+ All Categories
Home > Documents > Visual Inspection of the Transformer _ CsanyiGroup

Visual Inspection of the Transformer _ CsanyiGroup

Date post: 02-Jun-2018
Category:
Upload: adebayo-o-johnson
View: 218 times
Download: 0 times
Share this document with a friend

of 13

Transcript
  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    1/13

  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    2/13

  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    3/13

    12/15/2014 Visual Inspection Of The Transformer | CsanyiGroup

    http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer 3

    Figure 1.Conservator Oil Level

    Check the oil level gauge on the conservator. See figure 1at right. This gauge indicates oil level by displaying a temperature. Compar

    the indicated temperature on the conservator level gauge with the top oil temperature indicator. They should be approximately the same.

    Calibrate or replace the conservator oil level indicator if needed, but only after checking the top oil temperature indicator as shown in the

    above section. Reference also IEEE 62-1995 [11], section 6.6.2. If atmospheric gases (nitrogen, oxygen, carbon dioxide) an

    perhaps moisture increase suddenly in the DGA, a leak may have developed in the conservator diaphragm or bladder. With th

    transformer offline and under clearance, open the inspection port on top of the conservator and look inside with a flashlight. If there is a

    leak, oil will be visible on top of the diaphragm or inside the bladder. Reclose the conservator and replace the bladder or diaphragm a

    the first opportunity by scheduling an outage. If there is no gas inside the Buchholz Relay, the transformer may be re-energized aftebleeding the air out of the bladder failure relay.

    A DGA should be taken immediately to check for O2, N2, and moisture. However, the transformer may be operated until a new

    bladder is installed, keeping a close eye on the DGAs. It is recommended that DGAs be performed every 3 months until the new

    bladder is installed. After the bladder installation, the oil may need to be de-gassed if O2 exceeds 10,000 ppm. Also, carefully chec

    the moisture level in the DGAs to ensure it is below recommended levels for the particular transformer voltage. Check the desiccant in

    the breather often; never let more than two-thirds become discolored before renewing the desiccant. All efforts should be made to keep

    the oxygen level below 2,000 ppm and moisture as low as possible.

    1.5 Conservator Breather

    Figure 2.Conservator Breather

    Check the dehydrating (desiccant) breather for proper oil level if it is an oil type unit. Check the color of the desiccant and replace i

    when approximately one-third remains with the proper color. See figure 2for a modern oil type desiccant breather. Notice the pink

  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    4/13

    12/15/2014 Visual Inspection Of The Transformer | CsanyiGroup

    http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer 4

    desiccant at the bottom of the blue indicating that this portion is water saturated. Notice also that oil is visible in the very bottom 1-inch

    or so of the unit.

    Many times, the oil is clear, and the oil level will not be readily apparent. Normally, there is a thin line around the breather near th

    bottom of the glass; this indicates where the oil level should be.

    Compare the oil level with the level indicator line and refill, if necessary. Note the 1-inch pipe going from the breather to th

    conservator. Small tubing ( inch or so) is not large enough to admit air quickly when the transformer is de-energized in winter. A

    transformer can cool so quickly that a vacuum can be created from oil shrinkage with enough force to puncture a bladder. When this

    happens, the bladder is destroyed; and air is pulled into the conservator making a large bubble.

    1.6 Nitrogen

    If the transformer has a nitrogen blanket, check the pressure gauge for proper pressure. Look at the operators recording of pressures

    from the pressure gauge. If this does not change, the gauge is probably defective. Check the nitrogen bottle to insure the nitrogen is the

    proper quality (see PEB No. 5 [20]). Check for any increased usage of nitrogen which indicates a leak. Smaller transformers such a

    station service or smaller generator-step-up transformers may not have nitrogen bottles attached to replace lost nitrogen. Be especially

    watchful of the pressure gauge and the operators records of pressures with these.

    The pressure gauge can be defective for years, and no one will notice. The gauge will read nearly the same and will not vary much ove

    winter and summer or night and day. Meanwhile, a nitrogen leak can develop; and all the N2 will be lost. This allows air with oxygen

    and moisture to enter and deteriorate the oil and insulation. Watch for increased oxygen and moisture in the DGA. An ultrasonic andsonic leak detection instrument (P-2000) is used for locating N2 leaks.

    1.7 Oil Leaks

    Oil Leaks

    Check the entire transformer for oil leaks. Leaks develop due to gaskets wearing out, ultraviolet exposure, taking a set, or from

    expansion and contraction, especially after transformers have cooled, due to thermal shrinkage of gaskets and flanges. Many leaks ca

    be repaired by applying an epoxy or other patch.

