0102 ÷ 1004 Fan-coil for professional applications, with cabinet or built-inversion1,5 ÷ 7,5 kW
a-LIFE2
1. RANGE 3
2. GENERAL DEsCRiPTioN 4
3. ACCEssoRiEs CoMPATiBiLiTY 6
4. UNiT DEsCRiPTioN 8
5. oPERATiNG LiMiTs 9
6. TEChNiCAL DATA shEET 10
7. FAN PERFoRMANCEs 16
8. PREssURE DRoP 20
9. CoRRECTioN FACToRs iN CooLiNG oPERATioNWiTh GLYCoL WATER 22
10. CoRRECTioN FACToRs iN hEATiNG oPERATioNWiTh GLYCoL WATER 23
11. soUND PREssURE LEVEL 24
12. soUND PoWER LEVEL 24
13. FANCoiL CoNTRoLs 25
14. ACCEssoRiEs 31
15. DiMENsioNAL DATA AND WATER CoNNECTioNs 48
16. ELECTRiCAL CoNNECTioNs 53
SUMMARY
a-LIFE2
2A_LIFE2_0102_1004_201306_EN
Waiver of liability
This publication represents the sole property of Climaveneta.Any reproduction or disclosure of such is strictly prohibited with-out the written authorisation of Climaveneta.This document has been prepared with maximum care andattention paid to the content shown. Nonetheless, Climavenetawaives all liability deriving from the use of such document.Read this document carefully.
All work must be performed, components selected and materi-als used professionally and in complete accordance with thelegislation in force in material in the country concerned, andconsidering the operating conditions and intended uses of thesystem, by qualified personnel.The data contained in this publication may be changed withoutprior notice.
This company participates in the Eurovent Certifi cation Programme.The products are listed in the Directory of certifi ed products.Eurovent certifi cation applied to units with cooling capacity up to 1500 kWfor air cooled water chillers and water cooled liquid chillers.
WITh cABINET ModEL
a-LIFE2 dLMV/dLMo
version with cabinet, low air intakea-LIFE2 dFMV/dFMo
version with cabinet, front air intake
1. RANGE
BUILT-IN ModEL
a-LIFE2 dLIo/dLIV
built-in version, low air intakea-LIFE2 dFIV/dFIo
built-in version, front air intake
a-LIFE2
A_LIFE2_0102_1004_201306_EN3
100 mm
100 mm
Vertical wall mounted horizontal ceiling installation
Vertical wall mounted horizontal ceiling installation
100 mm
100 mm
Vertical wall mounted horizontal ceiling installation
Vertical wall mounted horizontal ceiling installation
Fan Coil is a terminal unit for air conditioning during summer(cooling) and winter (heating).a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds ofwhich 3 are factory-set. other speeds may be requested on theorder by the customer.
a-LIFE2 dLMV
version with cabinet, low air intake, vertical installation
a-LIFE2 dLMo
version with cabinet, low air intake, horizontal installation
a-LIFE2 dFMV
version with cabinet, front air intake, vertical installation
a-LIFE2 dFMo
version with cabinet, front air intake, horizontal installation
a-LIFE2 dLIV
built-in version, low air intake, vertical installation
a-LIFE2 dLIo
built-in version, low air intake, horizontal installation
a-LIFE2 dFIV
built-in version, front air intake, vertical installation
a-LIFE2 dFIo
built-in version, front air intake, horizontal installation
output from 1,5 kW - 7,5 kW. Standard water fittings,
reversible on site.
Available in 10 different versions with centrifugal fans, suitablefor use in the tertiary sector and for small ducted installations.structure made in metal panel, with inlet and outlet plasticgrilles. Available controls Ps, MT, AT and EK, iK with use of hBpower boardAvailable wall mounted controls: PsW, MTW, ATW and EKW, iKwith use of hB Power Board.Air filter on all models.
a-LIFE2
4A_LIFE2_0102_1004_201306_EN
2. GENERAL dEScRIPTIoN
1 Casing made from galvanised and coated sheet metal with ABs front intake grill on versions DFMo/DFMV (1’), and without grill on versionsDLMo/DLMV (1)
2 Load-bearing structure made from thick galvanised sheet metal, with holes for wall/ceiling mounting + thermal insulation and soundproofingon the inside (class M1)
3 Centrifugal fan with double-sided intake4 Electric motor coupled directly to the fan5 heat exchanger coil (1 coil for 2-pipe units; 2 coils for 4-pipe units)6 Coil water connections7 Manual air vent valve8 Manual water drain valve9 Condensate collection pan with drains + thermal insulation10 Condensate drain11 Air filter (filtration grade G2)
a-LIFE2
A_LIFE2_0102_1004_201306_EN5
2. GENERAL dEScRIPTIoN
dimensions
LiFE2 DLiVbuilt-in version, low air intake,vertical installation
LiFE2 DLMVversion with cabinet, low airintake, vertical installation
LiFE2 DLiobuilt-in version, low air intake,horizontal installation
LiFE2 DLMoversion with cabinet, low airintake, horizontal installation
LiFE2 DFiVbuilt-in version, front air intake,vertical installation
LiFE2 DFMVversion with cabinet, front airintake, vertical installation
LiFE2 DFiobuilt-in version, front air intake,horizontal installation
LiFE2 DFMoversion with cabinet, front airintake, horizontal installation
Built-in
version
dLIV
0102-0104
dLIV
0202-0204
dLIV
0302-0304
dLIV
0402-0404
dLIV
0502-0504
dLIV
0602-0604
dLIV
0702-0704
dLIV
0802-0804
dLIV
0902-0904
dLIV
1002-1004
L (mm) 450 450 650 650 850 850 1050 1050 1250 1250
h (mm) 450 450 450 450 450 450 450 450 450 450
s (mm) 215 215 215 215 215 215 215 215 215 215
Built-in
version
dLIo
0102-0104
dLIo
0202-0204
dLIo
0302-0304
dLIo
0402-0404
dLIo
0502-0504
dLIo
0602-0604
dLIo
0702-0704
dLIo
0802-0804
dLIo
0902-0904
dLIo
1002-1004
L (mm) 545 545 745 745 945 945 1145 1145 1345 1345
h (mm) 450 450 450 450 450 450 450 450 450 450
s (mm) 215 215 215 215 215 215 215 215 215 215
With cabinet
version
dLMV
0102-0104
dLMV
0202-0204
dLMV
0302-0304
dLMV
0402-0404
dLMV
0502-0504
dLMV
0602-0604
dLMV
0702-0704
dLMV
0802-0804
dLMV
0902-0904
dLMV
1002-1004
L (mm) 922 922 1112 1112 1302 1302 1492 1492 1682 1682
h (mm) 499 499 499 499 499 499 499 499 499 499
s (mm) 233 233 233 233 233 233 233 233 233 233
With cabinet
version
dLMo
0102-0104
dLMo
0202-0204
dLMo
0302-0304
dLMo
0402-0404
dLMo
0502-0504
dLMo
0602-0604
dLMo
0702-0704
dLMo
0802-0804
dLMo
0902-0904
dLMo
1002-1004
L (mm) 922 922 1112 1112 1302 1302 1492 1492 1682 1682
h (mm) 499 499 499 499 499 499 499 499 499 499
s (mm) 233 233 233 233 233 233 233 233 233 233
a-LIFE2
6A_LIFE2_0102_1004_201306_EN
3. AccESSoRIES coMPATIBILITY
description a-LIFE2
dFMo dLMo dFMV dLMV dFIo dLIo dFIV dLIV
AiR iNLET GRiLLE + FiLTER LiFE2 √ √ √ √
AiR oUTLET GRiLLE + FiLTER LiFE2 √ √ √ √
PLENUM KiT LiFE2 iNLET AiR 90° √ √
PLENUM KiT LiFE2 oUTLET AiR 90° √ √ √ √
PLENUM KiT LiFE2 sTREiGhT oUTLET √ √ √ √
PLENUM KiT LiFE2 sTREiGhT iNLET √ √ √ √
PLENUM KiT LiFE2 CiRCULAR 1XD.200/180/160 (iNLET) √ √ √ √
PLENUM KiT LiFE2 CiRCULAR 1XD.200/180/160 (oUTLET) √ √ √ √
ELECTRiCAL hEATER √ √ √ √
TERMiNAL MAMUT iP20 √ √ √ √ √ √ √ √
AUXiLiARY CoNDENsATE TRAY VERTiCAL iNsT. LiFE2 √ √ √ √
AUXiLiARY CoNDENsATE TRAY hoRiZ. iNsT. LiFE2 √ √ √ √
KiT VALV MAiN CoiL 1/2" oN/oFF 2V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 1/2" PWM 2V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 3/4" oN/oFF 2V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 3/4" PWM 2V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 1/2" 3P LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 3/4" 3P LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 1/2" 0-10V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 3/4" 0-10V 2V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 1/2" oN/oFF 3V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 1/2" PWM 3V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 3/4" oN/oFF 3V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 3/4" PWM 3V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 1/2" 3P3V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 3/4" 3P3V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 1/2" 0-10V 3V LiFE2 √ √ √ √ √ √ √ √
KiT VALV MAiN CoiL 3/4" 0-10V 3V LiFE2 √ √ √ √ √ √ √ √
KiT VALV ADD. CoiL 1/2" oN/oFF 2V LiFE2 √ √ √ √ √ √ √ √
KiT VALV ADD. CoiL 1/2" PWM 2V LiFE2 √ √ √ √ √ √ √ √
KiT VALV ADD. CoiL 1/2" 3P2V LiFE2 √ √ √ √ √ √ √ √
KiT VALV ADD. CoiL 0-10V 2V LiFE2 √ √ √ √ √ √ √ √
KiT VALV ADD. CoiL 1/2 oN/oFF 3V LiFE2 √ √ √ √ √ √ √ √
KiT VALV ADD. CoiL 1/2" PWM 3V LiFE2 √ √ √ √ √ √ √ √
KiT VALV ADD. CoiL 1/2" 3P3V LiFE2 √ √ √ √ √ √ √ √
KiT VALV ADD. CoiL 0-10V 3V LiFE2 √ √ √ √ √ √ √ √
WATER KiT FoR 3-WAYs 3/4" AND 2 BALL VALVE √ √ √ √ √ √ √ √
WATER KiT FoR 2-WAYs 3/4 AND 2 BALL VALVE √ √ √ √ √ √ √ √
WATER KiT FoR 3-WAYs 1/2" AND 2 BALL VALVE √ √ √ √ √ √ √ √
WATER KiT FoR 2-WAYs 1/2” AND 2 BALL VALVE √ √ √ √ √ √ √ √
MANUAL DAMPER FoR BUiLT-iN UNiTs LiFE2 √ √ √ √
MoT. DAMPER FoR BUiLT-iN UNiTs LiFE2 √ √ √ √
MoT. DAMPER FoR WiTh CABiNET UNiTs √
MANUAL DAMPER FoR WiTh CABiNET UNiTs √
DAMPER MoToR LiFE2 √ √ √ √ √
a-LIFE2
A_LIFE2_0102_1004_201306_EN7
3. AccESSoRIES coMPATIBILITY
description a-LIFE2
dFMo dLMo dFMV dLMV dFIo dLIo dFIV dLIV
AiR iNLET GRiLL FoR WiTh CABiNET UNiTs √ √
EsTETiCAL AND sTRUTURAL FEEDs √ √ √ √
KiT ADDiTioNAL CoiL 1 RoW √ √ √ √ √ √ √ √
CLosURE PANELs LiFE2 √ √ √ √
KiT LiFE2 BoX √ √
KiT CoNTRoL MT CLiMAVENETA LiFE2 √ √
KiT REMoTE CoNTRoL PsW CLiMAVENETA LiFE2 √ √ √ √ √ √ √ √
KiT CoNTRoL MT CLiMAVENETA LiFE2 √ √
KiT REMoTE CoNTRoL REMoTo MTW CLiMAVENETA LiFE2 √ √ √ √ √ √ √ √
KiT CoNTRoL AT MoDBUs CLiMAVENETA LiFE2 √ √
KiT REMoTE CoNTRoL ATW MoDBUs CLiMAVENETA LiFE2 √ √ √ √ √ √ √ √
KiT CoNTRoL EK CLiMAVENETA LiFE2 √ √
KiT REMoTE CoNTRoLD REMoTo EKW CLiMAVENETA LiFE2 √ √ √ √ √ √ √ √
KiT CoNTRoL iK CLiMAVENETA LiFE2 √ √
CARBoN FiLTER LiFE2 DFMo/V √ √
CARBoN FiLTER LiFE2 √ √ √ √ √ √
KiT PoWE BoARD LiFE2 hB √ √ √ √ √ √ √ √
KiT Rs485 LiFE2 √ √ √ √ √ √ √ √
KiT EsPANsioNE VALV. 0-10VDC LiFE2 √ √ √ √ √ √ √ √
KiT EsPANsioNE VALV. 3PUNTi LiFE2 √ √ √ √ √ √ √ √
KiT BUs ADAPTER √ √ √ √ √ √ √ √
KiT GATEWAY BiTiCiNo √ √ √ √ √ √ √ √
KiT sPB FoR MULTRiPLE CoNNECTioNs √ √ √ √ √ √ √ √
KiT FLEssiBLE TUBEs LiFE2 √ √ √ √ √ √ √ √
a-LIFE2
8A_LIFE2_0102_1004_201306_EN
4. UNIT dEScRIPTIoN
a-LIFE2 dLMV, dLMo
covering cabinet
Comprising components made from ABs for the sides andoutlet grills (adjustable by 180°) and thick coated sheet metalfor the front panel.Protective flap for controls in ABs with tamperproof fixing screwin conformity with directive EN iso 60335-2-40 in relation toamendment A1 concerning the automatic closure of the flap andprotection of electrical controls against spillage of water.Quick-fitting controls fixing bracket.
