    Voltage Quality Improvement Using DVR

    Abstract:-

    The problem of voltage sags and Swells and its severe impact on

    sensitive loads is well known. To solve this problem, custom power devices

    are used. One of those devices is the Dynamic Voltage Restorer (DVR),

    which is one of the most efficient and effective modern custom power

    devices used in power distribution networks. This paper described DVR

    principles and voltage correction methods for balanced and/or unbalanced

    voltage sags and swells in a distribution system. Simulation results were

    presented to illustrate and understand the performances of DVR under

    voltage sags/swells conditions. The results obtained by simulation using

    MATLAB confirmed the effectiveness of this device in compensating

    voltage sags and swells with very fast response (relative to voltage sag/swell

    time).

    1.Introduction

    Power quality has a significant influence on high-technology

    equipments related to communication, advanced control, automation, precise

    manufacturing technique and on-line service. For example, voltage sag can

    have a bad influence on the products of semiconductor fabrication with

    considerable financial losses. Power quality problems include transients,

    sags, interruptions and other distortions to the sinusoidal waveform. One of

    the most important power quality issues is voltage sag that is a sudden short

    duration reduction in voltage magnitude between 10 and 90% compared to

    nominal voltage. Voltage sag is deemed as a momentary decrease in the rms

    voltage, with duration ranging from half a cycle up to one minute. Deep

    voltage sags, even of relatively short duration, can have significant costs

    because of the proliferation of voltage-sensitive computer-based and

    variable speed drive loads. The fraction of load that is sensitive to low

    voltage is expected to grow rapidly in the coming decades.

  • 8/8/2019 Voltage Quality Improvement DVR

    2/30

    Studies have shown that transmission faults, while relatively rare, can cause

    widespread sags that may constitute a major source of process interruptions

    for very long distances from the faulted point. Distribution faults are

    considerably more common but the resulting sags are more limited in

    geographic extent. The majority of voltage sags are within 40%of the

    nominal voltage. Therefore, by designing drives and other critical loads

    capable of riding through sags with magnitude of up to 40%, interruption of

    processes can be reduced significantly. The DVR can correct sags resulting

    from faults in either the transmission or the distribution system.

    Faults at either the transmission or distribution level may cause voltage

    sag or swell in the entire system or a large part of it. Also, under heavy load

    conditions, a significant voltage drop may occur in the system. Voltage sagscan occur at any instant of time, with amplitudes ranging from 10 90%and

    a duration lastingfor half a cycle to one minute. Further, they could be either

    balanced or unbalanced, depending on the type of fault and they could have

    unpredictable magnitudes, depending on factors such as distance from the

    fault and the transformer connections. Voltage swell, on the other hand, is

    defined as a sudden increasing of supply voltage up 110% to 180% in RMS

    voltage at the network fundamental frequency with duration from 10 ms to 1

    minute. Voltage swells are not as important as voltage sags because they are

    less common in distribution systems. Voltage sag and swell can cause

    sensitive equipment (such as found in semiconductor or chemical plants) to

    fail, or shutdown, as well as create a large current unbalance that could blow

    fuses or trip breakers. These effects can be very expensive for the customer,

    ranging from minor quality variations to production downtime and

    equipment damage.

    There are many different methods to mitigate voltage sags and

    swells, but the use of a custom Power device is considered to be the most

    efficient method. The concept of custom Power was introduced by N.G.

    Hingorani in 1995. Like Flexible AC Transmission Systems (FACTS) fortransmission systems, the term custom power pertains to the use of power

    electronics controllers in a distribution system, especially, to deal with

    various power quality problems. Just as FACTS improves the power transfer

    capabilities and stability margins, custom power makes sure customers get

    pre-specified quality and reliability of supply. This pre-specified quality may

    contain a combination of specifications of the following:

  • 8/8/2019 Voltage Quality Improvement DVR

    3/30

    low phase unbalance, no power interruptions, low flicker at the load

    voltage, low harmonic distortion in load voltage, magnitude and duration of

    overvoltages and undervoltages within specified limits, acceptance of

    fluctuations, and poor factor loads without significant effect on the terminal

    voltage.

    Each of Custom Power devices has its own benefits and limitations.

    Dynamic Voltage Restorer (DVR) is one of the most effective type of these

    devices. There are numerous reasons why the DVR is preferred over the

    others. A few of these reasons are presented as follows. The SVC pre-dates

    the DVR, but the DVR is still preferred because the SVC has no ability to

    control active power flow. Another reason is that the DVR costs less

    compared to the UPS. Other reasons include that the DVR has a higher

    energy capacity and lower costs compared to the SMES device.