    Flange leaks may be stopped with these methods using rubberized epoxy forced into the flange under pressure. Very small leaks i

    welds and tanks may be stopped by peening with a ball-peen hammer, cleaning with the proper solvent, and applying a patch of the

    correct epoxy.

    Experienced leak mitigation contractors whose work is guaranteed may also be employed. Some leaks may have to be welded

    Welding may be done with oil in the transformer if an experienced, qualified, and knowledgeable welder is available. If welding with oi

    in the tank is the method chosen, oil samples must be taken for DGA both before and after welding. Welding may cause gases to appea

    in the DGA and it must be determined what gases are attributed to welding and which ones to transformer operation.

    1.8 Pressure Relief Device

    With the transformer under clearance, check the pressure relief device indicating arm on top of the Figure 3. Pressure Relief Device.

    transformer to see if it has operated. If it has operated, the arm will be in the up (vertical) position, and alarm and shutdown relays

    should have activated.

  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    5/13

    12/15/2014 Visual Inspection Of The Transformer | CsanyiGroup

    http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer 5

    Figure 3. Pressure Relief Device

    CAUTION:

    Do not re-energize a transformer after this device has operated and relays have de-energized the transformer, until

    extensive testing to determine and correct the cause has been undertaken. Explosive, catastrophic failure could be the

    result of energization after this device has operated.

    1.9 Oil Pumps

    If the transformer has oil pumps, check flow indicators and pump isolation valves to ensure oil is circulating properly. Pump motor(s

    may also have reversed rotation, and flow indicators may still show that oil is flowing. To ensure motors are turning in the prope

    direction, use an ammeter to check the motor current. Compare results with the full-load-current indicated on the motor nameplate. I

    the motor is reversed, the current will be much less than the nameplate full-load-current. Check oil pumps with a vibration analyzer

    they develop unusual noises.

    Have the DGA lab check for dissolved metals in the oil and run a metal particle count for metals if the bearings are suspect. This shoul

    be done immediately, as soon as a bearing becomes suspect; bad oil-pump bearings can put enough metal particles into the oil t

    threaten transformer insulation and cause flashover inside the tank. An explosive catastrophic failure of the transformer tank could be the

    result.

    1.10 Fans and Radiators

    Inspect all isolation valves at the tops and bottoms of radiators to ensure they are open. Inspect cooling fans and radiators for cleanlines

    and fans for proper rotation. Check for dirty or damaged fan blades or partially blocked radiators. Fans are much more efficient if the

    blades are clean and rotating in cool air. Normally, fans blow cool air through the radiators; they should not be pulling air through

    Check to see if fans are reversed electrically (i.e., pulling air first through the radiators and then through the fan blades). This means th

    blades are rotating in warm air after it passes through the radiator which is much less efficient. Place a hand on the radiator opposite th

    fans; air should be coming out of the radiator against your hand.

    Watch the blades as they rotate slowly when they are starting or stopping to determine which way they should be rotating and correcthe rotation if necessary.

    1.11 Buchholz Relay

  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    6/13

    12/15/2014 Visual Inspection Of The Transformer | CsanyiGroup

    http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer 6

    Figure 4.Buchholz Relay

    Inspect the isolation valve on the Buchholz relay to ensure it is open. With the transformer offline and under clearance, examine th

    Buchholz relay by lifting the window cover (center in figure 4at right) and looking inside. If there is gas inside, the oil will be displaced

    and the gas will be evident as a space on top the oil. If sufficient gas is found to displace the upper float, the alarm should be activated

    The small valve at the top left is to bleed the gas off and reset the relay. If a small amount of gas is found in this relay when thetransformer is new (a few months after startup), it is probably just air that has been trapped in the transformer structure and is now

    escaping; there is little cause for concern.

    If the transformer has been on line for some time (service aged), and gas is found in the Buchholz, oil samples must be sent to the lab fo

    DGA and extensive testing. Consult with the manufacturer and other transformer experts. A definite cause of the gas bubbles must b

    determined and corrected before re-energization of the transformer.

