING REFERENCE NUMBER
DRAWING SHEET NUMBER
DRAWING REFERENCE NUMBER
DRAWING REFERENCE NUMBER
DRAWING SHEET NUMBER
DRAWING SHEET NUMBER
FIRST FLOOR PLAN
1
A
101
ROOM NAME
ROOM NUMBER
CONSTRUCTION NOTES
DEMOLITION NOTES
ACCESSORIES (LETTERS)
DOOR NUMBER SYMBOL
WINDOW SYMBOL
WALL TYPE
REVISION / CHANGE
FLOOR DRAIN
ROOF DRAIN
ROD OR SHELF(CLOSETS)
PROTECTIVE CORNERGUARD (PLAN VIEW)
END WALL PROTECTOR
LIMIT OF CONSTRUCTIONAREA
FIRE EXTINGUISHER CABINETMOUNT @ 56" A.F.F. TO TOP OF UNIT)
SURFACE MOUNTEDLIGHT FIXTURES
RECESSEDLIGHT FIXTURES
CALL LIGHT
EXIT LIGHT
EMERGENCY EGRESS LIGHTWITH 90 MINUTE BATTERY
SUPPLY DIFFUSER
RETURN
SMOKE DETECTOR
SPEAKER
SPRINKLER HEAD
CURTAIN OR IV TRACK
CEILING HEIGHT
S
S
9'-6"
00
00
00
101
101
A1
14
F.D.
R.D.
C.G.
E.W.P.
FEC
DUPLEX RECEPTACLE
TELE/DATA OUTLET
LIGHT SWITCH
DUPLEX RECEPTACLE(EMERGENCY POWER)
NURSE CALL BUTTON
CODE BLUE BUTTON
MEDICAL GAS OUTLET
L
NC
CB
EXISTING CONSTRUCTION TO BE REMOVED
EXISTING CONSTRUCTION TO REMAIN
NEW CONSTRUCTION (REMODELING)
NEW CONSTRUCTION (NEW BUILDING OR ADDITION)
CHANGE IN ELEVATION
ELEVATION
GRANULAR FILL
EARTH
CONCRETE
CONCRETE BLOCK
GYPSUM
RIGID INSULATION
LOOSE ORBATTINSULATION
PLASTER
PLYWOOD
BLOCKING / SHIM
STEEL
BRICK
SOLID BRG. C.M.U.
WOOD, FINISHED
WOOD, DIMENSIONAL
4' -
6"
BO
TT
OM
2' -
6"
OF
TU
B
TO
P O
F E
XT
ING
UIS
HE
R
4' -
6"
MA
X.
7' -
6"
MIN
IMU
M
EXITWALL OR CEILING MOUNTED
AD
A
AD
A
L
4"
5' -
0"
MIN
.
6' -
8"
MA
X.
SIGNAGE
FIRE ALARMHORN/STROBE/CHIME
1' -
6"
DU
PLE
X
4-P
LEX
DA
TA
PO
RT
EM
ER
GE
NC
Y D
UP
LEX
FINISHFLOOR
4"
66".
54".
COAT RACK ROD FIRE EXTINGUISHERCABINET
TYPICAL SIGNAGE AND FIRE ALARMSTROBELIGHT LOCATION WHEN NEXT TO DOOR
GENERAL WALL DEVICES
AD
A
AD
A
AD
A
AD
A
AD
A
3' -
2"
4' -
0"
6' -
0"
8"
1' - 6"
2' - 3". 30" x 60" SHOWER
36" x 36" SHOWER
CURTAINROD
SHOWERSEAT
1' -
6" 3'
- 4
"
2' -
10"
FINISHFLOOR 6" MAX.
8" MIN.
MIN.
1' - 5".
9" 2' -
3"
MIN
.
2' -
5"
MIN
.
2' -
10"
MA
X.
BO
TT
OM
3' -
4"
MA
X.
OF
MIR
RO
R
1' - 3" 1' - 3"
2' -
5".
2' -
10"
MA
X.
3' -
4"
MA
X.
4' -
0"
MA
X.
4' -
0"
4' -
6"
3' -
6".
SOAPDISPENSER
PAPERTOWELDISPENSER
HAND DRYER
1' -
5"
1' - 0" 3' - 6" MIN.
4' - 0"
4' - 6" MIN.
NC
2' -
10" 4' -
0"
2' -
10"
6" 3' - 0"
1' - 6"
1' -
5" 3' -
8"
MA
X.
1' -
5"
1' - 3" 1' - 3" 1' - 3" 1' - 3"
2' -
0"
1' -
6"
3' -
6"
URINALSCREEN
2' -
3"
MA
X.
TO
SP
OU
T
3' -
0"
MA
X.
2' -
10"
SHOWER TOWEL BAR TYPICAL ADACLEARANCEAT LAVATORIES
ADALAVATORIESCLEARANCES
ADA TOILETCLEARANCES
TOILETTISSUE
ADA TOILETCLEARANCES
ADAURINAL
TYPICALURINAL
ADA WATER COOLER BABYCHANGINGSTATION
MOUNTING & CLEARANCE STANDARDS N.T.S. (FOLLOW THESE UNLESS NOTED OTHERWISE)
1' -
6"
3' -
3 1
/16"
NURSE CALL3' - 4"
INTERIOR ELEVATIONS
A1.1 2
1
3
4DRAWING REFERENCE NUMBER
DRAWING SHEET NUMBER
8"
1 1/
2"
one quarter inch = one foot
0
one eighth inch = one foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
three quarters inch = one foot
F
04
three eighths inch = one foot
80
E 4
one half inch = one foot
0
D 46"
02
one inch = one foot
C
6"
0
one and one half inches = one foot
2
B
6"
01
A
three inches = one foot
6"
0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE
100% SUBMITTAL 11/21/14
BID DOCUMENTS 12/19/146/10
/201
5 10
:56:
48 A
MF
ile N
ame A0.1
JKFPSH
ABBREVIATIONS AND SYMBOLS
11/21/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
F F
K
S
R
T
T T T
T
T
TT
T T
T
T
T
T
T
T
T
T
T T
T
TF F
K
S
R
CODE INFORMATION
PROJECT DESCRIPTION:
PROJECT CONSISTS OF RENOVATION TO BUILDING 015, SECOND FLOOR TO CREATE A NEWOFFICE SPACE AND PROVIDE NEW LABORATORY CASEWORK.
BUILDING DESCRIPTION:
BUILDING 015 CONSISTS OF 4 STORIES PLUS BASEMENT.
USE GROUP CLASSIFICATION:
HEIGHT AND AREA LIMITATIONS
CONSTRUCTION TYPE CLASSIFICATION:
OCCUPANT LOAD
INTERIOR FINISHES
(BASED ON 2012 NFPA 101 & OBC 2011)
FIRE PROTECTION
FIRE ALARM SYSTEM
LEGEND
OTHER PROVISIONS
NFPA 101 6.1.11
NFPA 101 6.2.2
= USE GROUP - BUSINESS
= HAZARDOUS CLASSIFICATION - ORDINARY
RENOVATION AREAS = SECOND FLOOR 2,954 SF (INTERIOR)
FIRE RESISTANT RATINGS:
CORRIDORS NO REQUIREMENTS
FLOOR OPENINGS 1/2 HR. (EXISTING OPENINGS IN EXISTING BUILDING)
EXIT ENCLOSURES 2 HRS. CONNECTING 4 STORIES OR MORE
NFPA 101 39.1.6. = EXISTING BLDG. CONSTRUCTION - NO REQUIREMENTS
NFPA 101 39.3.3 MINIMUM FINISHES REQUIREMENTS:
- INTERIOR WALL AND CEILING FINISHES - EITHER CLASS A, B, C - INTERIOR FLOOR FINISH - NO REQUIREMENTS - EXITS AND CORRIDORS - EITHER CLASS A, B
BUILDING DESCRIPTION: = FULLY AUTOMATIC FIRE SUPPRESSION
REQUIREMENT: REQUIRED
NFPA 101 39.1.7 / 7.3.1.2 30 PERSONS (100 NET OCCUPANTS / SF)
CLEAR WIDTH CORRIDOR (NFPA 39.2.3.2) = 44 IN. (MAX 50 OCCUPANTS)
DEAD END CORRIDOR (NFPA 39.2.5.2) = 50 FT. MAX.
COMMON PATH OF TRAVEL (NFPA 39.2.5.3.1) = 100 FT. MAX. (WITH SPRINKLER SYSTEM)
TRAVEL DISTANCE (NFPA 39.2.6.3) = 300 FT. MAX. (WITH SPRINKLER SYSTEM)
PORTABLE FIRE EXTINGUISHERS = MIN RATED 2-A(NFPA 101 9.7.4 / NFPA 10) 75 FT MAX TRAVEL DISTANCE
(2) PROVIDED
A. ALL PENETRATIONS IN FIRE RATED PARTITIONS SHALL BE FIRESTOPPED WHETHER NEWOR EXISTING. INCLUDING THOSE CREATED BY THE REMOVAL OF AN EXISTING PENETRATINGITEMS.
B. ALL FLOOR PENETRATIONS MUST BE FIRESTOPPED.
GENERAL NOTES
1 HR. FIRE BARRIER
1 HR. FIRE/SMOKE BARRIER
2 HR. FIRE BARRIER
2 HR. FIRE/SMOKE BARRIER
SMOKE RESISTIVE HAZARDOUS AREA
1 2 3 4 5 6 7 8 9
D.1
C
B
A.1
A
D
27 SF
STORAGE
207A
123 SF
OFFICE
201
19 SF
ELECTRIC
208
120 SF
OFFICE
205
117 SF
OFFICE
206
233 SF
STORAGE
207
123 SF
OFFICE
204
121 SF
OFFICE
203121 SF
OFFICE
202
103 SF
OFFICE
209A
9 SF
CLOSET
201A
CORRIDOR
C-2-1
CORRIDOR
C-2-2
CORRIDOR
C-2-3
CORRIDOR
C-2-4
411 SF
LAB
209
LAB
210
N.I.C.
N.I.C.
N.I.C.
N.I.C.
CLOSET
204A
CLOSET
205A
SIG
NA
LS C
LOS
ET
200 H.A.C.
214
one quarter inch = one foot
0
one eighth inch = one foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
three quarters inch = one foot
F
04
three eighths inch = one foot
80
E 4
one half inch = one foot
0
D 46"
02
one inch = one foot
C
6"
0
one and one half inches = one foot
2
B
6"
01
A
three inches = one foot
6"
0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE
100% SUBMITTAL 11/21/14
BID DOCUMENTS 12/19/146/10
/201
5 10
:56:
52 A
MF
ile N
ame A0.2
RNLPSH
SECOND FLOOR LIFE SAFETY PLAN
11/21/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
1/4" = 1'-0"F2 SECOND FLOOR LIFE SAFETY PLAN
1. CONTRACTOR TO PROVIDE SEAMING PLAN TO VA COR FOR REVIEW AND APPROVALPRIOR TO INSTALLATION.
2. HEAT WELD SEAMS IN RUBBER FLOORING.
3. 6" HIGH INTEGRAL FLASH COVE BASE.
4. NO FINISH WORK THIS ROOM.
GENERAL NOTES:FINISH SCHEDULE REMARKS:
A. REFER TO REFLECTED CEILING PLANS FOR CEILING HEIGHTS.
B. INSTALL RUBBER EDGE / TRANSITION STRIPS AT ALL LOCATIONS WHERECHANGE OF FLOORING MATERIALS OCCURS.
C. FLOORING TO BE INSTALLED UNDER ALL LAB CASEWORK.
TYPE F1FLUSH
TYPE NL1
8"8"
3' -
8"
2' -
8"
T1
8"
T1 INDICATES SAFETY CLEAR TEMPERED GLASS (1/4" THK)
DOOR ELEVATIONSS
EE
SC
HE
DU
LE2"
2"SEE
SCHEDULE 2"
TYPE 1SINGLE / PAIR
STANDARD
FRAME ELEVATIONS
GENERAL NOTES
A. ALL DOOR FRAMES TO BE PAINTED TP-1, UNLESS NOTEDOTHER WISE.
B. SEE SPECIFICATIONS SECTION 08 71 00 FOR HARDWARESETS.
C. FIELD VERIFY DIMENSIONS AND SWING DIRECTION OF ALLEXISTING DOORS AND FRAMES.
D. U/C = UNDER CUT DOOR 1/2"
E. CONTRACTOR RESPONSIBLE FOR ALL FLOOR PREPARATIONNECESSARY FOR INSTALLATION OF NEW FLOORING. THISINCLUDES BUT IS NOT LIMITED TO FILLING AND LEVELING OFTHE SUBFLOOR SLAB.
F. CONTRACTOR IS RESPONSIBLE FOR THE FIRST CLEANING,SEALING, AND WAXING OF NEW FLOORS AS RECOMMENDED BYFLOORING MANUFACTURER FOR SPECIFIC FLOORINGPRODUCT.
G. PRODUCTS, COLORS AND FINISHES ARE NOT BRAND NAMEDESIGNATIONS. COLOR, FINISHES AND MANUFACTURERSLISTED HERE ARE USED FOR AESTHETIC REFERENCE ONLY.
1. DOOR WITH CONTROL EGRESS HARDWARE. COORDINATE HARDWARE REQUIREMENTS WITHELECTRICAL DRAWINGS.
DOOR SCHEDULE ABBREVIATIONS:DOOR REMARKS:
WD - WOOD
HM - HOLLOW METAL
one quarter inch = one foot
0
one eighth inch = one foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
three quarters inch = one foot
F
04
three eighths inch = one foot
80
E 4
one half inch = one foot
0
D 46"
02
one inch = one foot
C
6"
0
one and one half inches = one foot
2
B
6"
01
A
three inches = one foot
6"
0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE
100% SUBMITTAL 11/21/14
BID DOCUMENTS 12/19/146/10
/201
5 10
:56:
52 A
MF
ile N
ame A0.3
RNLPSH
FINISH AND DOOR SCHEDULES
11/21/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
SECOND FLOOR ROOM FINISH SCHEDULE
ROOM No. ROOM NAME FLOOR BASEWALLS WALLS WALLS WALLS CEILING
REMARKSN S E W MAT.
Second Floor200 SIGNALS CLOSET EXISTIN
GEXISTING
P-1 P-1 P-1 P-1 -
201 OFFICE C-1 B-1 P-1 P-1 P-1 P-1 ACT-1201A CLOSET C-1 B-1 P-1 P-1 P-1 P-1 ACT-1202 OFFICE C-1 B-1 P-1 P-1 P-1 P-1 ACT-1203 OFFICE C-1 B-1 P-1 P-1 P-1 P-1 ACT-1204 OFFICE C-1 B-1 P-1 P-1 P-1 P-1 ACT-1204A CLOSET C-1 B-1 P-1 P-1 P-1 P-1 ACT-1205 OFFICE C-1 B-1 P-1 P-1 P-1 P-1 ACT-1205A CLOSET C-1 B-1 P-1 P-1 P-1 P-1 ACT-1206 OFFICE C-1 B-1 P-1 P-1 P-1 P-1 ACT-1207 STORAGE VCT-1 B-1 P-1 P-1 P-1 P-1 ACT-1207A STORAGE VCT-1 B-1 P-1 P-1 P-1 P-1 ACT-1208 ELECTRIC VCT-1 B-1 P-1 P-1 P-1 P-1 ACT-1209 LAB WSF-1 WSF-1 P-1 P-1 P-1 P-1 ACT-2 1,2,3209A OFFICE C-1 B-1 P-1 P-1 P-1 P-1 ACT-1210 LAB WSF-1 WSF-1 P-1 P-1 P-1 P-1 ACT-2 1,2,3214 H.A.C. - - - - - - - 4C-2-1 CORRIDOR VCT-1 B-1 P-1 P-1 P-1 P-1 ACT-1C-2-2 CORRIDOR VCT-1 B-1 P-1 P-1 P-1 P-1 ACT-1C-2-3 CORRIDOR VCT-1 B-1 P-1 P-1 P-1 P-1 ACT-1/CP
-1
C-2-4 CORRIDOR VCT-1 B-1 P-1 P-1 P-1 P-1 ACT-1/CP-1
SECOND FLOOR DOOR SCHEDULE
DOOR No. ROOM NAME
DOOR FRAME
FIRERTG. HDW SET REMARKS
SIZEMAT. TYPE FIN. MAT. TYPE FIN.
DETAILSW H T HEAD/JAMB
Second Floor201 OFFICE 3' - 0" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1A201A OFFICE 2' - 6" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1A202 OFFICE 3' - 0" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1A203 OFFICE 3' - 0" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1A204 OFFICE 3' - 0" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1A204A CLOSET 2' - 6" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1B205 OFFICE 3' - 0" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1A205A CLOSET 2' - 6" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1B206 OFFICE 3' - 0" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1A207A STORAGE 2' - 6" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1B208 ELECTRIC 3' - 0" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1B209A OFFICE 3' - 0" 7' - 0" 1 3/4" WD F1 WD HM 1 TP-1 B6/A4.1 - C6/A4.1 20 MIN. HW-1AC-2-1 CORRIDOR 3' - 6" 7' - 0" 1 3/4" HM NL1 TP-1 HM 1 TP-1 B6/A4.1 - C6/A4.1 - HW-2A 1
MATERIAL LEGEND
MARK FINISH TYPE MANUFACTURER PRODUCT/COLOR Comments
BASEB-1 RUBBER COVE BASE JOHNSONITE 6" HIGH, LONG TOE, PEWTER #38
CARPETC-1 CARPET TILE MOHAWK ABACA II, DESIGN FRAME, 116 ANTIQUITY BRICK ASHLAR INSTALLATION
CASEWORKPL-1 PLASTIC LAMINATE FORMICA ANTIQUE WHITE - 933-58
CEILINGACT-1 ACOUSTICAL CEILING TILE ARMSTRONG FINE FISSURED #1728, 2' x 2' x 5/8", WHITE SUSPENSION SYSTEM: PRELUDE
XL 15/16"
ACT-2 ACOUSTICAL CEILING TILE ARMSTRONG CLEAN ROOM VL #363, 2' x 2' X 5/8", WHITE,UNPERFORATED
SUSPENSION SYSTEM: PRELUDEXL 15/16"
CP-1 CEILING PAINT GLIDDEN PROFESSIONAL LIFEMASTER CEILING WHITE GLOSS LEVEL 1
DOORS/WINDOWSTP-1 TRIM PAINT GLIDDEN PROFESSIONAL QUIET HIDEAWAY #A0158 GLOSS LEVEL 5
FLOORT-1 FLOOR TRANSITION STRIP JOHNSONITE SSR-38-B PEWTER USE WITH VCT TO RUBBER
FLOORING
VCT-1 VINYL COMPOSITION TILE ARMSTRONG STANDARD EXCELON 12" x 12", ANTIQUE WHITE#51811
WSF-1 RUBBER SHEET NORA NORAPLAN ECO - 6151 ESPLANADE 2MM
METAL CASEWORKF-1 FABRIC PANEL HAMILTON SCIENTIFIC GM 238 GRAY MIX INSERT PANEL FABRICM-1 METAL CASEWORK HAMILTON SCIENTIFIC G1 DOVE GRAY METAL CASEWORK BODYM-2 METAL CASEWORK HAMILTON SCIENTIFIC G3 GRAY SLATE METAL CASEWORK
DOOR/DRAWER FACES
WALLP-1 PAINT GLIDDEN PROFESSIONAL QUIET HIDEAWAY #A0158 GLOSS LEVEL 3
OS
FFF
K
3
3
T
T
T
T
T T T T T T
T
T
T
TT
T T
T
T
TTT
T
OS
FFF
K
3
3
1 2 3 4 5 6 7 8 9
D.1
C
B
A.1
A
D
N.I.C.
N.I.C.
N.I.C.
N.I.C.
5
6
2
2
5
11
1
7 7
7
7
7
7
6
3
5 5
5
5
3
44
5
3
11
11
9
7
9
10 11 11
11
99
11
9
9
8
1
1
DEMOLITION NOTES
00 INDICATES DEMOLITION NOTE.
1. REMOVE EXISTING DOOR, METAL FRAME, AND ADJACENT 4" CMU.CONTRACTOR TO REMOVE MASONRY AS REQUIRED TO CREATEFLUSH CORNER CONDITION. REFER TO NEW WORK PLAN FOR MOREINFORMATION.
2. REMOVE EXISTING PARTITIONS.
GENERAL NOTES
A. DASHED LINES INDICATE BUILDING ELEMENTS, MATERIALS,AND EQUIPMENT TO BE REMOVED. REFER TO SHEET A0.1 FORDRAWING SYMBOLS AND ABBREVIATIONS
B. REPAIR, LEVEL, AND PREPARE EXISTING CONCRETEFLOOR SLABS TO RECEIVE NEW FLOOR FINISH. INCLUDINGAREAS WHERE EXISTING WALLS ARE REMOVED. REFER TOSPECIFICATION SECTION 09 05 16 SUBSURFACE PREPARATIONFOR FLOOR FINISHES.
C. PRIOR TO CONSTRUCTION FIELD INVESTIGATE EXISTINGCONDITIONS AND NOTIFY THE COR AND THE ARCHITECT OFDISCREPANCIES.
D. EXISTING WALL SURFACES TO RECEIVE NEW SCHEDULEDFINISHES SHALL BE PREPARED IN A MANNER ACCEPTABLE TOTHE FINISH MANUFACTURER.
3. REMOVE EXISTING EQUIPMENT AND DELIVER TO LOCATIONDETERMINED BY VA COR.
E. DEMOLISH CEILING, GRID, AND BULKHEADS THROUGHOUTUNLESS NOTED OTHERWISE.
F. SEE PLUMBING, HVAC, AND ELECTRICAL DRAWINGS FORREMOVAL WORK ASSOCIATED WITH THOSE TRADES.
4. REMOVE EXISTING FIXTURE. REFER TO PLUMBINGDRAWINGS.
5. REMOVE EXISTING CASEWORK AND ACCESSORIES.
6. REMOVE EXISTING DOOR AND METAL FRAME.
7. REMOVE EXISTING FLOORING AND WALL BASE. PREPAREFLOOR SLAB TO RECEIVE NEW FINISH MATERIAL. AS PART OFFLOOR DEMOLITION CONTRACTOR TO REMOVE ASBESTOSCONTAINING MATERIAL. REFER TO ASBESTOS SURVEY.REPORT AND SPECIFICATIONS FOR MORE INFORMATION.
G. ALL REMOVED LABORATORY CASEWORK IS PROPERTY OFCINCINNATI VAMC. CONTRACTOR TO DELIVER TO LOCATIONDETERMINED BY VA COR.
H. REMOVE WALL-HUNG ACCESSORIES AND EQUIPMENT ANDDELIVER TO LOCATION DETERMINED BY VA COR.
8. REMOVE PORTION OF EXISTING WALL TO ACCOMMODATEINSTALLATION OF NEW FLAME AND DOOR. REFER TO NEWWORK PLAN FOR MORE INFORMATION.
9. EXISTING ELECTRICAL PANEL. REFER TO ENGINEERINGDRAWINGS FOR MORE INFORMATION.
10. EXISTING GAS SUPPLY VALVES. REFER TO ENGINEERINGDRAWINGS.
11. EXISTING MECHANICAL EQUIPMENT SWITCH. REFER TOENGINEERING DRAWINGS.
one quarter inch = one foot
0
one eighth inch = one foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
three quarters inch = one foot
F
04
three eighths inch = one foot
80
E 4
one half inch = one foot
0
D 46"
02
one inch = one foot
C
6"
0
one and one half inches = one foot
2
B
6"
01
A
three inches = one foot
6"
0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE
100% SUBMITTAL 11/21/14
BID DOCUMENTS 12/19/146/10
/201
5 10
:56:
54 A
MF
ile N
ame A1.1
RNLPSH
DEMOLITION FLOOR PLAN
11/21/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
1/4" = 1'-0"F3 DEMOLITION PLAN
J
J
J
J
S
SF
SF
S
AP
APA
AP
FFF
VFS
JJ
J
J
J
J
S
SF
SF
S
AP
APA
AP
FFF
VFS
JJ
N.I.C.
N.I.C.
N.I.C.
N.I.C.
1
1 1
1
1
1
1
4 3 2TYP. TYP. TYP.
4TYP.
4TYP.
4TYP.
4TYP.
2TYP.
2TYP.
2TYP.
2TYP.
2TYP.
2TYP.
3TYP.
3TYP.
3TYP.
3TYP.
3TYP.
4
5
4
6
6
GENERAL NOTES
1. REMOVE EXISTING ACCOUSTICAL CEILING SYSTEM.
DEMOLITION NOTES
00 INDICATES DEMOLITION NOTE.
DEMOLITION LEGEND
2x2 SUSPENDING CEILING SYSTEM
A. DASHED LINES INDICATE BUILDING ELEMENTS, MATERIALS,AND EQUIPMENT TO BE REMOVED. REFER TO SHEET A0.1 FORDRAWING SYMBOLS AND ABBREVIATIONS
B. PRIOR TO CONSTRUCTION FIELD INVESTIGATE EXISTINGCONDITIONS AND NOTIFY THE COR AND THE ARCHITECT OFDISCREPANCIES.
C. DEMOLISH CEILING, GRID, AND BULKHEADS THROUGHOUTUNLESS NOTED OTHERWISE.
D. NOT ALL P.M.E. DEVICES SHOWN IN DEMOLITION PLAN.REFER TO ENGINEERING DRAWINGS FOR MOREINFORMATION.
2. EXISTING LIGHT FIXTURE. REFER TO ENGINEERING DRAWINGSFOR MORE INFORMATION.
3. EXISTING HVAC DEVICE. REFER TO ENGINEERING DRAWINGS FORMORE INFORMATION.
4. EXISTING SPRINKLER HEAD. REFER TO ENGINEERING DRAWINGSFOR MORE INFORMAITON.
5. EXISTING EMERGENCY SHOWER. REFER TO ENGINEERINGDRAWINGS FOR MORE INFORMATION.
6. EXISTING BELOW CEILING DUCTWORK TO REMAIN. REFER TOENGINEERING DRAWINGS FOR MORE INFORMATION.
one quarter inch = one foot
0
one eighth inch = one foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
three quarters inch = one foot
F
04
three eighths inch = one foot
80
E 4
one half inch = one foot
0
D 46"
02
one inch = one foot
C
6"
0
one and one half inches = one foot
2
B
6"
01
A
three inches = one foot
6"
0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE
100% SUBMITTAL 11/21/14
BID DOCUMENTS 12/19/146/10
/201
5 10
:56:
57 A
MF
ile N
ame A1.2
RNLPSH
DEMOLITION RCP PLAN
11/21/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
1/4" = 1'-0"F3 DEMOLITION RCP PLAN
3 3
33
3 3
OS
F F
OS
OS
K
S
R
3 3
33
33
3
3
T
T T T
T
T
TT
T T
T
T
T
T
T
T
T
T
T T
T
T
3 3
33
3 3
OS
F F
OS
OS
K
S
R
3 3
33
33
3
3
1 2 3 4 5 6 7 8 9
D.1
C
B
A.1
A
D
27 SF
STORAGE
207A
123 SF
OFFICE
201
19 SF
ELECTRIC
208
120 SF
OFFICE
205
117 SF
OFFICE
206
233 SF
STORAGE
207
123 SF
OFFICE
204
121 SF
OFFICE
203121 SF
OFFICE
202
103 SF
OFFICE
209A
MIN.
