Date post: | 18-Nov-2023 |
Category: |
Documents |
Upload: | independent |
View: | 0 times |
Download: | 0 times |
Case studies
Indoor environment and conservation in the Royal Museum of Fine Arts,
Antwerp, Belgium
Kristin Gysels a, Filip Delalieux a, Felix Deutsch a,1, René Van Grieken a,*, Dario Camuffo b,
Adriana Bernardi b, Giovanni Sturaro b, Hans-Jürgen Busse c, Monika Wieser c
a Department of Chemistry, University of Antwerp, Universiteitsplein 1, 2610 Antwerp, Belgiumb CNR-ISAC Corso Stati Uniti 4, 35127 Padova, Italy
c Institute of Bacteriology, Mycology and Hygiene, University of Veterinary Medicine Vienna, Veterinärplatz 1, 1210 Vienna, Austria
Received 20 June 2003; accepted 16 February 2004
Abstract
Indoor and outdoor atmospheres of the ‘Koninklijk Museum voor Schone Kunsten’ (KMSK, Royal Museum of Fine Arts) in Antwerp,
Belgium, were thoroughly characterised to determine the air quality inside the museum and the factors controlling it. During a winter and a
summer campaign aerosol particles, pollutant gases, bacteria and fungi were sampled and different indoors microclimatic parameters were
measured. The chemical composition of particulates suspended in indoor and outdoor air was analysed, both with reference to bulk aerosol
matter and to individual particles. Outdoor sources largely determined the composition of indoor aerosol. The main particle types identified in
winter were Ca-rich, Ca–Si and sea salt particles. In summer, S-rich particles were most abundant. Dry deposition was sampled in order to
determine the amount of particulate matter that could potentially deposit onto the works of art. The concentrations of NO2 and SO2 amounted
to 12 and 5–6 ppb, respectively, both in winter and in the summer. The microclimates inside the exhibition rooms were affected by poorly
balanced heating and air-conditioning, free-standing humidifiers, ventilating and lighting systems and the daily flux of visitors, which
produced rapid changes and marked thermo-hygrometric gradients. Based on these results, suggestions for the improvement of the heating and
air-conditioning system could be made. Microbial loads were higher in summer than in winter. However, the proportion of microorganisms
capable of degrading proteins or hydrolysing fats, and thus pernicious to works of art, was not significantly increased inside the museum.
© 2004 Elsevier SAS. All rights reserved.
Keywords: Aerosol particles; Gases; Microbiology; Microclimate; Conservation; Indoor air quality; Museum
1. Research aims
The conservation of works of art exhibited inside muse-
ums is influenced considerably by the indoor environment,
i.e. microclimate and air pollutants. Temperature and relative
humidity (RH) variations, metabolic actions and excretions
of microorganisms and gaseous and particulate pollution all
play an important role in the deterioration of works of art.
Daily temperature and RH cycles are induced by heating and
air-conditioning devices and cause mechanical stress. More-
over, crystallisation of salts in the micropores of the paintings
can cause further damage [1].
Atmospheric particles are potentially harmful because
they can cause significant soiling. Apart from the mere cos-
metic effect, dust deposited on works of art contains variable
amounts of moisture attracting compounds. Further damage
can be caused at the moist dust/surface interface by chemical
reactions with gases or by harmful compounds present in the
deposited particles. The following compounds can be consid-
ered threatening to the preservation of works of art. Organic
material, especially soot, can cause significant visual degra-
dation by soiling the surface [2] and it can constitute a
medium for SO2 adsorption [3]. CaSO4 can enhance these
effects by adsorption of soot [4]. (NH4)2SO4 and S-rich
material are threatening to the preservation of paintings,
because (NH4)2SO4 can induce bloom on varnish [5] and
oxidation of S-rich particles to H2SO4 can cause discolouring
of the paint (e.g. [3,6]). This process can be catalysed by
Fe-rich particles [7]. Therefore, a detailed characterisation of
the particulate and gaseous phases of the environment inside
museums can lead to improvements in the conservation of
works of art.
* Corresponding author.
E-mail address: [email protected] (R. Van Grieken).1 Present address: VITO, Centre for Remote Sensing and Atmospheric
Processes, Boeretang 200, 2400 Mol, Belgium.
Journal of Cultural Heritage 5 (2004) 221–230
www.elsevier.com/locate/culher
© 2004 Elsevier SAS. All rights reserved.
doi:10.1016/j.culher.2004.02.002
In this study, the Koninklijk Museum voor Schone Kun-
sten (KMSK) in Antwerp, was chosen for a closer investiga-
tion of indoor particulate and gaseous pollution, microbiol-
ogy and microclimate. Indoor climate and thermo-
hygrometric parameters had to be determined for different
rooms, including the Rubens room and the rooms in which a
popular exhibition was held about the (baroque) painter An-
toon Van Dyck. Horizontal and vertical distributions of tem-
perature, relative and specific humidity (SH) were recorded.
