3/11/2015
1
What’s Eating Your Pipes?
Douglas Nadeau, MSFPE, PE, CFPS, LEED APVice President of truVUE Inspection TechnologiesPresident of RAN Fire Protection Engineering, PCTel: 518-859-0122Email: [email protected]
g pHow Corrosion Can Cause Your Sprinkler System to
Fail and How to Fight It
AgendaAgenda
IntroductionFactsTypes of corrosion F t th t l t i Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion
truVUE Inspection Technologies 2
A Story of a Nursing HomeA Story of a Nursing Home
Nursing home facilities average 2,300 fires nationally per year.
Centers for Medicare & Medicaid Services mandate.
August 13, 2013.
truVUE Inspection Technologies 3
3/11/2015
2
A Story of a Nursing HomeA Story of a Nursing Home
April 30, 1998 at the Lamoni Nursing Center.
Fire in the north wing laundry room.
Total failure of the sprinkler system.
A single head should have controlled the fire.
truVUE Inspection Technologies 4
A Story of a Nursing HomeA Story of a Nursing Home
Dry system had been installed in 1972.
Sprinkler found plugged with hardened, rust‐colored granular material colored, granular material.
Every head in the wing.
Branch lines severely corroded and partially plugged.
truVUE Inspection Technologies 5
In recent years a state agency had a fire which ended up killing some group home
id t
A Story of ReactionA Story of Reaction
residents.
The reaction – fix all sprinkler systems that might have problems.
State identified 5 group homes.truVUE Inspection Technologies 6
3/11/2015
3
Just one of the homes had a problem due to leaking. The other 4 were unknown but built at the same time.
A Story of ReactionA Story of Reaction
The reaction was rip out all the systems.
The solution required education in corrosion.
Ultrasonic testing was performed.truVUE Inspection Technologies 7
4 out of the 5 group homes had a corrosion issue.
One of the homes was close to near perfect
A Story of ReactionA Story of Reaction
condition.
Replaced 4 systems, saved 1.
Over a $150,000 savings for a small investment.
truVUE Inspection Technologies 8
Case Example: Case Example: Five HighFive High‐‐Rise BuildingsRise BuildingsWhere to start?Where to start?
9truVUE Inspection Technologies
3/11/2015
4
Given:Given:5 High‐Rises. 44 stories and 22 stories.44 stories and 22 stories.Fully occupied.Standpipe system only, no sprinkler system.Standpipe system only, no sprinkler system.
Problems:Problems:
Case ExampleCase Example:: HighHigh‐‐RisesRises
Problems:Problems:Waterflow switches not working. Investigation reveals slime in water when replacing switches.Investigation reveals slime in water when replacing switches.Plugged piping observed.Extent of problem not known.Extent of problem not known.
Options:Options:Destructive testing – one location – cost $18,000 + downtime Ultrasonic Testing Ultrasonic Testing –– 250 locations 250 locations ––Cost $25,000 Cost $25,000 –– No downtime, No downtime, more locations.more locations.
10truVUE Inspection Technologies
AgendaAgenda
IntroductionFactsTypes of corrosion F t th t l t i Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion
truVUE Inspection Technologies 11
Corrosion Corrosion ‐‐DefinitionDefinition
Naturally destroys metal at a very slow rate
Reactions between metal + water = rust
Result ‐ "pit" the inside pipe wall or deposit tubercles (corrosion byproducts) there
truVUE Inspection Technologies 12
3/11/2015
5
Losses Due To CorrosionLosses Due To Corrosion
truVUE Inspection Technologies 13
Corrosion can be Indicative of Other Corrosion can be Indicative of Other ProblemsProblems
Non‐compliance with NFPA 13
Improper installation including improper slope, trapped air, or inadequate drainage
Improper operation or maintenance
Possible MIC activity
truVUE Inspection Technologies 14
Corrosion Can Cause Pinhole Leaks Corrosion Can Cause Pinhole Leaks
Disruptive to normal operations Potential damage to equipment and/or property Lead to loss of revenue due to shutdowns Cause the continuous introduction of oxygenated water due to repeated draining for repairs Lead to costly ongoing repairs
truVUE Inspection Technologies 15
3/11/2015
6
truVUE Inspection Technologies 16
truVUE Inspection Technologies 17
truVUE Inspection Technologies 18
3/11/2015
7
AgendaAgenda
IntroductionFactsTypes of corrosion F t th t l t i Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion
truVUE Inspection Technologies 19
Two Main Types of CorrosionTwo Main Types of Corrosion
Interior Exterior
truVUE Inspection Technologies 20
Exterior CorrosionExterior Corrosion
Corrosive atmosphere exists = corrosion‐resistant sprinklers.
