VVR
300 V 700 C PVC INSULATED AND SHEATHED ROUND TYPE
CABLE STRUCTURE
NUMBER OF CORE : Up to 4 coresCONDUCTOR : Solid and stranded annealed copper,
sizes 0.5 mm2 up to 35 mm2
INSULATION : PVCColor: Single core Light gray
2 cores Light gray and Black3 cores Light gray, Black and Red4 cores Light gray, Black, Red and Blue
SHEATH : PVCColor: White
CLASSIFICATION : Maximum conductor temperature 70 0C
Circuit voltage not exceeding 300 VTESTING VOLTAGE : 2,000 voltsREFERENCE : TIS 11-2531, Table 2 (Single core)
: TIS 11-2531, Table 3 (Multi core)
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
3/40
VVR (SINGLE CORE)TIS11-2531TABLE 2
Numberof core
Nominalcross
sectionarea
(mm2)
Numberand
diameterof wire
(No./mm)
Insulatiothickness
(mm)
Sheaththickness
(mm)
Maxoveralldiameter
(mm)
Minimuminsulationresistanceat 70
0C
(M-Km)
Maximumcontinuous
currentrating infree air
(Ampere)
Cableweight
(approx.)
(Kg/Km)
Standard length
(m)
1
0.5
1
1
1.5
1.5
2.5
2.5
4
4
6
10
16
25
35
1 / 0.80
1 / 1.13
7 / 0.43
1 / 1.38
7 / 0.53
1 / 1.78
7 / 0.67
1 / 2.25
7 / 0.85
7 / 1.04
7 / 1.35
7 / 1.70
7 / 2.14
19 / 1.53
0.6
0.6
0.6
0.6
0.6
0.7
0.7
0.8
0.8
0.8
0.9
1.0
1.2
1.2
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
1.2
1.2
1.2
4.4
4.8
5.0
5.2
5.4
5.8
6.2
6.6
7.0
7.6
8.6
11.0
12.5
14.0
0.0146
0.0115
0.0110
0.0100
0.0094
0.0092
0.0084
0.0086
0.0078
0.0066
0.0059
0.0053
0.0051
0.0043
10
15
15
19
19
26
26
35
35
46
64
87
117
144
21
28
30
34
37
48
50
65
70
95
140
220
330
430
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
D: Packing in drum.
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
4/40
8/14/2019 Wire.pdf
5/40
VVF-GRD,MEA TYE B-GRD
750 V 700
C PVC INSULATED AND SHEATHED FLAT TYPE, WITH GROUND
NDUCTOR
750 V PVC 70 C TIS 2531 TABLE 5THAI YAZAKI
INSULATION SHEATH
CABLE STRUCTURE
NUMBER OF CORE : 2 cores with safety-groundCONDUCTOR : Solid and stranded annealed copper,
Sizes 1 mm2 up to 35 mm2
GROUND WIRE : Ground conductor size 1 mm2
up to 10 mm2
INSULATION : PVCColor : Light grey, BlackGround core-Green/Yellow
SHEATH : PVCColor: White
CLASSIFICATION : Maximumconductor temperature 70 0C
Circuit voltage not exceeding 750 voltsTESTING VOLTAGE : 2,500 voltsREFERENCE : TIS 11-2531, Table 13
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
6/40
VVF-GRD
TIS 11-2531
TABLE 13
Overall diameter (mm)Approx.
Nominalcross
sectional
area
(mm2)
Numberand
diameter
of wire
(No./mm)
Insulationthickness
(mm)
Nominalcross
sectional
area ofgroundconductor(mm
2)
Groundinsulationthickness
(mm)
Sheaththickness
(mm)
Lower limit Upper limit
Minimuminsulationresistance
at 70
0
C
(M-Km)
Maximumcontinuous
current
rating infree air
(Ampere)
Cableweight
(approx.)
(Kg/Km)
Standardlength
(m)
1
1
1.5
1.5
2.5
2.5
4
4
6
10
16
25
35
7/ 1.13
1/ 0.43
1/ 1.38
7/ 0.53
1/ 1.78
7/ 0.67
1/ 2.25
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
19/ 1.53
0.8
0.8
0.8
0.8
0.8
0.8
0.9
0.9
0.9
1.1
1.1
1.3
1.3
1
1
1
1
1.5
1.5
2.5
2.5
4
4
6
6
10
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.7
5.2X10.0
5.4X10.0
5.6X10.5
5.6X11.0
5.8X11.5
6.2X12.0
6.6X13.0
6.2X13.0
6.8X14.0
8.8X18.5
9.8X21.0
11.5X24.5
13.0X28.0
6.4X12.0
6.6X12.5
6.6X12.5
7.0X13.0
7.2X14.0
7.4X14.5
7.8X15.5
8.2X16.5
8.8X18.5
10.5X21.5
11.5X24.5
13.5X28.0
13.0X32.0
0.0141
0.0135
0.0123
0.0116
0.0102
0.0093
0.0094
0.0085
0.0073
0.0069
0.0057
0.0054
0.0047
12
12
15
15
20
20
27
27
36
50
66
89
109
100
110
110
120
150
160
200
220
290
420
600
850
1,100
100/C
100/C
100/C
100/C
100/C
100/C
100/C
100/C
100/C
100/C
100/C
500/D
500/D
TISI Permitted to increase the maximum overall diameter by 5 %C: Packing in coil.D: Packing in drum.
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
7/40
VV, MEA TYPE B
750 V 700
C PVC INSULATED AND SHEATHED ROUND TYPE, SINGLE CORE
CABLE STRUCTURE
CONDUCTOR : Solid and stranded annealed copper,sizes 1 mm
2up to 35 mm
2
INSULATION : PVCColor : Light gray
SHEATH : PVCColor: White
CLASSIFICATION : Maximum conductor temperature 70 0C
Circuit voltage not exceeding 750 VoltsTESTING VOLTAGE : 2,500 voltsREFERENCE : TIS 11-2531, Table 5
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
8/40
8/14/2019 Wire.pdf
9/40
VCT-GRD
750 V 700
C PVC INSULATED AND SHEATHED FLEXIBLE CONDUCTOR WITH GROUND
CABLE STRUCTURE
NUMBER OF CORE : 2 up to 4 phase cores with ground coreCONDUCTOR : Flexible annealed copper wires,
sizes 1 mm2 up to 35 mm2
Ground conductor size 1 mm2 up 10 mm2
INSULATION : PVC
Color : 2 cores Light gray and Black3 cores Light gray, Black and Red4 cores - Light gray, Black, Red and Blue
SHEATH : PVCColor: White
CLASSIFICATION :Maximum conductor temperature 70
0
CCircuit voltage not exceeding 750 volts
TESTING VOLTAGE : 2,500 voltsREFERENCE : TIS 11-2531, Table 15
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
10/40
VCT - GRDTIS 11-2531
TABLE 12
Numberof core
Nominalcross
sectionarea
(mm2)
Numberand
diameterof wire
(No./mm)
Insulatiothickness
(mm)
Nominalcross
sectionalarea ofground
conductor (mm
2)
Groundinsulationthickness
(mm)
Sheaththickness
(mm)
Max.Overalldiameter
(mm)
Minimuminsulationresistanceat 70
0C
(M-Km)
Minimumcontinuouscurrentrating infree air
(Ampere)
Cableweight
(approx.)
(Kg/Km)
Standard length
(m)
2
11.52.546
10162535
32/0.2030/0.2550/0.2556/0.3084/0.3084/0.30126/0.40196/0.40280/0.40
0.80.80.80.90.91.11.11.31.3
111.52.54466
10
0.60.60.60.60.60.60.60.60.6
1.21.41.41.61.61.82.22.42.6
10.511.513.015.517.020.023.027.531.0
0.01270.01110.00920.00840.00710.00680.00500.00480.0041
14182433426080104130
100130170240330550750
1,1001,500
100/C100/C100/C100/C100/C500/D500/D500/D500/D
3
1
1.52.546
10162535
32/0.20
30/0.2550/0.2556/0.3084/0.3084/0.30126/0.40196/0.40280/0.40
0.8
0.80.80.90.91.11.11.31.3
1
11.52.54466
10
0.6
0.60.60.60.60.60.60.60.6
1.4
1.41.41.61.82.02.42.62.8
11.5
12.514.517.019.023.527.532.536.5
0.0127
0.01110.00920.00840.00710.00680.00500.00480.0041
12
15202735516787
108
130
160210310440650950
1,4001,800
100/C
100/C100/C100/C100/C500/D500/D500/D500/D
4
11.52.546
10
162535
32/0.2030/0.2550/0.2556/0.3084/0.3084/0.30
126/0.40196/0.40280/0.40
0.80.80.80.90.91.1
1.11.31.3
111.52.544
66
10
0.60.60.60.60.60.6
0.60.60.6
1.61.61.61.82.02.2
2.62.83.1
13.013.516.018.521.026.0
30.536.040.5
0.01270.01110.00920.00840.00710.0068
0.00500.00480.0041
111318253246
607897
180210270400550900
1,2001,7002,400
100/C100/C100/C100/C500/D500/D
500/D500/D500/D
TISI permitted to increase the maximum overall diameter by 5 %D : Packing in drum.