Together with the results of the aerosol, gaseous pollution
and microbiology investigations, an integrated view on the
indoor environment could be obtained. The results should be
interpreted with reference to the conservation of works of art.
This research was performed in the framework of a Euro-
pean project that studied four museums, having different
climate and pollution conditions: The Correr Museum, Ven-
ice, Italy [8]; Kunsthistorisches Museum, Vienna, Austria
[9]; KMSK and Sainsbury Centre for Visual Arts, Norwich,
UK [10]. The first three museums are of traditional design,
housed in historic buildings; the last one has a modern de-
sign, with use of new materials (glass and metal).
2. Experimental
2.1. Methodologies
2.1.1. Aerosol sampling and analysis
The KMSK is located just south of the city centre of
Antwerp near major traffic axes and the river Scheldt. The
surroundings can be characterised as urban with a moderate
maritime climate. Antwerp is situated about 100 km away
from the North Sea, in a heavily industrialised area. The
museum is housed in a historic limestone building, con-
structed between 1873 and 1890. A heating, ventilation and
air-conditioning (HVAC) system is operational throughout
the building. All the rooms have a parquet floor and painted
textile walls.
During two campaigns, organised in February 1999 and
July/August 1999, time-resolved aerosol samples were taken
for single particle analysis using streakers. The indoor sam-
pling site was situated on the first floor in room K (see Fig. 1).
Restoration works were carried out during the winter sam-
pling campaign. During the summer campaign a special
exhibition about Van Dyck, which attracted a lot of visitors
was held on the ground floor of the museum.
Aerosol samples for single particle analysis were taken
indoor and outdoor both with May cascade impactors (theo-
retical cut-offs 20, 8, 4, 2, 1 and 0.5 µm) on Apiezon-coated
Nuclepore filters and without size-segregation on Nuclepore
filters. The samples were analysed automatically by electron
probe X-ray micro-analysis (EPMA; JEOL Superprobe 733).
The resulting data was subjected to Hierarchical Cluster
Analysis (HCA) in order to identify different particle types
present in the samples (e.g. aluminosilicates, sea salt, Ca-
and S-rich).
Total particulate number concentrations were determined
by means of an optical particle counter (based on light scat-
tering by aerosols). The combination of these data with the
relative abundances of the different particle types gives the
absolute abundances of these particle types.
In order to measure dry deposition, Apiezon-coated
Nuclepore filters were attached vertically to the museum
walls at 17 different locations, at a height of approximately
2 m for a period of 6 months. The samples were analysed by
energy dispersive X-ray fluorescence spectrometry
(EDXRF; Tracor 5000).
Time-resolved aerosol samples were collected by means
of a streaker sampler. The streaker consists of two rotating
stages: an impaction stage with a theoretical cut-off of 2.5 µm
and a filter stage consisting of a 0.4 µm pore-size Nuclepore
filter. Particles >10 µm dae (aerodynamic diameter) impact on
the pre-impactor stage. The samples were analysed by
particle-induced X-ray emission (PIXE) spectrometry. Data
about (outdoor) wind speed, wind direction, temperature and
rainfall, were obtained from the Belgian Royal Meteorologi-
cal Institute.
2.1.2. Microclimate
The (indoor) microclimate was also investigated during
the winter and the summer of 1999, particularly in the rooms
I and K on the first floor and in some of the rooms on the
ground floor (Antwerpen I and Genova), where the much-
frequented Van Dyck exhibition was held. The main thermo-
hygrometric parameters analysed (day and night) were air
temperature (T), SH and RH measured with automatic data
loggers and with manually operated psychrometers during
specific surveys in winter (9–13 February) and summer (15–
17 July). The hygrometric parameters were obtained by us-
ing a high resolution (0.1 °C), fast response (5 s) psychrom-
eter.
2.1.3. Gaseous pollutants
SO2 and NO2 concentrations were determined using pas-
sive diffusion tubes (Gradko International Ltd.). SO2-tubes
were analysed with ion chromatography (Dionex 4000i),
NO2-tubes with photometry (UVIKON 930). Three diffusion
tubes for either gas were placed at each of the 20 sampling
sites.
2.1.4. Microbiology
Fungal attack on works of art displayed in a museum
environment with elevated humidity has long been a problem
and some conservators believe that bacteria may also present
risks (e.g. [11,12]). Airborne bacteria were sampled onto
agar strips (using a Biotest Hycon RCS Plus air sampler) and
subsequently cultured in the laboratory to count the number
of colony forming units (cfu), and to characterise the strains.
