+ All Categories

YCA.pdf

Date post: 29-Sep-2015
Category:
Upload: sugirin
View: 931 times
Download: 206 times
Share this document with a friend
Popular Tags:
44
YCA20 - YCA115 (A Series) (R22/R407C) 20 - 115 TON 70 - 400 kW AIR-COOLED SCROLL CHILLER FORM:YCA-A-CATL-102002 ≈HIGH PERFORMANCE SCROLL COMPRESSOR AT YOUR FINGER TIPS∆ ≈HIGH PERFORMANCE SCROLL COMPRESSOR AT YOUR FINGER TIPS∆
Transcript
  • 1YCA20 - YCA115 (A Series)(R22/R407C)20 - 115 TON70 - 400 kWAIR-COOLED SCROLL CHILLER

    FORM:YCA-A-CATL-102002

    HIGH PERFORMANCE SCROLL COMPRESSOR

    AT YOUR FINGER TIPS

    HIGH PERFORMANCE SCROLL COMPRESSOR

    AT YOUR FINGER TIPS

  • 2PAGE

    INTRODUCTION........................................................................................................................................... 3

    SPECIFICATIONS ........................................................................................................................................ 4

    MILLENNIUM CONTROL CENTER ...............................................................................................................5

    DESIGN PARAMETER ................................................................................................................................. 6

    WATER FLOW (GPM) AGAINST PRESSURE DROP (FT) .......................................................................... 6

    OPTIONS AND ACCESSORIES .................................................................................................................. 7-8

    SELECTION DATA ...................................................................................................................................... 8-10

    RATINGS DATA ......................................................................................................................................... 11-18

    PHYSICAL DATA........................................................................................................................................ 19-20

    DIMENSIONS ............................................................................................................................................ 21-32

    SPRING LOCATIONS ................................................................................................................................ 33-36

    ELECTRICAL NOTES ...................................................................................................................................37

    ELECTRICAL DATA ................................................................................................................................... 37-39

    SINGLE POINT WIRING DIAGRAM .............................................................................................................39

    APPLICATION DATA.....................................................................................................................................40

    GUIDE SPECIFICATIONS ......................................................................................................................... 40-44

    TABLE OF CONTENTS

    A GenerationYORK

    Air-Cooled

    Nominal CoolingCapacity

    Y C A 050 A

    Chiller

  • 3INTRODUCTION

    YORK Millennium Air-Cooled Scroll Chillers provide chilled water for all air conditioning

    applications using central station air handling units or terminal units. They are completely

    self-contained and are designed for outdoor (roof or ground level) installation. Each unit

    includes hermetic scroll compressors, a liquid cooler, air cooled condenser, and a weather

    proof microprocessor control center, all mounted on a formed steel base.

  • 4SPECIFICATIONS

    GENERAL

    The 20-115 Ton (70-400 kW) YCA Models are shippedcomplete from the factory ready for installation anduse.

    The unit is pressure-tested, evacuated, and fullycharged with Refrigerant-22 (HCFC-22) or optionalR-407C and includes an initial oil charge. Afterassembly, a complete operational test is performedwith water flowing through the cooler to ensure thatthe refrigeration circuit operates correctly.

    COMPRESSORS

    The chiller has suction-gas cooled, hermetic, scrollcompressors. The compressors features are no-contact scroll design utilizing floating tip seals. Highefficiency is achieved through a controlled orbit andthe use of an advanced scroll geometry. All rotatingparts are statically and dynamically balanced. A largeinternal volume and oil reservoir means greater liquidtolerance.

    COOLER

    The cooler is covered with 19mm (3/4) flexible,closed-cell, foam insulation (K=0.25).

    The water baffles are constructed of galvanized steelto resist corrosion.

    CONDENSER

    Coils -The condenser coils are seamless coppertubes arranged in staggered rows, mechanicallyexpanded into aluminum fins. Integral subcoolingis included. The testing pressure of the coil is 450PSIG(31 bar).

    Fans - The condenser fans consist of corrosionresistant aluminum hub and glass fiber reinforcedcomposite blades molded into a low noise design. Theyare designed for maximum efficiency and are staticallyand dynamically balanced for vibration free operation.They are directly driven by independent motors, andpositioned for vertical air discharge. The fan guardsare constructed of heavy-gauge, rust-resistant andoven baked polyester coating.

    Motors - The fan motors are Totally Enclosed ForceCooling, squirrel-cage type. They feature ball bearingsthat are double-sealed and permanently lubricated.

    Provisions are included for: pumpdown at shutdown;optional remote chilled water temperature reset andtwo steps of demand load limiting from an externalbuilding automation system. Unit alarm contacts arestandard.

    The operating program is stored in non-volatilememory (EPROM) to eliminate chiller failure due toAC powered failure/battery discharged. Programmedsetpoints are retained in lithium battery-backed RTCmemory for 5 years minimum.

    POWER PANEL

    Each panel contains: Compressor power terminals Compressor motor soft starters or across-the-line

    starting contactors per I.E.C. Control power terminals to accept incoming for

    115-1-50 / 60 control power Fan contactors & overload current protection

    The power wiring is routed through liquid-tight conduitto the compressors and fans.

    MILLENNIUM CONTROL CENTER

  • 5MILLENNIUM CONTROL CENTER

    All controls are contained in a weather proof cabinetwith hinged outer door and includes:

    Liquid Crystal Display with Light Emitting Diode back-lighting for outdoor viewing:-

    Two display linesTwenty characters per line

    Color coded 12-button non-tactile keypad withsections for:DISPLAY/PRINT of typical information:

    Chilled liquid temperaturesAmbient temperatureSystem pressures (each circuit)Operating hours and starts (each compressor)

    Operating data for the systemsHistory of fault shutdown data for up to the lastsix fault shutdown conditions.

    An RS-232 port, in conjunction with this pressto-print button, is provided to permit the capabilityof hard copy print-outs via a separate printer.

    ENTRY section to:ENTER setpoints or modify system values

    SETPOINTS updating can be performed to:Chilled liquid temperature setpoint and rangeRemote reset temperature rangeSet daily schedule/holiday for start/stopManual override for servicingLow and high ambient cutoutLow suction pressure cutoutHigh discharge pressure cutoutAnti-recycle timer (Compressor start cycle time)Anti-coincident timer (delay compressor starts)

    UNIT SECTION TO:Set TimeSet unit options

    UNIT ON/OFF switch

    The microprocessor control center is capable ofdisplaying the following:

    Return and leaving liquid temperature Low leaving liquid temperature cutout setting Low ambient temperature cutout setting Outdoor air temperature English or Metric data Suction pressure cutout setting Each system suction pressure Discharge pressure (optional) Liquid Temperature Reset via a YORK ISN DDC

    or Building Automation System (by others) via:- a pulse width modulated (PWM) input as standard- a 4-20 milliamp or 0-10 VDC input, or contactclosure with the optional B.A.S. interface option

    Anti-recycle timer status for each system Anti-coincident system start timer condition Compressor run status No cooling load condition Day, date and time Daily start/stop times Holiday status Automatic or manual system lead/lag control Lead system definition Compressor starts & operating hours (each

    compressor) Status of hot gas valves and fan operation Run permissive status Number of compressors running Liquid solenoid valve status Load & unload timer status Water pump status

  • 6DESIGN PARAMETER

    Notes:1 For leaving brine temp below 40F(4.4C), contact your nearest YORK office for application requirements.2 For leaving water temp higher than 50F(12.8C), contact the nearest YORK office for application guidelines.3 For operation at temp below 25F(-3.9C), the optional low ambient kit will need to be installed on the system.

    WATER FLOW (GPM) AGAINST PRESSURE DROP (FT)

    YCA Leaving water temp (F) Cooler Flow (GPM) Air on condenser (F)MIN MAX MIN MAX MIN MAX

    20 40 50 29 67 0 10525 40 50 37 84 0 10530 40 50 49 112 0 10540 40 50 61 140 0 10550 40 50 75 173 0 10560 40 50 94 217 0 10570 40 50 121 257 0 10580 40 50 124 284 0 10595 40 50 147 334 0 105115 40 50 182 419 0 105

    50.000.00

    10

    20

    30

    40

    50

    60

    70

    80

    100.00 125.00 150.00 175.00 200.00 225.00 250.00

    PRES

    SURE

    DRO

    P (FT

    )

    WATER FLOW (GPM)

    WATER FLOW (GPM) AGAINSTPRESSURE DROP (FT)

    YCA

    20

    YCA

    30

    YCA 4

    0

    YCA 2

    5

    YCA60

    YCA70

    YCA 50

    YCA 95

    YCA 115

    YCA 80

  • 7OPTIONS AND ACCESSORIES

    POWER OPTIONS:

    COMPRESSOR POWER CONNECTIONS - Seeelectrical data for specific voltage and options availability.(Factory-mounted.)

    SINGLE-POINT NON-FUSED DISCONNECTSWITCH - A disconnect switch with external, lockablehandle can be supplied by others to isolate the unitpower voltage for servicing. Separate external fusingmust be supplied, by others in the power wiring, whichmust comply with the National Electrical Code and/or local codes.

    SINGLE-POINT CIRCUIT BREAKER - A circuitbreaker with external, lockable handle can besupplied by others to isolate the power voltage forservicing.

    POWER FACTOR CORRECTION CAPACITORS -Will correct unit compressor power factors to a0.90-0.95. (Factory-mounted)

    CONTROLS OPTIONS:

    AMBIENT KIT (LOW) - Standard units will operateto 25F(4C). This accessory includes all necessarycomponents to permit chiller operation to 0F (-18C).(This option includes the Discharge PressureTransducer/Readout Capability option). For properhead pressure control in applications below 25F(-4C) where wind gusts may exceed 5 mph., it isrecommended that optional Condenser LouveredEnclosure Panels also be included. (Factory-mounted.)

    BUILDING AUTOMATION SYSTEM INTERFACE -The factory addition of a Printed Circuit Board toaccept a 4-20 milliamp, 0-10VDC or contact closureinput to reset the leaving chiller liquid temperaturefrom Building Automation System. (Only one offollowing options can be offered on a unit at a time:BAS, Remote Control Panel or Multiunit SequenceControl). (Factory-mounted)

    - The standard unit capabilities include remotestartstop, remote water temperature reset via aPWM input signal or up to two steps of demand(load) limiting depending on model.

    - The standard control panel can be directlyconnected to a YORK Building Automated Systemvia the standard on board RS485 communicationport.

    DISCHARGE PRESSURE TRANSDUCERS ANDREAD OUT CAPABILITY - The addition of pressuretransducers allows models to sense and displaydischarge pressure.This is recommended for brinechilling applications. (This option as included witheither the low or high ambient kits). (Factory-mounted)COMPRESSOR, PIPING, EVAPORATOR OPTIONS:

    LOW TEMPERATURE BRINE - For brine chillingapplications below 30F (-1C) LCWT. Standard unitswill operate down to 40F (4.4C). Option Includesresized thermal expansion valves. (Factory-mounted)

    DX COOLER 21 Bar (300 PSIG) DWP WATERSIDE- The waterside will be of 300 PSIG (21 bar) insteadof the standard 150 PSIG (10.5 bar) DWP. 300 PSIG(216mm) R.F. flanges are included on the DX coolernozzles. (Factory-mounted.) The companion flangeswill be field-supplied by others.

  • 8GUIDE TO SELECTION

    Capacity ratings for YORK YCA Packaged Air-CooledLiquid Chillers, shown on pages 11 cover the majorityof design applications for these units. For unusualapplications or uses beyond the scope of this catalog,please consult your nearest YORK Office orrepresentative.

    SELECTION RULES

    1. RATINGS - Ratings may be interpolated, but must notbe extrapolated. The Ratings given on pages 11and the DESIGN PARAMETERS given on thepage 6 indicate the limits of application for thesechillers.

    2. COOLER WATER - Ratings are based upon 2.4 GPMper ton (0.15L/S per cooling kW) which is equal toa 10F (5.6C) chilled water range and a 0.0001fouling factor for the cooler at sea level.Tables on pages 10 give capacity, and compressorkW required.

    OPTIONS AND ACCESSORIES (Continued)

    DIFFERENTIAL PRESSURE SWITCH - Alternativeto the above mentioned flow switch.

    COPPER FIN CONDENSER COILS - The unitconstructed with condenser coils which have copperfins. (This is not recommended for units in areaswhere they may be exposed to acid rain)

    GRILL (Condenser Coil Only) - Grille are mountedon the sides and ends of the condenser coils forprotection. (Factory-mounted)

    SELECTION DATA

    3. CONDENSER - Ratings are given in terms of air oncondenser in degrees Fahrenheit (Celcius)

    4. COPPER FIN CONDENSER RATINGS - Sincethe thermal conductivity of copper is slightly higherthan aluminum, apply the following corrections tothe standard ratings. Capacity x1.01 compressorkW x 0.99.

    5. PERFORMANCE DATA CORRECTIONFACTORS - Ratings are based on 0.0001cooler fouling factor, 10F (5.6C) chilled waterrange and at sea level. For operation at differentconditions, apply the appropriate correction factorfrom the following table.

    COMPRESSOR ACOUSTIC SOUND BLANKET -Each compressor is individually enclosed by anacoustic sound blanket. The sound blankets are madewith one layer of acounstical absorbent textilefiber of 5/8 (15mm) thickness; one layer ofanti-vibrating material, reinforced for temperature andUV resistance. (Factory-mounted)

  • 9SELECTION DATA (Continued)

    ALTITUDE CHILLED FOULING FACTOR

    WATER .0001 .00075 .00175

    T(F) TONS kW TONS kW TONS kW

    8 .995 .997 .967 .987 .920 .965

    SEA 10 1.000 1.000 .975 .989 .927 .968

    LEVEL 12 1.005 1.002 .981 .991 .933 .970

    14 1.010 1.004 .985 .993 .939 .973

    8 .985 1.005 .961 .993 .912 .972

    10 .989 1.007 .965 .995 .917 .975

    2000 FT 12 .995 1.009 .971 .999 .925 .977

    14 1.000 1.011 .975 1.001 .930 .981

    8 .974 1.012 .949 1.001 .903 .979

    4000 FT 10 .979 1.014 .955 1.004 .909 .983

    12 .984 1.017 .961 1.006 .914 .985

    14 .988 1.019 .962 1.008 .920 .988

    8 .963 1.020 .939 1.009 .893 .988

    6000 FT 10 .968 1.022 .945 1.011 .898 .990

    12 .972 1.024 .949 1.013 .904 .993

    14 .976 1.025 .955 1.016 .910 .995

    6. ETHYLENE GLYCOL CORRECTION FACTORS -The following factors are to be applied to thestandard ratings for units cooling ethylene glycol.

