292454-XTG-E-0109 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DM 036, 048, 060 3, 4 & 5 NOMINAL TONS 10.0 SEER (3, 4, & 5 Ton) EXPORT ONLY ® TECHNICAL GUIDE ISO 9001 Certified Quality Management System DESCRIPTION YORK Sunline 2000™ units are convertible single package air conditioners with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for light commercial and commercial applications. They can eas- ily be installed on a roof curb, slab, roof jack or frame. All units include: Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards Permanently lubricated motors Direct Drive or Belt Drive Blower with high static drive option Bottom or side air discharge configuration capability (field convertible) Manufactured under the quality standards of ISO9001 Simplicity ® Control Board Copper tube/aluminum fin coils Easy access to all components Rigging holes in base rails for lifting Fork lift slots on three sides Single point power connection Complete factory package - tested, charged and wired CSA agency listing on all units WARRANTY Factory Limited Parts Warranty One-year parts warranty A Five-year parts warranty on the compressor and electric heat elements. Ten-year parts warranty on the gas-fired heat exchangers.
Transcript
Page 1: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

SING

AND

AIR CDM 033, 4 & 5

10.0 SE

EXPOR

TEC

LE PACKAGE GAS/ELECTRIC UNITS

SINGLE PACKAGE

ONDITIONERS6, 048, 060 NOMINAL TONS

ER (3, 4, & 5 Ton)

T ONLY

� �

HNICAL GUIDE

ISO 9001Certified Quality

Management System

DESCRIPTIONYORK Sunline 2000™ units are convertible single package air conditioners with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for light commercial and commercial applications. They can eas-ily be installed on a roof curb, slab, roof jack or frame.

All units include:

• Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards

• Permanently lubricated motors

• Direct Drive or Belt Drive Blower with high static drive option

• Bottom or side air discharge configuration capability (field convertible)

• Manufactured under the quality standards of ISO9001

• Simplicity® Control Board

• Copper tube/aluminum fin coils

• Easy access to all components

• Rigging holes in base rails for lifting

• Fork lift slots on three sides

• Single point power connection

• Complete factory package - tested, charged and wired

• CSA agency listing on all units

WARRANTY

• Factory Limited Parts Warranty

• One-year parts warranty

• A Five-year parts warranty on the compressor andelectric heat elements.

• Ten-year parts warranty on the gas-fired heatexchangers.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 2: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . 2

PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . . 3

FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 6

FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . . 8

GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 32

LIST OF FIGURES

Fig. # Pg. #

1 UNIT CUTAWAY GAS/ELECTRIC . . . . . . . . . . . . . . . . . 5

2 UNIT CUTAWAY ELECTRIC/ELECTRIC . . . . . . 6

3 TYPICAL FIELD POWER & CONTROL WIRING . . . . 25

4 UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . 26

5 UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . 26

6 UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . . . . 27

7 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD. . . . . . . . . . . . . . . . . . . . . . . . . 27

8 UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . . . 28

9 DISCONNECT/BLOWER ACCESS LOCATION . . . . . 28

10 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . 29

11 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . . . . 30

12 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . . 31

LIST OF TABLES

Tbl. # Pg. #

13 SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . . . . 9

14 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . . . . . 9

15 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . 9

16 2 STAGE GAS HEAT RATINGS. . . . . . . . . . . . . . . . . . 9

17 DM036 COOLING CAPACITIES (3 TON) . . . . . . . . . . 10

18 DM048 COOLING CAPACITIES (4 TON) . . . . . . . . . . 11

19 DM060 COOLING CAPACITIES (5 TON) . . . . . . . . . . 12

20 SUPPLY AIR BLOWER PERFORMANCE (DM036 BELT DRIVE) - SIDE DUCT APPLICATION . . . . . . . . 13

Tbl. # Pg. #

21 SUPPLY AIR BLOWER PERFORMANCE (DM036 BELT DRIVE) - BOTTOM DUCT APPLICATION . . . . 13

22 SUPPLY AIR BLOWER PERFORMANCE (DM048 BELT DRIVE) - SIDE DUCT APPLICATION . . . . . . . . 13

23 SUPPLY AIR BLOWER PERFORMANCE (DM048 BELT DRIVE) - BOTTOM DUCT APPLICATION . . . . 13

24 SUPPLY AIR BLOWER PERFORMANCE (DM060 BELT DRIVE) - SIDE DUCT APPLICATION . . . . . . . . 14

25 SUPPLY AIR BLOWER PERFORMANCE (DM060 BELT DRIVE) - BOTTOM DUCT APPLICATION . . . . 14

26 SUPPLY AIR BLOWER PERFORMANCE (DM036, 048 & 060 DIRECT DRIVE) SIDE DUCT APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

27 SUPPLY AIR BLOWER PERFORMANCE (DM036, 048 & 060 DIRECT DRIVE) BOTTOM DUCT APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

28 BELT DRIVE RPM SELECTION . . . . . . . . . . . . . . . . . 15

29 BELT DRIVE BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

30 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . . 15

31 ELECTRIC HEATER CFM LIMITATIONS . . . . . . . . . . 17

32 ELECTRICAL DATA - DM036-060 DIRECT DRIVE W/O POWERED CONV. OUTLET . . . . . . . . . . . . . . . . 18

33 ELECTRICAL DATA - DM036-060 BELT DRIVE W/O POWERED CONV. OUTLET . . . . . . . . . . . . . . . . 19

34 ELECTRICAL DATA - DM036-060 BELT DRIVE HIGH STATIC W/O POWERED CONV. OUTLET . . . . 20

35 ELECTRICAL DATA - DM036-060 DIRECT DRIVE W/POWERED CONV. OUTLET . . . . . . . . . . . . . . . . . 21

36 ELECTRICAL DATA - DM036-060 BELT DRIVE W/POWERED CONV. OUTLET . . . . . . . . . . . . . . . . . 22

37 ELECTRICAL DATA - DM036-060 BELT DRIVE HIGH STATIC W/POWERED CONV. OUTLET . . . . . . 23

38 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

39 ELECTRIC HEAT CORRECTION FACTORS . . . . . . . 24

40 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . 24

41 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

42 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 28

43 DM 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

44 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . . 30

45 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . . 31

2 Johnson Controls Unitary Products

Page 3: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

PRODUCT NOMENCLATURE

D M 048 N04 A 2 A AA 1 0 1 2 4 A

D = A/C, Single Pkg., R-22

Product Category

A = Direct Drive

Airflow

B = Direct Drive/EconomizerD = Direct Drive/Motorized DamperN = Belt DriveP = Belt Drive/EconomizerR = Belt Drive/Motorized DamperT = Belt Drive High Static U = Belt Drive High Static/EconomizerV = Belt Drive High Static/Motorized Damper

1 = First Generation

Product Generation

2 = Second Generation3 = Third Generation

C00 = Cooling Only. Suitable for Field Installed Electric Heat

Heat Type and Nominal Heat Capacity

N04 = 40 MBH Output Aluminized Steel, 1 Stage (036)N06 = 60 MBH Output Aluminized Steel, 1 Stage (048)N08 = 80 MBH Output Aluminized Steel, 1 Stage

(036, 060)N10 = 100 MBH Output Aluminized Steel, 1 Stage

(048, 060)D06 = 60 MBH Output Aluminized Steel, 2 Stage

(036, 048, 060)D10 = 100 MBH Output Aluminized Steel, 2 Stage

(036*, 048, 060)S04 = 40 MBH Output Stainless Steel, 1 Stage (036)S06 = 60 MBH Output Stainless Steel, 1 Stage (048)S08 = 80 MBH Output Stainless Steel, 1 Stage

(036, 060)S10 = 100 MBH Output Stainless Steel, 1 Stage

(048, 060)T06 = 60 MBH Output Stainless Steel, 2 Stage

(036, 048, 060)T10 = 100 MBH Output Stainless Steel, 2 Stage

(036*, 048, 060)

E05 = 5 KWE07 = 7 KWE10 = 10 KWE15 = 15 KW E20 = 20 KW E30 = 30 KW

Gas Heat Options

Electric Heat Options

036 = 3.0 Ton

Nominal Cooling Capacity

048 = 4.0 Ton060 = 5.0 Ton

Product Identifier

M = 10.0 SEER A/C

Voltage

1 = 208/230-1-602 = 208/230-3-604 = 460-3-605 = 575-3-60

Product Style

A = Style A

A = No Options Installed

Installation Options

B = Option 1C = Option 2D = Options 1 & 2E = Option 3F = Option 4G = Options 1 & 3H = Options 1 & 4J = Options 1, 2 & 3K = Options 1, 2, & 4L = Options 1,3 & 4M = Options 1, 2, 3, & 4N = Options 2 & 3P = Options 2 & 4Q = Options 2, 3, & 4R = Options 3 & 4S = Option 5T = Options 1 & 5U = Options 1, 3, & 5V = Options 1, 4, & 5W = Options 1, 3, 4, & 5X = Options 3 & 5Y = Options 4 & 5Z = Options 3, 4 & 5

1 = Disconnect2 = Non-Pwr'd Conv. Outlet3 = Smoke Detector S.A.4 = Smoke Detector R.A.5 = Pwr'd Conv. Outlet

Options

SS Drain Pan

Configuration Options (not required for all units)These four digits will not be assigned until a quote is requested, or an order placed.

CPC Controller, DFS, APSJohnson Controller, DFS, APS

Honeywell Controller, DFS, APSNovar Controller, DFS, APSSimplicity IntelliComfort Controller

Simplicity IntelliComfort Controller w/ModLinc

2" Pleated filters

BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)

Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned

AA = None

Standard Cabinet

AB = Phase MonitorAC = Coil GuardAD = Dirty Filter SwitchAE = Phase Monitor & Coil GuardAF = Phase Monitor & Dirty Filter SwitchAG = Coil Guard & Dirty Filter SwitchAH = Phase Monitor, Coil Guard & Dirty Filter SwitchAS = Bottom Drain ConnectionRC = Coil Guard & American FlagTA = Technicoat Condenser CoilTJ = Technicoat Evaporator CoilTS = Technicoat Evaporator and Condenser Coil

Additional Options

Hinged Filter Door & Toolless Access Cabinet

3-5 Ton Sunline Model Number Nomenclature

BB = Phase Monitor, Hinged Filter Door & ToollessAccess Panels

BC = Coil Guard, Hinged Filter Door & ToollessAccess Panels

BD = Dirty Filter Switch, Hinged Filter Door &Toolless Access Panels

BE = Phase Monitor & Coil Guard, Hinged FilterDoor & Toolless Access Panels

BF = Phase Monitor & Dirty Filter Switch, HingedFilter Door & Toolless Access Panels

BG = Coil Guard & Dirty Filter Switch, Hinged FilterDoor & Toolless Access Panels

BH = Phase Monitor, Coil Guard & Dirty Filter Switch,Hinged Filter Door & Toolless Access Panels

BA = Hinged Filter Door & Toolless Access Panels

ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will belocated in digits 15-18.

*(D, T) 10 = 92 MBH Output on 036 Models

Johnson Controls Unitary Products 3

Page 4: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

FEATURES

All models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guard to make them suitable for almost every application.

All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for over-head rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.

All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit.

All models are available with these “factory mounted” outdoor air damper options:

• Single enthalpy economizer

• Motorized outdoor air damper

Supply air blowers are equipped with either a direct drive or a belt drive that can be adjusted to meet the exact require-ments of the job.