Airborne microorganisms were collected in February and
July 1999, both inside and outside the museum. The same
methodology was used as previously in other museums
[8,10]. Different growth media were used; CasMM agar and
222 K. Gysels et al. / Journal of Cultural Heritage 5 (2004) 221–230
commercial total count agar (TCA) for bacteria, and com-
mercial yeast/mould agar for fungi. TCA especially supports
the growth of bacteria with high nutritional requirements
such as bacteria associated with humans, animals and plants.
In contrast CasMM agar favours the growth of environmental
strains (bacteria with high nutritional requirements grow at
significantly reduced rates). In order to determine some as-
pects of the hazardous potential of the airborne microorgan-
isms, additional measurements were carried out. Hydrolysis
of Tween 80 would demonstrate the presence of lipolytic
activity and thus the microorganisms’ potential to destroy oil
paintings. Hydrolysis of Casein would demonstrate the abil-
ity to degrade proteins and thus all works of art containing
proteins [13].
Fig. 1. Map of the ground (top) and first (bottom) floor of the Museum voor Schone Kunsten. H, dry deposition sampling site.
223K. Gysels et al. / Journal of Cultural Heritage 5 (2004) 221–230
2.2. Results
2.2.1. Chemical characterisation of aerosol particles
2.2.1.1. Bulk concentrations and dry deposition. Especially
for Na and Cl, but also for other elements, the average bulk
indoor concentrations were higher in winter than in summer.
Only the concentrations of soil-derived elements as Al, Si
and Ti were higher in summer (Table 1). This can be ex-
plained by the more effective resuspension of particles and
the larger number of visitors during summer, which repre-
sented an important source of indoor soil dust.
The highest contributions of all elements (except Ti and
Si) occurred during winter in the fine size range, which was
dominated by Na and Cl. Cl was also the main element in the
coarse fraction. During summer, the coarse fraction (>10 µm)
was much larger. Si, Cl, K, Ca, Ti, Cu and Zn mainly oc-
curred in this fraction. Na, S, Fe and Pb were predominantly
present in the fine size range (<2.5 µm), while Al was mainly
detected in the intermediate fraction (2.5–10 µm). This indi-
cates that in summer, the relative importance of resuspension
of coarse particles was larger than in winter.
Because most elements detected in the time-resolved
samples were assumed to have an outdoor origin, the fluctua-
tions in their abundances were compared with meteorologi-
cal data. The fine aerosol concentration inside the museum
appeared to be anti-correlated with the outdoor wind speed.
During periods with low wind speed, fine aerosol concentra-
tions could build up and decrease again due to increased
ventilation and wash-out processes. The positive correlation
between the contribution of coarse particles and wind speed
can be explained by the increased resuspension of these
particles [14]. Variations in the weather conditions (wind
speed and precipitation) were directly reflected in the indoor
aerosol concentration, which indicates the strong outdoor
influence.
For the fine size fraction elemental concentrations (espe-
cially S) seemed to be anti-correlated with wind speed, while
for the coarse fraction, a clear positive correlation with wind
speed could be observed (especially for Cl and Fe). This was
the case during both summer and winter campaigns. From
this observation it is clear that these elements have an out-
door origin. Also Ca exhibited a clear positive correlation
with wind speed in summer and thus originated from an
outdoor source. In winter, the construction and restoration
works provided a strong indoor Ca-source.
In the dry deposition the highest elemental concentrations
were found for S; concentrations of Ca were rather low. In
general, the dry deposition turned out to be very homoge-
neous throughout the entire investigated area of the museum
(Fig. 1). Results of the analyses performed on dry deposition,
which in view of conservation are very important, will be
discussed in Chapter 3.
2.2.1.2. Single particle analysis. During the winter cam-
paign large particles (size range ≥4 µm) were characterised
by high abundances of Ca-rich, Ca–Si and aluminosilicate
particles. The same particle types were identified in the
intermediate size range (2–4 µm), but sea salt gained impor-
tance as well. The particles <2 µm were completely domi-
nated by sea salt and aged sea salt. Concerning potentially
dangerous aerosols (cf. Section 1); Fe-rich particles were
present in every investigated size range, while low-Z and
S-rich particles were only identified in the smallest size
fraction.