    % WT FACTORS FREEZE

    ETHYLENE POINT

    GLYCOL TONS COMPR. DELTA GPM/F/ (F)

    KW P TON

    10 .994 .997 1.03 24.1 26.6

    20 .986 .993 1.06 24.9 16

    30 .979 .990 1.09 25.9 5

    40 .970 .985 1.13 27.3 -10

    50 .959 .980 1.16 29.0 -32

    METHOD OF SELECTION

    To select of YORK Packaged Air-Cooled Liquid Chiller,the following data must be known:

    1. Design Capacity in tons cooling kW or refrigeration(TR).

    2. Entering and Leaving Liquid Temperatures.

    3. Outside ambient air temperature in degrees F (or C).

    4. L/S or GPM of chilled liquid.

    Determine capacity requirements from the followingformula:

    GPM = TR x 24RANGE (F)

    orL/S = kW (CAPACITY) x .239

    RANGE (C)

    EXAMPLE-WATER CHILLING

    1. GIVEN: Provide a capacity of 48 Tons at 44F leavingwater 10F range, 0.0001FF, 85F air on thecondenser, at sea level and 50 Hz.

    2. FIND: Unit SizeCompressor kW input

    3. From the Ratings on pages 11.

    SELECT: YCA50, R22 (English Units)49.9 Tons46.7 Compressor kW

    4. Calculate Compressor kW at 48 Tons:

    kW = 48 x 46.7kW = 44.9kW 49.9

    5. Calculate GPM :

    GPM = 48 Tons x 24 = 115.2GPM 10F Range

    6. From page 6, read 3.5ft. of water cooler pressuredrop for GPM:

    7. A YCA50SC is suitable.

    EXAMPLE -BRINE CHILLING

    1. GIVEN: Provide a capacity of 65 tons cooling 30%by weight Ethylene Glycol from 50F to 40F,0.0001FF, 95F air on the condenser, 50 Hz and4000ft. altitude.

    2. DETERMINE: Unit Size kW Input Ethylene Glycol GPM Cooler Pressure Drop

  • 10

    SELECTION DATA (Continued)

    3. See Ethylene Glycol correction factors, for 30%by weight Ethlene Glycol.

    READ: .979 Tons factor.990 Compr.kW factor25.9 Gal./F/Tons factor

    4. See performance Data Correction Factors for0.0001 fouling factor and 4000 ft. altitude.

    READ: .979 Tons factor1.014 kW factor

    5. From RATINGS on pages 12:

    SELECT: YCA70, R22 (English Units)70 Tons77.3 Compressor kW

    6. Determine YCA70, R22 brine cooling capacity andcompressor kW requirement:

    A. Tons = 70 x .979 x .979 = 67B. Compr. kW = 77.3 x .990 x 1.014 = 77.6

    7. Determine average full load Compressor kW at65 tons:

    65 tons x (77.3kW) = 74.9 Compressor kW67 tons

    8. Determine Ethylene Glycol GPM:

    GPM = Tons x Gal. F/min/Ton factorRange

    GPM = 67 x 25.910

    GPM = 173.53

    9. Determine Cooler Pressure Drop:

    A. See Ethylene Glycol correction factors for 30% by weight Ethylene Glycol.

    READ : 1.09 Pressure Drop Factor

    B. See page 6 at 173.53 GPM for YCA70, R22.READ : 17.5 Ft. H2O Pressure Drop

    C. Cooler Pressure Drop = 17.5 x 1.09 or 19.07 Ft H2O

    10.YCA70, R22 is suitable.

  • 11

    RATINGS DATA

    YCA 50Hz, R22 Performance Rating

    Air on condenser F

    Model LCWT (F) 75 80 85 90 95 100 105

    Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW

    40 18.8 16.1 18.5 16.9 18.1 17.8 17.6 18.8 17.2 19.8 16.7 20.9 16.2 22.1

    42 19.5 16.2 19.1 17.1 18.7 18.0 18.3 19.0 17.8 20.0 17.3 21.1 16.8 22.2

    44 20.2 16.4 19.8 17.2 19.4 18.2 19.0 19.1 18.5 20.1 18.0 21.2 17.4 22.4

    20 45 20.6 16.4 20.2 17.3 19.7 18.2 19.3 19.2 18.8 20.2 18.3 21.3 17.7 22.5

    46 20.9 16.5 20.5 17.4 20.1 18.3 19.6 19.3 19.1 20.3 18.6 21.4 18.1 22.6

    48 21.7 16.7 21.2 17.5 20.8 18.4 20.3 19.4 19.8 20.4 19.3 21.6 18.7 22.7

    50 22.4 16.8 22.0 17.7 21.5 18.6 21.0 19.6 20.5 20.6 20.0 21.8 19.4 22.9

    40 23.5 20.1 23.1 21.2 22.6 22.3 22.0 23.5 21.5 24.8 20.9 26.1 20.3 27.6

    42 24.4 20.3 23.9 21.3 23.4 22.5 22.8 23.7 22.3 25.0 21.7 26.3 21.0 27.8

    44 25.2 20.5 24.8 21.5 24.2 22.7 23.7 23.9 23.1 25.2 22.5 26.5 21.8 28.0

    25 45 25.7 20.6 25.2 21.6 24.7 22.8 24.1 24.0 23.5 25.3 22.9 26.6 22.2 28.1

    46 26.1 20.6 25.6 21.7 25.1 22.8 24.6 24.1 23.9 25.4 23.3 26.8 22.6 28.2

    48 27.1 20.8 26.5 21.9 26.0 23.0 25.4 24.3 24.8 25.6 24.1 27.0 23.4 28.4

    50 28.0 21.0 27.5 22.1 26.9 23.2 26.3 24.5 25.6 25.8 24.9 27.2 24.2 28.7

    40 31.4 26.9 30.8 28.2 30.1 29.8 29.4 31.4 28.7 33.1 27.9 34.9 27.1 36.8

    42 32.5 27.1 31.9 28.5 31.2 30.0 30.5 31.6 29.8 33.3 28.9 35.1 28.0 37.0

    44 33.7 27.3 33.1 28.7 32.3 30.3 31.6 31.9 30.8 33.6 30.0 35.4 29.1 37.4

    30 45 34.3 27.4 33.6 28.8 32.9 30.4 32.2 32.0 31.4 33.7 30.5 35.5 29.6 37.5

    46 34.9 27.5 34.2 29.0 33.5 30.5 32.8 32.1 31.9 33.8 31.0 35.7 30.1 37.7

    48 36.1 27.8 35.4 29.2 34.7 30.7 33.9 32.4 33.1 34.1 32.1 36.0 31.2 37.9

    50 37.4 28.0 36.6 29.5 35.9 31.0 35.0 32.6 34.2 34.4 33.3 36.3 32.3 38.2

    40 39.2 33.5 38.4 35.3 37.6 37.2 36.7 39.2 35.8 41.3 34.8 43.6 33.8 45.9

    42 40.6 33.8 39.8 35.5 39.0 37.5 38.1 39.5 37.2 41.6 36.1 43.9 35.0 46.3

    44 42.1 34.1 41.3 35.9 40.4 37.8 39.5 39.8 38.4 41.9 37.4 44.2 36.3 46.7

    40 45 42.8 34.2 42.0 36.0 41.1 37.9 40.2 39.9 39.2 42.1 38.1 44.4 37.0 46.8

    46 43.6 34.4 42.7 36.2 41.8 38.1 40.9 40.1 39.9 42.3 38.8 44.6 37.6 47.0

    48 45.1 34.7 44.2 36.5 43.3 38.4 42.3 40.4 41.3 42.6 40.1 44.9 39.0 47.4

    50 46.7 35.0 45.7 36.8 44.8 38.7 43.7 40.8 42.7 43.0 41.5 45.3 40.3 47.8

    40 48.5 41.5 47.5 43.6 46.5 45.9 45.4 48.4 44.3 51.1 43.1 53.9 41.8 56.8

    42 50.3 41.8 49.2 43.9 48.2 46.3 47.1 48.8 45.9 51.5 44.7 54.3 43.3 57.2

    44 52.0 42.2 51.1 44.3 49.9 46.7 48.8 49.2 47.5 51.9 46.3 54.6 44.9 57.7

    50 45 53.0 42.3 51.9 44.5 50.8 46.9 49.7 49.4 48.4 52.1 47.1 54.9 45.7 57.9

    46 53.9 42.5 52.8 44.7 51.7 47.1 50.6 49.6 49.3 52.3 47.9 55.1 46.5 58.2

    48 55.8 42.9 54.6 45.1 53.5 47.5 52.3 50.0 51.1 52.7 49.6 55.5 48.2 58.6

    50 57.7 43.3 56.6 45.5 55.4 47.9 54.1 50.4 52.8 53.1 51.4 56.0 49.9 59.0

    Notes :1. kW = compressor input power2. LCWT = leaving chilled water temperature3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

  • 12

    RATINGS DATA

    YCA 50Hz, R22 Performance Rating

    Air on condenser F

    Model LCWT (F) 75 80 85 90 95 100 105

    Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW

    40 60.7 51.9 59.5 54.6 58.2 57.5 56.8 60.6 55.4 63.9 53.9 67.4 52.3 71.1

    42 62.9 52.3 61.6 55.0 60.3 58.0 58.9 61.1 57.5 64.4 55.9 67.9 54.2 71.6

    44 65.1 52.8 63.9 55.5 62.5 58.5 61.1 61.6 59.5 64.9 57.9 68.4 56.2 72.2

    60 45 66.3 53.0 65.0 55.7 63.6 58.7 62.2 61.8 60.6 65.2 59.0 68.7 57.2 72.5

    46 67.4 53.2 66.1 56.0 64.7 58.9 63.3 62.1 61.7 65.4 60.0 69.0 58.2 72.8

    48 69.8 53.7 68.4 56.5 67.0 59.4 65.5 62.6 63.9 65.9 62.1 69.5 60.3 73.3

    50 72.2 54.2 70.8 57.0 69.3 59.9 67.7 63.1 66.1 66.5 64.3 70.1 62.4 73.9

    40 71.8 61.0 70.3 64.5 68.5 68.2 66.8 72.1 65.1 76.3 63.3 80.7 61.3 85.4

    42 74.4 61.4 72.8 65.0 71.2 68.6 69.4 72.6 67.5 76.8 65.6 81.2 63.7 85.9

    44 77.2 62.0 75.4 65.4 73.7 69.2 71.9 73.1 70.0 77.3 68.0 81.6 66.0 86.4

    70 45 78.5 62.2 76.9 65.6 75.0 69.4 73.2 73.3 71.3 77.6 69.3 81.9 67.2 86.6

    46 79.9 62.4 78.2 65.9 76.4 69.6 74.5 73.5 72.5 77.8 70.6 82.1 68.4 86.9

    48 82.7 62.9 80.9 66.3 79.1 70.1 77.2 74.0 75.1 78.3 73.1 82.6 70.9 87.4

    50 85.6 63.3 83.8 66.8 81.8 70.6 79.8 74.5 77.8 78.8 75.6 83.2 73.4 87.9

    40 79.7 68.2 78.1 71.7 76.4 75.5 74.6 79.6 72.8 83.9 70.8 88.5 68.7 93.4

    42 82.6 68.7 80.9 72.2 79.2 76.2 77.4 80.2 75.5 84.6 73.4 89.2 71.2 94.0

    44 85.5 69.3 83.9 72.9 82.1 76.8 80.2 80.9 78.1 85.2 76.0 89.8 73.8 94.8

    80 45 87.1 69.6 85.4 73.2 83.5 77.1 81.7 81.2 79.6 85.6 77.5 90.2 75.1 95.2

    46 88.5 69.9 86.8 73.6 85.0 77.4 83.1 81.6 81.0 85.9 78.8 90.6 76.4 95.6

    48 91.7 70.5 89.8 74.2 88.0 78.0 86.0 82.2 83.9 86.6 81.6 91.3 79.2 96.3

    50 94.8 71.2 93.0 74.9 91.0 78.7 88.9 82.9 86.8 87.3 84.5 92.1 82.0 97.1

    40 95.0 81.2 93.1 85.5 91.1 90.0 88.9 94.9 86.7 100.0 84.4 105.5 81.9 111.3

    42 98.5 81.9 96.4 86.1 94.4 90.8 92.2 95.6 90.0 100.8 87.5 106.3 84.8 112.1

    44 101.9 82.7 100.0 86.9 97.8 91.6 95.6 96.4 93.1 101.6 90.6 107.1 88.0 113.0

    95 45 103.8 83.0 101.7 87.2 99.6 91.9 97.4 96.7 94.9 102.1 92.4 107.5 89.5 113.5

    46 105.5 83.3 103.5 87.7 101.3 92.2 99.1 97.2 96.6 102.4 93.9 108.0 91.1 114.0

    48 109.3 84.1 107.1 88.4 104.9 93.0 102.5 98.0 100.0 103.2 97.2 108.8 94.4 114.7

    50 113.0 84.8 110.8 89.2 108.5 93.8 106.0 98.8 103.5 104.1 100.7 109.7 97.7 115.7

    40 117.2 100.2 114.9 105.5 112.4 111.1 109.7 117.0 107.0 123.4 104.1 130.2 101.0 137.3

    42 121.5 101.0 119.0 106.2 116.5 112.0 113.8 118.0 111.1 124.4 108.0 131.1 104.7 138.3

    44 125.7 102.0 123.4 107.2 120.7 113.0 118.0 119.0 114.9 125.4 111.8 132.1 108.5 139.5

    115 45 128.1 102.4 125.5 107.6 122.8 113.4 120.1 119.4 117.0 125.9 114.0 132.7 110.5 140.0

