Welcome to Kidde Pre- Engineered Systems Training KIDDE Wet Chemical System for Kitchens
Transcript
Page 1: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Welcome to Kidde Pre-

Engineered Systems Training

KIDDE Wet Chemical System

for Kitchens

Page 2: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Wet Chemical Systems

Introduction & Objectives

The Design Concept

Suppression Equipment Review

Nozzle Applications

Pipework Parameters

Detection & Control Equipment Review

Competitive Advantage

Worked Examples

Page 3: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Wet Chemical Systems

Training Course Objectives

How to design and quote the basic

system:

- Understanding the design concept

- Using the design tools

- Hardware familiarity

Page 4: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Where are Wet Chemical

Systems Used?

Commercial kitchen

equipment:

- Appliances

- Associated plenums

- Ducts

Page 5: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Design Standards

NFPA 17A „Wet Chem Ext Systems‟

NFPA 96 „Commercial Cooking Ops‟

These cover:-

- Hardware design

- Installation

- System design

Page 6: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Performance Standards

System performance tested to UL 300

New standard addressing:-

- Use of vegetable oil (reduced

saponification)

- Improved insulation (fuel

maintains heat for longer period)

Page 7: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Aqueous Potassium Carbonate

How does APC do its job?

Saponification

- forms a solid film over the fuel

- separates fuel from oxygen

- prevents recognition

Cooling

- upon application from the spray nozzle

- over time until below auto-ignition temp

Page 8: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

The Design Concept

Pre-engineered systems

Make the application fit

System demand is measured in Flowpoints

Match Flowpoints to cylinder capacity

Use design tools to develop proposal

Page 9: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Design Tools

The Manual

- note AD-1 (delete 3-14 to 3-21)

Survey Worksheet

BOM Calculator

Verification Worksheet

Parameter Guidance Notes:

Page 10: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Design Tools

Container Flowpoint Ratings

Appliance Descriptions

Pipe Sizes & Flowpoint Capacity

Pipework Parameters Checklist

Nozzle Performance Summary

Page 11: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Challenging Areas

Scoping the area to be protected

- insist on clear drawings

Classification of appliances

- multiple terminology & proper names

Installing the system as designed

- experienced site staff

- effective documentation

Page 12: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Design Review

Appliance protection

Plenum & Duct Protection

Actuator selection

Pipework & cylinders

Detection & Ancillaries

Page 13: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Suppression Systems Components

Page 14: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Cylinder & Valve Assembly

WHDR-125 (1.25 gal)

WHDR-260 (2.60 gal)

WHDR-400 (4.0 gal)

- 400S-Short Cylinder

- 400L-Long Cylinder

WHDR-600 (6.0 gal)

DOT 4BW Steel Shell

Pressure 175 psig

Page 15: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Cylinders Cy l

S ize

A B C

Pr e ss

C

Head

D

1.2 5 14 1 5 - 3/8 1 6 - 3/4 21 7 - 5/8

2.6 1 9 - 5/8 21 2 2 - 1/8 2 6 - 5/8 9

4 Shor t 1 7 - 5/8 19 2 0 - 3/8 2 4 - 5/8 12

4 Tal l 3 3 - 3/4 3 5 - 1/8 3 6 - 1/2 4 0 - 3/4 9

6 3 3 - 7/8 3 5 - 1/4 3 6 - 5/8 4 0 - 7/8 10

Page 2-1

Figure 2-1

Page 16: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Valve

Page 2-2, figure 2-3

Page 17: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Discharge Adapter Kit

Page 2-2, figure 2-4

Page 18: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Brackets for 1.25 -- 4 gallon

WHDR-125

WHDR-260

WHDR-400S

WHDR-400T

Steel

Page 2-3, figure 2-5

Page 19: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Bracket for Six Gallon

Page 2-4

Figure 2-6

Page 20: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

System Actuation Choices

Direct mount on cylinder valve

- Mechanical Control Head

- Electrical Control Head

Remote mount (surface fixing)

