UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051 + Model pp. 1–12 (col. fig: NIL)
ARTICLE IN PRESS
Engineering Structures xx (xxxx) xxx–xxxwww.elsevier.com/locate/engstruct
Experimental validation of seismic code provisions for RC columns
Elizabeth Vintzileou∗, T.P. Tassios, M. Chronopoulos
National Technical University of Athens, Greece
Received 20 March 2006; received in revised form 20 July 2006; accepted 21 August 2006
Abstract
The aim of the experimental programme was to check the validity of the provisions of Eurocode 8 regarding the confining reinforcement ofcolumns. Cyclic tests on 37 full-scale specimens were subjected to large cyclic displacements under constant axial load. Single rectangular hoops,even closely spaced, proved to be inadequate, as in most cases the target ductility was not reached. On the contrary, double or triple arrangementof hoops ensured satisfactory behaviour; they ensured acceptable force response degradation (lower than 20%), when the columns were subject tolarge displacement reversals (compatible with the target ductility).c© 2006 Published by Elsevier Ltd
Keywords: RC columns; Confinement; Cyclic actions; Force–response degradation; Ductility
1. Introduction1
According to Eurocode 8 (2004), the confining reinforce-2
ment that should be provided within the critical regions of3
columns is calculated as a function of several parameters, such4
as the normalized axial force (ν), the in-section and in-height5
arrangement of hoops, the confined part of the section as a6
percentage of the gross cross sectional area (Ac/A0), etc. The7
volumetric mechanical percentage of hoops, ωw, calculated ac-8
cording to the code, is assumed to provide to the column a9
corresponding value of curvature ductility factor, µ1/r . The10
value of the required curvature ductility factor depends on the11
ductility class to which the structure should belong. A value12
for the required curvature ductility factor µ1/r = 10 corre-13
sponds roughly to the Medium Ductility Class according to Eu-14
rocode 8.15
Following the definition of the code, a column is considered16
to behave satisfactorily under the following conditions: (a) the17
column is able to sustain displacement reversals at a maximum18
value compatible with the target ductility and (b) after three full19
reversals, the force response degradation of the column does not20
exceed 15% of its maximum resistance.21
∗ Corresponding address: Laboratory of Reinforced Concrete, NationalTechnical University of Athens, 5, Iroon Polytechniou Str., 15773 Zografou,Greece. Tel.: +30 210 7721272; fax: +30 210 7721273.
E-mail address: [email protected] (E. Vintzileou).
In the Laboratory of Reinforced Concrete at National 22
Technical University of Athens (NTUA), an extensive 23
experimental programme was carried out with the aim of 24
checking whether the behaviour of columns reinforced in 25
accordance with the code requirements is in conformity with 26
the anticipated behaviour. 27
Thirty-seven (37) full-scale columns were tested in cyclic 28
shear and bending, under constant axial load. In this paper, the 29
results of this programme are presented and commented upon, 30
whereas the efficiency of relevant code provisions is assessed. 31
2. The confinement model used 32
(a) The model for confinement adopted by Eurocode 8, 33
based on the model presented in Tassios et al. [2], is valid 34
for symmetrically reinforced sections, where the curvature at 35
yield is expressed in terms of the normalized axial force (ν) of 36
the element and the percentage of longitudinal reinforcement 37
(ρ), taking into account the degree of mobilization of the 38
compressed longitudinal reinforcement (σs/ fy ≤ 1.0, where 39
σs and fy denote the stress and the yield strength of the 40
compressed reinforcement). For the calculation of the curvature 41
at yield, the following assumptions were made in the model: (i) 42
the part of the concrete section that is not enclosed by the hoops 43
has spalled, (ii) the properties of the confined concrete of the 44
core follows the model adopted by CEB-FIP Model Code 1990, 45
(iii) the percentage of the longitudinal reinforcement is taken 46
0141-0296/$ - see front matter c© 2006 Published by Elsevier Ltddoi:10.1016/j.engstruct.2006.08.013
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013
UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051
ARTICLE IN PRESS2 E. Vintzileou et al. / Engineering Structures xx (xxxx) xxx–xxx
equal to 0.04 (the maximum allowed by the code), whereas1
(iv) both tensioned and compressed longitudinal reinforcement2
are assumed to have entered into the hardening branch of3
the stress–strain curve. Thus, an expression was derived for4
the effective confinement ratio (αωw) needed both to ensure5
