Date post: | 01-Feb-2023 |
Category: |
Documents |
Upload: | khangminh22 |
View: | 0 times |
Download: | 0 times |
R56 Compliance Audit APPENDIX F - R56Compliance Audit
Page 1 of 89/16/2017
WAC Responsibility Customer Responsibility WAC Failure
Customer Failure
DESCRIPTIONPassed Failed Passed Failed N/A
Date Corrected
Date Corrected
Reference
1 GENERAL
a. A copy of the Project Manager's Compliance Sheet has been completed, certified and supplied for attachment to this audit.
X N/A N/A
b. Project Manager's Compliance Sheet shows that all appropriate requirements have been met. X N/A N/A
TOTALS FOR SECTION 0 0 0 0 2
2
a. The ceiling height is sufficient to meet requirements for equipment installation. X N/A Paragraph 3.6.1
b. Cable runway system meets the proper installation requirements.X N/A Paragraph 3.10.5
c. The floor is sealed as required. X N/A N/A Paragraph 3.6.2
d. Transmission line entry ports, holes or openings which penetrate the outer surface of the building have been properly sealed.
X N/A Paragraph 3.7.1
e. Adequate lighting and air conditioning requirements met.X N/A N/A Paragraph 3.11
f. Minimum required fire suppression equipment is properly installed.X N/A Paragraph 3.12
g. A first aid kit is available and meets requirements.X N/A N/A Paragraph 3.13.1
h. Required personal protective safety items are available for servicing batteries which require such items. X N/A N/A Paragraph 3.13.2
i. A telephone, microwave link, or cellular phone has been made available. X N/A N/A Paragraph 3.14
j. Phone numbers of importance are posted at the site.X N/A N/A Paragraph 3.14
k. The minimum required signage is posted at the site.X N/A N/A Paragraph 3.15
TOTALS FOR SECTION 0 0 6 4 1
3 EXTERNAL GROUNDING
a. An External Ground Bus bar (EGB) of suitably sized material is properly installed at the transmission line entry point.
X N/A N/A Paragraph 4.4.3
b. The EGB grounding electrode conductor has been properly installed.
X N/A N/A Paragraph 4.4.3
c. When a tower ground bus bar (TGB) is used, it meets the proper installation and bonding requirements.
X N/A N/A Paragraph 4.4.3.1
BUILDING DESIGN AND INSTALLATION
Customer Name: County of Routt-Steamboat Springs, CO
Project Manager: Project #:
Site Name: Mt Werner
Inspector's Name: Roger Hays Audit Date: 9/1/2017
R56 Compliance Audit APPENDIX F - R56Compliance Audit
Page 2 of 89/16/2017
WAC Responsibility Customer Responsibility WAC Failure
Customer Failure
DESCRIPTIONPassed Failed Passed Failed N/A
Date Corrected
Date Corrected
Reference
d. Each transmission line outer shield is properly bonded to the tower or TGB at the transition of the vertical transmission line run with a weather sealed transmission line grounding kit.
X N/A Paragraph 4.7.9
e. Each transmission line outer shield is properly bonded to the EGB with a weather sealed transmission line grounding kit.
X N/A N/A Paragraph 4.7.9
f. The tower is properly bonded with the required number grounding conductors. X N/A
Paragraphs 4.7.6 & 4.9
g. Ice bridges / cable supports have been properly bonded to the EGB.X N/A Paragraph 4.7.10.2
h. Each ice bridge / cable support post has been properly bonded to the grounding electrode system. X N/A N/A Paragraph 4.7.10.2
i. Ice bridges / cable supports have been properly isolated from the tower. X N/A N/A Paragraph 4.7.10.2
j. Guy wires are properly bonded and their grounding conductor maintains a continuous vertical drop to the grounding electrode.
X N/A N/A Paragraph 4.7.6.2.1
k. Fencing has been properly bonded to a ground system as required.X N/A N/A Paragraph 4.7.10.1
l. Each fence gate is properly bonded to its supporting fence post as required. X N/A N/A Paragraph 4.7.10.1
m. Gate supporting fence posts are properly bonded as required.X N/A N/A Paragraph 4.7.10.1
n. Generator and support skids have been properly bonded as required. X N/A N/A
Paragraphs 4.7.7.1 & 6.9.7
o. Items listed below are properly bonded to the grounding electrode system as required. Paragraph 4.7.10
o.1 Metallic entry ports X N/A N/A Paragraph 4.7.10
o.2 Cable conduits or raceways X N/A N/A Paragraph 4.7.10
o.3 Metallic piping (water, gas, electrical conduits, etc..)X N/A N/A Paragraph 4.7.10
o.4 Air conditioner units X N/A N/A Paragraph 4.7.10
o.5 Metal siding and/or roofing on buildingsX N/A N/A Paragraph 4.7.11
o.6 Vent covers and grates X N/A N/A Paragraph 4.7.10
o.7 Metal fuel storage tanks (above or below ground)X N/A
Paragraphs 4.7.10 & 6.9.7
o.8 Building skid or pier foundations X N/A Paragraph 4.7.10
o.9 Anchors on prefabricated buildingsX N/A N/A Paragraph 4.7.10
o.10 Metallic structures for antenna supports, light fixtures, etc.X N/A N/A
Paragraphs 4.7.6.3 & 4.7.10
o.11 Satellite dish supports X N/A N/A Paragraph 4.8o.12 GPS antenna supports X N/A N/A Paragraph 4.8
o.13 Hand and safety rails X N/A N/A Paragraph 4.7.10o.14 Ladders and safety cages X N/A N/A Paragraph 4.7.10
o.15 Security bars and window frames X N/A N/A Paragraph 4.7.10o.16 Main electrical ground
X N/AParagraphs 4.3 &
6.2.2o.17 Main telco ground
X N/AParagraphs 4.3 &
4.7.10
R56 Compliance Audit APPENDIX F - R56Compliance Audit
Page 3 of 89/16/2017
WAC Responsibility Customer Responsibility WAC Failure
Customer Failure
DESCRIPTIONPassed Failed Passed Failed N/A
Date Corrected
Date Corrected
Reference
p. Approved bonding techniques have been used for the connection of dissimilar metals. X N/A Paragraph 4.5
q. Approved methods have been used for conductor connection and termination. X N/A N/A Paragraph 4.6
r. Bonding surfaces for lugs and clamps are free of paint and corrision and a conductive anti-oxidant compound has been applied.
X N/A N/AParagraphs 4.5.4 & 4.6.1
s. All painted or galvanized bonding surfaces for exothermic welds were cleaned and painted to inhibit rusting.
X N/A N/A Paragraph 4.6
t. All grounding conductors have been routed towards the EGB, TGB or the grounding electrode system and the minimum bending radius has been observed. X N/A Paragraph 4.4.2.2
u. Grounding conductors are routed as straight as possible and protected from physical damage as required.