- KRS-50 Control Box

Page 21: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Direct Mount Control Heads

Mechanical - automatic (fusible link) &

manual operation

- no switch

- one switch

- two switches

Electrical - automatic (Fenwal D-A-Fs) &

manual operation

- 120 VAC

- 24 VAC

Page 22: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Control Heads

Mechanical

- 486607: no switch

- 899063: 1 switch

- 899176: 2 switches

Page 23: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Mechanical Control Head

Maximum 100 feet cable: any port

Maximum 30 corner pulleys

Maximum 1 tee pulley on gas valve or

pull station port

Maximum 25 fusible links

Up to tow gas valves and two

mechanical pull stations

Page 24: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Electrical Control Head

899175

120 Volts A.C.

24 Volts D.C.

Use with Fenwal Detect-A-Fire

2 switches

Page 25: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Remote Mount

KRS-50 Control Box

Automatic (fusible link) & manual

operation

Pilot pressure operated unit

Utilises pressure actuators, one per

cylinder

Field installed pressure switches

Page 26: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

KRS-50 Control Box

87-120010-001

Up to five cylinders

Up to two microswitches

Remote, up to 23 feet from last cylinder

Includes one pressure operated actuator Page 2-8

Page 27: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

KRS-50 (pressure)

Actuation

Pg. 3-1

Fig. 3-1

Page 28: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Actuation

Mechanical (cable)

Pg. 3-1

Fig. 3-1

Page 29: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Actuation: Multiple Cylinders

Page 3-3,

Figure 3-5

Page 30: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

KRS-50 Control Box

Maximum 200 feet of cable

Maximum 30 fusible links

Maximum 40 corner pulleys

No more than 16 corner pulleys to gas valve

Page 31: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Pressure Operated Actuator

87-100012-001

Use with KRS-50

Use with KRS-100

KRS-50 CONTROL BOX TO

CONNECT with ?“ (.6 cm) O.D. TUBING

Page 2-9

Page 32: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Hood Seal Adapters

Page 33: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Kidde Nozzles

Only 6 Types

One Piece Design

Strainer Built In

Foil Seal

- Disc Cap Retains Seal

- Prevents Orifice Obstruction

- High Temperature

Grooved Rings for Ease of

Identification

Page 34: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Use it on any nozzle!

Swivel Adapter

Page 2-10

Figure 2-13

Page 35: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Seven Sizes

3/4, 1, 1 1/4, 1 1/2, 2,

2 1/2, 3”

Mechanical Gas Valve

Page 36: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Mechanical Gas Valve

Must be operated by:

- pneumatic release (on discharge

pipework)

- cable directly off KRS-50 discharge

lever

- directly off the actuating cam of the

ECH and MCH

Page 37: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Mechanical Gas Valves

Page 38: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Electrical Gas Valve

Manual Reset Relay MUST be used

Eight Sizes via ( also includes 1/2”)

Fig. 2-30

Page 39: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Vent Plug

One used on every

set of distribution

piping

Page 2-16

Fig. 2-26

Page 40: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

9189212

Max 20 per system

12 inches rise

Pneumatic Release

Page 41: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Page 2-21

Pressure Switch

SPDT switch rated at

- 15A/115 or 230 VAC

- 5A/28 VDC

Use the PS for pilot duty

Page 42: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Remote Controls

Control Head Type (Elec. & Mech.)

