Soft Drawn Solid or Stranded 600 Volt UL 90°C THHN/THWN Insulation Copper Conductor Application: For use on insulators for overhead distribution circuits or for grounding conductors. Conductor: Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8. Tin-coated soft, mediumhard, or hard drawn copper wire also available upon request. Additional Standards: Federal Specification CID A-A-59551 (non-insulated) soft drawn bare copper Soft Drawn Bare Copper - Solid AF000 0801S 8 16510 Solid .12 50 AF000 0601S 6 26240 Solid .16 79 AF000 0401S 4 41740 Solid .20 126 AF000 0201S 2 66360 Solid .25 201 Soft Drawn Bare Copper - Stranded AF000 01401 14 4110 7 .07 13 AF000 01201 12 6530 7 .09 20 AF000 01001 10 10380 7 .11 32 AF000 00801 8 16510 7 .14 51 AF000 00601 6 26240 7 .18 81 AF000 00401 4 41740 7 .23 129 AF000 00201 2 66360 7 .29 205 AF000 00101 1 83690 19 .33 258 AF000 10101 1/0 105600 19 .37 326 AF000 20101 2/0 133100 19 .41 411 AF000 30101 3/0 167800 19 .47 518 AF000 40101 4/0 211600 19 .52 653 AF000 25001 250 250000 37 .57 772 AF000 35001 350 350000 37 .68 1081 AF000 50001 500 500000 37 .81 1544 AF000 75001 750 750000 61 .99 2316 AF000 10001 1000 1000000 61 1.15 3088 Catalog No. Size AWG/kcmil No. of Strands Cross Sectional Area Circular Mils Overall Diameter Inch Net Weight Lbs/Mft Application: For use in general wiring applications for lighting and power in conduits, ducts, or other approved raceways with maximum conductor temperature of 90°C in dry locations and 75°C in wet locations. Chemical,gasoline and oil resistant. Conductor: Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8. Insulation: Heat and moisture resistant PVC per UL Standard 83. Specification Jacket: Clear Nylon per UL Standard 62. Flame Test: UL VW-1 Additional Standards: • Federal Specification CID A-A-55543 • UL 1063 (Type MTW for stranded items) • UL 758 (Type AWM 105°C dry, 80°C in oil) WIRE & CABLE Building & Bare Cu Wire www.afielektrik.com F 01 AF001 01401 14 19 15 4 .12 16 AF001 01201 12 19 15 4 .14 25 AF001 01001 10 19 20 4 .17 39 AF001 00801 8 19 30 4 .23 66 AF001 00601 6 19 30 5 .25 98 AF001 00401 4 19 40 6 .33 155 AF001 00301 3 19 40 6 .36 190 AF001 00201 2 19 40 6 .39 235 AF001 00101 1 19 50 7 .45 300 AF001 10101 1/0 19 50 7 .50 370 AF001 20101 2/0 19 50 7 .54 460 AF001 30101 3/0 19 50 7 .60 570 AF001 40101 4/0 19 50 7 .66 710 AF001 25001 250 37 60 8 .72 845 AF001 35001 350 37 60 8 .83 1165 AF001 50001 500 37 60 8 .96 1640 AF001 75001 750 61 70 9 1.17 2480 AF001 10001 1000 61 70 9 1.32 3300 Catalog No. Size AWG/kcmil No. of Strands PVC Insulation Thickness Mils Nylon Jacket Thickness Mils Overall Diameter Inch Net Weight Lbs/Mft
Transcript
Page 1: wire and cable - afielektrik.com · ¥ Federal Specification CID A-A-55543 ¥ UL 1063 (Type MTW for stranded items) ¥ UL 758 (Type AWM 105¡C dry, 80¡C in oil) WIRE & CABLE Building