Stainless steel sprinklersSprinkler coatings
Shop paint and manufacturer's coatings on the outside of the piping help some.
Rust film (oxide layer) that is found on pipe and fitting exteriors actually serves as a corrosion inhibitor.
truVUE Inspection Technologies 21
3/11/2015
8
Types of Interior CorrosionTypes of Interior Corrosion
Electrochemical CorrosionUnder Deposit CorrosionGalvanic CorrosionMi bi l i ll I fl d C i (MIC)Microbiologically Influenced Corrosion (MIC)Limescale AccumulationHypochlorite CorrosionDezincificationWelding
truVUE Inspection Technologies 22
Electrochemical CorrosionElectrochemical Corrosion
Oxygen CorrosionSteel pipe is 98% iron.Oxygen dissolved in water react with the iron
truVUE Inspection Technologies 23
iron.Forms iron hydroxide (rust).Fresh water = restart of corrosion process.
Under Deposit CorrosionUnder Deposit Corrosion
Very common Forms under sediment, deposits of debris or corrosion productspAs corrosion continues the pit will deepenA tubercle could form over the pit
truVUE Inspection Technologies 24
3/11/2015
9
Galvanic CorrosionGalvanic Corrosion
Dissimilar metals in physical contact
Requires the presences of waterRequires the presences of water
Black pipe connected to galvanized pipe – the zinc will dissolve
truVUE Inspection Technologies 25
Microbiologically Influenced Corrosion Microbiologically Influenced Corrosion (MIC)(MIC)
Corrosion caused by bacteriaTwo main classes of bacteriabacteria
Aerobic – needs oxygenAnaerobic – doesn’t require oxygen
6 primary types
truVUE Inspection Technologies 26
Mid‐1980s.
More prevalent in areaswith warmer climates
Microbiologically Influenced Corrosion Microbiologically Influenced Corrosion (MIC)(MIC)
with warmer climates.
Hard data confirming known causes of MIC in sprinkler systems is scarce.
truVUE Inspection Technologies 27
3/11/2015
10
AgendaAgenda
IntroductionFactsTypes of corrosion F t th t l t i Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion
truVUE Inspection Technologies 28
LifespanLifespan
Anticipated lifespan of a sprinkler system is 30‐40 years.
Lif f t i i kl t d Lifespan of wet‐pipe sprinkler systems exceed those of dry‐pipe systems.
Any testing over and above NFPA 25 or insurance carrier guidelines will cause added oxygen to rust system piping prematurely.
truVUE Inspection Technologies 29
LifespanLifespan
The type of black steel (domestic or imported) used to make the pipe matters little.
Using galvanized steel can help with a longer system life.
It is mainly what goes into the pipe.
truVUE Inspection Technologies 30
3/11/2015
11
Corrosion RatesCorrosion Rates
Schedule 40Acceptable Rate < 0.5 MPYLow Rate = 1 MPYAggressive Rate > 3.0 MPY
Schedule 10Aggressive Rate > 1.5 MPY
truVUE Inspection Technologies 31
4” Pipe Wall Thickness Comparison4” Pipe Wall Thickness Comparison
0.25
0.3
0.350.337
0.237
ss (in)
truVUE Inspection Technologies 32
0
0.05
0.1
0.15
0.2
Sch 80 Sch 40 Sch 10 Sch 5
0.1200.083
Thickn
es
Corrosion EffectCorrosion Effect
Steel, when corroded back into iron oxide (rust), produces a greater volume of less dense material by a factor of approximately 20 times.