Bearing structure
Galvanised steel frame with high rust resistance.insulated with self-extinuishing Class 1heat insulating panels.Unit fitted with condensate collection pan made from insulatedgalvanised sheet metal for vertical and horizontal installation.Terminal block for power and control connections with screwterminals for remote controls.
heat exchange
Coil with corrugated aluminium fins and copper pipes, 100%tested with dried air.The water fittings are provided with anti-torsion lock with airvent and water drainage.All units are delivered with left-hand water connections, easilyconvertible into right-hand by simply turning the coil.
Fan motor
Double intake centrifugal fans, statically and dinamically bal-anced and coupled directly to the electric motor.Powered by auto-trasformer with 6 speeds of which 3 are facto-ry-set.
Air filter
Made of metal frame and hosting the filtering material, classifi-cation G2.Comprising components made from ABs for the sides andoutlet grills (adjustable by 180°) and thick coated sheet metalfor the front panel.
a-LIFE2 dFMV, dFMo
covering cabinet
Comprising components made from ABs for the sides andoutlet grills (adjustable by 180°) and thick coated sheet metalfor the front panel.Protective flap for controls in ABs with tamperproof fixing screwin conformity with directive EN iso 60335-2-40 in relation toamendment A1 concerning the automatic closure of the flap andprotection of electrical controls against spillage of water.Quick-fitting controls fixing bracket
Bearing structure
Galvanised steel frame with high rust resistance.insulated with self-extinuishing Class 1heat insulating panels.Unit fitted with condensate collection pan made from insulatedgalvanised sheet metal for vertical and horizontal installation.Terminal block for power and control connections with screwterminals for remote controls.
heat exchange
Coil with corrugated aluminium fins and copper pipes, 100%tested with dried air.The water fittings are provided with anti-torsion lock with airvent and water drainage.All units are delivered with left-hand water connections, easilyconvertible into right-hand by simply turning the coil.
Fan motor
Double intake centrifugal fans, statically and dinamically bal-anced and coupled directly to the electric motor.Powered by auto-trasformer with 6 speeds of which 3 are facto-ry-set.
Air filter
Made of metal frame and hosting the filtering material, classifi-cation G2.Easily removable intake grille/filter by the ¼ turn screws.
a-LIFE2
A_LIFE2_0102_1004_201306_EN9
4. UNIT dEScRIPTIoN
a-LIFE2 dLIo, dLIV
Bearing structure
Galvanised steel frame with high rust resistance.insulated with self-extinuishing Class 1heat insulating panels.Unit fitted with condensate collection pan made from insulatedgalvanised sheet metal for horizontal and vertical installation.Double terminal block for power and control connections withquick connector for plug-in controls. Wall mounted controls arefixed by screws.
heat exchange
Coil with corrugated aluminium fins and copper pipes, 100%tested with dried air.The water fittings are provided with anti-torsion lock with airvent and water drainage.All units are delivered with left-hand water connections, easilyconvertible into right-hand by simply turning the coil.
Fan motor
Double intake centrifugal fans, statically and dinamically bal-anced and coupled directly to the electric motor.Powered by auto-trasformer with 6 speeds of which 3 are facto-ry-set.
Air filter
Made of metal frame and hosting the filtering material, classifi-cation G2.Filter removal is completely safe, and is simplified by turning theguides at the side to release the filter.
a-LIFE2 dFIo, dFIV
Bearing structure
Galvanised steel frame with high rust resistance.insulated with self-extinuishing Class 1heat insulating panels.Unit fitted with condensate collection pan made from insulatedgalvanised sheet metal per the horizontal and vertical installa-tion.Double terminal block for power and control connections withquick connector for plug-in controls. Wall mounted controls arefixed by screws.
heat exchange
Coil with corrugated aluminium fins and copper pipes, 100%tested with dried air.The water fittings are provided with anti-torsion lock with airvent and water drainage.All units are delivered with left-hand water connections, easilyconvertible into right-hand by simply turning the coil.
Fan motor
Double intake centrifugal fans, statically and dinamically bal-anced and coupled directly to the electric motor.Powered by auto-trasformer with 6 speeds of which 3 are facto-ry-set.
Air filter
Made of metal frame and hosting the filtering material, classifi-cation G2.The filter removal requires a tool as safety measure (accordingwith anti-tamper regulation).
5. oPERATING LIMITS
MINIMUM AVERAGE WATER TEMPERATUREdry bulb room temperature °c
21 23 25 27 29 31
Wet bulb room temperature °c.
15 3 3 3 3 3 3
17 3 3 3 3 3 3
19 3 3 3 3 3 3
21 6 5 4 3 3 3
23 - 8 7 7 5 5
Maximum water inlet temp. 80°CMaximum working pressure: 15 bar
Minimum room air temperature: 0°CMaximum room air temperature 45°C
Minimum average water temperature:
The limits specified above refer to operation with the fan at minimum speed.During extended periods in which the fan is off and of cold water is flowing through the coil, condensate may form on the outside of theappliance; consequently, the three-way valve should be installed.
FAcToRY-SET SPEEd
a-LiFE2 is provided with centrifugal fan, powered by auto-trasformer with 6 speeds of which 3 (speed wired standard 2-3-5) are factory-set by Climaveneta. other speeds may be selected on request in the order.
a-LIFE2
10A_LIFE2_0102_1004_201306_EN
6. TEchNIcAL dATA ShEET
a-LIFE2 / DLIO-DFIO 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbd power W 55 55 85 85 75 75 145 145 175 1752 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,258 0,344 0,491 0,585 0,654 0,757 0,887 0,981 1,059 1,291Mad pressure drop (1) kPa 9,0 12,7 30,8 36,1 12,6 17,2 24,2 26,9 32,9 46,8Total capacity in heating mode (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1Water flow in heating (2) m³/h 0,258 0,345 0,489 0,584 0,654 0,758 0,878 0,979 1,060 1,288Pressure drop in heating (2) kPa 7,6 10,9 26,0 34,5 10,7 14,6 20,3 23,3 29,1 40,9Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,200 0,300 0,401 0,491 0,530 0,646 0,775 0,871 0,931 1,140Mad pressure drop (1) kPa 5,4 9,6 20,5 28,0 8,2 12,4 18,5 21,2 25,5 36,5Total capacity in heating mode (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89Water flow in heating (2) m³/h 0,200 0,300 0,400 0,487 0,529 0,650 0,779 0,875 0,927 1,138Pressure drop in heating (2) kPa 4,7 8,3 17,7 24,9 7,2 10,9 16,2 18,8 22,8 32,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,172 0,257 0,356 0,398 0,491 0,520 0,699 0,775 0,811 0,930Mad pressure drop (1) kPa 4,0 7,0 16,2 20,7 7,0 8,0 15,0 16,8 19,4 24,3Total capacity in heating mode (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13Water flow in heating (2) m³/h 0,173 0,257 0,355 0,398 0,489 0,519 0,701 0,775 0,814 0,923Pressure drop in heating (2) kPa 3,5 6,2 14,1 17,3 6,2 7,1 13,3 15,0 17,9 22,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 545 545 745 745 945 945 1145 1145 1345 1345B (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 11 12 14 15 20 21 23 25 27 29
Notes:1 Room temperature 27°C d.b./19°C w.b.; Chilled water (in/out) 7/12°C2 Room temperature 20°C d.b.; Hot water (in/out) 50/* °C (with identical flow note1)3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.
a-LIFE2
A_LIFE2_0102_1004_201306_EN11
6. TEchNIcAL dATA ShEET
a-LIFE2 / DLIV-DFIV 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbd power W 55 55 85 85 75 75 145 145 175 1752 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,258 0,344 0,491 0,585 0,654 0,757 0,887 0,981 1,059 1,291Mad pressure drop (1) kPa 9,0 12,7 30,8 36,1 12,6 17,2 24,2 26,9 32,9 46,8Total capacity in heating mode (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1Water flow in heating (2) m³/h 0,258 0,345 0,489 0,584 0,654 0,758 0,878 0,979 1,060 1,288Pressure drop in heating (2) kPa 7,6 10,9 26,0 34,5 10,7 14,6 20,3 23,3 29,1 40,9Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,200 0,300 0,401 0,491 0,530 0,646 0,775 0,871 0,931 1,140Mad pressure drop (1) kPa 5,4 9,6 20,5 28,0 8,2 12,4 18,5 21,2 25,5 36,5Total capacity in heating mode (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89Water flow in heating (2) m³/h 0,200 0,300 0,400 0,487 0,529 0,650 0,779 0,875 0,927 1,138Pressure drop in heating (2) kPa 4,7 8,3 17,7 24,9 7,2 10,9 16,2 18,8 22,8 32,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,172 0,257 0,356 0,398 0,491 0,520 0,699 0,775 0,811 0,930Mad pressure drop (1) kPa 4,0 7,0 16,2 20,7 7,0 8,0 15,0 16,8 19,4 24,3Total capacity in heating mode (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13Water flow in heating (2) m³/h 0,173 0,257 0,355 0,398 0,489 0,519 0,701 0,775 0,814 0,923Pressure drop in heating (2) kPa 3,5 6,2 14,1 17,3 6,2 7,1 13,3 15,0 17,9 22,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mmB (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 11 12 14 15 20 21 23 25 27 29
Notes:1 Room temperature 27°C d.b./19°C w.b.; Chilled water (in/out) 7/12°C2 Room temperature 20°C d.b.; Hot water (in/out) 50/* °C (with identical flow note1)3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.