All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system compo-nents.

• Simplicity® Controls - Simplicity® control boards have standardized a number of features previously available only as options or by utilizing additional controls.

• Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis-tance. Optionally, the control board can be pro-grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

• Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.

• Fan Delays - Fan on and fan off delays are fully pro-grammable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.

• Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.

• Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor.

• On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

The Simplicity® control board used in this product will effectively operate the cooling system down to 0°F when this product is applied in a comfort cooling application for people. An economizer is typically included in this type of application. When applying this product for process cooling applications (com-puter rooms, switchgear, etc.), please reference applications bulletin AE-011-07 or call the applica-tions department for Unitary Products @ 1-877-UPG-SERV for guidance. Additional accessories may be needed for stable operation at temperatures below 30° F.

4 Johnson Controls Unitary Products

Page 5: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures.

All models are CSA listed.

• Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.

• Gas Heat Operation - All single phase models with gas heat have minimum annual fuel utilization efficiency (AFUE) of 80%. All three phase models with gas heat have minimum steady state efficiency of 80%. Each sec-tion includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.

The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.

• Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uni-form distribution of air across the heating elements. Every element is fully protected against excessive tem-perature by thermal limit switches.

The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.

• BAS Controls - York’s Sunline™ series units offer factory mounted BAS controls such as Simplicity® INTELLI-Comfort™, Novar, Honeywell, Johnson, and CPC.

FIGURE 1 - UNIT CUTAWAY GAS/ELECTRIC

3/4" PVC female condensate drain

Knockoutfor sidecontrol entry

GFCIconvenience outlet

Smokedetector

Slide-ineconomizer

Economizerhood

HACRbreaker

20 Gauge aluminizedsteel tubular heat exchanger

Electric heataccessory location

Power ventor motor withpost purge cycle

High efficiencycompressor

Knockout for sidegas supply entry

Simplicity® Lite™control board

Copper tube/aluminum fin

condensing coil

Full perimeter baserailswith forklift slots and

lifting holes

Knockoutfor sidepower entry

Belt drive orDirect drive

blower

Johnson Controls Unitary Products 5

Page 6: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

FIGURE 2 - UNIT CUTAWAY ELECTRIC/ELECTRIC

FACTORY-INSTALLED OPTIONS

• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

• MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2-posi-tion, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

• PHENOLIC COATED EVAPORATOR AND CON-DENSER COILS - Special coating process that utilizes Technicoat 10-1™ processes. Coating is applied by total immersion of the complete coil for maximum protection.

• ELECTRIC HEATERS - Wired for single point power supply. These nickel chromium heater elements are pro-vided with limit and automatic reset capability to prevent operation at excessive temperatures.

• FILTER OPTIONS - Standard units are shipped with 1” throw-away filters installed. 2” pleated filters are offered as a factory installed option.

• CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field.

• DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.

• BAS - Building Automation System ControlsSimplicity® INTELLI-Comfort™ CONTROL - The York® Simplicity® INTELLI-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Out-side Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Con-struction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventila-tion. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Com-fort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algo-rithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return

3/4" PVC female condensate drain

Knockoutfor sidecontrol entry

GFCIconvenience outlet

Smokedetector

Slide-ineconomizer

Economizerhood

HACRbreaker

Belt drive orDirect drive

blowerHigh efficiency

compressor

Copper tube/aluminum fin

condensing coil

Full perimeter baserailswith forklift slots and

lifting holes

Knockoutfor side

power entry

Electric Heataccessory location

Simplicity® Lite™control board

6 Johnson Controls Unitary Products

Page 7: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity® INTELLI-Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate comfort.

• Simplicity® INTELLI-Comfort™ with MOD LINK CON-TROL - The York® Simplicity® INTELLI-Comfort™ with Mod Link control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an addi-tional control to translate communications from MOD-BUS to the BACnet MSTP protocol.

• Novar® BAS CONTROL - The Novar® building auto-mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

• JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system con-troller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air prov-ing switch.

• CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto-mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.

• HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.

• SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

• STAINLESS STEEL HEAT EXCHANGER - For applica-tions in corrosive environments, this option provides a full stainless steel heat exchanger assembly.

• STAINLESS STEEL DRAIN PAN - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environ-ments.

• BOTTOM DRAIN CONNECTION - An optional bottom drain connection is available for inside the curb connec-tions for applications in cold environments to reduce freezing drain lines.

• PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of-phase condition.

• DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

• HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.

NOTE:Knobs are shipped inside the unit to prevent ship-ping damage. These must be field installed for tool-less operation.

• HIGH STATIC DRIVE OPTION - May include a belt, blower pulley, motor pulley or a motor change to enhance blower performance.

Factory installed Smoke Detectors in the return air,may be subjected to freezing temperatures during“off” times due to outside air infiltration. Thesesmoke detectors have an operational limit of 32°Fto 131°F. Smoke detectors installed in areas thatcould be outside those limitations will have to bemoved to prevent having false alarms.

Johnson Controls Unitary Products 7

Page 8: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

FIELD-INSTALLED ACCESSORIES• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-

MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

• MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2-position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

• ELECTRIC HEATERS wired for single point power sup-ply. These nickel chromium heater elements are pro-vided with limit and automatic reset capability to prevent operation at excessive temperatures.

• ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.

Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.

• HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.

• PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.

• HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at alti-tudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.

• LOW NOX KIT- Required to reduce the emission of nitrogen oxides below 40 nanograms per joule.

• POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the condi-tioned space from being over-pressurized during econo-mizer operation.

The power exhaust option can only be used on bot-tom duct configurations.

• BAROMETRIC RELIEF DAMPER - This damper acces-sory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.

• ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.

• BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.

• FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.

• CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits.

• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

• HAIL GUARD -Hail Guard Kit is available to protect coils from damage. This is a sloped hood that fits above the outdoor coil.

• GAS PIPING KIT - This kit supplies all necessary fittings and shut off valve.

8 Johnson Controls Unitary Products

Page 9: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 1: SOUND POWER RATING1

UNITSIZE CFM

ESP BLOWERSOUND POWER (db 10-12 Watts)

Octave Band Centerline Frequency (Hz)SWLdB(A)

dB(A)@

10Ft.2IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000

036 1,200 0.6 LOW 0.60 84 84 74 67 69 62 57 52 74 41

048 1,600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42

060 2,000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-tee requiring a dBA value or sound data in any other form than sound power level ratings.

2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 210/240)1

1. 80/67°F Indoor and 95°F outdoor.

MODEL MBH EER2

2. EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).

SEER3

3. SEER = Seasonal Energy Efficiency Ratio.

DM036 36.0 9.1 10.0DM048 47.4 9.0 10.0DM060 59.0 9.1 10.0

TABLE 3: GAS HEAT RATINGS1

1. All units are single-stage heating.

MODEL MBH INPUT

MBH OUTPUT

AFUE (%)

TEMP RISE ºF

DM036N04DM036N08

50100

4080

80.980.5

15 - 4545 - 75

DM048N06DM048N10

75125

60100

80.980.3

25 - 7045 - 75

DM060N08DM060N10

100125

80100

80.580.3

25 - 5535 - 75

TABLE 4: 2 STAGE GAS HEAT RATINGS

MODEL1, 2

1. Models are 3Ø only.2. All 2 Stage Gas Heat, 60% Capacity 1ST Stage, 40% Capacity 2ND Stage.

MBH INPUT MBH OUTPUT STEADY STATE EFFICIENCY RISE MINIMUM HEATINGAIRFLOW (CFM)1ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE MIN. MAX.

DM036D06 45 75 35.8 60.8 79.4 81.1 35 70 790 DM036D10 69 115 55.2 92 80.0 80.2 55 90 950 DM048D06 45 75 35.7 60.8 79.4 81.1 25 70 790 DM048D10 75 125 60.4 100.6 80.5 80.5 45 75 1230 DM060D06 45 75 35.8 60.8 79.4 81.1 20 55 1010 DM060D10 75 125 60.4 100.6 80.5 80.5 35 75 1230

Johnson Controls Unitary Products 9

Page 10: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 5: DM036 COOLING CAPACITIES (3 TON)

CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68

72 45 3.1 35 30 26 21 17 - - 43 3.3 35 30 26 21 17 - -67 43 3.0 43 38 34 29 25 20 16 41 3.3 41 38 34 29 25 21 1662 39 3.0 39 39 39 34 30 25 21 36 3.3 36 36 36 32 27 23 1857 40 2.9 40 40 40 35 31 26 22 38 3.2 38 38 38 33 29 24 2072 44 3.1 31 28 24 20 16 - - 42 3.3 31 27 23 20 16 - -67 41 3.0 39 35 31 27 23 19 16 39 3.3 37 35 31 27 23 19 1562 38 3.0 38 38 37 33 29 25 21 36 3.3 36 36 35 31 27 23 1957 39 2.9 39 39 39 35 31 27 23 37 3.2 37 37 36 32 28 25 2172 42 3.1 28 25 22 18 15 - - 41 3.3 28 24 21 18 14 - -67 40 3.0 35 32 28 25 22 18 15 38 3.2 34 31 28 25 21 18 1562 36 3.0 36 36 35 31 28 25 21 35 3.3 35 35 34 30 27 24 2057 37 2.9 37 37 37 34 31 27 24 36 3.2 36 36 35 32 28 25 2272 41 3.1 26 23 20 17 14 - - 39 3.2 26 23 20 17 14 - -67 38 3.0 32 30 27 24 21 18 15 37 3.2 32 29 26 23 20 17 1462 35 3.0 35 35 33 30 27 24 21 33 3.2 33 33 31 28 25 22 2057 36 2.9 36 36 35 32 29 26 23 34 3.2 34 34 32 30 27 24 2172 39 3.1 24 21 19 16 14 - - 38 3.2 23 21 18 16 13 - -67 37 3.0 30 27 25 22 20 17 15 36 3.2 29 26 24 21 19 16 1462 34 3.0 34 33 30 28 25 23 20 32 3.2 32 31 29 26 24 21 1957 34 2.9 34 34 33 30 27 25 22 33 3.1 33 33 30 27 25 22 20

CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68

72 41 3.7 34 29 25 20 16 - - 39 4.1 33 28 24 19 15 - -67 38 3.7 38 37 33 28 24 19 15 36 4.0 36 36 32 27 23 18 1462 34 3.7 34 34 34 30 25 21 16 32 4.0 32 32 32 27 23 18 1457 35 3.6 35 35 35 31 26 22 17 33 4.0 33 33 33 28 24 19 1572 40 3.7 30 26 23 19 15 - - 38 4.1 30 26 22 18 14 - -67 37 3.6 36 34 30 26 22 18 14 35 4.0 34 33 29 25 21 17 1362 33 3.7 33 33 33 29 25 21 17 31 4.0 31 31 31 27 23 19 1557 34 3.6 34 34 34 30 26 22 18 32 4.0 32 32 32 28 24 20 1672 39 3.7 27 24 20 17 14 - - 37 4.1 26 23 20 16 13 - -67 36 3.6 34 30 27 24 20 17 14 34 4.0 33 30 26 23 20 16 1362 32 3.6 32 32 32 29 25 22 19 30 4.0 30 30 30 27 24 20 1757 33 3.6 33 33 33 29 26 23 19 31 3.9 31 31 31 27 24 21 1772 37 3.6 25 22 19 16 13 - - 36 4.1 24 21 18 15 12 - -67 35 3.6 31 28 25 22 19 16 13 32 4.0 30 27 24 21 18 15 1262 31 3.6 31 31 29 27 24 21 18 29 4.0 29 29 28 25 22 19 1657 32 3.5 32 32 30 27 24 21 18 30 3.9 30 29 28 25 22 19 1672 36 3.6 22 20 17 15 12 - - 34 4.0 21 19 16 14 11 - -67 33 3.6 28 25 23 20 18 15 13 31 4.0 27 24 22 19 17 14 1162 30 3.6 30 29 27 24 22 19 17 28 4.0 28 28 25 22 20 17 1557 31 3.5 31 30 28 25 22 20 17 28 3.9 28 28 25 23 20 17 15

NOMINAL RATING

900

1050

85°F

POWER

INPUT2 kW

95°F

SENSIBLE CAPACITY1

ENTERING DRY BULB, °F

1750

1475

1200

SENSIBLE CAPACITY1

ENTERING DRY BULB, °F

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

1050

POWER

INPUT2 kW

ENTERING DRY BULB, °F ENTERING DRY BULB, °F

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

105°F 115°F

SENSIBLE CAPACITY1

SENSIBLE CAPACITY1

900

TOTAL

CAP.1

MBH

POWER

INPUT2 kW

TOTAL

CAP.1

MBH

TOTAL

CAP.1

MBH

POWER

INPUT2 kW

TOTAL

CAP.1

MBH

1750

1475

1200

1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.