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
11/40
VCT
750 V 700
C PVC INSULATED AND SHEATHED FLEXIBLE CABLE
THAI YAZAKI
CONDUCTOR
INSULATION SHEATH
THAI YAZAKI
CABLE STRUCTURE
NUMBER OF CORE : Up to 4 coresCONDUCTOR : Flexible annealed copper wire,
Sizes.0.5 mm2
up to 95 mm2
for single core0.5 mm2 up to 35 mm2 for multi core
INSULATION : PVCColor: Single core Light gray
2 cores Light gray and Black3 cores Light gray, Black and Red4 cores Light gray, Black, Red and Blue
SHEATH : PVCColor: White
CLASSIFICATION : Maximum conductor temperature 70 0C
Circuit voltage not exceeding 750 VoltsTESTING VOLTAGE : 2,500 voltsREFERENCE : TIS 11-2531, Table 9
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
12/40
VCTTIS 11-2531
TABLE 3
Numberof core
Nominalcrosssectionarea
(mm2)
Numberand
diameterof wire
(No./mm)
Insulationthickness
(mm)
Sheaththickness
(mm)
Maxoveralldiameter
(mm)
Minimuminsulationresistanceat 70
0C
(M-Km)
Maximumcontinuous
current ratingin free air
(Ampere)
Cableweight
(approx.)
(Kg/Km)
Standard length
(m)
1
0.50.75
11.52.5
46101625355070
95
16 / 0.2024 / 0.2032/ 0.2530/ 0.2550/ 0.2556/ 0.3084/ 0.3080/ 0.40
126/ 0.40196 /0.40280/ 0.40399 /0.40361/ 0.50
475 / 0.50
0.80.80.80.80.80.90.91.11.11.31.31.51.5
1.7
1.01.01.21.21.21.41.41.81.82.22.22.62.6
3.0
5.45.66.26.67.48.69.4
12.013.516.017.521.023.0
26.5
0.01600.01400.01270.01110.00920.00840.00710.00680.00500.00480.00410.00400.0034
0.0034
101315192736466788116145181226
268
283240476085
120200270400550750950
1,300
100/C100/C100/C100/C100/C100/C100/C100/C100/C100/C500/D500/D500/D
500/D
2
0.50.75
11.52.5
4610162535
16 / 0.2024 / 0.2032/ 0.2530/ 0.2550/ 0.2556/ 0.3084/ 0.3080/ 0.40
126/ 0.40196 /0.40280/ 0.40
0.80.80.80.80.80.90.91.11.11.31.3
1.21.21.21.41.41.61.61.82.22.42.6
8.89.29.6
11.012.514.516.020.023.027.531.0
0.01600.01400.01270.01110.00920.00840.00710.00680.00500.00480.0041
91214182433426080
104130
758595
120160230300500700
1,0001,400
100/C100/C100/C100/C100/C100/C100/C500/D500/D500/D500/D
3
0.5
0.751
1.52.5
4610162535
16 / 0.20
24 / 0.2032/ 0.2530/ 0.2550/ 0.2556/ 0.3084/ 0.3080/ 0.40
126/ 0.40196 /0.40280/ 0.40
0.8
0.80.80.80.80.90.91.11.11.31.3
1.2
1.21.41.41.41.61.82.02.42.62.8
7.8
8.69.0
10.010.511.512.513.514.015.519.0
0.0146
0.01150.01100.01000.00940.00920.00840.00860.00780.00660.0059
7
10101313181825253345
65
90100130140190200280300400650
500/D
500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D
4
0.50.75
1
1.52.5
4610162535
16 / 0.2024 / 0.2032/ 0.25
30/ 0.2550/ 0.2556/ 0.3084/ 0.3080/ 0.40
126/ 0.40196 /0.40280/ 0.40
0.80.80.8
0.80.80.90.91.11.11.31.3
0.90.90.9
1.21.21.21.21.21.21.21.4
7.88.69.0
10.010.511.512.513.514.015.519.0
0.01460.01150.0110
0.01000.00940.00920.00840.00860.00780.00660.0059
71010
1313181825253345
6590
100
130140190200280300400650
500/D500/D500/D
500/D500/D500/D500/D500/D500/D500/D500/D
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
13/40
0.6 /1.2 KV-CV
0.6/1 kV. 90oC
CROSS- LINMED POLYETHYLENE INSULATED PVC SHEATED POWER
CABLE STRUCTURE
NUMBER OF CORE : up to 4 coresCONDUCTOR : Concentric stranded and compact round
stranded annealed copper,Sizes. 1.5 mm
2up to 1,000 mm
2
INSULATION : Cross-linked polyethyleneColor : Natural (Translucent)Core identification: Compound colorBlack, White, Red, green or color tape
SHEATH : PVCCLASSIFICATION : Maximum conductor temperature 90C
Circuit voltage not exceeding 1,000 voltsTESTING VOLTAGE : 3,500 voltsREFERENCE : IEC 60502-2
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
14/40
10,500
0.6/1.2 KV-CVIEC 60502-1 Standard
Numberof
cores
Nominalcross
sectionalarea
(mm2)
Numberof
stranded
(Min)
Insulationthickness
(mm)
Sheaththickness
(mm)
Approx.overalldiameter.
(mm)
Maximumconductorresistanceat 20
0C
(M-Km)
Minimuminsulation
resistanceat 20
0C
(M-Km)
Maximumcontinuous
currentrating infree air
(M-Km)
Cableweight(approx.)
(Kg/Km)
Standardlength
(m)
1
1.52.54610162535507095
120150185
240300400500630800
1,000
7/0.537/0.677/0.857/1.04
66666
1215181830
34345353535353
0.70.70.70.70.70.70.90.91.01.11.11.21.41.6
1.71.82.02.22.42.62.8
1.41.41.41.41.41.41.41.41.41.41.51.51.61.6
1.71.81.92.02.22.32.4
6.36.87.37.98.49.4
11.012.013.515.017.519.0
2123
26293236404551
12.17.414.613.081.831.15
0.7270.5240.3870.2680.1930.1530.124
0.0991
0.07540.06010.04700.03660.02830.02210.0176
2,5002,1001,7001,4501,2501,0001,050900850800650650700700
650600600600550550500
2736486182
110145180220280345400460530
630725840975
1,1251,3201,510
506080
100140200300400500750
1,0001,2001,5001,900
2,5003,1003,9005,0006,5008,500
500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D
500/D500/D500/D500/D500/D300/D300/D
2
1.52.54610162535507095
120150185240300400
7/0.537/0.677/0.857/1.04
66666
1215181830343453
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
1.81.81.81.81.81.81.81.81.81.82.02.12.22.32.52.72.9
11.012.013.014.015.017.02023252933374145515663
12.17.414.613.081.831.15
0.7270.5240.3870.2680.1930.1530.124
0.09910.07540.06010.0470
2,5002,1001,7001,4501,2501,0001,050900850800650650700700650600600
130160200260340480700
9001,2001,7002,3002,8003,5004,3005,5007,0009,000
2534445777
100135165205255315365415485580675790
500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D300/D300/D
D : PACKING IN DRUM
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
15/40
0.6/1.2 K IEC 60502-1 Standard
V-CV
Numberof
cores
Nominalcross
sectionalarea
(mm2
)
Numberof
stranded
(Min)
Insulationthickness
(mm)
Sheaththickness
(mm)
Approx.overalldiameter.
(mm)
Maximumconductorresistanceat 20
0C
(M-Km)
Minimuminsulation
resistanceat 20
0C
(M-Km)
Maximumcontinuous
currentrating infree air
(M-Km)
Cableweight
(approx.)
