+ All Categories
Home > Documents > What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion...

What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion...

Date post: 10-Aug-2020
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
25
3/11/2015 1 What’s Eating Your Pipes? Douglas Nadeau, MSFPE, PE, CFPS, LEED AP Vice President of truVUE Inspection Technologies President of RAN Fire Protection Engineering, PC Tel: 518-859-0122 Email: [email protected] How Corrosion Can Cause Your Sprinkler System to Fail and How to Fight It Agenda Agenda ¾ Introduction ¾ Facts ¾ Types of corrosion ¾ F t th t l t i ¾ Factors that accelerate corrosion ¾ NFPA – 25 ¾ Sizing up the problem ¾ Mitigation ¾ Conclusion truVUE Inspection Technologies 2 A Story of a Nursing Home A Story of a Nursing Home ¾ Nursing home facilities average 2,300 fires nationally per year. ¾ Centers for Medicare & Medicaid Services mandate. ¾ August 13, 2013. truVUE Inspection Technologies 3
Transcript
Page 1: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

1

What’s Eating Your Pipes?

Douglas Nadeau, MSFPE, PE, CFPS, LEED APVice President of truVUE Inspection TechnologiesPresident of RAN Fire Protection Engineering, PCTel: 518-859-0122Email: [email protected]

g pHow Corrosion Can Cause Your Sprinkler System to

Fail and How to Fight It

AgendaAgenda

IntroductionFactsTypes of corrosion F t  th t  l t   i  Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion 

truVUE Inspection Technologies 2

A Story of a Nursing HomeA Story of a Nursing Home

Nursing home facilities average 2,300 fires nationally per year. 

Centers for Medicare & Medicaid Services mandate.

August 13, 2013.

truVUE Inspection Technologies 3

Page 2: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

2

A Story of a Nursing HomeA Story of a Nursing Home

April 30, 1998 at the Lamoni Nursing Center. 

Fire in the north wing laundry room. 

Total failure of the sprinkler system. 

A single head should have controlled the fire. 

truVUE Inspection Technologies 4

A Story of a Nursing HomeA Story of a Nursing Home

Dry system had been installed in 1972. 

Sprinkler found plugged with hardened, rust‐colored  granular material  colored, granular material. 

Every head in the wing. 

Branch lines severely corroded and partially plugged. 

truVUE Inspection Technologies 5

In recent years a state agency had a fire which ended up killing some group home 

id t  

A Story of ReactionA Story of Reaction

residents. 

The reaction – fix all sprinkler systems that might have problems.

State identified 5 group homes.truVUE Inspection Technologies 6

Page 3: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

3

Just one of the homes had a problem due to leaking.  The other 4 were unknown but built at the same time.

A Story of ReactionA Story of Reaction

The reaction was rip out all the systems.

The solution required education in corrosion.

Ultrasonic testing was performed.truVUE Inspection Technologies 7

4 out of the 5 group homes had a corrosion issue. 

One of the homes was close to near perfect 

A Story of ReactionA Story of Reaction

condition.

Replaced 4 systems, saved 1.  

Over a $150,000 savings for a small investment.

truVUE Inspection Technologies 8

Case Example: Case Example: Five HighFive High‐‐Rise BuildingsRise BuildingsWhere to start?Where to start?

9truVUE Inspection Technologies

Page 4: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

4

Given:Given:5 High‐Rises. 44 stories and 22 stories.44 stories and 22 stories.Fully occupied.Standpipe system only, no sprinkler system.Standpipe system only, no sprinkler system.

Problems:Problems:

Case ExampleCase Example:: HighHigh‐‐RisesRises

Problems:Problems:Waterflow switches not working. Investigation reveals slime in water when replacing switches.Investigation reveals slime in water when replacing switches.Plugged piping observed.Extent of problem not known.Extent of problem not known.

Options:Options:Destructive testing – one location – cost $18,000 + downtime Ultrasonic Testing Ultrasonic Testing –– 250 locations 250 locations ––Cost $25,000 Cost $25,000 –– No downtime, No downtime, more locations.more locations.