10 Johnson Controls Unitary Products

Page 11: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 6: DM048 COOLING CAPACITIES (4 TON)

CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68

72 60 4.1 44 39 33 28 23 - - 60 4.5 44 39 33 28 23 - -67 55 4.1 53 48 42 37 32 26 21 52 4.5 52 47 42 36 31 25 2062 51 4.0 51 51 51 45 40 34 29 48 4.4 48 48 48 42 37 32 2657 49 3.9 49 49 49 44 39 33 28 47 4.3 47 47 47 42 36 31 2672 58 4.1 41 36 31 26 21 - - 57 4.5 41 36 31 26 21 - -67 53 4.1 49 45 40 35 30 25 20 50 4.5 49 44 39 34 29 24 1962 49 4.0 49 49 48 43 38 33 28 46 4.4 46 46 46 41 36 31 2657 47 3.9 47 47 47 43 38 33 28 45 4.3 45 45 45 40 36 31 2672 56 4.1 38 34 29 25 20 - - 55 4.6 38 33 29 24 20 - -67 51 4.1 46 41 37 32 28 24 19 48 4.5 45 40 36 31 27 23 1862 47 4.0 47 47 45 41 36 32 27 44 4.4 44 44 44 40 35 31 2657 46 3.9 46 46 46 41 37 32 28 44 4.4 44 44 44 39 35 30 2672 54 4.1 35 31 27 23 19 - - 53 4.5 35 31 27 23 19 - -67 49 4.1 42 38 34 30 26 22 19 47 4.5 41 38 34 30 26 22 1862 45 4.0 45 45 42 38 34 30 26 43 4.4 43 43 41 37 33 29 2557 44 3.9 44 44 43 39 35 31 27 42 4.3 42 42 41 37 33 29 2572 52 4.1 32 29 25 22 18 - - 51 4.5 32 28 25 21 18 - -67 47 4.1 39 35 32 28 25 21 18 45 4.4 38 35 31 28 24 21 1762 43 4.0 43 43 39 36 32 29 25 41 4.3 41 41 38 35 31 28 2457 42 3.9 42 42 39 36 32 29 25 41 4.3 41 41 38 34 31 27 24

CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68

72 56 5.1 42 37 31 26 21 - - 53 5.6 40 35 29 24 19 - -67 49 5.0 49 46 40 35 29 24 19 46 5.5 46 44 39 33 28 23 1762 45 4.9 45 45 45 39 34 28 23 41 5.4 41 41 41 36 30 25 2057 44 4.9 44 44 44 39 33 28 22 41 5.4 41 41 41 35 30 25 1972 55 5.0 39 34 29 24 20 - - 52 5.5 38 33 28 23 18 - -67 48 5.0 47 43 38 33 28 23 18 45 5.4 45 42 37 32 27 22 1762 43 4.9 43 43 43 38 33 28 23 40 5.4 40 40 40 35 30 26 2157 43 4.9 43 43 43 38 33 28 23 40 5.4 40 40 40 35 30 25 2072 53 5.0 36 32 28 23 19 - - 51 5.5 35 31 26 22 17 - -67 46 4.9 44 40 35 31 26 22 17 44 5.4 44 39 35 30 26 21 1762 42 4.9 42 42 42 37 33 28 24 39 5.3 39 39 39 35 30 26 2157 41 4.8 41 41 41 37 32 28 23 39 5.3 39 39 39 34 30 25 2172 51 5.0 33 29 26 22 18 - - 48 5.5 32 28 24 20 16 - -67 44 4.9 41 37 33 29 25 21 17 42 5.3 40 36 32 28 24 20 1662 40 4.8 40 40 39 35 31 27 23 37 5.3 37 37 36 32 28 24 2057 40 4.8 40 40 38 34 30 26 22 37 5.3 37 37 36 32 28 24 2072 49 4.9 30 27 23 20 16 - - 46 5.4 29 26 22 19 15 - -67 42 4.9 37 34 30 27 23 20 16 39 5.3 36 33 29 26 22 19 1562 38 4.8 38 38 36 32 29 25 22 35 5.3 35 35 33 29 26 22 1957 38 4.8 38 38 35 32 28 25 21 35 5.3 35 35 33 29 26 22 19

NOMINAL RATING

1200

1400

85°F

POWER

INPUT2 kW

95°F

SENSIBLE CAPACITY1

ENTERING DRY BULB, °F

2000

1800

1600

SENSIBLE CAPACITY1

ENTERING DRY BULB, °F

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

1400

POWER

INPUT2 kW

ENTERING DRY BULB, °F ENTERING DRY BULB, °F

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

105°F 115°F

SENSIBLE CAPACITY1

SENSIBLE CAPACITY1

1200

TOTAL

CAP.1

MBH

POWER

INPUT2 kW

TOTAL

CAP.1

MBH

TOTAL

CAP.1

MBH

POWER

INPUT2 kW

TOTAL

CAP.1

MBH

2000

1800

1600

1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.

Johnson Controls Unitary Products 11

Page 12: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

12

TABLE 7: DM060 COOLING CAPACITIES (5 TON)

CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68

72 68 4.9 50 44 38 32 25 - - 65 5.6 50 43 37 31 24 - -67 62 4.8 62 56 50 43 37 31 24 60 5.3 60 54 48 42 35 29 2362 57 4.7 57 57 57 51 44 38 32 53 5.3 53 53 53 47 41 34 2857 55 4.7 55 55 55 48 42 36 29 51 5.4 51 51 51 44 38 32 2572 67 4.9 48 42 36 30 24 - - 65 5.4 47 41 35 29 23 - -67 62 4.8 59 53 47 41 35 30 24 59 5.2 57 51 45 40 34 28 2262 56 4.7 56 56 56 50 45 39 33 53 5.2 53 53 53 47 41 35 2957 54 4.7 54 54 54 48 42 36 31 50 5.3 50 50 50 44 39 33 2772 66 4.9 45 39 34 29 23 - - 64 5.3 44 39 33 28 22 - -67 61 4.8 55 50 44 39 34 28 23 58 5.1 54 48 43 38 32 27 2262 55 4.7 55 55 55 50 45 39 34 52 5.1 52 52 52 47 42 36 3157 53 4.6 53 53 53 48 42 37 32 50 5.2 50 50 50 44 39 34 2872 63 4.8 41 36 31 27 22 - - 61 5.4 40 35 31 26 21 - -67 58 4.7 51 46 41 36 32 27 22 56 5.1 49 44 39 35 30 25 2162 53 4.6 53 53 51 47 42 37 32 50 5.2 50 50 48 43 39 34 2957 51 4.6 51 51 49 44 40 35 30 47 5.2 47 47 46 41 36 32 2772 60 4.8 37 33 29 25 21 - - 58 5.4 36 32 28 24 20 - -67 56 4.7 46 42 38 34 30 26 21 53 5.2 44 40 36 32 28 24 2062 51 4.6 51 51 47 43 39 35 31 47 5.2 47 47 44 40 36 32 2757 49 4.6 49 49 45 41 37 33 29 45 5.3 45 45 42 38 34 29 25

CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68

72 61 6.1 48 41 35 29 22 - - 57 6.7 46 39 33 27 20 - -67 55 5.9 55 52 46 39 33 27 20 50 6.6 50 50 43 37 31 24 1862 49 5.9 49 49 49 42 36 30 23 44 6.5 44 44 44 38 31 25 1957 47 5.9 47 47 47 40 34 28 21 42 6.5 42 42 42 36 30 23 1772 61 6.0 45 39 33 28 22 - - 57 6.6 43 38 32 26 20 - -67 54 5.9 53 49 44 38 32 26 20 50 6.5 50 47 42 36 30 24 1862 48 5.8 48 48 48 42 37 31 25 44 6.4 44 44 44 38 32 26 2057 46 5.8 46 46 46 40 35 29 23 42 6.4 42 42 42 36 31 25 1972 60 6.0 42 37 32 26 21 - - 57 6.6 41 36 30 25 20 - -67 54 5.8 52 47 41 36 31 25 20 50 6.5 50 45 40 34 29 24 1862 48 5.7 48 48 48 43 37 32 27 44 6.4 44 44 44 38 33 28 2257 46 5.8 46 46 46 41 35 30 25 42 6.3 42 42 42 37 32 26 2172 57 6.0 38 34 29 24 19 - - 53 6.5 37 32 27 23 18 - -67 51 5.8 47 42 38 33 28 24 19 46 6.4 45 41 36 31 26 22 1762 45 5.7 45 45 44 39 34 30 25 41 6.3 41 41 39 35 30 25 2157 43 5.8 43 43 42 37 32 28 23 39 6.3 39 39 38 33 29 24 1972 54 6.0 34 30 26 22 18 - - 49 6.5 33 28 24 20 16 - -67 48 5.8 42 38 34 30 26 22 18 43 6.4 40 36 32 28 24 20 1662 43 5.7 43 43 39 35 31 27 23 38 6.3 38 38 35 31 27 23 1957 41 5.8 41 41 38 34 30 26 21 37 6.2 37 37 34 30 26 22 18

NOMINAL RATING

1500

1750

85°F

POWER

INPUT2 kW

95°F

SENSIBLE CAPACITY1

ENTERING DRY BULB, °F

2500

2250

2000

SENSIBLE CAPACITY1

ENTERING DRY BULB, °F

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

1750

POWER

INPUT2 kW

ENTERING DRY BULB, °F ENTERING DRY BULB, °F

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

105°F 115°F

SENSIBLE CAPACITY1

SENSIBLE CAPACITY1

1500

TOTAL

CAP.1

MBH

POWER

INPUT2 kW

TOTAL

CAP.1

MBH

TOTAL

CAP.1

MBH

POWER

INPUT2 kW

TOTAL

CAP.1

MBH

2500

2250

2000

1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.