Soft DrawnSolid or Stranded

600 Volt UL 90°CTHHN/THWN InsulationCopper Conductor

Application:For use on insulators for overhead distributioncircuits or for grounding conductors.Conductor:Soft bare annealed copper per ASTM B-3,Class B stranding per ASTM B-8. Tin-coatedsoft, mediumhard, or hard drawn copper wirealso available upon request.Additional Standards:Federal Specification CID A-A-59551 (non-insulated)

soft drawn bare copper

Soft Drawn Bare Copper - Solid

AF000 0801S 8 16510 Solid .12 50AF000 0601S 6 26240 Solid .16 79AF000 0401S 4 41740 Solid .20 126AF000 0201S 2 66360 Solid .25 201Soft Drawn Bare Copper - Stranded

AF000 01401 14 4110 7 .07 13AF000 01201 12 6530 7 .09 20AF000 01001 10 10380 7 .11 32AF000 00801 8 16510 7 .14 51AF000 00601 6 26240 7 .18 81AF000 00401 4 41740 7 .23 129AF000 00201 2 66360 7 .29 205AF000 00101 1 83690 19 .33 258AF000 10101 1/0 105600 19 .37 326AF000 20101 2/0 133100 19 .41 411AF000 30101 3/0 167800 19 .47 518AF000 40101 4/0 211600 19 .52 653AF000 25001 250 250000 37 .57 772AF000 35001 350 350000 37 .68 1081AF000 50001 500 500000 37 .81 1544AF000 75001 750 750000 61 .99 2316AF000 10001 1000 1000000 61 1.15 3088

Catalog No.Size

AWG/kcmilNo. of

Strands

CrossSectional

AreaCircular

Mils

OverallDiameter

Inch

NetWeightLbs/Mft

Application:For use in general wiring applications for lightingand power in conduits, ducts, or other approvedraceways with maximum conductor temperatureof 90°C in dry locations and 75°C in wet locations.Chemical,gasoline and oil resistant.Conductor:Soft bare annealed copper per ASTM B-3, ClassB stranding per ASTM B-8.Insulation:Heat and moisture resistant PVC per UL Standard83. SpecificationJacket:Clear Nylon per UL Standard 62.Flame Test:UL VW-1Additional Standards:• Federal Specification CID A-A-55543• UL 1063 (Type MTW for stranded items)• UL 758 (Type AWM 105°C dry, 80°C in oil)

WIRE & CABLEBuilding & Bare Cu Wire

www.afielektrik.comF 01

AF001 01401 14 19 15 4 .12 16AF001 01201 12 19 15 4 .14 25AF001 01001 10 19 20 4 .17 39AF001 00801 8 19 30 4 .23 66AF001 00601 6 19 30 5 .25 98AF001 00401 4 19 40 6 .33 155AF001 00301 3 19 40 6 .36 190AF001 00201 2 19 40 6 .39 235AF001 00101 1 19 50 7 .45 300AF001 10101 1/0 19 50 7 .50 370AF001 20101 2/0 19 50 7 .54 460AF001 30101 3/0 19 50 7 .60 570AF001 40101 4/0 19 50 7 .66 710AF001 25001 250 37 60 8 .72 845AF001 35001 350 37 60 8 .83 1165AF001 50001 500 37 60 8 .96 1640AF001 75001 750 61 70 9 1.17 2480AF001 10001 1000 61 70 9 1.32 3300

Catalog No.SizeAWG/kcmil

No. ofStrands

PVCInsulationThicknessMils

NylonJacketThicknessMils

OverallDiameterInch

NetWeightLbs/Mft

Page 2: wire and cable - afielektrik.com · ¥ Federal Specification CID A-A-55543 ¥ UL 1063 (Type MTW for stranded items) ¥ UL 758 (Type AWM 105¡C dry, 80¡C in oil) WIRE & CABLE Building

