+ All Categories
Home > Documents > Water-cooled Chillers with High Speed Centrifugal...

Water-cooled Chillers with High Speed Centrifugal...

Date post: 27-Mar-2021
Category:
Upload: others
View: 4 times
Download: 0 times
Share this document with a friend
12
Water-cooled Chillers with High Speed Centrifugal Compressors Model GVWF (R134a) 395 - 2660 kW Model GVWF G (R1234ze) 310 - 1820 kW
Transcript
Page 1: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

Water-cooled Chillers with High Speed Centrifugal Compressors

Model GVWF (R134a) 395 - 2660 kWModel GVWF G (R1234ze) 310 - 1820 kW

Page 2: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

2 Water-Cooled Chillers GVWF

XStream eXcellent is a new model within Trane’s XStream range able to reach market-

leading Energy Efficiency Ratio (EER) and European Seasonal Energy Efficiency Ratio

(ESEER) with lower sound levels.

This model GVWF is available with a choice of refrigerants: R134a or R1234ze which has

a GWP value of less than one to exceed current F-Gas legislation requirements and help

customers reduce their carbon dioxide (CO2) emissions and achieve extreme part load

and full load efficiencies.

Trane XStream™ eXcellentWater-cooled Chillers with High Speed Centrifugal Compressors

XStream eXcellent chillers are suited for critical environments like

Office buildings Healthcare Data Centers Automotive industry

Pharmaceutical industry Plastic industry Hospitality industry District Cooling

Page 3: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

3

Range descriptionA model for every need

Trane’s XStream eXcellent provides a wide capacity range up to 2.6 MW with industry-

leading part load and full load efficiencies.

200 400 600 1000 1200 1400 1600 1800 2000 kW800

465G

505G

405G

375G

350G

290G

270G

250G

220G

210G

185G

160G

135G

2 compressors

3 compressors

4 compressors

200 400 600 1000 1200 1400 1600 1800 2000 2200 2400 2600 kW800

420

410

380

370

320

275

390

325

300

260

215

190

570

515

760

695

590

480

2 compressors

2 compressors

3 compressors

4 compressors

Page 4: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

4 Water-Cooled Chillers GVWF

XStream eXcellent chillersExcellence is standard

Smart

Easy operation thanks to smart controls and a user-friendly touchscreen interface.

Energy Efficient

Choose from three different efficiency tiers to respond to every building or process requirement.

Green

Two different refrigerant alternatives:

R134a and the new HFO R1234ze with GWP<1.

Reliable

No compromise: You can count on Trane’s legendary reliability.

Standard on all models• Multiple compressors (2, 3 or 4)

• Double refrigerant circuit

• Economizer circuit

• EMC filter to avoid harmonic transfer to compressor(s)

Page 5: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

5

Multiple chiller plantsOverall efficiency can be further improved by using an alternative chiller lay-out to the conventional parallel-piped

configuration. For example, chillers can be piped in series, on the evaporator side, on the condenser side or both.

This layout provides the opportunity for

• Lower chilled water design temperature with larger ΔT

• Reduced design flow

• Installation and operational cost savings by fewer installed pumps and valves, reduced pipe diameters and chiller downsizing

• Maximized system efficiency

• Continuous temperatures allow better stability of controls

By combining series configuration with Variable Primary Flow (VPF) it is possible to further increase system efficiency.

Variable Primary Flow (VPF) capabilitiesVPF systems provide building owners with multiple cost savings derived directly from pump operation. The XStream series is

designed to make VPF easy to use.

• The evaporator on the XStream series can run safely with up to 50% water flow reduction.

• The microprocessor and capacity control algorithms are designed to handle a maximum of 10% change in water flow rate

per minute in order to maintain ±0.3°C temperature control leaving the evaporator.

• For applications in which system energy savings are the priority and tight temperature control is classified as +/- 1.1°C, up

to 30% change in flow per minute is possible.

• With the help of a TRANE software analysis tool, you can determine whether the anticipated energy savings justify the use

of VPF in a particular application.

7° C

12° C

30° C35° C

15° C

5° C

10° C

31° C

27° C

37° C

VPF

Page 6: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

6 Water-Cooled Chillers GVWF

HFC consumption

0%2015 2016 2018 2021 2024 2027 2030

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%93%

63%

45%

31%

24% 21%

Baseline value (100%) is the annual average of total quantity of CO2 equivalents placed on the EU market from 2009 to 2012.