10truVUE Inspection Technologies

AgendaAgenda

IntroductionFactsTypes of corrosion F t  th t  l t   i  Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion 

truVUE Inspection Technologies 11

Corrosion Corrosion ‐‐DefinitionDefinition

Naturally destroys metal at a very slow rate 

Reactions between metal + water = rust

Result ‐ "pit" the inside pipe wall or deposit tubercles (corrosion byproducts) there

truVUE Inspection Technologies 12

Page 5: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

5

Losses Due To CorrosionLosses Due To Corrosion

truVUE Inspection Technologies 13

Corrosion can be Indicative of Other Corrosion can be Indicative of Other ProblemsProblems

Non‐compliance with NFPA 13 

Improper installation including improper slope, trapped air, or inadequate drainage 

Improper operation or maintenance 

Possible MIC activity

truVUE Inspection Technologies 14

Corrosion Can Cause Pinhole Leaks Corrosion Can Cause Pinhole Leaks 

Disruptive to normal operations Potential damage to equipment and/or property Lead to loss of revenue due to shutdowns Cause the continuous introduction of oxygenated water due to repeated draining for repairs Lead to costly ongoing repairs

truVUE Inspection Technologies 15

Page 6: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

6

truVUE Inspection Technologies 16

truVUE Inspection Technologies 17

truVUE Inspection Technologies 18

Page 7: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

7

AgendaAgenda

IntroductionFactsTypes of corrosion F t  th t  l t   i  Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion 

truVUE Inspection Technologies 19

Two Main Types of CorrosionTwo Main Types of Corrosion

Interior Exterior

truVUE Inspection Technologies 20

Exterior CorrosionExterior Corrosion

Corrosive atmosphere exists = corrosion‐resistant sprinklers. 

Stainless steel sprinklersSprinkler coatings

Shop paint and manufacturer's coatings on the outside of the piping help some.

Rust film (oxide layer) that is found on pipe and fitting exteriors actually serves as a corrosion inhibitor. 

truVUE Inspection Technologies 21

Page 8: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

8

Types of Interior CorrosionTypes of Interior Corrosion

Electrochemical CorrosionUnder Deposit CorrosionGalvanic CorrosionMi bi l i ll  I fl d C i  (MIC)Microbiologically Influenced Corrosion (MIC)Limescale AccumulationHypochlorite CorrosionDezincificationWelding

truVUE Inspection Technologies 22

Electrochemical CorrosionElectrochemical Corrosion

Oxygen CorrosionSteel pipe is 98% iron.Oxygen dissolved in water react with the iron

truVUE Inspection Technologies 23

iron.Forms iron hydroxide (rust).Fresh water = restart of corrosion process.

Under Deposit CorrosionUnder Deposit Corrosion

Very common Forms under sediment, deposits of debris or corrosion productspAs corrosion continues the pit will deepenA tubercle could form over the pit

truVUE Inspection Technologies 24

Page 9: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

9

Galvanic CorrosionGalvanic Corrosion

Dissimilar metals in physical contact

Requires the presences of waterRequires the presences of water

Black pipe connected to galvanized pipe – the zinc will dissolve

truVUE Inspection Technologies 25

Microbiologically Influenced Corrosion Microbiologically Influenced Corrosion (MIC)(MIC)

Corrosion caused by bacteriaTwo main classes of bacteriabacteria

Aerobic – needs oxygenAnaerobic – doesn’t require oxygen

6 primary types 

truVUE Inspection Technologies 26

Mid‐1980s. 

More prevalent in areaswith warmer climates  

Microbiologically Influenced Corrosion Microbiologically Influenced Corrosion (MIC)(MIC)

with warmer climates. 

Hard data confirming known causes of MIC in sprinkler systems is scarce. 

truVUE Inspection Technologies 27

Page 10: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

10

AgendaAgenda

IntroductionFactsTypes of corrosion F t  th t  l t   i  Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion 

truVUE Inspection Technologies 28

LifespanLifespan

Anticipated lifespan of a sprinkler system is 30‐40 years.  

Lif   f  t i   i kl   t   d Lifespan of wet‐pipe sprinkler systems exceed those of dry‐pipe systems.

Any testing over and above NFPA 25 or insurance carrier guidelines will cause added oxygen to rust system piping prematurely. 

truVUE Inspection Technologies 29

LifespanLifespan

The type of black steel (domestic or imported) used to make the pipe matters little. 

Using galvanized steel can help with a longer system life. 

