+ All Categories
Home > Documents > XM-124 Standard Dynamic Measurement Module · The examples and diagrams in this manual are included...

XM-124 Standard Dynamic Measurement Module · The examples and diagrams in this manual are included...

Date post: 20-Jul-2018
Category:
Upload: truongngoc
View: 217 times
Download: 0 times
Share this document with a friend
20
Installation Instructions XM-124 Standard Dynamic Measurement Module Catalog Number 1440-SDM02-01RA Topic Page Important User Information 2 North American Hazardous Location Approval 3 Wiring Requirements 4 Install the Module 4 Additional Resources 19
Transcript
  • Installation Instructions

    XM-124 Standard Dynamic Measurement ModuleCatalog Number 1440-SDM02-01RA

    Topic Page

    Important User Information 2

    North American Hazardous Location Approval 3

    Wiring Requirements 4

    Install the Module 4

    Additional Resources 19

  • 2 XM-124 Standard Dynamic Measurement Module

    Important User Information

    Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

    In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

    The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

    No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

    Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

    Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

    WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

    ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.

    SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

    BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

    IMPORTANT Identifies information that is critical for successful application and understanding of the product.

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/sgi-in001_-en-p.pdfhttp://www.rockwellautomation.com/literature/

  • XM-124 Standard Dynamic Measurement Module 3

    North American Hazardous Location Approval

    The following information applies when operating this equipment in hazardous locations.

    Informations sur lutilisation de cet quipement en environnements dangereux.

    Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

    Les produits marqus "CL I, DIV 2, GP A, B, C, D" ne conviennent qu' une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livr avec des marquages sur sa plaque d'identification qui indiquent le code de temprature pour les environnements dangereux. Lorsque plusieurs produits sont combins dans un systme, le code de temprature le plus dfavorable (code de temprature le plus faible) peut tre utilis pour dterminer le code de temprature global du systme. Les combinaisons d'quipements dans le systme sont sujettes inspection par les autorits locales qualifies au moment de l'installation.

    WARNING:Explosion Hazard - Do not disconnect equipment

    unless power has been removed or the area is known to be nonhazardous.

    Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

    Substitution of components may impair suitability for Class I, Division 2.

    If this product contains batteries, they must only be changed in an area known to be nonhazardous.

    AVERTISSEMENT:Risque dExplosion Couper le courant ou s'assurer que

    l'environnement est class non dangereux avant de dbrancher l'quipement.

    Couper le courant ou s'assurer que l'environnement est class non dangereux avant de dbrancher les connecteurs. Fixer tous les connecteurs externes relis cet quipement l'aide de vis, loquets coulissants, connecteurs filets ou autres moyens fournis avec ce produit.

    La substitution de composants peut rendre cet quipement inadapt une utilisation en environnement de Classe I, Division 2.

    S'assurer que l'environnement est class non dangereux avant de changer les piles.

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • 4 XM-124 Standard Dynamic Measurement Module

    Wiring RequirementsUse solid or stranded wire. All wiring must meet the following specifications:

    1422 AWG copper conductors without pretreatment; 8 AWG required for grounding the DIN rail for electromagnetic interference (EMI) purposes

    Recommended strip length 8 mm (0.31 in.) Minimum insulation rating of 300V Soldering the conductor is forbidden Wire ferrules can be used with stranded conductors; copper ferrules

    recommended

    Install the ModuleTo install the XM-124 Standard Dynamic Measurement Module, follow these steps.

    1. Mount the terminal base unit.

    2. Wire the module.

    3. Mount the module.

    4. Connect the power supply.

    5. Connect the channel outputs.

    6. Establish a serial port connection.

    7. Establish a DeviceNet connection.

    ATTENTION: The XM-124 Dynamic Measurement Module is certified and approved for use only in the 1440-TB-A/C terminal base unit. Do not install the XM-124 module in any other terminal base unit.

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • XM-124 Standard Dynamic Measurement Module 5

    Mount the Terminal Base Unit

    The XM family includes several terminal base units to serve all of the XM modules. The 1440-TB-A/C terminal base unit is the only terminal base unit used with the Standard Dynamic Measurement Module (catalog number 1440-SDM02-01RA).

