Page 1: X57 - Ronan Engineering · 2019. 9. 10. · X57 Common Applications 5 These applications are intended as an aid in selecting possible barrier options. As with any I.S. installation,
Page 2: X57 - Ronan Engineering · 2019. 9. 10. · X57 Common Applications 5 These applications are intended as an aid in selecting possible barrier options. As with any I.S. installation,

Intrinsic Safety Barriers are devices

which limit the power (energy) that

can be delivered from a safe area into a

hazardous area. Explosions are therefore

prevented, not just contained, as in expan-

sion proof conduit and heavy cast housings.

Not only is electrical energy (voltage and

current) held within safe limits, but also

total energy, eliminating the possibility of

an explosion due to excessive heat. The use

of barriers and a total intrinsically safe

design philosophy offers considerable

advantages from both cost and safety

standpoints.

The following features indicate the clear benefits ofchoosing an intrinsically safe design instead of anexplosion-proof design, and reflect the unique features ofthe Series X57 family of barriers.

All system components are immediately accessible — no timeconsuming opening of explosion proof housings.

Personnel safety is assured because of low voltage operation.

Standard wiring techniques in open cable trays or lightgauge conduit save on material and labor cost duringinitial installation.

Calibration and maintenance can be performed with thesystem in operation.

Special skill levels are not needed to open heavy housings,to test for gas, or to shut down the process in order toservice or operate the instrumentation.

Barrier replacement is accomplished by simple exchange ofplug-in modules. There is no need to disconnect wiring orto remove ground bars.

Barriers are manufactured and stocked in the U.S.A. inWoodland Hills, California. (Los Angeles area)

Multiple channels in one barrier minimize the total numberof barrier modules needed and space required.

The Ronan I.S. Barriers are plug-in modules containingone to four channels. Up to twenty barrier modules can beinstalled in a 20 position surface mounted chassis. Singlebarrier surface or DIN rail chassis are also available. Eachmodule has eight screw terminals. The terminals arearranged in the chassis so that four are located in the safearea and four are located in a protected compartment forthe wiring to the hazardous area. The safe area terminalsare numbered 1 through 4 and the protected terminalsare numbered 5 through 8. These compression type screwterminals accept up to 12 AWG wire. The safe areaterminals are connected to equipment in a location wherethe sources of potential with respect to each other or toground do not exceed 250 Vdc or RMS. The I.S. groundingconnection for the barriers is provided by an integral,

fixed, #8 stud with self-locking nuts. Optional ground busbars and multi-pin cable connectors are also available.

X57I n t r i n s i c S a f e t y B a r r i e r sI n t r i n s i c S a f e t y B a r r i e r s

2

Page 3: X57 - Ronan Engineering · 2019. 9. 10. · X57 Common Applications 5 These applications are intended as an aid in selecting possible barrier options. As with any I.S. installation,

X57

Typical Barrier Choices:Field Devices Barrier Choices*Switches (dry contact) X57-128P, X57-228P,

X57-228PD, X57-228PCL,X57-328P, X57-428P

Thermocouples X57-205S(ungrounded only)RTDs and Potentiometers X57-305P, X57-405P2-Wire Transmitters X57-128N, X57-228PD

X57-228P-209PSolenoids/Relays/LEDs X57-128P, X57-228PDI/P Transducers X57-228PDStrain Gauges X57-210AMagnetic Flow Sensors X57-110A, X57-210Sand AC Sensors

S h u n t D i o d e Z e n e r ( P a s s i v e ) I . S . B a r r i e r sS h u n t D i o d e Z e n e r ( P a s s i v e ) I . S . B a r r i e r s

Ronan's Zener Barriers, especially the multi-

channel versions, are a logical choice when space

and cost are the major considerations. They do not

require their own power supply, but rather provide

protection passively. Most likely, there is a barrier

that will work, and a detailed analysis of the applica-

tion will usually identify a zener barrier that is right

for the application. However, zener barriers do

require a high integrity I.S. ground. This may present

a problem, especially in older plant installations.

When the quality or availability of an I.S. ground is

questionable, the designer should consider using

active barriers.