www.afielektrik.comF 02

APPLICATIONSRomex Type NM-B (nonmetallic-sheathed cable) may be used for both exposed and concealed work in normally dry locationsat temperatures not to exceed 90°C(with ampacity limited to that for 60°C conductors) as specified in the NationalElectrical Code. NM-B cable is primarily used in residential wiring as branchcircuits for outlets, switches, and otherloads. NM-B cable may be run in air voids of masonry block or tile walls where such walls are not wet or damp locations.Voltage rating for NM-B cable is 600 volts.SPECIFICATIONSRomex Type NM-B cable meets or exceeds UL Standard 83, UL Standard 719, Federal Specification A-A-59544,and requirements of the National Electrical Code.CONSTRUCTIONRomex Type NM-B cable is manufactured as 2, 3, or 4 conductor cable, with a ground wire. Copper conductors are annealed (soft) copper. Stranded conductorsare compressed stranded. Conductor insulation is 90°C-rated polyvinyl chloride (PVC), nylon jacketed. The cable jacket is color-coded for quick size identification;White - 14 AWG, Yellow -12 AWG, Orange - 10 AWG, and Black - 8 AWG and 6 AWG.

TWO CONDUCTOR14 2 1 19 14 1 360 X 162 57 15 EH12 2 1 19 12 1 410 X 179 82 20 EH10 2 1 24 10 1 494 X 210 124 30 EH8 2 1 35 10 1 612 X 269 186 40 BK6 2 1 35 10 1 683 X 304 255 55 BK

THREE CONDUCTOR14 3 1 19 14 1 307 74 15 BH12 3 1 19 12 1 347 107 20 BH10 3 1 24 10 1 422 164 30 BH8 3 7 35 10 1 565 253 40 BK6 3 7 35 10 1 650 357 55 BK4 3 7 46 8 1 814 560 70 CK2 3 7 46 8 1 952 816 95 CK

FOUR CONDUCTOR14 2/2 1* 19 14 1 336 91 15 BH14 4 1** 19 14 1 336 91 15 BH12 2/2 1* 19 12 1 381 132 20 BH12 4 1** 19 12 1 381 132 20 BH

StandardPackage

Conductor Ground Wire Approx.Cable

Dimension(mils)

SizeAWG

No.Conductors

inCable

No.Strands

inConductors

InsulationThickness

(mils)

No.Strands

Size(AWG)

Approx.Net

WeightPer

1000'(lbs.)

AllowableAmpacity+

NM - B

NOTE 1: Single conductor. Subject to special inquiry.†Not more than 3 conductors in cable per Table 310.16,National Electrical Code, 2005 Edition.

STANDARD PACKAGE CODESB – 1000 ft. reelC – 500 ft. reelE – 1000 ft. spoolH – 250 ft. coilK – 125 ft. coil

A P P L I C A T I O N S Suitable for use as follows:• Colonial Type UF-B cable is generally used as feeder to outside post lamps, pumps, and other loads or apparatus fed from a distribution point in an existingbuilding as specified in the National Electrical Code1• UF-B cable may be used underground, including direct burial• Multiple conductor UF-B cable may be used for interior branch circuit wiring in residential or agricultural buildings at conductor temperatures not to exceed90°C (with ampacity limited to that for 60°C conductors) as specified by the National ElectricalCode• UF-B can be used in applications permitted for NMC in Section 334.10(B) of the National Electrical Code. Voltage rating for UF-B cable is 600 voltsS T A N D A R D S & R E F E R E N C E SColonial Type UF-B cable meets or exceeds UL Standard 83, UL Standard 493, Federal Specification A-A-59544, and requirements of the National Electrical Code.C O N S T R U C T I O N• Colonial Type UF-B cable is manufactured as a 2 or 3 conductor cable, with or without a ground wire• Copper conductors are annealed (soft) copper, solid or compressed stranded• Phase conductors are polyvinyl chloride (PVC) insulated, nylon jacketed, color coded for identification purposes• Jacketed with sunlight, moisture and fungus resistant gray PVCS P E C I F I C A T I O N SCable shall be UL-listed Type UF-B, suitable for operation at 600 volts or less in all installations as specified in the National Electrical Code.Conductors shall be annealed copper manufactured by Southwire Company or approved equal.