    The terminal base unit can be DIN rail or panel mounted.

    DIN Rail Mounting

    Use the following steps to mount the terminal base unit on a DIN rail (Allen-Bradley catalog number 199-DR1 or 199-DR4).

    WARNING: If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.

    Be sure that power is removed or the area is nonhazardous before proceeding.

    ATTENTION: Do not remove or replace a terminal base unit while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • 6 XM-124 Standard Dynamic Measurement Module

    1. Position the terminal base unit on the 35 x 7.5 mm DIN rail (A).

    2. Slide the terminal base unit over, leaving room for the side connector (B).

    3. Rotate the terminal base unit onto the DIN rail with the top of the rail hooked under the lip on the rear of the terminal base unit.

    31887-M

    B

    A

    A

    31883-M

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • XM-124 Standard Dynamic Measurement Module 7

    4. Press down on the terminal base unit to lock the terminal base unit onto the DIN rail.

    If the terminal base unit does not lock into place, use a screwdriver or similar device to open the locking tab, press down on the terminal base unit until it is flush with the DIN rail, and release the locking tab to lock the base in place.

    Wire the Module

    Wiring to the module is made through the terminal base unit on which the module mounts. The XM-124 module is compatible only with the XM-940 terminal base unit, catalog number 1440-TB-A.

    XM-940 Terminal Base Unit

    XM-940 (catalog number 1440-TB-A)

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • 8 XM-124 Standard Dynamic Measurement Module

    Terminal Block Assignments

    The terminal block assignments for the XM-124 Standard Dynamic Measurement Module are detailed in this section.

    TIP The XM modules revision number is on the product label, which is on the front of the XM module, as shown on the example below (actual product label can have different ratings).

    WARNING: EXPLOSION HAZARD. Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

    Revision Number of XM Module

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • XM-124 Standard Dynamic Measurement Module 9

    Terminal Block Assignments

    No. Name Description

    0 Xducer 1 (+) Vibration transducer 1 connection

    1 Xducer 2 (+) Vibration transducer 2 connection

    2 Buffer 1 (+) Vibration signal 1 buffered output

    3 Buffer 2 (+) Vibration signal 2 buffered output

    4 Tach/Signal In (+) Tachometer transducer/signal input, positive side

    5 Buffer Power 1 IN Channel 1 buffer power inputConnect to terminal 6 for positive bias transducers or terminal 21 for negative bias transducers

    6 Positive Buffer Bias Provides positive (-5...24V) voltage compliance to buffered outputs Connect to terminals 5 (CH 1) and 22 (CH 2) for positive bias transducers

    7 TxD Personal computer serial port, transmit data

    8 RxD Personal computer serial port, receive data

    9 XRTN1 Circuit return for TxD and RxD

    10 Chassis Connection to DIN-rail ground spring or panel mounting hole

    11 4-20 mA 1 (+) 420 mA output 300 maximum load

    12 4-20 mA 1 (-)

    13 Chassis Connection to DIN-rail ground spring or panel mounting hole

    14 Chassis Connection to DIN-rail ground spring or panel mounting hole

    15 Chassis Connection to DIN-rail ground spring or panel mounting hole

    16 Xducer 1 (-)1 Vibration transducer 1 connection

    17 Xducer 2 (-)1 Vibration transducer 2 connection

    18 Signal Common1 Vibration buffered output return

    19 TACH Buffer Tachometer transducer/signal output

    20 Tachometer (-) Tachometer transducer/signal return, TACH Buffer return

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • 10 XM-124 Standard Dynamic Measurement Module

    21 Buffer/Xducer Pwr (-)

    Provides negative (-24...9V) voltage compliance to buffered outputsConnect to terminals 5 (CH 1) and 22 (CH 2) for negative bias transducersTransducer power supply output, negative side; used to power external sensor (40 mA maximum load)

    22 Buffer Power 2 IN Channel 2 buffer power inputConnect to terminal 6 for positive bias transducers or terminal 21 for negative bias transducers