It is mainly what goes into the pipe. 

truVUE Inspection Technologies 30

Page 11: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

11

Corrosion RatesCorrosion Rates

Schedule 40Acceptable Rate < 0.5 MPYLow Rate = 1 MPYAggressive Rate > 3.0 MPY

Schedule 10Aggressive Rate > 1.5 MPY

truVUE Inspection Technologies 31

4” Pipe Wall Thickness Comparison4” Pipe Wall Thickness Comparison

0.25

0.3

0.350.337

0.237

ss (in)

truVUE Inspection Technologies 32

0

0.05

0.1

0.15

0.2

Sch 80 Sch 40 Sch 10 Sch 5

0.1200.083

Thickn

es

Corrosion EffectCorrosion Effect

Steel, when corroded back into iron oxide (rust), produces a greater volume of less dense material by a factor of approximately 20 times. 

A 4” Schedule 40 pipe corroding at a rate of 5 MPY will lose about 20 lbs in 100 ft in 1 year.

2 years of corroding means 40 lbs of rust is in the 4 inch pipe.  

truVUE Inspection Technologies 33

Page 12: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

12

Wet Pipe System CorrosionWet Pipe System Corrosion

Oxygen is the rate limiting component. 

4Fe(s) + 3O2(g) ---> 2Fe2O3(s)

truVUE Inspection Technologies 34

Dry Pipe & Dry Pipe & PreactionPreactionSystem CorrosionSystem Corrosion

Oxygen corrosion is more aggressive in dry and preaction systems. 

Oxygen corrosion is limited to areas of the pipe that are wet with liquid moisture.

Oxygen for the corrosion reaction is in great excess and it will continue to react.

truVUE Inspection Technologies 35

Dry Pipe & Dry Pipe & PreactionPreactionSystem CorrosionSystem Corrosion

Temperature fluctuations cause the compressed air in the system piping to fall below the dew point, water condenses on the pipe walls as small droplets. droplets. 

Distilled water 

CO2 dissolves in the distilled water and forms carbonic acid which reduces the pH to about 5.5 

truVUE Inspection Technologies 36

Page 13: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

13

Conditions and ResultsConditions and ResultsCondition for Corrosion Type(s) of 

DepositsType(s) of Corrosion

Relative Rates of Corrosion

Relative Rates of Penetration

Iron + Water + Oxygen Generalized (rust-type) Generalized (rust-type) Slow Slow

Iron + Water + Oxygen + Chloride Generalized GeneralizedSome pitting

Generalized fasterPitting faster

Faster

Iron + Water + Oxygen + Microbes Isolated LocalizedPittingCreviceUnder-deposit acid attackOxygen

Generalized slowerPitting much faster

Much faster

truVUE Inspection Technologies 37

Iron + Water + Oxygen + Microbes + Chloride

Isolated LocalizedPittingCreviceUnder-deposit acid attackOxygen

Generalized fasterPitting very fast

Very fast

Iron + Water (no oxygen) None None Very slow, if any Very slow, if any

Iron + Water + Chloride (no oxygen) None None Very slow, if any Very slow, if any

Iron + Water + Microbes (no oxygen) Tends to be localized Tends to be localized Slow, in most cases Slow, in most cases

Iron + Water + Microbes + Chloride (no oxygen)

Localized Localized Faster than without salt

Faster than without salt

Iron + Oxygen + Microbes + Chloride (no water)

None None None None

Accelerate the Rate of CorrosionAccelerate the Rate of Corrosion1. More oxygen becomes available. 2. Solids (e.g., iron oxides, particulate 

matter, etc.). 3. Microbial contamination. 3 c ob a co ta at o4. Mechanical deposit removal – iron oxide 

corrosion by‐product. 5. Draining and refilling the system. 6. The low pH of condensate (dry and 

preaction systems). truVUE Inspection Technologies 38

AgendaAgenda

IntroductionFactsTypes of corrosion F t  th t  l t   i  Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion 

truVUE Inspection Technologies 39

Page 14: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

14

Corrosion Corrosion ––NFPA 25NFPA 25

1.2 Purpose.The purpose of this document is to provide requirements that ensure a reasonable degree of protection for life and property from fire through i i  i ti  t ti   d  i t  minimum inspection, testing, and maintenance 

methods for water‐based fire protection systems. In those cases where it is determined that an existing situation involves a distinct hazard to life or property, the authority having jurisdiction shall be permitted to require inspection, testing, and maintenance methods in excess of those required by the standard.

truVUE Inspection Technologies 40

13.2.1  An investigation of piping and branch line conditions shall be conducted every 5 years by opening a flushing connection at the end of one main and by removing a sprinkler toward the end 

NFPA 25 RequirementNFPA 25 Requirement

main and by removing a sprinkler toward the end of one branch line for the purpose of  investigating for the presence of foreign organic and inorganic  material.