sufficient curvature ductility and that the section will be able6
to carry the imposed design action effects after spalling of the7
concrete cover:8
αωw = k0µ1/rεyλν − 10εcu (1)9
where:10
ωw denotes the volumetric mechanical ratio of confining11
reinforcement (closed hoops and ties),12
α denotes the effectiveness of confinement, i.e. an indicator13
of the volume of the core that is effectively confined by hoops14
and ties,15
µ1/r denotes the targeted curvature ductility factor,16
εy denotes the yield strain of the steel,17
ν denotes the normalized axial force of the element, ν =18
N/Ac fc,19
λ = Ac/A0 denotes the gross cross sectional area20
normalized to the core section,21
εcu = 0.0035 is the strain at failure of the unconfined22
concrete and23
k0 is a coefficient depending on the ‘ductility class’ which24
was adopted for the design of the entire structure. In the final25
text of Eurocode 8, a value k0 = 30 was adopted for both26
ductility classes.27
(b) Moreover, EC8 requires that a minimum ωw-value is28
observed, equal to 0.08 or 0.12, for medium and high ductility29
class; this may roughly be translated into a minimum ‘αωw’30
requirement equal to 0.05, approximately.31
Finally, according to the code, spacings ‘s’ of consec-32
utive hoops should nor exceed specific maximum values33
(max s: db = 8, for medium ductility class, where ‘db’ denotes34
the diameter of longitudinal reinforcement).35
It is understood that these two additional requirements had36
the meaning that the analytical model of Eq. (1) is not valid37
unless both of these conditions are observed.38
3. Research objectives39
It is broadly accepted that confinement offers a more40
ductile behaviour to RC columns under post-yield reversed41
displacement [see i.a. [4–7]]. Such behaviour, however, is42
influenced by a large number of (at least five) parameters,43
as mentioned in the previous Section 2. Consequently,44
experimental research accounting simultaneously for such a45
large number of parameters is rather scarce. That is why the46
combination of available experimental data, taking into account47
only a limited number of parameters each time, is not an48
easy task. Since the model adopted in EC8 (Eq. (1)) was only49
analytically derived, the basic scope of this paper is to attempt50
an experimental overall check of the validity of the provisions51
of the Code, as follows:52
(a) By means of a large variety of combination of the53
aforementioned parameters, the validity of Eq. (1) will be54
experimentally checked, as explained in Section 4(b): checking 55
the ‘cyclic stability’ of force–response, after three full cycles at 56
the targeted ductility level. To this end, 37 different full-scale 57
columns were tested under identical experimental conditions. 58
(b) On the other hand, the validity of the two minimal 59
requirements of EC8 will also be checked, namely the 60
minimum ωw-values and the minimum (s/db)-values, as 61
explained in Section 2(b). 62
4. Description of the research programme 63
Specimens and tests were designed as follows: 64
(a) Several parameters affecting confinement were selected 65
for investigation, namely the in-section arrangement (the 66
format) of hoops, the diameter of hoops, the spacing of hoops 67
and the ratio between the gross cross-sectional area and the 68
core area of the column. To a number of specimens, the simple 69
square arrangement of hoops was applied, although the rule of 70
not having hoops legs arranged at a distance larger than 200 mm 71
from each other is not respected in this case. This arrangement 72
of hoops was tested, because in real structures, a large number 73
of columns (especially, corner columns in upper storeys) are 74
having sectional dimensions not larger than 300 mm. 75
It should be noted that the specimens were designed to fail 76
in flexure. 77
(b) Each specimen was allotted a target curvature ductility 78
factor ranging between 7 and 13 (see Table 1), whereas 79
the effective confinement ratio, αωw, and the Ac/A0 ratio 80
were predetermined. Thus, introducing the appropriate values 81
of the various parameters in Eq. (1), the maximum axial 82
load was calculated for each specimen, for which the target 83
curvature ductility factor can be reached. This axial force 84
value was imposed on each specimen during testing. Thus, all 85
code-conditions being respected, the cyclic stability of each 86
specimen was tested experimentally. In other words, it was to be 87
checked whether the specimens being reinforced and loaded in 88
conformity with the code and submitted to the target ductility, 89
show a force response degradation not exceeding 15% after 90
three full reversals. This is a final and comprehensive check of 91
the validity of code provisions in a multi-parameter field. 92