    46 130.2 102.8 127.7 108.2 125.0 113.8 122.3 119.9 119.2 126.3 115.9 133.3 112.4 140.6

    48 134.8 103.7 132.1 109.1 129.4 114.7 126.5 120.9 123.4 127.3 119.9 134.2 116.5 141.6

    50 139.5 104.7 136.7 110.1 133.9 115.7 130.8 121.9 127.7 128.4 124.2 135.4 120.5 142.7

    Notes :1. kW = compressor input power2. LCWT = leaving chilled water temperature3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

  • 13

    RATINGS DATAYCA 60Hz, R22 Performance Rating

    Air on condenser F

    Model LCWT (F) 75 80 85 90 95 100 105

    Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW

    40 18.6 15.9 18.3 16.8 17.9 17.7 17.4 18.6 17.0 19.6 16.6 20.7 16.1 21.8

    42 19.3 16.1 18.9 16.9 18.5 17.8 18.1 18.8 17.7 19.8 17.2 20.9 16.6 22.0

    44 20.0 16.2 19.6 17.0 19.2 18.0 18.8 18.9 18.3 19.9 17.8 21.0 17.3 22.2

    20 45 20.4 16.3 20.0 17.1 19.5 18.0 19.1 19.0 18.6 20.0 18.1 21.1 17.6 22.3

    46 20.7 16.3 20.3 17.2 19.9 18.1 19.4 19.1 19.0 20.1 18.4 21.2 17.9 22.4

    48 21.4 16.5 21.0 17.4 20.6 18.2 20.1 19.2 19.6 20.2 19.1 21.3 18.5 22.5

    50 22.2 16.6 21.7 17.5 21.3 18.4 20.8 19.4 20.3 20.4 19.8 21.5 19.2 22.7

    40 24.0 20.5 23.5 21.6 23.0 22.7 22.5 24.0 21.9 25.3 21.3 26.7 20.7 28.1

    42 24.9 20.7 24.4 21.8 23.8 22.9 23.3 24.2 22.7 25.5 22.1 26.9 21.4 28.3

    44 25.7 20.9 25.3 21.9 24.7 23.1 24.2 24.4 23.5 25.7 22.9 27.1 22.2 28.6

    25 45 26.2 21.0 25.7 22.0 25.2 23.2 24.6 24.4 24.0 25.8 23.3 27.2 22.6 28.7

    46 26.7 21.0 26.1 22.1 25.6 23.3 25.0 24.6 24.4 25.9 23.7 27.3 23.0 28.8

    48 27.6 21.2 27.1 22.3 26.5 23.5 25.9 24.8 25.3 26.1 24.6 27.5 23.8 29.0

    50 28.6 21.4 28.0 22.5 27.4 23.7 26.8 25.0 26.1 26.3 25.4 27.7 24.7 29.2

    40 29.2 25.0 28.6 26.3 28.0 27.7 27.3 29.2 26.7 30.7 25.9 32.4 25.2 34.2

    42 30.3 25.2 29.6 26.5 29.0 27.9 28.3 29.4 27.7 31.0 26.9 32.7 26.1 34.5

    44 31.3 25.4 30.7 26.7 30.1 28.1 29.4 29.6 28.6 31.2 27.9 32.9 27.0 34.7

    30 45 31.9 25.5 31.3 26.8 30.6 28.2 29.9 29.7 29.2 31.4 28.4 33.1 27.5 34.9

    46 32.4 25.6 31.8 26.9 31.1 28.3 30.5 29.9 29.7 31.5 28.9 33.2 28.0 35.0

    48 33.6 25.8 32.9 27.2 32.2 28.6 31.5 30.1 30.7 31.7 29.9 33.4 29.0 35.3

    50 34.7 26.1 34.1 27.4 33.3 28.8 32.6 30.4 31.8 32.0 30.9 33.7 30.0 35.6

    40 38.4 32.9 37.7 34.6 36.9 36.4 36.0 38.4 35.1 40.5 34.1 42.7 33.1 45.0

    42 39.8 33.1 39.0 34.8 38.2 36.7 37.3 38.7 36.4 40.8 35.4 43.0 34.3 45.3

    44 41.2 33.4 40.5 35.1 39.6 37.0 38.7 39.0 37.7 41.1 36.7 43.3 35.6 45.7

    40 45 42.0 33.6 41.2 35.3 40.3 37.2 39.4 39.1 38.4 41.3 37.4 43.5 36.2 45.9

    46 42.7 33.7 41.9 35.5 41.0 37.3 40.1 39.3 39.1 41.4 38.0 43.7 36.9 46.1

    48 44.2 34.0 43.3 35.8 42.4 37.6 41.5 39.6 40.5 41.7 39.3 44.0 38.2 46.4

    50 45.7 34.3 44.8 36.1 43.9 37.9 42.9 40.0 41.9 42.1 40.7 44.4 39.5 46.8

    40 48.5 41.5 47.5 43.6 46.5 45.9 45.4 48.4 44.2 51.0 43.0 53.8 41.8 56.8

    42 50.2 41.8 49.2 43.9 48.2 46.3 47.0 48.8 45.9 51.4 44.6 54.2 43.3 57.2

    44 52.0 42.2 51.0 44.3 49.9 46.7 48.8 49.2 47.5 51.8 46.2 54.6 44.9 57.7

    50 45 53.0 42.3 51.9 44.5 50.8 46.9 49.7 49.4 48.4 52.1 47.1 54.9 45.7 57.9

    46 53.8 42.5 52.8 44.7 51.7 47.0 50.6 49.6 49.3 52.2 47.9 55.1 46.5 58.1

    48 55.7 42.9 54.6 45.1 53.5 47.4 52.3 50.0 51.0 52.6 49.6 55.5 48.2 58.5

    50 57.7 43.3 56.5 45.5 55.3 47.8 54.1 50.4 52.8 53.1 51.4 56.0 49.8 59.0

    Notes :1. kW = compressor input power2. LCWT = leaving chilled water temperature3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

  • 14

    RATINGS DATAYCA 60Hz, R22 Performance Rating

    Air on condenser F

    Model LCWT (F) 75 80 85 90 95 100 105

    Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW

    40 59.3 50.68 58.1 53.32 56.8 56.1 55.5 59.2 54.1 62.4 52.6 65.8 51.1 69.4

    42 61.4 51.07 60.15 53.71 58.9 56.6 57.5 59.7 56.1 62.9 54.6 66.3 52.9 69.9

    44 63.6 51.56 62.4 54.2 61.0 57.1 59.7 60.2 58.1 63.4 56.5 66.8 54.9 70.5

    60 45 64.7 51.75 63.47 54.39 62.1 57.3 60.7 60.3 59.2 63.7 57.6 67.1 55.9 70.8

    46 65.8 51.95 64.55 54.68 63.2 57.5 61.8 60.6 60.3 63.9 58.6 67.4 56.8 71.1

    48 68.2 52.44 66.79 55.17 65.4 58.0 64.0 61.1 62.4 64.4 60.6 67.9 58.9 71.6

    50 70.5 52.93 69.14 55.66 67.7 58.5 66.1 61.6 64.5 64.9 62.8 68.5 60.9 72.2

    40 70.8 60.2 69.3 63.6 67.6 67.3 65.9 71.1 64.2 75.2 62.4 79.6 60.5 84.2

    42 73.4 60.6 71.8 64.1 70.2 67.7 68.4 71.6 66.6 75.7 64.7 80.1 62.8 84.7

    44 76.1 61.1 74.4 64.5 72.7 68.2 70.9 72.1 69.0 76.2 67.1 80.5 65.1 85.2

    70 45 77.4 61.3 75.8 64.7 74.0 68.4 72.2 72.3 70.3 76.5 68.3 80.8 66.3 85.4

    46 78.8 61.5 77.1 65.0 75.3 68.6 73.5 72.5 71.5 76.7 69.6 81.0 67.5 85.7

    48 81.6 62.0 79.8 65.4 78.0 69.1 76.1 73.0 74.1 77.2 72.1 81.5 69.9 86.2

    50 84.4 62.4 82.6 65.9 80.7 69.6 78.7 73.5 76.7 77.7 74.6 82.1 72.4 86.7

    40 78.7 67.3 77.2 70.8 75.5 74.6 73.7 78.6 71.9 82.9 69.9 87.4 67.8 92.2

    42 81.6 67.8 79.9 71.3 78.2 75.2 76.4 79.3 74.6 83.5 72.5 88.1 70.3 92.9

    44 84.5 68.5 82.9 72.0 81.1 75.9 79.3 79.9 77.2 84.2 75.1 88.7 72.9 93.7

    80 45 86.0 68.8 84.3 72.3 82.5 76.1 80.7 80.2 78.6 84.6 76.5 89.1 74.2 94.1

    46 87.4 69.0 85.7 72.6 83.9 76.4 82.1 80.6 80.0 84.8 77.8 89.5 75.5 94.4

    48 90.5 69.7 88.7 73.3 86.9 77.1 85.0 81.2 82.9 85.5 80.6 90.2 78.2 95.1

    50 93.7 70.3 91.8 73.9 89.9 77.7 87.8 81.9 85.7 86.3 83.4 90.9 80.9 95.9

    40 91.0 77.8 89.2 81.8 87.2 86.2 85.1 90.8 83.0 95.8 80.8 101.0 78.4 106.6

    42 94.3 78.4 92.3 82.4 90.4 86.9 88.3 91.6 86.2 96.5 83.8 101.8 81.2 107.3

    44 97.6 79.1 95.8 83.2 93.7 87.7 91.6 92.3 89.2 97.3 86.8 102.5 84.2 108.2

    95 45 99.4 79.4 97.4 83.5 95.3 88.0 93.2 92.6 90.8 97.7 88.4 103.0 85.7 108.7

    46 101.0 79.7 99.1 83.9 97.0 88.3 94.9 93.1 92.5 98.0 89.9 103.4 87.2 109.1

    48 104.6 80.5 102.5 84.7 100.4 89.0 98.2 93.8 95.8 98.8 93.1 104.2 90.4 109.9

    50 108.2 81.2 106.1 85.4 103.9 89.8 101.5 94.6 99.1 99.7 96.4 105.1 93.5 110.8

    40 115.8 99.0 113.5 104.2 111.0 109.7 108.4 115.6 105.7 121.9 102.8 128.6 99.8 135.7

    42 120.0 99.8 117.5 104.9 115.1 110.7 112.4 116.6 109.7 122.9 106.7 129.6 103.4 136.6

    44 124.2 100.7 121.9 105.9 119.3 111.6 116.6 117.5 113.5 123.8 110.5 130.5 107.2 137.8

    115 45 126.5 101.1 124.0 106.3 121.3 112.0 118.7 117.9 115.6 124.4 112.6 131.1 109.1 138.3

    46 128.6 101.5 126.1 106.8 123.4 112.4 120.8 118.5 117.7 124.8 114.5 131.7 111.0 138.9

    48 133.2 102.5 130.5 107.8 127.8 113.3 125.0 119.4 121.9 125.7 118.5 132.6 115.1 139.9

    50 137.8 103.4 135.1 108.8 132.2 114.3 129.2 120.4 126.1 126.9 122.7 133.8 119.1 141.0

    Notes :1. kW = compressor input power2. LCWT = leaving chilled water temperature3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

