CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/7: 1 DCPL-11Z02
VOLUME: IIIC
SCHEDULE‐IIIC/7
LOCAL CONTROL BOARDS/PANELS LOCAL ISOLATING SWITCH UNITS
AND LOCAL PUSH BUTTON STATIONS 1.0 EQUIPMENT 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Construction a) Degree of protection : b) Sheet metal thickness mm : c) Floor channel sills, vibration damping pads and kick plate furnished? : 1.5 Equipment Mounting a) All Supervision relays, with flag
indicator are flush mounted ? : 1.6 Nameplate a) Material : b) Thickness : c) Size for - Equipment : Panels : 1.7 Internal Illumination a) Volt : b) Watt : c) Door switch controlled : 1.8 Space Heater
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/7: 2 DCPL-11Z02
a) Volt : b) Watt : c) Thermostat Controlled ? : 1.9 Plug Socket a) Type : b) Rating : 1.10 Illumination, space heater & plug socket circuits provided with individual switch fuse units ? : 1.11 A.C./D.C. Supply Type & rating of isolating switch fuse units for - a) Incoming A.C. supply : b) Incoming D.C. supply : 1.12 Internal Wiring a) Wire type : b) Voltage grade : c) Conductor material : d) Conductor size for - i) Current/control circuit : ii) Voltage circuit : e) Wires identified at both ends with ferrules ? : 1.13 Terminal block a) Make : b) Type/Catalogue No. : c) 20% spare terminals furnished? : 1.14 Ground Bus
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/7: 3 DCPL-11Z02
a) Materials : b) Size mm : 1.15 Painting a) Type of finish : b) Colour Shade - Inside/ Outside : c) Details of painting procedure furnished ? : 1.16 Mimic a) Material : b) Width : 2.0 LAMPS 2.1 Make : 2.2 Type : 2.3 Reference Standard : 2.4 Voltage : 2.5 15% Extra lamps furnished ? : 3.0 AUXILIARY RELAYS Make Type Cat. No. 3.1 General Service A.C. Relay : 3.2 General Service D.C. Relay : 3.3 General Service Latch Relay : 3.4 Heavy Duty AC & DC Relay : 3.5 Timers - Electronic plug- in Type Version : 3.6 Circuit Supervision A.C. relay : 3.7 Circuit Supervision D.C. relay : 4.0 SWITCHES A.C. D.C. 4.1 Load Break Switch
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/7: 4 DCPL-11Z02
a) Make : b) Type : c) Reference Standard : d) Breaking Current at 415V A.C. or 220V D.C. : i) : ii) : iii) : iv) : 4.2 Breaker Control Switch a) Make : b) Type : c) Reference Standard : d) Contact Development as per specification Drawing ? : Yes/No e) Contact Rating 240V A.C. 220V D.C. i) Make & Continuous Amp. : ii) Break (Inductive) Amp. : 4.3 Meter Selector Switch a) Make : b) Type : c) Reference Standard : d) Contact Rating 240V A.C. 220V D.C. i) Make & Continuous Amp. : ii) Break (Inductive) Amp. : 5.0 FUSE 5.1 Make :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/7: 5 DCPL-11Z02
5.2 Type : 5.3 Reference Standard : 5.4 Rupturing Capacity KA rms (Sym) :
5.5 Continuous current at 50 Deg.C
ambient and within cubicle Amps. : 5.6 Cut-off currents KA peak : 5.7 Fuse characteristics furnished
for various fuse rating ? : 6.0 PUSH BUTTON 6.1 Make : 6.2 Type : 6.3 Reference Standard : 6.4 Contact Rating : 240V A.C. 220V D.C. a) Make & Continuous Amps. : b) Break (Inductive) Amps. : 6.5 No. & type of contacts provided per button : 7.0 INDICATING INSTRUMENT Ammeter Voltmeter 7.1 Make : 7.2 Type : 7.3 Reference Standard : 7.4 Type of Movement : 7.5 Accuracy class : 7.6 Scale in Degrees :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/7: 6 DCPL-11Z02
7.7 VA Burden a) Current Coil : b) Voltage Coil : 8.0 ANNUNCIATOR 8.1 Make & model : 8.2 Type : 8.3 Reference Standard : 8.4 Sequence designation : 8.5 No. of windows per group : 8.6 Overall dimension of a group (mm) : 8.7 Detailed write-up furnished ? : 9.0 TEMPERATURE SCANNER 9.1 Make & model : 9.2 Type : 9.3 Reference Standard : 9.4 No. of points per scanner : 9.5 Common alarm relay provided ? : 9.6 Overall dimension (mm) : 9.7 Detailed write-up furnished ? : 9.8 Rating of output contacts : 9.9 No. of 4-20 mA outputs provided : 10.0 CONTACTORS 10.1 Make : 10.2 Type : 10.3 Reference Standard : 10.4 Duty class :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/7: 7 DCPL-11Z02