The maximum displacement ‘dmax’ to apply in correspon- 93
dence with the targeted ductilities µ1/r were calculated as fol- 94
lows: assuming a nominal value for the expected length of the 95
plastic hinge (equal to approximately 10% of the length of the 96
element), the mean dmax/dy-values corresponding to these cur- 97
vature ductility factors were calculated: 98
µ1/r = 7 − dmax/dy ∼ 3.0, µ1/r = 10 − dmax/dy ∼ 4.0, 99
µ1/r = 13 − dmax/dy ∼ 5.0. 100
(c) The geometry of specimens tested within this programme 101
is shown in Fig. 1: specimens were 3.0 m long. The cross- 102
sectional dimensions were 250 × 250 [mm]. The specimen 103
is meant to simulate two cantilever columns fixed to a stiff, 104
heavily reinforced element 500×500 [mm]. It should be noted, 105
however, that in a real column fixed at floor level, horizontal 106
displacements due to an earthquake would generate tension (or 107
compression) to toe ‘A’ of the upper column and compression 108
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013
UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051
ARTICLE IN PRESSE. Vintzileou et al. / Engineering Structures xx (xxxx) xxx–xxx 3
Table 1Combination of parameters
In-sectionarrangementof hoops
Specimennumber
Diameterand spacingof hoops
Qualityofsteel(hoops)
Targetcurvatureductilityµ1/r
effectiveness ofconfinementα = αnαs
Effectiveconfinementratio αωw
Ac/A0 AxialforceN (kN)
Normalizedaxial force ν
1 ∅6/100 S220 10 0.19 0.01 1.42 50 0.022 2∅10/50 S220 10 0.26 0.14 1.42 450 0.183 ∅6/100 S220 10 0.18 0.01 1.64 50 0.024 ∅8/75 S220 10 0.22 0.03 1.64 200 0.086 ∅6/100 S220 10 0.18 0.01 1.83 20 0.017 2∅10/50 S220 10 0.25 0.15 1.83 840 0.348 ∅8/50 S220 13 0.25 0.05 1.64 100 0.049 ∅8/100 S220 10 0.19 0.02 1.42 290 0.1210 ∅8/100 S400 10 0.18 0.02 1.83 90 0.0411 ∅6/100 S220 10 0.19 0.01 1.42 221 0.0912 ∅8/125 S220 10 0.16 0.01 1.42 30 0.0113 ∅8/125 S220 10 0.15 0.01 1.79 26 0.0114 ∅6/100 S220 10 0.18 0.01 1.83 193 0.0815 ∅8/125 S220 10 0.15 0.01 1.83 25 0.01
16 ∅6/100 S220 10 0.39 0.03 1.42 100 0.0417 ∅8/75 S220 10 0.45 0.09 1.42 335 0.1318 ∅10/50 S220 10 0.52 0.23 1.42 700 0.2819 ∅6/100 S220 10 0.37 0.03 1.64 80 0.0320 ∅8/75 S220 10 0.44 0.09 1.64 419 0.1721 ∅10/50 S220 10 0.51 0.24 1.64 727 0.2922 ∅6/100 S220 10 0.36 0.03 1.83 80 0.0323 ∅8/75 S220 10 0.42 0.09 1.83 391 0.1624 ∅10/50 S220 10 0.50 0.25 1.83 699 0.2825 ∅8/75 S220 13 0.44 0.09 1.64 391 0.1626 ∅8/50 S220 7 0.52 0.15 1.42 1063 0.4327 ∅8/50 S220 7 0.51 0.16 1.64 690 0.2828 ∅8/50 S220 7 0.50 0.16 1.83 727 0.2929 ∅8/100 S400 10 0.39 0.07 1.42 391 0.1630 ∅8/100 S400 10 0.36 0.07 1.83 273 0.11
31 ∅6/100 S220 10 0.45 0.04 1.42 335 0.1332 ∅10/50 S220 10 0.60 0.32 1.42 913 0.3733 ∅6/100 S220 10 0.43 0.04 1.64 130 0.0534 ∅8/75 S220 10 0.51 0.12 1.64 475 0.1935 ∅10/50 S220 10 0.59 0.33 1.64 1006 0.4036 ∅6/100 S220 10 0.41 0.04 1.83 120 0.0537 ∅10/50 S220 10 0.58 0.35 1.83 1062 0.4238 ∅8/50 S220 13 0.59 0.21 1.64 600 0.24
Specimen No 5 was defective; it was not tested.
(or tension) respectively to toe ‘A’ of the lower column. In1
the case of specimens tested within this programme, however,2
tensioned (or compressed) zones of upper and lower column3
coincide. On the other hand, longitudinal reinforcements in4
the specimens were continuous throughout the toe, without5
lap splices; such an experimental set up does not allow a free6
pullout of bars to contribute to plastic rotations. Consequently,7
this testing arrangement will give rather conservative results.8
However, the magnitude of all action effects (axial load,9
bending moment and shear force) was the same as for a real10
double half-column subassembly.11
In the same Fig. 1, one can see the arrangement of both12
longitudinal and transverse reinforcement, as well as the testing13
sequence: the specimen is pinned at both ends. The axial load14
is applied (up to a predetermined value) and held constant15
during testing. At mid-height of the column (at ‘floor’ level)16
horizontal cyclic displacements are imposed, by means of a 17
500 kN actuator. 18
5. Construction of specimens—materials 19
5.1. Construction 20
Reinforcement cages were mounted and placed in the 21
wooden moulds. Strain gauges were glued on several 22
longitudinal bars and on hoops within the critical regions of 23
columns (Fig. 2). Ready mixed concrete was used for the 24
construction of the specimens in horizontal position. Specimens 25
were cured wet for seven days. Subsequently, they were stored 26
in the Laboratory up to their testing, without any further curing. 27
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013
UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051
ARTICLE IN PRESS4 E. Vintzileou et al. / Engineering Structures xx (xxxx) xxx–xxx
Fig. 1. Dimensions and reinforcement of specimens, and loading history.