    1.12 Sudden Pressure Relay

    Figure 5.Sudden Pressure Relay

    An example relay is shown in figure 5at the left. The purpose of this relay is to alarm if there is a sudden pressure rise inside the tank

    This relay is very sensitive and will operate if the pressure rises only a little. If a very small pressure change occurs caused by a smal

    electrical fault inside the tank, this relay will alarm. In contrast, the pressure relief device (shown above in figure 5) operates if a larg

    pressure builds inside the tank caused by heavy arcing and heating causing the oil to boil and bubble. Inspect the isolation valve t

    ensure it is open.

    With the transformer offline and under clearance, functionally test the sudden pressure relay by slowly closing the isolating valve. Leave

  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    7/13

  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    8/13

    12/15/2014 Visual Inspection Of The Transformer | CsanyiGroup

    http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer 8

    51 people recommend this.Recommend

    Posted by: ecsanyion Saturday, August 21, 2010 at 9:15 pm

    Tagged with:buchholz relay, conservator, fans, inpection, nitrogen, oil,pressure relief,pumps, radiators, sudden, temperature,

    transformer, visual

    Turn Your Thoughts Into Words

    Tell us what you're thinking... we care about your opinion!

    and oh, not to forget - if you want a picture to show with your comment, go get a free Gravatar!

    Name (required)

    Mail (will not be published) (required)

    Website

    CAPTCHA Code *

    Submit Comment

    Comments RSS Feed

    Comments

    6 Responses to Visual Inspection Of The Oil Transformer

    1. ecsanyisays:

    21 August, 2010 at 21:29

    Do you think this can be enough informations for technicians to visually inspect oil transformer?

    http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer/comment-page-1#comment-419http://www.csanyigroup.com/http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer/feedhttp://en.gravatar.com/http://www.csanyigroup.com/tag/visualhttp://www.csanyigroup.com/tag/transformerhttp://www.csanyigroup.com/tag/temperaturehttp://www.csanyigroup.com/tag/suddenhttp://www.csanyigroup.com/tag/radiatorshttp://www.csanyigroup.com/tag/pumpshttp://www.csanyigroup.com/tag/pressure-reliefhttp://www.csanyigroup.com/tag/oilhttp://www.csanyigroup.com/tag/nitrogenhttp://www.csanyigroup.com/tag/inpectionhttp://www.csanyigroup.com/tag/fanshttp://www.csanyigroup.com/tag/conservatorhttp://www.csanyigroup.com/tag/buchholz-relayhttp://www.csanyigroup.com/about-us
  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    9/13

    12/15/2014 Visual Inspection Of The Transformer | CsanyiGroup

    http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer 9

    Reply

    2. Jeremysays:

    22 August, 2010 at 09:36

    It depends on transformer condition. I had few very hard to detect problems with ABB's oil transformers 1600kVA.

    Reply

    Stefan Smithsays:

    25 August, 2010 at 15:08

    Of course it has a lot with transformer state. What problems did you have with ABBS transformers? You didnt mention

    rated primary voltage.

    Reply

    ecsanyisays:

    25 August, 2010 at 15:14

    After few years and bad or non-at-all inspections ANY oil transformer can became unstable in work or show some

    more or less serious problems.

    Reply

    3. fransiscosays:

    22 November, 2013 at 11:44

    hey guys do you think we can notice the level of transformer oil without visual inspection?

    Reply

    Trackbacks

    Check out what others are saying about this post...

    1. diesel generator: MEP-003a Onan/Libby Welding Military Generatorsays:

    23 August, 2010 at 13:09

    [...] Visual Inspection Of The Transformer | CsanyiGroup [...]

    Reply

    SUbscribe To Technical Articles

    7 Reasons to subscribeand receive

    technical articlesand updates via email:

    Subscribe

    Delivered via Google Feedburner

    http://www.csanyigroup.com/home/7-reasons-to-subscribehttp://www.csanyigroup.com/visual-inspection-of-the-oil-transformer?replytocom=427#respondhttp://www.csanyigroup.com/visual-inspection-of-the-oil-transformer/comment-page-1#comment-427http://dieselgeneratorreviews.net/mep-003a-onanlibby-welding-military-generator.htmlhttp://www.csanyigroup.com/visual-inspection-of-the-oil-transformer?replytocom=857#respondhttp://www.csanyigroup.com/visual-inspection-of-the-oil-transformer/comment-page-1#comment-857http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer?replytocom=434#respondhttp://www.csanyigroup.com/visual-inspection-of-the-oil-transformer/comment-page-1#comment-434http://www.csanyigroup.com/http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer?replytocom=433#respondhttp://www.csanyigroup.com/visual-inspection-of-the-oil-transformer/comment-page-1#comment-433http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer?replytocom=421#respondhttp://www.csanyigroup.com/visual-inspection-of-the-oil-transformer/comment-page-1#comment-421http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer?replytocom=419#respond
  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    10/13