5' - 0"
MIN.
5' - 0"
9 SF
CLOSET
201A
CORRIDOR
C-2-1
CORRIDOR
C-2-2
CORRIDOR
C-2-3
CORRIDOR
C-2-4
411 SF
LAB
209
LAB
210
A3.1C7
A3.1 C1
C4
C2
A3.1 B1A3.1B7 B4B2
202
201
203
204
201A
208
207A
206
205
C-2-1
A1
A1
A1
A2A1
A1
A1
A1
A1
A1
A1
A1
N.I.C.
N.I.C.
N.I.C.
N.I.C.
A3
1
1
1
11
A1
2' - 6" 2' - 6"
2
2
2
2
EQ
.E
Q.
EQ
.E
Q.
4' -
0"
4' - 10 1/4"
5' -
5"
EQ
.E
Q.
209A
4
3
Q-101
Q-102
9 SF
CLOSET
204A
9 SF
CLOSET
205A
204A
205A
1A3.1
2A3.1
3A3.1
4A3.1
5A3.1
6A3.1
7A3.1
Q-100
5 5
5
67 7 7 7
7 7 7 7 7 7
7
88888
8 8 8 8 8 8
3' -
0"
9
1A3.1
1 2
NEW WORK NOTES
INDICATES NEW WORK NOTE.
1. REPAIR CONCRETE BLOCK AT REMOVED DOOR AND FRAME.TOOTH IN NEW WORK TO COURSE WITH EXISTING. PROVIDE 4"THICK 2-HR FIRE RATED SOLID BLOCK. CONCRETE BLOCK TOCOMPLY WITH ASTM C90 AND MASONRY MORTAR TO COMPLYWITH ASTM C270. ALL NEW MATERIAL TO MATCH EXISTING. ALLEXPOSED OUTSIDE CORNERS TO BE BULL-NOSE.
2. ALIGN NEW WALL WITH FACE OF EXISTING CONC. BLOCKWALL.
3. CONTRACTOR TO REPAIR EXISTING MASONRY VOID. TOOTHIN NEW WORK TO COURSE WITH EXISTING.
4. CONTRACTOR TO PROVIDE NEW DOOR HARDWARE/KEYCYLINDER TO MEET VA STANDARDS FOR STORAGE ROOMFUNCTION.
5. PROVIDE NEW CLOSET SHELF AND ROD FULL WIDTH OFROOM AS PER DETAIL C8/A4.1.
6. CONTRACTOR TO PAINT EXISTING ROOF ACCESS STAIR,HANDRAIL, AND INTERIOR FACE OF METAL DOOR/FRAME TP-1.
7. CONTRACTOR TO PAINT EXISTING WINDOW OPENINGSURROUND TP-1 INCLUDING SILL.
8. CONTRACTOR TO PAINT EXISTING CONVECTOR P-1.
9. CONTRACTOR TO FRAME AROUND EXISTING ELECTRICALCONDUIT AS REQUIRED. COORDINATE SPECIFIC FRAMINGDETAILS WITH VA COR.
GENERAL NOTES
A. EQUIPMENT TO BE PROVIDED AND INSTALLED ASDESIGNATED IN THE EQUIPMENT SCHEDULE.
00
B. NOT ALL MOVEABLE EQUIPMENT PROVIDED BY THEVA IS SHOWN ON THIS FLOOR PLAN.
C. REFER TO THE ACCESSORIES SCHEDULE ANDINTERIOR ELEVATIONS FOR OTHER ACCESSORIESPROVIDED BY THE GC OR THE VA.
D. ALL DIMENSIONS ARE TAKEN FROM FACE OF GYPSUMWALL BOARD OR UNIT MASONRY.
E. ALL EXISTING AND NEW EXPOSED CONDUIT, PIPING,DUCTWORK TO BE PAINTED TO MATCH ADJACENT WALLSURFACE.
0 INDICATES BID ITEM NOTE.
BID ITEMS
1. AS PART OF BID ITEM 2, CONTRACTOR TO REMOVE (2) METALLABORATORY CASEWORK AND COUNTERTOP UNITS ON NORTH WALLOF ROOM 209.
2. AS PART OF BID ITEM 2, CONTRACTOR TO REMOVE (2) METALLABORATORY CASEWORK AND COUNTERTOP UNITS ON SOUTH WALLOF ROOM 209.
GENERAL NOTES
A. PROVIDE & INSTALL DEFLECTION TRACK AT ALL INTERIOR WALLS THAT EXTEND TO DECK. SEE SHEET A8.1 FOR TYPICAL WALL DETAILS.
B. UL TEST NUMBERS FOR INTERIOR PARTITIONS WILL VARY DEPENDING ON THE MANUFACTURER OF COMPONENTS ACTUALLY USED. MAINTAIN RATING AND ADVISE IF WALL THICKNESS WILL CHANGE.
C. DRYWALL CONTRACTOR TO PAINT WALL RATINGS LABELS AT MAX. 12 FEET O.C. ON ALL FIRE RATED PARTITIONS.LABEL TO BE PAINTED WITH A STENCIL MIN. OF 4 INCHES IN HEIGHT, BLACK COLOR.
D. FIRE RATED WALLS AND SMOKE PARTITIONS ARE TO BE CONSTRUCTED TIGHT TO STRUCTURE, PIPING AND OTHERPENETRATIONS. ALL PENETRATIONS AND PERIMETER OF WALLS TO BE FIRE CAULKED.
E. METAL STUD PARTITIONS SHALL BE BRACED TO STRUCTURE ABOVE.
F. REFER TO SHEET A4.1 FOR TYPICAL INTERIOR PARTITIONS DETAILS.
G. ALL PENETRATIONS IN FIRE RATED PARTITIONS SHALL BE FIRESTOPPED WHETHER NEW OR EXISTING. INCLUDINGTHOSE CREATED BY THE REMOVAL OF AN EXISTING PENETRATING ITEM.
A1 3 5/8"
5/8"
3 5/8" METAL STUDS @ 16" O.C.
3 1/2" SOUND ATTENUATION
5/8" TYPE "X" GYPSUM WALLBOARD
5/8" TYPE "X" GYPSUM WALLBOARD
4 7/8"
-
-
NOTES:EXTEND TO DECK ABOVEINSTALL ACOUSTICAL SEALANT TOP AND BOTTOMSEE DETAIL F1/A2.1
5/8"
TYPE
BASEWALLWIDTH
FIRE RATING
TESTING AGENCY,ASSEMBLY NO.
DETAILS & NOTES
INTERIOR WALL TYPES SCHEDULE X
A2 3 5/8"
5/8"
3 5/8" METAL STUDS @ 16" O.C.
3 1/2" SOUND ATTENUATION
5/8" TYPE "X" GYPSUM WALLBOARD
4 7/8"
-
-
NOTES:SEE DETAIL F1/A2.1
5/8"
A3 3 5/8"
5/8"
1 1/4" METAL STUDS @ 16" O.C.
1 1/4" SOUND ATTENUATION
5/8" TYPE "X" GYPSUM WALLBOARD
5/8" TYPE "X" GYPSUM WALLBOARD
MATCH EXISTING, FIELD VERIFY
-
-
5/8"
5/8" TYPE "X" GYPSUM WALLBOARD
FINISH CEILING, SEE RCP
BOTTOM OF DECK
EQUIPMENT SCHEDULE ABBREVIATIONS:
INDICATES EQUIPMENT TYPE
GENERAL CONTRACTOR AND/OR SUBCONTRACTORS (PLUMBING, MECHANICAL, ELECTRICAL)
DEPARTMENT OF VETERANS AFFAIRS HOSPITAL / OWNER
VENDOR AS PART OF SEPARATE CONTRACT WITH VA
Q-XXX
(GC)
(VA)
(VEN)
SEALANT
J CASING BEAD
5/8" TYPE 'X' GYPSUMWALL BOARD
5/8" TYPE 'X' GYPSUMWALL BOARD
DRYWALL EDGE TRIM,BASIS OF DESIGNMFR: FRY REGLET CORP.MODEL: DMET-150
SEALANT
EXISTING CMU WALLSOUND BATTINSULATION
METAL STUD
ALIGN
one quarter inch = one foot
0
one eighth inch = one foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
three quarters inch = one foot
F
04
three eighths inch = one foot
80
E 4
one half inch = one foot
0
D 46"
02
one inch = one foot
C
6"
0
one and one half inches = one foot
2
B
6"
01
A
three inches = one foot
6"
0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE
100% SUBMITTAL 11/21/14
BID DOCUMENTS 12/19/147/8/
2015
10:
08:2
0 A
MF
ile N
ame A2.1
RNLPSH
NEW WORK FLOOR PLAN
11/21/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
1/4" = 1'-0"F3 NEW WORK PLAN
EQUIPMENT SCHEDULE
Type Mark DescriptionTotal
QuantityNew
QuantityExistingQuantity
Equip.Provider
Equip.Installer
Equip.Connected By Comments
Q-100 FUME HOOD 1 1 0 GC GC GCQ-101 FUME HOOD 1 0 1 - - -Q-102 REFRIGERATED GLOVE BOX 1 0 1 VA VA VA
6" = 1'-0"F1 JOINT DETAIL AT BLOCK WALL
OS
OS
OS
OS
OS
OS
OSOS
F F
S
OSOS
OS
OS
VFS
OS OS
OS OS
SF
SF
SF
SF
SF
SF
SF
SF
SF
APEX/R
APEX/R AP
EX/R
AP
AP
AP
AP
SC SC SC SC
SC
SC
SCJJ
SCOS
OS
OS
OS
OS
OS
OSOS
F F
S
OSOS
OS
OS
VFS
OS OS
OS OS
SF
SF
SF
SF
SF
SF
SF
SF
SF
APEX/R
APEX/R AP
EX/R
AP
AP
AP
AP
SC SC SC SC
SC
SC
SCJJ
SC
9' - 6"
9' - 6"
8' - 0"
9' - 6"
8' - 0"
9' - 6"
7' - 11"
7' - 11"
OFFICE
202
OFFICE
203
OFFICE
204
CORRIDOR
C-2-3
OFFICE
201
CLOSET
201A
CORRIDOR
C-2-1
CO
RR
IDO
R
C-2
-4
OFFICE
205
OFFICE
206
STORAGE
207A
STORAGE
207
ELECTRIC
208
OFFICE
209A
LAB
209
CORRIDOR
C-2-2
LAB
210
9' - 6"
8' - 0"
9' - 6"
8' - 0"
N.I.C.
N.I.C.
N.I.C.
N.I.C.
8' - 0"
8' - 0"
9' - 6"
8' - 0"
9' - 6"
9' - 6"
1
1
2
2
2
2
2
2
22
2
2
2
2
2
2
2
2
2
F1A2.2
CLOSET
204A
CLOSET
205A
2
2 8' - 0"
8' - 0"
8' - 0"F1A2.2
CONSTRUCTION NOTES
00 INDICATES CONSTRUCTION NOTE.
1. GYPSUM WALLBOARD SOFFIT ON METAL FRAMING.
2. NEW 2X2 ACCOUSTICAL PANEL SYSTEM.
GENERAL NOTES
A. ALIGN ALL NEW SOFFIT FACES WITH FACE OF COLUMN / WALL
B. MEASURE CEILING AND LAYOUT GRIDS TO BALANCE BORDER WIDTHSAT OPPOSITE EDGES. INSTALL EDGE MOLDINGS AT PERIMETER UNLESSNOTED OTHERWISE.
C. REFER TO ENGINEERING DRAWINGS FOR CEILING DEVICES.
D. REFER TO ROOM FINISH SCHEDULE AND MATERIALS LIST FOR MOREINFORMATION.
INDICATES GYPSUM WALLBOARDSOFFIT AND/OR CEILING
CEILING LEGEND
INDICATES ACCOUSTICAL PANELCEILING SYSTEM
CORNERBEAD
ACOUSTICAL PANELCEILING
WIRE HANGERS
DIAGONAL BRACINGEVERY 4'-0" O.C.
3 5/8" STEEL STUDS
5/8" GYPSUMWALLBOARD, TYP.
ACOUSTICALPANEL CEILING
PAINT ALL
.
RE
FE
R T
O P
LAN
SF
OR
HE
IGH
T T
YP
.
ALIGN TO FACE OFEXISTING CMU
ALIGN TO FACE OFEXISTING CMU
1"
one quarter inch = one foot
0
one eighth inch = one foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
three quarters inch = one foot
F
04
three eighths inch = one foot
80
E 4
one half inch = one foot
0
D 46"
02
one inch = one foot
C
6"
0
one and one half inches = one foot
2
B
6"
01
A
three inches = one foot
6"
0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE
100% SUBMITTAL 11/21/14
BID DOCUMENTS 12/19/146/10
/201
5 10
:57:
08 A
MF
ile N
ame A2.2
RNLPSH
NEW WORK RCP PLAN
11/21/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
1/4" = 1'-0"F3 NEW WORK RCP PLAN 1 1/2" = 1'-0"F1 SOFFIT DETAIL
1
6A3.1
7A3.1
4
12
13
10
9
7
11
13
12
4 43
12
13
10
9
7
34
1A3.1
2A3.1
3A3.1
4A3.1
12
34 3 4
14
12
132
33333 15
5
8
1617
TYP.
18TYP.
1
5A3.1
12
13
10
9
7
11
17
TYP.18
TYP.
1
1A3.1
2A3.1
3A3.1
4A3.1
34
12
1313
12
13
5
3 4 3 153 3
10
2
7 8
1617TYP.
18TYP.
1
6A3.1
7A3.1
3 43444 33
12 12
13
10
9
7
13
11
17TYP.
1
1
1A3.1
3A3.1
2A3.1
34
1212
5
3 4 3 3 15 3
5
2
7
17TYP.
18TYP.
14
16
13
81
3
10
9
7A3.1
6A3.1
7
43444 33
12 12
13 13
17TYP.
2
1A3.1
3A3.1
2A3.1
1
12
10
2
7
1313
12
5
3 34 3 4
17TYP.
18TYP.
13
15 33
8
16
NEW WORK NOTES
INDICATES NEW WORK NOTE.
1. 6" RUBBER COVE BASE. REFER TO ROOM FINISH SCHEDULE.
2. WALL FRAME SECURED TO FLOOR. CONTRACTOR TOPROVIDE CEILING ATTACHMENT AS RECOMMENDED BYCASEWORK MANUFACTUER.
3. SUSPENDED METAL DRAWER UNIT.
4. SUSPENDED METAL CABINET UNIT.
5. METAL WALL CABINET WITH SLIDING GLASS DOORS.
6. CANTILEVERED TABLE FRAME.
7. EPOXY RESIN COUNTERTOP.
8. UNDERMOUNT EPOXY RESIN SINK.
9. WALL STRUCTURE AND PANEL SECURED TO WALL ANDFLOOR.
10. SUSPENDED OUTER SHELVE WITH END BRACKETS.
11. EXISTING LABORATORY FUME HOOD. REFER TOEQUIPMENT SCHEDULE.
12. FACING INSERT WITH FABRIC.
13. FACING PANEL WITH PAINTED STEEL.
14. EPOXY RESIN GLASSWARE PEGBOARD WITH 2" DEEP DRIPTROUGH.
15. SUSPENDED METAL SINK CABINET UNIT.
16. PROVIDE 6" HIGH INTEGRAL EPOXY RESIN BACKSPLASH.
17. INDICATES POWER RECEPTACLE LOCATION. REFER TOENGINEERING DRAWINGS FOR TYPE.
18. INDICATES DATA RECEPTACLE LOCATION. REFER TOENGINEERING DRAWINGS FOR TYPE.
GENERAL NOTES
A. REFER TO FINISH AND MATERIAL SCHEDULE ON SHEETA0.4 FOR MORE INFORMATION.
B. REFER TO ELECTRICAL DRAWINGS FOR DATA/POWEROUTLETS.
00
0 INDICATES BID ITEM NOTE.
BID ITEMS
1. AS PART OF BID ITEM 2, CONTRACTOR TO REMOVE (2) METALLABORATORY CASEWORK AND COUNTERTOP UNITS ON NORTH WALLOF ROOM 209.
2. AS PART OF BID ITEM 2, CONTRACTOR TO REMOVE (2) METALLABORATORY CASEWORK AND COUNTERTOP UNITS ON SOUTH WALLOF ROOM 209.
9' -
6"
6" 1' - 0"
7' -
0 1
/2"
1' -
4"
1' -
6"
3' -
0"6
15
7
8
2
14
10
10
1
9' -
6"
2' -
7"
1' -
6"
3' -
0"6
3
7
2
1
5
1' - 1 7/16" 6" 1' - 1 7/16"
9' -
6"1'
- 4
"1'
- 6
"3'
- 0
"
2' -
7"
1' -
6"
3' -
0"
1' - 1 7/16" 6" 1' - 0"
7
2
1
5
3
6
10
10
1' -
4"
1' -
6"
3' -
0"
9' -
6"
2' -
7"
1' -
6"
3' -
0"
7' -
0 1
/2"
7
2
1
5
4
6
10
10
1' - 0"6"1' - 1 7/16"
1' -
3"
2' -
0"
2' -
6"
9' -
6"
7' -
0 1
1/16
"
7
1
9
6
10
10
1' - 0"
3' -
0"
1' -
6"
1' -
3"
7' -
0 1
1/16
"
9' -
6"
7
1
9
6
10
10
4
1' - 0"
3' -
0"
1' -
6"
1' -
3"
7' -
0 1
1/16
"
9' -
6"
7
1
9
6
10
10
3
1' - 0"
one quarter inch = one foot
0
one eighth inch = one foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
three quarters inch = one foot
F
04
three eighths inch = one foot
80
E 4
one half inch = one foot
0
D 46"
02
one inch = one foot
C
6"
0
one and one half inches = one foot
2
B
6"
01
A
three inches = one foot
6"
0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE
100% SUBMITTAL 11/21/14
BID DOCUMENTS 12/19/147/8/
2015
10:
08:4
0 A
MF
ile N
ame A3.1
RNLPSH
INTERIOR ELEVATIONS
11/21/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
1/4" = 1'-0"C7 LAB 210 SOUTH - WALL 1/4" = 1'-0"C4 LAB 210 NORTH - CASEWORK
1/4" = 1'-0"C1 LAB 210 NORTH - WALL 1/4" = 1'-0"C2 LAB 210 SOUTH - CASEWORK
1/4" = 1'-0"B1 LAB 209 NORTH - WALL 1/4" = 1'-0"B4 LAB 209 NORTH - CASEWORK
1/4" = 1'-0"B7 LAB 209 SOUTH - WALL 1/4" = 1'-0"B2 LAB 209 SOUTH - CASEWORK
3/4" = 1'-0"1 CASEWORK SECTION 3/4" = 1'-0"2 CASEWORK SECTION
3/4" = 1'-0"3 CASEWORK SECTION 3/4" = 1'-0"4 CASEWORK SECTION
3/4" = 1'-0"5 CASEWORK SECTION
3/4" = 1'-0"6 CASEWORK SECTION 3/4" = 1'-0"7 CASEWORK SECTION
RESILIENT FLOORRUBBER EDGETRANSITION STRIP
CARPETCONCRETE SLAB
SUBFLOOR LEVERSYSTEM
METAL BOX LINTEL AT HEAD
ELASTOMERIC JOINT SEALANT
INTERIOR STEEL FRAME
5/8" GYPSUM WALLBOARD
SOUND ATTENUATIONBLANKETS
2"
DOOR - SEE DOOR & FRAMESCHEDULE
4 7/8"
1/2" TYP.
STUD ANCHOR
STEEL STUDS & RUNNERS
5/8" GYPSUM WALLBOARD
SOUND ATTENUATIONBLANKETS
DEEP LEG DEFLECTION TRACK
24 GAUGE MIN. CONTINUOUSCLOSURE STRIP
FLOOR SLAB
SEALANT
ACOUSTICAL SEALANT
STEEL STUDS & RUNNERS
ELASTOMERIC JOINT SEALANT
INTERIOR STEEL FRAME
5/8" GYPSUM WALLBOARD
SOUND ATTENUATION BLANKETS
2"4"
ADJACENT PARTITIONWHERE APPLICABLE
DOOR - SEE DOOR &FRAME SCHEDULE
4 7/8"
1/2" TYP.
STUD ANCHOR
11 1
5/16
"
CL
3/4" CHROME COATROD
3/4" PLASTIC LAMINATESHELF
1 1/
2"3
1/4"
PLASTIC LAMINATE SIDEBRACKET (EACH SIDE)
4'-6
" A
FF
.
1' - 4"
CONTROL JOINT.
GYPSUM WALLBOARD PERINTERIOR PARTITION SCHEDULE.
STEEL STUDS &RUNNERS
NOTE; EXPANSION JOINTS TO OCCUR EVERY 20'-0" OFUNINTERRUPTED WALL LENGTH.
STEEL STUDS & RUNNERS
5/8" GYPSUM WALLBOARD
INSTALL STUD AT CENTEROF WALL
SOUND ATTENUATIONBLANKETS
one quarter inch = one foot
0
one eighth inch = one foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
three quarters inch = one foot
F
04
three eighths inch = one foot
80
E 4
one half inch = one foot
0
D 46"
02
one inch = one foot
C
6"
0
one and one half inches = one foot
2
B
6"
01
A
three inches = one foot
6"
0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE
100% SUBMITTAL 11/21/14
BID DOCUMENTS 12/19/146/10
/201
5 10
:57:
22 A
MF
ile N
ame A4.1
RNLPSH
INTERIOR DETAILS
11/21/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
6" = 1'-0"F6 FLOOR TRANSITION DETAIL
3" = 1'-0"B6 GYP. DOOR HEAD DETAIL
3" = 1'-0"F8 HEAD OF WALL DETAIL
3" = 1'-0"C6 GYP. DOOR JAMB DETAIL 1 1/2" = 1'-0"C8 TYP CLOSET SHELF
3" = 1'-0"B8 TYP EXPANSION JOINT DETAIL
3" = 1'-0"D8 TYP WALL INTERSECTION
T
P
FOBFOT
V
TP
CO
S
P/T
M
FS
PIV
DD
RR
A1
OH1
2
1
P2
B
P2
S
CHECK VALVE
SHUTOFF VALVE (REFER TO SPECIFICATIONS FORREQUIRED TYPE BASED ON APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER WITH A BLOW DOWN VALVE AND HOSECONNECTION
DRAIN VALVE WITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER WITH P/T PLUGIN AND OUT
EXPANSION JOINT
PRESSURE REGULATING VALVE
SAFETY RELIEF VALVE. PIPE DISCHARGE AIRGAPPED TO FLOOR DRAIN UNLESS NOTEDOTHERWISE.
PRESSURE AND TEMPERATURE TEST PLUG
TRAP PRIMER
VACUUM GAUGE WITH STOP
CLEANOUT TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
WALL HYDRANT
PLUG VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
COMBINATION SHUTOFF AND BALANCINGVALVE (REFER TO SPECIFICATIONS FORREQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
VALVES AND FITTINGSDOUBLE LINE SINGLE LINE
SOLENOID VALVE
PRESSURE AND TEMPERATURE SAFETY RELIEFVALVE. PIPE DISCHARGE AIR GAPPED TO FLOORDRAIN UNLESS NOTED OTHERWISE.
WATER METER
PLUMBING AND FIRE SUPPRESSIONPIPING DESIGNATIONS
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
HOT WATER PIPE (140 DEGS. F.)
HOT WATER PIPE (180 DEGS. F.)
HOT WATER RETURN PIPE (140 DEGS. F.)
HOT WATER RETURN PIPE (180 DEGS. F.)