- Surface Mounted

KRS-50 Type

- Surface Mounted

- Flush Mounted

Page 43: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Remote Manual

Pull Station for

Mechanical / Electrical

Control Head

Remote Controls:

Control Heads

Page 2-13

Page 44: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Remote Controls: KRS-50

Surface Remote

for KRS-50

End of Line or In-

line Type

Page 45: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Recessed Remote Manual Release for KRS-50

End of Line or In-line Type

Remote Controls: KRS-50

CRIMP STOPSLEEVE

Fig. 2-22 Fig. 2-23 Fig. 2-24

Page 46: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Kidde Corner Pulleys

Used at Every Change in

Direction

Fits 1/2” EMT

High Temperature

Tee Pulley

- Used for 2 Gas Valves or 2

- Remote Manual Releases

- Equals 2 Corner Pulleys

- Not for Use with KRS-50

Page 47: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

844648

Corner Pulley

Page 2-25

Page 48: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

9197602

For KRS-50 In-line Pull ONLY

Three Way Pulley

Must use in-line kit or complete kit for NFPA 17A

Page 49: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Hardware Not Recommended

Tandem Control Head

Links other than KG Series

Page 50: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Appliance Protection

Page 51: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Appliance Protection -

Definitions

Page 3-4, Figure 3-6

Page 52: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Design Tools: Nozzles

The Manual

Appliance Description

Nozzle Performance Summary

Page 53: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Parabola Type Coverage

Fryer with drip board

Split Vat Fryer

Char Broilers

Page 54: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Fryer with

drip board

Split Vat

Fryer

Char Broilers

See figures:

3-7, 3-9, 3-19, 3-20, 3-21, 3-22

Page 55: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Fryer With Drip Board

Page 56: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Griddle

Nozzle must

be on the

perimeter of

the appliance.

Page 3-5, Figure 3-8

Page 57: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Split Vat Fryer

Page 58: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Fryer With No Drip Board

Page 3-6, Figure 3-11

Page 59: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Low Proximity Fryer

Split Vat Fryer ONLY

Nozzle anywhere

within the perimeter

Page 3-7, Figure 3-12, 3-13

Page 60: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Low Proximity Fryer

Page 61: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Modular Coverage

Coverage based on multiples of

appliance type

Fryers: Maximum size is 864 square

inches (6 square feet)

Page 62: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Modular Coverage

Page 3-8 Figure 3-14

Page 3-8 Figure 3-15

Page 63: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Modular Coverage

Page 3-9, Figure 3-16

Page 64: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Lava, Pumice, Ceramic,

Synthetic Rock Char Broiler

Page 65: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Gas, Electric Radiant

Char Broiler

Page 66: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Natural, Mesquite Charcoal

Char Broiler

Page 67: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Mesquite Logs Char Broiler

Page 68: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Upright & Salamander Broiler

Page 3-10, Figure 3-17

Page 69: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Woks

Measurement is exception to the rule

Measure to BOTTOM of Wok Page 3-10, Figure 3-18

Page 70: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Page 3-12 Figure 3-23

Chain Broiler, Closed Top

1/4 inch pipe drop required

Page 71: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Chain Broiler, Open Top

Two nozzles required

1/4 inch pipe drops required

Page 3-12 Figure 3-24

Page 72: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Ranges: Four Burner

Page 3-13 Figure 3-25

Page 73: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Ranges: Two Burner

Page 3-13 Figure 3-26

Page 74: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Aim BEHIND the burner

Range: One Burner

Page 3-13 Figure 3-27

Page 75: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Tilt Skillet

Protect like a Fryer

Page 76: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Plenums and Ducts

Pages 3-14 -- 3-21 are obsolete!

See addendum 1 in the front of the

manual

Refer to Design Notes

- Plenums

- Ducts

Page 77: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Plenum Protection

Page 78: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

12.50 IN.MAX.

15 .9 1 IN.MAX.

SQUARE DUCT

ROUND DUCT

RECTANGULAR DUCT2 “ A” + 2 “B” = 6 5 IN

DUCT ENTRANCE

ADP NOZZLE

0 “ -6 ” ( 15 2 mm )

VERTICAL/ HORIZONTAL DUCT

CL

CL

CL

ADP NOZZLE

OF VERTICAL DUCT

AIM POINT

OF HORIZONTAL DUCT

“B”

“A”

DUCT PERIMETER UP TO AND INCLUDING 5 0 INCHES

11 .78 inches maximum diagonal

11 .78 inches m aximum diagonal

2 t o 4 inchesNozzle t ip t o duct hip

DUCT

Duct Protection

Page 79: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

CL CL CL

SQUARE

? x ?x ?x ?x

CL

?d ?d

RECTANGULAR ROUND

TYP. (2) ADP NOZZLES,

87-120011-001

NOZ ZLES TO BE ALONG ONE

CEN TER LINE AT THE ? POINT S.