    23 CAN_High DeviceNet bus connection, high differential (white wire)

    24 CAN_Low DeviceNet bus connection, low differential (blue wire)

    25 +24 V Out Internally connected to 24V In (terminal 44)Used to daisy chain power if XM modules are not plugged into each otherIf power is not present on terminal 44, there is no power on this terminal

    26 DNet V (+) DeviceNet bus power input, positive side (red wire)

    27 DNet V (-) DeviceNet bus power input, negative side (black wire)

    28 24 V Common1 Internally connected to 24V Common (terminals 43 and 45)Used to daisy chain power if XM modules are not plugged into each other

    29 4-20 mA 2 (+) 4...20 mA output300 maximum load

    30 4-20 mA 2 (-)

    31 Chassis Connection to DIN-rail ground spring or panel mounting hole

    32 Chassis

    33 Chassis

    34 Chassis

    35 Chassis

    36 Chassis

    37 Chassis

    38 Chassis

    39 SetPtMult Switch input to activate Set Point Multiplication (active closed)

    40 Switch RTN Switch return, shared between SetPtMult and Reset Relay

    Terminal Block Assignments

    No. Name Description

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • XM-124 Standard Dynamic Measurement Module 11

    1 Terminals are internally connected and isolated from the chassis terminals.

    Mount the Module

    The XM-124 Standard Dynamic Measurement Module (catalog number1440-SDM02-01RA) is used only with the 1440-TB-A/C terminal base unit.

    41 Reset Relay Switch input to reset internal relay (active closed)

    42 Reserved

    43 24 V Common1 Internally DC-coupled to circuit ground

    44 +24 V In Connection to primary external +24V power supply, positive side

    45 24 V Common1 Connection to external +24V power supply, negative side (internally DC-coupled to circuit ground)

    46 Reserved

    47 Relay Common Relay Common contact

    48 Relay N.O. Relay Normally Open contact

    49 Reserved

    50 Reserved

    51 Reserved

    WARNING: An electrical arc can occur if you do the following:

    Insert or remove the module while backplane power is on Connect or disconnect wiring while the field-side power is onThis can cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

    IMPORTANT Install the overlay slide label to protect the serial connector and electronics when the serial port is not in use.

    Terminal Block Assignments

    No. Name Description

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • 12 XM-124 Standard Dynamic Measurement Module

    1. Make certain the keyswitch (D) on the terminal base unit (E) is at position 1 as required for the module.

    2. Make certain the side connector (B) is pushed all the way to the left.

    You cannot install the module unless the connector is fully extended.

    3. Make sure that the pins on the bottom of the module are straight so they will align properly with the connector in the terminal base unit.

    4. Position the module (A) with its alignment bar (G) so that it is aligned with the groove (F) on the terminal base unit.

    5. Press firmly and evenly to seat the module in the terminal base unit.

    The module is seated when the latching mechanism (C) is locked into the module.

    6. Repeat the above steps to install the next module in its terminal base unit.

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • XM-124 Standard Dynamic Measurement Module 13

    Connect the Power Supply

    Power supplied to the module must be 24V DC nominally (10%) and must be a Class 2 rated source.

    Wire the DC-input power supply to the terminal base unit as shown below.

    DC Input Power Supply Connection

    IMPORTANT A Class 2 circuit can be provided by use of an NEC Class 2 rated power supply, or by using a SELV or PELV rated power supply with a 5 A current limiting fuse installed before the XM module.

    IMPORTANT 24V DC must be wired to terminal 44 (+24V In) to provide power to the device and other XM modules linked to the wired terminal base unit via the side connector.

    ATTENTION: The power connections vary for different XM modules. Refer to the installation instructions for your specific XM module for complete wiring information.

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • 14 XM-124 Standard Dynamic Measurement Module

    Serial Port Connection

    The XM-124 module includes a serial port connection, which lets you connect a personal computer and configure the modules parameters via the Serial Configuration software utility.

    There are two methods of connecting an external device to the modules serial port:

    Terminal base unit - There are three terminals on the terminal base unit that you can use for the serial port connection. They are TxD, RxD, and RTN (terminals 7, 8, and 9, respectively). If these three terminals are wired to a DB-9 female connector, then a standard RS-232 serial cable with 9-pin (DB-9) connectors can be used to connect the module to a personal computer (no null modem is required). The DB-9 connector must be wired to the terminal block as follows.

