Designed to Meet Worldwide StandardsDesigned to Meet Worldwide Standards
• Agency Certification– Listed to UL508C and CAN/CSA-C2.2– Listed to UL508C for plenums– Marked for applicable European Directives
• Designed to meet the appropriate portions of the following specifications:– NFPA 70 – US National Electrical Code– NEMA ICS 3.1 – Safety standards for Construction and Guide for Selection,
Installation and Operation of Adjustable Speed Drive Systems– IEC 146 – International Electrical Code– Seismic requirements of the 2003 International Building Code as specified by
AC156
SpecificationsSpecifications
• Ratings:– 2-100HP (208V ac)– 3-200HP (480V ac)
• Short Circuit Rating:– 200,000Amps Symmetrical
• Efficiency:– 97.5% at rated amps, nominal line voltage
• Displacement Power Factor:– 0.98 across speed range
• Carrier (PWM) Frequency:– 2 to 10kHz (drive rating based upon 4kHz)
Control I/OControl I/O
2 – 25HP @ 208V ac
3 – 50HP @ 480V ac(frames B, C, D, E)
30 – 100HP @ 208V ac
60 – 200HP @ 480V ac(frames 4, 5, 6)
Digital Inputs(Run, Clear Fault, Enable, Purge, PI Enable, Etc.)
(6) Programmable, 24VDC (6) Programmable, 24VDC
Relay Outputs(Fault, Run, Ready, Alarm, At Speed, Current Limit, Etc.)
(2) Programmable Form C (2) Programmable Form C
Analog Inputs(Speed Reference, PI Feedback, Etc.)
(1) Non-Isolated (voltage or current)(1) Isolated, Bipolar (voltage or current)
(2) Isolated, Bipolar (voltage or current)
Analog Outputs(Output Freq, Output Amps, Output Power, PI Ref, Etc.)
(1) 0-10VDC (1) Bipolar +/-10V or 4-20mA
Hardware Features – FilteringHardware Features – Filtering
• EMC Filtering– Supplied with all ratings
– Internal Filter allows EN61800-3 Second Environment Levels to be met • Common Mode Filtering
– Common mode cores supplied with all ratings – help attenuate common mode noise– Common mode capacitors supplied with all ratings – provide low impedance path
World Class Motor ProtectionWorld Class Motor Protection
• Reflected Wave issues (also known as Standing Wave or transmission Line Effect) have been well documented in IGBT based drives
• This phenomenon can cause significant voltage peaks at the motor that present the possibility for insulation breakdown
• Rockwell Automation engineers have devoted years of research to develop industry-leading solutions for VTAC Drives– This has resulted in patented Software &
Hardware features that protect motors with long motor leads
– Each pulse is measured and controlled to avoid collisions with other reflected voltage pulses thus minimizing voltage amplification
– These solutions are supported with hundreds of hours of lab tests!
Hardware Features – Internal Bus InductorHardware Features – Internal Bus Inductor
• Provided with Every Rating: – 5HP and larger @ 208V ac– 7.5HP and larger @ 480V ac
• Supplied in pos. & neg. leg• Reduces Harmonics• Helps with transient
protection• Effective Impedance
– 3% (min) 7.5 - 50HP @ 480V ac– 5% (min) 60 - 200HP @ 480Vac
TDD - VTAC 9 vs. Leading Competitor
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.45
0 10 20 30 40 50 60
Motor Frequency at rated load (Hz)
Cu
rren
t d
isto
rtio
n (
TD
D)
TDD VTAC 9
Leading Competitor
THD VTAC 9 vs. Leading Competitor
0.00%
20.00%
40.00%
60.00%
80.00%
100.00%
120.00%
0 10 20 30 40 50 60 70
Motor Frequency at rated load (Hz)
Cu
rren
t D
isto
rtio
n (
TH
D)
VTAC 9
Leading Competitor
Operator KeypadOperator Keypad
• 5 Line LCD Keypad• Removable• Icon Based Programming• Multi-Language• Quick Start Feature• Password Protectable
Main Menu:
Diagnostics
Parameter
Device Select
0.00
F-> Stopped Ready A
Hz.
F Stopped Auto
- Fault - F05Overvoltage
Time Since Fault1:10:07
Main Menu:
Diagnostics
Parameter
Device Select
0.00
F-> Stopped Ready A
Hz.
F Stopped Auto
Fault Pop Up Parameter Edit
Operator KeypadOperator Keypad
Operating Status
Direction Indication
Menu, Programming Screen
Alarm Annunciation
Password Status
Auto / Hand Mode Status
Function Key Operation
Operator KeypadOperator Keypad
Horizontal Scroll Keys
Speed Control and Vertical Scroll Keys
Stop Key and Fault Reset
Start Operation
Enter Key
Escape / Program
Release Hand Reference Control
Configurable Function Keys
Enable Hand Reference Control
Main Menu Icons
Start-Up Parameters Control SourceSelect Diagnostics Display
1. Quickstart2. Input Voltage3. Motor Data4. Motor Tests5. Speed Limits6. Ref Setup7. Configure I/O8. Done
P Numbers Logic ControlRef Control
FaultsAlarmsReg VersionOIM VersionStatus Info
LanguageMonitorF KeysDrive IDDisplay Timeout
QS CSS
Device Select PasswordMemory
Reset DefaultsLoad from DriveLoad to DriveActive User Set
Keypad IconsKeypad Icons
Start Up Icon provides access to Quick Start Utility that allows for fast, easy set-up involving seven parameter groups.
Parameter Icon provides quick access to drive and peripheral component parameters.
Control Source Icon allows control and reference selection.
Diagnostic Icon provides information on faults and alarms.
Display Icon allows operators to configure the OIM for language, monitoring, function keys and other considerations.