X N/A N/A Paragraph 4.4.2.3
v. Grounding conductors maintain the minimum required separation from other cable groups. X N/A N/A Paragraph 9.9.3.2
w. Grounding conductors are securely fastened as required.X N/A N/A Paragraph 4.4.2.3
x. Grounding conductors meet or exceed the conductor size requirements. X N/A N/A
Paragraphs 4.4.2.1 & 4.8
y. Braided grounding conductors are not used anywhere in the external ground system. X N/A N/A Paragraph 4.7.9
TOTALS FOR SECTION 0 0 15 9 17
4 INTERNAL GROUNDING
a. A properly sized Master Ground Bus Bar (MGB) is installed as required. X N/A N/A Paragraph 5.3.1
b. The MGB grounding electrode conductor has been properly bonded and routed towards the grounding electrode system.
X N/A N/A Paragraph 5.3.1.3
c. All conductors connections to the MGB follow approved connection methods. X N/A N/A Paragraphs 5.4.3
d. Where required a Sub System Ground Bus Bar (SSGB) has been properly installed. X N/A N/A Paragraph 5.3.2
e. The SSGB has been bonded back to the MGB as required.X N/A N/A Paragraph 5.3.2.3
f. All conductor connections to the SSGB follow the approved connection methods. X N/A N/A Paragraphs 5.4.3
g. Where required an Internal Perimeter Ground Bus (IPGB) is properly installed. X N/A Paragraph 5.3.7
h. Only ancillary equipment is bonded to the IPGB.X N/A Paragraph 5.3.7
i. Each ancillary support apparatus is properly bonded to the IPGB, MGB, or SSGB. X N/A
Paragraphs 5.4.1 & 5.5.1.6
R56 Compliance Audit APPENDIX F - R56Compliance Audit
Page 4 of 89/16/2017
WAC Responsibility Customer Responsibility WAC Failure
Customer Failure
DESCRIPTIONPassed Failed Passed Failed N/A
Date Corrected
Date Corrected
Reference
j. Items listed below are properly bonded to the MGB, SSGB, or IPGB by the approved connection methods. Paragraphs 5.4.1 &
5.5.1
j.1 Piping systemsX N/A N/A
Paragraphs 5.5.1.6 & 5.5.1.7
j.2 Steel roof trusses X N/A N/A Paragraph 5.5.1.7
j.3 Exposed support beams or columnsX N/A N/A Paragraph 5.5.1.7
j.4 Ceiling grids X N/A N/A Paragraph 5.8.3.2
j.5 Raised equipment floor support structure at the proper intervals.X N/A N/A
Paragraphs 5.4.2 & 5.8.3.2
j.6 Any exposed metallic building materials (metal siding)X N/A N/A Paragraph 5.5.1.6
k. Surge Protection Device (SPD) metal housings are bonded to the MGB, SSGB or IPGB as required. X N/A Paragraph 5.5.1.6
l. Separately derived AC electrical systems are bonded to the MGB or SSGB as required. X N/A
Paragraphs 5.5.1.1 & 6.2.2
m. Primary telephone, control, and data network circuit SPDs are properly installed bonded to the MGB or SSGB as required.
X N/A N/A Paragraph 5.5.1.8.2
n. RF transmission line SPDs are bonded to the MGB or a separate equipment area SSGB as required. X N/A Paragraph 5.5.1.8.1
o. Cable runways are bonded to the MGB or SSGB as required.X N/A Paragraph 5.5.1.5
p. Each cable runway section is bonded to the adjoining section as required. X N/A Paragraph 5.5.1.5
q. Ground bus conductors and their extensions are sized as required.X N/A N/A
Paragraphs 5.3.5 & 5.3.6
r. All ground bus conductors, ground bus extensions and equipment grounding conductors are routed towards the MGB or SSGB as required. X N/A N/A Paragraph 5.3.4
s. Bonding connections to a ground bus or its extensions have been properly insulated as required. X N/A N/A Paragraph 5.3.4
t. Cabinets have been properly bonded back to the MGB, SSGB or ground bus by approved methods. X N/A N/A Paragraph 5.5.1.4
u. Racks have been properly bonded back to the MGB, SSGB or ground bus by approved methods. X N/A Paragraph 5.5.1.4
v. Any RGB located within a cabinet or rack is properly bonded back to the MGB, SSGB or ground bus as required.
X N/A Paragraph 5.3.3
w. Individual system component chassis equipment is properly bonded as required. X N/A Paragraph 5.5.1.3
x. Secondary telephone, control, and data network circuit SPDs are properly installed and bonded back to MGB or SSGB as required.
X N/A N/AParagraphs 5.5.1.8.3 & 5.8.3.1
y. All required control center and dispatch equipment is properly bonded back to the MGB, SSGB, or ground bus conductor as required. X N/A N/A Paragraph 5.8.3
R56 Compliance Audit APPENDIX F - R56Compliance Audit
Page 5 of 89/16/2017
WAC Responsibility Customer Responsibility WAC Failure
Customer Failure
DESCRIPTIONPassed Failed Passed Failed N/A
Date Corrected
Date Corrected
Reference
TOTALS FOR SECTION 0 0 7 11 12
5 POWER SOURCES
a. Circuit breakers are labeled to identify the receptacle outlet they are protecting. X N/A N/A Paragraph 6.2.6
b. Proper clearance requirements are being observed for power panels. X N/A Paragraph 6.2.4
c. Outlet boxes are permanently marked to identify their assigned circuit breakers and panels. X N/A Paragraph 6.2.10
d. Power receptacle outlets are mounted securely to the supporting structure. X N/A N/A Paragraph 6.2.11
e. Adequate service receptacle outlets are provided for the technician.X N/A N/A Paragraph 6.2
f. Each critical piece of equipment has a dedicated branch circuit and dedicated simplex receptacle. X N/A N/A Paragraph 6.2.10
g. Power receptacles are installed by the equipment load as required.X N/A N/A Paragraph 6.2.10
h. Extension cords including temporary outlet strips are not used in the final installation. X N/A N/A Paragraph 6.2.9
i. Exterior receptacle outlets and circuits are GFCI protected as required. X N/A N/A Paragraph 6.2.5.1
j. AC power receptacle outlets and strips are of the proper type and securely mounted off the floor. X N/A Paragraph 6.2.11
k. Appropriate clearance is being observed for safe servicing of UPS and battery banks. X N/A Paragraph 6.5.1
l. The neutral - ground bonding conductor has been properly installed in the main service disconnect as required.
X N/A Paragraph 6.2.1
m. Equipment grounding conductors have been installed as required.X N/A N/A Paragraph 6.2.7
n. Solar panels have been located away from objects that could damage or block sunlight to the panel.