ARGON PIPE
COMPRESSED AIR PIPE
MEDICAL CARBON DIOXIDE PIPE
COMBINATION FIRE SUPPRESSION AND DOMESTICWATER SERVICE
DIESEL FUEL PIPE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)
FIRE SERVICE
FUEL OIL FLOW LINE
FUEL OIL GAUGE LINE
FUEL OIL RETURN LINE
FUEL OIL SUPPLY LINE
NATURAL GAS PIPE
GARAGE DRAINAGE PIPE
GAS SERVICE
HYDROGEN PIPE
HELIUM PIPE
MEDICAL INSTRUMENT AIR PIPE
KITCHEN WASTE PIPE
LABORATORY COMPRESSED AIR PIPE
LABORATORY VENT PIPE
LABORATORY VACUUM PIPE
LABORATORY WASTE PIPE
MEDICAL NITROGEN PIPE
MEDICAL COMPRESSED AIR PIPE
MEDICAL-SURGICAL VACUUM PIPE
GASOLINE PIPE (NON-LEAD)
MEDICAL NITROUS OXIDE PIPE
NON-POTABLE WATER
MEDICAL OXYGEN PIPE
(OVERFLOW) SECONDARY STORM DRAINAGE PIPE
PROPANE GAS PIPE
PUMP DISCHARGE PIPE
PRE-ACTION / DELUGE SPRINKLER PIPE
PURE WATER PIPE
SPRINKLER PIPE (WET)
SANITARY DRAINAGE PIPE
SOFT COLD WATER
SPRINKLER DRAIN PIPE
STORM DRAINAGE PIPE
FUEL TANK VENT PIPE
TRAP PRIMER DISCHARGE PIPE
TEMPERED WATER PIPE
SANITARY SEWER VENT
WASTE ANESTHESIA GAS DISPOSAL PIPE
WATER SERVICE
140
LV
180
140R
180R
AR
CA
CO2
CWS
DF
DS
F
FS
FOF
FOG
FOR
FOS
G
GD
GS
H2
HE
IA
IV
IW
LA
LV
LW
N2
MA
MV
NG
NO
NPW
O2
OD
P
PD
PS
PW
S
SAN
SCW
SD
STM
T
TP
TW
V
WAGD
WS
INDIRECT VENT PIPE
INDIRECT WASTE PIPE
K
ACID VENT PIPEAV
ACID WASTE PIPEAW A1
P1 P1OR
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION P2 = SHEET WHERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND HAZARDCLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION P2 = SHEET WHERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TOSCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTERDESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWNUNLESS NOTED OTHERWISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
10" 10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOE: 3' - 0"
BOE: 0' - 6"
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP ORBOTTOM OF EQUIPMENT, UNLESS NOTED OTHERWISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINEOF PIPE, UNLESS NOTED OTHERWISE
3
3
FIRE SUPPRESSION SYMBOLSDOUBLE LINE SINGLE LINE
CONCEALED PENDENT SPRINKLER
FIRE HYDRANT
FLOW SWITCH
GATE VALVE OS&Y
INSTITUTIONAL PENDENT SPRINKLER
PENDENT SPRINKLER
POST INDICATOR VALVE
RECESSED PENDENT SPRINKLER
SIDE WALL SPRINKLER
SUPERVISED VALVE
UPRIGHT SPRINKLER
FIRE DEPARTMENT VALVE
ABBREVIATIONSAAP - AREA ALARM PANEL (MEDICAL GAS)AC - AIR COMPRESSOR OR AIR CONDITIONERACC - ACCESSACCU - AIR COOLED CONDENSING UNITAD - ACCESS DOOR OR AREA DRAINADB - ACID DILUTION BASINADJ - ADJUSTABLEAFF - ABOVE FINISHED FLOORAFG - ABOVE FINISHED GRADEALT - ALTERNATEAP - ACCESS PANELAPPROX - APPROXIMATEAR - AIR RECEIVER OR ARGONARCH - ARCHITECT OR ARCHITECTURALASSY - ASSEMBLYAV - ACID VENTAW - ACID WASTE
BDD - BACK DRAFT DAMPERBFP - BACKFLOW PREVENTERBLDG - BUILDINGBOB - BOTTOM OF BEAMBOD - BOTTOM OF DUCTBOE - BOTTOM OF EQUIPMENTBOF - BOTTOM OF FOOTINGBOG - BOTTOM OF GRILLEBOP - BOTTOM OF PIPEBOT - BOTTOMBT - BATHTUBBTU - BRITISH THERMAL UNITBTUH - BRITISH THERMAL UNIT PER HOURBTWN - BETWEEN
CA - COMPRESSED AIRCB - CATCH BASINCBD - COUNTER BALANCED BACKDRAFT DAMPERCFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLEDCFM - CUBIC FEET PER MINUTECHS - CHILLED WATER SUPPLYCHR - CHILLED WATER RETURNCI - CAST IRONCK - CLINICAL SINKCLG - CEILINGCMU - CONCRETE MASONRY UNITCO - CLEAN OUTCO2 - MEDICAL CARBON DIOXIDECONN - CONNECT OR CONNECTIONCONTR - CONTRACTORCORR - CORRIDORCS - CLINICAL SINK OR COLD SOFT WATERCTR - CENTERCU - COPPERCW - COLD WATERCWS - COMBINATION WATER SERVICE
OR CONDENSER WATER SUPPLYCWR - CONDENSER WATER RETURN
D - DEPTH OR DRAIN LINEDD - DECK DRAINDET - DETAILDF - DRINKING FOUNTAIN OR WATER COOLER
OR DIESEL FUELDFU - DRAINAGE FIXTURE UNITDI - DEIONIZED WATERDIA - DIAMETERDIM - DIMENSIONDN - DOWNDS - DOWN SPOUT OR SPRINKLER (DRY)DT - PERFORATED DRAIN TILEDWG - DRAWING
EA - EACHEC - ELECTRICAL CONTRACTOR (DIVISION 26)EEW - EMERGENCY EYE WASHEJ - EXPANSION JOINTELEC - ELECTRICALELEV - ELEVATOREQ - EQUALEQUIP - EQUIPMENTET - EXPANSION TANKETR - EXISTING TO REMAINES - EMERGENCY SHOWEREQS - EQUIPMENT SUPPLIEREWC - ELECTRICAL WATER COOLEREXH - EXHAUST AIREXP - EXPANSIONEXT - EXTERIOREX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)FCE - FIRE CONTROL EQUIPMENTFCO - FLOOR CLEANOUTFD - FLOOR DRAINFDC - FIRE DEPARTMENT CONNECTIONFDV - FIRE DEPARTMENT VALVEFF - FINISHED FLOOR ELEVATIONFHC - FIRE HOSE CABINETFLR - FLOORFM - FORCE MAINFOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOWFOG - FUEL OIL GAUGEFOR - FUEL OIL RETURNFOS - FUEL OIL SUPPLYFOT - FLAT ON TOPFPM - FEET PER MINUTEFR - FIRE RISERFS - FLOOR SINK OR FIRE SERVICEFSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)FT - FEETFTG - FOOTING
G - GAS OR NATURAL GASGA - GAUGEGAL - GALLONGALV - GALVANIZEDGC - GENERAL TRADES CONTRACTORGD - GARAGE DRAINAGEGPM - GALLONS PER MINUTEGS - GAS SERVICEGW - GREASE WASTE
H2 - HYDROGENHB - HOSE BIBBHC - HVAC CONTRACTOR (DIVISION 23)HD - HUB DRAINHE - HELIUMHG - REFRIGERANT HOT GASHP - HORSEPOWER OR HIGH POINTHPC - HIGH PRESSURE CONDENSATE RETURNHPS - HIGH PRESSURE STEAM SUPPLYHPW - HIGH PURITY WATERHPWR - HIGH PURITY WATER RETURNHR - HOSE REELHT - HEAT TRACEHTR - HEATERHVAC - HEATING, VENTILATING, AND AIR CONDITIONINGHW - HOT WATERHWR - HEATING HOT WATER RETURNHWS - HEATING HOT WATER SUPPLY
IA - MEDICAL INSTRUMENT AIRID - INSIDE DIAMETERINV - INVERT ELEVATIONIN - INCHESIV - INDIRECT VENTIW - INDIRECT WASTE
JS - JANITOR SINK
K - KITCHEN WASTEKEC - KITCHEN EQUIPMENT CONTRACTOR
K - KITCHEN WASTEKEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTHLA - LABORATORY COMPRESSED AIRLAV - LAVATORYLBS - POUNDSLCW - LABORATORY COLD WATERLEC - LABORATORY EQUIPMENT CONTRACTORLHW - LABORATORY HOT WATERLHWR - LABORATORY HOT WATER RETURNLPC - LOW PRESSURE CONDENSATE RETURNLPS - LOW PRESSURE STEAM SUPPLYLV - LABORATORY VACUUM OR LABORATORY VENTLW - LABORATORY WASTE
MA - MEDICAL COMPRESSED AIRMAP - MASTER ALARM PANEL (MEDICAL GAS)MAX - MAXIMUMMB - MOP BASINMC - MECHANICAL CONTRACTOR (DIVISION 23)MEZZ - MEZZANINEMFR - MANUFACTURERMH - MANHOLEMIN - MINIMUM OR MINUTEMISC - MISCELLANEOUSMTD - MOUNTEDMTG - MOUNTINGMPC - MEDIUM PRESSURE CONDENSATE RETURNMPS - MEDIUM PRESSURE STEAM SUPPLYMU - WATER MAKE-UPMV - MEDICAL SURGICAL VACUUM
N2 - MEDICAL NITROGENNG - GASOLINE (NON-LEAD)NIC - NOT IN CONTRACTNO - MEDICAL NITROUS OXIDENOM - NOMINALNPW - NON-POTABLE WATERNPT - NATIONAL PIPE THREADNTS - NOT TO SCALE
02 - MEDICAL OXYGENOA - OUTDOOR AIROD - OUTSIDE DIAMETER OR OVERFLOW DRAINOFCI - OWNER FURNISHED CONTRACTOR
INSTALLEDOFOI - OWNER FURNISHED OWNER INSTALLED
P - PROPANE GASPC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURNPD - PUMP DISCHARGE OR PARAPET DRAINPIV - POST INDICATOR VALVEPLBG - PLUMBINGPS - PRE-ACTION/DELUGE SPRINKLERPRESS - PRESSUREPRV - PRESSURE REGULATING VALVEPSF - POUNDS PER SQUARE FOOTPSI - POUNDS PER SQUARE INCHPSV - PRESSURE SUSTAINING VALVEPSIG - POUNDS PER SQUARE INCH GAUGEPW - PURE WATER
RA - RETURN AIRRAD - RADIUSRCP - REINFORCED CONCRETE PIPERD - ROOF DRAINREC - RECESSEDREQD - REQUIREDRI - ROUGH INRL - REFRIGERANT LIQUIDROS - REVERSE OSMOSIS WATER SUPPLYROR - REVERSE OSMOSIS WATER RETURNRPM - REVOLUTIONS PER MINUTERS - REFRIGERANT SUCTIONRV - RELIEF VALVE
S - SPRINKLER (WET)SA - SHOCK ARRESTOR OR SUPPLY AIRSAN - SANITARY OR SANITARY DRAINSCH - SCHEDULESCW - SOFT COLD WATERSD - SPRINKLER DRAIN OR SUBSOIL DRAINSH - SHOWERSHT - SHEETSK - SINKSPEC - SPECIFICATIONSSQ - SQUARESR - SUPPLY RISERSS - SANITARY STACK (SOIL OR WASTE) OR
STAINLESS STEELSTD - STANDARDSTM - STORM OR STORM DRAINAGESTRUC - STRUCTURAL OR STRUCTURESUC - SITE UTILITY CONTRACTOR
T - FUEL TANK VENTTD - TRENCH DRAINTEMP - TEMPERATURETOB - TOP OF BEAMTOD - TOP OF DUCTTOE - TOP OF EQUIPMENTTOF - TOP OF FOOTINGTOJ - TOP OF JOISTTOP - TOP OF PIPETOS - TOP OF SLAB OR TOP OF STEELTF - TRAP FILLERTP - TRAP PRIMER OR TRAP PRIMER DISCHARGETW - TEMPERED WATERTYP - TYPICAL
UR - URINALUNO - UNLESS NOTED OTHERWISE
V - VENT OR SANITARY SEWER VENTVAC - VACUUMVC - VACUUM CLEANINGVCV - VACUUM CLEANING VALVEVE - VACUUM EXHAUSTVEL - VELOCITYVIB - VALVE IN BOXVOL - VOLUMEVP - VACUUM PUMPVS - VENT STACKVTR - VENT THROUGH ROOFVR - VENT RISER
W/ - WITHW/0 - WITHOUTW - WASTEWAGD - WASTE ANESTHESIA GAS DISPOSALWC - WATER CLOSETWCO - WALL CLEANOUTWH - WALL HYDRANT OR WATER HEATERWIV - WALL INDICATOR VALVEWS - WATER SERVICE
YCO - YARD CLEANOUT
ZVC - ZONE VALVE CABINET
PIPING SYMBOLSDOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE NOT PERMITTED.)
DIRECTION OF PITCH
DROP
ELBOW DOWN
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
PIPE RISER
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOTNECESSARILY BE USED ON THIS PROJECT.
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
8/20
14 3
:09:
09 P
M
12/1
8/20
14 3
:09:
09 P
M
FX0.1DPBRLT
LEGENDS AND SYMBOLS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
FIRE SUPPRESSION DESIGN NOTESA PROVIDE COMPLETE REVISIONS TO THE EXISTING FIRE SUPPRESSION SPRINKLER
SYSTEMS IN THE RENOVATED AREAS.
B COORDINATE WORK WITH VAMC AND OTHER TRADES. EACH CONTRACTOR SHALLBE RESPONSIBLE FOR OFFSETTING AND/OR RELOCATING EXISTING SERVICES TOACCOMMODATE NEW WORK OF OTHER TRADES.
C DESIGN SERVICES SHALL FOLLOW ALL VA STANDARD DESIGN PRACTICES,DETAILS, SPECIFICATION, AND SITE SPECIFIC COR REQUIREMENTS AS WELL ASWORK SHOWN ON THESE DOCUMENTS. ALL DEVIATIONS FROM AFOREMENTIONEDREQUIREMENTS SHALL BE APPROVED BY THE COR.
D THE F.S.C. SHALL VERIFY THAT THERE IS ADEQUATE SPACE TO INSTALL ALL NEWPIPING REQUIRED TO COMPLETE THIS WORK.
E ALL SPRINKLER PIPING IS LOCATED ABOVE THE CEILING (AT THE BOTTOM OFSTRUCTURE) IN EXPOSED STRUCTURAL AREAS) UNLESS OTHERWISE INDICATED.
F THE BASIS OF DESIGN OF SPACING AND SIZING FOR THE COMPLETE FIRESUPPRESSION SPRINKLER SYSTEM IS FOR A WET PIPE SYSTEM HYDRAULICALLYCALCULATED FOR:
1 LIGHT HAZARD AREA LIMITED TO A MAXIMUM OF 225 SQ. FT. PER SPRINKLER WITH THE DENSITY OF 0.10 GPM/SQ. FT. OVER THE MOST REMOTE 1500 SQ. FT.PROVIDE AN ADDITION OF 100 GPM HOSE ALLOWANCE.
2 ALL MECHANICAL, ELECTRICAL, AND ETC. AREAS SHALL BE ORDINARY HAZARD(GROUP 1) LIMITED TO A MAXIMUM OF 130 SQ. FT. PER SPRINKLER WITH A DENSITYOF 0.15 GPM/SQ. FT. PROVIDE AN ADDITION OF 250 GPM HOSE ALLOWANCE.
3 ALL STORAGE, TRASH, FILE STORAGE AND ETC. AREAS SHALL BE ORDINARYHAZARD (GROUP 1) LIMITED TO A MAXIMUM OF 130 SQ. FT. PER SPRINKLER WITH ADENSITY OF 0.20 GPM/SQ. FT. PROVIDE AN ADDITION OF 250 GPM HOSEALLOWANCE.
G ALL SPRINKLER LOCATIONS AND RELATED PIPING SHALL BE BY THE F.S.C.
H THE ENTIRE SPRINKLER SYSTEM SHALL CONFORM TO VAMC, LOCAL, STATE, ANDNFPA STANDARD, RULES AND REGULATIONS.
I THE F.S.C. SHALL CAREFULLY COORDINATE THE LOCATION OF ALL SPRINKLERSAND PIPING WITH ALL OTHER TRADES AND THE ARCHITECT.
J THE F.S.C. SHALL VERIFY THE LOCATION OF ALL LIGHTING FIXTURES AND AIRDEVICES BEFORE INSTALLATION OF SPRINKLERS.
K ALL SPRINKLER PIPING LAYOUT AND SIZING SHALL BE BY THE F.S.C.
L ALL SPRINKLER LOCATIONS MUST BE COORDINATED WITH ALL EQUIPMENTKINDRED TO OTHER TRADES. SPRINKLER LOCATIONS MUST BE APPROVED BY THEARCHITECT BEFORE WORK COMMENCES. REFER TO THE ARCHITECTURAL ANDREFLECTIVE CEILING PLANS FOR ADDITIONAL INFORMATION ON ALL CEILINGTYPES, HEIGHTS, AND OTHER ARCHITECTURAL FEATURES.
M THE F.S.C. SHALL MAKE NECESSARY FLOW TEST, LAY OUT SYSTEMS, AND OBTAINAPPROVALS FROM THE AUTHORITIES HAVING JURISDICTION PRIOR TO BEGINNINGANY FABRICATION OR INSTALLATION WORK.
N SPRINKLER PIPING SHALL BE MINIMUM 1" SIZE.
O SPRINKLERS (UNLESS OTHERWISE NOTED):EXPOSED AREAS - UPRIGHT OR PENDENT TYPE - STANDARD BRASSCEILING AREAS - RECESSED PENDENT TYPE, ALL SPRINKLERS SHALL BE UL LISTEDAND FM APPROVED.
P SPRINKLERS SHALL BE "QUICK RESPONSE" TYPE IN ALL AREAS EXCEPT HIGHTEMPERATURE AREAS.
Q ALL PENDENT TYPE SPRINKLERS LOCATED IN SUSPENDED CEILING TILE AREASSHALL BE LOCATED IN THE CENTER OF THE CEILING TILE.
R ANNULAR SPACE AT PIPE AND OTHER SIMILAR PENETRATION OF FIRE RATEDASSEMBLIES SHALL BE FIRESTOPPED. REFER TO SPECIFICATION SECTION 07 8400 FIRESTOPPING. REFER TO ARCHITECTURAL DRAWINGS FOR CONSTRUCTION,LAYOUT AND FIRE RATING OF FLOWS, WALLS, PARTITIONS AND OTHER BUILDINGELEMENTS.
S REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL INFORMATION.
T REFER TO SPECIFICATION SECTION 21 13 13 FOR FLOW TEST INFORMATION.
U ALL EXISTING SMOKE COMPARTMENTS SHALL BE MAINTAINED. ALL SPRINKLERZONES SHALL MATCH SMOKE COMPARTMENTS.
V REFER TO ARCHITECTURAL PLANS FOR INFORMATION ON SMOKECOMPARTMENTS, SMOKE PARTITIONS AND FIRE BARRIERS.
W REFER TO ARCHITECTURAL FIRE-RATED PARTITION PLAN FOR LOCATIONS ANDFIRE RATINGS OF NEW AND EXISTING WALL ASSEMBLIES. ALL PENETRATIONSTHROUGH FIRE-RATED ASSEMBLIES SHALL BE PROTECTED AND/OR FIRE-STOPPED AS REQUIRED TO MAINTAIN FIRE RATINGS INDICATED. G.C. WILLCOORDINATE WITH ALL TRADES TO ENSURE FIRE-RATED PENETRATIONREQUIREMENTS AND DETAILS ARE MET.
INDEX OF DRAWINGS - FIRE SUPPRESSION
Sheet Number DescriptionH_SheetGroupi
ngFX0.1 LEGENDS AND SYMBOLS FXFX1.2 SECOND FLOOR PLAN - NEW WORK FX
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
FS S
1 2 3 4 5 6 7 8 9
A
B
C
D
1
3
LAB209
OFFICE209AOFFICE
206
OFFICE205
STORAGE207
STORAGE207A
CORRIDORC-2-4
ELECTRIC208
CORRIDORC-2-1
CORRIDORC-2-2
LAB210
CORRIDORC-2-3
OFFICE203
OFFICE202
OFFICE201
OFFICE204
CLOSET201A
1
1
1
3
11
1
1
OH1
OH2
OH2
S S S
S
1 1
1
1
1
2.5" FDV-
- 4" FR
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2 2
2
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
8/20
14 3
:09:
14 P
M
12/1
8/20
14 3
:09:
14 P
M
FX1.2DPBRLT
SECOND FLOOR PLAN - NEW WORK
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
SCALE: 1/4" = 1'-0"
SECOND FLOOR PLAN - NEW WORK1
NOTES1 EXISTING TO REMAIN.
2 MODIFY EXISTING WET-PIPE FIRE SUPPRESSION SPRINKLER SYSTEM TOCONFORM TO NEW LAYOUT INSIDE INDICATED AREA
3 GYPSUM BOARD CEILING.
GENERAL NOTESA REFER TO SHEET FX0.1 FOR FIRE SUPPRESSION DESIGN NOTES.
SCALE: NONE
TYPICAL SPRINKLER FLOOR CONTROL VALVE2
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
T
P
FOBFOT
V
TP
CO
S
P/T
M
FS
PIV
DD
RR
A1
OH1
2
1
P2
B
P2
S
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOTNECESSARILY BE USED ON THIS PROJECT.
CHECK VALVE
SHUTOFF VALVE (REFER TO SPECIFICATIONS FORREQUIRED TYPE BASED ON APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER WITH A BLOW DOWN VALVE AND HOSECONNECTION
DRAIN VALVE WITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER WITH P/T PLUGIN AND OUT
EXPANSION JOINT
PRESSURE REGULATING VALVE
SAFETY RELIEF VALVE. PIPE DISCHARGE AIRGAPPED TO FLOOR DRAIN UNLESS NOTEDOTHERWISE.
PRESSURE AND TEMPERATURE TEST PLUG
TRAP PRIMER
VACUUM GAUGE WITH STOP
CLEANOUT TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
WALL HYDRANT
PLUG VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
COMBINATION SHUTOFF AND BALANCINGVALVE (REFER TO SPECIFICATIONS FORREQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
VALVES AND FITTINGSDOUBLE LINE SINGLE LINE
SOLENOID VALVE
PRESSURE AND TEMPERATURE SAFETY RELIEFVALVE. PIPE DISCHARGE AIR GAPPED TO FLOORDRAIN UNLESS NOTED OTHERWISE.
WATER METER
PLUMBING AND FIRE SUPPRESSIONPIPING DESIGNATIONS
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
HOT WATER PIPE (140 DEGS. F.)
HOT WATER PIPE (180 DEGS. F.)
HOT WATER RETURN PIPE (140 DEGS. F.)
HOT WATER RETURN PIPE (180 DEGS. F.)
ARGON PIPE
COMPRESSED AIR PIPE
MEDICAL CARBON DIOXIDE PIPE
COMBINATION FIRE SUPPRESSION AND DOMESTICWATER SERVICE
DIESEL FUEL PIPE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)
FIRE SERVICE
FUEL OIL FLOW LINE
FUEL OIL GAUGE LINE
FUEL OIL RETURN LINE
FUEL OIL SUPPLY LINE
NATURAL GAS PIPE
GARAGE DRAINAGE PIPE
GAS SERVICE
HYDROGEN PIPE
HELIUM PIPE
MEDICAL INSTRUMENT AIR PIPE
KITCHEN WASTE PIPE
LABORATORY COMPRESSED AIR PIPE
LABORATORY VENT PIPE
LABORATORY VACUUM PIPE
LABORATORY WASTE PIPE
MEDICAL NITROGEN PIPE
MEDICAL COMPRESSED AIR PIPE
MEDICAL-SURGICAL VACUUM PIPE
GASOLINE PIPE (NON-LEAD)
MEDICAL NITROUS OXIDE PIPE
NON-POTABLE WATER
MEDICAL OXYGEN PIPE
(OVERFLOW) SECONDARY STORM DRAINAGE PIPE
PROPANE GAS PIPE
PUMP DISCHARGE PIPE
PRE-ACTION / DELUGE SPRINKLER PIPE
PURE WATER PIPE
SPRINKLER PIPE (WET)
SANITARY DRAINAGE PIPE
SOFT COLD WATER
SPRINKLER DRAIN PIPE
STORM DRAINAGE PIPE
FUEL TANK VENT PIPE
TRAP PRIMER DISCHARGE PIPE
TEMPERED WATER PIPE
SANITARY SEWER VENT
WASTE ANESTHESIA GAS DISPOSAL PIPE
WATER SERVICE
140
LV
180
140R
180R
AR
CA
CO2
CWS
DF
DS
F
FS
FOF
FOG
FOR
FOS
G
GD
GS
H2
HE
IA
IV
IW
LA
LV
LW
N2
MA
MV
NG
NO
NPW
O2
OD
P
PD
PS
PW
S
SAN
SCW
SD
STM
T
TP
TW
V
WAGD
WS
INDIRECT VENT PIPE
INDIRECT WASTE PIPE
K
ACID VENT PIPEAV
ACID WASTE PIPEAW A1
P1 P1OR
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION P2 = SHEET WHERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND HAZARDCLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION P2 = SHEET WHERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TOSCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTERDESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWNUNLESS NOTED OTHERWISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
10" 10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOE: 3' - 0"
BOE: 0' - 6"
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP ORBOTTOM OF EQUIPMENT, UNLESS NOTED OTHERWISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINEOF PIPE, UNLESS NOTED OTHERWISE
3
3
FIRE SUPPRESSION SYMBOLSDOUBLE LINE SINGLE LINE
CONCEALED PENDENT SPRINKLER
FIRE HYDRANT
FLOW SWITCH
GATE VALVE OS&Y
INSTITUTIONAL PENDENT SPRINKLER
PENDENT SPRINKLER
POST INDICATOR VALVE
RECESSED PENDENT SPRINKLER
SIDE WALL SPRINKLER
SUPERVISED VALVE
UPRIGHT SPRINKLER
FIRE DEPARTMENT VALVE
ABBREVIATIONSAAP - AREA ALARM PANEL (MEDICAL GAS)AC - AIR COMPRESSOR OR AIR CONDITIONERACC - ACCESSACCU - AIR COOLED CONDENSING UNITAD - ACCESS DOOR OR AREA DRAINADB - ACID DILUTION BASINADJ - ADJUSTABLEAFF - ABOVE FINISHED FLOORAFG - ABOVE FINISHED GRADEALT - ALTERNATEAP - ACCESS PANELAPPROX - APPROXIMATEAR - AIR RECEIVER OR ARGONARCH - ARCHITECT OR ARCHITECTURALASSY - ASSEMBLYAV - ACID VENTAW - ACID WASTE
BDD - BACK DRAFT DAMPERBFP - BACKFLOW PREVENTERBLDG - BUILDINGBOB - BOTTOM OF BEAMBOD - BOTTOM OF DUCTBOE - BOTTOM OF EQUIPMENTBOF - BOTTOM OF FOOTINGBOG - BOTTOM OF GRILLEBOP - BOTTOM OF PIPEBOT - BOTTOMBT - BATHTUBBTU - BRITISH THERMAL UNITBTUH - BRITISH THERMAL UNIT PER HOURBTWN - BETWEEN
CA - COMPRESSED AIRCB - CATCH BASINCBD - COUNTER BALANCED BACKDRAFT DAMPERCFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLEDCFM - CUBIC FEET PER MINUTECHS - CHILLED WATER SUPPLYCHR - CHILLED WATER RETURNCI - CAST IRONCK - CLINICAL SINKCLG - CEILINGCMU - CONCRETE MASONRY UNITCO - CLEAN OUTCO2 - MEDICAL CARBON DIOXIDECONN - CONNECT OR CONNECTIONCONTR - CONTRACTORCORR - CORRIDORCS - CLINICAL SINK OR COLD SOFT WATERCTR - CENTERCU - COPPERCW - COLD WATERCWS - COMBINATION WATER SERVICE
OR CONDENSER WATER SUPPLYCWR - CONDENSER WATER RETURN
D - DEPTH OR DRAIN LINEDD - DECK DRAINDET - DETAILDF - DRINKING FOUNTAIN OR WATER COOLER
OR DIESEL FUELDFU - DRAINAGE FIXTURE UNITDI - DEIONIZED WATERDIA - DIAMETERDIM - DIMENSIONDN - DOWNDS - DOWN SPOUT OR SPRINKLER (DRY)DT - PERFORATED DRAIN TILEDWG - DRAWING
EA - EACHEC - ELECTRICAL CONTRACTOR (DIVISION 26)EEW - EMERGENCY EYE WASHEJ - EXPANSION JOINTELEC - ELECTRICALELEV - ELEVATOREQ - EQUALEQUIP - EQUIPMENTET - EXPANSION TANKETR - EXISTING TO REMAINES - EMERGENCY SHOWEREQS - EQUIPMENT SUPPLIEREWC - ELECTRICAL WATER COOLEREXH - EXHAUST AIREXP - EXPANSIONEXT - EXTERIOREX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)FCE - FIRE CONTROL EQUIPMENTFCO - FLOOR CLEANOUTFD - FLOOR DRAINFDC - FIRE DEPARTMENT CONNECTIONFDV - FIRE DEPARTMENT VALVEFF - FINISHED FLOOR ELEVATIONFHC - FIRE HOSE CABINETFLR - FLOORFM - FORCE MAINFOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOWFOG - FUEL OIL GAUGEFOR - FUEL OIL RETURNFOS - FUEL OIL SUPPLYFOT - FLAT ON TOPFPM - FEET PER MINUTEFR - FIRE RISERFS - FLOOR SINK OR FIRE SERVICEFSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)FT - FEETFTG - FOOTING
G - GAS OR NATURAL GASGA - GAUGEGAL - GALLONGALV - GALVANIZEDGC - GENERAL TRADES CONTRACTORGD - GARAGE DRAINAGEGPM - GALLONS PER MINUTEGS - GAS SERVICEGW - GREASE WASTE
H2 - HYDROGENHB - HOSE BIBBHC - HVAC CONTRACTOR (DIVISION 23)HD - HUB DRAINHE - HELIUMHG - REFRIGERANT HOT GASHP - HORSEPOWER OR HIGH POINTHPC - HIGH PRESSURE CONDENSATE RETURNHPS - HIGH PRESSURE STEAM SUPPLYHPW - HIGH PURITY WATERHPWR - HIGH PURITY WATER RETURNHR - HOSE REELHT - HEAT TRACEHTR - HEATERHVAC - HEATING, VENTILATING, AND AIR CONDITIONINGHW - HOT WATERHWR - HEATING HOT WATER RETURNHWS - HEATING HOT WATER SUPPLY
IA - MEDICAL INSTRUMENT AIRID - INSIDE DIAMETERINV - INVERT ELEVATIONIN - INCHESIV - INDIRECT VENTIW - INDIRECT WASTE
JS - JANITOR SINK
K - KITCHEN WASTEKEC - KITCHEN EQUIPMENT CONTRACTOR
K - KITCHEN WASTEKEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTHLA - LABORATORY COMPRESSED AIRLAV - LAVATORYLBS - POUNDSLCW - LABORATORY COLD WATERLEC - LABORATORY EQUIPMENT CONTRACTORLHW - LABORATORY HOT WATERLHWR - LABORATORY HOT WATER RETURNLPC - LOW PRESSURE CONDENSATE RETURNLPS - LOW PRESSURE STEAM SUPPLYLV - LABORATORY VACUUM OR LABORATORY VENTLW - LABORATORY WASTE
MA - MEDICAL COMPRESSED AIRMAP - MASTER ALARM PANEL (MEDICAL GAS)MAX - MAXIMUMMB - MOP BASINMC - MECHANICAL CONTRACTOR (DIVISION 23)MEZZ - MEZZANINEMFR - MANUFACTURERMH - MANHOLEMIN - MINIMUM OR MINUTEMISC - MISCELLANEOUSMTD - MOUNTEDMTG - MOUNTINGMPC - MEDIUM PRESSURE CONDENSATE RETURNMPS - MEDIUM PRESSURE STEAM SUPPLYMU - WATER MAKE-UPMV - MEDICAL SURGICAL VACUUM
N2 - MEDICAL NITROGENNG - GASOLINE (NON-LEAD)NIC - NOT IN CONTRACTNO - MEDICAL NITROUS OXIDENOM - NOMINALNPW - NON-POTABLE WATERNPT - NATIONAL PIPE THREADNTS - NOT TO SCALE
02 - MEDICAL OXYGENOA - OUTDOOR AIROD - OUTSIDE DIAMETER OR OVERFLOW DRAINOFCI - OWNER FURNISHED CONTRACTOR
INSTALLEDOFOI - OWNER FURNISHED OWNER INSTALLED
P - PROPANE GASPC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURNPD - PUMP DISCHARGE OR PARAPET DRAINPIV - POST INDICATOR VALVEPLBG - PLUMBINGPS - PRE-ACTION/DELUGE SPRINKLERPRESS - PRESSUREPRV - PRESSURE REGULATING VALVEPSF - POUNDS PER SQUARE FOOTPSI - POUNDS PER SQUARE INCHPSV - PRESSURE SUSTAINING VALVEPSIG - POUNDS PER SQUARE INCH GAUGEPW - PURE WATER
RA - RETURN AIRRAD - RADIUSRCP - REINFORCED CONCRETE PIPERD - ROOF DRAINREC - RECESSEDREQD - REQUIREDRI - ROUGH INRL - REFRIGERANT LIQUIDROS - REVERSE OSMOSIS WATER SUPPLYROR - REVERSE OSMOSIS WATER RETURNRPM - REVOLUTIONS PER MINUTERS - REFRIGERANT SUCTIONRV - RELIEF VALVE
S - SPRINKLER (WET)SA - SHOCK ARRESTOR OR SUPPLY AIRSAN - SANITARY OR SANITARY DRAINSCH - SCHEDULESCW - SOFT COLD WATERSD - SPRINKLER DRAIN OR SUBSOIL DRAINSH - SHOWERSHT - SHEETSK - SINKSPEC - SPECIFICATIONSSQ - SQUARESR - SUPPLY RISERSS - SANITARY STACK (SOIL OR WASTE) OR
STAINLESS STEELSTD - STANDARDSTM - STORM OR STORM DRAINAGESTRUC - STRUCTURAL OR STRUCTURESUC - SITE UTILITY CONTRACTOR
T - FUEL TANK VENTTD - TRENCH DRAINTEMP - TEMPERATURETOB - TOP OF BEAMTOD - TOP OF DUCTTOE - TOP OF EQUIPMENTTOF - TOP OF FOOTINGTOJ - TOP OF JOISTTOP - TOP OF PIPETOS - TOP OF SLAB OR TOP OF STEELTF - TRAP FILLERTP - TRAP PRIMER OR TRAP PRIMER DISCHARGETW - TEMPERED WATERTYP - TYPICAL
UR - URINALUNO - UNLESS NOTED OTHERWISE
V - VENT OR SANITARY SEWER VENTVAC - VACUUMVC - VACUUM CLEANINGVCV - VACUUM CLEANING VALVEVE - VACUUM EXHAUSTVEL - VELOCITYVIB - VALVE IN BOXVOL - VOLUMEVP - VACUUM PUMPVS - VENT STACKVTR - VENT THROUGH ROOFVR - VENT RISER
W/ - WITHW/0 - WITHOUTW - WASTEWAGD - WASTE ANESTHESIA GAS DISPOSALWC - WATER CLOSETWCO - WALL CLEANOUTWH - WALL HYDRANT OR WATER HEATERWIV - WALL INDICATOR VALVEWS - WATER SERVICE
YCO - YARD CLEANOUT
ZVC - ZONE VALVE CABINET
PIPING SYMBOLSDOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE NOT PERMITTED.)