NOZ ZLES TO BE 0“ TO 6” UP FROMENT RAN CE OF VERTICAL DUCT

CLADP NOZZLE

DUCT ENTRANCE

0“ - 6”

CL OF VERTICAL DUCT

CL OF H ORIZONTAL DUCT

ADP NOZZLE AIM POINT

VER TICAL/HORIZON TAL DU CT

XX

Maximum Diameter: 31.83 inches

Maximum Diagonal: 11.78 inches

Maximum Diagonal:11.78 inches

2 to 4 inchesnozzle t ip to duc t hip

DUCTDuct

Page 80: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Large Ducts

15 15 15 15

18

Large Duct: 18 x 60 inchesTotal: 156 perimeter inches

XXXX

Nozzle to corner: 11.73 inches (Maximum allowable is 11.78)

Page 81: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Upper/Lower Plenum

Page 82: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Transitional Duct

6 inches

ADP Nozzle

Page 83: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

System Piping

Page 84: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Cylinder Sizes, Flow Points

Pipe Sizes, Flow Points

Manifolding

Equivalent Length Limitations

Volume Limitations

Use the Excel Verification Sheet

Piping Parameters

Page 85: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Piping Parameters

Use only sch 40 black and stainless pipe - no

galvanised

Manifolds: fabricate from pipe fittings

Use „Loctite 577‟ pipe dope to ensure tight

joints (overrides manual)

KRS-50: use 3/16” Enot‟s tubing system with 1/4” outlet adaptor

Fit a pressure bleed in pipe (to protect nozzle

seals)

Page 86: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Cylinder Sizes, Flow Points

Cylinder Flow Points

WHDR-125 4 flows

WHDR-260 8 flows

WHDR-400

1 cylinder 12 flows

2 cylinders 24 flows

3 cylinders 36 flows

4 cylinders 48 flows

WHDR-600

1 cylinder 18 flows

2 cylinders 36 flows

Page 87: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Pipe Size, Flow Points

Flow Numbers Pipe Size

1-2 1/4 inch

1-8 3/8 inch

1-12 1/2 inch

13-24 * 3/4 inch

25-48 * 1 inchTable 3.5

Page 88: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Pipe Sizes and Flows

Page 89: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Pipe Sizes and Flows

Page 90: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Pipe Sizes and Flows

Page 91: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Discharge Line Volume S i z e V o l u m e p e r f o o t

1 / 4 i n c h 1 . 2 5 c u b i c i n c h

3 / 8 2 . 2 9

1 / 2 3 . 6 5

3 / 4 6 . 4 0

1 i n c h 1 0 . 3 7

Cylinder Volume 3/8

WHDR-125 72 cu. in. 72

WHDR-260 139 95

WHDR-400 400 95

WHDR-600 400 95

Page 92: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Equivalent Length:

Remote Nozzles

1 2 5 3 9 3 3

C y l i n d e r C y l t o N o z z N o z z l e s

2 6 0 6 3 . 4 4 3 . 7

4 0 0 1 3 2 * 9 5 *

6 0 0 7 5 * 8 0 *

* A p p l i e s t o m a n i f o l d e d s y s t e m s

Page 93: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Equivalent Length: Example

1/2” Elbow = 1.5 equ. ft (Table 3.9)

1/2” Pipe = 1 equ. ft per ft

Total = 1.5 + 1.5 + 1 = 4 equ. ft

Page 94: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Equivalent Length

How to measure tees

Page 95: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Measuring Tees: Manifolds