450 450 650 650 850 850 1050 1050 1250 1250
a-LIFE2
12A_LIFE2_0102_1004_201306_EN
6. TEchNIcAL dATA ShEET
a-LIFE2 / DLMV-DFMV / DLMO-DFMO 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbd power W 55 55 85 85 75 75 145 145 175 1752 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,258 0,344 0,491 0,585 0,654 0,757 0,887 0,981 1,059 1,291Mad pressure drop (1) kPa 9,0 12,7 30,8 36,1 12,6 17,2 24,2 26,9 32,9 46,8Total capacity in heating mode (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1Water flow in heating (2) m³/h 0,258 0,345 0,489 0,584 0,654 0,758 0,878 0,979 1,060 1,288Pressure drop in heating (2) kPa 7,6 10,9 26,0 34,5 10,7 14,6 20,3 23,3 29,1 40,9Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,200 0,300 0,401 0,491 0,530 0,646 0,775 0,871 0,931 1,140Mad pressure drop (1) kPa 5,4 9,6 20,5 28,0 8,2 12,4 18,5 21,2 25,5 36,5Total capacity in heating mode (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89Water flow in heating (2) m³/h 0,200 0,300 0,400 0,487 0,529 0,650 0,779 0,875 0,927 1,138Pressure drop in heating (2) kPa 4,7 8,3 17,7 24,9 7,2 10,9 16,2 18,8 22,8 32,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,172 0,257 0,356 0,398 0,491 0,520 0,699 0,775 0,811 0,930Mad pressure drop (1) kPa 4,0 7,0 16,2 20,7 7,0 8,0 15,0 16,8 19,4 24,3Total capacity in heating mode (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13Water flow in heating (2) m³/h 0,173 0,257 0,355 0,398 0,489 0,519 0,701 0,775 0,814 0,923Pressure drop in heating (2) kPa 3,5 6,2 14,1 17,3 6,2 7,1 13,3 15,0 17,9 22,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 922 922 1112 1112 1302 1302 1492 1492 1682 1682B (5) mm 233 233 233 233 233 233 233 233 233 233H (5) mm 499 499 499 499 499 499 499 499 499 499Operating weight (5) kg 16 17 20 21 27 28 32 33 37 38
Notes:1 Room temperature 27°C d.b./19°C w.b.; Chilled water (in/out) 7/12°C2 Room temperature 20°C d.b.; Hot water (in/out) 50/* °C (with identical flow note1)3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.
a-LIFE2
A_LIFE2_0102_1004_201306_EN13
6. TEchNIcAL dATA ShEET
a-LIFE2 / DLIO-DFIO 0104 0204 0304 0404 0504 0604 0704 0804 0904 1004ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbd power W 55 55 85 85 75 75 145 145 175 1754 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,258 0,344 0,491 0,585 0,654 0,757 0,887 0,981 1,059 1,291Mad pressure drop (1) kPa 9,0 12,7 30,8 36,1 12,6 17,2 24,2 26,9 32,9 46,8Total capacity in heating mode (2) kW 1,25 1,67 2,31 2,76 3,34 3,87 4,36 4,82 5,18 6,32Water flow in heating (2) m³/h 0,110 0,146 0,203 0,242 0,293 0,339 0,382 0,423 0,454 0,554Pressure drop in heating (2) kPa 6,2 10,7 13,3 18,6 27,0 35,6 37,5 45,2 54,6 79,1Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,200 0,300 0,401 0,491 0,530 0,646 0,775 0,871 0,931 1,140Mad pressure drop (1) kPa 5,4 9,6 20,5 28,0 8,2 12,4 18,5 21,2 25,5 36,5Total capacity in heating mode (2) kW 0,97 1,45 1,89 2,31 2,71 3,30 3,81 4,28 4,56 5,57Water flow in heating (2) m³/h 0,085 0,127 0,166 0,203 0,238 0,289 0,334 0,375 0,400 0,488Pressure drop in heating (2) kPa 3,9 8,2 9,1 13,3 18,3 26,4 29,2 36,3 43,1 62,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,172 0,257 0,356 0,398 0,491 0,520 0,699 0,775 0,811 0,930Mad pressure drop (1) kPa 4,0 7,0 16,2 20,7 7,0 8,0 15,0 16,8 19,4 24,3Total capacity in heating mode (2) kW 0,83 1,24 1,68 1,88 2,51 2,65 3,43 3,81 3,97 4,55Water flow in heating (2) m³/h 0,073 0,109 0,147 0,165 0,220 0,232 0,301 0,334 0,348 0,399Pressure drop in heating (2) kPa 2,9 6,1 7,2 9,0 15,8 17,5 24,0 29,2 33,3 42,9Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mmB (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 12 12 14 15 21 22 24 25 28 29
Notes:1 Room temperature 27°C d.b./19°C w.b., Chilled water (in/out) 7/12°C2 Room temperature 20°C d.b., hot water (in/out) 70/60°C3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.
545 545 745 745 945 945 1145 1145 1345 1345
a-LIFE2
14A_LIFE2_0102_1004_201306_EN
6. TEchNIcAL dATA ShEET
a-LIFE2
A_LIFE2_0102_1004_201306_EN15
6. TEchNIcAL dATA ShEET
a-LIFE2 / DLMV-DFMV / DLMO-DFMO 0104 0204 0304 0404 0504 0604 0704 0804 0904 1004ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbd power W 55 55 85 85 75 75 145 145 175 1754 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,258 0,344 0,491 0,585 0,654 0,757 0,887 0,981 1,059 1,291Mad pressure drop (1) kPa 9,0 12,7 30,8 36,1 12,6 17,2 24,2 26,9 32,9 46,8Total capacity in heating mode (2) kW 1,25 1,67 2,31 2,76 3,34 3,87 4,36 4,82 5,18 6,32Water flow in heating (2) m³/h 0,110 0,146 0,203 0,242 0,293 0,339 0,382 0,423 0,454 0,554Pressure drop in heating (2) kPa 6,2 10,7 13,3 18,6 27,0 35,6 37,5 45,2 54,6 79,1Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,200 0,300 0,401 0,491 0,530 0,646 0,775 0,871 0,931 1,140Mad pressure drop (1) kPa 5,4 9,6 20,5 28,0 8,2 12,4 18,5 21,2 25,5 36,5Total capacity in heating mode (2) kW 0,97 1,45 1,89 2,31 2,71 3,30 3,81 4,28 4,56 5,57Water flow in heating (2) m³/h 0,085 0,127 0,166 0,203 0,238 0,289 0,334 0,375 0,400 0,488Pressure drop in heating (2) kPa 3,9 8,2 9,1 13,3 18,3 26,4 29,2 36,3 43,1 62,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,172 0,257 0,356 0,398 0,491 0,520 0,699 0,775 0,811 0,930Mad pressure drop (1) kPa 4,0 7,0 16,2 20,7 7,0 8,0 15,0 16,8 19,4 24,3Total capacity in heating mode (2) kW 0,83 1,24 1,68 1,88 2,51 2,65 3,43 3,81 3,97 4,55Water flow in heating (2) m³/h 0,073 0,109 0,147 0,165 0,220 0,232 0,301 0,334 0,348 0,399Pressure drop in heating (2) kPa 2,9 6,1 7,2 9,0 15,8 17,5 24,0 29,2 33,3 42,9Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 922 922 1112 1112 1302 1302 1492 1492 1682 1682B (5) mm 233 233 233 233 233 233 233 233 233 233H (5) mm 499 499 499 499 499 499 499 499 499 499Operating weight (5) kg 17 18 21 22 29 30 33 35 38 40
Notes:1 Room temperature 27°C d.b./19°C w.b.; Chilled water (in/out) 7/12°C2 Room temperature 20°C d.b.; Hot water (in/out) 70/60 °C; Supplementary coil 1-row3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.
7. FAN PERFoRMANcES
a-LIFE2
16A_LIFE2_0102_1004_201306_EN
a-LiFE2 is designed to assure high pressure also with pressuredrops due to complex ducts. They come with six different fanspeeds. A particular care has been reserved to the configurationsof the three fan speeds cabled by the manufacturer.The other three fan speeds can be cabled on site.
The graphs on the following pages show the useful head or work-ing pressures in relation to the air flow and the fan speed.
NoTE: the graphs refer to the versions with 3-row coils.
