AC500 to EMAX Modbus RTU
ABB LVP&S Training
Revision Date: Feb 16,2009
www.infoPLC.net
©AB
B G
roup
200
8 -
2
AC500 - PLC
CONTROLPRODUCTS Objective
Using AC500 to communicate to Emax Breaker with Modbus RTU.
This intermediate level course demonstrates how to connect an AC500 PLC to an Emax breaker. The student will wire an Emaxbreaker to a AC500 PLC with provided wiring diagrams. The student will also control and monitor Emax breaker with provided AC500 program (AC500_MODBUS_RTU_EMAX.pro).
www.infoPLC.net
©AB
B G
roup
200
8 -
3
AC500 - PLC
CONTROLPRODUCTS Required Items
Required Items Emax Breaker with Trip Unit PR122/3 or PR332/3
Communication Module PR120/D-M
AC500 PLC Program AC500_MODBUS_RTU_EMAX.pro
AC500 PM5xx
Instructional Manual – Trip Unit Modbus System Interface (1SDC200005D0201.pdf)
www.infoPLC.net
©AB
B G
roup
200
8 -
4
AC500 - PLC
CONTROLPRODUCTS Overview
Hardware ConnectionsCommunication ParametersMemory mappingPLC programEvaluationSummary
www.infoPLC.net
©AB
B G
roup
200
8 -
5
AC500 - PLC
CONTROLPRODUCTS Hardware Connections
Hardware ConnectionsCommunication Module Inside Trip Unit
Communication Module
Pin 1
Pin 10
W1 & W2 is your Modbus RTU twisted pair
W1 is Rx/Tx Data Positive connected to Pin 6
Rx/Tx +
W2 is Rx/Tx Data Negative Connected to Pin 5
Rx/Tx -
www.infoPLC.net
©AB
B G
roup
200
8 -
6
AC500 - PLC
CONTROLPRODUCTS Hardware Connections
Emax Internal Hardware Connections
Terminal K1= +24V
Terminal K2 = 0V
External 24V Power Supply Provide 24V Power to Trip Unit
W1 (Rx/Tx + )
W2 (Rx/Tx - )
Com Module to Terminal Strip
Emax Breaker
www.infoPLC.net
©AB
B G
roup
200
8 -
7
AC500 - PLC
CONTROLPRODUCTS Hardware Connections
Emax Breaker internal circuit diagrams
Optional Charging Motor, YC closing coil and YO opening coil
Refer to Emax Technical Catalog (1SDC200005D0201)
Wiring for Spring Charging motor if equipped YC wiring
through com module relay
YC wiring external circuit
YO wiring through com module relay
YO wiring external circuit
OROR
Communication Module
PR120/D-M
www.infoPLC.net
©AB
B G
roup
200
8 -
8
AC500 - PLC
CONTROLPRODUCTS Hardware Connections
AC500 External Communication Connections
Emax Breaker
AC500 COM1
W2 (Rx/Tx - )
OR
W1 (Rx/Tx + )
www.infoPLC.net
©AB
B G
roup
200
8 -
9
AC500 - PLC
CONTROLPRODUCTS Emax Communication Parameters
Setting the Com Module address, baud rate, and com mode.
In the Trip Unit display select <ESC> key.Go to Settings and select “Com Module”Select the Local option
Default password is “0001”Once module is in Local hit <ESC> key to go back until you are prompted to save and
confirm changesGo back to com module settings and select Address
Set address to “70”Select Baud Rate
Set baud rate to 19200kb/sSelect Protocol Type
Even, 8 data bits, 1 stop bit = “E,8,1”Select Addressing Type
Select Modbus StandardPlace Com Module back in Remote and confirm changes
www.infoPLC.net
©AB
B G
roup
200
8 -
10
AC500 - PLC
CONTROLPRODUCTS PLC Communication Parameters
PLC Com 1 port settingsBaud Rate, Parity, Stop Bits must match Emax communication module settings
Operation Mode must be set to Master
www.infoPLC.net
©AB
B G
roup
200
8 -
11
AC500 - PLC
CONTROLPRODUCTS Memory Mapping
Emax Memory Mapping Index table
www.infoPLC.net
©AB
B G
roup
200
8 -
12
AC500 - PLC
CONTROLPRODUCTS Memory Mapping
Memory Mapping Read Only Registers (Status)Example:Reading Parameter 101 (Word Address 101)
If the Value = 16 then CB is closed means Bit 4 is ON (Addr 101 = 0000 0000 0001 0000 = 16 decimal)
www.infoPLC.net
©AB
B G
roup
200
8 -
13
AC500 - PLC
CONTROLPRODUCTS Memory Mapping
Memory mapping Read Only registers (Status)
Example:Reading Parameter 1028 (Word Address 1028)
If the Value = 70 then the Slave address is 70
www.infoPLC.net
©AB
B G
roup
200
8 -
14
AC500 - PLC
CONTROLPRODUCTS Memory Mapping
Memory Mapping Write Only registers
Example:
Command Value:
Binary Decimal0000 0000 0000 1000 = Open 8 = Open0000 0000 0000 1001 = Close 9 = Close0000 0000 0000 0001 = Reset Trip 1 = Reset
Note:
When writing a command you must write both Command Type and Command Parameter. This means you must sent a double word (32bits) at one time.
www.infoPLC.net
©AB
B G
roup
200
8 -
15
AC500 - PLC
CONTROLPRODUCTS PLC Program
Operating circuit breaker remotelyWhen you Go online with the program AC500_MODBUS_RTU_EMAX.pro the
correct breaker address should show on the top left corner of the HMI. Verify Address matches the breaker you want to operate remotely.
* Breaker Com Module must be in remote to accept commands*
Status Indicators
Commands
www.infoPLC.net
©AB
B G
roup
200
8 -
16
AC500 - PLC
CONTROLPRODUCTS
Operating circuit breaker remotelyTest operation of breaker by opening and closing
PLC Program www.infoPLC.net
©AB
B G
roup
200
8 -
17
AC500 - PLC
CONTROLPRODUCTS Evaluation
Was hardware connection content defined?
Was memory mapping instructions defined?
Did the PLC program communicate with the Emax?
www.infoPLC.net
©AB
B G
roup
200
8 -
18
AC500 - PLC
CONTROLPRODUCTS Summary
The Course provided a quick-start guide to interfacing an AC500 PLC to an Emax Breaker.
Modbus RTU communication protocal was used to communicate between the AC500 and Emax breaker.
The Emax Memory Mapping table linked PLC memory addresses to breaker commands and parameters.
The PLC program provided a user interface to execute commands and retrieve breaker parameters.