13.2.1.1  Alternative nondestructive examination methods shall be permitted.

truVUE Inspection Technologies 41

Two levels of inspection:1. Assessment of internal condition – every 5 

years.  Does not require taking the piping apart

NFPA 25 Requirements and OptionsNFPA 25 Requirements and Options

apart.

2. Obstruction investigation – triggered by certain events. 

truVUE Inspection Technologies 42

Page 15: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

15

Obstruction Investigations: Obstruction Investigations: When to Conduct per NFPA 25When to Conduct per NFPA 25

The discharge of obstructive material during routine water tests

Foreign materials in fire pumps, in dry pipe valves, or in check valves

Foreign material in water during drain tests or plugging of inspector’s test connection (s)

Plugged sprinklers

Plugged piping in sprinkler systems dismantled during building alterations

truVUE Inspection Technologies 43

Obstruction Investigations:Obstruction Investigations:When to Conduct cont…When to Conduct cont…

Abnormally frequent false tripping of a dry pipe valve (s)

A system that is returned to service after an extended shutdown (greater than 1 year)

A system has been supplied with raw water via the fire department connection

Pinhole leaks

A 50‐percent increase in the time it takes water to travel to the inspector’s test connection from the time the valve trips during a full flow trip test of a dry pipe sprinkler system when compared to the original system acceptance test

truVUE Inspection Technologies 44

Justification for MaintenanceJustification for Maintenance

The NFPA ranks improper maintenance as the second most common reason for sprinkler system failure. 

National Fire Sprinkler Association lists corrosion as a major cause behind sprinkler system failure.

truVUE Inspection Technologies 45

Page 16: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

16

AgendaAgenda

IntroductionFactsTypes of corrosion F t  th t  l t   i  Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion 

truVUE Inspection Technologies 46

Steps to Assess Corrosion DamageSteps to Assess Corrosion Damage

There are five critical steps to addressing the damaging effects of corrosion, and the factors include: 

1. Understanding the effects of the destructive gprocess. 

2. Properly assessing corrosion damage. 3. Correcting system deficiencies. 4. Implementing a cleaning program.5. Corrosion mitigation plan and ongoing monitoring.

truVUE Inspection Technologies 47

Step 1: EffectsStep 1: Effects

Effect of the destructive process ATTACKS WEAKEST LINK

truVUE Inspection Technologies 48

Page 17: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

17

Locations of the Weakest LinkLocations of the Weakest Link

The thinnest pipe wall is often the first to go (Sch 5 & Sch 10) 

Piping near the higher elevations of a wet‐pipe system 

Closest to the water source is also at high risk 

truVUE Inspection Technologies 49

Locations of the Weakest LinkLocations of the Weakest Link

On a dry‐pipe system, piping near the low areas where water accumulates is at a higher corrosive risk

At the threaded ends of the piping (adjacent to fittings), where the pipe wall is the thinnest. 

truVUE Inspection Technologies 50Mohinder L. Nayyar, PIPING HANDBOOK, Seventh Edition, 2000, McGraw-Hill

Step 2: Assessing Corrosion DamageStep 2: Assessing Corrosion Damage

Some of the options to assess the corrosion damage are: 1. Corrosion Coupons2. Visual Observation (Section Removal)3. Borescope (Video)4. Water Testing5. Ultrasonic Testing

truVUE Inspection Technologies 51

Page 18: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

18

AnalysisTechnique

Corrosion Coupons

Cross Section Removal

Video Inspection

Water Testing

Ultrasonic Testing

Drain System YES YES YES NO NO

Change in System Conditions

YES YES YES NO NO

AnalysisTechnique

Corrosion Coupons

Cross Section Removal

Video Inspection

Water Testing

Drain System YES YES YES NO

Change in System Conditions

YES YES YES NO

AnalysisTechnique

Corrosion Coupons

Cross Section Removal

Video Inspection

Drain System YES YES YES

Change in System Conditions

YES YES YES

AnalysisTechnique

Corrosion Coupons

Cross Section Removal

Drain System YES YES

Change in System Conditions

YES YES

Comparison:Comparison:Assessment AlternativesAssessment AlternativesAnalysisTechnique