  • 15

    RATINGS DATAYCA 50Hz, R407C Performance Rating

    Air on condenser F

    Model LCWT (F) 75 80 85 90 95 100 105

    Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW

    40 18.0 16.2 17.5 17.1 17.0 18.1 16.5 19.2 15.9 20.3 15.4 21.5 14.8 22.8

    42 18.7 16.3 18.2 17.2 17.7 18.2 17.2 19.3 16.6 20.4 16.0 21.6 15.4 22.9

    44 19.5 16.4 19.0 17.3 18.4 18.3 17.9 19.4 17.3 20.5 16.7 21.7 16.1 23.0

    20 45 19.9 16.4 19.3 17.4 18.8 18.4 18.2 19.4 17.6 20.6 17.0 21.8 16.4 23.1

    46 20.2 16.5 19.7 17.4 19.2 18.4 18.6 19.5 18.0 20.6 17.4 21.9 16.7 23.1

    48 21.0 16.6 20.5 17.5 19.9 18.5 19.3 19.6 18.7 20.8 18.0 22.0 17.4 23.3

    50 21.8 16.7 21.2 17.7 20.7 18.7 20.1 19.7 19.4 20.9 18.7 22.1 18.0 23.4

    40 22.6 20.3 22.0 21.5 21.4 22.7 20.7 24.1 20.0 25.5 19.3 27.0 18.6 28.5

    42 23.5 20.4 22.9 21.6 22.2 22.9 21.5 24.2 20.8 25.6 20.1 27.1 19.3 28.7

    44 24.5 20.5 23.8 21.7 23.1 23.0 22.4 24.3 21.7 25.7 20.9 27.3 20.1 28.9

    25 45 24.9 20.6 24.3 21.8 23.6 23.1 22.9 24.4 22.1 25.8 21.4 27.3 20.5 28.9

    46 25.4 20.7 24.7 21.9 24.0 23.1 23.3 24.5 22.6 25.9 21.8 27.4 20.9 29.0

    48 26.4 20.8 25.7 22.0 25.0 23.3 24.2 24.6 23.4 26.1 22.6 27.6 21.8 29.2

    50 27.4 21.0 26.6 22.2 25.9 23.4 25.2 24.8 24.3 26.2 23.5 27.7 22.6 29.3

    40 30.0 27.0 29.3 28.6 28.4 30.3 27.6 32.1 26.6 33.9 25.7 35.9 24.7 38.0

    42 31.3 27.2 30.5 28.7 29.6 30.5 28.7 32.2 27.8 34.1 26.8 36.1 25.7 38.2

    44 32.6 27.4 31.7 28.9 30.8 30.6 29.8 32.4 28.9 34.3 27.9 36.3 26.8 38.4

    30 45 33.2 27.5 32.3 29.0 31.4 30.7 30.5 32.5 29.5 34.4 28.4 36.4 27.4 38.5

    46 33.8 27.6 32.9 29.1 32.0 30.8 31.0 32.6 30.0 34.5 29.0 36.5 27.9 38.6

    48 35.1 27.8 34.2 29.3 33.3 31.0 32.3 32.8 31.2 34.7 30.1 36.7 29.0 38.9

    50 36.5 27.9 35.5 29.5 34.6 31.2 33.5 33.0 32.4 34.9 31.3 36.9 30.1 39.1

    40 37.4 33.7 36.4 35.6 35.4 37.7 34.3 39.9 33.2 42.2 32.0 44.8 30.8 47.3

    42 39.0 33.9 37.9 35.8 36.8 37.9 35.7 40.1 34.6 42.4 33.3 45.0 32.1 47.6

    44 40.6 34.1 39.5 36.0 38.4 38.1 37.2 40.3 36.0 42.7 34.7 45.2 33.4 47.9

    40 45 41.3 34.2 40.2 36.1 39.1 38.2 37.9 40.4 36.7 42.8 35.4 45.3 34.1 48.0

    46 42.1 34.3 41.0 36.2 39.9 38.3 38.6 40.6 37.4 43.0 36.1 45.5 34.7 48.1

    48 43.7 34.6 42.6 36.5 41.4 38.6 40.2 40.8 38.8 43.2 37.5 45.7 36.1 48.4

    50 45.4 34.8 44.2 36.8 43.0 38.8 41.7 41.1 40.4 43.5 39.0 46.0 37.5 48.6

    40 46.4 41.7 45.2 44.1 43.9 46.7 42.5 49.5 41.1 52.4 39.6 55.5 38.1 58.7

    42 48.3 42.0 47.0 44.4 45.6 47.0 44.3 49.7 42.8 52.6 41.3 55.7 39.7 59.0

    44 50.3 42.2 48.9 44.6 47.6 47.2 46.0 50.0 44.6 52.9 43.0 56.0 41.4 59.3

    50 45 51.2 42.4 49.9 44.8 48.4 47.4 47.0 50.1 45.5 53.1 43.9 56.2 42.2 59.5

    46 52.2 42.5 50.8 44.9 49.4 47.5 47.9 50.3 46.4 53.2 44.8 56.3 43.0 59.6

    48 54.2 42.8 52.8 45.2 51.3 47.8 49.8 50.6 48.1 53.6 46.5 56.7 44.8 59.9

    50 56.3 43.1 54.8 45.6 53.3 48.1 51.7 50.9 50.0 53.9 48.3 57.0 46.5 60.3

    Notes :1. kW = compressor input power2. LCWT = leaving chilled water temperature3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

  • 16

    RATINGS DATAYCA 50Hz, R407C Performance Rating

    Air on condenser F

    Model LCWT (F) 75 80 85 90 95 100 105

    Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW

    40 58.0 52.2 56.5 55.2 54.9 58.4 53.2 61.9 51.4 65.5 49.6 69.4 47.7 73.4

    42 60.4 52.5 58.8 55.5 57.1 58.8 55.4 62.2 53.6 65.8 51.7 69.7 49.7 73.8

    44 62.9 52.8 61.2 55.8 59.5 59.1 57.6 62.5 55.8 66.2 53.8 70.1 51.8 74.2

    60 45 64.1 53.0 62.4 56.0 60.6 59.3 58.8 62.7 56.9 66.4 54.9 70.3 52.8 74.4

    46 65.3 53.2 63.6 56.2 61.8 59.4 59.9 62.9 58.0 66.6 56.0 70.5 53.8 74.6

    48 67.8 53.6 66.0 56.6 64.2 59.8 62.3 63.3 60.2 67.0 58.2 70.9 56.0 75.0

    50 70.4 53.9 68.5 57.0 66.7 60.2 64.7 63.7 62.6 67.4 60.4 71.3 58.2 75.4

    40 68.2 61.4 66.5 64.9 64.6 68.7 62.6 72.8 60.5 77.0 58.3 81.6 56.1 86.3

    42 71.0 61.8 69.2 65.3 67.2 69.2 65.2 73.2 63.0 77.4 60.8 82.0 58.5 86.8

    44 74.0 62.1 72.0 65.6 70.0 69.5 67.8 73.5 65.6 77.9 63.3 82.5 60.9 87.3

    70 45 75.4 62.3 73.4 65.9 71.3 69.8 69.2 73.8 66.9 78.1 64.6 82.7 62.1 87.5

    46 76.8 62.6 74.8 66.1 72.7 69.9 70.5 74.0 68.2 78.3 65.9 82.9 63.3 87.7

    48 79.7 63.0 77.6 66.6 75.5 70.3 73.3 74.5 70.8 78.8 68.5 83.4 65.9 88.2

    50 82.8 63.4 80.6 67.0 78.5 70.8 76.1 74.9 73.6 79.3 71.0 83.9 68.5 88.7

    40 76.1 68.5 74.2 72.4 72.1 76.6 69.8 81.2 67.5 86.0 65.1 91.1 62.6 96.3

    42 79.3 68.9 77.2 72.8 74.9 77.2 72.7 81.6 70.3 86.4 67.9 91.5 65.2 96.9

    44 82.6 69.3 80.3 73.2 78.1 77.6 75.6 82.0 73.2 86.9 70.6 92.0 68.0 97.4

    80 45 84.1 69.6 81.9 73.5 79.5 77.8 77.2 82.3 74.7 87.1 72.1 92.3 69.3 97.6

    46 85.7 69.8 83.5 73.8 81.1 78.0 78.6 82.6 76.1 87.4 73.5 92.5 70.6 97.9

    48 89.0 70.3 86.6 74.3 84.3 78.5 81.8 83.1 79.0 87.9 76.4 93.1 73.5 98.4

    50 92.4 70.7 89.9 74.8 87.5 79.0 84.9 83.6 82.2 88.5 79.3 93.6 76.4 99.0

    40 90.8 81.7 88.5 86.4 85.9 91.4 83.3 96.9 80.5 102.5 77.6 108.6 74.7 114.9

    42 94.6 82.2 92.1 86.9 89.4 92.1 86.7 97.4 83.9 103.0 80.9 109.1 77.8 115.5

    44 98.5 82.7 95.8 87.4 93.1 92.5 90.2 97.8 87.4 103.6 84.2 109.7 81.1 116.2

    95 45 100.3 83.0 97.7 87.7 94.9 92.8 92.1 98.2 89.1 103.9 85.9 110.1 82.7 116.5

    46 102.2 83.3 99.6 88.0 96.7 93.0 93.8 98.5 90.8 104.3 87.7 110.4 84.2 116.8

    48 106.1 83.9 103.3 88.6 100.5 93.6 97.5 99.1 94.2 104.9 91.1 111.0 87.7 117.4

    50 110.2 84.4 107.2 89.2 104.4 94.2 101.3 99.7 98.0 105.5 94.6 111.6 91.1 118.0

    40 111.9 100.7 109.0 106.5 106.0 112.7 102.7 119.5 99.2 126.4 95.7 133.9 92.1 141.7

    42 116.6 101.3 113.5 107.1 110.2 113.5 106.9 120.0 103.4 127.0 99.8 134.5 95.9 142.4

    44 121.4 101.9 118.1 107.7 114.8 114.1 111.2 120.6 107.7 127.8 103.8 135.3 100.0 143.2

    115 45 123.7 102.3 120.4 108.1 117.0 114.4 113.5 121.0 109.8 128.2 106.0 135.7 101.9 143.6

    46 126.0 102.7 122.7 108.5 119.3 114.6 115.6 121.4 111.9 128.5 108.1 136.1 103.8 144.0

    48 130.9 103.4 127.4 109.2 123.9 115.4 120.2 122.2 116.2 129.3 112.3 136.8 108.1 144.8

    50 135.9 104.0 132.2 110.0 128.7 116.2 124.9 122.9 120.8 130.1 116.6 137.6 112.3 145.5

    Notes :1. kW = compressor input power2. LCWT = leaving chilled water temperature3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

  • 17

    RATINGS DATA

    YCA 60Hz, R407C Performance Rating

    Air on condenser F

    Model LCWT (F) 75 80 85 90 95 100 105

    Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW

    40 17.8 16.0 17.3 16.9 16.8 17.9 16.3 19.0 15.8 20.1 15.2 21.3 14.6 22.5

    42 18.5 16.1 18.0 17.0 17.5 18.0 17.0 19.1 16.4 20.2 15.9 21.4 15.3 22.6

    44 19.3 16.2 18.8 17.1 18.3 18.1 17.7 19.2 17.1 20.3 16.5 21.5 15.9 22.8

    20 45 19.7 16.3 19.2 17.2 18.6 18.2 18.0 19.2 17.5 20.4 16.8 21.6 16.2 22.8

    46 20.0 16.3 19.5 17.2 19.0 18.2 18.4 19.3 17.8 20.4 17.2 21.6 16.5 22.9

    48 20.8 16.4 20.3 17.4 19.7 18.4 19.1 19.4 18.5 20.6 17.9 21.8 17.2 23.0

    50 21.6 16.5 21.0 17.5 20.5 18.5 19.9 19.5 19.2 20.7 18.5 21.9 17.9 23.1

    40 23.0 20.7 22.4 21.9 21.8 23.2 21.1 24.5 20.4 26.0 19.7 27.5 18.9 29.1

    42 24.0 20.8 23.3 22.0 22.6 23.3 22.0 24.7 21.3 26.1 20.5 27.6 19.7 29.3

    44 24.9 20.9 24.3 22.1 23.6 23.4 22.8 24.8 22.1 26.3 21.3 27.8 20.5 29.4

    25 45 25.4 21.0 24.7 22.2 24.0 23.5 23.3 24.9 22.6 26.3 21.8 27.9 20.9 29.5

    46 25.9 21.1 25.2 22.3 24.5 23.6 23.8 24.9 23.0 26.4 22.2 28.0 21.3 29.6

    48 26.9 21.3 26.2 22.4 25.5 23.7 24.7 25.1 23.9 26.6 23.1 28.1 22.2 29.7

    50 27.9 21.4 27.2 22.6 26.5 23.9 25.7 25.3 24.8 26.7 24.0 28.3 23.1 29.9

    40 27.9 25.1 27.2 26.6 26.4 28.1 25.6 29.8 24.8 31.6 23.9 33.4 23.0 35.4

    42 29.1 25.3 28.3 26.7 27.5 28.3 26.7 30.0 25.8 31.7 24.9 33.6 23.9 35.6

    44 30.3 25.4 29.5 26.9 28.7 28.5 27.7 30.1 26.9 31.9 25.9 33.8 25.0 35.7

    30 45 30.9 25.5 30.1 27.0 29.2 28.6 28.3 30.2 27.4 32.0 26.4 33.9 25.4 35.8

    46 31.5 25.6 30.6 27.1 29.8 28.6 28.9 30.3 27.9 32.1 27.0 34.0 25.9 35.9

    48 32.7 25.8 31.8 27.3 30.9 28.8 30.0 30.5 29.0 32.3 28.0 34.2 27.0 36.1

    50 33.9 26.0 33.0 27.5 32.1 29.0 31.2 30.7 30.2 32.5 29.1 34.3 28.0 36.3

    40 36.7 33.0 35.7 34.9 34.7 36.9 33.6 39.1 32.5 41.4 31.4 43.9 30.2 46.4

    42 38.2 33.2 37.2 35.1 36.1 37.2 35.0 39.3 33.9 41.6 32.7 44.1 31.4 46.6

    44 39.8 33.4 38.7 35.3 37.6 37.4 36.4 39.5 35.3 41.8 34.0 44.3 32.7 46.9

    40 45 40.5 33.5 39.4 35.4 38.3 37.5 37.2 39.6 36.0 42.0 34.7 44.4 33.4 47.0

    46 41.3 33.6 40.2 35.5 39.1 37.5 37.9 39.8 36.7 42.1 35.4 44.6 34.0 47.2

    48 42.9 33.9 41.7 35.8 40.6 37.8 39.4 40.0 38.1 42.4 36.8 44.8 35.4 47.4

    50 44.5 34.1 43.3 36.0 42.2 38.1 40.9 40.3 39.6 42.6 38.2 45.1 36.8 47.7

    40 46.3 41.7 45.1 44.1 43.9 46.7 42.5 49.5 41.1 52.3 39.6 55.4 38.1 58.6

    42 48.3 41.9 47.0 44.3 45.6 47.0 44.3 49.7 42.8 52.6 41.3 55.7 39.7 59.0

    44 50.3 42.2 48.9 44.6 47.5 47.2 46.0 49.9 44.6 52.9 43.0 56.0 41.4 59.3

    50 45 51.2 42.3 49.9 44.7 48.4 47.4 47.0 50.1 45.5 53.1 43.9 56.2 42.2 59.4

    46 52.2 42.5 50.8 44.9 49.4 47.5 47.9 50.3 46.3 53.2 44.7 56.3 43.0 59.6

    48 54.2 42.8 52.7 45.2 51.3 47.8 49.8 50.6 48.1 53.5 46.5 56.6 44.7 59.9

    50 56.2 43.1 54.7 45.5 53.3 48.1 51.7 50.9 50.0 53.9 48.3 57.0 46.5 60.2

    Notes :1. kW = compressor input power2. LCWT = leaving chilled water temperature3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