    Furthermore, the DVR is smaller in size and costs less compared to the

    DSTATCOM. Based on these reasons, it is no surprise that the DVR iswidely considered as an effective custom power device in mitigating voltage

    sags. In addition to voltage sags and swells compensation, DVR can also

    added other features such as harmonics and Power Factor correction.

    Compared to the other devices, the DVR is clearly considered to be one of

    the best economic solutions for its size and capabilities.

    This paper Introduced Dynamic Voltage Restorer (DVR) and its

    operating principle. Then, analyses of the voltage correction methods were

    presented. At the end, simulation results using MATLAB were illustrated

    and discussed.

    1.1 What Are Voltage Sags?

    Electronic devices function properly as long as the voltage (or driving force)

    of the electricity feeding the device stays within a consistent range. There

    are several types of voltage fluctuations that can cause problems, including

    surges and spikes, sags, harmonic distortions, and momentary disruptions.(For definitions of these terms, see the Power Quality Glossary sidebar,

    next page.) A voltage sag is not a complete interruption of power; it is a

    temporary drop below 90 percent of the nominal voltage level. Most voltage

    sags do not go below 50 percent of the nominal voltage, and they normally

    last from 3 to 10 cyclesor 50 to 170 milliseconds.

  • 8/8/2019 Voltage Quality Improvement DVR

    4/30

    Voltage sags are probably the most significant power quality (PQ) problem

    facing industrial customers today, and they can be a significant problem for

    large commercial customers as well.

    There are two sources of voltage sags: external (on the utilitys lines

    up to your facility) and internal (within your facility). Utilities continuously

    strive to provide the most reliable and consistent electric power possible. In

    the course of normal utility operations, however, many things can cause

    voltage sags. Storms are the most common cause of external sags and

    momentary interruptions in most areas of the U.S. A storm passing through

    an area can result in dozens of major and minor PQ variations, including

    sags. For example, consider how PQ would be affected by a lightning strike

    on or near a power line or by wind sending tree limbs into power lines.

    Other common causes of external voltage sags are ice storms, animals

    (particularly squirrels), and the start-up of large loads at neighboringfacilities. Internal causes of voltage sags can include starting major loads

    and grounding or wiring problems. Whether or not a voltage sag causes a

    problem will depend on the magnitude and duration of the sag and on the

    sensitivity of your equipment. Many types of electronic equipment are

    sensitive to voltage sags, including variable speed drive controls, motor

    starter contactors, robotics, programmable logic controllers, controller power

    supplies, and control relays. Much of this equipment is used in applications

    that are critical to an overall process, which can lead to very expensive

    downtime when voltage sags occur. If your facility is having frequent

    voltage sag problems, a good place to start is with your utility. Ask about the

    utilitys statistics regarding performance in your area. You should also look

    into possible internal causes. But whether the causes are mainly external or

    internal, you should consider taking charge of the problem and working

    toward a costeffective solution for your facility.

    1.2 Power Quality Glossary:

    Although specialists use complex equations for precise descriptions and

    analysis, the following definitions are adequate for most discussions.

    Harmonic distortion:Continuous or sporadic distortions of the 60-hertz (Hz) voltage sine waveform, usually caused by microprocessorbased

  • 8/8/2019 Voltage Quality Improvement DVR

    5/30

    loads in the building such as computer power supplies, lighting ballasts, and

    electronic adjustable speed drives. Harmonics can

    also be transmitted from an energy user down the block. These can cause

    telecommunications or computer interference; overheating

    in motors, transformers, or neutral conductors; decreased motor

    performance; deterioration of power factorcorrection capacitors; or

    erratic operation of breakers, fuses, and relays.

    Interruption, momentary:A very short loss of utility power thatlasts up to 2 seconds, usually caused by the utility switching operations

    to isolate a nearby electrical problem.

    Interruption, temporary:A loss of utility power lasting from 2seconds to 2 minutes, caused by a nearby short circuit due to something

    like animals, wet insulators, or accidents. Corrected by automated utility

    switching.

    Long-term outage: A loss of utility power lasting more than 2minutes due to major local, area, or regional electrical events.

    Noise:Sporadic voltage changes consisting of frequencies higher than thenormal 60-Hz power frequency due to any number of

    causes, including arc welders, loose wiring, and nearby radio and TV

    transmitters.