    Mini-connector - The mini-connector is on the top of the module, as shown below.

    Mini-connector

    A special cable (catalog number1440-SCDB9FXM2) is required for this connection.

    Product Name/Title Terminal Base Unit(catalog number 1440-TB-A)

    DB-9 Female Connector

    TX Terminal (terminal 7) ---------------------- Pin 2 (RD - receive data)

    RX Terminal (terminal 8) ---------------------- Pin 3 (TD - transmit data)

    RTN Terminal (terminal 9) --------------------- Pin 5 (SG - signal ground)

    Mini-connector

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • XM-124 Standard Dynamic Measurement Module 15

    The connector that inserts into the personal computer is a DB-9 female connector, and the connector that inserts into the module is a USB Mini-B male connector. The default communication rate is 19.2 Kbps.

    DeviceNet Connection

    The XM-124 module includes a DeviceNet connection that allows the modules to communicate with a programmable logic controller (PLC), distributed control system (DCS), or another XM module.

    The DeviceNet network is an open, global, industry-standard communication network designed to provide an interface through a single cable from a programmable controller to a smart device, such as the XM-124 module. As multiple XM modules are interconnected, the DeviceNet network also serves as the communication bus and protocol that efficiently transfers data between the XM modules.

    WARNING: If you connect or disconnect the serial cable with power applied to the module or the serial device on the other end of the cable, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

    IMPORTANT If 24V Common is not referenced to earth ground, we recommend that you use an RS-232 isolator, such as Phoenix PSM-ME-RS232/RS232-P (catalog number 1440-ISO-232-24), to protect both the XM module and the computer.

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • 16 XM-124 Standard Dynamic Measurement Module

    Connect the DeviceNet cable to the terminal base unit as follows.

    DeviceNet Cable Connections

    Connect To Terminal

    Red wire DNet V+ 26 (optional)

    White wire CAN High 23

    Bare wire Shield (Chassis) 10

    Blue wire CAN Low 24

    Black wire DNet V- 27

    IMPORTANT The DeviceNet power circuit through the XM module interconnect, which is rated at only 300 mA, is not intended or designed to power DeviceNet loads. Doing so could damage the module or terminal base unit.

    IMPORTANT If the module is configured to operate in Normal mode (fully ODVA compliant), DNet V+ must be connected. Refer to the Set the Module DIP Switch section of the XM-124 Standard Dynamic Measurement Module User Manual, publication 1440-UM001.

    ATTENTION: You must ground the DeviceNet shield at only one location. Connecting the DeviceNet shield to terminal 10 grounds the DeviceNet shield at the XM module. If you intend to terminate the shield elsewhere, do not connect the shield to terminal 10.

    ATTENTION: The DeviceNet network must also be referenced to earth ground at only one location. Connect DNet V- to earth ground or chassis at one of the XM modules.

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

    http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1440-um001_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/um/1440-um001_-en-p.pdf

  • XM-124 Standard Dynamic Measurement Module 17

    DeviceNet Mode, Communication Rate, and Address

    Under the slide at the top of the module is a 10-position DIP switch that is used for setting the modules DeviceNet behavior, node address, and communication rate. The switches are numbered from left to right and are applied as shown in the illustration below and in the following table.

    DIP Switch Bank

    ATTENTION: The DNet V+ and DNet V- terminals are inputs to the XM module. Do not attempt to pass DeviceNet power through the XM terminal base unit to other non-XM equipment by connecting to these terminals. Failure to comply can result in damage to the XM terminal base unit and/or other equipment.

    IMPORTANTI

    Terminate the DeviceNet network and adhere to the requirements and instructions in the ODVA Planning and Installation Manual - DeviceNet Cable Sys-tem, which is available on the ODVA website http://www.odva.org.