X N/A N/A Paragraph 6.6.2
o. Proper mounting practices are being observed for solar panels or wind generators. X N/A N/A Paragraph 6.6.2
p. Battery racks are bolted to the floor or wall.X N/A N/A Paragraph 6.7.9
q. Battery conductors are enclosed in PVC, metallic conduit or raceways. X N/A N/A Paragraph 6.7.9
r. A battery disconnect and suitable circuit protection device has been installed as required. X N/A N/A
Paragraphs 6.7.9,& 10
s. When a standby power generator has been installed, it meets the proper installation requirements. X N/A N/A Paragraphs 6.8,& 9
t. Standby generators are located in areas only accessible by authorized personnel. X N/A N/A Paragraph 6.9.1
R56 Compliance Audit APPENDIX F - R56Compliance Audit
Page 6 of 89/16/2017
WAC Responsibility Customer Responsibility WAC Failure
Customer Failure
DESCRIPTIONPassed Failed Passed Failed N/A
Date Corrected
Date Corrected
Reference
u. Standby generators have an adequate area provided for servicing.
X N/A N/A Paragraph 6.9.1
v. Fuel storage tanks for standby generators are located within a secured area. X N/A Paragraph 6.9.2
w. A dedicated electrical circuit has been provided at the generator.X N/A N/A Paragraph 6.9.4
x. A transfer switch of the proper ampacity rating has been installed to perform the switching between commercial power and standby generator power. X N/A N/A Paragraph 6.9.3
y. A main service disconnect has been installed as required.X N/A N/A
Paragraphs 6.2.1 & 6.2.5 & 6.9.3
z. Electrical panelboard ampacity ratings are properly coordinated.X N/A N/A Paragraph 6.2 & 6.9.3
TOTALS FOR SECTION 0 0 11 6 9
R56 Compliance Audit APPENDIX F - R56Compliance Audit
Page 7 of 89/16/2017
WAC Responsibility Customer Responsibility WAC Failure
Customer Failure
DESCRIPTIONPassed Failed Passed Failed N/A
Date Corrected
Date Corrected
Reference
6
a. A Type 1 SAD/MOV surge protection device (SPD) is installed as required. X N/A N/A Paragraph 7.4.1
b. A Type 2 MOV surge protection device (SPD) is installed as required. X N/A N/A Paragraph 7.4.1
c. Primary SPDs for telephone circuits are installed as required.X N/A Paragraph 7.5
d. Secondary SPDs for telephone circuits are installed as required.X N/A N/A Paragraph 7.5
e. Primary SPDs for control circuits are installed as required.X N/A N/A Paragraph 7.5
f. Secondary SPDs for control circuits installed as required.X N/A N/A Paragraph 7.5
g. Primary SPDs for data network circuits are installed as required.X N/A N/A Paragraph 7.5
h. Secondary SPDs for data network circuits are installed as required.X N/A N/A Paragraph 7.5
i. All RF transmission lines, including unused spares, have coaxial RF type SPDs properly installed as required.
X N/A N/A Paragraph 7.6
j. Where a tower top amplifier has been installed, the sample port and its control cables have SPDs installed as required.
X N/A N/A Paragraph 7.6
k. Tower lighting system AC power and data/alarm circuits have SPDs properly installed as required. X N/A N/A Paragraph 7.8
TOTALS FOR SECTION 0 0 2 1 8
7
a. Equipment spacing and aisle widths conform to guidelines.X N/A Paragraph 9.3.1
b. Equipment is level and plumb.X N/A N/A Paragraph 9.5
c. Equipment is square with surrounding equipment and walls.X N/A N/A Paragraph 9.5
d. Where applicable, seismic installation practices have been observed. X N/A N/A Paragraphs 9.4.1
e. Cabinets and racks are secured as required.X N/A N/A Paragraphs 9.6
f. Cables and cable groups of different function maintain a minimum 5 cm (2 in.) separation as required.
X N/AParagraph 9.9.1.5 & 9.9.3.2
g. RF cables meet or exceed minimum bending radius requirements.
X N/A N/AParagraphs 9.9.1.4 & 9.9.8
h. Plenum-rated cables are installed as required.X N/A N/A Paragraph 9.9.2
i. Proper cable lengths are used.X N/A N/A Paragraph 9.9.1.2
j. Cables are properly secured at the required intervals. X N/A Paragraph 9.9
k. AC power conductors installed on cable runway systems meet installation requirements. X N/A N/A
Paragraphs 3.10.4 & 9.9.3
EQUIPMENT INSTALLATION
TRANSIENT VOLTAGE SURGE SUPPRESSION
R56 Compliance Audit APPENDIX F - R56Compliance Audit
Page 8 of 89/16/2017
WAC Responsibility Customer Responsibility WAC Failure
Customer Failure
DESCRIPTIONPassed Failed Passed Failed N/A
Date Corrected
Date Corrected
Reference
l. Cables are properly identified with a standard, double-ended system.X N/A Paragraph 9.9.12
m. Distribution frame wiring conforms to the proper punch-down or wire-wrap techniques. X N/A Paragraph 9.9.11
n. CAT-5 cables maintain the proper separation from AC power cables.X N/A N/A Paragraph 9.9.6.4
o. CAT-5 cables do not have any sharp bends.X N/A N/A Paragraph 9.9.6.5
p. CAT-5 cables meet all other installation requirements.X N/A N/A Paragraph 9.9.6
q. Cables installed below raised flooring systems are properly installed.
X N/A N/AParagraphs 3.10.2 & 9.9
r. Cables installed above suspended ceilings are properly installed.X N/A N/A Paragraph 9.9.3.3
s. Electrostatic discharge practices are observed as required.X N/A Paragraph 9.10
TOTALS FOR SECTION 0 0 8 6 5
WAC CUSTOMER
Number of Passed
Number of Failed
Number of Passed
Number of Failed
Total N/A
AUDIT TOTALS 0 0 49 37 54
MT WERNER R56 AUDIT
W E RNE R M OU N TAI N S I T E
RO UT T E CO UNT Y, C OL O RA DO
RF SITE
READINESS INSPECTION REPORT
Wireless Advanced Communications
Mt Werner R56 Audit
MT WERNER SITE
SITE READINESS INSPECTION REPORT
1. INTRODUCTION
Today’s public safety communications and E911 systems have more
features and more functionality than ever before. The introduction of
computers and computer networking technology has created the ability to
provide more mission critical flexibility. However, computers, computer
based equipment, and networks provide unique challenges in order to ensure
safe and reliable operation. This is especially true in a public safety
environment.
The design and development of communications sites is critical not only to
optimal functioning of the communications system, but also to the safety of
installation, maintenance, and dispatch personnel. With this in mind,
Motorola has developed the publication Standards and Guidelines for
Communication Sites (commonly known as R56). This publication is a
compilation of requirements, guidelines, and best practices gathered from
sources including ANSI, IEEE, NFPA-70 (commonly known as National
Electrical Code), OSHA, UL, and others.