10.5 Utilization category : 10.6 Pair of Contacts/contactor : 10.7 Contact rating 204V A.C. 220V D.C. a) Make and continuous Amp : b) Break (inductive) Amp : 11.0 LOCAL PUSH BUTTON STATION 11.1 Make : 11.2 Type : 11.3 Enclosure : 11.4 Degree of protection : 11.5 Local Push Button Station enclosure furnished with : a) Inscription plate : b) Knock out for cable/circuit entry : c) Cable entry from bottom/side only : Yes/No 11.6 Contacts of each push button a) Number furnished :
b) Current rating make & continuous break (inductive) :
11.7 Stop P.B having provision of
locking in lockout position :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 1 DCPL-11Z02
VOLUME: IIIC
SCHEDULE‐IIIC/8
GENERATOR TRANSFORMER, UNIT TRANSFORMER
STANDBY TRANSFORMER AND HT AUXILIARY TRANSFORMER
A. GENERATOR TRANSFORMER 1.0 General 1.1 Make : 1.2 Type : 1.3 Number of Winding per Phase : 1.4 Number of Phase : 1.5 Number of Unit per set : 1.6 Reference Standard : 2.0 Rating 2.1 Type of Cooling : 2.2 Rated Output MVA :
i) With ONAN Cooling :
ii) With ONAF Cooling :
iii) With OFAN Cooling :
iv) With OFAF Cooling : 2.3 Rated Voltage KV
H.V. :
L.V. : 2.4 Rated Current Amps.
H.V :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 2 DCPL-11Z02
L.V. :
2.5 Rated Frequency Hz : 2.6 Connection
H.V. :
L.V. : 2.7 Vector Group Reference : 2.8 Voltage Withstand Time Sec.
a) 110% of rated voltage :
b) 125% of rated voltage :
c) 140% of rated voltage :
d) 150% of rated voltage : 2.9 Overfluxing Capability
a) For Overfluxing Factor 1.1... Sec. :
b) 1.25 ..Sec. :
c) 1.4….Sec. : 3.0 Temperature 3.1 Reference Ambient Temperature : 3.2 Temperature rise over
reference ambient Deg.C :
a) Of Top oil by thermometer :
b) Of winding by resistance :
3.3 Maximum continuous over
loading capacity of the transformer without exceeding the specified winding temperature :
4.0 Tappings 4.1 Type :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 3 DCPL-11Z02
4.2 Capacity : 4.3 Range - Steps x % Variation : 4.4 Taps provided on HV/LV Winding : 5.0 Insulation Level KVp/KV 5.1 H.V. : 5.2 L.V. : 5.3 H.V. Neutral : 5.4 L.V. Neutral : 6.0 Impedances at Principal Tap
at Rated Frequency and 75 Deg.C winding temperature % :
6.1 Base MVA : 6.2 Impedance : 6.3 Reactance : 6.4 Resistance at 75 Deg.C : 6.5 Zero Sequence Impedance at 75 Deg.C : 6.6 Capacitance of Windings micro farad/phase :
a) H.V. - Earth :
b) L.V. - Earth :
c) H.V. - L.V. : 7.0 Guaranteed Losses at
Principal Tap, Full Load and 75 Deg.C KW :
7.1 No load losses : 7.2 Load losses : 7.3 Cooler losses : 7.4 Tolerance on losses : 8.0 Efficiency at 75 Deg.C and
0.8 Power Factor Lag % :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 4 DCPL-11Z02
8.1 At full load : 8.2 At 3/4 full load : 8.3 At 1/2 full load : 8.4 Maximum Efficiency : 8.4.1 Load and Power Factor at
which it occurs : 9.0 Regulation at Full Load at 75 Deg.C % : 9.1 At unity power factor : 9.2 At 0.8 power factor lagging : 10.0 No Load Current referred to HV Amps. : 10.1 At 90% rated voltage : 10.2 At 100% rated voltage : 10.3 At 110% rated voltage : 10.4 At 125% rated voltage : 10.5 At 140% rated voltage : 11.0 Approximate Maximum Flux density Web/Sq.m :
11.1 At 90% rated voltage : 11.2 At 100% rated voltage : 11.3 At 110% rated voltage : 11.4 At 125% rated voltage : 11.5 At 140% rated voltage : 12.0 Maximum Current Density Amps/Sq.cm : 12.1 H.V. Winding : 12.2 L.V. Winding : 13.0 Withstand Time without
injury for Sec.