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • 18 XM-124 Standard Dynamic Measurement Module

    DIP Switch Functions and Defaults

    Switch Purpose Function Out-of-boxDefault Value

    Out-of-box Switch Setting

    1 DIP switch disable

    Determines whether DIP switches 310 are enabled. When this switch is in the off position, DIP switches 310 set the modules node address and communication rate. When the switch is on, the device ignores DIP switches 310 and uses the network address and communication rate programmed in nonvolatile storage.

    Switches enabled

    Off

    2 Network mode

    Sets the DeviceNet behavior of the module to either Normal mode (ODVA compliant) or Legacy mode, which is consistent with earlier XM module versions.

    Normal (fully compliant)

    On

    3, 4 Data rate When switch 1 is off (0), the DeviceNet communication rate is set.

    125 Kbps Both off

    510 Node address

    When switch #1 is off (0), the DeviceNet node address is set.

    63 All on

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

  • XM-124 Standard Dynamic Measurement Module 19

    Additional Resources

    These documents contain additional information concerning related products from Rockwell Automation.

    You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

    Resource Description

    XM-124 Dynamic Measurement Module User Manual, publication 1400-UM001

    Provides additional details on the installation of the XM-124 as well as module configuration, operation, and technical specifications.

    Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

    Provides general guidelines for installing a Rockwell Automation industrial system.

    Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details.

    Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

    http://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1400-UM001_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://www.rockwellautomation.com/literature/http://www.ab.com

  • Rockwell Automation Support

    Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support, you can find technical manuals, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http://www.rockwellautomation.com/knowledgebase for FAQs, technical information, support chat and forums, software updates, and to sign up for product notification updates.

    For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnectSM support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.

    Installation AssistanceIf you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.

    New Product Satisfaction ReturnRockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

    Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

    United States or Canada 1.440.646.3434

    Outside United States or Canada

    Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local Rockwell Automation representative.

    United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.

    Outside United States Please contact your local Rockwell Automation representative for the return procedure.

    Publication 1440-IN001B-EN-P - October 2013 PN-218576

    Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.

    Trademarks not belonging to Rockwell Automation are property of their respective companies.

    Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400

    Supersedes 1440-IN001A-EN-P - January 2013 Copyright 2013 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

    http://www.rockwellautomation.com/supporthttp://www.rockwellautomation.com/knowledgebasehttp://www.rockwellautomation.com/support/http://www.rockwellautomation.com/rockwellautomation/distributor-locator/sales-locator.pagehttp://www.rockwellautomation.com/literature/

    XM-124 Standard Dynamic Measurement Module Installation Instructions, 1440-PC001B-EN-PImportant User InformationNorth American Hazardous Location ApprovalWiring RequirementsInstall the ModuleMount the Terminal Base UnitDIN Rail MountingWire the ModuleMount the ModuleConnect the Power SupplySerial Port ConnectionDeviceNet ConnectionDeviceNet Mode, Communication Rate, and Address

    Additional Resources

    Back Cover

    Introduction_Category Types

    This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.

    Publication Type and Print Category

    Publication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder Min **Order Max **Life Cycle Usage / Release Option

    ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / Internal

    APA3D2Application Solution or Customer Success Story5100Presale / External

    ARNANAArticle/Editorial/BylineNANAPresale / Internal

    (press releases should not be checked into DocMan or printed)

    ATB3, B4D5Application techniques5100Presale / External

    BRA2 Primary, A1NABrochures5100Presale / External

    CAC2 Primary, C1NACatalogue150Presale / External

    CGNANACatalogue Guide150Presale / External

    CLNANACollection550Presale / External

    COA5, A6, A9D5Company Confidential InformationNANANA / Confidential

    CPE-onlyE-only, D5Competitive Information550NA / Confidential

    DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal

    DIA1, A3NADirect Mail5100Presale / Internal

    DMNANAProduct Demo550Presale / Internal

    DSB3D5Dimensions Sheet15Post / External

    DUB3D5Document Update15Post / External

    GRB2D6Getting Results15Post / External

    INB3 Primary, B2D5, D6Installation instructions15Post / External

    LMNANALaunch Materials550Presale / Internal

    PCB3D5Packaging Contents

    PLE-only primary, B3E-onlyPrice List550Presale / Internal

    PMB2D6Programming Manual15Post / External

    PPA3D1Profile (Single Product or Service). NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / External