A 4” Schedule 40 pipe corroding at a rate of 5 MPY will lose about 20 lbs in 100 ft in 1 year.
2 years of corroding means 40 lbs of rust is in the 4 inch pipe.
truVUE Inspection Technologies 33
3/11/2015
12
Wet Pipe System CorrosionWet Pipe System Corrosion
Oxygen is the rate limiting component.
4Fe(s) + 3O2(g) ---> 2Fe2O3(s)
truVUE Inspection Technologies 34
Dry Pipe & Dry Pipe & PreactionPreactionSystem CorrosionSystem Corrosion
Oxygen corrosion is more aggressive in dry and preaction systems.
Oxygen corrosion is limited to areas of the pipe that are wet with liquid moisture.
Oxygen for the corrosion reaction is in great excess and it will continue to react.
truVUE Inspection Technologies 35
Dry Pipe & Dry Pipe & PreactionPreactionSystem CorrosionSystem Corrosion
Temperature fluctuations cause the compressed air in the system piping to fall below the dew point, water condenses on the pipe walls as small droplets. droplets.
Distilled water
CO2 dissolves in the distilled water and forms carbonic acid which reduces the pH to about 5.5
truVUE Inspection Technologies 36
3/11/2015
13
Conditions and ResultsConditions and ResultsCondition for Corrosion Type(s) of
DepositsType(s) of Corrosion
Relative Rates of Corrosion
Relative Rates of Penetration
Iron + Water + Oxygen Generalized (rust-type) Generalized (rust-type) Slow Slow
Iron + Water + Oxygen + Chloride Generalized GeneralizedSome pitting
Generalized fasterPitting faster
Faster
Iron + Water + Oxygen + Microbes Isolated LocalizedPittingCreviceUnder-deposit acid attackOxygen
Generalized slowerPitting much faster
Much faster
truVUE Inspection Technologies 37
Iron + Water + Oxygen + Microbes + Chloride
Isolated LocalizedPittingCreviceUnder-deposit acid attackOxygen
Generalized fasterPitting very fast
Very fast
Iron + Water (no oxygen) None None Very slow, if any Very slow, if any
Iron + Water + Chloride (no oxygen) None None Very slow, if any Very slow, if any
Iron + Water + Microbes (no oxygen) Tends to be localized Tends to be localized Slow, in most cases Slow, in most cases
Iron + Water + Microbes + Chloride (no oxygen)
Localized Localized Faster than without salt
Faster than without salt
Iron + Oxygen + Microbes + Chloride (no water)
None None None None
Accelerate the Rate of CorrosionAccelerate the Rate of Corrosion1. More oxygen becomes available. 2. Solids (e.g., iron oxides, particulate
matter, etc.). 3. Microbial contamination. 3 c ob a co ta at o4. Mechanical deposit removal – iron oxide
corrosion by‐product. 5. Draining and refilling the system. 6. The low pH of condensate (dry and
preaction systems). truVUE Inspection Technologies 38
AgendaAgenda
IntroductionFactsTypes of corrosion F t th t l t i Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion
truVUE Inspection Technologies 39
3/11/2015
14
Corrosion Corrosion ––NFPA 25NFPA 25
1.2 Purpose.The purpose of this document is to provide requirements that ensure a reasonable degree of protection for life and property from fire through i i i ti t ti d i t minimum inspection, testing, and maintenance
methods for water‐based fire protection systems. In those cases where it is determined that an existing situation involves a distinct hazard to life or property, the authority having jurisdiction shall be permitted to require inspection, testing, and maintenance methods in excess of those required by the standard.
truVUE Inspection Technologies 40
13.2.1 An investigation of piping and branch line conditions shall be conducted every 5 years by opening a flushing connection at the end of one main and by removing a sprinkler toward the end
NFPA 25 RequirementNFPA 25 Requirement
main and by removing a sprinkler toward the end of one branch line for the purpose of investigating for the presence of foreign organic and inorganic material.