On September 1st, 2017, Wireless Advanced Communications performed a
site readiness inspection at the Werner Mountain Conventional RF Site
located near Steamboat Springs, Colorado. The site was inspected as to its
suitability to RF equipment in the existing building.
The site was inspected for electrical safety, equipment reliability, and site
quality as related to the operation of a mission critical radio
communications network. The National Electrical Code® and the Motorola
publication, Standards and Guidelines for Communication Sites were used as the basis of the inspection and this report. This report contains the
following topics:
Site Identification
Site Description
Executive Summary
Disclaimer
Electrical Wiring Inspection Results
Building Design and Installation
External Grounding Inspection Results
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247 Mt Werner R56 Audit
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 2 - Mt Werner R56 Audit
Internal Grounding Inspection Results
Power Sources Inspection Results
Transient Voltage Surge Suppression Inspection Results
Installation Inspection Results
This report is intended to be used in conjunction with the R56 audit form
provided as a separate document.
Project Identification
Identifying Name
Mt Werner
Customer or Buyer
Routt County
Motorola Contact for
this Document
Roger Hays, CETma,
(970-415-2902)
2. SITE IDENTIFICATION
Site Name
Mt Werner
Site Address
Steamboat Springs, Colorado
N 40.27.369’ W 106.44.430’
3. SITE DESCRIPTION
The Werner Mountain RF Site contains equipment for the county of Routt,
Colorado. The site is equipped with a backup generator and an automatic
transfer switch.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 3 - Mt Werner R56 Audit
4. EXECUTIVE SUMMARY
The Mt Werner Site is in fair condition in regards to its intended use as a
conventional RF site. My main concerns are making sure the site’s Internal
Perimeter Ground Bus (IPGB) only has ancillary equipment bonded to it
and a minimum 4” gap on the opposite wall of Master Ground Bus bar
(MGB). Also two of the tower leg’s ground are showing very high
resistance to earth ground. This would indicate the tower legs are not
properly bonded to a tower ring.
The National Electrical Code® violations revealed at the site are a
potential life safety issue.
5. DISCLAIMER
Wireless Advanced Communication offers recommendations within this
report solely for the purpose of improving life safety at the site, and
improving system reliability and availability. This report is not intended as a design specification or an instruction manual for untrained persons. No
opinions or recommendations expressed in this report shall result in liability to WAC or the author for any losses, damages, expenses, claims or causes
of action incurred or sustained by any citizen, employee, representative or contractor of Routt County for any reason whatsoever. All work performed
to correct the identified deficiencies shall be performed by properly trained,
licensed and qualified personnel. All work shall be performed in
compliance with the National Electrical Code®; the Motorola document,
Standards and Guidelines for Communication Sites (R56); and all other
applicable federal, state, and local codes.
6. ELECTRICAL WIRING INSPECTION RESULTS
A cursory inspection of wiring revealed no problems. It is suggested that the
site be inspected by a qualified, licensed electrician in order to verify.
7. BUILDING DESIGN AND INSTALLATION
The design and development of communications sites is critical not only to
optimal functioning of the communications system, but also to the safety of
installation, maintenance, and dispatch center personnel. The importance of
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 4 - Mt Werner R56 Audit
implementing and following safety programs during construction as well as
during the system's useful life cannot be overemphasized.
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
2.a
The ceiling height is sufficient to meet
requirements for equipment installation
The ceiling shall be high enough
to accommodate equipment racks,
cable trays, cabling, and servicing
of the associated equipment.
The minimum ceiling height for
communication sites utilizing 84-
inch (7 foot) racks is
recommended to be 8.5 feet.
The ceiling height is less than
the recommended 8.5 feet.
See R56 Section 3.6.1.
2.b
Cable runway system meets the proper
installation requirements
A minimum separation of 12
inches above the top of the cable
runway and the ceiling shall be
maintained.
A minimum separation of 6 inches
between the top of an equipment
rack or cabinet and the bottom of
the cable runway shall be
maintained.
The cable runway doesn’t not
meet the 12 inches of separation
between the ceiling and the top
of the rack.
Reference can also be found in
NFPA 70 (NEC), Article 392.
See R56 Section 3.10.5.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 5 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
2.d
Transmission line entry ports, holes or openings
which penetrate the outer surface of the building
have been properly sealed
All site buildings shall be weather
tight and shall deter entry by
animals, birds, and insects.
The building/shelter and the port
attachment to the building/shelter,
shall be designed to prevent
animals or birds from nesting in
and around the entry ports.
Unused transmission line ports
shall be properly sealed using a
cap supplied by the manufacturer.
Cable boots shall be the correct
size for the cable installed.
The MGB ground conductor is
not properly sealed where it
exits the transmission line port.
See R56 Section 3.7.1.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 6 - Mt Werner R56 Audit
2.f
Minimum required fire suppression equipment is
properly installed
All sites must have fire
suppression equipment available
on site.
A fixed or total flood fire
suppression system does not
nullify the need for portable fire
extinguishers.
There must be a minimum 15-20
lbs. Class ABC extinguisher for
general firefighting. Dry
chemical extinguishers are
acceptable, although FE-36 or
Halotron are preferred around
sensitive electronic equipment.
There must be at a minimum 7-10
lbs. Class BC, carbon dioxide
(CO2) or equivalent type
extinguisher for fighting electrical
equipment fires.
Portable fire extinguishers shall be
maintained in a fully charged and
operable condition.
Fixed suppression systems shall
be equipped with adequate
automatic detection devices and
automatic alarms.
For fixed suppression systems,
appropriate warning signs shall be
posted at the entrance of the
protected area.
Smoke detectors shall not be
located directly above a cable
tray.
The site does not contain either
portable fire extinguisher.
Reference can also be found in
NFPA 10, NFPA 12, and NFPA
2001.
See R56 section 3.12.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 7 - Mt Werner R56 Audit
8. EXTERNAL GROUNDING INSPECTION RESULTS
Some of the purposes for external grounding are:
• To help limit the voltage caused by accidental contact of the site AC supply
conductors with conductors of higher voltage.
• To help dissipate electrical surges and faults, to minimize the chances of
injury from grounding system potential differences.
• To help limit the voltages caused by lightning.
• To help maintain a low potential difference between exposed metallic
objects.
• To stabilize the AC voltage relative to the earth under normal conditions.
• To contribute to reliable equipment operation.
• To provide a common signal reference ground.
• See article 250 of the National Electrical Code® for more details.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 8 - Mt Werner R56 Audit
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 9 - Mt Werner R56 Audit
AUDIT
ITEM AUDIT REQUIREMENT RECOMMENDED CORRECTIVE ACTION
3.d
Each transmission line outer shield is properly bonded
to the tower or TGB at the transition of the vertical
transmission line run with a weather sealed
transmission line grounding kit.
