© 2002 Eaton Corporation. All rights reserved.
Powerware P65 UPS
4500 Watts / 5000 VA
208-240 Vac models
p65pres.ppt rev 09/13/05
2
Agenda
Key Benefits and Features Applications Product Features Overview Software and Connectivity Options Power Connection Examples Why P65? Collaterals
3
P65 Key Benefits
Consider the P65 if you… Have multiple PDUs
• 1-2 PDUs in a non-redundant power configuration
• 2-4 PDUs in a dual-redundant power configuration Want to maximize 30A/32A input (mains) power connection
capacity by providing 4,500 watts of output power Desire smallest space with highest watt/per U output
available (1800 Watts of power per U) Need flexibility in runtime, communication and output
connections Want the low-cost per Watt solution
4
P65 Key Features
High-Power Density – 3U Rack Height & High Power Factor 0.9pf Load-Segments Hot-Swappable batteries & Power Module Advanced Battery Management (ABM®) Technology Informative User Interface Power Management Software Native USB & Serial Port, unpopulated X-Slot Interface Bay Feature-Rich Options
Extended Battery Modules (EBMs) X-Slot Communications Cards for Web/SNMP, AS/400, AS/400 & Serial 120V convenience PDU Multiple PDU’s
5
• i5 servers
• iSeries servers
• p5 servers
• pSeries servers
Feature-rich, advanced power protection for:
P65 Applications
6
Application Matrix
Expected RuntimeIBM Server Watts Vac P65 (in minutes)
i5-iSeries
9406-520 Rack-mount 600 200-240 60+
9406-550 Rack-mount 1100 200-240 45
9406-570 2-4 Way 1300 200-240 35
9406-570 5-8 Way 2600 200-240 17
9406-570 9-12 Way 3900 200-240 9
9406-570 13-16 Way 5200 200-240 Select P93 or larger UPS
7
Application MatrixExpected
IBM Server Watts Vac P65 Runtime
p5-pSeries and OpenPower
9110-510 475 200-240 70+
9111-520 Rack-mount 600 200-240 60+
9113-550 Rack-mount 1100 200-240 45
9124-570 2-4 Way 1300 200-240 35
9124-570 5-8 Way 2600 200-240 17
9124-570 9-12 Way 3900 200-240 9
9124-570 13-16 Way 5200 200-240 Select P93 or larger UPS
7028-6C4 p630 750 200-240 60+
7029-6C3 P615 450 200-240 70+
9123-710 700 200-240 60+
9124-720 1572 200-240 28
8
P65 Product Snapshot P65
IBM Feature Code 9910-P65
IBM Part Number 39J2534
Topology Line-interactive
Power Rating 4500 Watts/5000 VA
Voltage 208, 220, 230, 240 Vac, Single Phase
Frequency 50/60 Hz
Configuration Rackmountable
Dimensions (HxWxD) 5.1 x 17.5 x 26 in
Weight 161.0 lbs
Input Connection L6-30P on 1.5ft cord
Output Connection (1) L6-30R on 2ft cord, (4) IEC-320-C13, (4) IEC-320-C19
Battery Runtime (half/full) 17/5 minutes
Color Black
9
High-Power Density
The most dense, power packed UPS available - offering customers more watts per U than any other UPS - allowing for more valuable rack space to be utilized by all your server, storage and networking equipment.
Compact UPS – Up to 4500 Watts in a 3U package including batteries
5.1” height
17.5” width
26.0” depth
10
Series 5 Power ProtectionThe P65 delivers power protection from power problems that threaten your equipment and priceless data
Power Failures
Power sags
Power surges
Brownouts
Overvoltage
The P65 also offers varying degrees of protection against other power problems as well
11
Advanced Battery Management(ABM®) Technology
Increases battery service life by charging only when needed
Optimizes recharge time Does not trickle charge & starve the electrolyte Microprocessor controlled – only true and automatic
battery check (periodic, controlled discharge) for accurate advanced battery failure protection
Sleep features – no unnecessary battery drain
12
Superior Voltage Regulation
Wide voltage input range -- Accommodates severe environments Tight output voltage -- provides “clean” power to connected
equipment Regulates voltage without using battery -- maximizes battery service
life
Nominal Voltage+6%
-10%
+20%
-30%
Input Voltage to UPS Output Voltage to Load
13
Load Segments Provides Load Control:
Power down sequencing of Load Segments• Extends runtime for critical devices
Power up sequencing of Load Segments• Orderly power up of connected devices
Scheduled on/off times• Cycle off equipment for security and power conservation
14
Hot-swappable Electronics and Battery Modules
When batteries reach the end of their useful life or the electronics modules fail, replacement is easy. With simple access through the front panel, users can safely install new battery and electronics modules without ever powering down connected server and server options or having to remove the unit from the rack
Batteries Electronics
Modular Design • Ease of service• High availability• Faster mean time to repair
Automatic Bypass:
• Allows you to continue working even while you’re hot-swapping the modules
16
Supports Non- & Dual-Redundant Power
1. UPS input (mains) power cord2. PDU to UPS power cord3. PDU to utility (mains) power cordTVSS – Transient Voltage Surge
Suppression.