(Kg/Km)
Standardlength
(m)
3
1.52.546
10162535507095
120150
185240300400
7/0.537/0.677/0.857/1.04
66666
12151818
30343453
0.70.70.70.70.70.70.90.91.01.11.11.21.4
1.61.71.82.0
1.81.81.81.81.81.81.81.81.81.92.02.12.3
2.42.62.83.1
11.512.513.515.016.018.022242731363944
49556168
12.17.414.613.081.831.15
0.7270.5240.3870.2680.1930.1530.124
0.09910.07540.06010.0470
2,5002,1001,7001,4501,2501,0001,050900850800650650700
700650600600
212837486486
115140170215260305350
405490565655
150190240320440650950
1,3001,6002,3003,1004,0004,900
6,0008,000
10,00012,500
500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D
500/D300/D300/D200/D
4
1.52.546
101625355070
95120150185240300400
7/0.537/0.677/0.857/1.04
66666
12
15181830343453
0.70.70.70.70.70.70.90.91.01.1
1.11.21.41.61.71.82.0
1.81.81.81.81.81.81.81.81.92.0
2.12.32.42.62.83.03.3
12.013.514.516.017.52024273035
39444954616876
12.17.414.613.081.831.15
0.7270.5240.3870.268
0.1930.1530.1240.09910.07540.06010.0470
2,5002,1001,7001,4501,2501,0001,050900850800
650650700700650600600
212837486486
115140170215
260305350405490565655
180230300400550800
1,2001,6002,2003,000
4,1005,0006,5008,000
10,50013,00016,500
500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D
500/D500/D500/D300/D300/D200/D200/D
D : PACKING IN DRUM
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
16/40
NYY-SWA
750 V 70oC PVC INSULATED AND DOUBLE SHEATHED POWER CABLE, WITH
GALVANIZED STEEL WIRES ARMOR
CABLE STRUCTURENUMBER OF CORE : 2 Up to 4 coresCONDUCTOR : Solid and stranded annealed copper,
sizes 1 mm2
up to 300 mm2
INSULATION : PVCColor : 2 cores - Light gray and Black
3 cores - Light gray, Black and Red4 cores - Light gray, Black, Red and Blue
UNDER SHEATH : PVC, Color :BlackSHEATH : PVC, Color :Black
ARMOUR : Galvanized Steel WiresCLASSIFICATION : Maximumconductor temperature 70
oC
Circuit voltage not exceeding 750 voltsTESTING VOLTAGE : 2,500 voltsREFERENCE : TIS 11-2531
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
17/40
NYY-SWA
NumberOf
core
NominalCross
Sectionalarea
(mm2)
Numberand
diameterof wire
(NO./mm)
Insulationthickness
(mm)
UnderSheath
thickness
(mm)
Diameterof steelwirearmor
(mm)
SheathThickness
(mm)
Approx.overalldiameter
(mm)
Maximumconductorresistance at 20
0C
(-Km)
MinimumInsulationresistanceat 70
oC
(M-Km)
Minimumcontinuouscurrentrating in
underground(Ampere)
Cableweight
(approx.)
(Kg/Km)
Standardlength
(m)
2
1
1
1.5
1.5
2.5
2.5
4
4
6
10
16
25
35
50
70
95
120
150
185
240
300
1/1.13
7/0.43
7/1.38
7/0.53
1/1.78
7/0.67
1/2.25
7/0.85
7/1.04
7/1.35
7/1.70
7/2.14
19/1.53
19/1.78
19/2.14
19/2.52
37/2.03
37/2.25
37/2.52
61/2.25
61/2.52
0.8
0.8
0.8
0.8
0.8
0.8
0.9
0.9
0.9
1.1
1.1
1.3
1.3
1.5
1.5
1.7
1.7
1.9
2.1
2.3
2.5
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1.2
1.2
1.2
1.5
1.5
1.5
1.8
1.8
2.0
2.0
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1.25
1.25
1.25
1.6
2.0
2.0
2.0
2.0
2.5
2.5
2.5
2.5
2.5
3.15
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
2.0
2.1
2.2
2.4
2.6
2.7
2.9
3.1
3.4
13.5
14.0
14.0
14.5
15.0
15.5
16.5
18.0
19.0
22.0
24.0
30.0
33.0
36.0
41.0
47.0
51.0
56.0
61.0
68.0
76.0
18.1
18.1
12.1
12.1
7.41
7.41
4.61
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.09910.07540.0601
0.0141
0.0135
0.0123
0.0116
0.0102
0.0093
0.0094
0.0085
0.0073
0.0069
0.0057
0.0054
0.0047
0.0046
0.0039
0.0038
0.0034
0.0034
0.0034
0.0033
0.0032
22
22
27
27
36
36
47
47
61
82
107
138
168
199
243
294
336
375
424
489
553
300
310
320
340
370
400
460
600
700
950
1,300
2,000
2,400
3,000
4,000
5,000
6,000
7,000
8,500
10,50013,500
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
300/D
300/D
200/D
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
18/40
NYY-SWA
NumberOf
core
NominalCross
Sectionalarea
(mm2)
Numberand
diameterof wire
(NO./mm)
Insulationthickness
(mm)
UnderSheath
thickness
(mm)
Diameterof steel
wirearmor
(mm)
SheathThickness
(mm)
Approx.overalldiameter
(mm)
Maximumconductorresistance at 20
0C
(-Km)
MinimumInsulationresistanceat 70
oC
(M-Km)
Minimumcontinuous
currentrating in
underground(Ampere)
Cableweight
(approx.)
(Kg/Km)
Standardlength
(m)
3
1
1
1.5
1.5
2.5
2.5
4
4
6
10
16
25
35
50
70
95
120
150
185
240
300
1/1.13
7/0.43
1/1.38
7/0.53
1/1.78
7/0.67
1/2.25
7/0.85
7/1.04
7/1.35
7/1.70
7/2.14
19/1.53
19/1.78
19/2.14
19/2.52
37/2.03
37/2.25
37/2.52
61/2.25
61/2.52
0.8
0.8
0.8
0.8
0.8
0.8
0.9
0.9
0.9
1.1
1.1
1.3
1.3
1.5
1.5
1.7
1.7
1.9
2.1
2.3
2.5
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1.2
1.2
1.2
1.5
1.5
1.5
1.8
1.8
2.0
2.0
2.2
0.8
0.8
0.8
0.8
0.8
0.8
1.25
1.25
1.25
1.6
1.6
2.0
2.0
2.0
2.0
2.5
2.5
2.5
2.5
2.5
3.15
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
2.0
2.2
2.3
2.5
2.7
2.8
3.0
3.3
3.5
14.0
14.5
14.5
15.0
15.5
16.5
18.0
18.5
20.0
23.0
26.0
31.0
34.0
39.0
43.0
50.0
55.0
59.0
65.0
73.0
81.0
18.1
18.1
12.1
12.1
7.41
7.41
4.61
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.09910.07540.0601
0.0141
0.0135
0.0123
0.0116
0.0102
0.0093
0.0094
0.0085
0.0073
0.0069
0.0057
0.0054
0.0047
0.0046
0.0039
0.0038
0.0034
0.0034
0.0034
0.0033
0.0032
18
18
23
23
30
30
40
40
51
69
88
115
140
164
202
244
277
310
350
406
457
330
340
350
380
420
450
650
700
800
1,200
1,600
2,300
2,800
3,600
4,600
6,500
7,500
9,000
10,50013,00017,000
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
300/D
300/D
300/D
200/D
200/D
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
19/40
8/14/2019 Wire.pdf
20/40
NYY-N, MEA TYPE C-N
750 V 700
C PVC INSULATED AND DOUBLE SHEATHED ROUND TYPE WITH NEUTRAL
CABLE STRUCTURE
NUMBER OF CORE : 3 phase core with 1 neutral coreCONDUCTOR : Stranded annealed copper,
Sizes : Phase conductor size.6 mm2 up to 300 mm2
Neutral conductor size. 4 mm2up to 150 mm2INSULATION : PVC
Color: 3 cores Black, Red Blue1 Neutral core Light gray
SHEATH AND : PVCUNDER SHEATH Color: Black
CLASSIFICATION : Maximumconductortemperature 700C
Circuit voltage not exceeding 750 voltsTESTING VOLTAGE : 2,500 voltsREFERENCE : TIS 11- 2531, Table 8
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
21/40
NYY-N, MEA TYPE C-NTIS 11-2531
TABLE 8
Maximumcontinuous current
rating in free air(Ampere)
Nominalcross
sectional area
(mm.2)
Numberand diameter
of wire
(No. / mm.)