The transmission line ground kit shall be weather
sealed and installed per manufacturer
specifications.
The transmission line ground kit shall be bonded
a properly installed TGB or to an effectively
grounded vertical member of the tower using
manufacturer approved methods.
The ground kit lead shall be installed without a
drip loop, parallel to the transmission line, and
pointed down towards the earth to provide a
direct discharge path for lightning.
A transmission line ground kit shall be installed
near the antenna mounting location and at the
bottom of the tower near the cable’s vertical to
horizontal transition point.
Most of the transmission lines have the proper
gr my not be pound kit installed. Please make
sure all transmission line have the same kit.
Any unused transmission lines should be
removed.
Reference can also be found in ANSI T1.334-
2002 and ANSI T1.313-2003.
See R56 section 4.7.9.
3.f
The tower is properly bonded with the required number
grounding conductors
Tower grounding conductors shall be bonded to
the grounding electrode system using exothermic
weld or irreversible high-compression crimping
connections.
Two of the three tower leg grounding
conductors have high resistance readings
indicating they may not be properly bonded to
the tower grounding conductor.
Reference can also be found in ANSI T1.334-
2002, ANSI T1.313-2003, MIL-HDBK-419A
and ANSI/EIA/TIA-222-F-R2003.
See R56 sections 4.7.6 & 4.9
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 10 - Mt Werner R56 Audit
AUDIT
ITEM AUDIT REQUIREMENT RECOMMENDED CORRECTIVE ACTION
3.g
Ice bridges / cable supports have been properly bonded
to the EGB
At the building or shelter cable entry location, the
cable support system needs to be bonded back to
the EGB with a #6 AWG or coarser copper
conductor, or it needs to be bonded directly back
to the grounding electrode system with a #2
AWG or coarser, bare tinned, copper conductor.
Conductor bonding to the cable support system
shall be made using exothermic welding, or listed
two-hole lug and stainless steel hardware.
Conductor bonding to the EGB shall be made
using exothermic welding, irreversible high
compression fitting or listed two-hole lug and
stainless steel hardware.
To help ensure effective bonding of the ice
bridge/cable bridge system, the separate sections
of the structure should be bonded together #6
AWG or coarser, jacketed, copper conductors.
The ice bridge/cable bridge system is not
bonded to the EGB.
Reference can also be found in ANSI T1.334-
2002.
See R56 section 4.7.10.2.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 11 - Mt Werner R56 Audit
AUDIT
ITEM AUDIT REQUIREMENT RECOMMENDED CORRECTIVE ACTION
3.o7
Metal fuel storage tanks (above or below ground)
All exterior above grade metallic objects that are
located within 6 ft. of the external grounding
system or within 6 ft. of a grounded object, shall
be bonded to the external grounding system with
a minimum # 6 AWG or coarser, copper
conductor.
Grounding conductors routed below or partially
below the earth surface shall be a minimum # 2
AWG or coarser, bare, copper conductor.
In high lightning prone geographical areas, or
areas of high soil resistivity, it is recommended to
bond all metallic items within 10 ft. of the
grounding electrode system or a grounded object.
The metal fuel tank located below the
generator platform needs to be bonded to the
grounding electrode system.
Reference can also be found in ANSI T1.313-
2003 and ANSI T1.334-2000.
See R56 sections 4.7.10 & 6.9.7.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 12 - Mt Werner R56 Audit
AUDIT
ITEM AUDIT REQUIREMENT RECOMMENDED CORRECTIVE ACTION
3.o.8
Building skid or pier foundations
All exterior above grade metallic objects that are
located within 6 ft. of the external grounding
system or within 6 ft. of a grounded object, shall
be bonded to the external grounding system with
a minimum # 6 AWG or coarser, copper
conductor.
Grounding conductors routed below or partially
below the earth surface shall be a minimum # 2
AWG or coarser, bare, copper conductor.
In high lightning prone geographical areas, or
areas of high soil resistivity, it is recommended to
bond all metallic items within 10 ft. of the
grounding electrode system or a grounded object.
The building skid that support the RF site
building is not bonded to the grounding
electrode system.
Reference can also be found in ANSI T1.313-
2003 and ANSI T1.334-2000.
See R56 section 4.7.10.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 13 - Mt Werner R56 Audit
AUDIT
ITEM AUDIT REQUIREMENT RECOMMENDED CORRECTIVE ACTION
3.o.16
Main electrical ground
All exterior above grade metallic objects that are
located within 6 ft. of the external grounding
system or within 6 ft. of a grounded object, shall
be bonded to the external grounding system with
a minimum # 6 AWG or coarser, copper
conductor.
Grounding conductors routed below or partially
below the earth surface shall be a minimum # 2
AWG or coarser, bare, copper conductor.
In high lightning prone geographical areas, or
areas of high soil resistivity, it is recommended to
bond all metallic items within 10 ft. of the
grounding electrode system or a grounded object.
Without a licensed electrician present during
the R56 audit it could not be determined if the
main electrical ground is properly bonded to
the grounding electrode system.
Reference can also be found in ANSI T1.313-
2003 and ANSI T1.334-2000.
See R56 sections 4.3 & 6.2.2.
3.o.17
Main telco ground
All exterior above grade metallic objects that are
located within 6 ft. of the external grounding
system or within 6 ft. of a grounded object, shall
be bonded to the external grounding system with
a minimum # 6 AWG or coarser, copper
conductor.
Grounding conductors routed below or partially
below the earth surface shall be a minimum # 2
AWG or coarser, bare, copper conductor.
In high lightning prone geographical areas, or
areas of high soil resistivity, it is recommended to
bond all metallic items within 10 ft. of the
grounding electrode system or a grounded object.
A ground for the main telco could not be seen.
Reference can also be found in ANSI T1.313-
2003 and ANSI T1.334-2000.
See R56 sections 4.3 & 4.7.10.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 14 - Mt Werner R56 Audit
AUDIT
ITEM AUDIT REQUIREMENT RECOMMENDED CORRECTIVE ACTION
3.p
Approved bonding techniques have been used for the
connection of dissimilar metals
Bare copper, brass and bronze metals shall not be
allowed to come in direct or incidental contact
with bare steel, galvanized steel or aluminum
metal surfaces.
Copper conductors shall not be bonded directly to
steel, galvanized steel or aluminum surfaces
unless using exothermic welds specifically
intended for the purpose.
Copper conductors may be joined to steel,
galvanized steel or aluminum surfaces with the
use of a properly listed bimetallic (stainless steel
or electro tin-plated) transition connectors
equipped with stainless steel securing hardware.
Bimetallic transition clamps shall be of the type,
which provide adequate separation between the
dissimilar metals.