17
Simple, User-friendly Interface
On
Off/Standby
Test/Alarm reset
Load level LEDs
1. General Alarm 3. Bad Battery/Low Battery 5. Utility LED2. On Battery 4. Site Wiring Fault Indicator
1 2 3 4 5
18
P65 Out-of-Box Usability
9910 philosophy of a complete package UPS, power & communication cables, software,
mounting hardware and manuals
19
ConnectivityWhat you need by application
Software Solution zSeries i5-Series p5-pSeries xSeries Storage Networking
LanSafe
AS/400 and serial (TTY) communication (IBM FC 2939)
NetWatch and ConnectUPS ! Web/SNMP card (IBM FC 2934) LPARs
Powerware Extensions for IBM Director
NetWatch
ConnectUPS Relay card andAS/400 cable (IBM FC 2936)
!Use ConnectUPS Web/SNMP/xHub card, IBM FC 2934 to support LPAR (POWER 4 Chip Set) servers. For p5 & pSeries configurations, each LPAR needs a network connection and will install Powerware provided NetWatch or LanSafe software.
20
Powerware Software SuiteThe industry’s most comprehensive software bundle, The Powerware Software Suite, is free and included with every P65
Power Management Software
Software Wizard guides you through software selection and installation. In addition to multimedia demonstrations, product data sheets, and video clips, the Software Suite contains the following power management software:
• LanSafe™ Network UPS shutdown and monitoring software
• PowerVision® (30-day trial version) UPS performance analysis and monitoring software
• Foreseer® (demonstration) facility and data center management software
21
Software Application Powerware
Extensions for Application LanSafe NetWatch IBM Director
Single p5-pSeries (serial/TTY) non-LPAR
Single p5-pSeries (network) non-LPAR * *
Single p5-pSeries (LPAR) *
Multiple p5-pSeries (non-LPAR) *
Multiple p5-pSeries (LPAR) *
IBM Director Network Device *
* Co-requisite FC 2934 ConnectUPS Web/SNMP network card.
Note: UPS for iSeries applications utilize OS/400 UPS monitoring functions.
22
Software Comparison Ambient
Email/ SSL/SSH1 TemperatureApplication Monitoring Shutdown GUI SMTP Security Humidity
LanSafe Yes Yes Yes Yes / Yes No/No No/No
NetWatch - Yes - No/No No/No No/No
ConnectUPS Web/ Yes2 Yes3 Yes Yes / Yes Yes / Yes Yes / Yes4
SNMP Card(FC 2934)
1SSL = Secure Sockets Layer. SSH = Secure Shell. 2Via Web Browser, LanSafe or Network Management System (e.g. IBM Director, Tivoli). 3In conjunction with NetWatch software. 4With optional FC 2938 EMP (Environmental Monitoring Probe) device attached.
23
P65 Options
Extended Battery Modules (EBMs) #6641 X-Slot Interface Cards
#2934 Web/SNMP/xHUB• Environmental Monitoring Probe #2938
#2936 Relay Interface #2939 Relay-Serial Interface
IBM Director Snap Ins 120V Convenience PDU #2916 IBM PDU to UPS Power Cord #2974
24
P65 Options MatrixIBM IBM Quantity for Quantity for Feature Part p5/pSeries Rack i5/iSeries Rack Code Number Description Worldwide Worldwide
2934 53P4619 ConnectUPS-X Web/SNMP card Kit Min:0, Max: 1 —
2936 97P3886 Relay Card and Cable Kit — Min: 0, Max: 1
2939 39J2627 Relay-Serial Card and Cable Kit — Min: 0, Max: 1
2938 38P9307 Environmental Monitoring Probe Min:0, Max: 1 and CAT 5 Cable Kit Co-requisite: FC 2934 —
6641 38P9300 Extended Battery Module (EBM) Min:0, Max: 4 Min:0, Max: 4
38P9311 EBM Accessory Kit 1 per FC 6641 1 per FC 6641
6631 97P5672 Left Adjustable Rail Assembly 1 per FC 6641 1 per FC 6641 (with rear hold-down bracket)
97P5673 Right Adjustable Rail Assembly 1 per FC 6641 1 per FC 6641 (with rear hold-down bracket)
53P1965 Rail Hardware Kit 1 per FC 6641 1 per FC 6641
97P5674 Rack Mounting Bracket Kit 1 per FC 6641 1 per FC 6641
2916 04N7025 120V Convenience PDU Min:0, Max: 1 Min:0, Max: 1(for modems, etc.)
2974 39J2590 PDU to UPS power cord for second PDU Min: 0, Max: 1 Min: 0, Max: 1
25
Option – EBMs
Add up to 4 EBMs (#6641) to extend backup time Each EBM occupies only 3U of rack space Hot-swap capability allows you to expand run times or replace
battery modules while keeping your critical load up and running
Attach EBMs with simple daisy-chain connection
Up to 4 EBMs3U rack height each
26
Battery Runtime (in minutes)
P65 Extended Battery Modules are FC #6641. This guide provides typical application information. Battery runtimes are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.