Insulationthickness
(mm.)
Phase Neutral Phase Neutral Phase Neutral
Undersheath
thickness
(mm)
Sheaththickness
(mm)
Max.overall
diameter
(mm)
Minimuminsulation
resistanceat 70
0C
(M-Km)Freeair
Underground
Cableweight
(approx.)
(Kg/Km)
Standardlength
(m)
3X6
3X10
3X16
3X25
3X35
3X50
3X70
3X95
3X120
3X150
3X185
3X240
3X300
1X4
1X6
1X10
1X16
1X16
1X25
1X35
1X50
1X70
1X70
1X95
1X120
1X150
7/1.04
7/1.35
7/1.70
7/2.14
19/1.53
19/1.78
19/2.14
19/2.52
37/2.03
37/2.25
37/2.52
61/2.25
61/2.52
7/0.85
7/1.04
7/1.35
7/1.70
7/1.70
7/2.14
19/1.53
19/1.78
19/2.14
19/2.14
19/2.52
37/2.03
37/2.25
0.9
1.1
1.1
1.3
1.3
1.5
1.5
1.7
1.7
1.9
2.1
2.3
2.5
0.9
0.9
1.1
1.1
1.1
1.3
1.3
1.5
1.5
1.5
1.7
1.7
1.9
0.8
0.8
1.2
1.2
1.5
1.5
1.5
1.8
1.8
2.0
2.0
2.2
2.2
1.8
2.0
2.0
2.0
2.2
2.2
2.4
2.6
2.8
3.0
3.2
3.4
3.8
19.0
23.0
26.5
31.0
35.0
39.5
44.5
51.5
56.0
62.0
68.0
76.5
84.5
0.0073
0.0069
0.0057
0.0054
0.0047
0.0046
0.0039
0.0038
0.0034
0.0034
0.0034
0.0033
0.0032
37
51
68
90
109
133
166
205
240
272
316
375
430
51
68
88
114
137
163
201
240
275
306
347
402
453
500
750
1,100
1,600
2,000
2,600
3,500
4,800
6,000
7,000
9,000
11,500
14,000
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
300/D
300/D
200/D
200/D
TISI PERMITTED TO INCREASE THE MAXIMUM OVERALL DIAMETER BY 5 %* REMARK : SPECIAL PROTECTION CAN BE PRODUCEDD: Packing in drum.
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
22/40
NYY, MEA TYPE C
750 V 700 C PVC INSULATED AND DOUBLE SHEATHED ROUND TYPE
CABLE STRUCTURE
NUMBER OF CORE : Up to4 coresCONDUCTOR : Solid and stranded annealed copper,
sizes 1 mm2 up to 500 mm2
: Multi core 1 mm2 up 300 mm2
INSULATION : PVC
Color: Single core Black2 cores Light gray and Black3 cores Light gray, Black and Red4 cores Light gray, Black, Red and Blue
SHEATH : PVCColor: Black
CLASSIFICATION : Maximum conductor temperature 70 0C
Circuit voltage not exceeding 750 voltsTESTING VOLTAGE : 2,500 voltsREFERENCE : TIS 11 Table 6 (Single core)
TIS 11 -2531, Table 7 (Multi core)
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
23/40
NYY, MEA TYPE C (SINGLE CORE)
TIS 11-2531TABLE 6
Maximumcontinuous current
rating in free air
(Ampere)
NominalCross
Sectional
area
(mm2)
Numberand
diameter
of wire
(No./mm)
Insulatiothickness
(mm)
Sheaththickness
(mm)
Max.Overall
diameter
(mm)
Minimuminsulationresistance
at 70
0
C
(M-Km)Free
airUnderair
Cableweight
(approx.)
(Kg/Km)
Standardlength
(m)
1
1
1.5
1.5
2.5
2.5
4
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
1 / 1.13
7 / 0.43
1 / 1.38
7 / 0.53
1 / 1.78
7 / 0.67
1 / 2.25
7 / 0.85
7 / 1.04
7 / 1.35
7 / 1.70
7 / 2.14
19 / 1.53
19 / 1.78
19 / 2.14
19 / 2.52
37 / 2.03
37 / 2.25
37 / 2.52
61 / 2.25
61 / 2.52
61 / 2.85
61 / 3.20
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.7
1.7
1.9
2.1
2.3
2.5
2.7
3.1
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.2
2.2
2.2
2.4
8.6
8.8
9.0
9.2
9.4
9.8
10.0
10.5
11.0
12.0
13.0
14.5
1.6.0
17.0
19.0
21.5
23.0
26.0
28.0
31.5
35.0
38.5
43.0
0.0207
0.0200
0.0184
0.0175
0.0157
0.0146
0.0135
0.0124
0.0107
0.0088
0.0074
0.0061
0.0053
0.0046
0.0039
0.0038
0.0034
0.0034
0.0034
0.0033
0.0032
0.0030
0.0031
17
17
21
21
28
28
38
38
49
67
89
118
146
177
222
274
318
362
416
492
565
655
757
22
22
27
27
36
36
47
47
60
81
105
136
165
196
241
289
330
370
419
486
551
629
717
80
80
85
90
100
110
120
130
160
210
280
390
490
600
850
1,100
1,400
1,700
2,100
2,700
3,400
4,300
5,400
100/C
100/C
100/C
100/C
100/C
100/C
100/C
100/C
100/C
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
TISI Permitted to increase the maximum overall diameter by 5 %C: Packing in coil.D: Packing in drum.
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
24/40
NYY, MEA TYPE CTIS 11-2531
TABLE 7
Maximumcontinuous current
rating in free air(Ampere)
Numberof
core
NominalCross
Sectionarea
(mm2)
Numberand
diameterof wire
(No./mm)
Insulatiothickness
(mm)
Undersheaththickness
(mm)
Sheaththickness
(mm)
Max.overall
diameter
(mm)
Minimuminsulationresistanceat 70
0C
(M-Km)Free
airUnderground
Cableweight
(approx.)
(Kg/Km)
Standardlength
(m)
2
111.51.52.52.544610162535
507095
120150185240300
1 / 1.137 / 0.431 / 1.387 / 0.531 / 1.787 / 0.671 / 2.257 / 0.857 / 1.047 / 1.357 / 1.707 / 2.14
19 / 1.53
19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52
0.80.80.80.80.80.80.90.90.91.11.11.31.3
1.51.51.71.71.92.12.32.5
0.80.80.80.80.80.80.80.80.80.80.81.21.2
1.21.51.51.51.81.82.02.0
1.81.81.81.81.81.81.81.81.81.82.02.02.0
2.22.22.22.42.62.83.03.2
12.012.512.513.013.514.015.015.517.019.522.527.029.5
33.538.042.546.552.057.064.070.5
0.01410.01350.01230.01160.01020.00930.00940.00850.00730.00690.00570.00540.0047
0.00460.00390.00380.00340.00340.00340.00330.0032
1515191925253333436080
106130
157195239280320370440507
21212727353547476081
105136165196240290332370419484547
160160170190210230270290360550700
1,1001,4001,8002,4003,2003,9004,8006,0007,5009,500
100/C100/C100/C100/C100/C100/C100/C100/C100/C500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D
3
11
1.51.52.52.5
446
10162535507095
120150185240300
1 / 1.137 / 0.431 / 1.387 / 0.531 / 1.787 / 0.67
1 / 2.257 / 0.857 / 1.047 / 1.357 / 1.707 / 2.14
19 / 1.5319 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52
0.80.80.80.80.80.8
0.90.90.91.11.11.31.31.51.51.71.71.92.12.32.5
0.80.80.80.80.80.8
0.80.80.80.81.21.21.21.51.51.51.81.82.02.02.2
1.81.81.81.81.81.8
1.81.81.81.82.02.02.02.22.22.42.62.83.03.23.4
12.513.013.013.514.015.0
15.516.518.020.524.528.531.536.040.546.050.556.061.569.076.0
0.01410.01350.01230.01160.01020.0093
0.00940.00850.00730.00690.00570.00540.00470.00460.00390.00380.00340.00340.00340.00330.0032
121216162121
282837506789
109131163202235269311371427
181822223030
3939506887
113137162200240273306346402453
180180200210240260
320350440650950
1,4001,7002,3003,1004,2005,0006,5008,000
10,00012,500
100/C100/C100/C100/C100/C100/C
100/C100/C100/C500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
25/40
NYY, MEA TYPE C
TIS 11-2531TABLE 7
Maximumcontinuous current
rating in free air(Ampere)
Numberof
core
NominalCross
Sectionalarea
(mm2)
Numberand
diameterof wire
(No./mm)
Insulatiothickness
(mm)
Undersheaththickness
(mm)
Sheaththickness
(mm)
Max.overall
diameter
(mm)
Minimuminsulationresistanceat 70
0C
(M-Km)Freeair
Underground
Cableweight(approx.)