Lowest Cost Barrier Option

1, 2, 3, and 4 Channel Barriers

Negative, Positive, or AC Voltage Versions

Highly Reliable Fast Acting Fuses

Power Supply is Not Required

NO FAULT “Blown Fuse” Barrier Replacement Policy

DIN Rail or Multi-Barrier Surface Mount Chassis

3.60"(91.44 mm)

2.50" (63.50 mm)

.88" (22.35 mm)

Specifications:

Type: Shunt zener diode with non-replaceable fuses

Mounting: Plug-in (chassis required) with gold platedconnections

Wiring: All wiring and grounding is attached to thechassis to simplify installation and maintenance

Wire Size: Up to #12 AWG

Size: (chassis not included): 3.60″ H x .88″ W x 2.50″ D(up to four (4) channels per barrier)

Weight: (chassis not included): 5.6 ounces

Operating Temperature: -20˚C to +50˚C

Storage Temperature: -40˚C to +80˚C

Relative Humidity: 95% non-condensing

With replaceable fuses, the chanceexists that the wrong type or rating offuse could be installed, or that thefuses could be defeated (bypassed witha short circuit). Circuit breakers are mechanical, andthey are therefore more susceptible toaging, corrosion, and damage. Also,they typically have lower accuracyspecifications.

Both the replaceable fuse and thecircuit breaker designs are harder andmore expensive to manufacture.Therefore, they cost you more money.

Ronan's zener barriers are pottedsolid. This means that if a fuse is blown,the barrier has done its job and protectedthe hazardous area as it was designed todo. It’s true the barrier can not be fieldrepaired. However, if you do “blow” a

barrier fuse (even if its your fault), justcontact the Ronan factory for a rushreplacement at 1/2 price. Also, for mostapplications, Ronan can provide aneasily installed in-line fuse device whichcan protect the barrier’s internal fuse(See accessory #X57-FUSE).

R e p l a c e a b l e F u s e s a n d C i r c u i t B r e a k e r s v s . N o n - R e p l a c e a b l e F u s e s

* Some European applications require an “EN” designator within the partnumber (i.e. X57EN-600). Contact your local Ronan sales office for details.

3

Page 4: X57 - Ronan Engineering · 2019. 9. 10. · X57 Common Applications 5 These applications are intended as an aid in selecting possible barrier options. As with any I.S. installation,

Typical Barrier Choices:Field Devices Barrier Choices*Switches (dry contact) X57-650 (dual channel)Proximity Sensors X57-653Thermocouples (grounded X57-606or ungrounded)RTDs and Poteneiometers X57-6052-Wire Transmitters X57-600, X57-660

Honeywell Protocol X57-600H, X57-660HRonan, Hart, Rosemount X57-600R, X57-660RI.S. Ground Required X57-528N

Solenoids/Relays/LEDs X57-610, X57-611(S)I/P Transducers X57-620

In numerous applications, zener diode barriers

will either not work, or they impose constraints that

complicate system design. The series resistance, fuse

rating and maximum working voltage of a zener

diode barrier, can cause the design engineer hours

of frustrating analysis to confirm both safety and

proper system operation. Ronan's line of active I.S.

barriers eliminates much of the tedious analysis re-

quired. In some cases, the active barrier can actually

double as a signal conditioner and eliminate other

devices from the loop. These considerations, along

with the fact that no I.S. ground is required, and the

fact that most circuits are short circuit proof, has

caused the active barriers to gain popularity.

4.75" (120.65 mm)

3.60"(91.44 mm)

.88" (22.35 mm)

Specifications:

Type: Active isolation

Power: Nominal 24 Vdc @ 50 to 100 mA(see individual barriers specifications)

Mounting: Plug-in (chassis required) with gold platedconnections

Wiring: All wiring is attached to the chassis, tosimplify installation and maintenance

Wire Size: Up to #12 AWG

Size: (chassis not included): 3.60″ H x .88″ W x 4.75″ D(1 to 2 channels; see individual data sheets)

Weight: (chassis not included): Approximately 6 ounces

Operating Temperature: -20˚C to +50˚C

Storage Temperature: -40˚C to +80˚C

Relative Humidity: 95% non-condensing

The concept of "Intrinsic Safety"originated in the European markets butis gaining in popularity all over theworld. Originally, and still the case withsome equipment, manufacturers hadtheir field instruments tested andapproved with a specific I.S. barrier(Loop Approvals). This limited theuser's choices of field instruments and

barriers. The Entity Approval concept isnow becoming the standard because itallows the user to select fieldinstruments and I.S. barriers from anyapproved supplier. The only stipulationis that the entity numbers of bothdevices are properly matched and thatthe equipment is properly installed perthe approved installation drawings.