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 5 DCPL-11Z02
13.1 Three phase dead short- circuit at terminal with rated voltage maintained on the other side :
13.2 Single phase short-circuit
at terminal with rated voltage maintained on other side :
14.0 Cooling System 14.1 a) No. x Capacity of
cooling unit furnished :
b) No. of cooling units required for full load operation :
14.2 Each Cooling Unit is
provided with :
a) No. x KW of oil pump motor :
b) No. x KW of fan motor :
c) No. of standby fan : d) No. of standby oil pumps :
14.3 Motors rated for voltage-
phase-frequency : 14.4 Automatic Operation of
cooler pumps and fans provided ? :
14.5 Transformer is capable of
delivering rated output under following conditions : a) Failure of all pumps and fans of one cooling unit :
i) Continuous in % rated, MVA :
ii) Rated output for... min. :
b) Failure of one complete cooling unit including radiator, fans, pumps etc. :
i) Continuous in % rated, MVA :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 6 DCPL-11Z02
ii) Rated output for ... min. :
c) Failure of fans and pumps of all the cooler units :
i) Continuous in % rated, MVA :
ii) Rated output for... min. :
d) Failure of complete cooling system including radiators, fans, pumps, etc. :
i) Continuous in % rated, MVA : ii) Rated output for... min. : 14.6 Schematic Flow Diagram of the Cooling System Furnished ? : 14.7 Oil Pumps
a) Make : b) Type : c) Catalogue Furnished :
15.0 Details of Tank 15.1 Material : 15.2 Thickness of sides mm : 15.3 Thickness of bottom mm : 15.4 Thickness of cover mm : 15.5 Tank Designed for :
Vacuum : ...... mm of Hg
Pressure : ...... 16.0 Core 16.1 Type - Core or shell : 16.2 Core material : 16.3 Thickness of lamination mm : 16.4 Insulation of lamination : 16.5 Equivalent cross-sectional area:
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 7 DCPL-11Z02
17.0 Coils 17.1 Type of Coil :
a) H.V. : b) L.V. : 17.2 Conductor Material : 17.3 Insulating Material :
a) H.V. - Turn :
b) L.V. - Turn :
c) L.V. - Earth :
d) H.V. - L.V. :
e) H.V. Earth : 18.0 Tap Changer 18.1 Make : 18.2 Type : 18.3 Rated Voltage KV : 18.4 Rated Current Amps. : 18.5 Auxiliary Power KW : 18.6 Time required for one step
change Secs. : 18.7 Rated Voltage Volts :
a) Tap-change motor :
b) Control circuit : 18.8 Control
a) Manual/Local Electrical/ Remote Electrical :
b) Group/Solo :
18.9 Voltage Control
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 8 DCPL-11Z02
Automatic/Non-automatic : 18.10 Provision for parallel
operation Yes/No : 18.11 Maximum Short Circuit Current withstand capability :
a) Current :
b) Time :
18.12 Loose equipment and provisions for remote control furnished as per specification ? : 18.13 Local manual operation feasible from
standing height from ground ? : 18.14 Local indicator furnished for :
a) Tap position :
b) Operation counter : 18.15 In case of off-circuit tap changer :
a) Padlocking provided : Yes/No b) Auxiliary switch for interlock provided : Yes/No
c) Safety limit switch provided : Yes/No d) Discrepancy detector provided : Yes/No 18.16 In case of On-load tap changer :
A . Interlocks as per specification provided : Yes/No
B. a) Voltage Regulating relay provided :
i) Make : ii) Type : iii) Sensitivity (Dead band) and nominal value range : iv) Timer range :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 9 DCPL-11Z02
v) Literature furnished ? :
b) Under voltage Relay :
i) Voltage range : ii) Timer range : 19.0 Insulating Oil 19.1 Approximate volume Litre : 19.2 10% excess oil furnished ? : 19.3.1 Oil conforms to : 19.3.2 Details of oil furnished : 19.4 a) Oil preservation system provided ? :
b) Type :
20.0 Bushings H V/LV HVN/LVN 20.1 Make : 20.2 Type : 20.3 Reference Standard : 20.4 Voltage class KV : 20.5 Type of atmosphere : 20.6 Creepage Distance mm : 20.7 Weight : 20.8 Free space required for
bushing removal : 20.9 Test terminals for H.V.