13.2.1.1 Alternative nondestructive examination methods shall be permitted.
truVUE Inspection Technologies 41
Two levels of inspection:1. Assessment of internal condition – every 5
years. Does not require taking the piping apart
NFPA 25 Requirements and OptionsNFPA 25 Requirements and Options
apart.
2. Obstruction investigation – triggered by certain events.
truVUE Inspection Technologies 42
3/11/2015
15
Obstruction Investigations: Obstruction Investigations: When to Conduct per NFPA 25When to Conduct per NFPA 25
The discharge of obstructive material during routine water tests
Foreign materials in fire pumps, in dry pipe valves, or in check valves
Foreign material in water during drain tests or plugging of inspector’s test connection (s)
Plugged sprinklers
Plugged piping in sprinkler systems dismantled during building alterations
truVUE Inspection Technologies 43
Obstruction Investigations:Obstruction Investigations:When to Conduct cont…When to Conduct cont…
Abnormally frequent false tripping of a dry pipe valve (s)
A system that is returned to service after an extended shutdown (greater than 1 year)
A system has been supplied with raw water via the fire department connection
Pinhole leaks
A 50‐percent increase in the time it takes water to travel to the inspector’s test connection from the time the valve trips during a full flow trip test of a dry pipe sprinkler system when compared to the original system acceptance test
truVUE Inspection Technologies 44
Justification for MaintenanceJustification for Maintenance
The NFPA ranks improper maintenance as the second most common reason for sprinkler system failure.
National Fire Sprinkler Association lists corrosion as a major cause behind sprinkler system failure.
truVUE Inspection Technologies 45
3/11/2015
16
AgendaAgenda
IntroductionFactsTypes of corrosion F t th t l t i Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion
truVUE Inspection Technologies 46
Steps to Assess Corrosion DamageSteps to Assess Corrosion Damage
There are five critical steps to addressing the damaging effects of corrosion, and the factors include:
1. Understanding the effects of the destructive gprocess.
2. Properly assessing corrosion damage. 3. Correcting system deficiencies. 4. Implementing a cleaning program.5. Corrosion mitigation plan and ongoing monitoring.
truVUE Inspection Technologies 47
Step 1: EffectsStep 1: Effects
Effect of the destructive process ATTACKS WEAKEST LINK
truVUE Inspection Technologies 48
3/11/2015
17
Locations of the Weakest LinkLocations of the Weakest Link
The thinnest pipe wall is often the first to go (Sch 5 & Sch 10)
Piping near the higher elevations of a wet‐pipe system
Closest to the water source is also at high risk
truVUE Inspection Technologies 49
Locations of the Weakest LinkLocations of the Weakest Link
On a dry‐pipe system, piping near the low areas where water accumulates is at a higher corrosive risk
At the threaded ends of the piping (adjacent to fittings), where the pipe wall is the thinnest.