Johnson Controls Unitary Products

Page 13: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (DM036 BELT DRIVE) - SIDE DUCT APPLICATIONAir

Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard Drive Option HIgh Static Drive Option800 679 0.34 762 0.41 842 0.49 918 0.57 992 0.66 1063 0.74 1131 0.83 1197 0.93 1260 1.02 1322 1.12

1000 703 0.39 786 0.47 866 0.54 942 0.62 1016 0.71 1087 0.79 1155 0.88 1221 0.98 1284 1.07 1345 1.171200 733 0.44 817 0.52 896 0.60 973 0.68 1047 0.76 1118 0.85 1186 0.94 1252 1.03 1315 1.12 1376 1.221400 770 0.52 853 0.60 933 0.67 1010 0.76 1083 0.84 1154 0.93 1222 1.02 1288 1.11 1352 1.20 1413 1.301600 811 0.64 895 0.71 974 0.79 1051 0.87 1125 0.96 1196 1.04 1264 1.13 1330 1.23 1393 1.32 1454 1.42

Field Supplied Drive

TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (DM036 BELT DRIVE) - BOTTOM DUCT APPLICATIONAir

Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard Drive Option HIgh Static Drive Option800 662 0.35 753 0.42 840 0.50 923 0.58 1003 0.66 1081 0.75 1155 0.83 1227 0.92 1296 1.02 1362 1.11

1000 688 0.40 779 0.47 866 0.55 949 0.63 1029 0.71 1107 0.80 1181 0.88 1253 0.97 1322 1.07 1388 1.161200 722 0.45 812 0.53 899 0.60 983 0.68 1063 0.76 1140 0.85 1215 0.93 1286 1.03 1355 1.12 1422 1.211400 761 0.53 852 0.60 939 0.68 1022 0.76 1103 0.84 1180 0.92 1254 1.01 1326 1.10 1395 1.20 1462 1.291600 807 0.65 897 0.72 984 0.79 1068 0.87 1148 0.95 1225 1.04 1300 1.13 1371 1.22 1440 1.31 1507 1.40

Field Supplied Drive

TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (DM048 BELT DRIVE) - SIDE DUCT APPLICATIONAir

Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard Drive Option HIgh Static Drive Option1000 659 0.39 760 0.45 853 0.51 939 0.57 1019 0.65 1094 0.72 1165 0.80 1232 0.89 1295 0.97 1356 1.061200 685 0.47 786 0.52 879 0.58 965 0.65 1045 0.72 1120 0.80 1191 0.88 1258 0.96 1321 1.05 1382 1.131400 716 0.57 816 0.62 909 0.68 995 0.75 1076 0.82 1151 0.90 1221 0.98 1288 1.06 1352 1.15 1413 1.231600 752 0.69 852 0.75 945 0.81 1032 0.88 1112 0.95 1187 1.03 1258 1.11 1324 1.19 1388 1.27 1449 1.361800 794 0.84 895 0.90 988 0.96 1074 1.03 1155 1.10 1230 1.18 1300 1.26 1367 1.34 1430 1.42 1492 1.512000 843 1.02 943 1.07 1036 1.14 1123 1.20 1203 1.27 1278 1.35 1349 1.43 1415 1.51 1479 1.60 1540 1.69

FS4

TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (DM048 BELT DRIVE) - BOTTOM DUCT APPLICATIONAir

Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard Drive Option HIgh Static Drive Option1000 640 0.40 751 0.46 853 0.52 947 0.58 1034 0.65 1116 0.73 1192 0.80 1264 0.89 1333 0.97 1399 1.051200 669 0.48 779 0.53 881 0.59 975 0.65 1063 0.73 1144 0.80 1220 0.88 1293 0.96 1361 1.04 1427 1.131400 702 0.57 812 0.63 914 0.69 1009 0.75 1096 0.82 1177 0.90 1254 0.98 1326 1.06 1394 1.14 1460 1.221600 741 0.70 852 0.75 954 0.81 1048 0.88 1135 0.95 1217 1.02 1293 1.10 1365 1.18 1434 1.26 1500 1.351800 787 0.84 898 0.90 1000 0.96 1094 1.02 1181 1.09 1263 1.17 1339 1.25 1411 1.33 1480 1.41 1546 1.502000 840 1.01 950 1.07 1052 1.13 1146 1.19 1234 1.26 1315 1.34 1391 1.42 1463 1.50 1532 1.58 1598 1.67

Field Supplied Drive

Johnson Controls Unitary Products 13

Page 14: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (DM060 BELT DRIVE) - SIDE DUCT APPLICATIONAir

Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard Drive Option HIgh Static Drive Option1200 685 0.47 786 0.52 879 0.58 965 0.65 1045 0.72 1120 0.80 1191 0.88 1258 0.96 1321 1.05 1382 1.131400 716 0.57 816 0.62 909 0.68 995 0.75 1076 0.82 1151 0.90 1221 0.98 1288 1.06 1352 1.15 1413 1.231600 752 0.69 852 0.75 945 0.81 1032 0.88 1112 0.95 1187 1.03 1258 1.11 1324 1.19 1388 1.27 1449 1.361800 794 0.84 895 0.90 988 0.96 1074 1.03 1155 1.10 1230 1.18 1300 1.26 1367 1.34 1430 1.42 1492 1.512000 843 1.02 943 1.07 1036 1.14 1123 1.20 1203 1.27 1278 1.35 1349 1.43 1415 1.51 1479 1.60 1540 1.692200 897 1.22 998 1.27 1091 1.33 1177 1.40 1258 1.47 1333 1.55 1403 1.63 1470 1.71 1534 1.80 1595 1.882400 958 1.43 1058 1.49 1151 1.55 1237 1.62 1318 1.69 1393 1.76 1463 1.84 1530 1.93 1594 2.01 1655 2.102600 1023 1.67 1124 1.72 1217 1.78 1303 1.85 1383 1.92 1459 2.00 1529 2.08 1596 2.16 1659 2.25 1721 2.33

FS4

TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (DM060 BELT DRIVE) - BOTTOM DUCT APPLICATIONAir

Flow(CFM)

Available External Static Pressure - IWG1

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive Standard Drive Option HIgh Static Drive Option1200 669 0.48 779 0.53 881 0.59 975 0.65 1063 0.73 1144 0.80 1220 0.88 1293 0.96 1361 1.04 1427 1.131400 702 0.57 812 0.63 914 0.69 1009 0.75 1096 0.82 1177 0.90 1254 0.98 1326 1.06 1394 1.14 1460 1.221600 741 0.70 852 0.75 954 0.81 1048 0.88 1135 0.95 1217 1.02 1293 1.10 1365 1.18 1434 1.26 1500 1.351800 787 0.84 898 0.90 1000 0.96 1094 1.02 1181 1.09 1263 1.17 1339 1.25 1411 1.33 1480 1.41 1546 1.502000 840 1.01 950 1.07 1052 1.13 1146 1.19 1234 1.26 1315 1.34 1391 1.42 1463 1.50 1532 1.58 1598 1.672200 899 1.21 1009 1.26 1111 1.32 1205 1.39 1292 1.46 1374 1.53 1450 1.61 1522 1.69 1591 1.77 1657 1.862400 963 1.42 1074 1.47 1176 1.53 1270 1.60 1357 1.67 1439 1.74 1515 1.82 1587 1.90 1656 1.98 1722 2.072600 1034 1.65 1144 1.70 1246 1.76 1340 1.83 1428 1.90 1509 1.97 1586 2.05 1658 2.13 1726 2.22 1792 2.30

Field Supplied Drive

TABLE 14: SUPPLY AIR BLOWER PERFORMANCE (DM036, 048 & 060 DIRECT DRIVE) SIDE DUCT APPLICATION

UNITTONNAGE

MOTOR1

SPEED

AVAILABLE EXTERNAL STATIC PRESSURE - IWG2

0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS33

HI - - - - 1699 825 1650 785 1570 755 1430 725 1360 700 1280 680 1180 655MED 1684 800 1631 780 1582 750 1524 720 1410 690 1324 650 1260 630 1185 610 1100 590LOW 1487 710 1464 690 1421 670 1367 650 1315 620 1246 605 1185 590 1110 570 1020 545

43HI 1996 960 1933 936 1868 910 1795 880 1722 845 1635 820 1544 790 1419 765 1300 740

MED 1804 838 1765 810 1714 785 1650 765 1589 735 1508 705 1407 675 1306 645 1195 625LOW 1681 760 1640 738 1604 715 1541 695 1490 670 1416 645 1337 620 1230 595 1120 575

53HI 2400 1155 2338 1125 2274 1095 2167 1045 2096 1010 1990 980 1887 945 1771 905 1629 855

MED 2290 1105 2214 1065 2145 1030 2071 990 1990 950 1911 920 1828 885 1724 835 1604 798LOW 2150 1020 2100 990 2029 950 1965 910 1905 880 1816 838 1724 800 1644 770 1531 710

1. Factory set on medium speed tap.2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.3. Side Duct application (230/460/575 Volts)

14 Johnson Controls Unitary Products

Page 15: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than

0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (DM036, 048 & 060 DIRECT DRIVE) BOTTOM DUCT APPLICATION

UNITTONNAGE

MOTOR1

SPEED

AVAILABLE EXTERNAL STATIC PRESSURE - IWG2

0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

CFM

WAT

TS

33HI - - - - 1641 798 1593 760 1516 731 1381 702 1314 678 1237 659 1140 634

MED 1626 774 1575 755 1528 726 1472 697 1362 668 1279 630 1217 610 1145 591 1063 572LOW 1436 687 1414 668 1373 649 1321 630 1270 601 1204 586 1145 572 1073 553 986 528

43HI 1927 928 1866 905 1803 880 1733 851 1663 818 1579 793 1491 765 1371 740 1256 716

MED 1742 811 1704 784 1655 760 1593 740 1535 712 1456 683 1359 654 1262 625 1155 606LOW 1623 736 1584 714 1549 692 1488 673 1439 649 1368 625 1292 601 1189 577 1083 557

53HI 2316 1116 2256 1087 2195 1058 2092 1010 2023 977 1921 948 1822 914 1710 875 1573 827

MED 2210 1068 2137 1030 2070 996 1999 957 1921 919 1845 890 1765 856 1665 808 1549 772LOW 2075 986 2027 957 1959 919 1897 880 1839 851 1753 811 1665 774 1588 745 1479 687

1. Factory set on medium speed tap.2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.3. Side Duct application (230/460/575 Volts)

TABLE 16: BELT DRIVE RPM SELECTION

Size(Tons) HP Max

BHPMotor

SheaveBlowerSheave

5 TurnsOpen

4 TurnsOpen

3 TurnsOpen

2 TurnsOpen

1 TurnOpen

FullyClosed

036(3)

1.5 1.73 1VL44 AK64 805 865 920 980 1035 10951.5 1.73 1VP56 AK66 1115 1170 1225 1280 1335 1390

048(4)

1.5 1.73 1VL44 AK56 930 995 1060 1130 1195 12601.5 1.73 1VP56 AK61 1210 1270 1330 1390 1455 1515

060(5)

1.5 1.73 1VL44 AK56 930 995 1060 1130 1195 12602 2.3 1VP56 AK56 1325 1395 1460 1525 1590 1660

TABLE 17: BELT DRIVE BLOWER MOTOR AND DRIVE DATA

MODELSIZE

MOTOR1 Motor Sheave Blower Sheave

BeltHP RPM Eff. SF Frame

DatumDia.(in.)