  • 18

    RATINGS DATA

    YCA 60Hz, R407C Performance Rating

    Air on condenser F

    Model LCWT (F) 75 80 85 90 95 100 105

    Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW Tons kW

    40 56.6 50.9 55.1 53.9 53.6 57.0 51.9 60.4 50.2 63.9 48.4 67.7 46.6 71.6

    42 59.0 51.2 57.4 54.2 55.7 57.4 54.1 60.7 52.3 64.2 50.5 68.0 48.5 72.0

    44 61.4 51.5 59.7 54.5 58.1 57.7 56.2 61.0 54.5 64.6 52.5 68.4 50.6 72.4

    60 45 62.6 51.7 60.9 54.7 59.1 57.9 57.4 61.2 55.5 64.8 53.6 68.6 51.5 72.6

    46 63.7 51.9 62.1 54.9 60.3 58.0 58.5 61.4 56.6 65.0 54.7 68.8 52.5 72.8

    48 66.2 52.3 64.4 55.2 62.7 58.4 60.8 61.8 58.8 65.4 56.8 69.2 54.7 73.2

    50 68.7 52.6 66.9 55.6 65.1 58.8 63.1 62.2 61.1 65.8 59.0 69.6 56.8 73.6

    40 67.3 60.5 65.5 64.0 63.7 67.7 61.7 71.8 59.6 76.0 57.5 80.5 55.3 85.1

    42 70.1 60.9 68.2 64.4 66.2 68.2 64.3 72.1 62.2 76.3 60.0 80.8 57.6 85.6

    44 73.0 61.2 71.0 64.7 69.0 68.5 66.8 72.5 64.7 76.8 62.4 81.3 60.1 86.1

    70 45 74.3 61.5 72.4 65.0 70.3 68.8 68.2 72.7 66.0 77.0 63.7 81.5 61.2 86.3

    46 75.7 61.7 73.8 65.2 71.7 68.9 69.5 73.0 67.3 77.2 65.0 81.8 62.4 86.5

    48 78.6 62.2 76.6 65.6 74.5 69.4 72.3 73.4 69.8 77.7 67.5 82.2 65.0 87.0

    50 81.7 62.5 79.5 66.1 77.4 69.8 75.0 73.9 72.6 78.2 70.1 82.7 67.5 87.5

    40 75.2 67.7 73.2 71.6 71.2 75.7 69.0 80.2 66.6 84.9 64.3 90.0 61.8 95.1

    42 78.3 68.1 76.2 71.9 74.0 76.2 71.8 80.6 69.5 85.3 67.0 90.4 64.4 95.7

    44 81.5 68.4 79.3 72.3 77.1 76.6 74.7 81.0 72.3 85.8 69.7 90.9 67.1 96.2

    80 45 83.1 68.7 80.9 72.6 78.6 76.9 76.2 81.3 73.8 86.1 71.2 91.1 68.4 96.4

    46 84.6 69.0 82.4 72.9 80.1 77.0 77.6 81.5 75.2 86.3 72.6 91.4 69.7 96.7

    48 87.9 69.5 85.6 73.4 83.2 77.5 80.8 82.1 78.0 86.9 75.4 91.9 72.6 97.2

    50 91.3 69.9 88.8 73.9 86.5 78.0 83.9 82.6 81.1 87.4 78.3 92.4 75.4 97.7

    40 87.0 78.3 84.7 82.8 82.3 87.6 79.8 92.8 77.1 98.2 74.4 104.0 71.5 110.0

    42 90.5 78.7 88.2 83.2 85.6 88.2 83.1 93.2 80.4 98.6 77.5 104.5 74.5 110.6

    44 94.3 79.2 91.7 83.7 89.2 88.6 86.4 93.7 83.7 99.2 80.7 105.1 77.7 111.2

    95 45 96.1 79.5 93.5 84.0 90.8 88.9 88.2 94.0 85.3 99.5 82.3 105.4 79.2 111.5

    46 97.9 79.8 95.3 84.3 92.6 89.1 89.8 94.3 87.0 99.8 84.0 105.7 80.7 111.8

    48 101.6 80.4 98.9 84.9 96.2 89.6 93.4 94.9 90.2 100.4 87.3 106.3 84.0 112.4

    50 105.5 80.8 102.7 85.5 100.0 90.2 97.0 95.5 93.8 101.0 90.5 106.9 87.3 113.0

    40 110.6 99.5 107.7 105.2 104.7 111.3 101.4 118.0 98.0 124.9 94.6 132.3 90.9 139.9

    42 115.2 100.1 112.1 105.8 108.9 112.1 105.6 118.6 102.2 125.4 98.6 132.9 94.8 140.7

    44 119.9 100.7 116.7 106.4 113.4 112.7 109.8 119.2 106.4 126.2 102.6 133.6 98.8 141.5

    115 45 122.2 101.0 119.0 106.8 115.5 113.1 112.1 119.5 108.5 126.6 104.7 134.0 100.7 141.8

    46 124.5 101.4 121.3 107.1 117.8 113.2 114.2 119.9 110.6 127.0 106.8 134.4 102.6 142.2

    48 129.3 102.2 125.8 107.9 122.4 114.0 118.8 120.7 114.8 127.7 111.0 135.2 106.8 143.0

    50 134.2 102.8 130.6 108.7 127.2 114.8 123.4 121.4 119.3 128.5 115.2 135.9 111.0 143.8

    Notes :1. kW = compressor input power2. LCWT = leaving chilled water temperature3. Ratings are based upon 2.4 USGPM cooler water per ton and 0.0001 fouling factor

  • 19

    PHYSICAL DATA

    YCA Physical Data (50Hz)

    Model YCA 20 YCA 25 YCA 30 YCA 40 YCA 50 YCA 60 YCA 70 YCA 80 YCA 95 YCA 115

    GENERAL

    Nominal Tons, R22 18.5 23.1 30.8 38.4 47.5 59.5 70 78.1 93.1 114.9

    Nominal Tons, R407C 17.3 21.7 28.9 36 44.6 55.8 65.6 73.2 87.4 107.7

    No. of Refrigerant Circuits 1 1 1 2 2 2 2 2 2 2

    Compressors/Circuit 2 2 2 2 2 3 3 2 3 3

    Compressors/Unit 2 2 2 4 4 6 6 4 6 6

    Capacity Steps of Compressor % 100-50 100-50 100-50 100-75- 100-75- 100-83-67- 100-83-67- 100-75- 100-83-67- 100-83-67-

    50-25 50-25 50-33-17 50-33-17 50-25 50-33-17 50-33-17

    COMPRESSOR

    Type scroll scroll scroll scroll scroll scroll scroll scroll scroll scroll

    Compressor Hp/Each 13 15 20 13 15 13 15 25 20 25

    Nominal Total Comp.kW Input, R22 20.1 25.2 33.6 41.9 51.9 64.9 77.3 85.2 101.6 125.4

    Nominal Total Comp.kW input, R407C 20.5 25.7 34.3 42.7 52.9 66.2 77.9 86.9 103.6 127.8

    RLA/Each (380V/3ph/50Hz), R22 17.1 23.6 29.6 17.1 23.6 17.1 23.6 36 29.6 36

    RLA/Each (380V/3ph/50Hz), R407C 20.7 24.5 29.5 20.7 24.5 20.7 24.5 35.7 29.5 35.7

    Locked Rotor Amps/Each 167 198 225 167 198 167 198 250 225 250

    Voltage Range 342-462V

    Power Supply 380/415V/3ph/50Hz

    Nominal Speed 2900 2900 2900 2900 2900 2900 2900 2900 2900 2900

    CONDENSER COIL

    Shape s s v v v w w w w w

    Tube Height 42 42 42 42 42 44 44 44 44 45

    Number of Rows 3 4 3 4 4 3 4 4 3 4

    Fins/Inch 12 12 12 12 14 12 12 14 12 14

    Tube Dia 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"

    Fins Length 81" 81" 93" 93" 93" 81" 81" 81" 110" 110"

    COOLER

    WPD, ft W.G. 6 4 13 13 5 17 16 5 15 17

    Max. Water Side Pressure, Psig 150 150 150 150 150 150 150 150 150 150

    Max. Ref. Side Pressure, Psig 300 300 300 300 300 300 300 300 300 300

    Water Connection 2.5" 2.5" 3" 3" 4.5" 4.5" 4.5" 6.6" 5.5" 6.6"

    CONDENSER FANS, STANDARD

    No. of Fans X Dia, mm 3 X 600 3 X 600 2 X 900 2 X 900 2 X 900 4 X 900 4 X 900 4 X 900 6 X 900 6 X 900

    Total cfm 12700 12700 26000 28000 32600 52000 49500 54400 74000 75600

    Fan Motor Hp/Each 5/8 5/8 2 3 4 2 2 3 2 3

    Fan Motor Poles 6 6 6 6 6 6 6 6 6 6

    SHIPPING WEIGHT

    AL Fin Coils, kg 875 904 1386 1468 1568 2414 2640 2740 4025 4500

    Cu Fin Coils, kg 975 1029 1586 1693 2393 2687 2999 3099 4534 4600

    OPERATING WEIGHT

    AL Fin Coils, kg 918 955 1454 1545 1645 2547 2780 2880 4240 4740

    Cu Fin Coils, kg 1018 1080 1654 1770 2502 2821 3139 3239 4739 4830

    Ref. Charge, ckt1/ckt2, kg 10 14 20 12/12 16/16 17/17 23/23 24/24 30/30 36/36

    DIMENSION

    Height, mm 1339 1339 1720 1720 1820 2055 2055 2055 2055 2055

    Width, mm 2680 2680 2894 2894 2894 2290 2290 2290 3322 3322

    Depth, mm 1515 1515 1911 1949 1944 2516 2516 2516 2302 2302

    Note: Nominal info based on LWCT of 44F and 95F ambient temp.All the model come with York Controller, control box without York Controller can be the optional item.

  • 20

    PHYSICAL DATA

    YCA Physical Data (60Hz)

    Model YCA 20 YCA 25 YCA 30 YCA 40 YCA 50 YCA 60 YCA 70 YCA 80 YCA 95 YCA 115

    GENERAL

    Nominal Tons, R22 18.3 23.5 28.6 37.7 47.5 58.1 69.0 77.2 89.2 113.5

    Nominal Tons, R407C 17.1 22.1 26.9 35.3 44.6 54.5 64.1 72.3 83.7 106.4

    No. Of Refrigerant Circuits 1 1 1 1 2 2 2 2 2 2

    Compressors/Circuit 2 2 2 2 2 2 3 2 2 3

    Compressors/Unit 2 2 2 2 4 4 6 4 4 6

    Capacity Steps Of Compressor % 100-50 100-50 100-50 100-50 100-75- 100-75- 100-83-67- 100-75- 100-75- 100-83-67-

    50-25 50-25 50-33-17 50-25 50-25 50-33-17

    COMPRESSOR

    Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll

    Compressor Hp/Each 10 13 15 20 13 15 13 20 25 20

    Nominal Total Comp.kW Input, R22 19.9 25.7 31.2 41.1 51.8 63.4 76.2 84.2 97.3 123.8

    Nominal Total Comp.kW Input, R407C 20.3 26.3 31.9 41.8 52.9 64.6 76.8 85.8 99.2 126.2

    RLA/Each (460V/3ph/60Hz), R22 16.3 17.1 23.6 30.6 17.1 23.6 17.1 30.6 36.7 30.6

    RLA/Each (460V/3ph/60Hz), R407c 17 20.7 24.5 30.7 20.7 24.5 20.7 30.7 37.2 30.7

    Locked Rotor Amps/Each 125 167 198 225 167 198 167 225 250 225

    Voltage Range 415 - 506 V

    Power Supply 460V/3ph/60Hz

    Nominal Speed 3500 3500 3500 3500 3500 3500 3500 3500 3500 3500

    CONDENSER COIL

    Shape S S V V V W W W W W

    Tube Height 42 42 42 42 42 44 44 44 44 45

    Number of Rows 3 4 3 4 4 3 4 4 3 4

    Fins/Inch 12 12 12 12 14 12 12 14 12 14

    Tube Dia 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"

    Fins Length 81" 81" 93" 93" 93" 81" 81" 81" 110" 110"

    COOLER

    WPD, ft W.G. 6 4 13 13 5 17 16 5 15 17

    Max. Water Side Pressure, Psig 150 150 150 150 150 150 150 150 150 150

    Max. Ref. Side Pressure, Psig 300 300 300 300 300 300 300 300 300 300

    Water Connection 2.5" 2.5" 3" 3 4.5" 4.5" 4.5" 6.6" 5.5" 6.6"

    CONDENSER FANS, STD

    No. Of Fans X Dia, mm 3 X 600 3 X 600 2 X 900 2 X 900 2 X 900 4 X 900 4 X 900 4 X 900 6 X 900 6 X 900

    Total cfm 12700 12700 26000 28000 32600 52000 49500 54400 74000 75600

    Fan Motor Hp/Each 5/8 5/8 3 3 5.5 3 3 3 2 3

    Fan Motor Poles 6 6 6 6 6 6 6 6 6 6

    SHIPPING WEIGHT

    Al Fin Coils, Kg 855 884 1356 1436 1538 2384 2610 2700 4025 4500

    Cu Fin Coils, Kg 955 1009 1556 1663 2363 2667 2969 3059 4534 4600

    OPERATING WEIGHT

    Al Fin Coils, Kg 918 955 1454 1545 1645 2547 2780 2880 4240 4740

    Cu Fin Coils, Kg 1018 1080 1654 1770 2502 2821 3139 3239 4739 4830

    Ref. Charge, Ckt1/Ckt2,Kg 10 14 20 24 16/16 17/17 23/23 24/24 30/30 36/36

    DIMENSION

    Height, mm 1339 1339 1720 1720 1820 2055 2055 2055 2055 2055

    Width, mm 2680 2680 2894 2894 2894 2290 2290 2290 3322 3322

    Depth, mm 1515 1515 1911 1911 1944 2516 2516 2516 2302 2302

    Note: Nominal info based on LWCT of 44F and 95F ambient temp.

  • 21

    DIMENSIONS

    YCA 20 50Hz & 60HzN

    ote:

    Pla

    cem

    ent

    on a

    lev

    el s

    urfa

    ce o

    f fr

    ee o

    f ob

    stru

    ctio

    ns(in

    clud

    ing

    snow

    , fo

    r w

    inte

    r op

    erat

    ion)

    or

    air

    circ

    ulat

    ion

    ensu

    res

    rate

    d pe

    rfor

    man

    ce, r

    elia

    ble

    oper

    atio

    n, a

    nd e

    ase

    of

    ma

    inte

    na

    nce

    . S

    ite r

    est

    rict

    ion

    s m

    ay

    com

    pro

    mis

    em

    inim

    um

    cle

    ara

    nce

    s in

    dic

    ate

    d b

    elo

    w,

    resu

    ltin

    g i

    nun

    pred

    icta

    ble

    airf

    low

    pat

    tern

    s an

    d po

    ssib

    le d

    imin

    ishe

    dpe

    rfor

    man

    ce. Y

    OR

    Ks

    uni

    t con

    trol

    s w

    ill o

    ptim

    ize

    oper

    atio

    nw

    ithou

    t nui

    sanc

    e hi

    gh-p

    ress

    ure

    safe

    ty c

    utou

    ts; h

    owev

    er,

    the

    sy

    ste

    m

    de

    sig

    ne

    r m

    ust

    co

    nsi

    de

    r p

    ote

    nti

    al

    perf

    orm

    ance

    deg

    rada

    tion.

