+ All Categories
Home > Documents > Wall Design 97

Wall Design 97

Date post: 10-Apr-2018
Category:
Upload: purplepink4u
View: 219 times
Download: 0 times
Share this document with a friend
41
0 Wall Form Design Example  Design forms for 14 ft high wall to be concreted at the rate of 3 ft per hour, internally vibrated. Assume the mix is made wit h Type I cement, with no pozzolans or admixtures, and that the temperature of concrete at placing is 60°F. Slump is 4 in. The forms will be used only once, so short-term loading stresses will apply. Form grade plywood sheathing ¾ in. thick is available in 4x8-ft sheets, and 4500-lb coil ties are on hand. Framing lumber of No. 2 Douglas Fir-Larch is to be purchased as required.
Transcript
Page 1: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 1/41

0

Wall Form Design Example

Design forms for 14 ft high wall to beconcreted at the rate of 3 ft per hour, internallyvibrated. Assume the mix is made with Type Icement, with no pozzolans or admixtures, and

that the temperature of concrete at placing is60°F. Slump is 4 in. The forms will be usedonly once, so short-term loading stresses willapply.

Form grade plywood sheathing ¾ in. thick isavailable in 4x8-ft sheets, and 4500-lb coil tiesare on hand. Framing lumber of No. 2 DouglasFir-Larch is to be purchased as required.

Page 2: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 2/41

1

Wall Form Design Example

STEP 1: FIND PRESSURE.The concrete used for this project satisfiedthe conditions of Table 5-4.

Using Table 5-5B, for R = 3 ft/hr, and T =60 rF, the minimum pressure for design is:

P = 600 psf Then the depth of the hydrostatic load zone,for a concrete with a unit weight of 15 0 pcf is:

Page 3: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 3/41

2

Wall Form Design Example

The diagram of lateral pressure onwall form is shown here:

10¶14¶

600 sf

Page 4: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 4/41

3

Wall Form Design Example

STEP 2: SHEATHING.4x8 sheets of plywood will beused. Use plywood the "strongway" (face grain parallel toplywood span). Design for uniformly spaced supports at1-ft center-to-center.

CHECK BENDINGConsider a 12-in. wide strip of plywood.For continuous beams (more than three supports)the following equation is used:

w

fS l 95.10!

Page 5: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 5/41

4

Wall Form Design Example From Table 4-2, the bending stress for plywood is 1545 psi.

The problem states that the forms will be used only once(single-use form), the bending stress must be multiplied byan adjustment factor of 1.25 for short term loading. Hence,the allowable stress:

psi 193 015 4525.1 $v f

Page 6: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 6/41

5

Wall Form Design Example

From Table 4-3, the section modulus, S , for ¾-in. plywood is: 0.412 in. 3

w, loading of the beam for a 1-ft wide strip of plywood is

lb/lf 600in .12

ps f 600in .12 !!!

pw

Page 7: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 7/41

6

Wall Form Design Example

Substituting in the equation:

in . 61.1233.195.10600

412.0193 095.10 !!!l

w

fS

l 95.

10!

Page 8: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 8/41

7

Wall Form Design Example CHECK DEFLECTION:

Again considering a 12-in. width of plywoodsheathing, check the maximum allowable deflection(( ) of the sheathing for l /360 of the span and 1 /16 in.,whichever is less.

From Table 4-2, the values for modulus of elasticityfor plywood can be found as E = 1,500,000 psi, andTable 4-3 renders the value for the moment of inertiafor plies parallel to the span as I = 0.197 in. 4.

in . 35.13897.769.1600

197.015 0000069.169.1 33 !v!v!!

w EI

l

in.

22.

15

41.

423.3

600

197.015 0000023.323.3 44 !

v!

v!!

w

EI

l

For ( = l /360 :

For ( = l /16 ´ :

Page 9: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 9/41

8

Wall Form Design Example CHECK ROLLING SHEAR :

From Table 4-2, allowable Fv (rolling shear stress) can be found to be F v = 57 psi, whichshould be multiplied by 1.25 for short-termloading. Therefore, the allowable rollingshear stress is:From Table 4-3, the value of the rolling shear constant, Ib/Q , can be found as 6.762.