Memory Icon allows operators to load and save different parameters sets into the OIM and, subsequently into the drive or to restore factory-set defaults.
Device Select Icon allows operators to identify and select the drive or peripheral device from which to obtain data.
Password Icon provides protection against modifications of all writable parameters by a unauthorized user and selects parameter access levels.
Icons provide users a intuitive interface as well as a logical method of grouping access to drive functions and operations
Programming – File, Group, ElementProgramming – File, Group, Element
Monitor************MeteringDrive Data
Motor Control****************Motor DataTorq AttributesVolts per Hertz
Speed Command*********************Spd Mode & LimitsSpeed ReferencesDiscrete SpeedsSpeed trimSlip CompProcess PI
Dynamic Control*********************Ramp RatesLoad LimitsStop/Brake ModesRestart ModesPower Loss
Utility*****************Reverse ConfigHIM ConfigMOP ConfigDrive Memory DiagnosticsFaultsAlarms
Communication*******************Comm ControlMasks & OwnersData Links
Inputs & Outputs*****************Analog InputsAnalog OutputsDigital InputsDigital OutputsPulse I/O
HVAC FeaturesHVAC Features
• Programmable Acceleration Time with S-Curve– Less mechanical stress on machinery and motors
• Skip Frequencies– 3 “Critical Avoidance” operating points– No continuous operation at these points
• Restart Modes– Line Loss – determines action after power is restored– Fault Conditions – Reset/Run allows certain faults to be automatically reset– Long Term Power Loss – Run on power-up
• Sleep-Wake Mode– Drive starts when analog signal greater than user-specified level
• PI Loop– Uses process feedback to compare against setpoint– Adjusts output Hz
HVAC FeaturesHVAC Features
• Flying Start– Reconnect to a spinning motor
• Shear Pin– Current limit adjustment for load and mechanical protection
• Purge Input– Overrides stop signal across network
• Intelligent Thermal Management– Carrier frequency reduction on overtemperature
• Electronic Motor Overload– Based on programmed motor FLA– Class 10 protection
TroubleshootingTroubleshooting
• Status LED– Flashing Green = Ready– Solid Green = Running
– Flashing Yellow = Start Inhibits– Solid Yellow = Alarm Condition Exists
– Flashing Red = Recoverable Fault– Solid Red = Non
Recoverable Fault
• Power LED• Viewable through the cover
Main Menu:DiagnosticsParameterDevice Select
0.00Auto
F-> Faulted
Hz.-- Fault-- F06M otor Stalled
Tim e since fault1:06:03
TroubleshootingTroubleshooting
• Alarms– User-Configurable: Alert operator of condition if left
untreated, may lead to fault condition– Non-Configurable: Alert operator of condition caused
by improper programming
• Faults– Auto-Reset/Run: Auto Restart can be used to attempt
to clear fault– Non-Resettable: Normally requires drive or motor
repair– User-Configurable: Enabled or disabled to annunciate
or ignore a fault
Drive Monitoring and Configuration SoftwareDrive Monitoring and Configuration Software
• V*S Utilities Software • Windows Explorer look and feel
– Left side tree view– Right side parameter list– HTML help
• Parameter Upload / Download– Configure parameter settings– Monitor I/O activity– Compare Files
• Monitor multiple drives when they’re on a communication network• Supported PC Operating Systems
– Windows 95/98/2000/NT
3 Contactor Full Feature Bypass with 3 Contactor Full Feature Bypass with DisconnectDisconnect
• Door interlock fused disconnect with Class J fuses– Some competitors offer disconnect switch which requires
upstream short-circuit branch protection• 100,000 AIC rating for direct connection to high capacity
power distribution lines– Some competitors offer circuit breaker which has AIC rating of 14-
20KA• 3 contactor bypass with Drive/DriveTest/Bypass modes
– Allows troubleshooting/programming of drive while in bypass– Some competitors offer 2 contactor bypass which does not allow
Drive to be electrically isolated should service be required• Bypass Control and Status Display provides quick visual
indication of drive/bypass status through LED’s and schematic diagram
• Class 20 motor overload protection in bypass circuit
• Single customer terminal block for all field wiring• Dedicated Purge Input for connection to fire and
life safety system• Switch for Hand/Off/Auto
– Hand = Keypad– Off = Off– Auto = Communication port or terminal block
• Remote activation of bypass
3 Contactor Full Feature Bypass with 3 Contactor Full Feature Bypass with DisconnectDisconnect
3 Contactor Full Feature Bypass with 3 Contactor Full Feature Bypass with DisconnectDisconnect
1
2
3
4
56
7
8
9
1
2
3
4
5
6
7
8
9
10
Bypass Control and Status Display
Bypass Control and Status Display Board
Drive Main Input Contactor
Drive Motor Output Contactor
Drive Bypass Contactor
Bypass Motor Overload Relay
115V AC Control Transformer
Field Control Wiring Terminal Block
Door Interlocked Main Input Disconnect
Main Input Disconnect Handle
10
Bypass Control and Status DisplayBypass Control and Status Display
• Hand/Off/Auto Selector Switch• Drive/Drive Test/Bypass Selector Switch• Status LEDs
– Ready– Interlock Open– Drive Output Enable– Purge– Bypass Trip– Bypass Run
Bypass ComponentsBypass Components
• Bypass Designs Utilize Rockwell Automation Industrial Components
• Disconnect Switch (Bulletin 194R)– Meets OSHA Lockout/Tagout– 100KA Fault Withstand Rating
• Contactors (Bulletin 100C)– Finger Safe– 3 Million manufactured per year– North American Market Leader for last 15 years (39% of
market share) • Overload Relay (Bulletin 193)
– Visible Trip Indication– Class 20 Overload Curve– Manual Reset with Test Button