+ All Categories
Transcript
Page 1: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

2015 CLEAN AND SAFE DRINKING WATER WORKSHOPCanada Pipe Company ULC

March 24, 2015

Page 2: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

OVERVIEW

• McWane Ductile & Canada Pipe• Corrosion Control (Poly Wrap)• Tuberculation (Cement Mortar Lining)

• Environmental Sustainability• Cast Iron vs. Ductile Iron • New Developments

– TR Flex– McWane Pocket Engineer

Page 3: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Corrosion“The Elephant in the Room” 

*THE DETERIORATION

OF A MATERIAL BY REACTION WITH

IT’S ENVIRONMENT

Page 4: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Polyethylene Investigation:Neihart, Montana

Installed: 1892 – Inspected: 1992Member: Cast Iron Pipe Century Club

Page 5: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Installed: 1892 – Inspected: 1992Member: Cast Iron Pipe Century Club

Pipe InvestigationPrinceton, Kentucky

Installed: 1963/1964 – Inspected: 1998

Page 6: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Installed: 1892 – Inspected: 1992Member: Cast Iron Pipe Century ClubInstalled: 1963/1964 – Inspected: 1998

Polyethylene Encasement“Corrosion Control”

Possible Moisture

Overlap

Page 7: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Installed: 1892 – Inspected: 1992Member: Cast Iron Pipe Century ClubInstalled: 1963/1964 – Inspected: 1998

Polyethylene Encasement“Corrosion Control”

Page 8: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Installed: 1892 – Inspected: 1992Member: Cast Iron Pipe Century ClubInstalled: 1963/1964 – Inspected: 1998

Polyethylene Encasement“Corrosion Control”

Page 9: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Installed: 1892 – Inspected: 1992Member: Cast Iron Pipe Century ClubInstalled: 1963/1964 – Inspected: 1998

Questions?

Page 10: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Tuberculation

Page 11: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Tuberculation‐ A build up of Sediment, Dirt or Rust

‐ Can Drastically reduce the Inside Diameter of the Pipe

‐ Interrupts and restricts the flow of Water Supply

Page 12: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Cement Mortar Lining

Page 13: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Cement Mortar Lining

• To prevent Tuberculation in Ductile Iron Pipe 

• Every Piece of  Pipe Used for the Transportation of Water goes Through this Process

• Became standard in Canada in 1976

• 1968‐1976 Ductile with no Cement Lining Could be Found 

• The Ductile Iron Pipe Research Association (DIPRA) Published a Brochure Solely on this Cement Mortar Lining which I can Provide to Anyone Interested

Page 14: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Environment:Sustainable development

Ductile Iron is Gold certified

Page 15: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Sustainable Development:Smart certification

• Safe for public health and environment

• Recycled materials

• Sustainable reuse / end of life management

• Energy efficiency

• 100 year design life

Page 16: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Environment:Manufacturing Ductile Iron

• Ductile Iron is made from 100 % recycled scrap ion and steel.

• Ductile Iron is 100 % recyclable.

• Ductile has 100 years of service life.

Page 17: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Sustainable DevelopmentProducts and by-products• Ductile Iron is made from 100% recycled iron and steel.• Ductile Iron is 100 % recyclable.• The by‐products of manufacturing are recyclable.• All Ductile Iron pipe manufacturers have a “buy‐back” policy

for Ductile Iron and Cast Iron pipes removed from service

Manufacturing• Manufacturing is a closed-loop process.• Waste heat from production is re-used.• Minimal water discharges, all waste waters are treated on-site before discharge.• Spent foundry sand is recycled and used as construction material.• Contaminants are removed from gas streams before venting to the atmosphere.

Page 18: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Raw Materials

Page 19: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

CAST IRON VS. DUCTILE IRON

• Ductile was Introduced to Canada in 1961

• From 1961 to 1968 Utilities were able to use Cast or Ductile

• In 1968 Cast Iron was no Longer Used with Specifications Shifting to Ductile Iron

Page 20: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Magnesium Treatment

• Iron:Molten at 2,500° F

• Magnesium:Vaporizes at 2,050° F

Page 21: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Typical Chemical Analysis

Gray Iron Ductile Iron3.00 - 3.75 ------------ Carbon ------------ 3.60

1.00 - 2.75 ------------ Silicon ------------ 2.40

0.90 max --------- Phosphorus --------- 0.05

0.20 - 1.00 --------- Manganese --------- 0.30

0.90 max ------------- Sulfur ------------- 0.01

N/A --------- Magnesium --------- 0.03

Page 22: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Photomicrographs

Ductile Iron Gray Iron

Page 23: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Comparative Strength(Minimum Standard Values)

35,000 psi

60,000 psi

30%

Yield Strength42,000 psi

Tensile Strength60,000 psi

10%Elongation

30,000 psi

Grade B Steel Ductile Iron Gray Iron

Page 24: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Casting Machine

Page 25: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Annealing

Page 26: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Ductile Iron impact Strength

Page 27: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Ductile Iron Beam Strength

Page 28: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Installed: 1892 – Inspected: 1992Member: Cast Iron Pipe Century ClubInstalled: 1963/1964 – Inspected: 1998

THANK YOU

Page 29: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Installed: 1892 – Inspected: 1992Member: Cast Iron Pipe Century ClubInstalled: 1963/1964 – Inspected: 1998

WHAT’S NEW TR FLEX®  Restrained Joint Ductile Iron 

Pipe Formerly US Pipe Exclusive We Now Manufacture Under License Effective and Simple to Install and Un‐Install Available in All Pipe Classes Ideal for HDD and Bridge Crossings Easier to Insulate with Smaller Bell Seismic Rated (Nuclear Power Plants)

Page 30: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Installed: 1892 – Inspected: 1992Member: Cast Iron Pipe Century ClubInstalled: 1963/1964 – Inspected: 1998

Page 31: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Installed: 1892 – Inspected: 1992Member: Cast Iron Pipe Century ClubInstalled: 1963/1964 – Inspected: 1998

McWane Pocket Engineer

http://pe.mcwane.com

“McWane Ductile, Building Iron Strong Utilities for Generation”

Page 32: 2015 CLEAN AND SAFE DRINKING WATER WORKSHOP

Installed: 1892 – Inspected: 1992Member: Cast Iron Pipe Century ClubInstalled: 1963/1964 – Inspected: 1998

Questions?