bushing provided ? : 20.10 One minute power frequency withstand voltage KV rins : 20.11 Impulse withstand voltage KV peak : 21.0 Minimum Clearance 21.1 Between Phases :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 10 DCPL-11Z02
a) In air
i) HV mm : ii) LV mm : b) In oil
i) HV mm :
ii) LV mm 21.2 Between Phase & Earth : a) In air
i) HV mm : ii) LV mm : b) In oil
i) HV mm :
ii) LV mm : 22.0 Terminal Connections 22.1 H.V. : 22.2 L.V. : 22.3 H.V. Neutral : 22.4 L.V. Neutral : 23.0 Marshalling Box 23.1 Weatherproof, suitable for
outdoor duty : 23.2 Degree of protection : 24.0 Terminal Blocks 24.1 Make : 24.2 Type : 24.3 20% spare terminals furnished ? : 25.0 Wiring 25.1 Cable type : 25.2 Voltage grade Volt :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 11 DCPL-11Z02
25.3 Conductor Size Sq.mm : Material Cu. : Stranded Yes/No : 26.0 Trip and Alarm Contacts Ratings
220V D.C
240V A.C.
26.1 Voltage Volt : 26.2 Rated Amps. :
Making Current : Breaking Current (Inductive Breaking) :
Each transformer furnished with fittings and accessories as per specification ? Yes/No:
28.0 Detail of Conservator 28.1 Volume of Conservator : 28.2 Volume of oil between the
highest and lowest levels : 29.0 Pressure Release Device a) Minimum pressure the device is set
to operation/rupture KN/Sq.m : b) Alarm and trip contacts provided : 30.0 Spare Parts
Each transformer furnished with spare parts as per specification :
31.0 Approximate Overall Dimension 31.1 Length mm : 31.2 Breadth mm : 31.3 Height mm : Crane lift (a) for untanking core and coil
assembly (including sling) (b) tank cover
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 12 DCPL-11Z02
in case of Bell type tank mm : 32.0 Approximate Weights 32.1 Core and Coil Kg. : 32.2 Tank cover for Bell type tank Kg. : 32.3 Tank and fittings Kg. : 32.4 Oil Kg. : 32.5 Total Weight Kg : 33.0 Shipping Data 33.1 Weight of the heaviest package Kg. :
33.2 Dimension of the largest
package (L x B x H) mm : 34.0 Tests to be conducted on
each Transformer 34.1 Routine tests as per speci-
fication/relevant standard : 34.2 Tank pressure test on each
transformer :
a) Test Pressure KN/Sq.m:
b) Duration Hours :
c) Permanent deflection : 34.3 Tank vacuum test on each transformer :
a) Vacuum KN/Sq.m :
b) Duration Hours :
c) Permanent deflection : 34.4 Oil leak test on each transformer :
a) Test pressure :
b) Duration :
34.5 Core bolt withstand voltage for 1 minute on each transformer KV :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 13 DCPL-11Z02
35.0. NEUTRAL CURRENT TRANSFORMER 35.1 General 35.2 Make : 35.3 Type : 35.4 Reference Standard : 35.5 Use : 35.6 Rating a) C.T. Ratio : b) Class : c) Insulation level : d) Burden : 35.7 Insulation Class a) Temperature rise at rated burden over
top oil temperature Deg.C : 35.8 Characteristics a) Secondary resistance Rct Ohm at 75 Deg.C :
b) Knee point voltage Vk Volt : c) Excitation current at Vk/2 Amps. : 35.9 Dimensions and Weights a) Dimension (L x B x H) mm : b) Weight Kg. : c) Tests As per Standard ? :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 14 DCPL-11Z02
B. UNIT TRANSFORMER, STANDBY TRANSFORMER AND HT AUXILIARY TRANSFORMER
UNIT TRANSF.