During the summer campaign, however, aluminosilicate
and low-Z particles were the most abundant types in the size
range ≥2 µm. Na- and K-containing particles were present as
well. The small particles (<2 µm) contained significant
amounts of sulphur. Outdoor samples contained higher rela-
tive amounts of sea salt particles (especially in the size
fraction ≥4 µm), but these were still lower than in winter. The
Table 1
Bulk aerosol concentrations (µg/m3)
Element February 1999 August 1999
Na 0.61 ± 0.55 0.004 ± 0.009
Si 0.005 ± 0.004 0.008 ± 0.002
Al <DL 0.006 ± 0.001
S 0.27 ± 0.14 0.05 ± 0.03
Cl 0.54 ± 0.76 0.009 ± 0.003
K 0.10 ± 0.11 0.005 ± 0.001
Ca 0.13 ± 0.06 0.016 ± 0.002
Ti 0.0003 ± 0.0003 0.0008 ± 0.0005
Mn 0.002 ± 0.002 0.0003 ± 0.0004
Fe 0.24 ± 0.26 0.016 ± 0.008
Cu 0.002 ± 0.002 0.0003 ± 0.0001
Zn 0.021 ± 0.016 0.004 ± 0.001
Pb 0.015 ± 0.028 0.0011 ± 0.0008
0.001
0.01
0.1
1
10
100
1000
10000
100000
0 3 6 9 12 15 18 21 0
Hours
Dg
old/
Nd
mc/1(
3)
0,1 µm
0,3 µm
0,5 µm
1 µm
2 µm
5 µm
10 µm
Fig. 2. Suspended particle density distribution dN/dlogD versus time for
February 10th 1999.
224 K. Gysels et al. / Journal of Cultural Heritage 5 (2004) 221–230
fraction 1–4 µm was mainly characterised by S-rich, low-Z,
Na–S and Na-rich particles, while in the smallest size range
(0.5–1 µm), S-rich and K–S particles were predominant. The
outdoor influence appeared to be most significant in the
smallest size range.
Both for the summer and winter campaigns, the results of
the filter samples were in very good agreement with those of
the impactor samples.
2.2.1.3. Comparison indoor/outdoor. The outdoor environ-
ment appeared to have a very significant influence on the
atmosphere inside the KMSK, especially in summer. Abso-
lute particle number concentrations were calculated and
compared for the indoor and outdoor environments.
Most of the time absolute sea salt concentrations were
higher in outdoor air compared to indoor air. The concentra-
tions of Ca-rich and Ca–Si particles were found to be highest
indoors in winter, as a consequence of the restoration works.
In summer, however, indoor concentrations were comparable
to or even lower than outdoor concentrations.
The average indoor/outdoor (I/O) ratios were clearly high-
est during the winter campaign. Especially Ca–Si particles
exhibited very high I/O ratios in winter (10.7), and thus
originate from indoor sources. Ca-rich and CaSO4 particles
also showed higher indoor concentrations in winter. These
particles (similar to the Ca–Si particles) originate from the
construction works, although outdoor sources might be
present as well.
It can be concluded that, for both seasons, the outdoor
influence was significant, i.e. the indoor aerosol composition
depended largely on the outdoor composition. In summer,
indoor concentrations were about 40% lower compared to
the outdoor concentrations. In winter, an extra indoor source
of mainly Ca-containing particles was present. This led to
higher I/O ratios for the total aerosol number concentration
in winter (0.9 vs. 0.6 in summer).
2.2.2. Microclimate
2.2.2.1. Winter campaign. The very large room I (Rubens
room, first floor) with several communicating doors is
equipped with an air-conditioning system. Nevertheless, the
thermo-hygrometrical gradients often exhibited perturba-
tions generated within the room by the entrance of condi-
tioned air or air from the neighbouring rooms (Fig. 3). Colder
and more humid air always penetrated especially from the
adjacent rooms into room I. In addition, the construction
works carried out during the winter campaign enhanced the
flow of external air into the museum. The microclimate was
relatively constant throughout the whole room, except in the
vicinity of the doors, where local gradients were always
present. The most pronounced effects were situated around
the main entrance. Fluctuations in SH amounted 2 g/kg
within 3–4 m. RH changed according to the same pattern,
with changes reaching levels as low as 34%. In general, less
steep gradients between rooms would be recommendable.
Fig. 3. Horizontal cross section of the distribution of temperature (°C), RH (%) and SH (g/kg) in the Rubens room on February 11th 1999, 10:00 h.
225K. Gysels et al. / Journal of Cultural Heritage 5 (2004) 221–230
The construction works might have aggravated the extent of
these gradients.
In room K (Fig. 4) on the first floor, marked gradients of T
(up to 1 °C within a few meters), SH (up to 1.5–2 g/kg within
a few meters) and RH (up to 10–15% within a few meters)
were measured. Airflow was observed originating from the
Rubens room (with its very different microclimate) crossing
room K to reach room L. In this way a significant difference
in humidity content could build up between the air in the
centre and along the walls of room K. When the glass door
between rooms K and L was closed, exchange of air was
prevented and the situation improved. The average RH level
(45–55%) was acceptable, but fluctuations could reach up to
15% in the course of the morning and the afternoon.
In room T (Fig. 5) on the first floor, very strong gradients
of T (differences reaching up to 8–9 °C within 1–2 m) and
RH were generated when the radiators switched on. At first
sight, this perturbation seemed acceptable as it was confined
to the centre of the room, far from the paintings. However, the
hot radiators caused a convective air current in the room with
hot air rising in the centre and cold air descending along the
walls, which led to increased inertial deposition of suspended
particles on to the paintings. In addition, discontinuous op-
eration of the radiators led to RH fluctuations that amounted
to 25–30%.