    12/15/2014 Visual Inspection Of The Transformer | CsanyiGroup

    http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer 10

    Electrical Engineering | Ads

    Electrical Engineering | Sponsors

    Electrical Engineering Articles

    Recent

    Most Read

    Comments

    ABB launches new generation 420kV gas insulated switchgear

    Superconducting transformers

    Largest Tesla Coil Ever Built

    ePlusMenuCAD 10 RC1 New Release

    ABB Power Transformers A guide to manufacturing

    Light Pollution

    Line Protection With Distance Relays

    UPS design criteria and selection

    The New ETS4: Easy, Fast, Open

    Arc-resistant low voltage switchgear

    ANSI/IEC Relay Symbols viewed 51,125 times

    Comparison Between Vacuum and SF6 Circuit Breaker viewed 49,177 times

    ANSI standards for protection devices viewed 47,613 timesTransformer heating and cooling viewed 26,359 times

    Substation, Its Function And Types viewed 20,128 times

    General about motors viewed 18,508 times

    Wind Power Applications viewed 16,085 times

    PLC-Based Monitoring Control System for Three-Phase Induction Motors Fed by PWM Inverter viewed 15,955 times

    Gas-Insulated Switchgear Type 8DN8 viewed 15,195 times

    Grounded or Ungrounded Systems viewed 15,154 times

    kinderklamotten aus china

    Dieses Site wird laufend von einem Suchmaschinen- Spezialisten weiterentwickelt, was Ihnen zustzlich die Gewhr bietet,