STANDBY TRANSF.
HT AUX. TRANSF.
1.0 General 1.1 Make : 1.2 Type : 1.3 Number of Winding per Phase : 1.4 Number of Phase : 1.5 Number of Unit per set : 1.6 Reference Standard : 2.0 Rating 2.1 Type of Cooling : 2.2 Rated Output MVA :
i) With ONAN Cooling :
ii) With ONAF Cooling :
iii) With OFAN Cooling :
iv) With OFAF Cooling : 2.3 Rated Voltage KV
H.V. :
L.V. : 2.4 Rated Current Amps.
H.V :
L.V. : 2.5 Rated Frequency Hz : 2.6 Connection
H.V. :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 15 DCPL-11Z02
UNIT TRANSF.
STANDBY TRANSF.
HT AUX. TRANSF.
L.V. :
2.7 Vector Group Reference : 2.8 Voltage Withstand Time Sec.
a) 110% of rated voltage :
b) 125% of rated voltage :
c) 140% of rated voltage :
d) 150% of rated voltage : 2.9 Overfluxing Capability
a) For Overfluxing Factor 1.1... Sec. :
b) 1.25 ..Sec. :
c) 1.4….Sec. : 3.0 Temperature 3.1 Reference Ambient Temperature : 3.2 Temperature rise over
reference ambient Deg.C :
a) Of Top oil by thermometer :
b) Of winding by resistance :
3.3 Maximum continuous over
loading capacity of the transformer without exceeding the specified winding temperature :
4.0 Tappings 4.1 Type : 4.2 Capacity : 4.3 Range - Steps x % Variation :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 16 DCPL-11Z02
4.4 Taps provided on HV/LV Winding : UNIT
TRANSF. STANDBY TRANSF.
HT AUX. TRANSF.
5.0 Insulation Level KVp/KV 5.1 H.V. : 5.2 L.V. : 5.3 H.V. Neutral : 5.4 L.V. Neutral : 6.0 Impedances at Principal Tap
at Rated Frequency and 75 Deg.C winding temperature % :
6.1 Base MVA : 6.2 Impedance : 6.3 Reactance : 6.4 Resistance at 75 Deg.C : 6.5 Zero Sequence Impedance at 75 Deg.C : 6.6 Capacitance of Windings micro farad/phase :
a) H.V. - Earth :
b) L.V. - Earth :
c) H.V. - L.V. : 7.0 Guaranteed Losses at
Principal Tap, Full Load and 75 Deg.C KW :
7.1 No load losses : 7.2 Load losses : 7.3 Cooler losses : 7.4 Tolerance on losses : 8.0 Efficiency at 75 Deg.C and
0.8 Power Factor Lag % : 8.1 At full load :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 17 DCPL-11Z02
8.2 At 3/4 full load :
UNIT TRANSF.
STANDBY TRANSF.
HT AUX. TRANSF.
8.3 At 1/2 full load : 8.4 Maximum Efficiency : 8.4.1 Load and Power Factor at
which it occurs : 9.0 Regulation at Full Load at 75 Deg.C % : 9.1 At unity power factor : 9.2 At 0.8 power factor lagging : 10.0 No Load Current referred to HV Amps. : 10.1 At 90% rated voltage : 10.2 At 100% rated voltage : 10.3 At 110% rated voltage : 10.4 At 125% rated voltage : 10.5 At 140% rated voltage : 11.0 Approximate Maximum Flux density Web/Sq.m :
11.1 At 90% rated voltage : 11.2 At 100% rated voltage : 11.3 At 110% rated voltage : 11.4 At 125% rated voltage : 11.5 At 140% rated voltage : 12.0 Maximum Current Density Amps/Sq.cm : 12.1 H.V. Winding : 12.2 L.V. Winding : 13.0 Withstand Time without
injury for Sec.
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 18 DCPL-11Z02
13.1 Three phase dead short- UNIT
TRANSF. STANDBY TRANSF.
.