Use the equation for maximum shear for acontinuous plyform and solve for L :

psi 7 125.157 !!S F

in . 16 .0ft . 33.17 62.66006.0

7 16.0

!!vv

!v!Q Ib

w F

L S

Page 10: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 10/41

9

Wall Form Design Example SPACING OF THE STUDS :

From the above calculations, the smallestvalue obtained for l is 12.61 in. (bendinggoverns), meaning that the studs

CANNOT be placed any further than 12.61inches apart.W e are using 8-ft.-wide plywood sheets.The sheets should have stud support atthe joints. Therefore an equal-spacing of studs at 12-inches satisfies all conditions.

@ USE STUDS WITH SPACING OF 1-FT.

Page 11: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 11/41

10

Wall Form Design Example

STEP 3: STUD SIZE and SPACING OFW ALES(Wales support the studs)

Page 12: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 12/41

11

Wall Form Design Example

Design for 2x

4 S4S studs. Find themaximum span that can support alateral pressure of 600 psf.Equivalent uniform load, w, is the max.lateral pressure times the stud spacing.Hence:

Studs can be considered as continuous beamssubjected to uniform loading. Like the previousset of calculations, check for allowable span for

bending, deflection, and shear.

lb/l f 600in . /ft .12

in .12 psf 600stud !

v!w

Page 13: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 13/41

Page 14: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 14/41

13

Wall Form Design Example The first adjustment factor is the short - term l oading f actor of 1.25. The secondadjustment factor is the size f actor obtainedfrom Table 4-2B, which is 1.5. Therefore:

psi 16871.51.25 psi9 00 !vv!db

F

Page 15: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 15/41

14

Wall Form Design Example

The values of section modulus, S , for 2x 4 S4S No. 2 Douglas Fir-Larch can beobtained from Table 4-1B as 3.06 in. 3.

Page 16: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 16/41

15

Wall Form Design Example

The allowable stud span as a continuousbeam is:

wS F l b

d! 95.10

in . 1.32600

06.3168795.10 !!l

Page 17: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 17/41

16

Wall Form Design Example

CHECK DEFLECTIONThe allowable deflection is less than l /360 of the span and 1 /8 in., whichever is less.Using Table 4-2, the values for modulus of

elasticity for 2 x 4 S4S No. 2 Douglas Fir-Larch is E = 1,600,000 psi, and in Table 4-1B the valuefor the moment of inertia for is: I = 5.36 in. 4

For ( = 1/8 ´ :

in . 0.413.2 469.1600

3 6.5160000069.169.1 33 !v!v!!w

EI l

in . 0.4293.108 4.3

600

3 6.516000008 4.38 4.3 44 !!!!

w

E I l

For ( = l /360 :

Page 18: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 18/41

17

Wall Form Design Example CHECK SHEAR

From Table 4-2, allowable F v (rolling shear stress) can be found to be F s = 95 psi, whichshould be multiplied by 1.25 for short-termloading, as well as by a factor of 2.0 for horizontal shear adjustment. Therefore, theallowable shear stress is: psi 22525.118 0 !v!d

V F

A 2x4 S4S has an actual b = 1 ½ in. and d = 3 ½in., which is obtained from Table 4-1B. Usethe equation for maximum shear for acontinuous beam and solve for l :

in . 33.272.2 62

132

600

2

13

2

11225

33.13233.13 !!!d! d

w

bd F l V

Page 19: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 19/41

18

Wall Form Design Example

SPACING OF THEW

ALESFrom the stud spans calculated above, theshortest span is based on bending whichis 32.1 inches.This means the wales, which are the studsupports CANNOT be spaced more than32.1 inches apart (this span can be increasednear the top, since in the top 4 ft., the pressuredecreases linearly from 600 psf to 0).

The top and bottom wales are often setabout 1 ft from top and bottom of wall

forms.