    Current Transformer

    Fuel Liquid Level Sensor

    Sight Glasses, Flowmeters

    flow points.co.uk

    Sight glasses, flow indicators and flowmeters

    for water andliquids

    Fuel Level Sender

    http://www.csanyigroup.com/siemens-mv-topic-loss-of-vacuum#comment-2371http://www.csanyigroup.com/wind-power-applicationshttp://www.csanyigroup.com/substation-its-function-and-typeshttp://www.csanyigroup.com/transformer-heating-and-coolinghttp://www.csanyigroup.com/comparison-between-vacuum-and-sf6-circuit-breakerhttp://www.csanyigroup.com/the-new-ets4-easy-fast-openhttp://googleads.g.doubleclick.net/aclk?sa=L&ai=C_uTRYviOVLWmAoiR7gbyhIGoDfGz2KcF8Yjp9NkBwI23ARAEIMmN6CAoBGC3vIOF9DDIAQGoAwHIA8MEqgSoAU_Qq70izN1_TYjxl0mPdKXRA3B5xYWTmZlle0jVBzl9eUqyxW9haxUTsbdfN41B0tB8mIMkaBnL8jxba_vp6TWMLJvlZN492QJcT2-ekYMCA5FaBKR0qURZK9jIVe82VkcjA8KtYtV8FEBoaJ4G31jKAIp3tokJC3psZyIFhGSu_WJev5ABHGpm0ziRLQocZcppCl_Hw7DzsyEa-jwcdrWfGP35v-QtioAHibfpMw&num=4&sig=AOD64_11XM5NsB2q1mHANNqcMLWdI4rckw&client=ca-pub-8074809922364090&adurl=http://www.ciescorp.nethttp://googleads.g.doubleclick.net/aclk?sa=L&ai=CQR5kYviOVLWmAoiR7gbyhIGoDb2pt4YCqdG3ugPAjbcBEAMgyY3oICgEYLe8g4X0MMgBAakCA2oE9xBIuj6oAwHIA8MEqgSlAU_Q6_U_zNp_TYjxl0mPdKXRA3B5xYWTmZlle0jVBzl9eUqyxW9haxUTsbdfN41B0tB8mIMkaBnL8jxba_vp6TWMLJvlZN492QJcT2-ekYMCA5FaBKR0qURZK9jIVe82VkcjA8KtYtV8FEBoaJ4G31jKAMJ3CuOIg0H2ys_uYeFPFuHlVHuwE3dm3c2S7_8fJT9qmqrE00Xwt9QZ_ssZdlefucFOR4AHmcvlBw&num=3&sig=AOD64_3sezJhdTI8YXXahASp17cPJBje2Q&client=ca-pub-8074809922364090&adurl=http://www.flowpoints.co.uk/home.htmhttp://googleads.g.doubleclick.net/aclk?sa=L&ai=CQR5kYviOVLWmAoiR7gbyhIGoDb2pt4YCqdG3ugPAjbcBEAMgyY3oICgEYLe8g4X0MMgBAakCA2oE9xBIuj6oAwHIA8MEqgSlAU_Q6_U_zNp_TYjxl0mPdKXRA3B5xYWTmZlle0jVBzl9eUqyxW9haxUTsbdfN41B0tB8mIMkaBnL8jxba_vp6TWMLJvlZN492QJcT2-ekYMCA5FaBKR0qURZK9jIVe82VkcjA8KtYtV8FEBoaJ4G31jKAMJ3CuOIg0H2ys_uYeFPFuHlVHuwE3dm3c2S7_8fJT9qmqrE00Xwt9QZ_ssZdlefucFOR4AHmcvlBw&num=3&sig=AOD64_3sezJhdTI8YXXahASp17cPJBje2Q&client=ca-pub-8074809922364090&adurl=http://www.flowpoints.co.uk/home.htmhttp://googleads.g.doubleclick.net/aclk?sa=L&ai=CQR5kYviOVLWmAoiR7gbyhIGoDb2pt4YCqdG3ugPAjbcBEAMgyY3oICgEYLe8g4X0MMgBAakCA2oE9xBIuj6oAwHIA8MEqgSlAU_Q6_U_zNp_TYjxl0mPdKXRA3B5xYWTmZlle0jVBzl9eUqyxW9haxUTsbdfN41B0tB8mIMkaBnL8jxba_vp6TWMLJvlZN492QJcT2-ekYMCA5FaBKR0qURZK9jIVe82VkcjA8KtYtV8FEBoaJ4G31jKAMJ3CuOIg0H2ys_uYeFPFuHlVHuwE3dm3c2S7_8fJT9qmqrE00Xwt9QZ_ssZdlefucFOR4AHmcvlBw&num=3&sig=AOD64_3sezJhdTI8YXXahASp17cPJBje2Q&client=ca-pub-8074809922364090&adurl=http://www.flowpoints.co.uk/home.htmhttp://googleads.g.doubleclick.net/aclk?sa=L&ai=CQR5kYviOVLWmAoiR7gbyhIGoDb2pt4YCqdG3ugPAjbcBEAMgyY3oICgEYLe8g4X0MMgBAakCA2oE9xBIuj6oAwHIA8MEqgSlAU_Q6_U_zNp_TYjxl0mPdKXRA3B5xYWTmZlle0jVBzl9eUqyxW9haxUTsbdfN41B0tB8mIMkaBnL8jxba_vp6TWMLJvlZN492QJcT2-ekYMCA5FaBKR0qURZK9jIVe82VkcjA8KtYtV8FEBoaJ4G31jKAMJ3CuOIg0H2ys_uYeFPFuHlVHuwE3dm3c2S7_8fJT9qmqrE00Xwt