Bore(in.) Model

DatumDia.(in.)

Bore(in.) Model

3 TON1-1/2 1725 0.8 1.15 56 2.8 - 3.8 7/8 1VL44 6.0 1 AK64 A37

1-1/2 1725 0.8 1.15 56 4.0 - 5.0 7/8 1VP56 6.2 1 AK66 A39

4 TON1-1/2 1725 0.8 1.15 56 2.8 - 3.8 7/8 1VL44 5.2 1 AK56 A36

1-1/2 1725 0.8 1.15 56 4.0 - 5.0 7/8 1VP56 5.7 1 AK61 A38

5 TON1-1/2 1725 0.8 1.15 56 2.8 - 3.8 7/8 1VL44 5.2 1 AK56 A36

2 1725 0.8 1.15 56 4.0 - 5.0 7/8 1VP56 5.2 1 AK56 A38

1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.

TABLE 18: STATIC RESISTANCES

DESCRIPTIONRESISTANCE, IWG

CFM1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000

ECONOMIZER1,3 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0.30

ELECTRICHEATERS1

7-15KW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.22

20-30KW 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26

COOLING ONLY2 0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.23 0.26 0.29 0.32

Johnson Controls Unitary Products 15

Page 16: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

Drive Selection

1. Determine side or bottom supply air duct application.2. Determine desired airflow.3. Calculate or measure the amount of external static pressure.4. Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table. (Linear

interpolation may be necessary.)5. Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table.6. Review the BHP compared to the motor options available. Select the appropriate motor and/or drive.7. Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the chosen motor.8. Determine turns open to obtain the desired operation point.Example1. 2200 CFM2. 1.6 iwg3. Using the supply air blower performance table below, the following data point was located: 1478 RPM & 1.82 BHP.4. Using the RPM selection table below, Size X and Model Y is found.5. 1.82 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.6. 1478 RPM is within the range of the 2 HP drive.7. Using the 2 HP motor and drive, 2.5 turns open will achieve 1478 RPM.

Example Supply Air Blower Performance

Air Flow(CFM)

Available External Static Pressure - IWG0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPField Supplied

Drive Standard Drive Option HIgh Static Drive Option

2000 907 1.00 990 1.07 1070 1.15 1146 1.23 1220 1.31 1291 1.40 1359 1.49 1425 1.58 1488 1.68 1550 1.772200 960 1.24 1043 1.31 1123 1.39 1199 1.47 1273 1.55 1344 1.64 1412 1.73 1478 1.82 1541 1.92 1602 2.012400 1015 1.51 1099 1.59 1178 1.66 1255 1.74 1329 1.83 1400 1.92 1468 2.01 1534 2.10 1597 2.19 1658 2.292600 1074 1.83 1157 1.90 1237 1.98 1314 2.06 1387 2.14 1458 2.23 - - - - - - - -

Table X: RPM Selection

Size(Tons) Model HP Max

BHPMotor

SheaveBlowerSheave

5 TurnsOpen

4 TurnsOpen

3 TurnsOpen

2 TurnsOpen

1 TurnOpen

FullyClosed

X Y1.5 1.73 1VL44 AK56 930 995 1060 1130 1195 12602 2.3 1VP56 AK56 1325 1395 1460 1525 1590 1660

16 Johnson Controls Unitary Products

Page 17: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

Altitude/Temperature Correction Factors

AirTemp.

Altitude (Ft.)0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000

40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.72950 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.71560 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.70170 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.68880 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.67690 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663

100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651

0.600

0.650

0.700

0.750

0.800

0.850

0.900

0.950

1.000

1.050

1.100

40 50 60 70 80 90 100Air Temperature (ºF)

Cor

rect

ion

Fact

or

Sea Level

1000 ft

2000 ft

3000 ft

4000 ft

6000 ft7000 ft

8000 ft9000 ft10000 ft

5000 ft

TABLE 19: ELECTRIC HEATER CFM LIMITATIONS

UNIT MODELNOMINAL TONS VOLTAGE

MINIMUM SUPPLY AIR CFMHEATER SIZE NOMINAL KW

5 7 10 15 20 30

036(3)

208/230-1-60 900 900 900 900 900 -208/230-3-60 900 900 900 900 900 -

460-3-60 - 900 900 900 900 -600-3-60 - - 900 900 900 -

048(4)

208/230-1-60 1200 1200 1200 1200 1200 -208/230-3-60 1200 1200 1200 1200 1200 -

460-3-60 - 1200 1200 1200 1200 -600-3-60 - - 1200 1200 1200 -

060(5)

208/230-1-60 1500 1500 1500 1500 1500 1500208/230-3-60 1500 1500 1500 1500 1500 1500

460-3-60 - 1500 1500 1500 1500 1500600-3-60 - - 1500 1500 1500 1500

Johnson Controls Unitary Products 17

Page 18: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 20: ELECTRICAL DATA - DM036-060 DIRECT DRIVE W/O POWERED CONV. OUTLET

Size(Tons) Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrConvOutlet

Electric Heat Option MCA1

(Amps)

1. Minimum Circuit Ampacity.

Max Fuse2/

Breaker3 Size

(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

RLA LRA MCC FLA FLA FLA Model kW Stages Amps

036(3.0)

208-3-60 8.7 72.0 13.6 1.3 4.4 0.0

None - - - 16.6 20E05 4.0 1 11.1 19.4 25E07 5.6 1 15.5 24.9 25E10 8.0 1 22.2 33.3 35E15 11.9 2 33.0 46.8 50E20 15.9 2 44.1 60.7 70

230-3-60 8.7 72.0 13.6 1.3 4.4 0.0

None - - - 16.6 20E05 5.3 1 13.3 21.4 25E07 7.5 1 18.8 28.1 30E10 10.6 1 26.6 37.4 40E15 15.9 2 39.9 53.3 60E20 21.2 2 53.2 69.2 70

460-3-60 4.9 45.0 7.7 0.8 2.2 0.0

None - - - 9.1 15E07 6.8 1 8.5 13.0 15E10 10.1 1 12.7 17.9 20E15 13.6 2 17.1 23.2 25E20 19.5 2 24.5 32.1 35

575-3-60 3.9 36.0 6.1 0.8 2.2 0.0

None - - - 7.3 15E10 10.6 1 10.6 14.9 15E15 15.9 1 16.0 21.3 25E20 21.2 2 21.3 27.7 30

048(4.0)

208-3-60 14.1 105.0 22.0 1.3 5.0 0.0

None - - - 23.9 30E05 4.0 1 11.1 23.9 30E07 5.6 1 15.5 25.7 35E10 8.0 1 22.2 34.0 35E15 11.9 2 33.0 47.5 50E20 15.9 2 44.1 61.4 70

230-3-60 14.1 105.0 22.0 1.3 5.0 0.0

None - - - 23.9 30E05 5.3 1 13.3 23.9 30E07 7.5 1 18.8 28.8 35E10 10.6 1 26.6 38.1 40E15 15.9 2 39.9 54.1 60E20 21.2 2 53.2 70.0 70

460-3-60 7.1 55.0 11.0 0.8 2.2 0.0

None - - - 11.9 15E07 6.8 1 8.5 13.0 15E10 10.1 1 12.7 17.9 20E15 13.6 2 17.1 23.2 25E20 19.5 2 24.5 32.1 35

575-3-60 5.8 44.0 9.0 0.8 2.2 0.0

None - - - 9.7 15E10 10.6 1 10.6 14.9 15E15 15.9 1 16.0 21.3 25E20 21.2 2 21.3 27.7 30

060(5.0)

208-3-60 16.0 125.0 25.0 1.3 6.6 0.0

None - - - 27.9 35E05 4.0 1 11.1 27.9 35E07 5.6 1 15.5 27.9 35E10 8.0 1 22.2 36.0 40E15 11.9 2 33.0 49.5 50E20 15.9 2 44.1 63.4 70E30 22.2 2 61.6 85.3 90

230-3-60 16.0 125.0 25.0 1.3 6.6 0.0

None - - - 27.9 35E05 5.3 1 13.3 27.9 35E07 7.5 1 18.8 30.8 40E10 10.6 1 26.6 40.1 45E15 15.9 2 39.9 56.1 60E20 21.2 2 53.2 72.0 80E30 29.6 2 74.3 97.3 100

460-3-60 8.0 66.5 12.5 0.8 3.3 0.0

None - - - 14.1 20E07 6.8 1 8.5 14.3 20E10 10.1 1 12.7 19.3 20E15 13.6 2 17.1 24.6 25E20 19.5 2 24.5 33.4 35E30 28.8 2 36.1 47.4 50

575-3-60 6.4 50.0 10.0 0.8 3.3 0.0

None - - - 11.3 15E10 10.6 1 10.6 16.0 20E15 15.9 1 16.0 22.4 25E20 21.2 2 21.3 28.8 30E30 30.4 2 30.5 39.9 40

18 Johnson Controls Unitary Products

Page 19: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 21: ELECTRICAL DATA - DM036-060 BELT DRIVE W/O POWERED CONV. OUTLET

Size(Tons) Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrConvOutlet

Electric Heat Option MCA1

(Amps)

1. Minimum Circuit Ampacity.

Max Fuse2/

Breaker3 Size

(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

RLA LRA MCC FLA FLA FLA Model kW Stages Amps

036(3.0)

208-3-60 8.7 72.0 13.6 1.3 5.2 0.0

None - - - 17.4 25E05 4.0 1 11.1 20.4 25E07 5.6 1 15.5 25.9 30E10 8.0 1 22.2 34.3 35E15 11.9 2 33.0 47.8 50E20 15.9 2 44.1 61.7 70

230-3-60 8.7 72.0 13.6 1.3 5.2 0.0

None - - - 17.4 25E05 5.3 1 13.3 22.4 25E07 7.5 1 18.8 29.1 30E10 10.6 1 26.6 38.4 40E15 15.9 2 39.9 54.3 60E20 21.2 2 53.2 70.2 80

460-3-60 4.9 45.0 7.7 0.8 2.6 0.0

None - - - 9.5 15E07 6.8 1 8.5 13.5 15E10 10.1 1 12.7 18.4 20E15 13.6 2 17.1 23.7 25E20 19.5 2 24.5 32.6 35

575-3-60 3.9 36.0 6.1 0.8 2.0 0.0

None - - - 7.5 15E10 10.6 1 10.6 15.2 20E15 15.9 1 16.0 21.6 25E20 21.2 2 21.3 28.0 30

048(4.0)

208-3-60 14.1 105.0 22.0 1.3 5.2 0.0

None - - - 24.1 35E05 4.0 1 11.1 24.1 35E07 5.6 1 15.5 25.9 35E10 8.0 1 22.2 34.3 35E15 11.9 2 33.0 47.8 50E20 15.9 2 44.1 61.7 70

230-3-60 14.1 105.0 22.0 1.3 5.2 0.0

None - - - 24.1 35E05 5.3 1 13.3 24.1 35E07 7.5 1 18.8 29.1 35E10 10.6 1 26.6 38.4 40E15 15.9 2 39.9 54.3 60E20 21.2 2 53.2 70.2 80

460-3-60 7.1 55.0 11.0 0.8 2.6 0.0

None - - - 12.3 15E07 6.8 1 8.5 13.5 15E10 10.1 1 12.7 18.4 20E15 13.6 2 17.1 23.7 25E20 19.5 2 24.5 32.6 35

