Wireless Remote Controller (MR-AH01/BH01) HQ SE
Transcript
Page 1: Wireless Remote Controller (MR-AH01/BH01) HQ SE.  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF.

Wireless Remote Controller(MR-AH01/BH01)

HQ SE

Page 2: Wireless Remote Controller (MR-AH01/BH01) HQ SE.  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF.

On/Off control

Air flow control

Temperature setting

Filter reset

Louver Control

Simple ON/OFF schedule

Service Mode

- Main/RMC address check

- Communication status check

Features MR-AH01 MR-BH01

Main Difference

MR-AH01 : ON/OFF schedule time Increase only

MR-BH01 : ON/OFF schedule time Increase/Decrease both

For MR-BH01, real time clock is not supported !

Wireless remote controller

Page 3: Wireless Remote Controller (MR-AH01/BH01) HQ SE.  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF.

Option code setting mode (MR-AH01)

1. Remove one battery from the wireless remote controller.

2. Press + together and put the battery back to enter the option code setting mode.

3. Use the Mode button to toggle the option code page.

4. Press the Set/Cancel button to change the option code.

Toggle option code page

Set option code

Entering option code mode Setting option code

Page 4: Wireless Remote Controller (MR-AH01/BH01) HQ SE.  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF.

Option code setting mode (MR-BH01)

1. Remove one battery from the wireless remote controller.

2. Press + together and put the battery back to enter the option code setting mode.

3. Use the Mode button to toggle the option code page

4. Press Power button to change the option code.

Toggle option code page

Set option code

Entering option code mode Setting option code

Press together

Page 5: Wireless Remote Controller (MR-AH01/BH01) HQ SE.  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF.

Option code setting mode (Neo forte R/C)

1. Remove one battery from the wireless remote controller.

2. Press Temp ▲▼ together and put the battery back to enter the option code setting mode.

3. Set option code 2 digits. And press “Mode” and set next 2 digits.

4. Press the On/Off power button to change the option code.

Entering option code mode Setting option code

<Initial display>

Page 6: Wireless Remote Controller (MR-AH01/BH01) HQ SE.  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF.

<Example : 027402 – 14221A – 200001 - 300000>

4) Then “OFF timer” is displayed.

5) Set next 2 digit.

6) After setting completion, press “On/Off”

※ Only blue colored 20 digits should be set

1) Set 2 digits using Temp ▲▼button

2) Press “Mode” , then will move to down. Set next 2 digit◀

3) After setting 10 digits, press “Mode”

Option code setting mode (Neo forte R/C)

Page 7: Wireless Remote Controller (MR-AH01/BH01) HQ SE.  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF.

Service mode (MR-AH01)

1. Remote one battery from the wireless remote controller.

2. Press + together and put the battery back to enter the Service Mode.

NOTE : Whenever Mode, Func1 and Func2 are changed, signal wave is transmitted from the wireless

remote controller.

Mode

Func1

Func2

Press Set/Cancel button

Entering service mode Selecting service mode

Page 8: Wireless Remote Controller (MR-AH01/BH01) HQ SE.  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF.

Service mode (MR-BH01)

1. Remote one battery from the wireless remote controller.

2. Press + together and put the battery back to enter the Service Mode.

NOTE : Whenever Mode, Func1 and Func2 are changed, signal wave is transmitted from the wireless

remote controller.

ModeFunc2

Press Set/Cancel button

Entering service mode

Func1

Selecting service mode

Press together

Page 9: Wireless Remote Controller (MR-AH01/BH01) HQ SE.  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF.

Service mode

Mode Func1 Func2 Description

0 0 0

COM1 communication status (Blinking display only is valid)

Operation LED Blinking – communication status of all channels

Schedule LED Blinking – Outdoor ↔ Indoor units communication status

Fan LED Blinking – Wired remote controller ↔ Indoor units communication status

Filter LED Blinking – Interface module ↔ Indoor units communication status

0 1 0

COM1 Main Address check

0 2 0LED display test (Rotating display)

Operation LED → Schedule LED → FAN LED → Filter LED → Defrost LED

All On → All Off → All On → All Off ………

MAIN addressOperation

LED

Schedule LED

FAN LED

Filter LED

0 OFF OFF OFF OFF

1 OFF OFF OFF ON

2 OFF OFF ON OFF

… … … … …

15 ON ON ON ON

Page 10: Wireless Remote Controller (MR-AH01/BH01) HQ SE.  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF.

Mode Func1 Func2 Description

10 x 0

MAIN address assigned by outdoor unit (if in the AUTO addressing mode)

(Read as decimal value)

x : MAIN address of indoor unit

If matched, all LEDs are lit ON.

Ex) For DVM Plus II, MAIN(1) = 1, MAIN(2) =2 MAIN address = 12

11 x 0

RMC Address check. (Read as HEX value)

x : RMC address of indoor unit

If matched, all LEDs are lit ON

Ex) For DVM Plus II, RMC(1)=1, RMC(2)=2 RMC address = 1*16 + 2 = 18

For DVM Plus II, RMC(1)=2, RMC(2)=1 RMC address = 2*16 + 1 = 22

13 x 0

Rotary switch MAIN address check (Read as decimal value)

x : MAIN address of indoor unit

If matched, all LEDs are lit ON

Ex) For DVM Plus II, MAIN(1) = 1, MAIN(2) =2 MAIN address = 12

NOTE : Exit the service mode by pressing any general keys in the Normal mode.

NOTE : Service mode 10,11 and 13 are not allowed for COM1-only indoor units.

NOTE : Applied for Cassette/Duct indoor units (not for Wall-mount indoor units)

Service mode


Recommended