    QRB2 primary, B3, B5D5, D6Quick Reference15Post / External

    QSB2 primary, B3, B5D5, D6Quick Start15Post / External

    RMB2D5, D6Reference Manual15Post / External

    RNB3D5Release Notes15Post / External

    SGB1 Primary, B4D5, D6Selection Guide Colour550Presale / External

    SGB2D5, D6Selection Guide B/W550Presale / External

    SPA1, A2, A3, A4NASales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / Internal

    SRB2, B3D5, D6Specification Rating Sheet5100Presale / External

    TDB2 Primary B3, B4, B5D5, D6Technical Data550Presale / External

    TGB2, B3D6Troubleshooting Guide15Post / External

    UMB2 Primary, B4D6User Manual B/W15Post / External

    WDB3D5Wiring Diagrams / Dwgs15Post / Internal

    WPB3 Primary, B5D5White Paper550Presale / External

    ** Minimum order quantities on all JIT items are based on the publication length. **

    Publication lengthMinimum Order Quantity

    77 or more pages1 (no shrink wrap required)

    33 to 76 pages25

    3 to 32 pages50

    1 or 2 pages100

    Pre-sale / MarketingAll paper in this category is White Brightness, 90% or better. Opacity 90% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    A14 color170 gsm 2pp100# gloss cover, 100# gloss text

    A24 color170 gsm , folded, 4pp100# gloss cover, 80# gloss text

    A34 colorCover 170 gsm with Body 120 gsm, > 4pp80# gloss cover, 80# gloss text

    A42 color170gsm Silk 120gsm Silk80# gloss cover, 80# gloss text

    A52 color170gsm Silk 120gsm Silk80# gloss cover, 80# matt sheet text

    A61 color170gsm Silk 120gsm Silk80# gloss cover, 80# matt sheet text

    A74 color cover2 color textSelection GuideCategory being deleted10 Point Cover C2S50# matte sheet text

    A84 color coverCategory being deleted50# matte sheet text, self cover

    2 color text

    Selection Guide

    A92 color100gsm bond50# matte sheet text, self cover

    Selection Guide

    Gray shading indicates Obsolete Print Catagories

    Post Sale / Technical Communication

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S

    2 color text50# matte sheet text

    B21 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

    B31 color100gsm bond50# matte sheet text, self cover

    B42 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

    B52 color100gsm bond50# matte sheet text, self cover

    Catalogs

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S

    4 color text45# Coated Sheet

    C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S

    2 color text32#-33# Coated Sheet

    JIT / PODAll paper in this category is White Brightness, 82% or better. Opacity 88% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    D14 color170gsm white silk80# gloss cover, coated 2 sides

    D24 color120gsm white silk80# gloss text, coated 2 sides, self cover

    D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sides

    D41 color160gsm tab90# index

    D51 color80gsm bond20# bond, self cover

    D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D72 color160gsm tab90# index

    D82 color80gsm bond20# bond, self cover

    D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bond

    Gray shading indicates Obsolete Print Catagories

    Just In Time (JIT) or Off Set (OS)?

    Use these guidelines to determine if your publication should be JIT (just in time/print on demand) or if it would be more economical to print OS (offset/on a press). OS print jobs require an RFQ (Request For Quote) in US. If your job fits into the Either category, an RFQ is recommended, but not required. In the US, RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the JIT category. Guidelines differ for black & white and color printing, so be sure to check the correct tables.

    Black & White Printing

    Color Printing

    Color Printing

    Print Spec Sheet

    JIT Printing SpecificationsRA-QR005J-EN-P - 6/14/2013

    Printing SpecificationYOUR DATA HEREInstructionsNO

    (required) Publication Number:1440-IN001B-EN-PSample: 2030-SP001B-EN-P11 x 17LOOSE -Loose LeafYESPre-sale / MarketingTOP

    Use Legacy Number:YES or NO8.5 x 11PERFECT - Perfect BoundA1LEFT

    Legacy Number if applicable:Sample Legacy Number: 0160-5.338.375 x 10.875SADDLE - Saddle StitchA2RIGHTCORNER