575-3-60 5.8 44.0 9.0 0.8 2.0 0.0

None - - - 9.9 15E10 10.6 1 10.6 15.2 20E15 15.9 1 16.0 21.6 25E20 21.2 2 21.3 28.0 30

060(5.0)

208-3-60 16.0 125.0 25.0 1.3 5.2 0.0

None - - - 26.5 35E05 4.0 1 11.1 26.5 35E07 5.6 1 15.5 26.5 35E10 8.0 1 22.2 34.3 40E15 11.9 2 33.0 47.8 50E20 15.9 2 44.1 61.7 70E30 22.2 2 61.6 83.5 90

230-3-60 16.0 125.0 25.0 1.3 5.2 0.0

None - - - 26.5 35E05 5.3 1 13.3 26.5 35E07 7.5 1 18.8 29.1 40E10 10.6 1 26.6 38.4 40E15 15.9 2 39.9 54.3 60E20 21.2 2 53.2 70.2 80E30 29.6 2 74.3 95.5 100

460-3-60 8.0 66.5 12.5 0.8 2.6 0.0

None - - - 13.4 20E07 6.8 1 8.5 13.5 20E10 10.1 1 12.7 18.4 20E15 13.6 2 17.1 23.7 25E20 19.5 2 24.5 32.6 35E30 28.8 2 36.1 46.6 50

575-3-60 6.4 50.0 10.0 0.8 2.0 0.0

None - - - 10.6 15E10 10.6 1 10.6 15.2 20E15 15.9 1 16.0 21.6 25E20 21.2 2 21.3 28.0 30E30 30.4 2 30.5 39.1 40

Johnson Controls Unitary Products 19

Page 20: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 22: ELECTRICAL DATA - DM036-060 BELT DRIVE HIGH STATIC W/O POWERED CONV. OUTLET

Size(Tons) Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrConvOutlet

Electric Heat Option MCA1

(Amps)

1. Minimum Circuit Ampacity.

Max Fuse2/

Breaker3 Size

(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

RLA LRA MCC FLA FLA FLA Model kW Stages Amps

036(3.0)

208-3-60 8.7 72.0 13.6 1.3 5.2 0.0

None - - - 17.4 25E05 4.0 1 11.1 20.4 25E07 5.6 1 15.5 25.9 30E10 8.0 1 22.2 34.3 35E15 11.9 2 33.0 47.8 50E20 15.9 2 44.1 61.7 70

230-3-60 8.7 72.0 13.6 1.3 5.2 0.0

None - - - 17.4 25E05 5.3 1 13.3 22.4 25E07 7.5 1 18.8 29.1 30E10 10.6 1 26.6 38.4 40E15 15.9 2 39.9 54.3 60E20 21.2 2 53.2 70.2 80

460-3-60 4.9 45.0 7.7 0.8 2.6 0.0

None - - - 9.5 15E07 6.8 1 8.5 13.5 15E10 10.1 1 12.7 18.4 20E15 13.6 2 17.1 23.7 25E20 19.5 2 24.5 32.6 35

575-3-60 3.9 36.0 6.1 0.8 2.0 0.0

None - - - 7.5 15E10 10.6 1 10.6 15.2 20E15 15.9 1 16.0 21.6 25E20 21.2 2 21.3 28.0 30

048(4.0)

208-3-60 14.1 105.0 22.0 1.3 5.2 0.0

None - - - 24.1 35E05 4.0 1 11.1 24.1 35E07 5.6 1 15.5 25.9 35E10 8.0 1 22.2 34.3 35E15 11.9 2 33.0 47.8 50E20 15.9 2 44.1 61.7 70

230-3-60 14.1 105.0 22.0 1.3 5.2 0.0

None - - - 24.1 35E05 5.3 1 13.3 24.1 35E07 7.5 1 18.8 29.1 35E10 10.6 1 26.6 38.4 40E15 15.9 2 39.9 54.3 60E20 21.2 2 53.2 70.2 80

460-3-60 7.1 55.0 11.0 0.8 2.6 0.0

None - - - 12.3 15E07 6.8 1 8.5 13.5 15E10 10.1 1 12.7 18.4 20E15 13.6 2 17.1 23.7 25E20 19.5 2 24.5 32.6 35

575-3-60 5.8 44.0 9.0 0.8 2.0 0.0

None - - - 9.9 15E10 10.6 1 10.6 15.2 20E15 15.9 1 16.0 21.6 25E20 21.2 2 21.3 28.0 30

060(5.0)

208-3-60 16.0 125.0 25.0 1.3 8.2 0.0

None - - - 29.5 40E05 4.0 1 11.1 29.5 40E07 5.6 1 15.5 29.7 40E10 8.0 1 22.2 38.0 45E15 11.9 2 33.0 51.5 60E20 15.9 2 44.1 65.4 70E30 22.2 2 61.6 87.3 90

230-3-60 16.0 125.0 25.0 1.3 8.2 0.0

None - - - 29.5 40E05 5.3 1 13.3 29.5 40E07 7.5 1 18.8 32.8 45E10 10.6 1 26.6 42.1 45E15 15.9 2 39.9 58.1 60E20 21.2 2 53.2 74.0 80E30 29.6 2 74.3 99.3 100

460-3-60 8.0 66.5 12.5 0.8 4.1 0.0

None - - - 14.9 20E07 6.8 1 8.5 15.3 20E10 10.1 1 12.7 20.3 25E15 13.6 2 17.1 25.6 30E20 19.5 2 24.5 34.4 35E30 28.8 2 36.1 48.4 50

575-3-60 6.4 50.0 10.0 0.8 3.6 0.0

None - - - 12.2 15E10 10.6 1 10.6 17.2 20E15 15.9 1 16.0 23.6 25E20 21.2 2 21.3 30.0 30E30 30.4 2 30.5 41.1 45

20 Johnson Controls Unitary Products

Page 21: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 23: ELECTRICAL DATA - DM036-060 DIRECT DRIVE W/POWERED CONV. OUTLET

Size(Tons) Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrConvOutlet

Electric Heat Option MCA1

(Amps)

1. Minimum Circuit Ampacity.

Max Fuse2/

Breaker3 Size

(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

RLA LRA MCC FLA FLA FLA Model kW Stages Amps

036(3.0)

208-3-60 8.7 72.0 13.6 1.3 4.4 10.0

None - - - 26.9 35E05 4.0 1 11.1 31.9 35E07 5.6 1 15.5 37.4 40E10 8.0 1 22.2 45.8 50E15 11.9 2 33.0 59.3 60E20 15.9 2 44.1 73.2 80

230-3-60 8.7 72.0 13.6 1.3 4.4 10.0

None - - - 26.9 35E05 5.3 1 13.3 33.9 35E07 7.5 1 18.8 40.6 45E10 10.6 1 26.6 49.9 50E15 15.9 2 39.9 65.8 70E20 21.2 2 53.2 81.7 90

460-3-60 4.9 45.0 7.7 0.8 2.2 5.0

None - - - 14.2 15E07 6.8 1 8.5 19.2 20E10 10.1 1 12.7 24.2 25E15 13.6 2 17.1 29.4 30E20 19.5 2 24.5 38.3 40

575-3-60 3.9 36.0 6.1 0.8 2.2 4.0

None - - - 11.3 15E10 10.6 1 10.6 19.9 20E15 15.9 1 16.0 26.3 30E20 21.2 2 21.3 32.7 35

048(4.0)

208-3-60 14.1 105.0 22.0 1.3 5.0 10.0

None - - - 33.9 45E05 4.0 1 11.1 33.9 45E07 5.6 1 15.5 38.2 45E10 8.0 1 22.2 46.5 50E15 11.9 2 33.0 60.0 70E20 15.9 2 44.1 73.9 80

230-3-60 14.1 105.0 22.0 1.3 5.0 10.0

None - - - 33.9 45E05 5.3 1 13.3 34.7 45E07 7.5 1 18.8 41.3 45E10 10.6 1 26.6 50.6 60E15 15.9 2 39.9 66.6 70E20 21.2 2 53.2 82.5 90

460-3-60 7.1 55.0 11.0 0.8 2.2 5.0

None - - - 16.9 20E07 6.8 1 8.5 19.2 20E10 10.1 1 12.7 24.2 25E15 13.6 2 17.1 29.4 30E20 19.5 2 24.5 38.3 40

575-3-60 5.8 44.0 9.0 0.8 2.2 4.0

None - - - 13.7 15E10 10.6 1 10.6 19.9 20E15 15.9 1 16.0 26.3 30E20 21.2 2 21.3 32.7 35

060(5.0)

208-3-60 16.0 125.0 25.0 1.3 8.2 10.0

None - - - 37.9 50E05 4.0 1 11.1 37.9 50E07 5.6 1 15.5 40.2 50E10 8.0 1 22.2 48.5 50E15 11.9 2 33.0 62.0 70E20 15.9 2 44.1 75.9 80E30 22.2 2 61.6 97.8 100

230-3-60 16.0 125.0 25.0 1.3 6.6 10.0

None - - - 37.9 50E05 5.3 1 13.3 37.9 50E07 7.5 1 18.8 43.3 50E10 10.6 1 26.6 52.6 60E15 15.9 2 39.9 68.6 70E20 21.2 2 53.2 84.5 90E30 29.6 2 74.3 109.8 110

460-3-60 8.0 66.5 12.5 0.8 3.3 5.0

None - - - 19.1 25E07 6.8 1 8.5 20.6 25E10 10.1 1 12.7 25.6 30E15 13.6 2 17.1 30.8 35E20 19.5 2 24.5 39.7 40E30 28.8 2 36.1 53.7 60

575-3-60 6.4 50.0 10.0 0.8 3.3 4.0

None - - - 15.3 20E10 10.6 1 10.6 21.0 25E15 15.9 1 16.0 27.4 30E20 21.2 2 21.3 33.8 35E30 30.4 2 30.5 44.9 45

Johnson Controls Unitary Products 21

Page 22: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 24: ELECTRICAL DATA - DM036-060 BELT DRIVE W/POWERED CONV. OUTLET

Size(Tons) Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrConvOutlet

Electric Heat Option MCA1

(Amps)

1. Minimum Circuit Ampacity.

Max Fuse2/

Breaker3 Size

(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

RLA LRA MCC FLA FLA FLA Model kW Stages Amps

036(3.0)

208-3-60 8.7 72.0 13.6 1.3 5.2 10.0

None - - - 27.7 35E05 4.0 1 11.1 32.9 35E07 5.6 1 15.5 38.4 40E10 8.0 1 22.2 46.8 50E15 11.9 2 33.0 60.3 70E20 15.9 2 44.1 74.2 80

230-3-60 8.7 72.0 13.6 1.3 5.2 10.0

None - - - 27.7 35E05 5.3 1 13.3 34.9 40E07 7.5 1 18.8 41.6 45E10 10.6 1 26.6 50.9 60E15 15.9 2 39.9 66.8 70E20 21.2 2 53.2 82.7 90

460-3-60 4.9 45.0 7.7 0.8 2.6 5.0

None - - - 14.6 15E07 6.8 1 8.5 19.7 20E10 10.1 1 12.7 24.7 25E15 13.6 2 17.1 29.9 30E20 19.5 2 24.5 38.8 40

575-3-60 3.9 36.0 6.1 0.8 2.0 4.0

None - - - 11.5 15E10 10.6 1 10.6 20.2 25E15 15.9 1 16.0 26.6 30E20 21.2 2 21.3 33.0 35