Page 20: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 20/41

19

Wall Form Design Example

Place wales 12 inches from both topand bottom of the wall form.Then, 14' 1' 1' = 12 ft. or 144 inches

remains for spacing the other wales,which can be no more than 32.1 inchesapart.Set them at 30 in., except one span at24 in. (smaller spans at the bottom).W e place the smaller span near thebottom of the form where theoretically

a higher pressure could occur.

Page 21: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 21/41

20

Wall Form Design Example

30µ = 2· 6µ

Page 22: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 22/41

21

Wall Form Design Example

Page 23: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 23/41

22

Wall Form Design Example

STEPS 4 & 5: TIE DESIGN,W

ALE SIZEand TIE SPACINGFrom the pressure diagram, theequivalent uniform load per lineal footof wale is determined to be 1500 lb /lf.The problem statement indicates that4500-lb coil ties are available and will

be used.

Page 24: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 24/41

23

Wall Form Design Example

STEPS 4 & 5: TIE DESIGN,W

ALE SIZEand TIE SPACING (Cont¶d)

W ith the maximum load per lineal foot of wale being 1500 lbs, then the maximumtie spacing is:

f t.3lb/f t15 00

lb45 00loadWale

ca pac ityTi eS pac ingTi e !!!

Page 25: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 25/41

24

Wall Form Design Example CHECK BENDING (C ont¶d)

M aximum bending moment for auniformly loaded continuous beam (morethan 3 supports) is:

lb .-in . 12 0

2wl M Max

!

The maximum moment of the member being designed is:

S F M bMaxd!

Therefore:12 0

2wl S F b !d

Or:

b F

wl S

d!

12 0

2

Page 26: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 26/41

25

Wall Form Design Example CHECK BENDINGF'

b is the allowable stress in theextreme fiber and was calculated to be1640 psi (refer to top of page 16 of the

handout). The span, l , is 3 ft. or 36inches, and w = 1500 lb /lf.Therefor the required section modulus, S , can be calculated using the aboveequation:

322

in . 60.9

1687

12

0

3 615 00

12

0

!!d

!b F

wl S

Page 27: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 27/41

26

Wall Form Design Example In order to avoid drilling of timbers, theycommonly use double-member wale. Sothe required section modulus of 9.6 in. 3 isfor two members.

Referring to Table 4-1B, double 2 x 4s willyield a section modulus of 2 x 3.06 or 6.12in. 3, which is less than 9.6 in. 3, andtherefore not acceptable.

Checking the next larger size, 3 x 4, willresult in: S = 2x 5.10 = 10.20 in. 3 > 9.6 in. 3,which satisfies the section modulusrequirements. Use double 3 x 4 wales .

Page 28: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 28/41

27

Wall Form Design Example CHECK SHEARTo check the horizontal shear for the double 3 x 4wales, use the horizontal shear stress formulafor a uniformly loaded continuous beam.

d l

bd

w f

V 2

33.13!

O.K. psi225 psi 18 642.214.7712

5.323

75.82

15 009.0 £$v!¹ º ¸

©ª¨ vv

vv!

V f

From Table 4-1B, the value of bd for a 3 x 4 member can be obtained as: 8.75 in. 2 ( or simply: 2.5´ x 3 .5´ =8 .75 in. 2 )

Therefore the stress in the double 3 x 4 membersmeets the requirements. (The value of theadjusted allowable shear stress of 225 psi was

calculated before).

¹ º

¸©ª

¨!

12

29.0 d L

bd

w f

V or

(They aree x actly thesame formulas)

Page 29: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 29/41

28

Wall Form Design Example

STEP 6: BEARING CHECK

Check:

1) bearing of the studs on wales and2) bearing between the tie washer or tie

holders and wales.

From Table 4-2, the value of compressionPerpendicular to grain, F c B , for No. 2Douglas Fir-Larch is 625 psi.