    Sag:A short-term decrease in voltage lasting anywhere from millisecondsup to a few seconds. Sags starve a machine of the electricity

    it needs to function, causing computer crashes or equipment lock-ups.

    Usually caused by equipment start-upsuch as elevators,

    heating and air-conditioning equipment, compressors, and copy machines

    or nearby short circuits on the utility system.

    Spike: A very brief (nanoseconds to milliseconds) change in voltageranging from tens to thousands of volts. Can be produced by

    utility and customer equipment operations, nearby lightning strikes, falling

    tree limbs on power lines, and even static discharges.

    Surge: A short-term increase in voltage, lasting up to a few seconds.They are due either to customer equipment operation, such as

  • 8/8/2019 Voltage Quality Improvement DVR

    6/30

    air conditioners or motors switching on and off, or to utility activities, such

    as capacitor switching.

    Transient: A sudden momentary change in voltage. Also called a spike.

    Undervoltage:A decrease in voltage lasting longer than a few seconds.Usually due to undersized wiring at the facility but can also

    be caused by overloaded utility circuits and result in brownouts.

    2. Dynamic Voltage Restorer (DVR)

    A Dynamic Voltage Restorer (DVR) is a series connected solid state

    device that injects voltage into the system in order to regulate the load side

    voltage. The DVR was first installed in 1996. It is normally installed in a

    distribution system between the supply and the critical load feeder. Its

    primary function is to rapidly boost up the load-side voltage in the event of a

    disturbance in order to avoid any power disruption to that load. There are

    various circuit topologies and control schemes that can be used to implement

    a DVR. In addition to voltage sags and swells compensation, DVR can alsoadded other features such as: line voltage harmonics compensation,

    reduction of transients in voltage and fault current limitations.

    The general configuration of the DVR consists of an Injection /Booster

    transformer, a Harmonic filter, a Voltage Source Converter (VSC), and a

    Control and Protection system as shown in Figure 1.

  • 8/8/2019 Voltage Quality Improvement DVR

    7/30

    Fig. 1 DVR series connected topology

    2.1 Injection/Booster Transformer

    The Injection /Booster transformer is a specially designed transformer that

    attempts to limit the coupling of noise and transient energy from the primary

    side to the secondary side. Its main tasks are: connects the DVR to the

    distribution network via the HV-windings and transforms and couples the

    injected compensating voltages generated by the voltage source converters

    to the incoming supply voltage. In addition, the Injection / Booster

    transformer serves the purpose of isolating the load from the system (VSC

    and control mechanism). It is one unit three phase construction.

    2.2 Harmonic Filter

    The main task of harmonic filter is to keep the harmonic voltage

    content generated by the voltage source converters to the permissible level

  • 8/8/2019 Voltage Quality Improvement DVR

    8/30

    (i.e., eliminate high frequency switching harmonics).It has a small rating

    approximately 2% of the load MVA.

    2.3 Voltage Source Converter

    A VSC is a power electronic system consists of a storage device

    and switching devices, which can generate a sinusoidal voltage at any

    required frequency, magnitude, and phase angle. In the DVR application, the

    VSC is used to temporarily replace the supply voltage or to generate the part

    of the supply voltage which is missing.

    Numerous circuit topologies are available for the VSC. A widely

    used method is the two level or multilevel three-phase converter which

    shares a dc capacitor between all phases. The purpose of this capacitor ismainly to absorb harmonic ripple and hence it has a relatively small energy

    storage requirement, particularly when operating in balanced conditions. The

    size of this capacitor has to be increased if needed to provide voltage support

    in unbalanced conditions. Also, as the capacitor is shared between the three

    phases, a sag on only one phase may cause a distortion in the injected

    current waveforms on the other phases.

    2.3.1 Switching Devices

    There are four main types of switching devices: Metal Oxide Semiconductor

    Field Effect Transistors (MOSFET), Gate Turn-Off thyristors (GTO),

    Insulated Gate Bipolar Transistors (IGBT), and Integrated Gate Commutated

    Thyristors (IGCT). Each type has its own benefits and drawbacks. The

    MOSFET requires a high on-resistance and has fast switching times. It is

    capable of working beyond the 20 kHz frequency. The limitations are that

    the increasing on-resistance with increasing voltage limits the device to

    applications with just a few hundred volts. The GTO is a latching device thatcan be turned off by a negative pulse of current to its gate. The GTO is best

    suited for high voltage applications. The disadvantages of the GTO are that

    GTO based devices are not able to meet the dynamic requirements of a

    DVR. The IGBT is considered to be a newer device compared to the

    MOSFET and GTO. It was first introduced in the early 1980s and has

    become a popular device because of its superior characteristics.