DIRECTION OF PITCH
DROP
ELBOW DOWN
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
PIPE RISER
C ALL PIPING IS ABOVE THE CEILING (AT THE UNDERSIDE OF STRUCTURE IN EXPOSED STRUCTURE AREAS), UNLESS OTHERWISE NOTED.
D REFER TO SCHEDULES, DETAILS AND DIAGRAMS FOR PIPING, PIPE SIZES AND PIPELINE DEVICES NOT INDICATED ON THE FLOOR PLAN.
E ABOVE CEILING UTILITY SPACE IS LIMITED. COORDINATION WITH ALL TRADES IS CRITICAL, PRIOR TO INSTALLATION ON ANY WORK.
F EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON AVAILABLE DRAWING INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY
G ALL PIPING SHALL BE REMOVED BACK TO ACTIVE MAINS AND CAPPED, OR REMOVED BACK TO POINTS OF CONNECTION OF NEW WORK. INACCESSIBLE PIPING, WHERE SO NOTED, TO BE ABANDONED SHALL BE DISCONNECTED FROM ACTIVE MAINS AND CAPPED OR PLUGGED IN CONCEALED LOCATIONS.
H NEW CONNECTIONS TO EXISTING PIPING SHALL BE WITH THE SAME SIZE AS THE EXISTING PIPING UNLESS OTHERWISE NOTED.
I ALL REMOVED MATERIAL AND EQUIPMENT SO DESIGNATED BY THE COR, SHALL BE TURNED OVER AND PLACED WHERE DIRECTED. ALL MATERIAL AND EQUIPMENT, WHICH THE COR DOES NOT WISH TO RETAIN, SHALL BECOME THE PROPERTY OF THE CONTRACTOR RESPONSIBLE FOR THE REMOVAL.
J REFER TO THE ARCHITECTURAL PLANS FOR PROJECT PHASING REQUIREMENTS.
K ALL LAB GAS SYSTEM INSTALLERS SHALL BE CERTIFIED TO THE REQUIREMENTS OF ASSE 6010. ALL LAB GAS SYSTEM VERIFIERS SHALL BE CERTIFIED TO THE REQUIREMENTS OF ASSE 6030.
L LAB GAS AND VACUUM SYSTEM INSTALLATION AND VERIFICATION SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 99C, LABORATORY SYSTEMS, 2005 EDITION.
A THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.
B SITE VISIT(S) SHALL BE AS OUTLINED IN PROJECT SPECIFICATIONS.
DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE CONTRACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL BE BROUGHT TO THE ATTENTION OF THE COR IN WRITING FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.
M ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT & OTHER SIMILAR PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS THROUGH 0-HOUR RATED WALLS & FLOORS SHALL BE FIRESTOPPED TO RETARD PASSAGE OF FIRE AND SMOKE.
N THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE WORK IN ADVANCE WITH ALL OTHER TRADES AND REPORT IMMEDIATELY ANY DIFFICULTIES WHICH CAN BE ANTICIPATED.
O FIELD VERIFY EXISTING CONDITIONS, INCLUDING PIPE SIZES, SERVICES AND LOCATIONS PRIOR TO PERFORMING WORK.
P ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER THIS WORK TO MATCH EXISTING.
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
8/20
14 3
:12:
58 P
M
12/1
8/20
14 3
:12:
58 P
M
P0.1DPBRLT
LEGENDS AND SYMBOLS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
GENERAL NOTES
INDEX OF DRAWINGS - PLUMBINGSheet Number Description
P0.1 LEGENDS AND SYMBOLSP0.2 SCHEDULES AND DIAGRAMSP1.2 SECOND FLOOR PLAN - REMOVALSP2.2 SECOND FLOOR PLAN - NEW WORK
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
MTG.HGT.SYMBOL
DRAINAGE CONNECTION
DIRECTDESCRIPTION
FIXTURE UNITS
DRAINS C/HWATER
COLD HOT
SUPPLY
OUTLET VENTREMARKS
INDIRECT
EQUIPMENT.5 SUPPLIES SHALL BE AS LISTED. TERMINAL OUTLETS ON EQUIPMENT MAY
4 MAKE ALL FINAL CONNECTIONS TO EXISTING/RELOCATED AND NEW
3 PROVIDE ALL NECESSARY SUPPLIES, STOPS, TRAPS, FIX. DRAINS,
DESCRIPTIONMARK
L1
1 PROVIDE ROUGH-IN.
BE SMALLER AND REDUCER FITTING REQUIRED.
2 INSTALL ALL "LOOSE" COMPONENTS.
CONTINUOUS WASTE, & ALL INDIRECT WASTE.
SE
E E
QU
IP'T
SC
HE
D. N
OT
ES
AIR
GA
P
AIR
BR
EA
K
TO
FLO
OR
DR
AIN
IND
IRE
CT
VE
NT
-MIN
IMU
M
WA
ST
E-M
INIM
UM
FIX
TU
RE
DR
AIN
TR
AP
FIX
TU
RE
OU
TLE
T
DH
W
DC
W
0.5" -
SUPPLY WASTE & VENT
LAB SINK/EMERGENCY EYE/FACEWASH/ACID WASTE TRAP
P706 EMERGENCY SHOWER/MOUNTED IN CEILING 1 6/6 - - - EMERGENCY EQUIPMENT TEMPERING VALVE/TEPID--
L3 FUME HOOD/ACID WASTE TRAP
0.5"
GA
S
LAB
AIR
LAB
VA
CU
UM
- - -
0.5" 0.5" 0.5"-
1.5" 1.5" 1.5" 2"
1.5"2"1.5"1.5"1.5"
1.5" - -
- - -
SA
NIT
AR
Y
KIT
CH
EN
WA
ST
E
AC
ID W
AS
TE
--
--
SEE
SPECS
-
-
TR
EA
TE
D W
AT
ER
-
-
WATER TO FIXTURE/10" DIA. STAINLESS STEEL
(2) (2)
ST
AN
DP
IPE
-
-
TEPID
1" -
0.5"
FIXTURES
EQUIPMENT
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
8/20
14 3
:12:
58 P
M
12/1
8/20
14 3
:12:
58 P
M
P0.2DPBRLT
SCHEDULES AND DIAGRAMS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
1 2 3 4 5 6 7 8 9
A
B
C
D
FUTUREAIR
INTAKESHAFT
DUCTSHAFT
207BSTERILE/SURGERY
207CSCRUB
213
FEMALETOILET
207PREP-LAB
203BIO-CHEMISTRY
AIRINTAKESHAFT
ELEV.201
OFFICE
216LOBBY
215CORRIDOR
200ELEC.
200ASTAIR #1
202RENAL
210AOFFICE
208
CONTROLROOM
210
HISTOLOGY/CHEMISTRY
212ASTAIR #2
214H.A.C.
1
1
1
22
4
4
4
1
3
5
6
7
8
9
10
11
12
13
1415
16
17
18
19
20
21
22
1
1 1 -COCO-1 1 -COCO-
111514 1414 1414 14
14 1414 14 14 1414 14
7
77
2 2
5
55
6
12 6
12
5
6
12
5
1 -CO
121212
77
55
13
6
12
512
6
12
7
5
6
12
7
5
7
12
2
5
1CO-
6
12
5
1CO-1 -CO
1 -CO
1 -CO1CO-
1515
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
8/20
14 3
:13:
01 P
M
12/1
8/20
14 3
:13:
01 P
M
P1.2DPBRLT
SECOND FLOOR PLAN - REMOVALS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
SCALE: 1/4" = 1'-0"
SECOND FLOOR PLAN1
GENERAL NOTESA REFER TO SHEET P0.1 FOR GENERAL NOTES.
NOTES1 EXISTING TO REMAIN.
2 REMOVE ALL DIVISION 22 PIPING CONNECTIONS TO LAB SINK BACK TOACTIVE MAIN OR POINT OF NEW CONNECTION.
3 EXISTING FUME HOOD TO REMAIN. MAINTAIN EXISTING DIVISION 22PIPING CONNECTIONS.
4 REMOVE ALL DIVISION 22 PIPING CONNECTIONS TO LAB FUME HOODBACK TO ACTIVE MAIN OR POINT OF NEW CONNECTION. REMOVE PIPINGTO ABOVE CEILING OR BELOW FLOOR SLAB WHERE WALLS ARE TO BEREMOVED. NO PIPE STUBS SHALL REMAIN VISIBLE IN FINISHED AREAS.
5 REMOVE EXISTING ACID TRAP LOCATED BELOW LAB FIXTURE ANDSANITARY DRAIN PIPING BACK TO ACTIVE MAIN OR POINT OF NEWCONNECTION.
6 REMOVE ALL DIVISION 22 PIPING CONNECTIONS TO CUP SINK BACK TOACTIVE MAIN OR POINT OF NEW CONNECTION.
7 REMOVE NATURAL GAS, LAB AIR, AND LAB VAC OUTLETS AND ALLEXTRANEOUS PIPING BACK TO ACTIVE MAIN OR POINT OF NEWCONNECTION.
8 REMOVE 0.5" LAB VAC PIPING AND WALL-MOUNTED LAB VAC OUTLET.
9 REMOVE WALL-MOUNTED 0.5" LAB VAC PIPING BACK TO ACTIVE MAIN ORPOINT OF NEW CONNECTION.
10 REMOVE WALL-MOUNTED 0.5" NATURAL GAS, 0.5" LAB AIR, AND 0.5" LABVAC PIPING AND OUTLETS.
11 REMOVE HOSE BIBB AND ALL EXTRANEOUS DCW PIPING BACK TOACTIVE MAIN OR POINT OF NEW CONNECTION.
12 REMOVE EXISTING DRAIN PIPING AND PROVIDE FLOOR CLEANOUTFLUSH WITH FINISHED FLOOR SLAB. MODIFY EXISTING PIPING AT FLOORTO ACCOMMODATE NEW FLOOR CLEANOUT.
13 EXISTING DRAIN THROUGH FLOOR SLAB TO REMAIN TO ACCOMMODATENEW DRAIN PIPING.
14 REMOVE EXISTING NATURAL GAS, LAB AIR, LAB VAC, DCW, AND DHWPIPING BACK TO SHUT-OFF VALVES LOCATED AT CHASE WALL AND CAP.
15 REMOVE EXISTING NATURAL GAS, LAB AIR, LAB VAC, DCW, AND DHWPIPING BACK TO POINT OF NEW CONNECTION TO ACCOMMODATE NEWWORK. REFER TO DRAWING P2.2 FOR NEW WORK LAYOUT.
16 REMOVE EXISTING IN-LINE FILTER AND ALL EXTRANEOUS PIPING BACKTO ACTIVE MAIN OR POINT OF NEW CONNECTION.
17 REMOVE EXISTING SANITARY TRAP AND EXTRANEOUS PIPING ANDPROVIDE FLOOR CLEANOUT FLUSH WITH FINISHED FLOOR. MODIFYEXISTING PIPING AT FLOOR TO ACCOMMODATE NEW FLOOR CLEANOUT.
18 REMOVE EXISTING EMERGENCY SHOWER AND ALL EXTRANEOUS PIPINGBACK TO ACTIVE MAIN OR POINT OF NEW CONNECTION.
19 REMOVE EXISTING EMERGENCY EYE/FACE WASH AND ALL EXTRANEOUSPIPING BACK TO ACTIVE MAIN OR POINT OF NEW CONNECTION.
20 REMOVE EXISTING NEUTRALIZING BASIN AND ALL EXTRANEOUS PIPINGBACK TO ACTIVE MAIN OR POINT OF NEW CONNECTION.
21 REMOVE EXISTING EMERGENCY SHOWER AND RETAIN EXISTING PIPINGABOVE CEILING TO ACCOMMODATE NEW EMERGENCY SHOWER INSAME LOCATION. REFER TO DRAWING P2.2 FOR NEW WORK LAYOUT.
22 REMOVE EXISTING WALL-MOUNTED LAB GAS OUTLET AND ALLEXTRANEOUS PIPING BACK TO ACTIVE MAIN.
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
1 2 3 4 5 6 7 8 9
A
B
C
D
CORRIDORC-2-2
LAB209
OFFICE209A
LAB210
OFFICE202
OFFICE203
OFFICE204
OFFICE206
OFFICE205
STORAGE207A
ELECTRIC208
STORAGE207
OFFICE201
CLOSET201A
CORRIDORC-2-3
CORRIDORC-2-1
CORRIDORC-2-4
1 2 3 4 5 6 7 8 9
A
B
C
D
1 2 3 4 5 6 7 8 9
A
B
C
D
1
1
2
1
3
1
1
- 3" SS 2" VS 0.75" G 0.75" LA 0.75" LV 1" DCW 1" DHW 0.5" DHWR
1 - 3" SS 2" VS 0.75" G 0.75" LA 0.75" LV 1" DCW 1" DHW 0.5" DHWR
GAV
GAV
L1 L1
111 1 1
1 1 1
1
1 11
1
1
55
44
GAV
GAV
55
44
L1L1
L1L1
ACID WASTE TRAP
DRAIN PIPING
LAB COUNTERTOP WITHINTEGRAL SINK, FAUCET,AND EMERGENCY EYEWASH (BY LABEQUIPMENT PROVIDER).
ACID WASTE TRAP
DRAIN PIPING
LAB COUNTERTOP WITHINTEGRAL SINK, FAUCET,
AND EMERGENCY EYEWASH (BY LAB
EQUIPMENT PROVIDER).
FLOOR
LAB COUNTERTOPWITH INTEGRAL SINK,FAUCET, ANDEMERGENCY EYEWASH (BY LABEQUIPMENTPROVIDER).
L1
ACID WASTE TRAP
FLOORDRAIN PIPING
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
8/20
14 3
:13:
05 P
M
12/1
8/20
14 3
:13:
05 P
M
P2.2DPBRLT
SECOND FLOOR PLAN - NEW WORK
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
SCALE: 1/4" = 1'-0"
SECOND FLOOR PLAN - NEW WORK1
GENERAL NOTESA REFER TO SHEET P0.1 FOR GENERAL NOTES.
NOTES1 EXISTING TO REMAIN.
2 EXISTING FUME HOOD TO REMAIN.
3 CONNECT EXISTING DIVISION 22 PIPING TO NEW FUME HOOD. REVISEEXISTING PIPING AS REQUIRED TO ACCOMMODATE NEW FUME HOOD.CUTTING AND PATCHING BY DIVISION 22 CONTRACT. COORDINATE ALLWORK WITH GENERAL CONTRACTOR.
4 EXTEND 0.5" DCW AND DHW TO BELOW LAB SINK. PROVIDE BALL-TYPESHUT-OFF VALVES WITH STAINLESS STEEL BALL AND STEM.
5 PROVIDE EMERGENCY THERMOSTATIC MIXING VALVE WITH INTEGRALBYPASS CERTIFIED TO ASSE 1071 TO SERVE EMERGENCY EYEWASH(PROVIDED BY LAB EQUIPMENT SUPPLIER). CAPACITY SHALL BE 3 GPM@ 10 PSI PRESSURE DROP. SET UNIT TO PROVIDE 85 DEGREE F TEPIDWATER.
SCALE: NONE
TYPICAL EXISTING SUPPLY CONNECTIONS2
SCALE: NONE
TYPICAL LAB - CASEWORK
SCALE: NONE
TYPICAL LAB - CASEWORK
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
SP
dP
H
T
T
T
T
C
AH7
2H4
DUCT THERMOSTAT WITH AVERAGING ELEMENT
DUCT STATIC PRESSURE SENSOR
DUCT HUMIDITY SENSOR
ROOM SENSOR: TEMPERATURE, HUMIDITY
LENGTH IN DUCT WHEN SPACE PERMITS)
REMOTE BULB THERMOSTAT
ROOM CONTROL: THERMOSTAT, HUMIDISTAT
DIFFERENTIAL PRESSURE SWITCH
DUCT TEMPERATURE SENSOR WITH AVERAGING ELEMENT
SMOKE DETECTOR (SEE ELECTRICAL SPECIFICATIONS)
DUCT OR PIPE TEMP. SENSOR (SEE NOTE 1 ABOVE)
DUCT OR PIPE THERMOSTAT (NOTE 1: PROVIDE 12" MIN.
AFTER FILTER
CURRENT SENSING RELAY
AIR HANDLING UNIT
ANALOG INPUT
AIR PRESSURE DROP
ANALOG OUTPUT
AUTOMATIC TEMPERATURE CONTROLS
AIR FLOW MEASURING DEVICE
ABOVE FINISHED FLOOR
DIFFERENTIAL OR STATIC PRESSURE TRANSMITTER
COOLING COIL
CONVERTOR
CONVECTOR
CLEAN OUT
CEILING GRILLE
CEILING DIFFUSER
BOTTOM REGISTER (WALL TYPE)
BOTTOM GRILLE (WALL TYPE)
CEILING REGISTER
DIGITAL OUTPUT
DIGITAL INPUT
DIRECT DIGITAL CONTROLS
DRY BULB TEMPERATURE, DEG. F
AUTOMATIC CONTROL DAMPER
ENGINEERING CONTROL CENTER
DOOR UNDERCUT BY GENERAL CONTRACTOR
OF LISTED SIZE OF PIPE.APPROXIMATE ELEVATION FROM FLOOR TO CENTER
MANUAL VOLUME DAMPER
U/C
9'-6"
FIRE DAMPER
BALL VALVE
MANUAL AIR VENT
AUTOMATIC FLOW CONTROL VALVE
TEST PLUG (PRESSURE/TEMPERATURE)
STRAIGHT-THRU MODULATING CONTROL VALVE
EX. EXISTING
ECC
DI
DO
dBA
DDC
D
Db
DECIBELS
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
EQUIPMENT ABBREVIATION (SUPPLY FAN)
SUPPLY FAN NO.3 IN BUILDING NO.1
DRAWING NUMBER WHERE DRAWN
DRAWING NUMBER WHERE DRAWN
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
EXHAUST DUCT (UP & DOWN)
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
EXHAUST OR RETURN TOP REGISTER OR GRILLE,
EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE,
EXHAUST OR RETURN CEILING REGISTER OR GRILLE
SUPPLY DUCT (UP & DOWN)
INCLINED RISE, IN DIRECTION OF AIR FLOW
NEW DUCT - WIDTH X DEPTH
RECTANGULAR ELBOWS WITH VANES)VANED ELBOW (PROVIDE ALL SQUARE OR
INCLINED DROP, IN DIRECTION OF AIR FLOW
ACCOUSTICAL DUCT LINING
STANDARD RADIUS ELBOW
R
10X8
FC
D
FLEXIBLE CONNECTION
(WALL TYPE)
(WALL TYPE)
1-01
1-SF3
AIR HANDLING UNIT NUMBER
TERMINAL UNIT DESIGNATION
TYPICAL UNIT NO.
SECTION LETTER
DETAIL NUMBER
DIRECTION OF FLOW
CAPPED OUTLET
SIDE CONNECTION
EXISTING WORK.POINT OF CONNECTION BETWEEN NEW AND
RISE OR DROP IN PIPE
BOTTOM CONNECTION, 45 DEG. OR 90 DEG.
TOP CONNECTION, 45 DEG. OR 90 DEG.
DIRECTION OF PIPE PITCH (DOWN)
THERMOMETER
STRAINER
GATE VALVE
PRESSURE GAGE
CHECK VALVE
EXISTING PIPE TO BE REMOVED
UNION
CONV
CR
CO
CG
CD
CC
C
BR
BG
ATC
AI
APD
AO
AHU
AFMD
AFF
AF
HEATING HOT WATER RETURN
HEATING HOT WATER SUPPLYHWS
HWR
HEATING
SPS
SF
T
H
T
T H
WET BULB TEMPERATURE, DEG. FWb
MAXIMUM
OUTSIDE AIR
PRE-FILTER
PREHEAT COIL
RELATIVE HUMIDITY
TRANSFER GRILLE
UNIT HEATER
STATIC PRESSURE (INCHES OF WATER)
POWER OPERATED, PARALLEL BLADE DAMPER
POWER OPERATED, OPPOSED BLADE DAMPER
PRESSURE DROP (FEET OF WATER)
TOP REGISTER (WALL TYPE)
STATIC PRESSURE SENSOR
DOOR UNDERCUT BY GENERAL CONTRACTOR
SPS
TR
U/C
UH
TG
S.P.
Rh
PD
PF
POD
PH
PPD
MAX
O.A.
NOM
MIN
NOMINAL
MINIMUM
HEATING COIL
HORSEPOWER
FIN TUBE RADIATION
MIXING BOX
POUNDS PER HOUR
LOCAL TEMPERATURE CONTROL PANELLTCP
LBS/HR
MB
FLR.
FTR
HC
HP
FLOOR
(FOUR WAYBLOW UNLESS OTHERWISECEILING DIFFUSERS
NOTED)
CONTROL CIRCUIT CONN.H1 N
ETCHED CLEAR LACQUERE.C.L.