truVUE Inspection Technologies 50Mohinder L. Nayyar, PIPING HANDBOOK, Seventh Edition, 2000, McGraw-Hill
Step 2: Assessing Corrosion DamageStep 2: Assessing Corrosion Damage
Some of the options to assess the corrosion damage are: 1. Corrosion Coupons2. Visual Observation (Section Removal)3. Borescope (Video)4. Water Testing5. Ultrasonic Testing
truVUE Inspection Technologies 51
3/11/2015
18
AnalysisTechnique
Corrosion Coupons
Cross Section Removal
Video Inspection
Water Testing
Ultrasonic Testing
Drain System YES YES YES NO NO
Change in System Conditions
YES YES YES NO NO
AnalysisTechnique
Corrosion Coupons
Cross Section Removal
Video Inspection
Water Testing
Drain System YES YES YES NO
Change in System Conditions
YES YES YES NO
AnalysisTechnique
Corrosion Coupons
Cross Section Removal
Video Inspection
Drain System YES YES YES
Change in System Conditions
YES YES YES
AnalysisTechnique
Corrosion Coupons
Cross Section Removal
Drain System YES YES
Change in System Conditions
YES YES
Comparison:Comparison:Assessment AlternativesAssessment AlternativesAnalysisTechnique
Corrosion Coupons
Drain System YES
Change in System Conditions
YES
AnalysisTechnique
Drain System
Change in System Conditions
Holistic Analysis
NO NO NO NO YES
Determine Remaining Service Life
NO NO NO NO YES
Cost/Sample LOW HIGH MODERATE MODERATE MODERATE
Cost/Sq. Ft. MODERATE HIGH HIGH LOW LOW
Holistic Analysis
NO NO NO NO
Determine Remaining Service Life
NO NO NO NO
Cost/Sample LOW HIGH MODERATE MODERATE
Cost/Sq. Ft. MODERATE HIGH HIGH LOW
Holistic Analysis
NO NO NO
Determine Remaining Service Life
NO NO NO
Cost/Sample LOW HIGH MODERATE
Cost/Sq. Ft. MODERATE HIGH HIGH
Holistic Analysis
NO NO
Determine Remaining Service Life
NO NO
Cost/Sample LOW HIGH
Cost/Sq. Ft. MODERATE HIGH
truVUE Inspection Technologies 52
Holistic Analysis
NO
Determine Remaining Service Life
NO
Cost/Sample LOW
Cost/Sq. Ft. MODERATE
Holistic Analysis
Determine Remaining Service Life
Cost/Sample
Cost/Sq. Ft.
Analysis Example: Analysis Example: Parking GarageParking Garage
+200K Sq. Feet, Multiple LevelsConstructed ~2002Unclear Service History ?Extent of Corrosion is Unknown
truVUE Inspection Technologies 53
CHALLENGE: HOW TO COST EFFECTIVELY ASSESS WHICH AREAS NEED REPLACEMENT?
?Application: Application: Using Video InspectionUsing Video Inspection
?truVUE Inspection Technologies 54
Video Inspection requires access to the system
Cannot determine the amount of corrosion
?
3/11/2015
19
Application: Application: Using Ultrasonic TestingUsing Ultrasonic Testing
truVUE Inspection Technologies 55
Ultrasonic Inspection does not require access
Determines the precise amount of corrosion
Application: Application: Data AnalysisData Analysis
Thickness data by itself is meaninglessRequires a contextual assessmentRaw data needs analysisClassifies each test locationAllows the creation of an “actionable plan”
truVUE Inspection Technologies 56
Acceptable Monitor Potential forFailure
REPLACE
Step 3: Correcting system deficienciesStep 3: Correcting system deficiencies
Little Damage Medium Damage Heavy Damage
Corrosion is divided into 3 categories:
truVUE Inspection Technologies 57
flushing some replacement & flushing
complete pipe array or parts replaced
3/11/2015
20
Step 4: Corrosion CleaningStep 4: Corrosion Cleaning
FlushingHydraulic methodHydropneumatic method
Once a system is properly cleaned, a secondary corrosion inhibitor can be injected if applicable.SolutionPowder
truVUE Inspection Technologies 58
Courtesy of NFPA 25
Step 5: Corrosion Control MeasuresStep 5: Corrosion Control Measures
When designing provide corrosion allowance to extend the life of the piping.
Inspect piping for wall thinning or build‐up of corrosion. Using non‐destructive technique of ultrasound An internal inspection using video borascope
truVUE Inspection Technologies 59
Corrosion Control MeasuresCorrosion Control Measures
Flush the piping system with a solution to remove insoluble material and biofilms
Remove all filings from cutting threading & Remove all filings from cutting, threading, & drilling
Keep pH below 9.0
truVUE Inspection Technologies 60
3/11/2015
21
Corrosion Control MeasuresCorrosion Control Measures
Treat water to minimize chloride & sulphate concentrations and reduce acid corrosion
Limit organic matter and lubricantsLimit organic matter and lubricants
Internal coating of the pipe to block electrochemical reactions
truVUE Inspection Technologies 61
Corrosion Control MeasuresCorrosion Control Measures
Uncontaminated water source.