  • 8/8/2019 Voltage Quality Improvement DVR

    9/30

    In essence, it is a three terminal controllable switch that combines the fast

    switching times of the MOSFET with the high voltage capabilities of the

    GTO. The result of this combination is a medium speed controllable switch

    capable of supporting the medium power range. The IGCT is a recent

    compact device with enhanced performance and reliability that allows

    building VSC with very large power ratings. Because of the highly

    sophisticated converter design with IGCTs, the DVR can compensate dips

    which are beyond the capability of the past DVRs using conventional

    devices.

    2.3.2 Storage Devices

    The purpose is to supply the necessary energy to the VSC via a dclink for the generation of injected voltages. Batteries and Ultracapacitors are

    the most common types of energy storage devices. In fact, the capacity of

    the stored energy directly determines the duration of the sag which can be

    mitigating by the DVR. Batteries are the common choice and can be highly

    effective if a high voltage battery configuration is used. This high voltage

    string of batteries can be placed across the regulated dc bus with little or no

    additional circuitry. However, batteries in general have a short lifetime and

    often require some type of battery management system, which can be quite

    costly. An interesting alternative to batteries is the use of ultracapacitors,which have a wider voltage range than batteries and can be directly

    paralleled across the input bus. Ultracapacitors have a specific energy

    density less than that of a battery, but a specific power greater than a battery,

    making them ideal for short (up to several seconds) pulses of power. Certain

    ultracapacitors (unsyrnmetrical electrochemical) can hold charge over

    extended periods of time, so as to act like a battery. However, unlike

    batteries, these ultracapacitors have a short charge time and much longer

    lifetime.

    2.4 Control and Protection system

    The control mechanism of the general configuration typically consists of

    Digital Signal Processing (DSP) boards. The software on the DSP board

  • 8/8/2019 Voltage Quality Improvement DVR

    10/30

    provides the controls such as detection and correction. Filters are commonly

    used for these purposes. The most common types of filter algorithm are the

    Fourier Transform (FT) and the Wavelet Transform (WT). Although, the

    Fourier Transform still remains the most common type.

    To maximize dynamic performance, a direct feedforward-type control

    architecture should be applied in the control concept of the DVR. With this

    concept a fast response time (approximately 1ms) can be achieved to

    compensate voltage sags.

    All protective functions of the DVR should be implemented in the

    software. Differential current protection of the transformer, or short circuit

    current on the customer load side are only two examples of many protection

    functions possibility. Depending on the particular fault condition, the fast

    control and protection may switch the DVR into bypass if it becomes

    inoperable, thus securing an uninterrupted energy flow to the customers

    plant.

    Basic Principle of DVR:

    To quantify voltage sag in radial distribution system, the voltage divider

    model, shown in Fig. 1, can be used on the assumption that the fault current

    is much larger than the load current during faults. The point of common

    coupling (PCC) is the point from which both the fault and the load are fed.Voltage sag is mostly unbalanced and accompanied by phase angle jump.

  • 8/8/2019 Voltage Quality Improvement DVR

    11/30

    From Fig. 1, the voltage at the PCC and phase angle jump can be obtained

    by

    The DVR is able to compensate the voltage sag especially at sensitive loads

    by injecting an appropriate voltage through an injection transformer. Figure

    2 shows a block diagram of the DVR power circuit. When examining the

    DVR it can be divided into four component blocks:

    1) Energy storage device,

    2) DC to DC power controller,

    3) A three-phase voltage converter,

    4) Three single-phase series injection transformers.

    The design of the DVR allows real and reactive power to be either supplied

    or absorbed when operating. If a small fault occurs on the protected system,

    then the DVR can correct it using only reactive power generated internally.

    For correction of larger faults, the DVR may be required to develop realpower. To enable the development of real power an energy storage device

    must be used; currently the DVR design uses a capacitor bank. Once the

    fault has been corrected and the supply is operating under normal conditions,

    the DVR replenishes the energy expended from the healthy system. The

    rating (in terms of energy storage capabilities) of the capacitor bank is

    dependent upon system factors such as the rating of the load that protects

  • 8/8/2019 Voltage Quality Improvement DVR

    12/30

    and the duration and depth of anticipated sags. When correcting large sag

    (using real power), the power electronics are fed from the capacitor bank via

    a DC-DC voltage conversion circuit.

    The core element in DVR design is the three-phase voltage converter. This

    inverter utilizes solid-state power electronics (insulated gate bipolar

    transistors, IGBTs) to convert DC to AC and back again during operation.