WHITE BAKED ENAMELW.B.E.
BRAKE HORSEPOWERBHP
BRITISH THERMAL UNITBTU
BRITISH THERMAL UNIT PER HOURBTUH
CUBIC FEET PER MINUTECFM
DEGREEDEG
DIAMETERDIA
DIFFERENTIAL PRESSURE SENSORDPS
ENTERINGENT
F FAHRENHEIT
FPM FEET PER MINUTE
FT FEET
GALLONS PER MINUTEGPM
HEADHD
HEATING HOT WATER RETURNHWR
HEATING HOT WATER SUPPLYHWS
INCHESIN
INCHES WATER COLUMNIN WC
INCHES WATER GAUGEIN WG
LEAVING AIR TEMPERATURELAT
LEAVINGLVG
MBH 1000 BTUH
MERV MINIMUM EFFICIENCY REPORTING VALUE
NC NOISE CRITERIA
REVOLUTIONS PER MINUTERPM
SMOKE DAMPER (SUPPLY)SDS
SMOKE DAMPER (RETURN)SDR
VARIABLE AIR VOLUMEVAV
PIPE UP
PIPE DOWN
RATED WALL ASSEMBLY. REFER TOARCHITECTURAL DRAWINGS FOR RATING.
B.O.D. 10'-2" OF LISTED DUCT.APPROXIMATE ELEVATION FROM FLOOR TO BOTTOM
1. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.
2. INSULATE DUCTWORK AND PIPING WHERE EXISTING INSULATION HAS BEEN DAMAGED AND/OR REMOVED IN THE PERFORMANCE OF WORK IN THISPROJECT.
3. THE CONTRACTORS SHALL REFER TO ALL SPECIFICATION SECTIONS AND THESE DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURESPACE AND SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS DRAWINGS COMPRISING THE SET ARE INTERDEPENDENT AND MUST BEUSED JOINTLY AT ALL TIMES. EACH CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS OF THE CONTRACT. THE NOTES AND SYMBOLSINDICATED ON THE DRAWINGS ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST BE FOLLOWED TO EXECUTE THE WORKAS INTENDED. IF DISCREPANCIES OCCUR, CONTACT THE VA COR THRU THE CONTRACTING OFFICER FOR CLARIFICATION BEFORE PROCEEDING.
4. EACH CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHERS. HE SHALL KEEP HIMSELF INFORMED OF THE PROGRESS AND DETAILDEVELOPMENT OF THE WORK OF OTHERS AND SHALL BE RESPONSIBLE FOR COORDINATING AND EXPEDITING HIS WORK WITH OTHERS SO THAT THEPROGRESS OF THE TOTAL WORK SHALL BE KEPT ON SCHEDULE.
5. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL GOVERNING CODES AND STANDARDS.
6. EXISTING CONDITIONS SHOWN HAVE BEEN BASED ON VISUAL OBSERVATION AND/OR AVAILABLE DRAWING INFORMATION, AND MAY BE AT VARIANCEWITH ACTUAL WORK IN PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL CONDITIONS AFFECTINGTHE EXECUTION OF THE WORK. ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE CONTRACT DOCUMENTS WHICHMAY IMPACT THE PROGRESS OF THE WORK SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING FOR RESOLUTIONBEFORE PROCEEDING WITH THE WORK.
7. EACH CONTRACTOR AND/OR TRADE, FITTING OR PLACING HIS WORK INTO OR ON THE WORK OF OTHERS DOES SO WITH THE UNDERSTANDING THATTHE INSTALLATION OF HIS WORK CONSTITUTES HIS ACCEPTANCE OF THE SUITABILITY OF THE WORK IN PLACE. IF THE WORK OF OTHERS IS NOTACCEPTABLE, HE SHALL NOTIFY THE VA PROJECT ENGINEER AND SUCH WORK SHALL BE CORRECTED. ANY NEW WORK INSTALLED IN UNSUITABLEEXISTING WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE INSTALLING THE NEW WORK. NO CLAIMS FOR ADDITIONALCOMPENSATION FOR CORRECTING WORK INSTALLED IN UNSUITABLE EXISTING CONDITIONS WILL BE CONSIDERED.
8. ABATEMENT, REMOVAL OR ENCAPSULATION OF EXISTING MATERIALS CONTAINING ASBESTOS IS INCLUDED IN THIS CONSTRUCTION CONTRACT. REFERTO DRAWINGS AND/OR SPECIFICATIONS FOR LOCATION OF ASBESTOS. ANY ASBESTOS WORK PERFORMED AS PART OF THIS PROJECT SHALL BECOMPLETED PRIOR TO STARTING ANY OTHER PROJECT SITE WORK. REFER TO SPECIFICATIONS FOR ASBESTOS ABATEMENT.
9. REFER TO ARCHITECTURAL FIRE-RATED PARTITION PLAN(S) FOR LOCATIONS AND FIRE-RATINGS OF NEW AND EXISTING WALL ASSEMBLIES. ALLPENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROTECTED AND/OR FIRE-STOPPED AS REQUIRED TO MAINTAIN FIRE-RATINGSINDICATED. COORDINATE WITH ALL TRADES TO ENSURE FIRE-RATED PENETRATION REQUIREMENTS AND DETAILS ARE MET.
10. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT & OTHER SIMILAR PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION,PENETRATIONS THROUGH 0-HOUR RATED WALLS & FLOORS SHALL BE FIRESTOPPED TO RETARD PASSAGE OF FIRE & SMOKE.
11. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.
12. ACCESS PANELS IN NON ACCESSIBLE SUSPENDED CEILINGS SHALL BE PROVIDED FOR ALL VALVES, TRAPS, DAMPERS, CLEANOUTS, FLOW METERS,CONTROLS, ETC.
13. FOR TYPICAL CONNECTIONS TO EQUIPMENT, SEE STANDARD DETAILS AND PIPING SCHEMATICS.
14. DIFFUSER SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES. REGISTER AND GRILLE SIZES SHOWN ARE FACE SIZES. REFER TO ARCHITECTURALREFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING DIFFUSERS, REGISTERS, AND GRILLES.
15. ALL ABANDONED EXTRANEOUS PIPING, DUCTWORK, SUPPORTS, CONTROLS, ETC. SHALL BE REMOVED.
16. WHERE DUCTS OR PIPES ARE REMOVED THRU WALL/FLOOR/ROOF THAT IS TO REMAIN, PATCH WALL/FLOOR/ROOF OPENING TO MATCH EXISTINGWHERE OPENING IS NOT RE-USED.
17. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER THISWORK TO MATCH EXISTING.
18. IN GENERAL, KEEP DUCT AND PIPING MAINS NEXT TO UNDERSIDE OF STRUCTURE.
19. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED BY THE VA SHALL BE REMOVED FROM THE PREMISES ANDDISPOSED OF PROPERLY BY THE CONTRACTOR.
20. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL OFFSET WHICH MAY BE NECESSARY TO COMPLETE THESYSTEMS. COORDINATE WORK IN ADVANCE WITH ALL OTHER TRADES AND REPORT IMMEDIATELY ANY DIFFICULTIES WHICH CAN BE ANTICIPATED.
21. HEPA FILTERED EXHAUST IS REQUIRED TO MAINTAIN A MINIMUM OF 0.01" W.G. NEGATIVE PRESSURE IN CONSTRUCTION AREAS. COORDINATE WITHGENERAL CONTRACTOR AND THE VA COR.
22. TERMINATE PIPING AND DUCTWORK BELOW FLOORS, ABOVE CEILINGS, ETC., IN CONCEALED SPACES. ALL CUTTING AND PATCHING SHALL MATCHEXISTING FINISHES.
23. WHERE CONTROL DEVICES ARE REMOVED, PNEUMATIC LINES SHALL BE REMOVED BACK TO MAIN AND CAPPED; AND CONTROL WIRING AND CONDUITSHALL BE REMOVED BACK TO SOURCE.
24. ALL EXISTING DUCTWORK, PIPING, EQUIPMENT, CONTROLS, ETC. SHOWN DASHED ON REMOVAL PLAN(S) SHALL BE REMOVED. THE MAJORITY OF WORKTO BE REMOVED IS SHOWN. REMOVE ALL INCIDENTAL AND/OR ABANDONED EQUIPMENT, DUCTWORK, PIPING, ETC. THAT MAY NOT BE SHOWN BUT ISASSOCIATED WITH THE REMOVAL WORK.
25. WHERE EXISTING HVAC UTILITIES IN SERVICE WILL BE DISRUPTED DURING THE CONSTRUCTION OF THIS PROJECT, THIS WORK SHALL BE PERFORMEDON WEEKENDS OR WEEK NIGHTS, IF REQUIRED BY THE VA COR. DOWNTIME SHALL BE KEPT TO A MINIMUM, AND SHALL BE COORDINATED ANDSCHEDULED WELL IN ADVANCE WITH THE VA COR.
26. RUNOUT PIPING TO TERMINAL UNITS AND FAN COIL UNITS SHALL BE 0.75" SIZE UNLESS OTHERWISE NOTED ON PLANS OR IN SCHEDULES.
27. APPROXIMATE ELEVATIONS NOTED ARE TO THE CENTER OF THE PIPE AND BOTTOM OF DUCT.
28. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE INSTALLED WITH BOTTOM OF REGISTERS SEVEN INCHES ABOVE FINISHEDFLOOR.
CARBON DIOXIDE SENSOR FOR SYSTEM ALARM
WELDED STAINLESS STEEL DUCT
DP
C
DRAWING SYMBOLS
DUCTWORK SYMBOLS
VALVES
GENERAL
ABBREVIATIONS
PIPING SYMBOLSCONTROLS GENERAL NOTES:ABBREVIATIONS
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 7
:57:
08 A
M
12/1
9/20
14 7
:57:
08 A
M
M0.1DRVWPCW
INDEX, LEGEND, AND GENERALNOTES
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
INDEX OF DRAWINGSSheet Number Description
M0.1 INDEX, LEGEND, AND GENERAL NOTESM0.2 SCHEDULES AND DETAILSM0.3 CONTROLS AND DETAILSM1.1 SECOND FLOOR PLAN - REMOVALSM2.1 SECOND FLOOR PLAN - NEW WORK
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
DUCTWORK TRANSITIONS
DUCTWORK SQUARE VANE ELBOWS
ROUND DUCT HANGERS
DESIGN ALTITUDE: 482 FT.74 DEG. F Wb SUMMEROUTSIDE DESIGN TEMPERATURES
INTERIOR DESIGN AREA
ALL ROOMS
DEG. F Db WINTER
% HUMIDITY
SUMMER
Db
70
5
50
Db
72
DEG. F Db SUMMER93
% HUMIDITY
WINTER
30
NOTES :
CFM
MIN.
240
WINTER
2402-01
UNITNO.
MAX.
240 6"
(IN.)SIZE
APPROX.INLET
SUMMERMIN.
353"0.35"
MAXIMUMROOM NC
REQUIREMENTSSOUND
(2)CFM
SPMAX.
MAX.AT
UNIT AT
SPACROSS
UNIT
ROOM
(3)(4)NC
MAX.CONTROL
(5)TYPE
(6)
2-02
2-03
2-04
2-05
2-06
165165 165 6" 353"0.35"
D.D.C.V.235235 235 6" 353"0.35"
D.D.C.V.8" 353"0.35"
6" 353"0.35"
6" 353"0.35"
1 PROVIDE DUCT TRANSITION AT UNIT INLET WHERE UNIT INLET SIZE AND DUCT RUNOUT SIZE AREDIFFERENT.
2 THE UNIT MAXIMUM SP IS THE PRESSURE DIFFERENCE BETWEEN THE UNIT INLET ANDDISCHARGE. IT IS ALSO THE MINIMUM PRESSURE REQUIRED AT THE UNIT INLET TO OBTAIN THERATED CFM.
3 UNIT NOISE LEVEL SELECTION SHALL NOT EXCEED A ROOM NC OF 35 FROM BOTH AIRBORNEAND RADIATED NOISE, BASED ON A 10 DB ROOM ABSORPTION COEFFICIENT WITH 3" S.P.DIFFERENTIAL ACROSS UNIT AT MAXIMUM CFM SETTING.
4 PROVIDE HOSPITAL GRADE SOUND ATTENUATOR WHERE REQUIRED TO COMPLY WITH THEMAXIMUM NC35 REQUIREMENT.
5 CONTROL TYPES: D.D.C.V.: DUAL DUCT CONSTANT VOLUME TERMINAL.
6 COORDINATE EXACT UNIT DESIGNATION WITH COR.
7 DUAL DUCT BOX IS EXISTING TO REMAIN. BALANCE TO SCHEDULED CFM.
555555 555
240240 240
165165 165
LAY-IN
TYPE MOUNTINGSYMBOL
CD1
DESCRIPTION
DIFFUSER ROUND NECKSTANDARD SQ. CONE CEILING
E.C.L.STEELSURFACE ALUM.
MATERIAL
OPPOSED BLADEDAMPER
ACCESSORIESW.B.E.
FINISHSIZE NOTES
ALL DUCTWORK EXCEPT AS LISTED BELOW.
SUPPLY AIR DUCTS FROM OUTLET OFAIR TERMINAL UNITS TO SUPPLY AIR DEVICES
SUPPLY AIR DUCTS FROM OUTLET OF AH-UNIT
DUCT INVOLVED
GENERAL EXHAUST DUCTS
SYSTEMSALL TO INLET OF AIR TERMINAL UNITS.
SYSTEM
N
P 2"
-2" A
A
NEGATIVE (N)PRESSURE
POSITIVE (P)
P/N
P
ORCLASS
2"
4"
W.G.
+-
A
CLASS
A
SMACNACONST.
SMACNASEAL
SMACNA LEAKAGE CLASS
ROUNDDUCT
6 3
OPPOSED BLADEADJUSTABLE BLADE
EXHAUST REGISTER DAMPER
SEE PLANSTR1
NOTE:UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
TYPICAL DUCTWORK TRANSITIONPLAN OR SIDE VIEW
15°
MAX.
15°M
AX
.
MAIN EXHAUST OR RETURN
PLAN VIEW
AIRFLOW AIR FLOW
W
PROVIDE VOLUME DAMPERAT EACH BRANCH DUCT
1/4W OR 4" MIN.
BRANCH DUCT
45 DEG.
BRANCH DUCT
BRANCH DUCT TAKE-OFF PLAN VIEW
PROVIDE VOLUMEDAMPER
1/4 W OR 4"MIN.
AIRFLOW
MAIN SUPPLYDUCT
W
AIR
FLO
W
SPIN IN TAP FITTINGWITH MANUAL DAMPER
TO AIR DEVICE
NOTES:
1.
2.
3.
4.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESSOF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2" MAXIMUM SPACE BETWEENVANES AND A 3/4" TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20", VANES SHALL BE DOUBLE VANE TYPE.
W2
W1
VANEVANE
NOTES:
1.
2.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALLSHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
R SHALLEQUALOR BEGREATERTHAN W.
R SHALLEQUALOR BEGREATERTHAN1/3W.
W
R
R
2/3W
1/3W R SHALL
EQUALOR BEGREATERTHAN1/6W.
STANDARD RADIUS ORLONG RADIUS ELBOW
SHORT RADIUS ELBOWWITH ONE VANE
SHORT RADIUS ELBOWWITH TWO VANES
W W
1/2W
1/3W
1/6W
R
HOUSING WELDEDTO DUCT SECTION
ROUND ORFLAT OVALDUCT SECTION
COVER WITH HANDLEAND CHAIN RETAINERGASKETED ANDPRESSURE SEALED
2500
1320
420ONE 1 x 18 GA STRAP36
TWO 1/2 DIA. RODS
TWO 3/8 DIA. RODS
ONE 1 x 16 GA STRAP
84
60
50 700
ONE 1 x 22 GA STRAP
QUANTITY/SIZEMAX. DUCT
26
HANGER STRAPS OR RODSMAX. LOADLBS.
260
MAX.
144
IN.SPACING
IN. IN.
144
144
144
144
NOTE:TABULATED DATA FROM SMACNAALLOWS FOR DUCT REINFORCING ANDINSULATION, BUT NO EXTERNAL LOAD.
BAND
OVER 50" DIA.
HANGER RODS
BAND OF SAMESIZE AS HANGERSTRAP
LOAD RATEDFASTENERS
50" DIA. &UNDER
RIGID DUCT TO AIR TERMINAL UNIT.REFER TO AIR TERMINAL UNIT DUCTCONNECTION DETAIL FOR CONTINUATION
ROUND SHEET METAL DUCT.
MAIN SUPPLY
"D"
45°MA
X.
PLAN VIEW
SMACNA FIGURE 4-6.45° LEED IN
MAIN SUPPLY
PLAN VIEW
FLOW
FLO
W
RIGID DUCT TO AIR TERMINAL UNIT. REFER TOAIR TERMINAL UNIT DUCT CONNECTION DETAILFOR CONTINUATION.
(1)
6 3
6 3
6 3
1601602-13 160 6" 353"0.35"
2-14
2-15
2-19
2-17
2-18
100100 100 6" 353"0.35"
110110 110 6" 353"0.35"
6" 353"0.35"
6" 353"0.35"
6" 353"0.35"
205205 205
235235 235
160160 160
CR1 EXHAUST REGISTERSTANDARD SQ. CONE CEILING 24"x24"
NOTES
D.D.C.V.
D.D.C.V.
D.D.C.V.
D.D.C.V.
D.D.C.V.
D.D.C.V.
D.D.C.V.
D.D.C.V.
D.D.C.V.
D.D.C.V.
1 HEATING ELEMENT AND PIPING SPECIALTIES ARE EXISTING TO REMAIN. PROVIDE NEW CONVECTOR CABINET AROUND EXISTING PIPING.
BTUH
2 WALL HUNG, SLOPING TOP, OPEN BOTTOM RETURN. MOUNT AT 0'-10" A.F.F.
MIN.TYPEUNITLOCATION
SEE PLANS15-CONV1
NOTES:
NO. UNIT
CONVECTORHOT WATER CABINET -
RUNOUT
-
GPMSIZE
VALVESIZE
24"
LENGTH
4.5"
WIDTH RECESS
14"
HEIGHT
AUTO APPROX. CABINET DIMS.
1,2
NOTES
7
7
7
7
7
7
7
7
7
- - NO
SUPPLY REGISTER DAMPER
TR2 FIXED BLADE RETURN/ OPPOSED BLADE SEE PLANS
CD2 DIFFUSER ROUND NECKSTANDARD SQ. CONE CEILING OPPOSED BLADE
DAMPER 12"x12"
24"x24"
7
RECTANGULARDUCT
HVAC DESIGN DATA
DUAL DUCT AIR TERMINAL UNITS
AIR DISTRIBUTION DEVICES
DUCT PRESSURE CLASS & LEAKAGE TABLE
EXHAUST OR RETURNBRANCH DUCTWORK
SUPPLY DUCTWORK TAKE-OFFS
DUCTWORK RADIUS ELBOWS
ACCESS SECTION FORROUND/OVAL DUCT
SUPPLY DUCT TAKEOFF -AIR TERMINAL UNIT
ALTERNATE SUPPLYDUCT TAKEOFF - AIRTERMINAL UNITS
HOT WATER CONVECTOR SCHEDULE
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 7
:57:
08 A
M
12/1
9/20
14 7
:57:
08 A
M
M0.2DRVWPCW
SCHEDULES AND DETAILS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
RETURN OR EXHAUST GRILLE/REGISTER CONNECTION
SECTION THRU FIRE DAMPER INSTALLATION
FLEXIBLE AIR DUCT CONNECTOR
ROOM SPACETEMPERATURESENSOR
24 VOLT POWERSUPPLY FROM LOCALDDC PANEL
AIR FLOWSENSOR
TO DDC LANTRUNK
DISCHARGE AIRTEMPERATURESENSOR
DDCV CONTROL TERMINAL
HI
LO
HI
D1
TERMINALBOX DDCCONTROLLER
LO
SUPPLY AIR
AIR FLOWSENSOR
HI
LO
D2
CONTROL DAMPER
LO HI
HOT
COLD
EACH TERMINAL UNIT SHALL INCLUDE AIRFLOW SENSORS FOR CALCULATING CFM, AND ADISCHARGE AIR TEMPERATURE SENSOR. EXTEND 24 VOLT POWER TO THE TERMINAL BOXCONTROLLER FROM EXISTING DDC CONTROL PANEL PROVIDED UNDER PREVIOUS PROJECT.ROOM SPACE TEMPERATURE SETPOINT SHALL BE ADJUSTABLE FROM THE FRONT-ENDCOMPUTER INTERFACE. COORDINATE AND ADJUST TEMPERATURE SETPOINT AND OCCUPANCYSCHEDULES WITH COR. AIRFLOW VOLUME (CFM) SHALL BE CONTROLLED BY TWO VOLUMECONTROLLERS FURNISHED WITH THE BOX. MODULATING DAMPER OPERATORS, CONTROLLEDFROM A WALL-MOUNTED THERMOSTAT, SHALL PROPORTION THE HOT AND COLD AIR DAMPERSTO SATISFY THE THERMOSTAT SETPOINTS.
T1
T2
1 A COMPLETE SYSTEM OF AUTOMATIC TEMPERATURE CONTROLS SHALL BE INSTALLED UNDER THISCONTRACT AS REQUIRED TO ACCOMPLISH THE SEQUENCE OF CONTROL FOR VARIOUS ITEMS OFEQUIPMENT AND SYSTEMS AS DESCRIBED HEREINAFTER. THE SYSTEM SHALL BE A DIRECT DIGITALCONTROL SYSTEM UTILIZING ELECTRIC ACTUATION.
2 ELECTRICAL WORK INCLUDES A POWER SOURCE TO THE MOTOR STARTERS. ALL HVAC POWERSOURCES REQUIRED BEYOND THESE STARTERS OR BEYOND SOURCES EXPLICITLY SHOWN ON THEELECTRICAL DRAWINGS, SHALL BE PROVIDED UNDER THE ATC WORK. THIS WORK SHALL INCLUDE BUTNOT BE LIMITED TO WIRING, CONDUIT, TRANSFORMERS, RELAYS AND FUSES.
3 CONTROL POINTS BELOW ARE SHOWN AS AN AID TO THE CONTRACTOR INDICATING THE MINIMUMPOINTS REQUIRED FOR CONTROL AND MONITORING. ALL INPUT AND OUTPUT POINTS, AND THEIRREQUIRED INTERFACE AND ACCESSORY HARDWARE, SHALL BE PROVIDED FOR A COMPLETE ANDFUNCTIONAL CONTROL SYSTEM. IF OR WHEN ADDITIONAL POINTS ARE REQUIRED TO ACCOMPLISH THESEQUENCES OF CONTROL SPECIFIED, THESE POINTS, ALONG WITH ADDITIONAL DIRECT DIGITALCONTROL PANEL(S) (IF REQUIRED), SHALL ALSO BE PROVIDED. DDC CONTROLS INSTALLED UNDER THISPROJECT SHALL COMMUNICATE WITH FRONT END OF CAMPUS CONTROL SYSTEM. PROVIDE NETWORKAREA CONTROLLERS (BUILDING PANEL) AND AUXILIARY CONTROL UNITS (LOCAL DDC PANELS) ASREQUIRED TO ACCOMPLISH CONTROL FOR RENOVATED AREAS OF BUILDING 15, CAMPUS-WIDECOMMUNICATION, AND GLOBAL CONTROL STRATEGIES. COORDINATE LOCATION OF REQUIRED NEWPANELS WITH COR.
NOTES:
1.
2.
3.
4.
5.
6.
7.
RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE AMINIMUM OF 3 TIMES THE DIAMETER OF INLET SO AS TO ACHIEVE ACCURATEAIRFLOW SENSOR READINGS.
A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THISBOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH3'-0".
PROVIDE DUCT TRANSITION WHERE SCHEDULED DUCT RUNOUT SIZE TO UNITIS DIFFERENT THAN TERMINAL UNIT INLET SIZE.
FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLYAIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0". USE RIGID ELBOWS FORCHANGE OF DIRECTION GREATER THAN 45°.
COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDEINSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.
PROVIDE SOUND ATTENUATOR IF REQUIRED TO MEET DESIGN ROOM NC.PROVIDE DUCT TRANSITION BETWEEN TERMINAL UNIT AND SOUNDATTENUATOR WHERE ATTENUATOR SIZE DIFFERS FROM TERMINAL UNITOUTLET SIZE.
DUCT RUNOUT TO DIFFUSERS SHALL BE SAME SIZE AS THE DIFFUSERNECK SIZE UNLESS OTHERWISE NOTED.
AIR TERMINAL UNIT(D.D.C.V.)
SOUNDATTENUATOR (NOTE6)
FLEXIBLE AIR DUCTCONNECTOR. SEE DETAILON THIS SHEET
DIFFUSER (TYP.)
SEE SPECIFICATIONS FOR CLAMPSAND SEALANT (TYP.)
SEE NOTE 5
SE
E N
OT
E 4
SEE NOTE 2
SEE NOTE 1
NOTE 3
NOTE 7(TYP.)
MAIN SUPPLY DUCT
REFER TO AIR TERMINAL UNITDUCT TAKEOFF DETAILON SHEET H2
DAMPER WHERE
TURNING VANES
STRAP HANGER
251 CFM TO 400 CFM - 10" DIA.401 CFM TO 700 CFM - 12" DIA.
101 CFM TO 250 CFM - 8" DIA.100 CFM AND LESS - 6" DIA.
ARE TO BE SIZED AS FOLLOWS:BRANCH DUCT SIZES, UNLESS NOTED ON PLANS
BRANCH DUCT TAKE-OFF WITH MANUAL DAMPER.1
2
STRAP HANGER
SPIN-IN TAPFITTING
6" MIN
RETURN/EXHAUST DUCT
CEILINGCEILING DEVICE
RECTANGULARDUCT, NOTE 1
MANUALDAMPER
STRAP HANGER
SCHEDULED
SPIN-IN BRANCH TAP FITTINGWITH MANUAL DAMPER
SHEETMETAL PLENUMSAME SIZE AS AIR DEVICE
NOTES:
FLEXIBLE AIR DUCTCONNECTOR. SEEDETAIL ON THIS SHEET
ROUND DUCT - NOTE 2
NOTES:
1.
2.
3.
4.
5.
6.
7.
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, IS SIMILAR. FOLLOWDAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FORSLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION ORFLOOR AND NOT OUTSIDE THE PENETRATION.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPERFRAME AND TO PERIMETER ANGLES.
PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1-1/2"x1-1/2" , 14 GAGE, TO PROVIDE 1"MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.
ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.
PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH ROCK WOOLFIRESTOP FIBER (ONLY IF PERMITTED BY THE DAMPER MANUFACTURER).
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS ANDMECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" HIGH CONCRETE CURB AROUNDOPENING FOR DUCT.