Standard Load Internalin Watts Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
900 59 169 303 452 612
1800 26 79 138 204 274
2250 19 61 106 156 210
2700 15 49 85 125 168
3150 13 43 73 110 142
4050 8 27 52 76 89
4500 7 24 46 67 80
27
X-Slot Communications Options
Web/SNMP/xHUB Card (optional), FC 2934, adds direct control and monitoring capabilities in SNMP-based networks. Ability to monitor UPS status and meters through web browser interface. Ideal for LPAR p5-pSeries applications
Relay Card (optional), FC 2936, adds integration to industrial environment and building management systems, shutdowns for IBM AS/400
Relay Serial Card and Cable Kit, FC 2939 provides DB-9 and DB-25 serial interface between the UPS and IBM i5-iSeries (AS/400) server and Serial Server (Microsoft Windows, Linux, AIX, or other operating systems)
Environmental Monitoring Probe (EMP), FC 2938 works with the ConnectUPS Web/SNMP card, remotely monitoring temperature, humidity, and the status of two contacts/sensors, such as smoke detector and open-door detector
28
Web/SNMP Card shown
Option – X-Slot Web/SNMP/xHub Card (#2934)
Web/SNMP/xHUB Card (optional), #2934, adds direct control and monitoring capabilities in SNMP-based networks. Ability to monitor UPS status and meters through web browser interface. Ideal for LPAR p5-pSeries applications
29
Relay card shown
*Single part number for Relay card and 25 ft. interface cable
Option – X-Slot Relay Card (#2936)
The Relay Interface card provides monitoring of UPS status through isolated, dry contact, Form-C relays. It also provides the interface for AS/400 (iSeries) computers as well as many industrial applications.
Features include: Isolated, dry contact Form-C relays for “utility failure”,
“low battery”, “UPS Alarm/OK” or “on bypass” User-selectable “normally open” or “normally closed” contacts Remote shutdown of UPS through integrated shutdown functions Hot-swappable - - UPS maintains power to critical applications while changing cards Replaces UPS X-Slot communications card 25 foot MT 9406 interface cable included IBM #2936, IBM PN 97P3886, Powerware PN 103003564*
30
Option – X-Slot Relay-Serial Card (#2939)The Relay-Serial Interface card provides
shutdown and monitoring of UPS status through
a connected i5-iSeries computer an a serial
(TTY) computer. The relay-serial interface card
provides the essential dry-contact interface (for
AS/400) and simultaneous serial communication
to any Wintel, LINUX, AIX or other common
O/S computer. Features include:
Isolated, dry contact Form-C relays for “utility failure”, “low battery”, “UPS Alarm/OK” or “on bypass”
User-selectable “normally open” or “normally closed” contacts Remote shutdown of UPS through integrated shutdown functions Hot-swappable - - UPS maintains power to critical applications while changing cards Replaces UPS X-Slot communications card 25 foot MT 9406 interface cable included 6 foot serial interface cable included IBM #2939, IBM PN 39J2627, Powerware PN 103004741-5501
Relay-Serial Card shown
31
Option – Powerware Extensions Software for IBM Director Seamless UPS and software
integration into IBM Director Network Management System (NMS)
Real time monitoring, management and alarm notification of all UPSs in the network: e.g. battery status, battery replacement, load level and metering information
Automatically launches LanSafe and ConnectUPS Web/SNMP Card applications from within Director
Available on Powerware web
FREE-OF-CHARGE
32
Option – 120V Convenience PDU (#2916)
The 120V Convenience PDU is ideal for low power loads such as a modem or a display
Mounts in side pocket of the rack
2 x NEMA 5-15 receptacles 250VA capacity Powered from C13 receptacle
on P65 or rack PDU Min: 0, Max: 2
33
Option – PDU to UPS Power Cord (#2974)
The PDU to UPS Power Cord, #2974, is ideal for powering a second PDU from the P65
Non-redundant power support for 2 PDUs
Dual-redundant power support for 4 PDUs
Plugs into C19 Outlet (receptacle) on rear of P65 Min: 0, Max: 1
36
Why P65?
Consider the P65 if you… Have multiple PDUs
• 1-2 PDUs non-redundant power
• 2-4 PDUs dual-redundant power Want to maximize 30A/32A input (mains) power connection
capacity by providing 4,500 watts of output power Desire smallest space with highest watt/per U output available
(1800 Watts of power per U) Need flexibility in runtime, communication and output
connections Want the low-cost per Watt solution
37
P65 Collaterals
Additional information available at
www.powerware.com/ibm Select your region. Click “Products”, click “9910 Solutions”
then click “Powerware pSeries” or “Powerware iSeries”
Materials available Data sheet Application overview chart Product presentation Documents (manuals)