    The DVR connects in series with the distribution line through an injection

    transformer, actually three single-phase transformers. The primary side

    (connected into the line) must be sized to carry the full line current.The

    primary voltage rating is the maximum voltage the DVR can inject into the

    line for a given application.The DVR rating (per phase), is the maximum

    injection voltage times the primary current.The bridge outputs on the

    secondary are filtered before being applied to the injection transformer. The

    bridges are independently controllable to allow each phase to becompensated separately. The output voltage wave shapes are generated by

    pulse-width modulated switching. When voltage sag reaches a value below

    the limit for correction using zero energy, the energy storage system within

    the DVR has to be used to aid voltage correction.

    The ideal restoration is to make load voltages unchanged. When DVR

    restores large voltage disturbances, active power or energy should be

    injected from DVR to distribution system. If the capability of energy storage

    of DVR were infinite, DVR could maintain load voltage unchanged ideally

    during any kind of faults. However, the stored energy in DVR is limitedpractically by the limit of DC link capacity of DVR. Namely, DVR cannot

    restore the load voltage constantly when the voltage across the DC link has

    gone down and stored energy has run out eventually during deep voltage sag

    with long duration. Therefore, it is necessary to minimize energy injection

    from DVR.

    There are several methods how to inject DVR mitigating voltage to

    distribution system: pre-sag compensation, in-phase compensation, and

    phase advance

  • 8/8/2019 Voltage Quality Improvement DVR

    13/30

    3. Operating Principle of DVR

    The basic function of the DVR is to inject a dynamically controlled voltage

    VDVRgenerated by a forced commutated converter in series to the bus voltage

    by means of a booster transformer. The momentary amplitudes of the threeinjected phase voltages are controlled such as to eliminate any detrimental

    effects of a bus fault to the load voltage VL. This means that any differential

    voltages caused by disturbances in the ac feeder will be compensated by an

    equivalent voltage generated by the converter and injected on the medium

    voltage level through the booster transformer.

    The DVR works independently of the type of fault or any event that

    happens in the system, provided that the whole system remains connected to

    the supply grid, i.e. the line breaker does not trip. For most practical cases, a

    more economical design can be achieved by only compensating the positiveand negative sequence components of the voltage disturbance seen at the

    input of the DVR (because for a typical distribution bus configuration, the

    zero sequence part of a disturbance will not pass through the step down

    transformer which has infinite impedance for this component).

    The DVR has two modes of operation which are: standby mode and

    boost mode. In standby mode (VDVR=0), the booster transformers low

    voltage winding is shorted through the converter. No switching of

    semiconductors occurs in this mode of operation, because the individual

    converter legs are triggered such as to establish a short-circuit path for the

    transformer connection. Therefore, only the comparatively low conductionlosses of the semiconductors in this current loop contribute to the losses. The

    DVR will be most of the time in this mode. In boost mode (VDVR>0), the

    DVR is injecting a compensation voltage through the booster transformer

    due to a detection of a supply voltage disturbance.

    4. DVR Voltage correction Methods

    The possibility of compensating voltage sag can be limited by a number

    of factors including finite DVR power rating, different load conditions and

    different types of voltage sag. Some loads are very sensitive to phase angle

    jump and others are tolerant to it. Therefore, the control strategy depends on

    the type of load characteristics. There are three different methods for DVR

    voltage correction which are presented below.

  • 8/8/2019 Voltage Quality Improvement DVR

    14/30

    4.1 Pre-Dip Compensation (PDC)

    The PDC method tracks the supply voltage continuously and

    compensates load voltage during fault to pre-fault condition. In this method,

    the load voltage can be restored ideally, but the injected active power cannot

    be controlled and it is determined by external conditions such as the type of

    faults and load conditions. This method is achieved by using a fault detector

    to freeze the output from the Phase Locked Loop (PLL) circuit, when the

    fault occurs. Then, the frozen angle is used to restore the previous balanced

    load voltages by using the Park transform. The lack of the negative sequence

    detection in this method leads to the phase-oscillation in the case of single-

    line faults. Fig. 2 shows the single-phase vector diagram of this method.

    L

    DVR

    S

    LV

    DVRV

    LI

    sV

    Fig. 2 Single-phase vector diagram of the PDC method.