9QZ_ssZdlefucFOR4AHmcvlBw&num=3&sig=AOD64_3sezJhdTI8YXXahASp17cPJBje2Q&client=ca-pub-8074809922364090&adurl=http://www.flowpoints.co.uk/home.htmhttp://www.googleadservices.com/pagead/aclk?sa=L&ai=CPlwMYviOVLWmAoiR7gbyhIGoDcX3ipUF_a7m0ZYBwI23ARACIMmN6CAoBGC3vIOF9DCgAdPloNADyAEBqQKMTu4LPAhxPqgDAcgDwwSqBKkBT9CbpKTWwUZ1OkKFLY90_JwTYnbSlZ2MhH9-FpgLO6rCTIbGbykhEhZbbB0ckUHWmmmY2yRoQIbiLlR86-f8KJYpxaho3H-AHUZJe5PQxwUekk8Cs2mvRRpp0YMM8zseBSUGg_RkxnMJVWF1gQ7IyisDCPW1QMOwZB-3ge5hh0MW4ddee7CtgY3cwWcsCByl_5-J38fTVQWwIRr-zep1t5seHR9IyUsGnYgGAYAHlZrfLw&num=1&cid=5GhP8e0enOyNtgHq4_1AV1XU&sig=AOD64_2NsjtU7yZFs9myLiyrBM5_jS9d2A&client=ca-pub-8074809922364090&adurl=http://en.autovision.com.ua/sistema-teletrack/oborydovanie/datchik-yrovnya-topliva-epsilon.htmlhttp://www.googleadservices.com/pagead/aclk?sa=L&ai=C3Vb3YviOVLWmAoiR7gbyhIGoDf6trb0G9ruK_rYBwI23ARABIMmN6CAoBGC3vIOF9DCgAZre-NADyAEBqQJGNIwDIa6FPqgDAcgDwwSqBKYBT9DLsvPVwUV1OkKFLY90_JwTYnbSlZ2MhH9-FpgLO6rCTIbGbykhEhZbbB0ckUHWmmmY2yRoQIbiLlR86-f8KJYpxaho3H-AHUZJe5PQxwUekk8Cs2mvRRpp0YMM8zseBSUGg_RkxnMJVWF1gQ7IyisDCL21r5s-4x0vLAOKYsb3ClTlkFscjpDcz5Ivyummv2qKTzLQRfCzJe_9yR1wt3ke61S-a4gGAYAHzqGHLw&num=2&cid=5GhP8e0enOyNtgHq4_1AV1XU&sig=AOD64_22DpYipH9-DcVkPY_wbauhL2Db2Q&client=ca-pub-8074809922364090&adurl=http://www.nuodewei.com/english/cpzs.asp%3Fsortsid%3D722%26sorts%3D%25B5%25E7%25C1%25F7%25BB%25A5%25B8%25D0%25C6%25F7http://www.csanyigroup.com/siemens-mv-topic-loss-of-vacuum#comment-2371http://www.csanyigroup.com/grounded-or-ungrounded-systemshttp://www.csanyigroup.com/gas-insulated-switchgear-type-8dn8http://www.csanyigroup.com/plc-based-monitoring-control-system-for-three-phase-induction-motors-fed-by-pwm-inverterhttp://www.csanyigroup.com/wind-power-applicationshttp://www.csanyigroup.com/general-about-motorshttp://www.csanyigroup.com/substation-its-function-and-typeshttp://www.csanyigroup.com/transformer-heating-and-coolinghttp://www.csanyigroup.com/ansi-standards-for-protection-deviceshttp://www.csanyigroup.com/comparison-between-vacuum-and-sf6-circuit-breakerhttp://www.csanyigroup.com/ansi-iec-relay-symbolshttp://www.csanyigroup.com/arc-resistant-low-voltage-switchgearhttp://www.csanyigroup.com/the-new-ets4-easy-fast-openhttp://www.csanyigroup.com/ups-design-criteria-and-selectionhttp://www.csanyigroup.com/line-protection-with-distance-relayshttp://www.csanyigroup.com/light-pollutionhttp://www.csanyigroup.com/abb-power-transformers-a-guide-to-manufacturinghttp://www.csanyigroup.com/eplusmenucad-10-rc1-new-releasehttp://www.csanyigroup.com/largest-tesla-coil-ever-builthttp://www.csanyigroup.com/superconducting-transformershttp://www.csanyigroup.com/abb-launches-new-generation-420kv-gas-insulated-switchgearhttp://www.elektroenergetika.info/http://news.csanyigroup.com/http://www.automatika.rs/http://electrical-engineering-portal.com/
  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    11/13