Corrosion Coupons

Drain System YES

Change in System Conditions

YES

AnalysisTechnique

Drain System

Change in System Conditions

Holistic Analysis

NO NO NO NO YES

Determine Remaining Service Life

NO NO NO NO YES

Cost/Sample LOW HIGH MODERATE MODERATE MODERATE

Cost/Sq. Ft. MODERATE HIGH HIGH LOW LOW

Holistic Analysis

NO NO NO NO

Determine Remaining Service Life

NO NO NO NO

Cost/Sample LOW HIGH MODERATE MODERATE

Cost/Sq. Ft. MODERATE HIGH HIGH LOW

Holistic Analysis

NO NO NO

Determine Remaining Service Life

NO NO NO

Cost/Sample LOW HIGH MODERATE

Cost/Sq. Ft. MODERATE HIGH HIGH

Holistic Analysis

NO NO

Determine Remaining Service Life

NO NO

Cost/Sample LOW HIGH

Cost/Sq. Ft. MODERATE HIGH

truVUE Inspection Technologies 52

Holistic Analysis

NO

Determine Remaining Service Life

NO

Cost/Sample LOW

Cost/Sq. Ft. MODERATE

Holistic Analysis

Determine Remaining Service Life

Cost/Sample

Cost/Sq. Ft.

Analysis Example: Analysis Example: Parking GarageParking Garage

+200K Sq. Feet, Multiple LevelsConstructed ~2002Unclear Service History ?Extent of Corrosion is Unknown

truVUE Inspection Technologies 53

CHALLENGE: HOW TO COST EFFECTIVELY ASSESS WHICH AREAS NEED REPLACEMENT?

?Application: Application: Using Video InspectionUsing Video Inspection

?truVUE Inspection Technologies 54

Video Inspection requires access to the system

Cannot determine the amount of corrosion

?

Page 19: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

19

Application: Application: Using Ultrasonic TestingUsing Ultrasonic Testing

truVUE Inspection Technologies 55

Ultrasonic Inspection does not require access

Determines the precise amount of corrosion

Application: Application: Data AnalysisData Analysis

Thickness data by itself is meaninglessRequires a contextual assessmentRaw data needs analysisClassifies each test locationAllows the creation of an “actionable plan”

truVUE Inspection Technologies 56

Acceptable Monitor Potential forFailure

REPLACE

Step 3: Correcting system deficienciesStep 3: Correcting system deficiencies

Little Damage Medium Damage Heavy Damage 

Corrosion is divided into 3 categories:

truVUE Inspection Technologies 57

flushing some replacement & flushing

complete pipe array or parts replaced

Page 20: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

20

Step 4: Corrosion CleaningStep 4: Corrosion Cleaning

FlushingHydraulic methodHydropneumatic method

Once a system is properly cleaned, a secondary corrosion inhibitor can be injected if applicable.SolutionPowder

truVUE Inspection Technologies 58

Courtesy of NFPA 25

Step 5: Corrosion Control MeasuresStep 5: Corrosion Control Measures

When designing provide corrosion allowance to extend the life of the piping.  

Inspect piping for wall thinning or build‐up of corrosion. Using non‐destructive technique of ultrasound An internal inspection using video borascope 

truVUE Inspection Technologies 59

Corrosion Control MeasuresCorrosion Control Measures

Flush the piping system with a solution to remove insoluble material and biofilms

Remove all filings from cutting  threading  & Remove all filings from cutting, threading, & drilling

Keep pH below 9.0

truVUE Inspection Technologies 60

Page 21: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

21

Corrosion Control MeasuresCorrosion Control Measures

Treat water to minimize chloride & sulphate concentrations and reduce acid corrosion

Limit organic matter and lubricantsLimit organic matter and lubricants

Internal coating of the pipe to block electrochemical reactions

truVUE Inspection Technologies 61

Corrosion Control MeasuresCorrosion Control Measures

Uncontaminated water source.