SIZE/CONST.(AWG)

NUMBEROF

STRANDS

INSULATION& JACKET

THICKNESS(mils)

JACKETTHICKNESS

(mils)

MULTIPLE CONDUCTOR

GROUND WIREWITHOUT GROUND

NUMBEROF

STRANDSSIZE

(AWG)

WITH GROUND

CABLEDIMENSION

(mils)

APPROX. NETWEIGHT PER1000 FT.(lbs)

CABLEDIMENSION

(mils)

APPROX. NETWEIGHT PER1000 FT.(lbs)

ALLOWABLEAMPACITY†

STANDARDPACKAGE

CONDUCTOR

W E I G H T S , M E A S U R E M E N T S A N D P A C K A G I N G

2 CONDUCTOR14 1 19 30 14 1 423 X 168 71 354 X 168 53 15 EQ12 1 19 30 12 1 463 X 183 97 386 X 183 71 20 EQ10 1 24 30 10 1 518 X 215 140 440 X 215 104 30 EQ6 7 35 45 10 1 678 X 302 223 576 X 302 178 40 CK8 7 35 45 10 1 770 X 338 304 668 X 338 256 55 CK

3 CONDUCTOR14 1 19 30 14 1 581 X 168 97 501 X 168 78 15 EQ12 1 19 30 12 1 626 X 183 131 581 X 183 110 20 BQ10 1 24 30 10 1 727 X 215 194 661 X 215 159 30 BQ6 7 35 45 10 1 1059 X 319 345 984 X 319 304 40 CK8 7 35 45 10 1 1223 X 361 480 1153 X 361 438 55 CK

UF - B

WIRE & CABLEUnderground Feeder Cable

+Ampacity per 310.15 and 334.80, National Electrical Code, 2008 edition.NOTE: Jacket thickness for all NM-B cable is 30 mils.*Color Code for 2/2 Conductor Cable is Black, White, Red, and White with Red Stripe.**Color Code for 4 Conductor Cable is Black, White, Red, and Blue.

STANDARD PACKAGE CODEB - 1000' ReelC - 500' ReelE - 1000' SpoolH - 250' CoilK - 125' Coil

Page 3: wire and cable - afielektrik.com · ¥ Federal Specification CID A-A-55543 ¥ UL 1063 (Type MTW for stranded items) ¥ UL 758 (Type AWM 105¡C dry, 80¡C in oil) WIRE & CABLE Building

18 AWG Types CL2, MP, CM, and FPL• 20 AWG Type CL2 Only, PVC/PVC,Plastic Jacketed (PJ) 20 and 18 AWGFEATURES• OSHA acceptable• UL listed• CL2 – Power Limited per Article 725• CM – Communication Cables per Article 800• FPL – Power Limited Fire Protective Signaling Cable per Article 760• Solid bare copper per UL-13• PVC insulation per UL-13• Sunlight resistant PVC jacket per UL-13• CSA CertifiedAPPLICATIONDesigned for indoor use in heating and air conditioning controls, bell and alarm systems.Color Code:2-conductor laid flat: Red, White Multi-conductor cabled round: Red, White, Green, Blue, Yellow, Tan, Orange, Black, Pink,BrownSurface Print:20 AWG: “Sun Res CL2 90°C 20 (UL)---CSA CMG FT4” 18 AWG: “Sun Res CL2 or CM or FPL 90°C 18 A.I.W. Corp. (UL)---CSA CMG FT4”

Note: CL2 can be used for CL2X and FPL can be used for CL3.

28082 2 4x500' spls/ctn .068x.118 1228083 3 4x500' spls/ctn .122 1628084 4 4x500' spls/ctn .134 2028085 5 4x500' spls/ctn .147 2428086 6 4x500' spls/ctn .161 2928087 7 4x500' spls/ctn .161 3228088 8 4x250' spls/ctn .174 3728089 9 4x250' spls/ctn .188 4028090 10 4x250' spls/ctn .197 44

29899 2 4x500' spls/ctn .085x.140 1629900 3 4x500' spls/ctn .145 2129901 4 4x500' spls/ctn .160 2829903 5 4x250' spls/ctn .175 3629904 6 4x250' spls/ctn .190 4129905 7 4x250' spls/ctn .190 4829906 8 4x250' spls/ctn .210 5329907 9 4x250' spls/ctn .225 5929908 10 4x250' spls/ctn .235 66

PARTNUMBER

NO. OFCOND.