It is important to remember that anl.S. barrier does not make a field devicesafe. The field instrument must be eithera "simple apparatus" or an l.S. devicewhich was certified under the entityconcept in order for it to be compatiblewith Ronan l.S. barriers. If you have aquestion or concern about your applica-tion, contact Ronan for assistance.

E n t i t y A p p r o v a l s v s . L o o p A p p r o v a l

Full Input, Output and Power Isolation(Eliminates ground loops)

Short Circuit Proof (Most models) or Fuse Protected

No I.S. Ground Required

Less Critical Circuit Design Constraints

Eliminates Other Signal Conditioning, therebyLowering Installed Cost

Discrete or Analog Input and Output Barrier Options

X57G a l v a n i c I s o l a t i o n ( A c t i v e ) B a r r i e r sG a l v a n i c I s o l a t i o n ( A c t i v e ) B a r r i e r s

* Some European applications require an “EN” designator within the partnumber (i.e. X57EN-600). Contact your local Ronan sales office for details.

4

Page 5: X57 - Ronan Engineering · 2019. 9. 10. · X57 Common Applications 5 These applications are intended as an aid in selecting possible barrier options. As with any I.S. installation,

X57C o m m o n A p p l i c a t i o n sC o m m o n A p p l i c a t i o n s

5

These applications are intended as an aid in selecting possiblebarrier options. As with any I.S. installation, variables such as areaclassification, make and model of field device, required approvalagency certification, and total loop design can all affect safety

and operation. Therefore, care should be excercised when selectinga barrier to assure compliance with approved installation drawingsand to assure proper circuit operations. Ronan engineers areavailable to help in your barrier selection.

X57-606

+- 24 Vdc

+

-4-20 mA (Non-Linear)

2

46

5

T/C

OptionalGround

X57-205S X57-210LTransmitter

2

4

7

5

I.S. Ground

T/C(No Ground)

+

-4-20 mA

+-

24 Vdc

+

-4-20 mA (Linear)

2

4

7

6

5

X57-605LRTD or

Potentiometer

2

4

7

5

X57-230Transmitter

6 3X57-305P

4

I.S. Ground

+

-4-20 mARTD or

Potentiometer

+-

24 Vdc

4-20 mAController

+

-X57-228 PD

+

-

2

4

7

5I/P

I.S. Ground

+-

24 Vdc

X57-620 4-20 mAController

+

-

3

47

5+

-I/P

2

47

5

X57-228 PD

I.S. Ground

+- 24 Vdc

2-WireTrans-mitter

+

-

100 Ω Loop Resistor

X51-422Trip

+

-24 Vdc

Signal

+-

24 Vdc

X57-600PLCor

DCS

+

-

3

47

5

250 Ω Loop Resistor4-20mA

2-WireTrans-mitter

+

-

+

-24 VdcX57-610

3

47

5+

-

LEDor

Solenoid

2

4

7

5

I.S. Ground

X57-228 PD+

-24 Vdc

+

-

LEDor

Solenoid

Hazardous Area Safe AreaHazardous Area Safe Area

P A S S I V E A C T I V E

C u r r e n t / V o l t a g e D r i v e r ( D i g i t a l ) O u t p u t

T w o - W i r e T r a n s m i t t e r ( A n a l o g ) I n p u t

I / P ( A n a l o g ) O u t p u t

R T D ( A n a l o g ) I n p u t

T h e r m o c o u p l e ( A n a l o g ) I n p u t

D r y C o n t a c t ( D i g i t a l ) I n p u t

AnnunciatorX57-228 PCL

2

47

5H

FC

+-

24-32 VdcI.S. Ground

Dry Contact Annunciator

H1

FC1

H2

FC2

X57-650

1

2

3

4

8

7

6

5

+-

24 Vdc

Dry Contact

Dry Contact

Page 6: X57 - Ronan Engineering · 2019. 9. 10. · X57 Common Applications 5 These applications are intended as an aid in selecting possible barrier options. As with any I.S. installation,

X57C h a s s i s O p t i o n s ( S u r f a c e M o u n t )C h a s s i s O p t i o n s ( S u r f a c e M o u n t )

S u r f a c e M o u n t f o r A c t i v e a n d Z e n e r B a r r i e r s

X57-SM-10 X57-SM-4with Ground Bars

X57-SM-1with Ground Bars

5.94 in.(150.82 mm)

3.56 in.(90.81 mm)

24

31

24

31

24

31

24

31

24

31

24

31

24

31

24

31

24

31

24

31

C

D

B A

.91 in.(23.11 mm)

1.71 in. (43.43 mm)4.00 in.