a-LIFE2 0102-0104
Pre
vale
nza
utile
[Pa]
- S
tatic
use
ful h
ead
[Pa]
L1
Velocità cablate in fabbricaFactory Wired speed
L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4
L5 Velocità minima Minimum Speed L6
L2L3L5
0
10
20
30
40
50
60
70
80
90
100
Portata aria [m3/h] - Air Flow [m3/h]
0 50 100 150 200 250 300 350
Pre
vale
nza
utile
[Pa]
- S
tatic
use
ful h
ead
[Pa]
Portata aria [m3/h] - Air Flow [m3/h]
L2L3L5
a-LIFE2 0202-0204
0
10
20
30
40
50
60
70
80
90
100
0 50 100 150 200 250 300 350 400 450
L1
Velocità cablate in fabbricaFactory Wired speed
L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4
L5 Velocità minima Minimum Speed L6
Pre
vale
nza
utile
[Pa]
- S
tatic
use
ful h
ead
[Pa]
Portata aria [m3/h] - Air Flow [m3/h]
a-LIFE2 0302-0304
0
10
20
30
40
50
60
70
80
90
100
0 50 100 150 200 250 300 350 400
L2L3L5 L1
Velocità cablate in fabbricaFactory Wired speed
L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4
L5 Velocità minima Minimum Speed L6
7. FAN PERFoRMANcES
a-LIFE2
A_LIFE2_0102_1004_201306_EN17
a-LIFE2 0402-0404
Pre
vale
nza
utile
[Pa]
- S
tatic
use
ful h
ead
[Pa]
0
10
20
30
40
50
60
70
80
90
100
Portata aria [m3/h] - Air Flow [m3/h]
L1
Velocità cablate in fabbricaFactory Wired speed
L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4
L5 Velocità minima Minimum Speed L6
0 50 100 150 200 250 300 350 400 450 500 550 600 650
L2L3L5
a-LIFE2 0502-0504
Portata aria [m3/h] - Air Flow [m3/h]
L1
Velocità cablate in fabbricaFactory Wired speed
L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4
L5 Velocità minima Minimum Speed L6 0
10
20
30
40
50
60
70
80
90
100
110
120
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700
L2L3L5
Pre
vale
nza
utile
[Pa]
- S
tatic
use
ful h
ead
[Pa]
a-LIFE2 0602-0604
Portata aria [m3/h] - Air Flow [m3/h]
L1
Velocità cablate in fabbricaFactory Wired speed
L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4
L5 Velocità minima Minimum Speed L6
L2L3L5
Pre
vale
nza
utile
[Pa]
- S
tatic
use
ful h
ead
[Pa]
0
10
20
30
40
50
60
70
80
90
100
110
120
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850
a-LIFE2
18A_LIFE2_0102_1004_201306_EN
7. FAN PERFoRMANcES
a-LIFE2 0702-0704
Portata aria [m3/h] - Air Flow [m3/h]
L1
Velocità cablate in fabbricaFactory Wired speed
L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4
L5 Velocità minima Minimum Speed L6
Pre
vale
nza
utile
[Pa]
- S
tatic
use
ful h
ead
[Pa]
0
10
20
30
40
50
60
70
80
90
100
110
120
130
0 100 200 300 400 500 600 700 800 900 1000
L2L3L5
a-LIFE2 0802-0804
Portata aria [m3/h] - Air Flow [m3/h]
L1
Velocità cablate in fabbricaFactory Wired speed
L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4
L5 Velocità minima Minimum Speed L6
Pre
vale
nza
utile
[Pa]
- S
tatic
use
ful h
ead
[Pa]
0
10
20
30
40
50
60
70
80
90
100
110
120
130
0 100 200 300 400 500 600 700 800 900 1000 1100
L2L3L5
a-LIFE2
A_LIFE2_0102_1004_201306_EN19
7. FAN PERFoRMANcES
a-LIFE2 0102-0104
Portata aria [m3/h] - Air Flow [m3/h]
Pre
vale
nza
utile
[Pa]
- S
tatic
use
ful h
ead
[Pa]
0
10
20
30
40
50
60
70
80
90
100
110
120
130
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400
L1
Velocità cablate in fabbricaFactory Wired speed
L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4
L5 Velocità minima Minimum Speed L6
L2L3L5
a-LIFE2 0902-0904
Portata aria [m3/h] - Air Flow [m3/h]
L1
Velocità cablate in fabbricaFactory Wired speed
L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4
L5 Velocità minima Minimum Speed L6
Pre
vale
nza
utile
[Pa]
- S
tatic
use
ful h
ead
[Pa]
0
10
20
30
40
50
60
70
80
90
100
110
120
130
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
L2L3L5
8. PRESSURE dRoP
a-LIFE2
20A_LIFE2_0102_1004_201306_EN
1
10
100
0,10 1,00
Perd
ita d
i car
ico
[kPa
] - P
ress
ure
drop
[kPa
]
Portata acqua [m3/h] - Water Flow [m3/h]
a-LIFE2 0102 a-LIFE2 0202 a-LIFE2 0302 a-LIFE2 0402
MAIN coIL
cooLING
a-LIFE2 0102÷0402 (2 pipes)
1
10
100
0,10 1,00
Perd
ita d
i car
ico
[kPa
] - P
ress
ure
drop
[kPa
]
Portata acqua [m3/h] - Water Flow [m3/h]
a-LIFE2 0102-0302 a-LIFE2 0202 a-LIFE2 0402
MAIN coIL
hEATING
a-LIFE2 0102÷0402 (2 pipes)
1
10
100
0,10 1,00
Perd
ita d
i car
ico
[kPa
] - P
ress
ure
drop
[kPa
]
Portata acqua [m3/h] - Water Flow [m3/h]
a-LIFE2 0104-0204a-LIFE2 0304-0404
AddITIoNAL coIL
hEATING
a-LIFE2 0104÷0404 (4 pipes)
a-LIFE2
A_LIFE2_0102_1004_201306_EN21
8. PRESSURE dRoP
1
10
100
0,15 1,50
Perd
ita d
i car
ico
[kPa
] - P
ress
ure
drop
[kPa
]
Portata acqua [m3/h] - Water Flow [m3/h]
a-LIFE20502-0602-0702
a-LIFE20802-0902-1002
MAIN coIL
cooLING
a-LIFE2 0502÷1002 (2 pipes)
1
10
100
0,15 1,50
Perd
ita d
i car
ico
[kPa
] - P
ress
ure
drop
[kPa
]
Portata acqua [m3/h] - Water Flow [m3/h]
a-LIFE20502-0602-0702
a-LIFE20802-0902-1002
MAIN coIL
hEATING
a-LIFE2 0502÷1002 (2 pipes)
1
10
100
0,10 1,00
Perd
ita d
i car
ico
[kPa
] - P
ress
ure
drop
[kPa
]
Portata acqua [m3/h] - Water Flow [m3/h]
a-LIFE2 0504-0604a-LIFE2 0704-0804 a-LIFE2 0904-1004
AddITIoNAL coIL
hEATING
a-LIFE2 0504÷1004 (4 pipes)
a-LIFE2
22A_LIFE2_0102_1004_201306_EN
9. coRREcTIoN FAcToRS IN cooLING oPERATIoN WITh GLYcoL WATER
1,2
1,1
1,0
0,9
0,8 6 7 8 9 10 11 12 13 14 15 16 17 °C
GLYcoL WATER AT 10%
Perdite di caricoPressure drop
ResaCapacity
PortataWater flow
Fa
tto
re d
i c
orr
ezio
ne
- C
orr
ec
tio
n f
ac
tor
1,2
1,1
1,0
0,9
0,8
0,7
0,6 6 7 8 9 10 11 12 13 14 15 16 17 °C
GLYcoL WATER AT 20%
Perdite di caricoPressure drop
ResaCapacity
PortataWater flow
Fatt
ore
di
co
rrezio
ne -
Co
rrecti
on
facto
r
1,6 1,5 1,4 1,3 1,2 1,1 1,0 0,9 0,8 0,7 0,6 0,5
6 7 8 9 10 11 12 13 14 15 16 17 18 °C
GLYcoL WATER AT 35%
Perdite di caricoPressure drop
ResaCapacity
PortataWater flow
Fatt
ore
di co
rrezio
ne -
Co
rrecti
on
facto
r
a-LIFE2
A_LIFE2_0102_1004_201306_EN23
10. coRREcTIoN FAcToRS IN hEATING oPERATIoN WITh GLYcoL WATER
1,4
1,3
1,2
1,1
1,0
0,6
0,830 40 50 60 70 80 90 °C
1
GLYcoL WATER AT 10%
Perdite di caricoPressure drop
ResaCapacity
PortataWater flow
Fa
tto
re d
i c
orr
ezio
ne
- C
orr
ec
tio
n f
ac
tor
1,4
1,3
1,2
1,1
1,0
0,6
0,830 40 50 60 70 80 90 °C
1
GLYcoL WATER AT 20%
Perdite di caricoPressure drop
ResaCapacity
PortataWater flow
Fatt
ore
di
co
rrezio
ne -
Co
rrecti
on
facto
r
1,4
1,3
1,2
1,1
1,0
0,6
0,830 40 50 60 70 80 90 °C
GLYcoL WATER AT 35%
Perdite di caricoPressure drop
ResaCapacity
PortataWater flow
Fatt
ore
di co
rrezio
ne -
Co
rrecti
on
facto
r
a-LIFE2
24A_LIFE2_0102_1004_201306_EN
11. SoUNd PRESSURE LEVEL
sound pressure levels in semi-anechoic chamber 1 (m) from fan at front and 1 (m) above the floor
Modela-LIFE2
0102-0104 0202-0204 0302-0304 0402-0404 0502-0504 0602-0604 0702-0704 0802-0804 0902-0904 1002-1004
sound pressure level at the minimum air flow dB(A) 28 37 36 37 37 39 47 44 41 45
sound pressure level at the average air flow dB(A) 31 39 37 42 39 45 44 47 45 51
sound pressure level at the maximum air flow dB(A) 39 45 42 47 45 50 41 50 48 55
a-LIFE2 0102-0104 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz
dB(A)
Minimum speed 29,1 29,9 28,3 20,3 14,3 10,5 4,7Medium speed 29,6 31,2 30,4 24,0 20,2 12,3 1,3Maximum speed 36,6 38,2 37,6 32,6 29,7 24,7 14,4
a-LIFE2 0302-0304 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz
dB(A)
Minimum speed 38,3 35,4 36,3 30,2 25,6 17,6 10,8Medium speed 36,3 38,1 35,5 30,1 28,1 21,9 13,1Maximum speed 41,2 43,0 39,6 35,0 33,3 28,9 24,4
a-LIFE2 0402-0404 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz
dB(A)
Minimum speed 36,6 39,1 37,0 30,9 26,3 18,3 11,5Medium speed 42,0 43,8 41,2 35,8 33,8 27,6 18,8Maximum speed 46,6 48,4 44,6 39,7 38,0 33,6 29,1
a-LIFE2 0502-0504 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz
dB(A)
Minimum speed 36,5 38,5 37,9 28,6 25,3 20,7 15,1Medium speed 37,9 39,7 39,3 32,9 29,3 22,0 12,9Maximum speed 42,6 44,9 44,1 38,2 35,3 28,6 20,0
a-LIFE2 0202-0204 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz
dB(A)
Minimum speed 37,6 37,7 37,0 29,0 23,0 19,2 13,4Medium speed 38,3 39,2 39,1 32,7 28,9 21,0 10,0Maximum speed 43,3 44,1 44,3 39,3 36,4 31,4 21,1
a-LIFE2 0602-0604 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz
dB(A)
Minimum speed 38,2 40,2 39,6 30,3 27,0 22,4 16,8Medium speed 44,8 45,7 45,0 38,6 35,0 27,7 18,6Maximum speed 49,9 50,2 49,8 43,9 41,0 34,3 25,7
a-LIFE2 0702-0704 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz
dB(A)
Minimum speed 42,7 47,5 46,5 40,3 37,5 28,8 17,2Medium speed 38,5 42,8 42,5 37,9 35,8 30,7 21,3Maximum speed 37,4 41,0 39,3 35,1 34,2 29,5 22,2
a-LIFE2 0802-0804 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz
dB(A)
Minimum speed 39,7 44,5 43,5 37,3 34,5 25,8 14,2Medium speed 41,5 45,8 45,5 40,9 38,8 33,7 24,3Maximum speed 46,4 50,0 48,3 44,1 43,2 38,5 31,2
a-LIFE2 0902-0904 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz
dB(A)
Minimum speed 34,5 40,5 39,9 35,3 33,3 24,8 15,4Medium speed 39,3 42,5 41,9 40,9 37,2 31,9 23,4Maximum speed 43,8 47,6 45,5 42,1 40,7 37,1 29,5
a-LIFE2 1002-1004 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz
dB(A)
Minimum speed 34,2 40,2 39,6 35,0 33,0 24,5 15,1Medium speed 40,0 43,2 43,5 39,9 37,9 32,6 24,1Maximum speed 43,5 47,3 45,2 41,8 40,4 36,8 29,2
12. SoUNd PoWER LEVEL
sound power on the basis of measurements made in compliance with Eurovent 8/2
Modela-LIFE2
0102-0104 0202-0204 0302-0304 0402-0404 0502-0504 0602-0604 0702-0704 0802-0804 0902-0904 1002-1004
sound power level max. speed (2) dB(A) 48 54 51 56 54 59 56 59 57 64
sound power level med. speed (3) dB(A) 40 48 46 51 48 54 53 56 54 60
sound power level min. speed (5) dB(A) 37 46 45 46 46 48 50 53 50 54
a-LIFE2
A_LIFE2_0102_1004_201306_EN25
13. FANcoIL coNTRoLS
on board controls PS
The Ps control is used to regulate the airflow (3 speeds), select the summer/winter mode of operation and switch the fan-coil on/off andhot start function by minimun thermostat kit.