HT AUX. TRANSF.
circuit at terminal with rated voltage maintained on the other side :
13.2 Single phase short-circuit
at terminal with rated voltage maintained on other side :
14.0 Cooling System 14.1 a) No. x Capacity of
cooling unit furnished :
b) No. of cooling units required for full load operation :
14.2 Each Cooling Unit is
provided with :
a) No. x KW of oil pump motor :
b) No. x KW of fan motor :
c) No. of standby fan : d) No. of standby oil pumps : 14.3 Motors rated for voltage-
phase-frequency : 14.4 Automatic Operation of
cooler pumps and fans provided ? :
14.5 Transformer is capable of
delivering rated output under following conditions : a) Failure of all pumps and fans of one cooling unit :
i) Continuous in % rated, MVA :
ii) Rated output for... min. :
b) Failure of one complete cooling unit including radiator, fans, pumps etc. :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 19 DCPL-11Z02
UNIT TRANSF.
STANDBY TRANSF.
HT AUX. TRANSF.
i) Continuous in % rated, MVA : ii) Rated output for ... min. :
c) Failure of fans and pumps of all the cooler units :
i) Continuous in % rated, MVA :
ii) Rated output for... min. :
d) Failure of complete cooling system including radiators, fans, pumps, etc. :
i) Continuous in % rated, MVA : ii) Rated output for... min. : 14.6 Schematic Flow Diagram of the Cooling System Furnished ? : 14.7 Oil Pumps
a) Make :
b) Type :
c) Catalogue Furnished : 15.0 Details of Tank 15.1 Material : 15.2 Thickness of sides mm : 15.3 Thickness of bottom mm : 15.4 Thickness of cover mm : 15.5 Tank Designed for :
Vacuum : ...... mm of Hg
Pressure : ...... 16.0 Core 16.1 Type - Core or shell :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 20 DCPL-11Z02
16.2 Core material :
UNIT TRANSF.
STANDBY TRANSF.
HT AUX. TRANSF.
16.3 Thickness of lamination mm : 16.4 Insulation of lamination : 16.5 Equivalent cross-sectional area: 17.0 Coils 17.1 Type of Coil :
a) H.V. : b) L.V. : 17.2 Conductor Material : 17.3 Insulating Material :
a) H.V. - Turn :
b) L.V. - Turn :
c) L.V. - Earth :
d) H.V. - L.V. : e) H.V. Earth : 18.0 Tap Changer 18.1 Make : 18.2 Type : 18.3 Rated Voltage KV : 18.4 Rated Current Amps. : 18.5 Auxiliary Power KW : 18.6 Time required for one step
change Secs. : 18.7 Rated Voltage Volts :
a) Tap-change motor :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 21 DCPL-11Z02
b) Control circuit :
UNIT TRANSF.
STANDBY TRANSF.
HT AUX. TRANSF.
18.8 Control :
a) Manual/Local Electrical/ Remote Electrical :
b) Group/Solo :
18.9 Voltage Control
Automatic/Non-automatic : 18.10 Provision for parallel
operation Yes/No :
18.11 Maximum Short Circuit Current withstand capability :
a) Current :
b) Time : 18.12 Loose equipment and provisions for remote control furnished as per
specification ? : 18.13 Local manual operation feasible from
standing height from ground ? : 18.14 Local indicator furnished for :
a) Tap position :
b) Operation counter : 18.15 In case of off-circuit tap changer :
a) Padlocking provided : Yes/No b) Auxiliary switch for interlock provided : Yes/No
c) Safety limit switch provided : Yes/No d) Discrepancy detector provided : Yes/No 18.16 In case of On-load tap changer :
A . Interlocks as per specification provided : Yes/No
B. a) Voltage Regulating relay
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 22 DCPL-11Z02
provided :
UNIT TRANSF.
STANDBY TRANSF.
HT AUX. TRANSF.
i) Make : ii) Type : iii) Sensitivity (Dead band) and nominal value range : iv) Timer range : v) Literature furnished ? :
b) Under voltage Relay : i) Voltage range : ii) Timer range : 19.0 Insulating Oil 19.1 Approximate volume Litre : 19.2 10% excess oil furnished ? : 19.3.1 Oil conforms to : 19.3.2 Details of oil furnished : 19.4 a) Oil preservation system provided ? :
b) Type :
20.0 Bushings H V/LV HVN/LVN 20.1 Make : 20.2 Type : 20.3 Reference Standard : 20.4 Voltage class KV : 20.5 Type of atmosphere : 20.6 Creepage Distance mm : 20.7 Weight :
20.8 Free space required for
bushing removal :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 23 DCPL-11Z02
20.9 Test terminals for H.V. bushing provided ? :
UNIT
TRANSF. STANDBY TRANSF.