  • 8/8/2019 Voltage Quality Improvement DVR

    15/30

    According to fig.2, the apparent power of DVR is,

    ( )SLSLSLL

    DVRLDVR

    VVVVI

    VIS

    +=

    =

    cos2

    3

    22

    And the active power of DVR is,

    ( )SSLLLDVR VVIP coscos3 =

    The magnitude and the angle of DVR voltage are:

    . ( )SLSLSLDVR VVVVV += cos222

    = SSLL

    SSLL

    DVR

    VV

    VV

    coscos

    sinsintan

    1

    4.2 In-Phase Compensation (IPC)

    This is the most straight forward and used method in which the injected

    DVR voltage is in phase with the supply side voltage regardless of the load

    current and the pre-fault voltage as shown in Fig. 3. The IPC method is

    suitable for minimum voltage or minimum energy operation strategies. Inother word, this approach requires large amounts of real power to mitigate

    the voltage sag, which means a large energy storage device.

  • 8/8/2019 Voltage Quality Improvement DVR

    16/30

    L DVR

    SLV

    DVRV

    LI

    dipLpreV

    SV

    Fig. 3 phasors diagram of the IPC method

    According to fig.3, the apparent power of DVR is,

    ( )SLLDVRLDVR VVIVIS == 33

    And the active power of DVR is,

    ( )SSLLSDVRLDVR

    VVIVIP cos3cos3 ==

    The magnitude and the angle of the DVR voltage are,

    SDVR

    SLDVRVVV

    =

    =

  • 8/8/2019 Voltage Quality Improvement DVR

    17/30

    4.3 In Phase Advance Compensation (IPAC)

    Pre-Dip and in-phase compensation method must inject active power

    to loads to correct voltage disturbance. However, the amount of possible

    injection active power is confined to the stored energy in DC link, which is

    one of the most expensive components in DVR. Due to the limit of energy

    storage capacity of DC link, the DVR restoration time and performance are

    confined in these methods.

    For the sake of controlling injection energy, in phase advance

    compensation method was proposed. The injection active power is made

    zero by means of having the injection voltage phasor perpendicular to theload current phasor. This method can reduce the consumption of energy

    stored in DC link by injecting reactive power instead of active power.

    Reducing energy consumption means that ride-through ability is increased

    when the energy storage capacity is fixed. On the other hand, the injection

    voltage magnitude of in-phase advance compensation method is larger than

    those of pre-dip or in-phase compensation methods and the voltage phase

    shift can cause voltage waveform discontinuity, inaccurate zero crossing and

    load power swing. Therefore, in phase advance compensation method should

    be adjusted to the load that is tolerant to phase angle jump, or transition

    period should be taken while phase angle is moved from pre-fault angle to

    advance angle.

    In short, IPAC method uses only reactive power and unfortunately, not

    al1 the sags can be mitigated without real power, as a consequence, this

    method is only suitable for a limited range of sags.

    5. Simulation

    In order to show the performance of the DVR in voltage sags and swells

    mitigation, a simple distribution network is simulated using MATLAB

    (fig.1).Voltage sags and swells are simulated by temporary connection of

  • 8/8/2019 Voltage Quality Improvement DVR

    18/30

    different impedances at the supply side bus. A DVR is connected to the

    system through a series transformer with a capability to insert a maximum

    voltage of 50% of the phase to ground system voltage. Apart from this, a

    series filter is also used to remove any high frequency components of power.

    In this simulation the In-Phase Compensation (IPC) method is used. Theload considered in the study is a 5.5 MVA capacity with 0.92 p.f., lagging.

    5.1 Voltage Sags

    A case of Three-phase voltage sag is simulated and the results are shown in

    Figure 4. Figure 4 (a) shows a 50% voltage sag initiated at 100 ms and it is

    kept until 300 ms, with total voltage sag duration of 200 ms. Figure 4 (b)

    and (c) show the voltage injected by the DVR and the compensated load

    voltage, respectively. As a result of DVR, the load voltage is kept at 1 p.u.throughout the simulation, including the voltage sag period. Observe that

    during normal operation, the DVR is doing nothing. It quickly injects

    necessary voltage components to smooth the load voltage upon detecting

    voltage sag.

    In order to understand the performance of the DVR under unbalanced

    conditions, Single-phase voltage sag at supply bus bar is simulated and the

    results are shown in Figure 5. The supply voltage with one phase voltage

    dropped down to 50% is shown in Figure 5 (a). The DVR injected voltage

    and the load voltage are shown in Figure 5 (b) and (c), respectively. As can

    be seen from the results, the DVR is able to produce the required voltagecomponents for different phases rapidly and help to maintain a balanced and

    constant load voltage at 1.00 p.u.