Function selector
Cooling
heating
off
Fan selector
Maximum fan speed
Medium fan speed
Minimum fan speed
Electrical connections
IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer)
ComBU RD WH BN GNYE
MaxMedMin
CMV
AU
TR
BU BN
YV2 BU BN
L
N L L L L L L
PEN
230V~50/60Hz
IG
1 2 3 4 5 6 7
123456789
10
YV1 2 1
J2 Acqua - Water BT2
GNYEBN BU
Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue
WHRD
Bianco - White Rosso – Red
L N PE
Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth
Com Min Med Max
Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)
MV C AUTR BT2
Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda acqua – Water sensor
ACCESSORI – ACCESSORIESYV1 YV2
Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve
J2
3 4 5 6 7
L L N
UNITÀ 2-TUBI: Eseguire questo collegamento sempre in caso di una sola valvola. 2-PIPES UNIT: Always carry out this connection when there is just one valve.
Valvola Valve7
8BN BU
a-LIFE2
26A_LIFE2_0102_1004_201306_EN
13. FANcoIL coNTRoLS
on board controls MT
The MT control is used to regulate the air (3 speeds), the temperature through electronic thermostat, to select the summer/winter modeof operation and to switch the fan-coil on/off.
Temperature selector
Adjust the temperature as required by turning the temperature selectorfrom +14°C to 30°C.
Led description
Blue Led: indicates fan-coil thermostat call
Function selector
Cooling
heating
off
Fan selector
Maximum fan speed
Medium fan speed
Minimum fan speed
Electrical connections
IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer)
ComBU RD WH BN GNYE
MaxMedMin
CMV
AU
TR
BU BN
YV2 BU BN
L
N L L L L L L
PEN
230V~50/60Hz
IG
1 2 3 4 5 6 7
YV1 2 1
J2 Acqua - Water BT2
J1 Aria - Air BT1
J2
3 4 5 6 7
GNYEBN BU
Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue
WHRD
Bianco - White Rosso – Red
L N PE
Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth
Com Min Med Max
Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)
MV C AUTR BT1 BT2
Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda aria – Air sensor Sonda acqua – Water sensor
ACCESSORI – ACCESSORIESYV1 YV2
Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve
L L N
UNITA’ 2-TUBI: Eseguire questo collegamento sempre in caso di una sola valvola. 2-PIPES UNIT: Always carry out this connection when there is just one valve.
Valvola ValveBN
BU
123456789
10
78
a-LIFE2
A_LIFE2_0102_1004_201306_EN27
13. FANcoIL coNTRoLS
on board controls AT
The AT control is used to regulate the air (3 speeds + auto), the temperature through electronic thermostat, to select the summer/win-ter/auto mode of operation and to switch the fan-coil on/off.
Temperature selector
Adjust the temperature as required by turning the temperature selectorfrom +14°C to 30°C.
Function button
La scelta del modo di funzionamento è possibile tramite il pulsante
Mode led
Cooling
heating
off
Automatic setting
Speed button
select the fan speed pushing the button.The repeated pressure of fan button determines speed required.
Maximum fan speed
Medium fan speed
Minimum fan speed
Automatic fan speed
Led
Blue LED: heating / Cooling plus regulator callBlue LED blinking: hot start / Too Cool function active
Blue LED: operation in Cooling mode
Blue LED: operation in heating mode
Blue LED: automatic cooling / heating mode selection
Electrical connections
GNYEBN BU
Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue
WHRD BK
Bianco - White Rosso - Red Nero - Black
L N PE
Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth
Com Min Med Max
Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)
MV C AUTR BT1 BT2
Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda aria – Air sensor Sonda acqua – Water sensor
ACCESSORI – ACCESSORIESYV1 YV2
Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve
AT BUS-ADAPTER
Kit BUS-ADAPTER
TTL J5
TTL
BUS L N
230V~
AT GATEWAY
Kit GATEWAY
TTL J5
TTL
BUS BTICINO
IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer) SA1 Contatto multifunzionale (a cura del cliente) - Multifunctional contact (by the customer)
ComBU RD WH BN GNYE
MaxMedMin
CMV
AU
TR
BU BN
YV2 BU BN
L
N L L L L L L
PEN
230V~50/60Hz
IG
1 2 3 4 5 6 7
SA1 1312
123456789
10
YV1 2 1
J2 Acqua - Water BT2
J1 Aria - Air BT1
a-LIFE2
28A_LIFE2_0102_1004_201306_EN
13. FANcoIL coNTRoLS
PSW wall-mounted control
The PsW control is used to regulate the airflow (3 speeds), select the summer/winter mode of operation and switch the fan-coil on/offand hot start function by minimun thermostat kit.
Function selector
Cooling
heating
off
Fan selector
Maximum fan speed
Medium fan speed
Minimum fan speed
Electrical connections
GNYEBN BU
Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue
WHRD
Bianco - White Rosso – Red
L N PE
Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth
Com Min Med Max
Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)
MV C AUTR BT2
Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda acqua – Water sensor
ACCESSORI – ACCESSORIESYV1 YV2
Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve
J2
3 4 5 6 7
L L N
UNITA’ 2-TUBI: Eseguire questo collegamento sempre in caso di una sola valvola. 2-PIPES UNIT: Always carry out this connection when there is just one valve
Valvola Valve7
8BN BU
Acqua - Water BT2 98
IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer)
ComBU RD WH BN GNYE
MaxMedMin
CMV
AU
TR
BU BN
YV2 BU BN
L
N L L L L L L
PEN
230V~50/60Hz
IG
1 2 3 4 5 6 7
123456789
10
YV1 2 1
a-LIFE2
A_LIFE2_0102_1004_201306_EN29
13. FANcoIL coNTRoLS
MTW wall-mounted control
The MTW control is used to regulate the air (3 speeds), the temperature through electronic thermostat, to select the summer/wintermode of operation and to switch the fan-coil on/off.
Temperature selector
Adjust the temperature as required by turning the temperature selectorfrom +14°C to 30°C.
Led
Blue Led: indicates fan-coil thermostat call
Function selector
Cooling
heating
off
Fan selector
Maximum fan speed
Medium fan speed
Minimum fan speed
Electrical connections
IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer)
ComBU RD WH BN GNYE
MaxMedMin
CMV
AU
TR
BU BN
YV2 BU BN
L
N L L L L L L
PEN
230V~50/60Hz
IG
1 2 3 4 5 6 7
YV1 2 1
J2
3 4 5 6 7
GNYEBN BU
Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue
WHRD
Bianco - White Rosso – Red
L N PE
Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth
Com Min Med Max
Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)
MV C AUTR BT1 BT2
Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda aria – Air sensor Sonda acqua – Water sensor
ACCESSORI – ACCESSORIESYV1 YV2
Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve
L L N
UNITA’ 2-TUBI: Eseguire questo collegamento sempre in caso di una sola valvola. 2-PIPES UNIT: Always carry out this connection when there is just one valve.
Valvola ValveBN
BU
123456789
10
78
Acqua - Water BT2 98
a-LIFE2
30A_LIFE2_0102_1004_201306_EN
13. FANcoIL coNTRoLS
ATW wall-mounted control
The ATW control is used to regulate the air (3 speeds + auto), the temperature through electronic thermostat, to select the summer /winter / auto mode of operation and to switch the fan-coil on / off.
Electrical connections
GNYEBN BU
Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue
WHRD BK
Bianco - White Rosso - Red Nero - Black
L N PE
Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth
Com Min Med Max
Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)
MV C AUTR BT1 BT2
Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda aria – Air sensor Sonda acqua – Water sensor
ACCESSORI – ACCESSORIESYV1 YV2
Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve
AT BUS-ADAPTER
Kit BUS-ADAPTER
TTL J5
TTL
BUS L N
230V~
AT GATEWAY
Kit GATEWAY
TTL J5
TTL
BUS BTICINO
3 4 5 6 7
L
Collegamento con accessorio Resistenza elettrica Connection with accessory Electrical heater
L N
230V~50/60Hz
BKResist.el. – El.heater Relay
WH RD
BU BU
TS1 TS2
Power Min = BK-RD Power Max = WH-RD Termostati Sicurezza:
TS1 riamo automatico TS2 riarmo manuale
Safety Thermostats: TS1 automatic resetTS2 manual reset
910
11
12
IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer) SA1 Contatto multifunzionale (a cura del cliente) - Multifunctional contact (by the customer)
ComBU RD WH BN GNYE
MaxMedMin
CMV
AU
TR
BU BN
YV2 BU BN
L
N L L L L L L
PEN
230V~50/60Hz
IG
1 2 3 4 5 6 7
123456789
10
YV1 2 1
SA1 1312
Acqua - Water BT2 98
Temperature selector
Adjust the temperature as required by turning the temperature selectorfrom +14°C to 30°C.
Function selector
select the mode of operation pushing the button.
Mode led
Cooling
heating
off
Automatic setting
Speed button
select the fan speed pushing the button.The repeated pressure of fan button determines speed required.
Maximum fan speed
Medium fan speed
Minimum fan speed
Automatic fan speed
Led
Blue LED: heating / Cooling plus regulator callBlue LED blinking: hot start / Too Cool function active
Blue LED: operation in Cooling mode
Blue LED: operation in heating mode
Blue LED: automatic cooling / heating mode selection
a-LIFE2
A_LIFE2_0102_1004_201306_EN31
14. ACCESSORIES
LIFE2 BOX
Kit composed by formwork, cover panel, frame and manual flap.
All components are in galvanised steel varnished finish. Life2
Box is placed in the wall niche arranging in advance hydraulic
connections. At work finished the fan-coil is positionate inside
the structure.
Main coil 2-way valve unit 1/2" and 3/4" kit
Kit with copper fittings and electromechanical actuator (oN-
off) 230V, PWM, 0-10V and suitable for 2-pipe systems.
This kit may be used to stop the flow of water of the main coil in
the fan coils. The electromechanical actuator is NC.
Additional coil 2-way valve unit 1/2" kit
Kit with copper fittings and electromechanical actuator (oN-
off) 230V, PWM, 0-10V and suitable for 4-pipe systems.
This kit may be used to stop the flow of water of the additional
coil in the fan coils. The electromechanical actuator is NC.
Main coil 3-way valve unit with by-pass way (4 idraulic con-
nections) 1/2" and 3/4” kit
Kit with copper fittings and electromechanical actuator (oN-
off) 230V, PWM, 0-10V and suitable for 2-pipe systems.