In general, several perturbations in microclimatic homo-
geneity were present on the first floor. Although the museum
is equipped with a central heating system that supplies hot
and moistened air to every room temperature fluctuations
amounting to 2–3 °C between neighbouring rooms could be
observed. The SH was not well balanced either; it was higher
in the outermost rooms, in particular in the rooms G, M, L, R,
S and T. As a consequence of the uneven distributions of
temperature and SH, RH fluctuations between rooms
amounted to 10–15% and RH levels in the inmost rooms
19
20
21
22
23
24
25
0 6 12 18 0 6 12 18 0
Time
erut
arep
meT
)C°(
30
40
50
60
70
ytidi
mu
H evit
aleR
)%(
T(0.1m) T(1m) T(2m)
T(4m) RH(1m) RH(4m)
Fig. 4. Profiles of vertical temperature (°C) and RH (%) on February 10th
and 11th 1999 in room K.
Fig. 5. Horizontal cross section of the distribution of temperature (°C), RH (%) and SH (g/kg) in room T on February 13th 1999, 10:30 h.
226 K. Gysels et al. / Journal of Cultural Heritage 5 (2004) 221–230
were too low (37–38%). These considerable differences in
thermo-hygrometrical conditions between rooms in combi-
nation with the free exchange of air caused unacceptable air
currents and spatial and temporal gradients.
The forced circulation caused by heating, the circulation
of air between adjacent rooms and the movement of visitors
generated turbulences that increased the deposition rate of
pollutants onto the works of art. The highest concentrations
of particles were consistently found during the visiting hours
of the museum (Fig. 2). Especially the largest particles (i.e.
between 5 and 10 µm), which settle during the night, were
resuspended during the day.
2.2.2.2. Summer campaign. Temperature gradients in room I
(Rubens room, first floor) appeared to be quite strong during
the day (differences of around 1 °C within 4–5 m) and
attenuated in the evening. A marked thermal minimum was
present in front of the door between rooms I and H. The SH
and RH distributions were good with weak gradients. Only
sometimes in front of open doors connecting adjacent rooms,
in particular H and K, weak maxima of RH were found
(coinciding with temperature minima). The average RH
(around 50–55%) was acceptable. In general, the microcli-
mate in summer was better than in winter.
The horizontal temperature distribution in room K on the
first floor exhibited differences reaching up to 1.5 °C within
2–3 m. Probably some of them were due to the air-
conditioning system. Colder air came in from room I and
strong gradients were found in front of the door. The glass
door between rooms K and L limited the exchange of air
masses between the two rooms. On the other hand, the
horizontal SH and RH distributions were quite homoge-
neous, showing only weak gradients. The average horizontal
RH level varied between 45% and 50% with week temporal
changes that were acceptable for an effective conservation.
The vertical distribution showed a stable thermal gradient
characterised by a temperature difference of 2 °C within 4 m.
This gradient tended to suppress turbulence and reduced the
deposition of suspended particles on the paintings.
In general, strong differences in the temperature distribu-
tion have been found within the rooms on the first floor. In
particular, the inmost rooms were colder compared to the
outermost rooms with differences reaching up to 4 °C. The
air inside the inmost rooms was characterised by a higher
humidity, compared to the outermost rooms, with differences
reaching up to 2 g/kg (SH) or 10% (RH).
In the large Antwerpen I room (ground floor), where the
Van Dyck exhibition was held, the horizontal temperature
distribution was uneven with strong gradients (2–3 °C within
2–3 m) that became less pronounced in the afternoon (about
1 °C within 2–3 m). This was due to the large number of
visitors and to different air masses that came from neighbour-
ing rooms. A marked thermal minimum was found, which
coincided with the presence of two humidifiers close to the
entrance. At this location, strong gradients of SH (1.2 g/kg
within 1–2 m) and RH were observed. The humidifiers were
operated at maximum power in the morning and were attenu-
ated in the afternoon. In the evening their effect disappeared.
A Van Dyck picture on the wall behind the humidifiers was
exposed to a flow of air, which changed its moisture content
by about 2 g/kg during the day. In the morning, the RH at this
place was 8–10% higher than the average level of the room
(about 57–58%), reaching equilibrium with the room only in
the evening when the humidifiers were turned off. Hence, the
humidifiers were placed too close to paintings that suffer
from the humidity changes. This was very evident in the
morning before opening hours. Later, the visitors were an-
other cause of internal perturbation.
In the Genova room (ground floor), the airflow of the
air-conditioning system is released from outlets located in
the ceiling and is extracted through grids all around the floor.