Fig. 2. Instruments for strains and displacements measurements: Strain gauges1–12 (measuring strains of longitudinal reinforcement and hoops), LVDTs 1measures the horizontal displacement at mid-height of the specimen, LVDTs2–5 (to measure the vertical deformation of regions close to the central stiffelement).
5.2. Concrete1
The mean compressive strength of concrete at the time2
of testing of the columns was measured on conventional3
specimens (cylinders 150 mm diameter and 300 mm height);4
it was found to be equal to 40 N/mm2. The characteristic5
compressive strength (5% fractile) was approximately equal6
to 35 N/mm2. Due to the very low scatter of this property,7
small differences in concrete compressive strength from one8
specimen to another were not taken into account. The mean9
value of the modulus of elasticity of concrete was equal to10
34 000 N/mm2.11
5.3. Steel12
Deformed bars 12 mm and 14 mm in diameter were used13
as longitudinal reinforcement. Their mean yield strength and14
tensile strength was equal to 450 N/mm2 and 650 N/mm215
respectively. The mean uniform deformation at failure was 16
approximately equal to 20%. Hardening was initiated at a strain 17
approximately equal to 4%. 18
Smooth or deformed bars were used for hoops: (a) smooth 19
bars S220, with yield strength and tensile strength equal to 20
350 N/mm2 and 450 N/mm2 respectively. Hardening was 21
initiated at a strain value of 3.5% approximately. The mean 22
uniform strain at failure was varying between 25% και 35%, 23
(b) deformed bars 8 mm in diameter, S400 with yield strength 24
and tensile strength of 450 N/mm2 and 650 N/mm2. Their 25
remaining characteristics were as for longitudinal bars. 26
6. Investigated parameters 27
The parameters investigated within the programme are the 28
following: 29
(a) In-section arrangement of hoops: The three alternative 30
formats of Fig. 1 were used. 31
(b) Quality of reinforcing steel: S220 and S400. 32
(c) Diameter and spacing of hoops: 6 mm, 8 mm or 10 mm 33
bars, at 50 mm or 75 mm or 100 mm or 125 mm. 34
(d) Ratio of the gross cross sectional area to the area of the core 35
(Ac/A0). By varying the clear concrete cover, ratio values 36
between 1.42 and 1.83 were used. 37
(e) Target curvature ductility factor: 7, 10 and 13. 38
(f) Normalized axial force, ν = N/ fc Ac: varying between 0.02 39
and 0.43. 40
The combination of parameters (a)–(d) led to a relatively 41
wide range of values for the effective confinement (between 42
0.01 and 0.35). It should be noted that effective confinement 43
values, αωw, as well as normalized axial load values, ν, were 44
calculated on the basis of mean values of mechanical properties 45
of materials. 46
The combination of parameters applicable to each individual 47
specimen is shown in Table 1. 48
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013
UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051
ARTICLE IN PRESSE. Vintzileou et al. / Engineering Structures xx (xxxx) xxx–xxx 5
7. Measurements—loading history1
During testing, the following measurements were made2
(Fig. 2): (a) axial load (held constant during testing) and shear3
force; (b) horizontal displacement at mid-height of specimen4
(LVDT1); (c) rotation of sections in the region of maximum5
bending moments (LVDTs 2–5); (d) strain of longitudinal bars6
(strain gauges 1–4); (e) strain of hoops (strain gauges 5–12)7
close to the critical regions.8
The loading history imposed on all specimens is the9
following (Fig. 1(b)): Step 1—The axial load is imposed up to10
a predetermined value (calculated as described in Section 4(b)).11
The axial load is held constant during testing. Step 2—12
Horizontal displacement is imposed at mid-height of the13
column up to a value dy , corresponding to the yield of the14
specimen. Displacement at yield is estimated during testing15
as follows: Since strains in longitudinal bars are measured, it16
may be assumed that the specimen reaches its yield moment17
when the tensioned bars yield. Moreover, the force vs. mid-18
height displacement curve was continuously recorded and19
observed; the point of initiation of inelastic response was then20
considered as the yield point of the specimen. It should be21
noted that the yield displacement values estimated according22
to the two methods showed a fairly good agreement. Once the23
displacement at yield is determined, a full cycle is performed at24
±dy . Step 3—The specimen is subjected to three full cycles at25
maximum horizontal displacement equal to 3dy or 4dy or 5dy ,26
depending on the magnitude of the target curvature ductility27
factor (7, 10 and 13 respectively). Step 4—The specimen28
is subjected to monotonically increasing displacements, until29
substantial response degradation is recorded. At this point, the30
test is considered completed. In all tests, displacements were31
applied almost statically; thus six to eight hours were needed32
for the completion of each test.33
8. Experimental results34
8.1. Failure mode35
As anticipated by the design of specimens, all columns36
exhibited a flexural failure mode. Initially, flexural cracks37
appeared within the critical regions on both sides of the38
simulated floor level. For larger values of imposed horizontal39
displacement, spalling of the concrete cover occurred within40
a length varying between 0.5h and h, h being the cross41
sectional dimension of the column. As expected, damage was42
mainly concentrated more to one of the two critical regions43
located on both sides of the central stiff element. In fact, in44
19 columns, damage was concentrated in the critical region45
above the simulated floor level, whereas in 18 columns the46
critical region of the lower column was more damaged. The47
behaviour of specimens during cycling at the predetermined48
displacement level depends on various parameters, mainly49
the in-section arrangement of hoops and their spacing. In50
general, two cases can be distinguished. In specimens with51
low confinement and/or large spacing of hoops, after the52
occurrence of concrete spalling, buckling of longitudinal bars53
Photo 1. Test set-up: 1-specimen, 2-Jack for the application of the axial load,3-reaction frame for the support of the actuator.