This kit may be used to divert the flow of water of the main coil
in the fan coils. The electromechanical actuator is NC.
Additional coil 3-way valve unit with by-pass way (4 idraulic
connections) 1/2" kit
Kit with copper fittings and electromechanical actuator (oN-
off) 230V, PWM, 0-10V and suitable for 4-pipe systems.
This kit may be used to divert the flow of water of the additional
coil in the fan coils. The electromechanical actuator is NC.
Water circuit kits
Water circuit kits complete with copper pipes and 2 ball valves,
only available as accessories, not fitted on the unit.
Hot water coil kit
The additional hot water 1 row is installed on top of the main
coil in the four-pipe systems. Using the controls with the addi-
tional coil valve kit, the additional coil may be regulated by
selecting the suitable mode of operation.
Straight plenum kit for air outlet
Made in galvanised sheet metal, this kit allows air conveyance
into ducts in horizontal and vertical built-in installations.
Angular plenum kit for air outlet (90°)
Made in galvanised sheet metal, this kit allows air conveyance
into ducts lying at 90° to the fan coil outlet. Suitable for horizon-
tal and vertical built-in installations.
Plenum kit with roud air ducts
Made in galvanised sheet metal, this kit allows air conveyance
into round ducts in horizontal and vertical built-in installations.
Straight plenum kit for air inlet
Made in galvanised sheet metal, this kit allows air conveyance
into ducts in horizontal and vertical built-in installations.
Angular plenum kit for air inlet (90°)
Made in galvanised sheet metal, this kit allows air conveyance
into ducts lying at 90° to the fan coil outlet. Suitable for horizon-
tal and vertical built-in installations.
Pair of decorative and structural feet
Plastic feet, granting a uniform colour and design, with cabinet.
This kit supports fan coil with cabinet.
Rear panel for vertical housing kit
This kit covers the back side of the fan coil with cabinet. it is
necessary to installation separate from the wall. The user can
not access to the terminal block.
Horizontal Fan Coil auxiliary tray
Made in thermoplastic material, this tray collects the conden-
sate that forms during summer operation. The kit is suitable for
horizontal fan coil installations.
Vertical Fan Coil auxiliary tray
Made from insulated galvanised sheet metal, this pan collects
the condensate that forms during cooling operation.
Interface SPB kit
The SPB interface kit is used for multiple connection of hydronic
terminal units, which may be managed with a single control. for
correct installation, install an SPB interface on every terminal
unit.
Hose kit
The hose kit is a manifold coupling for connecting the fan coil to
the main water system.
Air intake grid with filter
Grid with simple filter removal in order to easify cleaning main-
tenance without access directly to the fan coil installed into the
duct.
Air outlet grid
Grid with orientable louvers for installation in ducted system.
Manual damper kit for fresh air intake.
This kit is used to control the external fresh air that is put into
the room. The quantity of air put into the room varies from 0 to
approx. 30% of the volume handled by the fan coil.
Motor drive for external air intake lock
Motor drive for automatic adjustment of the fresh air intake lock
or damper.
Air intake grille for enclosed versions
Used to mask the lower part of the fan coil.
a-LIFE2
32A_LIFE2_0102_1004_201306_EN
14. AccESSoRIES
LIFE2 BoX
LiFE2 BoX is a wall-mounted accessory that allows users to pre-pare the fan coil water and electrical connections in advance. The fan coil is fitted inside the structure when the work has beencompleted, thus simplifying the operations to be performed onsite.
• The kit consists of a galvanised sheet metal structure, frontclosing panel and frame with manually adjustable flap. The kit isavailable in the galvanised sheet metal version and the coatedversion (RAL9010).
• LiFE2 BoX can house LiFE2 fan- coils, DLi version: low airinlet, vertical outlet. it is available for sizes 102÷602 - 104÷604.
739
103
40
40A
70
min. 240-max.247
660
B
240
206
7
1012
102
740
Modelli
LIFE2
0102
0104
0202
0204
0302
0304
0402
0404
0502
0504
0602
0604
A (mm) 812 812 1012 1012 1212 1212B (mm) 740 740 940 940 1140 1140
a-LIFE2
A_LIFE2_0102_1004_201306_EN33
14. AccESSoRIES
VALVE KIT ModULANTING 0-10V - 2 WAYS 1/2” FITTINGS
The water flow to be diverted for fan coil. Main coil or additionalcoil 2-ways valve kit allow valve unit 0-10V could be manageddirectly with Climaveneta's controls; install hB power board withcontrol board 0-10V on fan-coil's side.
2 WAYS MAIN coIL KIT VALVE 1/2" ANd
ModULANTING AcTUAToR 0-10V
2 WAY AddITIoNAL coIL KIT VALVE 1/2"
ANd ModULANTING AcTUAToR 0-10V
2 WAY MAIN ANd AddITIoNAL coIL KIT
VALVE WITh BY PASS 1/2”-1/2” ANd
ModULANTING AcTUAToR 0-10V
VALVE KIT ModULANTING 0-10V - 2 WAYS 3/4” FITTINGS
The water flow to be diverted for fan coil. Main coil or additionalcoil 2-ways valve kit allow valve unit 0-10V could be manageddirectly with Climaveneta's controls; install hB power board withcontrol board 0-10V on fan-coil's side.
2 WAYS MAIN coIL KIT VALVE 3/4" ANd
ModULANTING AcTUAToR 0-10V
2 WAY AddITIoNAL coIL KIT VALVE 3/4"
ANd ModULANTING AcTUAToR 0-10V
2 WAY MAIN ANd AddITIoNAL coIL KIT
VALVE WITh BY PASS 1/2”-3/4” ANd
ModULANTING AcTUAToR 0-10V
a-LIFE2
34A_LIFE2_0102_1004_201306_EN
14. AccESSoRIES
MAIN coIL VALVE KIT - 2 WAY - 1/2" FITTINGS
(oN/oFF - PWM)
This valve kit allows the main coil water flow to be diverted forfan coil with centrifugal fan.
2 WAYS MAIN coIL KIT VALVE 1/2"
+ AcTUAToR 230V
2 Way additional Coil Kit valve 1/2"
+ aCtUatoR 230v
2 Way Main and additional Coil Kit
valve With by Pass 1/2''-1/2'' + aCtUa-
toR 230v
MAIN coIL VALVE KIT - 2 WAY - 3/4" FITTINGS
(oN/oFF - PWM)
This valve kit allows the main coil water flow to be diverted forfan coil with centrifugal fan.
2 WAYS MAIN coIL KIT VALVE 3/4” 2 WAY AddITIoNAL coIL KIT VALVE 1/2” 2 WAY MAIN ANd AddITIoNAL coIL KIT
VALVE WITh BY PASS 3/4” ANd 1/2”
a-LIFE2
A_LIFE2_0102_1004_201306_EN35
14. AccESSoRIES
VALVE KIT ModULANTING 0-10V - 3 WAYS - 1/2” FITTINGS
The water flow to be diverted for fan coil. Main coil or additionalcoil 3-ways valve kit allow valve unit 0-10V could be manageddirectly with Climaveneta's controls; install hB power board withcontrol board 0-10V on fan-coil's side.
3 WAYS MAIN coIL KIT VALVE 1/2" + BY-
PASS 1/2” + ModULANTING AcTUAToR
0-10V
3 WAY AddITIoNAL coIL KIT VALVE 1/2" +
BY-PASS 1/2” + ModULANTING AcTUA-
ToR 0-10V
3 WAY MAIN ANd AddITIoNAL coIL KIT
VALVE WITh BY PASS 1/2”-1/2” +
ModULANTING AcTUAToR 0-10V
VALVE KIT ModULANTING 0-10V - 3 WAYS - 3/4” FITTINGS
The water flow to be diverted for fan coil. Main coil or additionalcoil 3-ways valve kit allow valve unit 0-10V could be manageddirectly with Climaveneta's controls; install hB power board withcontrol board 0-10V on fan-coil's side.
3 WAYS MAIN coIL KIT VALVE WITh BY
PASS 3/4" ANd ModULANTING AcTUA-
ToR 0-10V
3 WAY AddITIoNAL coIL KIT VALVE WITh
1/2" BYPASS ANd ModULANTING AcTUA-
ToR 0-10V
3 WAY MAIN ANd AddITIoNAL coIL KIT
VALVE WITh BY PASS 3/4” ANd 1/2” ANd
ModULANTING AcTUAToR 0-10V
a-LIFE2
36A_LIFE2_0102_1004_201306_EN
14. AccESSoRIES
MAIN coIL VALVE KIT - 3 WAY - 1/2" FITTINGS
(oN/oFF - PWM)
The valve kit allows the main coil water flow to be diverted forfan coil with centrifugal fan.
3 WAYS MAIN coIL KIT VALVE WITh 1/2"
BYPASS + AcTUAToR
3 WAYS AddITIoNAL coIL KIT VALVE
WITh BY PASS 1/2" + AcTUAToR
3 WAY MAIN ANd AddITIoNAL coIL KIT
VALVE WITh BY PASS 1/2”-1/2'' + AcTUA-
ToR
MAIN coIL VALVE KIT - 3 WAY - 3/4" FITTINGS
(oN/oFF - PWM)
The valve kit allows the main coil water flow to be diverted forfan coil with centrifugal fan.
3 WAY AddITIoNAL coIL KIT VALVE WITh
1/2" BYPASS
3 WAYS MAIN coIL KIT VALVE WITh BY
PASS 3/4"
3 WAY MAIN ANd AddITIoNAL coIL KIT
VALVE WITh BY PASS 3/4” ANd 1/2''
a-LIFE2
A_LIFE2_0102_1004_201306_EN37
14. AccESSoRIES
WATER KIT FoR 2-WAYS VALVE 1/2" FITTING WATER KIT FoR 2-WAYS VALVE 3/4" FITTING
WATER KIT FoR 3-WAYS VALVE + BY-PASS 1/2" FITTING WATER KIT FoR 3-WAYS VALVE + BY-PASS 3/4" FITTING
AddITIoNAL hoT WATER coIL KIT
This accessory kit is used for heating mode in four-pipe systems.
a-LIFE2
38A_LIFE2_0102_1004_201306_EN
14. AccESSoRIES
AIR SUPPLY PLENUM KIT
The plenum kit allows connection to the ductwork.
A
166
100
B
C
141
A140
200
STRAIGhT PLENUM
90° PLENUM
a-LIFE20102
0104
0202
0204
0302
0304
0402
0404
0502
0504
0602
0604
0702
0704
0802
0804
0902
0904
1002
1004
A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) 425 425 625 625 825 825 1025 1025 1225 1225c (mm) 437 437 637 637 837 837 1037 1037 1237 1237
description Qty.
straight plenum 1
self-tapping screws Ø 3.5x9.5 4
a-LIFE20102
0104
0202
0204
0302
0304
0402
0404
0502
0504
0602
0604
0702
0704
0802
0804
0902
0904
1002
1004
A (mm) 400 400 600 600 800 800 1000 1000 1200 1200
description Qty.