Bonding surfaces for clamped or bolted
connections shall be coated with the appropriate
type of conductive anti-oxidant compound.
Bare copper or tinned copper conductors must be
properly isolated from steel, galvanized steel and
aluminum surfaces with the appropriate type of
insulated standoffs or non-metallic conduit.
On the MGB, EGB, and TGB the ground
conductor lugs need to be coated with the
proper type of conductive anti-oxidant
compound.
Reference can also be found in ANSI T1.313-
2003, ANSI T1.334-2002, IEC 61024-1-2, IEE
STD 142-1991, BS 6651:1999, BS 7430:1998
and NFPA 70-2005.
See R56 section 4.5.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 15 - Mt Werner R56 Audit
AUDIT
ITEM AUDIT REQUIREMENT RECOMMENDED CORRECTIVE ACTION
3.t
All grounding conductors have been routed towards
the EGB, TGB or the grounding electrode system and
the minimum bending radius has been observed
Grounding conductors shall be run as short,
straight, and smoothly as possible, with the
fewest possible number of bends and curves.
A minimum bending radius of no less than 8
inches and no less than 90 degrees shall be
maintained.
All bends, curves, and connections shall be
routed towards the grounding electrode system,
ground rod, or ground bar.
Some of the EGB ground kits need to be
shortened to the proper length.
Reference can also be found in ANSI T1.313-
2003, ANSI T1.334-2002, NFPA 780-2004 and
NFPA 70-2005.
See R56 section 4.4.2.2.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 16 - Mt Werner R56 Audit
9. Internal Grounding Inspection Results
Safety of personnel and protection of sensitive electronic equipment from
ground faults, lightning, ground potential rise, electrical surges, and power
quality anomalies are of utmost importance at any communications site.
Though unexpected electrical events like lightning strikes and power surges
cannot be prevented, a properly designed and installed site grounding
electrode systems that may help minimize damage caused by these events.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 17 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
4.g
Where required an Internal Perimeter Ground
Bus (IPGB) is properly installed
Note: The picture below is from a different RF
site but it shows what needs to happen to the Mt
Werner RF IPGB.
The IPGB provides a suitable
ground conductor to the MGB for
bonding ancillary support
apparatus, electrical conduits, and
other metallic items.
An IPGB conductor is not required
in rooms or areas that are within a
larger building where support
apparatus is not present or where it
is more practical to bond the
support apparatus to the MGB or
an SSGB.
When used, the IPGB shall be
installed such that it encompasses
the interior of the equipment room
or area with two separately
independent ground bus connectors
on opposite sides of the room.
The two bus conductors should
meet at a point within the
equipment area and approximately
opposite of the MGB.
At the location where the two bus
conductors meet, they shall be
separated by at least 4 inches.
The conductors shall be supported
approximately 2 inches from the
wall surface on insulated standoffs.
On the opposite wall from the
location of the MGB a minimum
4 inch separation needs to be
completed.
See R56 section 5.3.7.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 18 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
4.h
Only ancillary equipment is bonded to the IPGB
Only metallic ancillary objects may
be connected to the IPGB.
The IPGB system shall not be used
for bonding communications
equipment, cabinets, or racks to the
MGB or a SSGB.
The radio rack and cable tray
ground conductors need to be
removed from the IPGB and
moved to the MGB.
Reference can also be found in
ANSI T1.334-2002.
See R56 section 5.3.7.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 19 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
4.i
Each ancillary support apparatus is properly
bonded to the IPGB, MGB, or SSGB
All metallic ancillary support
apparatus within an equipment
room or specific equipment area
shall be bonded to the IPGB, MGB,
or SSGB with a #6 AWG or
coarser grounding conductor.
When rigid metallic conduit
(RMC) and/or electrical metallic
tubing (EMT), are effectively
joined with threaded couplings or
thread-less compression connectors
and they are joined to an
effectively bonded cabinet, they
may be considered adequately
bonded and do not require
additional bonding.
If metallic conduit does not meet
the above specifications, electrical
conduits shall be bonded to the
IPGB conductor at any point where
they cross within 6 inches of the
IPGB conductor.
Any metal boxes inside the
building that are not currently
bonded to the IPGB need to be
properly bonded.
Reference can also be found in
ANSI T1.334-2002.
See R56 sections 5.4.1 & 5.5.1.6.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 20 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
4.k
Surge Protection Device (SPD) metal housings
are bonded to the MGB, SSGB or IPGB as
required.
SPD metallic housing shall be
bonded using a # 6 AWG or
coarser conductor.
The SPD metal box for the
incoming AC power needs to be
bonded to the MGB, or IPGB.
Reference can also be found in
NFPA 70-2005, Articles 250 and
800.
See R56 section 5.5.1.6.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 21 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
4.l
Separately derived AC electrical systems are
bonded to the MGB or SSGB as required
Separately derived electrical
systems have no direct electrical
connection between the input and
output.
A generator is only considered to
be a separately derived system
when the automatic transfer switch
(ATS) breaks the neutral
conductor.
A separately derived system shall
bond to the grounding electrode
system using a # 2 AWG or
coarser, green-jacketed grounding
conductor.
Where applicable, the grounding
conductor should be sized to meet
NFPA 70-2008, article 250.66
requirements.
Without a licensed electrician
present during the R56 audit it
could not be determined if the
generator transfer switch
electrical ground is properly
bonded to the grounding
electrode system. If the generator
transfer switch does not break
the neutral conductor from the
main neutral do not add a second
neutral-ground conductor.
Reference can also be found in
NFPA 70-2008.
See R56 sections 5.5.1.1 & 6.2.2.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 22 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
4.n
RF transmission line SPDs are bonded to the
MGB or a separate equipment area SSGB as
required
RF SPDs shall be installed and
bonded to the MGB or an SSGB
within 24 inches of the cable entry
point.
An RF SPD can be bonded to the
grounding electrode system by
directly bonding/securing it to the
MGB or an SSGB, or with the use
of a # 6 AWG or coarser grounding
conductor.
The RF SPD grounding conductor
route to the MGB grounding
electrode system should be no
greater than 20 linear feet. When
the grounding conductor is greater
than 20 linear feet, an additional #
2 AWG or coarser, copper
grounding conductor shall be
properly installed between the RF
SPD, or its associated SSGB, and
the nearest accessible location of
the common grounding electrode
system.
The 2 new VHF combiner SPDs
are currently bonded to the
IPGB and need to be removed
and bonded to the MGB.
Reference can also be found in
NFPA 70-2005, Articles 810.21,
820.93 and 820.100.
See R56 section 5.5.1.8.1.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 23 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
4.o
Cable runways are bonded to the MGB or SSGB
as required
The cable runway system shall be
bonded to the MGB or an SSGB
with a # 6 AWG, or coarser copper
conductor.