Page 96: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Minimum Pipe Length

For cylinder to an appliance

where there could be splash

1 / 4 a n d 3 / 8 8 . 5 + ( 1 ) e l l

P i p e S i z e M i n i m u m P i p e

1 / 2 7 . 0 + ( 2 ) e l l s

3 / 4 & 1 i n c h 1 0 e q . f e e t o f 1 / 2 i n c h

Page 97: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Special 3/8 Only System

L i m i t a t i o n s 1 2 5 2 6 0 4 0 0

M a x L i n e V o l u m e 7 2 9 9 1 6 1

M a x E q . C y l i n d e r t o N o z z l e 3 9 4 0 5 9

M a x E q . N o z z l e t o N o z z l e 3 3 4 2 5 0

M a x E q . 1 / 2 C y l i n d e r t o H o o d 1 2 1 2 2 4

M i n . E q . L i n e C y l t o L i q . H a z 8 . 5 + e l l 8 . 5 + e l l 8 . 5 + e l l

Page 98: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Things To Remember!

Maximum of 100

equivalent feet of 1/4 inch

pipe per branch line.

Maximum 40 linear feet

per branch line.

Highest point of system

no more than 12 feet

above cylinder outlet.

No more than 4 feet rise

for any branch line above

supply line.

Do not exceed maxi-

mum pipe volume.

Do not exceed maxi-

mum equivalent length

limitations.

Do not exceed flow

points for any given pipe

size.

No low points or traps.

Page 99: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Detection System Components

Page 100: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Detection Options

DAF‟s for Electrical Control Head

KG Series Fusible Links for MCH, KRS-50

- standard response

- rapid response

KML Series Links for MCH only

- 165°, 212°, 360°, 500° Low-Melt Solder Fusible Links

- plus Quartzoid Bulb Link 500°F

KRS Series - New glass bulb for high temp

Page 101: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Detection

Fusible Links for KRS-50

- Quartzoid Bulb for High Temp applications

Page 2-11, figure 2-16

Page 2-12, figure 2-18

Page 102: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Mechanical Detection

Systems

KRS-50 - KRS-50 Detector Assy (fig 2-18)

- Use Quartzoid Bulb 500°F (Fig 2-18)

- Or Fusible “A” Link 360°F (Page 2-12)

- Or KG Series 165°F to 500°F

MCH - Use KML Fusible Link (Page 2-11)

- KML Series 165°F, 212°F, 360°F and 500°F

- Or KG Series 165°F to 500°

Page 103: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Detection, KG Series

New Glass Bulb Technology for Special Hazards

Proven Technology in Fire Protection

Page 104: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

KG Series Links

Available in six temperatures

Available in Standard and Rapid Response

Listed with both KRS-50 and MCH

Will be in addendum number 2

Page 105: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Standard KML Fusible Links

for MCH Only

1-?“ MIN.

Page 106: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Placement of Fusible Links

Page 107: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Only in the plenum & ducts

Duct: at the hood/duct opening or a maximum

of 12” downstream

Appliances: one unit per 54” x 54” of

appliance area

Duplications for appliances below the

hood/duct is not required (Page 3-33)

Placement of Fusible Links

Page 108: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Electric Detection

One Detect-A-Fire for every 20 feet of plenum

One Detect-A-Fire in the duct

Page 109: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Detect-A-Fire for Electrical

Detection

LOW EXPANSIONSTRUTS

CONTACTPOINTS

BRAZE-SEALEDEND

ADJUSTINGSCREWS

EXPANDINGOUTER SHELL

ELECTRICALINSULATION

GLASS BEADS

HERMETIC SEAL

BRAZE-SEALEDHEAD

ELECTRICALLEADS

Page 110: Welcome to Kidde Pre-Engineered Systems  · PDF fileWelcome to Kidde Pre-Engineered Systems Training KIDDE Wet Chemical System for Kitchens

Competitive Advantage

Ansul is the benchmark competitor

Larger container than R101 (6g v. 3g)

Pressurised cylinder - pressure gauge

Manifold capability (up to 4 cyls)