STANDARDLENGTHS PUT-UP

NOMINALO.D.

SHIP WT.LBS./M FT

SIZE 20 AWG • CL2 ONLY SIZE 18 AWG • CL2, CM & FPL

PARTNUMBER

NO. OFCOND.

STANDARDLENGTHS PUT-UP

NOMINALO.D.

SHIP WT.LBS./M FT

16 - 12 AWG • 2 Conductors • 150 Volts • Sunlight Resistant • For Outdoor LightingUnderground Low Energy Circuit Cable

FEATURES• UL listed (file no. E18966)• OSHA acceptable• Bunch stranded copper conductors• Sunlight and water resistant grade PVC insulation (black)• Polarity ridge on one conductor for identification• CSA certified (file no. LL 8825)APPLICATIONDesigned for outdoor use above and below ground in landscape lighting and securitysystems. Also available in colors or as 3/C upon request.Indent print: “(size) 2/C Underground Low Energy Circuit Cable Sunlight Resistant forOutdoor Lighting (UL) E18966---LL8825 CSA low voltage landscape lighting 30V FT1"

27731 16 2 26x30 .045 .155x.315 13 1x500' spool/ctn 4231442 14 2 41x30 .045 .170x.350 18 1x500' spl/ctn 7428840 12 2 65x30 .045 .195x.390 25 1x500' spl/ctn 7835777 10 2 104x30 .045 .220x.440 30 1x250' spl/ctn 10437025 8 2 133x29 .060 .295x.590 40 1x500' spl/ctn 176

PARTNUMBER STRANDING

CONDUCTORSAWG NO.

APPROXIMATE INSUL. O.D. AMPS1

STANDARD LENGTHSPUT-UP

SHIP WT.LBS./M FT

1Ampacities (Amps per conductor) are based on 30°C ambient temperature in air per the 2008 NEC, Table 400.5(A).

• 2 - 10 Conductors• 90°C• Sunlight Resistant• CSA Type CMG

WIRE & CABLEThermostat Cable

www.afielektrik.comF 03

Page 4: wire and cable - afielektrik.com · ¥ Federal Specification CID A-A-55543 ¥ UL 1063 (Type MTW for stranded items) ¥ UL 758 (Type AWM 105¡C dry, 80¡C in oil) WIRE & CABLE Building

CatalogNo.

SizeAWG

Numberof

Strands

InsulationThickness

Mils

NylonJacket

ThicknessMils

OverallJacket

ThicknessMils

NetWeightLbs/Mft

Numberof

Conductors

OverallDiameter

Inch

AF151 01402* 14 2 7 15 4 45 .22 x .33 62AF151 01403 14 3 7 15 4 45 .35 80AF151 01404 14 4 7 15 4 45 .38 99AF151 01405 14 5 7 15 4 45 .41 118AF151 01406 14 6 7 15 4 45 .45 140AF151 01407 14 7 7 15 4 45 .45 153AF151 01409 14 9 7 15 4 45 .52 196AF151 01410 14 10 7 15 4 60 .60 230AF151 01412 14 12 7 15 4 60 .61 267AF151 01416 14 16 7 15 4 60 .68 343AF151 01419 14 19 7 15 4 60 .71 396AF151 01420 14 20 7 15 4 60 .75 423AF151 01425 14 25 7 15 4 80 .83 511AF151 01430 14 30 7 15 4 80 .93 636AF151 01437 14 37 7 15 4 80 .98 766AF151 01440 14 40 7 15 4 80 1.01 840AF151 01450 14 50 7 15 4 80 1.17 1043AF151 01460 14 60 7 15 4 80 1.21 1200