048(4.0)

208-3-60 14.1 105.0 22.0 1.3 5.2 10.0

None - - - 34.1 45E05 4.0 1 11.1 34.1 45E07 5.6 1 15.5 38.4 45E10 8.0 1 22.2 46.8 50E15 11.9 2 33.0 60.3 70E20 15.9 2 44.1 74.2 80

230-3-60 14.1 105.0 22.0 1.3 5.2 10.0

None - - - 34.1 45E05 5.3 1 13.3 34.9 45E07 7.5 1 18.8 41.6 45E10 10.6 1 26.6 50.9 60E15 15.9 2 39.9 66.8 70E20 21.2 2 53.2 82.7 90

460-3-60 7.1 55.0 11.0 0.8 2.6 5.0

None - - - 17.3 20E07 6.8 1 8.5 19.7 20E10 10.1 1 12.7 24.7 25E15 13.6 2 17.1 29.9 30E20 19.5 2 24.5 38.8 40

575-3-60 5.8 44.0 9.0 0.8 2.0 4.0

None - - - 13.9 15E10 10.6 1 10.6 20.2 25E15 15.9 1 16.0 26.6 30E20 21.2 2 21.3 33.0 35

060(5.0)

208-3-60 16.0 125.0 25.0 1.3 5.2 10.0

None - - - 36.5 50E05 4.0 1 11.1 36.5 50E07 5.6 1 15.5 38.4 50E10 8.0 1 22.2 46.8 50E15 11.9 2 33.0 60.3 70E20 15.9 2 44.1 74.2 80E30 22.2 2 61.6 96.0 100

230-3-60 16.0 125.0 25.0 1.3 5.2 10.0

None - - - 36.5 50E05 5.3 1 13.3 36.5 50E07 7.5 1 18.8 41.6 50E10 10.6 1 26.6 50.9 60E15 15.9 2 39.9 66.8 70E20 21.2 2 53.2 82.7 90E30 29.6 2 74.3 108.0 110

460-3-60 8.0 66.5 12.5 0.8 2.6 5.0

None - - - 18.4 25E07 6.8 1 8.5 19.7 25E10 10.1 1 12.7 24.7 25E15 13.6 2 17.1 29.9 30E20 19.5 2 24.5 38.8 40E30 28.8 2 36.1 52.8 60

575-3-60 6.4 50.0 10.0 0.8 2.0 4.0

None - - - 14.6 20E10 10.6 1 10.6 20.2 25E15 15.9 1 16.0 26.6 30E20 21.2 2 21.3 33.0 35E30 30.4 2 30.5 44.1 45

22 Johnson Controls Unitary Products

Page 23: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 25: ELECTRICAL DATA - DM036-060 BELT DRIVE HIGH STATIC W/POWERED CONV. OUTLET

Size(Tons) Volt

Compressors(each)

OD FanMotors(each)

SupplyBlowerMotor

PwrConvOutlet

Electric Heat Option MCA1

(Amps)

1. Minimum Circuit Ampacity.

Max Fuse2/

Breaker3 Size

(Amps)

2. Dual Element, Time Delay Type.3. HACR type per NEC.

RLA LRA MCC FLA FLA FLA Model kW Stages Amps

036(3.0)

208-3-60 8.7 72.0 13.6 1.3 5.2 10.0

None - - - 27.7 35E05 4.0 1 11.1 32.9 35E07 5.6 1 15.5 38.4 40E10 8.0 1 22.2 46.8 50E15 11.9 2 33.0 60.3 70E20 15.9 2 44.1 74.2 80

230-3-60 8.7 72.0 13.6 1.3 5.2 10.0

None - - - 27.7 35E05 5.3 1 13.3 34.9 40E07 7.5 1 18.8 41.6 45E10 10.6 1 26.6 50.9 60E15 15.9 2 39.9 66.8 70E20 21.2 2 53.2 82.7 90

460-3-60 4.9 45.0 7.7 0.8 2.6 5.0

None - - - 14.6 15E07 6.8 1 8.5 19.7 20E10 10.1 1 12.7 24.7 25E15 13.6 2 17.1 29.9 30E20 19.5 2 24.5 38.8 40

575-3-60 3.9 36.0 6.1 0.8 2.0 4.0

None - - - 11.5 15E10 10.6 1 10.6 20.2 25E15 15.9 1 16.0 26.6 30E20 21.2 2 21.3 33.0 35

048(4.0)

208-3-60 14.1 105.0 22.0 1.3 5.2 10.0

None - - - 34.1 45E05 4.0 1 11.1 34.1 45E07 5.6 1 15.5 38.4 45E10 8.0 1 22.2 46.8 50E15 11.9 2 33.0 60.3 70E20 15.9 2 44.1 74.2 80

230-3-60 14.1 105.0 22.0 1.3 5.2 10.0

None - - - 34.1 45E05 5.3 1 13.3 34.9 45E07 7.5 1 18.8 41.6 45E10 10.6 1 26.6 50.9 60E15 15.9 2 39.9 66.8 70E20 21.2 2 53.2 82.7 90

460-3-60 7.1 55.0 11.0 0.8 2.6 5.0

None - - - 17.3 20E07 6.8 1 8.5 19.7 20E10 10.1 1 12.7 24.7 25E15 13.6 2 17.1 29.9 30E20 19.5 2 24.5 38.8 40

575-3-60 5.8 44.0 9.0 0.8 2.0 4.0

None - - - 13.9 15E10 10.6 1 10.6 20.2 25E15 15.9 1 16.0 26.6 30E20 21.2 2 21.3 33.0 35

060(5.0)

208-3-60 16.0 125.0 25.0 1.3 8.2 10.0

None - - - 39.5 50E05 4.0 1 11.1 39.5 50E07 5.6 1 15.5 42.2 50E10 8.0 1 22.2 50.5 60E15 11.9 2 33.0 64.0 70E20 15.9 2 44.1 77.9 80E30 22.2 2 61.6 99.8 100

230-3-60 16.0 125.0 25.0 1.3 8.2 10.0

None - - - 39.5 50E05 5.3 1 13.3 39.5 50E07 7.5 1 18.8 45.3 50E10 10.6 1 26.6 54.6 60E15 15.9 2 39.9 70.6 80E20 21.2 2 53.2 86.5 90E30 29.6 2 74.3 111.8 125

460-3-60 8.0 66.5 12.5 0.8 4.1 5.0

None - - - 19.9 25E07 6.8 1 8.5 21.6 25E10 10.1 1 12.7 26.6 30E15 13.6 2 17.1 31.8 35E20 19.5 2 24.5 40.7 45E30 28.8 2 36.1 54.7 60

575-3-60 6.4 50.0 10.0 0.8 3.6 4.0

None - - - 16.2 20E10 10.6 1 10.6 22.2 25E15 15.9 1 16.0 28.6 30E20 21.2 2 21.3 35.0 35E30 30.4 2 30.5 46.1 50

Johnson Controls Unitary Products 23

Page 24: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 26: PHYSICAL DATA

MODELS DM036 048 060

EVAPORATORBLOWER

Centrifugal Blower (Dia. x Wd. in.) 12 X 10 12 X 10 12 X 10Fan Motor HP (Direct Drive) 1/2 3/4 1Fan Motor HP (Belt Drive) 1 1/2 1 1/2 1 1/2

Fan Motor HP (Belt Drive High Static) 1 1/2 1 1/2 2

EVAPORATORCOIL

Rows Deep 3 3 3Fins Per Inch 13 13 13

Face Area (Sq. Ft.) 3.6 4.3 5.1

CONDENSERFANS

Propeller Dia. (in.) 24 24 24Fan Motor Hp 1/4 1/4 1/4

Nom. CFM 3400 3400 3400

CONDENSERCOILS

Rows Deep 1 1 1Fins Per Inch 16 16 22

Face Area (Sq. Ft.) 17.1 17.1 17.1COMPRESSOR(Qty. Per Unit) Quantity / Type 1 / Recip 1 / Scroll 1 / Scroll

AIRFILTERS

Quantity Per Unit (15” X 20” X 1” or 2“) 2 2 2Quantity Per Unit (14” X 25” X 1” or 2“) 1 1 1

Total Face Area (sq. ft.) 6.3 6.3 6.3

CHARGE Refrigerant 22(lbs./oz.) 5/8 6/8 6/8

TABLE 27: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE VOLTAGE kW CAP.MULTIPLIER

208 208 0.75240 230 0.92480 460 0.92600 575 0.92

TABLE 28: VOLTAGE LIMITATIONS1

1. Utilization Range “A” in accordance with ARI Standard 110.

POWER SUPPLY VOLTAGEMIN. MAX.

208/230-3-60 187 253460-3-60 414 506575-3-60 540 630

24 Johnson Controls Unitary Products

Page 25: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

FIGURE 3 - TYPICAL FIELD POWER & CONTROL WIRING

REFER TO THE ELECTRICAL DATATABLES TO SIZE THE DISCONNECTSWITCH, OVERCURRENT PROTEC-TION AND WIRING.

RC

RH

Y1

Y2

W1

W2

G

LED 1

LED 2

COM

A1

A2

T

T

B

R

Y1

Y2

G

C

X

OCC

W2

W1

THERMOSTAT1

TERMINALS UNIT TERMINALSTRIP TB1 24 VOLT

TRANSFORMER

TO REMOTE SENSOR2TH040702224 IF USED

NOTUSED

ADDJUMPER

ADDJUMPER

4

4

3

2

1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).

2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.

3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE ELECTRIC HEATER OR 2 STAGE GAS HEAT.

4 REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTORP6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAYOUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THETHERMOSTAT SWITCHES TO THE SET-BACK POSITION.

COOLING / HEATING (ELECTRONIC THERMOSTAT)MULTI STAGE

RH

RC

Y

W

G

R

Y1

W1

C

G

ADDJUMPER

THERMOSTAT1

TERMINALS UNIT TERMINALSTRIP TB1

24 VOLTTRANSFORMER

1ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT2TH04700224.

COOLING / HEATING (ELECTRONIC THERMOSTAT)SINGLE STAGE

RV

YC

GF

R

Y1

C

Y2

THERMOSTAT1

TERMINALSUNIT TERMINAL

STRIP TB1

24 VOLTTRANSFORMER

124 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZERON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.

G

COOLING ONLY (24 VOLT THERMOSTAT)

RC

Y

R

Y1

Y2

W1W

W2

G

C

G

RH

THERMOSTATTERMINALS

UNIT TERMINALSTRIP TB1

24 VOLTTRANSFORMER

ADDJUMPER

1

24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECONDSTAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OFHEAT, USE THERMOSTAT 2TH0471024.