(101.60 mm)

.21 in. (5.41 mm)4 Places

I.S.GNDV+V–

10

9

8

7

6

5

4

3

2

1

ActiveIsolatedBarrierModule

Zener DiodeBarrierModule

Ground Bar

GroundConnection Clamp

18GA, Green

In/Out1 to 4

ChannelsUsed

ExtendedGround

ConnectionOptional

I.S.GoundI.S.

Ground

In/Out1 to 4ChannelsUsed

GroundConnection

Ground Bar

Clamp

ExtendedGround

ConnectionOptional

HazardousArea

SafeArea

24 Vdc

18GA, Green

5678

4321

V+V–

68

75

24

31

5.80 in.(147.32 mm)

3.57 in.(90.68 mm)

.16 in. (93.96 mm) Dia.4 Places

4.00 in.(101.60 mm)

5.82 in. (147.82 mm)

2.96 in.(75.56 mm)

2.58 in.(65.40 mm)

.91 in.(23.11 mm)

ActiveIsolatedBarrierModule

Zener DiodeBarrierModule

24

31

I.S.GND

V–V+

Ground Bar

Ground Connection

18GA, Green

In/Out1 to 4

ChannelsUsed

ExtendedGround

ConnectionOptional

I.S. Ground

In/Out1 to 4ChannelsUsed

24 Vdc

18GA, Green

5678

4321

V+V–

I.S. Ground

68

75

24

31

HazardousArea

SafeArea

6

X 5 7 S M - 1

X 5 7 S M - 1 0 X 5 7 S M - 4 , - 1 0 , - 1 6 , a n d - 2 0 W i r i n g

X 5 7 S M - 1 W i r i n g

MODEL NO. DIMENSION A DIMENSION B DIMENSION C DIMENSION D

X57SM-4 5.68 in. (144.27 mm) 5.28 in. (134.11 mm) 5.82 in. (147.82 mm)

X57SM-10 11.05 in. (280.67 mm) 10.65 in. (270.51 mm) 5.82 in. (147.82 mm)

X57SM-16 16.42 in. (417.07 mm) 16.02 in. (406.91 mm) 5.82 in. (147.82 mm)

X57SM-20 20.00 in. (508.00 mm) 19.60 in. (497.84 mm) 5.82 in. (147.82 mm)

X57SM-4EG 5.68 in. (144.27 mm) 5.28 in. (134.11 mm) 7.42 in. (188.46 mm)

X57SM-10EG 11.05 in. (280.67 mm) 10.65 in. (270.51 mm) 7.42 in. (188.46 mm)

X57SM-16EG 16.42 in. (417.07 mm) 16.02 in. (406.91 mm) 7.42 in. (188.46 mm)

X57SM-20EG 20.00 in. (508.00 mm) 19.60 in. (497.84 mm) 7.42 in. (188.46 mm)

Extended Ground Connection (Contact Ronan for complete model numbers)

Maximum Number of Modules (Position)

weiwenwu
Stamp
Page 7: X57 - Ronan Engineering · 2019. 9. 10. · X57 Common Applications 5 These applications are intended as an aid in selecting possible barrier options. As with any I.S. installation,

4.13 in.(104.78 mm)

5.21 in. (132.21 mm)

6.29 in. (159.64 mm)

SAFE AREAHAZARDOUSAREA

SAFE AREA SAFE AREA

8765 4 4 43 3 32 2 21 1 1

HAZARDOUSAREA

8765

HAZARDOUSAREA

8765

To I.S.Ground

To I.S.Ground

Optional GroundBar with Clampsfor Signal or ShieldGround Access.May be Located onEither End

.88 in.(22.23 mm)

.86 in.(21.84 mm)

4.28 in.(108.71 mm)

2.00 in.(50.00 mm)