600 Volt UL Type TC THHN or THWN Insulation PVC Jacket Copper Conductors copper conductor binder tape

Application:General purpose cable for use in power,control and lighting circuits in a broad rangeof commercial and industrial applications.Approved for installation indoors or outdoors,aerially, in conduits, ducts, cable trays ordirect burial in circuits not exceeding 600volts.May be used in NEC Class I and II,Division 2 hazardous locations. UL approvedfor use in continuous operation at 75°C in wetlocations, 90°C in dry locations, 130°C foremergency overload conditions, and 250°Cfor short circuit conditions.Conductors:Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.Insulation:Flame-retardant PVC per UL Standard 83for Type THHN or THWN wire.Insulation Jacket:Clear nylon per UL Standard 83 forType THHN or THWN wire.Jacket:Sunlight-resistant PVC per UL Standard 1277.Flame Tests:• IEEE 383 70,000 BTU/hr flame test• ICEA 210,000 BTU/hr flame testColor Code:ICEA Method 1, Table E-2

* Flat construction

Application:General purpose cable for use in power,control and lighting circuits in a broad rangeof commercial and industrial applications. Approved for installation indoors or outdoors,aerially, in conduits, ducts, cable trays or directburial in circuits not exceeding 600 volts. Maybe used in NEC Class I and II, Division 2hazardous locations. UL approved for use incontinuous operation at 75°C in wet locations,90°C in dry locations, 130°C for emergencyoverload conditions, and 250°C for short circuitconditions.Conductors:Soft bare annealed copper per ASTM B-3,Class B stranding per ASTM B-8.Insulation:Flame-retardant PVC per UL Standard 83 forType THHN or THWN wire.Insulation Jacket:Clear nylon per UL Standard 83 for TypeTHHN or THWN wire.Jacket:Sunlight-resistant PVC per UL Standard 1277.Flame Tests:• IEEE 383 70,000 BTU/hr flame test• ICEA 210,000 BTU/hr flame test

600 Volt UL Type TC THHN or THWN Insulation PVC JacketCopper Conductors copper conductor binder tape

F 04

www.afielektrik.com

Tray Cable - Control Cable

Tray Cable - Power Cable

Additional Standards:• UL Type TC per Article 336 of the NEC.• Approved for Class 1 remote-control andsignaling circuits per Article 725 of the NEC.

AF151 01202* 12 2 7 15 4 45 .24 x .37 77AF151 01203 12 3 7 15 4 45 .39 110AF151 01204 12 4 7 15 4 45 .42 138AF151 01205 12 5 7 15 4 45 .46 165AF151 01207 12 7 7 15 4 45 .50 216AF151 01209 12 9 7 15 4 60 .62 297AF151 01210 12 10 7 15 4 60 .67 324AF151 01212 12 12 7 15 4 60 .69 378AF151 01215 12 15 7 15 4 60 .76 468AF151 01216 12 16 7 15 4 60 .76 488AF151 01219 12 19 7 15 4 60 .80 568AF151 01220 12 20 7 15 4 80 .89 642AF151 01225 12 25 7 15 4 80 .99 775AF151 01230 12 30 7 15 4 80 1.03 910AF151 01237 12 37 7 15 4 80 1.14 1105

CatalogNo.

SizeAWG

Numberof

Strands

InsulationThickness

Mils

NylonJacket

ThicknessMils

OverallJacket

ThicknessMils

NetWeightLbs/Mft

Numberof

Conductors

OverallDiameter

Inch

* Flat construction

Additional Standards:• UL Type TC per Article 336 of the NEC.• Approved for Class 1 remote-control andsignalingcircuits per Article 725 of the NEC.