Thermal and hygrometric gradients were less marked than in
the large Antwerpen I room. Temperature proved to be the
most variable parameter (1–2 °C within 1–2 m). SH and RH
gradients were weak and the average RH was acceptable
(55–60%). Emission of air from the ceiling, with a moisture
content very different from the rest of the room, resulted in
relatively stable local gradients.
2.2.3. Gaseous pollution
The concentrations of NO2 and SO2 appeared to be dis-
tributed very homogeneously throughout the museum [15].
Indoor winter and summer concentrations were comparable
(12 ppb NO2 and 5–6 ppb SO2). However, the summer I/O
ratios were found to be about 1.3 times higher than the winter
I/O ratios for both compounds. This indicates a better air
exchange in summer. I/O ratios for NO2 were about twice as
high as the I/O ratios for SO2, reflecting the higher deposition
velocity of the latter. For particle types originating from an
outdoor source, winter and summer I/O ratios were compa-
rable. This suggests that the ventilation rate is not the only
factor determining I/O ratios of aerosol particles. Deposition,
as suggested by Tatcher and Layton [16], probably plays an
important role.
2.2.4. Microbiology
Generally, in summer higher bacterial counts were ob-
served on CasMM agar than on TCA while in winter the
opposite was observed (Tables 2 and 3). This might be
explained by the reduced growth of environmental strains
during the wintertime resulting in their low contribution to
counts of collected airborne bacteria. In contrast, the propor-
tion of human associated bacteria, such as staphylococci [17]
is higher. This assumption is supported by the observation
that after 9 days of incubation the bacterial counts on both
TCA and CasMM agar were almost identical. Since the
human associated bacteria grow more slowly on CasMM
agar, their colonies (which are counted for enumeration of
bacterial counts) were only visible after a prolonged incuba-
tion on the growth medium.
Both on the first floor (Table 2) and on the ground floor
(Table 3) of KMSK, microbial loads were significantly
227K. Gysels et al. / Journal of Cultural Heritage 5 (2004) 221–230
higher (at least threefold) in summer than in winter. This was
also noted for the outdoor samples (Table 4). This observa-
tion is in accordance with previous studies [8,10] and can be
explained by the fact that the growth of the majority of
bacteria is favoured during summertime due to the higher
temperature. Both in summer and in winter the bacterial
counts were higher on the ground floor than on the first floor.
In summer, the bacterial counts on the ground floor were
similar to those measured outdoors but significantly higher
(at least twofold) than on the first floor. This does not seem to
be caused by the exchange of air through the nearby main
entrance because the fungal counts measured outdoors were
threefold higher than those measured indoors. Even the
higher number of visitors on the ground floor during the
summer measurements should not have contributed signifi-
cantly to the higher counts of airborne bacteria. The growth
of human related bacteria is favoured on the TCA on which
lower counts were observed during the summer than on
CasMM agar. Thus, it has to be assumed that the ecological
niche(s) from where these airborne bacteria were suspended
to the air is (are) located somewhere on the ground floor
(inside the museum). Sampling on numerous surfaces on the
ground floor would be needed to pinpoint the source of these
bacteria. No significant counts of fungi were found indicat-
ing that the fungal load indoors cannot be considered as
harmful [18].
Counts of microorganisms able to hydrolyse Tween 80 or
Casein were not significantly increased (Tables 2 and 3). A
higher portion of either type of microorganisms would have
indicated that there is a source of microorganisms within the
confines of the museum, which are able to destroy oil paint-
ings or all works of art containing proteins, respectively.