OptionalX57 Fuse(Shown

2 places)Ground Bar

X57-DIN-32Base Assembly

DINRail

Zener DiodeBarrierModule

X57D I N R a i l M o u n t f o r A c t i v e a n d Z e n e r B a r r i e r s

C h a s s i s O p t i o n s ( D I N R a i l M o u n t )C h a s s i s O p t i o n s ( D I N R a i l M o u n t )

DINRail

6.44 in.(163.50 mm)

5.01 in. (147.45 mm)

6.89 in. (174.88 mm)

+ +SAFE

SAFE

AREA

AREA

- -

88 77 66 55 44 33 22 11

HAZARDOUSAREA

HAZARDOUSAREA

4.73 in.(120.02 mm)

.83 in.(21.08 mm)

Typical .86 in.(22.23 mm)

2.00 in.(50.00 mm)

ActiveIsolatedBarrierModule

OptionalX57 Fuse(Shown

2 Places)

X57-PDIN-32Base Assembly

88

77

66

55

44

33

22

11

++

--

Optional Fuse Protection DeviceThe X57-FUSE device attaches to the

existing terminal blocks of any X57 chassis,and it provides a duplicate/alternate set ofterminals for connecting the field wiring. TheX57-FUSE device contains up to 4 additionalfuses that are electronically placed in serieswith a barrier’s internal fuses. By sizing thefuses on the X57-FUSE device to values lessthan the barrier’s fuse you will protect thebarrier's fuses. The smaller value fuses on theX57-FUSE device will “blow” first, in the eventof over-voltage or short circuits.

7

X 5 7 - P D I N - 3 2 ( S h o w n ) a n d X 5 7 - P D I N - 3 5

X 5 7 - D I N - 3 2 ( S h o w n ) a n d X 5 7 - D I N - 3 5

X57-P DIN-32for Active Barriers

X57-DIN-32with Ground Barsfor Zener Barriers

The X57-PDIN chassis was designed for usewith X57-600 Series (active) barriers only.These chassis do not have safety ground con-nections. Therefore, they can not be usedwith zener barriers. Each chassis has a set ofterminals for connecting 24 Vdc power. Inmultiple barrier applications, “+” and “-”power wires must be connected separately toeach chassis or “daisychained” from chassis tochassis. On large systems, consider using thesurface mount chassis to simplify powerconnection wiring.

Note: The X57-DIN-32 and X57-PDIN-32 use 32mm “G” style rails.These chassis are also available for the 35 x 7.5 mm and 35 x 15 mm“U” style rails. Order X57-DIN-35 or X57-PDIN-35.Contact Ronan for availability.

The “DIN” rail chassis options are an idealchoice to save on panel space. Order onechassis for each barrier module. With theX57-DIN chassis (for zener barriers) eachchassis requires its own ground wire. Onmultiple chassis installations, the optionalground bars “buss” together the individualchassis grounds allowing one ground con-nection for the entire group. These groundbars and the ground bar clamps also providea convenient spot to terminate cable shields.Contact Ronan for assistance in specifyingground bars for your installation. On largersystems, consider using the surface mountchassis to simplify ground wiring.

Page 8: X57 - Ronan Engineering · 2019. 9. 10. · X57 Common Applications 5 These applications are intended as an aid in selecting possible barrier options. As with any I.S. installation,

Ronan warrants equipment of its own manufacture

to be free from defects in material and workmanship,

under normal conditions of use and service,

and will replace any component found to be defective,

on its return, transportation charges prepaid,

within one year of its original purchase.

This warranty carries no liability,

either expressed or implied, beyond our obligations

to replace the unit which carries the warranty.

R O N A N E N G I N E E R I N G C O M P A N YI / O P r o d u c t s D i v i s i o n

21200 Oxnard Street, Woodland Hills, CA 91367 U.S.A.800-327-6626 • Fax 818-992-6435

1 Tilley Road, Crowther Industrial Estate, Washington, Tyne & Wear U.K., NE38 OAE44-191-416-1689 • Fax 44-191-416-5856

32 Bermondsey Road, Toronto, Ontario, Canada M4B 1Z5416-752-0310 • Fax 416-752-8072

h t t p : / / w w w . r o n a n . c o m E - M a i l : s a l e s @ r o n a n . c o m

X57 Rev.0 10/98 Printed in U.S.A.

W a r r a n t yW a r r a n t y


Recommended