  • 8/8/2019 Voltage Quality Improvement DVR

    19/30

    (a)

    (b)

  • 8/8/2019 Voltage Quality Improvement DVR

    20/30

    (c)

    Fig. 4 Three-phase voltages sag: (a)-Source voltage, (b)-Injected

    voltage, (c)-Load voltage

    (a)

  • 8/8/2019 Voltage Quality Improvement DVR

    21/30

    (b)

    (c)

    Fig. 5 Single-phase voltage sag: (a)-Source voltage, (b)-Injected

    voltage, (c)-Load voltage.

    (a)

  • 8/8/2019 Voltage Quality Improvement DVR

    22/30

    (b)

    (c)

    Fig. 6 Three-phase voltages swell: (a)-Source voltage, (b)-Injected

    voltage, (c)-Load voltage

    (a)

  • 8/8/2019 Voltage Quality Improvement DVR

    23/30

    (b)

    (c)

    Fig. 7 Two-phase voltages swell: (a)-Source voltage, (b)-Injected

    voltage, (c)-Load voltage

  • 8/8/2019 Voltage Quality Improvement DVR

    24/30

    5.2 Voltage Swells

    The performance of DVR for a voltage swell condition is

    investigated. Here, the supply voltage swell is generated as shown in

    Figure 6 (a). The supply voltage amplitude is increased about 125% ofnominal voltage. The injected voltage that is produced by DVR in order to

    correct the load voltage and the load voltage are shown in Figure 6 (b) and

    (c), respectively. As can be seen from the results, the load voltage is kept at

    the nominal value with the help of the DVR. Similar to the case of voltage

    sag, the DVR reacts quickly to inject the appropriate voltage component

    (negative voltage magnitude) to correct the supply voltage.

    The performance of the DVR with an unbalanced voltage swell is

    shown in Figure 7. In this case, two of the three phases are higher by 25%

    than the third phase as shown in Figure 7(a). The injected voltage that isproduced by DVR in order to correct the load voltage and the load voltage

    are shown in Figure 7 (b) and (c), respectively. Notice the constant and

    balanced voltage at the load throughout the simulation, including during the

    unbalanced voltage swell event.

    6.Multilevel Dynamic Voltage Restorer:

    High voltage dynamic voltage restorer (HVDVR) is used in power

    distribution network to compensate for sags in utility voltages. The proposed

    HVDVR is implemented using a multilevel inverter topology with isolated

    dc energy storages, allowing the directconnection of the HVDVR to the distribution network without using a bulky

    and costly series injection transformer. A control algorithm, incorporating

    P+resonant and Posicast compensators, is also presented for controlling the

    HVDVR with perfect reference voltage tracking and effective damping of

    transient voltage oscillations at the instant of sag compensation. Finally,

  • 8/8/2019 Voltage Quality Improvement DVR

    25/30

    simulation results are presented to verify the performance of the proposed

    multilevel HVDVR.

    Figure shows the series connection of a dynamic voltage restorer

    (DVR) between the utility source and loads, through a coupling transformer.

    During normal operating conditions, the DVR can be switched offline [1] or

    controlled to compensate for any injected harmonic voltages in the utility

    grid [2]. Upon the occurrence of voltage sag, the DVR is commanded to

    inject a voltage Vo such that the magnitude of Vl remains essentially

    constant throughout the sag period. However, the phase of Vl can either be

    shifted or remain unchanged, depending on the compensation techniques

    adopted. Conventionally, the series voltage Vo is injected through a

    coupling transformer, Fig. 1, whose main functions are to provide voltageboosting and electrical isolation between the phases. Usage of a transformer,

    however, has the disadvantage of making the DVR bulky and costly, and

    other disadvantages, as summarized in [1]. To overcome these

    disadvantages, [1] has proposed the series/parallel connection of

    semiconductor switches, or H-bridges, to develop high voltage DVR

    (HVDVR), which can be connected directly to the utility grid without a

    coupling transformer. This letter now extends the concept to address issues

    that have not been discussed in [1].

    (Note that only the series connection of H-bridges is considered here, since

    the other option of series-connecting semiconductor switches usually require

    the use of complex snubber and gate driver circuitries, which can limit the

    speed of response of the HVDVR).

  • 8/8/2019 Voltage Quality Improvement DVR

    26/30

    Fig. System configuration with dynamic voltage restoration.