Color Code:ICEA Method 1, Table E-2

WIRE & CABLETray Cable

Page 5: wire and cable - afielektrik.com · ¥ Federal Specification CID A-A-55543 ¥ UL 1063 (Type MTW for stranded items) ¥ UL 758 (Type AWM 105¡C dry, 80¡C in oil) WIRE & CABLE Building

600 Volt UL Type TC THHN or THWN Insulation PVC Jacket Copper Conductors

Application:General purpose cable for use in power,control and lighting circuits in a broadrange of commercial and industrial applications.Approved for installation indoors or outdoors,aerially, in conduits, ducts, cable trays ordirect burial in circuits not exceeding 600volts. May be used in NEC Class I and II,Division 2 hazardous locations. UL approvedfor use in continuous operation at 75°C in wetlocations, 90°C in dry locations, 130°C foremergency overload conditions, and 250°Cfor short circuit conditions.

* Flat construction

Application:General purpose cable for use in primarypower and feeder circuits in a broad rangeof commercial and industrial applications.Approved for installation indoors or outdoors,aerially, in conduits, ducts, cable trays or directburial in circuits not exceeding 600 volts. May beused in NEC Class I and II, Division 2 hazardouslocations. UL approved for use in continuousoperation at 75°C in wet locations, 90°C in drylocations, 130°C for emergency overload conditions,and 250°C for short circuit conditions.

AF154 10103 1/0 3 19 50 7 6 80 1.22 1423AF154 10104 1/0 4 19 50 7 6 80 1.34 1832AF154 20103 2/0 3 19 50 7 6 80 1.32 1718AF154 20104 2/0 4 19 50 7 6 80 1.45 2223AF154 30103 3/0 3 19 50 7 4 80 1.42 2131AF154 30104 3/0 4 19 50 7 4 80 1.58 2756AF154 40103 4/0 3 19 50 7 3 80 1.54 2592AF154 40104 4/0 4 19 50 7 3 80 1.77 3457AF154 25003 250 3 37 60 8 3 110 1.75 3123AF154 25004 250 4 37 60 8 3 110 1.94 4046AF154 35003 350 3 37 60 8 3 110 1.97 4204AF154 35004 350 4 37 60 8 3 110 2.18 5469AF154 50003 500 3 37 60 8 2 110 2.26 5792AF154 50004 500 4 37 60 8 1 110 2.49 7556AF154 75003 750 3 37 60 9 1 110 2.82 9060

CatalogNo.

SizeAWG

Numberof

Strands

InsulationThickness

Mils

NylonJacket

ThicknessMils

OverallJacket

ThicknessMils

NetWeightLbs/Mft

Numberof

Conductors

OverallDiameter

Inch

GroundWire

Size AWG

Jacket:Sunlight-resistant PVC per UL Standard 1277.Flame Tests:• IEEE 383 70,000 BTU/hr flame test• ICEA 210,000 BTU/hr flame testColor Code:ICEA Method 1, Table E-2Additional Standards:• UL Type TC per Article 336 of the NEC.• Approved for Class 1 remote-controland signalingcircuits per Article 725 of the NEC.

Jacket:Sunlight-resistant PVC per UL Standard1277.Flame Tests:• IEEE 383 70,000 BTU/hr flame test• ICEA 210,000 BTU/hr flame testColor Code:ICEA Method 4Additional Standards:UL Type TC per Article 336 of the NEC.

AF151 01002* 10 2 7 20 4 45 .27 x .44 131AF151 01003 10 3 7 20 4 45 .45 169AF151 01004 10 4 7 20 4 60 .50 231AF151 01005 10 5 7 20 4 60 .58 276AF151 01006 10 6 7 20 4 60 .63 329AF151 01007 10 7 7 20 4 60 .63 361AF151 01009 10 9 7 20 4 60 .73 465AF151 01012 10 12 7 20 4 80 .86 647AF151 01016 10 16 7 20 4 80 .97 817AF151 01019 10 19 7 20 4 80 1.02 920

CatalogNo.