(Kg/Km)
Standardlength
(m)
4
1
1
1.5
1.5
2.5
2.5
4
4
6
10
16
25
35
50
70
95
120
150
185
240
300
1 / 1.13
7 / 0.43
1 / 1.38
7 / 0.53
1 / 1.78
7 / 0.67
1 / 2.25
7 / 0.85
7 / 1.04
7 / 1.35
7 / 1.70
7 / 2.14
19 / 1.53
19 / 1.78
19 / 2.14
19 / 2.52
37 / 2.03
37 / 2.25
37 / 2.52
61 / 2.25
61 / 2.52
0.8
0.8
0.8
0.8
0.8
0.8
0.9
0.9
0.9
1.1
1.1
1.3
1.3
1.5
1.5
1.7
1.7
1.9
2.1
2.3
2.5
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1.2
1.2
1.5
1.5
1.5
1.8
1.8
2.0
2.0
2.2
2.2
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.2
2.2
2.4
2.6
2.8
3.0
3.2
3.4
3.8
13.5
14.0
14.0
14.5
15.0
16.0
17.0
175
19.0
23.0
26.5
31.0
35.0
39.5
44.5
57.5
56.0
62.0
68.0
76.5
85.0
0.0141
0.0135
0.0123
0.0116
0.0102
0.0093
0.0094
0.0085
0.0073
0.0069
0.0057
0.0054
0.0047
0.0046
0.0039
0.0038
0.0034
0.0034
0.0034
0.0033
0.0032
11
11
14
14
19
19
25
25
33
45
60
79
97
117
147
182
213
243
282
335
385
16
16
20
20
27
27
35
35
45
60
77
100
120
144
176
211
241
270
306
354
399
200
210
230
240
290
310
390
410
550
800
1,100
1,700
2,200
2,900
4,000
5,500
6,500
8,000
10,000
13,000
16,000
100/C
100/C
100/C
100/C
100/C
100/C
100/C
100/C
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
TISI Permitted to increase the maximum overall diameter by 5 %* REMARK : Special protection can be produced,C: Packing in coil.D: Packing in drum.
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
26/40
NYY-GRD, MEA TYPE C-GRD
750 V 700
C PVC INSULATED AND DOUBLE SHEATHED ROUND TYPE ,WITH GROUND
CABLE STRUCTURE
NUMBER OF CORE : 2 Up to4 cores with safety groundCONDUCTOR : Solid and stranded annealed copper,
sizes 1 mm2 up to 300 mm2
: Ground conductor size 1 mm2 up 35 mm2
INSULATION : PVC
Color: 2 cores Light gray and Black3 cores Light gray, Black and Red4 cores Light gray, Black, Red and BlueGround core- Green/Yellow
SHEATH : PVCUNDER SHEATH Color: Black
CLASSIFICATION : Maximum conductor temperature 70 0C
Circuit voltage not exceeding 750 voltsTESTING VOLTAGE : 2,500 voltsREFERENCE : TIS 11-2531, Table 14
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
27/40
NYY-GRD, MEA TYPE C-GRD
TIS 11-2531
TABLE 14
Maximumcontinuous current
rating in free air(Ampere)
Numberof
core
NominalCross
Sectionalarea
(mm2)
Numberand
diameterof wire
(No./mm)
Insulatiothickness
(mm)
Nominalcross
sectionalarea ofground
conductor(m
2)
Groundinsulation
thickess
(mm)
Undersheath
hickness
(mm)
Sheaththickness
(mm)
Max.overall
diameter
(mm)
Minimuminsulation
resistance at 70
0C
(M-Km)
Freeair
Underground
Cableweight
(approx.)
(Kg/Km)
Standardlength
(m)
2
11
1.51.52.52.5446
10
162535507095120150185240300
1 / 1.137 / 0.431 / 1.387 / 0.531 / 1.787 / 0.671 / 2.257 / 0.857 / 1.047 / 1.35
7 / 1.707 / 2.1419 / 1.5319 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52
0.80.80.80.80.80.80.90.90.91.1
1.11.31.31.51.51.71.71.92.12.32.5
1111
1.51.52.52.544
66
101010161625253535
0.60.60.60.60.60.60.60.60.60.6
0.60.60.60.60.60.60.60.60.60.60.6
0.80.80.80.80.80.80.80.80.80.8
0.81.21.21.21.51.51.51.81.82.02.0
1.81.81.81.81.81.81.81.81.81.8
2.02.02.02.22.22.22.42.62.83.03.2
12.513.013.013.514.015.015.516.518.019.5
22.527.029.033.538.042.546.552.057.064.070.5
0.01410.01350.01230.01160.01020.00930.00940.00850.00730.0069
0.00570.00540.00470.00460.00390.00380.00340.00340.00340.00330.0032
15151919252533334360
80106130157195239280320370440507
21212727353547476081
105136165196240290332370419484547
170170180190220240290310390550
8001,2001,5001,9002,5003,4004,1005,0006,0008,000
10,000
500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D
500/D500/D500/D500/D500/D500/D500/D500/D500/D300/D300/D
3
11
1.5
1.52.52.5446
10162535507095
120150185
240300
1 / 1.137 / 0.431 / 1.38
7 / 0.531 / 0.787 / 0.671 / 2.257 / 0.857 / 1.047 / 1.357 / 1.707 / 2.14
19 / 1.5319 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.52
61 / 2.2561 / 2.52
0.80.80.8
0.80.80.80.90.90.91.11.11.31.31.51.51.71.71.92.1
2.32.5
111
11.51.52.52.54466
10101016162525
3535
0.60.60.6
0.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.6
0.60.6
0.80.80.8
0.80.80.80.80.80.80.81.21.21.21.51.51.51.81.82.0
2.02.2
1.81.81.8
1.81.81.81.81.81.81.82.02.02.02.22.22.42.62.83.0
3.23.4
13.514.014.0
14.515.016.017.017.519.022.526.531.034.036.040.546.050.556.561.5
69.076.0
0.01410.01350.0123
0.01160.01020.00930.00940.00850.00730.00690.00570.00540.00470.00460.00390.00380.00340.00340.0034
0.00330.0032
121216
162121282837506789
109131163202235269311
371427
181822
2230303939506887
113137162200240273306346
402453
190200210
230270290360380490700
1,0001,4001,8002,4003,2004,3005,5006,5008,000
10,50013,000
500/D500/D500/D
500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D300/D
300/D200/D
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
28/40
NYY-GRD, MEA TYPE C-GRDTIS 11-2531
TABLE 14
Maximumcontinuous currentrating in free air
(Ampere)
Numberof
core
Nominalcross
sectionarea
(mm2)
Numberand
diameterof wire
(No./mm)
Insulatiohickness
(mm)
Nominalcross
sectionalarea ofground
conductor(m
2)
Groundinsulationthickess
(mm)
Undersheath
thickness
(mm)
Sheathhickness
(mm)
Max.overalldiameter
(mm)
Minimuminsulationresistanceat 70
0C
(M-Km)
Freeair
Underground
Cableweight
(approx.)