    The letter begins by analyzing different topological possibilities for

    implementing the HVDVR with the main aim of designing a reliable custom

    power conditioner. The letter next presents an open-loop control schemewith Posicast compensator [3] incorporated for damping transient voltage

    oscillations at the instant of voltage injection (an issue which has not been

    actively investigated for DVR). The Posicast-based open-loop control is

    subsequently improved by adding a parallel multi-feedbackloop control path

    to give two-degrees-of-freedom in control tuning. This feedback path uses

    the P resonant compensator to force the steady-state voltage error to zero,

  • 8/8/2019 Voltage Quality Improvement DVR

    27/30

    hence, enhancing the DVR load voltage regulation performance. All

    principles presented have been verified in Matlab/Simulink simulation using

    a cascaded five-level and a binary seven-level inverter.

    Fig.2. Direct connection of multilevel HVDVR to utility grid.

    6.1 TOPOLOGY OF MULTILEVEL HVDVR:

    Fig. 2 shows the single-phase representation of a HVDVR

    implemented using multiple series-connected H-bridges, each with its own

    isolated dc energy storage. This inverter arrangement is commonly referred

    to as multilevel inverter in the power conversion literature, and its overall

  • 8/8/2019 Voltage Quality Improvement DVR

    28/30

    output voltage Vinv is given by the sum of voltages Vi ( i=1 to N ) of the

    H-bridges. Depending on its switching state, the output of each H-bridge can

    assume the three discrete dc voltage levels of +Vdc , 0 V and -Vdc. When

    series-connected, the resultant output Vinv of the multilevel inverter can

    then switch among a greater number of voltage levels, giving rise to an

    improved waveform quality. In addition, depending on the dc capacitor

    potentials used, the total number of voltage levels that can be assumed by

    Vinv varies, giving rise to four types of multilevel inverters, namely,

    cascaded [5], binary [6], [7], quasilinear [7] and tri-nary [7] inverters (the

    latter three inverters are referred to as hybrid inverters in this letter). The dc

    source potentials needed for implementing these inverters and expressions

    for their total number of output voltage levels are summarized in TableI.

    TABLE IDC CAPACITOR VOLTAGES AND NUMBER OF OUTPUT VOLTAGE

    LEVELS OF DIFFERENT MULTILEVEL INVERTERS (N = NUMBER OF H-

    BRIDGES)

    Referring to Table I and Fig. 2, it is noted that the output voltage of a hybrid

    inverter can assume a larger number of dc voltage levels than a cascaded

    inverter with the same number of series-connected H-bridges, by designing

    its upper H-bridges to block higher dc voltages (kN > kn > k1) .

    Therefore, the upper H-bridges of a hybrid inverter should be implemented

  • 8/8/2019 Voltage Quality Improvement DVR

    29/30

    using high-voltage thyristor-based power devices [e.g., integrated gate

    commutated thyristors (IGCTs)], while the lower H-bridges should be

    implemented using fast-switching power devices [e.g., insulated gate bipolar

    transistors (IGBTs)], as indicated in Fig. 2 [6]. In addition, the switching

    frequencies of the H-bridges should vary with the lowest H-bridge (with dc

    link voltage of K1Vdc ) pulse-width modulated at a high switching

    frequency, and while moving up the inverter phase-leg in Fig. 2, each H-

    bridge should be switched at a progressively slower switching frequency.

    Naturally, hybrid inverters offer the attractive advantage of significantly

    improving the inverter harmonic performance using the same number of H-

    bridges as a cascaded inverter. However, when considering cases of

    semiconductor failure, hybrid inverters are less reliable (especially trinary

    inverter) since a fault in the higher voltage H-bridge will significantly limit

    the sag compensation ability of the HVDVR and also increase the overall

    inverter harmonic content. With a greater emphasis on reliability rather thanharmonic performance, the HVDVR studied in this letter is therefore

    implemented using either a cascaded five-level inverter or a binary seven-

    level inverter with two series-connected H-bridges.

  • 8/8/2019 Voltage Quality Improvement DVR

    30/30

    CONCLUSION

    In this paper an overview of DVR is presented. DVR is an

    effective custom power device for voltage sags and swells

    mitigation. The impact of voltage sags on sensitive equipment issevere. Therefore, DVR is considered to be an efficient solution

    due to its relatively low cost and small size, also it has a fast

    dynamic response.

    The simulation results show clearly the performance of a

    DVR in mitigating voltage sags and swells. The DVR handles both

    balanced and unbalanced situations without any difficulties and

    injects the appropriate voltage component to correct rapidly any

    anomaly in the supply voltage to keep the load voltage balancedand constant at the nominal value.