Page 30: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 30/41

29

Wall Form Design Example

L e ngth of

bear ing, in1/2 1 1 1 /2 2 3 4 6 0 r

more

Fac tor« . 1.79 1.37 1.25 1.19 1.13 1.09 1.00

From page 6-10, the multiplying factors for indicatedlengths of bearing on small area plates and washers areshown below:

3.5 ´

(1.13+1.09) /2 = 1.11

Page 31: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 31/41

30

Wall Form Design Example TIES: Assume a 3½ in.-square tie washer.Then the bearing area is:(3½ t )2 ¾ tv 3½ t = 12.25 2. 63 = 9. 63 in.2

Since this is a shortbearing length, F c B

should be multiplied bya factor of 1.11 (refer topage 13 for 3½ in.bearing length):Adjusted F c B = 625 (1.11)

=694 psi

Page 32: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 32/41

31

Wall Form Design Example

The actual bearing stress is then:

psi 467in . 9. 63

lb 45 00area bear ing

loadtieMax im um2

!! < 6 94 psi O.K.

Page 33: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 33/41

32

Wall Form Design Example STUDS ON W ALES:The bearing area between2x 4 studs and double 3 x 4wales can be calculated as:

2 x (1½ ´ x 2½ ´ ) = 2 x 3.75 = 7.5 in. 2

Load transfer to the wale = ½ the studspan above and below the wale x thelateral pressure x the stud spacing

lb 15 00ft1 psf 60012

23 023 0!vv

psi 2 00in . 7.5

lb 15 00 stre ss bear ing 2

!! < 6 25 psi O.K.

Page 34: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 34/41

33

4x8-ft 3 /4 ´ thickplywood sheathing

2x4 S4S No. 2 Douglas Fir-Larch studs 12-in. O.C.

Double 3x4 wales

3 1 /2 in.-squaretie washer

4500-lb coil tieswith 3-ft spacing

Wall Form Design Example

Page 35: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 35/41

34

Consider the necessary bracing for awall form 14 ft. high, above grade, in anarea where the local building code

specifies a minimum 20 psf windloading.Table 5-7 indicated that 140 lb per linealfoot should be used for design of bracing, since the wind force prescribedby local code gives a value larger thanthe 100 lb /ft minimum established byACI Committee 347.

Wall Form Design Example Bracing for Lateral Loads

Page 36: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 36/41

35

Wall Form Design Example Bracing for Lateral Loads

Page 37: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 37/41

36

Wall Form Design Example Bracing for Lateral Loads

Strut BracingIf wooden strut bracing is provided,strong enough to take either a tension or

compression load, then single sidebracing may be used.Nailed connections at either end must bestrong enough to transmit the tension

load, and wales or other form membersmust be strong enough to transmitaccumulated horizontal forces to thestrut bracing.

Page 38: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 38/41

37

Wall Form Design Example Bracing for Lateral Loads

Strut BracingIf wooden bracing is attached 1 or 2 feetbelow the top of the wall, the bracing mustcarry more than the 140 lb per ft loadapplied at the top.

14 ¶12 ¶

HH¶

Page 39: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 39/41

38

Wall Form Design Example Bracing for Lateral Loads

Strut BracingH ¶ the horizontal bracing force 2 feet fromthe top of the wall would have to be

(14¶ /12¶)(140 lb /ft) = 163 lb per ft

in order to balance the 140 lb /lf designload applied at the top of the wall.If end of the brace is put 8 feet from thewall, use the relationship between sides of the right triangle to find the the length of brace and load it must carry.

Page 40: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 40/41

39

Wall Form Design Example Bracing for Lateral Loads

Strut Bracing

h= 1 2 ¶

X= 8 ¶

t

H¶=163 lb . /ft.22 xht !

ft42.142 0881222

!!!t

wallof f t per lb29 48

42.14163str utinncom pre ssiote nsi o n !v!

8'

14 .42'

Hstr utinncom pre ssio(te nsio n) vd!

Page 41: Wall Design 97

8/8/2019 Wall Design 97

http://slidepdf.com/reader/full/wall-design-97 41/41

40

Wall Form Design Example Bracing for Lateral Loads

If struts are spaced every 8 feet alongthe wall, then 8 x 294 = 2352lb must becarried by each brace.M any wood members strong enoughto carry this load in compression willalso be adequate in tension. However,

the strength of connections (nails,etc.) must be made adequate for thetension load.


Recommended