(Kg/Km)
Standardlength
(m)
4
1
1
1.5
1.5
2.5
2.5
4
4
6
10
16
25
35
50
70
95
120
150
185
240
300
1 / 1.13
7 / 0.43
1 / 1.38
7 / 0.53
1 / 1.78
7 / 0.67
1 / 2.25
7 / 0.85
7 / 1.04
7 / 1.35
7 / 1.70
7 / 2.14
19 / 1.53
19 / 1.78
19 / 2.14
19 / 2.52
37 / 2.03
37 / 2.25
37 / 2.52
61 / 2.25
61 / 2.52
0.8
0.8
0.8
0.8
0.8
0.8
0.9
0.9
0.9
1.1
1.1
1.3
1.3
1.5
1.5
1.7
1.7
1.9
2.1
2.3
2.5
1
1
1
1
1.5
1.5
2.5
2.5
4
4
6
6
10
10
10
16
16
25
25
35
35
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1.2
1.2
1.5
1.5
1.5
1.8
1.8
2.0
2.0
2.2
2.2
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.2
2.2
2.4
2.6
2.8
3.0
3.2
3.4
3.8
14.0
14.5
15.0
15.5
16.0
17.0
18.0
19.0
20.5
25.0
28.5
33.5
38.5
43.0
44.5
51.5
56.0
62.0
68.0
76.5
84.5
0.0141
0.0135
0.0123
0.0116
0.0102
0.0093
0.0094
0.0085
0.0073
0.0069
0.0057
0.0054
0.0047
0.0046
0.0039
0.0038
0.0034
0.0034
0.0034
0.0033
0.0032
11
11
14
14
19
19
25
25
33
45
60
79
97
117
147
182
213
243
282
335
385
16
16
20
20
27
27
35
35
45
60
77
100
120
144
176
211
241
270
306
354
399
230
240
260
280
320
350
440
470
600
850
1,200
1,800
2,400
3,000
4,100
5,500
7,000
8,500
10,500
13,500
16,500
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
500/D
300/D
300/D
200/D
200/D
TISI PERMITTED TO INCREASE THE MAXIMUM OVERALL DIAMETER BY 5%*REMARK : SPECIAL PROTECTION CAN BE PRODUCEDD : Packing in drum
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
29/40
NYCY
750 V 700
C PVC INSULATED AND DOUBLE SHEATHED POWER CABLE, WITH CONCENTRIC
CONDUCTORS
CABLE STRUCTURE
NUMBER OF CORE : 3 coresPHASE CONDUCTOR : Concentric stranded annealed copper wires,
sizes 16 mm2 up to 300 mm2
CONCENTRIC Annealed copper wires Size. 16 mm2up to 150 mm2CONDUCTORS
INSULATION : PVC
Color: Light gray, Black and BlueSHEATH AND UNDER : PVCSHEATH Color: Black
CLASSIFICATION : Maximumconductor temperature 700
C
Circuit voltage not exceeding 750 voltsTESTING VOLTAGE : 2,500 voltsREFERENCE : TIS 11- 2531
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
30/40
N Y
YC
THAI YAZAKI Standard
NominalCross
Sectional area(mm.
2)
Numberand diameter
of wire(No. / mm.)
Phase Concentric Phase Concentric
Insulationthickness
(mm)
Undersheathhickness
(mm)
Sheaththickness
(mm)
Approx.overalldiametor
(mm)
Maximumconductor
resistanceat 20
0C
(M-Km)
Minimuminsulationresistanceat 70
0C
(M-Km)
Maximumconductorcurrentrating infree air
(Ampere)
Cableweight
(approx.)
(Kg/Km)
Standardlength
(m)
3X25
3X35
3X50
3X70
3X95
3X120
3X150
3X185
3X240
3X300
16
16
25
35
50
70
70
95
120
150
7/2.14
19/1.53
19/1.78
19/2.14
19/2.52
37/2.03
37/2.25
37/2.52
61/2.25
61/2.52
19/1.04
19/1.04
25/1.13
23/1.38
27/1.53
31/1.70
31/1.70
36/1.83
37/2.03
41/2.14
1.3
1.3
1.5
1.5
1.7
1.7
1.9
2.1
2.3
2.5
1.2
1.2
1.5
1.5
1.5
1.8
1.8
2.0
2.0
2.2
2.0
2.0
2.2
2.2
2.4
2.6
2.8
3.0
3.2
3.4
30
33
38
43
48
53
58
64
72
79
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0601
0.0601
0.0054
0.0047
0.0046
0.0039
0.0038
0.0034
0.0034
0.0034
0.0033
0.0032
88
107
130
162
201
233
266
306
364
417
1,600
1,900
2,600
3,500
4,700
6,000
7,000
9,000
11,500
14,000
500/D
500/D
500/D
500/D
500/D
500/D
300/D
300/D
200/D
200/D
D : Packing in drum.
NominalCross
Sectional area(mm.
2)
Numberand diameter
of wire(No. / mm.)
Phase Concentric Phase Concentric
Insulationthickness
(mm)
Undersheath
hicknes
(mm)
Sheaththickness
(mm)
Approx.overall
diameter
(mm)
Maximumconductor
resistanceat 20
0C
(M-Km)
Minimuminsulation
resistanceat 70
0C
(M-Km)
Maximumconductor
currentrating infree air
(Ampere)
Cableweight
(approx.)
(Kg/Km)
Standardlength
(m)
3X16
3X25
3X35
3X50
3X70
3X95
3X120
3X150
3X150
3X185
16
25
25
35
50
70
95
95
1 20
120
7/1.70
7/2.14
19/1.53
19/1.78
19/2.14
19/2.52
37/2.03
37/2.25
37/2.25
37/2.52
19/1.04
25/1.13
25/1.13
23/1.38
27/1.53
31/1.70
36/1.83
36/1.83
37/2.03
37/2.03
1.1
1.3
1.3
1.5
1.5
1.7
1.7
1.9
1.9
2.1
1.2
1.2
1.2
1.5
1.5
1.5
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.2
2.2
2.4
2.6
2.8
2.8
3.0
26
30
33
39
43
49
54
58
59
65
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.124
0.0991
0.0057
0.0054
0.0047
0.0046
0.0039
0.0038
0.0034
0.0034
0.0034
0.0034
66
88
107
129
162
200
233
266
266
306
1,100
1,600
2,000
2,700
3,600
5,000
6,000
7,500
7,500
9,000
500/D
500/D
500/D
500/D
500/D
500/D
500/D
300/D
300/D
300/D
D : Packing in drum.
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
31/40
CVV
CVV-S
600 V 70o
C PVC INSULATED AND SHEATHED CONTROL CABLE
600 V 70o
C PVC INSULATED AND SHEATHED CONTROL CABLE WITH SHIELD
CABLE STRUCTURE
NUMBER OF CORE : 2 up to 48 coresCONDUCTOR : Flexible stranded annealed copper wires
Sizes. : 0.5 mm2up to 6 mm
2
INSULATION : PVCColor : 2-4 cores-Black, White, Red and GreenMore than 4 cores: Black with marking
numbers, colored white,printed continuouslythroughout the wholelength of insulated wires forthe purpose of coreidentification
SHEATH : PVC Color : BlackSHIELD : Copper tapeCLASSIFICATION : Maximumconductor temperature 70oC
Circuit voltage not exceeding 600 voltsTESTING VOLTAGE : 2,000 Volts
REFERENCE : THAI YAZAKI STANDARD
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
32/40
CVV
NumberOf core
NominalCross
sectionalarea
(mm2)
Numberand
diameterof wire
(No/mm)
Diameterof
Conductor
(approx.)
Insulationthickness
(mm)
Sheaththickness
(mm)
Approx.overall
diameter
(mm)
Maximumconductorresistanceat 20
0C
(-Km)
Minimuminsulationresistance
at 700C
(M-Km)
Cableweight
(approx.)
(Kg/Km)
StandardLength
(m)
2
0.50
0.751.01.52.54.06.0
16/0.20
24/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.95
1.151.301.602.102.603.40
0.6
0.60.60.60.70.80.8
0.9
1.21.21.21.21.21.4
7.5
8.58.79.310.512.014.0
39.0
26.019.513.37.984.953.30
0.0130
0.01140.01040.00890.00810.00760.0061
49
657590130170250
500/D
500/D500/D500/D500/D500/D500/D
3
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.21.21.21.21.21.21.4
8.58.99.19.811.013.015.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
658090110160230330
500/D500/D500/D500/D500/D500/D500/D
4
0.500.75
1.01.52.54.06.0
16/0.2024/0.20
32/0.2030/0.2550/0.2556/0.3084/0.30
0.951.15
1.301.602.102.603.40
0.60.6
0.60.60.70.80.8
1.21.2
1.21.21.21.41.4
9.19.6
9.810.512.014.516.5
39.026.0
19.513.37.984.953.30
0.01300.0114
0.01040.00890.00810.00760.0061
8095
110140200300410
500/D500/D
500/D500/D500/D500/D500/D
5
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.21.21.21.21.41.41.4
9.810.010.511.513.515.518.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
90110130160250350500
500/D500/D500/D500/D500/D500/D500/D
6
0.500.751.01.5
2.54.06.0
16/0.2024/0.2032/0.2030/0.25
50/0.2556/0.3084/0.30
0.951.151.301.60
2.102.603.40
0.60.60.60.6
0.70.80.8
1.21.21.21.2
1.41.41.4
10.511.011.512.0
14.517.019.5
39.026.019.513.3
7.984.953.30
0.01300.01140.01040.0089
0.00810.00760.0061
110130150190
290420600
500/D500/D500/D500/D
500/D500/D500/D
7
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.21.21.21.21.41.41.4
10.511.011.512.014.517.019.5
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
110140160210320460650
500/D500/D500/D500/D500/D500/D500/D
8
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.21.21.21.41.41.41.4
11.011.512.013.516.018.021.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
130160180240360550750
500/D500/D500/D500/D500/D500/D500/D
9
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.21.21.41.41.41.41.4
12.012.513.514.517.020.023.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
150180220270410600850
500/D500/D500/D500/D500/D500/D500/D
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
33/40
8/14/2019 Wire.pdf
34/40
CVV
NumberOf core
Nominalcross
sectionalarea
(mm2)
Numberand
diameterof wire
(No/mm)
Diameterof
Conductor
(approx.)