Ingersoll Rand and Trane - providers of sustainable solutions.

The fluorinated refrigerants phase-down, as defined in the new EU F-Gas Regulation,

is a step-by-step approach where the quantities of HFCs expressed in CO2 equivalent

that are placed on the market are gradually reduced. As a result of the phase-down,

HFC consumption will be reduced by 79% by 2030.

This is an unprecedented reduction and means that industry and users need to make,

over time, the transition to refrigerants with a lower global warming potential.

Trane, recognized as a leading innovator in the HVAC industry, introduces this new,

next generation, lower GWP refrigerant in Sintesis and other products to be front

running in the marketplace and to support your strong sustainability objectives.

The Future of F-Gases

Page 7: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

7

What is GWP?

GWP is the global warming impact relative to the impact of

the same quantity of carbon dioxide over a 100 year period.

What is ODP?

Ozone depletion potential of a chemical is the amount of

degradation to the ozone layer it can cause.

XStream Excellent chillers with low GWP refrigerants are

part of the Ingersoll Rand EcoWise™ portfolio of products

that are designed to lower their environmental impact

with next-generation, low global warming potential (GWP)

refrigerants and high-efficiency operation.New R1234ze

Ozone depletion potential = 0

Low global warming potential (GWP<1)

Refrigerant Global Warming Potential (GWP)

R410A 1924

R407C 1774

R134a 1300

R513A 572

R1233zd 1

R1234ze <1

An environmentally sustainable solution

Page 8: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

8 Water-Cooled Chillers GVWF

Two different refrigerant alternatives

• R134a

• R1234ze with GWP<1

High speed centrifugal compressor

• Oil free and silent operation thanks to magnetic bearings

• Integrated Variable Frequency Drive

• Soft starter module

• Only one moving part

1

3

4

2

1

FeaturesInnovative solutions to your needs

Trane combined smart control and interface*

• Leading TD7 touch screen with 7” color display

• Clear display of critical information

• Monitor settings, data trending, reports and alarms

• Simple, intuitive navigation

• Effective operation, monitoring and management

• Durable construction for both indoor and outdoor use

2

Page 9: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

9

* Trane Proprietary Technology

3

4

21

Trane patented Compact -

High performance - Integrated design -

Low charge (CHIL) flooded evaporator*

• Double pass or counter flow single pass,

depending on unit size

• Reduced refrigerant volume

• Increased efficiency

• Reduced carbon footprint

3

Dual refrigerant circuit Multi Compressor

• Provide redundancy

• Reduce the impact of any failure

4

Page 10: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

10 Water-Cooled Chillers GVWF

GVWF GVWF G

Condenser leaving water temperature (min/max) (°C) Low Lift units +20 / +55

High Lift units +20 / +42

Evaporator leaving water temperature (min/max) (°C) +5 / +20

Power supply (V/Ph/Hz) 400/3/50

Refrigerant R134a R1234ze

General Data for cooling performances

GVWF

Unit size GVWF 380 GVWF 410 GVWF 420 GVWF 480 GVWF 590 GVWF 515 GVWF 570 GVWF 695 GVWF 760

Compressor Lift High Low Low Low Low High Low Low Low

Maximum Gross Capacity (1) (kW) 1439 1697 1582 1776 2069 1924 2123 2430 2662

Performances at Optimum SEER (1)

Gross Cooling Capacity (kW) 1115 1271 1106 1347 1861 1538 1909 1943 1863

Gross EER (1) 5.81 6.03 5.82 5.76 5.95 5.79 5.59 5.96 5.71

Gross ESEER (Not certified) (1) 9.08 9.20 9.14 9.20 9.46 9.26 9.17 9.35 9.45

Net Cooling Capacity (1)(2) (kW) 1114.3 1270.4 1105.3 1346.3 1860.4 1537.2 1908.1 1942.4 1862.4