Reduce the frequency of filling a piping system.

Vent trapped air to minimize oxygen in the system

Institute a monitoring program.

truVUE Inspection Technologies 62

AgendaAgenda

IntroductionFactsTypes of corrosion F t  th t  l t   i  Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion 

truVUE Inspection Technologies 63

Page 22: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

22

Myth:Microbiologically‐influenced corrosion (MIC) is the major corrosion problem in fire protection systems. 

Myth Myth ‐‐RealityReality

Reality:In a study of 155 cases of failed sprinkler components collected between 1994 and 2000, the FM Global metallurgical laboratory found evidence of MIC in about 40% of the cases.  

truVUE Inspection Technologies 64

Myth:Galvanized piping solves all corrosion problems. 

Reality:

Myth Myth ‐‐RealityReality

truVUE Inspection Technologies 65

Reality:Galvanized piping allows zinc to corrode first.  Lack of zinc in an area becomes the point where corrosion is extremely aggressive to the steel.

Galvanized piping MIGHT be PART of a solution.  

Myth:Roll grooved piping will decrease corrosion because material is not removed from the pipe.

Myth Myth ‐‐RealityReality

truVUE Inspection Technologies 66

Reality:Roll groove piping creates a dam effect inside the piping, allowing water to be trapped in dry pipe systems. 

Page 23: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

23

Myth:Water treating dry and preaction systems will stop corrosion. 

Reality:

Myth Myth ‐‐RealityReality

truVUE Inspection Technologies 67

Reality:This is an oxymoron type of approach. No water is supposed to be in these systems.Therefore, treating a system without water does not address the basis of the corrosion problem.

Specific Building SituationsSpecific Building SituationsProblem 1:

What are the options for meeting NFPA 25 obstruction investigation requirements?

Solution 1:

Annual inspections including:p g1. external visual,2. internal by borescope, 3. water analysis chemical & microbiological, 4. solids and tubercles (if found in flow test) 5. ultrasonic pipe wall thickness evaluation. Cost: VariesEffectiveness: Varies depending on method.

truVUE Inspection Technologies 68

Specific Building SituationsSpecific Building Situations

Problem 2:What is an option of localized corrosion monitoring?

Solution 2: Corrosion monitoring and evaluation of coupons and/or report by corrosion monitoring probe. 

Cost: LowEffectiveness: Very limited to localized area.

truVUE Inspection Technologies 69

Page 24: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

24

Specific Building SituationsSpecific Building SituationsProblem 3:

Are there coatings available for treating corrosion?

Solution 3: It is evolving, corrosion mitigation by treating the internal system is typically done before corrosion occurs.

Cost: Moderate.Effectiveness: Very limited in most cases.

truVUE Inspection Technologies 70

Specific Building SituationsSpecific Building SituationsProblem 4:

What is one option for reducing corrosion in dry systems?

l iSolution 4: Convert to Nitrogen. 

Cost: LowEffectiveness: Could be effective for general corrosion. 

truVUE Inspection Technologies 71

Specific Building SituationsSpecific Building SituationsProblem 5:

What is the worse case solution for corrosion in a system?

Solution 5: 

Remediation may require the replacement of piping where Remediation may require the replacement of piping where integrity, flow restrictions and heavy tuberculation are present. 

Cost: High

Effectiveness: Limited if underlying reason for corrosion is not addressed.

truVUE Inspection Technologies 72

Page 25: What’s Eating Your Pipes? gp eating your pipes - … · Microbiologically Influenced Corrosion (MIC) ¾Corrosion caused by bacteria ¾Two main classes of bacteria 9Aerobic–needs

3/11/2015

25

ConclusionsConclusions

We only scratched the surface of corrosion in fire protection piping.

Corrosion is a very real threat to the Corrosion is a very real threat to the functionality of fire protection systems.

Properly address corrosion has to be done on a case by case basis.  

truVUE Inspection Technologies 73

A Word of CautionA Word of Caution

Need to use all appropriate evaluation options. 

There isn't an all encompassing single type of mitigation technique  mitigation technique. 

Ignoring a problem will not make it go away.  

truVUE Inspection Technologies 74


Recommended