Insulationthickness
(mm)
Sheaththickness
(mm)
Approx.overall
diameter
(mm)
Maximumconductorresistanceat 20
0C
(-Km)
Minimuminsulationresistance
at 700C
(M-Km)
Cableweight
(approx.)
(Kg/Km)
StandardLength
(m)
18
0.500.75
1.01.52.54.06.0
16/0.2024/0.20
32/0.2030/0.2550/0.2556/0.3084/0.30
0.951.15
1.301.602.102.603.40
0.60.6
0.60.60.70.80.8
1.41.4
1.41.41.41.81.8
15.516.5
17.018.522.027.031.0
39.026.0
19.513.37.984.953.30
0.01300.0114
0.01040.00890.00810.00760.0061
250310
3704707001,1001,600
500/D500/D
500/D500/D500/D500/D500/D
19
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.41.41.81.8
15.516.517.018.522.027.031.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
2603203804907501,1001,600
500/D500/D500/D500/D500/D500/D500/D
20
0.500.751.0
1.52.54.06.0
16/0.2024/0.2032/0.20
30/0.2550/0.2556/0.3084/0.30
0.951.151.30
1.602.102.603.40
0.60.60.6
0.60.70.80.8
1.41.41.4
1.41.41.81.8
16.017.017.5
19.023.028.032.0
39.026.019.5
13.37.984.953.30
0.01300.01140.0104
0.00890.00810.00760.0061
270330400
5008001,2001,700
500/D500/D500/D
500/D500/D500/D500/D
21
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.41.41.81.8
16.517.518.019.523.028.032.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
2803504205508001,3001,800
500/D500/D500/D500/D500/D500/D500/D
22
0.500.751.01.52.5
4.06.0
16/0.2024/0.2032/0.2030/0.2550/0.25
56/0.3084/0.30
0.951.151.301.602.10
2.603.40
0.60.60.60.60.7
0.80.8
1.41.41.41.41.8
1.81.8
17.018.018.520.025.0
30.034.0
39.026.019.513.37.98
4.953.30
0.01300.01140.01040.00890.0081
0.00760.0061
300370450550900
1,3001,900
500/D500/D500/D500/D500/D
500/D500/D
23
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.41.81.81.8
17.018.018.520.025.030.034.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
3103804606009501,4002,000
500/D500/D500/D500/D500/D500/D500/D
24
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.41.81.82.2
18.019.019.521.026.031.037.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
3204005006001,0001,4002,100
500/D500/D500/D500/D500/D500/D500/D
25
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.41.81.82.2
18.019.019.521.026.031.037.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
3304104906501,0001,5002,200
500/D500/D500/D500/D500/D500/D500/D
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
35/40
CVV
NumberOf core
Nominalcross
sectionalarea
(mm2)
Numberand
diameterof wire
(No/mm)
Diameterof
Conductor
(approx.)
Insulationthickness
(mm)
Sheaththickness
(mm)
Approx.overall
diameter
(mm)
Maximumconductorresistanceat 20
0C
(-Km)
Minimuminsulationresistance
at 700C
(M-Km)
Cableweight
(approx.)
(Kg/Km)
StandardLength
(m)
26
0.500.75
1.01.52.54.06.0
16/0.2024/0.20
32/0.2030/0.2550/0.2556/0.3084/0.30
0.951.15
1.301.602.102.603.40
0.60.6
0.60.60.70.80.8
1.41.4
1.41.41.81.82.2
18.019.0
19.521.026.031.037.0
39.026.0
19.513.37.984.953.30
0.01300.0114
0.01040.00890.00810.00760.0061
340420
5006501,0001,5002,300
500/D500/D
500/D500/D500/D500/D500/D
27
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.41.81.82.2
18.519.520.022.027.032.038.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
3404305006501,1001,6002,400
500/D500/D500/D500/D500/D500/D500/D
28
0.500.751.0
1.52.54.06.0
16/0.2024/0.2032/0.20
30/0.2550/0.2556/0.3084/0.30
0.951.151.30
1.602.102.603.40
0.60.60.6
0.60.70.80.8
1.41.41.4
1.41.81.82.2
19.020.021.0
23.028.033.039.0
39.026.019.5
13.37.984.953.30
0.01300.01140.0104
0.00890.00810.00760.0061
370460550
7001,1001,7002,500
500/D500/D500/D
500/D500/D500/D500/D
29
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.41.81.82.2
19.020.021.023.028.033.039.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
3704605507001,1001,7002,500
500/D500/D500/D500/D500/D500/D500/D
30
0.500.751.01.52.5
4.06.0
16/0.2024/0.2032/0.2030/0.2550/0.25
56/0.3084/0.30
0.951.151.301.602.10
2.603.40
0.60.60.60.60.7
0.80.8
1.41.41.41.41.8
1.82.2
19.020.021.023.028.0
33.039.0
39.026.019.513.37.98
4.953.30
0.01300.01140.01040.00890.0081
0.00760.0061
4705507501,200
1,7002,600
500/D500/D500/D500/D500/D
500/D500/D
31
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.81.81.82.2
19.521.022.024.029.034.041.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
4005006008501,3001,8002,700
500/D500/D500/D500/D500/D500/D500/D
32
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.81.81.82.2
19.521.022.024.029.034.041.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
4005006008501,3001,9002,800
500/D500/D500/D500/D500/D500/D500/D
33
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.81.81.82.2
19.521.022.024.029.034.041.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
4005006008501,3001,9002,800
500/D500/D500/D500/D500/D500/D500/D
370
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
36/40
CVV
NumberOf core
Nominalcross
sectionalarea
(mm2)
Numberand
diameterof wire
(No/mm)
Diameterof
Conductor
(approx.)
Insulationthickness
(mm)
Sheaththickness
(mm)
Approx.overall
diameter
(mm)
Maximumconductorresistanceat 20
0C
(-Km)
Minimuminsulationresistance
at 700C
(M-Km)
Cableweight
(approx.)