Thus an increased hazard for the works of art inside the
KMSK by lipolytic or proteolytic airborne bacteria should
not be assumed. However, caution is advisable with respect
to unexplained high counts of airborne bacteria during the
summer on the ground floor. Since it is assumed that their
ecological niche is situated somewhere on the ground floor
Table 2
Microbial counts collected in February and in July in room K (first floor) expressed in cfu obtained after 3, 5 and 9 days of incubation at room temperature (*
expressed as positive colonies per total counts of cfu)
Medium Volume [I]
collected
Day 3 Day 5 Day 9
February July February July February July
Mould agar 100 0 0 1 0 1 2
500 0 0 0 0 0 2
TCA 100 2 22 5 22 6 25
500 20 44 27 51 30 49
CasMM agar 100 2 43 3 44 5 46
500 5 125 16 134 33 168
Tween 80 100 2/15 0/9
Hydrolysis* 300 4/24 2/71
Casein 100 2/8 9/29
Hydrolysis* 300 0/6 11/29
Table 3
Microbial counts collected in February (Catalogue reading room) and in July (Antwerpen I room, both ground floor) expressed in cfu obtained after 3, 5 and
9 days of incubation at room temperature (* expressed as positive colonies per total counts of cfu)
Medium Volume [I]
collected
Day 3 Day 5 Day 9
February July February July February July
Mould agar 100 1 1 2 1 2 4
500 3 5 4 8 5 11
TCA 100 2 65 4 65 7 74
500 35 259 109 >300 145 >300
CasMM agar 100 6 74 18 89 23 99
500 18 306 53 >300 101 >300
Tween 80 100 3/25 2/117
Hydrolysis* 300 4/70 5/>300
Casein 100 7/25 2/82
Hydrolysis* 300 5/24 6/>300
Table 4
Microbial counts collected in February and in July outdoors near the back entrance of the museum obtained after 3, 5 and 9 days of incubation
Medium Volume [I]
collected
Day 3 Day 5 Day 9
February July February July February July
Mould agar 500 6 34 19 34 25 34
TCA 500 6 197 25 197 44 201
CasMM agar 500 38 290 152 >300 >200 >300
228 K. Gysels et al. / Journal of Cultural Heritage 5 (2004) 221–230
they must also have a source of nutrients (carbon, ammonia,
phosphate, etc.) in order to grow there. Since it is most likely
(based on the kind of growth media employed) that these
nutrients are not supplied via the air they have to come from
somewhere else. Hence, it is thought expedient to carefully
investigate all works of art for any onset of decay. In order to
study the contribution of such bacteria to any decay, bacteria
would have to be isolated from these surfaces and they would
have to be studied for their potential for biodecay.
3. Conclusions
It was shown that outdoor atmosphere significantly influ-
ences the indoor air of the Royal Museum of Fine Arts. This
impact is in particular revealed by the correlation between
the time-evolution of indoor aerosol concentrations and wind
speed. Fine particulate matter concentrations (<2.5 µm) were
inversely correlated with wind speed, due to the ventilation
effect. In the larger size range (2.5–10 µm), increased resus-
pension induced by higher wind speeds, was more important,
so the large particle concentrations were found to increase
with wind speed. In winter, restoration and construction
works constituted an additional indoor source of Ca-rich and
Ca–Si particles. Along with sea salt, these were the main
particle types identified in this season. In summer, S-rich
particles were most abundant. The summer abundances of
Ca-rich particles remained low, even though the museum is
situated in a limestone building. Interior wall plaster and
construction works apparently have a far greater influence on
indoor Ca-concentration.
Organic, S-rich and Fe-rich particles in the size range
around 0.5 µm can be considered most harmful with respect
to the preservation of works of art. The joint contributions of
low-Z, S-rich and Fe-rich particles to the 0.5–1 µm size range
were 15% in the winter and 90% in the summer. The contri-
butions to the total size range (0.5–20 µm) were 20% in
winter and 49% in summer. Hence, especially during the
summer, high relative abundances of potentially harmful
particles were measured. However, the absolute concentra-
tions of S and Fe (which are more important with respect to
preservation) remained low in the KMSK, i.e. 0.25 µg/m3 or
lower. Dry deposition measurements indicated nevertheless
that the S deposition was rather high (0.029 µg/cm2 in
6 months), probably because this element was mainly present
in small ammonium sulphate particles.
From the point of view of conservation, it became clear
that the works of art are not directly threatened by particulate
pollution. Still, the situation could be improved by employ-
ing filters with higher collection efficiency in the HVAC
system, especially for small particles. The microbiological
measurements have proved that airborne microorganisms do
not seem to represent an increased hazard for the works of
art.
As far as the microclimate is concerned, this study has
evidenced that the central HVAC system causes a very irregu-
lar airflow characterised by sharp changes in temperature and
RH. On the long run, these fluctuations cause ageing and
damage to the exhibits. Winter was shown to be the most
problematic period, because of the cold the building has to be
heated and the moisture content of the external air is very low
in comparison with the air inside the museum. Hence, the RH
drops to unacceptable levels unless it is well controlled.
The spatial distribution of microclimatic parameters
showed significant perturbations due to turbulences caused
by visitors and the outlets and suction grids of the HVAC
system. In addition, heat and moisture were not well distrib-
uted among the rooms on the same floor, causing strong
gradients at communicating doors. When doors were open,
air currents established from one room to another and gener-
ated microclimatic anomalies. On the long run, these cycles
are dangerous for the exhibits. The existing HVAC was
designed mainly to meet the needs of visitors rather than the
requirements to preserve works of art. Now it needs to be
improved to reach a better conservation standard. However, it
should be kept in mind that the construction works required
to make the changes could cause even more damage by
generating numerous particles. This was clearly demon-
strated by the results obtained in this study. Leaving the
situation as it is, even if not ideal, might cause less damage
than the construction works needed to alter it.
Acknowledgements
Special thanks are due to Dr. Paul Huvenne and Mrs.