When the cable runway is installed
parallel to the MGB or a separate
equipment room’s SSGB, it shall
be bonded to the associated bus bar
with bi-directional bonding
conductors.
The cable tray is currently
bonded to the IPGB and needs to
be removed and bonded to the
MGB.
Reference can also be found in
NFPA 70-2005, Article 392.
See R56 section 5.5.1.5.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 24 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
4.p
Each cable runway section is bonded to the
adjoining section as required
Each joint of a cable runway (tray)
section shall have a bonding
jumper across the joint. All
bonding conductors shall be
installed so that they provide a
direct flow path towards the single
point grounding system.
Exception: When a cable runway
system has labeling that shows it is
UL listed for use as a grounding
conductor.
Cable runway bonding jumpers
shall be # 6 AWG, or coarser.
Bonding jumpers shall be installed
on all metallic non-current-carrying
portions of the cable tray system.
Cable trays shall not be used for
bonding equipment or ancillary
support apparatus to the MGB or
SSGB.
The cable tray joints need a
jumper installed across each
joint.
Reference can also be found in
NFPA 70-2008, Article 392.
See R56 section 5.5.1.5.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 25 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
4.u
Racks have been properly bonded back to the
MGB, SSGB or ground bus by approved
method
All racks shall be bonded to a
ground bus conductor, SSGB or the
MGB.
All non-current carrying metallic
parts of the equipment rack shall be
effectively bonded.
The rack shall be bonded to one of
the following with a # 6 AWG
grounding conductor:
-MGB
-Rack ground bus bar (RGB)
-SSGB
-Ground bus conductor
Most of the racks are bonded to
the IPGB which needs to be
removed and bonded to the
MGB.
Reference can also be found in
NFPA 70-2008, Article 250.
See R56 section 5.5.1.4.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 26 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
4.v
Any RGB located within a cabinet or rack is
properly bonded back to the MGB, SSGB or
ground bus as required
The RGB is typically a small
ground bus bar located within a
cabinet or rack for bonding
equipment located within the rack
or cabinet.
The RGB shall be bonded to the
MGB or SSGB with a # 2 AWG or
coarser, ground bus conductor.
The VHF radio rack RGB
installed at the top of the rack
needs to be bonded to the MGB.
Reference can also be found in
See R56 section 5.3.3.
4.w
Individual system component chassis equipment
is properly bonded as required
All system component chassis,
panels, card cages, cross connect
panels, test jack field panels, and
other equipment that are equipped
with a ground connection point
shall be bonded to the grounding
system with a # 6 AWG jacketed
grounding conductor.
The VHF MTRs are bonded to
the IPGB which needs to be
removed and bonded to the
MGB. The FBI Quantars need to
be bonded to the MGB. All other
equipment needs to be checked.
See R56 section 5.5.1.3.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 27 - Mt Werner R56 Audit
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 28 - Mt Werner R56 Audit
10. POWER SOURCES INSPECTION RESULTS
Adherence to the National Electrical Code and applicable industry standards
is vital for the reliable and safe operation of communications equipment. In
order to make public safety communications systems as safe and reliable as
possible, the site power sources must be inspected by a qualified, licensed
electrician in order to ensure compliance with the NEC and R56 standards.
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
5.b
Proper clearance requirements are being
observed for power panels
Proper clearance around power
panels is necessary to comply with
the National Electrical Code® and
to ensure safety of personnel during
servicing.
A minimum depth clearance of 36
inches shall be provided in front of
any electrical panel that requires
operating or service.
The work space width required in
front of the electrical panel is the
greater of the width of the
equipment or 30 inches.
Equipment installed above or below
electrical panels shall not extend
more than 6 inches beyond the front
of the panel.
The batteries installed on the
ground below the electrical panel
exceed the 6 inches allowed
beyond the front of the panel.
Reference can also be found in
NFPA 70-2008, Article 110.26.
See R56 section 6.2.4.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 29 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
5.c
Outlet boxes are permanently marked to
identify their assigned circuit breakers and
panels
All communications equipment
receptacles shall have their
electrical box or cover plate
permanently marked with the
service panel and appropriate circuit
identification.
The identification shall be readily
visible without requiring the
removal of the plug.
Currently the outlet boxes are not
permanently identified with their
assigned circuit breaker and
panel.
See R56 section 6.2.10.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 30 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
5.j
AC power receptacle outlets and strips are of
the proper type and securely mounted off the
floor
Receptacle strips are limited to
specific applications where a
receptacle strip is suitable for use.
In all cases receptacle strips shall be
UL listed and of metal construction.
AC power receptacle strips shall
have a 3-prong power cord when
used for permanent installations.
Receptacle strips shall not include
ON/OFF switches unless the switch
is covered to prevent the switch
from being inadvertently switched
off.
Consumer-grade receptacle strips
shall not be used.
Receptacle strips shall be securely
mounted to the supporting structure
using appropriate hardware.
Receptacle strips shall not be
secured with tie-wraps.
The FBI installed power strip
installed below the cable tray fails
for many reasons listed above.
See R56 section 6.2.11.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 31 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
5.k
Appropriate clearance is being observed for
safe servicing of UPS and battery banks
There shall be adequate spacing for
the safe servicing of the UPS and
battery banks.
Working space for a UPS shall not
be less than 36 inches in the
direction of live parts.
The width of the working space
shall be the width of the UPS or 30
inches, whichever is greater.
The state batteries do not meet
the required 36 inches of work
space in the direction of live parts.
Reference can also be found in
NFPA 70-2008, article 110.26.
See R56 section 6.5.1.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 32 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
5.l
The neutral - ground bonding conductor has
been properly installed in the main service
disconnect as required
Unless otherwise permitted, there is
to be only one neutral-ground bond.
The neutral-ground bond is usually
found at the main disconnect panel
(first service disconnect).
Additional neutral-ground bonds
may be permitted, but only in the
case of a separately derived system
or other special applications (per the
National Electrical Code®).
More than one neutral-ground bond
can result in neutral current flowing
on the equipment grounding
conductors and/or metallic conduits.
Inspection of this audit item
typically requires a licensed
electrician. If unable to confirm
compliance, this audit item must be
failed and a follow-up inspection by
a licensed electrician is required.
The neutral-ground bonding
connection may be established with
a green grounding screw and/or an
appropriately sized bonding jumper.
Once the neutral-ground bond has
been established, the neutral
conductor shall remain isolated
from ground unless a separately
derived power source has been
installed.
Without a licensed electrician
present during the R56 audit it
could not be determined if the
proper neutral-ground conductor
has been properly installed in the
main service disconnect.
See R56 section 6.2.1.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 33 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
5.v
Fuel storage tanks for standby generators are
located within a secured area
Fuel storage tanks located outside a
structure shall be protected from
damage and tampering, and shall be
enclosed within a fenced area.