90° plenum 1
self-tapping screws Ø 3.5x9.5 4
A
215
150
B
RoUNd PIPES PLENUM Ø 160-180-200
a-LIFE20102
0104
0202
0204
0302
0304
0402
0404
0502
0504
0602
0604
0702
0704
0802
0804
0902
0904
1002
1004
A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) / / 300 300 400 400 350 350 300 300N. pipes 1 1 2 2 2 2 3 3 4 4
description Qty.
Round pipes plenum 1
self-tapping screws Ø 3.5x9.5 4
a-LIFE2
A_LIFE2_0102_1004_201306_EN39
14. AccESSoRIES
STRAIGhT PLENUM:
Made of galvanized steel, it is used to convery the air supply on the concealed units. optional suitable for installation on all concealedversions without cabinet.
90° PLENUM:
Made of galvanized steel, it is used to convery the air supply on the concealed units. optional suitable for installation on all concealedversions without cabinet.
Dimensioni in mm Dimensions in mm
L 200
Flangia da 15 mm 15 mm flange
140
H =
450
14
0
15 L 15
15
H = 450 90
S =
215
Flangia da 15 mm15 mm flange
50
110 21
5
15
90
140 15
15 L 15
200
15
90° PLENUM (PM 90°)
Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000
Dimensions L (mm) 400 600 800 1000 12002 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004
L
100
140
Flangia da 15 mm 15 mm flange
Dimensioni in mm Dimensions in mm
15 L 15
140
15
15
H =
450
10
0 15 L 15
H = 450 100
140
S =
215 60
15
15
Flangia da 15 mm15 mm flange
STRAIGhT PLENUM (PM)
Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000
Dimensions L (mm) 400 600 800 1000 12002 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004
a-LIFE2
40A_LIFE2_0102_1004_201306_EN
14. AccESSoRIES
RoUNd PIPES PLENUM:
Made of galvanized steel + internal Thermal-acoustic insulation. it is used to convery the air supply on the concealed units. optional suitablefor installation on all concealed versions without cabinet.
Dimensioni in mm Dimensions in mm
L 150
No. x Ø 160-180-200
A/2 15 A A/2 15 L
H =
450
50
150
215
= =
H = 450 150
Ø 2
00
S =
215
140
Ø 2
15
Ø 1
60
Ø 1
80
4545
RoUNd PIPES PLENUM Ø 160-180-200
Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000
Dimensions A (mm) / 300 400 350 300Dimensions L (mm) 400 600 800 1000 1200N° x d. (mm) 1x 2x 2x 3x 4x2 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004Spigots (made of plastic material): Ø 160, 180, 200
a-LIFE2
A_LIFE2_0102_1004_201306_EN41
14. AccESSoRIES
PLENUM KIT FoR AIR oUTLET
The plenum kit allows connection to the ductwork.
A
166
100
B
C
141
A140
200
STRAIGhT PLENUM
90° PLENUM
a-LIFE20102
0104
0202
0204
0302
0304
0402
0404
0502
0504
0602
0604
0702
0704
0802
0804
0902
0904
1002
1004
A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) 425 425 625 625 825 825 1025 1025 1225 1225B (mm) 437 437 637 637 837 837 1037 1037 1237 1237
description Qty.
Straight plenum 1
self-tapping screws Ø 3.5x9.5 4
a-LIFE20102
0104
0202
0204
0302
0304
0402
0404
0502
0504
0602
0604
0702
0704
0802
0804
0902
0904
1002
1004
A (mm) 400 400 600 600 800 800 1000 1000 1200 1200
description Qty.
90° plenum 1
self-tapping screws Ø 3.5x9.5 4
A
215
150
B
RoUNd PIPES PLENUM Ø 160-180-200
a-LIFE20102
0104
0202
0204
0302
0304
0402
0404
0502
0504
0602
0604
0702
0704
0802
0804
0902
0904
1002
1004
A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) / / 300 300 400 400 350 350 300 300N. pipes 1 1 2 2 2 2 3 3 4 4
description Qty.
Round pipes plenum 1
self-tapping screws Ø 3.5x9.5 4
a-LIFE2
42A_LIFE2_0102_1004_201306_EN
14. AccESSoRIES
STRAIGhT PLENUM:
Made of galvanized steel, it is used to convery the air intake on the concealed units. optional suitable for installation on all concealedversions without cabinet.
90° PLENUM:
Made of galvanized steel, it is used to convery the air intake on the concealed units. optional suitable for installation on all concealedversions without cabinet.
Dimensioni in mm Dimensions in mm
L
200
Flangia da 15 mm 15 mm flange
140
H =
450
14
0
15 L 15 15
Flangia da 15 mm 15 mm flange
H = 450
S =
215
15
90
215 90
11
0
50
140 15
15 L 15
200
15
90° PLENUM (PM 90°)
Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000
Dimensions L (mm) 400 600 800 1000 12002 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004
Dimensioni in mm Dimensions in mm
100
L
140
Flangia da 15 mm 15 mm flange
Flangia da 15 mm 15 mm flange
H = 450
37,5
S =
215
15
15
100
140
37,5
H =
450
10
0
15 L 15
15 L 15
140
15
15
STRAIGhT PLENUM (PM)
Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000
Dimensions L (mm) 400 600 800 1000 12002 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004
a-LIFE2
A_LIFE2_0102_1004_201306_EN43
14. AccESSoRIES
RoUNd PIPES PLENUM:
Made of galvanized steel + internal Thermal-acoustic insulation. it is used to convery the air intake on the concealed units. optional suitablefor installation on all concealed versions without cabinet.
Dimensioni in mm Dimensions in mm
150
L
215
A/2 15 A A/2 15 L
H =
450
50
15
0 45
45
H = 450
Ø 2
00
215
140
S =
215
= =
150
Filtro aria Air filter
Ø 1
60
Ø 1
80
No. x Ø 160-180-200
RoUNd PIPES PLENUM Ø 160-180-200
Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000
Dimensions A (mm) / 300 400 350 300Dimensions L (mm) 400 600 800 1000 1200N° x d. (mm) 1x 2x 2x 3x 4x2 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004Spigots (made of plastic material): Ø 160, 180, 200
a-LIFE2
44A_LIFE2_0102_1004_201306_EN
14. AccESSoRIES
FEET KIT
The feet kit allows the fan coils with housing to be placed on theground.
REAL PANEL FoR VERTIcAL hoUSING
This accessory kit covers the back side of the fan coil with cabi-net.
AUXILIARY coNdENSATE TRAY KIT FoR hoRIZoNTAL
INSTALLATIoN
The auxiliary condensate tray is designed to collect the conden-sate which forms on coil connections during operation in thecooling mode.
100
186,5 186,5 232,7
AUXILIARY coNdENSATE TRAY KIT FoR VERTIcAL
INSTALLATIoN
The auxiliary condensate tray is designed to collect the conden-sate which forms on coil connections during operation in thecooling mode.
d
a-LIFE2
A_LIFE2_0102_1004_201306_EN45
14. AccESSoRIES
71 mm 60 mm
mm 09
SPB INTERFAcE KIT
SIGILLARECON MASTICEDI TENUTA
SEAL WITHMASTIC SEALING
hoSE coNNEcTIoN KIT
The hose kit is a header connection for connecting the fan coilto the mains water supply.
AIR INTAKE GRId WITh FILTER
Kit accessory for air inlet of duct system. Accessory is providedwith air filter.
70 80
1018
0
B
A
130
GRIGLIA / GRILLEFILTRO ARIA / AIR FILTER
TELAIO DI CONTENIMENTO FILTROFRAME FILTER
a-LIFE20102
0104
0202
0204
0302
0304
0402
0404
0502
0504
0602
0604
0702
0704
0802
0804
0902
0904
1002
1004
A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) 450 450 650 650 850 850 1050 1050 1250 1250
a-LIFE2
46A_LIFE2_0102_1004_201306_EN
DAMPER MOTOR
2 X 6MA NUTS FORFASTENING ON THE PIN
FASTEN THE DAMPER OPENINGWITH THE Ø3.9X9.5 SCREW
14. AccESSoRIES
AIR oUTLET GRILLE
Kit accessory is used for air outlet in duct system. Air grille hasadjustable louvers.
FRESh AIR INTAKE dAMPER KIT
La serranda di ripresa aria può essere installata nei fan-coilLiFE2 con ripresa aria inferiore in versione mantellata o incasso.
KIT A – Manual fresh air intake damper kit. The kit is used toadjust the amount of fresh air introduced into the environment.The amount of fresh air introduced varies from 0 to approx. 30%of the volume handled by the fan coil.
KIT B – Motorised fresh air intake damper kit.Motor for motorised damper position adjustment. The two kits are supplied separately with their own productcodes. The air intake damper can be installed on LiFE2 fan coilswith air intake from below, in the version with casing or built-in.KIT c – Motor for fresh air intake damper
45
130
B
180
A
8011
a-LIFE20102
0104
0202
0204
0302
0304
0402
0404
0502
0504
0602
0604
0702
0704
0802
0804
0902
0904
1002
1004
A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) 450 450 650 650 850 850 1050 1050 1250 1250
KIT A (manual damper) KIT B (motorised damper)
dAMPER FoR UNITS WITh cASING
KIT A (manual damper) KIT B (motorised damper)
dAMPER FoR BUILT-IN UNITS
FISSARE VITE DA Ø3,9x9,5IN BASE ALL'APERTURADELLA SERRANDA
MOTORE SERRANDA
Nr.2 DADI da 6MAFISSAGGIO SU PERNO
a-LIFE2
A_LIFE2_0102_1004_201306_EN47
14. AccESSoRIES
“MRS1” TERMINAL BLocK KIT FoR ASYNchRoNoUS Fc
• Terminal block featuring a number of terminals based on unit configuration (min. PE+1+2+3+4) ; (max PE+….12)• Wiring according to the requirements of the configuration
Power Min = BK-RD Power Max = WH-RD Termostati Sicurezza:
TS1 riamo automatico TS2 riarmo manuale
Safety Thermostats: TS1 automatic resetTS2 manual reset
GNYEBN BU
Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue
WHRD BK
Bianco - White Rosso - Red Nero - Black
L N PE
Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth
Com Min Med Max
Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)
MV C AUTR
Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer
ACCESSORI – ACCESSORIESYV1 YV2
Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve
A CURA DEL CLIENTE - BY THE CUSTOMERCR IG
Comando remoto - Remote control Interruttore di protezione - Thermomagnetic switch
Collegamento con accessorio Resistenza elettrica
Connection with accessory Electrical heater
230V
~50/
60Hz
BK
Resist.el.El.heater Relay
WH RD
BU BU
TS1 TS2
9101112
ComBU RD WH BN GNYE
MaxMedMin
CMV
AU
TR
BU BN
YV2 BU BN
IG
123456789
10
YV1
L L L N
L NL N
CR
L N
L N
NL
PE
230V
~50/
60Hz
Potenza - Power
Potenza - Power
AIR INTAKE GRId FoR WITh cABINET VERSIoN
Kit accessory allows to cover space between feet of LiFE2 fancoil. Air intake grid for with cabinet is suitable for DLMV version(with cabinet and bottom air inlet). Air intake grille is painted asfan coil cabinet’s colour (RAL 9003) ensuring suitable anddesired aesthetic solution.