Photo 2. Test set-up: 1-specimen, 4-actuator (in horizontal position-duringtesting), 5-hinged head in front of the actuator.
was observed, as well as fracture of the closest to ‘floor 54
level’ hoops; in some cases, fracture of some longitudinal bars 55
was observed, as well as disintegration of the concrete core 56
(Photo 1); as a result, substantial force response degradation 57
of specimens was recorded. In well-confined specimens and/or 58
in specimens with closely spaced hoops, limited disintegration 59
of core concrete was observed (Photo 2), whereas limited 60
buckling of longitudinal bars occurred. Those specimens were 61
characterized by a stable behaviour with limited force–response 62
degradation due to cycling at the predetermined level of 63
displacement. 64
8.2. Hysteretic behaviour 65
In Fig. 3 hysteretic loops for some of the tested columns are 66
presented. One can observe that the behaviour of specimens is 67
indeed governed by flexure, as indicated by the large area of 68
hysteretic loops and the absence of pinching effect. 69
Moreover, one may distinguish specimens that exhibited 70
satisfactory cyclic behaviour (e.g. Specimens 2, 23 και 71
32) characterized by limited force response degradation for 72
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013
UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051
ARTICLE IN PRESS6 E. Vintzileou et al. / Engineering Structures xx (xxxx) xxx–xxx
Fig. 3. Hysteresis loops. Horizontal axis: Mid-height displacement (in mm). Vertical axis: Shear force (in kN).
maximum imposed displacement compatible with the target1
ductility, as well as specimens (e.g. columns 6, 11, 15) that2
exhibited substantial force response degradation. It should be3
noted that only horizontal force vs. horizontal displacement4
curves are presented: due to the geometry of specimens, there5
are two critical regions (both sides of the stiff mid-height part6
of the specimen). As damage is inevitably concentrated in one 7
of the two critical regions, for the same imposed displacement 8
the two half-columns exhibit unequal rotations (partly due to 9
the partial pullout of the longitudinal reinforcement). Thus, 10
second order bending moments are also unequal for the two 11
parts of the specimens. Moreover, the measurements taken 12
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013
UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051
ARTICLE IN PRESSE. Vintzileou et al. / Engineering Structures xx (xxxx) xxx–xxx 7
Photo 3. Failure of specimen No 23 d/dy = 4.
Photo 4. Failure of specimen No 38 d/dy = 5.
by LVDTs 2–5 were not reliable up to the completion of1
the testing procedure. Consequently, it was preferred not to2
translate the force–displacement curves to moment-curvature3
diagrams. Fig. 4 illustrates basic data of hysteretic behaviour4
of all specimens: the force response degradation for the third5
cycle is plotted for each of the tested specimens, along with the6
respective hysteretic damping, ζ , calculated as follows:7
ζ =1
4π
area of loopelastic energy
. (2)8
One may observe that significant force response degradation is9
associated with higher hysteretic damping values. Specimens10
with acceptable force response degradation (≤20%) exhibit11
practically the same ζ -value (∼0.20).12
8.3. Force–response degradation due to cycling—Mobilization13
of hoops14
(a) Fig. 5 shows the force–response degradation characteris-15
tics of the tested columns: the force–response (Vn) during the16
nth cycle normalized to the force–response (V1) during the first17
cycle, is plotted against the number of cycles of the imposed18
displacement ductility. As previously mentioned, in order to19
evaluate the seismic behaviour of the specimens, the follow-20
ing criterion (in conformity with Eurocode 8) is applied: It is21
assumed that a column designed for a given curvature ductility22
factor, behaves according to its design requirements if (when23
subjected to displacement reversals compatible with the target24
ductility) it exhibits during the third reversal a force–response 25
degradation not exceeding 15%. Based on this criterion, one 26
may observe that the majority of specimens 1–15 (specimens 27
with single rectangular hoops) do not fulfil the design require- 28
ments, although they do observe Eq. (1). In fact, most of the 29
specimens 1–15 exhibit force–response degradation larger than 30
15%; moreover, the recorded Vn/V1 values are extremely scat- 31
tered. The first impression is that the arrangement of ‘single 32
rectangular hoops’ cannot offer a completely reliable behaviour 33
of these columns, whereas the results for columns with double 34
or triple hoops are liable to substantially smaller uncertainties. 35
In Fig. 6, the V3/V1 values are plotted for all specimens, against 36
the effective confinement ratio, αωw. It is clear that for confine- 37
ment values smaller than 0.05, the results are very scattered, 38
independently of the in-section arrangement of hoops. This ob- 39