SLEEVE, NOTE 2
DUCTCONNECTIONNOTE 4
DAMPER,NOTE 1
DAMPER COLLAREXTENSION INTEGRALPART OF SLEEVE
SLEEVE, NOTE 2
NOTE 6FIRE BARRIERPARTITION OR CHASE
TYPICAL DUCTINSULATION
PERIMETER ANGLE, NOTE 3 (NOTFASTENED TO PARTITION)
ACCESSPANELNOTE 5
1"
FROM STRUCTURE
SAME AS DIFFUSERINLET: 5'-0" MAX
FLEXIBLE DUCT SIZE
LENGTH.
12"
CEILING
SUPPORT SADDLE
VOLUME DAMPER W/LOCKING QUADSADDLE
SHEET METAL
CONICAL OUTLET
BRANCH DUCT
FOR CHANGE OFDIRECTION GREATER
USE RIGID ELBOWS
THAN 45°
SEE SPECIFICATIONS FOR CLAMPSAND SEALANT (TYP.)
TYPICALDIFFUSER ORREGISTER INLAY-IN CLG.
THERMAL INSULATIONSEE SPECIFICATIONS
CONNECTION TYPICAL
BALL VALVEDIELECTRIC FITTING TYP.BALL VALVE
0.75" EXISTING PIPING
STRAINER
TEST PLUG FLOOR
CONTROL VALVESELF CONTAINED NON-ELECTRIC
AUTOMATIC FLOW CONTROL VALVE
EXISTING HEATING ELEMENT
SCREWHEAD VENT
HWS
PROVIDE NEW CABINET
UNION OR SOLDERHWR
NOTE: SINGLE DUCT CONNECTION SHOWN, DUAL DUCT CONNECTION SIMILAR
DUAL DUCT CONSTANT VOLUME AIR TERMINAL UNIT
GENERAL NOTES
DUCT CONNECTIONS-AIR TERMINAL UNITS
TYPICAL WATER PIPING CONNECTIONS TO CONVECTORS
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 7
:57:
09 A
M
12/1
9/20
14 7
:57:
09 A
M
M0.3DRVWPCW
CONTROLS AND DETAILS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
FS S
T
T
T
T
T T T T T T
T
T
T
TT
T T
T
T
TTT
T
1 2 3 4 5 6 7 8 9
A
B
C
D
1 2 3 4 5 6 7 8 9
A
B
C
D
5
5
13
12
313 2
4
5
3
3
12
13
13
5
5
1 1
1
1
5
5
5
5
5
4
13
13
2
13
13
13
3
12
3
12
12
6
7 7 7 7 7 7
7
7
7777117
7
6
145
138
8
8
8
8
8
8
8
8
8
6
6
61 1 1
1
1212
12
9
9
1
9
1
12
12
10
9
12
9
18ø
22ø
16ø
20ø
14ø
18ø
12ø
14ø
10ø
10ø
HWSHWR
HW
RH
WR
HW
S
HWRHWS
HW
SH
WR
HW
S
2-072-09
2-11
2-102-08
2-12
2-24
2-232-212-19
2-22
13
5
3
2-14
2-13 2-15
2-18
2-17
2-05
2-062-02
2-01
9
5
55
55
55
5
5
6
1
1
6
1
3
1
2
1
6
1
1
1
1
1 1
16
16
1616
16
16
16
16
16
16
15
15
15
1 1
14 14 14
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 7
:57:
12 A
M
12/1
9/20
14 7
:57:
12 A
M
M1.1DRVWPCW
SECOND FLOOR PLAN - REMOVALS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
A REFER TO SHEET M0.1 FOR LEGEND, ABBREVIATIONS, AND ADDITIONALGENERAL NOTES.
GENERAL NOTES
1 EXISTING DUCTWORK TO REMAIN.
2 REMOVE EXISTING AIR TERMINAL UNIT AND ASSOCIATED DUCTWORK, CONTROLS, ETC.REFER TO SHEET M2.1 FOR REPLACEMENT.
3 REMOVE EXISTING AIR DEVICE AND ASSOCIATED BRANCH DUCTWORK, SUPPORTS,ETC..
4 REMOVE DUCTWORK TO THIS POINT AND CAP.
5 REMOVE DUCTWORK TO THIS LOCATION FOR RECONNECTION IN NEW WORK.
6 EXISTING PIPING TO REMAIN.
7 EXISTING HEATING HOT WATER CONVECTOR TO REMAIN.
8 EXISTING AIR TERMINAL UNIT TO REMAIN.
9 EXISTING AIR DEVICE TO REMAIN.
10 EXISTING EXHAUST HOOD TO REMAIN.
11 REMOVE EXISTING CONVECTOR CABINET FOR REPLACEMENT IN NEW WORK - PIPING,SPECIALTIES, AND HEATING COIL TO REMAIN.
12 CAREFULLY REMOVE AIR DEVICE. CLEAN AND STORE AIR DEVICE FOR REINSTALLATIONIN NEW WORK.
13 EXISTING DUAL DUCT AIR TERMINAL UNIT TO REMAIN. BALANCE TO CFM INDICATED ONDUAL DUCT AIR TERMINAL UNITS SCHEDULE ON SHEET M0.2.
14. REMOVE EXISTING SIDEWALL EXHAUST BOTTOM REGISTER, CAP DUCT, AND SEALAIRTIGHT FOR INSTALLATION OF BLANK-OFF PANEL IN NEW WORK.
15. REMOVE EXISTING THERMOSTAT AND ASSOCIATED CONTROL WIRING, ETC. PATCHWALL TO MATCH EXISTING.
16. CAREFULLY REMOVE EXISTING THERMOSTAT AND ASSOCIATED CONTROL WIRING FORREINSTALLATION IN NEW WORK. PATCH WALL TO MATCH EXISTING.
PLAN NOTES
SCALE: 1/4" = 1'-0"
SECOND FLOOR PLAN
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
T
T T T
T
T
TT
T T
T
T
T
T
T
T
T
T
T T
T
T
1 2 3 4 5 6 7 8 9
A
B
C
D
CORRIDORC-2-2
LAB209
OFFICE209A
LAB210OFFICE
202
OFFICE203
OFFICE204
OFFICE206
OFFICE205
STORAGE207A
ELECTRIC208
STORAGE207
OFFICE201
CLOSET201A
CORRIDORC-2-3
CORRIDORC-2-1
CORRIDORC-2-4
SpaceC-2-5
SpaceC-2-6
SpaceC-2-7
SpaceC-2-8
SpaceC-2-9
SpaceC-2-10
Surgery210B
Scrub210C Space
C-2-13
SpaceC-2-14
SpaceC-2-15
1 1
1
3
3 3 3 3 3 3
3
333363
74
4 4
4
4
4
4
44
42-01
2-02
2-05
2-06
2-07
2-08
2-09
2-10
2-11
2-12
2-042-03
2-13
2-14
2-17
2-18
2-19 2-21
2-22
2-23
2-24
2
22
10x1
08ø
8ø6ø6ø
10øCD1
240 CFM
24x24165 CFM
CR1
10ø
10ø
24x24160 CFM
CR16ø
CD2
110 CFM
14øCD1
555 CFM
10øCD1
240 CFM
24x24165 CFM
CR1
8øCD1
165 CFM
10x1
0
12x8
8x8
24x24160 CFM
CR1
14ø
12ø
18ø
14ø
20ø
16ø 18ø
22ø
1
5
5
5
3
1
8
10
9
5
5
5
8
8
1
8
12x8100 CFM
TR1
1 1 1 1 1 1
1
1
11111
8x6
HWRHWS
HW
RH
WR
HW
S
HWRHWS
HW
SH
WR
HW
S
2-15
12x8240 CFM
TR212x8
240 CFM
TR2
12x8
8'-4" 8'-4"
12x8
12x8235 CFM
TR2
8'-4"
10x1
0
R
7
12
7
9
7
9
7
10
7
9
7
9
7
9 7
CD1 8ø
CD1 8ø
-100
205-
165-165-
1
2
-160
10'-6"
235-
160-
1
1
11
2
1
1
CD1 8ø
12x1
0
15-CONV1
8" DIA.
8" DIA.
8" DIA.
8" DIA.
8" DIA.8" DIA.
8" DIA.
8" DIA.
205-
10x8
6øCD1
70 CFM
2-01
17
2-03
17
17
2-05
2-02 2-06
17
17
172-13
2-14
2-15
1717 17
17
12
14
15
1515
14
14
1513
13
13
16
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 7
:57:
15 A
M
12/1
9/20
14 7
:57:
15 A
M
M2.1DRVWPCW
SECOND FLOOR PLAN - NEW WORK
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
A REFER TO SHEET M0.1 FOR LEGEND, ABBREVIATIONS, AND ADDITIONALGENERAL NOTES.
B EXISTING EXHAUST DUCT RISERS ARE CONSTRUCTED WITH MINIMUM 22"STEEL SUBDUCTS CARRIED UP INSIDE THE RISER FROM EACH INLET.THEREFORE, PER NFPA 90A, FIRE DAMPERS ARE NOT REQUIRED AT DUCTSPENETRATING THE SHAFT WALL.
GENERAL NOTES
1 EXISTING DUCTWORK TO REMAIN.
2 EXISTING PIPING TO REMAIN.
3 EXISTING HEATING HOT WATER CONVECTOR TO REMAIN.
4 EXISTING AIR TERMINAL UNIT TO REMAIN.
5 EXISTING AIR DEVICE TO REMAIN.
6 INSTALL NEW CABINET ON EXISTING HEATING HOT WATER CONVECTOR - PIPING,SPECIALTIES, AND HEATING COIL TO REMAIN.
7 EXISTING DUAL DUCT AIR TERMINAL UNIT TO REMAIN. BALANCE TO SCHEDULEDCFM. REFER TO DUAL DUCT AIR TERMINAL UNITS SCHEDULE ON SHEET M0.2.
8 REINSTALL EXISTING AIR DEVICE ASSOCIATED WITH EXISTING AIR TERMINAL UNIT.PROVIDE NEW BRANCH DUCTWORK AS INDICATED.
9 REINSTALL EXISTING AIR DEVICE ASSOCIATED WITH EXISTING AIR TERMINAL UNIT.BALANCE TO INDICATED CFM.
10 EXISTING AIR DEVICE TO REMAIN. BALANCE TO INDICATED CFM.
11 EXISTING EXHAUST HOOD TO REMAIN.
12 INSTALL NEW THERMOSTAT AND ASSOCIATED CONTROL WIRING FOR INDICATEDDUAL DUCT AIR TERMINAL UNIT IN THIS LOCATION.
13. PROVIDE INSULATED SHEETMETAL CAP. SEAL AIR TIGHT.
14. CONNECT NEW EXHAUST DUCT TO EXISTING OPENING ABOVE CEILING.
15. PROVIDE PAINT GRIP GALVANIZED WALL COVER PLATE ON LOWER SHAFT OPENING.PAINT TO MATCH WALL FINISH.
16. TRANSITION DUCT TO FULL SIZE OF EXHAUST HOOD CONNECTION. INSTALL PERMANUFACTURER'S RECOMMENDATIONS.
17. REINSTALL THERMOSTAT AND CONTROL WIRING ASSOCIATED WITH EXISTING DUALDUCT AIR TERMINAL UNIT IN THIS LOCATION.
18. INSTALL NEW THERMOSTAT AND ASSOCIATED CONTROL WIRING FOR INDICATEDDUAL DUCT AIR TERMINAL UNIT IN THIS LOCATION.
PLAN NOTES
SCALE: 1/4" = 1'-0"
SECOND FLOOR PLAN
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
LUMINAIRE SYMBOLS
LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOWER CASE LETTER DENOTES SWITCHINGARRANGEMENT.
LIGHTING FIXTURE ON NIGHT LIGHT OR EMERGENCY CIRCUIT.
EXIT LIGHTING FIXTURE, ARROWS AS INDICATED.
Aa
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUSWHERE REQUIRED.
ELECTRICAL CONNECTION.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).
20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).
SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.
20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERWISE) TWO GANG ASSEMBLY.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTEDOTHERWISE).
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERWISE) WITHSTANDARD COVER, VERTICAL MOUNT.
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MHUNLESS NOTED OTHERWISE), WITH STANDARD COVER, VERTICAL MOUNT.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, ON EMERGENCY POWER (18" MH UNLESS NOTED OTHERWISE).
JUNCTION BOX. SUBSCRIPT "HD" INDICATES ELECTRIC AIR HAND DRYER.
SINGLE POLE SWITCH (46" MH UNLESS NOTED OTHERWISE).
TWO POLE WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
THREE-WAY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
FOUR-WAY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
SWITCH WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERWISE).
KEY OPERATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
LED 0-10V DIMMER SWITCH (46" MH UNLESS OTHERWISE NOTED). SWITCH AND DOWNLIGHT MUST BE COMPATIBLEFOR 1% DIMMING. PROVIDE STAINLESS STEEL COVERPLATE AND TAMPERPROOF SCREWS.
DIGITAL TIMER WALL SWITCH. REFER TO FLOOR PLANS FOR DETAILS.
FLUSH FRACTIONAL HORSEPOWER MOTOR STARTER WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESSNOTED OTHERWISE).
HP RATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
DISCONNECT SWITCH.
MOTOR STARTER.
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.
ELECTRIC MOTOR.
ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.
PULL BOX.
LINE VOLTAGE THERMOSTAT.
UNIT HEATER.
FAN COIL.
ELECTRIC BASEBOARD HEATER.
AIR CONDITIONER.
CONDENSING UNIT.
UNIT VENTILATOR.
PHOTOELECTRIC SENSOR.
LIGHTING CONTACTOR.
CEILING MOUNTED OCCUPANCY SENSOR.
CEILING MOUNTED DAYLIGHT SENSOR.
OCCUPANCY SENSOR POWER PACK.
3
3
GF
WP
WP/GF
EM
JHD
2
3
4
P
K
DM
DT
H
UH
FC
AC
CU
UV
OS
DS
OP
PC
T
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERWISE).
M
LC
P/B
INTERCOM SYSTEM DESK MOUNTED MASTER CONTROL STATION. SUBSCRIPT "W" INDICATES WALL MOUNT (46" MHUNLESS NOTED OTHERWISE).
INTERCOM STAFF STATION (46" MH UNLESS NOTED OTHERWISE).
INTERCOM HORN TYPE SPEAKER (84" MH UNLESS NOTED OTHERWISE).
INTERCOM SPEAKER FLUSH MOUNT IN CEILING.
I
M
H
S
DUCT HEATER.HDH
HEB
LOW-VOLTAGE MOMENTARY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).L
FIRE ALARM SYMBOLS
FIRE ALARM BELL & SIGNAL LIGHT (80" AFF), (# WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # ISNOT SHOWN, THE STROBE SHALL BE RATED 75 CANDELA.
FIRE ALARM SPEAKER & SIGNAL LIGHT (80" AFF), (# WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A #IS NOT SHOWN, THE STROBE SHALL BE RATED 75 CANDELA.
FIRE ALARM CHIME & SIGNAL LIGHT (80" AFF), (# WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # ISNOT SHOWN, THE STROBE SHALL BE RATED 75 CANDELA.
FIRE ALARM HORN & SIGNAL LIGHT (80" AFF), (# WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # ISNOT SHOWN, THE STROBE SHALL BE RATED 75 CANDELA.
FIRE ALARM SIGNALING LIGHT (80" AFF), (# WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOTSHOWN, THE STROBE SHALL BE RATED 75 CANDELA.
FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "K" INDICATES KEY OPERATED.
CEILING MOUNTED SMOKE DETECTOR.
CEILING MOUNTED HEAT DETECTOR.
DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
ELECTRIC RELEASE DOOR CLOSER.
ELECTRO-MAGNETIC DOOR HOLDER.
WATER FLOW SWITCH.
VALVE SUPERVISORY SWITCH.
DUCT MOUNTED DETECTOR REMOTE TEST STATION AND ALARM INDICATOR LIGHT. SUBSCRIPT "W" INDICATES WALLMOUNTED.
SMOKE DAMPER.
F15
F15
F15
F15
15
SF
CEILING MOUNTED FIRE ALARM SPEAKER.
KF
S
H
C
D
FS
V
RW
SD
ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.
KNOX BOX.
AMC/I
K
FIRE ALARM CONTROL PANEL.
H
SS/R
S/R
FACP
1
E2
B
E2DETAIL: B = DETAIL DESIGNATION
E2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION E2 = SHEET WHERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
WIRE & CONDUIT IN WALL OR ABOVE CEILING.
WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.
EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S)DENOTES CIRCUIT(S).
LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
CONDUIT FOR DATA CIRCUITRY.DAT
WIRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA
EXISTING WIRE & CONDUIT TO REMAIN.EX
CONDUIT TO BE REMOVED.
X - 1,2
WIRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM
3
3
ABBREVIATIONSAAP - AREA ALARM PANEL - MEDICAL GASACC - ACCESSADJ - ADJUSTABLEAF - ARC FAULT CIRCUIT INTERRUPTERAFCI - ARC FAULT CIRCUIT INTERRUPTERAFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEMAFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEMALT - ALTERNATEAP - ACCESS PANELAPPROX - APPROXIMATEARCH - ARCHITECT OR ARCHITECTURALASSY - ASSEMBLYATS - AUTOMATIC TRANSFER SWITCH
BLDG - BUILDINGBOE - BOTTOM OF EQUIPMENTBOT - BOTTOMBTWN - BETWEEN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLEDCKT - CIRCUITCLG - CEILINGCMU - CONCRETE MASONRY UNITCONN - CONNECT OR CONNECTIONCONTR - CONTRACTORCORR - CORRIDORCTR - CENTER
D - DEPTHDET - DETAILDIA - DIAMETERDIM - DIMENSIONDIV - DIVISIONDN - DOWNDWG - DRAWING
EA - EACHEC - ELECTRICAL CONTRACTOR (DIVISION 26)EJ - EXPANSION JOINTELEC - ELECTRICALELEV - ELEVATION OR ELEVATOREM - EMERGENCYEQ - EQUALEQS - EQUIPMENT SUPPLIEREQUIP - EQUIPMENTETR - EXISTING TO REMAINEX - EXISTINGEX/R - EXISTING TO BE RELOCATEDEXP - EXPANSIONEXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENTFF - FINISHED FLOOR ELEVATIONFLR - FLOORFSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)FT - FEETFTG - FOOTING
GC - GENERAL CONTRACTORGF - GROUND FAULT CIRCUIT INTERRUPTERGFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT
FURNISHED CONTRACTOR INSTALLEDGFFT - GROUND FAULT FEED THRU
HC - HVAC CONTRACTOR (DIVISION 23)HP - HORSE POWER OR HIGH POINTHVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETERIN - INCHES
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTHLBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)MAX - MAXIMUMMEZZ - MEZZANINEMFR - MANUFACTURERMH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEMMIN - MINIMUM OR MINUTEMISC - MISCELLANEOUSMTD - MOUNTEDMTG - MOUNTING
NIC - NOT IN CONTRACTNOM - NOMINALNTS - NOT TO SCALE
OD - OUTSIDE DIAMETEROFCI - OWNER FURNISHED CONTRACTOR INSTALLEDOFOI - OWNER FURNISHED OWNER INSTALLED
PC - PLUMBING CONTRACTOR (DIVISION 22)PLBG - PLUMBING
RAD - RADIUSREC - RECESSEDREQD - REQUIREDRI - ROUGH-IN
S - SURFACE MOUNTEDSC - SECURITY CONTRACTORSCH - SCHEDULESHT - SHEETSMS - SECURITY MANAGEMENT SYSTEMSPEC - SPECIFICATIONSSQ - SQUARESS - STAINLESS STEELSTD - STANDARDSTRUC - STRUCTURAL OR STRUCTURESUC - SITE UTILITY CONTRACTOR
TC - TECHNOLOGY CONTRACTORTEMP - TEMPERATURETOE - TOP OF EQUIPMENTTYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VFD - VARIABLE FREQUENCY DRIVEVOL - VOLUME
W/ - WITHW/0 - WITHOUTWP - WEATHERPROOF
ZVC - ZONE VALVE CABINET
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOTNECESSARILY BE USED ON THIS PROJECT.
CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
4"
4"
4"
GENERAL NOTESA. ALL ELECTRICAL SPLICES FOR WIRE SIZES 6 AWG AND LARGER SHALL BE HYDRAULIC CRIMP TYPE.B. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.C. SITE VISIT(S) SHALL BE AS OUTLINED IN PROJECT SPECIFICATIONS.D. ANY ASBESTOS WORK PERFORMED AS PART OF THIS PROJECT SHALL BE COMPLETED PRIOR TO STARTING ANY OTHER PROJECT SITE
WORK.E. THE CONTRACTORS SHALL REFER TO ALL SPECIFICATION SECTIONS, AND ELECTRICAL DRAWINGS FOR DETAILS OF BUILDING
CONSTRUCTION TO ENSURE SPACE AND SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS DRAWINGS COMPRISING THESET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT ALL TIMES. EACH CONTRACTOR SHOULD REFER TO THE GENERALREQUIREMENTS OF THE CONTRACT. THESE NOTES AND SYMBOLS SET DOWN ON THE DRAWINGS ARE FOR THE GUIDANCE OF ALL TRADESINVOLVED IN THE PROJECT AND MUST BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES OCCUR, CONTACT THE CORTHRU THE CONTRACTING OFFICER FOR CLARIFICATION BEFORE PROCEEDING.
F. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, THE CONTRACTOR WILL BE SOLELY AND COMPLETELYRESPONSIBLE FOR THE CONDITIONS ON THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OFTHE WORK. THIS WILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. SEE SPECIFICATIONS FOR MORESPECIFIC DETAILS ON RESPONSIBILITIES.
G. ALL WORK MUST BE COORDINATED WITH THE COR TO MAINTAIN OPERATION OF THE EXISTING FACILITY.H. FIELD VERIFY DIMENSIONAL INFORMATION PRIOR TO ORDERING EQUIPMENT. DO NOT SCALE DRAWINGS.I. DIMENSIONS ARE TYPICALLY INDICATED TO THE FINISHED FACE OF WALLS OR PARTITIONS AND CENTER LINES OF COLUMNS UNLESS
OTHERWISE INDICATED.J. TITLES, CAPTIONS, HEADINGS, ETC. ARE INTENDED FOR GENERAL REFERENCE AND ARE NOT INTENDED TO LIMIT THE WORK REQUIRED IN
ANY WAY.K. EACH CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHERS. HE SHALL KEEP HIMSELF INFORMED OF THE PROGRESS
AND DETAIL DEVELOPMENT OF THE WORK OF OTHERS AND SHALL BE RESPONSIBLE FOR COORDINATING AND EXPEDITING HIS WORK WITHOTHERS SO THAT THE PROGRESS OF THE TOTAL WORK SHALL BE KEPT ON SCHEDULE.
L. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL GOVERNING CODES AND STANDARDS.M. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON AVAILABLE DRAWING INFORMATION AND MAY BE AT VARIANCE WITH ACTUAL
WORK IN PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL CONDITIONS AFFECTINGTHE EXECUTION OF THE WORK. ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE CONTRACTDOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER INWRITING FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.
N. EACH CONTRACTOR AND/OR TRADE FITTING OR PLACING HIS WORK INTO OR ON THE WORK OF OTHERS DOES SO WITH THEUNDERSTANDING THAT THE INSTALLATION OF HIS WORK CONSTITUTES HIS ACCEPTANCE OF THE SUITABILITY OF THE WORK IN PLACE. IFTHE WORK OF OTHERS IS NOT ACCEPTABLE, HE SHALL NOTIFY THE COR AND SUCH WORK SHALL BE CORRECTED. ANY NEW WORKINSTALLED IN UNSUITABLE EXISTING WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE INSTALLING THE NEW WORK.NO CLAIMS FOR ADDITIONAL COMPENSATION FOR CORRECTING WORK INSTALLED IN UNSUITABLE EXISTING CONDITIONS WILL BECONSIDERED.
O. ANY STRUCTURAL, MECHANICAL, ELECTRICAL, FIRE PROTECTION, OR PLUMBING INFORMATION INDICATED ON THE ARCHITECTURALDRAWINGS IS FOR REFERENCE PURPOSES ONLY UNLESS OTHERWISE INDICATED.
P. IF, IN THE PERFORMANCE OF THE ELECTRICAL WORK, MATERIALS ARE OBSERVED WHICH ARE SUSPECTED TO CONTAIN ASBESTOS, THEELECTRICAL CONTRACTOR SHALL IMMEDIATELY INFORM THE COR. WORK THAT WOULD EXPOSE WORKERS TO THE INHALATION OFASBESTOS PARTICLES SHALL BE TERMINATED. WORK MAY BE RESUMED ONLY AFTER A DETERMINATION HAS BEEN MADE AND UNSAFEMATERIALS HAVE BEEN REMOVED OR ENCAPSULATED AND THE AREA DECLARED SAFE.
Q. PROPER PERSONNEL PROTECTION EQUIPMENT SHALL BE WORN PER OSHA AND VA REQUIREMENTS WITH VAMC COR AND SAFETYOFFICER.
R. FIRESTOPPING ASSEMBLIES SHALL BE PROVIDED AT PENETRATIONS OF CONDUITS AND OTHER ELECTRICAL ITEMS THRU FIRE RATEDFLOORS, FIRE RATED WALLS AND PARTITIONS AND FIRE RATED SHAFT WALLS AND PARTITIONS. ALL PENETRATIONS THROUGH 0-HOURRATED WALLS SHALL BE CAULKED SMOKE-TIGHT. REFER TO SPECIFICATION SECTION 07 84 00.
S. REMOVE EXISTING ELECTRICAL SYSTEMS WHICH ARE MADE SUPERFLUOUS WHEN NEW SYSTEMS ARE INSTALLED INCLUDING ALLASSOCIATED WIRING AND DEVICES. PROVIDE BLANK STAINLESS STEEL COVERPLATES PROPERLY SIZED FOR EXISTING BACKBOX ANDWALL OPENING FOR ALL RECESSED WALL MOUNTED DEVICES REMOVED. ALL ABANDON RACEWAY, CONDUIT AND BOXES SHALL BEREMOVED.
T. REFER TO SPECIFICATION SECTION 01 00 00 GENERAL REQUIREMENTS FOR STATEMENT OF BID ITEM(S) AND DEDUCTIVE ALTERNATES.U. ON EXISTING FLOORS WITH NO ARCHITECTURAL SCOPE, CONTRACTOR IS REQUIRED TO PROVIDE FLOOR AND WALL PROTECTION (AS
NEEDED) AND REPLACE ANY DAMAGED CEILING TILES WITH NEW. RETURN AREA BACK TO ORIGINAL CONDITIONS UPON COMPLETION OFWORK.
TECHNOLOGY SYMBOLS
P WALL MOUNTED PHONE OUTLET (46" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT TO ABOVE ACCESSIBLECEILING, JACKS, FACEPLATE AND CABLE.
CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU WALL (1-2" SLEEVE UNLESS NOTED OTHERWISE).
DWALL MOUNTED VOICE/DATA OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT(S) TO ABOVECORRIDOR CEILING, JACKS, FACEPLATE AND CABLE. REFER TO FACEPLATE DETAILS.