    Acc

    ess

    to t

    he u

    nit

    cont

    rol

    cent

    er a

    ssum

    es t

    he u

    nit

    is n

    o hi

    gher

    tha

    n on

    spr

    ing

    isol

    ator

    s. R

    ecom

    men

    ded

    min

    imum

    cle

    aran

    ces:

    Sid

    e to

    wal

    l - 2

    m;

    rear

    to

    wal

    l - 2

    m;

    cont

    rol p

    anel

    to

    end

    wal

    l -1.

    2m;

    top

    - no

    obs

    truc

    tions

    allo

    wed

    ; di

    stan

    ce b

    etw

    een

    adja

    cent

    uni

    ts -

    3m

    . N

    o m

    ore

    than

    one

    adj

    acen

    t w

    all

    may

    be

    high

    er th

    an u

    nit.

  • 22

    DIMENSIONS

    YCA 25 50Hz & 60HzN

    ote:

    Pla

    cem

    ent

    on a

    lev

    el s

    urfa

    ce o

    f fr

    ee o

    f ob

    stru

    ctio

    ns(in

    clud

    ing

    snow

    , fo

    r w

    inte

    r op

    erat

    ion)

    or

    air

    circ

    ulat

    ion

    ensu

    res

    rate

    d pe

    rfor

    man

    ce, r

    elia

    ble

    oper

    atio

    n, a

    nd e

    ase

    of

    ma

    inte

    na

    nce

    . S

    ite r

    est

    rict

    ion

    s m

    ay

    com

    pro

    mis

    em

    inim

    um

    cle

    ara

    nce

    s in

    dic

    ate

    d b

    elo

    w,

    resu

    ltin

    g i

    nun

    pred

    icta

    ble

    airf

    low

    pat

    tern

    s an

    d po

    ssib

    le d

    imin

    ishe

    dpe

    rfor

    man

    ce. Y

    OR

    Ks

    uni

    t con

    trol

    s w

    ill o

    ptim

    ize

    oper

    atio

    nw

    ithou

    t nui

    sanc

    e hi

    gh-p

    ress

    ure

    safe

    ty c

    utou

    ts; h

    owev

    er,

    the

    sy

    ste

    m

    de

    sig

    ne

    r m

    ust

    co

    nsi

    de

    r p

    ote

    nti

    al

    perf

    orm

    ance

    deg

    rada

    tion.

    Acc

    ess

    to t

    he u

    nit

    cont

    rol

    cent

    er a

    ssum

    es t

    he u

    nit

    is n

    o hi

    gher

    tha

    n on

    spr

    ing

    isol

    ator

    s. R

    ecom

    men

    ded

    min

    imum

    cle

    aran

    ces:

    Sid

    e to

    wal

    l - 2

    m;

    rear

    to

    wal

    l - 2

    m;

    cont

    rol p

    anel

    to

    end

    wal

    l -1.

    2m;

    top

    - no

    obs

    truc

    tions

    allo

    wed

    ; di

    stan

    ce b

    etw

    een

    adja

    cent

    uni

    ts -

    3m

    . N

    o m

    ore

    than

    one

    adj

    acen

    t w

    all

    may

    be

    high

    er th

    an u

    nit.

  • 23

    DIMENSIONS

    YCA 30 50Hz & 60HzYCA 40 60Hz

    Not

    e:P

    lace

    men

    t on

    a l

    evel

    sur

    face

    of

    free

    of

    obst

    ruct

    ions

    (incl

    udin

    g sn

    ow,

    for

    win

    ter

    oper

    atio

    n) o

    r ai

    r ci

    rcul

    atio

    nen

    sure

    s ra

    ted

    perf

    orm

    ance

    , rel

    iabl

    e op

    erat

    ion,

    and

    eas

    eo

    f m

    ain

    ten

    an

    ce.

    Site

    re

    stri

    ctio

    ns

    ma

    y co

    mp

    rom

    ise

    min

    imu

    m c

    lea

    ran

    ces

    ind

    ica

    ted

    be

    low

    , re

    sulti

    ng

    in

    unpr

    edic

    tabl

    e ai

    rflo

    w p

    atte

    rns

    and

    poss

    ible

    dim

    inis

    hed

    perf

    orm

    ance

    . YO

    RK

    s u

    nit c

    ontr

    ols

    will

    opt

    imiz

    e op

    erat

    ion

    with

    out n

    uisa

    nce

    high

    -pre

    ssur

    e sa

    fety

    cut

    outs

    ; how

    ever

    ,th

    e

    syst

    em

    d

    esi

    gn

    er

    mu

    st

    con

    sid

    er

    po

    ten

    tia

    lpe

    rfor

    man

    ce d

    egra

    datio

    n. A

    cces

    s to

    the

    uni

    t co

    ntro

    lce

    nter

    ass

    umes

    the

    uni

    t is

    no

    high

    er t

    han

    on s

    prin

    gis

    olat

    ors.

    Rec

    omm

    ende

    d m

    inim

    um c

    lear

    ance

    s: S

    ide

    tow

    all -

    2m

    ; re

    ar t

    o w

    all -

    2m

    ; co

    ntro

    l pan

    el t

    o en

    d w

    all -

    1.2m

    ; to

    p -

    no o

    bstr

    uctio

    ns a

    llow

    ed;

    dist

    ance

    bet

    wee

    nad

    jace

    nt u

    nits

    - 3

    m.

    No

    mor

    e th

    an o

    ne a

    djac

    ent

    wal

    lm

    ay b

    e hi

    gher

    than

    uni

    t.

  • 24

    DIMENSIONS

    YCA 40 50HzN

    ote:

    Pla

    cem

    ent

    on a

    lev

    el s

    urfa

    ce o

    f fr

    ee o

    f ob

    stru

    ctio

    ns(in

    clud

    ing

    snow

    , fo

    r w

    inte

    r op

    erat

    ion)

    or

    air

    circ

    ulat

    ion

    ensu

    res

    rate

    d pe

    rfor

    man

    ce, r

    elia

    ble

    oper

    atio

    n, a

    nd e

    ase

    of

    ma

    inte

    na

    nce

    . S

    ite r

    est

    rict

    ion

    s m

    ay

    com

    pro

    mis

    em

    inim

    um

    cle

    ara

    nce

    s in

    dic

    ate

    d b

    elo

    w,

    resu

    ltin

    g i

    nun

    pred

    icta

    ble

    airf

    low

    pat

    tern

    s an

    d po

    ssib

    le d

    imin

    ishe

    dpe

    rfor

    man

    ce. Y

    OR

    Ks

    uni

    t con

    trol

    s w

    ill o

    ptim

    ize

    oper

    atio

    nw

    ithou

    t nui

    sanc

    e hi

    gh-p

    ress

    ure

    safe

    ty c

    utou

    ts; h

    owev

    er,

    the

    sy

    ste

    m

    de

    sig

    ne

    r m

    ust

    co

    nsi

    de

    r p

    ote

    nti

    al

    perf

    orm

    ance

    deg

    rada

    tion.

    Acc

    ess

    to t

    he u

    nit

    cont

    rol

    cent

    er a

    ssum

    es t

    he u

    nit

    is n

    o hi

    gher

    tha

    n on

    spr

    ing

    isol

    ator

    s. R

    ecom

    men

    ded

    min

    imum

    cle

    aran

    ces:

    Sid

    e to

    wal

    l - 2

    m;

    rear

    to

    wal

    l - 2

    m;

    cont

    rol p

    anel

    to

    end

    wal

    l -1.

    2m;

    top

    - no

    obs

    truc

    tions

    allo

    wed

    ; di

    stan

    ce b

    etw

    een

    adja

    cent

    uni

    ts -

    3m

    . N

    o m

    ore

    than

    one

    adj

    acen

    t w

    all

    may

    be

    high

    er th

    an u

    nit.

  • 25

    DIMENSIONS

    YCA 50 50Hz & 60HzN

    ote:

    Pla

    cem

    ent

    on a

    lev

    el s

    urfa

    ce o

    f fr

    ee o

    f ob

    stru

    ctio

    ns(in

    clud

    ing

    snow

    , fo

    r w

    inte

    r op

    erat

    ion)

    or

    air

    circ

    ulat

    ion

    ensu

    res

    rate

    d pe

    rfor

    man

    ce, r

    elia

    ble

    oper

    atio

    n, a

    nd e

    ase

    of

    ma

    inte

    na

    nce

    . S

    ite r

    est

    rict

    ion

    s m

    ay

    com

    pro

    mis

    em

    inim

    um

    cle

    ara

    nce

    s in

    dic

    ate

    d b

    elo

    w,

    resu

    ltin

    g i

    nun

    pred

    icta

    ble

    airf

    low

    pat

    tern

    s an

    d po

    ssib

    le d

    imin

    ishe

    dpe

    rfor

    man

    ce. Y

    OR

    Ks

    uni

    t con

    trol

    s w

    ill o

    ptim

    ize

    oper

    atio

    nw

    ithou

    t nui

    sanc

    e hi

    gh-p

    ress

    ure

    safe

    ty c

    utou

    ts; h

    owev

    er,

    the

    sy

    ste

    m

    de

    sig

    ne

    r m

    ust

    co

    nsi

    de

    r p

    ote

    nti

    al

    perf

    orm

    ance

    deg

    rada

    tion.

    Acc

    ess

    to t

    he u

    nit

    cont

    rol

    cent

    er a

    ssum

    es t

    he u

    nit

    is n

    o hi

    gher

    tha

    n on

    spr

    ing

    isol

    ator

    s. R

    ecom

    men

    ded

    min

    imum

    cle

    aran

    ces:

    Sid

    e to

    wal

    l - 2

    m;

    rear

    to

    wal

    l - 2

    m;

    cont

    rol p

    anel

    to

    end

    wal

    l -1.

    2m;

    top

    - no

    obs

    truc

    tions

    allo

    wed

    ; di

    stan

    ce b

    etw

    een

    adja

    cent

    uni

    ts -

    3m

    . N

    o m

    ore

    than

    one

    adj

    acen

    t w

    all

    may

    be

    high

    er th

    an u

    nit.

  • 26

    Not

    e:P

    lace

    men

    t on

    a l

    evel

    sur

    face

    of

    free

    of

    obst

    ruct

    ions

    (incl

    udin

    g sn

    ow,

    for

    win

    ter

    oper

    atio

    n) o

    r ai

    r ci

    rcul

    atio

    nen

    sure

    s ra

    ted

    perf

    orm

    ance

    , rel

    iabl

    e op

    erat

    ion,

    and

    eas

    eo

    f m

    ain

    ten

    an

    ce.

    Site

    re

    stri

    ctio

    ns

    ma

    y co

    mp

    rom

    ise

    min

    imu

    m c

    lea

    ran

    ces

    ind

    ica

    ted

    be

    low

    , re

    sulti

    ng

    in

    unpr

    edic

    tabl

    e ai

    rflo

    w p

    atte

    rns

    and

    poss

    ible

    dim

    inis

    hed

    perf

    orm

    ance

    . YO

    RK

    s u

    nit c

    ontr

    ols

    will

    opt

    imiz

    e op

    erat

    ion

    with

    out n

    uisa

    nce

    high

    -pre

    ssur

    e sa

    fety

    cut

    outs

    ; how

    ever

    ,th

    e

    syst

    em

    d

    esi

    gn

    er

    mu

    st

    con

    sid

    er

    po

    ten

    tia

    lpe

    rfor

    man

    ce d

    egra

    datio

    n. A

    cces

    s to

    the

    uni

    t co

    ntro

    lce

    nter

    ass

    umes

    the

    uni

    t is

    no

    high

    er t

    han

    on s

    prin

    gis

    olat

    ors.

    Rec

    omm

    ende

    d m

    inim

    um c

    lear

    ance

    s: S

    ide

    tow

    all -

    2m

    ; re

    ar t

    o w

    all -

    2m

    ; co

    ntro

    l pan

    el t

    o en

    d w

    all -

    1.2m

    ; to

    p -

    no o

    bstr

    uctio

    ns a

    llow

    ed;

    dist

    ance

    bet

    wee

    nad

    jace

    nt u

    nits

    - 3

    m.

    No

    mor

    e th

    an o

    ne a

    djac

    ent

    wal

    lm

    ay b

    e hi

    gher

    than

    uni

    t.

    DIMENSIONS

    YCA 60 50Hz

  • 27

    DIMENSIONS

    YCA 60 60HzN

    ote:

    Pla

    cem

    ent

    on a

    lev

    el s

    urfa

    ce o

    f fr

    ee o

    f ob

    stru

    ctio

    ns(in

    clud

    ing

    snow

    , fo

    r w

    inte

    r op

    erat

    ion)

    or

    air

    circ

    ulat

    ion

    ensu

    res

    rate

    d pe

    rfor

    man

    ce, r

    elia

    ble

    oper

    atio

    n, a

    nd e

    ase

    of

    ma

    inte

    na

    nce

    . S

    ite r

    est

    rict

    ion

    s m

    ay

    com

    pro

    mis

    em

    inim

    um

    cle

    ara

    nce

    s in

    dic

    ate

    d b

    elo

    w,

    resu

    ltin

    g i

    nun

    pred

    icta

    ble

    airf

    low

    pat

    tern

    s an

    d po

    ssib

    le d

    imin

    ishe

    dpe

    rfor

    man

    ce. Y

    OR

    Ks

    uni

    t con

    trol

    s w

    ill o

    ptim

    ize

    oper

    atio

    nw

    ithou

    t nui

    sanc

    e hi

    gh-p

    ress

    ure

    safe

    ty c

    utou

    ts; h

    owev

    er,

    the

    sy

    ste

    m

    de

    sig

    ne

    r m

    ust

    co

    nsi

    de

    r p

    ote

    nti

    al

    perf

    orm

    ance

    deg

    rada

    tion.