servation proves that a minimum value of the confining rein- 40
forcement is indeed needed and it should be expressed in terms 41
of effective confinement αωw > 0.05 rather than in terms of ωw 42
alone. Moreover, one should also mention that independently of 43
the value of confining reinforcement provided to a column, the 44
double and triple arrangement of hoops leads to less scattered 45
(hence, to less uncertain) results, possibly because of a better 46
fixing of longitudinal bars against buckling. 47
(b) It was also confirmed that another parameter affecting 48
the cyclic behaviour of columns is the spacing of hoops, 49
normalized to the diameter of longitudinal bars. Fig. 7 shows 50
the force–response at the third cycle, normalized to that of the 51
first cycle, as a function of the spacing of hoops normalized 52
to the longitudinal bars diameter. It is observed that when 53
the normalized spacing of hoops increases, both the scatter 54
of experimental results and the force–response degradation 55
increase. It is expected that as the spacing of hoops increases, 56
the probability of longitudinal bars to buckle increases, whereas 57
the disintegration of core concrete becomes more probable as 58
well; these phenomena lead to a substantial premature decrease 59
of the force–response. On the data plotted in Fig. 7, it may 60
also be observed that for s/db values equal or larger to 7.0, the 61
V3/V1 ratio exhibits unacceptably low values and large scatter. 62
It should be remembered here that the value s/db = 8.0 is set by 63
Eurocode 8 (Medium Ductility Class) as an upper value against 64
buckling of longitudinal bars. 65
(c) Obviously, the aforementioned three examined parame- 66
ters (namely the in-section arrangement of hoops, their spacing, 67
as well as the effective confinement ratio), are interconnected. 68
Experimental results have proved, however, that all three should 69
comply with some minimum requirements, in order to allow the 70
target ductility to be realized. 71
This observation is illustrated in Fig. 8, which shows the 72
effect of the normalized spacing of hoops on the force–response 73
degradation (as for Fig. 7), for specimens provided with 74
αωw larger than 0.05. It may now be observed that the 75
majority of results are over the threshold of the 0.85 residual 76
force–response level. 77
It should be noted, however, that the buckling of 78
longitudinal reinforcing bars per se remains to be systematically 79
investigated; however, such an investigation was out of the 80
scope of this research work. 81
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013
UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051
ARTICLE IN PRESS8 E. Vintzileou et al. / Engineering Structures xx (xxxx) xxx–xxx
Fig. 4. Hysteretic behaviour of specimens after three full displacement reversals: Force response degradation, ∆V , normalized to the maximum monotonic responseand hysteretic damping, ζ .
Fig. 5. Force response degradation at code-targeted cyclic displacement ductility levels, for various in-section hoop arrangements. The validity of Eq. (1) is ratherdoubtful in some cases where simple square hoops’ arrangement is used.
(d) A final very important remark concerns the stressing1
of hoops: single rectangular arrangement of hoops allows for2
premature disintegration of the concrete core and, subsequently, 3
for premature buckling of longitudinal bars, a feature more 4
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013
UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051
ARTICLE IN PRESSE. Vintzileou et al. / Engineering Structures xx (xxxx) xxx–xxx 9
Fig. 6. Force response degradation as a function of confinement ratio for various in-section hoops arrangements, required by code for given ductility levels. It isclearly shown that for αωw-values lower than 0.05, the quantitative confinement provisions of EC8 (Eq. (1)) are not valid.
Fig. 7. Effect of hoops spacing (normalized to the diameter of longitudinalbars) on the force response degradation due to cycling, when the code-requirement regarding effective confinement for targeted ductility-levels isobserved.
pronounced for large spacing of hoops. As a result, hoops are1
not fully mobilized (they do not reach their yield strength).2
This phenomenon is illustrated in Fig. 9 where the strain of3
hoops, normalized to their yield strain, is plotted against the in-4
section arrangement of hoops. It is clear that as the arrangement5
becomes more dense in-section, the mobilization of hoops is6
enhanced, and the scatter of the results is substantially reduced.7
Thus, in the more dense arrangement ‘3’, yield of hoops was8
reached in all tested columns.9
8.4. Displacement and curvature ductility factors10
(a) Another criterion in order to evaluate the seismic11
behaviour of specimens tested within this programme, is that12
Fig. 8. Effect of hoops spacing (normalized to the diameter of longitudinalbars) on force response degradation, for specimens with effective confinementratio at least equal to 0.05.