APEXISTING CEILING MOUNTED WIRELESS ACCESS POINT AND OUTLET. REMOVE AP AND CABLING BACK TO EXISTINGSIGNALS CLOSET. RE-INSTALL AP AND PROVIDE NEW 1-DATA DROP WITH 20' MANAGED SLACK COIL UTILIZING J-HOOKS ABOVE CEILINGTO NEW SIGNALS CLOSET. FINAL LCOATIONS OF APS TO BE DETERMINED AFTERPERFORMANCE OF RF SITE SURVEY.
SCNEW 2X2 CEILING MOUNTED VALCOM PAGING/INTERCOM SYSTEM SPEAKER. SUBSCRIPT "EX/R" INDICATES EXISTINGSPEAKER TO BE TEMPORARILY SUPPORTED DURNING DEMOLITION AND RE-INSTALLED IN NEW CEILING AT SAMELOCATION.
EX/R
EX/R
EXHAUST FANEXH
J WALL MOUNTED DATA OUTLET (18" MH UNLESS NOTED OTHERWISE) FOR RFID PORTAL. BOX WITH CONDUIT(S) TO ABOVECORRIDOR CEILING, JACKS, FACEPLATE AND CABLE. COORDINATE LOCATION AND MOUNTING HEIGHT WITH VA PROVIDEDPORTAL.
FAEP FIRE ALARM EXTENDER PANEL (NAC)
VARIABLE FREQUENCY DRIVE.
WALL MOUNTED FIRE ALARM SPEAKER / HORN.SF
WIREMOLD WITH SIMPLEX RECEPTACLES
APNEW CEILING MOUNTED WIRELESS ACCESS POINT AND OUTLET. INSTALL AP (FURNISHED BY VA) AND PROVIDE NEW 1-DATA DROP WITH 20' MANAGED SLACK COIL UTILIZING J-HOOKS ABOVE CEILINGTO NEW SIGNALS CLOSET. FINALLCOATIONS OF APS TO BE DETERMINED AFTER PERFORMANCE OF RF SITE SURVEY.
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 9
:02:
49 A
M
12/1
9/20
14 9
:02:
49 A
M
E0.1JRSMSG
LEGEND AND SYMBOLS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
INDEX OF DRAWINGSSheet Number Description
T000 All SchedulesE0.1 LEGEND AND SYMBOLSE0.2 SINGLE LINE DIAGRAME0.3 PANELBOARD SCHEDULESE0.4 LIGHTING DETAILSE0.5 TECHNOLOGY SYMBOLS AND DETAILSE0.6 EXISTING SIGNALS CLOSET DETAILSE1.1 BASEMENT FLOOR PLAN - REMOVALSE1.2 SECOND FLOOR PLAN - REMOVALSE2.1 SECOND FLOOR PLAN - NEW WORK - LIGHTINGE2.2 SECOND FLOOR PLAN - NEW WORK - POWERE2.3 SECOND FLOOR - NEW WORK - SIGNALS
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
EN
E NE NE N
SWBDMETERING
FIRST FLOOR
SECOND FLOOR
FIREPUMPCONTR.
20HPF.P. S.P.
25HPELEV.
W.H.PNL
BA
LPB
2M
THIRD FLOOR
FOURTH FLOOR
ROOF
2O 2P 2Q 2R 2S 2T 2U 2V 2W 2X
1A
2A 2B 2C 2D 2E 2F 2G 2H 2I 2J 2K 2L
LP2
3M 3N 3OLP3
4M 4N 4OLP4
2N
WEST BUS DUCT EAST BUS DUCT
TO US-1A, BLDG 1
15E1
15EMB
100 100 100 100 150 150
16MDP
400
ELEV.CU1/2CU3/4
208Y/120V-3PH-4W
A2
A1 B
1-#1
/0
1-#1
/01-
#1/0
1G
TO 1E3 (BLDG 1, B013)
25HPROOFEF-5
400A
1-500 KCMIL
(OPTIONAL STANDBY)16ATS1400A/4P
(OPTIONAL STANDBY)15ATS 2200A/3P
(EMERGENCY)15ATS 1100A/4P
(OPTIONAL STANDBY)15ATS 3400A/4P
SPD
15OSDP1208Y/120V-3PH-4W
EX.
EX.EX.
EX
EX 150S1
EX EX EX
EXEXEX EX
1-#6
1-#1
15MDP208Y/120V-3PH-4W
1234567891011121314151617
654321
SPD
EM PNL
EX
EXISTLOAD
300A 125A 300A
TO"ESB"
BLDG. 1 FEEDER TAPPINGWIREWAY
SPAR
E
18
400A/3PF.P.DISCONNECT
TAP
BUS TAP BOX BUS TAP BOX
TO "ESB"BLDG 1
1-#4/0
EX
EX
EX
EX
EX
EX
EX EX
1
2M 2O2N
27
15OS2
15E2
2
3
LP1
BASEMENT FLOORBASEMENT FLOOR
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
ROOF
3
4
6
1
2
5
3
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 9
:02:
51 A
M
12/1
9/20
14 9
:02:
51 A
M
E0.2JRSMSG
SINGLE LINE DIAGRAM
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
SCALE: NONE
SINGLE LINE DIAGRAM1
1. REMOVE ANTIQUATED PANELBOARD INTERIOR (COVER,BUSSING, BREAKERS, ETC.) AND REPLACEWITH NEW. PROVIDE NEW NAMEPLATE. CLEAN AND REMOVE ANY RUST/CORROSION FROM PANELTUB. RETERMINATE ALL EXISTING BRANCH CIRCUITS AND FEEDERS TO REMAIN TO NEW INTERIOR.EXISTING CIRCUIT NUMBERS SHALL MATCH NEW. INTERCEPT AND EXTEND CONDUCTORS ASREQUIRED TO MAKE CONNECTION TO NEW BREAKERS/LUGS. PRIOR TO SUBMITTING SHOPDRAWINGS AND AGAIN BEFORE ORDERING NEW PANEL INTERIOR AND CUSTOM COVER, REMOVEEXISTING PANELBOARD COVER, FIELD MEASURE EXACT TUB/FEEDER DIMENSIONS, AND VERIFYBREAKERS. RE-INSTALL COVER WHEN FINISHED MEASURING. PROVIDE CUSTOM INTERIOR ANDCOVER TO FIT TUB. NO ALLOWANCES WILL BE MADE FOR FAILURE TO DO SO. PANEL SHALL BERETRO-FITTED OUTSIDE OF NORMAL WORKING HOURS AND COMPLETED WITH A MAXIMUMOUTAGE OF 4 HOURS.
2. REFER TO PANEL SCHEDULE FOR FEEDER SIZE.3. UTILIZE SPARE 100A/3P BREAKER IN EXISTING PANEL (PROVIDED UNDER "CORRECT ELECTRICAL
FCA DEFICIENCIES PROJECT).4. FAULT CURRENT VALUE KNOWN FROM VA PROVIDED 2009 SHORT CIRCUIT STUDY.
PLAN NOTES
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
A. REFER TO SEQUENCE OF CONSTRUCTION NOTES FOR PHASING / TEMPORARYREQUIREMENTS.
B. FAULT CURRENT VALUES SHOWN FROM VA PROVIDED SHORT CIRCUIT STUDY. VERIFYALL PRIOR TO ORDERING.
C. REMOVE EXISTING AND PROVIDE NEW PHENOLIC NAMEPLATES (PER SPECIFICATIONS)FOR ALL EQUIPMENT SHOWN ON THIS SINGLE LINE DIAGRAM.
D. LIGHT LINEWEIGHT INDICATES EXISTING EQUIPMENT. DARK LINEWEIGHT INDICATESNEW EQUIPMENT. DARK DASHED LINEWEIGHT INDICATES EQUIPMENT TO BEREMOVED.
GENERAL NOTES
FAULT CURRENT
REF.POINT DESCRIPTION
AVAILABLESHORT
CIRCUIT AMPS
1 15MDP 15300 A2 LPB 6374 A3 2M/2O 6374 A4 2N 6100 A5 15OSDP1 14199 A6 15OS2 2524 A
4
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 9
:02:
53 A
M
12/1
9/20
14 9
:02:
53 A
M
E0.3JRSMSG
PANELBOARD SCHEDULES
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
25.12 kVATOTAL CONNECTED ESTIMATED DEMAND
NOTES: PANEL PROVIDED UNDER "CORRECT ELECTRICAL FCA DEFICIENCIES" PROJECT.
20 Space 0.00 kVA -- -- -- -- -- -- -- -- --
19 Space 0.00 kVA -- -- -- -- -- -- -- -- --
18 Spare 0.00 kVA -- 3 100 A -- -- -- -- -- --
17 2M / 2O 12.60 kVA 100 A 3 100 A TM 4 2 8 1.25" --
16 2N 6.12 kVA 100 A 3 100 A TM 4 2 8 1.25" --
15 4N 0.00 kVA 100 A 3 100 A TM -- -- -- -- --
14 3M / 3O 0.00 kVA 100 A 3 100 A TM -- -- -- -- --
13 3N 0.00 kVA 100 A 3 100 A TM -- -- -- -- --
12 Spare 0.00 kVA -- 3 300 A -- -- -- -- -- --
11 Spare 0.00 kVA -- 3 300 A -- -- -- -- -- --
10 BA 0.00 kVA 225 A 3 225 A TM -- -- -- -- --
9 ROOF EF-5 0.00 kVA 125 A 3 125 A TM -- -- -- -- --
8 LPB / LP2 / LP... 0.00 kVA 100 A 3 100 A TM -- -- -- -- --
7 15ATS3 /... 0.00 kVA 300 A 3 300 A TM -- -- -- -- --
6 15ATS1 / 15EMB 0.00 kVA 100 A 3 100 A TM -- -- -- -- --
5 15ATS2 / ELEV. 0.00 kVA 125 A 3 125 A TM -- -- -- -- --
4 16ATS1 / 16MDP 0.00 kVA 300 A 3 300 A TM -- -- -- -- --
3 SWBD... 0.00 kVA -- -- -- -- -- -- -- -- --
2 SPD 0.00 kVA 60 A 3 60 A TM -- -- -- -- --
1 MAIN BREAKER 0.00 kVA 800 A 3 800 A LSI -- -- -- -- --CKT
CIRCUITDESCRIPTION
APPROX.CONNECTED
LOADFRAME
SIZE POLESTRIP
SETTINGBREAKER
TYPENUMBER OF
CONDUCTORSWIRESIZE
GROUNDSIZE
CONDUITSIZE
SEENOTE
Feeder Size: 2 SETS OF (4-500 KCMIL, #1/0 GRD. IN 4"C) Spec. Ref. #: 26 24 13Voltage: 120/208 Wye-3PH-4W Mains Rating: 800 A
Supply From: Enclosure: Mains Type: MCBLocation: TRANSFORMER VAULT B02 Mounting: A.I.C. Rating:
DISTRIBUTION PANEL: 15MDP
6.4 kVA 6.56 kVA (18 A)TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 2.56 kVA 2.13 kVA 1.71 kVA
29 Space -- -- 0 VA 0 VA 1 20 A Spare 30
27 Space -- -- 0 VA 0 VA 1 20 A Spare 28
25 Space -- -- 0 VA 0 VA 1 20 A Spare 26
23 Space -- -- 0 VA 0 VA 1 20 A Spare 24
21 Space -- -- 0 VA 90 VA -- -- -- 22
19 Space -- -- 0 VA 90 VA 2 20 A Receptacle 20
17 Receptacle 20 A 1 180 VA 90 VA -- -- -- 18
15 Lighting 20 A 1 512 VA 90 VA 2 20 A Receptacle 16
13 Receptacle 20 A 1 720 VA 360 VA 1 20 A Receptacle 14
11 Receptacle 20 A 1 180 VA 180 VA 1 20 A Receptacle 12
9 Receptacle 20 A 1 360 VA 360 VA 1 20 A Receptacle 10
7 Receptacle LAB 210 20 A 1 720 VA 360 VA 1 20 A Receptacle 8
5 Receptacle LAB 210 20 A 1 360 VA 720 VA 1 20 A Receptacle LAB 209 6
3 Receptacle 20 A 1 360 VA 360 VA 1 20 A Receptacle LAB 209 4
1 Receptacle 20 A 1 180 VA 128 VA 1 20 A Lighting 2CKT Circuit Description Trip Poles
A B CPoles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 ASupply From: 15OSDP1 Enclosure: Type 1 Mains Type: MCB
Location: ELECTRIC 208 Mounting: Surface A.I.C. Rating:Panel: 15OS2
3.06 kVA 3.06 kVA (8 A)TOTAL CONNECTED ESTIMATED DEMAND
Notes: PROVIDE FEED-THROUGH LUGS.
Total Load: 1.44 kVA 1.08 kVA 0.54 kVA
29 Space -- -- 0 VA 0 VA -- -- Space 30
27 Space -- -- 0 VA 0 VA -- -- Space 28
25 Space -- -- 0 VA 0 VA -- -- Space 26
23 Space -- -- 0 VA 0 VA -- -- Space 24
21 Space -- -- 0 VA 0 VA 1 20 A Spare 22
19 Space -- -- 0 VA 0 VA 1 20 A Spare 20
17 Space -- -- 0 VA 0 VA 1 20 A Spare 18
15 Space -- -- 0 VA 0 VA 1 20 A Spare 16
13 Space -- -- 0 VA 0 VA 1 20 A Spare 14
11 Space -- -- 0 VA 0 VA 1 20 A Spare 12
9 Space -- -- 0 VA 180 VA 1 20 A Receptacle 10
7 Receptacle 20 A 1 360 VA 180 VA 1 20 A Receptacle 8
5 Receptacle 20 A 1 360 VA 180 VA 1 20 A Receptacle 6
3 Receptacle LAB 209 20 A 1 720 VA 180 VA 1 20 A Receptacle 4
1 Receptacle LAB 209 20 A 1 720 VA 180 VA 1 20 A Receptacle 2CKT Circuit Description Trip Poles
A B CPoles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 ASupply From: 15MDP Enclosure: Type 1 Mains Type: MCB
Location: ELECTRIC 208 Mounting: Surface A.I.C. Rating:Panel: 2M
6.12 kVA 6.12 kVA (17 A)TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 2.88 kVA 1.62 kVA 1.62 kVA
29 Space -- -- 0 VA 0 VA 1 20 A Spare 30
27 Space -- -- 0 VA 0 VA 1 20 A Spare 28
25 Space -- -- 0 VA 0 VA 1 20 A Spare 26
23 Space -- -- 0 VA 0 VA 1 20 A Spare 24
21 Space -- -- 0 VA 0 VA 1 20 A Spare 22
19 Space -- -- 0 VA 0 VA 1 20 A Spare 20
17 Space -- -- 0 VA 0 VA 1 20 A Spare 18
15 Space -- -- 0 VA 0 VA 1 20 A Spare 16
13 Receptacle 20 A 1 360 VA 0 VA 1 20 A Spare 14
11 Receptacle 20 A 1 360 VA 180 VA 1 20 A Receptacle 12
9 Receptacle 20 A 1 180 VA 720 VA 1 20 A Receptacle 10
7 Receptacle 20 A 1 900 VA 360 VA 1 20 A Receptacle 8
5 Receptacle 20 A 1 360 VA 720 VA 1 20 A Receptacle LAB 210 6
3 Receptacle 20 A 1 360 VA 360 VA 1 20 A Receptacle LAB 210 4
1 Receptacle 20 A 1 1080... 180 VA 1 20 A Receptacle 2CKT Circuit Description Trip Poles
A B CPoles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 ASupply From: 15MDP Enclosure: Type 1 Mains Type: MCB
Location: ELECTRIC 208 Mounting: Surface A.I.C. Rating:Panel: 2N
9.54 kVA 9.54 kVA (26 A)TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 3.78 kVA 3.96 kVA 1.80 kVA
29 Space -- -- 0 VA 0 VA -- -- Space 30
27 Space -- -- 0 VA 0 VA -- -- Space 28
25 Space -- -- 0 VA 0 VA -- -- Space 26
23 Space -- -- 0 VA 0 VA -- -- Space 24
21 Space -- -- 0 VA 0 VA -- -- Space 22
19 Space -- -- 0 VA 0 VA -- -- -- 20
17 Space -- -- 0 VA 0 VA -- -- -- 18
15 Space -- -- 0 VA 0 VA 3 20 A Spare 16
13 Space -- -- 0 VA 0 VA -- -- -- 14
11 Space -- -- 0 VA 0 VA 2 20 A Spare 12
9 Receptacle 20 A 1 180 VA 1260... 1 20 A Receptacle 10
7 Receptacle 20 A 1 180 VA 1260... 1 20 A Receptacle 8
5 Receptacle 20 A 1 540 VA 1260... 1 20 A Receptacle 6
3 Receptacle 20 A 1 1260... 1260... 1 20 A Receptacle 4
1 Receptacle 20 A 1 1080... 1260... 1 20 A Receptacle 2CKT Circuit Description Trip Poles
A B CPoles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 ASupply From: 15MDP Enclosure: Type 1 Mains Type: MCB
Location: ELECTRIC 208 Mounting: Surface A.I.C. Rating:Panel: 2O
6.40 kVATOTAL CONNECTED ESTIMATED DEMAND
NOTES: PANEL PROVIDED UNDER "CORRECT ELECTRICAL FCA DEFICIENCIES" PROJECT.
20
19
18
17
16
15
14
13
12
11
10
9
8
7 15OS2 6.40 kVA 100 A 3 100 A TM 4 2 8 1.25" --
6 1G / 2G 0.00 kVA 100 A 3 100 A TM -- -- -- -- --
5 PNL 1A 0.00 kVA 100 A 3 100 A TM -- -- -- -- --
4 WH PNL 0.00 kVA 100 A 3 100 A TM -- -- -- -- --
3 15OS1 0.00 kVA 150 A 3 150 A TM -- -- -- -- --
2 LP1 0.00 kVA 80 A 3 80 A TM -- -- -- -- --
1 SPD 0.00 kVA 30 A 3 30 A TM -- -- -- -- --CKT
CIRCUITDESCRIPTION
APPROX.CONNECTED
LOADFRAME
SIZE POLESTRIP
SETTINGBREAKER
TYPENUMBER OF
CONDUCTORSWIRESIZE
GROUNDSIZE
CONDUITSIZE
SEENOTE
Feeder Size: REFER TO 15MDP Spec. Ref. #: 26 24 16Voltage: 120/208 Wye-3PH-4W Mains Rating: 400 A
Supply From: 15MDP Enclosure: Mains Type: MLOLocation: TRANSFORMER VAULT B02 Mounting: A.I.C. Rating:
DISTRIBUTION PANEL: 15OSDP1
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
2.72 kVA 3.4 kVA (9 A)TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 1.25 kVA 1.02 kVA 0.45 kVA
27 Space -- -- 0 VA 0 VA -- -- Space 28
25 Space -- -- 0 VA 0 VA -- -- Space 26
23 Space -- -- 0 VA 0 VA -- -- Space 24
21 Space -- -- 0 VA 0 VA -- -- Space 22
19 Space -- -- 0 VA 0 VA -- -- Space 20
17 Space -- -- 0 VA 0 VA -- -- Space 18
15 Space -- -- 0 VA 0 VA -- -- Space 16
13 Space -- -- 0 VA 0 VA -- -- Space 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10
7 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 8
5 Spare 20 A 1 0 VA 448 VA 1 20 A Lighting 6
3 Lighting OFFICE 201 20 A 1 576 VA 448 VA 1 20 A Lighting LAB 210 4
1 Lighting OFFICE 201 20 A 1 672 VA 576 VA 1 20 A Lighting LAB 209 2CKT Circuit Description Trip Poles
A B CPoles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 ASupply From: Enclosure: Type 1 Mains Type: MLO
Location: CORRIDOR C-2-1 Mounting: Surface A.I.C. Rating:Panel: LP2
E E
E
SLIM WALL MOUNTE
EXIT SIGN
E
F2
X-1F-3 F-x
C-1
RECESSED FLUORESCENT FIXTURE RECESSED FLUORESCENT FIXTURE
FLUORESCENT INDUSTRIAL FIXTURE
SPECIFICATION GRADE RECESSED FLUORESCENT LIGHTING TROFFER WITH FLATLOW-BRIGHTNESS LENS PANEL, NOMINAL 2' X 4' IN SIZE AND APPROXIMATELY 4.25 INCHES DEEP.
HOUSING: DIE FORMED AND EMBOSSED CODE GAUGE STEEL. END CAPS HINGED AND SCREWEDTO HOUSING FOR RIGIDITY. DESIGNED FOR INSTALLATION IN CEILING TYPESHOWN ON ARCHITECTURAL DRAWINGS. INTEGRAL T-BAR CLIPS. HARDWAREFOR MINIMUM 4 POINTS OF SUPPORT. SEPARATE NON-CAPTIVE STUD FORFIXTURE GROUNDING.
REFLECTOR: HIGH REFLECTANCE BAKED WHITE ENAMEL AND SPECULAR SILVER INSERT.
FINISH: MULTI-STAGE PHOSPHATE BONDING TREATMENT AND HIGH REFLECTANCE BAKEDWHITE ENAMEL.
SHIELDING: 100% PRISMATIC VIRGIN ACRYLIC, PATTERN 12, .125" THICK (NOMINAL). FLUSH DOORWITH MITRED CORNERS, INCONSPICUOUS CAM ACTION LATCHES.
LAMPS: RAPID START 32W-T8 LAMPS, MIN CRI OF 85, 4100K.
BALLAST: HPF ELECTRONIC PROGRAMMED RAPID START STEP-DIMMING BALLAST, 0.88BF,120/277V.
VARIATIONS:
EF3a: SAME AS ABOVE EXCEPT 2'X2' IN SIZE WITH TWO 17W-T8 LAMPS.
SPECIFICATION GRADE RECESSED FLUORESCENT LIGHTING TROFFER WITH WHITE LOUVEREDDOOR, NOMINAL 2' X 4' IN SIZE AND APPROXIMATELY 4.5 INCHES DEEP.
HOUSING: DIE FORMED AND EMBOSSED CODE GAUGE STEEL. END CAPS HINGED AND SCREWEDTO HOUSING FOR RIGIDITY. DESIGNED FOR INSTALLATION IN CEILING TYPESHOWN ON ARCHITECTURAL DRAWINGS. INTEGRAL T-BAR CLIPS. HARDWAREFOR MINIMUM 4 POINTS OF SUPPORT. SEPARATE NON-CAPTIVE STUD FORFIXTURE GROUNDING.
OPTICS: RIBBED LOUVER WITH ARCHITECTURAL STYLING. S/MH 1.2, 89% EFFICIENCY MIN.
FINISH: MULTI-STAGE PHOSPHATE BONDING TREATMENT AND SOFT NON-GLARE HIGHREFLECTANCE POWDER COAT.
DOOR: FLUSH FRAME-LESS HINGED DOOR WITH INCONSPICUOUS CAM ACTION LATCHES.
LAMPS: TWO RAPID START 32W-T8 LAMPS, MIN CRI OF 85, 4100K.
BALLAST: HPF ELECTRONIC PROGRAMMED RAPID START STEP DIMMING , 0.88BF, 120/277V.
VARIATIONS:
EF1: AS LISTED ABOVE.
EF1a: SAME AS ABOVE EXCEPT 1'X4' IN SIZE WITH ONE T5HO LAMP.
EF1b: SAME AS ABOVE EXCEPT WITH STANDARD PROGRAMMED RAPID START BALLAST.
SPECIFICATION GRADE CHAIN HUNG INDUSTRIAL, NOMINAL 14" X 4' IN SIZE AND APPROXIMATELY6" DEEP.
HOUSING: CODE GAUGE STEEL HOUSING WITH LONGITUDINAL REINFORCING RIBS. SEPARATENON-CAPTIVE STUD FOR FIXTURE GROUNDING. DESIGNED FOR INDIVIDUAL ORCONTINUOUS ROW MOUNTING. SPRING LOADED TURRET LAMP HOLDERS. WIREGUARD.
REFLECTOR: DIE-EMBOSSED STEEL WITH TRANSVERSE RIBS FOR RIGIDITY. 10%-15%UPLIGHT APERTURES.
FINISH: MULTI-STAGE PHOSPHATE BONDING TREATMENT AND HIGH REFLECTANCE BAKEDENAMEL.
LAMPS: TWO RAPID START 32W-T8 LAMPS, MIN CRI OF 85, 4100K.
BALLAST: HPF ELECTRONIC PROGRAMMED RAPID START BALLAST, 0.88BF, 120/277V.
SPECIFICATION GRADE, WALL MOUNTED FIXTURE, NOMINAL 5"H x 4"D x 2' IN SIZE
HOUSING:
SHIELDING:
FINISH:
LAMPS: ONE RAPID START 17W-T8 LAMPS, MIN CRI OF 85, 4100K.
BALLAST: HPF ELECTRONIC PROGRAMMED RAPID START BALLAST, 0.88BF, 120/277V.
LOCATION: LOCATE OVER DOOR
HEAVY GAUGE STEEL HOUSING, DIE EMBOSSED FOR MAXIMUM RIGIDITY.PROVIDE WITH METAL END PIECES.
CLEAR ACRYLIC PRISMATIC DIFFUSER, FLAT BOTTOM WITH VERTICALSIDES. INJECTION MOLDED ENDS. 100% OPAL ACRYLIC EXTRUSION.
WHITE PAINTED. TREATED WITH 5-STAGE PHOSPHATE BONDING PROCESS.PAINT AFTER FABRICATION WITH MIN OF 90% REFLECTIVE GLOSS BAKEDENAMEL.
TYPE EX2 DENOTE DOUBLE FACED FIXTURES.
ARROWS WHERE SHOWN ON DRAWINGS AND
HINGED WITH ALUMINUM REINFORCED
AS INDICATED.
FURNISHED FIXTURES WITH DIRECTIONAL
WIRED FOR 120/277-VOLT OPERATION
NOTE:
RED L.E.D. 6" LETTERS
MULTIPLE L.E.D. LAMP ASSEMBLY WITHMINIMUM OF 20,000 HOURS LIFE.
MARINE GRADE VINYL CLAD ALUMINUM.
INSCRIPTION PANEL(S):
LAMPS:
FINISH COLOR:
DOOR FRAME:
BLACK
HOUSING AND CANOPY:
POLYCARBONATE SHIELD.
LOCATION: CEILING MOUNT WHERE SHOWN. WALL MOUNT AT 7'-6" AFFWHERE SHOWN UNLESS OTHERWISE NOTED.
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 9
:02:
55 A
M
12/1
9/20
14 9
:02:
55 A
M
E0.4JRSMSG
LIGHTING DETAILS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
4TH FLOOR -EXISTING CLOSET
12MM/6SM
SECOND FLOOR
SECOND FLOOR - EXISTING CLOSET
100PR.
12MM/6SM
THIRD FLOOR
100PR.