    Acc

    ess

    to t

    he u

    nit

    cont

    rol

    cent

    er a

    ssum

    es t

    he u

    nit

    is n

    o hi

    gher

    tha

    n on

    spr

    ing

    isol

    ator

    s. R

    ecom

    men

    ded

    min

    imum

    cle

    aran

    ces:

    Sid

    e to

    wal

    l - 2

    m;

    rear

    to

    wal

    l - 2

    m;

    cont

    rol p

    anel

    to

    end

    wal

    l -1.

    2m;

    top

    - no

    obs

    truc

    tions

    allo

    wed

    ; di

    stan

    ce b

    etw

    een

    adja

    cent

    uni

    ts -

    3m

    . N

    o m

    ore

    than

    one

    adj

    acen

    t w

    all

    may

    be

    high

    er th

    an u

    nit.

  • 28

    DIMENSIONS

    YCA 70 50Hz & 60HzN

    ote:

    Pla

    cem

    ent

    on a

    lev

    el s

    urfa

    ce o

    f fr

    ee o

    f ob

    stru

    ctio

    ns(in

    clud

    ing

    snow

    , fo

    r w

    inte

    r op

    erat

    ion)

    or

    air

    circ

    ulat

    ion

    ensu

    res

    rate

    d pe

    rfor

    man

    ce, r

    elia

    ble

    oper

    atio

    n, a

    nd e

    ase

    of

    ma

    inte

    na

    nce

    . S

    ite r

    est

    rict

    ion

    s m

    ay

    com

    pro

    mis

    em

    inim

    um

    cle

    ara

    nce

    s in

    dic

    ate

    d b

    elo

    w,

    resu

    ltin

    g i

    nun

    pred

    icta

    ble

    airf

    low

    pat

    tern

    s an

    d po

    ssib

    le d

    imin

    ishe

    dpe

    rfor

    man

    ce. Y

    OR

    Ks

    uni

    t con

    trol

    s w

    ill o

    ptim

    ize

    oper

    atio

    nw

    ithou

    t nui

    sanc

    e hi

    gh-p

    ress

    ure

    safe

    ty c

    utou

    ts; h

    owev

    er,

    the

    sy

    ste

    m

    de

    sig

    ne

    r m

    ust

    co

    nsi

    de

    r p

    ote

    nti

    al

    perf

    orm

    ance

    deg

    rada

    tion.

    Acc

    ess

    to t

    he u

    nit

    cont

    rol

    cent

    er a

    ssum

    es t

    he u

    nit

    is n

    o hi

    gher

    tha

    n on

    spr

    ing

    isol

    ator

    s. R

    ecom

    men

    ded

    min

    imum

    cle

    aran

    ces:

    Sid

    e to

    wal

    l - 2

    m;

    rear

    to

    wal

    l - 2

    m;

    cont

    rol p

    anel

    to

    end

    wal

    l -1.

    2m;

    top

    - no

    obs

    truc

    tions

    allo

    wed

    ; di

    stan

    ce b

    etw

    een

    adja

    cent

    uni

    ts -

    3m

    . N

    o m

    ore

    than

    one

    adj

    acen

    t w

    all

    may

    be

    high

    er th

    an u

    nit.

  • 29

    DIMENSIONS

    YCA 80 50Hz & 60HzN

    ote:

    Pla

    cem

    ent

    on a

    lev

    el s

    urfa

    ce o

    f fr

    ee o

    f ob

    stru

    ctio

    ns(in

    clud

    ing

    snow

    , fo

    r w

    inte

    r op

    erat

    ion)

    or

    air

    circ

    ulat

    ion

    ensu

    res

    rate

    d pe

    rfor

    man

    ce, r

    elia

    ble

    oper

    atio

    n, a

    nd e

    ase

    of

    ma

    inte

    na

    nce

    . S

    ite r

    est

    rict

    ion

    s m

    ay

    com

    pro

    mis

    em

    inim

    um

    cle

    ara

    nce

    s in

    dic

    ate

    d b

    elo

    w,

    resu

    ltin

    g i

    nun

    pred

    icta

    ble

    airf

    low

    pat

    tern

    s an

    d po

    ssib

    le d

    imin

    ishe

    dpe

    rfor

    man

    ce. Y

    OR

    Ks

    uni

    t con

    trol

    s w

    ill o

    ptim

    ize

    oper

    atio

    nw

    ithou

    t nui

    sanc

    e hi

    gh-p

    ress

    ure

    safe

    ty c

    utou

    ts; h

    owev

    er,

    the

    sy

    ste

    m

    de

    sig

    ne

    r m

    ust

    co

    nsi

    de

    r p

    ote

    nti

    al

    perf

    orm

    ance

    deg

    rada

    tion.

    Acc

    ess

    to t

    he u

    nit

    cont

    rol

    cent

    er a

    ssum

    es t

    he u

    nit

    is n

    o hi

    gher

    tha

    n on

    spr

    ing

    isol

    ator

    s. R

    ecom

    men

    ded

    min

    imum

    cle

    aran

    ces:

    Sid

    e to

    wal

    l - 2

    m;

    rear

    to

    wal

    l - 2

    m;

    cont

    rol p

    anel

    to

    end

    wal

    l -1.

    2m;

    top

    - no

    obs

    truc

    tions

    allo

    wed

    ; di

    stan

    ce b

    etw

    een

    adja

    cent

    uni

    ts -

    3m

    . N

    o m

    ore

    than

    one

    adj

    acen

    t w

    all

    may

    be

    high

    er th

    an u

    nit.

  • 30

    DIMENSIONS

    YCA 95 50Hz

    Not

    e:P

    lace

    men

    t on

    a l

    evel

    sur

    face

    of

    free

    of

    obst

    ruct

    ions

    (incl

    udin

    g sn

    ow,

    for

    win

    ter

    oper

    atio

    n) o

    r ai

    r ci

    rcul

    atio

    nen

    sure

    s ra

    ted

    perf

    orm

    ance

    , rel

    iabl

    e op

    erat

    ion,

    and

    eas

    eo

    f m

    ain

    ten

    an

    ce.

    Site

    re

    stri

    ctio

    ns

    ma

    y co

    mp

    rom

    ise

    min

    imu

    m c

    lea

    ran

    ces

    ind

    ica

    ted

    be

    low

    , re

    sulti

    ng

    in

    unpr

    edic

    tabl

    e ai

    rflo

    w p

    atte

    rns

    and

    poss

    ible

    dim

    inis

    hed

    pe

    rfo

    rma

    nce

    . Y

    OR

    Ks

    un

    it c

    on

    tro

    ls w

    i l l o

    pti

    miz

    eop

    erat

    ion

    with

    out n

    uisa

    nce

    high

    -pre

    ssur

    e sa

    fety

    cut

    outs

    ;ho

    wev

    er,

    the

    syst

    em d

    esig

    ner

    mus

    t co

    nsid

    er p

    oten

    tial

    perf

    orm

    ance

    deg

    rada

    tion.

    Acc

    ess

    to t

    he u

    nit

    cont

    rol

    cent

    er a

    ssum

    es t

    he u

    nit

    is n

    o hi

    gher

    tha

    n on

    spr

    ing

    isol

    ator

    s. R

    ecom

    men

    ded

    min

    imum

    cle

    aran

    ces:

    Sid

    e to

    wal

    l - 2

    m;

    rear

    to

    wal

    l - 2

    m;

    cont

    rol p

    anel

    to

    end

    wal

    l -1.

    2m;

    top

    - no

    obs

    truc

    tions

    allo

    wed

    ; di

    stan

    ce b

    etw

    een

    adja

    cent

    uni

    ts -

    3m

    . N

    o m

    ore

    than

    one

    adj

    acen

    t w

    all

    may

    be

    high

    er th

    an u

    nit.

  • 31

    DIMENSIONS

    YCA 95 60Hz

    Not

    e:P

    lace

    men

    t on

    a l

    evel

    sur

    face

    of

    free

    of

    obst

    ruct

    ions

    (incl

    udin

    g sn

    ow,

    for

    win

    ter

    oper

    atio

    n) o

    r ai

    r ci

    rcul

    atio

    nen

    sure

    s ra

    ted

    perf

    orm

    ance

    , rel

    iabl

    e op

    erat

    ion,

    and

    eas

    eo

    f m

    ain

    ten

    an

    ce.

    Site

    re

    stri

    ctio

    ns

    ma

    y co

    mp

    rom

    ise

    min

    imu

    m c

    lea

    ran

    ces

    ind

    ica

    ted

    be

    low

    , re

    sulti

    ng

    in

    unpr

    edic

    tabl

    e ai

    rflo

    w p

    atte

    rns

    and

    poss

    ible

    dim

    inis

    hed

    pe

    rfo

    rma

    nce

    . Y

    OR

    Ks

    un

    it c

    on

    tro

    ls w

    i l l o

    pti

    miz

    eop

    erat

    ion

    with

    out n

    uisa

    nce

    high

    -pre

    ssur

    e sa

    fety

    cut

    outs

    ;ho

    wev

    er,

    the

    syst

    em d

    esig

    ner

    mus

    t co

    nsid

    er p

    oten

    tial

    perf

    orm

    ance

    deg

    rada

    tion.

    Acc

    ess

    to t

    he u

    nit

    cont

    rol

    cent

    er a

    ssum

    es t

    he u

    nit

    is n

    o hi

    gher

    tha

    n on

    spr

    ing

    isol

    ator

    s. R

    ecom

    men

    ded

    min

    imum

    cle

    aran

    ces:

    Sid

    e to

    wal

    l - 2

    m;

    rear

    to

    wal

    l - 2

    m;

    cont

    rol p

    anel

    to

    end

    wal

    l -1.

    2m;

    top

    - no

    obs

    truc

    tions

    allo

    wed

    ; di

    stan

    ce b

    etw

    een

    adja

    cent

    uni

    ts -

    3m

    . N

    o m

    ore

    than

    one

    adj

    acen

    t w

    all

    may

    be

    high

    er th

    an u

    nit.

  • 32

    DIMENSIONS

    YCA 115 50Hz & 60Hz

    Not

    e:P

    lace

    men

    t on

    a l

    evel

    sur

    face

    of

    free

    of

    obst

    ruct

    ions

    (incl

    udin

    g sn

    ow,

    for

    win

    ter

    oper

    atio

    n) o

    r ai

    r ci

    rcul

    atio

    nen

    sure

    s ra

    ted

    perf

    orm

    ance

    , rel

    iabl

    e op

    erat

    ion,

    and

    eas

    eo

    f m

    ain

    ten

    an

    ce.

    Site

    re

    stri

    ctio

    ns

    ma

    y co

    mp

    rom

    ise

    min

    imu

    m c

    lea

    ran

    ces

    ind

    ica

    ted

    be

    low

    , re

    sulti

    ng

    in

    unpr

    edic

    tabl

    e ai

    rflo

    w p

    atte

    rns

    and

    poss

    ible

    dim

    inis

    hed

    pe

    rfo

    rma

    nce

    . Y

    OR

    Ks

    un

    it c

    on

    tro

    ls w

    i l l o

    pti

    miz

    eop

    erat

    ion

    with

    out n

    uisa

    nce

    high

    -pre

    ssur

    e sa

    fety

    cut

    outs

    ;ho

    wev

    er,

    the

    syst

    em d

    esig

    ner

    mus

    t co

    nsid

    er p

    oten

    tial

    perf

    orm

    ance

    deg

    rada

    tion.

    Acc

    ess

    to t

    he u

    nit

    cont

    rol

    cent

    er a

    ssum

    es t

    he u

    nit

    is n

    o hi

    gher

    tha

    n on

    spr

    ing

    isol

    ator

    s. R

    ecom

    men

    ded

    min

    imum

    cle

    aran

    ces:

    Sid

    e to

    wal

    l - 2

    m;

    rear

    to

    wal

    l - 2

    m;

    cont

    rol p

    anel

    to

    end

    wal

    l -1.

    2m;

    top

    - no

    obs

    truc

    tions

    allo

    wed

    ; di

    stan

    ce b

    etw

    een

    adja

    cent

    uni

    ts -

    3m

    . N

    o m

    ore

    than

    one

    adj

    acen

    t w

    all

    may

    be

    high

    er th

    an u

    nit.