A
B
100
LIFE20102
0104
0202
0204
0302
0304
0402
0404
0502
0504
0602
0604
0702
0704
0802
0804
0902
0904
1002
1004
A (mm) 922 922 1112 1112 1302 1302 1492 1492 1682 1692B (mm) 566 566 756 756 946 946 1136 1136 1326 1326
a-LIFE2
48A_LIFE2_0102_1004_201306_EN
Fan coils have been designed and made for installation in heating and air-conditioning systems.
15. dIMENSIoNAL dATA ANd WATER coNNEcTIoNS (VERToIcAL VERSIoN)
450 1512030217
25 15
261134
450
12033669
175,
9
4212
0155178
Atta
cchi
idra
ulic
i
1/2'
' GF
Wat
er c
onne
ctio
ns 1
/2'' F
emal
e
120230
D
Ø10
Ø16
33
C
Ø20
2525
15 185,8 15,815
B15
A
Mo
dello
a-L
IFE
2
0102
0104
020
2
020
4
0302
0304
0402
0404
0502
0504
0602
0604
0702
0704
0802
0804
0902
0904
1002
1004
A (
mm
)43
043
063
063
083
083
010
3010
3012
3012
30
B (
mm
)40
040
060
060
080
080
010
0010
0012
0012
00
c (
mm
)45
045
065
065
085
085
010
5010
5012
5012
50
d (
mm
)42
542
562
562
582
582
510
2510
2512
2512
25
a-LIFE2
A_LIFE2_0102_1004_201306_EN49
Fan coils have been designed and made for installation in heating and air-conditioning systems.
15. dIMENSIoNAL dATA ANd WATER coNNEcTIoNS (hoRIZoNTAL VERSIoN)
25
261134
450
33669
4212
0155178
Atta
cchi
idra
ulic
i
1/2'
' GF
Wat
er c
onne
ctio
ns 1
/2'' F
emal
e
120230
D
Ø16
33
C
204,8
75
Ø20
3010630
105
40
E
E
210 3312
Ø10
1560
015
630
15,8185,815
Mo
dello
a-L
IFE
2
0102
0104
0202
0204
0302
0304
0402
0404
0502
0504
0602
0604
0702
0704
0802
0804
0902
0904
1002
1004
A (
mm
)43
043
063
063
083
083
010
3010
3012
3012
30
B (
mm
)40
040
060
060
080
080
010
0010
0012
0012
00
c (
mm
)45
045
065
065
085
085
010
5010
5012
5012
50
d (
mm
)42
542
562
562
582
582
510
2510
2512
2512
25
E (
mm
)54
554
574
574
594
594
511
4511
4513
4513
45
a-LIFE2
50A_LIFE2_0102_1004_201306_EN
INVERTING ThE WATER coNNEcTIoNS
1
1
5
7
8
10
A
B
C
D
E
6
Premere sul fermoe ruotare per toglierel'imbuto
1211
F
G
14
H
3
2
4
13
15
14
9
WARNING! Run the electrical wiring on the opposite side to the final water connections.
Remove the transformer and the terminal block and reposition them on the opposite side.
If the controller is installed on the unit, remove the controller complete with fastening bracket.
If the room temperature probe cable is not long enough, move the room temperature probe to the opposite side.
INSTRUcTIoNS To MoVE ThE MAIN coIL FRoM LEFT To RIGhT oN VERTIcAL FAN coILS
A. Unscrew the 4 x Ø 3.9x9.5 screwsB. Remove the panel in the direction indicated by the arrow “2”. Unscrew the 4 x Ø 3.9x9.5 screws “3” that support the coil from the
left and right shoulders.c. slightly tilt the coil in the direction indicated by the arrow “4” and move it away from the left shoulder in the direction indicated by
arrow “5”.Press the catch that holds the funnel “6” to release it.
d. Move the coil from pos. 7 to pos. 8.E. open the knock-outs on the opposite shoulder “9”. insert the coil at an angle, as shown in the figure “10”, inserting the water con-
nections through the openings made.F. Tighten the 4 x Ø 3.9x9.5 screws in the holes aligning the shoulder - coil bracket “11”, on the right and left shoulders.
Remove the knock-out “12” and insert the funnel, making sure it is secured in place.G. Reposition the panel “13” and tighten the 4 x Ø 3.9x9.5 screws “14”.h. Use closed-cell insulation to cover in the holes left open on the left shoulder “15”.
INSTRUcTIoNS To MoVE ThE MAIN coIL FRoM RIGhT To LEFT oN VERTIcAL FAN coILS
To invert the position of the coil, follow the previous instructions, swapping the references to the right shoulder and left shoulder.
a-LIFE2
A_LIFE2_0102_1004_201306_EN51
INVERTING ThE WATER coNNEcTIoNS
A
1
1
B
2
3
6
7
9
D
E
10
F
G
H
12
5
C
4
12
13
8
11
96,5
WARNING! Run the electrical wiring on the opposite side to the final water connections.
Remove the transformer and the terminal block and reposition them on the opposite side.
If the controller is installed on the unit, remove the controller complete with fastening bracket.
If the room temperature probe cable is not long enough, move the room temperature probe to the opposite side.
INSTRUcTIoNS To MoVE ThE MAIN coIL FRoM LEFT To RIGhT oN hoRIZoNTAL FAN coILS:
A. Unscrew the 4 x Ø 3.9x9.5 screwsB. Remove the panel in the direction indicated by the arrow “2”. Unscrew the 4 x Ø 3.9x9.5 screws “3” that support the coil from the
left and right shoulders.c. slightly tilt the coil in the direction indicated by the arrow “4” and move it away from the left shoulder in the direction indicated by
arrow “5”.d. Move the coil from pos. 6 to pos. 7.E. open the knock-outs on the opposite shoulder “8”.
insert the coil at an angle, as shown in the figure “9”, inserting the water connections through the openings made.F. Tighten the 4 x Ø 3.9x9.5 screws in the holes aligning the shoulder - coil bracket “10”, on the right and left shoulders.G. Reposition the panel “11”, ensuring the distance of 96.5 mm, as shown in the figure.h. Tighten the 4 x Ø 3.9x9.5 screws “12”. Use closed-cell insulation to cover in the holes left open on the left shoulder “13”.
INSTRUcTIoNS To MoVE ThE MAIN coIL FRoM RIGhT To LEFT oN hoRIZoNTAL FAN coILS
To invert the position of the coil, follow the previous instructions, swapping the references to the right shoulder and left shoulder.
a-LIFE2
52A_LIFE2_0102_1004_201306_EN
15. dIMENSIoNAL dATA (WITh cABINET VERSIoN)
a-LIFE2 dLMV 0102-0104 0202-0204 0302-0304 0402-0404 0502-0504 0602-0604 0702-0704 0802-0804 0902-0904 1002-1004
A mm 922 922 1112 1112 1302 1302 1492 1492 1682 1682B mm 566 566 756 756 946 946 1136 1136 1326 1326
100
A
599499
186,5 233
A
547
1112
a-LIFE2
A_LIFE2_0102_1004_201306_EN53
The fan coil comes fully wired and only requires:
- Connecting to the mains electricity supply and to any room
control.
It is also recommended to check that:
- The characteristics of the mains electricity supply are suitable
for the input indicated in the table below, which (with maxi-
mum values) should serve for sizing both the circuit breakers
and the power cables (any other appliances working in paral-
lel should also be taken into consideration).
- The supply voltage corresponds to the rated value +/- 10%.
The following is compulsory:
Installation near the appliance of a delayed-action single-
pole linked magnetothermal circuit breaker, padlockable,
line isolating switch, in compliance with CEI-EN standards
(contact separation of at least 3 mm).
16. ELECTRICAL CONNECTIONS
Table electrical connections
Sizing table
a-LIFE2 Power supply Max. input (W) Max. absorbed current (A)
0102-0104 230 ~ 50 45 0,20
0202-0204 230 ~ 50 45 0,20
0302-0304 230 ~ 50 60 0,30
0402-0404 230 ~ 50 60 0,30
0502-0504 230 ~ 50 63 0,30
0602-0604 230 ~ 50 63 0,30
0702-0704 230 ~ 50 130 0,60
0802-0804 230 ~ 50 130 0,60
0902-0904 230 ~ 50 160 0,73
1002-1004 230 ~ 50 160 0,73
Sizing table with HEATER power 1
a-LIFE2 Power supply Max. input (W) Max. absorbed current (A)
0102-0104 230 ~ 50 1045 4,6
0202-0204 230 ~ 50 1045 4,6
0302-0304 230 ~ 50 1560 6,9
0402-0404 230 ~ 50 1560 6,9
0502-0504 230 ~ 50 2063 9,1
0602-0604 230 ~ 50 2063 9,1
0702-0704 230 ~ 50 3130 13,7
0802-0804 230 ~ 50 3130 13,7
0902-0904 230 ~ 50 3160 13,9
1002-1004 230 ~ 50 3160 13,9
Sizing table with HEATER power 1
a-LIFE2 Power supply Max. input (W) Max. absorbed current (A)
0102-0104 230 ~ 50 745 3,3
0202-0204 230 ~ 50 745 3,3
0302-0304 230 ~ 50 1060 4,7
0402-0404 230 ~ 50 1060 4,7
0502-0504 230 ~ 50 1563 6,9
0602-0604 230 ~ 50 1563 6,9
0702-0704 230 ~ 50 2130 9,4
0802-0804 230 ~ 50 2130 9,4
0902-0904 230 ~ 50 2160 9,5
1002-1004 230 ~ 50 2160 9,5
www.climaveneta.com
Climaveneta S.p.A. Via Sarson 57/c36061 Bassano del Grappa (VI)ItalyTel +39 0424 509 500Fax +39 0424 509 [email protected]
Climaveneta France 3, Village d’EntreprisesZA de la Couronne des PrésAvenue de la Mauldre78680 EpôneFranceTel +33 (0)1 30 95 19 19Fax +33 (0)1 30 95 18 [email protected]
Climaveneta Deutschland GmbHLyrenstraße 13 44866 Bochum Germany Tel +49 2327-95428-0 Fax +49 2327-95428-99 [email protected] www.climaveneta.de
Climaveneta España - Top Clima Londres 67, 1 4 08036 BarcelonaSpainTel +34 934 195 600Fax +34 934 195 [email protected]
Climaveneta Chat Union Refrig. Equipment Co Ltd88 Bai Yun Rd, Pudong XinghuoNew dev. zone 201419 ShanghaiChinaTel 008 621 575 055 66Fax 008 621 575 057 97
Climaveneta Polska Sp. z o.o. Ul. Sienkiewicza 13A,05-120 Legionowo,PolandTel +48 22 766 34 55-57Fax +48 22 784 39 [email protected]
Climaveneta Climate Technologies (P) Ltd #3487, 14th Main, HAL 2nd stage,Indiranagar, Bangalore 560008IndiaTel:+91-80-42466900 - 949, Fax: [email protected]
Climaveneta UK LTD. Highlands Road,Shirley SolihullWest Midlands B90 4NLTel: +44 (0)871 663 0664Fax: +44 (0)871 663 1664Freephone: 0800 801 [email protected]