1

COOLING / HEATING (24 VOLT THERMOSTAT)

TYPICAL POWER WIRING

TYPICAL CONTROL WIRING

Johnson Controls Unitary Products 25

Page 26: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

FIGURE 4 - UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW

FIGURE 5 - UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT) FRONT VIEW

26 Johnson Controls Unitary Products

Page 27: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

FIGURE 6 - UNIT WITH ECONOMIZER RAINHOOD

DETAIL “A”

FIGURE 7 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD

DETAIL “B”

Johnson Controls Unitary Products 27

Page 28: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

FIGURE 8 - UNIT DIMENSIONS (REAR VIEW)

FIGURE 9 - DISCONNECT/BLOWER ACCESS LOCA-TION

TABLE 29: UTILITIES ENTRYHOLE OPENING SIZE (DIA.) USED FOR

A 7/8” KO1 Control Wiring2Side

Bottom

B 2” KO1 Power WiringSide

BottomC 1-5/8” KO Gas Piping (Front)

D 1-1/2” KO Gas Piping (Bottom)

1. Opening in the bottom to the unit can be located by the side in the insulation.

2. Do not remove the 2” knockout ring.

Disconnect Switch Locationand Motor Access Panel forUnit with “Belt-Drive” Option

Control Box AccessA,BWiring Entry(See Detail “B”)

Mounting Bracket forDisconnect Switch(Field Supplied)

Field-Supplied DisconnectSwitch Location

Blower Motor Access

Filter Access

Dot Plugs

TABLE 30: MINIMUM CLEARANCESLOCATION CLEARANCE

Front24” (Cooling/Electric Heat)

32” (Gas Heat)

Rear12” (Less Economizer)

36” (With Economizer or Fixed Air/Motorized Damper)

Left Side (Filter Access) 24” (Less Economizer)36” (With Economizer)

Right Side (Cond. Coil) 24”

Below Unit1 0”

Above Unit272” (For

Condenser Air Discharge)

1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.

2. Units must be installed outdoors. Overhanging struc-tures or shrubs should not obstruct condenser air dis-charge outlet.

28 Johnson Controls Unitary Products

Page 29: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

FIGURE 10 - TYPICAL APPLICATIONS

Johnson Controls Unitary Products 29

Page 30: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

FIGURE 11 - FOUR AND SIX POINT LOADING

447/8821/4

Y

X

A

B

C

D

CONDENSER COILEND OF UNIT

FRONT OF UNIT

APPROXIMATECENTER OF GRAVITY

BACK OF UNIT447/8

821/4

Y

X

A

B

C

D

E

F

CONDENSER COILEND OF UNIT

FRONT OF UNIT

APPROXIMATECENTER OF GRAVITY

BACK OF UNIT

TABLE 31: DM 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION

UNIT TOTAL4-Point Loading (lb) 6-Point Loading (lb)

A B C D A B C D E FDM036 Cooling/ Electric 565 125 123 157 160 84 83 82 104 105 107DM036N04 605 134 132 168 171 90 89 88 112 113 114DM036D06 615 137 134 171 174 91 90 89 113 115 116DM036N08 625 139 136 173 177 93 92 91 115 117 118DM036D10 635 141 138 176 179 94 93 92 117 119 120DM048 Cooling/ Electric 615 137 134 171 174 91 90 89 113 115 116DM048(D,N)06 665 148 145 184 188 99 98 96 123 124 126DM048(D,N)10 685 152 149 190 194 102 100 99 126 128 129DM060 Cooling/ Electric 640 142 140 178 181 95 94 93 118 119 121DM060D06 690 153 150 191 195 102 101 100 127 129 130DM060N08 700 155 153 194 198 104 103 101 129 131 132DM060(D,N)10 710 158 155 197 201 105 104 103 131 132 134

TABLE 32: CENTER OF GRAVITYDIMENSION 3 - 5 TON

X 40-¾”

Y 19-¾”

30 Johnson Controls Unitary Products

Page 31: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

TABLE 33: OPERATING WEIGHTS (LBS.)MODEL SIZE 3 TON 4 TON 5 TON

BASICUNIT

DM (Cooling Only) 565 615 640

DM(Gas/Electric)

N04 605 - -N06 - 665 -N08 625 - 700N10 - 685 710D06 615 665 690D10 635 685 710

OPTIONS

Economizer 50Motorized Damper 26

Electric Heater5 - 7 kW 18

10 - 15 kW 2320 - 30 kW 28

ACCY.Roof Curb 92

Barometric Relief / Fixed Air Damper 10Belt-Drive Blower 5

FIGURE 12 - ROOF CURB DIMENSIONS

Johnson Controls Unitary Products 31

Page 32: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

GUIDE SPECIFICATIONSGENERAL

Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility.

York's Sunline 2000TM units are convertible single package-units. Although the units are primarily designed for curb mount-ing on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are avail-able with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to pro-vide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or hor-izontal duct connections. Models with power exhaust are suit-able for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit.

All non-Scroll compressors include crankcase heaters and all compressors have internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch.The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with a compressor lockout circuit, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTMB117 procedures. All models are CSA listed. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater ele-ments carry a 5-year warranty. Aluminized steel and Stainless steel tubular heat exchangers carry a 10-year warranty.

DESCRIPTION

Units shall be factory-assembled, single packaged, Electric Cooling/Gas Heat, Electric Cooling/Optional Electric Heat and designed for outdoor mounted installation.

The 3 thru 5 ton units shall have SEER ratings of 10.0. They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.

UNIT CABINETUnit cabinet shall be constructed of galvanized steel, with exte-rior surfaces coated with a non-chalking, powdered paint finish, certified at 1000 hours salt spray test per ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insu-lation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily removable for servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rig-ging and proper sealing on roof curb applications. Disposable 1" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1” or 2” filters. Fan performance measur-ing ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance with-out removing panels or creating air by-pass of the coils. Conden-sate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female and be a ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLYThe indoor fan shall be direct drive, multi-speed, or a factory installed belt drive assembly that includes an adjustable pitch motor pulley. Job site selected brake horsepower (B.H.P.) shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with for-ward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance.

OUTDOOR (CONDENSER) FAN ASSEMBLYThe outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to a corrosion resistant steel spider bracket and shall be dynami-cally balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bear-ings, internally protected against overload conditions and staged independently.

32 Johnson Controls Unitary Products

Page 33: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

REFRIGERANT COMPONENTSCompressor:

a. Shall be internally protected with internal high-pres-sure relief and over temperature protection.

b. Shall have internal spring isolation and sound muf-fling to minimize vibration and noise, and be exter-nally isolated on a dedicated, independent mounting.

Coils:a. Evaporator and condenser coils shall have alumi-

num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.

b. Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design.

Refrigerant Circuit and Refrigerant Safety Components shall include:

a. Independent fixed-orifice expansion devices.

b. Filter drier/strainer to eliminate any moisture or for-eign matter.

c. Accessible service gage connections on both suc-tion and liquid lines to charge, evacuate, and mea-sure refrigerant pressure during any necessary servicing or troubleshooting without losing charge.

d. The refrigeration system shall provide at least 15°F of sub-cooling at design conditions.

UNIT CONTROLS

a. Unit shall be complete with self-contained low-volt-age control circuit protected by a resetable circuit breaker on the 24-volt transformer side.

b. Unit shall incorporate a lockout circuit which pro-vides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.

c. Loss-of-charge/Low-pressure switch.

d. High-pressure switch.

e. Freeze-protection thermostat, evaporator coil.

f. If any of the above safety devices trip, a LED (light-emitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.

g. Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection.

h. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.

i. Unit control board shall have on-board diagnostics and fault code display.

j. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0°F.

k. Control board shall monitor each refrigerant safety switch independently.

l. Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss.

GAS HEATING SECTION (SINGLE OR 2 STAGE)

Shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redun-dant main gas valve. Venter wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25°F. Burners shall be of the inshot type, constructed of aluminum coated steel and con-tain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. Integrated control boards shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the fol-lowing minimum protection:

a. Primary and auxiliary high-temperature limit switches.

b. Induced draft motor speed sensor.

c. Flame roll out switch (manual reset).

d. Flame proving controls.

e. If any of the above safety devices trip, a LED (light-emitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.

NOTE: All 2 Stage Gas Heat, 60% Capacity 1ST Stage, 40% Capacity 2ND Stage.

ELECTRIC HEATING SECTION

An electric heating section, with nickel chromium elements, shall be provided in a range of 5 thru 30 KW, offering two stages of capacity - 16 KW and above on 208/230 volt heat-ers and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limit control(s) and auto-matic reset to prevent the heating element system from oper-ating at an excessive temperature. The heating section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).

Johnson Controls Unitary Products 33

Page 34: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

UNIT OPERATING CHARACTERISTICS

a. Unit shall be capable of starting and running at 125°F outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compres-sor, with standard controls, shall be capable of oper-ation down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES

• Compressor 5 Years

• Heat Exchanger 10 Years

• Electric Heat Element 5 Years

• Other Parts 1 Year

OPTIONAL OUTDOOR AIR (Shall be made available by either/or):

• ELECTRONIC ENTHALPY AUTOMATIC ECONO-MIZER- Outdoor and return air dampers that are inter-locked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti-ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi-tioned space during normal operation. During econo-mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer oper-ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out-door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil-ters shall be provided. Simultaneous economizer/com-pressor operation is also possible. Dampers shall fully close on power loss.

• MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air dampers are positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the out-door air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pres-sure differential of 0.5 IWG. A unit-mounted potentiome-ter shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to

meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE• ROOF CURB - 14"and 8” high, full perimeter curb with

wood nailer (shipped knocked-down).

• BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.

• PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required.

• HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude.

• HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit.

• LOW NOX - Required to reduce the emission of nitrogen oxides below 40 nanograms per joule.

• GAS PIPING - Contains 1/2” pipe nipples, fittings and gas cock (including panel assess gaskets) required for bottom gas supply connection with external shut off.

• POWER EXHAUST OPTION - To work in conjunction with economizers.

• ELECTRIC HEATERS• ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -

Contains all hood panels and the hardware for assem-bling.

• MANUAL OUTDOOR AIR DAMPER• COIL GUARD KIT - Guard for cooling coil.

• HAIL GUARD• FLUE EXHAUST EXTENSION

34 Johnson Controls Unitary Products

Page 35: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

292454-XTG-E-0109

OTHER FACTORY INSTALLED OPTIONS• POWER EXHAUST OPTION - To work in conjunction

with economizers.

• STAINLESS STEEL HEAT EXCHANGER• STAINLESS STEEL DRAIN PAN• BOTTOM DRAIN CONNECTION• TECHNICOAT PHENOLIC COATED CONDENSER

AND EVAPORATOR COIL• ELECTRONIC SINGLE ENTHALPY ECONOMIZER• DIRTY FILTER SWITCH• PHASE MONITOR• COIL GUARD• POWERED GFI CONVENIENCE OUTLET• NON-POWERED GFI CONVENIENCE OUTLET• BAS CONTROLS (Simplicity® INTELLI- Comfort™,

CPC, JOHNSON, HONEYWELL, NOVAR)• BAS READY ECONOMIZER (2 - 10 V. D. C.

ACTUATOR WITHOUT A CONTROLLER)• HINGED FILTER DOOR ACCESS AND TOOLESS

ACCESS PANELS• 2" PLEATED FILTERS• DISCONNECT SWITCH• SUPPLY AIR SMOKE DETECTOR• RETURN AIR SMOKE DETECTOR• HIGH STATIC DRIVE OPTION - May include a belt,

blower pulley, motor pulley or a motor change to enhance blower performance.

Johnson Controls Unitary Products 35

Page 36: Y-TG, SP G/E SPAC, Models: DM 036, 048, 060, 3, 4, & 5 Ton, 10 … · 292454-xtg-e-0109 for distribution use only - not to be used at point of retail sale single package gas/electric

Subject to change without notice. Printed in U.S.A. 292454-XTG-E-0109Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: 292454-YTG-D-0508

Johnson Controls Unitary Products5005 York Drive