HT AUX. TRANSF.
20.10 One minute power frequency withstand voltage KV rins : 20.11 Impulse withstand voltage KV peak : 21.0 Minimum Clearance 21.1 Between Phases :
a) In air i) HV mm : ii) LV mm : b) In oil
i) HV mm :
ii) LV mm 21.2 Between Phase & Earth : a) In air
i) HV mm : ii) LV mm : b) In oil
i) HV mm : ii) LV mm : 22.0 Terminal Connections 22.1 H.V. : 22.2 L.V. : 22.3 H.V. Neutral : 22.4 L.V. Neutral : 23.0 Marshalling Box 23.1 Weatherproof, suitable for
outdoor duty : 23.2 Degree of protection :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 24 DCPL-11Z02
24.0 Terminal Blocks
UNIT TRANSF.
STANDBY TRANSF.
HT AUX. TRANSF.
24.1 Make : 24.2 Type : 24.3 20% spare terminals furnished ? : 25.0 Wiring 25.1 Cable type : 25.2 Voltage grade Volt : 25.3 Conductor Size Sq.mm : Material Cu. : Stranded Yes/No : 26.0 Trip and Alarm Contacts Ratings
220V D.C
240V A.C.
26.1 Voltage Volt : 26.2 Rated Amps. :
Making Current : Breaking Current (Inductive Breaking) : 27.0 Accessories
Each transformer furnished with fittings and accessories as per specification ? Yes/No:
28.0 Detail of Conservator 28.1 Volume of Conservator : 28.2 Volume of oil between the
highest and lowest levels : 29.0 Pressure Release Device a) Minimum pressure the device is set
to operation/rupture KN/Sq.m :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 25 DCPL-11Z02
b) Alarm and trip contacts provided :
UNIT TRANSF.
STANDBY TRANSF.
HT AUX. TRANSF.
30.0 Spare Parts
Each transformer furnished with spare parts as per specification :
31.0 Approximate Overall Dimension 31.1 Length mm : 31.2 Breadth mm : 31.3 Height mm : Crane lift (a) for untanking core and coil
assembly (including sling) (b) tank cover in case of Bell type tank mm :
32.0 Approximate Weights 32.1 Core and Coil Kg. : 32.2 Tank cover for Bell type tank Kg. : 32.3 Tank and fittings Kg. : 32.4 Oil Kg. : 32.5 Total Weight Kg : 33.0 Shipping Data 33.1 Weight of the heaviest package Kg. :
33.2 Dimension of the largest
package (L x B x H) mm : 34.0 Tests to be conducted on
each Transformer 34.1 Routine tests as per speci-
fication/relevant standard : 34.2 Tank pressure test on each
transformer :
a) Test Pressure KN/Sq.m:
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 26 DCPL-11Z02
UNIT
TRANSF. STANDBY TRANSF.
HT AUX. TRANSF.
b) Duration Hours :
c) Permanent deflection : 34.3 Tank vacuum test on each transformer :
a) Vacuum KN/Sq.m :
b) Duration Hours :
c) Permanent deflection : 34.4 Oil leak test on each transformer :
a) Test pressure :
b) Duration :
34.5 Core bolt withstand voltage for 1 minute on each transformer KV : 35.0. NEUTRAL CURRENT TRANSFORMER 35.1 General 35.2 Make : 35.3 Type : 35.4 Reference Standard : 35.5 Use : 35.6 Rating a) C.T. Ratio : b) Class : c) Insulation level : d) Burden : 35.7 Insulation Class a) Temperature rise at rated burden over
top oil temperature Deg.C :
CPCPL-Super Critical TPP-Tharangambadi [2 x 660 MW] Main Plant Package Sch-IIIC/8: 27 DCPL-11Z02
UNIT TRANSF.
STANDBY TRANSF.
HT AUX. TRANSF.
35.8 Characteristics a) Secondary resistance Rct Ohm at 75 Deg.C :
b) Knee point voltage Vk Volt : c) Excitation current at Vk/2 Amps. : 35.9 Dimensions and Weights a) Dimension (L x B x H) mm : b) Weight Kg. : c) Tests As per Standard ? :