PREVIOUSPROJECT
3RD FLOOR EXISTING CLOSET
FOURTH FLOOR
PREVIOUSPROJECT
2
3
4
1
RISER DIAGRAM NOTES1. NEW WALL MOUNTED HINGED FRAMES FOR PATCH PANEL MOUNTING.2. EXISTING FIBER PANELS TO BE MAINTAINED.3. PROVIDE NEW WALL MOUNTED DATA STATION CABLING PATCH PANELS.4. RE-USE EXISTING WALL MOUNTED NETWORK SWITCHES (CISCO WS-C3750-48PS-S).5. EXISTING VOICE WALL FIELD TO BE MAINTAINED.6. EXISTING GROUND BAR TO BE MAINTAINED.
5
6
6
6
4TH FLOOR -EXISTING CLOSET
12MM/6SM
SECOND FLOOR
SECOND FLOOR - EXISTING CLOSET
100PR.
12MM/6SM
THIRD FLOOR
100PR.
PREVIOUSPROJECT
3RD FLOOR EXISTING CLOSET
FOURTH FLOOR
PREVIOUSPROJECT
RISER DIAGRAM NOTES1. EXISTING BACKBOARD MOUNTED FIBER PANELS TO BE MAINTAINED.2. REMOVE EXISTING DATA STATION PATCH PANELS AND CABLING.3. EXISTING WALL MOUNTED NETWORK SWITCHES TO BE RE-USED.4. EXISTING VOICE WALL FIELD TO BE MAINTAINED.
1
2
3
4
9
7
5
1
45
7
2
6
3
8
2
11
9
10
1
7
5
7
12
4
TEL
DATA
TELE
DR
"F"
PW
AP
DATA
APPROX3"
TELE
(BLUE) (YELLOW)
13
V
"F"
2
10
CC
DATA(BLUE)
1. RUN TO LOCAL VOICE STATION CABLE TERMINATION EQUIPMENT.2. 1-GANG BOX. SUBSCRIPT "W" INDICATES WALL PHONE PLATE. REFER TO LEGEND FOR MH.3. 4" SQ, 3.5" DEEP BOX WITH 1-GANG EXTENSION RING AND 1-GANG MODULAR 4-PORT
FACEPLATE.4. UTP VOICE JACK.5. UTP DATA JACK.6. DEFAULT OUTLET IS 2 DATA JACKS AND 2 VOICE JACKS (2D/2V). PROVIDE ALTERNATE
CONFIGURATION WHERE INDICATED ON THE DRAWINGS.7. RUN TO LOCAL DATA STATION CABLE TERMINATION EQUIPMENT.8. ELECTRICAL OUTLET.9. CATV COAXIAL TYPE "F" CONNECTOR.10. CONNECT TO LOCAL CATV DISTRIBUTION EQUIPMENT.11. SURFACE MOUNT ASSEMBLY FOR UTP DATA JACK ABOVE CEILING.12. PROVIDE 20' SLACK CABLE IN MANAGED COIL SUSPENDED FROM J-HOOK, FOR FIELD
RELOCATION OF DEVICE.13. SPLIT PAIRS BETWEEN JACKS.
DETAIL NOTES
SCSC SC
VALCOMPOWERSUPPLY
VALCOMPRE-AMP
IN
OUT
PWR110 VOICEWALLFIELD
CEILING SPEAKERS(TYPICAL)
PLENUM RATED CAT 3
PROVIDE CROSS CONNECT INTO EXISTINGVOICE RISER. COORDINATE WITH VA
LABELING1. POWER SUPPLY - MARK WITH FLOOR NUMBER AND
POWER SUPPLY NUMBER. COORDINATE NEXT AVAILABLENUMBER WITH VA. LABEL NUMBER OF SPEAKERSCONNECTED AND TOTAL NUMBER OF FUTURE SPEAKERSAVAILABLE (BASED UPON 25% MINIMUM SPARECAPACITY).
2. SPEAKER - MARK WITH FLOOR NUMBER/POWER SUPPLYNUMBER/SPEAKER NUMBER.
1. 120V-20A DEDICATED EMERGENCY CIRCUIT IN WALL MOUNTEDJUNCTION BOX. PROVIDE CONNECTION TO ALL SECURITY PANELS ASREQUIRED.
2. PROVIDE 120V DIRECT CONNECTION TO ALL SECURITY PANELS.3. EXTEND DATA DROP FROM LOCAL SIGNALS CLOSET INTO NEW
CONTROL PANEL.4. TYPICAL CONTROLLED DOOR DEVICES. REFER TO PLANS FOR
LOCATIONS.5. REQUEST TO EXIT ASSOCIATED WITH ELECTRIC STRIKE DOORS TO BE
CEILING MOUNTED PIR MOTION. REQUEST TO EXIT ASSOCIATED WITHELECTRIC LOCK/PANIC TO BE INTEGRATED WITH DOOR HARDWARE.
6. NEW ACCESS CONTROL CARD READER PANELS AS REQUIRED TOSUPPORT NEW CARD READER LOCATIONS AS INDICATED ON PLANS.
7. PROVIDE NEW CARD READER SYSTEM CONTROLLER PANEL ASREQUIRED.
8. PROVIDE DOOR LOCK LOW VOLTAGE REMOTE POWER SUPPLY PANEL.COORDINATE DOOR LOCK VOLTAGE AND REQUIREMENTS WITH DOORHARDWARE PROVIDER.
DETAIL NOTES
4 4
3
2
1
2
67 8
D
CRDMRX EL
JJ
NOTE: THIS DIAGRAM IS SCHEMATIC IN NATURE ONLY. IT IS
REFER TO DRAWINGS AND SPECIFICATIONS FOR WORK REQUIRED.INTENDED TO SHOW GENERAL CONFIGURATION OF THE SYSTEM.
MAINCONTROL
DOORCONTROL
PANEL
DOOR LOCKPOWERSUPPLYPANEL
ES
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 9
:03:
00 A
M
12/1
9/20
14 9
:03:
00 A
M
E0.5JDKNTL
TECHNOLOGY SYMBOLS ANDDETAILS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
SCALE: NONE
NEW VOICE/DATA RISER DIAGRAM2SCALE: NONE
EXISTING VOICE/DATA RISER DIAGRAM1
SCALE: NONE
TECHNOLOGY OUTLET DETAILS3
SCALE: NONE
PAGING SYSTEM DIAGRAM4 SCALE: NONE
SECURITY SYSTEM DETAIL5
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
F
SpaceC-2-8
E0.6
6
5
4
3
7
2-4"C.8
9
2
2
3
4
5
6
910
11
7
2
13
1
7
7
12
2-4"C.8
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 9
:03:
11 A
M
12/1
9/20
14 9
:03:
11 A
M
E0.6JDKNTL
EXISTING SIGNALS CLOSETDETAILS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
SCALE: 1" = 1'-0"
EXISTING SIGNALS CLOSET PLAN1
SCALE: 1/2" = 1'-0"
SIGNALS CLOSET-WEST WALL3
SCALE: 1/2" = 1'-0"
SIGNALS CLOSET-SOUTH WALL4 SCALE: 1/2" = 1'-0"
SIGNALS CLOSET-EAST WALL5
SCALE: 1/2" = 1'-0"
SIGNALS CLOSET-NORTH WALL6
SHEET NOTES1. PROVIDE NEW WALL MOUNTED HINGED FRAMES FOR NEW DATA STATION PATCH PANELS.2. MAINTAIN EXISTING FIBER TERMINATION PANELS.3. REPLACE EXISTING WALL MOUNTED DATA STATION CABLE TERMINATION PATCH PANELS WITH
NEW.4. PROVIDE NEW HORIZONTAL WIRE MANAGER PANELS.5. RE-USE EXISTING 48 PORT POE NETWORK SWITCHES.6. NEW DATA STASTION CABLE PATCH PANELS FOR WAP AND CCTV OUTLETS.7. NEW 12" WIDE HORIZONTAL LADDER RACK, WALL MOUNTED.8. PROVIDE CONDUIT SLEEVE THROUGH WALL WITH FIRE STOP ASSEMBLIES.9. EXISTING 110 WALL FIELDS.10. EXISTING TELECOMMUNICATIONS GROUND BAR.11. EXISTING WALL MOUNTED PROTECTOR PANEL TO BE MAINTAINED.12. 12" VERTICAL LADDER RACK.13. EXISTING DAS SYSTEM TO BE MAINTAINED.
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
CU
AC
AC
FP
FC
AC
1 2 3 4 5 6 7 8 9
C
1 2 3 4 5 6 7 8 9
C
1 2 3 4 5 6 7 8 9
C
VMUAIR COMP.20A/3HP
200A
EXIST.VMU CHILLER
125 MCA150A MOCP
OFFEF
ROOF
15E1
E.F. ROOF
WHPNL
PB
AIR COMP
VAC PUMP 6FIRE PUMP
2HP
PB
P1
15KW WATERHEATER (SERVESCAGE WASHER)208/3-50A
EXPB
400A
EMPNL
AIRCOMP
DRYERGF
WASH
DOM. WATERCOOLED208V/1PH9.1FLA
20A/EM
H2OSYST
REF. FRZ. FRZ.
MOTION CONTROLELEV. CABINET
30 KVAXFMR
JCI PNL
20HPELEV480V
LPB
ELEV.DISC.
CAB LTS
JOCKEY PUMP
FIRE PUMPCONTROLLER
RCP
15MDP
15ATS3 16ATS1
15OS1
15OSDP1
15ATS1
15ATS2
15EMB
BA
FISHER HOUSESERVICE
15ATS-2
EX
PB
PB
F.P.
2
2
2
2
1
1
1
1
B01
MECH.ROOM
B01B
AIRINTAKESHAFT
B01ASTOR.
B03
ELEV.EQUIP.ROOM
B08CORRIDOR
B06AIR COMP
B07STAIR #1
B04
CLASSWASH &
STILL
B04A
RESEARCHSTOR.
B05ASTOR.
B02
TRANS.VAULT
B05
A/C SHOPOFF.
33
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 9
:03:
15 A
M
12/1
9/20
14 9
:03:
15 A
M
E1.1JRSMSG
BASEMENT FLOOR PLAN -REMOVALS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
SCALE: 1/4" = 1'-0"
BASEMENT FLOOR PLAN - REMOVALS1
PLAN NOTES1. REMOVE ALL BUS DUCT AND ASSOCIATED DISCONNECTS, SUPPORTS,
CONDUIT, ETC. BACK TO DISTRIBUTION PANEL.2. PROVIDED UNDER CORRECT ELECTRICAL FCA DEFICIENCIES PROJECT.3. LOCATE AND INTERCEPT CONDUITS TO PANEL 2N AND PANEL 2O. EXTEND
CONDUIT TO MAIN DISTRIBUTION PANEL FOR NEW WORK.
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
A. MAINTAIN ALL LIGHTING AND RECEPTACLE CIRCUITS FOR NEW WORK (WHEREINDICATED OR REQUIRED).
B. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF ALL TYPES, OR CAP AND LABELIN JUNCTION BOX FOR RE-USE, IN COMPLIANCE WITH THE NATIONAL ELECTRICCODE.
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORSPASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
D. REMOVE ALL LIGHTING FIXTURES WIRING DEVICES, DATA OUTLETS, FIRE ALARM,CONDUIT, WIRE, ETC. AS REQUIRED TO ACCOMMODATE NEW WORK. NOT ALLITEMS NECESSARILY SHOWN.
GENERAL NOTES
GF
GF
GF
J
J
GFGFGF
GF
30A
30A
46" MH46" MH
J J J
30A
30A
GF
GFGF
GFGF
J
GF
GF
J
30A
JJJ
J
30A
JJ
J
J
J
D
D
D
D
D
D
D
D
D
D
D D
S
SF
SF
S
AP
APA
AP
FFF
K
50A
VFS
GF
J
3
3
1 2 3 4 5 6 7 8 9
A
B
C
D
1 2 3 4 5 6 7 8 9
A
B
C
D
1 2 3 4 5 6 7 8 9
A
B
C
D
2A 2B 2C 2D 2E 2F 2G 2H 2I 2J 2K 2L
2X2W2V2U2T2S2R2Q2P2O2N2M
111
2
1
1 1 1 11
ELECTRIC208
201OFFICE
203BIOCHEMISTRY
207
PREP.LAB
207B
STERILESURGERY
207CSCRUB 213
FEMALETOILET
215CORRIDOR
202RENAL
208
CONTROLROOM
210AOFFICE
210
HISTOLOGYCHEMISTRY
214H.A.C.
212ASTAIR #2
200ASTAIR #1
216LOBBY
216AELEV.
441
AIRINTAKESHAFT
440
FUTUREAIR
INTAKESHAFT
439
DUCTSHAFT
200ELEC.
3
3
3
3
EX/R
EX/R
EX/R
EX/R
EX/R
EX/R
1 1 1 1
4
5
5
55
6LP2
5
5
3
7
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 9
:03:
20 A
M
12/1
9/20
14 9
:03:
20 A
M
E1.2JRSMSG
SECOND FLOOR PLAN - REMOVALS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
A. REMOVE ALL VOICE / DATA CABLING BACK TO 2ND FLOOR SIGNALS CLOSET.B. REFER TO ARCHITECTURAL PHASING PLAN AND INCLUDE ALL WORK NECESSARY TO
ACCOMMODATE PHASING.C. REFER TO ARCHITECTURAL PLANS FOR SCOPE AND LOCATION OF DEDUCT ALTERNATES.D. MAINTAIN ALL LIGHTING AND RECEPTACLE CIRCUITS FOR NEW WORK (WHERE INDICATED
OR REQUIRED).E. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF ALL TYPES, OR CAP AND LABEL IN
JUNCTION BOX FOR RE-USE, IN COMPLIANCE WITH THE NATIONAL ELECTRIC CODE.F. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING
THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.G. REMOVE ALL LIGHTING FIXTURES WIRING DEVICES, DATA OUTLETS, FIRE ALARM, CONDUIT,
WIRE, ETC. AS REQUIRED TO ACCOMMODATE NEW WORK. NOT ALL ITEMS NECESSARILYSHOWN.
GENERAL NOTES
1. REMOVE EXISTING PANELBOARD, BUSSING, BREAKERS, TUB, BRANCH CIRCUITRY, ETC. ANDFEEDER BACK TO SOURCE (BUS DUCT IN BASEMENT). TURN OVER PANELBOARD ANDBREAKERS TO VA. GROUT CONDUIT FULL, FLUSH WITH FLOOR.
2. REMOVE PANEL TUB AND FEEDERS BACK TO DISTRIBUTION PANEL. MAINTAIN EXISTINGCONDUIT TO BASEMENT FOR NEW WORK.
3. DISCONNECT HOOD / EQUIPMENT AND REMOVE CIRCUITRY BACK TO SOURCE.4. DISCONNECT REFRIGERATED ROOM LIGHTING, RECEPTACLE, COMPRESSOR (ON TOP), AND
EVAPORATOR FROM PANEL AND RECIRCUIT AS INDICATED ON NEW WORK PLANS. PROVIDETEMPORARY POWER THROUGH CUTOVER.
5. KEEP AS EXISTING. DISCONNECT FROM PANEL AND RECIRCUIT AS INDICATED ON NEWWORK PLANS.
6. REFER TO SINGLE LINE DIAGRAM.7. REFER TO TECHNOLOGY ROOM CLOSET SHEETS FOR MORE INFORMATION.
PLAN NOTES
SCALE: 1/4" = 1'-0"
SECOND FLOOR PLAN - REMOVALS1
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
OS
OS
OS
OS
OS
OS
OSOS
3 3
33
3 3
OS
OSOS
OS
OS
OS
OS
3 3
33
OS OS
OS OS
J
33
3
3
1 2 3 4 5 6 7 8 9
A
B
C
D
CORRIDORC-2-2
LAB209
OFFICE209A
LAB210
OFFICE202
OFFICE203
OFFICE204
OFFICE206
OFFICE205
STORAGE207A
ELECTRIC208
STORAGE207
OFFICE201
CLOSET201A
CORRIDORC-2-3
CORRIDORC-2-1
CORRIDORC-2-4
SpaceC-2-5
SpaceC-2-6
SpaceC-2-7
SpaceC-2-8
SpaceC-2-9
SpaceC-2-10
SpaceC-2-11
SpaceC-2-12
SpaceC-2-13
SpaceC-2-14
SpaceC-2-15
1 2 3 4 5 6 7 8 9
A
B
C
D
1 2 3 4 5 6 7 8 9
A
B
C
D
EF3 EF3
EF1a
EF3 EF3
EF3 EF3EF3 EF3
EF1a
EF1a
EF1a
EF1a
EF3 EF3
EF3 EF3EF3EF3
EF3
EF3
EF1a
EF3 EF3
EF1a
EF1a
EC1
EF1
EF1
EF1
EF1
EF1 EF1 EF1 EF1
EF1
EF1
EF1 EF1
EF1a
EX.
EF1 EF1
EF1 EF1 EF1
EF1
EF1
EC1
EF1
EF1
EX/R
EX/REX1 EX1
EX/REX2
15OS22M
2N 2O EC1
Ex.
Ex. Ex.
Ex.
Ex. Ex.
Ex.
LP2
15OS2 - 2
1
EF2 EF2
EF2
EF1
EF1
EF1a EF1a
LP2 - 4
LP2 - 3
LP2 - 6
LP2 - 1
LP2 - 2
15OS2 - 15
2
SSS
SS
SSS
SS
EF3a
3
3
3
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 9
:03:
26 A
M
12/1
9/20
14 9
:03:
26 A
M
E2.1JRSMSG
SECOND FLOOR PLAN - NEW WORK- LIGHTING
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
1. CONNECT REFRIGERATED ROOM LIGHTING CIRCUIT TO EMERGENCY POWER.2. CONNECT TO EXISTING 120V EMERGENCY LIGHTING CIRCUIT.3. REPLACE EXISTING SWITCH WITH RED SWITCH TO INDICATE EMERGENCY CIRCUIT.
PLAN NOTES
SCALE: 1/4" = 1'-0"
SECOND FLOOR PLAN - NEW WORK - LIGHTING1
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
A. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.B. EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND COMMON/SHARED GREEN
INSULATED EQUIPMENT GROUNDING CONDUCTOR.C. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND
NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.D. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL
DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.E. WHERE SWITCHES ARE SHOWN IN SPACES CONTROLLED BY OCCUPANCY SENSORS, WIRE
SENSOR RELAY PACK AHEAD OF LOCAL SWITCHING.F. REFER TO ARCHITECTURAL DRAWINGS FOR RATED WALL LOCATIONS.G. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED
ABOVE OR BELOW CASEWORK, FURNITURE, LAVATORIES, ETC.H. WIRE ALL EXIT SIGNS AHEAD OF LOCAL SWITCHING.I. LABEL ALL WIRING DEVICES/JUNCTION BOXES WITH PANEL/CIRCUIT NUMBER. LABEL ALL
EXISTING DEVICES TO REMAIN AS WELL.J. UTILIZE FINISHED SURFACE METAL RACEWAY FOR DEVICES ON EXISTING BLOCK WALLS
(WHERE AN UNSUED ROUGH-IN DOES NOT EXISTING).
GENERAL NOTES
S
S
S
SS
S
S S
GF
GF
S
S
S
GF
EM/GF
EM
EM
EM
EM
EM
EMEM/S
S
EM/S
EM
46" MH
EM
46" MH
GF
EM
GF
GF
EM/S
S
EM/GF
GF
EM
GFGF
GF/S
EM
EM
EM
EM
EM
EM
EM
EM
S
JJ
EM
1 2 3 4 5 6 7 8 9
A
B
C
D
CORRIDORC-2-2
LAB209
OFFICE209A
LAB210
OFFICE202
OFFICE203
OFFICE204
OFFICE206
OFFICE205
STORAGE207A
ELECTRIC208
STORAGE207
OFFICE201
CLOSET201A
CORRIDORC-2-3
CORRIDORC-2-1
CORRIDORC-2-4
SpaceC-2-5
SpaceC-2-6
SpaceC-2-7
SpaceC-2-8
SpaceC-2-9
SpaceC-2-10
SpaceC-2-11
SpaceC-2-12
SpaceC-2-13
SpaceC-2-14
SpaceC-2-15
1 2 3 4 5 6 7 8 9
A
B
C
D
1 2 3 4 5 6 7 8 9
A
B
C
D
EX.
2
2N 2O
2M 15OS2
EX. EX.
TYP.1
TYP.1
LP23
4
2O - 10
2M - 5
2M - 1
15OS2 - 6
2M - 3
15OS2 - 1
2M - 2
2M - 6
15OS2 - 4
2M - 8
15OS2 - 3
15OS2 - 16,1815OS2 - 20,22
2O - 8
2O - 6
2N - 12O - 7
15OS2 - 14
2O - 9
2M - 10
2O - 515OS2 - 13
2M - 7
2O - 3 2O - 2
2O - 1 2O - 4
2N - 10
15OS2 - 7
2N - 6
2N - 13
15OS2 - 515OS2 - 8
15OS2 - 9
2N - 9
15OS2 - 11
2N - 11
15OS2 - 12
15OS2 - 10
2M - 4
2N - 5,8
2N - 32N - 4
2N - 12
52N - 7
5
5
TYP.1
TYP.1
46
(150S2)
15OS2 - 17
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 9
:03:
31 A
M
12/1
9/20
14 9
:03:
31 A
M
E2.2JRSMSG
SECOND FLOOR PLAN - NEW WORK- POWER
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
1. BACKBOX FURNISHED WITH LAB TABLE. DIV. 26 TO PROVIDE RECEPTACLE AND WIRECOMPLETE. VERIFY EXACT LOCATION WITH ARCHITECT.
2. COORDINATE EXACT EQUIPMENT RECEPTACLE LOCATION WITH V.A. PROVIDEHARDWIRED CONNECTION IN LIEU OF RECEPTACLE WHERE REQUIRED.
3. REFER TO SINGLE LINE DIAGRAM.4. UTILIZE EXISTING CONDUIT TO BASEMENT. INTERCEPT AND EXTEND TO NEW SOURCE /
PANEL.5. LOCATE CIRCUIT HOMERUN, REROUTE TO PANEL AS INDICATED.6. PROVIDE PAINTED GALVANIZED SHEET METAL ENCLOSURE TO CONCEAL NEW CONDUIT
DROP.
PLAN NOTES
SCALE: 1/4" = 1'-0"
SECOND FLOOR PLAN - NEW WORK - POWER1
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
A. PROVIDE DEDICATED NEUTRAL FOR ALL 120V-20A CIRCUITS.B. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SWITCH COVERPLATES INDICATING PANEL
AND CIRCUIT NUMBER. LABEL ALL EXISTING DEVICES AS WELL.C. EMT CONDUIT SHALL BE 0.75" MINIMUM.D. REFER TO DIVISION 22/ARCHITECTURAL DRAWINGS FOR LOCATIONS OF ALL PLUMBING
EQUIPMENT.E. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO ALLOW
FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.F. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH
BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND GREEN INSULATED EQUIPMENTGROUNDING CONDUCTOR.
G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMALBRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
H. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING.I. REFER TO ARCHITECTURAL DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.J. REFER TO ARCHITECTURAL DRAWINGS FOR RATED WALL LOCATIONS.K. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED ABOVE
OR BELOW CASEWORK, FURNITURE, LAVATORIES, ETC.L. UTILIZE FINISHED SURFACE METAL RACEWAY FOR DEVICES ON EXISTING BLOCK WALLS (WHERE
AN UNSUED ROUGH-IN DOES NOT EXISTING).
GENERAL NOTES
D
D
DD
D
D
D
D
DD
D
D
D D
D D
D D
D D
D D
D
D
F F
S
D
K
VFS
S
R
SF
SF
SF
SF
SF
SF
SF
SF
SF
APEX/R
APEX/R AP
EX/R
AP
AP
AP
AP
SC SC SC SC
SC
SC
SC
D
D
D
D
D
D
P
SC
D
D
D
D
D
D
D
1 2 3 4 5 6 7 8 9
A
B
C
D
CORRIDORC-2-2
LAB209
OFFICE209A
LAB210
OFFICE202
OFFICE203
OFFICE204
OFFICE206
OFFICE205
STORAGE207A
ELECTRIC208
STORAGE207
OFFICE201
CLOSET201A
CORRIDORC-2-3
CORRIDORC-2-1
CORRIDORC-2-4
SpaceC-2-5
SpaceC-2-6
SpaceC-2-7
SpaceC-2-8
SpaceC-2-9
SpaceC-2-10
SpaceC-2-11
SpaceC-2-12
SpaceC-2-13
SpaceC-2-14
SpaceC-2-15
E0.61
W
TYP.1
S
S S SS
S
1
1
S
S
TYP.1
1 1
one
quar
ter
inch
= o
ne fo
ot
0
one
eigh
th in
ch =
one
foot
48
16
VA FORM 08-6231,
1 2 3 4
CheckedApproved: Project Director
Drawing Title
5 6 7 8
Project Title
Building Number
9
Drawn
Drawing No.
Project No.
thre
e qu
arte
rs in
ch =
one
foot
F
04
thre
e ei
ghth
s in
ch =
one
foot
80
E 4
one
half
inch
= o
ne fo
ot
0
D 46"
02
one
inch
= o
ne fo
ot
C
6"0
one
and
one
half
inch
es =
one
foot
2
B
6"0
1
A
thre
e in
ches
= o
ne fo
ot
6"0
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
ARCHITECT / ENGINEERS:
--
15
3231.00
Office ofConstructionand FacilitiesManagement
Location
Date
CONSULTANTS:
Department ofVeterans Affairs
REVISIONS DATE HEAPY PROJECT No.: 2014-04017 FIRM LICENSE No.: 01528
12/1
9/20
14 9
:03:
37 A
M
12/1
9/20
14 9
:03:
37 A
M
E2.3JRSMSG
SECOND FLOOR - NEW WORK -SIGNALS
12/19/14
REMODEL 2nd FLOOR LABS, BLDG. 15
3200 VINE STREETCINCINNATI, OHIO 45220
539-15-103
SCALE: 1/4" = 1'-0"
SECOND FLOOR PLAN - NEW WORK - SIGNALS1
1. MOUNT VOICE / DATA OUTLET IN LAB TABLES. BACKBOX FURNISHED WITH LAB TABLES.UTILIZE FLOOR TO CEILING DIVIDED COLUMN FURNISHED WITH FURNITURE FOR NEWHORIZONTAL CABLING.
PLAN NOTES
BID DOCUMENTS 12/19/14100% SUBMITTAL 11/21/14
A. ALL NEW VOICE/DATA TO BE CABLED TO SIGNALS C-2-8 THIS SHEET.B. REFER TO ARCHITECTURAL DRAWINGS FOR RATED WALL LOCATIONS.C. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL
DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.D. COORDINATE ALL NEW FIRE ALARM/FIRE SUPPRESSION ZONES WITH COR.E. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED
ABOVE OR BELOW CASEWORK, FURNITURE, LAVATORIES, ETC.F. NEW FIRE ALARM NOTIFICATION APPLIANCES SHALL BE ON SAME ZONE AS EXISTING.
GENERAL NOTES