of the ratio between the targeted and the effective displacement 13
ductility: remembering that each specimen was subjected to 14
three large amplitude displacement cycles. The amplitude of the 15
displacement reversals (equal to several times the displacement 16
at yield) was compatible with the target curvature ductility, 17
and it was selected on the basis of the respective model of 18
Eurocode 8 (Eq. (1)). On the other hand, the actual ductility 19
exhibited by the specimens can be assessed on the basis of 20
hysteresis loops, as follows: (i) the hysteresis loops envelope 21
for the third loading cycle is traced for both loading directions, 22
(ii) a horizontal line is traced at a force–response level equal to 23
85% of the maximum response; thus, two points are determined 24
on each curve (one on the ascending branch, the other on 25
the descending branch). It is assumed that the mobilized 26
displacement ductility factor is equal to the ratio between 27
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013
UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051
ARTICLE IN PRESS10 E. Vintzileou et al. / Engineering Structures xx (xxxx) xxx–xxx
Fig. 9. Effect of in-section arrangement of hoops on the degree of theirmobilization, at the stage of targeted ductility: the average strain of hoops atthis stage seems to increase in arrangements of multi-leg hoops.
the displacement determined on the falling branch and that1
determined on the ascending branch of each curve. Fig. 102
summarizes the results regarding the displacement ductility3
factors (for both loading directions) as a function of the4
effective confinement ratio. As expected, the results are similar5
to those regarding the previous criterion of the force response-6
degradation V3/V1. In fact, for αωw values smaller than 0.05,7
the value of the normalized displacement ductility exhibits8
unacceptably large scatter (effective to target ductility varying9
between 0.20 and 1.70 approximately), whereas for a large10
number of specimens this ratio is lower than unity. On the11
contrary, for effective confinement ratio values larger than 0.05,12
the ratio between achieved and target ductility lies between 0.8013
and 1.20. This variation is considered to be acceptable, taking14
into account the inherent scatter of experimental results.15
(b) Strain gauges used to measure strains of longitudinal16
bars allowed for the calculation of experimental curvature17
values. On the other hand, moment-curvature diagrams were18
calculated for all specimens. Thus, experimentally obtained19
curvature ductilities can be compared to analytical ones:20
in Fig. 11(a), analytical µ1/r -values are plotted against21
experimentally derived curvature ductility values (on the basis22
of LVDT measurements in both loading directions, as well23
as using strain gauge measurements on different pairs of24
longitudinal bars). In Fig. 11(b), the same analytical values25
are plotted against the average experimental curvature ductility26
value for each specimen. One may observe that, although the27
scatter of experimental values in Fig. 11(a) is pronounced,28
the average values of µ1/r are close to the analytical ones.29
Furthermore, it is observed that, with the exception of those30
specimens that exhibited very poor cyclic behaviour (mainly31
those with single rectangular hoops), the columns reached or32
exceeded the target curvature ductility factor (µ1/r = 10 for33
the vast majority of specimens).34
Fig. 10. Normalized displacement ductility as a function of the confinementratio of columns.
8.5. Residual displacement 35
As shown in the hysteresis loops of Fig. 3, after cycling 36
to displacements as large as 40–100 mm in some cases, there 37
is a quite large residual displacement (of the order of several 38
millimetres). The evaluation of test results has shown that 39
the magnitude of the axial load or the effective confinement 40
ratio does not seem to affect the ratio between residual 41
and maximum imposed displacement. On the other hand, as 42
expected, the magnitude of the residual displacement seems 43
to increase with increasing maximum imposed displacement. 44
Moreover, as shown in Fig. 12, the ratio between residual 45
and maximum imposed displacement seems to increase for 46
larger displacement amplitudes. This is an important aspect of 47
the seismic behaviour of columns, as it may affect the post- 48
earthquake stability of the entire building. In the opinion of 49
the authors of this paper, in addition to the measures taken to 50
enhance the ductility properties of columns, an effort should 51
be made to reduce (via an appropriate conceptual design of the 52
structure) the absolute value of the displacements likely to be 53
imposed to the building. 54
9. Summary and concluding remarks 55
9.1 56
Eurocode 8 (EC8) provisions regarding the necessary 57
confinement of RC columns are based on an analytically 58
derived model (Eq. (1)), explicitly taking into account the 59
following parameters: targeted curvature ductility (µ1/r ), 60
longitudinal steel strain at yield (εsy), gross cross-sectional 61
area normalized to the core section (λ), normalized axial 62
load (ν), hoops arrangement leading to specific efficiency 63
factors (α), an allowable force response degradation lower than 64
15% after three post-yield reversed displacements compatible 65
with targeted curvature ductility. Moreover, by definition, the 66
mechanical volumetric ratio of the hoops to be provided is a 67
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013
UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051
ARTICLE IN PRESSE. Vintzileou et al. / Engineering Structures xx (xxxx) xxx–xxx 11
Fig. 11. Comparison between calculated and experimentally derived curvature ductility factors: (a) experimental values from LVDTs and from strain gauges onlongitudinal bars, (b) mean values per specimen of measurements plotted in (a).