SizeAWG

Numberof

Strands

InsulationThickness

Mils

NylonJacket

ThicknessMils

OverallJacket

ThicknessMils

NetWeightLbs/Mft

Numberof

Conductors

OverallDiameter

Inch

AF154 00803 8 3 7 30 5 10 60 .58 220AF154 00804 8 4 7 30 5 10 60 .61 286AF154 00603 6 3 7 30 5 8 60 .69 386AF154 00604 6 4 7 30 5 8 60 .76 505AF154 00403 4 3 7 40 6 8 60 .89 630AF154 00404 4 4 7 40 6 8 80 .97 828AF154 00203 2 3 7 40 6 6 80 1.03 930AF154 00204 2 4 7 40 6 6 80 1.13 1213AF154 00103 1 3 19 50 7 6 80 1.15 1252

CatalogNo.

SizeAWG

Numberof

Strands

InsulationThickness

Mils

NylonJacket

ThicknessMils

OverallJacket

ThicknessMils

NetWeightLbs/Mft

Numberof

Conductors

OverallDiameter

Inch

GroundWire

Size AWG

Application:General purpose cable for use in primary powerand feeder circuits in a broad range of commercialand industrial applications. Approved for installationindoors or outdoors, aerially, in conduits, ducts,cable trays or direct burial in circuits not exceeding600 volts. May be used in NEC Class I and II,Division 2 hazardous locations. UL approved foruse in continuous operation at 75°C in wetlocations, 90°C in dry locations, 130°C foremergency overload conditions, and 250°C forshort circuit conditions. Conductors: Soft bareannealed copper per ASTM B-3, Class Bstranding per ASTM B-8.Insulation:Flame-retardant PVC per UL Standard83 for Type THHN or THWN wire.

Flame Tests:• IEEE 383 70,000 BTU/hr flame test• ICEA 210,000 BTU/hr flame testColor Code:ICEA Method 4Additional Standards:UL Type TC per Article 336 of the NEC.

Tray Cable - Control Cable

Tray Cable - Power Cable

Tray Cable - Power Cable

Conductors:Soft bare annealed copper per ASTM B-3,Class B stranding per ASTM B-8.Insulation:Flame-retardant PVC per UL Standard 83for Type THHN or THWN wire.Insulation Jacket:Clear nylon per UL Standard 83 for TypeTHHN or THWN wire.

Conductors:Soft bare annealed copper per ASTM B-3, Class Bstranding per ASTM B-8.Insulation:Flame-retardant PVC per UL Standard 83for Type THHN or THWN wire.Insulation Jacket:Clear nylon per UL Standard 83 for TypeTHHN orTHWN wire.Grounding Conductor:Soft bare annealed copper per ASTMB-3, Class B stranding per ASTM B-8sized in accordance with UL Standard 1277.

Insulation Jacket:Clear nylon per UL Standard 83for Type THHN or THWN wire.Grounding Conductor:Soft bare annealed copperper ASTM B-3, Class B stranding per ASTMB-8 sized in accordance with UL Standard 1277.Jacket:Sunlight-resistant PVC per UL Standard 1277.

www.afielektrik.comF 05

WIRE & CABLETray Cable

Page 6: wire and cable - afielektrik.com · ¥ Federal Specification CID A-A-55543 ¥ UL 1063 (Type MTW for stranded items) ¥ UL 758 (Type AWM 105¡C dry, 80¡C in oil) WIRE & CABLE Building
Page 7: wire and cable - afielektrik.com · ¥ Federal Specification CID A-A-55543 ¥ UL 1063 (Type MTW for stranded items) ¥ UL 758 (Type AWM 105¡C dry, 80¡C in oil) WIRE & CABLE Building
Page 8: wire and cable - afielektrik.com · ¥ Federal Specification CID A-A-55543 ¥ UL 1063 (Type MTW for stranded items) ¥ UL 758 (Type AWM 105¡C dry, 80¡C in oil) WIRE & CABLE Building
Page 9: wire and cable - afielektrik.com · ¥ Federal Specification CID A-A-55543 ¥ UL 1063 (Type MTW for stranded items) ¥ UL 758 (Type AWM 105¡C dry, 80¡C in oil) WIRE & CABLE Building

Recommended