(Kg/Km)
StandardLength
(m)
34
0.500.75
1.01.52.54.06.0
16/0.2024/0.20
32/0.2030/0.2550/0.2556/0.3084/0.30
0.951.15
1.301.602.102.603.40
0.60.6
0.60.60.70.80.8
1.41.4
1.41.81.82.22.2
20.021.0
22.025.030.037.042.0
39.026.0
19.513.37.984.953.30
0.01300.0114
0.01040.00890.00810.00760.0061
430550
6509001,4002,1003,000
500/D500/D
500/D500/D500/D500/D500/D
35
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.81.82.22.2
20.021.022.025.030.037.042.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
4305506509001,4002,1003,000
500/D500/D500/D500/D500/D500/D500/D
36
0.500.751.0
1.52.54.06.0
16/0.2024/0.2032/0.20
30/0.2550/0.2556/0.3084/0.30
0.951.151.30
1.602.102.603.40
0.60.60.6
0.60.70.80.8
1.41.41.4
1.81.82.22.2
20.021.022.0
25.030.037.042.0
39.026.019.5
13.37.984.953.30
0.01300.01140.0104
0.00890.00810.00760.0061
440550650
9001,4002,1003,100
500/D500/D500/D
500/D500/D500/D500/D
37
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.81.82.22.2
20.021.022.025.030.037.042.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
4505507009501,4002,2003,100
500/D500/D500/D500/D500/D500/D500/D
38
0.500.751.01.52.5
4.06.0
16/0.2024/0.2032/0.2030/0.2550/0.25
56/0.3084/0.30
0.951.151.301.602.10
2.603.40
0.60.60.60.60.7
0.80.8
1.41.41.41.81.8
2.22.2
21.022.023.026.031.0
38.044.0
39.026.019.513.37.98
4.953.30
0.01300.01140.01040.00890.0081
0.00760.0061
4606007009501,500
2,2003,300
500/D500/D500/D500/D500/D
500/D500/D
39
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.81.82.22.2
21.022.023.026.031.038.044.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
470600700010001,5002,3003,300
500/D500/D500/D500/D500/D500/D500/D
40
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.41.81.82.22.2
21.022.023.026.031.038.044.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
4806007501,0001,5002,3003,400
500/D500/D500/D500/D500/D500/D500/D
41
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.81.81.82.22.2
22.023.025.027.033.040.046.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
50065080010001,6002,4003,500
500/D500/D500/D500/D500/D500/D500/D
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
37/40
CVV
THIS TABLE SHOW ONLY FLEXIBLE STRANDED CONDUCTOR. IF YOU WANT TO HAVE SOLID ORCONCENTRIC CONDUCTOR TYPE, PLEASE CONTACT WITH OUR SALES DEPARTMENTFOR CVV-S: THE OVERALL DIAMETER OF CABLE AND CABLE WEIGHT SHALL BE CHANGE ALITTLE BIT MORE
D : PACKING IN DRUM.* REMARK : SPECIAL PROTECTION CAN BE PRODUCED
NumberOf core
Nominalcross
sectionalarea
(mm2)
Numberand
diameterof wire
(No/mm)
Diameterof
Conductor
(approx.)
Insulationthickness
(mm)
Sheaththickness
(mm)
Approx.overall
diameter
(mm)
Maximumconductorresistanceat 20
0C
(-Km)
Minimuminsulationresistance
at 700C
(M-Km)
Cableweight
(approx.)
(Kg/Km)
StandardLength
(m)
42
0.500.75
1.01.52.54.06.0
16/0.2024/0.20
32/0.2030/0.2550/0.2556/0.3084/0.30
0.951.15
1.301.602.102.603.40
0.60.6
0.60.60.70.80.8
1.41.4
1.81.81.82.22.2
22.023.0
25.027.033.040.046.0
39.026.0
19.513.37.984.953.30
0.01300.0114
0.01040.00890.00810.00760.0061
550650
8001,1001,6002,5003,600
500/D500/D
500/D500/D500/D500/D500/D
43
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.81.81.82.22.2
22.023.025.027.033.040.046.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
5506508501,1001,6002,5003,600
500/D500/D500/D500/D500/D500/D500/D
44
0.500.751.0
1.52.54.06.0
16/0.2024/0.2032/0.20
30/0.2550/0.2556/0.3084/0.30
0.951.151.30
1.602.102.603.40
0.60.60.6
0.60.70.80.8
1.41.41.8
1.81.82.22.6
22.024.026.0
28.034.041.048.0
39.026.019.5
13.37.984.953.30
0.01300.01140.0104
0.00890.00810.00760.0061
550650850
1,1001,7002,6003,800
500/D500/D500/D
500/D500/D500/D500/D
45
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.81.81.82.22.6
22.024.026.028.034.041.048.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
5507008501,1001,7002,6003,900
500/D500/D500/D500/D500/D500/D500/D
46
0.500.751.01.52.5
4.06.0
16/0.2024/0.2032/0.2030/0.2550/0.25
56/0.3084/0.30
0.951.151.301.602.10
2.603.40
0.60.60.60.60.7
0.80.8
1.41.41.81.81.8
2.22.6
22.024.026.028.034.0
41.048.0
39.026.019.513.37.98
4.953.30
0.01300.01140.01040.00890.0081
0.00760.0061
5507009001,1001,800
2,7004,000
500/D500/D500/D500/D500/D
500/D500/D
47
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.41.81.81.82.22.6
22.024.026.028.034.041.048.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
5507009001,2001,8002,7004,000
500/D500/D500/D500/D500/D500/D500/D
48
0.500.751.01.52.54.06.0
16/0.2024/0.2032/0.2030/0.2550/0.2556/0.3084/0.30
0.951.151.301.602.102.603.40
0.60.60.60.60.70.80.8
1.41.81.81.81.82.22.6
23.025.026.029.034.042.049.0
39.026.019.513.37.984.953.30
0.01300.01140.01040.00890.00810.00760.0061
5507509001,2001,8002,8004,100
500/D500/D500/D500/D500/D500/D500/D
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
38/40
8/14/2019 Wire.pdf
39/40
VVR-GRD
300 V 700
C PVC INSULATED AND SHEATHED ROUND TYPE, WITH GROUND
CABLE STRUCTURE
NUMBER OF CORE : 2-4 cores with safety-groundCONDUCTOR : Solid and stranded annealed copper,
sizes 1 mm2 up to 35 mm2
GROUND WIRE : Ground conductor size 1 mm2 up 10 mm2
INSULATION : PVC
Color: 2 cores Light gray and Black3 cores Light gray, Black and Red4 cores - Light gray, Black, Red and Blue
SHEATH : PVCColor: White
CLASSIFICATION : Maximum conductor temperature 70 0C
Circuit voltage not exceeding 300 voltsTESTING VOLTAGE : 2,000 voltsREFERENCE : TIS 11-2531, Table 12
THAI-YAZAKI TECHNICAL DATA
8/14/2019 Wire.pdf
40/40
VVR - GRDTIS 11-2531
TABLE 12
Numberof core
Nominalcross
sectionarea
(mm2)
Numberand
diameterof wire
(No./mm)
Insulatiothickness
(mm)
Nominalcross
sectionalarea ofground
conductor (mm
2)
Groundinsulationthickness
(mm)
Sheaththickness
(mm)
Max.Overalldiameter
(mm)
Minimuminsulationresistanceat 70
0C
(M-Km)
Minimumcontinuouscurrentrating infree air
(Ampere)
Cableweight
(approx.)
(Kg/Km)
Standard length
(m)
2
11
1.51.52.52.5446
10162535
1 / 1.137 / 0.431 / 1.387 / 0.531 / 1.787 / 0.671 / 2.257 / 0.857 / 1.047 / 1.357 / 1.707 / 2.14
19 / 1.53
0.60.60.60.60.70.70.80.80.80.91.01.21.2
1111
1.51.52.52.54466
10
0.60.60.60.60.60.60.60.60.60.60.60.60.6
0.90.91.21.21.21.21.21.21.21.21.41.41.4
8.08.49.29.6
10.511.512.513.014.516.019.022.525.5
0.01150.01100.01000.00940.00920.00840.00860.00780.00660.00590.00530.00510.0043
1414181824243232436080107132
7585
100110140150200210290410600850
1,200
500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D
3
11
1.51.52.52.5446
10162535
1 / 1.137 / 0.431 / 1.387 / 0.531 / 1.787 / 0.671 / 2.257 / 0.857 / 1.047 / 1.357 / 1.707 / 2.14
19 / 1.53
0.60.60.60.60.70.70.80.80.80.91.01.21.2
1111
1.51.52.52.54466
10
0.60.60.60.60.60.60.60.60.60.60.60.60.6
0.90.91.21.21.21.21.21.21.21.21.41.81.8
8.69.0
10.010.511.512.513.514.015.518.522.027.530.5
0.01150.01100.01000.00940.00920.00840.00860.00780.00660.00590.00530.00510.0043
111115152020272736506790110
95100120140180190260280370550800
1,2001,600
500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D
4
11
1.51.52.52.5446
10162535
1 / 1.137 / 0.431 / 1.387 / 0.531 / 1.787 / 0.671 / 2.257 / 0.857 / 1.047 / 1.357 / 1.707 / 2.14
19 / 1.53
0.60.60.60.60.70.70.80.80.80.91.01.21.2
1111
1.51.52.52.54466
10
0.60.60.60.60.60.60.60.60.60.60.60.60.6
0.90.91.21.21.21.21.21.21.21.41.41.81.8
9.29.8
11.011.512.513.514.515.517.020.524.530.033.5
0.01150.01100.01000.00940.00920.00840.00860.00780.00660.00590.00530.00510.0043
10101313181825253345608199
120130160170220240320350470700
1,0001,6002,000
500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D500/D
TISI permitted to increase the maximum overall diameter by 5 %D : Packing in drum.