    Publication Title:XM-124 Standard Dynamic Measurement Module Installation InstructionsSample: ElectroGuard Selling Brief80 character limit - must match DocMan Title8.25 x 11 (RA product profile std)PLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDE

    Used in Manufacturing:YESYES or NO - If Yes, must have Part No. listed below8.25 x 10.875STAPLED1 -1 positionA3

    Part Number:PN-218576If SAP Part Number, be sure to enter PN- before the number7.385 x 9 (RSI Std)STAPLED1B - bottom 1 positionA5

    (required) CategoryD6Select Print Category A,B,C or D from category list, on "Introduction_Category Types" tab6 x 4STAPLED2 - 2 positionsA6

    Paper Stock Color:whiteWhite is assumed. For color options contact your vendor5.5 x 8.5 (half-size)THERMAL - Thermal bound (Tape bound)A7

    Ink Color:blackOne color assumes BLACK / 4 color assume CMYK / Indicate PMS number here4.75 x 7.75THERMALO - Thermal Bound (Tape bound - offline)A8

    (required) Page Count ofPublication:20Total page count including cover. Enter PAGE count, not SHEET count4.75 x 7 (slightly smaller half-size)A9

    (required) Finished Trim Size Width:4.75 x 7 (slightly smaller half-size)This is sheet size, before folding4.25" x 5.50"Post Sale / Technical Communication

    Fold:NoneReview key below. Leave blank if folded for saddle stitching4 x 6B1

    Finished Fold Size:This is size after folding is completed3 x 5B2

    Binding/Stitching:STAPLED1 -1 positionReview key below9 x 12 (Folder)B3None

    Stitching Location:CORNERBlank, Corner or SideA4 (8 x 11 ) (210 x 297 mm)B4Half or V or Single Fold

    Drill Hole (Yes/No):NOAll drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of inch from the inner page border.A5 (5.83 x 8.26) (148 x 210 mm)B5C or Tri-Fold

    Number of Tabs Needed:5 tab in stock at RR Donnelley36 x 24 PosterCatalogsDbleParll

    Number of Pages per Pad:Average sheets of paper. 25, 50 75,100 Max24 x 36 PosterC1Sample

    Glue Location on Pad:Glue location on pads18 x 24 PosterC2Short (must specify dimensions between folds in Comments)

    (required) Business Group:Marketing CommercialAs entered in DocManJIT/PODZ or Accordian Fold

    (required) Cost Center:19134 - IAIf your Business Unit is Marketing Commercial, add the appropriate division name after 19134 using the chart on the right. All other Business Units: Enter only the number as in DocMan, no description. Example - 1902119134 - Commerc 19134 - OEM 19134 - Compone 19134 - Power C19134 - Global 19134 - Process 19134 - IA 19134 - Service 19134 - IMC 19134 - Safety 19134 - Industr 19134 - Softwar19134 - Mkt Dig 19134 - US MarkeD1Microfold or French Fold - designate no. of folds in Comments - intended for single sheet only to be put in box for manufacturing

    Comments:D2Double Gate

    FoldsHalf, V, Single C or Tri

    Dble Parll

    Z or Accordian Microfold or French

    Double Gate

    Short FoldSaddle-Stitch Items All page quantities must be divisible by 4.Note: Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location.80 pgs max. on 20# (text and cover)76 pgs max. on 20# (text) and 24# (cover)72 pgs max. on 24# (text and cover)

    Perfect Bound Items940 pgs max. w/cover (90# index unless indicated otherwise)70 pgs. min. for spine without words200 pgs min. for spine with words

    Plastcoil Bound Items530 pgs max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise)

    Tape Bound Items250 pgs max. on 20# no cover240 pgs max. w/cover (90# index unless indicated otherwise)D3

    D4

    D5

    D6

    D7

    D8

    D9

    MBD000B0209.bin

    MBD000B020B.bin

    MBD000B020C.bin

    MBD000B020A.bin

    MBD000B0205.bin

    MBD000B0207.bin

    MBD000B0208.bin

    MBD000B0206.bin

    MBD000B0203.bin

    MBD000B0204.bin

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth 8 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /FlateEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice


Recommended