Yolande Deckers and all the staff of the Koninklijk Museum
voor Schone Kunsten in Antwerp for their sincere interest in
this work and their eager assistance during the measurement
campaigns. The PIXE analyses were performed at PIXE
Analytical Laboratories, Tallahassee, FL, USA. This study
was supported by the European Commission, Programme
Environment, contract ENV4-CT95-088 AER, aimed to
identify the main causes of environmental risk to cultural
heritage due to unsound use of technologies and mass tour-
ism. K.G. and F.D. were supported by the Flemish Fund for
Scientific Research (FWO).
References
[1] D. Camuffo, Microclimate for Cultural Heritage, Elsevier, Amster-
dam, 1998, pp. 235–292.
[2] N.S. Baer, P.N. Banks, Indoor air pollution: effects on cultural and
historical materials, International Journal of Museum Management
and Curatorship 4 (1985) 9–20.
[3] R.I. Larson, Air pollution damage to paint, American Paint Journal 42
(1957) 94–108.
[4] L. Leysen, E. Roekens, Z. Komy, R. Van Grieken, A study of the
weathering of a historic building, Analytica Chimica Acta 195 (1987)
247–255.
[5] P. Brimblecombe, Review article: the composition of museum atmo-
spheres, Atmospheric Environment 24B (1990) 1–8.
229K. Gysels et al. / Journal of Cultural Heritage 5 (2004) 221–230
[6] F. De Santis, V. Di Paolo, I. Allegrini, Determination of atmospheric
pollutants inside a museum: relationship with the concentration out-
side, Science of the Total Environment 127 (1992) 71–81.
[7] G. Thomson, Air pollution—a review for conservation chemists,
Studies in Conservation 10 (1965) 147–167.
[8] D. Camuffo, P. Brimblecombe, R. Van Grieken, H.-J. Busse,
G. Sturaro, A. Valentino, A. Bernardi, N. Blades, D. Shooter, L. De
Bock, K. Gysels, M. Wieser, O. Kim, Indoor air quality at the Correr
Museum, Venice, Italy, Science of the Total Environment 236 (1999)
135–152.
[9] G. Sturaro, D. Camuffo, P. Brimblecombe, R. Van Grieken,
H.-J. Busse, A. Bernardi, A. Valentino, N. Blades, D. Shooter,
K. Gysels, F. Deutsch, M. Wieser, S. Buczolits, Multidisciplinary
environmental monitoring at the Kunsthistorisches Museum, Vienna,
Journal of Trace and Microprobe Techniques 21 (2003) 273–294.
[10] P. Brimblecombe, N. Blades, D. Camuffo, G. Sturaro, A. Valentino,
K. Gysels, R. Van Grieken, H.-J. Busse, O. Kim, U. Ulrych,
M. Wieser, The indoor environment of a modern museum building,
the Sainsbury Centre for Visual Arts, Norwich, UK, Indoor Air 9
(1999) 146–164.
[11] W. Krumbein, C. Urzi, C. Gehrmann, Biocorrosion and biodeteriora-
tion of antique and medieval glass, Geomicrobiology Journal 9 (1991)
139–160.
[12] W. Krumbein, C. Urzi, Biologically induced decay phenomena of
antique marbles: some general considerations, The Conservation of
Monuments in the Mediterranean Basin, Proceedings of the Second
International Symposium, Geneva, Switzerland, 1991, pp. 135–219.
[13] P. Altenburger, P. Kämpfer, A. Makristathis, W. Lubitz, H.-J. Busse,
Classification of bacteria isolated from a medieval wall painting,
Journal of Biotechnology 47 (1996) 39–52.
[14] A.R. Deacon, R.G. Derwent, R.M. Harrison, D.R. Middleton,
S. Moorcroft, Analysis and interpretation of suspended particulate
matter at urban and background sites in the United Kingdom, Science
of the Total Environment 203 (1987) 17–36.
[15] C. Van Hoof, Passieve Monitoring van NO2 en SO2 in het Koninklijk
Museum voor Schone Kunsten te Antwerpen, University of Antwerp
(UIA), Antwerp, Belgium, 1999 M.Sc. thesis.
[16] T.L. Thatcher, D.W. Layton, Deposition, resuspension and penetration
of particles within a residence, Atmospheric Environment 29 (1995)
1487–1497.
[17] M. Wieser, H.-J. Busse, Rapid identification of Staphylococcus epi-
dermidis, International Journal of Systematic Evolution Microbiology
50 (2000) 1087–1093.
[18] D. Camuffo, R. Van Grieken, H.-J. Busse, G. Sturaro, A. Valentino,
A. Bernardi, N. Blades, D. Shooter, K. Gysels, F. Deutsch, M. Wieser,
O. Kim, U. Ulrych, Environmental monitoring in four European
museums, Atmospheric Environment 35 (2001) S127–S140.
230 K. Gysels et al. / Journal of Cultural Heritage 5 (2004) 221–230