    12/15/2014 Visual Inspection Of The Transformer | CsanyiGroup

    http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer 1

    im Web auch tatschlich unter den Suchbegriffen Regenbekleidung Hersteller, wasserdichte Regenhosen, Regenjacken und

    Regenmntel, Regenschutz Kleidung vom Friesennerz bis zum Motorradkombi, Kinder Regenjacke online Angebote etc.

    remodel loans

    Combining warm white lights with yellow lights or using it against a painted wall can exude warmth and welcome in a room

    The spacing of studs determines the energy efficiency of walls. Construction estimating software has become an essential

    tool in the arsenals of home renovation contractors, builders, DIY, as well as some home owners who are looking to

    educate themselves to better negotiating a pricing with contractors. If you have work that needs to be done in the house,

    you will need to consider their schedule. It means that you will have to refinance into a home rehab loan.

    ahmed elnhas

    and if it true , doesn't that mean that the continuity of the system will be affected if the upstream CB energize multiple

    parallel feeders

    ahmed elnhas

    all what i get is that upstream CB will trip before the fault current at downstream CB reach its maximum value , is that true

    ???

    Johnd895

    Do you mind if I quote a few of your posts as long as I provide credit and sources back to your weblog? My blog is in the

    very same niche as yours and my users would truly benefit from a lot of the information you present here. Please let me

    know if this alright with you. Thank you! cdgddggggbek

    Article Categories

    ANSI Standards

    AutoCADCables

    Energy And Power

    ePlusMenuCAD

    High Voltage

    Hydropower

    IEC Standards

    KNX

    Lighting

    Low Voltage

    Medium Voltage

    Motors

    Power Substations

    Programmable Logic Controller

    Protection Relays

    SCADA

    Solar Energy

    Tips & tricks

    Transformers

    Updates And Announcements

    Variable Speed Drives

    Wind Power

    http://www.csanyigroup.com/category/strucni-tekstovi/wind-power/feedhttp://www.csanyigroup.com/technical-articles/categories/category-wind-powerhttp://www.csanyigroup.com/category/strucni-tekstovi/variable-speed-drives/feedhttp://www.csanyigroup.com/technical-articles/categories/category-variable-speed-driveshttp://www.csanyigroup.com/category/updates-and-announcementshttp://www.csanyigroup.com/technical-articles/categories/category-updates-and-announcementshttp://www.csanyigroup.com/category/strucni-tekstovi/transformers/feedhttp://www.csanyigroup.com/technical-articles/categories/category-transformershttp://www.csanyigroup.com/category/tips-tricks/feedhttp://www.csanyigroup.com/technical-articles/categories/category-tips-and-trickshttp://www.csanyigroup.com/category/strucni-tekstovi/solar-energy/feedhttp://www.csanyigroup.com/technical-articles/categories/category-solar-energyhttp://www.csanyigroup.com/category/strucni-tekstovi/scada/feedhttp://www.csanyigroup.com/technical-articles/categories/category-scadahttp://www.csanyigroup.com/category/strucni-tekstovi/protection-relays/feedhttp://www.csanyigroup.com/technical-articles/categories/category-protection-relayshttp://www.csanyigroup.com/category/strucni-tekstovi/programmable-logic-controller/feedhttp://www.csanyigroup.com/technical-articles/categories/category-programmable-logic-controllerhttp://www.csanyigroup.com/category/strucni-tekstovi/power-substations/feedhttp://www.csanyigroup.com/technical-articles/categories/category-power-substationshttp://www.csanyigroup.com/category/strucni-tekstovi/motors/feedhttp://www.csanyigroup.com/technical-articles/categories/category-motorshttp://www.csanyigroup.com/category/strucni-tekstovi/medium-voltage/feedhttp://www.csanyigroup.com/technical-articles/categories/category-medium-voltagehttp://www.csanyigroup.com/category/strucni-tekstovi/low-voltage/feedhttp://www.csanyigroup.com/technical-articles/categories/category-low-voltagehttp://www.csanyigroup.com/category/strucni-tekstovi/lighting/feedhttp://www.csanyigroup.com/technical-articles/categories/category-lightinghttp://www.csanyigroup.com/category/strucni-tekstovi/knx/feedhttp://www.csanyigroup.com/technical-articles/categories/category-knxhttp://www.csanyigroup.com/category/iec-standards/feedhttp://www.csanyigroup.com/technical-articles/category-iec-standardshttp://www.csanyigroup.com/category/strucni-tekstovi/hydropower/feedhttp://www.csanyigroup.com/technical-articles/categories/category-hydropowerhttp://www.csanyigroup.com/category/strucni-tekstovi/high-voltage/feedhttp://www.csanyigroup.com/technical-articles/categories/category-high-voltagehttp://www.csanyigroup.com/category/software/eplusmenucad-software/feedhttp://www.csanyigroup.com/technical-articles/categories/category-eplusmenucadhttp://www.csanyigroup.com/category/strucni-tekstovi/energy-and-power/feedhttp://www.csanyigroup.com/technical-articles/categories/energy-and-powerhttp://www.csanyigroup.com/category/strucni-tekstovi/cables/feedhttp://www.csanyigroup.com/technical-articles/categories/category-cableshttp://www.csanyigroup.com/category/autocad/feedhttp://www.csanyigroup.com/technical-articles/category-autocadhttp://www.csanyigroup.com/category/strucni-tekstovi/ansi-standards/feedhttp://www.csanyigroup.com/technical-articles/category-ansi-standardshttp://www.csanyigroup.com/ups-design-criteria-and-selection#comment-913http://www.csanyigroup.com/cascading#comment-1551http://www.csanyigroup.com/cascading#comment-1552http://www.csanyigroup.com/field-test-procedure-for-protective-relays#comment-1704
  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    12/13