The minimum recommended
distance between the storage tank
and fence is four feet.
The minimum recommended
distance between the tank and
shelter is ten feet.
The fuel tank is not installed
inside a secure fence but it’s also
understood the Forest Service will
not allow a fence to be installed in
this location.
See R56 section 6.9.2.
11. TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS)
INSPECTION RESULTS
The installation of Transient Voltage Surge Suppression (TVSS) devices is
a requirement for all communication sites and is essential for all facilities
where communication- related electronics and electrical equipment are in
use. Surges and transient power anomalies are potentially destructive
electrical disturbances, the most damaging being over-voltage occurrences
and short duration over-voltage events. Sometimes referred to as “spikes”,
high-energy transient power anomalies can arise from inductive load
switching or other events within the power system or capacitive and
inductive coupling from environmental events such as nearby lightning
activity. Environmental and inductive power anomalies are wideband
occurrences with a frequency range from close to DC to well into the RF
high frequency spectrum. It is critical that each point of-entry (AC,
telephone, LAN, signal/control and RF) into the equipment area be
protected against these anomalies. This protection is essential to reduce the
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 34 - Mt Werner R56 Audit
risk of personal injury, physical equipment damage, and loss of operations
(equipment down time). Although lightning can cause the most visible
damage, it is not the predominant cause of transient voltages.
AUDIT
ITEM
AUDIT
REQUIREMENT
RECOMMENDED CORRECTIVE ACTION
6.c
Primary SPDs for
telephone circuits are
installed as required
The SPD shall be installed at the entrance point into the
shelter and within close proximity to the electrical service
entrance and the master ground bus bar.
The SPD shall comply with all applicable codes, and be UL
497 listed or conform to the international CE certification
mark.
SPDs that have the grounding conductor incorporated by
the manufacturer as an integral part of the device shall
utilize a # 10 AWG, green jacketed, stranded copper
conductor for a single line device. A multi-line device shall
utilize a # 6 AWG, green jacketed, stranded copper
conductor.
A primary SPD for the telephone circuits installed by
the FBI could not be found.
Reference can also be found in NFPA 70-2008, article 800.
See R56 section 7.5.
12. Installation Inspection Results Adhering to good installation practices and following industry guidelines
for installations of communications equipment helps to ensure the safety of
personnel working at the site, ease of maintenance, and proper functioning
of communications equipment. Refer to RF56 section 9 for requirements.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 35 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
7.a
Equipment spacing and aisle widths conform to
guidelines
A minimum depth clearance of 36
inches shall be provided in front of
any electrical panel that requires
operating or service.
A 36 inch aisle shall be maintained
between at least one end of an
equipment row and building wall or
other obstruction. Longer aisles
may require additional 36 inch
access breaks such that a fire in the
aisle does not prevent egress.
As stated in audit item 5b. The
batteries on the floor prevent the
required 36 inches of clearance in
front of the electrical panel.
Also 36 inches of clearance is
required between the 2 rows of
equipment (this would be difficult
to maintain with the size of the
interior).
Reference can also be found in
NFPA 70-2008, article 110.
See R56 section 9.3.1.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 36 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
7.f
Cables and cable groups of different function
maintain a minimum 5 cm (2 in.) separation as
required
The four groupings are RF lines;
power cables; ground conductors;
and control, data, telephone, alarm
and reference cables.
Cable groups shall be separated by a
minimum distance of 2 inches from
other cable groups.
Different cable groups can come in
contact with each other if they are
installed and secured so as to
maintain a 90 degree angle crossing.
Transmission lines for transmitting
equipment shall be separated a
minimum distance of 4 inches from
electrical lights, power, and
signaling circuits.
The required 2 inches of
separation between different
cables groups in not maintained in
the cable tray.
Reference can also be found in
NFPA 70-2008, Articles 800, 810,
820, 830 and ANSI/TIA/EIA-568-B
and 569-B.
See R56 sections 9.9.1.5 & 9.9.3.2.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 37 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
7.j
Cables are properly secured at the required
intervals
Cables and conductors shall be
secured at intervals of no greater
than 3 feet.
Nonmetallic cable ties shall be used
to secure cables and conductors.
Attachments shall be tight enough to
secure cables, yet not crushing the
cable.
Communication cables or wires
shall not be strapped, taped, or
attached by any means to the
exterior of any electrical conduit or
electrical raceway.
The CAT-5 cables around the
room need to be properly secured.
Reference can also be found in
NFPA 70-2008, article 800 and
ANSI/TIA/EIA-568-B and 569-B.
See R56 section 9.9.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 38 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
7.l
Cables are properly identified with a standard,
double-ended system
Because the cables are installed in
groupings, it may be difficult to
follow the individual cable for
servicing. All cables must be
properly labeled.
Cables shall be identified with a
standardized, double-ended system
to facilitate cable and equipment
connection identification. Note the
following requirements for cable
labeling:
-Equipment identification for each
end of cable.
-Connector reference designator for
each end of cable.
-Direction along the cable where
terminating equipment is used.
Labeling shall indicate the
destination ends of the cable, in
terms of equipment name and
connector reference designator or
name.
Most CAT-5, RF and electrical
cables do not meet the proper
form of label.
Reference can also be found in
ANSI/TIA/EIA-606.
See R56 section 9.9.12.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 39 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
7.m
Distribution frame wiring conforms to the
proper punch-down or wire-wrap techniques
Cross-connect wires shall be # 22 -
# 24 AWG plastic-insulated solid
copper wire.
Stranded wire shall not be used.
Wiring shall be properly secured
using industry-standard methods.
CAT 3, 4, 5, or 6 data wiring shall
enter punch terminals from the
middle such that one wire points up
while the other wire points down.
In this manner, the cable twist that
maintains the cable impedance stays
intact.
The wires in the “old” microwave
do not conform to the proper
requirement listed above.
See R56 section 9.9.11.
MT WERNER SITE
Wireless Advanced Communications 3901 West Service Road, Evans, CO. 80620 Tel: 800-456-0247
- 40 - Mt Werner R56 Audit
AUDIT
ITEM
AUDIT REQUIREMENT RECOMMENDED
CORRECTIVE ACTION
7.s
Electrostatic discharge practices are observed
as required
Static wrist straps shall be available
at the site.
Static proof packaging shall be
available at the site for storage and
transportation of static sensitive
components.
All precautions specifically stated
for the equipment being worked on
shall be adhered to in accordance
with the respective documentation
for the equipment.
An ESD wrist strap shall be worn
when handling ESD-sensitive
modules.
ESD-protected packaging shall be
available for containing modules
removed from equipment.
Static wrist straps and static proof
packaging need to be added to the
building.
Reference can also be found in
Motorola publication 68P81106E84.
See R56 section 9.10.