Fig. 12. The effect of maximum cyclic drift on the ratio between residual andmaximum imposed drift.
function of their yield strength ( fyw) and the concrete strength1
of the column ( fc).2
Available experimental investigations, simultaneously tak-3
ing into account all of these six basic parameters are rather4
scarce, although results of more than 450 tests on RC columns5
are available (Vintzileou and Statathos [8])-investigating how-6
ever the role of only some of the aforementioned parameters7
each time.8
That is why it was decided to undertake an overall9
experimental checking of the validity of the basic equation10
(1), by means of an experimental research on 37 columns,11
accounting for all the above parameters tested under identical12
conditions. The testing philosophy was performance-oriented:13
columns designed in conformity with Eq. (1) were subjected to14
post-yield reversed displacements compatible with the targeted15
curvature ductility level; it was checked whether after three16
such cycles, the residual force response capacity of the column17
was higher than 85% of its maximum capacity under monotonic18
loading.19
It was found that, under the minimal conditions discussed20
in the subsequent paragraph, the tested columns observed this21
performance condition; thus, Eq. (1) was experimentally proven 22
to be an appropriate design tool (Figs. 5, 10 and 11). 23
9.2 24
On the other hand, it was found that the following 25
prerequisites set forth by EC8 for the application of Eq. (1), 26
may need a slight modification. 27
For Medium Ductility Class (i.e. for targeted µ1/r = 10), it 28
is not sufficient to require that ωw > 0.10. This experimental 29
investigation has shown that the minimal requirement had better 30
be formulated in terms of ‘effective volumetric mechanical ratio 31
of confinement’ αωw > 0.05 (Figs. 6 and 10). 32
9.3 33
In order to avoid undesirable post-seismic second-order 34
effects, the residual displacements after the three code-required 35
cycles of post-yield displacements compatible with the targeted 36
ductility level, should if possible also be limited by means of an 37
appropriate new code provision, which however, was out of the 38
scope of this paper (Fig. 12). 39
9.4 40
It has to be noted that because of a particularity of the 41
tested specimen (Section 4(c)), the results of this experimental 42
investigation may be considered as somewhat conservative: 43
the contribution of pullout of anchorage lengths towards an 44
increase of available plastic rotation of the column base, was 45
smaller than in most real cases with spliced longitudinal bars. 46
But it should also be noted that the translation of the 47
targeted curvature ductility factors (µ1/r ) into displacement 48
ductility factors (dmax/dy) was made (Section 4(b)) by means 49
of somehow unconservative coefficients: in fact, the simple 50
numerical values used reflect rather average than worse 51
conditions; in view of these two opposite trends, however, it 52
may be said that the results of this investigation are valid for 53
practical design purposes. 54
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013
UN
CO
RR
ECTE
DPR
OO
F
JEST: 2051
ARTICLE IN PRESS12 E. Vintzileou et al. / Engineering Structures xx (xxxx) xxx–xxx
9.51
Finally, it should be noted that the results presented in this2
paper seem to be in accordance with the experimental results3
available in the literature (more than 450 tests of RC columns),4
as evaluated in [8].5
Uncited references6
Photo 3 and Photo 4. [1] and [3].7
References8
[1] CEN (2004) EN 1998-1. Eurocode 8: Design of structures for earthquake9
resistance—Part 1: General rules, seismic actions and rules for buildings.10
[2] Tassios TP, Vintzileou E, Chronopoulos M. Confinement of RC columns
for a given ductility factor. In: Duma, editor. 10th ECEE, vol. 3. Balkema; 11
1994. p. 1649–55. 12
[3] CEB-FIP Model code 1990. Bulletins d’ Information. No 213/214. 13
Lausanne; May 1993. 14
[4] Mo YL, Wang SJ. Seismic behaviour of reinforced concrete columns with 15
various tie configurations. Journal of Structural Engineering, ASCE 2000; 16
126:1122–30. 17
[5] Saatcioglu M, Ozcebe G. Response of reinforced concrete columns to 18
simulated seismic loading. ACI Structural Journal 1989;3–12. 19
[6] Watson S, Park R. Simulated seismic load tests on reinforced concrete 20
columns. Journal of Structural Engineering, ASCE 1994;120 ST(6): 21
1825–48. 22
[7] Wehbe N, Saiidi MS, Sanders D. Confinement of rectangular bridge 23
columns for moderate seismic areas. National center for earthquake 24
engineering research (NCEER) Bulletin 1998; 12 No. 1. 25
[8] Vintzileou E, Stathatos A. Assessment of the cyclic behaviour of RC 26
columns. Engineering Structures. 2006 [in press]. 27
Please cite this article as: Elizabeth Vintzileou et al., Experimental validation of seismic code provisions for RC columns, Engineering Structures (2006),doi:10.1016/j.engstruct.2006.08.013