  • 33

    MODEL: YCA 20 / 50

    SPRING LOCATIONS

    MODELISOLATOR MODEL/POINT LOAD CENTRE OF GRAVITY (IN)

    A B C D X1 X2 Y1 Y2 Z

    AL/HYP250kg 219kg 240kg 209kg 28 32 48 50 20FIN

    TRS-C1-900i TRS-C1-750 TRS-C1-750 TRS-C1-650YCA 20

    (918kg)COPPER

    277kg 242kg 266kg 233kg 28 32 48 50 18FINTRS-C1-900i TRS-C1-900i TRS-C1-900i TRS-C1-750(1018kg)

    AL/HYP256kg 232kg 245kg 222kg 28 32 48 50 20FIN

    TRS-C1-900i TRS-C1-750 TRS-C1-900i TRS-C1-750YCA 25

    (955kg)COPPER

    294kg 257kg 282kg 247kg 28 32 48 50 18FINTRS-C1-900i TRS-C1-900i TRS-C1-900i TRS-C1-900i(1080kg)

    AL/HYP436kg 298kg 428kg 292kg 30 44 53 54 20FIN

    TRS-C1-1260i TRS-C1-900i TRS-C1-1260i TRS-C1-900iYCA 30

    (1454kg)COPPER

    496kg 338kg 488kg 332kg 30 44 53 54 18FINTRS-C1-1470 TRS-C1-1040 TRS-C1-1470 TRS-C1-1040(1654kg)

    AL/HYP464kg 316kg 454kg 311kg 30 44 53 54 20FIN

    TRS-C1-1260i TRS-C1-900i TRS-C1-1260i TRS-C1-900iYCA 40

    (1545kg)COPPER

    531kg 362kg 522kg 355kg 30 44 53 54 18FINTRS-C1-1470 TRS-C1-1040 TRS-C1-1470 TRS-C1-1040(1770kg)

    AL/HYP494kg 336kg 484kg 331kg 30 44 53 54 20FIN

    TRS-C1-1470 TRS-C1-1040 TRS-C1-1470 TRS-C1-1040YCA 50

    (1645kg)COPPER

    751kg 512kg 737kg 502kg 30 44 53 54 20FINTRS-C1-1880i TRS-C1-1470 TRS-C1-1880i TRS-C1-1470(2502kg)

    X1

    CG

    BA

    C

    Y

    Z X

    D

    CO

    NT

    RO

    L P

    AN

    EL

    X2

    Y1

    Y2

  • 34

    SPRING LOCATIONS (Continued)

    MODELISOLATOR MODEL/POINT LOAD CENTRE OF GRAVITY (IN)

    A B C D X1 X2 Y1 Y2 Z

    AL/HYP723 kg 692kg 579kg 553kg 44 46 40 50 28FIN

    TRS-C1-1880i TRS-C1-1880i TRS-C1-1470 TRS-C1-1470YCA 60

    (2547kg)COPPER

    801kg 766kg 641kg 613kg 44 46 40 50 26FINTRS-C1-2080i TRS-C1-1880i TRS-C1-1720i TRS-C1-1720i2821(kg)

    AL/HYP789kg 755kg 632kg 604kg 44 46 40 50 29FIN

    TRS-C1-1880i TRS-C1-1880i TRS-C1-1720i TRS-C1-1720iYCA 70

    (2780kg)COPPER

    891kg 853kg 713kg 682kg 44 46 40 50 27FINTRS-C1-2080i TRS-C1-2080i TRS-C1-1720i TRS-C1-1720i(3139kg)

    MODEL: YCA 60 / 70

    MODELISOLATOR MODEL/POINT LOAD CENTRE OF GRAVITY (IN)

    A B C D X1 X2 Y1 Y2 Z

    AL/HYP782 kg 818kg 626kg 654kg 46 44 40 50 29FIN

    TRS-C1-1880i TRS-C1-2080i TRS-C1-1720i TRS-C1-1720iYCA 80

    (2880kg)COPPER

    880kg 920kg 703kg 736kg 46 44 40 50 27FINTRS-C1-2080 TRS-C1-2330 TRS-C1-1720i TRS-C1-1720i(3239kg)

    MODEL: YCA 80

    X1 X2

    Y1

    Y2

    CG

    A B

    DC

    CO

    NT

    RO

    L P

    AN

    EL

    Y

    Z X

    X1

    Y1

    Y2

    X2

    CG

    A B

    DC

    CO

    NT

    RO

    L P

    AN

    EL

    Y

    Z X

  • 35

    MODELISOLATOR MODEL/POINT LOAD CENTRE OF GRAVITY (IN)

    A B C D X1 X2 Y1 Y2 Z

    AL/HYP 1094 1026 1094 1026 60 64 45 45 30FIN TRS-C1-2510 TRS-C1-2510 TRS-C1-2510 TRS-C1-2510YCA 95

    4240COPPER

    1223 1147 1222 1147 60 64 45 45 28FINTRS-C2-2940 TRS-C2-2940 TRS-C2-2940 TRS-C2-29404739

    AL/HYP1223 1147 1223 1147 60 64 45 45 32FIN

    TRS-C2-2940 TRS-C2-2940 TRS-C2-2940 TRS-C2-2940YCA 115

    4740COPPER

    1246 1169 1246 1169 60 64 45 45 30FINTRS-C2-2940 TRS-C2-2940 TRS-C2-2940 TRS-C2-29404830

    MODEL: YCA 95 / 115

    SPRING LOCATIONS (Continued)

    X1 X2

    Y1

    Y2

    CG

    A B

    C D

    CO

    NT

    RO

    L P

    AN

    EL

    Y

    Z X

  • 36

    SPRING LOCATIONS (Continued)

    MODEL DIMENSION (MM)L W C M N T LS SW

    TRS-C1 225 90 195 170 90 16 5/8 12.5BSW

    TRS-C2 300 90 270 245 90 16 5/8 12.5BSW

  • 37

    NOTES:1. Minimum Circuit Ampacity (MCA) is based on

    125% of the rated load amps for the largestmotor plus 100% of the rated load amps for allother loads included in the circuit. Add the followingMCA values to the electrical tables for the systemproviding power to the transformer: 460V/3ph/60Hz, add 1.3 amps; 380-415/3ph/50Hz, add1.75 amps.

    2. Minimum fuse size is based upon 150% of therated load amps for the largest motor plus 100%of the rated load amps for all other loads includedin the circuit to avoid nuisance trips at start-updue to lock rotor amps. It is not recommendedin applications where brown outs, frequent startingand stopping of the unit, and/or operation atambient temperatures in excess of 35C(95F) is anticipated.

    3. Maximum fuse size is based upon 225% of therated load amps for the largest motor plus 100%of the rated load amps for all other loads includedin the circuit.

    ELECTRICAL NOTES

    4. The minimum recommended disconnect switchis based on 115% of the rated load amps for allloads included in the circuit.

    5. Circuit breakers must be UL listed and CSAcertified and maximum size is based on 225%of the rated load amps for the largest motor plus100% of the rated load amps for all other loadsincluded in the circuit.

    6. A ground lug is provided for each compressorsystem to accommodate a field groundingconductor. A control circuit grounding lug is alsosupplied.

    7. The supplied disconnect is a DisconnectingMeans and is intended for isolating the unit for theavailable power supply to perform maintenanceand troubleshooting. This disconnect is not intendedto be a Load Break Device.

    8. Field Wiring by others which complies to theNational Electrical Code & Local Codes.

    ELECTRICAL DATA

    STANDARD POWER CONNECTIONSYCA 20-115 - R22/50Hz

    FIELD SUPPLIED WIRING

    MODEL VOLT Hz MCA MIN N/F D.E FUSE CKT.BKR.

    YCA DISC SW MIN MAX MAX

    20 380/415 50 46 50 50 75 7525 380/415 50 60 75 75 100 10030 380/415 50 77 100 100 125 12540 380/415 50 86 100 100 125 12550 380/415 50 117 150 125 150 15060 380/415 50 125 150 150 150 15070 380/415 50 166 200 175 200 20080 380/415 50 177 200 200 225 22595 380/415 50 212 250 225 250 250115 380/415 50 260 300 300 300 300

    SYSTEM # 1 COMPRESSOR & FAN

    COMPR. # 1 COMPR. # 2 COMPR. # 3 FANS

    RLA LRA RLA LRA RLA LRA QTY RLA(EA)17.1 167 17.1 167 - - 3 1.8323.6 198 23.6 198 - - 3 1.8329.6 225 29.6 225 - - 2 4.217.1 167 17.1 167 - - 1 5.623.6 198 23.6 198 - - 1 7.417.1 167 17.1 167 17.1 167 2 4.223.6 198 23.6 198 23.6 198 2 4.236.0 250 36.0 250 - - 2 5.629.6 225 29.6 225 29.6 225 3 4.236.0 250 36.0 250 36.0 250 3 5.6

    LEGEND VOLTAGE- 380-415/3/50HZ

    CKT.BKR. Circuit BreakerD.E. Dual Element FuseDISC SW Disconnect SwitchHZ HertzMAX MaximumMCA Minimum Circuit AmpacityMIN MinimumMIN NF Minimum Non FusedRLA Rated Load AmpsLRA Locked Rotor Amps

    SYSTEM # 2 COMPRESSOR & FAN

    COMPR. # 1 COMPR. # 2 COMPR. # 3 FANS

    RLA LRA RLA LRA RLA LRA QTY RLA(EA)- - - - - - - -- - - - - - - -- - - - - - - -

    17.1 167 17.1 167 - - 1 5.623.6 198 23.6 198 - - 1 7.417.1 167 17.1 167 17.1 167 2 4.223.6 198 23.6 198 23.6 198 2 4.236.0 250 36.0 250 - - 2 5.629.6 225 29.6 225 29.6 225 3 4.236.0 250 36.0 250 36.0 250 3 5.6

  • 38

    ELECTRICAL DATA

    YCA 20-115 - R22/60Hz

    SYSTEM # 1 COMPRESSOR & FAN

    COMPR. # 1 COMPR. # 2 COMPR. # 3 FANS

    RLA LRA RLA LRA RLA LRA QTY RLA(EA)

    16.3 125 16.3 125 - - 3 1.8317.1 167 17.1 167 - - 3 1.8323.6 198 23.6 198 - - 2 5.9430.6 225 30.6 225 - - 1 5.9417.1 167 17.1 167 - - 1 10.123.6 198 23.6 198 - - 2 5.9417.1 167 17.1 167 17.1 167 2 5.9430.6 225 30.6 225 - - 2 5.9436.7 250 36.7 250 - - 3 4.1830.6 225 30.6 225 30.6 225 3 5.94

    LEGEND VOLTAGE- 460V/60HZ

    CKT.BKR. Circuit BreakerD.E. Dual Element FuseDISC SW Disconnect SwitchHZ HertzMAX MaximumMCA Minimum Circuit AmpacityMIN MinimumMIN NF Minimum Non FusedRLA Rated Load AmpsLRA Locked Rotor Amps

    SYSTEM # 2 COMPRESSOR & FAN

    COMPR. # 1 COMPR. # 2 COMPR. # 3 FANS

    RLA LRA RLA LRA RLA LRA QTY RLA(EA)

    16.3 125 16.3 125 - - - -17.1 167 17.1 167 - - - -23.6 198 23.6 198 - - - -30.6 225 30.6 225 - - 1 5.9417.1 167 17.1 167 - - 1 10.123.6 198 23.6 198 - - 2 5.9417.1 167 17.1 167 17.1 167 2 5.9430.6 225 30.6 225 - - 2 5.9436.7 250 36.7 250 - - 3 4.1830.6 225 30.6 225 30.6 225 3 5.94

    YCA 20-115 - R407C/50Hz

    SYSTEM # 1 COMPRESSOR & FAN

    COMPR. # 1 COMPR. # 2 COMPR. # 3 FANS

    RLA LRA RLA LRA RLA LRA QTY RLA(EA)

    20.7 167 20.7 167 - - 3 1.8324.5 198 24.5 198 - - 3 1.8329.5 225 29.5 225 - - 2 4.220.7 167 20.7 167 - - 1 5.624.5 198 24.5 198 - - 1 7.420.7 167 20.7 167 20.7 167 2 4.224.5 198 24.5 198 24.5 198 2 4.235.7 250 35.7 250 - - 2 5.629.5 225 29.5 225 29.5 225 3 4.235.7 250 35.7 250 35.7 250 3 5.6

    LEGEND VOLTAGE- 460V/60HZ

    CKT.BKR. Circuit BreakerD.E. Dual Element FuseDISC SW Disconnect SwitchHZ HertzMAX MaximumMCA Minimum Circuit AmpacityMIN MinimumMIN NF Minimum Non FusedRLA Rated Load AmpsLRA Locked Rotor Amps

    SYSTEM # 2 COMPRESSOR & FAN

    COMPR. # 1 COMPR. # 2 COMPR. # 3 FANS

    RLA LRA RLA LRA RLA LRA QTY RLA(EA)- - - - - - - -- - - - - - - -- - - - - - - -

    20.7 167 20.7 167 - - 1 5.624.5 198 24.5 198 - - 1 7.420.7 167 20.7 167 20.7 167 2 4.224.5 198 24.5 198 24.5 198 2 4.235.7 250 35.7 250 - - 2 5.629.5 225 29.5 225 29.5 225 3 4.235.7 250 35.7 250 35.7 250 3 5.6

    FIELD SUPPLIED WIRING

    MODEL VOLT Hz MCA MIN N/F D.E FUSE CKT.BKR.

    YCA DISC SW MIN MAX MAX20 460 60 43 50 50 60 6025 460 60 45 50 50 75 5030 460 60 66 75 75 100 10040 460 60 82 100 100 125 12550 460 60 94 125 100 125 12560 460 60 125 150 150 150 15070 460 60 132 150 150 150 15080 460 60 155 175 175 200 20090 460 60 182 200 200 225 225115 460 60 228 300 250 300 300

    FIELD SUPPLIED WIRING

    MODEL VOLT Hz MCA MIN N/F D.E FUSE CKT.BKR.

    YCA DISC SW MIN MAX MAX20 380/415 50 54 60 60 75 7525 380/415 50 62 75 75 100 10030 380/415 50 77 100 100 125 12540 380/415 50 101 125 125 125 12550 380/415 50 121 150 150 150 15060 380/415 50 148 175 175 175 17570 380/415 50 172 200 200 200 20080 380/415 50 176 200 200 225 22595 380/415 50 211 250 225 250 250115 380/415 50 258 300 300 300 300

  • 39

    ELECTRICAL DATA

    YCA 20-115 - R407C/60Hz

    SYSTEM # 1 COMPRESSOR & FAN

    COMPR. # 1 COMPR. # 2 COMPR. # 3 FANS

    RLA LRA RLA LRA RLA LRA QTY RLA(EA)

    17 125 17 125 - - 3 1.8320.7 167 20.7 167 - - 3 1.8324.5 198 24.5 198 - - 2 5.9430.7 225 30.7 225 - - 1 5.9420.7 167 20.7 167 - - 1 10.124.5 198 24.5 198 - - 2 5.9420.7 167 20.7 167 20.7 167 2 5.9430.7 225 30.7 225 - - 2 5.9437.2 250 37.2 250 - - 3 4.1830.7 225 30.7 225 30.7 225 3 5.94

    LEGEND VOLTAGE- 460V/60HZ

    CKT.BKR. Circuit BreakerD.E. Dual Element FuseDISC SW Disconnect SwitchHZ HertzMAX MaximumMCA Minimum Circuit AmpacityMIN MinimumMIN NF Minimum Non FusedRLA Rated Load AmpsLRA Locked Rotor Amps

    SYSTEM # 2 COMPRESSOR & FAN

    COMPR. # 1 COMPR. # 2 COMPR. # 3 FANS

    RLA LRA RLA LRA RLA LRA QTY RLA(EA)- - - - - - - -- - - - - - - -- - - - - - - -

    30.7 225 30.7 225 - - 1 5.9420.7 167 20.7 167 - - 1 10.124.5 198 24.5 198