Net EER (1)(3) 5.64 5.90 5.65 5.63 5.85 5.64 5.42 5.86 5.63

Eurovent Energy class - Cooling A A A A A A A A A

Net ESEER (Not certified) (1)(2) 8.06 8.44 8.11 8.36 8.83 8.23 7.99 8.70 8.81

SEER (4) 8.78 8.88 8.68 8.83 9.08 8.93 8.98 9.00 9.00

Space Cooling Efficiency ηs,c (3) (%) 343 347 339 345 355 349 351 352 352

Number of refrigerant circuits 2 2 2 2 2 2 2 2 2

Number of compressors 3 3 3 3 3 4 4 4 4

Sound power level (4) (dB(A)) 91 96 93 96 100 92 96 99 101

Weights and dimensions

Length (mm) 4730 4804 4730 4804 5245 4804 4804 5444 5444

Width (mm) 1700 1800 1700 1800 2141 1800 1800 2141 2141

Height (mm) 2032 2135 2032 2135 2315 2135 2135 2315 2315

Operating Weight (kg) 4317 5177 4317 5177 8076 5401 5574 8263 8323

(1) Evaporator 12/7°C and 0.0 m²K/kW, and condenser at 30/35°C and 0.0 m²K/kW(2) Net performances calculated as per EN 14511-2013.(3) ηs,c / SEER as defined in Directive 2009/125/EC of the European Parliament and of the Council with regard to Ecodesign requirements for Comfort Chillers with 2000 kW maximum capacity -

COMMISSION REGULATION (EU) N° 2016/2281 of 20 December 2016(4) At full load and in accordance with ISO9614

Unit size GVWF 190 GVWF 215 GVWF 260 GVWF 300 GVWF 325 GVWF 390 GVWF 275 GVWF 320 GVWF 370

Compressor Lift High High High Low Low Low High High Low

Maximum Gross Capacity (1) (kW) 684 828 972 1056 1230 1425 1031 1167 1424

Performances at Optimum SEER (1)

Gross Cooling Capacity (kW) 546 661 776 859 1089 1425 721 871 1280

Gross EER (1) 5.49 5.47 5.59 5.71 5.80 5.84 5.89 5.73 5.76

Gross ESEER (Not certified) (1) 8.60 8.48 8.49 8.70 9.11 9.16 9.24 9.10 9.27

Net Cooling Capacity (1)(2) (kW) 545.5 660.5 775.4 858.4 1088.3 1424.3 720.6 870.4 1279.4

Net EER (1)(3) 5.25 5.27 5.38 5.45 5.64 5.70 5.77 5.58 5.64

Eurovent Energy class - Cooling A A A A A A A A A

Net ESEER (Not certified) (1)(2) 7.21 7.31 7.29 7.29 8.10 8.26 8.46 8.17 8.48

SEER (4) 8.20 8.03 7.93 8.25 8.58 8.83 8.78 8.70 8.78

Space Cooling Efficiency ηs,c (3) (%) 320 313 309 322 335 345 343 340 343

Number of refrigerant circuits 2 2 2 2 2 2 2 2 2

Number of compressors 2 2 2 2 2 2 3 3 3

Sound power level (4) (dB(A)) 87 88 89 92 96 99 88 90 95

Weights and dimensions

Length (mm) 2976 2976 2976 3476 4730 4804 4730 4730 4804

Width (mm) 1125 1125 1125 1125 1700 1800 1700 1700 1800

Height (mm) 1920 1920 1920 1920 2032 2135 2032 2032 2135

Operating Weight (kg) 2310 2810 3020 3370 4094 4954 4110 4102 5177

General specifications

Page 11: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

11

Unit size GVWF 290 G GVWF 350 G GVWF 375 G GVWF 405 G GVWF 465 G GVWF 505 G

Compressor Lift Low Low High Low Low Low

Maximum Gross Capacity (1) (kW) 942 1120 1018 1356 1352 1672

Performances at Optimum SEER (1)