Reduce the frequency of filling a piping system.
Vent trapped air to minimize oxygen in the system
Institute a monitoring program.
truVUE Inspection Technologies 62
AgendaAgenda
IntroductionFactsTypes of corrosion F t th t l t i Factors that accelerate corrosion NFPA – 25Sizing up the problem Mitigation Conclusion
truVUE Inspection Technologies 63
3/11/2015
22
Myth:Microbiologically‐influenced corrosion (MIC) is the major corrosion problem in fire protection systems.
Myth Myth ‐‐RealityReality
Reality:In a study of 155 cases of failed sprinkler components collected between 1994 and 2000, the FM Global metallurgical laboratory found evidence of MIC in about 40% of the cases.
truVUE Inspection Technologies 64
Myth:Galvanized piping solves all corrosion problems.
Reality:
Myth Myth ‐‐RealityReality
truVUE Inspection Technologies 65
Reality:Galvanized piping allows zinc to corrode first. Lack of zinc in an area becomes the point where corrosion is extremely aggressive to the steel.
Galvanized piping MIGHT be PART of a solution.
Myth:Roll grooved piping will decrease corrosion because material is not removed from the pipe.
Myth Myth ‐‐RealityReality
truVUE Inspection Technologies 66
Reality:Roll groove piping creates a dam effect inside the piping, allowing water to be trapped in dry pipe systems.
3/11/2015
23
Myth:Water treating dry and preaction systems will stop corrosion.
Reality:
Myth Myth ‐‐RealityReality
truVUE Inspection Technologies 67
Reality:This is an oxymoron type of approach. No water is supposed to be in these systems.Therefore, treating a system without water does not address the basis of the corrosion problem.
Specific Building SituationsSpecific Building SituationsProblem 1:
What are the options for meeting NFPA 25 obstruction investigation requirements?
Solution 1:
Annual inspections including:p g1. external visual,2. internal by borescope, 3. water analysis chemical & microbiological, 4. solids and tubercles (if found in flow test) 5. ultrasonic pipe wall thickness evaluation. Cost: VariesEffectiveness: Varies depending on method.
truVUE Inspection Technologies 68
Specific Building SituationsSpecific Building Situations
Problem 2:What is an option of localized corrosion monitoring?
Solution 2: Corrosion monitoring and evaluation of coupons and/or report by corrosion monitoring probe.
Cost: LowEffectiveness: Very limited to localized area.
truVUE Inspection Technologies 69
3/11/2015
24
Specific Building SituationsSpecific Building SituationsProblem 3:
Are there coatings available for treating corrosion?
Solution 3: It is evolving, corrosion mitigation by treating the internal system is typically done before corrosion occurs.
Cost: Moderate.Effectiveness: Very limited in most cases.
truVUE Inspection Technologies 70
Specific Building SituationsSpecific Building SituationsProblem 4:
What is one option for reducing corrosion in dry systems?
l iSolution 4: Convert to Nitrogen.
Cost: LowEffectiveness: Could be effective for general corrosion.
truVUE Inspection Technologies 71
Specific Building SituationsSpecific Building SituationsProblem 5:
What is the worse case solution for corrosion in a system?
Solution 5:
Remediation may require the replacement of piping where Remediation may require the replacement of piping where integrity, flow restrictions and heavy tuberculation are present.
Cost: High
Effectiveness: Limited if underlying reason for corrosion is not addressed.
truVUE Inspection Technologies 72
3/11/2015
25
ConclusionsConclusions
We only scratched the surface of corrosion in fire protection piping.
Corrosion is a very real threat to the Corrosion is a very real threat to the functionality of fire protection systems.
Properly address corrosion has to be done on a case by case basis.
truVUE Inspection Technologies 73
A Word of CautionA Word of Caution
Need to use all appropriate evaluation options.
There isn't an all encompassing single type of mitigation technique mitigation technique.
Ignoring a problem will not make it go away.
truVUE Inspection Technologies 74