    12/15/2014 Visual Inspection Of The Transformer | CsanyiGroup

    http://www.csanyigroup.com/visual-inspection-of-the-oil-transformer 12

    Links

    Direktorijum Kvalitetnih Srpskih Sajtova

    Visitors

    Portal Content

    ePlusMenuCAD | DevelopmentElectric Power Books

    Technical Articles

    Electrical Design Software & Tools

    AutoCAD | Video Training

    Engineering Knowledge

    Translate to your language

    Hindi

    Arabic

    Filipino

    ive Traffic Feed

    eal-time view Menu

    visitor from Malaysia viewed Motor

    Operation Efficiency Under Abnorma...13

    ins agovisitor from Cordoba, Argentina viewed

    ePlusMenuCAD | CsanyiGroup22 mins ago

    visitor from Ho Chi Minh City, Vietnam

    iewed General about motors | CsanyiGroup

    28 mins agovisitor from Lagos viewed "Visual Inspection Of

    he Transformer | CsanyiGroup" 28 mins ago

    visitor from Kennesaw, Georgia viewed

    "Caterpillar C175 Diesel Generator |CsanyiGroup"32 mins agovisitor from Oran viewed "AutoCAD Video

    raining | CsanyiGroup" 36 mins ago

    visitor from Islamabad viewed "Field Test

    rocedure For Protective Relays | CsanyiGroup"

    52 mins agovisitor from New York viewed "ANSI/IEC

    elay Symbols | CsanyiGroup" 56 mins ago

    visitor from Louisville, Kentucky viewed "Guide

    o Low Voltage Busbar Trunking Systems (1) |

    CsanyiGroup" 56 mins ago

    visitor from United States viewed "ANSI/IECelay Symbols | CsanyiGroup" 59 mins ago

    visitor from Ho Chi Minh City, Ho Chi Minh

    iewed "General about motors | CsanyiGroup" 1 hr

    http://feedjit.com/freeLiveTrafficFeed/?utm_source=ltf&utm_medium=web&utm_campaign=ltfCampaignhttp://live.feedjit.com/live/csanyigroup.com/0/http://live.feedjit.com/live/csanyigroup.com/0/http://live.feedjit.com/live/csanyigroup.com/0/http://www.csanyigroup.com/guide-to-low-voltage-busbar-trunking-systems-1http://www.csanyigroup.com/guide-to-low-voltage-busbar-trunking-systems-1http://www.csanyigroup.com/guide-to-low-voltage-busbar-trunking-systems-1http://www.csanyigroup.com/ansi-iec-relay-symbolshttp://www.csanyigroup.com/field-test-procedure-for-protective-relayshttp://www.csanyigroup.com/download/autocad-traininghttp://www.csanyigroup.com/download/autocad-traininghttp://www.csanyigroup.com/download/autocad-traininghttp://www.csanyigroup.com/visual-inspection-of-the-oil-transformerhttp://www.csanyigroup.com/eplusmenucadhttp://www.csanyigroup.com/eplusmenucadhttp://www.csanyigroup.com/general-about-motorshttp://www.csanyigroup.com/ansi-iec-relay-symbolshttp://www.csanyigroup.com/guide-to-low-voltage-busbar-trunking-systems-1http://www.csanyigroup.com/ansi-iec-relay-symbolshttp://www.csanyigroup.com/field-test-procedure-for-protective-relayshttp://www.csanyigroup.com/download/autocad-traininghttp://www.csanyigroup.com/caterpillar-c175-diesel-generatorhttp://www.csanyigroup.com/visual-inspection-of-the-oil-transformerhttp://www.csanyigroup.com/general-about-motorshttp://www.csanyigroup.com/eplusmenucadhttp://www.csanyigroup.com/motor-operation-efficiency-under-abnormal-conditionshttp://feedjit.com/freeLiveTrafficFeed/?utm_source=ltf&utm_medium=web&utm_campaign=ltfCampaignhttp://live.feedjit.com/live/csanyigroup.com/0/http://live.feedjit.com/live/csanyigroup.com/0/http://www.bluehost.com/track/wordfence/fjnew1http://feedjit.com/?utm_source=ltf&utm_medium=web&utm_campaign=ltfCampaignhttp://bit.ly/cmLdvYhttp://bit.ly/aSwFZUhttp://bit.ly/cZZsoMhttp://www.webserbia.net/
  • 8/10/2019 Visual Inspection of the Transformer _ CsanyiGroup

    13/13


Recommended