Gross Cooling Capacity (kW) 942 1120 1018 1356 1352 1672

Gross EER (1) 5.73 5.48 6.12 5.65 5.53 5.98

Gross ESEER (Not certified) (1) 8.92 8.95 9.48 9.17 9.23 9.16

Net Cooling Capacity (1)(2) (kW) 941.4 1119.3 1017.5 1355.3 1351.4 1669.0

Net EER (1)(3) 5.59 5.33 5.99 5.50 5.43 5.90

Eurovent Energy class - Cooling A A A A A A

Net ESEER (Not certified) (1)(2) 8.03 7.90 8.68 8.14 8.49 8.65

SEER (4) 8.58 8.50 9.00 8.85 8.75 8.83

Space Cooling Efficiency ηs,c (3) (%) 335 332 352 346 342 345

Number of refrigerant circuits 2 2 2 2 2 2

Number of compressors 3 3 4 4 4 4

Sound power level (4) (dB(A)) 93 99 91 95 100 101

Weights and dimensions

Length (mm) 4730 4730 4804 4804 4804 5444

Width (mm) 1700 1700 1800 1800 1800 2141

Height (mm) 2032 2032 2135 2135 2135 2315

Operating Weight (kg) 4085 4304 5002 5128 5556 8239

(1) Evaporator 12/7°C and 0.0 m²K/kW, and condenser at 30/35°C and 0.0 m²K/kW(2) Net performances calculated as per EN 14511-2013.(3) ηs,c / SEER as defined in Directive 2009/125/EC of the European Parliament and of the Council with regard to Ecodesign requirements for Comfort Chillers with 2000 kW maximum capacity -

COMMISSION REGULATION (EU) N° 2016/2281 of 20 December 2016(4) At full load and in accordance with ISO9614

GVWF G

Unit size GVWF 135 G GVWF 160 G GVWF 185 G GVWF 210 G GVWF 220 G GVWF 250 G GVWF 270 G

Compressor Lift High High High Low Low Low High

Maximum Gross Capacity (1) (kW) 422 530 613 659 787 850 764

Performances at Optimum SEER (1)

Gross Cooling Capacity (kW) 422 530 613 659 787 850 764

Gross EER (1) 5.45 5.28 5.44 5.44 5.32 5.50 5.99

Gross ESEER (Not certified) (1) 8.39 8.35 8.39 8.17 8.46 8.19 9.24

Net Cooling Capacity (1)(2) (kW) 421.6 529.5 612.4 658.5 786.0 849.4 763.5

Net EER (1)(3) 5.25 5.05 5.17 5.22 5.09 5.27 5.85

Eurovent Energy class - Cooling A A A A A A A

Net ESEER (Not certified) (1)(2) 7.24 7.00 6.93 6.97 7.10 6.94 8.39

SEER (4) 7.88 7.88 7.90 7.73 7.63 7.53 8.78

Space Cooling Efficiency ηs,c (3) (%) 307 307 308 301 297 293 343

Number of refrigerant circuits 2 2 2 2 2 2 2

Number of compressors 2 2 2 2 2 2 3

Sound power level (4) (dB(A)) 86 88 89 92 96 98 90

Weights and dimensions

Length (mm) 2976 2976 2976 2976 2976 3476 4730

Width (mm) 1125 1125 1125 1125 1125 1125 1700

Height (mm) 1920 1920 1920 1920 1920 1920 2032

Operating Weight (kg) 2130 2280 2420 2740 3000 3380 4025

Page 12: Water-cooled Chillers with High Speed Centrifugal Compressorstranedanmark.dk/wp-content/uploads/2019/06/TRANE-GVWF-CTV-SL… · Speed Centrifugal Compressors Model GVWF (R134a) 395

The Trane advantage Trane is recognized as a world leader with over 100 years of experience in creating and sustaining safe, comfortable and

energy efficient environments while improving the performance of buildings and processes around the world.

Trane innovative solutions optimize indoor environments with the broadest portfolio of energy efficient heating,

ventilating and air conditioning systems, building services, parts support and advanced controls in the industry.

To ensure your equipment continues to work at its optimum, throughout the life of the building, Trane provides a full

range of service solutions, combined with in-house expertise and the most extensive service and support network in

the industry.

And with Trane’s extensive rental fleet all your temporary cooling and heating needs are served: we provide continuous

cooling or heating during equipment changeouts or supplemental supply for those times when your cooling loads exceed

your current system’s capacity. For more information: www.trane-chiller-rental.eu

Ingersoll Rand recognition

For the sixth consecutive year, Ingersoll Rand has been recognized as one of the World’s Most Admired Companies

according to FORTUNE Magazine.

Ingersoll Rand was recognized at the 2016 Climate Leadership Conference for its refrigerant phase-out efforts by the US

EPA, its greenhouse gas emissions reduction goal of 35% by 2020 and its commitment to reduce the climate impact of the

refrigerants used in its products by 50% by 2020.

© 2019 Trane – All rights reserved CTV-SLB060-GB January 2019

We are committed to using environmentally conscious print practices that reduce waste.

trane.eu ingersollrand.com

Trane® is a brand of Ingersoll Rand®. Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands—including Ingersoll Rand®, Trane®, Thermo King® and Club Car® — work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress and enduring results.


Recommended